MiCOM C264 LBUS Configuration PACiS Technical Training Level 2 CS&P Support Team
PCL
• Content LBUS Direct Implementation Use of Library
Schneider Electric - CS&P – C264 LBUS Configuration – E01
2
• Content LBUS Direct Implementation Use of Library
Schneider Electric - CS&P – C264 LBUS Configuration – E01
3
• Add / Configure a LBUS (1) 1) LBUS can be added at MiCOM C264 Level => Protocol Oriented
2) LBUS attributes (example given with T103, cf. C264 AP chapter) Number of retries : number of time C264 will try to poll IED
Acknowledgement time-out : IED response time-out
Synchronization cycle : periodic synchro. frames
Inter frame
Downgraded cycle : when IED not responding, periodic retry
Schneider Electric - CS&P – C264 LBUS Configuration – E01
4
• Add / Configure a LBUS (2) 3) Connect LBUS to communication port
4) Configure C264 communication Communication parameters Note that COM3 and COM4 should have same transmission speed For COM3 and COM4 => Tx carrier management set to Switched
Schneider Electric - CS&P – C264 LBUS Configuration – E01
5
• Add / Configure an IED (1) 1) IED can be added at LBUS Level
2) IED attributes (example given with T103, cf. C264 AP chapter) IED @ on LBUS
Automatic disturbance available for SMT + local name for COMTRADE file display in viewing tool (WaveWin, …) N/A for DNP3
No space in the name of the directory
Schneider Electric - CS&P – C264 LBUS Configuration – E01
6
• Add / Configure an IED (2) 3) IED Should be connected to a Acq Profile 1) Add the IED Acq Profile under LBUS 2) Complete relation “has for acq profile” between IED and acq profile
4) Acq Profile attributes (example given with T103, cf. C264 AP chapter) 4.1) General Tab
IED main protective function code here T103 FTYPE = 160 (OC)
Schneider Electric - CS&P – C264 LBUS Configuration – E01
7
• Add / Configure an IED (3) 4) Acq Profile attributes (example given with T103, cf. C264 AP chapter) 4.2) Acquisition Tab GI period : - 0 => GI at connection only - advised = 3600s (1h)
MV reduction coefficient : - 1.2 or 2.4 (cf. IED documentation) - MV = red_coeff x transmitted val x nominal val.
Nominal values per setting group AI channel : Channel number as per IED setting
5) Under Acq Profile => disturbance channels
Schneider Electric - CS&P – C264 LBUS Configuration – E01
8
• Add / Configure IED Mapping (1) 1) Add DP (DataPoints) addresses IED Mapping : set of SPS, DPS, MPS, MV, SPC, DPC, … managed by IED (cf. IED documentation)
To add a DP address : 1) select kind of DP Mapping 2) Through Objects Entry Window, add an address
Schneider Electric - CS&P – C264 LBUS Configuration – E01
9
• Add / Configure IED Mapping (2) 2) Configure DP addresses (example given with T103) 2.1) SPS address SPS address : as per IED documentation, here ASDU, FTYP and INF (as per IEC-60870-5-103 standard public or IED private)
2.2) DPS address DPS address : as per IED documentation, here ASDU, FTYP and INF (as per IED private)
Contact = relevant status
Schneider Electric - CS&P – C264 LBUS Configuration – E01
10
• Add / Configure IED Mapping (3) 2) Configure DP addresses (example given with T103) 2.3) SPC address SPC address : as per IED documentation, here ASDU, FTYP and INF (as per IEC-60870-5-103 standard public or IED private)
DE/SBO regarding LBUS protocol 2.4) MV address MV address : as per IED documentation, here ASDU, FTYP, INF and index=rank in ASDU (as per IEC-608705-103 standard public or IED private)
Schneider Electric - CS&P – C264 LBUS Configuration – E01
11
• Add / Configure IED Mapping (4) 3) Link DP with the relevant address (example given with T103) => Relation “has for IED address” Under datapoint : DP link with relevant address on the IED
Schneider Electric - CS&P – C264 LBUS Configuration – E01
12
• Miscellaneous (1) 1) IED System information
IED SPS Com : Gives connection status between C264 and IED (animated at PACiS OI Level)
IED SPS Synchro : Gives IED synchronization status
+ IED RDRE Ready : SPS indicates when IED disturbance file is ready at C264 level Note : “ext IEC Mapping” added by “SBUS automatic addressing”, but not in template
Schneider Electric - CS&P – C264 LBUS Configuration – E01
13
• Miscellaneous (2) 2) Modbus LBUS
Standard attributes : same as T103 (nb of retries, response timeout, …)
Synchronization : None/AREVA (for AREVA Modbus)
Modbus IED acq. Profile : definition of Modbus type (MiCOM S20 = AREVA Modbus)
Schneider Electric - CS&P – C264 LBUS Configuration – E01
14
• Miscellaneous (3) 3) Reminder Limits up to 4 communication links (LBUS+TBUS serial or ethernet) up to 4 LBUS up to 2 TBUS
Connections BIU port 1 => RS232/RS485
Jumpers on BIU board
BIU port 2 => RS232/RS485/RS422
CPU port 3 => RS232 CPU port 4 => RS232
Schneider Electric - CS&P – C264 LBUS Configuration – E01
ECU200 => Fiber Optics ECU201 => RS485/RS422
15
• Content LBUS Direct Implementation Use of Library
Schneider Electric - CS&P – C264 LBUS Configuration – E01
16
• Why using a template? 1) Direct implementation : => configure IED general info => add mapping (DP addresses) => add DP and link Repeat for each IED and then test resulting configuration => JOB INTENSIVE 2) Template instantiations : => DP and links already done => only configure IED name and @ => repeatable => all DP already tested OK => IED integration => SAVE TIME
Schneider Electric - CS&P – C264 LBUS Configuration – E01
17
• List of integrated IED and relevant templates 1) Integrated IED : => PACiS version + IED version => integration report => relevant template 2) List of integrated IED : => LN database “Products and System Info”
Schneider Electric - CS&P – C264 LBUS Configuration – E01