MCM3320 Application Training Switchgear Engineer Training 083006 Rev4 New Cummins Template

December 1, 2017 | Author: Vimal Das | Category: Relay, Control Theory, Device Driver, User Interface, Signal (Electrical Engineering)
Share Embed Donate


Short Description

Download MCM3320 Application Training Switchgear Engineer Training 083006 Rev4 New Cummins Template...

Description

MCM3320 QTQ Training

Rev 1.5 prd June 13, 2006

Presentation Outline

 Introduction  Features  Hardware  Operation  System Setup and Simulator (HANDS ON)  Operation (continued)  Variables  Interconnect  HMI & Simulator (HANDS ON)  InPower  Applications (GROUP)  Control and Component Mode Panels New  Discussion/Questions/Comments

2

Rev 1.5 prd June 13, 2006

Presentation Goals

 What are the capabilities of the MCM3320?  What are the board connections?  How does it operate?  How do I apply it?  How do I set it up?

3

Rev 1.5 prd June 13, 2006

MCM3320 Information

 Lotus Notes Database “Commercial ESB Controls”  Sort by “Category”  Look for “MCM3320”  This presentation and other technical information located there  An Application Guide is in the works to provide a one-stop document

4

Rev 1.5 prd June 13, 2006

MCM3320 Technical Support

 

Documentation PGA Controls Engineering: 1. 2. 3.

5

Rev 1.5 prd June 13, 2006

Kevin Aufderhar Paul Dahlen Rich Scroggins

FEATURES One-Line Feature Summary (Q2 2006)

MCM3320

Customer I/O

AC Metering Source Failure Gensets Start/Stop Main Breaker Control Sync/Volt Match Open/Closed Transition Load Ramping Extended Paralleling kW and kVAR Control Load Demand Load Add / Shed Scheduler Modbus Diagnostics

HMI211 Operator Panel #1

HMI112 Gensets Bargraph

HMI211 Operator Panel #2

HMI211 Utility Bargraph

G1 GM

UM

G2 G3 G4

Breakers or ATS

Load1

6

Rev 1.5 prd June 13, 2006

AUX101 AUX102

Load2

Load3

Load4

Load5

Load6

FEATURES Feature Validation

 All available features have been tested  Firmware test  Bench test w/simulator  Live test at Fridley Endurance Pad test facility  Live test at Fridley with real Utility Source (transfers, sync, base load / peak shave)

7

Rev 1.5 prd June 13, 2006

FEATURES

AC Metering

 3 Phase metering of genset bus and utility bus simultaneously  Phase and Total/avg metering of V, A, kW, kVAR, kVA, PF, Hz  Phase and total metering of +kWh, -kWh, +kVARh, kVARh, kVAh for each source  CT secondaries of 1A or 5A  PT accepts 0-480VLL directly; external PT for higher voltages (up to 35000V)  PT and CT inputs pre-calibrated

8

Rev 1.5 prd June 13, 2006

FEATURES

Master Sync / Volt Match

 both phase synchronization and voltage matching  20 genset limit for synchronizer  frequency offset range: +/- 1.0 Hz min; up to +/- 3.0Hz  output voltage offset range: +/- 6% min; up to +/- 10%  offset range generally independent of gen bus load

9

Rev 1.5 prd June 13, 2006

FEATURES

Master Sync / Volt Match

 controls frequency and voltage via PCC kW and kVAR load share lines  selectable phase synchronization (default) or slip frequency synchronization  sync enable input for manual control mode  option to invert synchronizer polarity if genset and utility swap positions in synchronizer only application (via Modbus)

10

Rev 1.5 prd June 13, 2006

FEATURES

Permissive Sync Check

 sync check function is independent of synchronizer  adjustable frequency window, phase window, voltage window, and window time for permissive check  includes configurable dead bus logic  sync check output  fail to synchronize diagnostic  phase rotation mismatch diagnostic

11

Rev 1.5 prd June 13, 2006

FEATURES

Breaker Control

 interface for both genset main and utility main  close and open control – momentary energization until desired position is achieved  a/b and tripped breaker position inputs  adjustable breaker recharge time delay to prevent fail to close due to inadequate charge time

12

Rev 1.5 prd June 13, 2006

FEATURES

Breaker Control

 utility paralleling enable output  breaker inhibit control input  breaker diagnostics with appropriate system control reaction  adjustable fail to close and fail to open time delays  paralleling fail to disconnect diagnostic with configurable system control reaction

13

Rev 1.5 prd June 13, 2006

FEATURES

Breaker Control

 anti-pump avoidance logic – external breaker position contacts not required in series with trip coil  breaker inhibit output to control individual genset paralleling breakers in applications with no gen main, and for backup disconnect protection capability

14

Rev 1.5 prd June 13, 2006

FEATURES

Power Transfer Control

 open transition w/pgm transition delay, hard closed transition (