Lighting Calculation-flurcent Lights

April 24, 2017 | Author: ganesh_dg | Category: N/A
Share Embed Donate


Short Description

Download Lighting Calculation-flurcent Lights...

Description

PREPARED BY

Fire Water PH

Guard Pond PH

Re-circulating water pump and sump house

Petrol pump

Sewage treatment plant

0.6 0.5

0.6 0.5

0.6 0.5

0.6 0.5

0.5 5

0.5 0.5

Gas Control Room 0.5 0.5

C.W Chlorination Plant-2

150

C.W Chlorination Plant-1

150

C.W Treatment Plant-2

150

C.W Treatment Plant-1

SHR NOM Required No. of lamp fittings in Length wise Required No. of lamp fittings in width wise

(N)

150

C.W / ACW PH-3

Required Flourcent Lamp fittings

150

m m

22 15

22 15

22 15

35 25

35 25

35 25

35 25

15 10

m m2 lux

4 330 150

4 330 150

4 330 150

4 875 150

4 875 150

4 875 150

4 875 150

4

lux

4900

4900

4900

4900

4900

4900

4900

0.6 0.5

0.6 0.5

0.6 0.5

0.6 0.5

0.6 0.5

0.6 0.5

0.6 0.5

2.23

2.23

2.23

3.65

3.65

3.65

3.65

34

34

34

90

90

90

90

1.04

1.04

1.04

1.04

1.04

1.04

1.04

No.

7.06

7.06

7.06

11.22

11.22

11.22

11.22

No.

4.81

4.81

4.81

8.02

8.02

8.02

8.02

(L x W)/ ( Hm (L+W)) (E x A)/ (F x uF x LLF)

(K)

150

C.W / ACW PH-2

Room Index

100

Unit

C.W / ACW PH-1

Length (L) Width (W) Mounting Height of Fitting (from working plane) (Hm) Area (A) (A) Required Lux (E) Individual Lamp fitting flux (F) Utilization or Maintenance Factor (uF) Light Loss Factor (L.L.F)

Outfall PH

LIGHTING CALCULATION -66MW IPP @ JAMSHEDPUR

SHR

D.GANESH

DG building & Compresor Unit

6.6 kv Switchgear Room

Water System C&R

Air Washer Room

Elevator M/C Room

Enviromental & Chemical Lab

DM Plant Building

Area of diff. Dist. Boards of stack

FGD

Occupational Health Centre

Cement Store

Simulation and training Complex

Cooling tower Electrical Buildings

Canteen

Workshop

Fire Station building

Ware house

Service Building

Permanent Store

Gate Complex

Admin Building

ETP MCC room

STP MCC room

Parking lot

20 15

20 10

14.33 13.05

17 17

20 10

20 10

10 10

25 10

15 10

15 10

50 10

15 15

15 15

15 10

50 10

20 30

20 15

50 10

50 10

10 5

25 10

20 15

20 15

25 40

3.5 300 150

3.5 200 200

3.5 186.94 200

3.5 289 150

3.5 200 200

3.5 200 300

3.5 100 150

3.5 250 150

3.5 150 30

3.5 150 300

3.5 500 200

3.5 225 300

4 225 200

3.5 150 150

3.5 500 250

4 600 150

4 300 150

4 500 150

3.5 500 200

3.5 50 30

3.5 250 300

3.5 300 200

3.5 300 200

3.5 1000 50

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

4900

0.6 0.5

0.7 0.7

0.7 0.7

0.6 0.5

0.7 0.7

0.7 0.7

0.6 0.5

0.6 0.5

0.5 0.3

0.75 0.7

0.6 0.5

0.7 0.7

0.6 0.7

0.6 0.7

0.6 0.7

0.6 0.7

0.6 0.7

0.6 0.7

0.6 0.7

0.6 0.7

0.75 0.7

0.7 0.7

0.7 0.7

0.6 0.6

2.45

1.9

1.95

2.43

1.9

1.9

1.43

2.04

1.71

1.71

2.38

2.14

1.88

1.71

2.38

3

2.14

2.08

2.38

0.95

2.04

2.45

2.45

4.4

31

17

16

30

17

25

11

26

7

18

69

29

22

11

61

44

22

37

49

1

30

25

25

29

1.18

1.18

1.18

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

0.57

No.

6.43

5.83

4.19

5.48

5.83

7.07

3.32

8.06

3.24

5.2

18.57

5.39

4.69

4.06

17.46

5.42

5.42

13.6

15.65

1.41

8.66

5.77

5.77

4.26

No.

4.82

2.92

3.82

5.48

2.92

3.54

3.32

3.22

2.16

3.46

3.71

5.39

4.69

2.71

3.49

8.12

4.06

2.72

3.13

0.71

3.46

4.33

4.33

6.81

Unit Length (L) Width (W) Mounting Height of Fitting (from working plane) (Hm) Area (A) (A) Required Lux (E) Individual Lamp fitting flux (F) Utilization or Maintenance Factor (uF) Light Loss Factor (L.L.F) Room Index Required Flourcent Lamp fittings SHR NOM Required No. of lamp fittings in Length wise Required No. of lamp fittings in width wise PREPARED BY

m m

m m2 lux

(N)

100

lux 0.7 0.5 (L x W)/ ( Hm (L+W)) (E x A)/ (F x uF x LLF)

(K)

Passage, Indoor Stair, Catwalk Tunnel, Toilet etc.

LIGHTING CALCULATION -66MW IPP @ JAMSHEDPUR

SHR

D.GANESH

LIGHTING CALCULATION -66MW IPP @ JAMSHEDPUR

PREPARED BY

Toilet-Ladies

SHR NOM Required No. of lamp fittings in Length wise Required No. of lamp fittings in width wise

Toilet-mens

Required Flourcent Lamp fittings

Shift Engineer Room ( false Ceiling)

Room Index

Unit m m

Battery Room

Length (L) Width (W) Mounting Height of Fitting (from working plane) (Hm) Area (A) (A) Required Lux (E) Individual Lamp fitting flux (F) Utilization or Maintenance Factor (uF) Light Loss Factor (L.L.F)

Switchgear Room

TG Building

30 10

10 9

5 5

2.5 2.5

2.5 2.5

m m2 lux

3.5 300 300

3.5 90 200

3.5 25 250

3.5 6.25

3.5 6.25

lux

4900

4900

4900

4900

4900

0.75 0.7

0.6 0.7

0.7 0.7

0.7 0.7

0.7 0.7

2.14

1.35

0.71

0

0

35

9

3

1

1

1.18

0.81

0.57

0.57

0.57

No.

10.25

3.16

1.73

1

1

No.

3.42

2.85

1.73

1

1

(L x W)/ ( Hm (L+W)) (E x A)/ (F x uF x LLF)

(K) (N) SHR

D.GANESH

LIGHTING CALCULATION -66MW IPP @ JAMSHEDPUR

(6.1M level)

(12.2 M level)

Battery Charger & DCDB Room

Switch gear Room

Battery Room

Toilet-mens

Toilet-Ladies

Switch gear Room

Switch gear Room

Shift Engineer Room ( false Ceiling)

Central Control Room

Other Control Room (false Sealing)

Other Control Room (w/o false Sealing)

Air Conditioning Plant Room

Power House General indoor (Aux. Equip Room)

Cable Spreader Area

TG Building

22 11

35 11

10 9

2.5 2.5

2.5 2.5

35 11

35 11

5 5

50 10

7.5 5

30 2.5

7.5 5

7.5 5

50 10

m m2 lux

3.5 242 200

3.5 385 200

3.5 90 200

3.5 6.25

3.5 6.25

3.5 385 200

3.5 385 200

3.5 25 250

3.5 500 350

3.5 37.5 300

3.5 75 300

3.5 37.5 150

3.5 37.5 150

3.5 500 100

lux

4900

4900

4900

4900

4900

4900

4900

5800

4900

4900

4900

4900

4900

5800

0.75 0.7

0.75 0.7

0.6 0.7

0.7 0.7

0.7 0.7

0.75 0.7

0.75 0.7

0.7 0.7

0.8 0.7

0.8 0.7

0.75 0.7

0.6 0.5

0.6 0.5

0.5 0.3

2.1

2.39

1.35

0

0

2.39

2.39

0.71

2.38

0.86

0.66

0.86

0.86

2.38

19

30

9

1

1

30

30

3

64

5

9

4

4

58

0.57

0.57

0.81

0.57

0.57

0.57

0.57

0.57

1.18

1.18

1.18

0.81

1.18

0.57

No.

6.16

9.77

3.16

1

1

9.77

9.77

1.73

17.89

2.74

10.39

2.45

2.45

17.03

No.

3.08

3.07

2.85

1

1

3.07

3.07

1.73

3.58

1.83

0.87

1.63

1.63

3.41

TG Building Ground Floor(0M level)

Length (L) Width (W) Mounting Height of Fitting (from working plane) (Hm) Area (A) (A) Required Lux (E) Individual Lamp fitting flux (F) Utilization or Maintenance Factor (uF) Light Loss Factor (L.L.F) Room Index Required Flourcent Lamp fittings SHR NOM Required No. of lamp fittings in Length wise Required No. of lamp fittings in width wise PREPARED BY

(K) (N)

Unit m m

(L x W)/ ( Hm (L+W)) (E x A)/ (F x uF x LLF)

SHR

D.GANESH

TG Building Second Floor

View more...