DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty Sheet 1 of 7 DOC. NO.
: 6104-EL-DSN-700-1009
LIGHTING DESIGN CALCULATION DOCUMENT 1.SCOPE: The scope of the calculation is to design the lighting for sea water in take pump house with the given illumination level. 2.REFERENCE: 1.IS:3646-code of practice for illumination 2.Cromton greaves lighting catalouge 3.Sizing criteria as per CI.NO.B7.9.9 of contract technical specification no.B7.9-illumination system.
The Lighting calculation have been carried out for the following area in sea water in take pump house and jetty based on the lux level requirement as tabulated below. AREA
SI.no
REQUIRED LUX LEVEL
1
Switchgear room
200
2
UPS battery charger room
200
3
Battery room
150
4
Control equipment room
400
5
Engg.room
150
6
Operator station
200
7
Mobile cleaning device room
200
8
Pump room
200
9
Jetty
10
Maintenance factor Control room and A/C rooms
:0.75
Other areas
:0.7
Height of the working plane Central control room
:0.85m
other areas
:0.00m
pump room
:0.00m
CHENNAI PETROLEUM CORPORATION LTD. 5.8MGD DESALINATION PLANT
DEVELOPMENT CONSULTANTS PVT LTD. CONSULTING ENGINEERS
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty Sheet 2 of 7 DOC. NO. : 6104-EL-DSN-700-1009 Note: 1.The type fitting to be used are given below (cromtom greaves catalouge): SI.no
Area
Type of fixture
1
Switchgear room (vitreous enameld)
IGP1324EB(2X40W)
2
UPS and battery charger,battery rom(corrosion proof)
IPFC1124EB(2X36W)
3
Control equipment room(decorative type)
CRFD24EB(2X36W)
4
Mobile cleaning device room(HPMV) and Pump room(HPMV )
IHB1325IH(250W)
5
Street light(HPSV)
SSG1315IH(150W)
6
Stair case
IGP1214EB+RVE14 (36W)
7
Emergency D.C lighting
IBH1110BC
8
Toilets
IGP1214EB+RVE14 (36W)
9
Approach Road
IGP1214EB+RVE14 (36W)
3. FORMULA'S TO BE USED: LxB Room Index
= (L + B)XH Where L
=
Length of area to be illuminated
B
=
Breadth of area to be illuminated
H
=
Mounting height of light fitting above working plane L x B x IR
No.of Fittings (NC)
= LOxCOUxMFxLLD
Illumination level in lux, NR x COU x LO x MF x LLD IL
No.of fittings calculated No. of fittings recommended
12.55
9.71
13
10
207.24
205.96
AREA
Room index Reflection factor Ceiling wall floor
capacity of lamp in watts Type of fitting
Actual illumination level based on estimation in lux.
Note : As the specification call for VE reflector, since the VE reflector are not in market Powder Coating(PC) reflector which are equivalent to VE reflector are used.
CHENNAI PETROLEUM CORPORATION LTD. 5.8MGD DESALINATION PLANT
DEVELOPMENT CONSULTANTS PVT LTD. CONSULTING ENGINEERS
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty Sheet 4 of 7 DOC. NO.
: 6104-EL-DSN-700-1009 LIGHTING DESIGN CALCULATION AT BATTERY ROOM AND CHARGER ROOM
BATTERY ROOM
UPS BATTERY CHARGER ROOM
5
3.5
Breadth of the room(B in mtrs)
1.987
3.3
Height of room from FFL (in mtrs)
4.25
4.25
Mounting height above working plane(H in mtrs)
4.25
4.25
Room index
0.33
0.4
70 50 10
70 50 10
Co-efficient of utilisation(COU)
0.25
0.25
Maintenance factor(MF)
0.7
0.75
Recommended illumination (lux)
150
200
2X36
2X36
IPFC1124EB
IPFC1124EB
lamp output in lumens
5100
5100
No.of fittings calculated
1.86
2.68
2
3
161.7
223.54
AREA
Length of the room(L in mtrs)
Reflection factor Ceiling wall floor
capacity of lamp in watts Type of fitting
No. of fittings recommended Actual illumination level based on estimation in lux.
CHENNAI PETROLEUM CORPORATION LTD. 5.8MGD DESALINATION PLANT
DEVELOPMENT CONSULTANTS PVT LTD. CONSULTING ENGINEERS
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty Sheet 5 of 7 DOC. NO.
: 6104-EL-DSN-700-1009
LIGHTING DESIGN CALCULATION AT CENTRAL CONTROL ROOM CONTROL EQUIPMENT ROOM
ENGG. ROOM
OPERATOR STATION
Length of the room(L in mtrs)
4
3.31
5
Breadth of the room(B in mtrs)
3.31
2
4.95
Height of room from FFL (in mtrs)
7.5
7.5
7.5
4
4
4
0.45
0.31
0.62
70 50 10
70 50 10
70 50 10
Co-efficient of utilisation(COU)
0.32
0.32
0.4
Maintenance factor(MF)
0.75
0.75
0.75
Recommended illumination (lux)
400
150
200
capacity of lamp in watts
2X36
2X36
2X36
CRFD24EB
CRFD24EB
CRFD24EB
lamp output in lumens
4900
4900
4900
No.of fittings calculated
5
0.94
3.74
No. of fittings recommended
5
1
4
399.7
159.88
213.82
AREA
Mounting height above working plane(H in mtrs) Room index Reflection factor Ceiling wall floor
Type of fitting
Actual illumination level based on estimation in lux.
CHENNAI PETROLEUM CORPORATION LTD. 5.8MGD DESALINATION PLANT
DEVELOPMENT CONSULTANTS PVT LTD. CONSULTING ENGINEERS
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty Sheet 6 of 7 DOC. NO.
: 6104-EL-DSN-700-1009 LIGHTING DESIGN CALCULATION AT PUMP ROOM SCREEN WASH PUMP AREA
SEA WATER PUMP ROOM
Length of the room(L in mtrs)
8.18
11.6
Breadth of the room(B in mtrs)
7.8
6.7
Height of room from FFL (in mtrs)
7.2
13.75
Mounting height above working plane(H in mtrs)
6.4
12.82
Room index
0.62
0.33
70 50 10
70 50 10
Co-efficient of utilisation(COU)
0.56
0.49
Maintenance factor(MF)
0.7
0.7
Recommended illumination (lux)
200
200
capacity of lamp in watts
250
250
IHB1325IH
IHB1325IH
13500
13500
2.41
3.36
3
4
248.82
238.32
AREA
Reflection factor Ceiling wall floor
Type of fitting lamp output in lumens No.of fittings calculated No. of fittings recommended Actual illumination level based on estimation in lux.
CHENNAI PETROLEUM CORPORATION LTD. 5.8MGD DESALINATION PLANT
DEVELOPMENT CONSULTANTS PVT LTD. CONSULTING ENGINEERS
DOC. TITLE : Lighting Calculation for Facilities at Sea Water Intake Pump House & Jetty Sheet 7 of 7 DOC. NO.