KOC-L-009 Rev 5_KOC Standard for Fire Protection Systems and Safety Equipment

October 10, 2017 | Author: Saif243 | Category: Pump, Fire Sprinkler System, Firefighting, Valve, Pumping Station
Share Embed Donate


Short Description

KOC-L-009 Rev 5_KOC Standard for Fire Protection Systems and Safety Equipment...

Description

~I J~r ~.:.l4"....t. ,,-"-I

A Subsidiary of KuwaC t F>WoleumCorporation

STANDARDS PUBLICATION

KOCSTANDARDFOR

FIRE PROTECTION SYSTEMS AND SAFETY

EQUIPMENT

DOC. NO. KOC-L-009 (Rev. 5)

STANDARDS TEAM

III

KOC-L-009

I

Page 1 of 66

I

REV.5

~J~~.:A...J"'!'~I ASubcldiMyolKitdlPI4t-..nCqrpont\orl

STANDARDS PUBLICATION

KOCSTANDARD

FOR

FIRE PROTECTION SYSTEMS AND

SAFETY EQUIPMENT

DOC. NO. KOC-L-009

ST ANDARDS TEAM

KOC-L-009

REV.S

Page 2 of 66

KOCSTANDARD FOR

FIRE PROTECTION SYSTEMS AND

SAFETY EQUIPMENT

DOC.NO. KOC-L-009

ISSUING AUTHORITY:

STANDARDS TEAM

Task Force ". I . ft~_ (TF-LP/16) ~~ ~.

01 .10.14

Issued as KOC Standard

4

05.08.10

Issued as KOC Standard

(TF-LP/16)

Rev.

Date

Description

Prepared by

5

Task Force

\

.:

V

Mr. Faisal Mairza

--------

Mr. Hamzah Ahmad

TF Leader

Snr. Engr. Stds.

Team Leader Standards

Tel. No. 61223

Tel. No. 61633

Tel. 61896

KOC-L-009

Page 3 of 66

REV.5

FOREWORD

5

1.0

SCOPE

8

2.0

APPLICATION

9

3.0

TERMINOLOGY 3.1 Definitions 3.2 Abbreviations

9

9

10

4.0 4.1 4.2

STANDARDS AND ~"'''LJL:.cJI Conflicts of Standards and Codes

5.0

ENVIRONMENTAL CONDITIONS

6.0

HEALTH,

7.0

FIRE PROTECTION SYSTEM AND

11

11

11

15

AND ENVIRONMENT

7.1

15

EQUIPMENT

16

General Fire Water System 7.3 Deluge Water Spray System 7.4 Foam Systems for Crude Storage Tanks 1.5 Fire Hydrant and Fire Engine Suction Riser Units I Plant Buildings 1.6 Dry/Wet Riser for Upper Floor 1.1 Fire Fighting Equipment for Facilities 7.8 Hose Reel with Cabinets for Plant Buildings 7.9 Trailer Mounted Foam I Water Cannons 1.10 Mobile Water Monitors 1.11 Fixed Water I Foam Monitors 1.12 Portable I Wheeled Extinguishers 1.13 Safety Showers, Eye Wash and Eye I Face Wash Units 4 Respiratory Protective Equipment

(Escape Only Respirator & SCBA) 7.15 First-Aid Kits and Stretchers 1.16 Safety Signs and Notices 7.11 Wind Socks

46

41

49

49

8.0

PERFORMANCE REQUIREMENTS 8.1 General

50

50

9.0

INSPECTION AND

50

10.0

QUALITY ASSURANCE

51

11.0

MARKING

51

NG

16

16

26

30

35

36

31

39

39

40

40

41

45

KOC-L-009

Page 4 of 66

REV.5

12.0

DOCUMENTATION

51

13.0

SPARE PARTS AND MAINTENANCE REQUIREMENTS

51

14.0

APPENDICES

52-64

APPENDIX 1

53-56

APPENDIX 1.1

TYPICAL LAYOUT DELUGE AND SEMI-FIXED

53

FOAM FOR CRUDE TANK

APPENDIX 1

TYPICAL LAYOUT OF DELUGE SYSTEM

APPENDIX 1.3

TYPICAL LAYOUT OF SEMI-FIXED FOAM SYSTEM

55

AND 4-WAY SUCTION COLLECTING HEAD

APPENDIX 1.4

TYPICAL DETAILS OF FOAM CHAMBER

56

APPENDIX 2

TYPICAL DETAILS OF FIRE HYDRANT

57

APPENDIX 3

TYPICAL DETAILS OF FIRE ENGINE SUCTION

RISER

58

APPENDIX 4

TYPICAL DETAILS OF FIRE EQUIPMENT BOX

59

APPENDIX 5

TYPICAL DETAILS MATERIALS FOR FIRE

WATER, DELUGE AND FOAM SYSTEMS

60

TYPICAL OF POST INDICATOR TYPE

ISOLATION VALVE

61

TYPICAL DETAILS OF TRAILER MOUNTED

FOAM I WATER CANNON

62

APPENDIX 8

TYPICAL DETAILS OF WIND SOCK

63

APPENDIX 9

TYPICAL DETAILS

STORZ COUPLING

APPENDIX 6

APPENDIX 7

15.0

DELUGE AND SEMI-FIXED FOAM SYSTEMS

(See Appendices 1.1 to 1.4 for typical details)

ACKNOWLEDGEMENT

HYDRANT CUM

64 65-66

FOREWORD

151

This document "KOC Standard for Fire Protection Systems and Safety Equipment" for n, (KOC-L-009, Rev. 5) is intended to provide the minimum technical requ manufacture, construction and performance of fire protection systems and safety equipment in KOC. The current document (KOC-L-009, with a view to protect personnel and Rev. 4) has for conformance with revision of relevant International I National Standards and incorporation of latest technological developments in this field. Standard has been approved by the Standards Team in consultation with Standards Technical Committee (STC) for use throughout and Operational functions of Kuwait Oil Company (K.S.C). This KOC Standard

out to

following objectives:

a)

identify equipment

basic KOC requirements on protection systems and safety protect personnel, plant and property for KOC Facilities.

b)

To provide a set of consistent guidelines for design, manufacture, construction and installation of protection system and safety equipment.

c)

To define the minimum standard requirements for fire protection system and safety equipment that have general applicability act as a for a consistent system and cost equipment.

Feedback with any comments derived from the application of this KOC Standard any stage of design, manufacture, construction, installation, commissioning, operation and maintenance are invited and shall be directed to:

The Standards (Chairman, Standards Technical Committee) Project & Support Services Group, Kuwait Oil Company O. Box 9758 Ahmadi 61008 State of Kuwait

The revision of this KOC Standard (Rev. has been entrusted by the Standards Force (TF-LP/16) comprising of the following members: Committee (STC) to the Mr. Mr. Mr. Mr. Mr. Mr. Mr. Mr. Mr. Mr. Mr. Mr. Mr.

M. Shakeel Anil Kumar Mukesh Mittal Sadeq AI Sharhan Christopher Subhra Kumar Ummer Kutty Mohit Narayan Javed Usmani Umair A. Usmani Mohamed John Lambert Leonardo Cortufo

Standards Fire Team Fire Team Team Safety OTS K) (WK) OTS (NK) HSE Standards Team PMC Fluor PMCAMEC PMC Worley

Leader Author/Member Member Member Member Member Member Member Member Member Member Member Member

No. 61223 Tel. No. 67527 Tel. No. 66048 No. 22188 Tel. No. 65409 No. Tel. No. 20051 Tel. No. No. 61362 Tel. No. 61869 Tel. No. 61763 Tel. No. 63184 Mb.60057966

KOC-L-009

Page 6 of 66

REV.S

Clause

5

7

"Guidelines with respect to KOC

16

7.3

17

7

18

7.5

19

7.6

20 21

Sub clauses c f - - - - + - - _7_.8_---4f-::: : :la -:-.,.u--'ses 7.8.1 to 7. 8.. 3.,---:c:-~_--:-:-c----,-_ _ _-=-~--::--____ :..--=---~ Title! Sub-Clauses Modified and New sub clauses & 7 9.6 22 7 added 23 Sub-Clauses and New sub 10.6 added Modified Modified and Table 3 elaborated under clause 7.1

KOC-L-009

Page 7 of 66

REV.5

Clause

28 .

8

13 14 f----'--'--+---­

with the respective Sub-

covering

KOC-L-009

III

l

Page 8 of 66

I

REV.5

151

1.0

SCOPE

1.1

This KOC Standard covers the minimum technical requirements and the basic guidelines for design, manufacture, construction and installation of fire protection system and safety equipment for KOC onshore facilities in Kuwait.

1.2

Fire protection requirements within KOC are broadly classified into Active Fire Protection and Passive Fire Protection. This KOC Standard covers Active Fire Protection system as mentioned below: a) Fire Water system

b) Water Sprinkler / Deluge system

c) Fixed or Semi-Fixed Foam system

d) Portable / Mobile Fire Fighting Equipment

1.3

This KOC Standard specifies the minimum requirements for the following Safety Equipment: a) Safety Showers, Eye Wash, and Eye / Face Wash Units b) Respiratory Protective Equipment

c) First-Aid kits, Stretchers, etc.

1.4

Exclusions a) This KOC Standard does not cover Passive Fire Protection requirements. For passive fire proofing / protection "KOC Standard for Fire Proofing of Structural Steelwork-Materials and Workmanship" (KOC-C-027) and other relevant standards shall be referred. b) Fire / Smoke / Gas / Heat detection Systems etc. For Fire & Gas Equipment, refer to KOC-L-006 "KOC Standard for Fire & Gas Detection Equipment". c) Buildings such as residential buildings, offices, sports complex, warehouse / stores etc. in Ahmadi and other office building as Burgan Office Complex, Fire Station etc., situated outside KOC Plant facilities are excluded from this KOC standard. Fire Protection requirements for such buildings have been defined in "KOC Standard for Fire Protection of Non-Plant Buildings" (KOC-L-020). d) Active Fire Protection system other than Substation(s), Control/Office / Utility Building.

e) Drilling rigs, Christmas tree and well heads.

fire

extinguishers

for

Electrical

I

KOC-L-009

II

Page 9 of 66

I

REV.S

NOTE: The requirements covered in this document "KOC Standard for Fire Protection Systems and Safety Equipment" (KOC-L-009, Rev. 5) shall supersede similar requirement(s) in the following KOC Standard 1015 Series Specification: KOC-L-008

KOC Standard for Fluoroprotein Foam Liquid Concentrate for Fire­ Fighting

381/016

Specification for 4-Wheeled portable water spray monitor for Fire­ Fighting.

381/017

Specification for twin barrel long-range foam 1 water cannon (foam 1 water monitor) for Fire-Fighting purposes.

015-YH-1 003

Loss Prevention Requirements

2.0

APPLICATION

2.1

The fire protection system and safety equipment requirements defined in this KOC Standard shall be applicable to KOC Plant Facilities viz. GCs, BSs, Tank Farms, EWDP etc.

2.2

Any exceptions or deviations from this KOC Standard, along with their merits and justification, shall be brought to the attention of KOC Controlling Team for review, consideration and amendment by the Standards Team (if required) .

2.3

It is the responsibility of KOC Controlling Team to seek advice 1 approval from KOC Fire Group for Fire Protection Systems & Firefighting Equipment and Asset HSE Team for Safety Equipment.

2.4

Compliance with this KOC Standard does not of itself confer immunity from technical, legal or statutory obligations.

3.0

TERMINOLOGY

3.1

Definitions

151

151

For the purpose of this Standard the following definitions shall apply: 3.1.1 Active Fire Protection A type of fire protection which needs activation (manual or automatic) in case of any firel emergency to control situation in order to protect people, equipment, structure, material etc. (Active fire protection includes water spray system, foam system etc.). 3.1.2 Contractor The person, persons, firm or company contracted by KOC to undertake the execution of the work defined by the signed contract.

REV.5

Page 10 of 66 3.1.3 Fire and Explosion Risk Assessment (FERA).

is a study to characterize the risk associated with that the of concern, their probability, and their potential consequences. It shall identify study and list the potential sources and types of fire as well as explosion potential. shall be conducted as NFPA 551 and lor as specified in project document. report same shall be shall be prepared as per the project requirements I specifications and reviewed and approved by concerned KOC 1.4 KOC Controlling Any KOC Team authorized to initiate a request for procurement of materials I equipment(s) for KOC. 3.1.5

and

of a project or

Protection A type of fire protection engineering to protect the equipment I structure from damage without requiring I triggering any action during fire incident.

3.1

Purchase Order A document issued by KOC I PMC or Contractor, authorized by KOC to a Manufacturer I for the supply of Fire Protection and Safety Equipment(s) indicating technical requirements covered by this Standard I Project Specification.

3.1

Safety Equipment Equipment items are required at operating facilities to protect the personnel. {Example: Safety Showers, Wash and Eye I Face Wash Units, Self-Contained Breathing Apparatus (SCBA), Stretchers etc.}.

3.1

Vendor An Organ or Body approved by KOC, who manufactures and I or assembles and I or supplies the Protection System and Equipment(s) and on whom the the overall responsibility of the complete purchase order is placed and who also Protection System Safety Equipment(s) supplied.

3.1.9 Worst-case accident Worst-case accident scenario typically considers near instantaneous release of the amount of hydrocarbon I flammable inventory a Facility. In using worst-case scenario, only one parameter 'damage potential' is considered and the probability of occurrence is generally low.

3.2 BS

Booster

CRU

Condensate Recovery Unit

DPC

Dry Powder Chemical Effluent Water Disposal Plant

F&G

FERA

Fire & and Explosion Risk Assessment Factory Mutual

KOC-L-009

Page 11 of 66

FMB

Foam Making Branch (pipe)

GC

Gathering

REV.5

Glass-Reinforced Plastic , Safety and Environment Management System IR

Infra-red

KOC

Kuwait Oil Company (K.S.C.) Kuwait Fire

Directorate

LPM

Liter

OEM

Original Equipment Manufacturer

Minute

Personal Alert Safety System PMC

Project Management Consultants

PLC

Programmable Logic Controller

PVC

Poly Vinyl Chloride Reinforced Concrete Cement

SCBA

Self-Contained

Apparatus

Water Treatment

SWTP

Tank

TV

Tank Vapor

UL

Underwriters Laboratories

UPS

Uninterruptible Power Supply

USG/USGPM

US Gallons I US Gallons Per Minute

UV

Ultraviolet

4.0

REFERENCE STANDARDS AND CODES

4.1

Conflicts

151

In event of conflicts between this KOC Standard and latest edition of standards I codes herein or other purchase or contractual requirements, the most stringent requirement(s) shall apply.

4.2 4

1 International I National Standards Latest

of the following standards, COCles and specifications shall apply:

ANSIiISEA Z358.1

American National Standard for Emergency Eyewash and Shower Equipment

Page 12 of 66

KOC-L-009

REV.5

API RP 581

Risk Based Inspection Technology

ASTM F 467

Standard Specification for Nonferrous

ASTM F

Standard Specification for Nonferrous Bolts, Hex Cap Screws, Socket Cap and for Use

ASME SEC VIII-1

Section VIII Division 1: Ru

Specification for

336 5041

1-5

for Construction of Pressure

Hose Couplings and Ancillary

uipment

Hydrant Systems Equipment

5423

for

BS 5499 Parts 4 &10 BS 6391

Fire Extinguishers

Signs Including

Safety Sign.

Specification for Non - percolating Lay Delivery Hose blies for Firefighting Purposes Portable Extinguishers. Characteristics, Requirements and Test Methods

3-7: + A1

Fixed Fire-Fighting Systems Reels Semi-Rigid Hose

BS EN 671-1

694

Fire-Fighting

BS EN ISO 10497

&2

Semi-Rigid

for

and

Performance

1: Hose

Hose Systems -

Testing of Valves - Fire

Systems

Requirements

Workshop Steel Part 1 and 2: Horizontal Cylindrical Single Skin and Double Skin Tanks for The Underground I Aboveground Storage of Flammable and Nonmmable Water Polluting Liquids

EN

of Protection Provided by Enclosures (IP code)

ISO 7010

Safety Signs and Sym

ISO 9000

Quality Management Systems

NFPA 1

Fire Code

N

Use

for Extinguishing Equipment on Premises - Part 1: Hose and foam inlets

BS 5306-1

EN 1

for

10

Standard

Portable

Fundamentals

Vocabulary

Extinguishers

NFPA 11

Standard for Low, Medium

NFPA 13

Standard for the Installation of Sprinkler

NFPA 15

Standard for Water

High

Fixed

nsion

for

Protection

KOC-l-009

13 of 66

NFPA 16

for the Foam-Water Spray

NFPA 20

Standard for Protection

NFPA 22

Standard

I\IFPA 24

Standard for the Installation of Private Fire their Appurtenances.

NFPA

of

Stationary

Private Fire

Water

Pum

for

I.Jrntol"t

Mains and

Life Safety High Challenge

1

Wall, Fire Walls and

Marking of

NFPA 291

Recommended Practice for Hydrants

NFPA 551

Guide for the Evaluation of Fire Risk

NFPA 750

Standard on Water Mist

NFPA 1981

Standard on Open-Circuit Self-Contained Breathing Apparatus (SCBA) for Emergency Services

Kuwait 4

Installation

for the Inspection, Testing and Maintenance of Water Protection

NFPA 101 N

the

of Foam-Water Sprinkler

Flow Testing

/""\;:';:>\::;:',;:'1

re Protection Systems

as applicable

Service Directorate (KFSD)

KOC Standards KOC Standard

rdous

Classification

KOC-G-004

KOC Standard for Packing, Marking and Documentation

KOC-G-007

KOC

KOC-G-009

KOC Standard for

KOC-I-001

KOC Standard for Instrumentation and

KOC-I-002

KOC Standard for Instrument Illation

KOC-I-005

KOC Recommended Practice for

KOC-L-006

KOC Standard for

KOC-L-015

KOC Standards for Cathodic Underground Pipelines & Piping Networks

KOC-L-018

KOC Standards for Cathodic Protection of Internal Steel Tanks & Vessels

for Basic Parts and Maintenance

&

System

& Gas System

Detection

ipment Protection

of

of

KOC-L-009 KOC-L-020

KOC Standard for Fire Protection in Non-Plant Buildings

KOC-L-024

KOC Recommended Practice for Alternative

Halon System

KOC-L-026

KOC Recommended Practice for External Cathodic Protection of on-Grade Steel nk Bottom

KOC-L-027

KOC Standard for Layout, Spacing and Diking of Aboveground Petroleum Storage Tanks

KOC-L-028

KOC Recommended Practice for Plant Layout (Includes Spacing Charts)

KOC-M-007

KOC Standard for

KOC-ME-009

KOC Standard for Stationary Firewater Pump

KOC-MP-010

KOC Standard for Piping Material

KOC-MV-007

KOC Standard for

KOC-P-001

KOC Standard for Painting and Coating Surfaces

KOC-P-002

4.2

REV.S

Page 14 of 66

2

Agents

Hose

IJICl;:);::'O;:;;::'

Erected Storage External

KOC Standard for Internal Lining of Steel Tanks and Vessels: Tanks Part 2: Internal Lining of Above Ground Coating of Pipelines (Parts

KOC-P-004

KOC Standard for 8 &9)

KOC-P-005

KOC Standard for Internal Coating of Pipelines

KOC-P-017

KOC Standard for Colour Coding Identification of Fluids & Services

KOC-Q-014

KOC Standard for Project QAlQC Requirements

of

4,5,

Pipework

for

KOC Specifications 015-CH-1002 015-YH-1 003

Light Duty Drums Prevention Requirements

o15-.JH-1903

General Instruments

015-JH-1909

Instrumentation for Package Equipment

381/29

specification for Instrument Engineering in Industrial Process

4.2.4 KOC Health, KOC.GE.028

& Environment Management System (HSEMS) Training, Awareness and Continued HSE

Process

KOC-L-009

Page 15 of 66

1

KOC

KOC Fire Safety Management

Occupational Health and Hygiene

Aid

Process Safety Management (PSM) Manual

.PS.001 KOC.SA.004

Permit to Work Procedure

KOC.

Self-Contained Breathing Apparatus

Procedure for Personal Protective

10

ipment

Job Safety Analysis (JSA)

KOC.SA.040

Guidelines for Quantitative Risk t-\~::it::~i~

KOC

Rule Set for Quantitative Risk

KOC

1

Policy & KOC

J..\.s~,;t::~

(QRA)



Guide

Any Other relevant KOC HSEMS 5.0

ENVIRONMENTAL CONDITIONS

5.1

For environmental conditions in Kuwait, Design Data", which provides environmental, site and utility supply Facilities.

5.2

The atmosphere shall be considered to of H2S, S02 and airborne chemical

as

151 "KOC Standard for Basic regarding the throughout the KOC

and may contain traces

The equipment and material shall conditions as mentioned in C project documents.

in environmental continuous this KOC Standard and the relevant

6.0

HEALTH. SAFETY AND ENVIRONMENT

15 r

6.1

The Vendor I Contractor shall ensure compliance of all Health, Safety and Management ures to protect personnel, property and surrounding environment during field works.

6.2

All relevant complied while performing

3

6.3

of KOC HSE policy and HSEMS Procedures shall works within KOC areas.

work (PTW) with applicable Job Safety Analysis (JSA) II be prepared in accordance to KOC out and prior to commencement of work. The PTW and HSE requirements specified by the fire protection applicable KOC HSEMS Procedures.

KOC-l-009

6.4

Page 16 of 66

REV.5

The Contractor shall all necessary precautionary appropriate personal protective equipment (PPE), equipment during installation of fire protection

including the use ensure the safe handling of

All Contractor utilized for the works shall have successfully undergone all the applicable training required for the pertinent works. All Contractor shall have attended the awareness course(s) as identified in "Matrix of nel need 'HSE Training' and' Awareness identified Categories of Contractors' Employees" under HSEMS procedure KOC.

7.0

FIRE PROTECTION SYSTEM AND SAFETY EQUIPMENT

7.1

General

I5I

15 I

1.1 All Fire protection systems, firefighting equipment safety accordance with the this KOC Standard and 4 of this KOG

ipment shall be in referred in

1

protection systems firefighting equipment shall be and I or FM Kuwait laws & regulations; subjected to prior approved and in compliance with inspection, testing and approval by KOC Controlling Team and

1.3

one complete drawing with specifications etc. for protection system, firefighting equipment and safety and Safety ! equipment shall be provided to KOC Controlling from Controlling HSE Team for approval. Upon receipt of submit one sample of firefighting I , Vendor I Contractor shall equipment Vendor I Contractor procure such or protection I safety system, to equipment(s) upon KOC approval in writing.

I Contractor shall consult!

1

system!

with KOC Controlling Team and Group firefighting appropriate locations for installation of fire protection & equipment and submit drawings showing locations of ipment for KOC approval.

7.1.5 A detailed FERA of entire Facility shall

ca

out and reports shall

IIC!\Ai,:>n

I

approved by concerned KOC Teams.

7.2 7.2.1

to KOC Facilities segregated into different ease of firefighting study. For process areas contain combustible liquids or limited to the following shall be applicable: a)

Minimum d

between equipment and and KOG-L-028 or as I"Qr"I'irY'\

151 for the purpose of fire the Fire and Explosion vessels and equipment which guidelines including but not

Areas" shall

as

KOC-L-009

Page 17 of 66

b)

shall identified

fire veh access from at least two opposite in accordance with KOC-L-028. areas. Road width shall

c)

Any connection from be itted.

7.2.2 Design Basis

water network to any utility of whatever nature shall not

151

a)

Fire water system shall designed to supply fire at rated flow and to facilitate desired operation of protection consisting of deluge water spray system, fixed & semi fixed foam systems, fixed I trolley mounted water monitors, hydrants, hose lines The shall capable to maintain a re of 150 psi(g) [10.3 bar(g)] at the farthest point in the fire water minimum ring main discharging the fire at rated flow. The firewater storage tank shall be designed for catering to minimum six (6) Hours duration (at all times even during maintenance fire water storage tank) maximum anticipated water

b)

be based on full surface tank on fire Gathering Centers & Farms and full bore rupture scenario Equipment I Vessels containing maximum inventory at Booster Station. water demand shall calculated as Standard or based on FERA whichever is higher.

7.2.3

of the

sub

7.2.3 of this KOC

Maximum Anticipated Firewater Demand Calculations: 15 I General Maximum AntiCipated Firewater Demand shall based on highest obtained considering all Combinations of fire protection system operating for each identified scenarios in accordance with the design basis under Clause for various KOC facilities: a) For Gathering Centers (GC): (Fixed Roof (Cone) Crude Storage Tanks)

L Deluge Water Spray

shall be calculated for 100% of roof area, considering the Tank on Fire.(Application Rate = 10.2 Ipm 1m2 [0.25 gpm/ff]), and

Ii.

Deluge Water Spray System be calculated for side of tank(s). (Calculated on 50% roof surface area with application rate = 10.2 Ipm 1m2 [0.25 gpmlW]), and

III.

Foam System shall calculated for 100% of liquid surface area of tank on fire. (Application Rate= 4.1 Ipm/m 2 [0.1 gpm/ft. 2 ]),and Allowance water I foam hose Nos. of mm diameter (One [250 USGPM]).

shall calculated for four (4) line discharge rate = 946.35 I/min

OR worst case scenario identified based on of the Facility.

& Explosion Risk Assessment

KOC-L-009

Page 18 of 66

REV.5

b) For Tank Farms (TF): (Floating Roof Crude Storage Tanks) i.

Water Spray System shall be calculated for upper half of tank shell area considering the Tank (Application Rate:::: 1 Ipm I m2 [0.25 gpm/ff]), and

100% of on Fire.

ii. Deluge Water Spray System shall be calculated for exposed side of ** adjacent tank(s) (Calculated on 50% of the upper half of tank shell area with application :::: 10.2 Ipm I m2 [0.25 gpm/ft2]), and iii. Fixed Foam System shall be calculated for rim (Application 12.2 Ipm I m2 [0.30 gpm/ft2]). and

area of tank on fire

Allowance for water I foam hose shall be calculated four (4) :::: 946.35 I/min Nos. of 63 mm diameter (One hose line discharge PM (22712.48 Ipm) high volume USGPMD and 1 No 6000 long range monitor.

Any other worst case (FERA) of the Facility.

identified based on Fire & Explosion Risk Assessment

** The

adjacent tank(s) refers to tank(s) within an inter distance (Shell-to-Sh e II), where the calculated radiation exposure are in excess of 1 5 kWlm2 from the tank on based on FERA. However, in absence of such analysis, the adjacent tank(s) to tank(s) within an distance (Shell-to-She/I) of three (3) times the diameter of the tank on c) For Booster Station (BS): i.

Deluge Water Spray System shall be calculated for the affected surfaces in full bore rupture scenario of equipment I vessels containing maximum inventory on fire. (Application rate shall as per NFPA 15), and

ii. Deluge Water Spray requirement shall be calculated for cooling the exposed surfaces nearby equipment I vessels where the calculated radiation exposure levels are in excess of 12.5 kW/m2 , and iii.

calculated for four (4) Allowance water I foam hose lines shall Nos. of 63 mm diameter (One hose line discharge rate : : : 946.35 I/min [250 USGPM]). OR

Any other worst case scenario identified based on (FERA) of the Facility.

& Explosion Risk Assessment

Page 19 of 66 such as Effluent Water Treatment Plant, Water Treatment Plant:

d)

and

design philosophy shall be developed as per in line with this KOC Standard and other International Standards (like NFPA etc.) in consultation with KOC Fire Group. However, as , following shall be followed: i.

shall be calculated for 100% of liquid area of tank* on fire. (Application 4.1 Ipm/m 2 [0.1 gpm/ft. 2 D, and

(*Effluent Recovered oil ) one (1)

Surge I Balance tanks, Treated water wherein it is expected to have oil layer more

ii. Allowance for of 63 mm USGPM]).

foam hose lines shall be calculated for four (4) Nos. rate == 946.35 I/min [250

Any other worst case (FERA) of the Facility.

& Explosion Risk Assessment

Note: Deluge water spray 2 Ipm / installed based on water protection from adjacent crude oil radiation exposure levels are in excess of

7.2.4

[0. gpm I If] of 100 % tank roof area shall be tank, Recovered oil tank etc. in GC for exposure I equipment fires where the calculated 5 kWlm2.

Components of Firewater System Firewater System shall constitute of, but not limited to, a)

Firewater Storage Tank(s).

b)

Firewater Pump(s), Pressure Maintaining

c)

Buried underground Firewater Mains.

d)

Manual and Automatic Fire Suppression Water Spray Systems, Fixed I Semi

151 following components:

Isolation Valves and other related equipment. f)

Hydrants, Risers, Fire Brigade Inlet (Suction Collection

Unless otherwise specified, the Water System described piping, shall handle 'Brackish Water' Components of valves, fittings, instrumentation, pumps etc. shall also suitable for brackish water. Any electrical and instrumentation equipment shall be suitable for the area classification of installed location with Ingress Protection IP 65 (minimum).

KOC-L-009

III

7.2.5

I

Firewater Storage Tanks

Page 20 of 66

I

REV.5

151

a) Firewater shall be stored in aboveground metallic fixed cone roof storage tank(s). The tank shall be designed to cater the fire water demand as stipulated in clauses 7.2.2 and 7.2.3 of this KOC Standard. Design shall be capable for an automatic filling arrangement with flow rate of not less than 25% of the maximum fire water demand or 5,678.1 I/min [1500 USGPM], whichever is higher. However, this filling rate shall not be accounted for the purpose of firewater storage design calculations. b) The design of Fire Water Tank shall be in accordance with the requirement of KOC-MV-007 "KOC Standard for Field Erected Storage Tanks". c) A dedicated standby firewater reserve tank shall also be provided so that the minimum Six (6) hours reliable firewater storage is available during maintenance period. In cases where, a separate dedicated reserve tank is not feasible due to site constraints or any other reason with proper justification, a dual service tank (Brackish Water + Fire Water) shall be provided with prior approval from KOC Controlling Team I Fire Group. However, it shall be ensured that adequate Fire water reserve shall be constantly and automatically maintained in the tank for the Fire protection purpose. d) Firewater tank(s) shall be provided with Facility for inspection, cleaning, maintenance and repairs etc. e) Fire Water storage tank bottom shall be provided with cathodic protection in accordance with KOC-L-026 "KOC Recommended Practice for External Cathodic Protection of on-Grade New Steel Tank Bottom" and the internal surface shall be provided with cathodic protection in accordance with KOC-L-018 "KOC Standards for Cathodic Protection of Internal Surfaces of Steel Tanks & Vessels". f)

Fire Water storage tank bottom shall be internally lined as per KOC-P-002, Part 2, "KOC Standard for Internal Lining of Steel Tanks & Vessels Part 2: Internal Lining of Above Ground Steel Tanks".

g) Fire Water Storage tanks shall meet the design requirements and other provisionsl fittings as defined in NFPA 22 for welded Steel Gravity Tanks or the type of storage selected. h) The level alarms for Fire Water Storage Tank shall be provided in the Facility Control Room and tank level indicators shall be provided near the tank in accessible I visible location. i)

Fire Water Storage tanks shall be provided with Eight (8) Nos. of 2% Inch. male instantaneous coupling tanker filling connections I fire brigade inlet.

j)

Fire engine suction riser (as per Appendix 3) shall be provided near the fire water storage tank and accessible to fire engine.

k) The drainage arrangement shall be made around the tank I area to avoid any accumulation of water around it.

Page

KOC-L-009

of66 151

Firewater Pump House a)

distance pump house shall be located at a Dedicated spacing chart of KOC-L-028 in such a manner (minimum 60.0 areas and is identified based on contours of that it is away from (FERA) to operate during worst case Fire & Explosion scenarios.

b) The Firewater Pump shall not be located prevailing wind direction. The location of Firewater Pump House shall on higher ground contour to any flooding in case of area. The firewater pump(s) including jockey pumps shall as as possible to the firewater tanks or alternate firewater source. However, it shall be within the High rity (HSF) of the Facility protected. c)

Firewater pump(s) and drivers shall be easily by fire trucks, heavy mobile equipment , by at least two alternate approach roads to facilitate and maintenance access. uipment handling facilities such cranes etc. shall be provided in Water Pump house for and major overhaul.

d)

Tank(s), Fire Water Pump Riser shall have paved maneuverability around them.

e)

arrangement to handle discharge capacity provided and connected to storm water drain around the fire water pump from the pressure relief to avoid any accumulation of discharge, other water leakages, accidental leakages from system. drain with grating to provided longitudinal side of pump shed or both ends based on pump house size.

f)

shall

g)

Normal and

h)

pump house shall be equipped which shall be hooked up to the

i)

pump house enclosing diesel automatic sprinkler system installed in

j)

k) I)

and

Engine Suction Trucks with good

suitably sloped for drainage of escaping water equipment such as the pump, driver, controller etc. lighting shall lighting shall not con

Pump House shall be in

provided in the firewater pump house. to engine starting battery. manual call points

pump drivers shall be with NFPA 13.

with an

clo::;ea or semi-enclosed sheds.

location shall be protected from dust I water etc. curb (Kerbing) of 150 mm height to be provided all around the pump house except in the maintenance access area.

Page 22 of 66

KOC-L-009

7.2.7

REV.5

151

Firewater Pumps

The Main Firewater Pump(s) shall rated to meet maximum anticipated water demand calculated based on clause 7.2 of this ndard. In addition main pump(s), shall Stand-by pump(s) of the same capacity as that of main pump(s). recommended numbers of Main(s) I be as follows: );> 1 Main );> 2 Mains

nd-by pump(s) configuration

+ 1 Stand-by + 1 Stand-by

);;>

3 Mains + 2 Stand-by

);;>

4 Mains + 2

);;>

5 Mains + 3 Stand-by.

nd-by

b) The firewater pump(s) shall be capable to maintain a minimum re of 1 psi(g) [10.3 bar(g)] at the farthest paint in the fire water ring main while discharging maximum anticipated firewater demand. gauges shall be provided on such remote location (minimum 2 locations) for monitoring the pressure in the ring main.

c)

water pump(s) shall diesel engine driven, centrifugal pumps, desig and installed in with KOC-ME-009 "KOC Standard for Stationary Firewater Pump NFPA 20.

d)

performance of Water mp shall such that it shall fumish not less than 65% of total head and total shut than 150% of rated capacity at not off shall not exceed 140% of head in accordance with N 20.

e)

pump(s) installation shall allow of performance as per Manufacturer curves. listed capable of flow not than 175% of provided in the system.

f)

Fire Water Pumps shall tested as Stationary Firewater Pumpsets".

g)

fuel storage tank shall be Stationary Firewater Pump sets".

h)

Coupling guards shall be installed on couplings and flexible connecting

fire pump to its device or fixed nozzle pump capacity shall be

KOC-ME-009 "KOC Standard for

as

KOC-ME-009 "KOC Standard for

Page 23 of 66

KOC-L-009

7 .8

151

Jockey Pumps

Minimum of Two (2) numbers (One in Operation + One Stand-by) electrically pressure maintaining jockey pumps shall provided for operation to maintain pressure in the ring main for making up Jockey pump shall have a minimum discharge capacity m3/hour [110 USGPM] or higher. Jockey pump(s) shall be centrifugal installed in accordance with KOC-ME-009 "KOC Pump sets" and NFPA 20.

7.2.9

151

Water Pump Drivers and Controllers a)

Pump II be dedicated to various 'fire protection service. Pump(s) {Main(s) and Standby(s)} shall normally be started by a signal from switch upon loss of fire water ring main beyond capacity of the jockey pump to recover.

b)

c)

pump shall have its own dedicated driver. Each driver shall have its own controller. shall to provide the required power to operate at rated and maximum pump load under any flow condition i.e. up to 1 rated flow.

d) Automatic with rated (25.4 mm)

shall have a minimum size of 0.75" (19 mm) for pumps capacity not exceeding 9,463.5 [2500 USGPM] and 1" IImin [5000 USGPM] as per NFPA 20. provided for Main(s), Standby Fire Water pump(s) & Panel in Facility's control

e)

icated Pumps and room.

f)

Serial communication panel to DCS for monitoring

g) Should "Main ce>f""nnrH:: then the

h)

i)

pump of the

from the local fire water pump PLC running" not received back within thirty Pump(s)" shall be operated.

arrangements including provision of supplied complete with & indications to

shall comply with NFPA 20 and mounted PLC panel. Each pump own local controller which shall have in Facility's control room.

Fire water system shall be in Auto Mode and continuous alarm (non-reset type) shall be displayed I sounded in control room when anyone or more fire pumps are kept in OFF! Manual Mode.

j) Siren and Beacon shall be provided in pump alarm I shutdown in the pump control panel.

(NOTE:

PLC Panel shall be provided requirement and approved by KOC.)

in

to alert if there is any to

project

specific

Page 24 of 66

KOC-L-009 10

Pump Suction and Discharge Piping

REV.5

151

a) The suction shall be adequately operating simultaneously at 150 percent of rated b) Outside screw I approved) shall

and yoke (OS&Y) valve (UL listed and I or FM installed in the suction pipe and II be approved by KOC.

c) If a single suction pipe supplies to multiple pumps, pumps shall be so that each pump shall d)

so as to cater all pump(s)

For pump(s) taking be installed at the

suction pipe layout at proportional supply. breaker shall

from a stored water of the tank to the

Firewater pump(s) suction provided with an to clean inlet strainer (Bucket type) with a pressure indication. If individual pump inlet strainers are maintain, then each pump discharge line shall equipped with a flushing Facility. Each pump discharge line shall fitted with a check valve, gauge and indicating isolation valve. f)

firewater pump including jockey pumps have independent connection to discharge manifold. The common manifold shall connected to the firewater ring main of the Facility by two (connections), each of the same size as the ring main indicating block valve. All the isolation valves in

pump house shall

h)

No regulating as permitted in this KOC

shall be installed in the d and NFPA.

i)

(8) way 2%" male instantaneous coupling fire brigade in with gate type isolation valve shall be provided in the discharge I near the fire pump house. Fire Brigade in shall have clear paved access for fire trucksl heavy vehicles to feed water to the fire water network.

j)

tapered reducer or suction pipe and pump suction

pipe except

shall be installed

con

valves shall return line fitted with flow meter back to firewater storage

Underground Fire Mains and Post Indicator Isolation Valves

151

a) The firewater ring main shall be typically underground piping nd as well as '"''''''"''.... the maximum anticipated 150% of the fire water pump(s) rated rge capacity. b)

pump

II be made to test each pump individually; the

k)

7.2.11

type.

Fire

UI

to deliver the required flow piping network shall point from the fire water pumps at a at the psi(g) [10.3 bar(g)].

Page 25 of 66

KOC-L-009

c) The entire network piping (140% of rated pressure) of shall be rated for minimum of

REV.5

the Shut off head pumps. Piping components

d) The pipe size of the fire water ring lated based on design the take-off points of flow rates at 10.3 bar(g) [150 psi(g)J appropriate section even if one of supply sides been blocked or is out of operation. However, the fire ring mains shall not be less than 12 diameter. main shall not exceed 3.5 mls at maximum e) The velocity of fire water in the anticipated fire water demand or discha capacity of the fire pumps, 150% of such demand. whichever is higher, and 6 mls

f)

No firewater mains piping shall terminate as a dead end. The mains of the distribution piping network II laid out in closed loops with dual supply. no more than four (4) nos. fire protection devices. branch line shall constitute no more than 50% any single piece of process equipment. be of 6 inch diameter.

g)

minimum h) Piping and fittings this standard. epoxy-lined carbon for Internal Coating extruded HOPE in designed considering firewater pumps,

system shall comply with 'Appendix 5' of ring mains shall be laid with phenolic piping in accordance KOC-P-005 "KOC and externally coated with three shall nce with KOC-P-004 Part severe stress during start-up and shutdown etc. system, hose streams, and hydra rO\A,/'=lYl:>r

i)

and it hydraulics shall be using KOC Fire water network approved for simulation of the hydraulic model. Simulation

carried out for various scenarios as specified in the project documents.

j)

state modeling shall also be carried for the network, to of surge pressures or water hammer that can occur due to Fire water pumps or rapid closing of any valves. If such is identified, contractor shall provide suitable surge arrester to control the surge pressure I water hammer.

k)

analyzed with computer program for maximum stress include co-incidental due to start up and shutdown of fire deluge valves, hydrants

pumps, I)

for underground ring mains shall be provided to reo underground piping of ring installed at turning, change of elevations, branch movement of underground ring mains, unless determine the exact location of the thrust blocks

ground piping of fire pipes I joints under blocks shall be to restrict the analysis is carried out to

KOC-L-009

Page 26 of 66

REV.5

m) Firewater mains shall not be installed passing under buildings, pipe racks and heavy structures. No new structures shall be made over fire water ring mains. n) Clearance requirements of underground buried pipelines used in fire water services shall be as per KOC Standard KOC-L-002. Wherever heavy maintenance crane movement is envisaged, pipes shall be encased with concrete. 0) Where firewater mains may be extended in the future, valves and blinded flange shall be provided for future connections. p) The firewater mains shall be provided with full bore valve flushing connections at the most remote ends, so that all sections can be properly flushed out. The flushing connections shall be sized for a fluid velocity in the relevant piping of not less than 80% of the velocity under normal design conditions, but shall not be less than 2.0 m/s. Flushing connections shall be routed to storm water ditch. q) In addition to the above mentioned dedicated fire water network, the firewater ring mains shall be connected to Facility brackish water network (if available) by providing two normally closed (locked I car seal) indicating isolation valves and non-return valve in such a manner that fire water network is able to draw water from the brackish water network but cannot deliver back to it. r)

Post Indicator type sectioning block valves (gate valve of solid wedge type) as per 'Appendix 6' of this standard shall be utilized to isolate a section of the fire water mains provided at approximately 100 m intervals and on each point of branch line. Post indicator valves shall be set so that the top of the post is approximately 0.9 m above the final grade level. This close spacing, limits the number of hydrants or systems directly affected by any failure and means that emergency operations will be disrupted far less, if an situation arises.

7.3

Deluge Water Spray System

7.3.1

General

151

a) The deluge water spray system shall be provided but not limited to, hydrocarbon vessel(s), hydrocarbon tank(s), suction & discharge scrubber in CRU, gas compressors, separator, desalter, chemical shelter and export feed crude oil pumps based on NFPA 15 and any other systems I equipment where the Calculated Radiation Levels are in excess of 12.5 kW/m2. b) A single Deluge Water Spray System shall not protect more than one fire area. The number of systems expected to operate simultaneously shall be determined by FERA. FERA shall identify / list out all the potential sources of fire and fire areas to be simultaneously cooled and lor extinguished. c) The location(s) of the deluge valve station(s) shall be as detailed in the relevant Project Specific Drawings. The drawings shall show the minimum KOC requirements. Vendor I Contractor shall review the scheme and to comply with this KOC standard and NFPA 13, NFPA 15 & NFPA 16.

KOC-L-009

d)

REV.5

Page 27 of 66

In project specific drawings are not supplied by Vendor I Contractor shall develop the necessary drawings to comply with this KOC NFPA requirements and submit the same to KOC for I

e)

application

i. application rate shall be 10.2 Ipm I m2 [0.25 gpmlW] of 100% tank for fixed tank on 'fire.

area

application shall be 10.2 Ipm I m2 [0.25 gpmltr] of 100% of of tank area for floating roof tank on fire.

f)

standard determined as per 7.3.1 (e) of and 15, whichever is higher.

or as g) 7.3.2

Butterfly va

water spray system.

All deluge valve Appendix 1.1 & 1 associated at a safer decided based on radiation zone. distance preferably upwind or water spray on ipment a) Deluge valves approved deSigned from Nickel-Aluminu suitable for brackish

arranged in accordance with valve assemblies and their shall be installed and air protected The location shall be it shall be at least 30.0 meter to prevailing wind direction of

I

diaphragm type with UL listed and I or FM protection system. It shall be made bod and internals of non-ferrous

b) Filter shall be of a bucket type n, with a insert. Each filter shall have a minimum capacity of 800% of nominal inlet piping diameter. The filter openings shall maximum 50% ray nozzle orifice opening or 4 mm diameter whichever is c) Hydraulic calculations shall

conducted as system to determine that required

nozzle. The minimum operating pressure

be as per NFPA 13 and NFPA 1

d) Rated pressure of the equipment shall not shut-off pressure. e) These deluge valve stations shall be provision of radiation shields or other methods

of the design of the piping flow is available at hazard

than the

pump

by the

KOC-L-009

f)

Page 28 of 66 clearance shall be provided for access to inspect, maintain, remove the . Deluge system piping and fitting materials shall conform ix of this standard. positioned to impinge water directly on the areas of spills are likely to spread or accumulate.

g)

source

7.3.3

be held closed by air pressure supplied from instrument air system. Removal of air pressure to the valve shall result in the valve opening. An air vessel shall be provided to instrument air failure to delay or prevent Air shall be designed to ASME Sec. VIII. Div. 1.

7.3.4

Deluge valves removal of instrument air a) By air melting of fusible plug. b)

fully within 40 seconds (as NFPA 1 by operation of any of the following.

on

from fusible plug detection network due to the

transmitter on the release of air pressure from plug

c) Receipt of detectors.

detector or confirmed fire from flame

d) Remote operation a the main fire and gas panel, located in the Facility control room, by a solenoid valve (fail to open) resulting in loss of instrument air supply to the deluge valve. e) Local operation by pressing local push button station at the deluge valve station.

f)

Local operation of a mechanical case of total power failure.

unit at the deluge valve station in

7.3.5

A full size deluge system bypass line complete with a normally CIOlsea indicating manual block valve shall be installed around the valve.

7.3.6

Instrument air system tubing and fitting materials shall

7.7

Fire Brigade Inlet (Suction Collection Head) shall location* and arranged to connect downstream of allow a secondary supply of water to the deluge (*Additional inlets shall be allowed if FERA / Project Specific document) a)

31

as per

connection shall be provided with a normally closed manual block and accessible from outside the bund. The number of in Suction Collection shall be based on flow requirements but not than 4 way inlet (calculated @ 946.35 IImin [250 USGPM] on each way) instantaneous coupling to BS 336 as described in this KOC Standard for collection heads.

Page 29

KOC-L-009

66

REV.S

b) Fire-sensing such as UV I IR flame detection; Linear Heat Sensing System, fusible bulb I plugs system of rated temperature for actuation at 93°C. shall be used to fire in the area that automatically actuates a alarm in field and Control room deluge valve and sounds an audio & & Gas System. shall be connected to c)

7.3.8

All small-bore trim lines, pneumatic and arrangement, fittings, valves, and sundry shall be supplied, mounted on an instrument board, sited locally and readily accessible for all CIO!,ed, the enclosure shall be protected to IP 65 in If 60529. accordance with

system piping shall run across the bund, below ground, before the tank foundations to to the tank connection.

fittings and system rise r

and flow requirements shall be determined by hydraulic calculations in with NFPA 1

7.3.9

7.3.10 The spray shall be provided on roof for fixed roof (cone) tank; and only on the floating roof tank. nozzles and piping on other upper half of tank shell NFPA 15, equipment! area shall be as per this KOC standards NFPA 13, NFPA 16 as applicable. 11

7.3.12

13

.14

distributed using upright / pendent spray sprinkler in arrays of pipe work arranged over tank roof for fixed tank shell for floating roof tank. Such water distribution arrangement shall 1.1 & 1.2 of KOC Standard. two (2) as shown in the Append At the rim, beyond the roof and shell, a deflector shell on flowing the roof, back onto per 'Appendix 1 of this KOC Spray marine shaped Insulating provide a potential safe type,

installed to tanks as rundown

installed tanks or split into

water, as

(medium I high as per NFPA 15) shall be constructed with a corrosion-proof protective coating, and produce adjustable conepattern with uniform characteristics. "'I..." ..'''''''''

gaskets and / or kits shall be supplied, wherever necessary, at junctions dissimilar having an electromotive greater than 0.05 Valve station block valves shall be to BS EN 12266,

15 The drainage arrangement shall made around the equipment / area protected by deluge system to avoid any accumulation of water around it. NOTE:

Water Mist System: If the Specific specifies specialized areas / equipment, accordance with 750.

of FERA and / or the Project mist system required for be designed and installed in

KOC-L-009 7.4

Page 30 of66

Foam Systems for Crude Storage Tanks

REV.5

151

purpose of firefighting foam systems is to hydrocarbon pool to control flammable vapors (blanketing) between fuel and to extinguish fire. for Floating

7.4.1

onto a liquid as a barrier

Crude Storage

Foam for Floating Roof Crude Storage Tanks shall consist of a foam pump house, proportioning unit, foam pourer I foam maker, foam collecting box and associated piping, fittings etc. a)

installed at a from the protected area, able to foam solution to desired foam application system (2) minutes of activation. Radiation heat flux calculation shall be location. to determine the

b)

system for floating roof hydrocarbon (crude) storage be as per this standard and NFPA 11. positive d with engine driver, together with for firefighting service, complete with all be supplied completely assembled, mounted on a common skid.

shall c) The engine shall be in accordance with this KOC Standard, shall be in all conform to KOC-ME-009 and NFPA 20. The respects as drive for the pump for which it is intended. The and controller shall be specifically listed for fire by a testing I certifying agency as UL and I or FM. of the equipment shall be more than the fire water pump shut-off foam concentrate pump rated pressure as the case may be. d)

Skid mounted diesel-driven foam liquid pump un i.

The unit shall consist of Two (2) nos. concentrate-positive for displacement pumps I rotary or screw type, with relief valve, su handling Fluoroprotein Each pump shall have the following



jj

and piping assembly:

Capacity (Minimum' 12 Ipm [60 USGPM].

.78 Ipm [15 U

PM] & Maximum:

psi (g).

"

Rated Discharge



of diesel k shall be sufficient to supply d minimum Six (6) hours for both pump operating simultaneously.

for

The pumps shall be supplied complete with suction discharge piping, isolating valves, flushing connections, suction and discharge gauges, instrumentation, drain and pressure regulating

KOC-L-009

Page 31 of 66

REV.5

valve with manual by-pass connection, check valves, suction strainer, return line & connections, etc., piped up to the foam tank on the suction and up to the common discharge on the outlet.

e)

iii.

The foam concentrate supply valve(s) in foam pump house shall be suitable for automatic remote operation as well as local manual operation. These foam concentrate isolating valves shall be gate I ball type with SS body and SS trim. The piping material shall be API 5L, Grade B.

IV.

There shall be one minimum (1) Main and one (1) standby foam concentrate pump and one (1) foam concentrate tank. However, the pumps shall be suitable for parallel operation in emergency for quick charging of foam concentrate in ring mains.

v.

The pumps shall also be suitable for handling brackish water for the purpose of flushing the system after use.

vi.

Foam pump house piping with foam concentrate system network drawings, operation and maintenance instruction shall be displayed at foam pump house. Such instruction, layout shall be minimum AO size metallic I plastic sheet printed in distinguishable colours, duly laminated, framed and fixed on wall of foam pump house.

Foam Concentrate Storage Tank: i.

The Fluoroprotein Foam concentrate tank shall be horizontal, atmosphere pressure type of minimum 2000 US gallons (7570.82 liters) capacity or based on largest credible fire scenario whichever is higher. It shall be of welded carbon steel construction, generally as per KOC Specification 015-CH-1 002 "Light Duty Drums" and comply with relevant NFPA Standard and shall be subject to KOC approval.

ii.

The internal surface of the foam tanks shall be lined with phenolic epoxy lining as per KOC-P-002 Pt. 2 "KOC Standard for Internal Lining of Steel Tanks and Vessels: Part 2 - Internal Lining of Above Ground Steel Tanks" and the external painting system of the foam tank shall be according to KOC-P-001 "KOC Standard for Painting and Coating of External Metal Surfaces".

iii.

Filling I Discharge Facilities: • For bulk supply filling, a 2Y2 inch nominal diameter suction hose connection shall be provided to fill the tank by use of foam pump. • A drum unloading Facility shall be provided comprising of a collecting pit (nominal size 1.0 m 3 fabricated from GRP) and a drum unloading rack capable of handling three (3) Nos. drums of 200 liters [52.5 USG] capacity at a time. A removable cover shall also be provided to avoid dirt entering into the pit. The drum unloading shall have sufficient space to maneuver drum by use of forklift.

KOC-L-009

III

f)

I

Page 32 of 66

REV.5

I

In-line Balanced Pressure Foam Proportioning Unit: i.

The unit shall consist of one Ratio Controller suitable for a foam solution flow range of minimum 946.35 Ipm [250 USGPM] to a maximum 4,807.5 Ipm [1270 USGPM]. The unit shall be of stainless steel super duplex grade as minimum, suitable for Fluoroprotein Foam and brackish I sea water complete with the items as listed below: •

3% integral foam concentrate liquid metering device for use with foam concentrate and brackish water (occasionally sea water)



Water inlet and foam-water discharge connections flanged



Threaded foam concentrate inlet connection



One diaphragm control valve with manual bypass Facility



Pressure gauges for water and foam solution lines



Ball valves manually operated for foam concentrate and foam-water solution lines



One Duplex pressure gauge & Check valves and



One additional connection with check valve for emergency foam concentrates injection.

7.4.2

ii.

All the above mentioned items shall be subjected to approval by KOC prior to their supply.

III.

The unit shall be enclosed in a dust I water resistant double sealed doors cabinet and shall be complete with interconnecting foam liquid piping, check valves, other valves, fittings and sensing lines for brackishl sea water and foam solution.

g)

Foam pourer unit and foam maker unit suitable for mounting on the floating roof tank complete with Orifice Plate I Nozzle, Strainer, Deflector, Splash Board of bolted connection for mounting on existing tanks with dimensions as per NFPA 11. The number and capacity shall be based on actual calculations. Foam pourer should be UL listed I FM approved.

h)

In addition to the fixed foam system, a four-way 2~ inch instantaneous male coupling collecting head or breeching inlet shall be installed to introduce foam solution from the fire engine into the lines to the tank foam pourers. It shall be according to BS 336. Foam solution collecting heads shall be installed inside steel cabinets, upwind outside the bund wall of the crude tanks in a safe heat radiation zone.

Foam System for Fixed Roof (Cone) Storage Tanks. Combustible liquid storage tanks):

(Crude,

Flammable I

Basic fire protection for storage tank(s) shall be provided as stated below: a)

Fixed Roof Storage tanks up to 9 m diameter, Foam Hand Hose lines shall be provided.

KOC-L-009

REV.S

Page 33 of 66

b) Fixed Roof Storage tanks above 9 m Monitors shall be provided at liquid surface area for 65 minutes duration. c) Fixed Roof Storage tanks with semi-fixed foam system at following requirements:­

18 m diameter, Fixed Foam Ipm 1m2 [0.16 gpm/ft.2] for tank

more than 18 m provided with of 4.1 Ipm 1m2 [0.1 gpm/ft.2] with the

i.

A four-way 2'Y:z inch male coupling collecting or breeching inlet to provided to introduce foam solution from the fire engine into foam system. It shall be arranged in accordance with Appendix 1.3 of this Standard. Foam system piping and fitting materials shall conform to Appendix 5 of this KOC Standard.

II.

Foam collecting shall be installed inside steel cabinets, preferably upwind or perpendicular to prevailing wind direction outside the bund wall of the crude oil . The installed cabinets shall protected by the provision of company approved concrete or shields. Foam collecting head boxes shall installed in a they are accessible by fire trucks with use of maximum one length m fire hose.

III.

Foam fittings and on"'lorn system and NFPA 11.

run across the bund, belowground, using the tank foundations to connect to the provided in accordance with this KOC

iv.

shall be based on hydraulic

not less than 4" diameter for the wet I dry I dual

tanks and diameter for test tanks. The Vendor I

verify and provide adequate system

with this standards and NFPA 11.

design in

v.

wet I dry I dual Crude storage tank and liquid tanks shall have minimum in the below Table 1 :

I Combustible with foam chamber as

Table 1: Number of Foam Discharge Outlet(s) !lIn'lit:lTt:U'

(or Equivalent Area)

Minimum number of Discharge Outlet

m

4

36 to 42 m

6

number of foam than 42 m) shall be decided and approved requirement.

diameter tanks (more Group as per project

III

KOC-L-009

I

Page 34 of 66

I

REV.S

Notes:

y The minimum requirement as mentioned in Table 1 is based on the location I access constraint during emergency.

y The capacity of foam chamber shall be selected in such a manner that 50% of installed foam chamber (2 out of 4) shall meet rated foam discharge of foam system for the tank protected.

y Test Tanks, irrespective of its diameter, shall have Two (2) foam system risers and foam chamber arrangement. vi.

Generally, the foam system piping arrangements shall be as detailed in Appendix 1.4 of this KOC Standard and rated pressure of the equipment shall be minimum 16 bar.

vii.

Foam chamber selection shall be such that it can be inspected I tested without removing from the tanks and discharging foam outside the tank.

viii.

Vertical foam chamber shall be mounted on tank nozzle. Isolation valves shall not be installed inside the tank dike area at upstream or downstream of foam chamber.

ix.

The Vapor seal of the foam pourer shall be strong enough to sustain tank internal pressure and vibrations but weak enough to be broken by residual foam solution pressure inside the foam chamber at the time of use.

x.

Foam collection heads box shall be of gunmetal-bronze body having minimum four (4) inlets and one (1) outlet.

Xl.

The inlets of foam collection head box shall be gunmetal 212 inch diameter male instantaneous couplings to BS 336 and shall be furnished with spring operated non-return mechanisms and brass caps.

xii.

Each manifold shall be complete with a piping adaptor, one end beveled, the other threaded male to BS 336 round threads.

xiii.

The steel box for the foam inlet shall conform generally to BS 5041, Part 5, except the following: • The glass door shall be replaced by a steel panel • Robust latch shall be provided instead of the lock and key

xiv.

The units shall be installed with center line of minimum 750 mm and a maximum of 1250 mm above grade.

xv.

A valve drain line shall be provided at the system low point. The drain line shall be routed to a drainage pit built by the Vendor I Contractor.

XVI.

Arrangement shall be made for quick flushing of the piping I foam system after use I periodical testing by connecting fire hose.

KOC-l-009 xvii.

Page 35 of 66

Platform with access shall be provided to carryout inspection / maintenance and performance testing foam chamber.

7.5

7

1

151

Fire hydrants shall conform to the following: a) Fire hydrants shall be in accordance with details shown in Appendix 2 of this suction riser piping and 'fittings Standard. Materials for fire hydrant and fire shall conform to Appendix 5 this Standard. b)

Hydrant assemblies shall designed for maximum network pressure to code based on hydraulic calculation and shall be hydrostatically ASME hydrants shall subject to a pressure of up 16 bar (g) (232 psi (g)) under no or low-flow conditions. rated pressure the equipment shall more than the water pump shut-off pressure.

c) The of fire hydrant shall be the same around all the Facility. It shall be fabricated from pipe and standard fittings, having a Six (6) inch diameter barrel with dual-valve two and half (2%) inch diameter instantaneous female couplings according to BS 336. d) Hyd shall "Wet" barrel, valve types connected through extension a flanged-T connection on the buried firewater ring main. e) Hydrant post inlet valve shall be a ball valve with a inlet and outlet.

to

(6) inch diameter flanged

f) All

hydrant valves shall fire rated, diaphragms type suitable for brackish water on-shore application. The diaphragm shall made of Viton or Teflon material or equivalent.

g) A suitable arrangement shall be incorporated to drain 7.2

hydrant barrel.

The locations and spacing of fire hydrants shall be as follows: a)

The location of the hydrants shall Drawings. drawings shall show

as detailed in the relevant minimum KOC requirements.

Specific

b) The Vendor / Contractor shall review the scheme, and if necessary, modify the system to fully comply with this standard. In the event no drawings are supplied by KOC, the Vendor / Contractor shall develop the necessary drawings and submit them to KOC for approval. c)

Hydrants shall provided at a minimum spacing of Thirty (30) m for Gathering Booster Stations, Tank Farms, SWTP & Manifolds spacing for other areas shall determined as per fire risk assessment in consultation with KOC Controlling and Group. Isolation valves shall be provided at each Hundred (100) m.

d) Hydrants shall be readily from roads and located in such a way that possible damage by traffic shall minimized. They shall be provided with crash location shall not be within Two (2) m from curb of the road and at least Ten (10) m from road crossings, sharp road curves, buildings or other structure as pipe rack etc. processing unitsl areas protected, the distance to the nearest hydrant shall not exceed Thirty (30) m. Each hydrant shall be provided with a hard paved grade. 7.5.3

The

engine suction risers shall

provided in compliance with the following:

Fire engine suction riser shall generally in Appendix-3 of this Standard.

in accordance with the details shown

b) The engine suction riser shall be protected by "Crash Barriers" painted in black and yellow. In the event that no drawing is supplied by KOC, the Vendor I Contractor shall develop and submit the necessary drawings for KOC approval. c)

two nos. inches threaded valve outlets of the suction riser shall be suitable for use with rigid suction hose.

d) During detailed design, the Vendor I Contractor shall investigate the operational of alternative hydrant designs and their spacing with particular emphasis on the provision of 6" Storz connections at strategic locations around Facility to protected. e)

water ring mains around crude storage tanks shall have combined hydrant cum fire engine suction riser at every Sixty (60) m instead of fire hydrant as (c) of this Standard. Such arrangements shall be specified in Clause 7. by trucks. of such combination post having hydrants & suction minimum 12". Such larger diameter connection shall have 6" storz shall couplings with end

f) Twelve (12) inch

Engine Suction shall be provided near to fire pump house directly connected fire water storage tank. Such arrangement shall have coupling with end caps 336. Two (2) nos. 5%" round threads

7.6

151

The dry I wet riser having hydrant valve at landing point above ground shall be provided for upper floor process units and plant buildings. a) The size of shall depend on the number for automatic air arrangement shall be

hydrants upper floors. The at the top end of the pipe.

b) 4 way 2W' male instantaneous fire brigade inlet as Appendix 1.3 shall be provided at ground floor at unobstructed location accessible by fire trucks for dry I wet risers. Rated pressure of the equipment shall pressure.

more than the fire water pump shut-off

Page 37 of 66

KOC-L-009 d)

Air vents shall be provided for releasing from provided to control at different floors.

REV.5 and orifice plates shall

Hose shall as per KFSD Regulations / British standards with 2 nos. synthetic rubber fire hoses to 6391 Type 3 shall provided at landing floors. 7.7

Fire Fighting Equipment Boxes for Facilities

7.7.1

General

I5I

a) Fire Fighting equipment boxes shall be provided in compliance with the relevant Project document and Layout Drawings at strategic locations of the facilities. If KOC has not supplied any drawings, the Vendor / Contractor shall develop and submit layout drawings KOC approval. b) As a general guideline each Fire Fighting Boxes shall cover maximum Eight (8) Nos. of hydrant posts (16 nos. single hydrant outlets). They shall be installed at easily approachable, safe area away from process equipment.

7.7.2

Fire Fighting equipment DO)
View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF