MINERVA MZX 125/250 ADDRESSABLE FIRE DETECTION SYSTEMS USER MANUAL
V1.0/13/11/08
NOTICE All rights reserved. Reproduction of any part of this manual in any form whatsoever without Thorn Security’s express written permission is forbidden. The contents of this manual are subject to change without notice. All effort has been made to ensure that the accuracy of this manual. However, should any errors be detected, Thorn Security would greatly appreciate being informed of them. The above not withstanding, Thorn Security can assume no resposibility for any errors in this manual or their consequences.
For further information, see Tyco Safety Product’s web site at: www.tycoemea.com
MZX 125/250 Fire Detection Systems
Content 1
Guide to this manual ............................................ 6
2
Introduction .......................................................... 6
2.1
Key function and features ............................................................................ 6
3
Operating Instructions....................................... 10
3.1 3.1.1 3.1.2 3.1.3 3.1.4
Operator’s indicators and controls ............................................................ 10 General ....................................................................................................................................... 10 Display control module .......................................................................................................... 10 Indicators ................................................................................................................................... 14 Switches..................................................................................................................................... 14
3.2 3.2.1 3.2.2 3.2.3 3.2.4
LCD display ................................................................................................... 15 Fire window............................................................................................................................... 15 Status window.......................................................................................................................... 16 Main window ............................................................................................................................ 16 Softkey window ....................................................................................................................... 16
3.3 3.3.1 3.3.2
Normal operation ......................................................................................... 16 Event monitoring ..................................................................................................................... 17 Event display ............................................................................................................................. 17
3.4 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5
Operation in alarm ....................................................................................... 18 System response ..................................................................................................................... 18 Sounder silencing .................................................................................................................... 19 Resetting the controller.......................................................................................................... 20 Multiple events......................................................................................................................... 20 Pre-alarm warning ................................................................................................................... 21
3.5 3.5.1 3.5.2
Operation in fault condition........................................................................ 21 System response ..................................................................................................................... 21 Operator action ........................................................................................................................ 21
3.6 3.6.1 3.6.2 3.6.3 3.6.4
Fire control keys .......................................................................................... 22 Evacuate..................................................................................................................................... 23 Day/night mode....................................................................................................................... 23 Investigate delay ...................................................................................................................... 23 Test .............................................................................................................................................. 24
3.7 3.7.1 3.7.2 3.7.3 3.7.4
Auxiliary display devices ............................................................................ 24 General ....................................................................................................................................... 24 Repeaters................................................................................................................................... 24 Printers ....................................................................................................................................... 24 LCD repeaters ........................................................................................................................... 24
3
Doc version 1
MZX 125/250 Fire Detection Systems
4
Controller Functions...........................................25
4.1 4.1.1
Access levels ............................................................................................... 25 General ....................................................................................................................................... 25
4.2
Entering passcodes ..................................................................................... 26
4.3
Valid values .................................................................................................. 26
4.4
Main menu.................................................................................................... 27
4.5
Accept events .............................................................................................. 28
4.6
View status .................................................................................................. 28
4.7
Isolate/de-isolate ........................................................................................ 31
4.8 4.8.1 4.8.2
Time/date ..................................................................................................... 34 Set time/date ........................................................................................................................... 34 Summer/winter....................................................................................................................... 35
4.9 4.9.1 4.9.2 4.9.3
Event log....................................................................................................... 35 View event log.......................................................................................................................... 36 Print event log .......................................................................................................................... 36 Filter ............................................................................................................................................ 37
4.10 4.10.1 4.10.2 4.10.3 4.10.4 4.10.5 4.10.6 4.10.7
View/print status......................................................................................... 38 View/print point isolated....................................................................................................... 38 View/print points untested/failed ...................................................................................... 39 View/print point values ......................................................................................................... 40 View faults................................................................................................................................. 41 View loop point counters....................................................................................................... 41 Active points ............................................................................................................................. 44 By function ................................................................................................................................ 45
4.11 4.11.1 4.11.2 4.11.3
Service .......................................................................................................... 47 Walk test.................................................................................................................................... 47 Maintenance............................................................................................................................. 52 Configuration............................................................................................................................ 55
5
Routine checks ...................................................63
5.1
General ......................................................................................................... 63
5.2
Daily checks................................................................................................. 63
5.3
Weekly checks ............................................................................................ 63
4
Doc version 1
MZX125/250
1
Manual Guide
Guide to this manual
In this documentation keywords and symbols denote warnings, info or instructions (see table 1). Keyword DANGER
Symbol
Explanation Warning. Imminent danger. Death or severe injury when disregarded.
WARNING
Warning. Potentially dangerous situation. Death or severe injury possible when disregarded.
CAUTION
Warning. Potentially dangerous situation. Minor injury or material damage possible when disregarded. Helpful information.
Tab. 1: Keywords and symbols in this documentation
Doc. version 1
5
MZX 125/250 Fire Detection Systems
Fig.. 1:
6
MZX125
Doc. version 1
MZX125/250 Fire Detection Systems
Fig.. 2:
Doc. version 1
MZX250
7
MZX 125/250 Fire Detection Systems
2
INTRODUCTION The instructions given in this document are common to all the ‘MZX125 and MZX250’ fire controllers, any differences being outlined as appropriate This document is written for Firmware Version 14. The MINERVA MZX 125/250, form a comprehensive and compatible range of modular and flexible EN54 approved addressable fire controllers using Tyco MZX TechnologyTM. Both variants fully comply with the requirements of EN54 parts 2 and 4 and may be installed in a system which complies with the requirements of BS 5839 : Part 1.
2.1
KEY FUNCTIONS AND FEATURES
The MZX controllers are built around common hardware and software modules incorporating the following common functions and features:
8
Full EN54 compliant control switches and indicators with keyswitch enable and optional programmable LED indicators and control switches.
Large backlit 16 line x 40 character LCD display with detailed and precise identification of all sectors, zones and points, comprehensive 95 character emergency procedure instructions and full system status indication including counters of number of points in alarm, fault, disabled and test mode.
Extensive menu driven and password controlled operator and engineer functions including extensive isolate, override, test, service and diagnostic functions.
System manager and engineer functions including editing of point descriptions and viewing/printing of point values including CO levels, temperatures and detector obscuration levels.
Optional self-test and verification of detectors from the controller.
Peer-to-peer communication with up to 98 other controllers providing a seamless operator interface to all other relevant defined controllers on the network.
Event log for logging of up to 3000 events which can be viewed, selected and printed.
Constant monitoring of all detectors and input circuits and processing of detector sensor information using standard, CCO and FastLogic fuzzy logic algorithms.
Long term averaging and condition monitoring of smoke detectors with dirty detector identification.
Automatic or manual switching of detector modes and sensitivities according to changes in occupancy patterns (day mode) and variations in fire risk.
Doc. version 1
MZX125/250 Fire Detection Systems
Constant fault monitoring of all hardware components, power supplies, batteries, relays, sounder and speaker circuits, addressable loops, detectors and addressable devices, monitored input circuits, remote and local communication links.
Communication with up to 125 addresses on one detection loop (MZX125) or 250 addresses on one detection loops (MZX250) per controller and a combination of up to 1500 auxiliary I/O, controller plus 7 full function repeaters and multiple remote printers.
Signalling, supervision, status and fault indication of central station alarm signalling equipment such as BT Redcare STU.
Option for one repeater to be provided from a remote PC computer using MX-Remote service and diagnostics software over the public switched telephone network (PSTN).
Default cause and effect providing computer control of all outputs, sounders, beacons and speakers in the event of alarm conditions.
Powerful programmable cause and effect using the flexible and easily configured MINERVA group based event/action programming language.
Synchronisation and multiple output pulse patterns for phased evacuation of up to 16 zones (MZX125) or 32 zones (MZX250) using “Bell Mapping”.
Powerful programmable cause and effect using the flexible and easily configured MINERVA group based event/action programming language.
Doc. version 1
9
MZX 125/250 Fire Detection Systems
3
OPERATING INSTRUCTIONS 3.1
OPERATOR’S INDICATORS AND CONTROLS
3.1.1
GENERAL
ALL operator controls and indicators are mounted on the front panel.
3.1.2
DISPLAY CONTROL MODULE
The Display Control Module (Fig. 3 MZX125 and Fig. 4 MZX250) contain the following indicators and controls:
10
A 640 character backlit LCD alphanumeric display, arranged in 16 rows of 40 characters. This is used to display information about the system status and alarms. The backlight is on when the keyswitch is set to the ‘enable’ position, when a key is pressed or when an Alarm or Fault is present.
Switches F1 to F5 - used to carry out the functions displayed on the bottom line of the LCD display.
An alphanumeric keypad used for entering access codes, text strings or general information as follows:
Doc. version 1
MZX125/250 Fire Detection Systems
0
Used to enter the number 0
1
Used to enter the number 1 or special symbols
2
Used to enter the number 2 or letters ‘A’, ‘B’ or ‘C’
DEF
3
Used to enter the number 3 or letters ‘D’, ‘E’ or ‘F’
4 GHI
Used to enter the number 4 or letters ‘G’, ‘H’ or ‘I’
ABC
JKL
5
Used to enter the number 5 or letters ‘J’, ‘K’ or ‘L’
6 MNO
Used to enter the number 6 or letters ‘M’, ‘N’ or ‘O’
7
Used to enter the number 7 or letters ‘P’, ‘Q’, ‘R’ or ‘S’
TUV
8
Used to enter the number 8 or letters ‘T’, ‘U’ or ‘V’
9 WXYZ
Used to enter the number 9 or letters ‘W’, ‘X’, ‘Y’ or ‘Z’
PQRS
SCROLL UP and SCROLL DOWN keys - used to scroll through a display or log one entry at a time. These keys will auto-repeat if held down, ie, will scroll continuously.
When used in conjunction with the Configuration menu, the UP key switches to upper case and the DOWN key to lower case.
Doc. version 1
11
12
0
F1
1
F2 SILENCE RESOUND
DAY NIGHT
EVACUATE
ACTIVATED FAULT DISABLED
ACTIVATED FAULT DISABLED
ACTIVATED FAULT DISABLED
SYSTEM FAULT DAY MODE
DISABLED TEST
PROTECTION
INVESTIGATE DELAY
SIGNALLING
RESET
POWER ON
SOUNDERS
SILENCE BUZZER
16
15
7 8
14
6
MAINS FAULT
PANEL
F5
WXYZ
13
5
FAULT
F4
0
TUV
9
12
4
11
10
2 3
9
1
FIRE
GENERAL
F3
PQRS
8
7
MNO
6
JKL
5
3
DEF
2
ABC
GHI
4
*
1
MZX 125/250 Fire Detection Systems
Fig.. 3: MZX125 Display Control Module
Doc. version 1
MZX125/250 Fire Detection Systems
1
2
*
3
ABC
4
DEF
5
GHI
6
MNO
JKL
7
8
PQRS
TUV
9
WXYZ
0 F3
F2
F1
SILENCE BUZZER
SILENCE RESOUND
GENERAL
F4
RESET
PANEL
DAY NIGHT
0
F5
1
INVESTIGATE DELAY
SOUNDERS
EVACUATE
SIGNALLING
PROTECTION
FIRE
POWER ON
ACTIVATED
ACTIVATED
ACTIVATED
FAULT
MAINS FAULT
FAULT
FAULT
FAULT
DISABLED
SYSTEM FAULT
DISABLED
DISABLED
DISABLED
TEST
DAY MODE
ZONE DISPLAY 1
5
9
13
17
21
25
29
2
6
10
14
18
22
26
30
3
7
11
15
19
23
27
31
4
8
12
16
20
24
28
32
Fig.. 4: MZX250 Display Control Module
Doc. version 1
13
MZX 125/250 Fire Detection Systems
3.1.3
CONTROL CONTROL MODULE
The Display Control Module contains the following indicators and controls: INDICATORS GENERAL A red Fire LED. A yellow Fault LED. A yellow Disabled LED. A yellow Test LED.
PANEL A green Power ON LED. A yellow LED to indicate Mains Fault. A yellow LED to indicate System Fault. A yellow LED to indicate Day Mode.
SOUNDER A red Activated LED. A yellow Fault LED. A yellow Disabled LED.
SIGNALLING A red Activated LED. A yellow Fault LED. A yellow Disabled LED.
PROTECTION A red Activated LED. A yellow Fault LED. A yellow Disabled LED.
ZONES
One red (Fire) and one yellow (Fault) LED per zone .
SWITCHES
14
‘ENABLE’ keyswitch - a two position keyswitch, with positions ‘normal’ and ‘enable’.
Seven control switches:
‘SILENCE BUZZER’ - used to silence the internal buzzer.
‘SILENCE/RESOUND’ - used to silence/resound external sounders.
‘RESET’ - used to reset the system after an alarm or event has occurred.
Doc. version 1
MZX125/250 Fire Detection Systems
3.2
‘DAY MODE’ - used to set the system into the daytime operation mode.
‘INVESTIGATE DELAY’ - is used to end signalling delay time and start the investigation time.
‘SPARE’ - is configurable to customer requirements.
‘EVACUATE’ - is used to activate external sounders.
LCD DISPLAY
The LCD display is divided into four windows as shown in Fig. 5:
Fire19 characters x 8 lines
Main
19 characters x 14 lines
Status
19 characters x 5 lines
Softkeys
F1, F2, F4 and F5 - 7 characters, F3 - 8 characters
1 1234567890123456789 2 3 Fire 4 Window 5 6 7 8 1 2 3 4 5
Status Window
S'key 1 S'key 2
1 1234567890123456789 2 3 Main 4 Window 5 6 7 8 9 0 1 2 3 4
S'key 3
S'key 4 S'key 5
Fig.. 5:
3.2.1
FIRE WINDOW
The fire window in the quiescent mode will display the product name, date/ time and company name. On detection of an Alarm condition, the fire window will display ‘First Fire’ and associated information. For multiple alarms in the system the fire window will display the first and last alarms. The number of alarms is displayed at the right hand side of line 5 in the fire window.
Doc. version 1
15
MZX 125/250 Fire Detection Systems
First Fire Zone 002 B001 1st Floor Corridoor Room 117 Last Fire 002 Zone 030 B055 4th Floor Washroom / Window
3.2.2
STATUS WINDOW
The status window displays the number of faults, isolates etc.
3.2.3
MAIN WINDOW
The main window displays logs, information text, menus and device identification.
3.2.4
SOFTKEY WINDOW
The softkey windows change dependant on the option selected.
3.3
NORMAL OPERATION
When the controller is initially powered up, with no faults or alarms in the system and the ‘Enable’ key in the ‘off’ position, the following screen is displayed:
MX Panel Fri, 17-Mar-08 11:57 Company Name
General
LED Tst
16
Not Clr Light
Doc. version 1
MZX125/250 Fire Detection Systems
3.3.1
EVENT MONITORING
The term ‘event’ is used to describe a change in system status that must be acknowledged and/or generates an output. Examples of events include:
Mains failure
Detection of a fire condition
Operation of ‘EVACUATE’ key
All events trigger a response, the category of which depends on the event type and will be one of the following (in priority order):
Full Alarm or Alert
Pre-Alarm
Fault
Isolation
Test Mode
Warning
Information
When an event occurs, it is stored in the event log. The contents of this log may be displayed in two formats:
Unaccepted and locally accepted events
All events in chronological order of occurrence
The events are stored in chronological order with unaccepted events marked as outstanding. The event log may hold up to 3000 events; in the unlikely occurrence of the log filling up, the oldest record will be overwritten.
3.3.2
EVENT DISPLAY
The display automatically shows the last event of the category with the highest priority. With Scroll keys, it is possible to get all events in this category in chronological order. With Softkey F5 the user can change to another category (if available). Important: Category ‘Full Alarm/Alert’ shows only the first point of a zone in alarm. If two points of one zone are in alarm, only the first one which was in alarm will be displayed. The second alarm can only be accessed via the menu option ‘View Event Log’.
Doc. version 1
17
MZX 125/250 Fire Detection Systems
3.4
OPERATION IN ALARM
3.4.1
SYSTEM RESPONSE
When a fire condition is detected, the system responds as follows: 1
The internal buzzer will sound in a continuous tone.
2
The red ‘FIRE’ LED will light.
3
The SOUNDERS and NOTIFICATION STATUS ‘ACTIVATED’ red LEDs will light.
If the alarm is initiated by a detector, there may be a delay of from 1 to 10 minutes before the NOTIFICATION STATUS ‘ACTIVATED’ led lights. This is to allow time for the alarm to be investigated and any relevant action taken before signalling is initiated. A Callpoint set to evacuate will initiate signalling immediately. Refer to Section 2.6.3. 4
For the MZX controllers, the sounders and any other configured outputs will be activated.
5
The LCD will display a message in the format:
FirstFirst Fire Fire Zone 002 B002 1st Floor Corridoor Room 117 001 Information
General
Menu
Passcode
More
The message format is as follows: Under ‘FIRE’: The top line shows the Zone and Point number of the device in alarm. The second line shows the zone description (defined at configuration). The third line shows the point description (defined at configuration). The fourth line shows the type of alarm. If no information text is shown:
18
Doc. version 1
MZX125/250 Fire Detection Systems
The fifth line shows date and time. The sixth line shows the device type. The seventh line shows the actual CURRENT temperature (if heat sensor). The above is only displayed if Extended Alarm Information has been selected at configuration. Under ‘First Fire’: The first three lines from ‘FIRE’ are repeated. The number of alarms is displayed on the black bar underneath the first fire information.
3.4.2
SOUNDER SILENCING
When a FIRE ALARM is received, investigate the cause of the alarm. WARNING: WHEN SEARCHING AN AREA FOR THE SOURCE OF A FIRE ALARM SIGNAL, WHERE A FIRE ALARM HAS BEEN INITIATED BY A ‘CARBON MONOXIDE’ FIRE DETECTOR, IT MUST BE REMEMBERED THAT A CARBON MONOXIDE FIRE DETECTOR MAY GENERATE AN ALARM BEFORE OTHER FIRE INDICATORS (SUCH AS SMOKE) ARE PRESENT. THIS OCCURS MOST NOTABLY IN DEEP SEATED FIRES IN DENSELY PACKED MATERIALS, AREAS WHERE FIRES MAY OCCUR IN CUPBOARDS AND STOREROOMS REMOTE FROM DETECTORS AND WHERE SMOKE IMPERVIOUS BARRIERS EXIST BETWEEN THE SEAT OF THE FIRE AND THE DETECTOR (SUCH AS WITHIN WALL CAVITIES). THESE FACTORS SHOULD BE CONSIDERED CAREFULLY BEFORE DECLARING SAFE ANY AREA WHERE A CARBON MONOXIDE FIRE DETECTOR HAS RAISED AN ALARM. Once the cause of the alarm has been determined and all appropriate action has been taken, silence the sounders as follows: 1
Insert the key into the front panel keyswitch and turn it clockwise to the ‘enable’ position.
2
Press ‘SILENCE/RESOUND’.
Doc. version 1
19
MZX 125/250 Fire Detection Systems
The system will respond as follows: 1
The sounders will be silenced.
2
The ‘SOUNDER ACTIVATED’ LED will extinguish.
3
All other outputs will remain activated.
4
The LCD display will remain showing the type of alarm and the full zone identification. The ‘GENERAL’ display window will show ‘Sounder SIL’.
If it is required to manually resound the sounders, pressing the ‘SILENCE/ RESOUND’ key will reactivate the sounders.
3.4.3
RESETTING THE CONTROLLER
When the system is in a Fire Alarm state, Silence must be operated before Reset is possible. This interlock is always present under Fire Alarm condition, even if all sounders are isolated. The controller should also NOT be reset until the source of the alarm has been determined by the Fire Brigade or the cause otherwise found (and the condition removed). Once the notes above have been observed, press the ‘RESET’ key. The display will show the following message: Reset in Progress... * After 17 to 20 seconds, the LCD will return to the normal display (Section 2.3) if no faults or other events are present.
3.4.4
MULTIPLE EVENTS
If, when in alarm condition, a second alarm (of another zone) is received, the system response is dependent on the nature and source of the second alarm as follows:
20
1
If the sounders have NOT been silenced, the following will occur:
2
The internal buzzer will continue to sound without interruption.
3
The LCD will continue to display the alarm message for the FIRST fire alarm and also the last fire alarm.
4
The alarm count will be incremented.
Doc. version 1
MZX125/250 Fire Detection Systems
3.4.5
PRE-ALARM WARNINGS
If the LCD shows a message including a “warning” indication, a pre-alarm condition has been detected by the controller. This may be indicated for example, if a detector identifies a build-up of smoke or heat that might result from a fire, but the alarm threshold has not yet been reached. The internal buzzer will sound but the sounders and visual fire indicators will remain inactive at this stage. Proceed as follows: 1
Accept the event, (if the option is available), noting the location of the event.
2
Initiate action to deal with the condition indicated, taking care to determine if the warning was initiated by a fire condition or by a system fault.
If the detector subsequently shows an alarm condition, an alarm will be generated, regardless of whether the pre-alarm warning was accepted.
3.5
OPERATION IN FAULT CONDITION
3.5.1
SYSTEM RESPONSE
When a Fault condition is detected, the system will respond as follows: 1
The internal buzzer will pulse.
2
The yellow ‘GENERAL FAULT’ LED will light.
3
The LCD backlight will come on and will display the following type of screen:
MX Panel Fri, 17-Mar-08 15:00
FAULT Zone 000 R10 System Zone Battery Fault IP
Company Name BATTERY FAULT
General Flt P 002
LED Tst
Info
17-Mar-00 15:00:00 Digital Input
Not Clr
More
The message format is as follows: The top line shows the Zone and point number in fault condition. The second line shows the zone description (defined in configuration).
Doc. version 1
21
MZX 125/250 Fire Detection Systems
The third line shows the point description (defined in configuration). The fourth line shows the type of fault. If no information text is shown: The fifth line shows the date and time. the sixth line shows the device type. The message will continue to be displayed until the intervention of an operator or the fault is cleared.
3.5.2
OPERATOR ACTION
When a Fault condition occurs, proceed as follows: 1
Press the ‘SILENCE BUZZER’ key. The internal buzzer will silence, but the LED and display will continue to operate as described.
2
Investigate the source of the fault and where possible remove.
If the fault cannot be cured, contact your local supplier and arrange for a service visit. The fault information will be displayed until the fault is cleared.
3.6
FIRE CONTROL KEYS
There are six fire control keys on the Display Control Module, namely:
SILENCE BUZZER
SILENCE/RESOUND
RESET
DAY MODE
INVESTIGATE DELAY
EVACUATE
Only the ‘SILENCE BUZZER’ key is active without the ‘Enable’ key being inserted and turned to the ‘Enabled’ position. The functions of ‘SILENCE BUZZER’, SILENCE/RESOUND’ and ‘RESET have already been described. The functions of ‘EVACUATE or FIRE ALARM’, ‘INVESTIGATE DELAY’ and ‘DAY MODE’ are described in the following paragraphs.
22
Doc. version 1
MZX125/250 Fire Detection Systems
3.6.1
EVACUATE
Once enabled by the keyswitch, pressing ‘EVACUATE’ will cause the following: 1
The internal buzzer will sound continuously.
2
The red ‘FIRE’ LEDs will light.
3
The sounders and any other configured outputs are activated.
4
The LCD will display the following type of screen:
FirstFirst Fire Fire Zone 000 RB002R12 System Zone Evacuate Button 001
F I R E
General
Information Not Available
Menu
3.6.2
Info
Passcode Not Clr
More
DAY/NIGHT MODE
In night mode the system activates immediately when an alarm is received, the internal buzzer, all sounders and alarm signalling outputs operate. In day mode, on receipt of an alarm, only the internal buzzer and sounders are activated immediately. A delay time is started (default 60 seconds) in which the alarm message must be acknowledged (‘Investigate delay’ switch) to start the investigation time. If there is no acknowledgement within this time, the alarm signalling outputs will be activated. The investigation time (default 10 minutes) is the time remaining for staff to carry out investigation of the alarm source, before the alarm signalling outputs will be activated. An evacuate callpoint will initiate an immediate alarm. Signalling is always immediate if sounder faults exist in the system.
3.6.3
INVESTIGATE DELAY
The ‘INVESTIGATE DELAY’ switch is only active when the controller is in the ‘DAY MODE’ of operation. If a Fire Alert is received at the controller, the signalling output is delayed for 1 minute, if the ‘Investigate Delay’ switch is pressed during this period a further delay (configurable between 1 and 10 minutes) is initiated. This delay allows for the alarm to be investigated, if it is a false alarm, the cause of the alarm can be removed and the controller to be silenced and reset. If the alarm is real, then pressing the ‘EVACUATE/ FIRE ALARM, switch will cause the signalling output to activate. Doc. version 1
23
MZX 125/250 Fire Detection Systems
3.6.4
TEST
Pressing ‘LED TEST’ causes all the LEDs and internal buzzer to operate for a few seconds. If the system includes a repeater panel, only the panel that is operated is activated.
3.7
AUXILIARY DISPLAY DEVICES
3.7.1
GENERAL
Depending on the configuration of the system, there may be one or more auxiliary display devices fitted. These devices may be of the following types:
Repeaters
Printers
The functions of and operating instructions for these devices are given in the following paragraphs.
3.7.2
REPEATERS
A repeater allows the controller to be operated from a remote location and provides remote indications of the state of the controller. The front panel of the repeater is identical to that of the controller (see Fig. 1) and all controller operations may be performed at the repeater panel.
3.7.3
PRINTERS
Refer to the manual supplied with the printer for operating instructions.
3.7.4
LCD REPEATERS
LCD Repeaters can:
24
Display the alarm and fault messages as displayed on the Controller on a backlit 4 x 20-character alphanumeric display.
Provide an internal log for up to 150 events.
Provide an internal audible warning of an event.
Allow the event log to be displayed using the scroll keys.
Silence the internal buzzer and external sounder (if fitted) with the MUTE key.
Doc. version 1
MZX125/250 Fire Detection Systems
4
CONTROLLER FUNCTIONS
As stated, the MZX controller has built-in functions. These functions allow the operator to perform such actions as viewing the event log, setting the date and time, etc. The functions are arranged according to sophistication and access to certain of them necessarily needs to be restricted to trained staff. The control of access has been achieved by assigning functions to Access Levels, each Access Level having an associated numeric passcode. The passcode for a particular Access Level is defined at system configuration.
4.1
ACCESS LEVELS
4.1.1
GENERAL
The access levels available are as follows:
Customer Operator 1 to 7 - 4 digits
Customer Manager 1 - 5 digits
Customer Manager 2 - 6 digits
These access levels are described in the following paragraphs. A maximum of 99 Passcodes are available which may be split between Access Levels as required. The Customer Operator 1 Access Level is achieved by turning the ‘ENABLE’ key to the enable position (ie, a Passcode is not required). Table 1 contains Access Levels and Menu Options available at each level.
Doc. version 1
25
MZX 125/250 Fire Detection Systems
Lamp/Buzzer/LCD Test Unrestored Events Information Text View Events (Scrolling) MAIN MENU
1 ✔ ✔ ✔ ✔
2 ✔ ✔ ✔ ✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
Accept Events ✔
View Status
Customer Operator 3 4 5 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Event log View Event Log Print Event Log Filter View/print status Points Isolated Points Untested/Failed Point Values View Faults Loop Point Counter Active Points By Function
7 ✔ ✔ ✔ ✔
✔
✔
✔
✔
✔
ON
18
✔
✔
✔
✔
✔
ON
18
✔
✔
✔
✔
✔
ON
18
✔
✔
✔
✔
ON
20
✔ ✔ ✔
✔ ✔ ✔
✔ ✔ ✔
✔ ✔ ✔
✔ ✔ ✔
ON ON ON
21 21 21
✔ ✔ ✔ ✔
✔ ✔ ✔ ✔
✔ ✔ ✔ ✔
✔ ✔ ✔ ✔
✔ ✔ ✔ ✔
✔ ✔ ✔ ✔
ON ON ON ON
21 22 22 22
✔
✔ ✔ ✔ ✔ ✔
✔ ✔ ✔ ✔ ✔
✔ ✔ ✔ ✔ ✔
✔ ✔ ✔ ✔ ✔
✔ ✔ ✔ ✔ ✔
✔ ✔
✔ ✔
✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
ON ON ON ON ON ON ON ON
23 23 23 23 24 24
✔ ✔
✔ ✔ ✔ ✔ ✔ ✔
✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
ON ON ON ON ON ON ON ON ON ON ON
25 26 28 28 28 28 29 29 29 29 30
✔ ✔
4.2
OFF OFF OFF OFF
✔ ✔ ✔ ✔
Service Walk Test Maintenance engineer Fire Alarm Cycle Count Maintenance Request Battery Test Project Numbers Software Versions Menu Points Configuration Change Text
Table. 1
Enable Page No. Key
6 ✔ ✔ ✔ ✔
Isolate/De-Isolate Time/Date Set time/Date Summer/Winter
Customer Manager 1 2 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Menu Options and Access Levels
ENTERING PASSCODES
In order to avoid repetition, however, the general procedure for entering a PASSCODE is described as follows: 1
4.3
Turn the ‘ENABLE’ key to the ON position, press F3 (Passcode), enter your ID (press F5 ‘Enter’ if the ID has only one digit).
VALID VALUES
The following are values which may be entered for each option: Panel Number Zone Number Sector Number RBus Number
26
1 - 99 1240* 1 - 240 0 - 15
Doc. version 1
MZX125/250 Fire Detection Systems
Real Point Pseudo Point XBus Point Local I/O Real Point Pseudo Point IOBus point Timer Point User Point
1 - 24 1-8 1 - 96 1 - 18 1 - 42 1 - 24 1 - 10 1 - 10
‘*’ depending on the configuration 40/80/120/160/200 or 240 zones.
4.4
MAIN MENU
When the system is in quiescent mode (ie, displaying the date and time), entering a passcode affords the user access to the main menu. The structure of this menu is shown below.
Main menu MX Panel Thu, 26-Jul-07 00:01 Company Name
General
1 2 3 4 5 6 7 8 9
-
Accept Events View Status Isolate/De-Isol Time / Date Event Log View/Print Data Service Configuration Test Buzzer, LEDs & Display
Alarm Count:
0021
Back The menu shown is for Customer Manager 2 level. Only the options appropriate to the access level entered will be displayed. Each of the options available leads to further menus or functions, which are described in the following paragraphs.
Doc. version 1
27
MZX 125/250 Fire Detection Systems
4.5
ACCEPT EVENTS
Allows displayed events to be accepted. Press 1 from the main menu, the following type of screen will be displayed:
Accept Events SYSTEM Zone 000 R10 System Zone Battery Fault IP
Thu, 26-Jul-07 14:15 Company Name
BATTERY FAULT
General
01-Mar-00 14:15:02 Digital Input
Fault 02
Accept
Back
>
Use the F4 Key ‘’ keys to move between events. Usr F3 ‘Accept’ to accept an event.
4.6
VIEW STATUS
Allows the status of all points and zones on the system to be viewed. Press 2 from the Main menu, the following type of screen will be displayed:
View Status MX Panel Wed, 01-Mar-08 14:15 Company Name
1 2 3 4 5
-
Point Point I/P only Point O/P only Zone Zone Maps
General
Back
Point - allows the status of any points on the system (both inputs and outputs) to be checked. Point I/P only - allows the status of only input devices to be checked (eg, detectors). Point O/P only- allows the status of only output devices to be checked (eg, sounders, functional bases, etc.). Zone - allows the total status of all points in a specified zone to be checked.
28
Doc. version 1
MZX125/250 Fire Detection Systems
Select the required number from the View Status menu, the following type of screen will be displayed:
View Status MX Panel Point Thu, 26-Jul-07 14:15
1 - Loop Point 2 - RBus Point 3 - Local I/O Point
Company Name
General
Back Select the type of Point or Zone: 1
Loop Point (Addressable Loop).
2
RBus Point.
3
Local I/O Point.
The following type of screen will be displayed: If the panel is in a networked system, the panel number will be shown as in the following example.
View Status MX Panel Point Wed, 01-Mar-08 14:15
Panel 02 Loop A
Company Name
Point 001
General
Back
>>
-
+
Enter
Loop Point (Addressable Loop) Use the ‘+’, ‘-’ and ‘>>’ keys to select the required Loop and Point, then press Enter key.
RBus Point (Remote Bus) Use the ‘+’, ‘-’ and ‘>>’ keys to select the required RBus, Category and Point, then press Enter key.
Local I/O Point (Field Interface Module) Use the ‘+’, ‘-’ and ‘>>’ keys to select the required Category and Point, then press Enter key.
Doc. version 1
29
MZX 125/250 Fire Detection Systems
The following type of screen will be displayed:
View Status MX Panel Point Zone 006
Thu, 26-Jul-07 14:15
A007
Zone 06 Call alarm in room CP 820
Company Name
General Input
Output
Normal Back
Point Input and Point Output are displayed in the same format. The top line shows the selected option. The second line shows the Zone and Point number of the device. The third line shows the Sector description (defined at configuration). The fourth line shows the Zone description (defined at configuration). The fifth line shows the Point description (defined at configuration). The sixth line shows the device type. Actual Status Input can be in one of the following states:
Normal
Fault
Active
PreAlarm
Actual Status Ootput can be in one of the following conditions:
On
Off
Pulse 1
Pulse 2
Selecting Zone will display the following type of screen:
View Status MX Panel Zone 002 South Building 1st Floor Corridoor
Thu, 26-Jul-07 14:15 Company Name
Alarm Fault Isolate Walk Test
General
Back
30
_
: : : :
NO* NO* NONE** NO*
+
Doc. version 1
MZX125/250 Fire Detection Systems
Screen display (the asterisks are not shown on the screen): *YES/NO **NONE/ PARTIAL/ALL Function Keys F3/F4 will decrement/increment the zone number. Description Alarm
Yes
One or more devices of a zone in Alarm Mode
Fault
Yes
One or more devices of the zone in Fault Mode
Isolate
All
All alarm input devices of the zone are Isolated
Isolate
Partial
At least one, but not all alarm input devices are Isollated
Walk Test
Yes
All alarm input devices of the zone in Walk Test
4.7
ISOLATE/DE-ISOLATE
The Isolate/De-isolate option allows the following to be isolated/deisolated:
Point Complete 1
Point Input
2
Point Output
3
Zone Detectors 4
Zone Callpoints (also interrupt devices)5
Zone Alarm I/Ps 6
Zone Sounders 7
Zone Controls
Zone Extinguish 9
Extinguish ControlsF2
Fault Signalling F3
Alarm Signalling F4
All Sounders
8
F5
Press 3 from the Main menu. The following screen will be displayed:
Doc. version 1
31
MZX 125/250 Fire Detection Systems
Isolate/De-Isolate
MX Panel Thu, 26-Jul-07 14:15 Company Name
General
Back
Ext.Ctl
1 2 3 4 5 6 7 8 9
-
Flt Sig
Point Point I/P only Point O/P only Zone Detectors Zone Callpoints Zone Alarm I/Ps Zone Sounders Zone Controls Zone Extinguish
Alm Sig All SND
Select the required number from the Isolate/De-Isolate menu, then select the type of point (as described in Section 3.5):
Loop Point (Addressable Loop) Use the ‘+’, ‘-’ and ‘>>’ keys to select the required Loop and Point, then press Enter key.
RBus Point (Remote Bus) Use the ‘+’, ‘-’ and ‘>>’ keys to select the required RBus, Category and Point, then press Enter key.
Local I/O Point (Field Interface Module) Use the ‘+’, ‘-’ and ‘>>’ keys to select the required Category and Point, then press Enter key. CAUTION:
Isolating I/O points may break compliance with EN54. Caution should be exercised when dealing with mandatory switches and indicators. Such operations are reserved for authorised trained personnel only.
The following screen shows an example of Point isolation:
Isolate/De-Isolate
MX Panel Thu, 26-Jul-07 14:15 Company Name
General Isola 001
Point Complete Zone 002 B002 South Building 1st Floor Corridoor Room 117 801 H Status IP: Normal ISOLATED INPUT 1 - Isolate 2 - De-Isolate
Back Isolation Status In the ‘Customer Operator’ access levels, only points on the addressable loop can be isolated or de-isolated.
32
Doc. version 1
MZX125/250 Fire Detection Systems
Isolations are counted and displayed (eg, Isol 001). If only the input or output of a point is isolated, this is counted as a complete isolation of the point. The following screen shows an example of Zone isolation:
MX Panel Thu, 26-Jul-07 14:15
Isolate/De-Isolate Zone Detectors Zone 001
Zone 01
Company Name
General Isola 003
Isolate All Successes Matches
: 003 : 003
Back
Successes: Number of points that were De-Isolated Matches:
Number of points in Zone (detectors)
The following screen shows an example of All Sounders isolation:
Isolate/De-Isolate
MX Panel
All Sounders
Thu, 26-Jul-007 14:15 Company Name
General Isola 006
Successes Matches
: 006 : 006
Back
Successes:
Number of sounders (De-)Isolated
Matches:
Number of sounders in Zone
Doc. version 1
33
MZX 125/250 Fire Detection Systems
4.8
TIME/DATE
Press 4 from the Main menu. The following type of screen will be displayed:
Time / Date MX Panel 1 - Set Time/Date 2 - Summer/Winter
Thu, 26-Jul-07 14:15 Company Name
General
Back
4.8.1
SET TIME/DATE
Press 1 from the Time/Date menu. The following type of screen will be displayed:
Time / Date MX Panel
Date : 01-Mar-00 Time : 14:15:17
Thu, 26-Jul-07 14:15 Company Name
General
Back
>>
-
+
Save
Use the ‘>>’ key to move the cursor between options, enter date and time values via the keypad or Softkey F3 (‘-’) and F4 (‘+’).
When a value has been changed, F5 shows ‘Save’, use this key when all editing has been completed. Months January to September can also be entered with the keypad: 1 = January ................... 9 = September
34
Doc. version 1
MZX125/250 Fire Detection Systems
4.8.2
SUMMER/WINTER
Press 2 from the Time/Date menu. The following type of screen will be displayed:
MX Panel
Summer/Winter Summertime
Thu, 26-Jul-07 14:15 Company Name
General
Winter
Back
These screens cannot be changed, use F5 to toggle between Winter and Summer.
4.9
EVENT LOG
Press 5 from the Main menu. The following type of screen will be displayed:
Event Log
MX Panel Thu, 26-Jul-07 00:01
1 - View Event Log 2 - Print Event Log 3 - Filter
Company Name
General
Back
Doc. version 1
35
MZX 125/250 Fire Detection Systems
4.9.1
VIEW EVENT LOG
This option allows all events in the event log to be viewed or printed. Select option 1 from the Event Log menu, the following type of screen will be displayed: Event Log
MX Panel Zone 000 System Zone
Thu, 26-Jul-07 14:15
TEST FINISHED
Company Name
04-Feb-02 19:30:00 - Empty Information only
General
0001/0010
Back
>>
The latest event is displayed, use the ‘’ keys to scroll through the log and the ‘||’ key to move to the front of the log.
EventID - Displays the absolute number of an event (1 to 65,535). After 65,535 it starts with 1 again.
0001/0010 - The first number is the actual position in the event log (1 means it displays the newest event log entry. The second number displays the number of entries in the event log (max. 3,000).
The newest/last event will be displayed when the Event Log is entered.
4.9.2
PRINT EVENT LOG
Select option 2 from the Event Log menu, the following type of screen will be displayed:
Event Log MX Panel Destination : Default Printer
Thu, 26-Jul-07 14:15
How far back: to start:
Company Name
0010
How many entries required: 0010
General
Lowest priority of interest : 00 Print initiated
Back
>>
-
+
Print
This menu option is only available if at least one printer is configured. The destination printer can be selected if more than one printer is configured.
36
Doc. version 1
MZX125/250 Fire Detection Systems
The priorities available are shown in the following table: Lowest Priority . . . . . . . . . . . . Highest Priority
Information Only Level 2 Expected Events Isolates Warnings Visible Isolate Other Faults Critical Faults Gas Alert Alarm Threshold Non-Life Risk Level 12 Life Risk Alarms General Alarm
It is always printed from the selected priority (eg, Non Life Risk) to the Highest Priority (eg, Non Life Risk, Level 12, Life Risk Alarm and General Alarm).
4.9.3
FILTER
Select option 3 from the Event Log menu, the following type of screen will be displayed:
Event Log MX Panel Thu, 26-Jul-07 14:15 Company Name
General
Back
1 2 3 4 5 6 7 8 9
-
Fire Gas Alert Pre Alarm Supervisory Fault Isolate Test Mode Warning Information
View
-
Print
It is possible to view and to print the events of single categories. The category is selected by pressing the appropriate option number. It is also possible to select several categories, the selected categories are denoted by a ‘+’ sign. Press F4 to view the selected categorie(s) as described in Section 3.8.1 or F5 to print the selected category(s) as described in Section 3.8.2.
Doc. version 1
37
MZX 125/250 Fire Detection Systems
4.10 VIEW/PRINT STATUS Allows the following options to be viewed/printed. On networked systems, the status of any panel on the network may be viewed/printed:
Points Isolated
Points Untested/Failed (during Walk Test)
Point Values
View Faults (no print option)
Loop Point Counters (no print option)
Select option 6 from the Main menu, the following type of screen will be displayed:
View/Print Data MX Panel Wed, 01-Jan-08 14:15 Company Name
General
1 2 3 4 5
-
Points Isolated Pts Unt./Failed Point Values View Faults Loop Point Ctrs
7 - Active Points 8 - By Function
Back
4.10.1 VIEW/PRINT POINTS ISOLATED Select option 1 from the View/Print Status menu, the following type of screen will be displayed:
Points Isolated MX Panel Thu, 26-Jul-07 14:15 Company Name
General
Back
Output
Input Total
: 004
Zone 001 -001 B Point Text -------------------001 -002 B Point Text
Print
If the panel is part of a networked system, another screen is displayed before the above screen where the panel number may be selected.
38
Doc. version 1
MZX125/250 Fire Detection Systems
Press F5 ‘Print’ to print a list of all isolated points. The F2 Key selects either isolated inputs or isolated outputs. Points which are completely isolated (input and output) will be shown in both lists.
4.10.2 VIEW/PRINT POINTS UNTESTED/ FAILED This option only works whilst still in Walktest.
Select option 2 from the View/Print Status menu, the following type of screen will be displayed:
Pts Untested/Failed MX Panel Thu, 26-Jul-07 14:15 Company Name
General
Total
: 004
Zone 001 -001 B Point Text -------------------Zone 001 -002 B Point Text
Back
Print
If the panel is part of a networked system, another screen is displayed before the above screen where the panel number may be selected.
Press F5 to print the Untested/Failed points. Points which are not tested or points which return the wrong condition are then listed.
Doc. version 1
39
MZX 125/250 Fire Detection Systems
4.10.3 VIEW/PRINT POINT VALUES Select option 3 from the View/Print Status menu, the following type of screen will be displayed:
Point Values MX Panel Panel 02 Thu, 26-Jul-07 14:15
Loop A
Point 002
Company Name
General
Back
>>
-
+
Enter
Select the panel number (if the panel is part of a networked system), loop and point number required. ‘>>’ - next field ‘_’ - the number is decremented ‘+’ - the number is incremented Pressing F5 displays the following screen:
Point Values MX Panel Thu, 26-Jul-07 14:15 Company Name
General
Zone 002 B002 South Building 1st Floor Corridoor Room 117 801H Real: 801 H (020) Mode: 1 Sens.: 0 20 oC
Back
(032)
Print
Press F5 to print the Point Values of the selected loop (not only the displayed point).
40
Doc. version 1
MZX125/250 Fire Detection Systems
4.10.4 VIEW FAULTS Select option 4 from the View/Print Status menu, the following type of screen will be displayed:
View Faults MX Panel Total Wed, 01-Jan-08 14:15
: 002
Zone 000 Zone 000
R10 R12
Company Name
General Flt P 002
Back This option is view only.
4.10.5 VIEW LOOP POINT COUNTERS This option is view only. Select option 5 from the View/Print Status menu, the following screen will be displayed:
Loop Point Counters MX Panel Panel 02
Thu, 26-Jul-07 14:15
Loop A
Company Name
General
Back
>>
-
+
Enter
Only the Loop will be shown if the panel is not networked.
Select the required panel (only if the panel is networked) and loop, then press the Enter key. The following message is displayed: Please Wait... for approximately 2 minutes until the count is complete, if no faults are found, the following type of screen will be displayed:
Doc. version 1
41
MZX 125/250 Fire Detection Systems
Loop Point Counters MX Panel Thu, 26-Jul-07 14:15
Counter Loop : A PASSED
Company Name
Configured
: 010
General
Back
Details
Scan
Configured - the number of points configured.
Conditions for ‘PASSED’
The number of configured points is equal the detected count of points on the loop.
There are no unconfigured points.
Detected points from left, right and both sides are equal.
If all conditions are not satisfied, the ‘ATTENTION’ screen will be displayed showing the relevant counters.
Loop Point Counters MX Panel Thu, 26-Jul-07 14:15 Company Name
General
Back
Details
Counter Loop : A A T T E N T I O N Configured
: 010
Conf. & Ident: 009
Scan
Configured - the number of points configured.
Conf & Ident - shows how many points are connected, identified and configured on the loop.
Not Conf. - shows how many points were identified on the loop but not configured.
Both Sides/Left Side/Right Side - Shows how many points on the loop are recognised by the panel. ‘Left Side’ and ‘Right Side’ is the count from both sides. ‘Both Sides’ means the detection of a closed loop.
If the value of ‘Conf & Ident’ is different to the number of installed devices, multiple reserved address may be the cause.
42
Doc. version 1
MZX125/250 Fire Detection Systems
4.10.5.1 DETAILS Press the ‘Details’ key (F2), the following type of screen will be displayed:
Loop Point Counters MX Panel Thu, 26-Jul-07 14:15 Company Name
General
Back
Details Loop : Point 0 : 10 : 20 : 30 : 40 : 50 : 60 : 70 : 80 :
A 0123456789 ......u... .......... .c........ ...o...... .......... .......... ooooo..... .......... ..........
>>
All 250 addresses may be displayed using the ‘>>’ key. The connection detail of each point is shown by the following symbols: o c u
OK: point connected, configured and identified (eg, point 33 and points 60 to 64) Point was configured but not connected or identified (eg, point 21) Point was not configured but connected (eg, point 6)
Function key F2 scrolls through the loop.
4.10.5.2 SCAN Press the ‘Scan’ key (F3), the following type of screen will be displayed:
Loop Point Counters MX Panel Thu, 26-Jul-07 14:15 Company Name
General
Back
Left / Right Scan Loop : A Point 0123456789 0 : ....l..... 10 : .......... 20 : .l........ 30 : ...*...... 40 : .......... 50 : .......... 60 : rrrrr..... 70 : .......... 80 : ..*.......
>>
The points are shown which were detected from both sides (Left/Right). They are displayed as follows:
Doc. version 1
43
MZX 125/250 Fire Detection Systems
.
Empty (not used)
*
OK: detected from both sides (eg, points 33 and 82)
l
Only detected from left side (eg, points 4 and 21)
r Only detected from right side (eg, 60 to 64) Function key F2 scrolls through the loop.
4.10.6 ACTIVE POINTS Select option 7 from the View/Print Status Menu. The following type of screen will be displayed:
Active Points MX Panel Wed, 01-Jan-08 14:15
1 2 3 4
-
Fire Inputs Non-Fire Inputs Loop Outputs Sounders
Company Name
General
Back
4.10.6.1 FIRE INPUTS Select option 1 from the Active Points menu, the following screen will be displayed:
MX Panel Wed, 21-Aug-07 08:01
Active Points Current active pts. Total : 0
Company Name
General
Back
44
Iso&Act
Print
Doc. version 1
MZX125/250 Fire Detection Systems
Pressing Iso&Act (F2) will display the following screen:
MX Panel Wed, 21-Aug-07 08:01
Active Points Isolated active pts Total : 0
Company Name
General
Back
Print
Iso&For
Pressing Iso&For (F2) will display the following screen:
MX Panel Wed, 21-Aug-07 08:01
Active Points Isolated active pts Total : 0
Company Name
General
Back
Print
Iso&For
4.10.7 BY FUNCTION Select option 8 from the View/Print Status Menu. The following type of screen will be displayed:
By Function MX Panel Wed, 21-Aug-07 08:01 Company Name
General
1 2 3 4 5 6
-
Fire Inputs Non-Fire Inputs Loop Outputs Sounders Protection Eqp. Plant Equipment
Back Screens for options 2, 3 and 4 are the same type as for option 1 Fire Inputs.
Doc. version 1
45
MZX 125/250 Fire Detection Systems
4.10.7.1 FIRE INPUTS Select option 1 from the By Function menu, the following screen will be displayed:
Fire Inputs MX Panel Wed, 21-Aug-07 08:01
1 - Active 2 - Fault 3 - Isolated
Company Name
General
Back Select option 1 from the Fire Inputs menu, the following screen will be displayed:
Active Fire IPs MX Panel Wed, 21-Aug-07 08:01 Company Name
Panel: Total : Page :
1 0 0/ 0
General
Back
Select option 2 from the Fire Inputs menu, the following screen will be displayed:
Fire IPs in Fault MX Panel Wed, 21-Aug-07 08:01 Company Name
Panel: Total : Page :
1 0 0/ 0
General
Back Select option 3 from the Fire Inputs menu, the following screen will be displayed:
46
Doc. version 1
MZX125/250 Fire Detection Systems
Isolated Fire IPs MX Panel Wed, 21-Aug-07 08:01 Company Name
Panel: Total : Page :
1 0 0/ 0
General
Back
4.11 SERVICE Press 7 from the Main menu. The following type of screen will be displayed:
Service MX Panel Wed, 09-Aug-08 00:01
1 - Walk Test 2 - Maintenance
Company Name
General
Back The Maintenance and Diagnostics options are only available at Customer Manager level and will not be displayed for lower levels.
4.11.1 WALK TEST When selected, this option allows single or multiple points to be tested without an alarm being raised. Press 1 from the Service menu. Only one Walk Test session can be active at one time.
Doc. version 1
47
MZX 125/250 Fire Detection Systems
Walk test MX Panel Panel Area Type Loop
Wed, 09-Mar-08 00:01
: : : :
01 All Input All
Company Name
General Mode
: MANUAL
Multisensor : Part
Back
>>
+
-
Start
Use the ‘>>’, ‘-’ and ‘+’ keys to select the required options. The Panel number is only displayed when it is part of a networked system. Depending on the selected settings, the display will change. The following screen is an example of ‘Area’ selected as ‘Point’.
Walk test MX Panel Panel Area Type Location Zone Point
Thu, 26-Jul-07 00:01 Company Name
General
: : : : : :
01 Point Input Loop 01 01
Mode : MANUAL Multisensor : Part
Back
>>
+
-
Start
To start the Walk Test press F5. Possible Settings Panel Panel selection is only available for panels that are in a networked system. Area
48
All
Walk Test of all elements of a specific type. (Selection in the field ‘Type’ eg, callpoints).
Zone
Walk Test of all elements of a specific type in a special zone.
Point
Walk Test of the input of a single point.
Doc. version 1
MZX125/250 Fire Detection Systems
Type
Input Detectors Alarm I/Ps Call Points Sounders
Walk Test of all inputs. Walk Test of detectors. Walk Test of default inputs covered by supergroup ‘Fire Alarm Inputs SG’. Walk Test of call points. Walk Test of sounders by loop or all loops plus FIM sounders.
Loop Only with Area as ‘All’ or ‘Zone’. Walk Test of all loops or of a specific loop (A, B, C or D). Location Only with Area selected as ‘Point’.
Loop
A point on the loop.
Zone Only with Area selected as ‘Point’.
Loop
Selection of a specific zone is possible.
Point Only with Area selected as ‘Point’. Selection of a specific zone is possible. Mode MANUAL Detectors to be tested manually. AUTOMATIC Only if type selected is ‘detector’ Self test will be carried out by detectors. The following detectors support the self test function: 801PH 801PHEx 801CH 801CHEx 801I 813P This mode is only available if an 813P detector is configured. If an 813P detector fails this test, it must be manually tested to confirm the failure. Multisensor
Full Part
It is only possible to select either ‘Automatic’, ‘Lasertest’ or ‘Multisensor. The panel itself prevents selection of more than one option.
Doc. version 1
49
MZX 125/250 Fire Detection Systems
If ‘Full’ Walk Test is selected, both modes of the detector must be activated (eg, both heat and optical mode for 801PH). If ‘Part’ Walk Test is selected, the detector has to be activated in the mode in which it is operating (eg, for 801PH optical and heat, both modes active, then activation of either the optical or heat will activate the processing. If only the heat mode is active, then only activation of the heat mode will create an alarm.
4.11.1.1 ALL INPUTS Select the following settings:
Area:
All
Type:
Input
Loop:
All
Press F5 to start the Walk Test. The following screen shows an example for the Walk Test ‘All Inputs’ option:
Walk test MX Panel All Inputs Wed, 09-Mar-08 00:01 Company Name Selected Excluded Been Active Been Clear Successful Curr.Active
General TestZ 001
Back Selected: Excluded: Been Active: Been Clear: Successful: Curr.Active: TestZ:
Settings
: : : : : :
007 000 005 007 005 000 End
Number of points selected by the test. Number of Points not in Walk Test (ie, points isolated). Number of points which have been activated during Walk Test. Number of points which were not active when starting Walk Test. Number of tested points. Points which are currently active. Number of zones which are in Walk Test. The pointer is only counted if all points in a zone are in Walk Test.
Press F3 to display selected settings. Press F5 to end Walk Test. CAUTION: THE FINISHING OF A WALK TEST IS ONLY POSSIBLE IF ALL POINTS IN THE WALK TEST ARE INACTIVE.
50
Doc. version 1
MZX125/250 Fire Detection Systems
4.11.1.2 SOUNDERS Select ‘Sounders’ in the Type field. No results will be shown on the display. The selected sounders will be activated in a pulsing mode.
4.11.1.3 POINT Select the following settings:
Area: Type: Location: Zone: Point:
Point. Input (appears automatically). Loop (appears automatically). Required number. Required number.
Press F5 to start the Walk Test. The following screen shows an example for the Walk Test of ‘Point Input’:
Walk test MX Panel Wed, 09-Mar-08 00:01 Company Name
Point I/P only Zone 006 A007 Zone 06 Call alarm in room CP820
General TestZ 001
Back
Details Settings
Selected: Excluded:
Activations:
Curr.Active: TestZ 001
Selected Excluded Activations Curr.Active
: : : :
1 0 0 NO End
1, if point is in Walk test. 1, if point is not in Walk Test (ie, if point is isolated). 1, if point was activated during Walk Test. Yes, if point is currently active. Number of zones which are in Walk Test. (The pointer is only counted if all points of a zone are in Walk Test. If one detector on the zone is switched off, the pointer is not decreased. In the case of Walk Test for one point, the pointer is only decreased if that point is the only point on the zone).
Press F3 for a display of selected settings. Press F5 to end Walk Test. CAUTION: THE FINISHING OF A WALK TEST IS ONLY POSSIBLE IF ALL POINTS IN THE WALK TEST ARE INACTIVE.
Doc. version 1
51
MZX 125/250 Fire Detection Systems
4.11.2 MAINTENANCE Press 2 from the Service menu. The following type of screen will be displayed:
MX Panel Wed, 01-Mar-08 14:15
Maintenance 1 - Fire Cycle Count 3 - Maint. Request 4 - Battery Test
Company Name
General
6 - Project Numbers 7 - S/W Versions 9 - Menu Points
Back
4.11.2.1 VIEW FIRE ALARM CYCLE COUNT When selected, the number of Alarm sequences may be viewed. Press 1 from the Maintenance menu. The following type of screen will be displayed:
Fire AL.Cycle Count MX Panel Wed, 01-Mar-08 14:15
Count : 0025
Company Name
General
Back
4.11.2.2 VIEW/PRINT MAINTENANCE REQUEST When selected, this option displays a list of detectors which are near the limit of their threshold compensation limit. Press 3 from the Maintenance menu. The following type of screen will be displayed:
52
Doc. version 1
MZX125/250 Fire Detection Systems
Maintenance Request MX Panel Wed, 01-Mar-08 14:15 Company Name
Total Zone 002 Zone 004 Zone 008
: 003 B002 A126 B006
General
Back
Print
Press F5 to print the Maintenance Request.
4.11.2.3 BATTERY TEST When selected, this option allows the state of the battery and the charger current to be displayed. Press 4 from the Maintenance menu. The following type of screen will be displayed:
Battery Test MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Battery State Battery Low
:
Battery Voltage : 20.764 V Charger Current : 00.500 A
Back
4.11.2.4 PROJECT NUMBERS When selected, this option allows the project and MX CONSYS information to be displayed. Press 6 from the Maintenance menu. The following type of screen will be displayed:
Project Numbers MX Panel Wed, 01-Mar-06 00:01 Company Name
General
Project: Queen El. Hospital Consys: V10.0 Version: 34 Created: 21-Jul-07 10:18 Downloaded: 27-Jul-07 08:20
Back Doc. version 1
53
MZX 125/250 Fire Detection Systems
4.11.2.5 SOFTWARE VERSIONS When selected, the software versions of the following are displayed:
Firmware
Local I/O
Each Loop
Each MPM
Network card (if fitted)
Press 7 from the Maintenance menu. The following type of screen will be displayed:
Software Versions MX Panel Thu, 26-Jul-07 14:15 Company Name
General
Back
-Firmware -Bootrom -Local I/O -Loop A -Loop B -OCM00 -OCM01
+
V V V V V V V
10.0 1.2 1.0 2.1 2.1 2.0 2.0
Print
Press F5(+) for additional details of the software versions.
4.11.2.6 MENU POINTS When selected, this option allows any configured point displayed to be operated by pressing the appropriate number button, this will toggle from OFF to ON and ON to OFF. Press 9 from the Maintenance menu. The following type of screen will be displayed:
Menu Points MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Menu Point 1: OFF Isolate Zone Menu Point 2: ON Sensit.Change Menu Point 3: -UnconfiguredMenu Point 4: -Unconfigured-
Back
54
>>
Doc. version 1
MZX125/250 Fire Detection Systems
4.11.3 CONFIGURATION Press 8 from the Main menu. The following screen will be displayed:
MX Panel
Configuration 1 - Change Text
Wed, 01-Mar-08 14:15 Company Name
General
Back ‘Menu option 9- Restart’ will only be displayed if text has been changed and the changes saved. RESTRICTIONS ON THE USE OF THE FOLLOWING OPTION When using Configuration menu option 1, ALWAYS commit configuration
changes by using ‘Menu option 9 - Restart’ before leaving the panel. Avoid ‘inactivity’ timeouts. NEVER use the ‘Back’ option from the configuration menu if ‘Menu option 9 - Restart’ is showing. If you do not want to commit changes, by using ‘Menu option 9 - Restart’, option, turn the keyswitch to ‘OFF’ position to avoid a timeout situation, do NOT USE the ‘Back’ option. Configuration changes across a network are possible, but changes to more than one panel at a time MUST NOT be attempted within one session. When a panels configuration has been changed, it must be restarted using menu option 9 ‘Restart’. Failure to comply with these restrictions may lead to unpredictable effects or system instability.
4.11.3.1 CHANGE TEXT Press 1 from the Configuration menu. The following screen will be displayed:
MX Panel Wed, 01-Mar-08 14:15 Company Name
1 2 3 4 5
Change Text - Point Text - Zone Text - Sector Text - Panel Text - Info Text
General
Back Doc. version 1
55
MZX 125/250 Fire Detection Systems
4.11.3.2 POINT TEXT MODIFY Press 1 from the Change Text menu. The following screen will be displayed:
Point Text Modify MX Panel Loop Point
Wed, 01-Mar-08 14:15
: :
A 001
Company Name
General
Back
-
>>
+
Enter
Select the required loop and point then press Enter. The following type of screen will be displayed:
Point Text Modify Zone 255 -007 A
MX Panel Wed, 01-Mar-08 14:15
Old text Callp. alarm room
Company Name
New text
General
Back
>>
-
+
Enter
‘>>’ - copies the ‘old text’ to the ‘New text’ position. ‘-’ moves the cursor back one position. ‘+’ moves the cursor forward one position. Modify the old text or insert new text using the alphanumeric keypad, when finished press Enter. Pressing the scroll up key Pressing the scroll down key
allows text to be entered in upper case. changes to lower case text.
The message ‘Save Data?’ appears and the functions change F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text modifications to be changed. Selecting F4 ‘Yes’ displays the message: Please wait..... then the following screen is displayed:
56
Doc. version 1
MZX125/250 Fire Detection Systems
Change Text 1 - Point Text
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back It is now possible to change the text for another Point. Selecting F1 ‘Back’ will display the following screen:
Configuration 1 - Change Text
MX Panel Wed, 01-Mar-08 14:15 Company Name
General 9 - Restart
Back Only ‘Change Text’ and ‘Restart’ are available allowing more points to be changed or using ‘Restart’ to allow the changes to take effect.
4.11.3.3 ZONE TEXT MODIFY Press 2 from the Configuration menu. The following screen will be displayed:
Zone Text Modify MX Panel Wed, 01-Mar-08 14:15
Zone
:
001
Company Name
General
Back
-
+
Enter
Select the required and press Enter. The following type of screen will be displayed:
Doc. version 1
57
MZX 125/250 Fire Detection Systems
Zone Text Modify Zone : 001
MX Panel Wed, 01-Mar-08 14:15
Old text Zone 01
Company Name
New text
General
Back
-
>>
+
Enter
‘>>’ - copies the ‘old text’ to the ‘New text’ position. ‘-’ moves the cursor back one position. ‘+’ moves the cursor forward one position. Modify the old text or insert new text using the alphanumeric keypad, when finished press Enter. The message ‘Save Data?’ appears and the function change F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text modifications to be changed. Selecting F4 ‘Yes’ displays the message: Please wait..... then the following screen is displayed:
Change Text MX Panel Wed, 01-Mar-08 14:15
2 - Zone Text
Company Name
General
Back It is now possible to change the text for another Zone. Selecting F1 ‘Back’ will display the following screen:
MX Panel
Configuration 1 - Change Text
Wed, 01-Mar-08 14:15 Company Name
General 9 - Restart
Back 58
Doc. version 1
MZX125/250 Fire Detection Systems
Only ‘Change Text’ and ‘Restart’ are available allowing more points to be changed or using ‘Restart’ to allow the changes to take effect.
4.11.3.4 SECTOR TEXT MODIFY Press 3 from the Configuration menu. The following screen will be displayed:
Sector Text Modify MX Panel Wed, 01-Mar-08 14:15
Sector
:
001
Company Name
General
-
Back
+
Enter
Select the required sector, then press Enter. The following type of screen will be displayed:
Sector Text Modify Sector 001
MX Panel Wed, 01-Mar-08 14:15
Old text Sector 01
Company Name
New text
General
Back
>>
-
+
Enter
‘>>’ - copies the ‘old text’ to the ‘New text’ position. ‘-’ moves the cursor back one position. ‘+’ moves the cursor forward one position. Modify the old text or insert new text using the alphanumeric keypad, when finished press Enter. The message ‘Save Data?’ appears and the function change F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text modifications to be changed. Selecting F4 ‘Yes’ displays the message: Please wait.....
Doc. version 1
59
MZX 125/250 Fire Detection Systems
then the following screen is displayed:
Change Text MX Panel Wed, 01-Mar-08 14:15
3 - Sector Text
Company Name
General
Back It is now possible to change the text for another Sector. Selecting F1 ‘Back’ will display the following screen:
Configuration 1 - Change Text
MX Panel Wed, 01-Mar-08 14:15 Company Name
General 9 - Restart
Back 4.11.3.5 PANEL TEXT MODIFY Press 4 from the Configuration menu. The following screen will be displayed:
Panel Text Modify Panel 00
MX Panel Wed, 01-Mar-08 14:15
Old Text ADT
Company Name
New Text
General
Back
>>
-
+
Enter
Select the required Panel. ‘>>’ - copies the ‘old text’ to the ‘New text’ position. ‘-’ moves the cursor back one position. ‘+’ moves the cursor forward one position.
60
Doc. version 1
MZX125/250 Fire Detection Systems
Modify the old text or insert new text using the alphanumeric keypad, when finished press Enter. The message ‘Save Data?’ appears and the function change F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text modifications to be changed. Selecting F4 ‘Yes’ displays the message: Please wait..... then the following screen is displayed:
Change Text MX Panel Wed, 01-Mar-08 14:15
4 - Panel Text
Company Name
General
Back It is now possible to change the text for another Panel. Selecting F1 ‘Back’ will display the following screen:
Configuration 1 - Change Text
MX Panel Wed, 01-Mar-08 14:15 Company Name
General 9 - Restart
Back
4.11.3.6 INFO TEXT MODIFY This option allows Info Text created in CONSYS to be modified. Press 5 from the Change Text menu. The following screen will be displayed:
Info text modify MX Panel Wed, 01-Mar-08 14:15 Company Name
Infotext No. : 001
General
Back Doc. version 1
-
+
Enter 61
MZX 125/250 Fire Detection Systems
Using the ‘+’ and ‘-’ keys select the Info Text message to modify, then press ‘Enter’. The following type of screen will appear:
Info text modify Infotext No. : 001 This zone is in a Hazardous Area Special precautions are required
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
>>
+
-
Enter
The ‘>>’ key deletes all text. The ‘+’ key advances the cursor one space, the ‘-’ key goes one space back. Use the alphanumeric keys to modify the text, when finished, press ‘Enter’. The following screen will be displayed:
MX Panel Wed, 01-Mar-08 14:15 Company Name
Info text modify Infotext No. : 001 This zone is in a Hazardous Area Special precautions are required
General
Save data?
Back
62
Yes
No
Doc. version 1
MZX125/250 Fire Detection Systems
5
ROUTINE CHECKS
5.1
GENERAL
In order to comply with the requirements of British Standard BS 5839 Part 1, the installation must be checked on a regular basis by a responsible member of staff to confirm that the controller and all ancillary devices are operating correctly. The required routine checks are described in the following paragraphs.
5.2
DAILY CHECKS
Proceed as follows: 1
Ensure the front panel of the controller is indicating a normal condition (ie, no alarm or fault LEDs are lit and the LCD is displaying the date and time).
If the panel is not indicating a normal condition record the condition in the log book and take any necessary action.
2
5.3
Check that any fault recorded on the previous day has received attention.
WEEKLY CHECKS
These checks would normally be carried out by a responsible member of the customer’s staff. WARNING: WARN ALL PERSONNEL THAT THE SOUNDERS ARE ABOUT TO BE TESTED.
Proceed as follows: 1
If necessary, clean the front panel of the controller with a suitable cleansing agent.
Doc. version 1
63
MZX 125/250 Fire Detection Systems
2
Set one device (either a callpoint or detector) from one zone into alarm and check that the system responds as follows: •
The controller’s internal buzzer sounds in a continuous tone.
•
The two red ‘FIRE’ LEDs on the controller front panel light.
•
The appropriate red ‘FIRE ZONAL’ LED flashes (if configured).
•
The general and zonal sounders operate.
•
The alphanumeric display gives the location of the alarm.
1
Record the device used to initiate the test in the site log book and reset the controller.
2
Check the condition of the printout on any printers attached to the system and replace the ribbon if it is becoming feint.
3
Ensure that each printer has an adequate supply of paper.
Any defect should be recorded in the log book and appropriate action taken.
64
Doc. version 1
Tyco Safety Products Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
120.415.992 V1.0/13/11/08