Download Motor Controls Troubleshooting of Electric Motors...
Description
Motor Controls & Troubleshooting of Electric Motors
Introduction
to Motor Controls
Devices that pass power to the motor
1.
Relays
2.
Contactors
3.
Starters
The contacts are controlled by a coil in the control circuit
The starting relay is only in the circuit for a short period of time
The type of motor control device is determined by the size of the motor
Run--load and LockedRun Locked-rotor current
Run load amperage (RLA)
1. 2.
Also called full load amperage (FLA) Current drawn while the motor is running Locked rotor amperage (LRA) Amperage drawn at startstart-up Approximately five times the RLA Both currents must be considered when selecting a control device
1. 2.
Relays
Relay Uses a magnetic coil to close one or more sets of contacts. Cannot be repaired ±± considered a throw a away away device. device. Used for light duty applications Can be used as a pilot duty relay (A relay used for switching loads such as another relay or solenoid valve coils. The pilot duty relay contacts are located in a second control circuit. Pilot duty relays are rated in volt volt-amperes amperes (VA).) The contacts must be able to handle the current draw of the load Can have normallynormally-open open (NO) contacts, normallynormally-closed closed (NC) contacts, or both normally open and normally closed contacts
Relays, Contactors, &
Starters
Contactor
Larger versions of the relay
Has moveable and stationary contacts
Holding coils of different voltage ratings are available
Can have one or more sets of contacts
Some are equipped with auxiliary contacts
Use exact replacement whenever possible
Motor Starters
Described as a contactor with overload protection built in
Can be rebuilt Should be replaced when the become pitted
1.
2.
Heaters and holding coils can also be replaced
As the contacts become pitted the resistance increases
Motor Protection
Because of the cost of electric motors they need to be protected from damage
Fuses protect the entire circuit, not the
components Motors can operate at a slightly higher current for a short period of time
Very small motors do not have overload protection
The larger the motor, the more elaborate the protection should be Motor protection can be inherent (internal) or external
Inherent (Internal)
Motor Protection
Internal
thermal overloads, OR
Thermally activated bimetal snap disc
External Motor Protection
Devices that pass power to the holding coil of the starter or contactor The device can open its contacts when a current overload deenergize occurs, causing the holding coil to deThe trip point and type of overload protection is determined by the manufacturer The overload protection takes the service factor into consideration Phase monitoring devices that shut down power if leg is lost to prevent single phasing three phase motors
Temperature ± Sensing Devices
1. 2. 3. 4.
1. 2. 3.
Bi-metal element BiHeated by a device called a heater The heater is in series with the load and senses the load current The bimetal warps when it becomes too warm The bimetal interrupts the circuit feeding the holding coil of the starter Solder pot Uses a low low--melting solder The solder melts when excessive heat is generated The excessive heat is generated from an over overcurrent condition
Magnetic Overload Devices
Not attached to the starter
Not affected by ambient temperature Very accurate overload device
Restarting the Motor
If a motor shuts off on a safety, it should not be immediately restarted The cause for the overload must be found The motor must be given enough time to cool down Many control circuits have manual resets to prevent automatic restarting Some controls reset only after a prepre-determied time period Time delay devices prevent the unit from short cycling
Electric Motor Troubleshooting
Problems are either mechanical or
electrical Mechanical problems often appear to be electrical problems
Technicians must be able to diagnose the problems correctly
Mechanical Motor Problems
Normally occur in the bearings or drive
connection Bearing Failure (tight or worn)
1.
Lack of lubrication
2.
Excessive grit in the bearing
3.
Over--tight belts Over
Removing Drive Assemblies
Pulley, coupling, or fan wheel must be removed from a motor shaft with care
1.
The fit can be very tight The assembly must not be damaged Special pulley pullers can be used
2. 3.
Set screws are tightened to the motor shaft
1.
Set screw is made of hardened steel Tightened to the flat portion of the shaft
2.
The end of the motor shaft should not be hammered
Removing Drive Assemblies
Belt Tension
Over--tightened can cause motor failure Over
and or bearing damage A belt tension gauge should be used
Pulley Alignment
Drive and driven pulleys should be
properly aligned Drive mechanisms can become damaged
Belt life can be reduced
Belts can skip off the pulleys
Electrical Problems
Easy to diagnose
Motor may smell burned An open motor winding
A short circuit from the winding to ground
A short circuit from winding to winding
Open Windings
Can be found with an ohmmeter
There should be a measurable resistance between the common, start, and run terminals
A reading of infinite resistance is an indication that the winding is open
Shorted Motor Windings
Caused when winding insulation develops a hole An alternative current path is created This path reduces the resistance of the winding
The current flow through the winding will increase
1. 2.
Motor overload may trip Circuit breaker may trip
Short in the run winding
1. 2.
Motor may start Motor will draw excessive current
Short in the start winding
1. 2.
Motor may not start If it does start it will draw excessive current on startstart-up
Three--phase motor windings should all have the same resistance Three
Short Circuit to Ground (Frame)
There should be no detectable circuit from a winding to ground
Motors should be checked for grounds using a good quality ground ohmmeter
1.
The meter should be set to its highest setting Megohmmeters (megger) can detect 10,000,000 ±ohm ±ohm range
2.
Dirty motors may show resistance from winding to ground if the atmosphere is damp
Hermetic ground compressors may show a slight
1.
The oil may be dirty Liquid refrigerant in the compressor worsens the condition A suction line drier may help clean the oil
2. 3.
Single--Phase Motor Starting Single Problems
Fairly easy to troubleshoot
Check for full power to motor
1.
Low voltage Loose connection Undersized wire Low voltage from electrical panel Measure voltage at the motor terminals Voltage must be within 10% of rated voltage
2. 3. 4. 5. 6.
Open Motors
Checked with voltage supplied to both
windings Start windings is removed when motor reaches 75% of rated speed
Uses centrifugal switch
The opening and closing of the switch can be heard
CSCR Motors
Have the start winding energized all
the time The start capacitor stays in the circuit whenever the motor is energized
Symptoms of Electric Motor Starting Problems
Motor hums and then shuts off
Motor runs for a short period and shuts off
Motor will not try to start
Types of Problems to Consider
Motor mechanical problem
Electrical problem
Motor circuit problem
Motor load problem
If
motor and load turn freely, technician should check motor windings If
motor hums and does not start, starting components should be checked
Checking Capacitors
Capacitors can be checked with an analog
ohmmeter Ohmmeter leads placed across a charged capacitor can cause damage to the meter
Procedure for Checking Capacitors
Turn power off to the and remove capacitor lead Short across a charged capacitor Set ohmmeter to the R X 10 scale Touch meter leads to capacitor terminals A good capacitor would show the ohmmeter needle sweeping up to zero (0) ohms value and begin to fall back toward infinity Internal shorted capacitors ± needle will sweep to (0) ohms value and fall back toward infinity If the ohmmeter needle will not rise at all, switch the meter leads on the capacitor and look for a needle deflection that rises and returns to infinity No meter scale reading indicates an open capacitor If the capacitor has a bleed resistor, the ohmmeter will sweep to 0 ohms and fall back to the resistance value of the bleed resistor.
Identification
of Capacitors
Run Capacitors
1. 3.
Metal case Oil filled If the capacitor swells, it should be replaced
4.
Have identified terminals which should be connected to the start terminals
Start capacitors
1.
Dry tape Encased in plastic (bakelite) Older capacitors should be encased in paper
2.
2. 3.
Over current can cause the ³vent´ at the top to bulge If the capacitor pops it should be replaced
Wiring and Connectors
Wiring must be in good condition
Loose connections
1.
Can cause oxidation
2.
Oxidation causes an increase in resistance
3.
Resistance creates heat
4.
Could result in low voltage at the motor
5.
Low voltage at the motor can result in higher motor amperage draws
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.