L2 V4 03 Datapoints Profiles E 01
Short Description
SAS...
Description
Datapoints Profiles PACiS Technical Training Level 2 CS&P – Support Team
PCL
• Content Generalities Inputs Profiles Outputs Profiles
Schneider Electric - CS&P – Datapoints Profiles – E01
2
• Content Generalities Inputs Profiles Outputs Profiles
Schneider Electric - CS&P – Datapoints Profiles – E01
3
• SCE Profiles : Input Profiles Supervision Profiles … What are Supervision DataPoint? xPS
SPS, DPS, MPS,
FSS, SBMC dependency Few acquisition options
SPS_Profile DPS_Profile MPS_Profile
State labels
MV MV,
MV_Profile FOR
Archive&Logging / state
xCT Counter, Counter_Profile
Interlock Boolean / state Alarm / state
Schneider Electric - CS&P – Datapoints Profiles – E01
4
• SCE Profiles : Output Profiles Control Profiles … What are Control DataPoint? xPC
SPC, DPC,
DE / SBO Few acquisition options
SPC_Profile DPC_Profile
State labels
SetPoint SetPoint, SetPoint_Profile FOR
Archive&Logging on event Interlock Boolean / state Alarm on Negative Ack.
Schneider Electric - CS&P – Datapoints Profiles – E01
5
• Content Generalities Inputs Profiles Outputs Profiles
Schneider Electric - CS&P – Datapoints Profiles – E01
6
• xPS Profiles (1) Single, Double, Multi Point Status : General Tab Allow FSS on DP
No
Yes/No
Allow SBMC on DP
No
(Yes/No) when bay has SBMC ON : SBMC Substitutes values to RCP by: - SPS : Set/Reset/Suppressed - DPS : Jammed/Open/Close/Suppressed - MPS : Undefined/Suppressed
Toggling Filtering for SPS, DPS Yes/No
Initial Status For software info => status at start-up Never use Motion Schneider Electric - CS&P – Datapoints Profiles – E01
7
• xPS Profiles (2) Single, Double, Multi Point Status : State Labels tab : Alarms / Log Print SPS : Set/Reset DPS : Jammed/Open/Close/Undefined MPS : 1 among N( Open/Close R/L => Remote/Local N and associate DP impact labels
Schneider Electric - CS&P – Datapoints Profiles – E01
8
• xPS Profiles (3) Single, Double, Multi Point Status : State Treatment Tab State by State, archiving policy For OI :
For C264 : - Archive & Logging = Archive means stored in event list (2048 events in memory) & Logging means displayed in event list of front face (200 events).
- No Archive, No logging = nothing in SQL Historian database - Archive only = all states in VTQ (states/values) SQL Historian database tables (Trend Viewer) - Archive & Logging = all states in VTQ (states/values) SQL Historian database tables + states marked with “Logging” in Events SQL database table (Event Viewer + Archive viewer + printer)
Relation “has events logged on” for SOE printing Schneider Electric - CS&P – Datapoints Profiles – E01
9
• xPS Profiles (4) Single, Double, Multi Point Status : Interlock tab : Boolean value by state SPS Set and Reset Boolean value in all PSL and interlocking : convention : SET=TRUE, RESET=FALSE
DPS Jammed, Open and Closed Boolean value in all PSL and interlocking : convention : CLOSED=TRUE, OPEN=FALSE, JAMMED=INVALID,UNDEFINED=INVALID
Note : For MPS, no convention => depends on context of use Schneider Electric - CS&P – Datapoints Profiles – E01
10
• xPS Profiles (5) Single, Double, Multi Point Status : Alarm tab, Alarm definition state by state Alarm Generation Appearance/Appearance disappearance 1 / 2 alarms
Alarmed state or not Spurious SPS is Set and never reset Alarm not generated if state follow control (RFI SBUS) Delay before alarm generation (if DP reset for example) Gravity 1->5 Audibility (klaxon)
Relation “has alarm events logged on” for alarm printing Schneider Electric - CS&P – Datapoints Profiles – E01
Alarms are acknowledged by operator, but clearing can be manual or automatic 11
• MV Profile (1) Measurement Values : General tab Allow FSS on MV
No
Yes/No
Allow SBMC on MV
No
(Yes/No) when bay in SBMC ON: Substitutes values by Suppressed
MV value display on OI Mimic No # after decimal. U to display unit
Schneider Electric - CS&P – Datapoints Profiles – E01
12
• MV Profile (2) Measurement Values : State Labels tab
Alarms Log Print IED disconnected Board acquisition saturated Digital Measurement coding error 4-20mA DC input when under 4mA Threshold violation
Schneider Electric - CS&P – Datapoints Profiles – E01
13
• MV Profile (3) Measurement Values : State Treatment Tab State by State, archiving policy For OI : - No Archive, No logging = nothing in SQL Historian database - Archive only = all states in VTQ (states/values) SQL Historian database tables (Trend Viewer) - Archive & Logging = all states in VTQ (states/values) SQL Historian database tables + states marked with “Logging” in Events SQL database table (Event Viewer + Archive viewer + printer)
Note : - Archive only for valid => value will be available for trend viewer - Archive & Logging for SelfCheckFault and Unknown to store acquisition errors Schneider Electric - CS&P – Datapoints Profiles – E01
14
• MV Profile (4) Measurement Values :
Interlocking tab
Note : Goal is use MV associated status in PSL. No convention => depends on context of use
Schneider Electric - CS&P – Datapoints Profiles – E01
15
• MV Profile (5) Measurement Values :
Alarm Management tab Alarm Generation Appearance/Appearance disappearance 1 / 2 alarms
Alarmed state or not
Delay before alarm generation Gravity 1->5 Audibility (klaxon)
Alarms are acknowledged by operator, but clearing can be manual or automatic Schneider Electric - CS&P – Datapoints Profiles – E01
16
• MV Profile (6) Measurement Values :
Mean Value tab cf. PS06 Reference hour : - Hour of day for min/max/average values calculation - Daily mean values stored in monthly VTQ table for 15 months
Reference day : - Day of month for min/max/average values calculation - Monthly mean values stored in yearly VTQ table for about 5 years
.csv VTQ tables SQL HISTORIAN VTQ SQL HISTORIAN Event
Daily
Monthly
Yearly
Schneider Electric - CS&P – Datapoints Profiles – E01
35 days storing
15 months storing
5 years storing
17
• Counter Profile Single, Double CounTer: Status…
Like MV Except
Pulse value multiplicative coefficient
Counter over max value
Double Counter invalidity Schneider Electric - CS&P – Datapoints Profiles – E01
18
• Content Generalities Inputs Profiles Outputs Profiles
Schneider Electric - CS&P – Datapoints Profiles – E01
19
• xPC Profiles (1) Single, Double Point Control: General tab
Define SBUS control sequence in one or two steps : In DE : Client send control to Server Server send back Ack to Client In SBO : - Step Selection kept by Server with Time Out [0..600](s) - Step Execution SBO Many => transformer Note : At PACiS OI Level, DE/SBO pop-up. DE with SBO popup = Control is DE appearing in SBO-like popup Schneider Electric - CS&P – Datapoints Profiles – E01
20
• xPC Profiles (2) Single, Double Point Control: Set Point => no order
use and labels
Usage : Some controls are using only one “channel” e.g. Master Trip Reset
Labels “status” for control send logging, alarms, popup buttons
On Control Schneider Electric - CS&P – Datapoints Profiles – E01
21
• xPC Profiles (3) Single, Double Point Control:
interlocking and FBD tab
PSL status on control False/True
Note : Goal is use xPC associated status in PSL.
Schneider Electric - CS&P – Datapoints Profiles – E01
22
• xPC Profiles (4) Single, Double Point Control:
Alarm on NACK
Alarm on control Yes/No Delay [0..120] Gravity [1..5] Klaxon [Yes/No] + Relation Clearing Acknowledged alarms
V4.7
Schneider Electric - CS&P – Datapoints Profiles – E01
23