6000 (W) x 5000 (D) x 4000 (H) 6000 (W) x 5000 (D) x 4000 (H) 10000 (W) x 4500 (D) x 4000 (H) 8500 (W) x 9000 (D) x 4000 (H)
LV Switch Room 2.
Generator Set Room
4.
Security System
Electrical Riser
2500 (W) x 1000 (D)
MDF Room Telephone Riser
6000 (W) x 8500 (D) x 3000 (H) 1000 (W) x 750 (D)
Located at Basement Car Park Located at every floor
1500 kVA
6500 (W) x 9000 (D) x 5000 (H)
Located beside TNB room
ELV Riser
800 (W) x 750 (D)
Data Riser
1000 (W) x 750 (D)
For CCTV, SMATV, PA & Card Access System For structure cabling system
Fire Protection Fire Pump Room (for sprinkler & hose reel pumps) Fire Control Room
Hose Tank
Reel/Wet
15000 (W) x 10000 (D) 3500 (W) x 3500 (D) RC Tank 1: 55m2 x 3500 (H) RC Tank 2: 47m2 X 3500 (H)
Sprinkler Tank
Riser
Fire Riser 6.
Located beside TNB Room Located adjacent to Genset Room Located adjacent to TNB Sub Station Located at every floor
Telephone
3.
5.
Remarks
Electrical
RC Tank: 31m2 X 3500 (H)
1300 (W) x 650 (D)
To be located at Carpark Level 1 between Sprinkler Tank and Hose/Wet Riser Tank To be located near entry to building at Ground Floor. Can be combined with Security Room To be located flush with Fire Pump Room at Carpark Level 1. Tank to be compartmented inot 2 half To be located flush with Fire Pump Roomks at Carpark Level 1 Within every staircase/fire lobby
escape
Domestic Cold & Hot Water DCW Suction Tank
RC Tank : 167m2 X 3500 (H)
DCW Transfer Pump Room DCW Roof Storage Tank – Podium West Block
4000 x 4000 x 3500(H)
DCW Roof Storage Tank – Podium Centre Block
8000 x 6000 x 2500(H)
DCW Roof Storage Tank – Podium East Block
7000 x 6000 x 2500(H)
7000 x 6000 x 2500(H)
Rc tank located Carpark Level 1 Tank to be compartmented into 2 half. Attached to rc suction tank between the tank compartment FRP Sectional Tank located on RC Flat Roof c/w 600 high rc plinth FRP Sectional Tank located on RC Flat Roof c/w 600 high rc plinth FRP Sectional Tank located on RC Flat Roof c/w 600 high rc plinth
Located at building perimeter, actual location to be determine Located within the public toilets
Air Conditioning
AHU Room (Tower)
5000 x 6500
AHU Room Podium Block)
5000 x 6500
(Each
Hex & Chilled Water Pump Room Toilet Exhaust Shaft (AllPodium Block) Toilet Exhaust Shaft (Tower) Smoke Spill Make Up shaft (All Podium Block & Tower) Smoke Spill Shaft (All Podium Bloc & Tower) Carpark Fresh Air Shaft
16000 x 13000 x 4000 (H)
Located on RC Flat Roof above toilet (if enclosure is require, otherwise fan is exposed) 2 nos. per floor for on floor units around Lift core Area. Size include Fresh air Duct within(OR 2 nos.. 25m x 25m central AHU Room on Roof ) 2 nos. per floor for on floor units around Lift Core Area. Size include Fresh air Duct within (OR 2 nos. 20m x 15m central AHU Room on Roof) Located at Capark Level 2
600 (W) x 900 (D)
Located within or next to toilet
1200 (W) x 900 (D)
Located within or next to toilet
1500 (W) x 1500 (D)
Around Lift Core area
1500 (W) x 1500 (D)
Around Lift Core area
3 nos. 4000 (W) x 3000 (D)
Carpark Shaft
Exhaust
Air
3 nos. 4000 (W) x 3000 (D)
Carpark
Exhaust
Fan
4500 (W) x 4500 (D) x 3000 (H)
Carpark Levels. Locate so that the shaft discharge to Ground floor open area and opposite side of Fresh Air Shaft for cross ventilation Carpark Levels. Locate so that the shaft discharge to Ground floor open area and opposite side of Fresh Air Shaft for cross ventilation Locate next to Exhaust Air Shaft
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.