MAINTENANCE
TK50G
TK50G MANUAL
Overseas Engineering Team
ThyssenKrupp Dongyang Elevator
-1-
Printed in KOREA January, 2007
MAINTENANCE
TK50G
2. Inspection operation preparation 2.1 Voltage check before Main power turn ON Check Point
Check
Remarks
P24G, G24
DC24V Voltage
TRANS Voltage
P24, G24
DC24V Voltage
SMPS Voltage
R-S, S-T, T-R
AC380V Voltage
R-N, S-N, T-N
AC220V Voltage
Building main power supply
R-AC1, S-AC1, T-AC1, - AC
AC220V Voltage
C/P power supply
2.2 M/R Wiring 17,18
Motor PG ; X907
EE,U,V,W,1,2
U,V,W,EE
BM1,BM2
R,S,T,N Picture 1
Picture 2
Motor wiring Box
C/P CPIK wiring
1. U,V,W,EE of Picture 1 connect to U(24),V(25),W(26),EE of picture 2 (CPIK). 2. Motor temperature detection sensor 1, 2 connect to 17(TM1),18(TM2) of picture 2 (CPIK). 3. Break signal BM1,BM2 connect to C/P PWR terminal 46(40),47(41).
1. Motor PG cable of picture 2 connect to CPIK connector X907. 2. U,V,W,EE connect to Motor U,V,W,EE. 3. R,S,T,N connect to Main supply panel of building R,S,T,N. 4. 17(TM1),18(TM2) connect to Motor Box 1,2.
ThyssenKrupp Dongyang Elevator
-2-
Printed in KOREA January, 2007
MAINTENANCE
TK50G
Temporary Remote control ; CNL2
Gov. PG
CNHV 3 Pin No. 1,2
CNHV 4 Pin No. 1,2,3,4,7/6,8
Picture 3
IOC PCB 1. Gov. PG connect to Gov. PG connector (When Inspection operation, no required) 2. Pin No. 1,2 of CNHV 3 are Jumper (123A,123) 3. Pin No. 1,2,3,4,7 of CNHV 4 are Jumper (CDCF,HDIF,DLT,DLB,AC1B) Pin No. 6,8 of CNHV 4 are Jumper (If don’t have Back Door) 4. Temporary remote control connect to pin 1 (Common), pin 3 (UP), pin 4 (DOWN).
E,F
3,4
40,41,44,45
Picture 4
C/P Wiring 1. Gov. S/W connect to 3 and 4. 2. MOTOR Brake connect to 40 and 41. 3. 5,7,9,11 Jumper ; Hoist-way and Car Safety line jumper. 4. Rope Brake Jumper ; E.F 5. SDB & SDT connect to 44 and 45. ThyssenKrupp Dongyang Elevator
-3-
Printed in KOREA January, 2007
MAINTENANCE
TK50G
2.3 Brake wiring check ㉠. Remove BRK+ and BRK- from Brake Controller(BRC) and check short or not between BRK+ and Earth and BRK- and Earth. (Insulation check) ㉡. Ohm check between BRK+ and BRK- by Ohmmeter - 260-290Ω. ㉢. Brake Coil should connect by serial connection. ㉣. Brake Controller(BRC) receive 220VAC and make DC voltage and control Brake. There are T-VR(Forcing= 1 sec) and V-VR(Holding voltage= DC100V).(Initial voltage = 185-190V, Holding voltage = 100V) 2.4 Encoder Wiring and check ①. Gov. Encoder Wiring (Wiring to CNL3 of IOC PCB) ㉠. Specification 105m/min below = GDY-1A(Ø242mm) ⇒ P 16 = 465 Check 120m/min over = GD-4A1(Ø240mm) ⇒ P 16 = 465 Check ㉡. Type : Incremental Type Output pulse :
300 (Pulse/revolution)
Output type :
Line Drive(A, A/, B, B/)
Supply voltage : ㉢. Wiring check :
DC 5V
1 PIN = PEA (Green) 2 PIN = PEA/ (Blue) 3 PIN = PEB (White) 4 PIN = PEB/ (Pink) 5 PIN = PENC(+5V) (Red) 6 PIN = GND(Grounding) (Black) 7 PIN = SHIELD 8 PIN = SPARE
*. If use Motor encoder only P 16 = 465 -> 15815 setting (This data is not fixed data) This data will be changed depend on car speed.
ThyssenKrupp Dongyang Elevator
-4-
Printed in KOREA January, 2007
MAINTENANCE
TK50G
②. Motor Encoder Wiring (X907 of CPI-K) ㉠.Specification : DY88-30C-1024VL ㉡.Type : Incremental Type Output Pulse : 1024 (Pulse/revolution) Output type : Line Drive(A, A/, B, B/, Z, Z/) Supply voltage : DC 5V ㉢. Wiring check : X907
1 = A/ (Blue) 2 = A (Green) 3 = B (White) 4 = B/ (Pink) 5 = Z/ (Orange) 6 = Z (Yellow) 7 = GND (Black) 8 = SHIELD 9 = +5V (Red)
㉣. Check by Remote FAST - M 50 = 1024 (45-105m/min) check (TK50M (MRL) - M 50 = 2048) ㉤. Installed bracket(Steal) is difference between TW(ThyssenKrupp Worm Gear)63 and TW130,160.
TW63
ThyssenKrupp Dongyang Elevator
TW130,160
-5-
Printed in KOREA January, 2007
MAINTENANCE
TK50G
2.5 Jumper for Inspection operation 1. JUMPER check GOV JUMPER = 101, 102 ( CHRT - 3, 4 ) HOISTWAY JUMPER = 103, 109 ( CHRT - 5, 7 ) CAR JUMPER = 109, 121 ( CHRT - 7, 11 ) ETSD JUMPER = 123, 123A ( IOC PCB ; CNHV 3 – Pin No. 1, 2 ) Front CAR Door (CDCF) = AC1B, 202 ( IOC PCB ; CNHV 4 - 1, 7 ) Front HALL Door (HDIF) = AC1B, 215 ( IOC PCB ; CNHV 4 - 2, 7 ) Rear CAR Door = AC1B, 204 ( IOC PCB ; CNHV 5 – 1 and CNHV 4 - 7 ) Rear HALL Door = AC1B, 225 ( IOC PCB ; CNHV 5 - 2 CNHV 4 - 7 ) => If no Rear Door jumper DZB and DZC ( CNHV 4 - 6, 8 ) DLB(3LS), DLT(4LS) JUMPER = DLB, DLT ( IOC PCB ; CNHV 4 - 3, 4, 7 ) EPNP(Emergency and Normal Power) JUMPER = IOC PCB - NP JUMPER PIN RGOK(Rope Gripper Okay) JUMPER = IOC PCB - CNL 8 – 2 and G24 IOC DIP S/W(INRB=INS RUN BUG) Turn ON
and check INRB LED ON position.
2. Temporary remote control connection (Refer to Picture 3) Connect it to CNL 2 of IOC PCB to move low speed operation. UP = CNL 2-3 (INCNU) DOWN = CNL 2-4 (INCND) Common = CNL 2-1 ( P24 ) 2.6 LED Check 1. IOC PCB - 101, AC1B, P24(DC24V), P24G(DC24V), P5B(DC5V), P5 6 pcs of LED are must ON 2. 186C PCB - EGOOD/EBAD LED must ON/OFF repeatedly (Flickering). After setting ESTD (120m/min above), EGOOD is ON and EBAD is OFF. 3. 186C PCB - WD/STAT LED are FLICKER then OFF 4. After few second later, WD LED must ON. (If WD LED is not ON, 186C Program is something wrong) 5. INRB(Ins Run Bug=Normal signal from Car top) LED must ON.
ThyssenKrupp Dongyang Elevator
-6-
Printed in KOREA January, 2007
MAINTENANCE
TK50G
2.7 Moving Direction check 1. In Remote FAST, INS speed(M16 = 50fpm(15m/min)), MOTOR Encoder PPR(Pulse per Revolution)(M50 =1024, MRL;M50=2048) check (1 fpm = 0.3048 m/min) 2. If not install Gov. Encoder, set M 60 = 0 or 25. Otherwise, Encoder Cross Check between Motor encoder and Gov. Encoder, Error will be happened. If M 60 = 255, Doing Encoder Cross Check between Motor and Gov. Encoder. 3. Revolution direction is wrong, change CPIK Parameter 3 and Parameter 4. 4. After change any DATA in Remote FAS, you should write WRT for saving data. 5. If car speed difference, you should check CPIK Parameter SHEAVE Diameter(P14), GEAR RATIO (P13). 6. In IMS Motion Diagnostic, check the Demand Velocity and Car Velocity whether it is same or not. If not same these data, check M51(Motor RPM). - M51 is only Monitoring of car speed, can not change actual car speed. 2.8 Signal explanation Inspection mode under installation Input/ Output
Ready-To -Run Status
After High speed I/O
Running
Explanation
Status
Mnemonic
Inspection Not Running
Up Run
Automatic Not Running
Up Run
ON=Green , OFF=Grey BRKC
OFF
ON
B/K open command
BRKC
Grey
Green
Grey
Green
BRKCD
ON
OFF
BRKC RY B contact(NC)
BRKCD
Green
Grey
Green
Grey
BRKD
ON
OFF
BRK RY B contact(NC)
BRKD
Green
Grey
Green
Grey
BRKE
OFF
ON
BRK RY A contact(NO)
BRKE
Green
Grey
Green
Grey
BSLE
OFF
ON
Brake A contact(NO) (TK50M)
BSLE
Green
Green
Green
Green
BSLM
OFF
ON
Brake B contact(NC) (TK50M)
BSLM
Green
Green
Green
Green
CDCF
ON
ON
Car door(Front)
CDCF
Green
Green
Green
Green
CDCFM
OFF
OFF
Car door(Front) RY B contact(NC)
CDCFM
Grey
Grey
Grey
Grey
CST
OFF
ON
Safety line
CST
Green
Green
Green
Green
CSTO RY B contact(NC)
CSTOM
Green
Green
Green
Green
DLT
OFF
OFF
4 LS(Direction Limit Bottom)
DLT
Green
Green
Green
Green
DLB
OFF
OFF
3 LS(Direction Limit Top)
DLB
Green
Green
Green
Green
ThyssenKrupp Dongyang Elevator
-7-
Printed in KOREA January, 2007
MAINTENANCE
DRVE
ON
TK50G
ON
DRVE
Green
Green
Green
Green
DZ1 RY B contact(NC)
DZ1M
*
#
*
#
*
#
*
#
DZ2 RY B contact(NC)
DZ2M
*
#
*
#
*
#
*
#
EPNP
ON
ON
Emergency power signal
EPNP
Green
Green
Green
Green
HDIF
ON
ON
Hall Door(Front)
HDIF
Green
Green
Green
Green
HDIFM
OFF
OFF
HDIF RY B contact(NC)
HDIFM
Grey
Grey
Grey
Grey
HDIR
ON
ON
Hall Door (Rear)
HDIR
Green
Green
Green
Green
Green
Green
Green
Green
Hall Door (Rear) B contact(NC) HDIRM INCN
OFF
ON
M/R Ins
INCN
Green
Green
Grey
Grey
INCND
OFF
ON
M/R Ins DOWN
INCND
Green
Green
Grey
Grey
INCNM
OFF
ON
M/R Normal
INCNM
Green
Green
Grey
Grey
INCNU
OFF
ON
M/R Ins UP
INCNU
Green
Green
Grey
Grey
Car top Ins
INCT
Green
Green
Grey
Grey
Car top Ins DOWN
INCTD
Green
Green
Grey
Grey
Car top Normal
INCTM
Green
Green
Grey
Grey
Car top Ins UP
INCTU
Green
Green
Grey
Grey
INRB
ON
ON
INS RUN BUG
INRB
Grey
Green
Grey
Grey
INRBM
OFF
ON
INRB B contact(NC)
INRBM
Grey
Green
Grey
Grey
MCCD
ON
OFF
MCC RY B contact(NC)
MCCD
Grey
Grey
Grey
Grey
MCD
ON
OFF
MC1 B contact(NC)
MCD
Green
Grey
Green
Grey
NCE
OFF
ON
MC1 A contact
MCE
Grey
Green
Grey
Green
MCPD
ON
OFF
MCP B contact(NC)
MCPD
Green
Green
Green
Green
RGC1
ON
ON
R/G control signal
RGC1
Green
Green
Green
Green
RGC2
ON
ON
R/G control signal
RGC2
Green
Green
Green
Green
RGC1,2 RY B contact(NC)
RGM
Green
Green
Green
Green
RGOK
ON
ON
R/G Feedback Sigan
RGOK
Green
Green
Green
Green
SAF2
ON
ON
Safety + Door are okay
SAF2
Green
Green
Green
Green
SAF3
ON
ON
Safety + Door + CPIK
SAF3
Green
Green
Green
Green
SAF4
ON
ON
Safety+Door+CPIK+LSM(CPU program)
SAF4
Green
Green
Green
Green
SAFC
ON
ON
Software check signal(LSM)
SAFC
Green
Green
Green
Green
SAFCD
OFF
OFF
SAFC RY B contact(NC)
SAFCD
Grey
Grey
Grey
Grey
SAFE
ON
ON
Safety Line is okay
SAFE
Green
Green
Green
Green
ThyssenKrupp Dongyang Elevator
-8-
Printed in KOREA January, 2007
MAINTENANCE
TK50G
EPW
OFF
OFF
CDCR
ON
ON
Car door(Rear)
CDCRM
OFF
OFF
CDCR RY B contact(NC)
--- D, --- M(Monitoring) ⇒ NC contact
* : Off in Door Zone
--- E ⇒ NO contact
# : On out of Door Zone
Temporary Operation I/O Status as seen on IMS Car I/O screen using Positive Logic
2.9 Landing sensor (Landing s/w) operation check 1. Set M16 (Car inspection speed) = 50(15m/min) -> 15 fpm(4.5m/min). 2. Loaded balance load. 3. Door blocking (Door disconnection).(D 26 = 1) 4. Move the lift to middle floor level. 5. Check DZ1, DZ2 , LVU, LVD signal are ON.(Metered Logic) 6. Move the Car 25.4mm lower than Level and check LVU is ON and LVD is OFF. 7. Move the Car 25.4mm upper than Level and check LVD is ON and LVU is OFF. 8. Move the Car 150mm upper than Level and check DZ1 and DZ2 are OFF.
2.10 Position count check 1. In Motion Diagnostic, if car up direction, PULSE should be increase. 2. If Position Count is wrong with car moving, change CNL 3 – A(1 pin) and B(3 pin), A/(2 pin) and B/(4 pin) at IOC PCB.
2.11 Over balance ratio check 1. Set M 99. (105m/min above = 45%, 120m/min above = 48% ) 2. Set weight unit by lbs (Pound). (1 lbs = 0.45359kg,
ThyssenKrupp Dongyang Elevator
1 Kg = 2.2 lbs)
-9-
Printed in KOREA January, 2007
MAINTENANCE
TK50G
2.12 PCB(Printed Circuit Board) LED 1. IOC PCB LED and IOC/186C Fuse LED
Fuse
AC1B
F13
If no problem of AC220V to IOC PCB and F13 Fuse is okay.
101
F6
Provide voltage to Safety Circuit 101 and F6 Fuse is okay
P24
F2,F4
Provide voltage P24 to IOC PCB and Fuse F2,F4 are okay.
P24G
F1
Function and explanation
Provide voltage P24G to IOC PCB (CNHC1,CNHC2)
P5
Provide voltage P5 to IOC PCB
P5B
Provide PENC(DC5V, Gov. encoder power supply) to IOC PCB
INRB
DIPSW of INRB (INS RUN BUG) at IOC is ON condition F5
P12(DC12V) power supply
F8
P24 of CNL2 (M/R Ins/Auto switch)
F14
P24 of CNL3 (GOV PG)
F1(186C)
P12 power supply (CON11)
F2(186C)
P5 power supply (186C power supply)
ThyssenKrupp Dongyang Elevator
- 10 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
2. IOC PCB JUMPER Pin setting explanation Jumper HC1S
HC2S
CCS
LCS
DLS
GCS
NP
Position
Function and explanation
ON
HC1 CAN Channel Shield connect to CHASSIS
OFF
HC1 CAN Channel Shield disconnect from CHASSIS
ON
HC2 CAN Channel Shield connect to CHASSIS
OFF
HC2 CAN Channel Shield disconnect from CHASSIS
ON
CC CAN Channel Shield connect to CHASSIS
OFF
CC CAN Channel Shield disconnect from CHASSIS
ON
LC CAN Channel Shield connect to CHASSIS
OFF
LC CAN Channel Shield disconnect from CHASSIS
ON
DL CAN Channel Shield connect to CHASSIS
OFF
DL CAN Channel Shield disconnect from CHASSIS
ON
SDLC CAN Channel Shield connect to CHASSIS
OFF
SDLC CAN Channel Shield disconnect from CHASSIS
ON
If don’t have Emergency power operation - ON
OFF
If have Emergency power operation – OFF and connect this signal to CNL9-1 Pin
3. IOC PCB Switch and Connector Jumper explanation Jumper RUN/STOP DOB
(Door open Button)
123-123A (CNHV3) DZB-DZC (CNHV4)
Location RUN(Top)
Explanation Normal operation
STOP
Cut the Safety Circuit
Push
Door Open command
ON
Before ETSD Scan - Jumper
OFF
After ETSD Scan – No jumper, Can operation of ETSD
ON
No Rear(Back) Door - Jumper
OFF
Rear(Back) Door – No Jumper
ThyssenKrupp Dongyang Elevator
- 11 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
4. 186C PCB LED explanation
LED
Description
STAT
Microprocess or Status
Color LED State(1=on,0=off)
RED
110011001100_Repeat Software UP-Load required by Zed Modem 100010001000_Repeat Boot Block require update ed 1000000000_Repeated
EBAD
ETSD Bad
RED
EGOO ETSD Good GREEN D
WD
Watchdog (Monitoring GREEN device)
Status
RAM Job file lost
EBAD and EGOOD Flicker
ETSD is not set-up
EBAD - ON
Set-up but problem
EBAD and EGOOD Flicker
ETSD is not set-up
EGOOD - ON
Set-up good and no problem
ON
Program normal
OFF
Program abnormal
5. Brake Controller(BRC) LED Explanation
LED
Color
LED
Status
PWR
RED
ON
If AC220V supply to Brake Controller (BRC), PWR LED will be ON.
ON
Under output condition
OPER GREEN
ThyssenKrupp Dongyang Elevator
- 12 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
2.13 CPIK Hyper-terminal handling method 1. Select CPIK_Entry(CPIK-Hyper-terminal). 2. If no good communication with CPI, can’t open next step. The picture of telephone is lift up condition as picture 1, this means communication was started. 3. Push Enter Key or H Key, “Password :
” will be appeared as picture 1 then
input “NAT” then picture 2 will be appeared. Possible to no ask Password.
Picture 1
Picture 2
4. Foe example, if you want to change Control type parameter, input “P 8” Enter after “>” as picture 2 then picture 3 will be appeared.
Parameter A Present Parameter Picture 3
ThyssenKrupp Dongyang Elevator
- 13 -
Present Parameter al e
Printed in KOREA January, 2007
MAINTENANCE
TK50G
5. If you don’t know parameter range of P 8, Enter in A part of picture 3 and “R” Enter then picture 4 will be appeared.
B
Picture 4
6. When you change parameter, refer to B part data of picture 4 and input some data to A part of picture 3. 7. “H” Enter after “>” of picture 2, the following window will be appeared.
Explanation of Shorten key. ; ?, P, R, D, T, V, S, F, C, >, “R” Enter in the above window, picture 5 will be appeared. “R” Enter again at cursor location of picture 5 then picture 6 will be appeared.
← ←
Changed Parameter
C Picture 5
Cursor location
Picture 6
6. Picture 5 and 6 are parameter range of CPIK which are allowed to change parameter. 7. CPIK data of picture 5, 6 monitor, drag and copy and paste to MEMO program and save(Required information should mentioned together such as capacity, speed and so on), it can be use for back-up file data if any problem occurred. 8. C part symbol means is changed Parameter.
ThyssenKrupp Dongyang Elevator
- 15 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
9. How to save Parameter. If “S” Enter after “>” of picture 2,
Overwrite old parameters ? (Y/N) then “Y” input, Save completed will be appeared then changed Parameter will be saved.
If you are not save data, the lift was operated by changed parameter. But when main power are Off/On, changed parameter will be changed to original parameter.
2.14 CPIK Inverter Data check for Inspection operation P2 → MOTOR RPM P3 → MOTOR Revolution direction - U,V,W P4 → MOTOR PG Revolution direction P8 → Model selection - MODE 5 (TAC50K) P13 → Gear Ratio, TK50M (MRL) - "1" P14 → Sheave Diameter TK50M – Refer to MOTOR name plate P15 → Roping (1:1- 1, 2:1- 2 set) P40 → MOTOR TYPE P96 → MOTOR PG TYPE ; Data - "0" (1024). (TK50M - "2048")
ThyssenKrupp Dongyang Elevator
- 16 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
Gear ratio and Sheave diameter
TM
TW 63
Speed
Gear ratio (input value)
Sheave diameter
passenger
Remarks
45m/min
48:1(48.0)
510
P6 – P11
5.7Kw, 340V,1350rpm
60m/min
33:1(33.0)
510
P6 – P9
5.7Kw, 340V, 1250rpm
P10, P11
11Kw, 340V, 1250rpm
90m/min 105m/min 45m/min 60m/min TW 130
48:2(24.1)
42:1(42.0)
90m/min 105m/min
45:2(22.6)
P8 – P11
590
P8 – P11
11Kw, 340V, 1100rpm
640
11Kw, 340V, 1250rpm
540 640
45m/min
640
50:1(50.0)
720
90m/min
57:2(28.6)
640
105m/min
51:2(25.1)
640
120m/min
45:2(22.6)
640
ThyssenKrupp Dongyang Elevator
11Kw, 340V, 1350rpm
540
120m/min
60m/min
TW 160
510
- 17 -
P13,P15
16Kw, 340V, 1200rpm 16Kw, 340V, 1400rpm 16Kw, 340V, 1350rpm
P17,P20
11Kw, 340V, 1100rpm
P24
16Kw, 340V, 1100rpm
P17,P20,P24
16Kw, 340V, 1350rpm
P17
16Kw, 340V, 1250rpm
P20,P24
20.5Kw, 340V, 1250rpm
P17,P20
20.5Kw, 340V, 1350rpm
P24
27.5Kw, 325V, 1350rpm
P17
20.5Kw, 340V, 1350rpm
P20,P24
27.5Kw, 325V, 1350rpm
Printed in KOREA January, 2007
MAINTENANCE
TK50G
2.15 186C DATA check and input 1. Select IMS and enter. (Don’t connect 186C and laptop computer by 232 cable)
Picture 1
Picture 2
2. In Control Panel of IMS, select Network and click right button of Mouse. In Pull Down Manu, select Add a Net and click then you can get Net01.(picture 1,2) 3. Select Net01 and click right button of Mouse. In Pull Down Manu, select Add a Group and click then you can get Group01.(picture 2,3)
Picture 3
ThyssenKrupp Dongyang Elevator
Picture 4
- 18 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
1. Select Group01 and click right button of Mouse. In Pull Down Manu, select Add a Car and click then you can get Car01.(picture 3,4)
5. Select Net01 and change the name by project name and connect RS232 cable. 6. After connecting to 186C, you can get A of picture 5. :
Red
Electric
Plug=On
Line
communication A
Lighted
Bulb=Download
is
success
and
communication is okay between IMS and Controller.
Picture 5
7. Refer to picture 6 and check the following data by Remote FAST.
Picture 6
DATA input
ThyssenKrupp Dongyang Elevator
- 19 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
186C parameter check CEF = 111111111111 (12pcs) (Auto Announcer) D12 = 7 D24 = Handicap lift →100, Passenger lift →50 (DOOR OPEN TIME when HALL CALL generation, 100=10SEC) D25 = Handicap lift →100, Passenger lift →50 (DOOR OPEN TIME when CAR CALL generation, 100=10SEC) D26 = Before High speed operation 1, After High speed operation 0 D27 = 0 D35 = 100 F16 = Option of Fire-man lift (Passenger lift 0, Emergency lift 15) H10 = Parking floor setting, Lowest floor = 01 H16 = Door open time after landing at Parking floor = 70 J10 = Passenger capacity (15 persons 1000*2.2 = 2200) J11 = Lift Index, Lift No. 1 = 1, Lift No. 2 = 2 J15 = The total numbers of stopping floor M16 = 53 → Inspection speed (53 = 15~16m/min) M30=Rating speed (45m/min→147,60m/min→197,90m/min→295,105m/min→344, 120m/min→393,150m/min→492) M31 = 5~6 M32 = 50 → Hunting speed M35 = 100 M50 = TK50G (Geared Lift) ; 1024, TK50M (MRL) ; 2048 M51 = MOTOR RPM (Table 1, Table 2 Reference) In case of TK50M(MRL), change this data in Diagnostics of IMS to make same CAR Speed and Dmd(Damand) speed.
ThyssenKrupp Dongyang Elevator
- 20 -
Printed in KOREA January, 2007
MAINTENANCE
45m/min ( 0.75m/s )
TK50G
60m/min ( 1.0m/s )
90m/min ( 1.5m/s )
105m/min ( 1.75m/s )
120m/min ( 2.0m/s )
150m/min ( 2.5m/s )
TW63 (Φ12*3) TW63 (Φ12*3) CPIK 15 CPIK 15 P6 5.7kW340V 5.7kW340V (450kg) 1350rpm 1250rpm Φ51048:1 Φ51033:1 TW63 (Φ12*3) TW63 (Φ12*3 ) TW63 (Φ12*4 ) TW63 (Φ12*4 ) CPIK 15 CPIK 15 CPIK 15 CPIK 15 P8 5.7kW340V 5.7kW340V 7.5kW340V 9.5kW340V (550kg) 1350rpm 1250rpm 1350rpm 1350rpm Φ51048:1 Φ51033:1 Φ51048:2 Φ59048:2 TW63 (Φ12*3 ) TW63 (Φ12*3 ) TW63 (Φ12*4 ) TW63 (Φ12*4 ) CPIK 15 CPIK 15 CPIK 15 CPIK 15 P9 5.7kW340V 5.7kW340V 7.5kW340V 9.5kW340V (600kg) 1350rpm 1250rpm 1350rpm 1350rpm Φ51048:1 Φ51033:1 Φ51048:2 Φ59048:2 TW63 (Φ12*4 ) TW63 (Φ12*4 ) TW63 (Φ12*4 ) TW63 (Φ12*4 ) CPIK 15 CPIK 15 CPIK 15 CPIK 32 P10 5.7kW340V 7.5kW340V 9.5kW340V 11kW340V (680kg) 1350rpm 1250rpm 1350rpm 1350rpm Φ51048:1 Φ51033:1 Φ51048:2 Φ59048:2 TW63 (Φ12*4 ) TW63 (Φ12*4 ) TW63 (Φ12*4 ) TW63 (Φ12*4 ) CPIK 15 CPIK 15 CPIK 15 CPIK 32 P11 5.7kW340V 7.5kW340V 9.5kW340V 11kW340V (750kg) 1350rpm 1250rpm 1350rpm 1350rpm Φ51048:1 Φ51033:1 Φ51048:2 Φ59048:2 TW130 TW63 (Φ12*5 ) TW63 (Φ12*5 ) TW130 (Φ12*5 ) TW130 (Φ12*5 ) (Φ12*7 )CPIK CPIK 15 CPIK 15 CPIK 32 CPIK 32 P13 48 7.5kW340V 9.5kW340V 11kW340V 13kW340V (900kg) 16kW340V 1350rpm 1250rpm 1200rpm 1400rpm 1350rpm Φ51048:1 Φ51033:1 Φ54045:2 Φ54045:2 Φ64045:2
TW160 (Φ14*6 ) CPIK 48 18.5kW340V 1350rpm Φ80045:2
TW130 TW63 (Φ12*5 ) TW63 (Φ12*5 ) TW130 (Φ12*5 ) TW130 (Φ12*5 ) (Φ12*7 )CPIK CPIK 15 CPIK 15 CPIK 32 CPIK 48 48 P15 7.5kW340V 9.5kW340V 13kW340V 16kW340V 16kW340V (1000kg) 1350rpm 1250rpm 1200rpm 1400rpm 1350rpm Φ51048:1 Φ51033:1 Φ54045:2 Φ54045:2 Φ64045:2
TW160 (Φ14*6 ) CPIK 60 20.5kW340V 1350rpm Φ80045:2
ThyssenKrupp Dongyang Elevator
- 21 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
45m/min ( 0.75m/s )
60m/min ( 1.0m/s )
90m/min ( 1.5m/s )
105m/min ( 1.75m/s )
120m/min ( 2.0m/s )
150m/min ( 2.5m/s )
TW130 (Φ12*6 ) CPIK 15 9.5kW340V 1125rpm Φ54042:1 TW130 (Φ12*7 )CPI K 32 9.5kW340V 1125rpm Φ54042:1
TW130 (Φ12*6 ) CPIK 32 11kW340V 1250rpm Φ64042:1 TW130 (Φ12*7 )CPIK 32 13kW340V 1250rpm Φ64042:1
TW130 (Φ12*6 ) CPIK 48 16kW340V 1200rpm Φ54045:2 TW130 (Φ12*7 ) CPIK 48 18.5kW340V 1200rpm Φ54045:2
TW130 (Φ12*6 ) CPIK 48 16kW340V 1400rpm Φ54045:2 TW130 (Φ12*7 ) CPIK 48 18.5kW340V 1400rpm Φ54045:2
TW130 (Φ12*7 ) CPIK 48 18.5kW340V 1350rpm Φ64045:2 TW160 (Φ14*6 )CPIK 60 20.5kW340V 1350rpm Φ64045:2
P24 (1600kg)
TW160 (Φ14*6 ) CPIK 32 13kW340V 1125rpm Φ64050:1
TW160 (Φ14*6 ) CPIK 48 16kW340V 1350rpm Φ72050:1
TW160 (Φ14*6 ) CPIK 48 20.5kW340V 1250rpm Φ64057:2
TW160 (Φ14*6 ) CPIK 60 22kW340V 1350rpm Φ64051:2
TW160 (Φ14*7 ) CPIK 60 27.5kW340V 1350rpm Φ64045:2
TW160 (Φ14*6) CPIK 60 22kW340V 1350rpm Φ80045:2 TW160 (Φ14*7 ) CPIK 60 27.5kW340V 1350rpm Φ80045:2 TM90D (Φ16*6 ) CPIK 105 30kW340V 1450rpm Φ80073:3 [148.1A]
P27 (1800kg)
TW160 (Φ14*7 ) CPIK 48 13kW340V 1125rpm Φ64050:1
P30 (2000kg)
TW160 (Φ14*7 ) CPIK 48 16kW340V 1125rpm Φ64050:1
TM90D (Φ16*6 ) CPIK 60 19kW340V 1450rpm Φ75056:1 [99.9A] TM90D (Φ16*6 ) CPIK 60 22kW340V 1450rpm Φ75056:1 [106.3A]
TM90D (Φ16*6 ) CPIK 105 30kW340V 1450rpm Φ75077:2 [114.7A] TM90D (Φ16*6 ) CPIK 105 30kW340V 1450rpm Φ75077:2 [122.9A]
TM90D (Φ16*6 ) CPIK 105 30kW340V 1450rpm Φ75065:2 [128.5A] TM90D (Φ16*6 ) CPIK 105 30kW340V 1450rpm Φ75065:2 [138.0A]
P17 (1150kg)
P20 (1350kg)
Table 1 Geared TM for Passenger E/L (1:1)
ThyssenKrupp Dongyang Elevator
- 22 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
45m/min (0.75)
60m/min (1.0)
90m/min (1.5)
105m/min (1.75)
P6 (450kg)
TW63 (Φ12*3) TW63 (Φ12*3) 5.7kW340V1350rpm 5.7kW340V1250rpm CPIK 15 CPIK 15 Φ51048:1 Φ51033:1
P8 (550kg)
TW63 (Φ12*4) TW63 (Φ12*4) TW63 (Φ12*4) TW63 (Φ12*4) 5.7kW340V1350rpm 5.7kW340V1250rpm 7.5kW340V1350rpm 9.5kW340V CPIK 15 CPIK 15 CPIK 15 1350rpmCPIK 15 Φ51048:1 Φ51033:1 Φ51048:2 Φ59048:2
P9 (600kg)
TW63 (Φ12*4) TW63 (Φ12*4) TW63 (Φ12*4) TW63 (Φ12*4) 5.7kW340V1350rpm 5.7kW340V1250rpm 7.5kW340V1350rpm 9.5kW340V CPIK 15 CPIK 15 CPIK 15 1350rpmCPIK 15 Φ51048:1 Φ51033:1 Φ51048:2 Φ59048:2
P10 (680kg)
TW63 (Φ12*5) TW63 (Φ12*5) TW63 (Φ12*5) TW63 (Φ12*5) 5.7kW340V1350rpm 7.5kW340V 9.5kW340V1350rpm 11kW340V CPIK 15 1250rpmCPIK 15 CPIK 15 1350rpmCPIK 32 Φ51048:1 Φ51033:1 Φ51048:2 Φ59048:2
P11 (750kg)
TW63 (Φ12*5) TW63 (Φ12*5) TW63 (Φ12*5) TW63 (Φ12*5) 5.7kW340V1350rpm 7.5kW340V 9.5kW340V1350rpm 11kW340V CPIK 15 1250rpmCPIK 15 CPIK 15 1350rpmCPIK 32 Φ51048:1 Φ51033:1 Φ51048:2 Φ59048:2
120m/min (2.0)
P13 (900kg)
TW130 (Φ12*6) 7.5kW340V 1125rpmCPIK 15 Φ54042:1
TW130 (Φ12*6) TW130 (Φ12*6) TW130 (Φ12*6) TW130 (Φ12*7) 9.5kW340V 13kW340V1200rpm 13kW340V1400rpm 16kW340V 1250rpmCPIK 32 CPIK 32 CPIK 48 1350rpmCPIK 48 Φ64042:1 Φ54045:2 Φ54045:2 Φ64045:2
P15 (1000kg)
TW130 (Φ12*6) 7.5kW340V 1125rpmCPIK 15 Φ54042:1
TW130 (Φ12*6) TW130 (Φ12*7) TW130 (Φ12*6) TW130 (Φ12*6) 16kW340V 9.5kW340V 13kW340V1200rpm 16kW340V1400rpm 1350rpmCPIK 48 1250rpmCPIK 32 CPIK 32 CPIK 48 Φ64045:2 Φ64042:1 Φ54045:2 Φ54045:2
P17 (1150kg)
TW160 (Φ14*6) 9.5kW340V 1125rpmCPIK 32 Φ64050:1
TW160 (Φ14*6) 11kW340V 1350rpmCPIK 48 Φ72050:1
TW160 (Φ14*6) 16kW340V 1250rpmCPIK 48 Φ64057:2
TW160 (Φ14*6) 18.5kW340V 1350rpmCPIK 48 Φ64051:2
TW160 (Φ14*6) 18.5kW340V 1350rpmCPIK 48 Φ64045:2
P20 (1350kg)
TW160 (Φ14*6) 11kW340V 1125rpmCPIK 32 Φ64050:1
TW160 (Φ14*6) 13kW340V 1350rpmCPIK 48 Φ72050:1
TW160 (Φ14*7) 18.5kW340V 1250rpmCPIK 48 Φ64057:2
TW160 (Φ14*7) 20.5kW340V 1350rpmCPIK 60 Φ64051:2
TW160 (Φ14*7) 22kW340V 1350rpmCPIK 60 Φ64045:2
P24 (1600kg)
TW160 (Φ14*7) 13kW340V 1125rpmCPIK 32 Φ64050:1
TW160 (Φ14*7) 16kW340V 1350rpmCPIK 48 Φ72050:1
TW160 (Φ14*7) 20.5kW340V 1250rpmCPIK 48 Φ64057:2
TW160 (Φ14*7) 27.5kW340V 1350rpmCPIK 60 Φ64051:2
TW160 (Φ14*7) 27.5kW340V 1350rpmCPIK 60 Φ64045:2
Table 2 Geared TM for Observation E/L (1:1)
ThyssenKrupp Dongyang Elevator
- 23 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
30m/min ( 0.5m/sec )
45m/min ( 0.75m/sec )
60m/min ( 1.0m/sec )
TW130 (Φ12*5) 9.5kW340V 1250rpmCPIK 32 Φ64042:1 TW130 (Φ12*6) 11kW340V 1250rpmCPIK 32 Φ64042:1 TW160 (Φ12*6) 13kW340V 1350rpmCPIK 48 Φ72050:1 TW160 (Φ14*6) 16kW340V 1350rpmCPIK 48 Φ72050:1 TM90D (Φ14*6) 19kW340V 1450rpmCPIK 60 Φ75056:1 TM90D (Φ16*6) 22kW340V 1450rpmCPIK 60 Φ75056:1
TW130 (Φ12*5) 7.5kW340V 1125rpmCPIK 15 Φ54042:1 TW130 (Φ12*6) 7.5kW340V 1125rpmCPIK 15 Φ54042:1 TW130 (Φ12*5) 11kW340V 1200rpmCPIK 32 Φ54045:2 TW130 (Φ12*6) 16kW340V 1200rpmCPIK 48 Φ54045:2 TW160 (Φ12*6) 18.5kW340V 1250rpmCPIK 48 Φ64057:2 TW160 (Φ14*6) 22kW340V 1250rpmCPIK 60 Φ64057:2 TM90D (Φ14*6) 30kW340V 1450rpmCPIK 105 Φ75077:2 TM90D (Φ16*6) 30kW340V 1450rpmCPIK 105 Φ75077:2
TW130 (Φ12*5) 7.5kW340V 1250rpmCPIK 15 Φ64042:1 TW130 (Φ12*6) 9.5kW340V 1250rpmCPIK 32 Φ64042:1 TW130 (Φ12*5) 16kW340V 1350rpmCPIK 48 Φ64045:2 TW130 (Φ12*6) 18.5kW340V 1350rpmCPIK 48 Φ64045:2 TW160 (Φ12*6) 22kW340V 1350rpmCPIK 60 Φ64045:2 TW160 (Φ14*6) 27.5kW340V 1350rpmCPIK 60 Φ64045:2
750 kg (1:1 roping) 1000 kg (1:1 roping)
1500 kg
2000 kg
2500 kg
3000 kg
3500 kg
4000 kg
30m/min (3:1 or 4:1 roping)
TW160 (Φ14*6)3:1 22kW340V 1250rpmCPIK 60 Φ64057:2 TW160 (Φ14*6)4:1 27.5kW340V 1350rpmCPIK 105 Φ64045:2 TW160 (Φ14*6)4:1 27.5kW340V 1350rpmCPIK 105 Φ64045:2
4500 kg
5000 kg
6000 kg
Table 3 Geared TM for Freight E/L (2:1)
ThyssenKrupp Dongyang Elevator
- 24 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
M52=Rating speed(45m/min→147,60m/min→197,90m/min→295,105m/min→344, 120m/min→393,150m/min→492) M60 = Under ins operation (Not connection Gov. encoder) 0 or 25, High speed operation 255 M61 = Under inspection operation 100 (Not connection Gov. encoder), High speed operation 50
M92 = 250 weight, pound (Anti-nuisance call) M94 = 100 (Overload) M99 = 45 (Over Balance) O10 = 3 (Anti-nuisance call number) O25 = 0 (DOOR short) O26 = 1 (DOOR short) O35 = 180 (18 sec) (LIGHT,FAN OFF time without CALL) O43 = 11 X11 = 2 X22 = 0 Z21 = 16 HALL Position Indicator LAMP1
Independent: 4
Z22 = 4 HALL Position Indicator LAMP2
Inspection: 41(32+8+1)
Z23 = 1
Fire-man: 16
Z24 = 41 HALL Position Indicator LAMP3
27
26=2x2x2x2x2x2
25
24
23
22
21
20
128
64
32
16
8
4
2
1
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
Auto
Full(80%) Inspection
Fire- FD(Fault Independent Overload Parking man Detection)
After changing any data, doing WRT enter until displaying Write complete, WRT enter interval is 4~5 sec.
ThyssenKrupp Dongyang Elevator
- 25 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
3. Inspection operation -. After wiring and data input as above, please check the hoist-way condition. Try UP/DN and can’t move the lift by inspection mode, check the following point. - Power supply is okay ? - 186C PCB is working normally ? (WD LAMP ON?) - Wiring is okay ? - CPIK and 186C Data are correct ? - If not correct UP/DN direction, please change P3 of CPIK. (0->1, 1->0) 4. Preparation work of High speed operation 4.1 CAR DUCT Wiring 1. Gov. link S/W : 112 - 113 2. Exit door S/W : 113 - 114 3. Car top STOP S/W : 116 -117 4. COP STOP S/W : 117A - 118 5. CAR DOOR S/W : 201 - 202 6. DLS(Safety Edge) S/W : SE(Safety Edge) G24(Grounding) 7. LDS S/W : EE(Electric Eye:Photo-cell, Micro Scan, Pana-40, Mini-max)
- G24
8. 1WLS : LWO(Overload – 100%) 9. 3WLS : LWB(Balance Load – 45%) 10. 8WLS : LWA(Anti-Nuisance call – 150kg) 11. NC2 = G24
ThyssenKrupp Dongyang Elevator
- 26 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
4.2 CN wiring
CWIK PCB wiring CNT(Traveling cable)1 : Safety line CNT2 : Power and LANDING S/W CNT8 : Car communication input CN2 : Car communication output CND(Duct)1 : Safety line CND2 : Light and FAN CND3 : Car communication and power CND401 : LANDING S/W Passenger lift : CN1-4(CSTOM) Ù G24 jumper CN PCB Wiring CN1, CN5 : Normal and handicap button CN3, CN7 : Normal and handicap button lamp CN9 : COP S/W INPUT CN17 : COP S/W I/O PORT ETC CN23 : Interphone, BGM CNT3 : Light and power BGM2,BGM4,1,2 : TB terminal 3 TB terminal G24 and CWIK CN1-4
4.3 DOOR Controller(DCU-2A) Wiring
CN1: DOOR C/P communication line CN2: DLS,LDS,P24,G24 CN3: DOOR MOTOR U,V,W 3 phase CN4: DOOR MOTOR Pulse Generator CN5: 18DS(Door open limit sensor),23DS(Door close limit sensor) CN6: DOOR C/P power(AC220V)
ThyssenKrupp Dongyang Elevator
- 27 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
4.4 Hoist-way Wiring (Limit S/W)
SDB(Slow down
2LS DLT(4LS)
Car speed
1,2LS Final limit s/w (NC)
DLB,DLT Direction limit s/w (NC)
down top) (Slow down limit s/w) (NO)
SDT(6LS)
SDB(5LS)
bottom),SDT(slow
30m/min
- 200
- 30
+ 130
45m/min
- 200
- 30
+ 320
60m/min
- 200
- 30
+ 550mm
90m/min
- 200
- 30
+ 1000
105m/min
- 200
- 30
+ 1300
DLB(3LS) 1LS
ThyssenKrupp Dongyang Elevator
120m/min - 200
- 30
ESTD Van
150m/min - 200
- 30
ESTD Van
- 28 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
5. High speed operation 5.1 DATA input Input data when INS operation, change some required data of High speed operation. 5.2 CAR communication check
Picture 1
CN Teach-In operation TECCR ENTER, TECC ENTER => Car CN board Teach-In operation command. Car CN communication check DCN ENTER then in Remote Fast, you can see Main COP --- 1 (Normal) in picture 2, if it is 0 – No good communication. If Car CN communication is okay, CSTOM must Green color, CAR top auto – INCTM(INs Car Top Monitoring)Green and Car top INS – INCT Green in Picture 1.
Picture 2
CN PCB identify method TP Passenger CN-1A 08 ~16 stop CN-2A 12 ~32 stop CN-3A 16 ~48 stop
Handicap ~8 stop ~16 stop ~24 stop
DCNAT^0^16 enter -> WRT -> Power reset -> TECCR, TECC
ThyssenKrupp Dongyang Elevator
- 29 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
5.3 Hoist-way Hall HN(Hall Node) communication HN Teach-In Command TECCR ENTER, TECF(Teach-In Front, TECR;Teach-In Rear)ENTER, TECC ENTER in Remote fast for checking Hoist-way Hall HN communication. AS pictures 3, “Teach-In failed at HN4 check All Connections” will display, this means HN can’t communication from lowest floor to 4 floors. Ex) Building has 18stop, if display “Teach In failed at HN16, check All Connections”, this means that 17~18 floor - Communication okay 1~16 floor - Communication no good. If all floors(18stop) are no problem, Picture 3
Teach In Complete_found 18HN’s should displayed. DHNF ENTER in Remote Fast, if display ON column to 1, this means no problem of HN communication. If display ON column to 0, this means HN communication has problem. Ex) ON 0 – 1 floor ; communication problem 1 – 2 floor ; communication no problem 1 – 3 floor 1 – 4 floor 1 – 5 floor 1 – 6 floor HN PCB version – V28 When power ON/OFF, HN PCB LED will display V01 – Version12 V02 – Version24 V03 – Version28
그림 4
ThyssenKrupp Dongyang Elevator
End terminal resistor – Resistor jumper at lowest floor. Resistor spec - 120 ohm
- 30 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
5.4 Hoist-way Scan After finish CN and HN Teach In, please doing Hoist-way Scan(Pulse Date-SET) operation as follow. 1. D26(Door Disconnection)=0->1 2. Select
icon of Custom toolbar in IMS or select Service → Hoist-way Setup→
Hoist-way Scan. 3. Hoist-way Scan window will be displayed. 4. Click Run Setup -> Turn to Auto at INS/Auto S/W at C/P. 5. Click YES. 6. The lift will be moved to lowest floor and moved to top floor automatically. 7. The lift will be re-level automatically. 8. Finished Hoist-way Scan(PDSET) successfully.
When the lift touch DLB (Down Limit Bottom limit) limit s/w, it will be changed NO ->PASS. When the lift re-level, it will be changed NO ->PASS. When DLT has on -> off, it will be changed NO ->PASS.
ThyssenKrupp Dongyang Elevator
- 31 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
5.5 DOWN LOAD After finish Hoist-way scan operation and all commissioning works, you have to download Job file(Specific files) as follows.
A
- Select Car01 in Control panel. - Click
icon of Custom toolbar in IMS or select Service → Transfer.
- The above window will be displayed and click Start then Download will be started. - If finished Download, Download Complete will be displayed in the above picture "A" part. - Finished save. - File saved destination is My computer → Local disk C → Program Files → Thyssen → IMS → Project name. - You can see _050000.11 then copy this file and paste and rename to _058000.11 - Delete others files (2 pcs).
ThyssenKrupp Dongyang Elevator
- 32 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
5.6 DATA UP LOAD
- Click 186C Hyper-terminal. - Click Transfer. - Click Send then the above picture will be displayed. - Find files(Generic files or Specific files) which you want to upload and click open. - Click send. (Can’t select 2 files at same time, therefore change file name “*.11” to send 2 files at same time) - Push UDL first and then push RST at 186C PCB. - Release RST button. - If display Transfer as below picture, release UDL button.
- Waiting 186C re-booting and WD LED ON.
ThyssenKrupp Dongyang Elevator
- 33 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
6. TK50M Wiring and Inspection & High speed operation 6.1 Wiring Temporary Remote control
Gov. PG ; CNL 3
IOC-3A PCB 1,2
1,2,3,4,7/6,8
Picture 10
- Gov. PG connect to CNL3 connector as above picture 10. (No required connect it when inspection operation) - CNHV3 connector pin No. 1 and 2 (123A, 123) jumper when inspection operation. - CNHV4 connector pin No. 1, 2, 3, 4, 7 Jumper when inspection operation. (CDCF,HDIF,DLT,DLB,AC1B), pin No. 6, 8 Jumper(If no Back Door) - Temporary remote control cable connect to pin No. 1(Common), 3 (UP), 4 (Down). CHRT
R20 & T20 - AC220V L1
L2
L3
L12
L22 L32
U U1
PE
PE
N
N
R20 T20
Picture 11
ThyssenKrupp Dongyang Elevator
- 34 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
- CHRT Wiring (Picture 11) Hoist-way light : WL1, WL4
GOV21, GOV22 Jumper : Battery operation
BM3, BM4 Jump : Brake release
Governor machine TRIP coil : V203, TRP
Governor machine RESET coil :V203, RST
Governor S/W : 109, 110
Hoist-way Top Stop S/W : MS, DESTOP
Hoist-way TOP consent : WL1, WL4
L1.L2.L3 : Main power supply from building side L12,L22,L32 : Connect it to L12,L22,L32 of CPIK U, U1 : Ampere measuring when Government inspection PE : EARTH from building side / PE : Connect it to PE of CPIK N : N phase from building side N : Connect it to T20 (5.5SQ above) R20 : Connect it to L1 (5.5SQ above) T20 : Connect it to N (5.5SQ above)
- Please jumper below signal for Inspection operation, refer to picture 11. MS, DESTOP, CESTOP Jumper 101, 113, 120, 121, 202, 215 Jumper
U,V,W of Picture 12 connect to U,V,W of CPIK. 1,2(Motor thermal) connect to 17, 18 of CPIK. (Refer to electrical diagram 18 page) 1,2
U, V, W, E
Picture 12
ThyssenKrupp Dongyang Elevator
- 35 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
1) L12,L22,L32 : connect it to L12,L22,L32 of C/P. 2) U,U1 : Ampere measuring when Government inspection. 3) U,V,W : Connect it to U,V,W of MOTOR.
L12,L22,L32,U,U1,U,V,W
CLW(Car Load Weigher) PCB
③
Gov. link S/W : 111, 113 Car Door S/W : 121, 202 Safety S/W : G24, SE Photo cell : G24, EE(Normal Close contact) Micro scan : G24, EE Machine fix device : 113, 114 (Connect it by serial connection) Safety fence S/W : 117, 118A (ON contact when not use it – lift down) Safety fence S/W : 118B, 119 (ON contact when use it – lift up) Exit S/W : 115, 116 ⓛ : Car communication line ② : Potential-meter connection Red 1, White 2, Black 3 ③ : Leveling Sensor (Landing S/W)
①
②
Car Duct front side
ThyssenKrupp Dongyang Elevator
- 36 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DCU-2A CN1 : Communication line CN2 : LDS, DLS
CN1
CN3 : DOOR MOTR U,V,W
CN6
CN2
CN4 : DOOR MOTOR PG
CN5
CN5 : 18DS(Door open limit sensor),
CN4
CN3
23DS(Door close limit sensor)
SENSOR CN6 : DOOR C/P power AC220V
Door PCB ; DCU-2A
6.2 Inspection operation Almost same as TK50G model and some data of CPIK and 186C are difference. (Reference to CPIK, 186C inspection DATA of TK50G) 6.3 High speed operation Almost same as TK50G model and some data of CPIK and 186C are difference. (Reference to CPIK, 186C inspection DATA of TK50G) - Balance load check Connect laptop computer to X908 of CPIK and open CPIK hyper-terminal. P107 – Monitoring of actual Ampere, move the Car by Up/down and check the Ampere by P107 when car reach middle floor, this Ampere should be same both up and down direction at middle floor. If not same, add or remove counterweight from counterweight frame. P107 can be check by PEP(Parameter Entry Panel). 6.4 Load compensation - Make No load. - Adjust potential-meter to make ≒3.5VDC between G24(-) and VO(+) check pin by Volt-meter at CLW-1A PCB of Car Duct. - Make auto mode and set D26=1. - Move the Car to lowest floor and DLW Enter in Remote Fast of IMS then you can get below window.
ThyssenKrupp Dongyang Elevator
- 37 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
- Check Avg=58~68 (A part, this data can be difference per job site) - Locate CAR to lowest floor and NLD(No Load) Enter in REMOTE FAST of IMS to input lowest floor NO load status. (B part) A
- Locate CAR to TOP floor and NLD Enter in REMOTE FAST of IMS to input top floor NO load status. (C part) B
- Locate CAR to lowest floor and DLW Enter in REMOTE FAST of IMS and check Loo value is
C
63±2. (D part, this data can be difference per job site) - Locate CAR to lowest floor and make FULL LOAD(100% load). - Locate CAR to lowest floor and FLD(Full Load) Enter in REMOTE FAST of IMS to input lowest D
floor full load status. (E part)
E
ThyssenKrupp Dongyang Elevator
- 38 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
- Locate CAR to lowest floor and DLW Enter in REMOTE FAST of IMS and check PreTorque Enable (F part) -. P50(CPIK) : Load Data Setting -. P54 : Load Gain Setting
F
-. Roll-back adjustment method (CPI PEP Parameter)
Address
Meaning
Value
P50
Load Weighting option
ON/OFF
P51
Measured Value Of Load Weight
0
%
P52
Input Value Load Compensation
+50
%
P53
Load-Weighting Gain Of Load Current
0.0
A
-80
%
P54
Gain Of Load Weight
unit
Adjustment range Load mode Present car load display Balance ratio Roll-back adjustment (Auto) Roll-back adjustment (Auto)
P53 Setting method 1. P50(load Weighting) – Off (0). 2. Move to P53 by PEP and push “Param/Wert” button. 3. When No Load (0%) Top floor, move lift by INS Down and when Ampere is stable, push (+) button of PEP (Parameter Entry Panel).
ThyssenKrupp Dongyang Elevator
- 39 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
4. Reading the value of P53 will be saved to P54 automatically. P53 will be change 0.001A again. 5. Push “Param/Wert” button and move P54. 4. Checking value of P54 and push “Sichern (Enter key)” button to save. Try move the lift by INS down, check Roll-back and if happen to Roll-back problem, increase or decrease parameter of P54 to remove Roll-back problem. 5. Change P50(Load Weighting) to ON(Data =1) and move NOR operation and check Roll-back. 6.5 Adjusting method of Encoder Rotor(Motor Encoder) Position(Off-Set) 1. When Balance Load, move the lift to middle floor. When open brake, the lift should not move. 2. Turn to inspection s/w to INS. 3. Check the P96(=2048) Encoder specification. 4. Change P86 from Normal Operation → Align Rotor. (Cursor located P86, Ready signal will be OFF → ON) 5. Push up or down button during 1~2sec, the motor happen to noise to move and stop automatically. 6. P86 will be change from Align Rotor → Store Reference Position → Normal Operation and “Ready” LED of TMI PCB at CPI-K will be OFF and ON automatically. (Cursor located P86) 7. Check P86 parameter to 0(Rotor Position Store in Encoder), “Error-Stack” message change to “Rotor Position Store in Encoder”. 8. Power reset (Off and On). 9. If required Hoist-way Scan, do it again. - Geared lift 1. Applied Load S/W (1 WLS – Overload 100%, 3 WLS – Full load 80% ,8 WLS – Anti-nuisance call 150kg) Load compensation value “0” – 8 WLS OFF, 3 WLS OFF Load compensation value “50” – 8 WLS ON, 3 WLS off Load compensation value “100” – 8 WLS ON, 3 WLS ON 2. Data check 186C – M91=0, M98=1 CPI-K – P50=ON, P54=Gain adjustment (Increase or decrease) for roll-back problem.
ThyssenKrupp Dongyang Elevator
- 40 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
12. CPIK / 186C Hyper-Terminal installation method
12.1 Starting In window, click START and find "Hyper-terminal”. All program Accessories Communication
Hyper-terminal
(1) The following window will be appeared and make program name “CPIK_EnteryPanel” as follow.
186C-Hyper
Confirm
Cancel
(2) Click the CONFIRM button. (2) Select COM Port. In Windows, find Control Panel → System → Hardware → Device manager → Port(COM and LPT) and check communication port, select used modem(N). (Ex : COM1 or COM2).
ThyssenKrupp Dongyang Elevator
- 41 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
Confirm
Cancel
(3) Click the Confirm button. (4) Select the each value of “CPIK_EntryPanel” and “186C upload”.
9600
38400
None
None
None
Hardware
CPIK_EntryPanel
ThyssenKrupp Dongyang Elevator
186C upload
- 42 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
13. How to set “Add Or Change An I/O” Manu of IMS I/O MAP. (1) Select START and RUN, type “regedit” and click confirm button. (2) Please find HKEY_CURRENT_USER Software Thyssen Dover IMS Settings
(3) Click “Setting” and then the following window will be appeared.
ThyssenKrupp Dongyang Elevator
- 43 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
(4) Click “AddIO” and then the following window will be appeared.
Value data (V) :
Confirm
(5) “Value data(V):” change “0” to “1” and click confirm button. (6) Check whether “Add Or Change An I/O” Menu was created or not.
ThyssenKrupp Dongyang Elevator
- 44 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
8. Car Adjustments Table NOTE : Utilize Car Remote Fast / Smart Fast for the following adjustments ADJ
FAST
DESCRIPTION
REMOTE
SMART
×(Enable)
Disable
ASI
Add Special Inversion
B10
Coded Car Call Entry Code Digit 0
×
×
B11
Code Digit 1
×
×
B12
Code Digit 2
×
×
B13
Code Digit 3
×
×
B14
Code Digit 4
×
×
B15
Code Digit 5
×
×
B16
Code Digit 6
×
×
B17
Code Digit 7
×
×
B18
Code Digit 8
×
×
B19
Code Digit 9
×
×
B20
Coded Car Call Code Entry Time
×
×
B21
Coded Car Call Code Entry Count
×
×
B22
Coded Car Call Entry Sound Buzzer on Entry
×
×
B23
Coded Car Call Acknowledge Time
×
×
BCW
Store the position count
×
BYE
Logically disconnect IMS Monitoring
×
BKP
Nonvolatile memory BacK uP
×
CAN
Display CAN errors
×
CAT
Category
×
CEF
Enable/disable voice messages
×
CNN
Display CAN errors
×
Clear CAN errors
×
D10
Limited Door Reversal Type
×
×
D11
Nudging Enable
×
×
CNNC
ThyssenKrupp Dongyang Elevator
- 45 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
SMART
D12
Front Door Type
×
×
D13
Rear Door Type
×
×
D14
Safety Edge Door Time
×
×
D15
Electric Eye Door Time
×
×
D16
Door Open Button Door Time
×
×
D17
Door Hold Button Door Time
×
×
D18
Open High Speed time
×
×
D19
Nudging Door Time
×
×
D20
Door Reversal time (optional)
×
×
D21
Front Door Watchdog time
×
×
D22
Rear Door Watchdog time
×
×
D23
ADA Hall Call Door Time
×
×
D24
Car Call Door Time
×
×
D25
Hall Call Door Time
×
×
D26
Door Disconnect
×
×
D27
ADA Actuator
×
D28
Stuck Device Time
×
×
D29
Extended Door Time Enable
×
×
D30
Extended Door Time
×
×
D31
Extended Door Time Landing
×
×
D32
Remote Car Station
×
×
D33
Pre-Opening Door Enable
×
×
D34
Non-Simultaneous door enable
×
×
DAT
Date adjustment command
×
DCN
Arrangement of car CAN boards
×
DCNP
Ping Node Port
×
Display Expansion Boards
×
DEB
ThyssenKrupp Dongyang Elevator
- 46 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
DHN
HN Help
×
DHNS
Scan for Unresponsive HN Ports
×
DHNM
Master / Slave Can Command
×
DHNF
Display HN Nodes Front
DHNR
Display HN Nodes Rear
DLC
Data Loc Table display
×
DRD
Data Record Dump
×
DSF
Display Secured Floors
×
DSI
Deletes Special I/O Inversion
×
DSO
Display Scheduler Overruns
×
DSV
Enable / Disable Daylight Savings Time
×
EBRKO
Emergency Brake Output
×
EBRK1
Emergency Brake Level 1
×
EBRK2
Emergency Brake Level 2
×
EBRK3
Emergency Brake Level 3
×
EBRK4
Emergency Brake Level 4
×
EBRK5
Emergency Brake Level 5
×
EID
Display elevator ID number for field contract
×
EIO
Expansion I/O Board Type
×
ELD
Elevator Designator Display
×
Emergency Operation Brake Pick
×
Emergency Operation Brake Pick Monitor
×
EP1
Emergency Power Type
×
EP2
Emergency Power Return Floor
×
EP3
Emergency Power Door
×
EP4
Emergency Power Manual Select Time
×
EP5
Emergency Power Hold Doors Open
EOBP EOBPM
ThyssenKrupp Dongyang Elevator
- 47 -
SMART
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
SMART
ERC
Display Encoder Recall Errors
ETSB
Emergency Terminal Bottom
×
ETSC
Clear ETS Faults
×
ETSF
ETS Faults
×
ETSP
ETS Parameters
×
ETST
Emergency Terminal Top
×
ETSV
ETS Software Version
×
F10
Fire Main Landing
×
×
F11
Fire Alt Landing
×
×
F12
Fire Main Landing Door
×
×
F13
Fire Alt Landing Door
×
×
F14
Fire Override Time (sec)
×
×
F15
Fire Service Switch Type
×
×
F16
Fire Service Type
×
×
F17
Hall Fire Door Open Time (sec)
×
×
F18
Phase 1 Safety Edge operation
×
×
F19
Phase 2 Safety Edge operation
×
×
F20
Fire Lift
×
×
F21
B44 Phase 2 Activation Location
×
×
F22
PHASE 2 Reduced Speed Enable
×
×
F23
B44 Phase 2 Return Door Speed
×
×
FCD
Force Doors Closed
×
×
FCN
Display Feature Control
×
×
FCP
Floor Count Position Display
×
×
FIS
Field Contract # IMS Remote Monitoring
×
×
FLTN
Display Faults
×
×
FOP
Front Openings Display
×
ThyssenKrupp Dongyang Elevator
- 48 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ FSSR
TK50G
FAST
DESCRIPTION
REMOTE
SMART
Fire Service Sensor Reset (Michigan)
×
FST
Fire Service Sensor High Temp
×
FTD
Fault Display
×
FTM
Format Time Display
×
GET
Get
×
GIC
Group Inconspicuous Calls
×
GSC
Group Served Calls
×
GSS
Displays Slide After Safety Sets
×
H10
Homing Return Landing 1
×
×
H11
Homing Return Door 1
×
×
H12
Homing Return Landing 2
×
×
H13
Homing Return Door 2
×
×
H14
Homing Return Landing 3
×
×
H15
Homing Return Door 3
×
×
H16
Homing Door Time
×
×
HLP
Help
×
I10
Event Inhibit during Inspection
×
×
I11
Event Office Single
×
×
I12
Event Owner Single
×
×
I13
Remote Monitor Aux
×
×
I14
Remote Monitor Service Count
×
×
I15
Long Level Time
×
×
I16
Stuck Car #1 Time
×
×
I17
Stuck Car #2 Time
×
×
I18
Car Stop Switch Time
×
×
I19
Independent Service Time
×
×
I20
Event Door Drag Time
×
×
ThyssenKrupp Dongyang Elevator
- 49 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
SMART ×
I21
Event AM Alive
×
IRL
Inconspicuous Riser Lockouts
×
J10
Capacity (lbs)
×
×
J11
Car ID
×
×
J12
Car Comm Number
×
×
J13
Group ID
×
×
J14
Lobby Floor
×
×
J15
Number of Floors
×
×
J16
Number of I/O Ports
×
×
J17
Number of Lon Channel 1 Ports
×
×
J18
Number of Lon Channel 2 Ports
×
×
J19
Relevel on Stop Switch
×
×
J20
Stop Switch Type
×
×
JBD
Job Information Display
×
M13
Restart Delay
×
×
M16
Inspection Speed
×
×
M17
Brake Step #1 Duration
×
×
M18
Brake Step #2 Duration
×
×
M19
Brake Step Economy Duration
×
×
M20
Number of Brake Steps to Full Lift amps
×
×
M21
Brake Step #1 amps
×
×
M22
Brake Step #2 amps
×
×
M23
Brake Step #3 amps
×
×
M24
Brake Step Economy amps
×
×
M25
Brake Amps Rate (time)
×
×
M26
Wind Sensor Speed
×
×
M27
Emergency Brake Pick
×
×
ThyssenKrupp Dongyang Elevator
- 50 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
SMART
M28
Emergency Brake Hold
×
×
M29
Emergency Brake Amps
×
×
M30
Top Speed fpm
×
×
M31
Leveling Speed fpm
×
×
M32
Floor Hunt Speed fpm
×
×
M33
Velocity Damping
×
×
M34
Constant Gain (1/sec)
×
×
M35
Final Stop Rate (fpm/sec/sec)
×
×
M36
Jerk into Acceleration (fpm/sec/sec)
×
×
M37
Jerk into Top Speed (fpm/sec/sec)
×
×
M38
Jerk into Deceleration (fpm/sec/sec)
×
×
M39
Acceleration (fpm/sec)
×
×
M40
Deceleration (fpm/sec)
×
×
M41
Target Offset (dpp)
×
×
M42
Lag (sec/64)
×
×
M43
Start Delay (sec)
×
×
M44
PreTorque Calibration Delay (sec)
×
×
M45
PreTorque Delay (sec)
×
×
M46
Brake Drop Delay (sec)
×
×
M50
Motor Encoder Pulses per Rev (ppr)
×
×
M51
Motor Encoder RPM (rpm)
×
×
M52
Contract Speed (fpm)
×
×
M53
UnSafe Motor Rotation (rev)
×
×
M60
Enable Encoder Fault Checks (bits)
×
×
M61
Speed Tracking Margin (fpm)
×
×
M62
Speed Over speed Margin (fpm)
×
×
M63
Velocity Error (fpm)
×
×
M64
Motor Encoder Tach Attempts
×
×
ThyssenKrupp Dongyang Elevator
- 51 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
SMART
M70
Primary Brake Current Limit
×
×
M71
Secondary Brake Current
×
×
M91
CAN Loadweigher Scaling
×
×
M92
Loadweigher Anti-nuisance
×
×
M93
Loadweigher / Load Bypassing
×
×
M94
Loadweigher / Load Shutdown
×
×
M95
Loadweigher / U-Peak
×
×
M96
Loadweigher / Emergency Power
×
×
M97
Loadweigher Car Overload Indicator
×
×
M98
Load-weigher Pre-torque Enable
×
×
M99
Percent Counterweight
×
×
NVS
Nonvolatile Memory Status
×
O10
Anti-nuisance car calls
×
×
O11
Hoistway Access Bottom Zone
×
×
O12
Car Cycle Floor 1
×
×
O13
Car Cycle Floor 2
×
×
O14
Hall Independent Return Floor
×
×
O15
Hall Independent Return Door
×
×
O18
Massachusetts Medical Floor
×
×
O19
Massachusetts Medical Door
×
×
O20
Independent overrides Lockouts
×
×
O21
Hoistway Access Top Floor
×
×
O22
Hoistway Access Top Zone (in)
×
×
O24
Transfer Calls On Door Close
×
×
O25
B44 Type
×
×
O26
A17 Type
×
×
O27
EN81 Type
×
×
ThyssenKrupp Dongyang Elevator
- 52 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
SMART
O28
Non-Interference Time
×
×
O33
Lobby Recall return landing
×
×
O34
Lobby Recall Door
×
×
O35
Fan-Light Shutdown Timer
×
×
O36
Capture Return Ldg
×
×
O37
Capture Door To Open
×
×
O38
Capture Door Operation
×
×
O39
Capture Over Ride Independent Service
×
×
O40
Capture Over Ride Car Stop Sw
×
×
O41
Attendant Service Call Latch
×
×
O42
Reverse Car Call Cancel
×
×
O43
CE Fixtures, Vista Monitor
×
×
OVT
Over Travel
×
P10
Slowdown Type
×
×
P11
Position Type
×
×
P12
Rear Leveling Vane
×
×
P13
Front Leveling Type
×
×
P14
Rear Leveling Type
×
×
P15
Long Terminal Slowdowns
×
×
P16
Encoder Counts per Foot
×
×
P17
Up Slowdown Distance (512/ft)
×
×
P18
Down Slowdown Distance (512/ft)
×
×
P19
Encoder Level Distance (512/ft)
×
×
P20
Encoder Count Tolerance (512/ft)
×
×
P21
Encoder Leveling
×
×
PCL
Permission Change Log
×
ThyssenKrupp Dongyang Elevator
- 53 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
SMART
PIA
Position Indication Adjustment
×
×
PSI
Print Special I/O Inversion
×
×
PTI
Pre-Torque Settings Initialize
×
PUP
Power Up Message display
×
R10
Inconspicuous Riser Monitor Operation
×
×
R11
Inconspicuous Riser Activates On HCP Loss
×
×
R12
Inconspicuous Riser Activates On Comm Loss
×
×
R13
Inconspicuous Riser Deactivates On Emergency Power
×
×
R14
Inconspicuous Riser Deactivates On Up Peak
×
×
R15
Inconspicuous Riser Deactivates On Down Peak
×
×
R16
Inconspicuous Riser Inhibits Front Car Calls
×
×
R17
Inconspicuous Riser Inhibits Rear Car Calls
×
×
R18
No Lantern for Onward Car Calls On Inconspicuous Riser
×
×
R19
No Inconspicuous Riser Lantern At Front Group Landings
×
×
R20
No Inconspicuous Riser Lantern At Rear Group Landings
×
×
R21
Inconspicuous Riser Deactivates On Code Blue
×
×
R22
Independent Service serves Inconspicuous Riser landings only
×
×
R23
Independent Service serves Group landings only
×
×
R24
Group Calls only On Group Operation
×
×
R25
Inconspicuous Riser Activates On Attendant Service
×
×
R26
Inconspicuous Riser Deactivation time
×
×
R27
Inconspicuous Riser Activates Program B
×
×
R28
Inconspicuous Riser Deactivates Tenant Security
×
×
R29
Answer All Group Calls Before Inconspicuous Riser Activates
×
×
R30
Answer All Inconspicuous Riser Calls Before Group Activates
×
×
ThyssenKrupp Dongyang Elevator
- 54 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
SMART ×
RFL
Clear the fault buffer
×
ROP
Rear Openings Display
×
RRF
Reset Run monitor Faults
×
RSC
Resynchronize LON Channel
×
RUT
Reset Up Time
×
S10
Security Type
×
×
S11
Security Return Landing
×
×
S12
Door to Open upon Return
×
×
S13
Allow DOB on Security
×
×
S14
One Car Call at a Time on Sec
×
×
S15
Security Homing Delay
×
×
S16
Security Door Time
×
×
S17
Security Exit Not Required
×
×
S18
Security Homes between Calls
×
×
S19
Security Prog. A Lockout Activate
×
×
S20
Security Prog. A Lockout Override Activate
×
×
S21
Security Program A Home On Init
×
×
S22
Security Prog. A Car Shuts Down
×
×
S23
Security Prog. A Car Shuts Down
×
×
S24
Security Prog. A Independent Service Overrides
×
×
S25
Security Prog. A Independent Service Activates Security
×
×
S26
Security Prog. A Inconspicuous Riser Overrides
×
×
S27
Security Prog. A Lanterns Only on Hall Call
×
×
S28
Security Prog. B Lockout Activate
×
×
S29
Security Prog. B Lockout Override Activate
×
×
S30
Security Prog. B Home On Init
×
×
S31
Security Prog. B Car Shuts Down
×
×
ThyssenKrupp Dongyang Elevator
- 55 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
SMART
S32
Security Prog. B Car Shuts Down
×
×
S33
Security Prog. B Independent Service Overrides
×
×
S34
Security Prog. B Independent Service Activates Security
×
×
S35
Security Prog. B Inconspicuous Riser Overrides
×
×
S36
Security Prog. B Lanterns
×
×
S37
Security Prog. A Car Avail. Delay
×
×
S38
Security Prog. B Car Avail. Delay
×
×
S39
Car Call Lockout Override Registers Car Call
×
×
S40
Neo Natal Landing A
×
×
S41
Neo Natal Landing B
×
×
SCC
Set Car Call
×
SCF
Close Floors Display
×
SFA
Secured Floors All display
×
SFD
Secured Floors Dispatch
×
SFL
Secure Floor Lockout
×
SFT
Secured Floor Tenant
×
SFS
Security Floor Subset
×
SLD
Selector Diagnostics Display
×
SRC
Set Rear Car Call
×
SRL
Rear Landing Display
×
SRQ
Show Requests
×
SSE
Toggle Motion Screen
×
STBC
Shut Trip Breaker Control (Detroit)
×
STU
Selector Setup Command
×
SXZ
Express Zone Display
×
TAG
Display LAST TAG in memory
×
TCW
Counterweight Position Count Car Top
×
ThyssenKrupp Dongyang Elevator
- 56 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
SMART
TDM
Spawn 485 COM
×
TECC
Teach CAN Configuration
×
TECF
Teach Nodes Front
×
TECR
Teach Nodes Rear
×
TIM
up TIMe
×
TR1
Trace Record Type
×
×
TR2
Number of Data Words
×
×
TR3
Index into Trace Record Buffer
×
×
TR4
Trace Record Changes Only
×
×
TRA
Trace Recorder
×
TRG
Data Record Trigger command
×
UTM
Up Time Display
×
VER
Software Version Display
×
WRT
Write
×
X10
Audible Car Call Enable
×
×
X11
Arrow Type
×
×
X12
Car Lant. at Door Reversal Limit
×
×
X13
Car Lantern at Lobby
×
×
X14
Flasher Rate (sec)
×
×
X15
Front Lantern Type
×
×
X16
Lantern Delay at Lobby
×
×
X17
Lantern Fire Position
×
×
X18
Lantern off Time
×
×
X19
Lantern on Time
×
×
X20
PI Timeout Time (min)
×
×
X21
Rear Lantern Type
×
×
ThyssenKrupp Dongyang Elevator
- 57 -
Printed in KOREA January, 2007
MAINTENANCE
ADJ
TK50G
FAST
DESCRIPTION
REMOTE
SMART
X22
car buzzer floor passing tone
×
×
X23
Number of Display Characters
×
×
X24
GAL Tone Timer Adjustment
×
×
Z10
Emergency Dispatch Enable
×
×
Z11
Lobby Stop Landing
×
×
Z12
Independent Service Call Latch
×
×
Z13
VIP Service
×
×
Z14
Door Open Timer Saver Using SE
×
×
Z15
Door Closing Forcing
×
×
Z16
B44 Nudging
×
×
ThyssenKrupp Dongyang Elevator
- 58 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
11. Trouble Shooting
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
SIGNAL ORIGIN OR DEST.
FUNCTION I/O TYPE
ACO
Freight Auto Close Override Front
O
ON
MR
C
ACOR
Freight Auto Close Override Front
O
ON
MR
C
ADC
Auxiliary Door Close
O
L
HW
C
ADCL
Auxiliary Door Close Limit(DCL)
O
L
HW
C
AFI
AT Floor Indicator
O
L
HW
C
ALBA
Alarm Button Activated
I
L
CAR
C
ALBI
Alarm Button Activated Indicator
O
L
HW
C
ALBL
Alarm Bell(Fire Bell)
O
L
HW
C
ARDC
Auxiliary Rear Door Close
O
L
HW
C
ARDCL
Auxiliary Rear Door Close(DCL)
O
L
HW
C
ARL
Arrival Lantern
O
L
HW
C
ARLR
SAPB Arrival Lantern- Rear
O
L
HW
C
ARL1-ARL16
Arrival Lantern-Per Floor
O
L
HW
C
ATB
Attendant Bypass Push Button
I
L
CAR
C
ATBI
Attendant Bypass Indicator
O
L
CAR
C
ATD
Attendant Operation Door Speed
O
L
CAR
C
ATDB
Attendant Down Push Button
I
L
CAR
C
ATDC
Attendant Door Close Speed
O
L
CAR
C
ATDI
Attendant Down Indicator
O
L
CAR
C
ATDR
Attendant Operation Door Speed-Rear
O
L
CAR
C
ATT
Attendant Service
I
L
CAR
C
ATTI
Attendant Service Indicator
I
L
CAR
C
ATUB
Attendant UP Push Button
I
L
CAR
C
ATUI
Attendant UP Indicator
O
L
CAR
C
AUD
Freight Door Auto Open Front
O
ON
MR
C
AUDR
Freight Door Auto Open Rear
O
ON
MR
C
ThyssenKrupp Dongyang Elevator
- 59 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
AUDX
Auto Open-Rear(Freight Doors)
O
L
CAR
C
AUTOI
O
L
HW
C
BEEP
Automatic Operation Indicator Coded Car Call Entry-Code Button Acknowledge Output
O
L
CTRL
C
BLO
Bottom Limit Override
O
L
CTRL
C
BLOM
Bottom Limit Override Monitor
I
L
CTRL
C
BLSE
Brake Lift Switch Emergency
O
L
CTRL
C
BLSM
Brake Lift Switch Monitor
O
L
CTRL
C
BK1
Brake Control Level #1
O
L
CTRL
C
BK2
Brake Control Level #2
O
L
CTRL
C
BK3
Brake Control Level #3
O
L
CTRL
C
BPP
Binary Position Parity
O
L
CTRL
BRKDRV
Brake Drive
ON
C
DSP
C Drive Oupput
BRKCPUD
CPU Brake Contactor DE-Energize Control
HI
C
CPU
Input
BRKCPU
CPU Brake Contactor Control
ON
C
Controller
Relay Output
BRK2
Brake Contactor #2
O
L
CTRL
C
BRK3
Brake Contactor #3
O
L
CTRL
C
BRKC
Brake Contactor Control
O
L
CTRL
C
BRKCD
Brake Contactor For Safety Check
O
L
CTRL
C
BRKD
Brake Contactor DE-Energize
LO
C
CPU
Input
BRKE
Brake Contactor Energize
LO
C
CPU
Input
BSLE
Brake Lifted Switch-Emergency Brake
O
L
CTRL
C
BSLM
Brake Lifted Switch-Main Brake
O
L
CTRL
C
BSSE
Brake Switch Set-Emergency Brake
O
L
CTRL
C
BSSM
Brake Switch Set-Main Brake
O
L
CTRL
C
BUZ
Buzzer-Floor Passing,Fire&Nudging
O
L
CAR
C
CAPT
Capture Operation
O
L
CAR
C
ThyssenKrupp Dongyang Elevator
- 60 -
ACTIVE ON STATE
SIGNAL ORIGIN OR DEST.
FUNCTION I/O TYPE
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
CAPTD
Capture Operation Door Open
O
L
CAR
C
CAPTI
Capture Operation Indicator
O
L
CAR
C
CAPTR
Capture Operation Reset
O
L
CAR
C
CBEL
O
L
CTRL
C
CBELL
Freight Door Call Bell Door Close Request Call Bell (Freight Doors)
O
L
CAR
C
CBAI
Code Blue Active Indicator
O
L
HW
G
CB1-CB16
Code Blue Call-COMB.I/O
I/O
L
HW
G
CBI1-CBI16
Code Blue Call-Input
I
ON
HW
G
CBO1-CBO16
Code Blue Call-Output
O
ON
HW
G
CBR1-CBR16
Code Blue Call-Rear-COMB.I/O
I/O
L
HW
G
CBRI1-CBRI16
Code Blue Call-Rear-Input
I
ON
HW
G
CBRO1CBRO16
Code Blue Call-Rear-Output
O
ON
HW
G
CCA
Car Calls Allowed
O
L
CAR
C
CCIE
O
L
CTRL
C
CCREG
Car Call Indicator Enable Car Call Registered Allow Freight Doors To Close
O
L
CAR
C
CDCF
Car Door Contact Front
I
ON
CTRL
C
CDBM
Car Door Bypass Monitor
HI
C
CPU
Input
CDBM2
Car Door Bypass Enabled Monitor
I
L
CPU
Input
CDCFM
Car Door Contact Monitor
I
L
CTRL
C
CDCM
Car Door Contact Monitor
I
ON
CTRL
C
CDCR
Car Door Contact Rear
I
ON
CTRL
C
CDCRM
Car Door Contact Rear Monitor
I
L
CTRL
C
CDI
Car Delayed Indicator
O
L
HW
C
CL1-CL16
Car Call Lockout
I
L
CAR
C/G/C&G
CLR1-CLR16
Car Call Lockout-Rear
I
L
CAR
C/G/C&G
ThyssenKrupp Dongyang Elevator
- 61 -
ACTIVE ON STATE
SIGNAL FUNCTION ORIGIN OR I/O TYPE DEST.
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
SIGNAL ORIGIN OR DEST.
FUNCTION I/O TYPE
CLI1-CLI16
Car Call Lockout Indicator
O
L
CAR
C/G/C&G
CLIR1-CLIR16
Car Call Lockout Indicator-Rear
O
L
CAR
C/G/C&G
CLO1-CLO16
Car Call Lockout Override
I
L
CAR
C
CLOR1CLOR16
Car Call Lockout Override-Rear
I
L
CAR
C
CLD
Car Lantern-Down
O
L
CAR
C
CLDR
Car Lantern-Down-Rear
O
L
CAR
C
CLU
Car Lantern-Up
O
L
CAR
C
CLUR
Car Lantern-Up-Rear
O
L
CAR
C
CLFS
Car Light/Fan Shutdown
O
L
CAR
C
C1-C16
Car Call-COMB. I/O
I/O
L
CAR
C
CI1-CI16
Car Call-Input
I
ON
CAR
C
CO1-CO16
Car Call-Output
O
ON
CAR
C
CR1-CR16
Car Call-Rear-COMB. I/O
I/O
L
CAR
C
CRI1-CRI16
Car Call-Rear-Input
I
ON
CAR
C
CRO1-CRO16
Car Call-Rear-Output
O
ON
CAR
C
CSTI
Car Stop Switch Indicator
O
L
HW
C
CST
Car Stop Switch Monitor
I
ON
CTRL
C
CSTO
Car Stop Switch Override
O
L
CTRL
C
CSTO1
Car Stop Switch Override #1
O
L
CTRL
C
CSTO2
Car Stop Switch Override #2
O
L
CTRL
C
CSTOM
Car Stop Switch Override Monitor
I
L
CTRL
C
CSTO1M
Car Stop Switch Override #1 Monitor
I
L
CTRL
C
CSTO2M
Car Stop Switch Override #2 Monitor
I
L
CTRL
C
CWD
Counterweight Derailed
I
L
HW
C
D2-D16
Hall Call-Down-COMB. I/O
I/O
L
HW
G
ThyssenKrupp Dongyang Elevator
- 62 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
DAD
Direction Arrow-Down
O
L
HW
C
DADH
Direction Arrow-Down-Hall
O
L
HW
C
DAU
Direction Arrow-Up
O
L
HW
C
DAUH
O
L
HW
C
DBEH
Direction Arrow-Up-Hall Door Button Enable-Hall Front (Freight Doors)
O
L
HW
C
DC
Door Close
O
L
CTRL
C
DCR
Door Close-Rear
O
L
CTRL
C
DCA
Door Close Assist
O
L
CTRL
C
DCAR
Door Close Assist-Rear
O
L
CTRL
C
DCAER
Door Close Automatic Enable-Rear
O
L
CTRL
C
DCAE
Door Close Automatic Enable
O
L
CTRL
C
DCB
Door Close Button-Front-Main COP Door Close Button-FrontFront AUX. COP
I
L
CAR
C
I
L
CAR
C
I
L
CAR
C
DCB4
Door Close Button-Front-Rear COP Door Close ButtonFront-Rear AUX.COP
I
L
CAR
C
DCBR
Door Close Button-Rear-Main COP
I
L
CAR
C
DCBR2
Door Close Button-Rear-AUX. COP
I
L
CAR
C
DCBR3
I
L
CAR
C
DCBR4
Door Close Button-Rear-Rear COP Door Close Button-RearRear AUX. COP
I
L
CAR
C
DCL
Freight Door Close Limit Front
I
ON
MR
C
DCLR
Freight Door Close Limit Rear
I
ON
MR
C
DCL6
Door Close Limit 6인치
I
L
CAR
C
DCL6R
Door Close Limit 6인치-Rear
I
L
CAR
C
DCN
Door Close Nudging
O
L
CTRL
C
DCNR
Door Close Nudging-Rear
O
L
CTRL
C
DD
Door Disconnect
I
L
CTRL
C
DCB2 DCB3
ThyssenKrupp Dongyang Elevator
- 63 -
SIGNAL FUNCTION ORIGIN OR I/O TYPE DEST.
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
DFI
Dispatch Failure Indicator
O
L
HW
C
DHB
Door Hold Button
O
L
CAR
C
DHBR
Door Hold Button-Rear
O
L
CAR
C
DHI
Door Hold Indicator
O
L
HW
C
DHIR
Door Hold Indicator-Rear
O
L
HW
C
DHS
Door Hold Switch
I
L
CAR
C
DHSR
Door Hold Switch-Rear
I
L
CAR
C
DI2-DI16
Hall Call-Down-Input
I
ON
HW
G
DISBZ
Distress Buzzer
O
L
HW
C
DISBR
Distress Buzzer Reset
I
L
HW
C
DISI
Distress Indicator
O
L
HW
C
DLB
Direction Limit-Bottom
I
L
CAR/HW
C
DLT
Direction Limit-Top
I
L
CAR/HW
C
Hall Call-Down-Output
O
ON
HW
G
DO
Door Open
O
L
CTRL
C
DOR
Door Open-Rear
O
L
CTRL
C
DOB
Door Open Button-Front-Main COP
I
L
CAR
C
DOB2
Door Open Button-Front-AUX. COP
I
L
CAR
C
DOB3
I
L
CAR
C
DOB4
Door Open Button-Front-Rear COP Door Open Button-FrontRear AUX. COP
I
L
CAR
C
DOBR
Door Open Button-Rear-Main COP
I
L
CAR
C
DOBR2
Door Open Button-Rear-AUX. COP
I
L
CAR
C
DOBR3
I
L
CAR
C
DOBR4
Door Open Button-Rear-Rear COP Door Open Button-RearRear AUX. COP
I
L
CAR
C
DOH
Door Open High Speed
O
L
CTRL
C
DOHR
Door Open High Speed-Rear
O
L
CTRL
C
DO2-DO16
ThyssenKrupp Dongyang Elevator
- 64 -
SIGNAL FUNCTION ORIGIN OR I/O TYPE DEST.
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
DOI
Door Open Indicator
O
L
HW
C
DOIR
Door Open Indicator-Rear
O
L
HW
C
DOL
Door Open Limit
I
L
CAR
C
DOL
Freight Door Open Limit Front
I
ON
MR
C
DOLR
Freight Door Open Limit Rear
I
ON
MR
C
DOPE
Freight Door Open Enable
O
ON
MR
C
DOPER
Freight Door Open Enable-Rear
O
ON
MR
G
DORL
Door Open Reversal Limit
I
L
CAR
C
DORLR
Door Open Reversal Limit-Rear
I
L
CAR
C
DR2-DR16
Hall Call-Down-Rear-COMB. I/O
I/O
L
HW
G
DRI2-DRI16
Hall Call-Down-Rear-Input
I
ON
HW
G
DRO2-DRO16
Hall Call-Down-Rear-Output
O
ON
HW
G
DZE
Door Zone Enable
O
ON
CTRL
C
DZER
Door Zone Enable-Rear
O
L
CTRL
C
DZM
Door Zone Monitor
I
L
CTRL
C
DZ1M
Door Zone #1 Monitor
I
L
CTRL
C
DZ1RM
Door Zone #1-Rear- Monitor
I
L
CTRL
C
DZ2M
Door Zone #2 Monitor
I
L
CTRL
C
DZ2RM
Door Zone #2-Rear- Monitor
I
L
CTRL
C
DZMR
Door Zone Monitor-Rear
I
L
CTRL
C
DZ1
Door Zone #1
I
H
CAR
C
DZ1R
Door Zone #1-Rear
I
H
CAR
C
DZ2
Door Zone #2
I
H
CAR
C
DZ2R
Door Zone #2-Rear
I
H
CAR
C
EQDR
Earthquake Detection Reset
I
L
CTRL
C
EQI
Earthquake Seismic Indicator
O
L
HW
C
ThyssenKrupp Dongyang Elevator
- 65 -
SIGNAL FUNCTION ORIGIN OR I/O TYPE DEST.
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
EQD
Earthquake (Seismic) Detector
I
L
HW
C
EE
Electric Eye
I
L
CAR
C
EER
Electric Eye-Rear
I
L
CAR
C
EES
Electric Eye Shutoff Switch
I
L
CAR
C
EESR
Electric Eye Shutoff Switch-Rear
I
L
CAR
G
EPA
I
L
HW
G
O
L
HW
C
I
L
HW
C
O
L
HW
C
I
L
HW
G
I
L
HW
G
I
L
HW
G
EPCS4
Emergency Power-Automatic Emergency PowerAcknowledge Indicator Emergency Power-Manual Car Select -Per Car Emergency Power - Car Selected Indicator Emergency Power-Manual Car Select -Car #1 Emergency Power-Manual Car Select -Car #2 Emergency Power-Manual Car Select -Car #3 Emergency Power-Manual Car Select -Car #4
I
L
HW
G
EPNP
Emergency Power-Normal Power
I
L
MR
C&G
EPLI
Emergency Power Lowering Indicator
O
L
HW
C
EPW
I
L
MR
G
I
L
CAR
C
ETSL2
Emergency Power Warning Emergency Terminal Speed LimitTop #1 Emergency Terminal Speed LimitTop #2
I
L
CAR
C
EZNI
Express Zone Indicator
O
L
HW
C
FDD
Freight Door Disable Front
O
ON
MR
C
FDDR
Freight Door Disable Rear
O
ON
MR
C
HDC
Freight Hall Door PB Cutout Front
O
ON
MR
C
HDCR
Freight Hall Door PB Cutout Rear
O
ON
MR
C
FALI
Failure Indicator
O
L
HW
C
EPAI EPCS EPCSI EPCS1 EPCS2 EPCS3
ETSL1
ThyssenKrupp Dongyang Elevator
- 66 -
SIGNAL FUNCTION ORIGIN OR I/O TYPE DEST.
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
FALNI
Not Failed Indicator
O
L
HW
C
FDH
Freight Door Hold Front
O
ON
MR
C
FDHR
Freight Door Hold Rear
O
ON
MR
C
FDIM
Freight Door Interlock Monitor
I
L
CTRL
C
FRC
Freight Retiring Can-Front
O
ON
MR
C
FRCR
O
ON
MR
C
O
ON
MR
C
FS1RA
Freight Retiring Can-Rear Fire Service Phase 1 Recall Active (Front) Fire Service Phase 1 Recall Active (Rear)
O
ON
MR
C
FSA
Fire Active Service(Front)
O
ON
MR
C
FSA
Fire Active Service(Rear)
O
ON
MR
C
FS1A
Fire Service Phase 1 Active(Front)
O
ON
MR
C
FS1A
Fire Service Phase 1 Active(Rear)
O
ON
MR
C
FS2A
Fire Service Phase 2 Active(Front)
O
ON
MR
C
FS2A
Fire Service Phase 2 Active(Rear)
O
ON
MR
C
FS2ON
Fire Service Phase 2 On(Front)
O
ON
MR
C
FS2ON
Fire Service Phase 2 On(Rear)
O
ON
MR
C
FS2OF
Fire Service Phase 2 Off(Front)
O
ON
MR
C
FS2OF
O
ON
MR
C
O
ON
MR
C
FSAL
Fire Service Phase 2 Off(Rear) Fire Service AT Designated Landing (Front) Fire Service AT Designated Landing (Rear)
O
ON
MR
C
FDR
Freight Door Reset(Front)
O
ON
MR
C
FDR
Freight Door Reset(Rear)
O
ON
MR
C
F1-F16
Freight SAPB Call-COMB. I/O
I/O
L
HW
C
FI1-FI16
Freight SAPB Call-Input
I
ON
HW
C
FO1-FO16
Freight SAPB Call-Output
O
ON
HW
C
FR1-FR16
Freight SAPB Call-Rear-COMB. I/O
I/O
L
HW
C
FS1RA
FSAL
ThyssenKrupp Dongyang Elevator
- 67 -
SIGNAL FUNCTION ORIGIN OR I/O TYPE DEST.
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
FRI1-FRI16
Freight SAPB Call-Rear-Input
I
ON
HW
C
FRO1-FRO16
Freight SAPB Call-Rear-Output
O
ON
HW
C
FSAFI
Fire Service-ALT. Floor Indicator
O
L
HW
C
FSCC
Fire Service-Call Cancel
I
L
CAR
C
FSC1
Fire Service-Car-On
I
L
CAR
C
FSC2
Fire Service-Car-Off
I
L
CAR
C
FSDB
Fire Service-Door Bypass
I
L
CAR
C
FSDFI
Fire Service-Door Failed Indicator
O
L
CAR
C
FSE
Fire Service Sensor-Equipment
I
L
MR
C
FSDO
Fire Service-Fireman’s Door Open
I
L
CAR
C
FSH1
Fire Service-Hall-On Main
I
L
HW
C&G
FSH2
Fire Service-Hall-Off Main
I
L
HW
C&G
FSH3
Fire Service-Hall-On Aux
I
L
HW
C&G
FSH4
Fire Service-Hall-Off Aux
I
L
HW
C&G
FSH5
Fire Service-Hall-Reset
I
L
HW
C&G
FSMFI
Fire Service-Main Floor Indicator
O
L
HW
C
FS1I
Fire Service-Phase 1 Indicator
O
L
CTRL
C
FS2I
Fire Service-Phase 2 Indicator
O
L
CTRL
C
FSTFL
Fire Service-Top Final Limit
I
L
HW
C
FSI
Fire Service Indicator
O
L
HW
C
FSRI
Fire Service Return Indicator
O
L
CAR
C
FSX
Fire Service Sensor-Aux.
I
L
MR
C&G
FSM
Fire Service Sensor-Main
I
L
MR
C&G
FHS
Flashing Hall Signs
O
L
CTRL
C
FPI
Flashing Position Indicator
O
L
HW
C
FPT
Floor Passing Tone
O
L
CAR
C
ThyssenKrupp Dongyang Elevator
- 68 -
SIGNAL FUNCTION ORIGIN OR I/O TYPE DEST.
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
HA
Hoistway Access Front
ON
HW
Controller
HAM
Hoistway Access Front Monitor
ON
HW
Controller
HAR
Hoistway Access Rear
ON
L
HW
HARM
Hoistway Access Rear Monitor
ON
L
HW
HAT
Hoistway Access Top
ON
L
HW
HATM
Hoistway Access Top Monitor
ON
L
HW
HAB
Hoistway Access Bottom
ON
L
HW
HABM
Hoistway Access Bottom Monitor
ON
L
HW
HABU
Hoistway Access Bottom Up
ON
L
HW
HABUM
Hoistway Access Bottom Up Monitor
ON
L
HW
HABD
Hoistway Access Bottom Down
ON
L
HW
HABDM
Hoistway Access Bottom Down Monitor
ON
L
HW
HATR
Hoistway Access Top Rear
ON
L
HW
HATD
Hoistway Access Top Down
ON
L
HW
HATDM
Hoistway Access Top Down Monitor
ON
L
HW
HATU
Hoistway Access Top Up
ON
L
HW
HATUM
Hoistway Access Top Up Monitor
ON
L
HW
HABR
Hoistway Access Bottom Rear
ON
L
HW
HCIE
Hall Call Indicator Enable
O
L
CTRL
G
HCPI
Hall Call Power Indicator
O
L
HW
G
HCP
Hall Call Power Monitor
I
H
HW
G
HCLD
Hall/Car Lantern-Down-Front
O
L
HW/CAR
C
ThyssenKrupp Dongyang Elevator
- 69 -
SIGNAL FUNCTION ORIGIN OR I/O TYPE DEST.
Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output Relay Output
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
HCLU
Hall/Car Lantern-Up-Front
O
L
HW/CAR
C
HDBM
Hoistway Door Bypass Monitor
I
L
CTRL
C
HDBM2
Hoistway Door Bypass Enabled Monitor
I
L
CTRL
C
HDIF
Hoistway Door Interlock-Front
I
ON
CTRL
C
HDIR
Hoistway Door Interlock-Rear
I
ON
CTRL
C
HDIFM
Hoistway Door Interlock Front Monitor
I
L
CTRL
C
HDIRM
Hoistway Door Interlock Rear Monitor
I
L
CTRL
C
HES
I
L
CAR
C
HESI
Hospital Emergency Service Hospital Emergency Service Active Indicator
O
L
HW
C
HLD
Hall Lantern-Down-Front
O
L
HW
C
HLD2-HLD16
Hall Lantern-Down-Front-Per Landing
O
L
HW
C
HLDR HLDR2HLDR16
Hall Lantern-Down-Rear
O
L
HW
C
Hall Lantern-Down-Rear-Per Landing
O
L
HW
C
HL1-HL16
Hall Lantern-Landing Signal
O
L
HW
C
HLU
Hall Lantern-Up-Front
O
L
HW
C
HL1-HL16
Hall Lantern-Landing Signal
O
L
HW
C
HLU
Hall Lantern-Up-Front
O
L
HW
C
HLU1-HLU15
Hall Lantern-Up-Front-Per Landing
O
L
HW
C
HLUR HLUR1HLUR15
Hall Lantern-Up-Rear
O
L
HW
C
Hall Lantern-Up-Rear-Per Landing
O
L
HW
C
HMCLI
Homing-Car AT Lobby Indicator
O
L
HW
C
HMLI
Homing-Lob Recall Oper.Active IND.
O
L
HW
C
HMLNI
Homing-Lob Recall Oper.Not IND.
O
L
HW
C
HML
Homing-Lobby Recall
I
L
HW
C
HM1
Homing-#1
I
L
HW
C
HM2
Homing-#2
I
L
HW
C
ThyssenKrupp Dongyang Elevator
- 70 -
SIGNAL FUNCTION ORIGIN OR I/O TYPE DEST.
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
HM3
Homing-#3
I
L
HW
C
HM1I
Homing #1 Indicator
O
L
HW
C
HM1NI
Homing #1 Not Active Indicator
O
L
HW
C
HM2I
Homing #2 Indicator
O
L
HW
C
HM3I
Homing #3 Indicator
O
L
HW
C
HPID
Hall PI Disable
O
L
CTRL
C
IUL
In Use Light
O
L
HW
C
IRO
Inconspicuous Riser Operation
I
L
HW
C
IROI
Inconspicuous Riser Operation Indicator
O
L
HW
C
ID2-ID16
Inconspicuous Riser Call-Down-COMB. I/O
I/O
L
HW
C
IDI2-IDI16
Inconspicuous Riser Call-Down-Input
I
ON
HW
C
IDO2-IDO16
Inconspicuous Riser Call-Down-Output
O
ON
HW
C
I/O
L
HW
C
I
ON
HW
C
O
ON
HW
C
I/O
L
HW
C
SIGNAL FUNCTION ORIGIN OR I/O TYPE DEST.
IU1-IU15
Inconspicuous Riser Call-Down-RearCOMB. I/O Inconspicuous Riser Call-Down-RearInput Inconspicuous Riser Call-Down-RearOutput Inconspicuous Riser Call-UpCOMB. I/O
IUI1-IUI15
Inconspicuous Riser Call-Up-Input
I
ON
HW
C
IUO1-IUO15
O
ON
HW
C
I/O
L
HW
C
I
ON
HW
C
IURO1IURO15
Inconspicuous Riser Call-Up-Output Inconspicuous Riser Call-UpRear-COMB. I/O Inconspicuous Riser Call-UpRear-Input Inconspicuous Riser Call-UpRear-Output
O
ON
HW
C
ISC
Independent Service-Car
I
L
CAR
C
ISCI
Independent Service-Car-Indicator
O
L
HW
C
ISH
Independent Service-Hall
I
L
HW
C
IDR2-IDR16 IDRI2-IDRI16 IDRO2IDRO16
IUR1-IUR15 IURI1-IURI15
ThyssenKrupp Dongyang Elevator
- 71 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
ISHI
Independent Service-Hall-Indicator
O
L
HW
C
IN
Inspection-Auto
I
H
CTRL
C
INCT
Inspection-Car Top
I
H
CTRL
C
INCN
Inspection-Controller
I
H
CTRL
C
INCTM
Inspection-Car Top Monitor
I
H
CTRL
C
INCTU
Inspection-Car Top Up
I
H
CTRL
C
INCTD
Inspection-Car Top Down
I
H
CTRL
C
IND
Inspection-Down Button
I
H
CTRL
C
INHA
Inspection-Hoistway Access
I
H
CTRL
C
INHAM
Inspection-Hoistway Access Monitor
I
CTRL
C
INOP
Inspection-Operating Panel
I
H
CTRL
C
INSP
Inspection-Spare
I
H
CTRL
C
INU
Inspection-Up Button
I
H
CTRL
C
INRB
Inspection-Run Bug
I
H
CTRL
C
INRBM
Inspection-Run Bug Monitor
I
H
CTRL
C
INRBU
Inspection-Run Bug Up
I
H
CTRL
C
INRBD
Inspection-Run Bug Down
I
H
CTRL
C
LVD
Level Down
I
L
CAR
C
LVDR
Level Down-Rear
I
L
CAR
C
LVU
Level Up
I
L
CAR
C
LVUR
Level Up-Rear
I
L
CAR
C
LWA
Loadweigher-Antinuisance
I
L
CAR
C
LWB
Loadweigher-Bypass
I
L
CAR
C
LWBI
Loadweigher-Bypass-Indicator
O
L
CAR
C
LWD
Loadweigher-Dispatch
I
L
CAR
C
LWF
Loadweigher-Full Load
I
L
CAR
C
LWO
Loadweigher-Overload
I
L
CAR
C
ThyssenKrupp Dongyang Elevator
- 72 -
SIGNAL FUNCTION ORIGIN OR I/O TYPE DEST.
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
SIGNAL ORIGIN OR DEST.
FUNCTION I/O TYPE
LWOI
Loadweigher-Overload-Indicator
O
L
CAR
C
MEC
Medical Emergency-Car
I
L
CAR
C
MEH
Medical Emergency-Hall
I
L
HW
C
MEI
Medical Emergency-Indicator
O
L
HW
C
MCC1
Motor Contactor Control #1
O
ON
CTRL
C
MCE
Motor Contactor Energized
I
L
CTRL
C
NXUP
Next Up Indicator
O
L
HW
C
OFLNI
Off Line Indicator
O
L
HW
C
PID1-PID16 PIDC1PIDC16
Position Indicator-Digital-Discrete Interf
O
L
CAR/HW
C
O
L
CAR/HW
C
PIA1-PIA16
Position Indicator-Digital-Car-Discrete Interf Position Indicator-Discrete Car & Main Landing Position Indicator-Discrete-Alternate Landing
O
L
CAR/HW
C
PIC1-PIC16
Position Indicator-Discrete-Car
SAFE
Safety Circuit Monitor
I
ON
CTRL
C
SAHI1
Spare Active High Input #1
I
H
CTRL
C
SAHI2
Spare Active High Input #2
I
H
CTRL
C
SDD
Slowdown-Down
I
L
HW
C
SDDR
Slowdown-Down-Rear
I
L
HW
C
SDU
Slowdown-Up
I
L
HW
C
SDUR
Slowdown-Up-Rear
I
L
HW
C
SE
Safety Edge-Front
I
L
CAR
C
SER
Safety Edge-Rear
I
L
CAR
C
SOA
Security Operation Activation
I
L
HW
C/G/C&G
SOO
Security Operation Override
I
L
HW
CF
SOTL
Security Operation Total Lockout
I
L
HW
C/G/C&G
PI1-PI16
ThyssenKrupp Dongyang Elevator
- 73 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
INPUT OR OUTPUT
ACTIVE ON STATE
SIGNAL ORIGIN OR DEST.
FUNCTION I/O TYPE
SOTLI
Security Operation Total Lockout INDIC.
O
L
HW
C/G/C&G
SOTOAI
Security Operation Total Override Active INDIC.
O
L
HW
GRF
SOTOA
Security Operation Total Override Active
I
L
HW
C/G/C&G
SPDLV
Speed-Leveling
O
ON
CTRL
C
SPD1
Speed #1
O
ON
CTRL
C
SPD2
Speed #2
O
ON
CTRL
C
SPD3
Speed #3
O
ON
CTRL
C
U1-U15
Hall Call-Up-COMB. I/O
I/O
L
HW
G
UI1-UI15
Hall Call-Up-Input
I
ON
HW
G
UO1-UO15
Hall Call-Up-Output
O
ON
HW
G
UR1-UR15
Hall Call-Up-Rear-COMB. I/O
I/O
L
HW
G
URI1-URI15
Hall Call-Up-Rear-Input
I
ON
HW
G
URO1-URO15
Hall Call-Up-Rear-Output
O
ON
HW
G
ThyssenKrupp Dongyang Elevator
- 74 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
ACTIVE ON STATE
MCDDRV
Motor Contactor DE-Energize Drive
LO
C
DCP
Drive Input
MCCD
Motor Contactor Control CPU
HI
C
CPU
Input
NDET
Normal Slowdown Count Det
HI
C
DSP
Drive Input
NCNT
Normal Slowdown Count
HI
C
DSP
Drive Input
SAFETSXD
Emergency Terminal Slowdown DEEnergize
HI
C
CPU
Input
SAFCPUD
CPU Safety DE-Energize Safe
HI
C
CPU
Input
SAFDRV
Safety Drive
ON
C
DSP
Relay Output
SAFCPU
Safety CPU
ON
C
CPU
Relay Output
SAFETSX
Emergency Terminal Slowdown Safe
ON
C
CPU
Relay Input
SAF2
Safety Check 121-122
HI
C
CPU
Input
SAF3
Safety Check 122-123
HI
C
CPU
Input
SAF4
Safety Check 123-125
HI
C
CPU
Input
SAF5
Safety Check 125-126
HI
C
CPU
Input
PIH1-PIH16
Position Indicator Hall Discrete
LO
C
DUCT LON
Output
DTOK
Drive Tempurature OK
LO
C
CPU
Input
DRVECPU
Drive Enable Control
ON
C
CPU
Relay Output
DRVEN
Drive Enable
HI
C
DSP
Drive Input
ECNT
Emergency Slowdown Count
HI
C
CPU
Input
EDET
Emergency Slowdown Detect
HI
C
CPU
Input
EBRKD
Emergency Brake Contactor Detect
C
CPU
Input
FAN
Drive Fan
C
CPU
Output
C
CPU
FUNCTION
LOCATION
INPUT OR OUTPUT
INF
HI
FST EBRKCPU
CPU Emergency Brake Contactor
ON
C
CPU
Relay Output
MCCCPU
Motor Contactor Control CPU
ON
C
CPU
Relay Output
ThyssenKrupp Dongyang Elevator
- 75 -
Printed in KOREA January, 2007
MAINTENANCE
TK50G
DESIGNATOR
NAME
ACTIVE ON STATE
MCPDRV
Motor Contactor Pilot Drive
ON
C
DSP
Relay Output
MFPDRV
Motor Field Pilot Drive
ON
C
DPS
Relay Output
MCPCPUD
CPU Motor Contactor Pilot DEEnergize
LO
C
CPU
Input
ThyssenKrupp Dongyang Elevator
- 76 -
FUNCTION
LOCATION
INPUT OR OUTPUT
Printed in KOREA January, 2007