Module 2

October 30, 2017 | Author: harp_p24 | Category: Electrical Wiring, Fuse (Electrical), Ac Power Plugs And Sockets, Alternating Current, Switch
Share Embed Donate


Short Description

mock test...

Description

Mock Exams

In this section there are five mock test papers. These are only meant to be a representation what your final exam might be. As mentioned at the beginning, your final exam is comprised from a database of 500 questions of which 30 or 60 questions will be selected at random. If you passed your 16th Edition BS 7671 after June 2001, then you will only need to do the 1 hour / 30 question test (2382-20). Any electrician who qualified before June 2001 will have to do the 2 hour / 60 question test (2382-10). Paper 1 is a 30 question mock exam. For this exam you need to allow yourself 1 hour to complete it and to score 20 out of 30 to pass (65%). Papers 2 to 5 are 60 question mock exams. For these exams you need to allow yourself 2 hours per paper. To pass, you will need to score 39 out of 60, (65%). All answers, and where to locate them within BS 7671:2008, can be found in the answer section of this e-book. REMEMBER you are allowed to take your BS 7671:2008 into the exam, and within that book are ALL the answers to any of the questions that may come up.

Below you can print off a blank answer sheet to fill in your answers.

Answer Sheet 2382-20 TEST QUESTIONS – PAPER 1 Time: 1 hour 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

2382-10 TEST QUESTIONS – PAPER 2 Time: 2 Hours 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

2382-10 TEST QUESTIONS – PAPER 3 Time: 2 Hours 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

2382-10 TEST QUESTIONS – PAPER 4 Time: 2 Hours 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

2382-10 TEST QUESTIONS – PAPER 5 Time: 2 Hours 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

MOCK EXAM PAPER 1

2382-20 TEST QUESTIONS – PAPER 1 1.

BS7671 applies to: a) b) c) d)

2.

BS 7671 does not apply to: a) b) c) d)

3.

neutral conductor line conductor neutral bar PEN conductor

Every installation should be divided into circuits as necessary to avoid: a) b) c) d)

6.

basic protection fault protection additional protection supplementary protection

Which of the following would not be defined as a live part? a) b) c) d)

5.

railway traction equipment photovoltaic systems marinas fairgrounds

Protection against electric shock under single fault conditions is: a) b) c) d)

4.

aircraft photovoltaic supplies distributors equipment electrical equipment of machines

fuse discrimination problems hazards to minimise inconvenience in the event of a fault unauthorised interference with safety supplies wiring impracticability

The protective measure ‘automatic disconnection of supply’: a) b) c) d)

is only permitted if the installation is under effective supervision is a method of reducing thermal effects is a combination of basic and fault protection is a combination of under and over voltage protection

7.

The maximum disconnection time for a 16A final circuit having Uo 230V ac on a TN system is: a) b) c) d)

8.

Where there is a danger of fire due to the nature of stored materials a motor with star – delta starting must be protected against excessive temperature: a) b) c) d)

9.

placing out of reach use of class II equipment earthing and bonding electrical separation

For a TT system where disconnection in the case of earth fault is achieved by RCD, the maximum disconnection time for a general socket in a domestic kitchen is: a) b) c) d)

12.

supplementary bonding use of a time delay 100mA RCD use of a RCD with l∆n not exceeding 30mA electrical separation

Which of the following is not a method of fault protection: a) b) c) d)

11.

in star in delta in both star and delta only if 10 kw or more

In the event of failure of the provision for basic protection, additional protection may be provided by: a) b) c) d)

10.

5s 0.2 s 0.4 s 0.1 s

0.1 s 0.2 s 0.4 s 5s

In the event of an earth fault on the HV side of a substation, the LV installation may be affected by: a) b) c) d)

power frequency fault currents power frequency stress voltages power current stresses power plus current stresses

13.

Connection of extraneous conductive parts to the MET of an installation forms part of the requirements for: a) b) c) d)

14.

Thermoplastic PVC T&E buried less than 50mm must be protected by: a) b) c) d)

15.

underground structural steel work welded metal reinforcement water utility supply pipes earth plates

Socket outlets with a rating not exceeding 20A for general use by ordinary persons should be: a) b) c) d)

18.

30 mA 100 mA 300 mA 500 mA

Which of the following may not be used as an earth electrode: a) b) c) d)

17.

MCB cpc the same size as the P & N 30mA RCD disconnection time of 0.4 s

RCD installed for protection against fire must have a rating not exceeding: a) b) c) d)

16.

SELV enclosures basic protection fault protection

connected as a ring circuit connected as a radial circuit protected by a 30mA RCD protected by a 20A CB

Lighting installations in bus shelters must be protected by: a) b) c) d)

CCTV double pole circuit breakers graffiti proof covers 30mA RCD

19.

Busbar trunking systems must comply with: a) b) c) d)

20.

The minimum acceptable value for insulation resistance in 230v supply is: a) b) c) d)

21.

high voltage is present parts inside may still be live following isolation PV array must be cleaned regularly PV arrays are fragile

All circuits in a bathroom must have: a) b) c) d)

24.

0.25 MΩ 0.5 MΩ 0.75 MΩ 1.0 MΩ

A PV generator and array junction box must have a warning label indicating that: a) b) c) d)

23.

0.25 MΩ 0.5 MΩ 1.0 MΩ 5.0 MΩ

Insulation resistance measured between line and neutral of a 230v domestic installation should not be less than: a) b) c) d)

22.

BSEN 60439-2 BSEN 61534-1 BSEN 60898-7 BSEN 60309-2

protection by a 30mA RCD disconnection time of 5 s supplementary bonding protected by a CB

Electrical cables in Zone 1 of a fountain shall be protected against mechanical impact to: a) b) c) d)

AG1 AG2 AH2 AH3

25.

On agricultural premises an RCD may be used for protection against fire providing that the rating of the RCD does not exceed: a) b) c) d)

26.

Any luminaries of lighting chains used at a circus must be firmly fixed when at a height less than: a) b) c) d)

27.

any earth conductors a PEN conductor any RCD’s protective devices

For a 100 mA non-delay RCD to BSEN 61008 the residual test currents and maximum permitted disconnection times are: a) b) c) d)

30.

allowed in all zones allowed in zones 1 & 2 allowed in zone 2 only not allowed

Where a TN system of earthing is used in a marina the final circuits for the supply of a pleasure craft must not include: a) b) c) d)

29.

1m 1.5 m 2m 2.5 m

In a bathroom the protective measure of obstacles is: a) b) c) d)

28.

30 mA 150 mA 300 mA 500 mA

100 mA 100 mA 100 mA 100 mA

300ms 130ms 0ms 400ms

500 mA 1500 mA 100 mA 500 mA

40ms 150ms 40ms 50ms

Flat T & E cable clipped direct to a ceiling joist where thermal insulation exceeds 100mm thickness is installation method: a) b) c) d)

101 100 3 20

2 HOUR MOCK EXAM PAPER 2

2382-10 TEST QUESTIONS – PAPER 2 1.

To which of the following electrical installations does the IEE Regulations NOT apply? a) b) c) d)

2.

The BS 7671 relates to permanent and temporary installations for: a) b) c) d)

3.

swimming pools petrol filling stations agricultural saunas

The MAXIMUM accessible distance that it should be assumed a person can reach when standing on a surface is: a) b) c) d)

6.

extra-low voltage low voltage safety extra-low voltage reduced low voltage

Which one of the following types of installation is NOT included in the special installations recognised by the IEE Wiring Regulations? a) b) c) d)

5.

equipment on board ships aircraft equipment construction sites electric traction equipment

An a.c. voltage of 90 V between conductors is classified as: a) b) c) d)

4.

agricultural and horticultural premises construction sites systems for transmission of energy to the public caravans and their sites

0.75 m 1.25 m 2.50 m 3.00 m

BS 7671 requires that the designer of a new installation shall: a) b) c) d)

have at least three years experience recommend future inspection and testing complete a periodic test report have a copy of BSD 7671

7.

Non-sheathed cables for fixed wiring, other than protective conductors, should always be installed in: a) b) c) d)

8.

A final circuit is the wiring between the: a) b) c) d)

9.

the kWh meter and an installation the distribution cables to an installation the consumer’s terminals of an installation a single source of energy and an installation

The total number of socket-outlets that may be connected to a fused spur is: a) b) c) d)

12.

estimating the external earth loop impedance supplying diversity factor for the installation selecting the system of earthing for the supply selecting the type of overcurrent protective device to be installed

A system is defined as: a) b) c) d)

11.

main cut-out and the energy meter main switch and the distribution board distribution board and current-using equipment consumer’s main earth terminal and circuit protective device

The prospective short circuit current at the origin of the consumer’s installation must be taken into account when: a) b) c) d)

10.

dry conditions trenches conduit or trunking sub-zero temperatures

one twin or one single socket – outlet equal to the total number of socket – outlets on the ring equal to half the number of socket – outlets on the ring unlimited depending upon the load

Residual current circuit breakers shall NOT be used on a TN system where a circuit incorporates: a) b) c) d)

protective conductors exposed conductive parts earthing conductors PEN conductors

13.

Which one of the following is a method of providing fault protection? a) b) c) d)

14.

In addition to regular maintenance of an installation, which one of the following is NOT an essential requirement? a) b) c) d)

15.

d)

that causes protective devices to operate of correctly occurring in a circuit which is electrically sound resulting from a fault of negligible impedance between live conductors of different phases flowing in a line conductor when in contact with exposed conductive parts

The IEE Regulations are designed to provide: a) b) c) d)

18.

12 V a.c. 25 V a.c 50 V a.c. 110 V a.c.

Overload current is defined as the overcurrent: a) b) c)

17.

periodic inspection and testing may be readily and safely carried out the name and address of the contractor is permanently displayed adjacent to the main intake position the reliability of the equipment is sustained protective measures for safety remain effective

Where separated extra-low voltage is used to provide basic protection and fault protection, the nominal voltage shall NOT exceed: a) b) c) d)

16.

placing out of reach double insulation protection by obstacles insulation of live parts

instructions for untrained persons safety especially from fire, shock and burns a detailed specification instructions for every circumstance in an installation

Which one of the following is not permitted as a means of isolation in a circuit? a) b) c) d)

double-pole switch fuse 13 A plug and socket semi-conductor device linked switch

19.

When a line conductor comes in contact with the neutral conductor, the type of fault is called: a) b) c) d)

20.

A means of isolation must be provided in an electrical installation. This is required to be: a) b) c) d)

21

b) c) d)

the fire fighter’s switch is fixed 4 m above the ground and the off at the top the fire fighter’s switch is coloured red and the off position is at the bottom The fire fighter’s switch is coloured red and fixed 2.5 m above the floor The fire fighter’s switch is fixed 2 m above the floor and off at the bottom

A fire fighter’s emergency switch should be provided for: a) b) c) d)

23.

clearly identified always placed next to the equipment it isolates automatic in operation available for emergency switching

Which one of the arrangements complies with the IEE Wiring Regulations? a)

22.

a short circuit fault an earth fault an overload fault an open circuit fault

emergency lighting systems operating at low voltage interior low-voltage discharge lighting installation exterior discharge lighting installations exceeding low voltage multi-storey office block fire alarm circuits operating above low voltage

The three general categories of external influence are environment, utilisation and: a) b) c) d)

the number and type of live conductors construction of building method of installation the installation earthing arrangements

24.

BS 7671 details the requirements of devices for emergency switching. Which of the following devices would NOT satisfy these requirements? a) b) c) d)

25.

Which one of the following is required to be considered by BS 7671 when assessing the general characteristics of an electrical installation? a) b) c) d)

26.

an emergency stop button which breaks the control circuit of a contactor a switch which breaks the control circuit of a contactor a 32 A plug and socket outlet a switch which breaks all live conductors

the standard of electricians working on site diversity switchgear rating maintainability

The following factors are used when calculating the minimum size of cable: ln Cg Ca Ci

= = = =

nominal current of protective device grouping correction factor ambient temperature correction factor thermal insulation correction factor

A circuit protected by a circuit breaker type B to BS EN 60898 would be supplied by a cable with a current carrying capacity not less than: a) b) c) d) 27.

I n x Ca C g x Ci I n x C g x Ci Ca In C a x C g x Ci Ca x Cg x Ci x In

When calculating the voltage drop in an installation which one of the following should be taken into account? a) b) c) d)

the cable current carrying capacity the operating current of the fuse the current rating of the fuse the circuit design current

28.

Which one of the following is not considered when calculating the minimum current carrying capacity of live conductors of a cable? a) b) c) d)

29.

For single circuit cable selection purposes the correction factors must be applied to the: a) b) c) d)

30.

25º C 20º C 30º C 35º C

Which one of the following is not recognised by BS 7671:2008 as the sole means of earthing an installation? a) b) c) d)

33.

AS3 AR3 AP3 AN3

Rating factors are applied to the fuse rating of a circuit to determine the minimum current-carrying capacity of cables. A rating factor of 1 is used when a circuit is wired in 70º C thermoplastic insulated cable and operating in an ambient temperature of: a) b) c) d)

32.

prospective short circuit current current carrying capacity of the cable current rating of the protective device the earth fault current of the circuit

The classification code for high wind is: a) b) c) d)

31.

ambient temperature grouping type of protective device the maximum permitted volt drop

metallic sheath of cables metal bars embedded in the building foundations metallic rod driven into the ground gas and water supply pipes

A BS 1361 fuse, rated at 45 A, is carrying a fault current of 240A, the protective device should operate in: a) b) c) d)

0.4 s 8.0 s 300 s 5.0 s

34.

The maximum permissible earth fault loop impedance on a TN system for a ring final circuit protected by a 30 A BS 1361 fuse is: a) b) c) d)

35.

The wording of a permanent warning notice fixed at the point of connection of an earthing conductor to an earth electrode is: a) b) c) d)

36.

c) d)

a safely isolating transformer to BS EN 61558 a motor generator with windings providing equivalent isolation to that of a safety isolating transformer a centre tapped transformer giving 55 V to earth a battery system operating at extra low voltage

The minimum size of a copper earthing conductor buried in the ground, NOT mechanically protected and NOT protected against corrosion is: a) b) c) d)

38.

Earth Connection – Do Not Remove Do Not Remove This Connection Electrical Earth Connection – Danger Safety Electrical Connection – Do Not Remove

Which one of the following sources does not comply with BS 7671 as a SELV system? a) b)

37.

1.15Ω 1.2Ω 1.92Ω 2.76Ω

10 mm² 16 mm² 25 mm² 50 mm²

When calculating the minimum cross-sectional area of a protective conductor, the following information is available: Fault current = 650 A Operating time of protective device = 0.35 sec Constant, k, for protective conductor material = 115 The selected size of the protective conductor should be: a) b) c) d)

2.5 mm² 4.0 mm² 6.0 mm² 10 mm²

39.

When a residual current device protects a socket outlet in a domestic garage it must operate when: a) b) c) d)

40.

Where an auto-transformer is connected to a single-phase supply (phase and neutral) the common terminal of the winding should be connected to the: a) b) c) d)

41.

full-load 1.5 x full-load 6 x full-load 10 x full load

As part of a detailed inspection which of the following must be checked? a) b) c) d)

43.

neutral conductor phase conductor circuit protective conductor main earthing terminal

Circuit cables required to carry the starting, accelerating and load currents of motors shall have a current rating not less than: a) b) c) d)

42.

an earth fault on the garage lighting circuit occurs the protective conductor in a flexible cord to a lawn mower breaks someone comes in direct contact with an exposed line conductor and earth someone comes in contact with exposed earth metalwork

the presence of fire barriers and protection against thermal effects the prospective short circuit current at the origin of the installation the maximum permissible voltage drop the manufacturer’s name of any RCD fitted

Which of the following items should be included for checking during the initial verification of an installation: a) b) c) d)

site works orders and alterations presence of diagrams and instructions minutes of all site meetings all variations of contract

44.

One item that should be included on charts and diagrams made available to the person carrying out an inspection and test is: a) b) c) d)

45.

Which on of the following insulation resistance test results, meets the minimum acceptable value for an installation with a 400 V supply? a) b) c) d)

46.

Zs Ze R1 R2

Electrical installation certificates should be signed by those responsible for the: a) b) c) d)

49.

250 V dc 400 V dc 500 V dc 1000 V dc

An earth fault loop impedance test determines the actual value of: a) b) c) d)

48.

5.0 MΩ 0.25 MΩ 0.5 MΩ 1.0 MΩ

The test voltage required to carry out an insulation resistance test on an installation with a nominal supply voltage of 400 V is: a) b) c) d)

47.

all isolation and switching arrangements the location details of portable equipment the total number of outlets in the installation the details of the original contract arrangements

inspection and testing only installation work only main contract design, construction and inspection testing

The result and extent of a Periodic Inspection and Test shall be recorded and given to the: a) b) c) d)

original installer person ordering the inspection representative of the supplier installation designer

50.

The following tests are to be carried out on a new installation 1 insulation resistance 2 continuity of ring final circuit 3 continuity of protective conductors 4 earth loop impedance 5 polarity The correct order of carrying out the tests is: a) b) c) d)

51.

One reason for carrying out a polarity test is: a) b) c) d)

52.

500 V and delivers a short circuit current of 100 mA 50 V and delivers a short circuit current of 200 mA 20 V and delivers a short circuit current of 100 mA 20 V and delivers a short circuit current of 200 mA

One of the purposes of an inspection prior to initial testing of an installation, is to verify that the installed equipment is: a) b) c) d)

54.

lighting switches work the outer screwed contact is connected to the phase conductor sockets are switched fuses are fitted in the phase conductor

When carrying out a continuity of circuit protective conductor test, it is recommended that a test instrument operates at: a) b) c) d)

53.

1, 2, 3, 4, 5 3, 2, 1, 5, 4 2, 3, 5, 1, 4 5, 4, 1, 2, 3

connected to the supply and energised not visibly damaged functioning safely when energised exceeds the minimum insulation resistance value

Electrical equipment installed above a swimming pool diving board should not be fixed at a height less than: a) b) c) d)

1.5 m 2.0 m 2.5 m 3.0 m

55.

Which of the following may be installed inside a hot air sauna? a) b) c) d)

56.

Construction site special regulations apply to: a) b) c) d)

57.

1.5 mm² 2.5 mm² 4.0 mm² 6.0 mm²

The maximum permissible height for a caravan inlet is: a) b) c) d)

60.

30 mA 150 mA 300 mA 500 mA

The minimum cross-sectional area of any conductor in a caravan is: a) b) c) d)

59.

all site offices earthworks site canteens site toilets

In agricultural premises, an RCD may be used for protection against fire providing the operating current does not exceed: a) b) c) d)

58.

a socket outlet fed from an SELV supply source a ceiling mounted cord operated light switch a thermostat mounted on the sauna any equipment and accessories to IP24

0.5 m 1m 1.5 m 1.8 m

One method acceptable to the IEE Regulations for providing fault protection on circuits feeding street furniture is by: a) b) c) d)

a non-conducting location earth free equipotential bonding automatic disconnection of supply electrical separation

PAPER 3 MOCK EXAM 2 HOURS

2382-10 TEST QUESTIONS- Paper 3

1.

BS7671 relates to electrical installations in and around buildings but excludes: a) b) c) d)

2.

Parts 3 to 7 of BS 7671 covers in detail methods and practices which meets the requirements of: a) b) c) d)

3.

dangerous chemicals shock currents high winds asbestos

Which one of the following types of installations is NOT within the statutory control of an authoritative body? a) b) c) d)

5.

Chapter 11 Chapter 12 Chapter 13 Part 2

The IEE Regulations recognises that in electrical installations there is a risk of injury from: a) b) c) d)

4.

agricultural and horticultural premises construction sites electrical equipment on board ships caravans

petrol stations caravan site theatre domestic

The type of building construction in which an installation is to be carried out may affect the design and safe operation of the installation. This effect is called: a) b) c) d)

the nature of the supply compatibility installation arrangements an external influence

6.

Which one of the following is not classed as a Band 1 voltage circuit? a) b) c) d)

7.

Which one of the following external influences requires an increase in the current ratings of cables above those normally required? a) b) c) d)

8.

earthing arrangements environment method of installation nature of supply

Where the circuit protective conductor is not a metal cable covering or metal trunking and conduit, the c.p.c for a ring final circuit must: a) b) c) d)

10.

the presence of light dust low ambient temperature high wind high ambient temperature

One of the general categories of external influences is: a) b) c) d)

9.

a bell circuit a 230 V lighting circuit a SELV circuit a 25 V signalling circuit

be run in the form of a ring having both ends connected to the earthing terminal have a cross-sectional area not less than that of the live conductors of the ring be made of aluminium be wired in single-core cable

A TN-C-S system has: a) b) c) d)

the neutral and earth functions combined in a single conductor in part of the system the exposed conductive parts of an installation connected to an earth electrode which is independent to the source a separate protective conductor connecting the source earth to the consumers main earth terminal the neutral and protective conductors are combined throughout the system

11.

Installations should be arranged so as to avoid danger and minimise inconvenience in the event of a fault and facilitate safe operation, inspection, testing and maintenance. One method of complying with this is to: a) b) c) d)

12.

The prospective short circuit current at the origin of the consumer’s installation must be taken into account when: a) b) c) d)

13.

use 10 A circuit breakers for the lighting circuits reduce the load on the consumer unit avoid danger in the event of a fault enable a greater variety of luminaires to be used

With reference to the general characteristics of an electrical installation, the maximum demand should be: a) b) c) d)

15.

assessing the value of the external earth loop impedance selecting the number of ways required for the main distribution board assessing the methods to be used to provide basic protection selecting the type of overcurrent protective device to be installed

A two-storey domestic dwelling should have a minimum of two lighting circuits in order to: a) b) c) d)

14.

connect all circuits on the radial principle fit an RCD at the main intake position divide the installation into separate circuits divide the installation into lighting and power

determined by the supply company calculated from the installation drawings obtained from the architect assessed, taking diversity into account

The requirements for both basic and fault protection can be provided by SELV. One suitable source of SELV would be a: a) b) c) d)

50 V storage battery 230 V diesel generator 230/110 V single phase generator 230/50 V auto-transformer

16.

Residual current circuit breakers shall NOT be used on a TN system where a circuit incorporates: a) b) c) d

17.

A component of a support system consisting of regularly spaced elements which mechanically retains a cable is defined as a cable: a) b) c) d)

18.

12 V ac 25 V ac 50 V ac 110 V ac

Which one of the following classifications of external influences would be appropriate for an item of electrical equipment installed where it would be subject to an atmosphere where heavy dust is present? a) b) c) d)

20.

bracket ladder cleat tray

SELV can be used as a means to meet the requirements of both basic and fault protection. In such cases the nominal voltage must not exceed: a) b) c) d)

19.

fuses exposed conductive parts socket outlets PEN conductors

AE1 BC1 AE6 AG1

The fault current due to an earth fault of negligible impedance in a 400 V, three phase, four wire circuit having an earth loop impedance of 0.3 ohms, is: a) b) c) d)

1383 A 767 A 124.5A 72A

21.

A section of a factory requires urgent repairs to a machine. The type of switching provided to allow this work to proceed would be switching for: a) b) c) d)

22.

The correct classifications of an external influence consisting of light dust is: a) b) c) d)

23.

0.725 1.45 1.8 5

A fault current caused by the line and neutral conductors to come in contact with each other is referred to as: a) b) c) d)

26.

lb = 22A, ln = 25A, lz = 18A lb = 18A, ln – 15A, lz = 15A lb = 9A, ln = 15A, lz = 17A lb = 8A, ln = 10A, lz = 8A

Where the overcurrent device is intended to afford protection against overload, l2 must NOT exceed lz times: a) b) c) d)

25.

AC2 BA2 AE4 AH3

lz is the current rating of a circuit conductor. The requirements for overload current protection are fulfilled when: a) b) c) d)

24.

mechanical movement mechanical maintenance emergency safe operation

an earth fault an overload fault a short circuit fault an open circuit fault

A 230 V single-phase circuit supplying a pump motor is protected by a 20 A circuit breaker to BS EN 60898 type B. The minimum value of fault current to ensure compliance with thermal and shock constraints is: a) b) c) d)

20 A 100 A 150 A 200 A

27.

Where a means of isolation is provided in an electrical installation, the means must be: a) b) c) d)

28.

Overload current is an overcurrent occurring in a circuit: a) b) c) d)

29.

1.0 mm² 1.5 mm² 2.5 mm² 4.0 mm²

The correction factor for a cable surrounded by thermal insulation for a length of 200 mm is: a) b) c) d)

32.

number of rooms within the installation number of heating units installed position of the junction boxes leakage capacitance

When 13 A socket outlets are wired from a fused spur using 70º thermoplastic insulated cable with copper conductors, the minimum conductor size permissible is: a) b) c) d)

31.

due to an earth fault due to a short-circuit fault that is electrically sound that is not fully loaded

The designer/installer of a ceiling heating system must provide a plan for the installation. Information NOT required on the plan would be the: a) b) c) d)

30.

clearly labelled always adjacent to equipment available for emergency switching automatic in operation

0.5 0.63 0.75 1.0

When selecting a cable for a single circuit installation, correction factors are to be used and applied to the: a) b) c) d)

total current taken by the installation current-carrying capacity of the cable design current of the circuit nominal current of the protective device

33.

Where protection against overload is provided by a semi-enclosed fuse to BS 3036, the current rating of the cable must be at least: a) b) c) d)

34.

Correct co-ordination between conductors and overcurrent protection device is achieved when: a) b) c) d)

35.

0.725 times the current rating of the fuse the nominal current rating of the fuse divided by 0.725 the same rating as the design current of the circuit 0.725 times the design current of the circuit

ln is not less than the design current lb ln exceeds the lowest current carrying capacity lz the current causing effective operation (l2) exceeds 1.45 l2 lb is greater than lz

In order to calculate the minimum value of the cross-sectional area of a protective conductor the following information is available Fault current = 300 A Operating time of the protective device = 0.6 s Constant k, for protective conductor material = 115 The minimum, cross-sectional area of the protective conductor should be: a) b) c) d)

36.

The rating factor to be applied for eight equally loaded circuits grouped together in conduit is: a) b) c) d)

37.

2.5 mm² 1.5 mm² 6.0 mm² 4.0 mm²

0.54 0.52 0.50 0.71

A circuit is protected by a 10 A BS 3036 semi-enclosed (rewireable) fuse. The minimum permissible current rating (lz) of a conductor protected by this fuse would be: a) b) c) d)

7.25 A 10 A 13.8 A 20 A

38.

An office installation is connected to a TT system and earth fault protection is provided by a residual current device. The product of the rated residual operating current of the device and the earth electrode resistance plus the protective conductor’s resistance connecting it to the exposed conductive parts shall not exceed: a) b) c) d)

39.

A circuit is connected to a TN system, the maximum permissible earth fault loop impedance (Zs) for a 32 A socket outlet circuit protected by a BS 88 fuse is: a) b) c) d)

40.

7.2 s 8.2 s 5s 0.4 s

The purpose of having equipotential bonding conductors connected to the other services as close as practicable to their entry into the premises is to: a) b) c) d)

42.

1.04Ω 1.09Ω 1.44Ω 0.92Ω

Regulation 434.5.2 gives the maximum time which may be permitted for a fault to be maintained without damaging the conductors. Assume a prospective fault current of 1000 A with a copper 25 mm² cable with 70º C thermoplastic insulation. The clearance time (t) is: a) b) c) d)

41.

0.5 V 230 V 50 V 500 V

ensure that earth leakage is minimised ensure that the maximum current will flow to earth under fault conditions reduce the chance of shock risk within the premises reduce the chance of electrolytic corrosion between metal sheath of cable and metal pipes

Where practicable main equipotential bonding to the gas services in a building should be made: a) b) c) d)

within 6 m of the meter on the supply side outside the building within 600 mm of the meter on the supply side within 600 mm of the meter on the consumer’s side

43.

Heating cables laid directly in soil, roads or building structures must be installed so that they are: a) b) c) d)

44.

For circuits of TN or TT systems, the outer contact of Edison type screw lamp holders must be connected to the: a) b) c) d)

45.

0.45 0.54 0.57 0.6

Which one of the following does NOT determine the frequency of periodic inspection and testing of an installation? a) b) c) d)

48.

55º C 65º C 70º C 80ºC

The correct grouping factor for 6 circuits of three conductors per circuit, run in the same conduit is: a) b) c) d)

47.

phase conductor earthing conductor neutral conductor protective conductor

The temperature limit for non-metallic equipment which is intended to be touched but not hand held is: a) b) c) d)

46.

at least 1 m below the surface fed only from an extra-low voltage supply completely embedded in the substance which they are intended to heat operated at 5º C

formal qualifications of the inspection and test staff the type of installation frequency of maintenance any external influence to which it is subjected

Every new installation on completion and before being energised must FIRST be: a) b) c) d)

subjected to a detailed inspection tested for continuity of ring circuit conductors tested for continuity of protective conductors given a test for insulation resistance

49.

Which one of the following items should be included for checking during the initial verification of an installation? a) b) c) d)

50.

Which one of the following British Standards covers residual current devices? a) b) c) d)

51.

40 ms 200 ms 0.4s 5s

The minimum value of insulation resistance when measured at the consumer unit of a 230 V domestic installation is: a) b) c) d)

54.

460 dc 500 dc 250 dc 1000 dc

When a 30 mA residual current device used to provide additional protection is tested at a residual current of 150 mA, the device should open in no more than: a) b) c) d)

53.

BS EN 61008 BS EN 60898 BS EN 60947 BS EN 60742

For an insulation resistance test on a 230 V ac installation containing surge protected socket-outlets, the value of the test voltage may be: a) b) c) d)

52.

site works orders and alterations presence of all diagrams and instructions electrical contractor’s site diary all variations of contract

0.25 MΩ 0.5 MΩ 1.0 MΩ 5.0 MΩ

The results of periodic inspection and testing should be recorded on a report and signed by the: a) b) c) d)

person ordering the inspection design engineer site engineer person carrying out the inspection and test

55.

Equipment fitted in Zone 1 of a bathroom must: a) b) c) d)

56.

In agricultural premises, an RCD may be used for protection against fire providing the operating current does not exceed: a) b) c) d)

57.

protection by earth free local equipotential bonding individual protection by electrical separation SELV protection by an RCD in accordance with Regulation 415.1.1

Which one of the following may be installed inside Zone 1 of a hot air sauna? a) b) c) d)

60.

at or near the main distribution point under the cover of the caravan electricity inlet box near the main electrical isolating switch inside the caravan on the inside of the main door of the caravan

In a swimming pool which of the following protective measures is NOT applicable to equipment installed in Zone 2? a) b) c) d)

59.

30 mA 100 mA 300 mA 500 mA

For all caravans using a mains electricity supply, an instruction notice must be fixed: a) b) c) d)

58.

be rated at a voltage not exceeding 12 V have a minimum IP rating of IPX5 have a minimum IP rating of IPX4 be fed from a plug and socket outlet

a ceiling mounted cord operated light switch a shaver socket to BS 3535 a thermostat attached to the side of the sauna any equipment to IP2X

With regards to a transportable unit, a notice fixed in a prominent position on the unit need not display: a) b) c) d)

the frequency of the supply the type of supply maximum power requirement voltage rating of the unit

PAPER 4 MOCK EXAM 2 Hours

2382-10 Test Questions – Paper 4 1

Particular requirements are included in BS 7671 for electrical installations of: a) b) c) d)

2.

Which one of the following types of installation is NOT included in the special installations recognised by BS 7671 a) b) c) d)

3.

extra-low voltage low voltage reduced low voltage SELV

The type of system known as PME is also referred to as: a) b) c) d)

6.

Electricity Safety, Quality and Continuity Regulations Electricity at Work Regulations Building Standards Regulations BS 7671 Requirements for Electrical Installations

A d.c. voltage of 125 V between conductors is classified as: a) b) c) d)

5.

swimming pools petrol filling stations agricultural saunas

Which one of the following sets of regulations is non-statutory? a) b) c) d)

4.

life installation covered by BS 5655 equipment of fixed offshore installations distributors equipment locations containing bath or shower

TN-S TN-C TN-C-S IT

A circuit protective conductor connects: a) b) c) d)

a gas pipe to the main earthing terminal a water pipe to the earth terminal of a switch in a bathroom the main earthing terminal to the earth terminal of a socketoutlet two water pipes in a bathroom

7.

An external influence categorized as AG1 applies to a: a) b) c) d)

8.

A building constructed solely of wood would have an external influence category of: a) b) c) d)

9.

factory low-voltage burglar alarm systems interior low-voltage discharge lighting installations exterior discharge lighting installations exceeding low-voltage factory fire alarm circuits operating at low-voltage

The protective conductor used within a final circuit has high protective conductor currents in excess of 10 mA when supplying more than one item of electrical equipment. The minimal cross-sectional area may be 4 mm², provided that: a) b) c) d)

11.

CA1 CA2 CA3 CA4

A fire fighter’s emergency switch should be provided for: a) b) c) d)

10.

quarry factory house workshop

additional protection from the use of a residual current device is present the protective conductor has additional mechanical protection individual items of equipment are supplied through an isolating transformer the protective conductor is in the form of a complete ring

Installations should be arranged so as to avoid hazards in the event of a fault, and to facilitate safe operation, inspection, testing and maintenance. One method of complying with this is to: a) b) c) d)

connect all circuits on the radial principle connect all circuits on the ring principle divide the installation into separate circuits divide the installation into bands of circuits

12.

A domestic 30A radial final circuit is used to supply BS 1363 socket outlets. If the floor area to be served is 55m², the rating of the protective device and the live conductor’s csa must not be less than: a) b) c) d)

13.

Which one of the following is not a characteristic of the supply? a) b) c) d)

14.

Class II enclosures extra-low voltage terminals exposed conductive parts made live by a fault live parts

The requirements regarding basic protection have not been applied if livestock comes into contact with: a) b) c) d)

17.

by enquiry to the local council offices after consultation with the local distributor by reference to BS 7671 by reference to the Electricity, Safety, Quality and Continuity Regulations

Basic protection protects persons and/or livestock from contact with: a) b) c) d)

16.

nominal voltage frequency earth loop impedance Ze emergency switching

The number and type of live conductors of a new electrical supply to a building may be determined: a) b) c) d)

15.

20A and 4 mm² 30A and 2.5 mm² 20A and 2.5 mm² 30A and 4 mm²

exposed conductive parts made live by a fault an exposed terminal within a faulty enclosure a protective conductor carrying fault current extraneous conductive parts made live by an earth fault

One method of providing basic protection is by: a) b) c) d)

earth free local equipotential bonding electrical separation automatic disconnection of supply barriers or enclosures

18.

A piece of electrical equipment having a protective conductor current of 15 mA is to be connected to the supply by means of a 16A plug and socket outlet complying with BS EN 60309-2. The cross sectional area of the protective conductor of the associated flexible cable shall not be less than: a) b) c) d)

19.

1.00mm² 1.5mm² 2.5mm² 4mm²

The maximum time (t) in seconds for the clearance of each and short circuit faults can be found from: k 2S 2 t= 2 I Given that k= s= I= t=

115 95 16000 time in seconds

The value of t is: a) b) c) d) 20.

The temperature limit for non-metallic equipment which is intended to be touched but not hand-held is: a) b) c) d)

21.

0.466s 0.683s 0.745s 0.826s

55ºC 65ºC 70ºC 80ºC

The prospective fault current at the origin of an electrical installation must be taken into account when: a) b) c) d)

estimating the external earth fault loop impedance applying diversity to the installation assessing the earthing arrangement selecting the type of overcurrent device to be installed

22.

Omission of devices for protection against overload is NOT permitted for: a) b) c) d)

23.

The nominal rating of an overcurrent protective device should be: a) b) c) d)

24.

b) c) d)

can be locked in the off position using a lock and key common to all other such isolators can be locked in the off position using a lock and key that are unique to that isolator is located so as to be in full view of persons working on the equipment is manually operated and a visual display is located next to the equipment

A firefighter’s switch should be installed at not more than: a) b) c) d)

26.

not less than the design current greater than the current carrying capacity of the conductors 1.45 times the load current equal to the prospective short-circuit current

The means of isolation for a particular item of equipment may be installed in a position remote from that equipment, providing that it: a)

25.

secondary circuits of current transformers circuits which supply fire extinguishing devices exciter circuits of rotating machines circuits which supply emergency lighting

2.75m from the ground and the ‘off’ position at the top 2m from the ground and the ‘off’ position at the bottom and coloured red 2.75m from the ground and the ‘off’ position at the bottom 2.75m from the ground and the ‘on’ position at the top and coloured red

Where the nominal voltage of an installation is 230V, the required minimum impulse withstand voltage for Category II equipment for overvoltage protection is: a) b) c) d)

1.5kV 2.5kV 4.0kV 6.0kV

27.

In a location where a risk of danger from fire exists due to manufacture or storage of combustible materials, enclosures of heaters shall not attain a surface temperature under normal working conditions exceeding: a) b) c) d)

28.

For a.c., the preferred frequencies which are taken into account in BS 7671 are: a) b) c) d)

29.

possible vertically falling drops of water low ambient temperature severe mechanical vibration high ambient temperature

To prevent circulating eddy currents (an electromagnetic effect) in steel conduit, trunking or cable armouring: a) b) c) d)

31.

25 Hz, 50 Hz and 60 Hz 50 Hz, 60 Hz and 400 Hz 25 Hz, 50 Hz and 250 Hz 50 Hz, 100 Hz and 400 Hz

Which one of the following external influences requires an increase in the current ratings of cables above those normally required? a) b) c) d)

30.

70ºC 90ºC 100ºC 115ºC

only d.c. must be used line and neutral conductors are to be kept separate the enclosures should be solidly earthed all live conductors of a circuit must be contained in the same enclosure

It is required that all circuits in a barn on an agricultural installation be protected by an RCD. The maximum rating (l∆n) for a circuit protected by a 40A BS 88 protective device should not exceed: a) b) c) d)

30 mA 100 mA 300 mA 500 mA

32.

In agricultural premises in locations where tractors are used, which one of the following methods of installation shall NOT be applied: a) b) c) d)

33.

A permanent warning notice must be fixed at or near the point of connection of every earthing conductor to an earth electrode. This notice must bear the words: a) b) c) d)

34.

0.37Ω 1.15Ω 2.3Ω 2.87Ω

Which one of the following is excluded as a protective earth electrode? a) b) c) d)

37.

linked switch residual current device disconnector circuit breaker

Where ADS is the means of providing fault protection and a 20 A type B circuit breaker to BS EN 60898 is used, the maximum earth fault loop impedance is: a) b) c) d)

36.

Earth Bonding Connection, Do Not Remove Safety Bonding Connection, Do Not Remove Earth Electrical Connection, Do Not Remove Safety Electrical Connection, Do Not Remove

Overcurrent protection may be provided by a: a) b) c) d)

35.

cables shall be buried at a depth of at least 0.6m with additional protection cables in arable ground shall be buried at a depth of at least 1m self supporting suspension cables at a height of at least 6m self supporting suspension cables at a height in excess of that accessible by rodents

underground structural metalwork embedded in foundations welded metal reinforcement of concrete embedded in the earth earth plates metalwork of public water services

A copper earthing conductor not mechanically protected and not protected against corrosion is buried in soil. The minimum size of the earthing conductor is: a) b) c) d)

4mm² 16mm² 25mm² 50mm²

38.

By employing an RCD protected socket-outlet to supply a Class II portable tool, the user is: a) b) c) d)

39.

A 13A socket-outlet supplies mobile equipment for use outdoors. Additional protection should be provided by means of a: a) b) c) d)

40.

d)

it shall be compatible with the material of the wiring system it shall prevent thermal movement of the wiring system it shall be of adequate mechanical stability to withstand the stresses which may arise it shall resist relevant external influences to the same degree as the wiring system

Where an autotransformer is used for step-up purposes: a) b) c) d)

42.

general purpose fuse circuit breaker residual current device class II equipment enclosure

In order to prevent the spread of fire where a wiring system passes through elements of building structures, any holes must be sealed around the cables. Which of the following is NOT a requirement for such sealing materials? a) b) c)

41.

protected against an earth fault in the windings of the tool protected against breakage of the protective conductor of the flexible cable provided with additional fault protection against contact with a live conductor exposed by carelessness of the user unable to operate the tool until the earthing circuit is complete and monitored

a single-pole switch can be used a linked switch breaking all live conductors must be used no controlling switch is required only a fuse is required

When installing socket outlets which will be mounted vertically on a wall or working surface, they should be: a) b) c) d)

shuttered and suitable for a.c. and complying with BS 1363 mounted 50mm from the floor level or working surface mounted so the flexible cord and plug top can be withdrawn or inserted without mechanical damage mounted so that the flexible cord and plug are 50mm from floor or working surface level

43.

Any circuit or equipment vulnerable to a particular test should be identified by: a) b) c) d)

44.

Which one of the following tests is carried out after the supply is connected? a) b) c) d)

45.

0.5Ω 1Ω 0.5MΩ 1MΩ

No alteration shall be made to an existing installation unless the: a) b) c) d)

48.

all ring final circuit connections are correct equipment is not damaged or defective only British Standard equipment is installed all electrical cables and conduits are pointed orange for identification

When testing a 230V installation, the minimum value of insulation resistance is: a) b) c) d)

47.

insulation resistance continuity of protective conductors continuity of ring final circuit conductors effectiveness of an RCD

The purpose of the inspection conducted prior to testing an installation is to verify that: a) b) c) d)

46.

the provision of a legible diagram, chart or table prior to testing a visual inspection prior to testing the manufacturer’s warning notice on the equipment the inventory for the building being tested

electricity supplier has been informed local authority has been informed it is established that the alteration will not impair the safety of the existing installation existing equipment meets BS and BS EN standards

The inspecting and testing required during a periodic inspection should be recorded on a Periodic Inspection Report and carried out by: a) b) c) d)

the person ordering the inspection a design engineer a site engineer a competent inspector

49.

Which one of the following factors does not affect the frequency of periodic inspection? a) b) c) d)

50.

Which one of the following numbers is the correct grouping factor for six circuits installed as method B? a) b) c) d)

51.

AB BC1 AD4 AG1

In rooms containing a bath or shower, the measures of protection by obstacles and placing out of reach are: a) b) c) d)

54.

E B F G

Which one of the following classifications of external influences would be appropriate for an item of electrical equipment installed where it would be subject to ‘splashes of water’? a) b) c) d)

53.

0.45 0.55 0.57 0.69

The reference for the installation method that has multi-core cables having a non metallic sheath, in surface mounted conduit is: a) b) c) d)

52.

type of installation installation use and operation frequency of maintenance supplies for safety services

permitted in zones 1 and 2 only not permitted in any circumstance permitted for SELV circuits only not permitted except for luminaries

The nominal supply voltage on temporary installations in shows and stands shall not exceed 230/400 V ac, or a) b) c) d)

110 V dc 230 V dc 240 V dc 500 V dc

55.

In a conduit system on an agricultural installation where livestock are kept, the external influence shall be classified as: a) b) c) d)

56.

On agricultural premises, heating appliances shall be fixed so as to maintain an appropriate distance from livestock. In the absence of manufacturer’s guidance, a radiant heater used in the vicinity of livestock should be placed at a distance of not less than: a) b) c) d)

57.

1m 2.5m 3m 5m

For household installations, as a rule of thumb, the floor area served by a single 20A radial circuit using socket outlets to BS 1363 may be: a) b) c) d)

60.

2 3 6 1

In exhibitions, protection against thermal effects must be provided for luminaries mounted below a height of: a) b) c) d)

59.

0.5m 1.5m 2.0m 2.5m

In a caravan park, the maximum number of socket outlets which can be protected by an RCD is: a) b) c) d)

58.

AF4 AG3 AF3 AG1

up to 20m² up to 50m² up to 100m² unlimited

Prior to an inspection in accordance with BS 7671, the competent person carrying out the work shall normally: a) b) c) d)

ensure that all switches are off disconnect the installation from the supply disconnect all fixed appliances ensure that the supply is connected

PAPER 5 MOCK EXAM 2 Hours

2382-10 Test Questions-Paper 5 1.

To which one of the following situations does BS 7671 apply? a) b) c) d)

2.

Which one of the following is listed under exclusions from the scope of BS 7671? a) b) c) d)

3.

below 250 V a.c below 1000 V a.c. but above 50 V a.c. above 50 V a.c. but below 500 V a.c. above 250 V a.c. but below 1000 V a.c.

An ordinary person is a person who: a) b) c) d)

6.

Electricity Safety, Quality and Continuity Regulations Electricity at Work Regulations Building Regulations BS 7671

BS 7671 defines low voltage a.c. between conductors as voltage: a) b) c) d)

5.

saunas swimming pools marinas lightning protection

Which one of the following sets of regulations is non-statutory? a) b) c) d)

4.

the manufacture of electrical equipment the inspection and testing of the electrical installation on an oil rig the design of an electrical installation for a caravan site the public electricity supply system

is skilled at electrical work works in electrical maintenance is neither skilled nor instructed at least 18 years old

A 12 V fire alarm circuit is classified by BS 7671 as: a) b) c) d)

a Band I circuit a Band II circuit a Band III circuit an unclassified circuit

7.

Which one of the following is NOT a classification of external influence? a) b) c) d)

8.

The type of building construction is an external influence which, in an electrical installation, will affect the choice of: a) b) c) d)

9.

4 mm² 2.5 mm² 1.5 mm² 6 mm²

A domestic final ring circuit may: a) b) c) d)

12.

dry conditions trenches conduit or trunking sub-zero temperatures

Domestic ring final circuits are used to supply BS 1363 socket outlets. If the floor area to be served is limited to 50 m², the cable feeding the circuit must be: a) b) c) d)

11.

equipment and wiring method of earthing overcurrent protection supply voltage

Non-sheathed cables for fixed wiring, other than protective conductors, should always be installed in: a) b) c) d)

10.

current rating environmental conditions construction of buildings utilisation

supply any number of socket-outlets over an area of 200 m² feed an immersion heater require additional protection by an RCD supply a cooker rated at 2.5 kW

Where thermoplastic insulated and sheathed cables are installed in a plastered wall at a depth of 20 mm and are not protected against mechanical damage, they must be: a) b) c) d)

run in “safe zones” protected by a 30 mA RCD coloured red protected by a 30 mA RCD and run in the “safe zones”

13.

A two-storey domestic dwelling should have a minimum of two lighting circuits in order to: a) b) c) d)

14.

A system is defined as: a) b) c) d)

15.

opened without use of a key or tool left unearthed used to accommodate SELV circuits used to accommodate ELV circuit conductors

A socket-outlet used for a SELV system should: a) b) c) d)

18.

protection against electric shock under fault free conditions extra-low voltage terminals protection against electric shock under a single fault condition live parts within an appliance

Within a 230 V single-phase, metal clad fuse board, access to the line and neutral busbars are protected by insulation and by secured intermediate barriers. The fuse board may be: a) b) c) d)

17.

the kWh meter and an installation the distribution cables to an installation the consumer’s terminals of an installation a single source of energy and an installation

The term “basic protection” refers to: a) b) c) d)

16.

make the installation process easier reduce the load on the consumer’s control unit avoid danger in the event of a fault enable a greater variety of luminaries to be used

not have a protective conductor contact be of a two-pin type be marked SELV have a protective conductor contact

Which one of the following is recognised as a means of providing fault protection? a) b) c) d)

protection by insulation of live parts protection by automatic disconnection protection by placing out of reach protection by obstacles

19.

Where SELV is used in normally dry conditions, basic protection is unnecessary where the nominal voltage does not exceed: a) b) c) d)

20.

Obstacles may be used to provide basic protection providing: a) b) c) d)

21.

c) d)

excessive mechanical load is applied to an electric motor a forward/reverse controller attempts to switch a motor both directions simultaneously contamination of a motor terminal block results in tracking an electrician drills into a busbar chamber and touches a live busbar with the drill

Where the overcurrent device is intended to afford protection against overload, l2 must not exceed lz multiplied by: a) b) c) d)

24.

that causes protective devices to operate correctly occurring in a circuit which is electrically sound resulting from a fault of negligible impedance flowing in a phase conductor when in contact with exposed conductive parts

An overload current could arise when: a) b)

23.

the circuit voltage does not exceed 250 V the installation is under the control of a skilled person the installation is contained within steel conduit an RCD is fitted

Overload current is defined as the overcurrent: a) b) c) d)

22.

12 V a.c. 25 V a.c 50 V a.c 60 V a.c.

0.735 1.45 1.8 2.5

Omission of devices for protection against overload is not permitted for: a) b) c) d)

secondary circuits of current transformers circuits which supply fire extinguishing devices exciter circuits of rotating machines circuits which supply emergency lighting

25.

Which one of the following may be used to provide emergency switching for an electric motor? a) b) c) d)

26.

A section of a factory requires urgent non-electrical repairs to a machine. The type of switching provided to allow this work to proceed would be switching for: a) b) c) d)

27.

b) c) d)

half the csa of the earthing conductor and with reference to Table 54.7 selected in accordance with the supply neutral and Table 54.8 determined after consultation with the consumer the same csa as the incoming line conductor

Which one of the following cannot be used as an earth electrode? a) b) c) d)

30.

circuit breakers plugs and socket outlets semiconductor devices fuse links

Where PME conditions apply, the main protective bonding conductor shall be: a)

29.

mechanical movement mechanical maintenance emergency safe operation

Which one of the following shall not be used as an isolator? a) b) c) d)

28.

a key switch latched in the on position a plug and socket a switch fuse with a removable handle a device which latches in the off position

copper water supply pipe earth tape or wire lead sheath covering of cable welded reinforcement of concrete embedded in the earth

Using Table 54.7 of BS 7671, the minimum cross-sectional area of a circuit protective conductor with a 10 mm² line conductor will be: a) b) c) d)

25 mm² 16 mm² 10 mm² 4 mm²

31.

In order to calculate the minimum value of the cross-sectional area of a protective conductor, the following information is available: Fault current = 700 A Operating time of protective device = 0.4 s Constant k, for protective conductor material = 115 The selected size of the protective conductor should be: a) b) c) d)

32.

Supplementary bonding conductors having mechanical protection connected between two extraneous conductive parts are subject to a minimum cross-sectional area of: a) b) c) d)

33.

presence of water reduction in body resistance contact of body with earth potential the reduced resistance of salt water

A final circuit supplying 13 A socket-outlets is to be used by ordinary persons. The circuit must be provided with: a) b) c) d)

35.

1.5 mm² 2.5 mm² 4 mm ² 6 mm²

In a marina, corrosive elements exist, structures can move, mechanical damage can occur, a possible presence of flammable fuel is present and an increase in the risk of electric shock is possible. Which one of the following is NOT taken into consideration when determining any external influence requirements? a) b) c) d)

34.

2.5 mm² 4 mm² 6 mm² 16 mm²

protection by an RCD a BS EN 60898 circuit breaker additional protection in accordance with Regulation 415.1 switched socket-outlets

Socket outlets which are under the supervision of skilled persons: a) b) c) d)

do not require additional protection must be mounted 450 mm above the floor must disconnect within 5 s in the event of an earth fault must be to BS EN 60309

36.

Ceiling roses are only allowed where the circuit voltage does not exceed: a) b) c) d)

37.

The minimum cross-sectional area for a buried copper earthing conductor that is provided with mechanical protection but no protection against corrosion is: a) b) c) d)

38.

b)

c) d)

it must be set to a higher value corresponding to the normal insulation of the system it must be designed in such a way that it is impossible to modify the setting without the use of a tool, if the location is accessible to ordinary persons an IT system must not be used instruction must be available that indicate how to switch the device off if it detects a fault

A circuit with a design current of 45 A is installed using a cable with a current rating of 50 A. If the voltage drop for the cable is 8 mV per amp per metre, the circuit voltage drop for a 10 m run will be: a) b) c) d)

40.

2.5 mm² 10 mm² 16 mm² 25 mm²

When an insulation monitoring device (IMD) is installed: a)

39.

110 V 250 V 415 V 11 kV

2.5 V 3.6 V 4V 6V

Which one of the following should be taken into consideration when calculating the voltage drop in an installation? a) b) c) d)

nominal current setting of the protective device design current of the circuit current carrying capacity of the conductors the current that ensures effective operation of the protective device

41.

On a mobile or transportable unit, plugs used to connect the unit to the supply shall comply with BE EN 60309-2 and: a) b) c) d)

42.

The fault current due to an earth fault of negligible impedance in a 400 V, three phase, four wire circuit having an earth fault loop impedance of 0.3 Ω is: a) b) c) d)

43.

line 1 of a three phase a.c. circuit earth conductor line 2 of a three phase a.c. circuit line 3 of a three phase a.c. circuit

An unfused spur connected to a 30 A ring circuit may supply: a) b) c) d)

46.

0.2 s 0.4 s 4s 5s

A black sleeve or disc is placed on one of the conductors of a threecore MICC cable. This indicates the: a) b) c) d)

45.

1383 A 766.6 A 124.5 A 72 A

A 30 A protective device to BS 1361 when carrying a fault current of 200 A should operate in: a) b) c) d)

44.

shall be enclosed in a metal enclosure the plug part be on the supply distribution board any plug and socket outlets shall afford a degree of protection of not less than IP44 if located inside appliance inlets with their enclosures shall provide a degree of protection of at least IP44

two fixed appliances two twin socket-outlets or one fixed applianced one twin socket-outlet or one single socket-outlet an unlimited number of socket-outlets

Prior to an inspection in accordance with BS 7671, the competent person carrying out the test shall normally: a) b) c) d)

ensure that all switches are off disconnect the installation from the supply disconnect all fixed appliances ensure that the supply is connected

47.

A legible diagram, chart or table relating to an installation must be provided to indicate: a) b) c) d)

48.

When carrying out an insulation resistance test on a 230 V socketoutlet circuit incorporating surge protective devices (SPD), the test voltage may be reduced to: a) b) c) d)

49.

0.25 MΩ 0.5 MΩ 1 MΩ 5 MΩ

Which one of the following is the required test procedure if an existing installation is extended to include extra lighting and socket outlets? a) b) c) d)

52.

inform the client make good and complete the Periodic Inspection Report make good and complete the Electrical Installation Certificate record the fault on the Periodic Inspection Report

For circuits having a nominal voltage above 500 V, the minimum insulation resistance is: a) b) c) d)

51.

500 V 1000 V 50 V 250 V

During an initial verification, a test result fails to comply with BS 7671 Part 6. The procedure to be adopted is to: a) b) c) d)

50.

the location of all fixed equipment for testing purposes any circuit of equipment vulnerable to a typical test location of all portable equipment for testing purposes that the original installation design has not changed

insulation resistance no testing is required, only visual inspection ring circuit continuity test only all relevant tests must be carried out

It is a requirement of BS 7671 that a Schedule of Test Results should always be attached to an Electrical Installation Certificate for: a) b) c) d)

new installations, alterations or additions to existing installations new installations only major installations only modified installations only

53.

BS 7671 requires that the person ordering installation work must be informed of the: a) b) c) d)

54.

Which one of the following factors does not affect the frequency of the periodic inspection? a) b) c) d)

55.

IPX8 IP4X IP2X IPX4

Construction site regulations apply to: a) b) c) d)

58.

supplied from an electrically separated source covered with at least 50 mm of screed surrounded with thermal insulating material covered by an earthed metallic grid

Electrical equipment installed in Zone 1 of a swimming pool must have a minimum degree of protection in accordance with: a) b) c) d)

57.

type of installation installation use and operation frequency of maintenance supplies for safety services

Electric heating units embedded in the floor of a bathroom and intended for heating the location may be installed below any zone provided they are: a) b) c) d)

56.

need for periodic testing name and address of the regional electricity company anticipated life of the installation diversity factors applied to circuit

all site offices earthworks site canteens site toilets

In agricultural premises, heating appliances shall be fixed so as to maintain an appropriate distance from livestock. In the absence of manufacturer’s guidance, a radiant heater used in the vicinity of livestock should be placed at a distance of not less than: a) b) c) d)

0.5m 1.5m 2m 2.5 m

59.

The socket outlet and its enclosure, forming part of a pitch supply equipment for a caravan park, must comply with BS EN 60309-2 and have a minimum index of protection of: a) b) c) d)

60.

IP40 IP55 IP54 IP44

Inspection and testing of a fairground installation must take place: a) b) c) d)

every three months after each assembly on site only if it is fed from the public supply system only if it is fed from an a.c. supply

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF