Electric Load Estimation For High Rise Buildings
Total Electric Load Estimation For residential Buildings In general for the first estimation of the total power required for residential buildings 1- Economic Residential Building Power density = 2 – 4 KV KVA A / 100 m2 2- Moderate Residential Building Power density = 5 – 7 KVA / 100 m2 3- Luxurious Residential Building Power density = 8 10 KVA / 100 m2
Lighting Indoor Lighting
Lighting Power Estimation 1- Residential Buildings, Pd = 10 VA / m2 2- Offices, Pd = 20 VA / m2 3- Malls, Pd = 40 VA /m2 4- Colleges and Schools, Pd = 25 VA / m2 5- Hospitals, Pd = 20 VA / m2
Allowed lighting power There are two Methods to estimate the lighting power in commercial buildings: A. Complete Building Method. B. Area Category Method.
A. Complete Building Method The building must consist of one type of use for a minimum of 90% of the floor area of the entire building (in determining the area of the primary type of use, include the following areas if they serve as support for the primary type of use: lobbies, corridors, restrooms and storage closets).
Tabl e 1 – C o m p l e te B u i l d i n g M e t h o d Li gh tin g Pow er Dens ity Values (Watts/m²)
TYPE OF USE Auditoriums Convention centers Financial institutions General commercial and industrial work buildings High bay Low bay Grocery stores Hotel Industrial and commercial storage buildings Medical buildings and clinics Office buildings Parking Garages Religious facilities Restaurants Retail and wholesale stores* Schools Theaters All others
ALLOWED LIGHTING POWER 17 14 12 12 11 17 15 8.0 12 12 5.0 17 13 17 14 15 7.0
Example: Complete Building Method
A 1000-m² medical clinic building is to be built. What is its allowed lighting power under the complete building approach?
Answer From Table the Standards, medical buildings and clinics are allowed 12 w/m2. The allowed lighting power is 1000 x 12 = 12000 W. = 12 KW.
B. Area Category Method For purposes of the area category method, an "area" is defined as all contiguous spaces that accommodate or are associated with a single primary function as listed in Standards Table
Table 2 – Standards Table for Area Category Method Lighting Power Density Values (Watts/m²) •
PRIMARY FUNCTION
ALLOWED LIGHTING POWER
•
Auditorium
17*
•
Auto repair
13 **
•
Classrooms, lecture, training, vocational room
14
•
Civic Meeting Place
15*
•
Commercial and industrial storage
7.0
•
Convention, conference, multipurpose and meeting centers
16*
•
Corridors, restrooms, stairs and support areas
7.0
•
Dining
12*
•
Electrical, mechanical rooms
8 **
•
Exercise center, gymnasium
11
•
Exhibit, museum
20
•
Financial transactions
13*
•
General commercial and industrial work
•
High bay
12**
•
Low bay
11 **
•
Precision
15 ***
•
Grocery sales
18
•
Housing, Public and Commons Areas
•
Multi-family
11
•
Dormitory, Senior Housing
16
•
Hotel function area
16*
Table 2 – Standards Table for Area Category Method Lighting Power Density Values (Watts/m²) •
Kitchen, food preparation
18
•
Laundry
10
•
Library
•
Reading areas
14
•
Stacks
18
•
Stacks
•
Lobbies
•
Hotel lobby
12*
•
Main entry lobby
18*
•
Locker/dressing room
10
•
Lounge/recreation
12
•
Malls and atria
14*
•
Medical and clinical care
14
•
Office
14
•
Parking garage
5.0
•
Religious worship
16*
•
Retail merchandise sales, wholesale showrooms
•
Tenant lease space
•
Transportation function
•
Theaters
•
Motion picture
•
Performance
16*
•
Waiting area
13*
•
All other
7.0
18
20 11 12 10*
Table 2 – Standards Table for Area Category Method Lighting Power Density Values (Watts/m²) • • • • • • • • • • • • • • • • • •
Lobbies Hotel lobby Main entry lobby Locker/dressing room Lounge/recreation Malls and atria Medical and clinical care Office Parking garage Religious worship Retail merchandise sales, wholesale showrooms Tenant lease space Transportation function Theaters Motion picture Performance Waiting area All other
12* 18* 10 12 14* 14 14 5.0 16* 20 11 12 10* 16* 13* 7.0
Example: Area Category Method A small bank building has the following area distribution: Corridors 80 m2 Main Entry Lobby 20 m2 Financial Transactions 120 m2 Manager’s Office 20 m2
What is the allowed lighting power for this building under the area category method? Answer The following Lighting Power Densities apply (from Table 2): Space LPD Area Allowed Watts Corridors Main Entry Financial Transactions Manager’s Office
Total
7.0 W 16 W 13 W
80 m2 20 m2 120 m2
560 320 1560
14 W
20 m2
280
______ 2720 W
Question •
A 1000-m2 multi-use building is to be built consisting of:
•
A) 50 m2 main entry lobby,
•
B) 200 m2 corridors and restroom,
•
C) 300 m2 grocery store,
•
D) 250 m2 retail, and
•
E) 200 m2 future development.
•
What is the allowed lighting power under the area category method?
Normal Sockets In general sockets can arranged in the free spaces between furniture OR One socket can be assigned for each 5 m The power of a normal socket can be taken as 250 VA
Power Sockets Power sockets can be put in the kitchens and offices The power of the power sockets can be 1 KVA 2 KVA 3 KVA OR as required
UPS Sockets For the information technology equipments it is required to use UPS to supply the sockets supplies these equipments.
Air Conditioning Power Estimation Houses, Pd
= 65 w/m2
Offices, Pd
= 70 w / m2
Shops, Pd
= 90 w / m2
Malls, Pd
= 80 w / m2
Colleges and Schools, Pd = 100 w / m2
Air Conditioning Power Estimation OR From 3.5 to 5.5 ton / 100 m2 Power in Kw = No. of tons x (1.6 – 2.5)
Kw
Elevators The number and type of the elevators will be determined by the architecture engineer. To estimate the power required for the elevators
P elev. = 15 – 25
Kw
Pumps Number and size of the water pump can be determined by the mechanical engineer To estimate the power required for the pumps
1- Water pump power = 5 KVA 2- Fire pump power
= 15 KVA