L2 V4 02 Datapoints Configuration E 01

April 29, 2017 | Author: Rinda_Rayna | Category: N/A
Share Embed Donate


Short Description

SAS...

Description

Datapoints Configuration PACiS Technical Training Level 2 CS&P – Support Team

PCL

• Content  SPS, DPS, MPS  MV, TPI, Counters  SPC, DPC, SetPoints  Datapoints Quality

Schneider Electric - CS&P – Datapoints Configuration – E01

2

• Content  SPS, DPS, MPS  MV, TPI, Counters  SPC, DPC, SetPoints  Datapoints Quality

Schneider Electric - CS&P – Datapoints Configuration – E01

3

• Typed / Generic xPS  TYPED DIGITAL INFORMATION It is an information which is representing a special input regarding the MiCOM C264 inner automations. Examples : - Switchgear Position DPS, Locking device status SPS, Bay Local/Remote DPS

 GENERIC INFORMATION It is a standard information which can be configured at any level. Examples : - Module xPS, Bay xPS, VoltageLevel xPS, Substation xPS (x=S,D,M)

Schneider Electric - CS&P – Datapoints Configuration – E01

4

• Typed / Generic xPS  Mapping SPS It is an input which is produced by mapping to another DP. Each state of this DP is mapped and corresponds to a state of the mapping SPS.

 Day cyclic SPS It is a transient SPS which is triggered every day at fixed time. (accuracy of +/- 1 minute)(8 max per C264).

Schneider Electric - CS&P – Datapoints Configuration – E01

5

• Add / Configure a SPS (1) 1) SPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some SPS are System Info. 2) SPS attributes Short Name : SCE Key + appears in C264 local SOE

Long Name : appears in viewers + printers

Detection Mode : permanent : DI remains ON as far as signal is ON

Time tagging : done at starting/end of signal filtering

Persistence filtering : LHMI display :

SPS should remain valid “Set” or “Reset” during the configured timer

yes = SPS in state list (MSC)

Forcing Management : if FSS enabled, auto/manual force Schneider Electric - CS&P – Datapoints Configuration – E01

6

• Add / Configure a SPS (2) 3) SPS can be acquired by DIU/CCU board, IED. Some SPS are computed by C264 application (C264 automation, …) => Relations under a SPS

Has for IED address : SPS acquired by IED

V4.7

Wired on : DI Channel SPS acquired by DIU/CCU board Schneider Electric - CS&P – Datapoints Configuration – E01

7

• Add / Configure a DPS (1) 1) DPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some DPS are System Info. 2) DPS attributes Short Name : SCE Key + appears in C264 local SOE

Long Name : appears in viewers + printers

Time tagging : done at starting/end of motion

Motion & Persistence filtering :

LHMI display :

Motion : eliminate transients 00 and/or 11 motion states Persistence : DPS should remain valid “Open” or “Closed” during the configured timer

yes = DPS in state list (MSC)

Forcing Management : if FSS enabled, auto/manual force Schneider Electric - CS&P – Datapoints Configuration – E01

8

• Add / Configure a DPS (2) 3) DPS can be acquired by DIU/CCU board, IED. Some DPS are computed by C264 application (C264 automation, …) => Relations under a DPS Wired on : DPS acquired by 2 channels (“open” and “closed”) on DIU/CCU board

DPS computed from 2 SPS : DPS acquired using 2 SPS, 1 for “open” and 1 for “closed”

Has for IED address : DPS acquired by IED

Schneider Electric - CS&P – Datapoints Configuration – E01

9

• Add / Configure a MPS (1) 1) MPS can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some MPS are System Info. A MPS can have a maximum 16 valid states. 2) MPS attributes

Short Name : SCE Key + appears in C264 local SOE

Long Name : appears in viewers + printers

Motion & Persistence filtering : Motion : inhibition (cf. next slide) Persistence : MPS should remain in one valid state during the configured timer

LHMI display : yes = MPS in state list (MSC)

Forcing Management : if FSS enabled, auto/manual force

Schneider Electric - CS&P – Datapoints Configuration – E01

10

• Add / Configure a MPS (2) Example : Change State with Filtering “all DI =0 “ 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16

Before change state

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16

During change all DI =0

0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16

End of change state

Example : Change State with Filtering “all DI =1 “ 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 Schneider Electric - CS&P – Datapoints Configuration – E01

During change all DI =1

11

• Add / Configure a MPS (3) 3) MPS can be acquired by DIU/CCU board, IED. Some MPS are computed by C264 application (C264 automation, …) => Relations under a MPS Wired on : MPS acquired by a maximum of 16 channels on DIU/CCU boards

Has for IED address : MPS acquired by IED Schneider Electric - CS&P – Datapoints Configuration – E01

12

• Content  SPS, DPS, MPS  MV, TPI, Counters  SPC, DPC, SetPoints  Datapoints Quality

Schneider Electric - CS&P – Datapoints Configuration – E01

13

• Add / Configure a MV (1) 1) MV can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some MV are System Info. 2) MV attributes in General Tab Short Name : SCE Key + appears in C264 local SOE

Long Name : appears in viewers + printers

Analogue Type : Analogue (AI,CT/VT,IED) or Digital Measurement

Forcing Management : if FSS enabled, automatic force to a given value

LHMI display : yes = MV in measurements list (MSC)

Schneider Electric - CS&P – Datapoints Configuration – E01

MV transmission : SBUS, LHMI

14

• Add / Configure a MV (2) 3) MV attributes in Value Features Tab

Minimum / Maximum Value : scaled values for SCADA and OI display + Full Scale definition

Thresholds definition : scaled values for LLL, LL, L, H, HH, HHH thresholds + hysteresis

Schneider Electric - CS&P – Datapoints Configuration – E01

15

• Add / Configure a MV (3) 4) MV attributes in Scaling Tab

Scaling Low : Linear / Quadratic

Minimum / Maximum acquisition values : Scaling coefficients : scaled value = A1 x acq. Value + B1

Up to 20 segments

Additional segments : A2, B2 - A3, B3 - ... Schneider Electric - CS&P – Datapoints Configuration – E01

- if transducer 0/10 mA : min=0, max=10* - if transducer 4/20 mA : min=0, max=16* - if voltage of CT/VT with nominal ph-N = 57.7 V min=0, max=57.7* - if IED (T103 : min=0, max=1; Modbus : cf. IED documentation) … * schedule a max value = 120% of expected max max=12, max=20, max=70 ... (transducers can measure more and display overflow and undershoot measurements). 16

• Add / Configure a MV (4) 5) MV can be acquired by AIU/TMU/DIU/CCU board, IED. Some MV are computed by C264 application (C264 automation, …) => Relations under a MV Wired on DI Channels : Digital Measurements acquired by a maximum of 64 channels on DIU/CCU boards

Has for IED address : MV acquired by IED

Computed by CT/VT board : relation to be configured

Wired on AI Channel : Channel to be configured (cf. next slide) Schneider Electric - CS&P – Datapoints Configuration – E01

17

• Add / Configure a MV (5) 6) AI Board channel configuration Transducer range :

Scanning acquisition period : cf. C264 configuration, Measurements tab

Schneider Electric - CS&P – Datapoints Configuration – E01

18

• Add / Configure a TPI (1) 1) TPI can ONLY be added under a Tap Changer object belonging to a Transformer module. => Add / Configure a Tap Changer object : Built-in function : Tap Changer

Min TAP, Max TAP

Execution timeout : Time allowed for Tap Changing

Schneider Electric - CS&P – Datapoints Configuration – E01

19

• Add / Configure a TPI (2) 2) TPI attributes : 2.1) General Tab

TPI type : - Analogue Tap Position acquired by AIU or IED, - Coded Digital Measurement (1/N, decimal, gray, BCD) acquired by DIU

Note : Tabs are not the same - Value Features is common to Analogue and Digital TPI - Scaling & Tap Position for Analogue - Tap Position for Digital Schneider Electric - CS&P – Datapoints Configuration – E01

20

• Add / Configure a TPI (3) 2) TPI attributes : 2.2) Value Features Tab

Minimum / Maximum Value : Should comply with Tap Changer object configuration

Thresholds definition : scaled values for LLL, LL, L, H, HH, HHH thresholds

Schneider Electric - CS&P – Datapoints Configuration – E01

21

• Add / Configure a TPI (4) 2) TPI attributes : 2.3) Scaling Tab (for Analogue TPI only) Minimum / Maximum Acquisition Value : Same as for a MV

2.4) Tap Position Tab For Analogue TPI : filtering => transient “intertap” filtering current valid range => gives validity DC input range for each tap

For Digital TPI : filtering => signal validation inhibition => transient “intertap” filtering

Schneider Electric - CS&P – Datapoints Configuration – E01

22

• Add / Configure a TPI (5) 3) TPI can be acquired by AIU/DIU/CCU board, IED. => Relations under a TPI

Wired on DI Channels : Digital TPI acquired by a maximum of 64 channels on DIU/CCU boards

Has for IED address : TPI acquired by IED

Wired on AI Channel : Channel to be configured

Schneider Electric - CS&P – Datapoints Configuration – E01

23

• Add / Configure a Counter (1) 1) Counter can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. 2) Counter attributes in General Tab Short Name : SCE Key + appears in C264 local SOE

Long Name : appears in viewers + printers

Counter Type : Standard (standard DI counting) Energy import / Energy export

Counter Acquisition : validation => min pulse length to be counted invalidity => for double, non complementarity

LHMI display : yes = Counter in measurements list (MSC) Schneider Electric - CS&P – Datapoints Configuration – E01

Counter Management : cf. next slide

24

• Add / Configure a Counter (2) 2) Counter attributes in General Tab

Counter Total for IED counters : Yes => IED is sending real counter value No => IED is sending non-scaled value

Counter cumulative period : - configure a period at the end of which the counter value is transmitted (SBUS, LHMI) - possible values : 10mn, 15mn, 30mn, 1h, 2h, 3h, … 24h -at the end of this period, counter value can be reset (C264 re-start counting from 0)

Schneider Electric - CS&P – Datapoints Configuration – E01

25

• Add / Configure a Counter (3) 3) Counter can be acquired by DIU/CCU board, IED. Some Counters are computed by C264 application (C264 automation, …) => Relations under a Counter Wired on : Single counter => 1 DI Channel Double counter => 2 DI Channels

Has for IED address : Counter acquired by IED

integrate : Counter computed by MV integration (example : P) Counter type is not “Standard” but “Energy import” or “Energy export”

!

Schneider Electric - CS&P – Datapoints Configuration – E01

Integration of P or Q : In case the scale and unit is to big ((MVarh MVarh for ex.), if energy is changing of less than 1MVarh in 10 minutes, the value is not sent (counter is integer so 0.2 value is equal to 0). 26

• Content  SPS, DPS, MPS  MV, TPI, Counters  SPC, DPC, SetPoints  Datapoints Quality

Schneider Electric - CS&P – Datapoints Configuration – E01

27

• Typed / Generic xPC  TYPED CONTROL It is an information which is representing a special functionality regarding the MiCOM C264 inner automations. Examples : - Switch Ctrl DPC, Locking device status SPC, Bay Local/Remote DPC, Sync CB Close

 GENERIC CONTROL It is a standard control which can be configured at any level. Examples : - Module xPC, Bay xPC, VoltageLevel xPC, Substation xPC (x=S,D)

Schneider Electric - CS&P – Datapoints Configuration – E01

28

• Add / Configure a SPC (1) 1) SPC can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some SPC are System Info. 2) SPC attributes General Tab Short Name : SCE Key + appears in C264 local SOE

Long Name : appears in viewers + printers

Activation Mode : - transient => configure pulse duration - permanent - permanent until feedback

LHMI display : yes = SPC in control list (MSC)

Schneider Electric - CS&P – Datapoints Configuration – E01

Inter Control timeout : no possibility to execute 2 consecutive orders during this timer

29

• Add / Configure a SPC (2) 3) SPC execution may be dependant on Local/Remote status of Substation/Bay, on SBMC and/or on control uniqueness => SPC attributes Dependencies tab Bay Local/Remote : Bay Local => control from LHMI allowed, from OI & SCADA not allowed

SBMC : advised not to use SBMC (put No) if needed, local transfer when SS is in Remote

Control Uniqueness Substation Local/Remote : SS Local => control from OI allowed, from SCADA forbidden Note : This is internal automation existing and configurable for all xPC.

Schneider Electric - CS&P – Datapoints Configuration – E01

30

• Add / Configure a SPC (3) 4) SPC can be executed on DOU/CCU board, IED. Some SPC are computed by C264 application (C264 automation, …) => Relations under a SPC Interlock SPS : holds a logic allowing/blocking the control

Associated DO channel status SPS : for hardwired SPC only

Auto/Manu dependency : blocks the operator control if an automation is in progress => connect to SPS/DPS giving automation status

Feedback definition : Wired on : DO Channel

for C264 acknowledgement cf. slide “§3.4”

SPC executed on DOU/CCU board

Has for IED address : SPC executed by IED Schneider Electric - CS&P – Datapoints Configuration – E01

31

• Add / Configure a DPC (1) 1) DPC can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. Some DPC are System Info. 2) DPC attributes Short Name : SCE Key + appears in C264 local SOE

Long Name : appears in viewers + printers

Activation Mode : - transient => configure pulse duration (2 channels “open” / “close”) - permanent - permanent until feedback

LHMI display : yes = DPC in control list (MSC)

Schneider Electric - CS&P – Datapoints Configuration – E01

Inter Control timeout : no possibility to execute 2 consecutive orders during this timer

32

• Add / Configure a DPC (2) 3) DPC execution is dependant on one hand from Local/Remote status of Substation/Bay and on the other hand from control uniqueness => DPC attributes Dependencies tab Bay Local/Remote : Bay Local => control from LHMI allowed, from OI & SCADA not allowed

SBMC : advised not to use SBMC (put No) if needed, local transfer when SS is in Remote

Control Uniqueness Substation Local/Remote : SS Local => control from OI allowed, from SCADA forbidden Note : This is internal automation existing and configurable for all xPC.

Schneider Electric - CS&P – Datapoints Configuration – E01

33

• Add / Configure a DPC (2) 4) DPC can be executed on DOU/CCU board, IED. Some DPC are computed by C264 application (C264 automation, …) => Relations under a DPC 2 Interlock SPS (open/close): holds a logic allowing/blocking the controls

2 Associated DO channel status SPS : for hardwired DPC only

Auto/Manu dependency : blocks the operator control if an automation is in progress => connect to SPS/DPS giving automation status

Feedback definition : Wired on : DO Channel

for C264 acknowledgement cf. slide “§3.4”

DPC executed on DOU/CCU board

Has for IED address : DPC executed by IED Schneider Electric - CS&P – Datapoints Configuration – E01

34

• Configure a xPC feedback 1) SPC/DPC can have for feedback a SPS/DPS => C264 checks if control success (ex: CB control, feedback CB position) => Example given for DPC with DPS feedback DPC Relation “has for feedback” with 2 attributes : DPS

Schneider Electric - CS&P – Datapoints Configuration – E01

- execution timeout : maximum time allowed to get feedback - status check : C264 will check status before performing control

35

• Add / Configure a SetPoint (1) 1) SetPoints can be added at Substation, Voltage Level, Bay, Module, ISaGRAF automation level in Electric hierarchy. 2) SetPoint attributes Short Name : SCE Key + appears in C264 local SOE

Long Name : appears in viewers + printers

SetPoint type :

For Digital SetPoint : LHMI display :

increment value pulse duration

yes = SetPoint in control list (MSC)

Minimum / Maximum value : raw values for SetPoint validity Schneider Electric - CS&P – Datapoints Configuration – E01

36

• Add / Configure a SetPoint (2) 3) SetPoint execution is dependant on one hand from Local/Remote status of Substation/Bay and on the other hand from control uniqueness => SetPoint attributes Dependencies tab Bay Local/Remote : Bay Local => control from LHMI allowed, from OI & SCADA not allowed

SBMC : advised not to use SBMC (put No) if needed, local transfer when SS is in Remote

Control Uniqueness Substation Local/Remote : SS Local => control from OI allowed, from SCADA forbidden Note : This is internal automation existing and configurable for all Setpoints.

Schneider Electric - CS&P – Datapoints Configuration – E01

37

• Add / Configure a SetPoint (3) 4) SetPoints can be executed on DOU/CCU board, IED. Some SetPoints are computed by C264 application (C264 automation, …) => Relations under a SetPoints DO Channels : C264 will close DO channels using configured code (BCD, binary, …)

Auto/Manu dependency : blocks the operator control if an automation is in progress => connect to SPS/DPS giving automation status

Has for IED address : SP executed by IED

AO Channels : C264 will set AO channel

Schneider Electric - CS&P – Datapoints Configuration – E01

38

• Content  SPS, DPS, MPS  MV, TPI, Counters  SPC, DPC, SetPoints  Datapoints Quality

Schneider Electric - CS&P – Datapoints Configuration – E01

39

• SPS Status SPS STATUS

MEANING

RESET

Electric status 0

SET

Electric status 1

SELF CHECK FAULTY

Faulty DI Channel on board

TOGGLING

Toggling filtering has detected behaviour

UNKNOWN

IED acquiring DP is disconnected from C264

FORCED SET *

SPS is Forced Set by C264 (FSS enable)

SUBSTITUTED SET *

SPS is Substituted Set by Oper. (FSS enable)

SUPPRESSED

SPS is Suppressed by Oper. (FSS enable)

* => Same for RESET Quality => gives the nature of invalidity

Schneider Electric - CS&P – Datapoints Configuration – E01

40

• DPS Status DPS STATUS

MEANING

OPEN

Electric status 01

CLOSED

Electric status 10

JAMMED

Electric status 00

UNDEFINED

Electric status 11

SELF CHECK FAULTY

Faulty DI Channel on board

TOGGLING

Toggling filtering has detected behaviour

UNKNOWN

IED acquiring DP is disconnected from C264

FORCED OPEN *

DPS is Forced Open by C264 (FSS enable)

SUBSTITUTED OPEN *

DPS is Substituted Open by Op. (FSS enable)

SUPPRESSED

DPS is Suppressed by Oper. (FSS enable)

* => Same for CLOSED Quality => gives the nature of invalidity Schneider Electric - CS&P – Datapoints Configuration – E01

41

• MPS Status MPS STATUS

MEANING

STATE 1 -> STATE 16

Only one channel activated

UNDEFINED

No channel or more than one activated

SELF CHECK FAULTY

Faulty DI Channel on board

TOGGLING

Toggling filtering has detected behaviour

UNKNOWN

IED acquiring DP is disconnected from C264

FORCED STATE N *

MPS is Forced St. N by C264 (FSS enable)

SUBSTITUTED STATE N *

MPS is Substituted St. N by Op. (FSS enable)

SUPPRESSED

MPS is Suppressed by Oper. (FSS enable)

Quality => gives the nature of invalidity Schneider Electric - CS&P – Datapoints Configuration – E01

42

• MV Status MV STATUS

MEANING

VALID

MV in between min/MAX and/or L/H threshold

UNDEFINED

No DI channel or more than one activated DM

SELF CHECK FAULTY

Faulty DI/AI Channel on board

TOGGLING

Toggling filtering has detected behaviour

UNKNOWN

IED acquiring DP is disconnected from C264

FORCED

MV is Forced C264 (FSS enable)

SUBSTITUTED STATE N *

MV is Substituted by Op. (FSS enable)

SUPPRESSED

MV is Suppressed by Oper. (FSS enable)

OVERRANGE

Acquisition out of range

OPEN CIRCUIT

No current on AI channel (mA)

OVERSHOOT [1,2,3]

Over H, HH, HHH Threshold

UNDERSHOOT [1,2,3]

Under L, LL, LLL Threshold

Quality => gives the nature of invalidity Schneider Electric - CS&P – Datapoints Configuration – E01

43

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF