MiCOM C264 LHMI Configuration PACiS Technical Training Level 2 CS&P – Support Team

PCL

• Content  GHU Board Configuration  Bitmaps configuration  LCD configuration  LED assignment

Schneider Electric - CS&P – C264 LHMI Configuration – E01

2

• Content  GHU Board Configuration  Bitmaps configuration  LCD configuration  LED assignment

Schneider Electric - CS&P – C264 LHMI Configuration – E01

3

• Configure the GHU board 1) C264 with or without LCD => 2 possible GHU boards

2) GHU attributes

HMI Type : - Simple : no LCD and LED#4 is not configurable - Complete : LCD, LED#4 is configurable and GHU should be linked to a graphic object typed Computer Workspace

Schneider Electric - CS&P – C264 LHMI Configuration – E01

4

• GHU Board Sons & Relations Board status MPS

Set of LED : LED#4 not configurable if GHU type = Simple

Relation with graphic configuration : Completed if GHU type = Complete

Schneider Electric - CS&P – C264 LHMI Configuration – E01

5

• Content  GHU Board Configuration  Bitmaps configuration  LCD configuration  LED assignment

Schneider Electric - CS&P – C264 LHMI Configuration – E01

6

• What for? 1) On C264 LCD, in bay panels = > Single Line Diagrams - static objects (lines, bitmaps) - animated objects

2) Graphic table for bitmaps (up to 150)

Note : Starting database is containing bitmap table (IEC)

Schneider Electric - CS&P – C264 LHMI Configuration – E01

7

• Bitmap Attributes Short Name : Rule : put bitmap index in prefix

Bitmap index : Bitmap index = bitmap identification used at LCD configuration level

Bitmap type : -5-uple = animated -single = non-animated

Schneider Electric - CS&P – C264 LHMI Configuration – E01

8

• Bitmap Representation (1) Default Open* Closed*

* associated information in Closed/Set or Open/Reset state Note : bitmap max size = 64x64 pixels Schneider Electric - CS&P – C264 LHMI Configuration – E01

9

• Bitmap Representation (2)

Default

Open

Closed

Withdrawn Open

Withdrawn Closed

Note : withdrawn = combination of DPS position + withdrawn SPS Schneider Electric - CS&P – C264 LHMI Configuration – E01

10

• Content  GHU Board Configuration  Bitmaps configuration  LCD configuration  LED assignment

Schneider Electric - CS&P – C264 LHMI Configuration – E01

11

• Add / Configure a Computer Workspace 1) Graphic Part / Computer Workspace

2) Attributes

Short Name L/R password protection : Operator has to enter password when changing bay control mode (Local/Remote)

Schneider Electric - CS&P – C264 LHMI Configuration – E01

12

• Add / Configure a Bay Mimic 1) Graphic Part / Computer Workspace

2) Attributes Short Name MV bargraph : Horizontal / Vertical Advise to not use

Module Name display 3) Relations => relation with the represented bay Mimic rank : one bay can be represented on 1 or 2 mimics Schneider Electric - CS&P – C264 LHMI Configuration – E01

13

• Add Graphic Objects in Bay Mimic (1) 1) Typical Bay Mimic (128x128 pixels) Time : optional

Mandatory : - Bay L/R - Interlock bypass (local activation) - Synchrocheck bypass (local activation)

Controllable devices : - LHMI Gen Modules - up to 9 per mimic

Static graphics : lines, single bitmaps

Note : no graphics outside of area => C264 failure Schneider Electric - CS&P – C264 LHMI Configuration – E01

14

• Add Animated Objects in Bay Mimic (2) 2) Add a LHMI Gen Module

3) Configure a LHMI Gen Module Short Name : different from displayed name

Control availability : Yes = controllable from LCD

4) LHMI Gen Module Sons Graphic object with datapoint relation is managed by SPS or DPS

Displayed name 4 characters

Representing bitmap index Schneider Electric - CS&P – C264 LHMI Configuration – E01

15

• Add Animated Objects in Bay Mimic (3) 5) Add a LHMI Transformer

6) LHMI Transformer configuration Graphic object with TPI relation is managed by TPI

Minimum, Current and Maximum TPI values are mandatory

Bitmap index Schneider Electric - CS&P – C264 LHMI Configuration – E01

16

• Content  GHU Board Configuration  Bitmaps configuration  LCD configuration  LED assignment

Schneider Electric - CS&P – C264 LHMI Configuration – E01

17

• Reminder 1) LED can be animated by SPS or DPS status

13 available LED for Complete HMI 12 available LED for Simple HMI (LED#4 = C264 Local/Remote)

LED can be : - Off - On - Blinking fast - Blinking slow

Schneider Electric - CS&P – C264 LHMI Configuration – E01

18

• Assign a SPS/DPS to LED 1) Under SPS, add the relation “has state displayed on LED”

2) Complete the relation

Complete the relation by selecting LED of the GHU board Schneider Electric - CS&P – C264 LHMI Configuration – E01

19

• Assign a SPS/DPS to LED 3) Configure the relation for behaviour of LED :

LED Behaviour : - For status - For alarm

LED Behaviour per status : Closed / OPEN / Invalid behaviour Off / On / Blinking Slow / Blinking Fast

LED Behaviour for alarm : Off / On / Blinking Slow / Blinking Fast

Note 1 : 1 LED represents only 1 datapoint Note 2 : behaviour for alarm will depend on alarm definition in datapoint profile of this DP. Schneider Electric - CS&P – C264 LHMI Configuration – E01