LCU+ M221S M222S M223S M224S user manual V1.0 20100330

March 18, 2017 | Author: JoelMalang | Category: N/A
Share Embed Donate


Short Description

Emerson rectifier service manual...

Description

LCU+ Series Controller User Manual Version Revision date BOM

V1.0 March 30, 2010 31011833

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

Copyright © 2010 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change without notice.

Emerson Network Power Co., Ltd. Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China Homepage: www.emersonnetworkpower.com.cn E-mail: [email protected]

Safety Instructions Authorization User/Operator A user/operator who has no training for the equipment in question is authorized only to handle the equipment under normal operation, and to take the first measures in case of alarm according to the MAINTENANCE INSTRUCTIONS of the equipment. Trained User/Operator A user/operator who has been trained for the equipment in question is authorized to have the responsibility for this equipment, to perform tests, fault tracing, exchange of units and repairs of the said equipment. Intervention in live equipment may be performed by a trained user/operator only. Installer The installation personnel shall be responsible for the installation and the test of the equipment in question according to the installation and test documents in force. The installer is also liable for using the correct cable to and from the equipment and for protecting it with the adequate fuses or circuit breakers. Local authorization regulations for work with electric equipment shall always be observed.

Basic Guidelines

Danger Danger Contact the site operations manager or other responsible local personnel before commencing work. Inform all personnel near the equipment that work is in progress and the equipment is under power. Reduce the risk of accidents and increase the operation reliability by keeping the power or cooling room clean and clear of any unauthorized material. While work is in progress, the equipment also must be protected against damages and unauthorized intervention. Busbars, live cabinets, etc., shall be protected during work using protective sheeting. Never work alone in the power or cooling room. Do not leave equipment with unprotected parts under power unattended. Inform the site operations manager or other responsible local personnel when the work is complete.

Thunderstorms

Danger Danger Avoid working with electrical installations or being close to towers during thunderstorms. Thunderstorms generate strong electric fields that may result in lightning strokes. It is essential that equipment and facilities be properly earthed to minimize the risks of personal injury and equipment damage.

Contents Chapter 1 Introduction ......................................................................................................................................................... 1 1.1 Overview ............................................................................................................................................................... 1 1.1.1 General ...................................................................................................................................................... 1 1.1.2 Models Of LCU+ ........................................................................................................................................ 1 1.2 Technical Specifications ....................................................................................................................................... 2 1.2.1 Operating Conditions ................................................................................................................................. 2 1.2.2 EMC Requirements ................................................................................................................................... 2 1.2.3 RoHS Compliance ..................................................................................................................................... 2 1.2.4 Safety Requirement: .................................................................................................................................. 2 1.2.5 Protective Level ......................................................................................................................................... 2 1.2.6 Mechanical Data ........................................................................................................................................ 2 1.3 Main Functions...................................................................................................................................................... 3 1.3.1 Measurement Functions: ........................................................................................................................... 3 1.3.2 Display And Indicating Functions ............................................................................................................... 3 1.3.3 Communication Functions ......................................................................................................................... 4 1.3.4 Alarm Functions ......................................................................................................................................... 4 1.3.5 Battery Management Functions: ................................................................................................................ 4 1.3.6 Low Voltage Disconnect ............................................................................................................................ 5 1.4 Hardware Interfaces.............................................................................................................................................. 6 1.4.1 I/O Connector Of Motherboard .................................................................................................................. 6 1.4.2 RS232 Interface......................................................................................................................................... 6 1.4.3 Ethernet Port ............................................................................................................................................. 6 Chapter 2 Installation, Replacement And Power-On ........................................................................................................... 7 2.1 Installation And Replacement ............................................................................................................................... 7 2.1.1 Pre-Steps................................................................................................................................................... 7 2.1.2 Controller Removal .................................................................................................................................... 7 2.1.3 Controller Installation/Replacement ........................................................................................................... 8 2.1.4 Post-Steps ................................................................................................................................................. 8 2.2 Initially Starting, Configuring, And Checking Controller Operation ........................................................................ 8 2.2.1 Controller Initialization ............................................................................................................................... 8 2.2.2 Checking System Status............................................................................................................................ 9 Chapter 3 Operation .......................................................................................................................................................... 10 3.1 Local Controls And Indicators ............................................................................................................................. 10 3.1.1 Front Panel .............................................................................................................................................. 10 3.1.2 Functions Of Indicators ............................................................................................................................ 11 3.1.3 Functions Of Controls .............................................................................................................................. 11 3.2 LCD Menu Tree .................................................................................................................................................. 11

3.2.1 Status ...................................................................................................................................................... 12 3.2.2 Settings.................................................................................................................................................... 12 3.2.3 Manual ..................................................................................................................................................... 20 3.2.4 ECO ......................................................................................................................................................... 20 3.2.5 Quick Setting ........................................................................................................................................... 20 3.2.6 Controller Setting ..................................................................................................................................... 21 3.3 WEB Interface Operation .................................................................................................................................... 22 3.3.1 Setting Up The Internet Explorer Web Browser ....................................................................................... 22 3.3.2 Logging Into The Controller ..................................................................................................................... 23 3.3.3 Homepage Introduction ........................................................................................................................... 24 3.4 WEB Bootloader Interface Operation .................................................................................................................. 28 3.5 Serial Bootloader Interface Operation ................................................................................................................. 29 Appendix 1 Hardware Interfaces ....................................................................................................................................... 33

Chapter 1

Introduction

Chapter 1 Introduction 1.1 Overview 1.1.1 General LCU+ is the next generation DC power controller developed by Emerson Network Power. The LCU+ offers power supply management function, and a user-friendly and easy-to-use interface. Refer to Figure 1-1 for an image of the LCU+.

Figure 1-1

LCU+

1.1.2 Models Of LCU+ The LCU+ is available in four different models as listed in Table 1-1. Table 1-1 Models of LCU+ Models Configuration Display Communication port Protocol

HTTP, SNMP YDN23

Input

M221S

M222S

M223S

RS232,Ethernet

RS232

RS232,Ethernet

RS232

HTTP,SNMP

-

HTTP,SNMP

-

128 × 128 LCD

M224S No LCD

YDN23

YDN23

Analog signal

One battery current input, one bus voltage input, two temperature inputs, four battery mid-voltage inputs

Digital signal

Two load fuse status inputs, four battery fuse status inputs, one bi-stable contactor sampling signal input, four digital signal inputs Load fuse status input and battery fuse status input circuits can be changed into battery fuse status input, load fuse status input or battery mid-voltage input circuits

Output

One mono-stable contactor or bi-stable contactor, one mono-stable contactor, eight dry contact outputs (configurable, realized by external board)

LCU+ Series Controller

User Manual

1

2

Chapter 1

Introduction

1.2 Technical Specifications 1.2.1 Operating Conditions Table 1-2 Operating Conditions Item

Range

Input voltage

19V ~ 60V

Operating temperature range (ambient temperature)

-10C ~ +55C*

Storage temperature

-40C ~ +75C

Relative humidity

≤ 90%RH

Elevation

≤ 3000m

*: The LCD display may become difficult to display at the temperature above 50C or below -10C, and user may need to adjust contrast of the LCD at these temperatures for easy reading.

1.2.2 EMC Requirements Table 1-3 EMC Requirements Item EMI

Test Item

Standard

Requirement

Criterion

Remarks

Radiated Emission

EN55022

Class B

--

--

Conducted Emission

EN55022

Class B

--

--

Immunity to ESD

IEC61000-4-2

8kV contact discharge, 15kV air discharge

A

To enclosure, RS232, Ethernet Port, LCD Panel, and Keys

Immunity to Radiated Magnetic Field

IEC61000-4-3

10V/m, 80MHz-1GHz 1.4 - 2 GHz

A

--

Immunity to EFT

IEC61000-4-4

2kV for DC Power Input Port, 1kV for Communication Port

B

CAN, RS232, Ethernet Communication Port

Immunity to Surge

IEC61000-4-5

800V Common Mode for DC Power Port, 12ohm Internal Resistance; 500V Differential Mode, 2ohm Internal Resistance; 1kV for Signal Port, Common Mode, 42ohm Internal Resistance

B

Signal Ports include CAN, RS232, Ethernet

Immunity to Conducted Magnetic Field

IEC61000-4-6

10Vrms

A

Power Supply, CAN, RS232, Ethernet

EMS

1.2.3 RoHS Compliance Complies with RoHS R6 standard.

1.2.4 Safety Requirement: CE,UL: Certification by third party.

1.2.5 Protective Level IP20

1.2.6 Mechanical Data Dimensions: 202 × 86.8 × 42 (mm, excluding golden finger), 211.5 × 86.6 × 42 (mm, including golden finger) LCU+ Series Controller

User Manual

Chapter 1

Introduction

3

Weight: 400mV + 50mV fault.

DI for Status of bi-stable contactor

1

Absolute Value: 15V ~ 60V open, 0V ~ 1V close.

DI for Auxiliary Contact of SPD

1

--

Extended User DI

4

Expansion board needs to be connected

Digital output Table 1-6 Digital output Item

Quantity

Extended User DO

8

Parameter Capacity of Contact: 1A / 30Vdc or 125Vac, expansion board is needed

Power output Table 1-7 Power Output Item

Parameter

Power Out of External Interface Board

5VDC, 300mA

Power Out of Temperature Sensor

10V ~ 12V, 10mA

LVD drive The controller has 2 LVD drive outputs that can drive two bi-stable / mono-stable contactors. 1. Bi-stable Contactor: 2A maximum drive current with drive pulse width of 500ms ~ 1s. 2. Mono-stable Contactor: 3A maximum starting current and 1A maximum holding current.

1.3.2 Display And Indicating Functions The controller has a green LED for indicating operating status, a yellow LED for indicating observation alarm, and a red LED for indicating major and critical alarms. It also provides a drive output for alarm LED on a system cabinet. The controller LCD can display the AC parameters, DC parameters, rectifier and battery parameters, operating status, alarm status, settings, and control parameters.

LCU+ Series Controller

User Manual

4

Chapter 1

Introduction

1.3.3 Communication Functions The controller can communicate with the host computer in three modes: RS232, Modem, and Ethernet (WEB and SNMP). It can communicate with the rectifiers in CAN-bus mode.

1.3.4 Alarm Functions When the DC power system is in alarm status, the controller generates an alarm automatically and reports the alarm to higher level controller according to actual requirements. The controller records the history alarm and a user can query history alarm through the controller. The alarm contents include communication failure, SPD fault, DC over/under voltage, load disconnection, battery disconnection, BLVD, battery/ambient temperature abnormal, and rectifier alarm. The controller has four different alarm categories. 1. CA, Critical Alarm 2. MA, Major Alarm 3. OA, Observation Alarm 4. None User can set the alarm category for each alarm. User can also block all outgoing alarms from reporting to remote computer and affecting any relay. This function can be programmed to reset automatically after 24 hours. When outgoing alarms are blocked, an ‘Outgoing Alarms Blocked’ alarm is generated.

1.3.5 Battery Management Functions: Battery test The purpose of a battery test is to check the condition of the battery. This test discharges the battery and monitors battery voltage and current. During a battery test, the controller reduces rectifier output to a predefined value and the battery supplies the load and begins to discharge. The controller monitors the battery and saves the result in a battery test log. The controller has two separate battery tests: full load current test and stable current test. Below are the requirements of the full load current test and stable current test. The test can be programmed to start under the following conditions. 1. Manual start 2. Cyclic start after a predefined time schedule Starting a full load battery test or stable current is determined by the discharge current parameter of the stable current test, as illustrated in Figure 1-2.

Figure 1-2 The Principle of Battery Test

Battery boost charge When the batteries have been discharged, the controller can raise system voltage to recharge the batteries quicker, as illustrated in Figure 1-3. The boost charge function can also be used to equalize the difference between the different battery blocks/cells.

LCU+ Series Controller

User Manual

Chapter 1

Introduction

5

Figure 1-3 The Principle of Battery Boost Charge

The boost charge function can be programmed to start under the following conditions. 1. Automatic start after Commercial AC Fault (programmed to start after low battery capacity or high battery charging current is detected) or Battery Test 2. Manual start 3. Cyclic start after a predefined time schedule Temperature compensated battery charge In order to extend battery life, the controller can automatically adjust system voltage as battery ambient temperature changes. Battery temperature compensated charging is a function that lowers system voltage when battery temperature increases and raises system voltage when battery temperature decreases. System voltage follows the characteristics as shown in Figure 1-4.

Figure 1-4 The Principle of Temperature Compensation

Battery current limitation The controller can limit the current to the batteries by adjusting the current limit of the rectifiers. If battery current exceeds the alarm setting of Battery Over Current, a Battery Over Current alarm is issued. Battery prediction The controller can calculate the remaining capacity and the remaining time of the battery while charging or discharging.

1.3.6 Low Voltage Disconnect The controller can disconnect the load or battery in case of under voltage or after a predefined time from when a Commercial AC Fault occurs, in order to prevent the batteries from deep discharge. Deep discharge can result in permanently damaged batteries. The load or battery can be disconnected through the two internal LVD drive outputs. The features of the LVD function are:  The controller can manage a maximum of 2 LVDs, which are internal LVD drive outputs. The controller disconnects these LVDs during an under voltage condition. The disconnection level for each LVD can be set LCU+ Series Controller

User Manual

6

Chapter 1

Introduction

individually. There is one reconnection level for all LVDs. These LVDs can be used for load disconnection and/or battery disconnection.  LVD Disconnection Setting Precautions (1) The disconnection level for load contactor should be set higher than the battery contactor so that the load contactor can always be disconnected before the battery contactor. (2) Maximum 1 LVD is used for battery disconnection to protect from the large current difference between batteries (using the internal LVD2 of the controller is suggested). When Commercial AC returns, the batteries can be close to complete discharge and the voltage difference can generate a large current. Therefore, the current of rectifiers should be limited before the battery reconnection.  The controller can individually disable LVD1 and LVD2, preventing the contactor from opening during an LVD condition.  The controller can reconnect the LVDs when the Commercial AC Fault alarm is inactive and system voltage is higher than the reconnection level.  An LVD alarm is issued when the controller automatically or a User through the controller manually activates an LVD. An LVD Detection Fault alarm is also issued when the controller detects the auxiliary input status is not identical with the LVD operation.

1.4 Hardware Interfaces 1.4.1 I/O Connector Of Motherboard This connector is located at the lower rear part of the controller. It is a 50 PIN PCB golden finger connector. For connector pin-outs, refer to Appendix 1 Hardware Interfaces.

1.4.2 RS232 Interface This connector is located in the left lower part on the controller front panel and it is an RJ45 connector. Table 1-8 RS232 Connector Pin

Name

Definition

1

RTS232

Request for Sending

2

DTR232

Terminal is Ready

3

TXD232

Data Transmit

4

GND

Communication Ground

5

GND

Communication Ground

6

RXD232

Data Receiving

7

DCD232

Carrier Wave Checking

8

--

No connection

1.4.3 Ethernet Port This connector is located in the left upper part on the controller front panel and it is an RJ45 connector. Table 1-9 Definition of Ethernet Port Pin

Name

Definition

1

TX+

Write Signal +

2

TX-

Write Signal -

3

RX+

Read Signal +

4

--

no connection

5

--

no connection

6

RX-

Read Signal -

7

--

no connection

8

--

no connection

LCU+ Series Controller

User Manual

Chapter 2

Installation, Replacement And Power-On

7

Chapter 2 Installation, Replacement And Power-On 2.1 Installation And Replacement The controller is hot swappable. It can be removed and installed with the system operating.

2.1.1 Pre-Steps 1. Performing this procedure may activate external alarms. Do one of the following: 1) If possible, disable these alarms. 2) If these alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system. 2. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.

2.1.2 Controller Removal 1. Loosen the captive fastener securing the top of the latch mechanism to the front of the controller. Pull the top of the latch mechanism away from the controller (this will retract the latch mechanism located on the underside of the controller). This unlocks the controller from the shelf. Refer to Figure 2-1.

Handle is opened

Handle is closed Figure 2-1

Latch Mechanism on the controller

2. Slide the controller completely from the shelf.

LCU+ Series Controller

User Manual

8

Chapter 2

Installation, Replacement And Power-On

2.1.3 Controller Installation/Replacement 1. Loosen the captive fastener securing the top of the latch mechanism to the front of the controller to be installed. Pull the top of the latch mechanism away from the controller (this will retract the latch mechanism located on the underside of the controller). 2. Slide the controller completely into its mounting position. 3. Push the top of the latch mechanism into the front panel of the controller, and secure by tightening the captive fastener. This locks the controller securely to the shelf.

2.1.4 Post-Steps 1. Perform the next procedure, ‘Initially Starting, Configuring, and Checking Controller Operation’. 2. Enable the external alarms, or notify appropriate personnel that this procedure is finished. 3. Ensure that there are no local or remote alarms active on the system.

2.2 Initially Starting, Configuring, And Checking Controller Operation 2.2.1 Controller Initialization After power is first applied to the controller, the following initialization routine is performed. Procedure 1. After the controller is powered on, the language screen appears. 英语 English

Figure 2-2

Language screen

Press the ▲, or ▼ key to select the desired language. Press ENT key to confirm the selection. If no key is pressed within 10 seconds, the controller selects the displayed language automatically.

Wait….

Figure 2-3

Wait screen

2. The controller displays ‘Wait...’ as it performs an initialization routine. The controller has a ‘System Type’ parameter that was pre-programmed for your specific system. This setting determines the initial configuration of the controller parameters such as output voltage and alarm levels. 3. Once initialized, the Main screen is displayed. Note that at the top of the screen the date and time are alternately displayed. 18:15:10

2009-07-28

Float

Float

53.5V

7.8A

53.5V

7.8A

Auto

Alarm

Auto

Alarm

or

Figure 2-4 Main screen

LCU+ Series Controller

User Manual

Chapter 2

Installation, Replacement And Power-On

4. From the Main screen, press ENT key to go to the ‘Main Menu’ screen. MAIN MENU Status Settings Manual ECO Quick Settings

Figure 2-5 Main Menu screen

5. From the Main Menu, select a submenu by repetitively pressing the ▲ or ▼ key on the screen. The selected submenu will be indicated by the cursor. Press ENT key to open the submenu. 

Note

Repeatedly press the ESC key to return in reverse order level by level from any submenu until the Main screen appears. 6. Verify and set the controller as required for your application. Refer to Chapter 3

Operation for procedures.

2.2.2 Checking System Status Procedure 1. Observe the status of the indicators located on the controller. If the system is operating normally, the status is shown in Table 2-1. Table 2-1 Status and Alarm Indicators Indicator Status Minor Alarm Major Alarm

Color

Normal State

Green Yellow Red

LCU+ Series Controller

On Off Off

User Manual

9

10

Chapter 3

Operation

Chapter 3 Operation 3.1 Local Controls And Indicators 3.1.1 Front Panel The controller is offered in four different Models. Each Model provides different features. Refer to Figure 3-1 to Figure 3-4 for a front view of each Model.

Figure 3-1 Front Panel of Controller Model M221S

Figure 3-2 Front Panel of Controller Model M222S

Figure 3-3 Front Panel of Controller Model M223S

Figure 3-4 Front Panel of Controller Model M224S

LCU+ Series Controller

User Manual

Chapter 3

Operation

11

3.1.2 Functions Of Indicators Table 3-1 Functions of Indicators Normal State

Fault State

Status (green)

Indicator

On

Off

If this LED is on, this means the system is operating normally

Fault Cause

Observation Alarm (yellow)

Off

On

The power system has one or more active observation alarms. Alarm conditions are programmable. Refer to Table 3-3 for defaults

Major Alarm (red)*

Off

On

The power system has one or more active major alarms (Major and Critical Alarms). Alarm conditions are programmable. Refer to Table 3-3 for defaults

Note: A Major Alarm initiates an alarm report if alarm report is enabled

3.1.3 Functions Of Controls Table 3-2 Function of Keys on the Panel Key Symbol

Key Name

Function

ENT

Enter



Up

Move Up Cursor or Select the Previous Screen



Down

Move Down Cursor or Select the Next Screen

ESC

Escape

Confirm or Execute

Escape or Cancel

3.2 LCD Menu Tree The overall menu structure is shown in Figure 3-5. 09:20:20 Float 53.4V 404A Manual Normal 08 -11 - 03 Float 53.4V 404A Manual Normal

ENT MAIN MENU Status Settings Manual ECO Quick Settings

ENT

STATUS Active Alarm Rectifiers History Alarm

SETTINGS Alarm Battery AC DC Rectifier Controller Communication

MANUAL Sys Mode: Auto ▼ In Manual

ECO Disable CycPeriod: 168h RectWork: 80% Rect Limit: 1 System Type: 48V / set Capacity: 300Ah LCD Rotation: On

Figure 3-5 Main menu screen

LCU+ Series Controller

User Manual

12

Chapter 3

Operation

3.2.1 Status In the screen of MAINMENU, when cursor is at ‘Status’, press ‘ENT’ to go to the status screen: Status Active Alarm Rectifiers History Alarm

ALARM: 1/2 ALARM: 2/2 ENT Batt Discharge ENT Batt Volt Low Critical Alarm Observation Alarm Start Time: Start Time: 081104 15:52:53 081104 15:52:55 RECTIFIER 1/3 ID: 02070801232 R48800B00 DC Volt: 53.4V DC Curr : 0.0A Curr Limit: 109% AC Volt: 201V AC Status: On DC Status: On AC Derated : N Temp Derated : N

ALARM 001 ENT SPD Fault 08- 07 -10 11:35:22 08- 07 - 10 12:35:22

ALARM 002 DC Volt Low 08 - 07-10 11:35:25 08 - 07-10 12:35:25

Figure 3-6 Status screen

In the status screen, you can move the cursor to ‘Active Alarm’, ‘Rectifiers’, and ‘History Alarm’ respectively and press ‘ENT’ to check the information of active alarm, rectifiers, and history alarm. The rectifier screen shows the information of first rectifier, if you want see the information of next rectifier, just press ‘ENT’. In screen of ‘Active Alarm’, ‘Alarm 1/2’, ‘1/2’ means there are 2 active alarms and this screen is displaying the first active alarm. The alarm level and alarm start time are displayed in the screen In the screen of ‘History Alarm’, the ‘ALARM 001’ means this screen is displaying the first history alarm. The alarm start time and end time are displayed in the screen.

3.2.2 Settings In the Main Menu screen, move the cursor to the item of ‘Setting’ and press ‘ENT’ to enter the Setting menus. Before you access the Setting menu, the system will require you to enter the password first. Method of entering password: For example, to enter the password of ‘640275’: Press ‘ENT’, and the bit will be highlighted, now you can press ▲ or ▼ continuously to enter the numbers from 0 to 9, or enter the letters from ‘a’ to ‘z’ or from capital letter ‘A’ to ‘Z’. After entering ‘6’, press ‘ENT’ and the cursor will move to the next bit, and in the same way, press ▲ or ▼ continuously to enter ‘4’, and you can enter the rest bits ‘0275’ in the same way.

LCU+ Series Controller

User Manual

Chapter 3 ALARM Alarm Level Alarm Control DI Setting

AC Over Volt: 280V Under Volt: 180V PH Fail: 80V AC Input: N AC PH: 3-PH

RECTIFIER Position: Disabl R -Posi: 1-1 HVSD: 59.0V Default V: 53.5V Walk-in On: N Walk-in T: 8s Interval T: 0s AC OverV On: N ACCurrLim : 30A

SETTINGS Alarm Battery AC DC Rectifier Controller Communication

CONTROLLER Lang: English Tzone: GMT + 08:00 Date: 2009-03 -23 Time: 22:17:18 System Type: 48V/1000A DownloadMode:N Reset PWD: N Reset Para: N Oper1PWD: ****** Oper2PWD: ****** AdminPWD: ******

Operation

13

BATTERY Basic LVD Charge Test Temp Comp DC Over Volt2: 58.2V Over Volt1: 58.5V Under V1: 45.0V Under V2: 45.0V Amb High: 40C Amb Low: - 5C

COMMUNICATION Address: 1 CommMode : RS232 Protocol: YDN23 BaudRate: 9600 IP/Subnet/Gate: 10.163.210.91 255.255.255.0 10.163.210.1 CallbackTime: 3 PhoneNumber: 86010677 86010808

Figure 3-7 Settings screen

In the Setting menu, there are 7 items that are ‘Alarm’, ‘Rectifier’, ‘LVD’, ‘AC’, ‘DC’, ‘Controller’ and ‘Communication’ respectively. Move the cursor to ‘Rectifier’ and press ENT, you can configure the following rectifier parameters: Position: Enable or disable the shelf setting. R-Posi: rectifier position in shelf. HVSD: high voltage shut down, rectifier will shut down when its output voltage exceeds this HVSD point. Default V: rectifier default output voltage. Walk-in ON: rectifier walk-in function (soft start) is enabled. Walk-in T: rectifier walk-in time (soft start time). Interval T: rectifier sequential startup interval. AC OverV on: rectifier will shutdown when AC input exceeds AC over voltage point. ACCurrLim: rectifier current limiting value during startup process. Move the cursor to ‘AC’ and press ENT, you can configure the following AC parameters: Over Volt: set the over voltage protection point. Under Volt: set the under voltage protection point. PH Fail: set the phase failure voltage point.

LCU+ Series Controller

User Manual

14

Chapter 3

Operation

AC PH: can set the AC input to 3-phase or single phase (‘1-PH’). Move the cursor to ‘DC’ and press ENT, you can configure the following DC parameters: Over Volt2: set the over voltage protection point2. Over Volt1: set the over voltage protection point1. Under V1: set the DC output under voltage point 1. Under V2: set the DC output under voltage point 2. AmbHigh: set the high ambient temperature. AmbLow: set the low ambient temperature. Move the cursor to ‘Controller’ and press ENT, you can configure the following controller parameters: Lang: set the display language of LCD, you can select English or your local language. Tzone: set the time zone. Date: set the current date. Time: set the current time. System Type: set the system type. DownloadMode: enter the download mode through serial port. Reset PWD: Reset the password to default. Reset Para: Reset parameters to default. Oper1PWD: set the password of operator 1. Oper2PWD: set the password of operator 2. AdminPWD: set the password of administrator. There are three levels password. Default passwords: 1 for operator1, 2 for operator2, and 640275 for administrator. Only administrator can transfer to serial and web download mode and reset the password. Operator2 can change the system type and reset the parameters. Move the cursor to ‘Alarm’ and press ENT, you can enter the alarm menus: Alarm Alarm Level Alarm Control DI Setting

ENT

ALARM LEVEL ENT ALARM LEVEL Alarm Block SPD fault Severity: Severity: Observation Alarm Major Alarm Out Relay: 0 Out Relay: 0

ENT ALARM LEVEL LFuse Alarm Severity: Critical Alarm Out Relay: 6

ALARM CONTROL Alm Voice: Open Clear: History

DI SETTINGS DI NO.: 1 Digital1 Alarm Active: High

Figure 3-8 Alarm screen

Alarm level setting In the submenu of alarm level setting, move cursor before ‘Alarm Block’, press ‘ENT’, then you can set the alarm levels of other alarms such as ‘SPD fault’, ‘LFuse Alarm’, ‘Digital3 Alarm’, etc. In the submenu of alarm level setting, you can set the alarm level of each alarm to observe alarm, major alarm, or critical alarm. You can also set the output relay number that outputs the alarm signal.

LCU+ Series Controller

User Manual

Chapter 3

Operation

15

The characteristics of 4 alarm categories are given in the following table: Table 3-3 characteristics of 4 alarm categories

Alarm levels

Red alarm indicator of controller and system

Yellow alarm indicator of controller and system

Alarm buzzer

Alarm report

Remark

CA (critical alarm)

On

On

Yes

Alarm report is enabled

MA (major alarm)

On

On

Yes

Alarm report is enabled

On

Off

No

Off

Off

No

OA (observation alarm) No alarm

Off

Note: 1. The alarm levels of temperature sensor disconnected alarm and temperature sensor failure alarm, and the corresponding relay output cannot be set through the LCD. The alarm levels of these two alarms and the corresponding relay are the same with those of the high temperature alarm setting. 2. If the analog alarm has two levels of alarm thresholds, and if these two alarm thresholds are set to the same value, then the second level will be cancelled and the first level of the alarm will be displayed in LCD. For example: If the alarm threshold of ‘high temperature 1’ is set to the same with the threshold of ‘high temperature 2’, and if this threshold is set to 40 deg C, then when the temperature exceeds 40 deg C, the system will only issue ‘high temperature 1 alarm’, and will not issue the ‘high temperature 2 alarm’. In the alarm level setting submenu, you can also set the output relay no. for the corresponding alarm. Alarm control menu For the submenu of ‘AlmVoice’ of alarm control menu, you can set it to ‘Open’(audible alarm is enabled) or ‘Close’ (no audible alarm), and you can also set the time of audible alarm and the time can be ‘3min’, ‘10min’, ‘1h’ and ‘4h’. For the submenu of ‘Block Alarm’, you can set ‘Y’ or ‘N’ to select whether the alarm should be blocked or not. For the submenu of ‘Clear’, you can select ‘History’, ‘ECOFail’, ‘Maintain’, ‘ShortTest’, ‘TestFail’ ,’Rect Lost’ ‘Rect Commb’ and ‘Rect Not respond’ to clear corresponding alarm.

LCU+ Series Controller

User Manual

16

Chapter 3

Operation

DI SETTINGS All the alarms can be configured with No.1 to No.8 alarm contacts. ‘0’ means no alarm dry contacts. All the alarm dry contacts provide NC (normally closed) or NO (normally opened) output and the default alarm dry contacts are given in the following table. Table 3-4 Default alarm dry contact setting Dry contact No.

Default alarm

Dry contact 1

Mains Failure

Dry contact 2

DC Under Volt or DC Over Volt

Dry contact 3

Rectifier alarm

Dry contact 4

LVD2

Dry contact 5

LVD1

Dry contact 6

None

Dry contact 7

None

Dry contact 8

None

Table 3-5 lists the alarms that you can scroll through in the ALARM SETTINGS/ALARM LEVEL menu, and also shows their factory default ‘Alarm Level’ and ‘Mapped Output Relay’ settings. Table 3-5 Controller Alarms and Factory Default Settings Alarm name Alarm Block Batt Imbalance

Alarm description

Condition

Default alarm level

Alarm Block

Alarms are blocked by the LCU+

Observation

Batt Imbalance

Battery middle voltage out of the range of ( bus voltage /2) ± 0.6

Major

Into and out of save power status for 5 times in one hour

Major

SavePowerF SavePowerFault ault

Default mapped output relay

Save Power

Save Power Function System is in save power status

Observation

AC High

AC Voltage High

Input phase voltage higher than AC High point

Observation

AC Low

AC Voltage Low

Input phase voltage lower than AC Low point

Observation

AC PH Fail

AC Phase Fail

Input phase fails

Observation

Temp High2

Temperature High 2

Ambient/ Battery temperature higher than Temperature High 2

Major

Temp High1

Temperature High1

Ambient/ Battery temperature higher than normal operation range

Major

Temp Low

Temperature Low

Ambient/ Battery temperature lower than normal operation range

Observation

Batt Over Chg

Battery Over Charge

The charging current over the maximum value

Observation

DC Volt High+

DC Voltage High+

System output voltage much higher than float charge voltage

Critical

2

DC Volt High DC Voltage High

System output voltage higher than float charge voltage

Critical

2

DC Volt Low

System output voltage slightly lower than float charge voltage

Critical

2

DC Volt Low- DC Voltage Low-

System output voltage is much lower than float charge voltage

Critical

2

Rect HVSD

Rectifier HVSD

Rectifier HVSD circuit activated

Major

3

Rectifier LoadShare

The difference between rectifier output current and average output current larger than 8A (+/-4A), and the load of the rectifier greater than 10% of its capacity

Observation

3

Rect Derated Rectifier Derated

The output power of at least one rectifier is derated because of AC undervoltage or overtemperature

Observation

3

Rect Fan Fails

Rectifier Fan Fails

Fan of at least one rectifier fails

Major

3

Rect Protect

Rectifier Protect

AC input voltage out of the range of 85Vac to 295Vac results in at least one rectifier protected

Observation

3

Rect LoadShare

DC Voltage Low

LCU+ Series Controller

User Manual

Chapter 3 Alarm name

Alarm description

Condition

Operation

Default alarm level

17

Default mapped output relay

Rect Failure

Rectifier Failure

Serious load sharing alarm (the output current of the rectifier is lower than 1A, and the average load is Critical greater than 10% of the total rectifier capacity)

Rect TempHigh

Rectifier Temperature High

High temperature protection activated in at least one Major rectifier

3

Rect AC Fail

Rectifier AC Fail

AC input voltage lower than 80Vac

Major

3

Rect Comm Fail

Rectifier Communication Fail

Rectifier(s) unable to communicate with LCU+

Major

3

MultiRect Alarm

Multi rectifier Alarm

Two or more rectifiers have alarms

Critical

System Maintain

System Maintain

System has not been maintained within preset maintenance time

None

Rect Lost

Rectifier Lost

Rectifier reduction detected

Critical

Rect OverLoad

Rectifier OverLoad

Total load current greater than the High Load value

Observation

Mains Failure

Mains Failure

AC input voltage lower than 80Vac

Major

1

LVD2

LVD2

LVD contactor 2 open due to low battery voltage

Critical

4

LVD1

LVD1

LVD contactor 1 open due to low battery voltage

Critical

5

Batt Test Fail Battery Test Fail

Battery discharge test failure (battery voltage is Observation lower than setting value before test time is reached)

DC Volt Fail

DC Voltage Fail

The difference between bus voltage and the set output voltage larger than the set value

Observation

Curr Imbalance

Current Imbalance

The total output current not equal to the sum of the battery current and the load current

Observation

Batt Discharge

Battery Discharge

Batteries are discharging

Observation

Batt Test

Battery Test

The batteries are testing

None

Boost Charge

Boost Charge

The batteries are in boost charge state

None

Manual Mode

Manual Mode

The system is in manual mode

Observation

SelfDetect Fail

SelfDetect Fail

LCU+ detects error in hardware self test

Observation

LVD2Ctrl Fail LVD2 Control Fail

After battery disconnection/ connection signal is sent out, the feedback signal of the contactor is false

Critical

BattFuse Fail

Battery Fuse Fail

Battery fuse(s) or circuit breaker(s) open

Critical

LoadFuse Fail

Load Fuse Fail

Distribution (load) fuse(s) or circuit breaker(s) open

Critical

Digital4

Digital4

User programmable

Major

Digital3

Digital3

User programmable

Major

Digital2

Digital2

User programmable

Major

Digital1

Digital1

User programmable

Major

SPD

SPD

SPD signal interrupted

Major

LCU+ Series Controller

User Manual

3

18

Chapter 3

Operation

Move the cursor to ‘Battery’ to set the battery parameters: Sys Mode: Auto BattFuse : 2 Capacity: 600Ah Bat. Shunt: Y Shunt Coeff -Current: 500A -Volt: 25mV

LVD1: Enbl LVD2: Enbl LVD1 Volt: 44.0V LVD2 Volt: 43.2V

ENT

BATTERY Basic LVD Charge Test Temp Comp

Center Temp: 25C Coeff : 72mV / C Temp1: N Temp2: N Batt T H2: 50C Batt T H1: 50C Batt T L1: 0C

Float: 51.8V Boost: 57.6V Limit: 0.100C Over: 0.300C Auto Boost: - Enable -Current: 0.060C - Capacity: 80.0% Const Boost: - Curr: 0.01C - Time: 180min Cyc Boost: - Enable - Period: 2400h -Time: 720min Boost Limit Time: 1080min

End Test - Volt: 45.2V - Time: 300min - Capacity: 0.70C Cyc Test: Disabl Cyc Test Time: 01 - 01 00:00 04 - 01 00:00 07 - 01 00:00 10 - 01 00:00 Short Test: - Enable: No - Alarm 10A - Period: 1h - Time: 1min ConCurr Test: - Enable: No - Current: 9999A

Figure 3-9 Battery screen

Move cursor to ‘Basic’, you can configure the following parameters: Sys Mode: set the system mode from ‘Auto’ to ‘Manual’ or from ‘Manual’ to ‘Auto’. Method of changing ‘Auto’ to ‘Manual’: As shown in screen of ‘Basic’, in the item of ‘Sys Mode’, press ‘ENT’ to highlight ‘Auto’, and then press ▲ or ▼ to change it into ‘Manual’, and then press ‘ENT’ again to validate the change. BattFuse: set the number of battery fuses. Capacity: Set the battery capacities. Bat. Shunt: set if battery shunt is configured. Shunt Coeff: set current and voltage coefficients. Move cursor to ‘LVD’, you can configure the following parameters: LVD1: Enable or disable LVD1. LVD2: Enable or disable LVD2. LVD1 Volt: set the voltage point at which the LVD1 contactor disconnects. LVD2 Volt: set the voltage point at which the LVD2 contactor disconnects. Move cursor to ‘Charge’, you can configure the following parameters: Float: set the float charging voltage. Boost: set the boost charging voltage.

LCU+ Series Controller

User Manual

Chapter 3

Operation

19

Limit: set the charging current limit. This is the maximum charging current that should be allowed into the battery at any time, as regards to the nominal capacity of the battery. For example, a value of 0.150C10 means that the charging current is limited to 15% of the battery’s nominal capacity. Over: set the over boost charging current. This is the charging current, as regards to the nominal capacity of the battery, at which an over current alarm will be initiated if this current is reached. For example, a value of 0.300C10 means that when the charging current reaches 30% of the battery’s nominal capacity, an alarm will be extended. AutoBoost: An Automatic Boost is started when one of the following conditions is reached. -Enable: Use this submenu to enable or disable auto boost charging. -Curr: This is the battery discharge current, as regards to the nominal capacity of the battery, above which an Automatic Boost is started, when the Automatic Boost function is enabled. For example, a value of 0.060C10 means that an Automatic Boost is started if the battery current is greater than 6% of the battery’s nominal capacity. -Cap: This is the remaining battery capacity under which (less than) an Automatic Boost is started when the Automatic Boost function is enabled. CycBoost -Enable: Use this submenu to enable or disable cyclic boost charging. -Period: Use this submenu to set cyclic boost charging period. This is the interval, in hours, between the boost cycles. -Time: Use this submenu to set cyclic boost charging time. This is the duration of each cycle for the Cyclic Boost when this function is enabled. Const Boost -Curr: Use this submenu to set constant boost charging current. -Time: Use this submenu to set constant boost charging time. BoostLimitTime: Use this submenu to set boost charging time limit beyond which boost charge will be stopped. Move cursor to ‘Test’, you can configure the following parameters: End Test: A Battery Test is interrupted when one of the following conditions is reached. -Volt: This is the ‘end of test voltage level’ for each battery test. -Time: This is the maximum duration, in minutes, for each battery test. -Cap: This is the remaining battery capacity, as regards to the nominal capacity of the battery, at which a Battery Test will be interrupted. For example, a value of 0.700C10 means that when the charging current reaches 70% of the battery’s nominal capacity, the battery test is interrupted. Cyc Test: Displays whether the time (on specific dates) battery test function is enabled (Y) or not (N). During a Timed Battery Test, the output voltage of the rectifiers is reduced so that the batteries power the load. If the batteries fail, the rectifiers power the load. Short Test: A short test is a short duration battery discharge test used to verify that parallel batteries are discharging equally. If the discharge current difference between the two batteries exceeds a preset level (default is 10 A), a Short Test Fault alarm is generated. -Enable: Displays whether the short (at specific intervals) battery test function is enabled (Y) or not (N). -Alarm: Displays the battery current difference at which an alarm will be extended. -Time: Displays the interval, in hours, between short battery tests. -Duration: Displays the duration, in minutes, of each short battery test. ConCurr Test: A Constant Current test is a battery discharge test done at constant current. The controller will automatically adjust the rectifiers to maintain the battery discharge current at the preset value. -Enable: Displays whether the constant current battery test function is enabled (Y) or not (N). -Current: Displays the stable test current. Move cursor to ‘TEMP COMP’, you can configure the following parameters: Center Temp: Displays the temperature, in °C, at which the system operates at normal voltage levels. Temp 1: Displays whether a temperature probe on MB is installed and enabled (Battery or Ambient) or not (None) in position No. 1, and if there is one, whether it is used for battery or ambient temperature measurements.

LCU+ Series Controller

User Manual

20

Chapter 3

Operation

Temp 2: Displays whether a temperature probe on MB is installed and enabled (Battery or Ambient) or not (None) in position No. 2, and if there is one, whether it is used for battery or ambient temperature measurements. Coeff: Displays the temperature compensation slope or rate of change per °C above or below the normal operation level selected in the second line. This value is expressed in millivolt per °C per string (mV/°C/str). For example, for a rate of change of 72mV/°C/str in a 24-cell, 48 V nominal, battery string, the rate of change is 3 mV per cell.

3.2.3 Manual In the Main Menu, move the cursor to ‘Manual’ and press ENT to enter Manual control menu: Change to'Manual' from 'Auto' MANUAL Start: Float LVD1: Reconn LVD2: Reconn RectTrim : 53.5V RectLimit : 121%

MAIN MENU Status Settings Manual ECO Quick Settings

MANUAL ENT Sys Mode: Auto ▼ In Manual

Figure 3-10 Manual screen

In the manual screen, you can perform the following manual control operations: Start: To start float or boost charging or battery test. LVD1: To reconnect or disconnect LVD1 contactor. LVD2: To reconnect or disconnect LVD2 contactor. RectTrim: To adjust the rectifier output voltage. RectLimit: To adjust the rectifier current limiting point.

3.2.4 ECO In the Main Menu, move the cursor to ‘ECO’ and press ENT to enter ECO menu: MAIN MENU Status Settings Manual ECO Quick Settings

ENT

ECO Disable Cyc Period: 168h Rect Work: 80% Rect Limit: 1

Figure 3-11 ECO screen

The following parameters can be configured: ECO: To disable or enable ECO function. Cyc Period: Rectifier redundancy cycle. Rect Work: Optimum operating load point of rectifier. Rect Limit: In ECO mode, the minimum number of rectifiers required.

3.2.5 Quick Setting In the Main Menu, move the cursor to ‘Quick Setting’ and press ENT to enter Quick Setting menu: MAIN MENU Status Settings Manual ECO Quick Settings

ENT

System Type: 48V / 1000A Capacity: 300Ah LCD Rotation: On

Figure 3-12 Quick Settings screen

In the Quick Setting screen, you set the system type and system capacity, as well as the parameters (current, voltage) of load shunts and battery shunts.

LCU+ Series Controller

User Manual

Chapter 3

Operation

21

3.2.6 Controller Setting Table 3-7 summarizes all the settings of the controller. Table 3-6 Controller Settings

DI alarm mode HVSD point Default voltage Restart time upon over voltage Soft-start time with load Soft-start with load enabled Startup upon AC over voltage System ECO enabled Sequencial start interval Input current limiting Rectifier slot setting enabled Rectifier slot setting Number of fuses Nominal capacity Shunt

Available Settings Low limit High limit High / low 56 59 48 58 0 300 8 128 Enabled/Disabled Enabled/Disabled Enabled/Disabled 0 10 1 50 Enabled/Disabled 1 30 0 5 20 5000 Yes / No

Shunt current

1

Shunt voltage Temperature 1 Temperature 2 Float charging voltage Boost charging voltage Charging current limiting Auto boost charging enabled Constant charging current Constant current charging time To boost charging current To boost charging capacity Scheduled boost charging enabled Boost charging protection time Scheduled boost charging cycle Scheduled boost charging time Battery test end time Battery test end voltage Battery test end capacity Scheduled test enabled Constant current test enabled Constant battery test current Short test enabled Short test alarm point Short test cycle Short test time Temperature compensation central point Battery compensation coefficient Battery over temperature point Battery high temperature point Battery low temperature point Over voltage 1 Under voltage 1 Under voltage 2 High ambient temperature Low ambient temperature

1 500 None/Battery/Ambient None/Battery/Ambient 42 58 42 58 0.1 0.25 Yes / No 0.002 0.02 5 1440 0.04 0.08 10 99 Yes / No 60 2880 2 8760 30 2880 5 1440 43.1 57.9 0 1 Yes Yes / No 1 9999 Yes / No 1 100 24 8760 1 60

According to system type 25 Disabled Disabled 53.5 56.4 0.1 Yes 0.01 180 0.06 80 Yes 1080 2400 720 300 45.2 0.7 No No 9999 No 10 720 5

10

40

25

deg.C

0 10 10 -40 40 40 40 10 -40

500 100 100 10 60 60 60 100 10

72 50 50 0 58.5 45 45 40 -5

mv/deg.C deg.C deg.C deg.C V V V deg.C deg.C

Components Alarm

Rectifier

Basic battery parameters

Battery

Battery charge parameters

Battery charge parameters

Battery test parameters

Battery temp compensation coefficient

DC unit

Name

LCU+ Series Controller

2000

User Manual

Default setting High 59 53.5 300 8 Disabled Disabled Disabled 0 30 Disabled 1-1/2-2… 2 600

Unit / V s s / / / s / / Ah

A mV / / V V C10 / C10 Min C10 % / H h Min Min Min C10 / / A / A h min

22

Chapter 3

Operation

LVD1 voltage LVD2 voltage

Available Settings Low limit High limit Yes / No Disabled / Enabled Disabled Disabled /Enabled 40 60 40 60

Over voltage alarm point

0

Under voltage alarm point

0

Phase failure alarm point

0

IP address Subnet code Default gateway Local address Port type Baud rate Protocol Alarm call-back enabled Call back times Call back number 1 Call back number 2 Call back number 3 Language Display time zone System date System time Restore default configurations Set rotating screens

Components

Name Load shunt LVD1 Enabled LVD2 enabled

LVD

AC unit

Communication parameters

Controller parameters

System type

Default setting No Disabled

Unit / /

/ 43.2 43.2

V V

500(866)

280(485)

V

500(866)

180(304)

V

500(866)

80(255)

%

0-255 0-255 0-255 1 RS232/Modem/ETH 1200/2400/4800/9600 YDN23/EEM/RSOC/SOCTPE Yes / No 0 10

192.168.1.2 255.255.255.0 192.168.1.1 255 1 RS232 9600 YDN23 No 3

/ / / / /

English / Chinese

English GMT+08:00

Yes / No Horizontal/Vertical 48V/set, 48V/1000A, 48V/500A, 48V/300A, 48V/100A, 24V/set, 24V/1000A, 24V/500A, 24V/300A and 24V/100A

No Horizontal

/ /

48V/set

3.3 WEB Interface Operation Through the WEB Interface, a remote user can:  View real-time operating information.  Send control commands.  Set programmable parameters.  Set which new alarms are displayed in a pop-up WEB window.  Download and upload configuration files.

3.3.1 Setting Up The Internet Explorer Web Browser Procedure 

Note

This procedure needs to be performed only when the controller is connected to an Internet and the User has set that the access to the Internet needs to be made through proxy. If the controller is connected Internet and the user computer is connected to the Internet, the user cannot disable the proxy, otherwise he will have no access to the controller. 1. Launch Internet Explorer.

LCU+ Series Controller

User Manual

Chapter 3 2. Select Internet Options from the Tools menu. The ‘Internet Options’ window opens. window, select the Connections tab.

Operation

23

In the ‘Internet Options’

Figure 3-13 Internet options window

3. Click on the LAN Settings... button. box and click OK.

The following window opens. In the LAN Settings window, uncheck the proxy

Figure 3-14

LAN settings window

3.3.2 Logging Into The Controller Procedure In Internet Explorer, enter the IP address programmed into the controller and press ENTER. The following WEB Interface window opens. Enter a valid User Name and Password, and then click OK. By default, there are two ‘User Name’ and ‘Password’ combinations, one is ‘admin’ and ‘640275’, the other is ‘operator’ and ‘1’. The username of ‘admin’ has the highest authority and the username ‘operator’ has no authority for uploading and downloading configuration files.

LCU+ Series Controller

User Manual

24

Chapter 3

Operation

Figure 3-15 Access to controller

3.3.3 Homepage Introduction After entering a valid User Name and Password, and clicking OK; the homepage window opens. The homepage window is divided into three areas: System Information, Parameter Settings and Control Functions, and Upload/Download Files.

Figure 3-16

Homepage window

System information At the top of homepage, System Information is displayed, such as System Voltage, System Load, MA/CA Number, OA Number, Battery Mode, Site Name, HW Version, and SW Version. Parameter and control function You can set the following parameters and control functions:  Battery Temp Comp: To disable or enable the battery temperature compensation function. LCU+ Series Controller

User Manual

Chapter 3

Operation

25

 Battery Test: To disable or enable the periodical battery test function. This setting has no effect on the short test.  Current Limitation: To disable or enable the battery charging current limitation function.  Boost Charge: To disable or enable the periodical battery boost charging function. This setting has no effect on auto boost charging.  LVD1 Level, LVD2 Level: To set the low voltage disconnection point.  Under Voltage Level 1, Under Voltage Level 2: To set the under voltage point.  System Volt: To set the system voltage.  Boost Volt: To set the battery boost charging voltage.  NMS1 IP, NMS2 IP: To set the IP address of SNMP  Remote1 IP, Remote2 IP: To set the IP address of EEM protocol.  TCP IP address: To set the IP address of TCP IP protocol. Upload/download files 1. Procedure 1) To upload a configuration file, click the Upload button. The following window opens. Click the Save button.

Figure 3-17

Uploading the configuration file

2) The following window opens. Navigate to where you want the file to be saved. Click the Save button.

Figure 3-18 Save as window

LCU+ Series Controller

User Manual

26

Chapter 3

Operation

After the upload is completed, the system will pop up a window to prompt the user that the upload is successful:

Figure 3-19

Upload successful

3) Users can also upload up to 80 active alarms or history alarms. 4) To download a file, click the Browse button. Navigate to and select the configuration file to be downloaded:

Figure 3-20 Selecting the configuration file

LCU+ Series Controller

User Manual

Chapter 3 Then click Open:

Figure 3-21 Access to the homepage

Then click Download button, the system will pop up a window requiring you to confirm:

Figure 3-22

Confirmation window

LCU+ Series Controller

User Manual

Operation

27

28

Chapter 3

Operation

Click OK, the system will prompt you that the download is successful:

Figure 3-23

Download successful

In the above screen, you can click ‘Back to the Homepage’ to return to the Homepage. Administrator can click ‘Go to Firmware Download Mode’ to enter Bootloader download interface.

3.4 WEB Bootloader Interface Operation Below is the web download webpage. In this webpage administrator can update the firmware. Please ensure that the file name of the firmware is M221S.bin.

Figure 3-24 WEB webpage

LCU+ Series Controller

User Manual

Chapter 3

Operation

29

3.5 Serial Bootloader Interface Operation Serial COM PORT can be used to download and upload files through the following procedure: 1. Connect Serial line to the computer and LCU+. Connect the DB9 terminal to computer, while connect the RJ45 terminal to the port assigned with ‘IOIO’ on LCU+. 2. Open the software of HyperTerminal on the computer, set the parameters according to the following method, here we use COM1, however, other COM PORT is optional dependent on your computer.

Figure 3-25

Choose the COM port

Figure 3-26 Set the parameters of COM port

LCU+ Series Controller

User Manual

30

Chapter 3

Operation

Figure 3-27 Main menu of download/upload

Here we can see there are 4 options, choose ‘1’ to download the application program, choose ‘2’ to download the configuration data, choose ‘3’ to upload the data configuration file, choose ‘4’ to execute the application program. 1. Method of downloading the application program: 1) Press ‘1’ on the keyboard, enter the surface of download; 2) Choose Transfer->Send File…, select the .bin file you want to download;

Figure 3-28

Choose the file

Pay attention that the protocol is Ymodem

LCU+ Series Controller

User Manual

Chapter 3

Figure 3-29

Operation

Choose Ymodem as protocol

3) Press ‘Send’, ‘.bin’ file is transmitted from computer to LCU+;

Figure 3-30 The process of downloading file

4) After the file downloading is completed successfully, the following interface pops up:

Figure 3-31

Downloading file successfully

2. Method of downloading the configuration data: Similar to the download of application program, will not be introduced here; 3. Method of uploading the data configuration file: 1) Press ‘3’ on the keyboard, enter the interface of uploading files:

Figure 3-32

Uploading the file

2) Choose Transfer->Receive File… to select the position in which you save the file

LCU+ Series Controller

User Manual

31

32

Chapter 3

Operation

Figure 3-33 Select the position in which you save the file

Pay attention that the protocol is Ymodem.

Figure 3-34

Choose Ymodem as protocol

3) Press Receive, the file is transmitted from LCU+ to computer.

Figure 3-35 The process of uploading file

4) After the file downloading is completed successfully, the following interface pops up.

Figure 3-36

Uploading file successfully

LCU+ Series Controller

User Manual

Appendix 1

Hardware Interfaces

Appendix 1 Hardware Interfaces Table 1 Pin 1 2 3 4 5 6 7 8 9 10 11

Signal name CRLY1 CAN_L CRLY2 CAN_H CRLY3 IB0DI4 CRLY4 IB0DI3 CRLY5 IB0DI2 CRLY6

12

V_REF_IB

13 14 15 16 17 18

CRLY7 IB0DI1 VCC_IB NC CRLY8 NC

19

TEMP_PS

20

BAT1_SH-

21

TEMP_PS

22

BAT1_SH+

23 24 25 26 27 28 29 30

TEMP2 BFA4 TEMP1 BFA3 FA2 BFA2 FA1 BFA1

31

V_REF

32 33 34 35 36 37

V_BAT NC NC V_BUS NC NC

38

LVD1_AUX

39

LVD2-

40

41

Pin definition of MB1 golden finger

Reference designation DO1 control output signal CAN communication negative DO2 control output signal CAN communication positive DO3 control output signal DI4 input detection signal DO4 control output signal DI3 input detection signal DO5 control output signal DI2 input detection signal DO6 control output signal Reference ground of external interface board DO7 control output signal DI1 input detection signal Power of external interface board Empty DO8 control output signal Empty +12Voutput (temperature sensor power) Route 1 battery current (shunt) input negative The same as PIN19 Route 1 battery current (shunt) input positive Route 2 temperature sensor input Battery fuse 4 Route 1 temperature sensor input Battery fuse 3 Load fuse 2 Battery fuse 2 Load fuse 1 Battery fuse 1 Reference ground of main control circuit (-48V-BUS-, +24V-BUS+) Battery voltage measurement Empty Empty Busbar voltage measurement Empty Empty Contactor 1 auxiliary contact signal sampling

Logic relation OC (voltage endurance: 140V) Standard CAN voltage OC (voltage endurance: 140V) Standard CAN voltage OC (voltage endurance: 140V) 0V ~ 3.3V, voltage signal OC (voltage endurance: 140V) 0V ~ 3.3V, voltage signal OC (voltage endurance: 140V) 0V ~ 3.3V, voltage signal OC (voltage endurance: 140V)

Comments CRLY1 CAN_L CRLY2 CAN_H CRLY3 IB0DI4 CRLY4 IB0DI3 CRLY5 IB0DI2 CRLY6

Reference ground

V_REF_IB

OC (voltage endurance: 140V) 0V ~ 3.3V, voltage signal 4.5V ~ 5.5V / OC (voltage endurance: 140V) /

CRLY7 IB0DI1 VCC_IB NC CRLY8 NC

11V ~ 13V

TEMP_PS

-75 ~ 75mV

BAT1_SH-

11V ~ 13V

TEMP_PS

-75mV ~ 75mV

BAT1_SH+

233µA ~ 373µA 0V ~ 30V, -60V ~ 0V 233µa ~ 373µA 0V ~ 30V, -60V ~ 0V 0V ~ 30V, -60V ~ 0V 0V ~ 30V, -60V ~ 0V 0V ~ 30V, -60V ~ 0V 0V ~ 30V, -60V ~ 0V

TEMP2 BFA4 TEMP1 BFA3 FA2 BFA2 FA1 BFA1

Reference ground

V_REF

0V ~ 30V, -60V ~ 0V / / 0V ~ 30V, -60V ~ 0V / /

V_BAT NC NC V_BUS NC NC

0V ~ 30V, -60V ~ 0V

LVD1_AUX

LVD2 drive signal output

0V ~ 30V, -60V ~ 0V, voltage signal or pulse signal

LVD2-

SPD+

SPD detection positive (internal power supplied)

Switch signal

SPD+

LVD2+

LVD2 drive signal output

0V ~ 30V, -60V ~ 0V, voltage signal or pulse signal

LVD2+

LCU+ Series Controller

User Manual

33

34

Appendix 1 Pin

Hardware Interfaces Signal name

42

SPD-

43

LVD1-

44

Reference designation SPD detection negative (internal power supplied)

Logic relation

Comments

Switch signal

SPD-

LVD1 drive signal output

0V ~ 30V, -60V ~ 0V, voltage signal or pulse signal

LVD1-

PS_BAT-

Battery input negative (-48V battery)

0V ~ 30V, -60V ~ 0V

PS_BAT-

45

LVD1+

LVD1 drive signal output

0V ~ 30V, -60V ~ 0V, voltage signal

LVD1+

46

PS_BUS-

0V ~ 30V, -60V ~ 0V

PS_BUS-

47 48

PS_BAT+ NC

0V ~ 30V, -60V ~ 0V /

PS_BAT+ NC

49

PS_BUS+

0V ~ 30V, -60V ~ 0V

PS_BUS+

50

PGND

Connected to ground

PGND

Bus output negative (-48V rectifier /+24V bus) Battery input (+24V battery) Null Bus output positive (-48V bus/+24V rectifier) Ground

LCU+ Series Controller

User Manual

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF