Main - Power System Training Material V1.0-20071012

May 2, 2018 | Author: pr3m4n | Category: Electric Power System, Power Supply, Rectifier, Alternating Current, Direct Current
Share Embed Donate


Short Description

TELECOM...

Description

12.OCT 2007

Security Level: Internal Open

Power System Power System Training Material Material V1.0 www.huawei.com

HUAWEI TECHNOLOGIES TECHNOLOGIES Co., Ltd .

HUAWEI Confidential

Index 1. Brief Introduction of Power System 2. Parameter of Power Power System and and Vendor Vendor 3. Ma Mainte intenan nance ce of Power Power System 4. Links of Power Power System System Data in 3ms 3ms

1

Brief Introduction of Power System

Power Supply A device which can change a type of electrical energy to other type of electrical energy. Classification by

Classification Result

Function

Rectifier (AC/DC Power Supply) Converter (DC/DC Power Supply) Inverter (DC/AC Power Supply) Transducer (AC/AC Power Supply, UPS)

 Application Area

Design Principle

Power System

Industry Power Supply Military Power Supply Household Power Supply Linear Power Supply Switching Mode Power Supply Including rectifier  controller  AC distribution and DC distribution

Classification by

Classification Result

Function

AC/DC Power System DC/DC Power System

Installation

Embedded Power System Independent Power System( AC/DC Power System)

AC Alternating Current, DC Direct Current

1

Brief Introduction of Power System

Rectifier (AC/DC Power supply) such as HD4830-3, R48-1800A, R48-2900U, HD48100-5 is below.

HD4830-3

R48-1800A

R48-2900U

HD48100-5

Power system such as PS48300-1A/30, PS48300/1800-X6, PS48600-3/2900-X5, PS481000-5/100 is below.

PS48300-1A/30

PS48300/1800-X6

PS48600-3/2900-X5

PS481000-5/100

1

Brief Introduction of Power System The parts within the red dash line is the parts of power system.

1

Brief Introduction of Power System Power system in the telecom office and relationship with other equipment.

 AC Grid

Generator 

 AC Distribution Box (With two AC routes and switching device )

Terminal/ Service

UPS Inverter   Air Conditioner 

Lighting

Battery1

Swithing

Power System

PDF

transmission

Battery2 Other 

PE Bus Bar 

Index 1. Brief Introduction of Power System 2. Parameter of Power System and Vendor 3. Maintenance of Power System 4. Links of Power System Data in 3ms

2

Parameter of Power System

There are four power system manufacturers certificated below providing power system to our company. Manufacturer Name

Manufacturer Logo

Detail Description

Emerson 艾默生

Emerson Network Power Co.,Ltd Production mainly on power system, DC/DC module ,UPS and so on. Power system type including 120A,180A,300A,600A,1000A.

Delta-Cimic 中达

Delta electronics power Co.,Ltd Production mainly on power system, DC/DC module ,UPS and so on. Power system type including 120A,180A,300A,600A,1000A.

Eltek 易达

Eltek energy technology Ltd Production mainly on power system. Power system type including 120A,180A,300A,600A,1000A.

DongLiYuan 动力源

Bejing dynamic power Co.,Ltd Production mainly on power system, DC/DC module. Power system type including 120A,300A.

2

Parameter of Power System

Power

Type of power

Detail introduction

Similar to the old version

System

system

120A

PS48120/1800-X6 MCS48/120-QLUA1

600mm*600mm*2000mm(W*D*H), With space for two battery strings, each string is 100Ah or 150Ah

PS48100-2/25

180A

PS48180/1800-X6 MCS48/180-QLUA1

600mm*600mm*2000mm(W*D*H), With space for four battery strings, each string is 100Ah or 150Ah

PS48350-1B/25

300A

PS48300/1800-X1 PS48300/1800-X6 PS48300/1800-X7 MCS48/300-QMUA1

600mm*600mm*1600mm(W*D*H), Battery should be put outside the power system. It is the most common power system in our company.

PS48300-3A/25 PS48300-3B/25 PS48300-1A/30 PS48300-1B/30 PS48300-1A/30-X2 PS48300-1B/30-X2

600A

PS48600-3/2900-X5 PS48600-3/2900-X7 MCS48/600-TLUA5

600mm*600mm*2000mm(W*D*H), Battery should be put outside the power system.

PS48600-2B/50

1000A

PS481000-5/100 MCS48/1000-RLCH

Height is 2000mm, Battery should be put outside the power system.

PS481000-2/100

power system

2

Parameter of Power System How to read the Emerson power system type?

PS 48 120 / 1800-X6 Power system version Output power of each rectifier Maximum current of power system Output current of power system  Abbreviation of Power system

Notice: Name of PS48180/1800-X6 and PS48300/1800-X6 is the same style as PS48120/1800-X6.

2

Parameter of Power System PS 48 600 -3/ 2900-X5 Version 6 Output power of each rectifier Power system Generation Maximum current of power system Output current of power system  Abbreviation of Power system

PS 48 1000-5/ 100 Output power of each rectifier Power system Generation Maximum current of power system Output current of power system  Abbreviation of Power system

2

Parameter of Power System-120A

Emerson: PS48120/1800-X6, Delta: MCS48/120-QLUA1, Item

Detail Description

size

600mm×600mm×2000mm(W ×D×H),

 AC input

Single phase,two routes AC input with manual switching; 90Vac~290Vac,rated voltage is 220Vac,

DC outpu t

30A each rectifier ,Maximum output current is 120A, Battery fuses:2×100A(fuse); 7 routes load outputs including: 1×63A (MCB), 2×32A(MCB), 1×10A(MCB), 1×100A(fuse), 1×50A(fuse), 1×6A(fuse) ,

Batte ry

With space for two battery strings, each string is 100Ah or 150Ah

2

Parameter of Power System-180A

Emerson:PS48180/1800-X6; Delta:MCS48/180-QLUA1; Item

Detail Description

Size

600mm×600mm×2000mm(W ×D×H);

 AC input

Three phase, one route AC input. 90Vac~290Vac,rated voltage is 220Vac;

DC outpu t

30A each rectifier, Maximum output current is 180A, Battery MCB:4×100A(MCB); 7 routes load outputs including: LLVD:3×100A(MCB) ; BLVD:2×32A(MCB),2×10A(M CB);

Batte ry

With space for four battery strings, each string is 100Ah or 150Ah

2

Parameter of Power System-300A

Emerson:PS48300/1800-X6; Delta:MCS48/300-QMUA1; Item

Detail Description

Size

600mm×600mm×1600mm( W ×D×H);

 AC input

Three phase, one route AC input. 90Vac~290Vac,rated voltage is 220Vac;

DC output

30A each rectifier, Maximum output current is 300A, Battery fuses:2×160A(fuse); 7 routes load outputs including: LLVD:3×100A(fuse) ; BLVD:2×32A(MCB),2×10A (MCB);

 AC output

1×16A (MCB/3P),1×16A (MCB/1P),

Batter  y

Battery should be put outside the power system.

2

Parameter of Power System-600A

Emerson:PS48600-3/2900; Delta:MCS48/600-TLUA1; Item

Detail Description

Size

600mm×600mm×2000mm(W × D×H);

 AC input

Three phase, Two route AC input with manual switching. 90Vac~290Vac,rated voltage is 220Vac;

DC output

50A each rectifier, Maximum output current is 600A, Battery fuses:2×500A(fuse); 18 routes load outputs including: LLVD: 3×160A (fuse) , 2×100A (fuse) , 2×63A (MCB) ,3×32A (MCB) ,2×10A (MCB) ; BLVD:2×32A(MCB),2×10A(MC B); BLVD: 2×63A (MCB) ,2×32A (MCB) ,2×10A (MCB) ;

 AC output

2×16A (MCB/3P),3×16A (MCB/1P),

Batter  y

Battery should be put outside the power system.

2

Parameter of Power System-1000A

Emerson:PS481000-5/100; Delta:MCS48/1000-RLCH; Item

Detail Description

Type and size

Power system include AC,DC distribution cabinet, rectifier cabinet. Emerson:PD380/600AFH-2(AC distribution cabinet 800mm ×600mm×2000mm), PD48/2500-DF(DC distribution cabinet 800mm×600mm×2000mm) PD48/1200BFH(AC&DC distribution cabinet 800mm ×600mm×2000mm) Rack1000-5(Rectifier cabinet 600mm ×600mm×2000mm)

PD380/600  AC Input of PD380/600AFH-2 is three phase, two AC input with manual switching.  AFH-2 12 routes three phase and 6 routes single phase AC output including: 5×250A/3P, 5×100A/3P, 1×63A/3P, 1×32A/3P, 3×32A/1P, 3×20A/1P PD48/2500 -DF

Two battery fuse:2×2000A; 30 routes load output including: 8×500A, 4×400A, 4×200A, 8×100A, 6×63A

PD48/1200 BFH

Two routes AC input with manual switching, three phase. 8 routes three phase and 6 routes single phase AC output including: 2×250A/3P,3×160A/3P,1×63A/3P, 2×32A/3P,3×32A/1P,3×20A/1P; Two battery fuses: 2 ×1000A; 19 routes load output including: 3×400A,4×250A, 4×160A, 4×100A, 4×50A

DC output

100A each rectifier, Maximum output current of one rectifier cabinet is 1000A; The maximum current of power system by parallel the rectifier cabinet is 10000A; Generally in our company the maximum current is 3500A;

 AC output

Battery should be put outside the power system.

2

Parameter of Power System-1000A Indicators Rectifier MCB Monitor PSM-A AC Distribution Cabinet

Rectifier HD48100-5 DC Distribution Cabinet

Rectifier Cabinet

AC Distribution Cabinet

Rectifier Cabinet

DC Distribution Cabinet

AC and DC Distribution Cabinet

Index 1. Brief Introduction of Power System 2. Parameter of Power System and Vendor 3. Maintenance of Power System 4. Links of Power System Data in 3ms

3

Maintenance of Power System (1) Two AC input of Power system: Two routes of AC input in power system, manual switching. If one AC input is fail down, another can provide AC to power system. Generally, there are two AC input with switching device on the wall of telecom office.

(2)Convenient maintenance: Rectifier can be hot plugged in while power system running and pulled out while rectifier running.

3

Maintenance of Power System

(3)LLVD: Load Low Voltage Disconnection. Once the AC input fail down, the battery discharging and the voltage come down to the LLVD voltage such as 44V, then the load connected to the LLVD contactor will be disconnected to protect the BLVD load.

+ bus bar AC Input

Battery1 BLVD

AC/DC Rectifier

Contactor -bus bar

(4)BLVD: Battery Low Voltage Disconnection. Once the AC input broken down and LLVD contactor is disconnected, the battery voltage still goes down to the BLVD voltage such as 43.2V,then the load connected to the BLVD contactor will be disconnected to protected the battery. Notice: Load connected to BLVD is not battery, but the important load such as transport or optical telecom equipment. Generally the power of  BLVD load is smaller than the power of LLVD load.

Battery2

LLVD Contactor

MCB

32A 32A

Fuse

10A 10A 100A 100A 100A

PS48300/1800-X6 Power system LLVD and BLVD diagram The parts in the red dashed frame is the parts in pow er system.

3

Maintenance of Pow er System

(5)Power system Cable including:  AC input cable, Battery cable, Load cable, PE cable

Load Cable

 A B

L1 L2

C

L3

 AC input Cable

PE

Telecom Equipme nt

Power system -48V RTN

Battery Cable

PE Cable





Battery

PE of telecom office

Cable of Power system of three phase AC input

3

Maintenance of Pow er System

Let’s have a look at “Emerson Power

System Installation”.

3

Maintenance of Pow er System

How to read the Emerson power system user manual and description?

Index 1. Brief Introduction of Power System 2. Parameter of Power System and Vendor 3. Maintenance of Power System 4. Links of Power System Data in 3ms

4

Links of Pow er System Data in 3ms

Item

Address on 3ms Website

Power system

http://3ms.huawei.com/ Cabinet

Configuration Guide

http://3ms.huawei.com/ Home Others Power System/Battery/UPS/Distribution Cabinet General Guide Configuration Guide

Sales Guide

http://3ms.huawei.com/ Home Others Cabinet General Guide Sales Guide

Power System/Battery/UPS/Distribution

http://3ms.huawei.com/ Home Others Cabinet Power System User Manual

Power System/Battery/UPS/Distribution





Product Description



Power System/Battery/UPS/Distribution















Others









User Manual

Home









http://3ms.huawei.com/ Home Others Power System/Battery/UPS/Distribution Cabinet Power System Product Description →



Notice Useful Document







12.OCT 2007

Security Level: Internal Open

Thank You www.huawei.com www.huawei.com

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

View more...

Comments