3877-3 MECHANICAL & ELECTRICAL SERVICES 1 _______________________________________________________________________ _ Services 1.

Description

Size (mm) (Minimum)

TNB Room Consumer HT Room Transformer Room

6000 (W) x 5000 (D) x 4000 (H) 6000 (W) x 5000 (D) x 4000 (H) 10000 (W) x 4500 (D) x 4000 (H) 8500 (W) x 9000 (D) x 4000 (H)

LV Switch Room 2.

Generator Set Room

4.

Security System

Electrical Riser

2500 (W) x 1000 (D)

MDF Room Telephone Riser

6000 (W) x 8500 (D) x 3000 (H) 1000 (W) x 750 (D)

Located at Basement Car Park Located at every floor

1500 kVA

6500 (W) x 9000 (D) x 5000 (H)

Located beside TNB room

ELV Riser

800 (W) x 750 (D)

Data Riser

1000 (W) x 750 (D)

For CCTV, SMATV, PA & Card Access System For structure cabling system

Fire Protection Fire Pump Room (for sprinkler & hose reel pumps) Fire Control Room

Hose Tank

Reel/Wet

15000 (W) x 10000 (D) 3500 (W) x 3500 (D) RC Tank 1: 55m2 x 3500 (H) RC Tank 2: 47m2 X 3500 (H)

Sprinkler Tank

Riser

Fire Riser 6.

Located beside TNB Room Located adjacent to Genset Room Located adjacent to TNB Sub Station Located at every floor

Telephone

3.

5.

Remarks

Electrical

RC Tank: 31m2 X 3500 (H)

1300 (W) x 650 (D)

To be located at Carpark Level 1 between Sprinkler Tank and Hose/Wet Riser Tank To be located near entry to building at Ground Floor. Can be combined with Security Room To be located flush with Fire Pump Room at Carpark Level 1. Tank to be compartmented inot 2 half To be located flush with Fire Pump Roomks at Carpark Level 1 Within every staircase/fire lobby

escape

Domestic Cold & Hot Water DCW Suction Tank

RC Tank : 167m2 X 3500 (H)

DCW Transfer Pump Room DCW Roof Storage Tank – Podium West Block

4000 x 4000 x 3500(H)

DCW Roof Storage Tank – Podium Centre Block

8000 x 6000 x 2500(H)

DCW Roof Storage Tank – Podium East Block

7000 x 6000 x 2500(H)

7000 x 6000 x 2500(H)

Rc tank located Carpark Level 1 Tank to be compartmented into 2 half. Attached to rc suction tank between the tank compartment FRP Sectional Tank located on RC Flat Roof c/w 600 high rc plinth FRP Sectional Tank located on RC Flat Roof c/w 600 high rc plinth FRP Sectional Tank located on RC Flat Roof c/w 600 high rc plinth

3877-3 MECHANICAL & ELECTRICAL SERVICES 2 _______________________________________________________________________ _ Services Description Size (mm) (Minimum) Remarks

7.

DCW Roof Storage Tank - Tower

14000 x 6000 x 2500(H)

Cold Water Riser (All Podium Block & Tower)

600 (W) x 600 (D)

DCW Hydro Pneumatic Pump Room (All block and Tower)

2500 x 2500 x 3000(H)

Located at roof level near to DCW Tank – All Blocks & Tower

Sanitary Plumbing Last manhole

8.

FRP Sectional Tank located on RC Flat Roof c/w 600 high rc plinth Located within the public toilets

Sanitary Plumbing Riser (All Podium Block & Tower)

600 (W) x 600 (D)

Toilet Exhaust Fan Room

2500 x 2500 x 3000 (H)

Located at building perimeter, actual location to be determine Located within the public toilets

Air Conditioning

AHU Room (Tower)

5000 x 6500

AHU Room Podium Block)

5000 x 6500

(Each

Hex & Chilled Water Pump Room Toilet Exhaust Shaft (AllPodium Block) Toilet Exhaust Shaft (Tower) Smoke Spill Make Up shaft (All Podium Block & Tower) Smoke Spill Shaft (All Podium Bloc & Tower) Carpark Fresh Air Shaft

16000 x 13000 x 4000 (H)

Located on RC Flat Roof above toilet (if enclosure is require, otherwise fan is exposed) 2 nos. per floor for on floor units around Lift core Area. Size include Fresh air Duct within(OR 2 nos.. 25m x 25m central AHU Room on Roof ) 2 nos. per floor for on floor units around Lift Core Area. Size include Fresh air Duct within (OR 2 nos. 20m x 15m central AHU Room on Roof) Located at Capark Level 2

600 (W) x 900 (D)

Located within or next to toilet

1200 (W) x 900 (D)

Located within or next to toilet

1500 (W) x 1500 (D)

Around Lift Core area

1500 (W) x 1500 (D)

Around Lift Core area

3 nos. 4000 (W) x 3000 (D)

Carpark Shaft

Exhaust

Air

3 nos. 4000 (W) x 3000 (D)

Carpark

Exhaust

Fan

4500 (W) x 4500 (D) x 3000 (H)

Carpark Levels. Locate so that the shaft discharge to Ground floor open area and opposite side of Fresh Air Shaft for cross ventilation Carpark Levels. Locate so that the shaft discharge to Ground floor open area and opposite side of Fresh Air Shaft for cross ventilation Locate next to Exhaust Air Shaft

3877-3 MECHANICAL & ELECTRICAL SERVICES 3 _______________________________________________________________________ _ Services Description Size (mm) (Minimum) Remarks Room Carpark Supply Air Fan Room Pressurization Shaft (All Podium Block & Tower)

9.

4500 (W) x 4500 (D) x 3000 (H)

Locate next to Exhaust Air Shaft

600 (W ) x 1500 (H)

Attached to All internal Escape Staircases, perimeter Staircase without window and Bomba Lift Lobby Locate at RC Flat Room

Pressurization Fan Room (All Podium Block & Tower)

3500 (W) x 300 (D) x 3000 (H)

BAS Riser (All Podium Block & Tower)

600 (W) x 600 (D)

BAS Around Lift Core area

10. LPG LPG Farm LPG Riser

7500 (W) x 1000 (D) x 3000 (H) 600 (W) x 600 (D)

Note: All dimensions are shown for room clearance only.