Datapoints Profiles PACiS Technical Training Level 2 CS&P – Support Team

PCL

• Content  Generalities  Inputs Profiles  Outputs Profiles

Schneider Electric - CS&P – Datapoints Profiles – E01

2

• Content  Generalities  Inputs Profiles  Outputs Profiles

Schneider Electric - CS&P – Datapoints Profiles – E01

3

• SCE Profiles : Input Profiles Supervision Profiles … What are Supervision DataPoint? xPS

SPS, DPS, MPS,

FSS, SBMC dependency Few acquisition options

SPS_Profile DPS_Profile MPS_Profile

State labels

MV MV,

MV_Profile FOR

Archive&Logging / state

xCT Counter, Counter_Profile

Interlock Boolean / state Alarm / state

Schneider Electric - CS&P – Datapoints Profiles – E01

4

• SCE Profiles : Output Profiles Control Profiles … What are Control DataPoint? xPC

SPC, DPC,

DE / SBO Few acquisition options

SPC_Profile DPC_Profile

State labels

SetPoint SetPoint, SetPoint_Profile FOR

Archive&Logging on event Interlock Boolean / state Alarm on Negative Ack.

Schneider Electric - CS&P – Datapoints Profiles – E01

5

• Content  Generalities  Inputs Profiles  Outputs Profiles

Schneider Electric - CS&P – Datapoints Profiles – E01

6

• xPS Profiles (1) Single, Double, Multi Point Status : General Tab Allow FSS on DP

No

Yes/No

Allow SBMC on DP

No

(Yes/No) when bay has SBMC ON : SBMC Substitutes values to RCP by: - SPS : Set/Reset/Suppressed - DPS : Jammed/Open/Close/Suppressed - MPS : Undefined/Suppressed

Toggling Filtering for SPS, DPS Yes/No

Initial Status For software info => status at start-up Never use Motion Schneider Electric - CS&P – Datapoints Profiles – E01

7

• xPS Profiles (2) Single, Double, Multi Point Status : State Labels tab : Alarms / Log Print SPS : Set/Reset DPS : Jammed/Open/Close/Undefined MPS : 1 among N( Open/Close R/L => Remote/Local N and associate DP impact labels

Schneider Electric - CS&P – Datapoints Profiles – E01

8

• xPS Profiles (3) Single, Double, Multi Point Status : State Treatment Tab State by State, archiving policy For OI :

For C264 : - Archive & Logging = Archive means stored in event list (2048 events in memory) & Logging means displayed in event list of front face (200 events).

- No Archive, No logging = nothing in SQL Historian database - Archive only = all states in VTQ (states/values) SQL Historian database tables (Trend Viewer) - Archive & Logging = all states in VTQ (states/values) SQL Historian database tables + states marked with “Logging” in Events SQL database table (Event Viewer + Archive viewer + printer)

Relation “has events logged on” for SOE printing Schneider Electric - CS&P – Datapoints Profiles – E01

9

• xPS Profiles (4) Single, Double, Multi Point Status : Interlock tab : Boolean value by state SPS Set and Reset Boolean value in all PSL and interlocking : convention : SET=TRUE, RESET=FALSE

DPS Jammed, Open and Closed Boolean value in all PSL and interlocking : convention : CLOSED=TRUE, OPEN=FALSE, JAMMED=INVALID,UNDEFINED=INVALID

Note : For MPS, no convention => depends on context of use Schneider Electric - CS&P – Datapoints Profiles – E01

10

• xPS Profiles (5) Single, Double, Multi Point Status : Alarm tab, Alarm definition state by state Alarm Generation Appearance/Appearance disappearance 1 / 2 alarms

Alarmed state or not Spurious SPS is Set and never reset Alarm not generated if state follow control (RFI SBUS) Delay before alarm generation (if DP reset for example) Gravity 1->5 Audibility (klaxon)

Relation “has alarm events logged on” for alarm printing Schneider Electric - CS&P – Datapoints Profiles – E01

Alarms are acknowledged by operator, but clearing can be manual or automatic 11

• MV Profile (1) Measurement Values : General tab Allow FSS on MV

No

Yes/No

Allow SBMC on MV

No

(Yes/No) when bay in SBMC ON: Substitutes values by Suppressed

MV value display on OI Mimic No # after decimal. U to display unit

Schneider Electric - CS&P – Datapoints Profiles – E01

12

• MV Profile (2) Measurement Values : State Labels tab

Alarms Log Print IED disconnected Board acquisition saturated Digital Measurement coding error 4-20mA DC input when under 4mA Threshold violation

Schneider Electric - CS&P – Datapoints Profiles – E01

13

• MV Profile (3) Measurement Values : State Treatment Tab State by State, archiving policy For OI : - No Archive, No logging = nothing in SQL Historian database - Archive only = all states in VTQ (states/values) SQL Historian database tables (Trend Viewer) - Archive & Logging = all states in VTQ (states/values) SQL Historian database tables + states marked with “Logging” in Events SQL database table (Event Viewer + Archive viewer + printer)

Note : - Archive only for valid => value will be available for trend viewer - Archive & Logging for SelfCheckFault and Unknown to store acquisition errors Schneider Electric - CS&P – Datapoints Profiles – E01

14

• MV Profile (4) Measurement Values :

Interlocking tab

Note : Goal is use MV associated status in PSL. No convention => depends on context of use

Schneider Electric - CS&P – Datapoints Profiles – E01

15

• MV Profile (5) Measurement Values :

Alarm Management tab Alarm Generation Appearance/Appearance disappearance 1 / 2 alarms

Alarmed state or not

Delay before alarm generation Gravity 1->5 Audibility (klaxon)

Alarms are acknowledged by operator, but clearing can be manual or automatic Schneider Electric - CS&P – Datapoints Profiles – E01

16

• MV Profile (6) Measurement Values :

Mean Value tab cf. PS06 Reference hour : - Hour of day for min/max/average values calculation - Daily mean values stored in monthly VTQ table for 15 months

Reference day : - Day of month for min/max/average values calculation - Monthly mean values stored in yearly VTQ table for about 5 years

.csv VTQ tables SQL HISTORIAN VTQ SQL HISTORIAN Event

Daily

Monthly

Yearly

Schneider Electric - CS&P – Datapoints Profiles – E01

35 days storing

15 months storing

5 years storing

17

• Counter Profile Single, Double CounTer: Status…

Like MV Except

Pulse value multiplicative coefficient

Counter over max value

Double Counter invalidity Schneider Electric - CS&P – Datapoints Profiles – E01

18

• Content  Generalities  Inputs Profiles  Outputs Profiles

Schneider Electric - CS&P – Datapoints Profiles – E01

19

• xPC Profiles (1) Single, Double Point Control: General tab

Define SBUS control sequence in one or two steps : In DE : Client send control to Server Server send back Ack to Client In SBO : - Step Selection kept by Server with Time Out [0..600](s) - Step Execution SBO Many => transformer Note : At PACiS OI Level, DE/SBO pop-up. DE with SBO popup = Control is DE appearing in SBO-like popup Schneider Electric - CS&P – Datapoints Profiles – E01

20

• xPC Profiles (2) Single, Double Point Control: Set Point => no order

use and labels

Usage : Some controls are using only one “channel” e.g. Master Trip Reset

Labels “status” for control send logging, alarms, popup buttons

On Control Schneider Electric - CS&P – Datapoints Profiles – E01

21

• xPC Profiles (3) Single, Double Point Control:

interlocking and FBD tab

PSL status on control False/True

Note : Goal is use xPC associated status in PSL.

Schneider Electric - CS&P – Datapoints Profiles – E01

22

• xPC Profiles (4) Single, Double Point Control:

Alarm on NACK

Alarm on control Yes/No Delay [0..120] Gravity [1..5] Klaxon [Yes/No] + Relation Clearing Acknowledged alarms

V4.7

Schneider Electric - CS&P – Datapoints Profiles – E01

23