Basic Modules Configuration PACiS Technical Training Level 2 CS&P – Support Team

PCL

• Content  Circuit Breaker  Disconnector Switch  Transformer  Generic Module

Schneider Electric - CS&P – Basic Modules Configuration – E01

2

• Content  Circuit Breaker  Disconnector Switch  Transformer  Generic Module

Schneider Electric - CS&P – Basic Modules Configuration – E01

3

• Add / Configure a CB 1) Circuit Breaker can be added at Bay level in Electric hierarchy. CB 3 phases (1 DPS for global position) / CB 1 phase (single phase acq.) 2) CB attributes Short Name : SCE Key + appears in viewers + printers

CB Type : 3-ph, 1-ph, other

Nodes definition : AVR

Schneider Electric - CS&P – Basic Modules Configuration – E01

4

• CB-1ph Configuration (1) 1) CB 1 phase basic configuration 1.1) Type 1 Typed CB Computed Position DPS : - Global CB Position, computed by C264 - is feedback of DPC command - is animated on PACiS OI / C264 LCD

Typed Switchgear ph A,B,C DPS : CB single phase position, acquired by C264 (DI/CCU or IED)

Typed Switch Ctrl DPC : 1.2) Type 2

DPC Open/Close

Position can be computed by : - typed Switch ph A DPS - typed Phases Not Together SPS Note : Positions can be SPS Schneider Electric - CS&P – Basic Modules Configuration – E01

5

• CB-1ph Configuration (2) 2) CB enhanced configuration => possible sons Typed Lock Control SPC : Operator lock

Typed Selection SPC : when SBO, activated at selection

Typed Sync CB Close : Synchrocheck

Typed Lock SPS : Lock status

Typed Phase Not Together SPS : - Indicates if all phases are in same position - holds a timer for CB trip

Typed withdrawn SPS : brushable devices

Schneider Electric - CS&P – Basic Modules Configuration – E01

6

• CB-3ph Configuration 1) CB 3 phases basic configuration 1.1) Type 1 Typed Switch Ctrl DPC : DPC Open/Close

Typed CB Computed Position DPS : - Global CB Position, computed by C264 - is feedback of DPC command - is animated on PACiS OI / C264 LCD

Typed Switchgear position DPS : CB Position, acquired by C264 (DI/CCU or IED)

1.2) Type 2 Typed Switch Ctrl DPC can be replaced by : - typed Switch Ctrl SPC for CLOSE - typed Switch ph A SPC for OPEN Note : Positions can be SPS Schneider Electric - CS&P – Basic Modules Configuration – E01

7

• Content  Circuit Breaker  Disconnector Switch  Transformer  Generic Module

Schneider Electric - CS&P – Basic Modules Configuration – E01

8

• Add / Configure a Disconnector Switch 1) Disconnector switch is a Switchgear, it can be added at Bay level in Electric hierarchy. 2) DS attributes Short Name : SCE Key + appears in viewers + printers

Nodes definition : AVR

Schneider Electric - CS&P – Basic Modules Configuration – E01

9

• Switchgear Configuration (1) 1) Switchgear basic configuration Typed Switch Ctrl DPC : DPC Open/Close

Typed Switchgear position DPS : Switchgear Position, acquired by C264 (DI/CCU or IED)

Note : Position can be SPS Schneider Electric - CS&P – Basic Modules Configuration – E01

10

• Switchgear Configuration (2) 2) Switchgear enhanced configuration => possible sons Typed Lock Control SPC : Operator lock

Typed Selection SPC : when SBO, activated at selection

Typed Lock SPS : Lock status

Typed withdrawn SPS : brushable devices

Schneider Electric - CS&P – Basic Modules Configuration – E01

11

• Content  Circuit Breaker  Disconnector Switch  Transformer  Generic Module

Schneider Electric - CS&P – Basic Modules Configuration – E01

12

• Add / Configure a Transformer 1) Transformer module can be added at Transformer or Generic Bay level in Electric hierarchy. 2) Transformer attributes Short Name : SCE Key + appears in viewers + printers

Transformer Type : - Auto wound : no galvanic isolation between HV and LV sides, tap changer acts simultaneously in primary and secondary : TAP RAISE = LV LOWER - Double wound : galvanic isolation between HV and LV sides, tap changer acts in primary : TAP RAISE = LV RAISE

Power value / impedance : AVR

Nodes definition : AVR Schneider Electric - CS&P – Basic Modules Configuration – E01

13

• Transformer Configuration (1) 1) Transformer basic configuration Tap Changer built-in function: cf. DATAPOINTS CONFIGURATION course

Typed Raise/Lower DPC : Tap Change control

Typed TPI MV : cf. DATAPOINTS CONFIGURATION course

Schneider Electric - CS&P – Basic Modules Configuration – E01

14

• Transformer Configuration (2) 2) Transformer enhanced configuration => possible sons Typed MCB Open SPC : - AVR - In case of invalid tap changing, it will stop supplying tap changer (power cutting)

Typed TAP Select SPC : when SBO, activated at selection

Typed Higher Position / Lower Position SPS : - SET when max tap and min tap are reached

Typed Tap in progress SPS : - physically acquired by C264 - impact on control sequence

Typed Goto min/max DPC : DPC doing raise until max tap / lower until min tap

Schneider Electric - CS&P – Basic Modules Configuration – E01

15

• Content  Circuit Breaker  Disconnector Switch  Transformer  Generic Module

Schneider Electric - CS&P – Basic Modules Configuration – E01

16

• Features 1) Generic Modules are : - non typed modules - contains generic datapoints - huge range of use => non particular context

- ADVISE : DON’T USE GENERIC MODULES for CB and disconnector if you have : - Built-in automation (AVR, Synchrocheck, Autorecloser) - lock, hardware selection, withdrawn

Example for switching device

Schneider Electric - CS&P – Basic Modules Configuration – E01

17