Lightning Protection -1
Short Description
Lightning Protection Step By step Procedure...
Description
STATE OF QATAR NEW PORT PROJECT STEERING Committee
CONTAINER TERMINAL, INFRASTRUCTURE AND UTILITY BUILDINGS NPP/0026 DOCUMENT TITLE:
CONTAINER TERMINAL 1- BUILDINGS (D&B) PHASE: DETAILED DESIGN LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS Document No.: NPP0026-TCC-CAL-EL-00001
TEYSEER CONTRACTING COMPANY WLL/ CONSOLIDATED CONTRACTORS GROUP S.A.L. (OFFSHORE) (CCC) JV TCC/CCC JV
A Rev
ISSUED FOR REVIEW
Renjith.P
E.Koyess
S.Sayegh
Prepared by
Reviewed by
Approved by
16.02.2014
16.02.2014
16.02.2014
Signature: Date:
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
Page 2 of 97
TABLE OF CONTENTS 1. 2. 3. 3.1 3.1.1 3.2 3.2.1 3.3 3.3.1 3.3.2 3.3.3 3.3.4 4. 4.1 4.2 4.3 5. 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 6.
SCOPE:................................................................................................................................ 3 REFERENCES: ................................................................................................................... 3 EXPLANATION OF TERMS AS PER CLAUSE 4 OF 62305-2:......................................... 3 Damage and Loss ................................................................................................................. 3 Source of Damage ................................................................................................................ 3 Type of damage .................................................................................................................... 4 Type of loss .......................................................................................................................... 4 Risk and Risk Components ...................................................................................................4 Risk...................................................................................................................................... 4 Composition of Risk Components Related to a Structure as Per Clause 4.3 of IEC 62305-2 .5 Risk Components For A Structure Due To Flashes To The Struture...................................... 5 Risk Components For A Structure Due To Flashes Near The Structure.................................6 Risk management: ................................................................................................................ 6 Basic Procedure:................................................................................................................... 6 Tolerable Risk (RT).............................................................................................................. 7 Specific Procedure to Evaluate the Need of Protection.......................................................... 7 The Results Summary........................................................................................................... 8 Administration Building: For Detail Refer Attachment 3 ...................................................... 8 Administration Substation Building (CTAS): For Detail Refer Attachment 4 ....................... 8 Mosque: For Detail Refer Attachment 5 ............................................................................... 9 Workshop Building: For Detail Refer Attachment 6 ........................................................... 10 Washdown Area : For Detail Refer Attachment 7 ............................................................... 10 Driver Reception Building: For Detail Refer Attachment 8 ................................................. 11 Gate Complex Building: For Detail Refer Attachment 9 ..................................................... 12 Quayside Amenities Building: For Detail Refer Attachment 10 ......................................... 13 ATTACHMENTS .............................................................................................................. 14
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NP0026-TCC-CAL-EL-00001
1.
Page 3 of 97
SCOPE:
This document explores the necessity of lightning protection system for the Container Terminal -1 buildings under the Design & Build package of the New Port Project as per contract NPP/0026. The software “FURSE STRIKE RISK version 5.0” will be used in this project to calculate all types of risk and compare it with the tolerable values based on IEC 62305.
2.
REFERENCES: DPCT-TCC-RPT-GEN-00004
Basis of Design
NPP0026-TCC-SPC-EL-00001
Electrical Specification
IEC 62305-1
Protection Against lightning – General Principles
IEC 62305-2
Protection Against lightning – Risk Management
IEC 62305-3
Protection Against lightning – Physical Damage to Structures and life hazard
3.
EXPLANATION OF TERMS AS PER CLAUSE 4 OF IEC 62305-2:
3.1
Damage and Loss
3.1.1 Source of Damage The lightning current is the primary source of damage. The following sources are distinguished by the strike attachment point as per table-1 of IEC 62305-2. S1: Flash to a Structure S2: Flash near a structure S3: Flashes to a service S4: Flashes near a service
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
3.2
Page 4 of 97
Type of damage
A lightning flash may cause damage depending on the characteristics of the object to be protected. Some of the most important characteristics are: type of construction, contents and application, type of service and protection measures provided. For practical application of this risk assessment, it is useful to distinguish between three basic types of damage which can appear as the consequence of lightning flashes. They D1: Injury to living beings D2: Physical damage D3: Failure of electrical and electronic systems
3.2.1 Type of loss Each type of damage, alone or in combination with others, may produce a different consequential loss in the object to be protected. The type of loss that may occur depends on the characteristics of the objects itself and its content. The following types of loss will be taken into account; L1: Loss of human life L2: Loss of service to the public L3: Loss of cultural heritage L4: Loss of economic value (Structure and its content)
3.3
Risk and Risk Components
3.3.1 Risk The Risk R is the value of a probable average annual loss. For each type of loss which may appear in a structure or in a service, the relevant risk will be evaluated. The risks to be evaluated in a structure may be as follows: R1: Risk of loss of human life R2: Risk of loss of service to the public R3: Risk of loss of cultural heritage R4: Risk of loss of economic value
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
Page 5 of 97
The evaluate risks, R, the relevant risk components will be defined and calculated. For the D & B buildings, in general the risk component R1, R2 & R4 is considered for all the buildings. Risk R3 (cultural heritage) is to be considered only for the Mosque. Each risk, R, is the sum of risk components. When calculating a risk, the risk components may be grouped according to the source of damage and type of damage.
3.3.2 Composition of Risk Components Related to a Structure as Per Clause 4.3 of IEC 62305-2
Risk components to be considered for each type of loss in a structure are listed below: R1: Risk of loss of human life: R1 = RA + RB + RC + RM + RU + RV + RW + RZ RC, RM, RW and RZ are not applicable as they are applicable only for structures with risk of explosion and for hospitals with life-saving electrical equipment or other structures when failure of internal systems immediately endangers human life. RU, RV and RW are the risk components to be considered due to the flashes to a line connected to the structure. In this case, all D & B buildings are is not connected to overhead line and only connected through cables, thus the risk components are not applicable. Therefore, R1 = RA + RB R2: Risk of loss of service to the public: R2 = RB + RC + RM + RV + RW + RZ = RB + RC + RM R3: Risk of loss of cultural heritage: R3 = RB + RV R4: Risk of loss of economic value: R4 = RB + RC + RM + RV + RW + RZ = RB + RC + RM The above risk components equations corresponding to each type of loss are based on Page51, Table-3 of IEC 62305-2
3.3.3 Risk Components For A Structure Due To Flashes To The Struture
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
Page 6 of 97
RA: Component related to injury to living beings caused by touch and step voltages in the zones up to 3 m outside the structure. Loss of type L1 and, in the case of Loss of type L1 and, in the case of structures holding livestock, loss of type L4 with possible loss of animals may also arise. RB: Component related to Physical damage caused by dangerous sparking inside the structure triggering fire or explosion, which may also endanger the environment. All type of loss (L1, L2, L3 and L4) may arise. RC: Component related to failure of internal systems caused by LEMP (Lightning Electromagnetic Impulse). Loss of type L2 and L4 could occur in all cases along with type L1 in the case of structures with risk of explosion and hospitals or other structures where failure of internal system immediately endangers human life.
3.3.4 Risk Components For A Structure Due To Flashes Near The Structure
RM: Component related to failure of internal systems caused by LEMP (Lightning Electromagnetic impulse). Loss of type L2 and L4 could occur in all cases along with type L1 in case of structures with risk of explosion and hospitals or other structures where failure of internal system immediately endangers human life.
4. RISK MANAGEMENT: 4.1
Basic Procedure:
The decision to protect a structure or a service against lightning, as well as the protection of selection of protection measures, will be performed according to IEC 62305-2. The following procedure will be applied: Identification of the object to be protected and its characteristics Identification of all the types of loss in the object and the relevant corresponding risk R (R1 to R4) Evaluation of risk R for each type of loss (R1 to R4) Evaluation of need of protection, by comparison of risk R1, R2 and R3 for a structure with the tolerable risk RT Evaluation of cost effectiveness of protection by comparison of the costs of total loss with and without protection measures. In this case, the assessment of components of risk R4 for a structure will be performed in order to evaluate such costs.
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
4.2
Page 7 of 97
Tolerable Risk (RT)
As per Clause 5.4 of IEC 62305-2 Table-7 Page-59, Tolerable risk for Loss of human life or permanent injuries is 10-5. Tolerable risk for Loss of service to the public is 10-3 Tolerable risk for Loss of cultural heritage is 10-3 Tolerable risk for Loss of economic value is 10-3
4.3
Specific Procedure to Evaluate the Need of Protection
As per IEC 62305-1, the following risks will be considered in the evaluation of the need of protection against lightning for a structure: Risks R1, R2 and R3 Besides the need for lightning protection for the object to be protected, it may be useful to evaluate the economic benefits of providing protection measures in order to reduce the economic loss L4. In this case, the risk R4 of loss of economic values will be assessed. The assessment risk R4 allows the evaluation of the cost of the economic loss with and without the adopted protection measures. For each risk to be considered, the following steps will be taken: Identification of the components RX which make up the risk, Calculation of the identified risk components RX, Calculation of the total risk R, Comparison of the risk R with tolerable value RT. If R ≤ RT, lightning protection is not necessary. If R > RT protection measures will be adopted in order to reduce R ≤ RT for all risks to which the object is subjected. In D & B buildings, protection level shall be level four, therefore level four protection will be considered and all risks will be calculated based on that consideration and it will be proved that all the calculated risks are less than the tolerable risks values. Attachment- 3 -10 shows the calculation report and the results.
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
Page 8 of 97
5. THE RESULTS SUMMARY 5.1
Administration Building: For Detail Refer Attachment 3
Type of Risk
Risk
Calculated Value
Tolerable Value
Result
Loss of human life in the structure
R1
8.9429E-06
1.0E-05
Safe
Loss of service to the public in the structure
R2
4.2585E-07
1.0E-03
Safe
Loss of cultural heritage in the structure
R3
2.1293E-08
1.0E-03
Safe
Loss of economic value in the structure
R4
2.3679E-03
1.0E-03
Safe
Conclusion: - As per the calculation R1, R2 and R4 is less than tolerable risk RT (As per table-7, clause 5.4, Page 59 of IEC 62305-2). Hence the Lightning protection for the building is not required. However as an additional precautionary measure LPS Class IV will be provided for Administration & Amenities Building. Lightning protection will be provided through a system of meshed conductors spaced 20m x 20m (Refer page 31, table-2 of IEC 62305-3), and down conductors spaced at 20m (Refer page 39, table-4 of IEC 62305-3).Down conductor will be provided on the wall of the building and will be connected to the earth ring and dedicated earth electrodes. The lightning protection layout (DPCT-DD-EL-CT-GLP-00004) will be developed accordingly.
5.2
Administration Substation Building (CTAS): For Detail Refer Attachment 4
Type of Risk
Risk
Calculated Value
Tolerable Value
Result
Loss of human life in the structure
R1
8.5252E-06
1.0E-05
Safe
Loss of service to the public in the structure
R2
8.8749E-07
1.0E-03
Safe
Loss of cultural heritage in the structure
R3
1.0283E-08
1.0E-03
Safe
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
Loss of economic value in the structure
Page 9 of 97
R4
4.8979E-06
1.0E-03
Safe
Conclusion: - As per the calculation R1, R2 and R4 is less than tolerable risk RT (As per table-7, clause 5.4, Page 59 of IEC 62305-2). Hence the Lightning protection for the building is not required. However as an additional precautionary measure LPS Class IV will be provided for Administration Substation Building. Lightning protection will be provided through a system of meshed conductors spaced 20m x 20m (Refer page 31, table-2 of IEC 62305-3), and down conductors spaced at 20m (Refer page 39, table-4 of IEC 62305-3).Down conductor will be provided on the wall of the building and will be connected to the earth ring and dedicated earth electrodes. The lightning protection layout (DPCT-DD-EL-CT-GLP-00050) will be developed accordingly.
5.3
Mosque: For Detail Refer Attachment 5
Type of Risk
Risk
Calculated Value
Tolerable Value
Result
Loss of human life in the structure
R1
1.9645E-07
1.0E-05
Safe
Loss of service to the public in the structure
R2
1.298E-05
1.0E-03
Safe
Loss of cultural heritage in the structure
R3
6.1391E-09
1.0E-03
Safe
Loss of economic value in the structure
R4
1.5313E-06
1.0E-03
Safe
Conclusion: - As per the calculation R1, R2 and R4 is less than tolerable risk RT (As per table7, clause 5.4, Page 59 of IEC 62305-2). Hence the Lightning protection for the building is not required. However as an additional precautionary measure LPS Class IV will be provided for Mosque. Lightning protection will be provided through a system of meshed conductors spaced 20m x 20m (Refer page 31, table-2 of IEC 62305-3), and down conductors spaced at 20m (Refer page 39, table-4 of IEC 62305-3).Down conductor will be provided on the wall of the building and will be connected to the earth ring and dedicated earth electrodes. The lightning protection layout (DPCT-DD-EL-CT-GLP-00044) will be developed accordingly.
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
5.4
Page 10 of 97
Workshop Building: For Detail Refer Attachment 6
Type of Risk
Risk
Calculated Value
Tolerable Value
Result
Loss of human life in the structure
R1
8.442E-06
1.0E-05
Safe
Loss of service to the public in the structure
R2
1.5906E-05
1.0E-03
Safe
Loss of cultural heritage in the structure
R3
3.15E-09
1.0E-03
Safe
Loss of economic value in the structure
R4
2.2143E-05
1.0E-03
Safe
Conclusion: - As per the calculation R1, R2 and R4 is less than tolerable risk RT (As per table7, clause 5.4, Page 59 of IEC 62305-2). Hence the Lightning protection for the building is not required. However as an additional precautionary measure LPS Class IV will be provided for Workshop Building. Lightning protection will be provided by bonding the roof metallic structures (metallic structures as air-termination component – Refer page-35,caluse 5.2.5, & table-3 of IEC 62305-3) and provide bonding to the meshed conductors spaced 20m x 20m (Refer page 31, table-2 of IEC 62305-3), at the concrete roof area and down conductors spaced at 20m (Refer page 39, table-4 of IEC 62305-3).Down conductor will be provided on the wall of the structure / building and will be connected to the earth ring and dedicated earth electrodes. The lightning protection layout (DPCT-DD-EL-CT-GLP-00024) will be developed accordingly.
5.5
Washdown Area : For Detail Refer Attachment 7 a) REEFER WASH DOWN AREA
Type of Risk
Risk
Calculated Value
Tolerable Value
Result
Loss of human life in the structure
R1
2.2491E-06
1.0E-05
Safe
Loss of service to the public in the structure
R2
3.9656E-05
1.0E-03
Safe
Loss of cultural heritage in the
R3
1.6784E-08
1.0E-03
Safe
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
Page 11 of 97
structure R4
8.1449E-05
1.0E-03
Safe
Type of Risk
Risk
Calculated Value
Tolerable Value
Result
Loss of human life in the structure
R1
6.0522E-06
1.0E-05
Safe
Loss of service to the public in the structure
R2
9.1465E-05
1.0E-03
Safe
Loss of cultural heritage in the structure
R3
9.0331E-08
1.0E-03
Safe
Loss of economic value in the structure
R4
3.1639E-04
1.0E-03
Safe
Loss of economic value in the structure b) RTG WASH DOWN AREA
Conclusion: - As per the calculation R1, R2 and R4 is less than tolerable risk RT (As per table-7, clause 5.4, Page 59 of IEC 62305-2). Hence the Lightning protection for the building is not required. However as an additional precautionary measure LPS Class IV will be provided for Reefer & RTG Wash-down Area Buildings. Lightning protection will be provided by bonding the roof metallic structures (metallic structures as air-termination component – Refer page35,caluse 5.2.5, & table-3 of IEC 62305-3) and provide bonding to the meshed conductors spaced 20m x 20m (Refer page 31, table-2 of IEC 62305-3), at the concrete roof area and down conductors spaced at 20m (Refer page 39, table-4 of IEC 62305-3).Down conductor will be provided on the wall of the structure / building and will be connected to the earth ring and dedicated earth electrodes. The lightning protection layout (DPCT-DD-EL-CT-GLP-00029) will be developed accordingly.
5.6
Driver Reception Building: For Detail Refer Attachment 8
Type of Risk
Risk
Calculated Value
Tolerable Value
Result
Loss of human life in the structure
R1
3.9309E-06
1.0E-05
Safe
Loss of service to the public in the
R2
1.2426E-05
1.0E-03
Safe
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
Page 12 of 97
structure Loss of cultural heritage in the structure
R3
2.3398E-08
1.0E-03
Safe
Loss of economic value in the structure
R4
1.4251E-05
1.0E-03
Safe
Conclusion: - As per the calculation R1, R2 and R4 is less than tolerable risk RT (As per table7, clause 5.4, Page 59 of IEC 62305-2). Hence the Lightning protection for the building is not required. However as an additional precautionary measure LPS Class IV will be provided for Driver Reception Building. Lightning protection will be provided through a system of meshed conductors spaced 20m x 20m (Refer page 31, table-2 of IEC 62305-3), and down conductors spaced at 20m (Refer page 39, table-4 of IEC 62305-3).Down conductor will be provided on the wall of the building and will be connected to the earth ring and dedicated earth electrodes. The lightning protection layout (DPCT-DD-EL-CT-GLP-00035) will be developed accordingly.
5.7
Gate Complex Building: For Detail Refer Attachment 9 a) GATE COMPLEX – CANOPY AREA
Type of Risk
Risk
Calculated Value
Tolerable Value
Result
Loss of human life in the structure
R1
1.3092E-06
1.0E-05
Safe
Loss of service to the public in the structure
R2
1.7168E-05
1.0E-03
Safe
Loss of cultural heritage in the structure
R3
1.5585E-07
1.0E-03
Safe
Loss of economic value in the structure
R4
1.7324E-05
1.0E-03
Safe
Tolerable Value
Result
b) GATE MANAGER AND FACILITIES BUILDING
Type of Risk
Risk
Calculated Value
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
Page 13 of 97
Loss of human life in the structure
R1
6.2225E-07
1.0E-05
Safe
Loss of service to the public in the structure
R2
8.768E-06
1.0E-03
Safe
Loss of cultural heritage in the structure
R3
3.7039E-09
1.0E-03
Safe
Loss of economic value in the structure
R4
8.8421E-06
1.0E-03
Safe
Conclusion: - As per the calculation R1, R2 and R4 is less than tolerable risk RT (As per table7, clause 5.4, Page 59 of IEC 62305-2). Hence the Lightning protection for the building is not required. However as an additional precautionary measure LPS Class IV will be provided for Gate complex structures and Gate Manager Facilities Buildings. Lightning protection will be provided by bonding the roof metallic structures (metallic structures as air-termination component – Refer page-35,caluse 5.2.5, & table-3 of IEC 62305-3) and provide bonding to the meshed conductors spaced 20m x 20m (Refer page 31, table-2 of IEC 62305-3), at the concrete roof area and down conductors spaced at 20m (Refer page 39, table-4 of IEC 62305-3).Down conductor will be provided on the wall of the structure / building and will be connected to the earth ring and dedicated earth electrodes. The lightning protection layout (DPCT-DD-EL-CT-GLP-00009 & DPCTDD-EL-CT-GLP-00056) will be developed accordingly.
5.8
Quayside Amenities Building: For Detail Refer Attachment 10
Type of Risk
Risk
Calculated Value
Tolerable Value
Result
Loss of human life in the structure
R1
1.6572E-06
1.0E-05
Safe
Loss of service to the public in the structure
R2
3.943E-05
1.0E-03
Safe
Loss of cultural heritage in the structure
R3
9.8643E-08
1.0E-03
Safe
Loss of economic value in the structure
R4
3.9628E-05
1.0E-03
Safe
TEYSEER CONTRACTING COMPANY WLL / CONSOLIDATED CONTRACTORS GROUP S.A.L (OFFSHORE) (CCC) JV
LIGHTNING PROTECTION RISK ASSESSMENT CALCULATIONS DOC No. NPP0026-TCC-CAL-EL-00001
Page 14 of 97
Conclusion: - As per the calculation R1, R2 and R4 is less than tolerable risk RT (As per table7, clause 5.4, Page 59 of IEC 62305-2). Hence the Lightning protection for the building is not required. However as an additional precautionary measure LPS Class IV will be provided for Quayside & Amenities Building – North & South. Lightning protection will be provided through a system of meshed conductors spaced 20m x 20m (Refer page 31, table-2 of IEC 62305-3), and down conductors spaced at 20m (Refer page 39, table-4 of IEC 62305-3).Down conductor will be provided on the wall of the building and will be connected to the earth ring and dedicated earth electrodes. The lightning protection layout (DPCT-DD-EL-CT-GLP-00014 & DPCT-DDEL-CT-GLP-00018) will be developed accordingly
6. ATTACHMENTS Attachment 1:- Isokeraunic Map (Map showing thunderstorm days per year throughout the world) Attachment 2:- Mesh type air termination system on flat roof structure. (Extract from IEC 623053) Attachment 3:- LIGHTNING RISK CALCULATION for Administration & Amenities Building. Attachment 4:- LIGHTNING RISK CALCULATION for Administration Substation Building. Attachment 5:- LIGHTNING RISK CALCULATION for Mosque Building. Attachment 6:- LIGHTNING RISK CALCULATION for Workshop Building. Attachment 7:- LIGHTNING RISK CALCULATION for Wash-down Area Buildings. Attachment 8:- LIGHTNING RISK CALCULATION for Driver Reception Building. Attachment 9:- LIGHTNING RISK CALCULATION for Gate area Buildings. Attachment 10:- LIGHTNING RISK CALCULATION for Quayside Amenities Building.
Attachment 1:- Isokeraunic Map (Map showing thunderstorm days per year throughout the world)
29 Figure 3.6: World Thunderstorm days map (BS EN 62305-2 Figure NK.2)
NPP0026-TCC-CAL-EL-00001
www.furse.com
REV. A
Page 15 of 97
World thunderstorm days map | BS EN 62305-2
Attachment 2:- Mesh type air termination system on flat roof structure. (Extract from IEC 62305-3)
62305-3 © IEC:2006
– 187 –
w
IEC 2142/05
Figure E.22a – LPS air-termination on a flat-roof structure
w
IEC 2143/05
Key w Mesh size
NOTE
The mesh size should comply with Table 2.
--``,`,`,`,,`````,``,,`,`,,`,```-`-`,,`,,`,`,,`---
Figure E.22b – LPS air-termination on a sloped-roof structure
NPP0026-TCC-CAL-EL-00001 Copyright International Electrotechnical Commission Provided by IHS under license with IEC No reproduction or networking permitted without license from IHS
REV. A Licensee=Oman/5940240038, User=Matuszewski, Leszek Not for Resale, 01/19/2010 03:47:44 MST
Page 16 of 97
Attachment 3 - ADMINISTRATION AMENITITES BUILDING File: Administration&and Amenities Building.src
BS EN 62305-2:2006 Risk Management Calculations Project details Project name:
CONTAINER TERMINAL - 1 (D&B)
Project title:
ADMINISTRATION & AMENITIES BUILDING
Project address: Project ref: Calculation ref: Calculation notes: Project author: Created:
15 February 2014
Modified:
15 February 2014
Case details Case name:
Administration and Amenities Building
Case title: Created:
05 February 2014
Modified:
10 February 2014
Case notes:
Primary risk totals
R1_T
8.9429E-06
Risk of loss of human life in the structure The tolerable risk is not exceeded, no additional protection required
R2_T
4.2585E-07
Risk of loss of service to the public in the structure The tolerable risk is not exceeded, no additional protection required
R3_T
2.1293E-08
Risk of loss of cultural heritage in the structure The tolerable risk is not exceeded, no additional protection required
R4_T
2.3679E-03
Risk of loss of economic value in the structure
StrikeRisk Version 5.0 Run identification 2/15/2014 1:27:50PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 1 of 11 Page 17 of 97
File: Administration and Amenities Building.src
Protection system design parameters LPS
LPL IV
Protect the structure with a Class LPL IV Lightning Protection System in accordance with BS EN 62305-3
Imax
100.00kA
Maximum peak current
97.00%
Probability that lightning current parameters are smaller than the maximum value defined above
16.00kA
Minimum peak current
84.00%
Probability that lightning current parameters are greater than the minimum value defined above
60.00m
Radius of rolling sphere
16.67kA
Maximum peak current of equipotential bonding SPD's for each of 'n' lines defined (based upon simple current division concept)
Imin
ISPD
NOTE: The worst case surge that could be expected on a two-wire telephone or data line is 2.5kA (10/350 µs) per line (Category D test to BS EN 61643-21) to earth or 5 kA (10/350 µs) per pair.
Line 1
Protect Line 1 at its entrance to the structure with a standard equipotential bonding SPD (rated to ISPD above) in accordance with BS EN 62305-3 NOTE: Where SPDs are required but an LPS is not (ISPD = 0), protect overhead lines with Type 1 SPDs (mains 12.5kA 10/350µs, data/telecom 2.5kA 10/350µs), protect underground lines with overvoltage or Type 2 SPDs (tested with an 8/20 µs waveform)
Line 2
Protect Line 2 at its entrance to the structure with a standard equipotential bonding SPD (rated to ISPD above) in accordance with BS EN 62305-3 NOTE: Where SPDs are required but an LPS is not (ISPD = 0), protect overhead lines with Type 1 SPDs (mains 12.5kA 10/350µs, data/telecom 2.5kA 10/350µs), protect underground lines with overvoltage or Type 2 SPDs (tested with an 8/20 µs waveform)
Line 3
Protect Line 3 at its entrance to the structure with a standard equipotential bonding SPD (rated to ISPD above) in accordance with BS EN 62305-3 NOTE: Where SPDs are required but an LPS is not (ISPD = 0), protect overhead lines with Type 1 SPDs (mains 12.5kA 10/350µs, data/telecom 2.5kA 10/350µs), protect underground lines with overvoltage or Type 2 SPDs (tested with an 8/20 µs waveform)
Environment Ng Cd Ce
1.00
Lightning flash density (Flashes/km²/year)
0.50
Location factor
0.10
Environmental factor
Rho
3.00 W m
Soil resistivity (Ohm metres)
StrikeRisk Version 5.0 Run identification 2/15/2014 1:27:50PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 2 of 11 Page 18 of 97
File: Administration and Amenities Building.src
Assessment of Ax - Collection areas (BS EN 62305-2 Annex A.2) Ad/b Am Al (L1) Al (L2) Al (L3) Al Ai (L1) Ai (L2) Ai (L3) Ai
21,287.71 m²
Collection area of primary structure
236,679.06 m²
Collection area of surrounding ground
10.74 m²
Collection area of flashes striking line 1
19.40 m²
Collection area of flashes striking line 2
36.72 m²
Collection area of flashes striking line 3
66.86 m²
Total collection area of flashes striking lines
2,814.58 m²
Collection area of flashes near line 1
3,031.09 m²
Collection area of flashes near line 2
3,464.10 m²
Collection area of flashes near line 3
9,309.77 m²
Total collection area of flashes near lines
Structures Primary structure Structure ID:
- Rectangular with a flat roof
Lb Wb Hb
56.40 m
Length of primary structure
21.80 m
Width of primary structure
19.60 m
Height of primary structure
Secondary structures
StrikeRisk Version 5.0 Run identification 2/15/2014 1:27:50PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 3 of 11 Page 19 of 97
File: Administration and Amenities Building.src
Lines Line 1
LV Cables Incomer 1
KS3 (L1) PSPD (L1)
0.02
Factor relevant to the characteristics of internal wiring for line 1
0.03
Probability of failure of internal systems or a service when SPDs are provided for equipotential bonding (in accordance with BS EN 62305-3) for line 1
PSPDc (L1)
1.00
Probability of failure of internal systems or a service when coordinated SPDs are provided (in accordance with BS EN 62305-4) for line 1
Ct (L1) Cdc (L1) Uw (L1) Lc (L1) Hc (L1)
1.00
Correction factor for a hv/lv transformer on line 1
0.25
Location factor for line 1
2.50 kV
Rated impulse withstand voltage of a system connected to line 1
65.00 m
Length of line 1
0.00 m
Height of the conductors above ground for line 1
Line 2
LV Cable Incomer 2
KS3 (L2) PSPD (L2)
1.00
Factor relevant to the characteristics of internal wiring for line 2
0.03
Probability of failure of internal systems or a service when SPDs are provided for equipotential bonding (in accordance with BS EN 62305-3) for line 2
PSPDc (L2)
1.00
Probability of failure of internal systems or a service when coordinated SPDs are provided (in accordance with BS EN 62305-4) for line 2
Ct (L2) Cdc (L2) Uw (L2) Lc (L2) Hc (L2)
1.00
Correction factor for a hv/lv transformer on line 2
0.25
Location factor for line 2
2.50 kV
Rated impulse withstand voltage of a system connected to line 2
70.00 m
Length of line 2
0.00 m
Height of the conductors above ground for line 2
Line 3
LV Cable Incomer 3
KS3 (L3) PSPD (L3)
1.00
Factor relevant to the characteristics of internal wiring for line 3
0.03
Probability of failure of internal systems or a service when SPDs are provided for equipotential bonding (in accordance with BS EN 62305-3) for line 3
PSPDc (L3)
1.00
Probability of failure of internal systems or a service when coordinated SPDs are provided (in accordance with BS EN 62305-4) for line 3
Ct (L3) Cdc (L3) Uw (L3) Lc (L3) Hc (L3)
1.00
Correction factor for a hv/lv transformer on line 3
0.25
Location factor for line 3
2.50 kV
Rated impulse withstand voltage of a system connected to line 3
80.00 m
Length of line 3
0.00 m
Height of the conductors above ground for line 3
StrikeRisk Version 5.0 Run identification 2/15/2014 1:27:50PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 4 of 11 Page 20 of 97
File: Administration and Amenities Building.src
Zones Factor
Zone 1
Zone 2
rp
2.0E-01
5.0E-01
rf
1.0E-02
1.0E-02
ra / ru
1.0E-02
1.0E-02
hz1
5
2
hz4
1
1
Lt1
1.0E-04
0.0E00
Lf1
4.2E-01
4.2E-01
Lo1
0.0E00
0.0E00
Lf2
1.0E-01
1.0E-01
Lo2
0.0E00
1.0E-02
Lf3
1.0E-02
1.0E-02
Lt4
0.0E00
0.0E00
Lf4
2.0E-01
2.0E-01
Lo4
1.0E-02
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Assessment of Nx - Annual number of dangerous events (BS EN 62305-2 Annex A) Nd/b Nm Nl (L1) Nl (L2) Nl (L3) Ni (L1) Ni (L2) Ni (L3)
0.010644
Average number of flashes to main structure
0.226035
Average number of flashes to surrounding ground
0.000003
Average number of flashes to line 1
0.000005
Average number of flashes to line 2
0.000009
Average number of flashes to line 3
0.000281
Average number of flashes near line 1
0.000303
Average number of flashes near line 2
0.000346
Average number of flashes near line 3
StrikeRisk Version 5.0 Run identification 2/15/2014 1:27:50PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 5 of 11 Page 21 of 97
File: Administration and Amenities Building.src
Assessment of Px - Probability of damage for a structure (BS EN 62305-2 Annex NB) Factor
Zone 1
Zone 2
PA
0
0
Zone 3
Zone 4
Zone 5
Zone 6
PB
0.2
PC (L1)
1
PC (L2)
1
PC (L3)
1
PC
1
KS1
1
KS2
1
Zone 8
Zone 9
Zone 10
NA
KS4 (L1)
0.6
KS4 (L2)
0.6
KS4 (L3)
0.6
KMS (L1)
1.2E-02
NA
KMS (L2)
6.0E-01
NA
KMS (L3)
6.0E-01
NA
PMS (L1)
1.0E-04
NA
PMS (L2)
1.08E00
NA
PMS (L3)
1.08E00
NA
PM (L1)
1.0E-04
NA
PM (L2)
1.0E00
NA
PM (L3)
1.0E00
NA
PM
1.0E00
NA
PLD (L1)
6.0E-01
PLD (L2)
6.0E-01
PLD (L3)
6.0E-01
PLI (L1)
2.0E-02
PLI (L2)
2.0E-02
PLI (L3)
2.0E-02
PU (L1)
3.0E-02
PU (L2)
3.0E-02
PU (L3)
3.0E-02
PV (L1)
3.0E-02
PV (L2)
3.0E-02
PV (L3)
3.0E-02
PW (L1)
6.0E-01
StrikeRisk Version 5.0 Run identification 2/15/2014 1:27:50PM NPP0026-TCC-CAL-EL-00001
Zone 7
REV. A
Page 6 of 11 Page 22 of 97
File: Administration and Amenities Building.src
PW (L2)
6.0E-01
PW (L3)
6.0E-01
PZ (L1)
2.0E-02
PZ (L2)
2.0E-02
PZ (L3)
2.0E-02
Assessment of Lx - Amount of loss for a structure (BS EN 62305-2 Annex NC) Loss factors relevant to R1 Factor
Zone 1
Zone 2
LA
1.0E-06
0.0E00
LB
4.2E-03
4.2E-03
LC
0.0E00
0.0E00
LM
0.0E00
0.0E00
LU
1.0E-06
0.0E00
LV
4.2E-03
4.2E-03
LW
0.0E00
0.0E00
LZ
0.0E00
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Loss factors relevant to R2 Factor
Zone 1
Zone 2
LB
2.0E-04
5.0E-04
LC
0.0E00
1.0E-02
LM
0.0E00
1.0E-02
LV
2.0E-04
5.0E-04
LW
0.0E00
1.0E-02
LZ
0.0E00
1.0E-02
Loss factors relevant to R3 Factor
Zone 1
Zone 2
LB
1.0E-05
2.5E-05
LV
1.0E-05
2.5E-05
StrikeRisk Version 5.0 Run identification 2/15/2014 1:27:50PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 7 of 11 Page 23 of 97
File: Administration and Amenities Building.src
Loss factors relevant to R4 Factor
Zone 1
Zone 2
LA
0.0E00
0.0E00
LB
4.0E-04
1.0E-03
LC
1.0E-02
0.0E00
LM
1.0E-02
0.0E00
LU
0.0E00
0.0E00
LV
4.0E-04
1.0E-03
LW
1.0E-02
0.0E00
LZ
1.0E-02
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Assessment of Rx - Risk components Risk components relevant to R1 Factor
Zone 1
Zone 2
RA
0.0E00
0.0E00
RB
8.9408E-06
0.0E00
RC
0.0E00
0.0E00
RM
0.0E00
0.0E00
RU (L1)
0.0E00
0.0E00
RU (L2)
0.0E00
0.0E00
RU (L3)
0.0E00
0.0E00
RV (L1)
3.3827E-10
0.0E00
RV (L2)
6.1107E-10
0.0E00
RV (L3)
1.1567E-09
0.0E00
RW (L1)
0.0E00
0.0E00
RW (L2)
0.0E00
0.0E00
RW (L3)
0.0E00
0.0E00
RZ (L1)
0.0E00
0.0E00
RZ (L2)
0.0E00
0.0E00
RZ (L3)
0.0E00
0.0E00
Zone 3
Zone 4
StrikeRisk Version 5.0 Run identification 2/15/2014 1:27:50PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 8 of 11 Page 24 of 97
File: Administration and Amenities Building.src
Risk components relevant to R2 Factor
Zone 1
Zone 2
RB
4.2575E-07
0.0E00
RC
0.0E00
0.0E00
RM
0.0E00
0.0E00
RV (L1)
1.6108E-11
0.0E00
RV (L2)
2.9098E-11
0.0E00
RV (L3)
5.5079E-11
0.0E00
RW (L1)
0.0E00
0.0E00
RW (L2)
0.0E00
0.0E00
RW (L3)
0.0E00
0.0E00
RZ (L1)
0.0E00
0.0E00
RZ (L2)
0.0E00
0.0E00
RZ (L3)
0.0E00
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Risk components relevant to R3 Factor
Zone 1
Zone 2
RB
2.1288E-08
0.0E00
RV (L1)
8.054E-13
0.0E00
RV (L2)
1.4549E-12
0.0E00
RV (L3)
2.754E-12
0.0E00
Zone 3
StrikeRisk Version 5.0 Run identification 2/15/2014 1:27:50PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 9 of 11 Page 25 of 97
File: Administration and Amenities Building.src
Risk components relevant to R4 Factor
Zone 1
Zone 2
RA
0.0E00
0.0E00
RB
8.5151E-07
0.0E00
RC
1.0644E-04
0.0E00
RM
2.2604E-03
0.0E00
RU (L1)
0.0E00
0.0E00
RU (L2)
0.0E00
0.0E00
RU (L3)
0.0E00
0.0E00
RV (L1)
3.2216E-11
0.0E00
RV (L2)
5.8197E-11
0.0E00
RV (L3)
1.1016E-10
0.0E00
RW (L1)
1.6108E-08
0.0E00
RW (L2)
2.9098E-08
0.0E00
RW (L3)
5.5079E-08
0.0E00
RZ (L1)
5.5755E-08
0.0E00
RZ (L2)
5.9652E-08
0.0E00
RZ (L3)
6.7446E-08
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Primary risk totals R1_T R2_T R3_T R4_T
8.9429E-06
Risk of loss of human life in the structure
4.2585E-07
Risk of loss of service to the public in the structure
2.1293E-08
Risk of loss of cultural heritage in the structure
2.3679E-03
Risk of loss of economic value in the structure
Primary risk with respect to source of damage R1_D R2_D R3_D R4_D R1_I
8.9408E-06
Risk of loss of human life in the structure due to flashes to the structure (S1)
4.2575E-07
Risk of loss of service to the public in the structure due to flashes to the structure (S1)
2.1288E-08
Risk of loss of cultural heritage in the structure due to flashes to the structure (S1)
1.0729E-04
Risk of loss of economic value in the structure due to flashes to the structure (S1)
2.106E-09
Risk of loss of human life in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R2_I
1.0029E-10
Risk of loss of service to the public in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R3_I
5.0143E-12
Risk of loss of cultural heritage in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R4_I
2.2606E-03
Risk of loss of economic value in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
StrikeRisk Version 5.0 Run identification 2/15/2014 1:27:50PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 10 of 11 Page 26 of 97
File: Administration and Amenities Building.src
Primary risk with respect to type of damage R1_S R2_S R3_S R4_S R1_F R2_F R3_F R4_F R1_O R2_O R3_O R4_O
0.E00
Risk of loss of human life in the structure due to injury to living beings (D1)
0.E00
Risk of loss of service to the public in the structure due to injury to living beings (D1)
0.E00
Risk of loss of cultural heritage in the structure due to injury to living beings (D1)
0.E00
Risk of loss of economic value in the structure due to injury to living beings (D1)
8.9429E-06
Risk of loss of human life in the structure due to physical damage (D2)
4.2585E-07
Risk of loss of service to the public in the structure due to physical damage (D2)
8.9429E-06
Risk of loss of cultural heritage in the structure due to physical damage (D2)
8.5171E-07
Risk of loss of economic value in the structure due to physical damage (D2)
0.E00
Risk of loss of human life in the structure due to failure of internal systems (D3)
0.E00
Risk of loss of service to the public in the structure due to failure of internal systems (D3)
0.E00
Risk of loss of cultural heritage in the structure due to failure of internal systems (D3)
2.3671E-03
Risk of loss of economic value in the structure due to failure of internal systems (D3)
StrikeRisk Version 5.0 Run identification 2/15/2014 1:27:50PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 11 of 11 Page 27 of 97
Attachment 4 - ADMINISTRATION SUBSTATION File: Administration Substation.src (CTAS)
BS EN 62305-2:2006 Risk Management Calculations Project details Project name:
CONTAINER TERMINAL -1 (D&B)
Project title:
ADMINISTRATION SUBSTATION (CTAS)
Project address: Project ref: Calculation ref: Calculation notes: Project author: Created:
13 February 2014
Modified:
13 February 2014
Case details Case name:
Administration Substation (CTAS)
Case title:
Substation (CTAS)
Created:
08 February 2014
Modified:
12 February 2014
Case notes:
Primary risk totals
R1_T
8.5252E-06
Risk of loss of human life in the structure The tolerable risk is not exceeded, no additional protection required
R2_T
8.8749E-07
Risk of loss of service to the public in the structure The tolerable risk is not exceeded, no additional protection required
R3_T
1.0283E-08
Risk of loss of cultural heritage in the structure The tolerable risk is not exceeded, no additional protection required
R4_T
4.8979E-06
Risk of loss of economic value in the structure
StrikeRisk Version 5.0 Run identification 2/13/2014 6:31:54PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 1 of 11 Page 28 of 97
File: Administration Substation.src
Protection system design parameters LPS
LPL IV
Protect the structure with a Class LPL IV Lightning Protection System in accordance with BS EN 62305-3
Imax
100.00kA
Maximum peak current
97.00%
Probability that lightning current parameters are smaller than the maximum value defined above
16.00kA
Minimum peak current
84.00%
Probability that lightning current parameters are greater than the minimum value defined above
60.00m
Radius of rolling sphere
16.67kA
Maximum peak current of equipotential bonding SPD's for each of 'n' lines defined (based upon simple current division concept)
Imin
ISPD
NOTE: The worst case surge that could be expected on a two-wire telephone or data line is 2.5kA (10/350 µs) per line (Category D test to BS EN 61643-21) to earth or 5 kA (10/350 µs) per pair.
Line 1
Protect Line 1 at its entrance to the structure with a enhanced equipotential bonding SPD (rated to ISPD above) in accordance with BS EN 62305-3 NOTE: Where SPDs are required but an LPS is not (ISPD = 0), protect overhead lines with Type 1 SPDs (mains 12.5kA 10/350µs, data/telecom 2.5kA 10/350µs), protect underground lines with overvoltage or Type 2 SPDs (tested with an 8/20 µs waveform)
Protect all internal systems connected to Line 1 with a coordinated set of enhanced SPDs in accordance with BS EN 62305-4 Line 2
Protect Line 2 at its entrance to the structure with a enhanced equipotential bonding SPD (rated to ISPD above) in accordance with BS EN 62305-3 NOTE: Where SPDs are required but an LPS is not (ISPD = 0), protect overhead lines with Type 1 SPDs (mains 12.5kA 10/350µs, data/telecom 2.5kA 10/350µs), protect underground lines with overvoltage or Type 2 SPDs (tested with an 8/20 µs waveform)
Protect all internal systems connected to Line 2 with a coordinated set of enhanced SPDs in accordance with BS EN 62305-4 Line 3
Protect Line 3 at its entrance to the structure with a enhanced equipotential bonding SPD (rated to ISPD above) in accordance with BS EN 62305-3 NOTE: Where SPDs are required but an LPS is not (ISPD = 0), protect overhead lines with Type 1 SPDs (mains 12.5kA 10/350µs, data/telecom 2.5kA 10/350µs), protect underground lines with overvoltage or Type 2 SPDs (tested with an 8/20 µs waveform)
Protect all internal systems connected to Line 3 with a coordinated set of enhanced SPDs in accordance with BS EN 62305-4
Environment Ng Cd Ce
1.00
Lightning flash density (Flashes/km²/year)
0.25
Location factor
0.50
Environmental factor
Rho
3.00 W m
Soil resistivity (Ohm metres)
StrikeRisk Version 5.0 Run identification 2/13/2014 6:31:54PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 2 of 11 Page 29 of 97
File: Administration Substation.src
Assessment of Ax - Collection areas (BS EN 62305-2 Annex A.2) Ad/b Am Al (L1) Al (L2) Al (L3) Al Ai (L1) Ai (L2) Ai (L3) Ai
4,111.87 m²
Collection area of primary structure
212,368.93 m²
Collection area of surrounding ground
127.22 m²
Collection area of flashes striking line 1
127.22 m²
Collection area of flashes striking line 2
40.62 m²
Collection area of flashes striking line 3
295.05 m²
Total collection area of flashes striking lines
4,330.13 m²
Collection area of flashes near line 1
4,330.13 m²
Collection area of flashes near line 2
2,165.06 m²
Collection area of flashes near line 3
10,825.32 m²
Total collection area of flashes near lines
Structures Primary structure Structure ID:
- Rectangular with a flat roof
Lb Wb Hb
21.30 m
Length of primary structure
10.30 m
Width of primary structure
8.85 m
Height of primary structure
Secondary structures
StrikeRisk Version 5.0 Run identification 2/13/2014 6:31:54PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 3 of 11 Page 30 of 97
File: Administration Substation.src
Lines Line 1
Main HV Cable entry (Ring circuit 1)
KS3 (L1) PSPD (L1)
0.00
Factor relevant to the characteristics of internal wiring for line 1
0.00
Probability of failure of internal systems or a service when SPDs are provided for equipotential bonding (in accordance with BS EN 62305-3) for line 1
PSPDc (L1)
0.00
Probability of failure of internal systems or a service when coordinated SPDs are provided (in accordance with BS EN 62305-4) for line 1
Ct (L1) Cdc (L1) Uw (L1) Lc (L1) Hc (L1)
0.20
Correction factor for a hv/lv transformer on line 1
0.25
Location factor for line 1
6.00 kV
Rated impulse withstand voltage of a system connected to line 1
100.00 m
Length of line 1
0.00 m
Height of the conductors above ground for line 1
Line 2
Main HV Cable entry (Ring circuit 2)
KS3 (L2) PSPD (L2)
0.00
Factor relevant to the characteristics of internal wiring for line 2
0.00
Probability of failure of internal systems or a service when SPDs are provided for equipotential bonding (in accordance with BS EN 62305-3) for line 2
PSPDc (L2)
0.00
Probability of failure of internal systems or a service when coordinated SPDs are provided (in accordance with BS EN 62305-4) for line 2
Ct (L2) Cdc (L2) Uw (L2) Lc (L2) Hc (L2)
0.20
Correction factor for a hv/lv transformer on line 2
0.25
Location factor for line 2
6.00 kV
Rated impulse withstand voltage of a system connected to line 2
100.00 m
Length of line 2
0.00 m
Height of the conductors above ground for line 2
Line 3
LV Cable - Standby Generator
KS3 (L3) PSPD (L3)
0.00
Factor relevant to the characteristics of internal wiring for line 3
0.00
Probability of failure of internal systems or a service when SPDs are provided for equipotential bonding (in accordance with BS EN 62305-3) for line 3
PSPDc (L3)
0.00
Probability of failure of internal systems or a service when coordinated SPDs are provided (in accordance with BS EN 62305-4) for line 3
Ct (L3) Cdc (L3) Uw (L3) Lc (L3) Hc (L3)
1.00
Correction factor for a hv/lv transformer on line 3
0.25
Location factor for line 3
2.50 kV
Rated impulse withstand voltage of a system connected to line 3
50.00 m
Length of line 3
0.00 m
Height of the conductors above ground for line 3
StrikeRisk Version 5.0 Run identification 2/13/2014 6:31:54PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 4 of 11 Page 31 of 97
File: Administration Substation.src
Zones Factor
Zone 1
Zone 2
rp
5.0E-01
5.0E-01
rf
1.0E-02
1.0E-02
ra / ru
1.0E-02
1.0E-04
hz1
2
2
hz4
20
1
Lt1
0.0E00
0.0E00
Lf1
3.3E-01
3.3E-01
Lo1
1.0E-01
1.0E-01
Lf2
1.0E-01
1.0E-01
Lo2
1.0E-02
1.0E-02
Lf3
1.0E-02
1.0E-01
Lt4
0.0E00
0.0E00
Lf4
2.0E-01
5.0E-01
Lo4
1.0E-02
1.0E-02
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Assessment of Nx - Annual number of dangerous events (BS EN 62305-2 Annex A) Nd/b Nm Nl (L1) Nl (L2) Nl (L3) Ni (L1) Ni (L2) Ni (L3)
0.001028
Average number of flashes to main structure
0.211341
Average number of flashes to surrounding ground
0.000006
Average number of flashes to line 1
0.000006
Average number of flashes to line 2
0.000010
Average number of flashes to line 3
0.000433
Average number of flashes near line 1
0.000433
Average number of flashes near line 2
0.001083
Average number of flashes near line 3
StrikeRisk Version 5.0 Run identification 2/13/2014 6:31:54PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 5 of 11 Page 32 of 97
File: Administration Substation.src
Assessment of Px - Probability of damage for a structure (BS EN 62305-2 Annex NB) Factor
Zone 1
Zone 2
PA
0
0
Zone 3
Zone 4
Zone 5
Zone 6
PB
0.2
PC (L1)
0.003
PC (L2)
0.003
PC (L3)
0.003
PC
8.97302700000002E-03
KS1
1
KS2
1
Zone 8
Zone 9
Zone 10
NA
KS4 (L1)
0.25
KS4 (L2)
0.25
KS4 (L3)
0.6
KMS (L1)
5.0E-05
NA
KMS (L2)
5.0E-05
NA
KMS (L3)
1.2E-04
NA
PMS (L1)
1.0E-04
NA
PMS (L2)
1.0E-04
NA
PMS (L3)
1.0E-04
NA
PM (L1)
1.0E-04
NA
PM (L2)
1.0E-04
NA
PM (L3)
1.0E-04
NA
PM
2.9997E-04
NA
PLD (L1)
1.0E-01
PLD (L2)
1.0E-01
PLD (L3)
6.0E-01
PLI (L1)
4.0E-03
PLI (L2)
4.0E-03
PLI (L3)
2.0E-02
PU (L1)
3.0E-03
PU (L2)
3.0E-03
PU (L3)
3.0E-03
PV (L1)
3.0E-03
PV (L2)
3.0E-03
PV (L3)
3.0E-03
PW (L1)
3.0E-03
StrikeRisk Version 5.0 Run identification 2/13/2014 6:31:54PM NPP0026-TCC-CAL-EL-00001
Zone 7
REV. A
Page 6 of 11 Page 33 of 97
File: Administration Substation.src
PW (L2)
3.0E-03
PW (L3)
3.0E-03
PZ (L1)
3.0E-03
PZ (L2)
3.0E-03
PZ (L3)
3.0E-03
Assessment of Lx - Amount of loss for a structure (BS EN 62305-2 Annex NC) Loss factors relevant to R1 Factor
Zone 1
Zone 2
LA
0.0E00
0.0E00
LB
3.3E-03
3.3E-03
LC
1.0E-01
1.0E-01
LM
1.0E-01
1.0E-01
LU
0.0E00
0.0E00
LV
3.3E-03
3.3E-03
LW
1.0E-01
1.0E-01
LZ
1.0E-01
1.0E-01
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Loss factors relevant to R2 Factor
Zone 1
Zone 2
LB
5.0E-04
5.0E-04
LC
1.0E-02
1.0E-02
LM
1.0E-02
1.0E-02
LV
5.0E-04
5.0E-04
LW
1.0E-02
1.0E-02
LZ
1.0E-02
1.0E-02
Loss factors relevant to R3 Factor
Zone 1
Zone 2
LB
5.0E-05
5.0E-04
LV
5.0E-05
5.0E-04
StrikeRisk Version 5.0 Run identification 2/13/2014 6:31:54PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 7 of 11 Page 34 of 97
File: Administration Substation.src
Loss factors relevant to R4 Factor
Zone 1
Zone 2
LA
0.0E00
0.0E00
LB
2.0E-02
2.5E-03
LC
1.0E-02
1.0E-02
LM
1.0E-02
1.0E-02
LU
0.0E00
0.0E00
LV
2.0E-02
2.5E-03
LW
1.0E-02
1.0E-02
LZ
1.0E-02
1.0E-02
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Assessment of Rx - Risk components Risk components relevant to R1 Factor
Zone 1
Zone 2
RA
0.0E00
0.0E00
RB
6.7846E-07
0.0E00
RC
9.224E-07
0.0E00
RM
6.3396E-06
0.0E00
RU (L1)
0.0E00
0.0E00
RU (L2)
0.0E00
0.0E00
RU (L3)
0.0E00
0.0E00
RV (L1)
6.2973E-11
0.0E00
RV (L2)
6.2973E-11
0.0E00
RV (L3)
1.0053E-10
0.0E00
RW (L1)
1.9083E-09
0.0E00
RW (L2)
1.9083E-09
0.0E00
RW (L3)
3.0462E-09
0.0E00
RZ (L1)
1.28E-07
0.0E00
RZ (L2)
1.28E-07
0.0E00
RZ (L3)
3.2171E-07
0.0E00
Zone 3
Zone 4
StrikeRisk Version 5.0 Run identification 2/13/2014 6:31:54PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 8 of 11 Page 35 of 97
File: Administration Substation.src
Risk components relevant to R2 Factor
Zone 1
Zone 2
RB
1.028E-07
0.0E00
RC
9.224E-08
0.0E00
RM
6.3396E-07
0.0E00
RV (L1)
9.5414E-12
0.0E00
RV (L2)
9.5414E-12
0.0E00
RV (L3)
1.5231E-11
0.0E00
RW (L1)
1.9083E-10
0.0E00
RW (L2)
1.9083E-10
0.0E00
RW (L3)
3.0462E-10
0.0E00
RZ (L1)
1.28E-08
0.0E00
RZ (L2)
1.28E-08
0.0E00
RZ (L3)
3.2171E-08
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Risk components relevant to R3 Factor
Zone 1
Zone 2
RB
1.028E-08
0.0E00
RV (L1)
9.5414E-13
0.0E00
RV (L2)
9.5414E-13
0.0E00
RV (L3)
1.5231E-12
0.0E00
Zone 3
StrikeRisk Version 5.0 Run identification 2/13/2014 6:31:54PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 9 of 11 Page 36 of 97
File: Administration Substation.src
Risk components relevant to R4 Factor
Zone 1
Zone 2
RA
0.0E00
0.0E00
RB
4.1119E-06
0.0E00
RC
9.224E-08
0.0E00
RM
6.3396E-07
0.0E00
RU (L1)
0.0E00
0.0E00
RU (L2)
0.0E00
0.0E00
RU (L3)
0.0E00
0.0E00
RV (L1)
3.8166E-10
0.0E00
RV (L2)
3.8166E-10
0.0E00
RV (L3)
6.0925E-10
0.0E00
RW (L1)
1.9083E-10
0.0E00
RW (L2)
1.9083E-10
0.0E00
RW (L3)
3.0462E-10
0.0E00
RZ (L1)
1.28E-08
0.0E00
RZ (L2)
1.28E-08
0.0E00
RZ (L3)
3.2171E-08
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Primary risk totals R1_T R2_T R3_T R4_T
8.5252E-06
Risk of loss of human life in the structure
8.8749E-07
Risk of loss of service to the public in the structure
1.0283E-08
Risk of loss of cultural heritage in the structure
4.8979E-06
Risk of loss of economic value in the structure
Primary risk with respect to source of damage R1_D R2_D R3_D R4_D R1_I
1.6009E-06
Risk of loss of human life in the structure due to flashes to the structure (S1)
1.9504E-07
Risk of loss of service to the public in the structure due to flashes to the structure (S1)
1.028E-08
Risk of loss of cultural heritage in the structure due to flashes to the structure (S1)
4.2041E-06
Risk of loss of economic value in the structure due to flashes to the structure (S1)
6.9244E-06
Risk of loss of human life in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R2_I
6.9245E-07
Risk of loss of service to the public in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R3_I
3.4314E-12
Risk of loss of cultural heritage in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R4_I
6.9379E-07
Risk of loss of economic value in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
StrikeRisk Version 5.0 Run identification 2/13/2014 6:31:54PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 10 of 11 Page 37 of 97
File: Administration Substation.src
Primary risk with respect to type of damage R1_S R2_S R3_S R4_S R1_F R2_F R3_F R4_F R1_O R2_O R3_O R4_O
0.E00
Risk of loss of human life in the structure due to injury to living beings (D1)
0.E00
Risk of loss of service to the public in the structure due to injury to living beings (D1)
0.E00
Risk of loss of cultural heritage in the structure due to injury to living beings (D1)
0.E00
Risk of loss of economic value in the structure due to injury to living beings (D1)
6.7868E-07
Risk of loss of human life in the structure due to physical damage (D2)
1.0283E-07
Risk of loss of service to the public in the structure due to physical damage (D2)
6.7868E-07
Risk of loss of cultural heritage in the structure due to physical damage (D2)
4.1132E-06
Risk of loss of economic value in the structure due to physical damage (D2)
7.8466E-06
Risk of loss of human life in the structure due to failure of internal systems (D3)
7.8466E-07
Risk of loss of service to the public in the structure due to failure of internal systems (D3)
0.E00
Risk of loss of cultural heritage in the structure due to failure of internal systems (D3)
7.8466E-07
Risk of loss of economic value in the structure due to failure of internal systems (D3)
StrikeRisk Version 5.0 Run identification 2/13/2014 6:31:54PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 11 of 11 Page 38 of 97
Attachment 5 - MOSQUE File: Mosque.src
BS EN 62305-2:2006 Risk Management Calculations Project details Project name:
CONTAINER TERMINAL - 1(D&B)
Project title:
MOSQUE
Project address: Project ref: Calculation ref: Calculation notes: Project author: Created:
15 February 2014
Modified:
15 February 2014
Case details Case name:
Mosque
Case title:
Mosque
Created:
08 February 2014
Modified:
15 February 2014
Case notes:
Primary risk totals
R1_T
1.9645E-07
Risk of loss of human life in the structure The tolerable risk is not exceeded, no additional protection required
R2_T
1.298E-05
Risk of loss of service to the public in the structure The tolerable risk is not exceeded, no additional protection required
R3_T
6.1391E-09
Risk of loss of cultural heritage in the structure The tolerable risk is not exceeded, no additional protection required
R4_T
1.5313E-06
Risk of loss of economic value in the structure
StrikeRisk Version 5.0 Run identification 2/15/2014 1:46:55PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 1 of 10 Page 39 of 97
File: Mosque.src
Protection system design parameters LPS
LPL IV
Protect the structure with a Class LPL IV Lightning Protection System in accordance with BS EN 62305-3
Imax
100.00kA
Maximum peak current
97.00%
Probability that lightning current parameters are smaller than the maximum value defined above
16.00kA
Minimum peak current
84.00%
Probability that lightning current parameters are greater than the minimum value defined above
60.00m
Radius of rolling sphere
25.00kA
Maximum peak current of equipotential bonding SPD's for each of 'n' lines defined (based upon simple current division concept)
Imin
ISPD
NOTE: The worst case surge that could be expected on a two-wire telephone or data line is 2.5kA (10/350 µs) per line (Category D test to BS EN 61643-21) to earth or 5 kA (10/350 µs) per pair.
Line 1
Protect Line 1 at its entrance to the structure with a standard equipotential bonding SPD (rated to ISPD above) in accordance with BS EN 62305-3 NOTE: Where SPDs are required but an LPS is not (ISPD = 0), protect overhead lines with Type 1 SPDs (mains 12.5kA 10/350µs, data/telecom 2.5kA 10/350µs), protect underground lines with overvoltage or Type 2 SPDs (tested with an 8/20 µs waveform)
Line 2
Protect Line 2 at its entrance to the structure with a standard equipotential bonding SPD (rated to ISPD above) in accordance with BS EN 62305-3 NOTE: Where SPDs are required but an LPS is not (ISPD = 0), protect overhead lines with Type 1 SPDs (mains 12.5kA 10/350µs, data/telecom 2.5kA 10/350µs), protect underground lines with overvoltage or Type 2 SPDs (tested with an 8/20 µs waveform)
Environment Ng Cd Ce
1.00
Lightning flash density (Flashes/km²/year)
0.25
Location factor
0.00
Environmental factor
Rho
3.00 W m
Soil resistivity (Ohm metres)
StrikeRisk Version 5.0 Run identification 2/15/2014 1:46:55PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 2 of 10 Page 40 of 97
File: Mosque.src
Assessment of Ax - Collection areas (BS EN 62305-2 Annex A.2) Ad/b Ad/a (2) Am Al (L1) Al (L2) Al Ai (L1) Ai (L2) Ai
4,897.27 m²
Collection area of primary structure
14,144.74 m²
Collection area of structure 2 (adjacent)
215,191.79 m²
Collection area of surrounding ground
55.29 m²
Collection area of flashes striking line 1
37.97 m²
Collection area of flashes striking line 2
93.25 m²
Total collection area of flashes striking lines
2,598.08 m²
Collection area of flashes near line 1
2,165.06 m²
Collection area of flashes near line 2
4,763.14 m²
Total collection area of flashes near lines
Structures Primary structure Structure ID:
Mosque - Rectangular with a flat roof
Lb Wb Hb
18.50 m
Length of primary structure
18.50 m
Width of primary structure
9.36 m
Height of primary structure
Secondary structures Structure No
Minaret - Cylindrical
Cda Da Ha
0.25
Location factor for structure 2 (adjacent)
2.20 m
Diameter of secondary structure
22.00 m
Height of secondary structure
StrikeRisk Version 5.0 Run identification 2/15/2014 1:46:55PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 3 of 10 Page 41 of 97
File: Mosque.src
Lines Line 1
Main LV Incomer
KS3 (L1) PSPD (L1)
0.00
Factor relevant to the characteristics of internal wiring for line 1
0.03
Probability of failure of internal systems or a service when SPDs are provided for equipotential bonding (in accordance with BS EN 62305-3) for line 1
PSPDc (L1)
1.00
Probability of failure of internal systems or a service when coordinated SPDs are provided (in accordance with BS EN 62305-4) for line 1
Ct (L1) Cdc (L1) Uw (L1) Lc (L1) Hc (L1)
1.00
Correction factor for a hv/lv transformer on line 1
0.25
Location factor for line 1
1.50 kV
Rated impulse withstand voltage of a system connected to line 1
60.00 m
Length of line 1
0.00 m
Height of the conductors above ground for line 1
Line 2
UPS DB Incomer
KS3 (L2) PSPD (L2)
0.00
Factor relevant to the characteristics of internal wiring for line 2
0.03
Probability of failure of internal systems or a service when SPDs are provided for equipotential bonding (in accordance with BS EN 62305-3) for line 2
PSPDc (L2)
1.00
Probability of failure of internal systems or a service when coordinated SPDs are provided (in accordance with BS EN 62305-4) for line 2
Ct (L2) Cdc (L2) Uw (L2) Lc (L2) Hc (L2)
1.00
Correction factor for a hv/lv transformer on line 2
0.25
Location factor for line 2
1.50 kV
Rated impulse withstand voltage of a system connected to line 2
50.00 m
Length of line 2
0.00 m
Height of the conductors above ground for line 2
StrikeRisk Version 5.0 Run identification 2/15/2014 1:46:55PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 4 of 10 Page 42 of 97
File: Mosque.src
Zones Factor
Zone 1
Zone 2
rp
5.0E-01
5.0E-01
rf
1.0E-02
1.0E-02
ra / ru
1.0E-02
1.0E-02
hz1
2
2
hz4
1
1
Lt1
1.0E-04
0.0E00
Lf1
8.0E-02
8.0E-02
Lo1
0.0E00
0.0E00
Lf2
1.0E-01
1.0E-01
Lo2
1.0E-02
1.0E-02
Lf3
1.0E-02
1.0E-02
Lt4
0.0E00
0.0E00
Lf4
2.0E-01
2.0E-01
Lo4
1.0E-03
1.0E-03
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Assessment of Nx - Annual number of dangerous events (BS EN 62305-2 Annex A) Nd/b Nd/a (2) Nm Nl (L1) Nl (L2) Ni (L1) Ni (L2)
0.001224
Average number of flashes to main structure
0.003536
Average number of flashes to structure 2 (adjacent)
0.213967
Average number of flashes to surrounding ground
0.000014
Average number of flashes to line 1
0.000009
Average number of flashes to line 2
0.000000
Average number of flashes near line 1
0.000000
Average number of flashes near line 2
StrikeRisk Version 5.0 Run identification 2/15/2014 1:46:55PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 5 of 10 Page 43 of 97
File: Mosque.src
Assessment of Px - Probability of damage for a structure (BS EN 62305-2 Annex NB) Factor
Zone 1
Zone 2
PA
0.00001
0.00001
Zone 3
Zone 4
Zone 5
Zone 6
PB
0.2
PC (L1)
1
PC (L2)
1
PC
1
KS1
1
KS2
1
Zone 8
Zone 9
Zone 10
NA
KS4 (L1)
1
KS4 (L2)
1
KMS (L1)
2.0E-04
NA
KMS (L2)
2.0E-04
NA
PMS (L1)
1.0E-04
NA
PMS (L2)
1.0E-04
NA
PM (L1)
1.0E-04
NA
PM (L2)
1.0E-04
NA
PM
1.9999E-04
NA
PLD (L1)
8.0E-01
PLD (L2)
8.0E-01
PLI (L1)
4.0E-02
PLI (L2)
4.0E-02
PU (L1)
3.0E-02
PU (L2)
3.0E-02
PV (L1)
3.0E-02
PV (L2)
3.0E-02
PW (L1)
8.0E-01
PW (L2)
8.0E-01
PZ (L1)
4.0E-02
PZ (L2)
4.0E-02
StrikeRisk Version 5.0 Run identification 2/15/2014 1:46:55PM NPP0026-TCC-CAL-EL-00001
Zone 7
REV. A
Page 6 of 10 Page 44 of 97
File: Mosque.src
Assessment of Lx - Amount of loss for a structure (BS EN 62305-2 Annex NC) Loss factors relevant to R1 Factor
Zone 1
Zone 2
LA
1.0E-06
0.0E00
LB
8.0E-04
8.0E-04
LC
0.0E00
0.0E00
LM
0.0E00
0.0E00
LU
1.0E-06
0.0E00
LV
8.0E-04
8.0E-04
LW
0.0E00
0.0E00
LZ
0.0E00
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Loss factors relevant to R2 Factor
Zone 1
Zone 2
LB
5.0E-04
5.0E-04
LC
1.0E-02
1.0E-02
LM
1.0E-02
1.0E-02
LV
5.0E-04
5.0E-04
LW
1.0E-02
1.0E-02
LZ
1.0E-02
1.0E-02
Loss factors relevant to R3 Factor
Zone 1
Zone 2
LB
2.5E-05
2.5E-05
LV
2.5E-05
2.5E-05
Loss factors relevant to R4 Factor
Zone 1
Zone 2
LA
0.0E00
0.0E00
LB
1.0E-03
1.0E-03
LC
1.0E-03
1.0E-03
LM
1.0E-03
1.0E-03
LU
0.0E00
0.0E00
LV
1.0E-03
1.0E-03
LW
1.0E-03
1.0E-03
LZ
1.0E-03
1.0E-03
StrikeRisk Version 5.0 Run identification 2/15/2014 1:46:55PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 7 of 10 Page 45 of 97
File: Mosque.src
Assessment of Rx - Risk components Risk components relevant to R1 Factor
Zone 1
Zone 2
RA
0.0E00
0.0E00
RB
1.9589E-07
0.0E00
RC
0.0E00
0.0E00
RM
0.0E00
0.0E00
RU (L1)
4.1465E-18
0.0E00
RU (L2)
2.8475E-18
0.0E00
RV (L1)
3.3172E-10
0.0E00
RV (L2)
2.278E-10
0.0E00
RW (L1)
0.0E00
0.0E00
RW (L2)
0.0E00
0.0E00
RZ (L1)
0.0E00
0.0E00
RZ (L2)
0.0E00
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Risk components relevant to R2 Factor
Zone 1
Zone 2
RB
1.2243E-07
0.0E00
RC
1.2243E-05
0.0E00
RM
4.2791E-07
0.0E00
RV (L1)
2.0733E-10
0.0E00
RV (L2)
1.4237E-10
0.0E00
RW (L1)
1.1057E-07
0.0E00
RW (L2)
7.5933E-08
0.0E00
RZ (L1)
0.0E00
0.0E00
RZ (L2)
0.0E00
0.0E00
Zone 3
Risk components relevant to R3 Factor
Zone 1
Zone 2
RB
6.1216E-09
0.0E00
RV (L1)
1.0366E-11
0.0E00
RV (L2)
7.1187E-12
0.0E00
Zone 3
StrikeRisk Version 5.0 Run identification 2/15/2014 1:46:55PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 8 of 10 Page 46 of 97
File: Mosque.src
Risk components relevant to R4 Factor
Zone 1
Zone 2
RA
0.0E00
0.0E00
RB
2.4486E-07
0.0E00
RC
1.2243E-06
0.0E00
RM
4.2791E-08
0.0E00
RU (L1)
0.0E00
0.0E00
RU (L2)
0.0E00
0.0E00
RV (L1)
4.1465E-10
0.0E00
RV (L2)
2.8475E-10
0.0E00
RW (L1)
1.1057E-08
0.0E00
RW (L2)
7.5933E-09
0.0E00
RZ (L1)
0.0E00
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Primary risk totals R1_T R2_T R3_T R4_T
1.9645E-07
Risk of loss of human life in the structure
1.298E-05
Risk of loss of service to the public in the structure
6.1391E-09
Risk of loss of cultural heritage in the structure
1.5313E-06
Risk of loss of economic value in the structure
Primary risk with respect to source of damage R1_D R2_D R3_D R4_D R1_I
1.9589E-07
Risk of loss of human life in the structure due to flashes to the structure (S1)
1.2366E-05
Risk of loss of service to the public in the structure due to flashes to the structure (S1)
6.1216E-09
Risk of loss of cultural heritage in the structure due to flashes to the structure (S1)
1.4692E-06
Risk of loss of economic value in the structure due to flashes to the structure (S1)
5.5952E-10
Risk of loss of human life in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R2_I
6.1477E-07
Risk of loss of service to the public in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R3_I
1.7485E-11
Risk of loss of cultural heritage in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R4_I
6.2141E-08
Risk of loss of economic value in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
StrikeRisk Version 5.0 Run identification 2/15/2014 1:46:55PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 9 of 10 Page 47 of 97
File: Mosque.src
Primary risk with respect to type of damage R1_S R2_S R3_S R4_S R1_F R2_F R3_F R4_F R1_O R2_O R3_O R4_O
6.994E-18
Risk of loss of human life in the structure due to injury to living beings (D1)
0.E00
Risk of loss of service to the public in the structure due to injury to living beings (D1)
0.E00
Risk of loss of cultural heritage in the structure due to injury to living beings (D1)
0.E00
Risk of loss of economic value in the structure due to injury to living beings (D1)
1.9645E-07
Risk of loss of human life in the structure due to physical damage (D2)
1.2278E-07
Risk of loss of service to the public in the structure due to physical damage (D2)
1.9645E-07
Risk of loss of cultural heritage in the structure due to physical damage (D2)
2.4556E-07
Risk of loss of economic value in the structure due to physical damage (D2)
0.E00
Risk of loss of human life in the structure due to failure of internal systems (D3)
1.2858E-05
Risk of loss of service to the public in the structure due to failure of internal systems (D3)
0.E00
Risk of loss of cultural heritage in the structure due to failure of internal systems (D3)
1.2858E-06
Risk of loss of economic value in the structure due to failure of internal systems (D3)
StrikeRisk Version 5.0 Run identification 2/15/2014 1:46:55PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 10 of 10 Page 48 of 97
Attachment 6 - WORKSHOP BUILDING File: Workshop.src
BS EN 62305-2:2006 Risk Management Calculations Project details Project name:
CONTAINER TERMINAL - 1(D&B)
Project title:
WORKSHOP
Project address: Project ref: Calculation ref: Calculation notes: Project author: Created:
15 February 2014
Modified:
15 February 2014
Case details Case name:
Workshop
Case title:
Workshop
Created:
08 February 2014
Modified:
10 February 2014
Case notes:
Primary risk totals
R1_T
8.442E-06
Risk of loss of human life in the structure The tolerable risk is not exceeded, no additional protection required
R2_T
1.5906E-05
Risk of loss of service to the public in the structure The tolerable risk is not exceeded, no additional protection required
R3_T
3.15E-09
Risk of loss of cultural heritage in the structure The tolerable risk is not exceeded, no additional protection required
R4_T
2.2143E-05
Risk of loss of economic value in the structure
StrikeRisk Version 5.0 Run identification 2/15/2014 1:58:19PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 1 of 7 Page 49 of 97
File: Workshop.src
Protection system design parameters LPS
LPL IV
Protect the structure with a Class LPL IV Lightning Protection System in accordance with BS EN 62305-3
Imax
100.00kA
Maximum peak current
97.00%
Probability that lightning current parameters are smaller than the maximum value defined above
16.00kA
Minimum peak current
84.00%
Probability that lightning current parameters are greater than the minimum value defined above
60.00m
Radius of rolling sphere
50.00kA
Maximum peak current of equipotential bonding SPD's for each of 'n' lines defined (based upon simple current division concept)
Imin
ISPD
NOTE: The worst case surge that could be expected on a two-wire telephone or data line is 2.5kA (10/350 µs) per line (Category D test to BS EN 61643-21) to earth or 5 kA (10/350 µs) per pair.
Line 1
Protect Line 1 at its entrance to the structure with a standard equipotential bonding SPD (rated to ISPD above) in accordance with BS EN 62305-3 NOTE: Where SPDs are required but an LPS is not (ISPD = 0), protect overhead lines with Type 1 SPDs (mains 12.5kA 10/350µs, data/telecom 2.5kA 10/350µs), protect underground lines with overvoltage or Type 2 SPDs (tested with an 8/20 µs waveform)
Environment Ng Cd Ce
1.00
Lightning flash density (Flashes/km²/year)
0.25
Location factor
0.10
Environmental factor
Rho
3.00 W m
Soil resistivity (Ohm metres)
Assessment of Ax - Collection areas (BS EN 62305-2 Annex A.2) Ad/b Am Al (L1) Al Ai (L1) Ai
6,300.00 m²
Collection area of primary structure
7,670.90 m²
Collection area of surrounding ground
0.00 m²
Collection area of flashes striking line 1
0.00 m²
Total collection area of flashes striking lines
2,165.06 m²
Collection area of flashes near line 1
2,165.06 m²
Total collection area of flashes near lines
StrikeRisk Version 5.0 Run identification 2/15/2014 1:58:19PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 2 of 7 Page 50 of 97
File: Workshop.src
Structures Primary structure Structure ID:
- Complex with a known collection area
Ad Hb Am
6,300.00 m²
Collection area of primary structure
17.20 m
Height of primary structure
7,670.90 m²
Collection area of surrounding ground
Secondary structures
Lines Line 1
KS3 (L1) PSPD (L1)
0.00
Factor relevant to the characteristics of internal wiring for line 1
0.03
Probability of failure of internal systems or a service when SPDs are provided for equipotential bonding (in accordance with BS EN 62305-3) for line 1
PSPDc (L1)
1.00
Probability of failure of internal systems or a service when coordinated SPDs are provided (in accordance with BS EN 62305-4) for line 1
Ct (L1) Cdc (L1) Uw (L1) Lc (L1) Hc (L1)
1.00
Correction factor for a hv/lv transformer on line 1
0.25
Location factor for line 1
1.50 kV
Rated impulse withstand voltage of a system connected to line 1
50.00 m
Length of line 1
0.00 m
Height of the conductors above ground for line 1
Zones Factor
Zone 1
Zone 2
rp
2.0E-01
5.0E-01
rf
1.0E-02
1.0E-02
ra / ru
1.0E-02
1.0E-02
hz1
20
2
hz4
20
1
Lt1
1.0E-04
0.0E00
Lf1
6.7E-01
6.7E-01
Lo1
0.0E00
0.0E00
Lf2
1.0E-01
1.0E-01
Lo2
1.0E-02
1.0E-02
Lf3
1.0E-02
1.0E-02
Lt4
0.0E00
0.0E00
Lf4
5.0E-01
5.0E-01
Lo4
1.0E-02
1.0E-02
Zone 3
Zone 4
Zone 5
Zone 6
StrikeRisk Version 5.0 Run identification 2/15/2014 1:58:19PM NPP0026-TCC-CAL-EL-00001
REV. A
Zone 7
Zone 8
Zone 9
Zone 10
Page 3 of 7 Page 51 of 97
File: Workshop.src
Assessment of Nx - Annual number of dangerous events (BS EN 62305-2 Annex A) 0.001575 Average number of flashes to main structure Nd/b 0.006096 Average number of flashes to surrounding ground Nm 0.000000 Average number of flashes to line 1 Nl (L1) 0.000217 Average number of flashes near line 1 Ni (L1) Assessment of Px - Probability of damage for a structure (BS EN 62305-2 Annex NB)
Factor
Zone 1
Zone 2
PA
0
0
Zone 3
Zone 4
Zone 5
Zone 6
PB
0.2
PC (L1)
1
PC
1
KS1
0.25
KS2
0.6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 9
Zone 10
NA
KS4 (L1)
1
KMS (L1)
3.0E-05
NA
PMS (L1)
1.0E-04
NA
PM (L1)
1.0E-04
NA
PM
1.0E-04
NA
PLD (L1)
8.0E-01
PLI (L1)
4.0E-02
PU (L1)
3.0E-02
PV (L1)
3.0E-02
PW (L1)
8.0E-01
PZ (L1)
4.0E-02
Assessment of Lx - Amount of loss for a structure (BS EN 62305-2 Annex NC) Loss factors relevant to R1 Factor
Zone 1
Zone 2
LA
1.0E-06
0.0E00
LB
2.68E-02
6.7E-03
LC
0.0E00
0.0E00
LM
0.0E00
0.0E00
LU
1.0E-06
0.0E00
LV
2.68E-02
6.7E-03
LW
0.0E00
0.0E00
LZ
0.0E00
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
StrikeRisk Version 5.0 Run identification 2/15/2014 1:58:19PM NPP0026-TCC-CAL-EL-00001
REV. A
Zone 7
Zone 8
Page 4 of 7 Page 52 of 97
File: Workshop.src
Loss factors relevant to R2 Factor
Zone 1
Zone 2
LB
2.0E-04
5.0E-04
LC
1.0E-02
1.0E-02
LM
1.0E-02
1.0E-02
LV
2.0E-04
5.0E-04
LW
1.0E-02
1.0E-02
LZ
1.0E-02
1.0E-02
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Loss factors relevant to R3 Factor
Zone 1
Zone 2
LB
1.0E-05
2.5E-05
LV
1.0E-05
2.5E-05
Loss factors relevant to R4 Factor
Zone 1
Zone 2
LA
0.0E00
0.0E00
LB
2.0E-02
2.5E-03
LC
1.0E-02
1.0E-02
LM
1.0E-02
1.0E-02
LU
0.0E00
0.0E00
LV
2.0E-02
2.5E-03
LW
1.0E-02
1.0E-02
LZ
1.0E-02
1.0E-02
Assessment of Rx - Risk components Risk components relevant to R1 Factor
Zone 1
Zone 2
RA
0.0E00
0.0E00
RB
8.442E-06
0.0E00
RC
0.0E00
0.0E00
RM
0.0E00
0.0E00
RU (L1)
0.0E00
0.0E00
RV (L1)
0.0E00
0.0E00
RW (L1)
0.0E00
0.0E00
RZ (L1)
0.0E00
0.0E00
Zone 3
Zone 4
StrikeRisk Version 5.0 Run identification 2/15/2014 1:58:19PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 5 of 7 Page 53 of 97
File: Workshop.src
Risk components relevant to R2 Factor
Zone 1
Zone 2
RB
6.3E-08
0.0E00
RC
1.575E-05
0.0E00
RM
6.0959E-09
0.0E00
RV (L1)
0.0E00
0.0E00
RW (L1)
0.0E00
0.0E00
RZ (L1)
8.6603E-08
0.0E00
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Risk components relevant to R3 Factor
Zone 1
Zone 2
RB
3.15E-09
0.0E00
RV (L1)
0.0E00
0.0E00
Zone 3
Risk components relevant to R4 Factor
Zone 1
Zone 2
RA
0.0E00
0.0E00
RB
6.3E-06
0.0E00
RC
1.575E-05
0.0E00
RM
6.0959E-09
0.0E00
RU (L1)
0.0E00
0.0E00
RV (L1)
0.0E00
0.0E00
RW (L1)
0.0E00
0.0E00
RZ (L1)
8.6603E-08
0.0E00
Zone 3
Primary risk totals R1_T R2_T R3_T R4_T
8.442E-06
Risk of loss of human life in the structure
1.5906E-05
Risk of loss of service to the public in the structure
3.15E-09
Risk of loss of cultural heritage in the structure
2.2143E-05
Risk of loss of economic value in the structure
StrikeRisk Version 5.0 Run identification 2/15/2014 1:58:19PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 6 of 7 Page 54 of 97
File: Workshop.src
Primary risk with respect to source of damage R1_D R2_D R3_D R4_D R1_I
8.442E-06
Risk of loss of human life in the structure due to flashes to the structure (S1)
1.5813E-05
Risk of loss of service to the public in the structure due to flashes to the structure (S1)
3.15E-09
Risk of loss of cultural heritage in the structure due to flashes to the structure (S1)
2.205E-05
Risk of loss of economic value in the structure due to flashes to the structure (S1)
0.E00
Risk of loss of human life in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R2_I
9.2698E-08
Risk of loss of service to the public in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R3_I
0.E00
Risk of loss of cultural heritage in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
R4_I
9.2698E-08
Risk of loss of economic value in the structure due to flashes influencing, but not striking the structure (S2, S3, S4)
Primary risk with respect to type of damage R1_S R2_S R3_S R4_S R1_F R2_F R3_F R4_F R1_O R2_O R3_O R4_O
0.E00
Risk of loss of human life in the structure due to injury to living beings (D1)
0.E00
Risk of loss of service to the public in the structure due to injury to living beings (D1)
0.E00
Risk of loss of cultural heritage in the structure due to injury to living beings (D1)
0.E00
Risk of loss of economic value in the structure due to injury to living beings (D1)
8.442E-06
Risk of loss of human life in the structure due to physical damage (D2)
6.3E-08
Risk of loss of service to the public in the structure due to physical damage (D2)
8.442E-06
Risk of loss of cultural heritage in the structure due to physical damage (D2)
6.3E-06
Risk of loss of economic value in the structure due to physical damage (D2)
0.E00
Risk of loss of human life in the structure due to failure of internal systems (D3)
1.5843E-05
Risk of loss of service to the public in the structure due to failure of internal systems (D3)
0.E00
Risk of loss of cultural heritage in the structure due to failure of internal systems (D3)
1.5843E-05
Risk of loss of economic value in the structure due to failure of internal systems (D3)
StrikeRisk Version 5.0 Run identification 2/15/2014 1:58:19PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 7 of 7 Page 55 of 97
Attachment 7 - (a) REEFER WASH DOWN AREA File: Reefer WashDown Area.src
BS EN 62305-2:2006 Risk Management Calculations Project details Project name:
CONTAINER TERMINAL - 1 (D&B)
Project title:
REEFER WASH DOWN AREA
Project address: Project ref: Calculation ref: Calculation notes: Project author: Created:
15 February 2014
Modified:
15 February 2014
Case details Case name:
Reefer WashDown Area
Case title:
Reefer WashDown Area
Created:
08 February 2014
Modified:
10 February 2014
Case notes:
Primary risk totals
R1_T
2.2491E-06
Risk of loss of human life in the structure The tolerable risk is not exceeded, no additional protection required
R2_T
3.9656E-05
Risk of loss of service to the public in the structure The tolerable risk is not exceeded, no additional protection required
R3_T
1.6784E-08
Risk of loss of cultural heritage in the structure The tolerable risk is not exceeded, no additional protection required
R4_T
8.1449E-05
Risk of loss of economic value in the structure
StrikeRisk Version 5.0 Run identification 2/15/2014 1:50:24PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 1 of 7 Page 56 of 97
File: Reefer WashDown Area.src
Protection system design parameters LPS
LPL IV
Protect the structure with a Class LPL IV Lightning Protection System in accordance with BS EN 62305-3
Imax
100.00kA
Maximum peak current
97.00%
Probability that lightning current parameters are smaller than the maximum value defined above
16.00kA
Minimum peak current
84.00%
Probability that lightning current parameters are greater than the minimum value defined above
60.00m
Radius of rolling sphere
50.00kA
Maximum peak current of equipotential bonding SPD's for each of 'n' lines defined (based upon simple current division concept)
Imin
ISPD
NOTE: The worst case surge that could be expected on a two-wire telephone or data line is 2.5kA (10/350 µs) per line (Category D test to BS EN 61643-21) to earth or 5 kA (10/350 µs) per pair.
Line 1
Protect Line 1 at its entrance to the structure with a standard equipotential bonding SPD (rated to ISPD above) in accordance with BS EN 62305-3 NOTE: Where SPDs are required but an LPS is not (ISPD = 0), protect overhead lines with Type 1 SPDs (mains 12.5kA 10/350µs, data/telecom 2.5kA 10/350µs), protect underground lines with overvoltage or Type 2 SPDs (tested with an 8/20 µs waveform)
Environment Ng Cd Ce
1.00
Lightning flash density (Flashes/km²/year)
0.25
Location factor
0.50
Environmental factor
Rho
3.00 W m
Soil resistivity (Ohm metres)
Assessment of Ax - Collection areas (BS EN 62305-2 Annex A.2) Ad/b Am Al (L1) Al Ai (L1) Ai
6,693.59 m²
Collection area of primary structure
242,038.70 m²
Collection area of surrounding ground
134.23 m²
Collection area of flashes striking line 1
134.23 m²
Total collection area of flashes striking lines
4,330.13 m²
Collection area of flashes near line 1
4,330.13 m²
Total collection area of flashes near lines
StrikeRisk Version 5.0 Run identification 2/15/2014 1:50:24PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 2 of 7 Page 57 of 97
File: Reefer WashDown Area.src
Structures Primary structure Structure ID:
- Rectangular with a flat roof
Lb Wb Hb
74.60 m
Length of primary structure
14.60 m
Width of primary structure
7.50 m
Height of primary structure
Secondary structures
Lines Line 1
KS3 (L1) PSPD (L1)
0.02
Factor relevant to the characteristics of internal wiring for line 1
0.03
Probability of failure of internal systems or a service when SPDs are provided for equipotential bonding (in accordance with BS EN 62305-3) for line 1
PSPDc (L1)
1.00
Probability of failure of internal systems or a service when coordinated SPDs are provided (in accordance with BS EN 62305-4) for line 1
Ct (L1) Cdc (L1) Uw (L1) Lc (L1) Hc (L1)
1.00
Correction factor for a hv/lv transformer on line 1
0.25
Location factor for line 1
1.50 kV
Rated impulse withstand voltage of a system connected to line 1
100.00 m
Length of line 1
0.00 m
Height of the conductors above ground for line 1
Zones Factor
Zone 1
rp
5.0E-01
rf
1.0E-02
ra / ru
1.0E-02
hz1
2
hz4
50
Lt1
1.0E-04
Lf1
6.7E-01
Lo1
0.0E00
Lf2
1.0E-01
Lo2
1.0E-02
Lf3
1.0E-02
Lt4
0.0E00
Lf4
5.0E-01
Lo4
1.0E-02
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
StrikeRisk Version 5.0 Run identification 2/15/2014 1:50:24PM NPP0026-TCC-CAL-EL-00001
REV. A
Zone 7
Zone 8
Zone 9
Zone 10
Page 3 of 7 Page 58 of 97
File: Reefer WashDown Area.src
Assessment of Nx - Annual number of dangerous events (BS EN 62305-2 Annex A) 0.001673 Average number of flashes to main structure Nd/b 0.240365 Average number of flashes to surrounding ground Nm 0.000034 Average number of flashes to line 1 Nl (L1) 0.002165 Average number of flashes near line 1 Ni (L1) Assessment of Px - Probability of damage for a structure (BS EN 62305-2 Annex NB)
Factor
Zone 1
PA
0
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
PB
0.2
PC (L1)
1
PC
1
KS1
1
KS2
Zone 7
Zone 8
Zone 9
Zone 10
Zone 9
Zone 10
1
KS4 (L1)
1
KMS (L1)
2.0E-02
PMS (L1)
9.0E-03
PM (L1)
9.0E-03
PM
9.0E-03
PLD (L1)
8.0E-01
PLI (L1)
4.0E-02
PU (L1)
3.0E-02
PV (L1)
3.0E-02
PW (L1)
8.0E-01
PZ (L1)
4.0E-02
Assessment of Lx - Amount of loss for a structure (BS EN 62305-2 Annex NC) Loss factors relevant to R1 Factor
Zone 1
LA
1.0E-06
LB
6.7E-03
LC
0.0E00
LM
0.0E00
LU
1.0E-06
LV
6.7E-03
LW
0.0E00
LZ
0.0E00
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
StrikeRisk Version 5.0 Run identification 2/15/2014 1:50:24PM NPP0026-TCC-CAL-EL-00001
REV. A
Zone 7
Zone 8
Page 4 of 7 Page 59 of 97
File: Reefer WashDown Area.src
Loss factors relevant to R2 Factor
Zone 1
LB
5.0E-04
LC
1.0E-02
LM
1.0E-02
LV
5.0E-04
LW
1.0E-02
LZ
1.0E-02
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Loss factors relevant to R3 Factor
Zone 1
LB
5.0E-05
LV
5.0E-05
Zone 2
Loss factors relevant to R4 Factor
Zone 1
LA
0.0E00
LB
1.25E-01
LC
1.0E-02
LM
1.0E-02
LU
0.0E00
LV
1.25E-01
LW
1.0E-02
LZ
1.0E-02
Zone 2
Assessment of Rx - Risk components Risk components relevant to R1 Factor
Zone 1
RA
0.0E00
RB
2.2424E-06
RC
0.0E00
RM
0.0E00
RU (L1)
0.0E00
RV (L1)
6.7453E-09
RW (L1)
0.0E00
RZ (L1)
0.0E00
Zone 2
Zone 3
Zone 4
StrikeRisk Version 5.0 Run identification 2/15/2014 1:50:24PM NPP0026-TCC-CAL-EL-00001
REV. A
Page 5 of 7 Page 60 of 97
View more...
Comments