CONSORTIUM
RELAY SETTING CALCULATION FOR OVERCURRENT AND VOLTAGE OPERATED RELAYS OF LBDS-9
Subject. Project
Relay Setting Calculation – Doc. No. ISP/AREVA-EMC-A/IX/22/16/29/DE/1007J LBDS Package – 22 - New Stream 2.5 MT Expansions at IISCO Steel Plant Page- 1
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
A. Setting of Relays For 33 KV I/C 1.0 BASIC DATA a
System voltage in kV
33
b
Selected CT Ratio =
800/1
A
d
In = Rated current in amps corresponding to CT ratio of 800/1A =
800
A
e
Minimum symmetrical 3-Ph S/C current in amps at 33 KV bus =
11650
A
g
Total load on 33kV bus =
34000
KVA
h
Load current =
594.86
A
f.
Relay used
g.
Setting ranges :
MICOM P127 steps
I>
0.1-25In
@ 0.01 In
I>>
0.5-40In
@ 0.01 In
I>>>
0.5-40In
@ 0.01 In
TMS =
0.025-1.5
@ 0.025
Definite time setting =
0-150 sec
@ 0.01 sec
2.0 SETTING VALUES 2.1 Proposed Is (IDMT) setting for O/C (51) a.
Curve used for Is (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
b.
Plug setting (PS) proposed =
c.
Is = Current in amps corresponding to PS = PS*In
d.
Proposed TMS setting =
IEC SI
Standard Inverse
1 800 0.550
2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a.
Minimum Isc setting proposed in multiples M of In
1.75
b.
Isc Current in amps corresponding to Isc setting = M*In
1400
c.
Proposed DT time in sec =
1.55
2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a.
Minimum Isc setting proposed in multiples (M) of In
4.5
b.
Isc Current in amps corresponding to Isc setting = M*In
3600
c.
Proposed DT time in sec =
0.65
2.4 Time of Operation for Different Fault Current Current in Amps
Multiples of Set Current
Equivalent MVA
Time of Operation in sec.
Zone of Operation
16000
20
914.52
0.65
DT zone
3600
4.5
205.77
0.65
I>>>
3600
4.5
205.77
1.55
3600
4.5
205.77
1.55
Consultant : SATCON
DT zone
Page 2 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 1400
1.75
80.02
1.55
I>>
1400
1.75
80.02
6.84
11650
14.5625
665.89
1.40
8000
10
457.26
1.63
4800
6
274.36
2.11
3200
4
182.90
2.74
1600
2
91.45
5.52
1520
1.9
86.88
5.96
IDMT zone
1440
1.8
82.31
6.51
I>
1400
1.75
80.02
6.84
1360
1.7
77.73
7.22
1280
1.6
73.16
8.15
1200
1.5
68.59
9.46
1120
1.4
64.02
11.40
1040
1.3
59.44
14.64
960
1.2
54.87
21.08
880
1.1
50.30
40.36
2.5 Undervoltage protection (27) a.
V< in volts = 0.4*Vn (I/C brkr trip)
44
b.
DT setting in sec =
2.5
c.
V in volts = 1.1*Vn (For annunciation)
b.
DT setting in sec =
121 1
B. Settings of Relays for 33 KV Bus PT 1
RELAY TYPE
1.1 Rated PT secondary voltage (Vn)
MICOM P922 110
1.2 Undervoltage protection (27) a.
V< in volts = 0.4*Vn (I/C and B/C brkr closing circuit interlock)
44
b.
DT setting in sec =
2.5
c.
V> in volts = 1.1*Vn (For annunciation)
b.
DT setting in sec =
Consultant : SATCON
121 1
Page 3 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
1.4 Residual overvoltage/neutral displacement protection (60) a.
V0> in volts = 0.06*Vn (For Alarm)
6.6
b.
DT setting in sec =
0.05
c.
V0>> in volts = 0.2*Vn (for tripping of respective I/C)
20
d.
DT setting in sec =
0.1
C. Settings of Relays For 33 KV Bus Coupler 1.0 BASIC DATA a.
System voltage in kV
33
b.
Selected CT Ratio =
400/ 1A
c.
In = Rated current in amps corresponding to CT ratio of 1500/1A =
d.
Minimum symmetrical 3-Ph S/C current in amps at 11 KV bus =
e.
Relay used
f.
Setting ranges :
400
A
11650
A
MICOM P132
IDMT
0.1-4In
I> DT
0.1-40In
I>> DT
0.1-40In
I>>> DT
0.1-40In
TMS = Definite time setting =
0.05-10 0-100 sec
2.0 SETTING VALUES 2.1 Proposed IDMT setting for O/C (51), a.
Curve used for IDMT setting : t = TMS[0.14/{(I/Is)^0.02-1}]
b.
Plug setting (PS) proposed =
c.
I>1 = Current in amps corresponding to PS = PS*In
d.
Proposed TMS setting =
IEC SI
Standard inverse
1.5 600 0.475
2.2 Proposed I> (DT) setting for O/C (50-1) a.
Minimum Isc setting proposed in multiples M of In
b.
Isc Current in amps corresponding to Isc setting = M*In
1200
c.
Proposed DT time in sec =
1.25
3
2.3 Proposed I>> (DT) setting for O/C (50-2) a.
Minimum Isc setting proposed in multiples M of In
8.25
b.
Isc Current in amps corresponding to Isc setting = M*In
3300
c.
Proposed DT time in sec =
0.35
2.4 Proposed I>>> (DT) setting for O/C (50-3) a.
Not used
Minimum Isc setting proposed in multiples (M) of In
Consultant : SATCON
Page 4 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J b.
Isc Current in amps corresponding to Isc setting = M*In
c.
Proposed DT time in sec =
2.5 Time of Operation for Different Fault Current Current in Amps
Multiples of Set Current
Equivalent MVA
Time of Operation in sec.
Zone of Operation
8000
20
457.26
0.35
DT zone
3300
8.25
188.62
0.35
I>>
3300
8.25
188.62
1.25
DT zone
1200
3
68.59
1.25
I>
1200
3
68.59
4.76
11650
19.417
665.88
1.09
6000
10
342.95
1.41
3000
5
171.47
2.03
1800
3
102.88
2.99
1200
2
68.59
4.76
1140
1.9
65.16
5.15
1080
1.8
61.73
5.62
1020
1.7
58.30
6.23
960
1.6
54.87
7.04
900
1.5
51.44
8.17
840
1.4
48.01
9.85
780
1.3
44.58
12.64
720
1.2
41.15
18.20
660
1.1
37.72
34.85
IDMT zone
2.6 25 Check Synchronisation o
a.
Phase angle setting
b.
Vdiff setting in volts
15 5.5
5%
c.
Slip frequency setting in Hz
0.1
d.
Dead Bus Charging Voltage setting in volts
20
> 20%
e.
Live Bus Voltage setting in volts
32
> 30%
D. Settings of Relays For 33 KV Transformer Feeder 1.0 BASIC DATA a.
System voltage
b.
Selected CT Ratio =
33
kV
600/1
A
c.
In = Rated current in amps corresponding to CT ratio of 250/1A =
600
A
d.
Minimum symmetrical 3-Ph S/C current in amps at 33 KV bus =
11650
A
e.
Reflected current on 33 KV side due to fault at 6.6kV side of trafo and minimum fault level condition =
2256
A
f.
Rated primary current in amps of 31.5 MVA Transformer =
551
A
Consultant : SATCON
Page 5 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
g.
Relay used
h.
Setting ranges :
MICOM P122 steps
I>
0.1-25In
@ 0.01 In
I>>
0.5-40In
@ 0.01 In
I>>>
0.5-40In
@ 0.01 In
TMS =
0.025-1.5
@ 0.025
Definite time setting =
0-150 sec
@ 0.01 sec
2.0 SETTING VALUES 2.1 Proposed Is (IDMT) setting for O/C (51), I> a.
Curve used for Is (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
b.
Plug setting (PS) proposed =
c.
Is = Current in amps corresponding to PS = PS*In
d.
Proposed TMS setting =
IEC SI
Standard inverse
1 600 0.325
2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a.
Minimum Isc setting proposed in multiples M of In
1.5
b.
Isc Current in amps corresponding to Isc setting = M*In
900
c.
Proposed DT time in sec =
0.95
2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a.
Minimum Isc setting proposed in multiples (M) of In
5
b.
Isc Current in amps corresponding to Isc setting = M*In
3000
c.
Proposed DT time in sec =
0.05
2.4 Time of Operation for Different Fault Current Current in Amps
Multiples of Set Current
Equivalent MVA
Time of Operation in sec.
Zone of Operation
12000
20
685.89
0.05
DT Zone
3000
5
171.47
0.05
(I>>>)
3000
5
171.47
0.95
3000
5
171.47
0.95
DT Zone
900
1.5
51.44
0.95
(I>>)
900
1.5
51.44
5.59
11650
19.42
665.89
0.74
6000
10.00
342.95
0.97
4200
7.00
240.06
1.15
3000
5.00
171.47
1.39
2256
3.76
128.95
1.70
Consultant : SATCON
Page 6 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 1200
2.00
68.59
3.26
IDMT zone
1140
1.9
65.16
3.52
I>
1080
1.8
61.73
3.85
1020
1.7
58.30
4.26
960
1.6
54.87
4.82
900
1.5
51.44
5.59
840
1.4
48.01
6.74
780
1.3
44.58
8.65
720
1.2
41.15
12.46
660
1.1
37.72
23.85
E. Settings of Relays for 6.6 KV I/C From 25/31.5 MVA Trafo 1.0 BASIC DATA a.
System voltage
6.6
kV
b.
Selected CT Ratio =
3000/1
A
c.
In = Rated current in amps corresponding to CT ratio of 250/1A =
3000
A
d.
Minimum symmetrical 3-Ph S/C current in amps at 6.6 KV bus =
11280
A
e.
Reflected current on 33 KV side due to fault on 6.6kV side of trafo and minimum fault level condition =
2256
A
f.
Rated primary current (at 6.6kV) in amps of 31.5 MVA Transformer =
2756
A
g.
Relay used
h.
Setting ranges for overcurrent relays :
MICOM P632
I> (IDMT)
0.1-4 In
I>> (DT-1)
0.1-30 In
I>>> (DT-2)
0.1-30 In
TMS =
0.05 - 10
Definite time setting =
0-100 sec
2.0 SETTING VALUES 2.1 Proposed IDMT setting for O/C (51), a.
Curve used for IDMT setting : t = TMS[0.14/{(I/Is)^0.02-1}]
IEC SI
b. c.
Plug setting (PS) proposed = I>1 = Current in amps corresponding to PS = PS*In
0.9 2700
d.
Proposed TMS setting =
0.275
Standard inverse
2.2 Proposed I> (DT) setting for O/C (50-1) a.
Minimum Isc setting proposed in multiples M of In
b. c.
Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
2.3 Proposed I>> (DT) setting for O/C (50-2) a. Minimum Isc setting proposed in multiples M of In b.
1.5 4500 0.65 Not used
Isc Current in amps corresponding to Isc setting = M*In
Consultant : SATCON
Page 7 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J c.
Proposed DT time in sec =
2.4 Time of Operation for Different Fault Current Current in Amps
Multiples of Set Current
Equivalent MVA
Time of Operation in sec.
60000
20
685.89
0.65
Zone of Operation DT zone
4500
1.5
51.44
0.65
I>>
4500
1.5
51.44
3.75
27000
10
308.65
0.82
24300
9
277.79
0.86
18900
7
216.06
0.97
10800
4
123.46
1.37
11280
4.1777
128.95
1.33
8100
3
92.60
1.73
5400
2
61.73
2.76
5130
1.9
58.64
2.98
IDMT zone
4860
1.8
55.56
3.26
I>
4590
1.7
52.47
3.61
4500
1.6666
51.44
3.75
4320
1.6
49.38
4.08
4050
1.5
46.30
4.73
3780
1.4
43.21
5.70
3510
1.3
40.12
7.32
3240
1.2
37.04
10.54
2970
1.1
33.95
20.18
2.5 Undervoltage protection (27) a.
V< in volts = 0.4*Vn (I/C brkr trip)
44
b.
DT setting in sec =
2.5
c.
V in volts = 1.1*Vn (For annunciation)
b.
DT setting in sec =
121 1
2.7 Transformer Differential Protection (87T)
Available range
a.
m1
0.3
0.2-0.5
b.
m2
0.8
0.4-1.5
c.
I ref = Trafo full load current in amps on 31.5 MVA base (FLC)
d.
Idiff> in amps = 0.2 x I ref
551
e.
Idiff>> in amps = 10 x I ref
27556
5-30 x I ref
f.
Idiff>>> in amps = 20 x I ref
55112
5-30 x I ref
Consultant : SATCON
2756 0.1-2.5 x I ref
Page 8 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J g.
IRm2 in amps = 4 x I ref
h.
Rush I in amps = 0.2 x I ref
11022
1.5-10 x I ref
551
0.1-0.5 x I ref
F. Settings of Relays for 6.6 KV Bus Coupler 1.0 BASIC DATA a. System voltage in kV
6.6
b.
Selected CT Ratio =
c.
In = Rated current in amps corresponding to CT ratio of 1500/1A =
1500
A
d.
Minimum symmetrical 3-Ph S/C current in amps at 11 KV bus =
11280
A
e.
Relay used
f.
Setting ranges :
1500/ 1A
MICOM P132
IDMT
0.1-4In
I> DT
0.1-40In
I>> DT
0.1-40In
I>>> DT
0.1-40In
TMS =
0.05-10
Definite time setting =
0-100 sec
2.0 SETTING VALUES 2.1 a. b. c. d.
Proposed IDMT setting for O/C (51), Curve used for IDMT setting : t = TMS[0.14/{(I/Is)^0.02-1}] Plug setting (PS) proposed = I>1 = Current in amps corresponding to PS = PS*In Proposed TMS setting =
2.2 Proposed I> (DT) setting for O/C (50-1) a. Minimum Isc setting proposed in multiples M of In b.
Isc Current in amps corresponding to Isc setting = M*In
c.
Proposed DT time in sec =
Standard inverse
1.5 2250 1.3
2.3 Proposed I>> (DT) setting for O/C (50-2) a. Minimum Isc setting proposed in multiples M of In b. c.
IEC SI 1 1500 0.275
3
Isc Current in amps corresponding to Isc setting = M*In Proposed DT time in sec =
4500 0.35 Not used
2.4 Proposed I>>> (DT) setting for O/C (50-3) a. Minimum Isc setting proposed in multiples (M) of In b.
Isc Current in amps corresponding to Isc setting = M*In
c.
Proposed DT time in sec =
2.5 Time of Operation for Different Fault Current Current in Amps
Multiples of Set Current
Equivalent MVA
Time of Operation in sec.
30000
20
342.95
0.35
Consultant : SATCON
Zone of Operation DT zone Page 9 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 4500
3
51.44
0.35
I>>
4500
3
51.44
1.30
DT zone
2250
1.5
25.72
1.30
I>
2250
1.5
25.72
4.73
11280
7.520
128.95
0.93
4500
3
51.44
1.73
3750
2.5
42.87
2.08
3000
2
34.29
2.76
2850
1.9
32.58
2.98
2700
1.8
30.87
3.26
2550
1.7
29.15
3.61
2400
1.6
27.44
4.08
2250
1.5
25.72
4.73
2100
1.4
24.01
5.70
1950
1.3
22.29
7.32
1800
1.2
20.58
10.54
1650
1.1
18.86
20.18
IDMT zone
2.6 25 Check Synchronisation a.
Phase angle setting
b.
Vdiff setting in volts
15o 5.5
c.
Slip frequency setting in Hz
0.1
d. e.
Dead Bus Charging Voltage setting in volts Live Bus Voltage setting in volts
20 32
5% > 20% > 30%
G. Settings of Relays for 6.6 KV O/G Fdr to Capacitor bank 1.0 BASIC DATA a System voltage in kV
6.6
b
Selected CT Ratio =
125/1
A
d
In = Rated current in amps corresponding to CT ratio of 125/1A =
125
A
e
Minimum symmetrical 3-Ph S/C current in amps at 6.6 KV bus =
11280
A
g
Capacitor bank rating =
h
Load current =
f.
Relay used
g.
Setting ranges :
250 21.87
KVAR A
MICOM P127 steps
I>
0.1-25In
@ 0.01 In
I>>
0.5-40In
@ 0.01 In
I>>>
0.5-40In
@ 0.01 In
TMS =
0.025-1.5
@ 0.025
Definite time setting =
0-150 sec
@ 0.01 sec
2.0 SETTING VALUES
Consultant : SATCON
Page 10 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 2.1 Proposed Is (IDMT) setting for O/C (51) a. Curve used for Is (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
IEC SI
b.
Plug setting (PS) proposed =
0.225
c.
Is = Current in amps corresponding to PS = PS*In
28.125
d.
Proposed TMS setting =
0.200
2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a. Minimum Isc setting proposed in multiples M of In
4
b.
Isc Current in amps corresponding to Isc setting = M*In
500
c.
Proposed DT time in sec =
0.05 Not used
2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a. Minimum Isc setting proposed in multiples (M) of In b.
Isc Current in amps corresponding to Isc setting = M*In
c.
Proposed DT time in sec =
Standard Inverse
2.4 Time of Operation for Different Fault Current Current in Amps
Multiples of Set Current
Equivalent MVA
Time of Operation in sec.
2500
20
28.58
0.05
Zone of Operation DT zone
500
4
5.72
0.05
I>>
500
4
5.72
0.47
500
17.7777
5.72
0.47
281
10
3.22
0.59
169
6
1.93
0.77
113
4
1.29
1.00
56
2
0.64
2.01
IDMT zone
53
1.9
0.61
2.17
I>
51
1.8
0.58
2.37
48
1.7
0.55
2.62
45
1.6
0.51
2.96
42
1.5
0.48
3.44
39
1.4
0.45
4.15
37
1.3
0.42
5.32
34
1.2
0.39
7.66
31
1.1
0.35
14.67
2.5 Undervoltage protection (27) a. U< in volts = 0.8*Vn (For tripping) b.
DT setting in sec =
88 1.00
2.6 Residual overvoltage/neutral displacement protection (60) a. Ue> in volts = 0.06*Vn (For Alarm)
6.6
b.
0.05
DT setting in sec =
Consultant : SATCON
Bus PT supply =110V
Bus PT supply =110V
Page 11 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J c.
Ue>> in volts = 0.2*Vn (For tripping)
22
d.
DT setting in sec =
0.1
H. Settings of Relays for 6.6 KV O/G Fdr to 1600 KVA Transformer 1.0 BASIC DATA a.
System voltage
b.
Selected CT Ratio =
c.
In = Rated current in amps corresponding to CT ratio of 250/1A =
d. e.
6.6
kV
250/1
A
250
A
Minimum symmetrical 3-Ph S/C current in amps at 6.6 KV bus =
11280
A
2165
A
f.
Reflected current on 6.6 KV side due to fault on 415V side of trafo and minimum fault level condition = Rated primary current in amps of 1600 KVA Transformer =
140
A
g.
Relay used
h.
Setting ranges :
MICOM P122 steps
I>
0.1-25In
@ 0.01 In
I>>
0.5-40In
@ 0.01 In
I>>>
0.5-40In
@ 0.01 In
TMS =
0.025-1.5
@ 0.025
Definite time setting =
0-150 sec
@ 0.01 sec
2.0 SETTING VALUES 2.1 Proposed Is (IDMT) setting for O/C (51), I> a. Curve used for Is (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
IEC SI
b. c.
Plug setting (PS) proposed = Is = Current in amps corresponding to PS = PS*In
0.75 187.5
d.
Proposed TMS setting =
0.375
2.2 Proposed Is (DT) setting for O/C (I>>) (50-1/DT) a. Minimum Isc setting proposed in multiples M of In
0.9
b.
Isc Current in amps corresponding to Isc setting = M*In
225
c.
Proposed DT time in sec =
Standard inverse
1
2.3 Proposed Is (DT) setting for S/C (I>>>) (50-2/DT) a. Minimum Isc setting proposed in multiples (M) of In
11.5
b.
Isc Current in amps corresponding to Isc setting = M*In
2875
c.
Proposed DT time in sec =
0.05
2.4 Time of Operation for Different Fault Current Current in Amps
Multiples of Set Current
Equivalent MVA
Time of Operation in sec.
5000
20
57.16
0.05
Zone of Operation DT Zone
2875
11.5
32.87
0.05
(I>>>)
2875
11.5
32.87
1.00
Consultant : SATCON
Page 12 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 2875
11.5
32.87
1.00
DT Zone
225
0.9
2.57
1.00
(I>>)
225
0.9
2.57
14.37
11280
60.16
128.95
0.61
2165
11.55
24.75
1.05
1688
9.00
19.29
1.17
938
5.00
10.72
1.60
375
2.00
4.29
3.76
356
1.9
4.07
4.06
IDMT zone
338
1.8
3.86
4.44
I>
319
1.7
3.64
4.92
300
1.6
3.43
5.56
281
1.5
3.22
6.45
263
1.4
3.00
7.78
244
1.3
2.79
9.98
225
1.2
2.57
14.37
206
1.1
2.36
27.52
I. Settings of Relays for 6.6 KV Bus PT 1
RELAY TYPE
1.1 Rated PT secondary voltage (Vn)
MICOM P922 110
1.2 Undervoltage protection (27) a. b.
V< in volts = 0.4*Vn (I/C and B/C brkr closing circuit interlock) DT setting in sec =
44 2.5
c.
V in volts = 1.1*Vn (For annunciation and tripping of capacitor feeders)
b.
DT setting in sec =
121 1
1.4 Residual overvoltage/neutral displacement protection (60) a.
V0> in volts = 0.06*Vn (For Alarm)
6.6
b.
DT setting in sec =
0.05
c.
V0>> in volts = 0.2*Vn (for tripping of respective I/C)
20
d.
DT setting in sec =
0.1
J. Settings of Relays for IC & BC at 415V PCC 1.0 BASIC DATA Consultant : SATCON
Page 13 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J a.
System voltage in kV
0.415
kV
b.
Selected CT Ratio =
3000/5
A
c.
Symmetrical S/C current in amps at 415V bus during 3phase fault =
33007
A
d.
In = Rated primary current in amps corresponding to selected CT ratio
3000
A
e.
Relay used
f.
Setting ranges :
SPAJ 140C
(ABB)
I> inverse
0.5 - 2.5 In
I> definite time
0.5 - 5.0 In
I>> definite time
0.5 - 40.0 In and infinity
TMS =
0.05 - 1.0
Definite time setting for I> =
0.05 - 300s
Definite time setting for I>> =
0.04 - 300s
g.
Transformer rating =
h.
Voltage ratio =
6600/433
V
i.
Transformer full load current, HV =
140
A
j.
Transformer full load current, LV =
2133
A
k.
Transformer vector group =
Dyn11
l.
Transformer % impedance =
6.25%
m. Through fault current at LV side =
33007
n.
Through fault current at HV side =
1600
2165.46
kVA
A (From ETAP output) A
2.0 SETTING VALUES 2.1 Proposed I> (IDMT) setting for O/C (51), a.
Curve used for I> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
b.
Plug setting (PS) proposed =
c.
I> = Current in amps corresponding to PS = PS*In
2550
d.
Proposed TMS setting =
0.275
2.2 Proposed I> (DT) setting for O/C (50) a.
Minimum Isc setting proposed in multiples M of In
b.
Isc Current in amps corresponding to Isc setting = M*In
c.
Proposed DT time in sec =
2.3 Proposed I>> (DT) setting for O/C (50) a.
Minimum Isc setting proposed in multiples (M) of In
b.
Isc Current in amps corresponding to Isc setting = M*In
c.
Proposed DT time in sec =
IEC SI
Standard inverse
0.85
1.1 3300 0.7
(Assumed)
Not used
2.4 Time of Operation for Different Fault Current
Consultant : SATCON
Page 14 of 15
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Overcurrent and Voltage operated Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J CURRENT IN AMPS (I)
MULTIPLES OF SET CURRENT (M)
EQUIVALENT TIME OF OPERATIOM MVA (sec)
ZONE OF OPERATION
I = MxIs
M
MVA
sec
60000
20
43.13
0.7
DT Zone
3300
1.1
2.37
0.7
(I>>)
3300
1.1
2.37
7.45
33007
12.9439
23.73
0.73
25500
10
18.33
0.82
22950
9
16.50
0.86
20400
8
14.66
0.91
17850
7
12.83
0.97
15300
6
11.00
1.06
12750
5
9.16
1.18
IDMT Zone
10200
4
7.33
1.37
(I>)
7650
3
5.50
1.73
5100
2
3.67
2.76
4845
1.9
3.48
2.98
4590
1.8
3.30
3.26
4335
1.7
3.12
3.61
4080
1.6
2.93
4.08
3825
1.5
2.75
4.73
3570
1.4
2.57
5.70
3315
1.3
2.38
7.32
3300
1.29411
2.37
7.45
3060
1.2
2.20
10.54
2805
1.1
2.02
20.18
2.5 Undervoltage protection (27) at incomer a. Relay used b.
Available setting =
c.
Time =
d.
Selected setting =
e.
Purpose
VAGM22 40-80
%
Inst. 40
%
Tripping & Annc.
2.6 Overvoltage protection (59) at incomer a.
Relay used
VAGM22
b.
Available setting =
110-140
c.
Time =
Inst.
d.
Selected setting =
110
e.
Purpose
Consultant : SATCON
% %
Tripping
Page 15 of 15
OVERCURRENT COORDINATION CHART FOR LBDS-9
TIME IN SECONDS
10
1
0.1
0.01 1.00
10.00
100.00
MVA
33kV INCOMER
33KV BUS COUPLER
33KV TRAFO FDR
6.6KV BUS COUPLER
6.6KV TRAFO FDR LTPCC
415V PCC INCOMER
1000.00 6.6KV INCOMER
CONSORTIUM
RELAY SETTING CALCULATION FOR EARTH FAULT RELAYS OF LBDS-9
Subject. Project
Relay Setting Calculation – Doc. No. ISP/AREVA-EMC-A/IX/22/16/29/DE/1007J LBDS Package – 22 - New Stream 2.5 MT Expansions at IISCO Steel Plant Page- 1
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J A.
33kV INCOMER
1.0
BASIC DATA
a.
System voltage in kV
33
kV
b.
Selected CT Ratio =
800/1
A
c.
Symmetrical S/C current in amps at 6.6kV bus during SLG fault =
400
A
d.
Rated primary current in amps corresponding to selected CT ratio, In =
800
A
e.
Relay used
f.
Setting ranges :
2.0
MICOM P127
Ie>
0.1 - 1.0 In
Ie>>
0.1 - 8 In
@ 0.005 In (Inverse time) @ 0.005 In (Definite time)
TMS =
0.025 - 1.5
@ 0.025
Definite time setting =
0 - 150 sec
@ 0.01 sec
SETTING VALUES
2.1
Proposed Ie> (IDMT) setting for E/F (51N),
a.
Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
b.
Plug setting (PS) proposed =
0.15
c.
Ie> = Current in amps corresponding to PS = PS*In
120
d.
Proposed TMS setting =
0.15
2.2
Proposed Ie>> (DT) setting for E/F (50N)
IEC SI
a.
Minimum Isc setting proposed in multiples M of In
0.25
b.
Isc Current in amps corresponding to Isc setting = M*In
200
c.
Proposed DT time in sec =
0.7
2.3
Standard inverse
Time of Operation for Different Fault Current CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs
EQUIVALENT MVA
TIME OF OPERATIOM (sec)
ZONE OF OPERATION
M
MVA
sec
16000
20
914.52
0.7
DT Zone
200
0.25
11.43
0.7
(Ie>>)
200
0.25
11.43
2.05
2400
20
137.18
0.34
1800
15
102.88
0.38
1200
10
68.59
0.45
1080
9
61.73
0.47
960
8
54.87
0.49
840
7
48.01
0.53
720
6
41.15
0.58
IDMT Zone
600
5
34.29
0.64
(Ie>)
480
4
27.44
0.75
400
3.3333
22.86
0.86
360
3
20.58
0.95
240
2
13.72
1.50
Consultant : SATCON
Page 2 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 228
1.9
13.03
1.63
216 204
1.8
12.35
1.78
1.7
11.66
1.97
200
1.6666
11.43
2.05
192
1.6
10.97
2.22
180
1.5
10.29
2.58
168
1.4
9.60
3.11
156
1.3
8.92
3.99
144
1.2
8.23
5.75
132
1.1
7.54
11.01
B.
33kV BUS COUPLER
1.0
BASIC DATA
a.
System voltage in kV
33
kV
b.
Selected CT Ratio =
400/1
A
c.
Symmetrical S/C current in amps at 6.6kV bus during SLG fault =
400
A
d.
Rated primary current in amps corresponding to selected CT ratio, In =
400
A
e.
Relay used
f.
Setting ranges :
MICOM P132
Ie>
0.01 - 4.0 In
(Inverse time)
Ie>>
0.002 - 8.0 In
(Definite time)
TMS =
0.05 - 10
Definite time setting =
0 - 100 sec
2.0
SETTING VALUES
2.1
Proposed Ie> (IDMT) setting for E/F (51N),
a.
Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
b.
Plug setting (PS) proposed =
0.2
c.
Ie> = Current in amps corresponding to PS = PS*In
80
d.
Proposed TMS setting =
IEC SI
0.125
2.2
Proposed Ie>> (DT) setting for E/F (50N)
a.
Minimum Isc setting proposed in multiples M of In
0.4
b.
Isc Current in amps corresponding to Isc setting = M*In
160
c.
Proposed DT time in sec =
0.4
2.3
Standard inverse
Time of Operation for Different Fault Current CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs
EQUIVALENT MVA
TIME OF OPERATIOM (sec)
ZONE OF OPERATION
M
MVA
8000
20
457.26
0.4
DT Zone
160
0.4
9.15
0.4
(Ie>>)
160
0.4
9.15
1.25
Consultant : SATCON
sec
Page 3 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
800
10
45.73
0.37
720
9
41.15
0.39
640
8
36.58
0.41
560
7
32.01
0.44
480
6
27.44
0.48
IDMT Zone
400
5
22.86
0.53
(Ie>)
240
3
13.72
0.79
160
2
9.15
1.25
152
1.9
8.69
1.35
144
1.8
8.23
1.48
136
1.7
7.77
1.64
128
1.6
7.32
1.85
120
1.5
6.86
2.15
112
1.4
6.40
2.59
104
1.3
5.94
3.33
96
1.2
5.49
4.79
88
1.1
5.03
9.17
C.
33kV TRANSFORMER FEEDER FOR 25/31.5 MVA TRAFO
1.0
BASIC DATA
a.
System voltage in kV
33
kV
b.
Selected CT Ratio =
600/1
A
c.
Symmetrical S/C current in amps at 6.6kV bus during SLG fault =
400
A
d.
Rated primary current in amps corresponding to selected CT ratio, In =
600
A
e.
Relay used
f.
Setting ranges :
MICOM P122
Ie>
0.1 - 1.0 In
Ie>>
0.1 - 8 In
@ 0.005 In (Inverse time) @ 0.005 In (Definite time)
TMS =
0.025 - 1.5
@ 0.025
Definite time setting =
0 - 150 sec
@ 0.01 sec
2.0
SETTING VALUES
2.1
Proposed Ie> (IDMT) setting for E/F (51N),
a.
Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
b.
Plug setting (PS) proposed =
c.
Ie> = Current in amps corresponding to PS = PS*In
d.
Proposed TMS setting =
2.2
Proposed Ie>> (DT) setting for E/F (50N)
IEC SI 60 0.05
a.
Minimum Isc setting proposed in multiples M of In
0.2
b.
Isc Current in amps corresponding to Isc setting = M*In
120
c.
Proposed DT time in sec =
0.1
2.3
Standard inverse
0.1
Time of Operation for Different Fault Current
Consultant : SATCON
Page 4 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs
EQUIVALENT MVA
TIME OF OPERATIOM (sec)
ZONE OF OPERATION
M
MVA
sec
12000
20
685.89
0.1
DT Zone
120
0.2
6.86
0.1
(Ie>>)
120
0.2
6.86
0.50
1200
20
68.59
0.11
900
15
51.44
0.13
600
10
34.29
0.15
540
9
30.87
0.16
480
8
27.44
0.16
420
7
24.01
0.18
400
6.6666
22.86
0.18
360
6
20.58
0.19
IDMT Zone
300
5
17.15
0.21
(Ie>)
240
4
13.72
0.25
180
3
10.29
0.32
120
2
6.86
0.50
114
1.9
6.52
0.54
108
1.8
6.17
0.59
102
1.7
5.83
0.66
96
1.6
5.49
0.74
90
1.5
5.14
0.86
84
1.4
4.80
1.04
78
1.3
4.46
1.33
72
1.2
4.12
1.92
66
1.1
3.77
3.67
D.
6.6KV INCOMER FROM 25/31.5 MVA TRAFO
1.0
BASIC DATA
a.
System voltage in kV
6.6
kV
b.
Selected CT Ratio =
3000/1
A
c.
Symmetrical S/C current in amps at 415V bus during SLG fault =
600
A
d.
Rated primary current in amps corresponding to selected CT ratio, In =
3000
A
e.
Relay used
f.
Setting ranges :
MICOM P632
Ie>
0.1 - 0.8 In
(Inverse time)
Ie>>
0.1 - 8 In
(Definite time)
TMS =
0.05 - 10
Definite time setting =
0 - 100
2.0
SETTING VALUES
2.1
Proposed Ie> (IDMT) setting for E/F (51N),
Consultant : SATCON
sec
Page 5 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J a.
Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
IEC SI
b.
Plug setting (PS) proposed =
0.1
c.
Ie> = Current in amps corresponding to PS = PS*In
300
d.
Proposed TMS setting =
0.075
2.2
Proposed Ie>> (DT) setting for E/F (50N)
a.
Minimum Isc setting proposed in multiples M of In
0.12
b.
Isc Current in amps corresponding to Isc setting = M*In
360
c.
Proposed DT time in sec =
0.7
2.3
Standard inverse
Time of Operation for Different Fault Current CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs
EQUIVALENT MVA
TIME OF OPERATIOM (sec)
ZONE OF OPERATION
M
MVA
sec
60000
20
685.89
0.7
DT Zone
360
0.12
4.12
0.7
(Ie>>)
360
0.12
4.12
2.87
3000
10
34.29
0.22
2700
9
30.87
0.23
2400
8
27.44
0.25
2100
7
24.01
0.26
1800
6
20.58
0.29
1500
5
17.15
0.32
IDMT Zone
1200
4
13.72
0.37
(Ie>)
900
3
10.29
0.47
600
2
6.86
0.75
570
1.9
6.52
0.81
540
1.8
6.17
0.89
510
1.7
5.83
0.98
480
1.6
5.49
1.11
450
1.5
5.14
1.29
420
1.4
4.80
1.56
390
1.3
4.46
2.00
375
1.25
4.29
2.35
360
1.2
4.12
2.87
330
1.1
3.77
5.50
2.4
REF (64R) [Biasing by residual current] Instantaneous
a.
Idiff> in amps = 0.1*FLC
b.
m=
E.
BACK UP E/F (51G) AT 25/31.5 MVA TRAFO NEUTRAL
1.0
BASIC DATA
a. b.
300 1.005
(fixed slope)
System voltage in kV
0.415
kV
Selected CT Ratio =
600/1
A
Consultant : SATCON
Page 6 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J c.
Symmetrical S/C current in amps at 415V bus during SLG fault =
d.
Rated primary current in amps corresponding to selected CT ratio, In =
e.
Relay used
f.
Setting ranges :
600
Ie>
0.01 - 1.0 In
TMS =
0.025 - 1.2
SETTING VALUES
2.1
Proposed Ie> (IDMT) setting for E/F (51G), Curve used for Ie>1 (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
IEC SI
b
Plug setting (PS) proposed =
0.55
c
Ie> = Current in amps corresponding to PS = PS*In
330
d
Proposed TMS setting =
0.1
2.2
A (Based on ETAP fault calculation) A
MICOM P111
2.0 a
36950
(Inverse time)
Standard inverse
Time of Operation for Different Fault Current CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M)
EQUIVALENT MVA
TIME OF OPERATIOM (sec)
I = MxIs
M
MVA
sec
6600
20
75.45
0.23
4950
15
56.59
0.25
3300
10
37.72
0.30
2970
9
33.95
0.31
2640
8
30.18
0.33
2310
7
26.41
0.35
1980
6
22.63
0.38
ZONE OF OPERATION
1650
5
18.86
0.43
1320
4
15.09
0.50
IDMT Zone
990
3
11.32
0.63
(Ie>)
660
2
7.54
1.00
627
1.9
7.17
1.08
600
1.8181
6.86
1.16
594
1.8
6.79
1.18
561
1.7
6.41
1.31
528
1.6
6.04
1.48
495
1.5
5.66
1.72
462
1.4
5.28
2.07
429
1.3
4.90
2.66
396
1.2
4.53
3.83
363
1.1
4.15
7.34
F.
6.6kV BUS COUPLER
1.0
BASIC DATA
a.
System voltage in kV
Consultant : SATCON
6.6
kV
Page 7 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J b.
Selected CT Ratio =
1500/1
A
c.
Symmetrical S/C current in amps at 6.6kV bus during SLG fault =
600
A
d.
Rated primary current in amps corresponding to selected CT ratio, In =
1500
A
e.
Relay used
f.
Setting ranges :
MICOM P132
Ie>
0.01 - 4.0 In
(Inverse time)
Ie>>
0.002 - 8.0 In
(Definite time)
TMS =
0.05 - 10
Definite time setting =
0 - 100 sec
2.0
SETTING VALUES
2.1
Proposed Ie> (IDMT) setting for E/F (51N),
a.
Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
b.
Plug setting (PS) proposed =
IEC SI 0.09
c.
Ie> = Current in amps corresponding to PS = PS*In
135
d.
Proposed TMS setting =
0.1
2.2
Proposed Ie>> (DT) setting for E/F (50N)
a.
Minimum Isc setting proposed in multiples M of In
0.15
b.
Isc Current in amps corresponding to Isc setting = M*In
225
c.
Proposed DT time in sec =
0.4
2.3
Standard inverse
Time of Operation for Different Fault Current CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs
EQUIVALENT MVA
TIME OF OPERATIOM (sec)
ZONE OF OPERATION
M
MVA
sec
30000
20
342.95
0.4
DT Zone
225
0.15
2.57
0.4
(Ie>>)
225
0.15
2.57
1.36
1350
10
15.43
0.30
1215
9
13.89
0.31
1080
8
12.35
0.33
945
7
10.80
0.35
810
6
9.26
0.38
675
5
7.72
0.43
IDMT Zone
600
4.4444
6.86
0.46
(Ie>)
405
3
4.63
0.63
270
2
3.09
1.00
257
1.9
2.93
1.08
243
1.8
2.78
1.18
225
1.66666
2.57
1.36
216
1.6
2.47
1.48
203
1.5
2.31
1.72
189
1.4
2.16
2.07
Consultant : SATCON
Page 8 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 176
1.3
2.01
2.66
162 149
1.2
1.85
3.83
1.1
1.70
7.34
G.
6.6kV TRANSFORMER FEEDER FOR LTPCC
1.0
BASIC DATA
a.
System voltage in kV
6.6
b.
Selected CT Ratio =
250/1
A
c.
Symmetrical S/C current in amps at 6.6kV bus during SLG fault =
600
A
d.
Rated primary current in amps corresponding to selected CT ratio, In =
250
A
e.
Relay used
f.
Setting ranges :
MICOM P122
Ie>
0.1 - 1.0 In
Ie>>
0.1 - 8 In
@ 0.005 In (Inverse time) @ 0.005 In (Definite time)
TMS =
0.025 - 1.5
@ 0.025
Definite time setting =
0 - 150 sec
@ 0.01 sec
2.0
SETTING VALUES
2.1
Proposed Ie> (IDMT) setting for E/F (51N),
a.
Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
b.
Plug setting (PS) proposed =
0.1
c.
Ie> = Current in amps corresponding to PS = PS*In
25
d.
Proposed TMS setting =
IEC SI
Standard inverse
0.075
2.2
Proposed Ie>> (DT) setting for E/F (50N)
a.
Minimum Isc setting proposed in multiples M of In
0.2
b.
Isc Current in amps corresponding to Isc setting = M*In
50
c.
Proposed DT time in sec =
0.1
2.3
kV
Time of Operation for Different Fault Current CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs
EQUIVALENT MVA
TIME OF OPERATIOM (sec)
ZONE OF OPERATION
M
MVA
sec
5000
20
57.16
0.1
DT Zone
50
0.2
0.57
0.1
(Ie>>)
50
0.2
0.57
0.75
600
24
6.86
0.16
375
15
4.29
0.19
250
10
2.86
0.22
225
9
2.57
0.23
200
8
2.29
0.25
175
7
2.00
0.26
150
6
1.71
0.29
Consultant : SATCON
IDMT Zone
Page 9 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J
H.
125
5
1.43
0.32
100
4
1.14
0.37
75
3
0.86
0.47
50
2
0.57
0.75
48
1.9
0.54
0.81
45
1.8
0.51
0.89
43
1.7
0.49
0.98
40
1.6
0.46
1.11
38
1.5
0.43
1.29
35
1.4
0.40
1.56
33
1.3
0.37
2.00
30
1.2
0.34
2.87
28
1.1
0.31
5.50
(Ie>)
415V INCOMER AND BUS COUPLER
1.0
BASIC DATA
a.
System voltage in kV
0.415
kV
b.
Selected CT Ratio =
3000/5
A
c.
Symmetrical S/C current in amps at 415V bus during SLG fault =
36950
A (Based on ETAP fault calculation)
d.
Rated primary current in amps corresponding to selected CT ratio, In =
3000
A
e.
Relay used
f.
Setting ranges :
SPAJ 140C
Ie>
0.1 - 0.8 In
(Inverse time)
Ie>>
0.1 - 10 In
(Definite time)
TMS =
0.05 - 1.0
Definite time setting =
0.05 - 300
2.0
SETTING VALUES
2.1
Proposed Ie> (IDMT) setting for E/F (51N),
a.
Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
b.
Plug setting (PS) proposed =
IEC SI
Standard inverse
0.1
c.
Ie> = Current in amps corresponding to PS = PS*In
d.
Proposed TMS setting =
2.2
Proposed Ie>> (DT) setting for E/F (50N)
a.
Minimum Isc setting proposed in multiples M of In
0.12
b.
Isc Current in amps corresponding to Isc setting = M*In
360
c.
Proposed DT time in sec =
0.7
2.3
sec
300 0.525
Time of Operation for Different Fault Current CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M) I = MxIs M
60000
Consultant : SATCON
20
EQUIVALENT MVA MVA
43.13
TIME OF OPERATIOM (sec) sec
0.7
ZONE OF OPERATION DT Zone
Page 10 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J 360
0.12
0.26
0.7
360
0.12
0.26
20.12
36950
123.1666
26.56
0.73
4500
15
3.23
1.32
3000
10
2.16
1.56
2700
9
1.94
1.64
2400
8
1.73
1.73
2100
7
1.51
1.85
1800
6
1.29
2.01
IDMT Zone (Ie>)
1500
5
1.08
2.25
1200
4
0.86
2.61
900
3
0.65
3.31
600
2
0.43
5.27
570
1.9
0.41
5.69
540
1.8
0.39
6.22
510
1.7
0.37
6.89
480
1.6
0.35
7.78
450
1.5
0.32
9.03
420
1.4
0.30
10.89
390
1.3
0.28
13.97
375
1.25
0.27
16.43
360
1.2
0.26
20.12
330
1.1
0.24
38.52
J.
BACK UP E/F (51G) AT 1.6 MVA TRAFO NEUTRAL
1.0
BASIC DATA
a.
System voltage in kV
(Ie>>)
0.415
kV
b.
Selected CT Ratio =
500/5
A
c.
Symmetrical S/C current in amps at 415V bus during SLG fault =
36950
A (Based on ETAP fault calculation)
d.
Rated primary current in amps corresponding to selected CT ratio, In =
e.
Relay used
f.
Setting ranges :
500
CDG 11
Ie>
0.2 - 0.8 In
TMS =
0.1 - 1.0
2.0
SETTING VALUES
2.1
Proposed Ie> (IDMT) setting for E/F (51G),
a
Curve used for Ie> (IDMT) setting : t = TMS[0.14/{(I/Is)^0.02-1}]
b
Plug setting (PS) proposed =
IEC SI
(3 sec version)
(Inverse time)
Standard inverse
0.6
c
Ie> = Current in amps corresponding to PS = PS*In
300
d
Proposed TMS setting =
0.75
2.2
A
Time of Operation for Different Fault Current
Consultant : SATCON
Page 11 of 12
SAIL, ISP Package-22 Relay Setting Calculation & Charts Settings of Various Earth Fault Relays for LBDS-9 Drawing no. ISP/AREVA-EMC/A/IX/22/16/29/DE/01007J CURRENT IN MULTIPLES OF AMPS (I) SET CURRENT (M)
EQUIVALENT MVA
TIME OF OPERATIOM (sec)
I = MxIs
M
MVA
sec
36950
123.1666
26.56
1.04
4500
15
3.23
1.89
3000
10
2.16
2.23
2700
9
1.94
2.34
2400
8
1.73
2.47
ZONE OF OPERATION
2100
7
1.51
2.65
1800
6
1.29
2.88
1500
5
1.08
3.21
1200
4
0.86
3.73
IDMT Zone (Ie>)
900
3
0.65
4.73
600
2
0.43
7.52
570
1.9
0.41
8.13
540
1.8
0.39
8.88
510
1.7
0.37
9.84
480
1.6
0.35
11.12
450
1.5
0.32
12.90
420
1.4
0.30
15.55
390
1.3
0.28
19.96
360
1.2
0.26
28.74
330
1.1
0.24
55.03
Consultant : SATCON
Page 12 of 12
EARTH FAULT PROTECTION COORDINATION CURVES FOR 415V
SLG Fault Current = 36950A
100
TIME IN SEC
10
1
0.1 0.10
1.00 415V Incomer
Consultant : SATCON
MVA Back Up 51G
10.00 SLGF fault Current 36950A
100.00
EARTH FAULT PROTECTION COORDINATION CURVES FOR 6.6KV
TIME IN SEC
600A SLG
10
1
0.1 0.10
1.00 6.6kV TRAFO FDR
Consultant : SATCON
10.00 6.6KV BUS COUPLER
6.6KV INCOMER
MVA
100.00
51G at 6.6kV NEUTRAL
1000.00 600A SLG FAULT
EARTH FAULT PROTECTION COORDINATION CURVES FOR 33KV
100
TIME IN SEC
400A SLG Fault Current
10
1
0.1 1.00
10.00 33kV TRAFO FDR
Consultant : SATCON
MVA 33KV BUS COUPLER
100.00 400A SLG FAULT
1000.00 33KV INCOMER
Project:
ETAP
ISP MODERNISATION
7.0.0C
Page:
1
Location:
BURNPUR
Date:
07-08-2011
Contract:
AREVA
SN:
SATCON2007
Engineer:
SATCON
Revision:
Base
Filename:
LBDS9LT
Config.:
Normal
Study Case: SC
SHORT CIRCUIT CALCULATION AT LT BUS
Short-Circuit Summary Report 3-Phase, LG, LL, LLG Fault Currents Bus ID LV SWBD
3-Phase Fault kV 0.433
I"k 33.007
Line-to-Ground Fault
ip 79.775
Ik 33.007
All fault currents are in rms kA. Current ip is calculated using Method C. * LLG fault current is the larger of the two faulted line currents.
I"k 36.954
ip 89.314
Ib 36.954
Line-to-Line Fault Ik 36.954
I"k 28.585
ip 69.087
Ib 28.585
*Line-to-Line-to-Ground Ik 28.585
I"k 35.685
ip 86.248
Ib 35.685
Ik 35.685
Project:
ETAP
ISP MODERNISATION
7.0.0C
Page:
2
Location:
BURNPUR
Date:
07-08-2011
Contract:
AREVA
SN:
SATCON2007
Engineer:
SATCON
Revision:
Base
Filename:
LBDS9LT
Config.:
Normal
Study Case: SC
SHORT CIRCUIT CALCULATION AT LT BUS
Sequence Impedance Summary Report Bus ID LV SWBD
Positive Seq. Imp. (ohm) kV 0.433
Negative Seq. Imp. (ohm)
Zero Seq. Imp. (ohm)
Fault Zf (ohm)
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
0.00093
0.00790
0.00795
0.00093
0.00790
0.00795
0.00075
0.00535
0.00541
0.00000
0.00000
0.00000
One-Line Diagram - OLV1 (Short-Circuit Analysis - 3 PHASE FAULT)
6.6KV BUS 129 MVAsc
MV SWBD 6.6 kV
2.17 kV 8 2 5.
T1 1.6 MVA 6.6/0.433 kV 6.25 %Z
DS
LV SWBD 0.433 kV
page 1
33.01 33.0
kA
LV LOAD 1.2 MVA 10:37:45
Aug 07, 2011
Project File: LBDS9LT
One-Line Diagram - OLV1 (Short-Circuit Analysis - SLG FAULT)
6.6KV BUS 129 MVAsc
MV SWBD 6.6 kV kV 1 8 3.
T1 1.6 MVA 6.6/0.433 kV 6.25 %Z
DS
LV SWBD 0.433 kV
page 1
kV 3 2 0.
36.95 36.9
5 kA
LV LOAD 1.2 MVA 10:38:58