L2 V4 02 Datapoints Configuration E 01
April 29, 2017 | Author: Rinda_Rayna | Category: N/A
Short Description
SAS...
Description
Datapoints Configuration PACiS Technical Training Level 2 CS&P – Support Team
PCL
• Content SPS, DPS, MPS MV, TPI, Counters SPC, DPC, SetPoints Datapoints Quality
Schneider Electric - CS&P – Datapoints Configuration – E01
2
• Content SPS, DPS, MPS MV, TPI, Counters SPC, DPC, SetPoints Datapoints Quality
Schneider Electric - CS&P – Datapoints Configuration – E01
3
• Typed / Generic xPS TYPED DIGITAL INFORMATION It is an information which is representing a special input regarding the MiCOM C264 inner automations. Examples : - Switchgear Position DPS, Locking device status SPS, Bay Local/Remote DPS
GENERIC INFORMATION It is a standard information which can be configured at any level. Examples : - Module xPS, Bay xPS, VoltageLevel xPS, Substation xPS (x=S,D,M)
Schneider Electric - CS&P – Datapoints Configuration – E01
4
• Typed / Generic xPS Mapping SPS It is an input which is produced by mapping to another DP. Each state of this DP is mapped and corresponds to a state of the mapping SPS.
Day cyclic SPS It is a transient SPS which is triggered every day at fixed time. (accuracy of +/- 1 minute)(8 max per C264).
Schneider Electric - CS&P – Datapoints Configuration – E01
5
• Add / Configure a SPS (1) 1) SPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some SPS are System Info. 2) SPS attributes Short Name : SCE Key + appears in C264 local SOE
Long Name : appears in viewers + printers
Detection Mode : permanent : DI remains ON as far as signal is ON
Time tagging : done at starting/end of signal filtering
Persistence filtering : LHMI display :
SPS should remain valid “Set” or “Reset” during the configured timer
yes = SPS in state list (MSC)
Forcing Management : if FSS enabled, auto/manual force Schneider Electric - CS&P – Datapoints Configuration – E01
6
• Add / Configure a SPS (2) 3) SPS can be acquired by DIU/CCU board, IED. Some SPS are computed by C264 application (C264 automation, …) => Relations under a SPS
Has for IED address : SPS acquired by IED
V4.7
Wired on : DI Channel SPS acquired by DIU/CCU board Schneider Electric - CS&P – Datapoints Configuration – E01
7
• Add / Configure a DPS (1) 1) DPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some DPS are System Info. 2) DPS attributes Short Name : SCE Key + appears in C264 local SOE
Long Name : appears in viewers + printers
Time tagging : done at starting/end of motion
Motion & Persistence filtering :
LHMI display :
Motion : eliminate transients 00 and/or 11 motion states Persistence : DPS should remain valid “Open” or “Closed” during the configured timer
yes = DPS in state list (MSC)
Forcing Management : if FSS enabled, auto/manual force Schneider Electric - CS&P – Datapoints Configuration – E01
8
• Add / Configure a DPS (2) 3) DPS can be acquired by DIU/CCU board, IED. Some DPS are computed by C264 application (C264 automation, …) => Relations under a DPS Wired on : DPS acquired by 2 channels (“open” and “closed”) on DIU/CCU board
DPS computed from 2 SPS : DPS acquired using 2 SPS, 1 for “open” and 1 for “closed”
Has for IED address : DPS acquired by IED
Schneider Electric - CS&P – Datapoints Configuration – E01
9
• Add / Configure a MPS (1) 1) MPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some MPS are System Info. A MPS can have a maximum 16 valid states. 2) MPS attributes
Short Name : SCE Key + appears in C264 local SOE
Long Name : appears in viewers + printers
Motion & Persistence filtering : Motion : inhibition (cf. next slide) Persistence : MPS should remain in one valid state during the configured timer
LHMI display : yes = MPS in state list (MSC)
Forcing Management : if FSS enabled, auto/manual force
Schneider Electric - CS&P – Datapoints Configuration – E01
10
• Add / Configure a MPS (2) Example : Change State with Filtering “all DI =0 “ 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
Before change state
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
During change all DI =0
0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16
End of change state
Example : Change State with Filtering “all DI =1 “ 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 Schneider Electric - CS&P – Datapoints Configuration – E01
During change all DI =1
11
• Add / Configure a MPS (3) 3) MPS can be acquired by DIU/CCU board, IED. Some MPS are computed by C264 application (C264 automation, …) => Relations under a MPS Wired on : MPS acquired by a maximum of 16 channels on DIU/CCU boards
Has for IED address : MPS acquired by IED Schneider Electric - CS&P – Datapoints Configuration – E01
12
• Content SPS, DPS, MPS MV, TPI, Counters SPC, DPC, SetPoints Datapoints Quality
Schneider Electric - CS&P – Datapoints Configuration – E01
13
• Add / Configure a MV (1) 1) MV can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some MV are System Info. 2) MV attributes in General Tab Short Name : SCE Key + appears in C264 local SOE
Long Name : appears in viewers + printers
Analogue Type : Analogue (AI,CT/VT,IED) or Digital Measurement
Forcing Management : if FSS enabled, automatic force to a given value
LHMI display : yes = MV in measurements list (MSC)
Schneider Electric - CS&P – Datapoints Configuration – E01
MV transmission : SBUS, LHMI
14
• Add / Configure a MV (2) 3) MV attributes in Value Features Tab
Minimum / Maximum Value : scaled values for SCADA and OI display + Full Scale definition
Thresholds definition : scaled values for LLL, LL, L, H, HH, HHH thresholds + hysteresis
Schneider Electric - CS&P – Datapoints Configuration – E01
15
• Add / Configure a MV (3) 4) MV attributes in Scaling Tab
Scaling Low : Linear / Quadratic
Minimum / Maximum acquisition values : Scaling coefficients : scaled value = A1 x acq. Value + B1
Up to 20 segments
Additional segments : A2, B2 - A3, B3 - ... Schneider Electric - CS&P – Datapoints Configuration – E01
- if transducer 0/10 mA : min=0, max=10* - if transducer 4/20 mA : min=0, max=16* - if voltage of CT/VT with nominal ph-N = 57.7 V min=0, max=57.7* - if IED (T103 : min=0, max=1; Modbus : cf. IED documentation) … * schedule a max value = 120% of expected max max=12, max=20, max=70 ... (transducers can measure more and display overflow and undershoot measurements). 16
• Add / Configure a MV (4) 5) MV can be acquired by AIU/TMU/DIU/CCU board, IED. Some MV are computed by C264 application (C264 automation, …) => Relations under a MV Wired on DI Channels : Digital Measurements acquired by a maximum of 64 channels on DIU/CCU boards
Has for IED address : MV acquired by IED
Computed by CT/VT board : relation to be configured
Wired on AI Channel : Channel to be configured (cf. next slide) Schneider Electric - CS&P – Datapoints Configuration – E01
17
• Add / Configure a MV (5) 6) AI Board channel configuration Transducer range :
Scanning acquisition period : cf. C264 configuration, Measurements tab
Schneider Electric - CS&P – Datapoints Configuration – E01
18
• Add / Configure a TPI (1) 1) TPI can ONLY be added under a Tap Changer object belonging to a Transformer module. => Add / Configure a Tap Changer object : Built-in function : Tap Changer
Min TAP, Max TAP
Execution timeout : Time allowed for Tap Changing
Schneider Electric - CS&P – Datapoints Configuration – E01
19
• Add / Configure a TPI (2) 2) TPI attributes : 2.1) General Tab
TPI type : - Analogue Tap Position acquired by AIU or IED, - Coded Digital Measurement (1/N, decimal, gray, BCD) acquired by DIU
Note : Tabs are not the same - Value Features is common to Analogue and Digital TPI - Scaling & Tap Position for Analogue - Tap Position for Digital Schneider Electric - CS&P – Datapoints Configuration – E01
20
• Add / Configure a TPI (3) 2) TPI attributes : 2.2) Value Features Tab
Minimum / Maximum Value : Should comply with Tap Changer object configuration
Thresholds definition : scaled values for LLL, LL, L, H, HH, HHH thresholds
Schneider Electric - CS&P – Datapoints Configuration – E01
21
• Add / Configure a TPI (4) 2) TPI attributes : 2.3) Scaling Tab (for Analogue TPI only) Minimum / Maximum Acquisition Value : Same as for a MV
2.4) Tap Position Tab For Analogue TPI : filtering => transient “intertap” filtering current valid range => gives validity DC input range for each tap
For Digital TPI : filtering => signal validation inhibition => transient “intertap” filtering
Schneider Electric - CS&P – Datapoints Configuration – E01
22
• Add / Configure a TPI (5) 3) TPI can be acquired by AIU/DIU/CCU board, IED. => Relations under a TPI
Wired on DI Channels : Digital TPI acquired by a maximum of 64 channels on DIU/CCU boards
Has for IED address : TPI acquired by IED
Wired on AI Channel : Channel to be configured
Schneider Electric - CS&P – Datapoints Configuration – E01
23
• Add / Configure a Counter (1) 1) Counter can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. 2) Counter attributes in General Tab Short Name : SCE Key + appears in C264 local SOE
Long Name : appears in viewers + printers
Counter Type : Standard (standard DI counting) Energy import / Energy export
Counter Acquisition : validation => min pulse length to be counted invalidity => for double, non complementarity
LHMI display : yes = Counter in measurements list (MSC) Schneider Electric - CS&P – Datapoints Configuration – E01
Counter Management : cf. next slide
24
• Add / Configure a Counter (2) 2) Counter attributes in General Tab
Counter Total for IED counters : Yes => IED is sending real counter value No => IED is sending non-scaled value
Counter cumulative period : - configure a period at the end of which the counter value is transmitted (SBUS, LHMI) - possible values : 10mn, 15mn, 30mn, 1h, 2h, 3h, … 24h -at the end of this period, counter value can be reset (C264 re-start counting from 0)
Schneider Electric - CS&P – Datapoints Configuration – E01
25
• Add / Configure a Counter (3) 3) Counter can be acquired by DIU/CCU board, IED. Some Counters are computed by C264 application (C264 automation, …) => Relations under a Counter Wired on : Single counter => 1 DI Channel Double counter => 2 DI Channels
Has for IED address : Counter acquired by IED
integrate : Counter computed by MV integration (example : P) Counter type is not “Standard” but “Energy import” or “Energy export”
!
Schneider Electric - CS&P – Datapoints Configuration – E01
Integration of P or Q : In case the scale and unit is to big ((MVarh MVarh for ex.), if energy is changing of less than 1MVarh in 10 minutes, the value is not sent (counter is integer so 0.2 value is equal to 0). 26
• Content SPS, DPS, MPS MV, TPI, Counters SPC, DPC, SetPoints Datapoints Quality
Schneider Electric - CS&P – Datapoints Configuration – E01
27
• Typed / Generic xPC TYPED CONTROL It is an information which is representing a special functionality regarding the MiCOM C264 inner automations. Examples : - Switch Ctrl DPC, Locking device status SPC, Bay Local/Remote DPC, Sync CB Close
GENERIC CONTROL It is a standard control which can be configured at any level. Examples : - Module xPC, Bay xPC, VoltageLevel xPC, Substation xPC (x=S,D)
Schneider Electric - CS&P – Datapoints Configuration – E01
28
• Add / Configure a SPC (1) 1) SPC can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some SPC are System Info. 2) SPC attributes General Tab Short Name : SCE Key + appears in C264 local SOE
Long Name : appears in viewers + printers
Activation Mode : - transient => configure pulse duration - permanent - permanent until feedback
LHMI display : yes = SPC in control list (MSC)
Schneider Electric - CS&P – Datapoints Configuration – E01
Inter Control timeout : no possibility to execute 2 consecutive orders during this timer
29
• Add / Configure a SPC (2) 3) SPC execution may be dependant on Local/Remote status of Substation/Bay, on SBMC and/or on control uniqueness => SPC attributes Dependencies tab Bay Local/Remote : Bay Local => control from LHMI allowed, from OI & SCADA not allowed
SBMC : advised not to use SBMC (put No) if needed, local transfer when SS is in Remote
Control Uniqueness Substation Local/Remote : SS Local => control from OI allowed, from SCADA forbidden Note : This is internal automation existing and configurable for all xPC.
Schneider Electric - CS&P – Datapoints Configuration – E01
30
• Add / Configure a SPC (3) 4) SPC can be executed on DOU/CCU board, IED. Some SPC are computed by C264 application (C264 automation, …) => Relations under a SPC Interlock SPS : holds a logic allowing/blocking the control
Associated DO channel status SPS : for hardwired SPC only
Auto/Manu dependency : blocks the operator control if an automation is in progress => connect to SPS/DPS giving automation status
Feedback definition : Wired on : DO Channel
for C264 acknowledgement cf. slide “§3.4”
SPC executed on DOU/CCU board
Has for IED address : SPC executed by IED Schneider Electric - CS&P – Datapoints Configuration – E01
31
• Add / Configure a DPC (1) 1) DPC can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some DPC are System Info. 2) DPC attributes Short Name : SCE Key + appears in C264 local SOE
Long Name : appears in viewers + printers
Activation Mode : - transient => configure pulse duration (2 channels “open” / “close”) - permanent - permanent until feedback
LHMI display : yes = DPC in control list (MSC)
Schneider Electric - CS&P – Datapoints Configuration – E01
Inter Control timeout : no possibility to execute 2 consecutive orders during this timer
32
• Add / Configure a DPC (2) 3) DPC execution is dependant on one hand from Local/Remote status of Substation/Bay and on the other hand from control uniqueness => DPC attributes Dependencies tab Bay Local/Remote : Bay Local => control from LHMI allowed, from OI & SCADA not allowed
SBMC : advised not to use SBMC (put No) if needed, local transfer when SS is in Remote
Control Uniqueness Substation Local/Remote : SS Local => control from OI allowed, from SCADA forbidden Note : This is internal automation existing and configurable for all xPC.
Schneider Electric - CS&P – Datapoints Configuration – E01
33
• Add / Configure a DPC (2) 4) DPC can be executed on DOU/CCU board, IED. Some DPC are computed by C264 application (C264 automation, …) => Relations under a DPC 2 Interlock SPS (open/close): holds a logic allowing/blocking the controls
2 Associated DO channel status SPS : for hardwired DPC only
Auto/Manu dependency : blocks the operator control if an automation is in progress => connect to SPS/DPS giving automation status
Feedback definition : Wired on : DO Channel
for C264 acknowledgement cf. slide “§3.4”
DPC executed on DOU/CCU board
Has for IED address : DPC executed by IED Schneider Electric - CS&P – Datapoints Configuration – E01
34
• Configure a xPC feedback 1) SPC/DPC can have for feedback a SPS/DPS => C264 checks if control success (ex: CB control, feedback CB position) => Example given for DPC with DPS feedback DPC Relation “has for feedback” with 2 attributes : DPS
Schneider Electric - CS&P – Datapoints Configuration – E01
- execution timeout : maximum time allowed to get feedback - status check : C264 will check status before performing control
35
• Add / Configure a SetPoint (1) 1) SetPoints can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. 2) SetPoint attributes Short Name : SCE Key + appears in C264 local SOE
Long Name : appears in viewers + printers
SetPoint type :
For Digital SetPoint : LHMI display :
increment value pulse duration
yes = SetPoint in control list (MSC)
Minimum / Maximum value : raw values for SetPoint validity Schneider Electric - CS&P – Datapoints Configuration – E01
36
• Add / Configure a SetPoint (2) 3) SetPoint execution is dependant on one hand from Local/Remote status of Substation/Bay and on the other hand from control uniqueness => SetPoint attributes Dependencies tab Bay Local/Remote : Bay Local => control from LHMI allowed, from OI & SCADA not allowed
SBMC : advised not to use SBMC (put No) if needed, local transfer when SS is in Remote
Control Uniqueness Substation Local/Remote : SS Local => control from OI allowed, from SCADA forbidden Note : This is internal automation existing and configurable for all Setpoints.
Schneider Electric - CS&P – Datapoints Configuration – E01
37
• Add / Configure a SetPoint (3) 4) SetPoints can be executed on DOU/CCU board, IED. Some SetPoints are computed by C264 application (C264 automation, …) => Relations under a SetPoints DO Channels : C264 will close DO channels using configured code (BCD, binary, …)
Auto/Manu dependency : blocks the operator control if an automation is in progress => connect to SPS/DPS giving automation status
Has for IED address : SP executed by IED
AO Channels : C264 will set AO channel
Schneider Electric - CS&P – Datapoints Configuration – E01
38
• Content SPS, DPS, MPS MV, TPI, Counters SPC, DPC, SetPoints Datapoints Quality
Schneider Electric - CS&P – Datapoints Configuration – E01
39
• SPS Status SPS STATUS
MEANING
RESET
Electric status 0
SET
Electric status 1
SELF CHECK FAULTY
Faulty DI Channel on board
TOGGLING
Toggling filtering has detected behaviour
UNKNOWN
IED acquiring DP is disconnected from C264
FORCED SET *
SPS is Forced Set by C264 (FSS enable)
SUBSTITUTED SET *
SPS is Substituted Set by Oper. (FSS enable)
SUPPRESSED
SPS is Suppressed by Oper. (FSS enable)
* => Same for RESET Quality => gives the nature of invalidity
Schneider Electric - CS&P – Datapoints Configuration – E01
40
• DPS Status DPS STATUS
MEANING
OPEN
Electric status 01
CLOSED
Electric status 10
JAMMED
Electric status 00
UNDEFINED
Electric status 11
SELF CHECK FAULTY
Faulty DI Channel on board
TOGGLING
Toggling filtering has detected behaviour
UNKNOWN
IED acquiring DP is disconnected from C264
FORCED OPEN *
DPS is Forced Open by C264 (FSS enable)
SUBSTITUTED OPEN *
DPS is Substituted Open by Op. (FSS enable)
SUPPRESSED
DPS is Suppressed by Oper. (FSS enable)
* => Same for CLOSED Quality => gives the nature of invalidity Schneider Electric - CS&P – Datapoints Configuration – E01
41
• MPS Status MPS STATUS
MEANING
STATE 1 -> STATE 16
Only one channel activated
UNDEFINED
No channel or more than one activated
SELF CHECK FAULTY
Faulty DI Channel on board
TOGGLING
Toggling filtering has detected behaviour
UNKNOWN
IED acquiring DP is disconnected from C264
FORCED STATE N *
MPS is Forced St. N by C264 (FSS enable)
SUBSTITUTED STATE N *
MPS is Substituted St. N by Op. (FSS enable)
SUPPRESSED
MPS is Suppressed by Oper. (FSS enable)
Quality => gives the nature of invalidity Schneider Electric - CS&P – Datapoints Configuration – E01
42
• MV Status MV STATUS
MEANING
VALID
MV in between min/MAX and/or L/H threshold
UNDEFINED
No DI channel or more than one activated DM
SELF CHECK FAULTY
Faulty DI/AI Channel on board
TOGGLING
Toggling filtering has detected behaviour
UNKNOWN
IED acquiring DP is disconnected from C264
FORCED
MV is Forced C264 (FSS enable)
SUBSTITUTED STATE N *
MV is Substituted by Op. (FSS enable)
SUPPRESSED
MV is Suppressed by Oper. (FSS enable)
OVERRANGE
Acquisition out of range
OPEN CIRCUIT
No current on AI channel (mA)
OVERSHOOT [1,2,3]
Over H, HH, HHH Threshold
UNDERSHOOT [1,2,3]
Under L, LL, LLL Threshold
Quality => gives the nature of invalidity Schneider Electric - CS&P – Datapoints Configuration – E01
43
View more...
Comments