PROYECTO PROYEC TO REACTIVACION DE DE LA CADENA CA DENA PRODUCTIVA PRODUCTIVA DE ACRILONIT ACRILONITRILO RILO UNIDAD: COMPLEJO COMPLEJ O PETROQUIMICO MORELOS COATZACOALCOS, VERACRUZ

MEMORIAS MEMO RIAS DE CÁLCULO CÁL CULO CABLES CABL ES DE DE BAJA BA JA TENSIO TENSION N DT-JE-MC-002-08

REVISION UNIGEL ING. ESPECIALISTA: ING. DAMASO SALOMON

FECHA:   19-Dic-08  APROBO UNIGEL

ING. J. MILLAN

FECHA:   19-Dic-08  APROBO CHEMISA 1 0

REV. 

 

19-Dic-08 10-Dic-08

FECHA 

SE ACTUALIZAN PARTIDAS APROBADO PARA CONSTRUCCION

DESCRIPCION

 A.D.S.  A.D.S.

A. DIAZ  ING. FERNANDO SANCHEZ A. DIAZ  FECHA:   19-Dic-08

ELABORO REVISO  HOJA: 1 DE: 15

Rev.

1

 

 

No. DE PROYECTO: HOJA 2

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSIO TENSION N

DOC. No. DT-JE-MC-002-08

DT-JE-MC-002-08

FECHA: 10-DICIEMBRE-08

INDICE

1. ALCANCE. 2. CONSIDERACIONES GENERAL GENERALES. ES. 3. DATOS GENER GENERAL ALES. ES. 4. CÁLCUL CÁLCULO O DE LA CORRI CORRIENTE ENTE NOMIN NOMINAL AL.. 5. CÁLCUL CÁLCULO O POR AMPACIDAD. 6. CÁLCUL CÁLCULO O POR CAÍDA D DE E TENSI TENSIÓN. ÓN. 7. SELECCIÓN DEL CONDUCTOR. 8. SELECCIÓN DE LA PROTECCIÓN. 9. SELECCIÓN DE TUBERÍA CONDU CONDUIT IT 10. RESULTADOS. 11. NORM NORMAS AS A APLICAB PLICABLES LES Y DOCUME DOCUMENTOS NTOS DE REFEREN REFERENCIA. CIA. 12. ANEXOS.

DE: 15

REVISION 1

 

 

No. DE PROYECTO: HOJA 3

MEMORIAS MEMO RIAS DE CÁL CULO DOC. No. DT-JE-MC-002-08

CABLES DE BAJ A TENSIO TENSION N

DT-JE-MC-002-08

DE: 15

REVISION 1

FECHA: 10-DICIEMBRE-08

1. ALCANCE: Los cálculos que se adjuntan tienen por objeto determinar las secciones de los cables de fuerza que alimentan a los motores y cargas varias del sistema de 480 y 220 V, 60 Hz, del proyecto REACTIVACIÓN DE LA CADENA PRODUCTIVA DE ACRILONITRILO, EN EL

COMPLEJO PETROQUÍMICO PETROQUÍMICO MORELOS, EN COATZA COATZACOAL COALCOS, COS, VERACRUZ... 2. CONSIDERACIONES GENERAL GENERALES: ES: 2.1

Los cálculos serán desarrollados siguiendo los lineamientos establecidos en la norma

oficial

mexicana

NOM-SEDE-001-2005,

Instalaciones

Eléctricas

(utilización). 2.2

Los cables serán de las siguientes características constructivas: Tipo “TC” Multiconductor y monopolar exclusivamente para la alimentación en 480v del transformador de 1500 Kva. - Aislamiento THW-LS/THHW-LS - Temperatura de servicio: 75/90º C. - Temperatura máxima en cortocircuito:

150º C.

- Material: Cobre 2.3

La tensión del

sistema será: 480/220 VCA y la corriente del conductor se

seleccionara de acuerdo a la tabla 310-16, 310-17, considerando que seleccionamos la capacidad de conducción para una protección con interruptor de 100 amp y menor en la columna de 60 °C y para interruptor mayor de 100 amp. En la columna de 75 °C. 2.4

Se supone una temperatura ambiente máxima de diseño de 42º C.

2.5

Al existir una gran diversidad de motores y cargas de B. T. en la central, se estima un factor de potencia de 0,85 con una eficiencia de 0.9 para todos los motores. Para las cargas varias la eficiencia será de 1.0, en el anexo 2 se indican estos datos (columna 9 y 10).

2.6

El tendido de los cables se realizará en charola tipo escalera y/o tubería conduit. Tomando en cuenta las consideraciones del artículo 318 de la NOM-001-SEDE2005 (Soportes tipo charola para cables).

 

 

No. DE PROYECTO: HOJA 4

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSIO TENSION N

DOC. No. DT-JE-MC-002-08

DT-JE-MC-002-08

DE: 15

REVISION 1

FECHA: 10-DICIEMBRE-08

El factor de corrección por agrupamiento a aplicar será el indicado en la NOM-001SEDE-2005, del anexo 2 ver (columna 15, 16 y 17). Fa = Factor por agrupamiento – 1.0 Fch = Factor por agrupamiento en charola = 0.95 Art. 318-11 a) Excepción 1, para multiconductores y 0.65 para monopolares art. 318-11 (b,2). 2.7

El factor de corrección por temperatura ambiente se selecciona considerando la temperatura ambiente del sitio, la temperatura de operación del conductor y de acuerdo a las recomendaciones del artículo 110-14 de la NOM-SEDE-2005 y al tipo de instalación de los conductores. De la tabla 310-16, y 310-17, para conductores de calibre 1 AWG y menores, seleccionamos el factor de temperatura en la columna de 60 ºC que para una temperatura ambiente de 42 ºC el factor es 0.71, y para conductores de calibre mayor de 1 AWG seleccionamos el factor de temperatura de la columna de 75 ºC , este es 0.82.

2.8

Los cables de alimentación a motores se dimensionan para un 125 % de su corriente nominal para el cálculo de la sección mínima de acuerdo al artículo 430 de la NOM del anexo 2 (ver columna 13)..

2.9

Las caída de tensión máxima que puedan tener los cables será de: ΔV

= 3%

Los valores de las resistencias y reactancias de los cables se han obtenido de tablas del NEC. 2.10 Los cables de B.T. se calcularán por criterios de ampacidad y de caída de tensión. 2.11 Se editaran una tabla con los resultados de los cálculos en el anexo 2: - Memoria de cálculo de cables eléctricos BT.

3. DATOS GENER GENERAL ALES: ES: El cálculo llevara como datos generales lo siguiente (columnas 1 a la 10) : Nº de partida No. De circuito. Clave del equipo. Descripción. Potencia:

 

 

No. DE PROYECTO: HOJA 5

MEMORIAS MEMO RIAS DE CÁL CULO DOC. No. DT-JE-MC-002-08

CABLES DE BAJ A TENSIO TENSION N

DT-JE-MC-002-08

DE: 15

REVISION 1

FECHA: 10-DICIEMBRE-08

Tensión: No. De fases. Factor de potencia. Eficiencia.

4. CAL CALCULO CULO DE LA CORR CORRIENTE IENTE NOMI NOMINAL: NAL: Para el cálculo de la corriente nominal se emplea lo siguiente: • 

para motores motores la corriente corriente nominal nominal se obtendrá obtendrá de la tabla 430.150 430.150 de la NOM-001-SEDE-2005.

• 

También de los datos de placa del motor, (si se tienen), o con la siguiente expresión: Parar motores trifásicos

 In =

 HPx 0.746  x 1000

3  y la tensión es de fase a neutro.

Para motores monofásicos se omite la • 

 

3  x V   x F .P.  x  N 

Para alimentadores alimentadores trifásicos la corriente corriente nominal nominal se se obtiene obtiene de la siguiente siguiente expresión (columna 11):

 In  =



 

3  x V   x F .P.

Para alimentadores monofásicos se omite la

3   y la tensión es de fase a

neutro. Donde:

In

=

Corriente Nominal en Amperes

W =

Potencia en watts

V

Tensión en Volts

=

F.P. =

Factor de Potencia

N

Eficiencia

=

 

 

No. DE PROYECTO: HOJA 6

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSIO TENSION N

DOC. No. DT-JE-MC-002-08

DT-JE-MC-002-08

DE: 15

REVISION 1

FECHA: 10-DICIEMBRE-08

5. CÁL CÁLCULO CULO POR AMPACIDAD:

Para motores la corriente nominal se afectara por 1.25 de acuerdo a NOM-001SEDE-2005. Se elige el cable y la corriente del conductor se afecta por los valores de corrección por temperatura ambiente y por agrupamiento el cual deberá de cumplirse lo siguiente: Para el caso de motores (columnas 11 y de la 13 a la 20 del anexo 2):

1.25 x  In 



 Icond  x Ft  x Fa ó Fch  

Para el caso de alimentadores ver anexo 4 y 6:

 In   ≤  Icond  x Ft  x Fa ó Fch  Donde:

In

=

Corriente Nominal en Amperes

Icond=

Corriente del conductor seleccionado en amperes

Ft

=

Factor de temperatura

Fa

=

Factor de agrupamiento en tubería

Fch =

Factor de agrupamiento en charola

6. CÁL CÁLCULO CULO POR CAÍDA DE TENSI TENSIÓN: ÓN: Para la caída de Tensión se emplea la siguiente expresión columnas 23 a la 32):

%V  =

  l  x ( R cos Ø 3  x  In  x

 



+

 XsenØ)

x 100  

 

 

No. DE PROYECTO: HOJA 7

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSIO TENSION N

DT-JE-MC-002-08 Donde:

DOC. No. DT-JE-MC-002-08

DE: 15

FECHA: 10-DICIEMBRE-08

%V =

Caída de Tensión en %.

In

=

Corriente nominal, en amperes

l



Longitud, en metros.

R X

= =

Resistencia del conductor, en ohms/metro Reactancia del conductor, en ohms/metro

Cos =

Factor de potencia.

V

Voltaje entre líneas, en volts.

=

REVISION 1

Nota: para la carga monofásica se cambia la

3   por 2 y el voltaje será de línea a tierra.

7. SELECCIÓN DEL CONDUCTOR: Se selecciona el calibre del conductor de acuerdo al resultado mas critico ya sea por ampacidad ampacidad o por caída de de tensión, mismo mismo que se refleja en en la columna 33 y 34 respectivamente. respectivamente.

8. SELECCIÓN DE LA PROTEC PROTECCIÓN: CIÓN: Para motores (columna 12 anexo 2). Se selecciona el interruptor para motores de acuerdo a NOM-001-SEDE-2005, Art. 430.52.1. Para alimentadores (anexo 4 y 6). Se selecciona el interruptor para alimentadores de acuerdo a NOM-001-SEDE-2005, Art. 210.20, 215.3

9. SELECCIÓN DE TUBERÍA CONDUIT (COLUMNA 37): Este será de acuerdo a la NOM-001-SEDE-2005, Art. Art. Capitulo 10, Tablas, Tabla 10-4., con un factor de relleno del 53%.

10. RESULTA RESULTADOS: DOS: La recolección de resultados se hará mediante tablas divididas en columnas numeradas como se ha venido indicando en los diferentes incisos donde se reflejan los cálculos de los circuitos de los diagramas unifilares de referencia. Ver anexos del 1 al 6.

 

 

No. DE PROYECTO: HOJA 8

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSIO TENSION N

DT-JE-MC-002-08

DOC. No. DT-JE-MC-002-08

DE: 15

REVISION 1

FECHA: 10-DICIEMBRE-08

- Memoria de cálculo de cables eléctricos en baja tensión.

11. NORMAS NORMAS A PLICAB PLICABLES LES Y DOCUME DOCUMENTOS NTOS DE REFER REFERENCIA: ENCIA: 1.

Norma Oficial Mexicana, Relativa a las Instalaciones Destinadas al Suministro y Uso de la Energía Eléctrica. (NOM-001-SEDE-2005).

2.

NRF-048-PEMEX-2007 Diseño de Instalaciones Eléctricas.

3.

DIAGRAMA DIAGRAMAS S UNIFILARES ANEXO PLANOS L-001, L-007, L-009, L-010 Y L-013

12. ANEXOS:  Anexo  An exo 1. Cálculo de conductores eléctricos en B.T (ejemplos)  Anexo  An exo 2. Cálculos de cables eléctricos en baja tensión (480 volts)  Anexo  An exo 3. Cálculos de cables eléctricos en baja tensión (220 volts)  Anexo  An exo 4. Cálculos de cables eléctricos en baja tensión (480 volts)  Anexo  An exo 5. Cálculos de alimentadores CCM-03A/CCM-04A  Anexo  An exo 6. Cálculos de alimentadores CCM-02A/CCM-02B  Anexo  An exo 7. Cálculos de alimentadores CCM-840 A/B

1

 

 

No. DE PROYECTO:

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSION

DT-JE-MC-002-08

DOC. No. DT-JE-MC-002-08

HOJA 9

REVISION

DE: 15

0

FECHA: 10-DICIEMBRE-08

 Anexo 1

Cálculo de Conductores Eléctricos en 480 Volts B.T. (ejemplos)

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 1

REV.

CALCULO DE ALIMENTADORES

EJEMPLO DE CALCULO DE CONDUCTORES ELECTRICOS EN B.T. (MOTOR DE 200 HP)

  I.-

A NTE CE DE NT ES :

LA MEMORIA DE CALCULO ESTA BASADA EN LA NORMA OFICIAL MEXICANA NOM-001-SEDE-2005  ARTICULO 430

Alimentador parte " B " Parte " E " Protección contra corto circuito y falla a tierra

Parte " I " Desconectador  Parte " D " proteccion contra corto circuito y falla a tierra

Parte " C " proteccion contra sobrecarga Parte " B " Alimentador 

Motor 

1

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 1

REV.

CALCULO DE ALIMENTADORES

  2.- DATOS: CLAVE DEL EQUIPO: CIRCUITO No. POTENCIA DEL MOTOR: TENSION DEL SISTEMA ( V ): No. DE FASES: FRECUENCIA: SEN. Ø : F.P. = COS Ø : TEMPERATURA AMBIENTE: AISLAMIENTO DEL CONDUCTOR: TEMPERATURA DEL AISL.: LONGITUD DEL CIRCUITO: CANALIZACION EFICIENCIA

BGA-116A CF-16 200 H.P. 480 VOLTS 3 60 Hz. 0.53 0.85 O C. 42 THW-LS O C: 75 200 MTS. TUBO CONDUIT/CHAROLA 0.9

(estimada)

  3.- CORRIENTE NOMINAL ( In ):

In =  

H.P. x 746 = 1.732 x V x F.P. x Fe

In =

(DATOS DE PLACA)

In=

( TABLA 430-150 )

1

 _ 

AMP.

-----

AMP.

240

AMP.

500

AWG

300.0

AMP.

620

AMP.

  4.- SELECCIÓN DEL CONDUCTOR POR AMPACIDA D CALIBRE DEL CONDUCTOR SELECCIONADO

Imax =

In x 1.25 =

CORRIENTE DEL CONDUCTOR SELECCIONADO PARA UN CONDUCTOR POR FASE

Tabla 310-17

APLICANDO FACTORES DE CORRECCION (ft, fa.) FACTOR DE TEMPERATURA AMBIENTE ( ft ) = FACTOR DE AGRUPAMIENTO EN TUBERIA ( fa ) = FACTOR DE AGRUPAMIENTO EN CHAROLA ( fch ) = Icond= Icond > Imax

0.82 1.0 0.65

Ic x ft x fa x fch = 330.46

330.46 > Im a x .

=

300.00

AMP. CUMPLE

ART'S. 110.14.c, 430.22 Y TABLAS 310.16. HASTA 310.61 5.- SELECCIÓN DEL CONDUCTOR POR AMPACIDAD CALIBRE DEL CONDUCTOR POR AMPACIDAD CALIBRE DEL CONDUCTOR DE TIERRA TABLA 250.94, 250-95

500 2

AWG AWG

420.00

AMP.

  6.- YS SELECCIÓN ELECCIÓN DEL DISPOSITIVO PROTECCION POR SOBRECORRIENTE FALLA A TIERRA (art. 430.52 yDE 240.6). I INT. =

175% x In =

(TA B L A 430-152)

1

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 1

REV.

CALCULO DE ALIMENTADORES

INTERRUPTOR TERMOMAGNETICO SELECCIONADO

500

AMP.

2.83

CUMPLE

  7.- S SELECCIÓN ELECCIÓN DEL CONDUCTOR POR C CAIDA AIDA DE T TENSION ENSION ( %V ) %V = 1.732x In x L x ( R cos Ø + X sen Ø ) x 100 = V In = CORRIENTE NOMINAL V = TENSION DE OPERACIÓN CALIBRE DEL CONDUCTOR SELECCIONADO L = LONGITUD DEL CIRCUITO R = RESISTENCIA DEL CONDUCTOR (Tabla No. 9, Cap. 9, NEC-2005) X = REACTANCIA DEL CONDUCTOR (Tabla No. 9, Cap. 9, NEC-2005) SEN Ø = COS Ø =

240.00 480 500 0.200 0.0950 0.1570 0.53 0.85

AMP. VOLTS. AWG/MCM KM. OHMS/KM OHMS/KM

  8.- SELECCI SELECCIÓN ÓN DE LA CANALIZACION LAS CANALIZACIONES SE SELECCIONARAN EN BASE AL CAPITULO 10, TABLAS 10-4,10-5 MONOPOLAR CAL IBRE SELECCIONADO FUERZA CALIBRE SELECCIONADO DE PUESTA A TIERRA AREA DEL CABLE SELECCIONADO DE FUERZA AREA DEL CABLE SELECCIONADO DE PUESTA A TIERRA CANTIDAD DE CABLES DEL CIRCUITO AREA TOTAL

500 2 510.71 86.59 3 1618.72

mm²

TUBO CONDUIT SELECCIONADO ( fr = 40 % ) =  AREA PERMISIB LE DE OCUPACION.

103.00 3282

mm²

>

3282.00

1618.72

AWG AWG mm² mm²

CUMPLE

UN TUBO CONDUIT DE 78 MM DE DIAMETRO PARA FUERZA Y TIERRAS CALIBRE CONTROL AREA DELSELECCIONADO CABLE SELECCIONADO CANTIDAD DE CABLES AREA SUBTOTAL

 MULTICONDUCTOR

 AREA TOTA L DE LOS CA CABLES BLES

172.27

mm²

TUBO CONDUIT SELECCIONADO ( fr = 40 % ) =  AREA PERMISIB LE DE OCUPACION.

27.00 222

mm²

222 172.27 > UN TUBO CONDUIT DE 27 MM DE DIAMETRO PARA CONTROL Notas:

1C(3X12+1X12) AWG 172.27 mm² 1 172.27 mm²

CUMPLE

1

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 1

REV.

CALCULO DE ALIMENTADOR ALIMENTADORES ES

EJEMPLO DE CALCULO DE CONDUCTORES ELECTRICOS EN B.T. (MOTOR DE 200 HP)

  I.- A N T E C E D E N T E S : LA MEMORIA DE CALCULO ESTA BASADA EN LA NORMA OFICIAL MEXICANA NOM-001-SEDE-2005  ARTICULO 430

Alimentador parte " B " Parte " E " Protección contra corto circuito y falla a tierra

Parte " I " Desconectador  Parte " D " proteccion contra corto circuito y falla a tierra

Parte " C " proteccion contra sobrecarga Parte " B " Alimentador 

Motor 

1

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 1

1

REV.

CALCULO DE ALIMENTADOR ALIMENTADORES ES   2.- DATOS: CLAVE DEL EQUIPO: CIRCUITO No. POTENCIA DEL MOTOR: TENSION DEL SISTEMA ( V ): No. DE FASES: FRECUENCIA: SEN. Ø : F.P. = COS Ø : TEMPERATURA AMBIENTE: AISLAMIENTO DEL CONDUCTOR: TEMPERATURA DEL AISL.: LONGITUD DEL CIRCUITO: CANALIZACION EFICIENCIA

BGA-110A CF-302 200 H.P. 480 VOLTS 3 60 Hz. 0.53 0.85 O C. 42 THW-LS O C: 75 52 MTS. TUBO CONDUIT 0.9

(estimada)

  3.- CORRIENTE NOMINAL ( In ))::

In =  

H.P. x 746

=

 _ 

AMP.

-----

AMP.

240

AMP.

500

AWG

300.0

AMP.

380 380

AMP.

1.732 x V x F.P. x Fe

In =

(DATOS DE PLACA)

In=

( TABLA 430-150 )

1

  4.- SELECCIÓN DEL CONDUCTOR POR AMPACIDA D CALIBRE DEL CONDUCTOR SELECCIONADO

Imax =

In x 1.25 =

CORRIENTE DEL CONDUCTOR SELECCIONADO PARA UN CONDUCTOR POR FASE

Tabla 310-16

APLICANDO FACTORES DE CORRECCION (ft, fa.) FACTOR DE TEMPERATURA AMBIENTE ( ft ) = FACTOR DE AGRUPAMIENTO EN TUBERIA ( fa ) =

0.82 1.0

FACTOR DE AGRUPAMIENTO EN CHAROLA ( fch ) =

1.0

Icond= Icond > Imax

Ic x ft x fa x fch = 311.6

311.6 > Im ax .

=

300.00

AMP. CUMPLE

ART'S. 110.14.c, 430.22 Y TABLAS 310.16. HASTA 310.61 5.- SELECCIÓN DEL CONDUCTOR POR AMPACIDAD CALIBRE DEL CONDUCTOR POR AMPACIDAD CALIBRE DEL CONDUCTOR DE TIERRA TABLA 250.94, 250-95

500 2

AWG AWG

420.00

AMP.

500

AMP.

  6.- SELECCIÓN SELECCIÓN DEL DISPOSITIVO DE PRO PROTECCION TECCION POR SOBRECORRIENTE Y FALL A A TIERR TIERRA A (art. 430.52 y 240.6). I INT. =

175% x In =

(TA B L A 430-152)

INTERRUPTOR TERMOMAGNETICO SELECCIONADO   7.- SELECCIÓN DEL CONDUCTOR POR CAIDA DE TENSION ( %V

1

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 1

REV.

CALCULO DE ALIMENTADOR ALIMENTADORES ES

%V = 1.732x In x L x ( R cos Ø + X sen Ø ) x 100 =

0.74

CUMPLE

V In = CORRIENTE NOMINAL V = TENSION DE OPERACIÓN CALIBRE DEL CONDUCTOR SELECCIONADO L = LONGITUD DEL CIRCUITO R = RESISTENCIA DEL CONDUCTOR (Tabla No. 9, Cap. 9, NEC-2005) X = REACTANCIA DEL CONDUCTOR (Tabla No. 9, Cap. 9, NEC-2005) SEN Ø = COS Ø =

240.00 480 500 0.052 0.0950 0.1570 0.53 0.85

AMP. VOLTS. AWG/MCM KM. OHMS/KM OHMS/KM

  8.- SELECCIÓN DE LA CANAL IZACION LAS CANALIZACIONES SE SELECCIONARAN EN BASE AL CAPITULO 10, TABLAS 10-4,10-5 MONOPOLAR CALIB RE SELECCIONADO FUERZA CALIBRE SELECCIONADO DE PUESTA A TIERRA AREA DEL CABLE SELECCIONADO DE FUERZA AREA DEL CABLE SELECCIONADO DE PUESTA A TIERRA CANTIDAD DE CABLES DEL CIRCUITO AREA TOTAL TUBO CONDUIT SELECCIONADO ( fr = 40 % ) =  AREA PERMISIBL E DE OCUPACION. 3282.00

>

500 2 510.71 86.59 3 1618.72 1

103 3282

1618.72

AWG AWG mm² mm² mm² mm² CUMPLE

UN TUBO CONDUIT DE 41 MM DE DIAMETRO PARA FUERZA Y TIERRAS CALIBRE SELECCIONADO CONTROL AREA DEL CABLE SELECCIONADO CANTIDAD DE CABLES AREA SUBTOTAL

 MULTICONDUCTOR

 AREA TOTAL TOTA L DE LOS CAB LES TUBO CONDUIT SELECCIONADO ( fr = 40 % ) =  AREA PERMISIBL E DE OCUPACION.

Nota Notas: s:

1C(3X12+1X12) AWG 172.27 mm² 1 172.27 mm² 172.27

mm²

27 222

mm²

222 > 172.27 UN TUBO CONDUIT DE 27 MM DE DIAMETRO PARA CONTROL Se se sele lecc ccio iona na un tubo tubo cond condui uitt de 103 103 m mm. m. ( 4" ) de de d dia iame metr tro o par para aa alilime ment ntad ador ores es de fu fuer erza za

CUMPLE

1

 

 

No. DE PROYECTO:

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSION

DT-JE-MC-002-08

DOC. No. DT-JE-MC-002-08

HOJA 10

REVISION

DE: 15

0

FECHA: 10-DICIEMBRE-08

 Anexo 2

Cálculos de Cables Eléctricos en 480 volts B. T. (resumen)

 

DOCUMENTO No.

 ANEXO 2 1

DT-JE-MC-002-08 MEMORIAS DE CALCULO DE CABLES ELECTRICOS EN BAJA TENSION 480 VOLTS 1

REV. DA TOS

1

partida

2

Circuito

3

Clave del equipo

4

A MPA CIDA D

INT.

5

6

potencia

7

Tension

8

Fases

9

F. P.

10

Ef.

11

12

Inom

Interrupt. Selecc. In * 1,75

Descripcion

13

Imax=

14

15

16

17

Factores de correccion

Ic

1.25 x (11) Temp.amb.(OC)=

42

18

19

Cant. de Tipo de cables cond por fase

CA IDA DE T ENSION

20

21

Cable calibre

I del conductor seleccionado finalmente  Amp

22

23

24

N/R

Longitud

Cant. de cables por fase

Amp

Mts.

25

26

27

SEL ECCIÓN FINA L

28

29

30

31

32

caida de tension acumulada (menor del 5%)

Tipo de cond

Cable calibre

R Resist.

X React.

parc.

parc.

parc.

tot.

MO/MC

 AWG/ MCM

oh ohms ms/K /Km m

oh ohms ms/K /Km m

%V

%V

%V

%V

3 33 3

34

35

36

Conductor seleccionado AWG/MCM

37

38

Diametro Canalización FUERZA

Diametro Canalización CONTROL

mm

calibre (AWG/KCM) cant.

HP/KW/KVA

V

Amp

Amp.

Amp

Ft

Fa

Fch

MO/MC  AWG/ MCM

fuerza

control

tierra

mm

MOTORES CONECTADOS AL CCM-01A Y CCM-02A

BOMBA DE CIRCULACION DE

1

2

CF-302

CF-303

BGA-110A

 AGUA AL ABSORBEDOR 103

BGA-110B

BOMBA DE CIRCULACION DE  AGUA AL ABSORBEDOR BDA103

BDA-

500 200

200

HP

480

3

0.85

0 0..9

240.00

3 x

500

300.00

365.85

0.82

1.00

1

1

MO

KCM

380

365.85

52

1

MO

500

0.0950

0.1570

0.74

0.74

3

500

12

2

103

27

HP

480

3

0.85

0 0..9

240.00

3 x

500

300.00

365.85

0.82

1.00

1

1

MO

500 KCM

380

365.85

50

1

MO

500

0.0950

0.1570

0.71

0.71

3

500

12

2

103

27

 

 

No. DE PROYECTO:

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSION

DT-JE-MC-002-08

DOC. No. DT-JE-MC-002-08

HOJA 11

REVISION

DE: 15

0

FECHA: 10-DICIEMBRE-08

 Anexo 3

Cálculos de Cables Eléctricos en 220 volts B. T. (resumen)

 

 

No. DE PROYECTO:

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSION

DT-JE-MC-002-08

DOC. No. DT-JE-MC-002-08 FECHA: 10-DICIEMBRE-08

 Anexo 4

HOJA 12

REVISION

DE: 15

0

1 Cálculos de Cables Eléctricos en 480 volts B. T. (resumen)

 

DOCUMENTO No.

 ANEXO 4 1

DT-JE-MC-002-08

MEMORIAS DE CALCULO DE CABLES ELECTRICOS EN BAJA TENSION 480 VOLTS 1

REV. DA TOS

1

partida

2

Circuito

3

Clave del equipo

INT.

4

5

6

potencia

7

Tension

8

Fases

9

F. P.

10

Ef.

11

12

Inom

Interrupt. Selecc. In * 1,75

Descripcion

A MPA CIDA D

13

Imax=

14

15

16

17

Factores de correccion

Ic

1.25 x (11) O

Temp.amb.( C)=

42

18

19

Cant. Tipo de de cond cables por fase

CA IDA DE T ENSION

20

21

Cable calibre

I del conductor seleccionado finalmente  Amp

22

23

24

N/R

Longitud

Cant. de cables por fase

Amp

Mts.

25

26

27

SELECCIÓN FINAL

28

Tipo de cond

Cable calibre

R Resist.

X React.

MO/MC

 AWG/ MCM

oh ohms ms/K /Km m

oh ohms ms/K /Km m

29

30

31

32

caida de tension acumulada (menor del 5%) parc.

parc.

parc.

tot.

%V

%V

%V

%V

3 33 3

34

35

36

Conductor seleccionado AWG/MCM

37

38

Diametro Canalización FUERZA

Diametro Canalización CONTROL

mm

mm

calibre (AWG/KCM) cant.

HP/KW/KVA

V

Amp

Amp.

Amp

Ft

Fa

Fch

MO/MC  AWG/ MCM

fuerza

control

tierra

MOTORES CONECTADOS AL CCM-840

1 1

CF-250

BGA-651-A

BOMBA DE ALIMENTACION DE  ACETONA AL PROCESO

2

CF-251

BGA-653-A

BOMBA PARA CARGA DE ISOCONTENEDORES DE ACH

3

CF-252

BGA-650A

BOMBA DE DESCARGA DE  ACETONA A PIPAS

4

CF-260

BGA-650B

BOMBA DE DESCARGA DE  ACETONA A PIPAS

5

CF-261

BGA-653-B

6

CF-262

BGA-651-B

BOMBA PARA CARGA DE ISOCONTENEDORES DE ACH BOMBA DE ALIMENTACION DE  ACETONA AL PROCESO

2.4 50 5 5

12  AWG 1/0  AWG 12  AWG

30

8.63

55

1

MO

10

3.9000

0.2070

0.32

0.32

1

10

12

12

21

27

125

114.44

50

1

MO

1/0

0.3900

0.1800

0.39

0.39

1

1/0

12

6

41

21

30

13.38

55

1

MO

10

3.9000

0.2070

0.53

0.53

1

10

12

12

21

JUNTO CON FUERZA

MO

12  AWG

30

13.38

55

1

MO

10

3.9000

0.2070

0.53

0.53

1

10

12

12

21

JUNTO CON FUERZA

1

MO

1/0  AWG

125

114.44

50

1

MO

1/0

0.3900

0.1800

0.57

0.57

1

1/0

12

6

41

21

1

MO

12  AWG

30

8.63

55

1

MO

10

3.9000

0.2070

0.34

0.34

1

10

12

12

21

27

KW

480

3

0.85

_

4.90

3 x

15

6.13

8.63

0.71

1.00

1.00

1

MO

HP

480

3

0.85

0.9

65.00

3 x

125

81.25

114.44

0.71

1.00

1

1

MO

HP

480

3

0.85

0.9

7.60

3 x

15

9.50

13.38

0.71

1.00

1

1

MO

HP

480

3

0.85

0.9

7.60

3 x

15

9.50

13.38

0.71

1.00

1

1

HP

480

3

0.85

0.9

65.00

3 x

125

81.25

114.44

0.71

1.00

1

KW

480

3

0.85

_

4.90

3 x

15

6.13

8.63

0.71

1.00

1

50 2.4

1

 

 

No. DE PROYECTO:

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSION

DT-JE-MC-002-08

DOC. No. DT-JE-MC-002-08

HOJA 13

REVISION

DE: 15

0

FECHA: 10-DICIEMBRE-08

 Anexo 5

Cálculos de Alimentadores CCM-03A / CCM-04A

 

DOCUMENTO No.

 ANEXO 5

DT-JE-MC-002-08

1

1

REV.

CALCULO DE A LIMENTADORES LIMENTADORES CCM-03A CALCULO PARA ALIMENTADORES Y DISPOSITIVOS DE PROTECCION PARA TABLEROS TA BLEROS DE DISTRIBUCION DISTRIBUCION EN BAJ BAJA A TENSION REFERENCIAS : LA MEMORIA DE CALCULO ESTA BASADA EN LA NORMA OFICIAL MEXICANA NOM-001-SEDE-2005 TODOS LOS ARTICULOS Y TABLAS QUE SE MENCIONAN EN LA MEMORIA FUERON TOMADOS DE LA NOM-001-SEDE-2005 ALIMENTADOR Y PROTECCIONES PARA CCM Y/O TABLERO CON CARGAS DERIVADAS EN LOS MISMOS

 

Parte " E " Protección contra corto circuito y falla a tierra

 

Parte " B " Alimentador 

  Parte " E " Protección contra corto circuito y falla a tierra

 

   

CCM Y/O TABLERO

Otras cargas

Motores

1.- DATOS CLAVE DEL EQUIPO CIRCUITO No. A.-DEL MOTOR MAYOR (EN OPERACIÓN) B.-DE OTRAS CARGAS (EN OPERACIÓN) TENSION DEL SISTEMA (V) No. DE HILOS: FRECUENCIA: FACTOR DE POTENCIA (FP) TEMPERATURA AMBIENTE: AISLAMIENTO DEL CONDUCTOR TEMPERATURA DEL AISLAMIENTO LONGITUD DEL CIRCUITO (L) CANALIZACION

CCM-03A CF-200 200 292.798 480 3 60 0.85 42 THW-L S 90 25 CH/TC

H.P. KW VOLTS HILOS Hz.

1

°C MONOPOL AR AR °C Mts.

 

DOCUMENTO No.

 ANEXO 5

DT-JE-MC-002-08

1

1

REV.

CALCULO DE A LIMENTADORES LIMENTADORES CCM-03A 2.- CALCULO DE LA CORRIENTE NOMINAL INOMOT = CORRIENTE NOMINAL MOTORES EN OPERACIÓN

240.28

AMP

174.06

AMP.

IN = (INOMOT + INOC)

414.34

AMP.

IM = DATO TOM TOMADO ADO DE LAS TABLAS TABLAS DEL   ARTICULO 430

240.0

AMP.

654.34

AMP.

845.21

AMP.

INOC = CORRIENTE NOMINAL DE OTRAS CARGAS INOC = KW   3 X E X F.P.

PARA SIST. DE 3 FASES

IN = CORRIENTE NOMINAL DE TODAS LAS CARGAS SIN INCLUIR EL MOTOR MAYOR

  IN = CORRIENTE NOMINAL DE TODAS LAS CARGAS ∑ DERIVADAS DEL CCM Y/O TABLERO

∑ IN =

IM + IN

3.- CALCULO DEL CONDUCTOR POR AMPACIDAD I MAX = IN + 25% IM

ART. 430-24, Y 220-3(a)

I MAX = CO CONSIDERANDO NSIDERANDO 2 20% 0% FUTURO

EL CONDUCTOR SE SELECCIONA EN BASE AL RANGO DE LAS TERMINALES DEL EQUIPO EQUIPO DE ACUERDO AL ARTICULO 110-14 (c), Y UTILIZANDO LAS TABLAS 310-16 Y/O 310-17 CONDUCTOR SELECCIONADO DE TABLA 310-17 CALIBRE DEL CONDUCTOR SELECCIONADO

3x F

3/0

3

CALLIBRE CONSIDERANDO ARREGLO DE CABLES EN CHAROLA CORRIENTE NOMINAL DEL CONDUCTOR SELECCIONADO (IC) :310-17 CORRIENTE NOMINAL DEL CONDUCTOR SELECCIONADO (IC) :310-16

500 700 430

4.- FACTORES DE CORRECCION. LOS FACTORES DE CORRECCION SE SELECCIONARAN DE ACUERDO CON LOS REQUERIMIENTOS ESTABLECIDOS EN LOS ARTICULOS 310-15, 318-11, Y DE LAS TABLAS 310-16, 310-17, 310-18, 310-19. FT = FACTOR DE CORRECCION POR TEMPERATURA AM AMBIENTE BIENTE 0.87   t cond. = 60°C (Ipc =100 AMPS.)   t cond. = 90°C (Ipc >100 AMPS.)

FACT.TEMP.= FACT.TEMP.= FACT.TEMP.=

FA = FACTOR DE CORRECCION POR AGRUPAMIENT AGRUPAMIENTO O EN TUBERIA CONDUIT

0.71 0.82 0.87

K CM AMP AMP

FACTOR DE AGRUPAMENTO

1

FCH = FACTOR DE CORRECCION PO POR R AGRUPAMIENTO EN CHAROLA ( ARTICULO DE ACUERDO A ARREGLO DE CABLES EN CHAROLA)

0.65  ART. 318-11,B),2)

5.- APLICACIÓN DE LOS FACTORES DE CORRECCION OBTENCION DE LA CORRIENTE CORREGIDA DEL CONDUCTOR SELECCIONADO (ICC) EN TUBERIA CONDUIT:

 

DOCUMENTO No.

 ANEXO 5

DT-JE-MC-002-08

1 REV.

1

CALCULO DE A LIMENTADORES LIMENTADORES CCM-03A  ICC= IC X FA X FT

374.1

AMP

395.85

AMP

EN CHAROLA:  ICC= IC X FCH X FT

SI LA CORRIENTE CORREGIDA DEL CONDUCTOR SELECCIONADO ( ICC ) RESULTA MAYOR O IGUAL A LA CORRIENTE NOMINAL ( I MAX ) DEL MISMO LA SELECCIÓN DEL CONDUCTOR FUE LA CORRECTA. ICC >

I MAX

1122.30

>

845.21

AMP

CUMPLE

PARA TEMPERATURA DEL CONDUCTOR 90º C

6.- CALCULO DE ALIMENTADOR POR CAIDA DE TENSION DABERA CUMPLIR CON LAS RECOMENDACIONES DE LOS ARTICULOS 210-19 ( a ) NOTA 4 Y 215-2 ( b ) NOTA 1. FORMULAS A UTILIZAR: % V=  

3x

∑IN. x L x [( R COSø) + ( X SENø )] x 100 E

DONDE : %V = CAIDA DE TENSION EN EL CONDUCTOR EN % E = TENSION  ∑ .IN = CORRIENTE NOMINAL CALIBRE DEL CONDUCTOR SELECCIONADO

480 845.21 500

VOLTS AMP. AWG/KCM

L LONGITUD DEL CONDUCTOR R == RESISTENCIA DEL CONDUCTOR X = REACTANCIA DEL CONDUCTOR COS ø = FACTOR DE PO POTENCIA TENCIA SEN ø =

0.025 0.0950 0.1570 0.85 0.53

kM OHMS/KM OHMS/KM

3xF

LA CAIDA DE TENSION NO DEBERA SER MAYOR DEL 3 % %V= PARA CIRCUITOS TRIFASICOS

0.42

7.- SELECCIÓN DEL DISPOSITIVO DE PROTECCION CONTRA CORTO CIRCUITO Y FALLA A TIERRA ( IN.INT ).

%

CUMPLE

LA SELECCIÓN DEBERA ESTAR DE ACUERDO A LO ESTABLECIDO EN EL ARTICULO 430-62 TIPO DE DISPOSITIVO SELECCIONADO

INTERRUPTOR TERMOMAGNETICO

CAPACIDAD DEL MAYOR DE LOS DISPOSITIVOS DE PROTECCION CONECTADOS AL CCM Y/O TABLERO ( INT ). INT =

500

AMP

CORRIENTE NOMINAL DE TODAS LAS CARGAS DERIVADAS SIN CONSIDERAR LA CORRIENTE NOMINAL DEL CIRCUITO QUE TIENE EL MAYOR DE LOS DISPOSITIVOS DE PROTECCION ( IN2 ). IN2 = 414.34

AMP

IN. INT = INT + IN2 =

914.34

AMP

1000

AMP

EL DISPOSITIVO SELECCIONADO DEBERA SER DE:

 

DOCUMENTO No.

 ANEXO 5

DT-JE-MC-002-08

1

1

REV.

CALCULO DE A LIMENTADORES LIMENTADORES CCM-03A 8.- SELECCION DEL CONDUCTOR DE TIERRAS LA SELECCION DEBERA ESTAR DE ACUERDO AL ARTICULO 250-91 Y TABLA 250-95 Y A LAS RECOMENDACIONES ESTABLECIDAS EN EL ARTICULO 318-3(b)(1). DE ACUERDO CON EL DISPOSITIVO DE PROTECCION SELECCIONADO EN EL PUNTO N0. 7 PARA UNA PROTECCION DE: 1000 AMP LE CORRESPONDE UNA SECCION DE CONDUCTOR DE: CONDUCTOR DE TIERRAS SELECCIONADO:

67.430

 MM²

2/0

AWG

1701.83 78 mm Ø 510.7 169.7 3

MM. MM. MM. MM.

9.- CALCULO DE LA CANALIZACION DIAMETRO DE LAS CANALIZACIONES AREA TOTAL DE LOS CONDUCTORES Dt = DIAMETRO DE TUBO CONDUIT (FUERZA) Ac = AREA DE LOS CONDUCTORES FUERZA Ac = AREA DEL CONDUCTOR CONDUCTOR DE TIERRAS N = NUMERO DE CONDUCTORES FUERZA POR TUBO

10.- RESUMEN :

3 tubos

 9 - 500 , 3 - 2/0 t , 3 - T -78 mm Ø

 

 

No. DE PROYECTO:

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSION

DT-JE-MC-002-08

DOC. No. DT-JE-MC-002-08 FECHA: 10-DICIEMBRE-08

 Anexo 6

HOJA 14

REVISION

DE: 15

0

Cálculos de Alimentadores CCM-02A / CCM-02B

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 6 1

REV.

CALCULO DE AL ALIMEN IMENTADORES TADORES CCM-02 A CALCULO PARA ALIMENTADORES Y DISPOSITIVOS DE PROTECCION PARA TABLEROS TA BLEROS DE DISTRI DISTRIBUCION BUCION EN BAJ A TENSION TENSION REFERENCIAS : LA MEMORIA DE CALCULO ESTA BASADA EN LA NORMA OFICIAL MEXICANA NOM-001-SEDE-2005 TODOS LOS ARTICULOS Y TABLAS QUE SE MENCIONAN EN LA MEMORIA FUERON TOMADOS DE LA NOM-001-SEDE-2005 ALIMENTADOR Y PROTECCIONES PARA CCM Y/O TABLERO CON CARGAS DERIVADAS EN LOS MISMOS

 

Parte " E " Protección contra corto circuito y falla a tierra

 

Parte " B " Alimentador 

 

Parte " E " Protección contra corto circuito y falla a tierra

 

CCM Y/O TABLERO

1

   

Otras cargas

Motores

1.- DATOS CLAVE DEL EQUIPO CIRCUITO No. A.-DEL MOTOR MAYOR (EN OPERACIÓN)

CCM-02 CF-100 0.50

B US A

B.-DE OTRAS CARGAS (EN OPERACIÓN) TENSION DEL SISTEMA (V) No. DE HILOS: FRECUENCIA: FACTOR DE POTENCIA (FP) TEMPERATURA AMBIENTE: AISLAMIENTO DEL CONDUCTOR TEMPERATURA DEL AISLAMIENTO LONGITUD DEL CIRCUITO (L)

15.53 220 3 60 0.85 42 THW-L S 75 25

KW VOLTS HILOS Hz.

H.P. 1

°C MONOPOL AR AR °C Mts.

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 6

1

REV.

1

CALCULO DE AL ALIMEN IMENTADORES TADORES CCM-02 A CANALIZACION

TC

2.- CALCULO DE LA CORRIENTE NOMINAL INOMOT = CORRIENTE NOMINAL MOTORES EN OPERACIÓN

0.64

AMP

47.93

AMP.

48.57

AMP.

58.29

AMP.

INOC = CORRIENTE NOMINAL DE OTRAS CARGAS INOC = KW   3 X E X F.P.

PARA SIST. DE 3 FASES

IN = CORRIENTE NOMINAL DE TODAS LAS CARGAS IN = (INOMOT + INOC)

3.- CALCULO DEL CONDUCTOR POR AMPACIDAD I MAX = IN + 25% IM

ART. 430-24, Y 220-3(a)

I MAX = CONSIDER CONSIDERANDO ANDO 20% FUTURO

EL CONDUCTOR SE SELECCIONA EN BASE AL RANGO DE LAS TERMINALES DEL EQUIPO DE ACUERDO AL ARTICULO 110-14 (c), Y UTILIZANDO LAS TABLAS 310-16 Y/O 310-17 CONDUCTOR SELECCIONADO DE TABLA 310-16 CALIBRE DEL CONDUCTOR SELECCIONADO

1x F

CALLIBRE CONSIDERANDO ARREGLO DE CABLES EN CHAROLA

6

1

A WG 4/0

A WG

CORRIENTE NOMINAL DEL CONDUCTOR SELECCIONADO (IC) :310-16

195

AMP

4.- FACTORES DE CORRECCION. LOS FACTORES DE CORRECCION SE SELECCIONARAN DE ACUERDO CON LOS REQUERIMIENTOS ESTABLECIDOS EN LOS ARTICULOS 310-15, 318-11, Y DE LAS TABLAS 310-16, 310-17, 310-18, 310-19. FT = FACTOR DE CORRECCION POR TEMPER TEMPERATURA ATURA AMBIENTE

0.71

FA = FACTOR DE CORRECCION POR AGRUPAMIENTO AGRUPAMIENTO EN TUBERIA CONDUIT FACTOR DE AGRUPAMENTO

1

5.- APLICACIÓN DE LOS FACTORES DE CORRECCION OBTENCION DE LA CORRIENTE CORREGIDA DEL CONDUCTOR SELECCIONADO (ICC) EN TUBERIA CONDUIT: ICC= IC X FA X FT

138.45

AMP

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 6 REV.

1

1

CALCULO DE AL ALIMEN IMENTADORES TADORES CCM-02 A SI LA CORRIENTE CORREGIDA DEL CONDUCTOR SELECCIONADO ( ICC ) RESULTA MAYOR O IGUAL A LA CORRIENTE NOMINAL ( I MAX ) DEL MISMO LA SELECCIÓN DEL CONDUCTOR FUE LA CORRECTA. ICC >

I MAX

138.45

>

58.29

AMP

CUMPLE

PARA TEMPERATURA DEL CONDUCTOR 90º C

6.- CALCULO DE ALIMENTADOR POR CAIDA DE TENSION DABERA CUMPLIR CON LAS RECOMENDACIONES DE LOS ARTICULOS 210-19 ( a ) NOTA 4 Y 215-2 ( b ) NOTA 1. FORMULAS A UTILIZAR: % V=  

3x

∑IN. x L x [( R COSø) + ( X SENø )] x 100 E

DONDE : %V = CAIDA DE TENSION E EN N EL CONDUCTOR E EN N% E = TENSION   .IN = CORRIENTE NOMINAL ∑ CALIBRE DEL CONDUCTOR SELECCIONADO L = LONGITUD DEL CONDUCTOR R = RESISTENCIA DEL CONDUCTOR X = REACTANCIA DEL CONDUCTOR COS ø = FACTOR DE POTENCIA SEN ø = LA CAIDA DE TENSION NO DEBERA SER MAYOR DEL 3 %

220 58.29 4/0 0.025 0.2070 0.1670 0.85 0.53

VOLTS AMP. AWG/KCM kM OHMS/KM OHMS/KM

1xF

%V PARA CIRCUITOS TRIFASICOS

0.30

%

CUMPLE

7.- SELECCIÓN DEL DISPOSITIVO DE PROTECCION CONTRA CONTRA CORTO CIRCUITO Y FALLA A TIERRA ( IN.INT ). LA SELECCIÓN DEBERA ESTAR DE ACUERDO A LO ESTABLECIDO EN EL ARTICULO 430-62 INTERRUPTOR TERMOMAGNETICO

TIPO DE DISPOSITIVO SELECCIONADO

CAPACIDAD DEL MAYOR DE LOS DISPOSITIVOS DE PROTECCION CONECTADOS AL CCM Y/O TABLERO ( INT ). INT =

100

AMP

EL DE LOS DISPOSITIVOS DE PROTECCION ( IN2 ). IN2MAYOR =

48.57

AMP

IN. INT = INT + IN2 =

148.57

AMP

150

AMP

CORRIENTE NOMINAL DE TODAS LAS CARGAS DERIVADAS SIN CONSIDERAR LA CORRIENTE NOMINAL DEL CIRCUITO QUE TIENE

EL DISPOSITIVO SELECCIONADO DEBERA SER DE:

8.- SELECCION DEL CONDUCTOR DE TIERRAS

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 6 REV.

1

1

CALCULO DE AL ALIMEN IMENTADORES TADORES CCM-02 A LA SELECCION DEBERA ESTAR DE ACUERDO AL ARTICULO 250-91 Y TABLA 250-95 Y A LAS RECOMENDACIONES ESTABLECIDAS EN EL ARTICULO 318-3(b)(1). DE ACUERDO CON EL DISPOSITIVO DE PROTECCION SELECCIONADO EN EL PUNTO N0. 7 PARA UNA PROTECCION DE: 150 AMP LE CORRESPONDE UNA SECCION DE CONDUCTOR DE: CONDUCTOR DE TIERRAS SELECCIONADO:

67.430

 MM²

2/0

AWG

891.30 63 mm Ø 240.5 169.7 3

MM. MM. MM. MM.

9.- CALCULO DE LA CANALIZACION CANA LIZACION DIAMETRO DE LAS CANALIZACIONES AREA TOTAL DE LOS CONDUCTORES Dt = DIAMETRO DE TUBO CONDUIT (FUERZA) Ac = AREA DE LOS CONDUCTORES FUERZA Ac = AREA DEL CONDUCTOR DE TIERRAS N = NUMERO DE COND CONDUCTORES UCTORES FUERZA POR TUBO

10.- RESUMEN :

 3 - 4/0 , 1 - 2/0 t , 1 - T -63 mm Ø

NOTA: EL ALIMENTADOR SE SELECCIONO EN BASE A UNA TEMPERATURA DE AISLAMIENTO DEL CONDUCTOR DE 75° C

1 tubo

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 6 1 REV.

CALCULO DE ALIMENTADORES A LIMENTADORES CCM-02 B CALCULO PARA ALIMENT AL IMENTADORES ADORES Y DISPOS DISPOSITIVO ITIVOS S DE PROTECCION PROTECCION PARA TABLEROS TA BLEROS DE DISTRIBUCI DISTRIBUCION ON EN BAJ A TENSION REFERENCIAS REFERENC IAS : LA MEMORIA DE CALCULO ESTA BASADA EN LA NORMA OFICIAL MEXICANA NOM-001-SEDE-2005 TODOS LOS ARTICULOS Y TABLAS QUE SE MENCIONAN EN LA MEMORIA FUERON TOMADOS DE LA NOM-001-SEDE-2005 ALIMENTADOR Y PROTECCIONES PARA CCM Y/O TABLERO CON CARGAS DERIVADAS EN LOS MISMOS

 

Parte " E " Protección contra corto circuito y falla a tierra

 

Parte " B " Alimentador 

  Parte " E " Protección contra corto circuito y falla a tierra

 

CCM Y/O TABLERO

1

   

Otras cargas

Motores

1.- DATOS CLAVE DEL EQUIPO CIRCUITO No.

CCM-02 CF-101

B US B

A.-DELOTRAS MOTORCARGAS MAYOR (EN (EN OPERACIÓN) OPERACIÓN) B.-DE TENSION DEL SISTEMA (V) No. DE HILOS: FRECUENCIA: FACTOR DE POTENCIA (FP) TEMPERATURA AMBIENTE: AISLAMIENTO DEL CONDUCTOR TEMPERATURA DEL AISLAMIENTO

0.75 12.29 220 3 60 0.85 42 THW-L S 75

H.P. KW VOLTS HILOS Hz.

1

°C MONOPOL A AR R °C

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 6 1 REV.

1

CALCULO DE ALIMENTADORES A LIMENTADORES CCM-02 B LONGITUD DEL CIRCUITO (L) CANALIZACION

25 TC

Mts.

3.32

AMP

37.94

AMP.

41.26

AMP.

49.52

AMP.

2.- CALCULO DE LA CORRI CORRIENTE ENTE NOMINAL NOMINAL INOMOT = CORRIENTE NOMINAL MOTORES EN OPERACIÓN INOC = CORRIENTE NOMINAL DE OTRAS CARGAS INOC = KW   3 X E X F.P.

PARA SIST. DE 3 FASES

IN = CORRIENTE NOMINAL DE TODAS LAS CARGAS IN = (INOMOT + INOC)

3.- CALCULO DEL CONDUCTOR CONDUCTOR POR AMPACIDAD I MAX = IN + 25% IM

ART. 430-24, Y 220-3(a)

I MAX = CONSIDERANDO 20% FUTURO

EL CONDUCTOR SE SELECCIONA EN BASE AL RANGO DE LAS TERMINALES DEL EQUIPO DE ACUERDO AL ARTICULO 110-14 (c), Y UTILIZANDO LAS TABLAS 310-16 Y/O 310-17 CONDUCTOR SELECCIONADO DE TABLA 310-16 CALIBRE DEL CONDUCTOR SELECCIONADO

1x F

8

A WG

1

CALLIBRE CONSIDERANDO ARREGLO DE CABLES EN CHAROLA

4/0

CORRIENTE NOMINAL DEL CONDUCTOR SELECCIONADO (IC) :310-16

195

A WG AMP

4.- FACTORES DE CORRECCION. LOS FACTORES DE CORRECCION SE SELECCIONARAN DE ACUERDO CON LOS REQUERIMIENTOS ESTABLECIDOS EN LOS ARTICULOS 310-15, 318-11, Y DE LAS TABLAS 310-16, 310-17, 310-18, 310-19. FT = FACTOR DE CORRECCION POR TEMPERATURA AMBIENTE

0.71

FA = FACTOR DE CORRECCION POR AGRUPAMIENTO EN TUBERIA CONDUIT FACTOR DE AGRUPAMENTO

1

5.- APLICACIÓN DE LOS FACTORES DE CORRECCION OBTENCION DE LA CORRIENTE CORREGIDA DEL CONDUCTOR SELECCIONADO (ICC) EN TUBERIA CONDUIT: ICC= IC X FA X FT

138.45

AMP

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 6 1 REV.

1

CALCULO DE ALIMENTADORES A LIMENTADORES CCM-02 B SI LA CORRIENTE CORREGIDA DEL CONDUCTOR SELECCIONADO ( ICC ) RESULTA MAYOR O IGUAL A LA CORRIENTE NOMINAL ( I MAX ) DEL MISMO LA SELECCIÓN DEL CONDUCTOR FUE LA CORRECTA. ICC >

I MAX

138.45

>

49.52

AMP

CUMPLE

PARA TEMPERATURA DEL CONDUCTOR 90º C

6.- CALCULO DE ALIMENTADOR POR CAIDA DE TENSION DABERA CUMPLIR CON LAS RECOMENDACIONES DE LOS ARTICULOS 210-19 ( a ) NOTA 4 Y 215-2 ( b ) NOTA 1. FORMULAS A UTILIZAR: % V=  

3x

∑IN. x L x [( R COSø) + ( X SENø )] x 100 E

DONDE : %V = CAIDA DE TENSION EN EL CONDUCTOR EN % E = TENSION   .IN = CORRIENTE NOMINAL ∑ CALIBRE DEL CONDUCTOR SELECCIONADO L = LONGITUD DEL CONDUCTOR R = RESISTENCIA DEL CONDUCTOR X = REACTANCIA DEL CONDUCTOR COS ø = FACTOR DE POTENCIA SEN ø = LA CAIDA DE TENSION NO DEBERA SER MAYOR DEL 3 %

220 49.52 4/0 0.025 0.2070 0.1670 0.85 0.53

VOLTS AMP. AWG/KCM kM OHMS/KM OHMS/KM

1xF

%V= PARA CIRCUITOS TRIFASICOS

0.26

%

CUMPLE

7.- SELECCIÓN DEL DISPOSITIVO DE PROTECCION CONTRA CORTO CIRCUITO CIRCU ITO Y FALL A A TIERR TIERRA A ( IN.I IN.INT NT ). LA SELECCIÓN DEBERA ESTAR DE ACUERDO A LO ESTABLECIDO EN EL ARTICULO 430-62 TIPO DE DISPOSITIVO SELECCIONADO

INTERRUPTOR INTERRUP TOR TERMOMAGNETICO

CAPACIDAD DEL MAYOR DE LOS DISPOSITIVOS DE PROTECCION CONECTADOS AL CCM Y/O TABLERO ( INT ). INT =

70

AMP

CORRIENTE NOMINAL DE TODAS LAS CARGAS DERIVADAS SIN CONSIDERAR LA CORRIENTE NOMINAL DEL CIRCUITO QUE TIENE EL MAYOR DE LOS DISPOSITIVOS DE PROTECCION ( IN2 ). IN2 = 41.26

AMP

IN. INT = INT + IN IN2 2 =

111.26

AMP

125

AMP

EL DISPOSITIVO SELECCIONADO DEBERA SER DE:

8.- SELECCION DEL CONDUCTOR DE TIERRAS

 

DOCUMENTO No.

DT-JE-MC-002-08

 ANEXO 6 1 REV.

1

CALCULO DE ALIMENTADORES A LIMENTADORES CCM-02 B LA SELECCION DEBERA ESTAR DE ACUERDO AL ARTICULO 250-91 Y TABLA 250-95 Y A LAS RECOMENDACIONES ESTABLECIDAS EN EL ARTICULO 318-3(b)(1). DE ACUERDO CON EL DISPOSITIVO DE PROTECCION SELECCIONADO EN EL PUNTO N0. 7 PARA UNA PROTECCION DE: 150 AMP LE CORRESPONDE UNA SECCION DE CONDUCTOR DE: CONDUCTOR DE TIERRAS SELECCIONADO:

67.430

 MM²

2/0

AWG

891.30 63 mm Ø 240.5 169.7 3

MM. MM. MM. MM.

9.- CALCULO DE LA CANALIZACION DIAMETRO DE LAS CANALIZACIONES AREA TOTAL DE LOS CONDUCTORES Dt = DIAMETRO DE TU TUBO BO CONDUIT (FUE (FUERZA) RZA) Ac = AREA DE LOS CONDUCTORES FUERZA Ac = AREA DEL CONDUCTOR DE TIERRAS N = NUMERO DE CONDUCTORES FUERZA POR TUBO

10.- RESUMEN :

 3 - 4/0 , 1 - 2/0 t , 1 - T -63 mm Ø

NOTA: EL ALIMENTADOR SE SELECCIONO EN BASE A UNA TEMPERATURA DE AISLAMIENTO DEL CONDUCTOR DE 75° C

1 tubo

 

 

No. DE PROYECTO:

MEMORIAS MEMO RIAS DE CÁL CULO CABLES DE BAJ A TENSION

DT-JE-MC-002-08

DOC. No. DT-JE-MC-002-08 FECHA: 10-DICIEMBRE-08

 Anexo 7

HOJA 15

REVISION

DE: 15

0

Cálculos de Alimentadores CCM-840 A/ CCM-840 B

 

DOCUMENTO No.

 ANEXO 7

DT-JE-MC-002-08

1 REV.

CALCULO DE ALIMENTADORE ALIMENTADORES S CCM-840 CALCULO PARA ALIMENTADORES Y DISPOSITIVOS DE PROTECCION PARA TABLEROS DE DISTRIBUCION DISTRIBUCION EN BAJ A TENSION TENSION REFERENCIAS : LA MEMORIA DE CALCULO ESTA BASADA EN LA NORMA OFICIAL MEXICANA NOM-001-SEDE-2005 TODOS LOS ARTICULOS Y TABLAS QUE SE MENCIONAN EN LA MEMORIA FUERON TOMADOS DE LA NOM-001-SEDE-2005 ALIMENTADOR Y PROTECCIONES PARA CCM Y/O TABLERO CON CARGAS DERIVADAS EN LOS MISMOS

 

Parte " E " Protección contra corto circuito y falla a tierra

 

Parte " B " Alimentador 

  Parte " E " Protección contra corto circuito y falla a tierra

 

CCM Y/O TABLERO

1

   

Otras cargas

Motores

1.- DATOS CLAVE DEL EQUIPO CIRCUITO No. A.-DEL MOTOR MAYOR (EN OPERACIÓN) B.-DE OTRAS CARGAS (EN OPERACIÓN) TENSION DEL SISTEMA (V) No. DE HILOS: FRECUENCIA: FACTOR DE POTENCIA (FP) TEMPERATURA AMBIENTE: AISLAMIENTO DEL CONDUCTOR TEMPERATURA DEL AISLAMIENTO LONGITUD DEL CIRCUITO (L) CANALIZACION

CCM-840A/B CF-840A/B 50 5.5 480 3 60 0.85 42 THW-L S 90 3 CH/TC

H.P. KW VOLTS HILOS Hz. °C MONOPOL A R °C Mts.

 

DOCUMENTO No.

 ANEXO 7

DT-JE-MC-002-08

1 REV.

CALCULO DE ALIMENTADORE ALIMENTADORES S CCM-840 2.- CALCULO DE LA CORRIENTE NOMINAL INOMOT = CORRIENTE NOMINAL MOTORES EN OPERACIÓN

12.50

AMP

INOC = CORRIENTE NOMINAL DE OTRAS CARGAS INOC = KW   3 X E X F.P.

PARA SIST. DE 3 FASES

AMP.

IN = CORRIENTE NOMINAL DE TODAS LAS CARGAS SIN INCLUIR EL MOTOR MAYOR IN = (INOMOT + INOC) IM = DATO TOMADO DE LAS TABLAS DEL   ARTICULO 430

12.50

AMP.

65.0

AMP.

77.50

AMP.

109.25

AMP.

  IN = CORRIENTE NOMINAL DE TODAS LAS CARGAS ∑ DERIVADAS DEL CCM Y/O TABLERO

∑ IN =

IM + IN

3.- CALCULO DEL CONDUCTOR POR AMPACIDAD I MAX = IN + 25% IM

ART. 430-24, Y 220-3(a)

I MAX = CONSI CONSIDERANDO DERANDO 20% FUTURO

EL CONDUCTOR SE SELECCIONA EN BASE A LA CORRIENTE NOMINAL DEL BUS DEL CCM-840

1

DE ACUERDO AL ARTICULO 240-21 c) 2), Y UTILIZANDO LAS TABLAS 310-16 Y/O 310-17 CONDUCTOR SELECCIONADO DE TABLA 310-16 CALIBRE DEL CONDUCTOR SELECCIONADO

1x F

1

4

CALLIBRE CONSIDERANDO ARREGLO DE CABLES EN UNA CANALIZACION

350

CORRIENTE NOMINAL DEL CONDUCTOR SELECCIONADO (IC) :310-17 CORRIENTE NOMINAL DEL CONDUCTOR SELECCIONADO (IC) :310-16

505 310

K CM AMP AMP

4.- FACTORES DE CORRECCION. LOS FACTORES DE CORRECCION SE SELECCIONARAN DE ACUERDO CON LOS REQUERIMIENTOS ESTABLECIDOS EN LOS ARTICULOS 310-15, 318-11, Y DE LAS TABLAS 310-16, 310-17, 310-18, 310-19. FT = FACTOR DE CORRECCION POR TE TEMPERATURA MPERATURA AMBIENTE 0.87   t cond. = 60°C (Ipc =100 AMPS.)   t cond. = 90°C (Ipc >100 AMPS.)

FACT.TEMP.= FACT.TEMP.= FACT.TEMP.=

0.71 0.82 0.87

FA = FACTOR DE CORRECCION POR AGRUPA AGRUPAMIENTO MIENTO EN TUBERIA CONDUIT FACTOR DE AGRUPAMENTO FCH = FACTOR DE CORRECCION POR AGRUPAMIENTO EN CHAROLA ( ARTICULO DE ACUERDO A ARREGLO DE CABLES EN CHAROLA)

1

 ART. 318-11,B),2)

 

DOCUMENTO No.

 ANEXO 7

DT-JE-MC-002-08

1 REV.

1

CALCULO DE ALIMENTADORE ALIMENTADORES S CCM-840 5.- APLICACIÓN DE LOS FACTORES DE CORRECCION OBTENCION DE LA CORRIENTE CORREGIDA DEL CONDUCTOR SELECCIONADO (ICC) EN TUBERIA CONDUIT: ICC= IC X FA X FT

269.7

AMP

0

AMP

EN CHAROLA:  ICC= IC X FCH X FT

SI LA CORRIENTE CORREGIDA DEL CONDUCTOR SELECCIONADO ( ICC ) RESULTA MAYOR O IGUAL A LA CORRIENTE NOMINAL ( I MAX ) DEL MISMO LA SELECCIÓN DEL CONDUCTOR FUE LA CORRECTA. ICC >

I MAX

269.70

>

109.25

AMP

PARA TEMPERATURA DEL CONDUCTOR 75º C

6.- CALCULO DE ALIMENTADOR POR CAIDA DE TENSION DABERA CUMPLIR CON LAS RECOMENDACIONES DE LOS ARTICULOS 210-19 ( a ) NOTA 4 Y 215-2 ( b ) NOTA 1. FORMULAS A UTILIZAR: % V=  

3x

∑IN. x L x [( R COSø) + ( X SENø )] x 100 E

CUMPLE

DONDE : %V = CAIDA D DE E TENSION EN EL CONDUCTOR EN % E = TENSION   .IN = CORRIENTE NOMINAL ∑ CALIBRE DEL CONDUCTOR SELECCIONADO L = LONGITUD DEL CONDUCTOR R = RESISTENCIA DEL CONDUCTOR X = REACTANCIA DEL CONDUCTOR COS ø = FACTOR DE POTENCIA SEN ø =

480 109.25 350 0.003 0.1280 0.1640 0.85 0.53

VOLTS AMP. AWG/KCM kM OHMS/KM OHMS/KM

1xF

LA CAIDA DE TENSION NO DEBERA SER MAYOR DEL 3 % %V= PARA CIRCUITOS TRIFASICOS

0.02

%

CUMPLE

7.- SELECCIÓN DEL DISPOSITIVO DE PROTECCION CONTRA CONTRA CORTO CIRCUITO Y FALLA A TIERRA ( IN.INT ). LA SELECCIÓN DEBERA ESTAR DE ACUERDO A LO ESTABLECIDO EN EL ARTICULO 430-62. b) TIPO DE DISPOSITIVO SELECCIONADO

INTERRUPTOR TERMOMAGNETICO

CAPACIDAD DEL MAYOR DE LOS DISPOSITIVOS DE PROTECCION CONECTADOS AL CCM Y/O TABLERO ( INT ).

 

DOCUMENTO No.

 ANEXO 7

DT-JE-MC-002-08

1 REV.

CALCULO DE ALIMENTADORE ALIMENTADORES S CCM-840 INT =

125

AMP

CORRIENTE NOMINAL DE TODAS LAS CARGAS DERIVADAS SIN CONSIDERAR LA CORRIENTE NOMINAL DEL CIRCUITO QUE TIENE EL MAYOR DE LOS DISPOSITIVOS DE PROTECCION ( IN2 ). IN2 = 12.50

AMP

IN. INT = INT + IN2 =

137.50

AMP

225

AMP

EL DISPOSITIVO SELECCIONADO DEBERA SER DE:

NOTAS: 1.- EL ALIMENTADOR SE SELECCIONO DE ACUERDO AL ARTICULO 240-21 c) 2) DE LA NOM-001-SEDE-2005 2.- EL INTERRUPTOR SELECCIONADO FUNCIONARA UNICAMENTE COMO DISPOSITIVO DE DESCONEXION