Manual Eltek Flatpack
Short Description
Descripción: Manual de usuario de rectificador Eltek Flatpack...
Description
SISTEMA FLATPACK 2 >
José Rodas Utani Jefe de Servicios & Soporte Técnico Perú, Ecuador y Bolivia
Slide 2 of 23 29.04.2013
Generation 4
Slide 3 of 23 29.04.2013
1. Highest Power Density 33W/in3
FP2 3000
Generation 4
25W/in3
FP2 2000 FP2 1800
20W/in3
Generation 3
15W/in3
Flatpack 1800 Flatpack 1500
10W/in3
SMPS 1000
5W/in3 SMPS 60/20 Generation Saves the customer money by :
-
Slide 4 of 23 29.04.2013
1
More space for customer equipment and/or batteries Thus less cabinets and less footprint in the location
1. Highest Power Density – FP2 2KW SHELF
Dimensions
Slide 5 of 23 29.04.2013
Modular Configuration 48 VDC
17.5” Wide –
167A Maximum Per Shelf
brackets mount 19”, 21” or 23”
125A Redundant
14.5” Deep
With four rectifiers installed
1U – 1.75” Height
1. Highest Power Density – FP2 3KW SHELF
Dimensions
Slide 6 of 23 29.04.2013
Modular Configuration 48 VDC
17.5” Wide –
250A Maximum Per Shelf
brackets mount 19”, 21” or 23”
187,5A Redundant
17” Deep
With four rectifiers installed
1U – 1.75” Height
2. Pequeño y ligero
< 1.9 Kg 41.5mm 327 mm 109 mm
Más fácil para dirigir : -
Slide 7 of 23 29.04.2013
Personal de mantenimiento - especialmente como repuestos Logística - un peso más ligero, significa menos costos de envío
3. Operación de los ventiladores 2 Fans – Front to back airflow - will work with only one (Back to front version in design stage)
Ahorros por costos de mantenimiento y operación por : • -
Slide 8 of 23 29.04.2013
Evitar las salidas de llamadas de prioridad (fuera de horas normales) Da una alta eficacia del rectificador
4. Controles digitales 2 controlador digital : Dan mas supervisión y control.
Ahorro de tiempo y dinero por : -
Slide 9 of 23 29.04.2013
Dando al operadores una información más en tiempo real del sistema El personal de mantenimiento sabe exactamente qué necesita hacer con las ayudas.
5. Edge connectors Communications AC Input DC Output
Edge-connector technology
Ahorra tiempo (y dinero) : -
Slide 10 of 23 29.04.2013
Módulos intercambiables en caliente. Reduce fallas de interconexión.
6. Amplio Rango de entrada CA
Output Power vs. Input voltage 2000W 1800W
Nominal Input
850W 650W
0W 185
85V Red LED
Slide 11 of 23 29.04.2013
Yellow LED
290 300 Green LED
Red LED
6. Large AC input range
Mains derating
Output Power (%)
120
> Derating below 176Vac (185Vac on 2kW module)
100 80 60
> 1382W (46%) at 85Vac
40 20 0 0
50
100
150
200
250
Voltage (Vac) FP2 48/2000
Slide 12 of 23 29.04.2013
FP2 48/3000
300
350
7. Temperatura De-rating
Temperatura ambiente (max full carga de salida)
2000W 1800W 1400W
Linear De-rating Zone
o
o
+75
+45 Green LED
Slide 13 of 23 29.04.2013
1200W
Yellow LED
0W
Red LED
7. Temperature De-rating
Temperature derating
Output Power (%)
120
> Derating above 45 oC
100 80
> 2100W (67%) at 75 oC
60 40
> Delivers 50A at 65 oC
20
> Operating down to -40 oC
0 0
10
20
30
40
50
60
Ambient temperature FP2 48/2000
Slide 14 of 23 29.04.2013
FP248/3000
70
80
8. Excelente protección en AC/DC
Mains fuse: 2x15 A (fast) in Live and Neutral
Varistor across the lines for transient protection Hi -ohmic disconnect above 290V / 300V AC (with auto reconnect when in range)
DC Output
DC output : Blocking Diode Slide 15 of 23 29.04.2013
· Short circuit proof (constant current) · Single or double fan blockage/failure
9. Highly Efficient – 2 KW 2000W rectifier : Efficiency at 230Vac input 93
92,5
Eff.(%)
92
Max Efficiency Zone
91,5
91
90,5
90 0
200
400
600
800
1000 Pout(W)
Slide 16 of 23 29.04.2013
1200
1400
1600
1800
2000
9. Highly Efficient – 3 KW > Efficiency above 93% at 40-80% load, 92.4% at 100% load
94
93
> 10% loss reduction on system level Efficiency (%)
> Low load efficiency also improved
92
91
90
89
88
87 3000W 2000W
86 0
10
20
30
40
50
60
Load (% )
Slide 17 of 23 29.04.2013
70
80
90 100
9. Highly Efficient – 2 KW HE
Slide 18 of 23 29.04.2013
Technical Data – 24V 2000 W
Slide 19 of 23 29.04.2013
Technical Data – 48 V 1800 W
Slide 20 of 23 29.04.2013
Technical Data – 48 V 2000 W
Slide 21 of 23 29.04.2013
Technical Data – 48 V 3000 W
Slide 22 of 23 29.04.2013
Technical Data – 48 V 2000 W HE
Slide 23 of 23 29.04.2013
Procedimiento de instalación
Handle in locked position
Hole to release the handle’s spring mechanism
Handle in unlocked position
Slide 24 of 23 29.04.2013
Panel Frontal
Dual Fan Cooling
GREEN Power LED
Slide 25 of 23 29.04.2013
RED Alarm LED
YELLOW Warning LED
Panel Frontal
Power (green)
Slide 26 of 23 29.04.2013
ON
Rectifier is powered
Flashing
Smartpack controller accessing information on the rectifier
OFF
Mains are unavailable
Panel Frontal
Warning (yellow) ON
Slide 27 of 23 29.04.2013
Rectifier is in Derating Mode (reduced output power) high internal temperature (+65 to 70 C) or low input voltage (lower than 176VAC) or single fan failure The remote Battery Current Limit is activated AC input voltage is out of range Rectifier in stand-alone mode (or loss of communication with the Smartpack controller
Flashing
Rectifier is in Over-voltage Protection Mode
OFF
No abnormal situation is present
Panel Frontal
Alarm (red) ON
OFF
Slide 28 of 23 29.04.2013
Rectifier is in Shut-down Mode due to low mains (0 – 85VAC) or high internal temperature (+75 C or higher) or high output voltage (higher than 59.5 VDC) Internal rectifier failure (malfunction) Fan failure (double fan malfunction) Low output voltage (0 to 43.5VDC) CAN bus failure No alarm situation is present
Unidad de Control
> Scaleable y modular, control flexible para la gama entera de productos Eltek
Slide 29 of 23 29.04.2013
Unidad de Control
Slide 30 of 23 29.04.2013
>
Front panel backlit LCD (2x16) and key pad
>
USB for PC connection and easy FW uploading
>
CAN bus para comunicacion con modulos Eltek
>
6 entradas digitales programables
>
6 relay de salidas configurables
>
Latched contactor control
>
Monitoreo y test de baterias
>
Compensacion de carga por temperatura
>
8 symmetry measurements
>
log de eventos(10000) con hora y fecha.
>
Windows-based PC communication software
Pequeño pero de gran alcance
< 300g
44mm 144 mm
109 mm Slide 31 of 23 29.04.2013
Smartpack Vista Frontal
>
”Top-level alarms” scrolls on display when active •
Slide 32 of 23 29.04.2013
Battery, Load, Rectifier, Control System & Mains
>
Alarm LED (red) = Major Alarm active
>
Warning LED (yellow) = Minor Alarm active
>
Power LED (green) = Normal status active
Panel Trasero CAN Bus CAN bus
ID based serial bus communications •
Part No : 242100.110 (RoHS compliant)
Slide 33 of 23 29.04.2013
•
Max 8 Smartpack
•
Max 50 Rectifiers
Panel Trasero Monitoreo de Baterías Monitoreo de Baterías Con 4 : Standard Con 3 : Extended •
Symmetry measurement
•
8 strings mid point or 2 strings 12V block
•
Sensor de Temp.
Part No : 242100.110 (RoHS compliant)
Slide 34 of 23 29.04.2013
Conectividad Batería
> CON3 & CON4 – Conexiones de baterías
Cable Sensor de Temperatura
Pin
Function
1
Symmetry I/P 1
2
Symmetry I/P 2
3
Symmetry I/P 3
4
Symmetry I/P 4
5
Symmetry I/P 5
6
Symmetry I/P 6
7
Symmetry I/P 7
8
Symmetry I/P 8
9-10
Con 3 : Temp sense 2 Con 4 : Temp sense 1
11 - 14
Con 3 – 2nd batt current, batt fuse Con 4 : Not used
Slide 35 of 23 29.04.2013
Conectividad - Batería > CON3 & CON4 – Conexión de batería
Slide 36 of 23 29.04.2013
Conectividad Symmetry
> Symmetry measurement options
Slide 37 of 23 29.04.2013
Panel Trasero Sistema interno Sistema Interno System measurements Unit Power 2xLVD control (Latched)
Part No : 242100.110 (RoHS compliant)
Slide 38 of 23 29.04.2013
Battery fuse fail
Conectividad Sistema > CON5 – Conexión del sistema
System Connection Card. Art 200625 Slide 39 of 23 29.04.2013
Pin
Function
1
Positive Input
2
Negative Input
3
Batt Current +ve
4
Batt Current -ve
5
Batt Fuse +ve
6
Batt Fuse -ve
7
Load Fuse Fail
8
LVD1 Active
9
LVD1 Common
10
LVD2 Active
11
LVD2 Common
Conectividad Sistema
> Sistema de Configuración de la tarjeta
JP1 -48v system = 1-2 +24v system = 2-3 JP2 -48v system = „Neg‟ +24v system = „Pos‟
Slide 40 of 23 29.04.2013
Panel Trasero Alarmas I/O
Alarma I/O Con 1 (standard):2 + 2 relay input / output
Part No : 242100.110 (RoHS compliant)
Slide 41 of 23 29.04.2013
Con 2 (extended):4 + 4 relay input / output
Conectividad Externa y Alarm I/O
> CON1 & CON2 – I/O Conexiones
Alarm Output & Input Card Art 105954 Slide 42 of 23 29.04.2013
Pin
Function
1-2
Alarm input 1 ( + / -)
3–4
Alarm input 2 ( + / -)
5-7
Alarm output 1 ( NO /C / NC)
8 - 10
Alarm output 2 ( NO /C / NC)
1-2
Alarm input 3 ( + / -)
3-4
Alarm input 4 ( + / -)
5-6
Alarm input 5 ( + / -)
7-8
Alarm input 6 ( + / -)
9 - 11
Alarm output 3 ( NO /C / NC)
12 - 14
Alarm output 4 ( NO /C / NC)
15 - 17
Alarm output 5 ( NO /C / NC)
18 - 20
Alarm output 6 ( NO /C / NC)
RS-232 Opciones
RS-232 mounted Enables connection of Standalone Webpower or modem • Part No : 242100.112 (RoHS compliant)
Rear position : Replaces extended Battery symmetry card •
Slide 43 of 23 29.04.2013
Part No : 242100.111 (RoHS compliant)
Smartpack
Smartpack Extended RS232
Slide 44 of 23 29.04.2013
Panel Trasero Webpower incluido Embedded WebPower
Part No : 242100.113 (RoHS compliant)
Slide 45 of 23 29.04.2013
Ethernet interface of remote monitoring of Smartpack Is possible to “tunnel” Powersuite remotely also.
Smartpack Smartpack SNMP/Webpower
Slide 46 of 23 29.04.2013
Escalabilidad CAN/Power bus
Smartpack Master
Smartpack Slave n
Smartpack Slave 1
System functionality
System functionality
System functionality with 8 modules
Voltage input
1
Voltage inputs
2
Voltage inputs
8
Symmetry inputs
8 (2x4x12V)
Symmetry inputs
16 (4x4x12V)
Symmetry inputs
64 (16x4x12V)
Current inputs
2
Current inputs
4
Current inputs
2x8
Temperature inputs
2
Temperature inputs
4
Temperature inputs
2x8
General purpose inputs 6
General purpose inputs 12
General purpose inputs 6x8
Load fuse input
1
Load fuse input
2
Load fuse input
1x8
Batt fuse input
2
Batt fuse input
4
Batt fuse input
2x8
Relay outputs
6
Relay outputs
12
Relay outputs
6x8
Contactor control
2+
Contactor control
4+
Contactor control
2+x8
Slide 47 of 23 29.04.2013
Conectividad Latched Contactors
A latching contactor changes state only when a reversed pulse voltage is applied to the coil.
Slide 48 of 23 29.04.2013
Protection Diode
PowerSuite
> Explorer oriented easy to use PC SW
> USB gives simple access.
> Wide functionality with clear graphic presentation.
Slide 49 of 23 29.04.2013
Smartpack Front / Power Suite Content >
Front menu
>
Password levels
>
Alarm ”monitor”
>
AlarmGroups and output (relay) mapping
>
”Programmable” inputs
>
Event log
>
Operational mode and ”Critical” conditions
>
Low Voltage Disconnect (LVD)
>
Battery functions • Battery discharge test • Test results • Battery tables • Temp. comp & Charge curr. limitation • Test results • Special monitors • Boost • Symmetry
>
Calibration & shunt Scaling
>
Rectifier ID’s
>
Mains measurement
>
PowerSuite installation and basic introduction
Slide 50 of 23 29.04.2013
Niveles de acceso > Smartpack/PowerSuite password •
4 digit pin-code
> Nivel de usuario •
No password
> Novel de Servicio •
Password: ”0003” (default)
> Nivel de Fabrica •
Password:
> Si perdió la contraseña de servicio, envíe el numero de serie a fabrica, para poder enviar ”PUK-code” de retorno.
Slide 51 of 23 29.04.2013
Smartpack menu frontal
> VoltageInfo - details
Slide 52 of 23 29.04.2013
Option
Description
NomVolt
Nominal output voltage
BoostVolt
Battery boost-charging voltage
LowBatt1
Voltage limit for MinorLow Battery Alarm
LowBatt2
Voltage limit for MajorLow Battery Alarm
HighBatt1
Voltage limit for MinorHigh Battery Alarm
HighBatt2
Voltage limit for MajorHigh Battery Alarm
LVBD
Voltage limit for Low Voltage Battery Disconnect (LVBD)
LVLD 1.1
Voltage limit for Low Voltage Load Disconnect (LVLD)
Smartpack menu frontal > RectifierInfo - details
Slide 53 of 23 29.04.2013
Option
Description
NoOfRects.
Number of rectifiers installed in the system.
RectCurrent
Rectifier current
RectSerialNumber
Rectifier ID and serial number
Rect.PrimaryVolt
Rectifier input mains voltage
Rectifier Status
Rectifier status
Rectifier Temp
Rectifier temperature
Alarm ”monitor” cont’
Slide 54 of 23 29.04.2013
Entradas programables > 6 entradas digitales programables.
Slide 55 of 23 29.04.2013
Entradas programables > Input ”Monitor” •
Event is selectable in ”drop-down-list” - Not all activates a function (yet...)
•
Description may be changed
> Description and Event text listed in Event log
Slide 56 of 23 29.04.2013
Log de Eventos > Smartpack front: ”DisplayMessages” > PowerSuite: “Event Log”
> El Smartpack controlador puede almacenar hasta 1000 eventos cronológicos. Cuando el registro esta lleno, se sobre escribe el más viejo evento. > El registro se almacena en EEPROME Ejemplo
Slide 57 of 23 29.04.2013
•
27-09-2005 (Date ”dd-mm-yyyy”)
•
17:15 (Time ”hh:mm”)
•
Battery Voltage (Monitor name/Description)
•
MinorLow: ON (Event status in monitor)
Desconexión por bajo voltaje (LVD) > Se toma la acción de desconexión cuando el sistema está en “crítico” y: - El voltaje de la batería esta debajo del limite. - Delay time ha expirado, si es activo.
> Volver a conectar se toma cuando el sistema “NO es crítico” y: - El voltaje de la batería está sobre límite.
> Default hysteresis entre reconexión y desconexión es de 4V
Slide 58 of 23 29.04.2013
Funciones de Batería Test de Descarga > Smartpack Tiene dos tipos de test batería. •
Normal – usa la tabla de batería
•
Simplificado – usa el voltaje final y el tiempo a criterio - Si se alcanza el tiempo de la prueba las baterías son buenas - Si se alcanza el voltaje final de las baterías primero son malas
> Tres diferentes modos de test son posibles (para ambos tipos)
Slide 59 of 23 29.04.2013
•
Manual: Empiezo y parada por una entrada manual
•
Periódico/Intervalo: Programado por tiempo, fecha y el intervalo de periodos.
Funciones de Batería Resultado del Test >
Hasta 10 diferentes resultados de la prueba de descarga almacenados en la EEPROM • Empiezo Fecha [mm/dd/yyyy] • Tiempo Final [hh:mm] • Tipo de Test [Manual/Periodic/Automatic] • Tabla de batería • Duración del Test [m] • Corriente de descarga [Ah] • Voltaje final [V] • Calidad Calculada [%] • Resultado del Test
>
Datos Registardos • Corriente de bateria(1 & 2) • Voltaje de bateria • Temperatura(1 & 2) • Voltaje de simetria (8)
>
Los Resulatados pueden ser vistos haciendo click en el icono de batería en la columna del resultado de la prueba • First 10 min and last 10 min logging are done every minute • In between every - 10 min (test duration < 300 min) - 20 min (300 min < test duration < 600 min) - 40 min (600 min < test duration < 1200 min)
Slide 60 of 23 29.04.2013
Funciones de Batería Tabla de Batería > Smartpack puede almacenar dos tablas de batería definida por el usuario con: •
Tiempo [min] • Corriente de Bateria 1.9V/cell Voltaje final alto [A] • Corriente de Bateria 1.75V/cell Voltaje final bajo [A]
> NOTE. Muchas tablas de batería pueden ser almacenadas en la PC y facil de uploaded al Smartpack con PowerSuite > What is Eltek Std? •
Slide 61 of 23 29.04.2013
Es el promedio de valores no cambiables de los diferentes tipos de fabricantes de baterías.
Funciones de Batería Tabla de Batería > Configuración de la tabla de baterías por Powersuite
Slide 62 of 23 29.04.2013
Funciones de Batería Tabla de Batería
Slide 63 of 23 29.04.2013
Funciones de Batería Temp. Comp. & Curr. Lim. > Compensacion por temperatura •
Slope
•
Ref. temp
•
Min comp. volt
•
Max comp. volt
> Limitación corriente de batería
Slide 64 of 23 29.04.2013
•
Dos limitación configurables (v1.02)
•
Planta generadora, indicando con una entrada digital.
Funciones de Batería Temp. Comp. & Curr. Lim.
Output Voltage [Vdc]
55,5 55 54,5 54
Slope 53,5 53 52,5 Min Comp, volt
Slide 65 of 23 29.04.2013
o
Temperature T [ C]
Max Comp, Volt
Battery Current (A)
Funciones de Batería Temp. Comp. & Curr. Lim.
Battery current limit [A] = 0.3*C10 Float current Mains OK
Mains failure
Mains OK, Recharge
Load current Mains
Slide 66 of 23 29.04.2013
Mains OK
Rectifier ID’s cont’ > Reset number of rectifiers
Slide 68 of 23 29.04.2013
Soluciones de Sistemas Cuanta potencia usted necesita ?
>
Mas densidad de potencia
Up to 8000W per 1PR shelf
1U
Slide 70 of 23 29.04.2013
Montaje Flexible
Smartpack mounting options
Smartpack in PR
Slide 71 of 23 29.04.2013
Smartpack in Distribtuion
Soluciones Integradas
Soluciones Integradas 2U
Incluye (up to) :
5 kg
Slide 72 of 23 29.04.2013
(exc rectifiers)
1U Distribucion + 1 PR 8000W (166A@48V) Smartpack 2 x 100A Breakers de Bateria 6 x 2–32A Breakers de Carga 2 x LVD (150A)
Soluciones Integradas
Solucion Integrada 5 - 8U Incluye (up to) :
8 kg
Slide 73 of 23 29.04.2013
(exc rectifiers)
4U Distribucion + 1-4 PR 32000W (660A@48V) Smartpack 6 x 100A Breakers de Bateria* 18 x 2–63A Breakers de carga* 2 x LVD (up to 600A) * Verficar en datasheet por otra for otra configuracion disponible
Soluciones Integradas
23” EIA Seismic Equipment Rack
FP2NX-48-9U power system block
7U available equipment space Battery Disconnect #4 Battery Tray #4 Battery Disconnect #3
Slide 74 of 23 29.04.2013
Battery Tray #3
Battery Disconnect #2
Battery Tray #2
Battery Disconnect #1
Battery Tray #1
Gabinetes
> 8 - 96 kW en un solo Gabinete
> Max 2000A@48V = 96kW
(CAN bus limitation)
> Típicamente hasta 4PR por sistema con baterías. Example 32 kW Slide 75 of 23 29.04.2013
> Variedad de gabientes disponibles
Solución Gabinete 96kW
Slide 76 of 23 29.04.2013
•
Input 230V/400V 3-phase
•
FP2 2kW rectifiers
•
Max Output 48V 2000A
•
Cabinet dimensions: 600x2000x600mm
•
2 SmartPacks (Master-Slave)
Gracias!!
Slide 77 of 23 29.04.2013
View more...
Comments