PACiS Terminology PACiS Technical Training CS&P – Support Team

PCL

• Content

 Electric Network Definition  Primary Devices  Protections  Datapoints

Schneider Electric - CS&P – System Terminology – E01

2

• Content

 Electric Network Definition  Primary Devices  Protections  Datapoints

Schneider Electric - CS&P – System Terminology – E01

3

• What is Electric Network  Electric Network is a Hierarchy of Voltage

Transmission Transport 600-400kV

Repartition 220kV

kV 400

225 kV

Bi-directional Mesh

Distribution

90 kV

Distribution 110-90 kV Directional Antenna

Delivery 2-6-20kV Antenna / Annealing

Schneider Electric - CS&P – System Terminology – E01

6-20 kV

4

• What is Electric Network  Carry Electricity from Producers to Consumers

Producer Industrial Consumer Schneider Electric - CS&P – System Terminology – E01

Domestic Consumer 5

• What is Substation  Substation is a node in the grid electric network  Substation is linked to one voltage level

Schneider Electric - CS&P – System Terminology – E01

1.

Dispatch power flow on branch/lines

2.

Allow maintenance (line/device)

3.

Select/eliminate fault in only one section

4.

Mesh network (stability) 6

• System Terminology

SITE SUBSTATION VOLTAGE LEVEL BAY

MODULE Schneider Electric - CS&P – System Terminology – E01

7

• Content

 Electric Network Definition  Primary Devices  Protections  Datapoints

Schneider Electric - CS&P – System Terminology – E01

8

• Primary Device: Bus Bar  Feeder => interface to Voltage level (line branch, transformer)  Bus Bar => Backbone to dispatch power between feeders

Schneider Electric - CS&P – System Terminology – E01

9

• Primary Device: Circuit Breaker  Make / Break Current then Power flow  Operate under Nominal or Faulty condition

Schneider Electric - CS&P – System Terminology – E01

- exploitation - shortcut current

10

• Primary Device: Bar / Line Isolator  Bar Isolator : Isolate CB / Bar (maintenance/exploitation)  Line Isolator : Isolate CB / Line (line maintenance)

Schneider Electric - CS&P – System Terminology – E01

11

• Primary Device: Earth switch Isolator  Ground a isolated part of the circuit for maintenance

Schneider Electric - CS&P – System Terminology – E01

12

• Primary Devices list  Feeder (line)  Bus bar  Circuit Breaker  Bar Isolator  Line Isolator  Earth Isolator

• Transformer • Generator

G

• Motor

M

• Capacitor Bank • Reactor Schneider Electric - CS&P – System Terminology – E01

13

• Switching Devices Kind Breaking

Isolation

ICC

4IN

IN

VN

VPeak

 Breaker

X

X

X

-

-

 Isolator

-

-

-

X

X

-

X

X

-

-

 Switch disconnector

-

X

X

X

X

 Contactor

-

-

X

X

-

 Breaker Isolator

X

X

X

X

X

 Switch

Roughly : ICC =10 IN Roughly : VPeak = 2 VN Schneider Electric - CS&P – System Terminology – E01

between phase, phase to earth up to 6 VN (thunder peak 50ms) 14

• Measurement Transformer CT/VT  Provide current / voltage measurement to Protection/Control System

Schneider Electric - CS&P – System Terminology – E01

15

• Why measurement CT/VT  CT/VT : Lower Primary Values (HV) to Secondary Values (LV) • Galvanic Isolation (no current between HV / LV) • Measurement Reduction

3 000 Amps

1 Amp

Schneider Electric - CS&P – System Terminology – E01

64 000 Volts

120 Volts

16

• Voltage Transformer Overview (1)  Description (1)

245 kV

100 V

Schneider Electric - CS&P – System Terminology – E01

17

• Voltage Transformer Overview (2)  Description (2)

P1 S1

P2

S2

Np.Us = Ns.Up

Schneider Electric - CS&P – System Terminology – E01

18

• Current Transformer Overview (1)  Description (1) 3000 A

3000 A

3000 spires

1A 245 kV

1A Schneider Electric - CS&P – System Terminology – E01

19

• Current Transformer Overview (2)  Description (2)

P1

S1

P2

S2

Np.Ip = Ns.Is

Schneider Electric - CS&P – System Terminology – E01

20

• Electric Definitions  Substation •Site Partition => Local/Remote substation •Substation Control Uniqueness •(nb=1) The Business DB (except Cascade)  Voltage Level •Association of Bus Bars for Auto Volt. Regul. •Often only one BB (nb 4-5-x)  Bay •ANSI => 1 CB with associate circuits & protections •Association of switchgears/transformers & functions •Local/Remote Bay, SBMC, Bay Control Uniqueness •Special (coupler, section, feeder, transformer) •Often Generic (more easy) •Bay belongs to only one C264  Module •Primary Electric Device, ANSI functions, Group of DP •Special (CB, disconnector, transformer, AR, Sync) •Often Generic (DPS/DPC association possible)  Datapoint •Real Time information (95% electric) •At any level Schneider Electric - CS&P – System Terminology – E01

21

• SCE Preview SITE SUBSTATION

SUBSTATION VOLTAGE LEVEL 1 BAY FEEDER 1

CB 1

VOLTAGE LEVEL N

VOLTAGE LEVEL 2

BAY TRANSFO

SW 1

BAY FEEDER 2

TR 1

SW 2

Position

Position

TPI

Control

Control

Control

Schneider Electric - CS&P – System Terminology – E01

22

• Content

 Electric Network Definition  Primary Devices  Protections  Datapoints

Schneider Electric - CS&P – System Terminology – E01

23

• Why protecting  Control

=> dispatch energy => keep service => maintenance operation  Protection => Fault (Shortcut)

• • • •

(continuity, quality)

Short circuit implies unbalancing, voltage drop… Isolate Faulty section Save device from destruction Secure installation fire / explosion (arc) people security (insulation)

 Protection => Exploitation (Overload)

• Unbalanced exploitation • Damaging isolation • Degrading devices

Schneider Electric - CS&P – System Terminology – E01

24

• MiCOM Range P

Protection

C

Computer

M

Measurement

S

System

H

Hubb=> Hubb=> Switch

Schneider Electric - CS&P – System Terminology – E01

25

• MiCOM Naming Pxyz for Protection e.g. Pxyz P

Protection

X

Application (e.g.: 1=overcurrent 1=overcurrent) overcurrent)

Y

Hardware platform (e.g. 20 serie) serie)

Z

Options (additional hard, threshold..)

Schneider Electric - CS&P – System Terminology – E01

26

• MiCOM Naming P_y_ Hardware platform

20 Series

30 Series

40 Series Schneider Electric - CS&P – System Terminology – E01

27

• MiCOM Naming Px__ P900 Voltage/Frequency P800 Auxiliary P700 Bars Differential P600 Transformer Differential P500 Line Differential P400 Distance P300 Generator P200 Motor P100 Overcurrent Schneider Electric - CS&P – System Terminology – E01

28

• MiCOM P Application  Substation: P540

P440

P900 Voltage/Frequency

P845

P120

P920 P940

P800 Auxiliary P700 Bars Differential P140

P600 Transformer Differential

P630 T&D

P500 Line Differential P400 Distance P300 Generator M

P200 Motor G

P100 Overcurrent

P220 P120

Schneider Electric - CS&P – System Terminology – E01

P240 P520 ou P540

P340 29

• Content

 Electric Network Definition  Primary Devices  Protections  Datapoints

Schneider Electric - CS&P – System Terminology – E01

30

• Datapoint Terminology REAL TIME DATA = DATAPOINTS Several KIND of DP

IEC61850

 SPS  DPS  MPS

Single Point Status Double Point Status Multiple Point Status

BINARY

 MV  TPI

Measurement Value Tap Position Indication

MV, WYE_MX, DEL MEASUR. BST_ST &

 SCT  DCT

Single CounTer Double CounTer

 SPC  DPC  SP

Single Point Control Double Point Control SetPoint

Schneider Electric - CS&P – System Terminology – E01

INPUTS

SPS_ST , SPC_ST DPS_ST, DPC_ST INS_ST

COUNTERS BCR_ST

SPC_CO OUTPUTS DPC_CO,BST_CO APC_SP

31

• Supervision Datapoint Attributes Supervision Status/Value

Quality

 SPS

Reset/Set

Valid / FSS / Invalid

 DPS

Open(01)/Close(10)

Valid / FSS / Invalid

 MPS

State16

Valid / FSS / Threshold / Invalid

 MV, TPI, DM

Value (Float32)

Valid / FSS / Threshold / Invalid

 SCT, DCT

Integer

Common Invalid +DPS invalid +MV, xCT invalid

Unknown (IED), Self-Check Fault (Hard) Jammed (00) Undefined (11) Open Circuit, Undefined, OverRange

FSS

Force (auto/Manu) an Invalid DP Suppress (Make DP invalid) Substitute (Force the Status/Value of DP)

Threshold

For Alarms / Events L,LL,LLL, H, HH, HHH with hysteresis

Schneider Electric - CS&P – System Terminology – E01

32

• Control Datapoint SPC, DPC, SP Kind Direct Execute

Select Before Operate

One Shot Medium/Low Volt.

Selection / Wait(cancel) / Execute HV + Control Uniqueness => order run Bay

Where 2) Supervision OI SCADA

Direct Execute

Select Before Operate

DE, SBO like pop-up DE, SBO

SBO pop-up DE, SBO

1) SBUS/C264

DE

SBO Select Open/Close Execute Open/Close

3) IED

DE, SBO

DE, SBO

Schneider Electric - CS&P – System Terminology – E01

33

• Control Checks  Station •Operator Right / Gateway channel in control •Remote/Local Station •Device operating mode (operational, not stand-by…) •Control Uniqueness Station (GOOSE) •Topological ILK  Bay •Control Uniqueness Bay (order running) •Remote/Local Bay  Module (switch, transformer..) •Current Module State/Value •Bay interlock open/close (including module specific conditions) •Locking •Auto/Manu Dependency (automation running) •Recuperation Time  Inner Simple “Built-in” Automation •Output / feedback input (Delays….) •Physical SBO, Direct Execute, 3 phases, Communication IED Schneider Electric - CS&P – System Terminology – E01

34