L1 V4 03 MiCOM C264 Hardware Presentation E 01
Short Description
Download L1 V4 03 MiCOM C264 Hardware Presentation E 01...
Description
MiCOM C264 Hardware Presentation PACiS Technical Training CS&P – Support Team
PCL
• Content
Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards
Schneider Electric - CS&P – C264 Hardware Presentation – E01
2
• Content
Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards
Schneider Electric - CS&P – C264 Hardware Presentation – E01
3
• Modular Racks
MiCOM C264C 4U / 170mm / 40 TE with 4 or 6 slots for I/O boards
Schneider Electric - CS&P – C264 Hardware Presentation – E01
MiCOM C264 4U / 170mm / 80 TE with 14 or 15 slots for I/O boards
4
• Connections Modular Construction (Back) Shed Contacts should be grounded
Easy to Install
Optional connectors Removable connectors for for 4 mm2 wires 0.8 to 2.5 mm2 wires I/Os direct CT/VT boards & connection Power supply Schneider Electric - CS&P – C264 Hardware Presentation – E01
Connector Screwing
Optional : optic/ Ethernet IED Com, IRIG B 5
• Boards List Short designation GHU 2xx BIU 2x1 CPU 2x0 TMU 2xx DSP 2xx DSPIO 2xx
DIU 2xx DOU 2xx CCU 2xx AIU 2xx AOU 2xx SWx 2xx SWU 2xx SWR 2xx SWD 2xx
CAS 2xx FBP 2xx
Designation
Details
Graphic Humain Unit Front panel / LCD Power supply and 2 RS Basic Interface Unit Computer Processing Unit Transducerless Measurement 4 CT Unit / 4-5 VT Digital Signal Processor TMU Signal Digital Signal Processor Input Output TMU Signal + 5 DI / 5 DO (1 slot) Digital Input Unit 16 DI
Digital Output Unit CB Control Unit Analog Inputs Unit Analog Output Unit SWitch Ethernet
10 DO 8 DI + 4 DO (4) 8 AI 4 AO
SWitch Unit (standard switch) SWitch Ring Redundancy SWitch Dual Hamming redundancy
max 6 ports 2 Fx + 4 Tx 2 Fx Redundant + 4 Tx 2 Fx Redundant + 4 Tx
Package CASe (rack 4U) Front Back Plane ( Bus )
Package CASe (rack 4U) Front Back Plane ( Bus )
Schneider Electric - CS&P – C264 Hardware Presentation – E01
6
• Capabilities
MiCOM C264C 4/6 slots
MiCOM C264 14/15 slots
BIU 241 (power + 2RS)
1
1
CPU260 (2RS + RJ45) / CPU270 options : Optic Fx, IRIG-B, DSP
1
1
GHU 2xx : 20x=LCD, 21x=no LCD, 22x=remote
1
1
DIU211 (16DI)
6 (96 DI)
15 (240 DI)
DIU220 (16DI)
6 (96 DI)
15 (240 DI)
DOU201 (10DO)
6 (60 DO)
15 (150 DO)
CCU211 (8 DI + 4 DO)
6 (48 DI + 24 DO)
15 (120 DI + 60 DO)
AIU201 (4 AI, mA or V)
6 (24 AI)
6 (24 AI)
AIU211 (8 AI, mA)
6 (48 AI)
6 (48 AI)
TMU220
1 (4 CT, 5 VT)
1 (4 CT, 5 VT)
TMU210
C264-P : 1 (4CT, 4VT)
C264-P: 1 (4CT, 4VT)
6 (24AO + 24DO)
6 (24AO + 24DO)
AOU200 (4AO + 4DO)
With CPU270, boards 2x1 address is defined in SCE (jumpers optional) : DIU211, CCU211 Schneider Electric - CS&P – C264 Hardware Presentation – E01
7
• Example of 80TE Rack Content Front Automatic Production Placement
H
I
J
K
L
M
N
O
P
Q
CPU260
DSP IO
SWX
AIU201_@0
AIU210_@0
AIU210_@1
DOU200_@0
DOU200_@1
DOU200_@2
CCU200_@2
CCU200_@1
CCU200_@0
DIU200_@2
DIU200_@1
DIU200_@0
TMU210
1
2
3
4
5
6
7
8
9
10
11
12
13
7
8
9
10
11
12
13
14
15 B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
I
BIU 241
BIU 241
H
CPU260
6 BIU 241
BIU 241
5
G
CT / VT
G
CT / VT
F
BIU 241 Protection DSP IO Slot
Schneider Electric - CS&P – C264 Hardware Presentation – E01
TMU200 DIU200_@0
E
DIU200_@0
DIU200_@1
D
DIU200_@1
DIU200_@2
C
DIU200_@2
CCU200_@0
B
With TMU210
CCU200_@0
CCU200_@1
14
CCU200_@1
CCU200_@2
13
CCU200_@2
DOU200_@2
12
DOU200_@2 DOU200_@1
11
DOU200_@1 DOU200_@0
10
DOU200_@0 AIU210_@1
9
AIU210_@1 AIU210_@0
8
AIU210_@0
AIU201_@0
7
AIU201_@0
SWX
6
SWX
5
4 CPU260
4
BIU 241
3
3
F
8
2
A
1
2 A
1
With TMU200
Q P O N M E
L D
K C
J B A
Basic
• Example of 40TE Rack Content Front Automatic Production Placement A
G
H
1
2
3
4
B
C
D
E
F
1
2
3
G
H
CT / VT
F
CT / VT
DIU200_@0
E
TMU210
D
TMU200
C
DIU200_@0
B
DIU200_@0
6
DOU200_@0
5
DIU200_@1
4
SWX
3
DOU200_@0
2
DSP IO
1 SWX
DIU200_@1
H
CCU200_@0
G
DOU200_@0
F
AIU210_@0
E
SWX
D
CPU260
BIU 241
Schneider Electric - CS&P – C264 Hardware Presentation – E01
C
CPU260
BIU 241
A
BIU 241
Protection DSP IO Slot
A
BIU 241
With TMU210
BIU 241
BIU 241
With TMU200
B
CPU260
Basic
9
• Content
Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards
Schneider Electric - CS&P – C264 Hardware Presentation – E01
10
• Rack Mounting Cubicle Mounting (6 screws) on 19’’ Rack LCD Removal (6 Poz drive 10)
C264 Screwing
19’’ Rack Support
Cabinet Mounting
Front Face Screwing Schneider Electric - CS&P – C264 Hardware Presentation – E01
11
• Rack / Board Overview Board + rail removing (torque drive 10) Bus
Board Name
Board Number
BIU
CPU DIU Schneider Electric - CS&P – C264 Hardware Presentation – E01
DOU
CCU
AIU 12
• Board Number (Address) Each board has an address, unique per type, starting from 0 by jumpers
CLOSED = 0 Rules :
OPEN (see below) If Open : address = address + 1 If Open : address = address + 2 If Open : address = address + 4 If Open : address = address + 8
Example : => + 2 => 2 + 8 = 10 => + 8 Schneider Electric - CS&P – C264 Hardware Presentation – E01
13
• Content
Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards
Schneider Electric - CS&P – C264 Hardware Presentation – E01
14
• Front Faces GHU200 GHU210 GHU220 GHU201 GHU211 GHU221
40 TE 40 TE 40 TE 80 TE 80TE 80 TE
Front Panel Front Panel Front Panel Front Panel Front Panel Front Panel
Leds + L/R switch + Graphic Display LCD Leds + L/R switch : Simple Blind : Leds + L/R switch + Graphic Display LCD : Leds + L/R switch : Simple Blind
2071004 2071010 2071174 2070962 2070966 2071172
RJ11
Schneider Electric - CS&P – C264 Hardware Presentation – E01
15
• Basic Interface Unit – BIU241 Main characteristics : • Power Supply (4 possible ranges : 24 / 48 / 110 / 220V) • 1 Watchdog contact • 2 DI & 2 DO used for redundancy • RS1 (232/485) • RS2 (232/422/485)
Schneider Electric - CS&P – C264 Hardware Presentation – E01
16
• Central Processing Unit – CPU260 Main characteristics : • 32-bit Power PC-base processor (80 MHz) • DRAM (64Mo) & Flash (16Mo) • VxWorks for RT OS • Powerful DSP TMS320C6713 for CT/VT • Ethernet-Based 10/100Base-FX or Base-TX • 2 Serial links up to 64 Kbit/s RS232 • IRIG-B port • Bus
Central Processing Unit board
CPU260
12 3 4 5 6 7 8
10/100 Base-Tx Ethernet-based link RJ-45 (female)
OPTIONNAL LINKS:
10/100 Base-Fx Ethernet-based link
1
1
DCD
2
RXD / T-
3
TXD / T+
5
GND
7
RTS
RS232
Serial
6 2 7 3 8
link 3
4 9 5
8 1
1
6 2 7
2
8
3
3
CTS # DCD
RS232
RXD / TTXD / T+
Serial
4 9 5
5
7 8
link 4
GND
RTS CTS #
IRIG B Schneider Electric - CS&P – C264 Hardware Presentation – E01
17
• Central Processing Unit – CPU270 Main characteristics : • 32-bit Power PC-base processor (260 MHz) • More DRAM (128Mb) and Flash (64Mb) • VxWorks for RT OS • Powerful DSP TMS320C6713 for CT/VT • 2 Ethernet ports 10/100Base-TX • 2 Serial links up to 64 Kbit/s RS232 • IRIG-B port • New bus
Central Processing Unit board
CPU270
12 3 4 5 6 7 8
10/100 Base-Tx Ethernet-based link RJ-45 (female) 12 3 4 5 6 7 8
10/100 Base-Tx Ethernet-based link RJ-45 (female)
1 2
1
3
DCD
RS232
RXD / TTXD / T+
Serial
6 2 7 3
!
Good Practice : In “Boot Parameters” from CMT, make sure IP address 1 and IP address 2 are belonging to different domains.
8
5
GND
7
RTS
link 3
4 9 5
8 1
1
6 2 7
2
8
3
3
CTS # DCD
RS232
RXD / TTXD / T+
Serial
4 9 5
5
7 8
link 4
GND
RTS CTS #
IRIG B Schneider Electric - CS&P – C264 Hardware Presentation – E01
18
• Content
Generalities Rack Hardware Main Boards Description I/O Boards description Communication Boards
Schneider Electric - CS&P – C264 Hardware Presentation – E01
19
• Digital Input Unit – DIU200 Main characteristics A01 Vnom : 24-30 Vdc A02 Vnom : 40 Vdc (range 20 to 60 Vdc) A03 Vnom : 100 Vdc (range 40 to 150 Vdc) A04 Vnom : 220 Vdc (range 180 to 264 Vdc) 16 Opto Isolated DI but 40% Thresholds Board addressing
Digital Input Unit
DIU20x
board
Signal inputs
PIN 1 2
+ -
VIN -
DI1
+ -
DI3
+ -
DI5
+ -
DI7
+ -
DI9
+ -
DI11
+ -
DI13
+ -
DI15
+ -
V IN -
DI2
3 4 5
+ -
VIN -
V IN -
DI4
6 7 8
+ -
VIN -
V IN -
DI6
9 10
SPS, DPS SCT, DCT DM
11
+ -
VIN -
V IN -
DI8
12 13 14
+ -
VIN -
V IN -
DI10
15 16 17
+ -
VIN -
V IN -
DI12
18 19 20
+ -
VIN -
V IN -
DI14
21 22 23
+ -
VIN -
V IN -
24
Schneider Electric - CS&P – C264 Hardware Presentation – E01
20
DI16
• Digital Input Unit – DIU210 Main characteristics Capabilities : A01 Vnom : 24-30 Vdc A02 Vnom : 40 Vdc (range 20 to 60 Vdc) A03 Vnom : 100 Vdc (range 40 to 150 Vdc) A04 Vnom : 220 Vdc (range 180 to 264 Vdc) 1 ms Time-tag 16 Opto Insulated DI 2kV (1mn) Peak > 25mA when Set
40TE 2 6 3 1
80TE 8 15 10 5
SPS, DPS SCT, DCT DM
Schneider Electric - CS&P – C264 Hardware Presentation – E01
21
• Digital Input Unit – DIU211 Main characteristics : Accept all Nominal Voltages according on jumpers definition
Board address 1 ms Time-tag Opto Isolated (2kV during 1mn) 27mA peak for 2ms Board Auto-addressed (CPU3)
16 DI usable for : SPS, DPS SCT, DCT DM
Schneider Electric - CS&P – C264 Hardware Presentation – E01
22
• Digital Input Unit – DIU220 Main characteristics : Accept 2 different Nominal Voltages : VA, nom : 48 Vdc (range 20 to 60 Vdc) VA, nom : 110 Vdc (range 40 to 125 Vdc) 1 ms Time-tag Opto Isolated (2kV)
Digital Input Unit
DIU20x
board
Signal inputs
PIN 1 2
+ -
VIN -
DI1
+ -
DI3
+ -
DI5
+ -
DI7
+ -
DI9
+ -
DI11
+ -
DI13
+ -
DI15
+ -
V IN -
DI2
3
16 DI usable for : SPS, DPS SCT, DCT DM
4 5
+ -
VIN -
V IN -
DI4
6 7 8
+ -
VIN -
V IN -
DI6
9 10 11
+ -
VIN -
V IN -
DI8
12 13 14
+ -
VIN -
V IN -
DI10
15 16 17
+ -
VIN -
V IN -
DI12
18 19 20
+ -
VIN -
V IN -
DI14
21 22 23
+ -
VIN -
V IN -
24
Schneider Electric - CS&P – C264 Hardware Presentation – E01
23
DI16
• Digital output Board – DOU200 Main characteristics 8 outputs NO contacts and 2 outputs NO/NC UN ≤ 250 Vdc / 230 Vac Isol. 2kV Making 70 VA/W 2.5 A permanent 100 A peak for 30ms
Digital Output Unit board
PIN
DOU200
Signal outputs
1 2
DO 1
3 4
DO 2
5 6
DO 3
7 8
DO 4
9 10
DO 5
11 12
DO 6
13 14
DO 7
15 16
DO 8
17 18 19 20 21
DO 9
22 23 24
Schneider Electric - CS&P – C264 Hardware Presentation – E01
DO 10
24
• Digital output Board – DOU201 Main characteristics : 10 DO (8 NO contacts & 2 NO/NC contacts) UN ≤ 250 Vdc / 230 Vac Isolation 2kV Making Power : 140 VA/W Permanent : 5A Peak for 30ms : 250 A
Digital Output Unit board
PIN
DOU200
Signal outputs
1 2
DO 1
3 4
DO 2
5 6
DO 3
7 8
DO 4
9 10
DO 5
11 12
DO 6
13 14
DO 7
15 16
DO 8
17 18 19 20 21
DO 9
22 23 24
Schneider Electric - CS&P – C264 Hardware Presentation – E01
DO 10
25
• CB Control Unit – CCU200 8DI and 4DO DI main characteristics like DIU2xx DO main characteristics : 4 power output relays (2 NO contacts each) Making Power 140 VA/W Permanent : 5A 500ms : 30A 30ms : 250A
Circuit breaker Control Unit board
CCU 200
PIN Signal inputs 1 2
+ -
VIN -
+ -
DI1
VIN -
DI2
3 4 5
+
VIN -
-
+
DI3
VIN -
-
DI4
6 7 8
+ -
VIN -
+ -
DI5
VIN -
DI6
9 10
+
11
-
VIN -
+
DI7
-
VIN -
DI8
12 13 14 15 16 17
Signal outputs B A A B
CO 1
CO 2
18 19 20 21 22 23
B A A B
CO 3
CO 4
24
Schneider Electric - CS&P – C264 Hardware Presentation – E01
26
• CB Control Unit – CCU211 CB Control Unit (8DI and 4DO) DI Voltage selected by jumpers DI Trigger threshold selected by jumpers 4 DO Double Cut Board Auto-addressed (CPU3)
Circuit breaker Control Unit board
CCU 211
PIN Signal inputs 1 2
+ -
VIN -
DI1
+ -
DI3
+ -
DI5
+ -
DI7
+ -
VIN -
DI2
3 4 5
+ -
VIN -
VIN -
DI4
6 7 8
+ -
VIN -
VIN -
DI6
9 10 11
+ -
VIN -
VIN -
DI8
12 13 14 15 16 17
Signal outputs B A A B
CO 1
CO 2
18 19 20 21 22 23
B A A B
CO 3
CO 4
24
Schneider Electric - CS&P – C264 Hardware Presentation – E01
27
• CCU211 – Double Cut CCU board wiring : Double pole relays (A&B contacts) wired in serial CCU pins no
Circuit Breaker side Open Coil CB1 Vcc+
Internal CCU relays description Simultaneous change of both contacts A and B
Close Coil CB1 VccOpen Coil CB2 Vcc+ Close Coil CB2 VccSchneider Electric - CS&P – C264 Hardware Presentation – E01
28
• Analogue Input Board – AIU201 Main characteristics : 4 opto-isolated AI (Current or Voltage) 20 ms time tagging (acquisition) 16 bits A/D converter with 0.1% accuracy SMRR : 98dB CMRR : 150dB
Schneider Electric - CS&P – C264 Hardware Presentation – E01
29
• Analogue Input Board – AIU211 Main characteristics : • 8 independent opto-isolated AI (Current only) • 20 ms time tagging (acquisition) • 16 bits A/D converter 0.1% accuracy • SMRR : 98dB • CMRR : 150dB • Input impedance : 75ohms ! This board is replacing the AIU210
Schneider Electric - CS&P – C264 Hardware Presentation – E01
30
• Analogue Output Board – AOU200 Main characteristics : 4 AO + 4DO as Read Inhibit signals 100 ms stabilisation time external voltage power source 48VDC 0.1% accuracy 4-20mA, ±10mA, ±20mA …
Schneider Electric - CS&P – C264 Hardware Presentation – E01
N° 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Description External power supply +48V NIL External power supply (0V) NIL WDOG+ WDOGNIL READ INHIBIT AO n° 1+ READ INHIBIT AO n° 1READ INHIBIT AO n° 2+ READ INHIBIT AO n° 2READ INHIBIT AO n° 3+ READ INHIBIT AO n° 3READ INHIBIT AO n° 4+ READ INHIBIT AO n° 4NIL AO n° 1+ AO n° 1AO n° 2+ AO n° 2AO n° 3+ AO n° 3AO n° 4+ AO n° 4-
31
• Transducerless Measure Unit – TMU220 4 CT 2 ranges each (1-5A)
Range 0.2 In to 4 In accuracy 0.2%
5 VT for TMU220 (4VT on old TMU200) Input Nom: 57 to 500V Range 4V to 500V(800V) acc. 0.2%
(possibility to use TMU220 instead of TMU200 on old substations without changing configuration)
Direct measurement
RMS values of line/phase voltage (Van, Vab, ...) RMS values of line current (Ia, Ib, Ic) RMS values of residual current and voltage (Ir and Vr) Frequency Active power (Pa, Pb, Pc and Ptotal) Reactive power (Qa, Qb, Qc and Qtotal)
Derived Measurements
Fundamental magnitudes and phase angles Apparent Power (Sa, Sb , Sc and Stotal) Import/Export active and reactive energy Power factor (displacement, distortion and true factor) Fundamental Sequence components (Id, Ii, I0, Vd, Vi, V0) Rolling, Peak, Dip demand values Phase and amplitude difference 15th Harmonic 64 samples/period
+ Daughter Board DSP on CPU board Schneider Electric - CS&P – C264 Hardware Presentation – E01
32
• Transducerless Measure Unit – TMU220 TMU220 wiring :
Schneider Electric - CS&P – C264 Hardware Presentation – E01
33
• Transducerless Measure Unit – TMU210 CT/VT acquisition module (32 samples/period) 3 ¨Phase + 1 neutral current transformer (3*I + Io) Ratings In: 1 or 5 Amperes by jumper Phase Current: 0.1 to 40 In Earth Current: 0.002 to 1 Ien 0.01 to 8 Ien Sensitivity 0.1 to 40 Ien Thermal heating 4 In permanent, 30 In during10secs, 100 In 1sec Bandwidth : 10th harmonic (no MV) Threshold acc : 2% Compatibility with external CT : 5VA, 5P10 4 Phase voltage transformer (4 VT) Nominal voltage 57 to 130 VRMS Thermal heating : 2 Vn (Phase-N )permanent 2.6 Vn (Phase –N) -10seconds Connection options : defined by setting Threshold acc : 2% Schneider Electric - CS&P – C264 Hardware Presentation – E01
34
• DSPIO210 => DSPIO211 CPU Daughter board using one slot “C” Digital Signal Processor (DSP TMS320C6711) for protection functions (like P127 + P923) 5 Digital Input - isolated A02_48Vdc , A03_110-125Vdc, A04_220Vdc Consumption 5mA in 48V Settable filtering 4 Digital Output - isolated contacts (NO type) 250Vdc 50W resistive or 25W inductive (L/R=40ms) Carry : 5A 30A during 30s Operation time 4 TX
SWR204 - monomode
2FX -> 4 TX
Good Practice : switch number = end of BCU IP
Schneider Electric - CS&P – C264 Hardware Presentation – E01
40
• Switch Board – SWD2xx !
SWD21x is new version able to communicate with Switch Manager software SWD202 - multimode
2FX -> 4 TX
SWD204 - monomode
2FX -> 4 TX
Good Practice : switch number = end of BCU IP
Schneider Electric - CS&P – C264 Hardware Presentation – E01
41
• Communication Module – ECU20x ECU200 / ECU201 Extended Communication Unit for CPU • ECU200 : converts RS232 -> Fx • ST connector • Wavelength : 820nm • Jumper set : Light On • Jumper reset : Light Off
• ECU201 : converts RS232 -> RS4xx • Jumper set : RS422 (4 wires) • Jumper reset : RS485 (2 wires)
Schneider Electric - CS&P – C264 Hardware Presentation – E01
42
View more...