L1 V5 02 PACiS System Presentation G 01
Short Description
PACiS System...
Description
PACiS System General Presentation PACiS Technical Training Level 1 CS&P – Support Team
PCL
• Content What is a DCS? PACiS Devices and Tools PACiS Architectures PACiS Station Bus Cyber Security PACiS System Key Concepts
Schneider Electric - CS&P - PACiS System Presentation – G01
2
• Content What is a DCS? PACiS Devices and Tools PACiS Architectures PACiS Station Bus Cyber Security PACiS System Key Concepts PACiS 5 new features summary
Schneider Electric - CS&P - PACiS System Presentation – G01
3
• System Definition System is : a set of devices with specific functions that interact one to/with other with common rules HMI
BCU
To SCADA GTW
Fast Ethernet IEC61850
I/Os
IED
BCU
System is
BCU
Intelligent Electronic Device (IED)
CONFIGURATION & COMMUNICATION
SBUS TBUS
Station BUS (system federal network ...) (Ethernet / IP) Tele control BUS (Remote Control Point or SCADA)
LBUS
Legacy BUS (Field BUS to IED)
Schneider Electric - CS&P - PACiS System Presentation – G01
4
• Main System Functions Supervision
Control
from Bay Substation SCADA
Maintenance
HMI Flow Printing Archives Alarms State/Event
Station/Bay Sequence Of Event, Log in with reports Manage/audible/viewer/printing viewer/printing
Control Mode (local/remote : Bay, Substation) Operating Mode (run, stand-by, maintenance…) Uniqueness, InterLocK, automation running Force - Suppress - Substitute of DP Basic control sequence (DE, SBO) Built-in Control (ATCC, Synchrocheck, AutoRecloser) PSL, PLC Time management Databases management (download, switch, version) Test mode, SBMC Disturbance upload/viewing
Schneider Electric - CS&P - PACiS System Presentation – G01
5
• Content What is a DCS? PACiS Devices and Tools PACiS Architectures PACiS Station Bus Cyber Security PACiS System Key Concepts PACiS 5 new features summary
Schneider Electric - CS&P - PACiS System Presentation – G01
6
• PACiS Devices Range Visible to customer PACiS Operator Interface / SUI (Local / web access) PACiS System Management Tool (C264 / C264C) MiCOM C264 Computer MiCOM Ethernet Switches (H3xx / H6xx / H1xx / SWx) PACiS GTW (Gateway)
Hidden to customer PACiS Agency (Station BUS) (PACiS V4 = IEC61850) PACiS System Configuration Editor
Schneider Electric - CS&P - PACiS System Presentation – G01
7
• PACiS Devices HMI : SUI – Substation User Interface
C264- MiCOM C264 BCU
MiCOM Ethernet Switches
GTW - PACiS Gateway Schneider Electric - CS&P - PACiS System Presentation – G01
8
• PACiS Tools SMT - PACiS System Management Tool SCE - PACiS System Configuration Editor CAT - PACiS Computer Administration Tool (for C264) CGAT - PACiS Computer & GTW Administration Tool (C264 + Gateway) Schneider Electric - CS&P - PACiS System Presentation – G01
9
• Content What is a DCS? PACiS Devices and Tools PACiS Architectures PACiS Station Bus Cyber Security PACiS System Key Concepts PACiS 5 new features summary
Schneider Electric - CS&P - PACiS System Presentation – G01
10
• Principle System Architecture Up to 8 PACiS OI/SUI Clients
PACiS OI or SUI Server + Client
1 Remote PACiS Gateway
TBUS
Redundant Server SBUS IEC61850 MiCOM C264
11:32:28 17/02/06
GPS Clock
LBUS I/O Redundancy
SBUS IED
Set of MiCOM C264 Schneider Electric - CS&P - PACiS System Presentation – G01
11
• Distributed Architecture Example Applications : HV Substations Distribution Stations Industry Railway Oil & Gas
PACiS OI Twin Server or Hot Redundancy (V4.6.x) SOE printing Data reports
MiCOM C264 Redundancy Internal Synchrocheck Auto Recloser IED Management Advanced automation
PACiS Gateway Serial SCADA communication Ethernet SCADA communication
Schneider Electric - CS&P - PACiS System Presentation – G01
12
• MiCOM Computer Stand-Alone Example Up to 4 Serial Links (RS 485/232) for SCADA & IED interface C264C 2 x DIU200 1
2 3
4
IEC-60870-5-101
3xModbus RS485
11HKL
12HKL
Regional center
RS232
ION7330
ION7330
WAGO Vesuvius
13HKL
14HKL
ION7330
21HKL
ION7330
22HKL
WAGO
23HKL
ION7330
ION7330
Etna WAGO Ketelhuis
Schneider Electric - CS&P - PACiS System Presentation – G01
13
• PACIS GTW – Multiple use cases PACiS HMI
DCS interface
PACiS HMI
SCADA GATEWAYS
PACiS HMI
Ring A IEC61850
GATEWAY IEC/IEC
FLS GTW
FLS ring IEC61850
Ring B IEC61850 GATEWAY Data Concentr.
FLS HMI
C264 C264s - Feeders
LV
Schneider Electric - CS&P - PACiS System Presentation – G01
14
• Content What is a DCS? PACiS Devices and Tools PACiS Architectures PACiS Station Bus Cyber Security PACiS System Key Concepts PACiS 5 new features summary
Schneider Electric - CS&P - PACiS System Presentation – G01
15
• Station BUS : Definition SBUS Station BUS (integrate all system devices) Except PACiS SCE for configuration
Use a Communication Agency Common Application Program. Interface to all system device
Schneider Electric - CS&P - PACiS System Presentation – G01
16
• Station BUS : Overview Network: Ethernet Standard 10/100 Mbps, Copper Tx, Optic Fx EMC Electric Plant Public : RuggedCom, Belden-Hirshmann AREVA Specific : Immunity, Power Supply Star/Tree => MiCOM H34x, SWU20x Redundancy => MiCOM H35x, SWR20x, SWR21x Dual Homing => MiCOM H36x, SWD20x, SWD21x Dual Ring + Dual Star => MiCOM H356 & H362, SWD21x RSTP - Compatible => MiCOM H17x, SWS21x PRP - Compatible => MiCOM H18, REU board for C264 Protocol: IEC61850 Client/Server Standard/Open N Clients & M Servers Optimized traffic Fast Communication
Schneider Electric - CS&P - PACiS System Presentation – G01
17
• Station BUS : Client/Server Mechanism (1) Protocol: IEC61850 SERVERS
Client/Server These are all my data
HMI OI or SUI Server
MiCOM C264
SBUS IED
CLIENTS
I subscribe to these data
I report the change of state of these data you subscribed
PACiS Gateway MiCOM C264 (TBUS)
OPTIMIZED TRAFFIC Schneider Electric - CS&P - PACiS System Presentation – G01
18
• Station BUS : Client/Server Mechanism (2) Protocol: IEC61850
Client/Server
SERVER Send Reports (RP) Receive Controls Send Control Acknowledgements
CLIENT Receive Reports (RP) Send Controls Receive Control Acknowledgements
Send GOOSE (fast message for shared automation)
Schneider Electric - CS&P - PACiS System Presentation – G01
19
• Station BUS : Network devices (1) Ethernet Switch: Actual Range Reference
Description
SWU 200 SWU 202/ 204 SWR 212/ 214 SWD 212/ 214 SWS 212/ 214 MICOM H 140 MICOM H 152/ 154/ 156/ 158 MICOM H 162/ 164/ 166/ 168 MICOM H 172/ 174/ 176/ 178 MICOM H 340 MICOM H341/ 343 MICOM H 342/ 344 MICOM H 352/ 354 MICOM H 356/ 358
Switch “ simple” copper Switch “ simple” (multi/ mono) Switch “ Redundant” (multi/ mono) Switch “ Dual Homing” (multi/ mono) Switch “ RSTP compatible” (multi/ mono) Switch “ simple” Copper Switch “ Redundant” (multi/ mono/ LC) Switch “ Dual Homing” (multi/ mono/ LC) Switch “ RSTP compatible” (multi/ mono/ LC) Switch “ simple” Copper Switch “ simple” (multi/ mono) Switch “ simple” (multi/ mono) Switch “ Redundant” (multi/ mono ST) Switch “ dual Ring / dual Star” (multi/ mono LC ) Switch “ Dual Homing” (multi/ mono ST) Optical Star with 1 to 4 of following board V2 double switch (multi/ mono) V3 (multi/ mono)
MICOM H 362/ 364 MICOM H 60x MICOM H 621/ 623 MICOM H 631/ 633
Ethernet Tx Fx 4 0 4 2 4 2 4 2 4 2 6 0 4 2 4 2 4 2 6 0 6 1 6 2 6 2 2 2+ 4 6 2
2*4 2
Device Cx6x board Cx6x board Cx6x board Cx6x board Cx6x board PCI board PCI board PCI board PCI board DIN Rack DIN Rack DIN Rack DIN Rack DIN Rack DIN Rack 19’ Rack
2*1 6
New in 2013 : compatible PRP C264 board = REU (ex SWP) PCi board = MICOM H18 Schneider Electric - CS&P - PACiS System Presentation – G01
20
• Station BUS : Network devices (2)
Example : MiCOM H352
Schneider Electric - CS&P - PACiS System Presentation – G01
21
• Station BUS : Topology Star / Tree SWU20x / H34x
Redundant Ring SWR20x or SWR21x / H35x
Dual Homing SWD20x or SWD21x / H36x + H63x
Schneider Electric - CS&P - PACiS System Presentation – G01
Dual Ring + Dual Star SWD202 / H362 + H356
22
• Station BUS : PRP Integration PRP on C264 PRP on PCi board SAN SAN
SAN DAN VDAN RedBox
: Single Attached Node : Dual Attached Node : Virtual Dual Attached Node : Redundancy Box
C264 with REU Schneider Electric - CS&P - PACiS System Presentation – G01
PC SUI with H18
C264 with REU 23
• Content What is a DCS? PACiS Devices and Tools PACiS Architectures PACiS Station Bus Cyber Security PACiS System Key Concepts PACiS 5 new features summary
Schneider Electric - CS&P - PACiS System Presentation – G01
24
• Cyber Security 4 levels of password Hardening (disabling unused logical/physical ports) Account management (log off, nb of tentatives) Security logs Antivirus (AVIRA Antivir v10) White-Listing (Savant Protection) Banner/Disclaimer
Schneider Electric - CS&P - PACiS System Presentation – G01
25
• Content What is a DCS? PACiS Devices and Tools PACiS Architectures PACiS Station Bus Cyber Security PACiS System Key Concepts PACiS 5 new features summary
Schneider Electric - CS&P - PACiS System Presentation – G01
26
• Key Concepts System is
Communication Configuration
PACiS Devices & Softwares SUI, SMT, CAT MiCOM C264, MiCOM Switches, PACiS Gateway SBUS Agency, PACiS SCE PACiS Architectures Distributed Computer Stand alone RTU Ethernet Architectures Star - Tree Ring Dual Homing Dual Ring + Dual Star Networks
SBUS TBUS LBUS
Station BUS TeleControl BUS Legacy BUS
Schneider Electric - CS&P - PACiS System Presentation – G01
Copper Optical
Client/Server protocol (61850) T101, T104, DNP3, ModBus,… ModBus, T103, T101, DNP3 27
• Content What is a DCS? PACiS Devices and Tools PACiS Architectures PACiS Station Bus Cyber Security PACiS System Key Concepts PACiS 5 new features summary
Schneider Electric - CS&P - PACiS System Presentation – G01
28
• PACiS 5 New features (1) SUI = New SCADA / HMI, for demanding Utilities, Large industrial sites • • • • • •
Cyber security : NERC compliance , Anti-Virus Zooming, cluttering / decluttering New Graphical objects : XY curves, Advanced reports Multi Clustering architecture: to split the CPU load Alarms : External klaxon management Archiver : available on a separate PC
• Windows 7, Windows server 2008 • Localization with multiple languages • Compatible with extended FLS (Fast Load Shedding)
Schneider Electric - CS&P - PACiS System Presentation – G01
29
PACiS 5 New features (2) NEW GATEWAY = with extended capabilities • GTW IEC/IEC : Coupling IEC61850 networks -> Flexible architectures • GTW IEC/IEC : Goose transfer, with filtering • GTW Data concentrator (HV, MV and LV devices): • IEDs Protocols (ModBus TCP and serial), IEC101, DNP3/IP • up to 16 serial links (up to 200 IEDs) • GTW to Remote Control Center : up to 6 Scada links • Hot redundancy -> availability • IEDs in daisy chain connection with network Split -> availability • Simulator of Legacy IEDs : HELPS IED
RCP networks
IED
IED
IEC61850 Station bus
GTW Field bus networks
IED
IED
IED
IED
IED
IED
IED
IED
IED
IED
IED
IED
IED
IED
IED
IED
IED
IED
• New rugged Hw Plate-form : MiCOM G9xx IEC61850-3 (environment and EMC) certified 19” rackable, no rotating parts • O.S. update : Windows 7 and Real Time OS= RTX on MiCOM G WES2009 on A300 • Cyber-security : White Listing
Schneider Electric - CS&P - PACiS System Presentation – G01
30
PACiS 5 New features (3) Companion facilities Redundant ETHERNET Architectures • IEC62439 – PRP Redundant Protocol : embedded in PCs (H18x), in MiCOMC264, MiCOM Px40 • Third party Ethernet switches with IEC62439- PRP • RSTP compatibility (Rapid Spanning Tree Protocol) – industry
INTEGRATED IEDs • Meters : ION7650 over IEC61850 • SEPAM 40,60,80 series
PSE Power Scada Expert – companion HMI for PACIS basic solutions Fast Load Shedding for large Installations • Extended FLS for up to 3000 loads, 60ms • Load Restore
C264 New hardware • New BIU261 Dual Source Power Supply • New 60TE racks with 9 Slots (to extend current range 40T & 80T )
TVDA RTU based : HV-MV, MV/MV simple solution based on C264 RTU Schneider Electric - CS&P - PACiS System Presentation – G01
31