Download Increased Power Flow Guidebook...
Effective December 6, 2006, this report has been made publicly available in accordance with Section 734.3(b)(3) and published in accordance with Section 734.7 of the U.S. Export Administration Regulations. As a result of this publication, this report is subject to only copyright protection and does not require any license agreement from EPRI. This notice supersedes the export control restrictions and any proprietary licensed material notices embedded in the document prior to publication.
Increased Power Flow Guidebook Increasing Power Flow in Transmission and Substation Circuits
Increased Power Flow Guidebook: Increasing Power Flow in Transmission and Substation Circuits 1010627
Final Report, November 2005
EPRI Project Manager R. Adapa
ELECTRIC POWER RESEARCH INSTITUTE 3420 Hillview Avenue, Palo Alto, California 94304-1395 ▪ PO Box 10412, Palo Alto, California 94303-0813 ▪ USA 800.313.3774 ▪ 650.855.2121 ▪
[email protected] ▪ www.epri.com
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES THIS DOCUMENT WAS PREPARED BY THE ORGANIZATION(S) NAMED BELOW AS AN ACCOUNT OF WORK SPONSORED OR COSPONSORED BY THE ELECTRIC POWER RESEARCH INSTITUTE, INC. (EPRI). NEITHER EPRI, ANY MEMBER OF EPRI, ANY COSPONSOR, THE ORGANIZATION(S) BELOW, NOR ANY PERSON ACTING ON BEHALF OF ANY OF THEM: (A) MAKES ANY WARRANTY OR REPRESENTATION WHATSOEVER, EXPRESS OR IMPLIED, (I) WITH RESPECT TO THE USE OF ANY INFORMATION, APPARATUS, METHOD, PROCESS, OR SIMILAR ITEM DISCLOSED IN THIS DOCUMENT, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, OR (II) THAT SUCH USE DOES NOT INFRINGE ON OR INTERFERE WITH PRIVATELY OWNED RIGHTS, INCLUDING ANY PARTY'S INTELLECTUAL PROPERTY, OR (III) THAT THIS DOCUMENT IS SUITABLE TO ANY PARTICULAR USER'S CIRCUMSTANCE; OR (B) ASSUMES RESPONSIBILITY FOR ANY DAMAGES OR OTHER LIABILITY WHATSOEVER (INCLUDING ANY CONSEQUENTIAL DAMAGES, EVEN IF EPRI OR ANY EPRI REPRESENTATIVE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES) RESULTING FROM YOUR SELECTION OR USE OF THIS DOCUMENT OR ANY INFORMATION, APPARATUS, METHOD, PROCESS, OR SIMILAR ITEM DISCLOSED IN THIS DOCUMENT. ORGANIZATION(S) THAT PREPARED THIS DOCUMENT EPRI Power Delivery Consultants, Inc.
NOTE For further information about EPRI, call the EPRI Customer Assistance Center at (800) 313-3774 or email
[email protected] Electric Power Research Institute and EPRI are registered service marks of the Electric Power Research Institute, Inc. Copyright © 2005 Electric Power Research Institute, Inc. All rights reserved.
CITATIONS This report was prepared by EPRI 115 East New Lenox Road Lenox, MA 01240 Principal Investigator B. Clairmont Power Delivery Consultants Inc. 28 Lundy Lane, Suite 102 Ballston Lake, NY 12019 Principal Investigators D. A. Douglass E. C. Bascom, III T. C. Raymond J. Stewart 59 St. Stephens Lane N Scotia, NY 12302 This report describes research sponsored by the Electric Power Research Institute (EPRI). The report is a corporate document that should be cited in the literature in the following manner: Increased Power Flow Guidebook: Increasing Power Flow on Transmission and Substation Circuits. EPRI, Palo Alto, CA: 2005. 1010627.
iii
PRODUCT DESCRIPTION
The Increased Power Flow (IPF) Guidebook is a state-of-the-art and “best practices” guidebook on increasing power flow capacities of existing overhead transmission lines, underground cables, power transformers, and substation equipment without compromising safety and reliability. The Guidebook discusses power system concerns and limiting conditions to increasing capacity, reviews available technology options and methods, illustrates alternatives with case studies, and analyzes costs and benefits of different approaches. Results & Findings The IPF Guidebook clearly identifies those cases where increasing power flow might be an alternative to upgrading the grid with major investment. The document reviews both established technologies and new developments in technologies with the potential to increase power flow— and addresses how to apply them for lines, cables, and substations. Because the guide compares the economic benefits of each available technology, it will assist utilities in making informed decisions in terms of what options for IPF are available and which options are most economical for application at their utility sites. By implementing one or more of the IPF technologies, utilities can obtain increased asset utilization with minimal cost. For example, if a utility decides to implement one of the IPF technologies, such as Dynamic Thermal Circuit Rating (DTCR) technology, that implementation will allow increased power flows on the order of 15-20% over the existing static ratings and, thus, increase utility revenue. Challenges & Objective(s) Motivations for increasing power flow limits on existing transmission facilities (rather than constructing new facilities) are economic, environmental, and practical. Due to limited incentives for new construction and time delays that may result from public opposition to new power facilities, utilities around the world are being forced to find new ways of relieving modest constraints or increasing power flow through existing transmission corridors with minimal investment. This Guidebook will be an excellent reference document for transmission and substation engineers since it provides all possible IPF options in one place for ease of use. Applications, Values & Use Training materials will be developed with the IPF Guidebook, including hands-on workshops at EPRI's full-scale laboratories. In addition, it is anticipated that, in the coming years, technical reports will be produced annually on new and updated aspects of IPF as well as new material on costing, economics, power storage, voltage upgrading, and case studies. This information will be incorporated into the Guidebook during subsequent work.
v
EPRI Perspective Due to limited incentives for new construction, utilities around the world are undergoing a major transformation that is redefining the use of existing power equipment in the electric transmission network. Under these circumstances, utilities are forced to find new ways of increasing power flow through the existing transmission corridors with minimal investments. EPRI’s Increased Transmission Capacity Program directly responds to the needs of owners and operators of the transmission grid to get the most out of existing equipment in today’s competitive electricity business while increasing the availability and reliability of transmission and substation equipment. This Program helps customers accomplish these goals strategically, without jeopardizing reliability and driving up costs. A number of projects have been undertaken by EPRI in this Program under the Project Set 38A—Increase Power Flow Capability in the Transmission Systems. One major effort under Project Set 38A is the IPF Guidebook, the only available utility compendium of “best practices” for increasing power flow in transmission circuits. Other major EPRI developments include DTCR (Dynamic Thermal Circuit Ratings) software to calculate dynamic ratings of transmission circuits and Video Sagometer to measure sag of transmission lines. Approach The Guidebook was developed by industry experts and draws on a combination of technology, documented case studies, and associated engineering and safety guidelines. Keywords Overhead transmission Substations Transmission capacity Underground transmission
vi
ABSTRACT The Increased Power Flow (IPF) Guidebook documents the state-of-science for increasing power flow capacities of existing overhead transmission lines, cables, and substation equipment. The Guidebook provides an overview of the electrical, mechanical, thermal, and system concerns that are important to increased power flow, presents all possible IPF options, uses case studies to illustrate the options, and compares their potential economic benefits. The Guidebook also provides an overview of dynamic thermal rating methods and summarizes other developments in hardware and software that are instrumental for IPF. The IPF Guidebook provides utilities with the only available compendium of “best practices” for increasing power flow. The Guidebook will assist utilities in making informed decisions in terms of what options for IPF are available and which options are most economical for application at their utility sites.
vii
Increased Power Flow Guidebook
Contents
Chapter 1
Increased Power Flow Fundamentals and Principles
1.1
INTRODUCTION
1-1
1.2
POWER SYSTEM ISSUES
1-2
1.3
LIMITING CONDITIONS
1-3
Circuit Power Flow Limits Surge Impedance Loading of Lines Voltage Drop Limitations Thermal Limits Environmental Limits Examples – Overhead Lines
1-3 1-4 1-5 1-6 1-7 1-8
1.4
CHAPTER PREVIEW Overhead Lines (Chapter 2) Underground Cables (Chapter 3) Power Transformers (Chapter 4) Substation Terminal Equipment (Chapter 5) Dynamic Rating and Monitoring (Chapter 6)
REFERENCES
Chapter 2 2.1
2.2
2.3
2.4
1-9 1-9 1-10 1-10 2.5 1-10 1-10 1-11
Overhead Transmission Lines
INTRODUCTION
2-1
Surge Impedance Loading Voltage Drop Thermal Limits Environmental Limits
2-2 2-2 2-2 2-2
UPRATING CONSTRAINTS
2-3
Introduction Sag-tension Calculations Limiting High Temperature Sag Uprating Constraints Related to Wind-Induced Conductor Motion Electrical Clearance Loss of Conductor Strength Constraints on Structural Loads Environmental Effects
2-3 2-3 2-5 2-8 2-10 2-12 2-13 2-15
LINE THERMAL RATINGS
2-15
Introduction Maximum Conductor Temperature Weather Conditions for Rating Calculation How Line Design Temperature Affects Line Ratings Heat Balance Methods Thermal Ratings— Dependence on Weather Conditions Transient Thermal Ratings
2-15 2-16 2-16 2-17 2-17 2-21 2-22
2.6
EFFECTS OF HIGH-TEMPERATURE OPERATIONS 2-23 Introduction Annealing of Aluminum and Copper Sag Tension Models for ACSR Conductors Axial Compressive Stresses Built–In Stresses Sag Tension Calculations Sag and Tension of Inclined Spans Calculation of Conductor High-Temperature Sag and Tension Results of High-Temperature Sag Tension Calculations Effects of Wind Speed on Thermal Ratings Thermal Elongation Creep Elongation Connectors at High Temperature Conductor Hardware
2-34 2-40 2-41 2-42 2-46 2-49
2.8
2-32
UPRATING WITHOUT RECONDUCTORING
2-51
Introduction Deterministic Methods Probabilistic Methods Development of a “Measure of Safety” as a Basis for Line Rating Comparison of Probabilistic Rating Methods Device for Mitigating Line Sag - SLiM
2-51 2-51 2-56 2-60 2-62 2-62
RECONDUCTORING WITHOUT STRUCTURAL MODIFICATIONS
2-65
Introduction TW Aluminum Wires – ACSR/TW or AAC/TW ACSS and ACSS/TW High-Temperature Aluminum Alloy Conductors Special Invar Steel Core Gapped Construction ACCR Conductor Conductors with Exotic Cores Comparing ACSS and High-Temperature Alloy Conductors 2.7
2-23 2-23 2-27 2-28 2-29 2-29 2-31
2-65 2-66 2-67 2-70 2-70 2-71 2-74 2-74 2-74
DYNAMIC MONITORING AND LINE RATING
2-75
Introduction Dynamic Ratings Versus Static Ratings Advantages of Dynamic Rating Disadvantages of Dynamic Rating Real-time Monitors Dynamic Rating Calculations Field Test Results Summary
2-75 2-75 2-76 2-76 2-77 2-79 2-82 2-84
CASE STUDIES
2-84
Introduction Selecting a Line Uprating Method Preliminary Selection of Uprating Methods Uprating Test Cases—Preliminary Uprating Study Economic Comparison of Line Uprating Alternatives
2-84 2-84 2-85 2-87 2-95
ix
Contents
2.9
Detailed Comparison of Uprating Alternatives— An Example Conclusions
2-99 2-103
REFERENCES
2-104
Chapter 3 3.1 3.2
3.3
3.4
3.5
3.6
3.7
x
Increased Power Flow Guidebook
Cupric Oxide Strand Coating Voltage Upgrading Superconducting Cables 3.8
Underground Cables
INTRODUCTION CABLE SYSTEM TYPES
3-1 3-2
High-Pressure Pipe-Type (Fluid- and Gas-Filled) Extruded Dielectric Self-Contained Liquid-Filled (SCLF) Other Cable Types
3-2 3-5 3-8 3-10
POWER FLOW LIMITS AND SYSTEM CONSIDERATIONS
3-11
3.9
3.10
3-44 3-45 3-45
DYNAMIC RATINGS OF UNDERGROUND CABLE SYSTEMS
3-46
Background EPRI Dynamic Ratings on Cables Benefit of Dynamic Ratings Required Monitoring Quasi-Dynamic (Real-Time) Ratings
3-46 3-46 3-49 3-51 3-51
CASE STUDIES FOR UNDERGROUND CABLE CIRCUITS
3-51
CenterPoint Energy United Illuminating Company
3-51 3-53
SUMMARY OF UPRATING AND UPGRADING APPROACHES AND ECONOMIC FACTORS
3-55
Thermal, Stability, and Surge Impedance Loading Limits Load Flow Considerations Uprating Hybrid (Underground and Overhead) Circuits
3-11 3-14
REFERENCES Appendix 3.1
Pipe-Type Ampacity Example
3-58
3-14
Appendix 3.2
Extruded Ampacity Example
3-65
UNDERGROUND CABLE RATINGS
3-15
Introduction Concept of Ampacity Losses Equivalent Thermal Circuit and Thermal Resistances Calculating Ampacity Effect of Various Parameters on Ampacity Emergency Ratings Inferring Conductor Temperatures from Measured Temperatures
3-15 3-15 3-16
Chapter 4
Power Transformers
3-26
UPRATING AND UPGRADING CONSTRAINTS
3-26
Direct Buried Cable Systems Fluid-Filled Cable Systems Duct Bank Installations Trenchless Installations Other Installation Locations Hot Spot Identification Accessories Hydraulic Circuit
3-26 3-26 3-27 3-27 3-27 3-28 3-28 3-28
3-19 3-23 3-24 3-25
INCREASING THE AMPACITY OF UNDERGROUND CABLES 3-28 Route Thermal Survey Review Circuit Plan and Profile Evaluate Daily, Seasonal, or Other Periodic Load Patterns Temperature Monitoring Ampacity Audit Remediation of “Hot Spots” Active Uprating Shield/Sheath Bonding Scheme
3-36 3-38 3-40 3-40 3-40 3-43
RECONDUCTORING (UPGRADING)
3-43
Introduction Larger Conductor Sizes
3-43 3-44
4.1 4.2
4.3
4.4
4.5
3-56
INTRODUCTION
4-1
TRANSFORMER DESIGN
4-2
General Construction Types of Cooling Losses Factory Testing
4-2 4-5 4-5 4-6
RISKS OF INCREASED LOADING
4-9
Short-Term Risks Long-Term Risks Additional Risks
4-9 4-11 4-18
THERMAL MODELING
4-21
Mechanisms of Heat Transfer Top Oil Model (IEEE C57.91-1995, Clause 7) Bottom Oil Model (IEEE C57.91-1995, Annex G) IEC Model (IEC 354-1991) Proposed IEC Model
4-21 4-24 4-26 4-30 4-32
THERMAL RATINGS
4-33
Ambient Air Temperature Load Rating Type and Duration Rating Procedure Condition-Based Loading Maintenance Considerations
4-34 4-34 4-35 4-35 4-36 4-37
4.6
WINDING TEMPERATURE MEASUREMENT
4-38
4.7
MODEST INCREASES IN CAPACITY FROM EXISTING TRANSFORMERS
4-39
EXAMPLES
4-39
3-28 3-36
4.8
REFERENCES
4-43
Contents
Chapter 5
Increased Power Flow Guidebook
Substation Terminal Equipment
Chapter 6
5.1
INTRODUCTION
5.2
SUMMARY—EQUIPMENT TYPES AND IPF OPPORTUNITIES
5-2
Equipment Rating Parameters Thermal Rating Parameter Comparison
5-2 5-4
THERMAL MODELS FOR TERMINAL EQUIPMENT
5-4
5.3
Bus Conductors Switch (Air Disconnect) Air-core Reactor Oil Circuit Breaker SF6 Circuit Breaker Bushings (Oil-immersed Equipment Only) Current Transformers Line Traps Other Types of Terminal Equipment 5.4
5.5
5.6
5-1
5-4 5-6 5-8 5-9 5-10 5-10 5-11 5-11 5-12
UPRATING OF SUBSTATION TERMINAL EQUIPMENT
5-12
Monitoring and Communications Maintenance and Inspection Procedures Reliability and Consequences of Failure
5-13 5-13 5-13
THERMAL PARAMETERS FOR TERMINAL EQUIPMENT
5-14
Manufacturer Test Report Data
5-14
CONCLUSIONS AND SUMMARY
5-14
REFERENCES
Dynamic Thermal Ratings Monitors and Calculation Methods
6.1
INTRODUCTION
6.2
ISSUES RELATED TO DYNAMIC THERMAL RATING METHODS 6-2
6.3 6.4
Where Should Dynamic Thermal Circuit Rating Calculations Be Performed? Costs—Capital and Otherwise Why Dynamic Ratings Go With Increased Utilization
6-2 6-3 6-4
POWER EQUIPMENT CONDITION ASSESSMENT AND REAL-TIME MONITORS
6-4
DYNAMIC THERMAL RATING MODELS FOR POWER EQUIPMENT 6-5 Accounting for Heat Storage (Pre-load Monitoring) Overhead Lines Power Transformers Underground Cables Substation Terminal Equipment
6.5
6.6
5-15
6.7
6.8
6-1
6-5 6-6 6-7 6-10 6-11
EPRI'S DTCR TECHNOLOGY
6-13
Power Circuit Modeling DTCR Output DTCR is a Calculation Engine for SCADA Modeling Complex Interfaces—California “Path 15” Conclusions about the Dynamic Rating of Complex Interfaces
6-13 6-13 6-14 6-14 6-16
OPERATING WITH DYNAMIC THERMAL RATINGS
6-16
Traditional Rating Definitions Traditional Operating Rules Operating with Dynamic Ratings
6-16 6-17 6-17
FIELD STUDIES OF DYNAMIC RATINGS
6-19
Overhead Lines Power Transformers Underground Cables Substation Terminal Equipment Power Circuits Communications and Monitoring
6-19 6-20 6-20 6-20 6-20 6-21
CONCLUSIONS
6-21
REFERENCES
6-22
Glossary
G-1
Index
I-1
xi
Increased Power Flow Guidebook
CHAPTER 1
Increased Power Flow Fundamentals and Principles
1.1
INTRODUCTION
The purpose of this guidebook is to provide technical information and explain concepts that may aid power transmission company technical personnel in finding economic, technically sound ways to increase the power flow capacity of existing circuits without compromising safety or reliability. The motivations for increasing the power flow limits on existing transmission facilities (rather than constructing new facilities) are economic, environmental, and practical. The methods discussed are generally modest in cost—ranging from virtually free to about 30% of the cost of equipment replacement. The corresponding increase in equipment rating is similarly modest, usually between 5% and 30% (with the exception of overhead lines where reconductoring may yield an increase of over 100%). The methods are practical since the environmental and/or visual impact is normally low, regulatory approval and public hearings may not be needed, and extended power outages are often avoided. Given the extended time delays that may result from public opposition to the construction of new power transmission facilities or even to any visible, physical modification of existing facilities, the use of increased power flow (IPF) methods may offer the only practical solution to relieving modest constraints on power flow. Determining the degree to which maximum power flow constraints can be eased on existing power equipment (overhead lines, power transformers, etc.), power circuits (multiple power equipment elements in series), and power system interfaces (multiple “parallel” power circuits connecting power system regions) can be quite complex. For example, consider the following:
• For an overhead line, any increase in power flow capacity is dependent on its length, the original design assumptions, present-day environmental concerns, the condition of its existing structures, and the type of conductors originally selected. Depending on these multiple factors and which of the IPF methods suggested in Chapter 2 is applied, the resulting increase in the line’s thermal rating could be as little as 5% or as much as 100%.
• But overhead lines are only part of the transmission path (circuit). The lines are terminated at substations by air disconnects, circuit breakers, line traps, etc. The power flow through all of the circuit elements must be limited to avoid damaging the line or the terminating equipment, and the maximum allowable power flow over this circuit may be limited by any one of the circuit elements.
• Finally, when seen as part of a power system interface, any increase in maximum allowable power flow through any component circuit or circuit element does not necessarily yield a higher rating for the complex interface.
1-1
Chapter 1: Increased Power Flow Fundamentals and Principles
In general, it may be stated that maximum power flow on the transmission system is a function of the overall system topology (transmission lines, transformers, generation, series and shunt compensation, and load), and that many non-thermal system considerations can also limit the maximum power flow on a specific transmission circuit. Therefore, transmission circuit ratings are often developed on a system basis, rather than on an individual line basis. The overall limit may be between operating areas irrespective of ownership or individual lines, and may change during a day based on system conditions. Chapter 1 provides an overview of the electrical, mechanical, thermal, and system concerns that are important to increased power flow. The chapter includes three sections:
Increased Power Flow Guidebook
2834 MW from A to B. Given this level of transfer, the power flows would be as shown in Figure 1.2-2. Notice in Figure 1.2-2 that, even though load area C is not importing power, the lines connecting load area C to the other areas are carrying almost half of the total power transferred. Now let us assume that the customers in load area B would like to buy even more than 2834 MW from the low-cost generator in load area A. Consequently, they contest the limit of 2834 MW set by the system operator, noting that the emergency rating of the lines is 1000 MW. The power system operator explains that the limitation on power import to load area B is not due to nor-
• Section 1.2, Power System Issues, presents a simple power flow example to illustrate several principles about increasing power flow.
• Section 1.3, Limiting Conditions, describes limits on power flow imposed by circuit power flow, surge impedance loading, voltage drop, thermal factors, and environmental constraints.
• Section 1.4, Chapter Previews, presents brief descriptions of the chapters in this guidebook. 1.2
POWER SYSTEM ISSUES
The power transmission system, in any region, is a complex combination of lines (including underground cable) and substations. With the exception of relatively short “radial” lines connecting generating stations to the system, power flow reaching any load point in the system flows over multiple “parallel” paths (circuits). In any path (circuit), the power flow moves through multiple series elements.
Figure 1.2-1 Base system operating "normally" with local generation being similar in cost and able to supply all local load.
This can be illustrated by the following simple power system (NERC 1995) shown in Figure 1.2-1. There are three load areas (A, B, and C). Each load area has sufficient generation to supply the local load. With the system operating “normally,” there is no net power transfer between load areas. Nonetheless, as a result of the available electrical paths connecting the load areas, the diagram shows a “loop” flow of 200 MW. This loop flow occurs even though there is no net power transfer to any of the areas. Consider the situation where power generated in load area A is considerably less expensive than local generation in load area B. It would then be advantageous for power customers in load area B to buy power from the generators in load area A. In doing this, the power transmission system operator sets a transfer limit of
1-2
Figure 1.2-2 Base system operating "normally" with local generation at A being much cheaper than at B, causing a net power transfer of 2834 MW.
Increased Power Flow Guidebook
Chapter 1: Increased Power Flow Fundamentals and Principles
limits and electrical impedance of interconnected power circuits.
mal power flows but rather to the emergency power flow through one of the lines (#2) between A and C, as shown in Figure 1.2-3! With line #1 out of service, the redistributed power flow through line #2 reaches the emergency thermal limit of 1000 MW. Thus the imposed power transfer limit of 2834 MW from A to B.
• Note that these observations do not depend on the
As shown in Figure 1.2-3, if the net power transfer from A to B with all lines in service had exceeded the transfer limit of 2834 MW then, under this single contingency loss of line #1 between A and C, the power flow in line #2 from A to C would have exceeded the line’s emergency thermal limit.
1.3
LIMITING CONDITIONS
1.3.1
Circuit Power Flow Limits
One can reach a number of conclusions regarding power flow limits from this simple example:
• Economic power transfers can be limited by circuits that do not directly connect the low-cost generation source and the customer.
• A 5% increase (50 MW) in the emergency rating of lines #1 and #2 connecting A and C from 1000 MW to 1050 MW might allow a similar 5% increase (141 MW) in the power transfer limit from 2834 to 2975 MW.
• A 5% increase in the emergency rating of either line #1 or #2 between A and B would not allow any increase in power transfer from A to B.
• The long-term value of projects to increase the power flow in any particular circuit is dependent on changes in the cost of generation and the power flow
reason for the power flow limit in any of the circuits. They would be equally valid whether the limitation on power flow is due to equipment temperature limits, limits on voltage drop, or electrical phase shift stability issues.
Power circuits consist of series and parallel combinations of electrical equipment (each subjected to mechanical, electrical, and thermal stresses) whose collective purpose is to transmit power safely and reliably under widely varying operational situations. Each element of such circuits is typically specified to have certain power flow limits that allow their safe, reliable operation for an extended period of time (e.g., 40 years). Increased power flow inevitably means increased electrical current flow or increased circuit voltage since power is the product of these quantities. In general, for substation equipment and underground cables, increasing the operating voltage is difficult or impossible, whereas increasing the maximum electrical current is both possible and economic. Overhead lines are often capable of either higher voltage or higher current levels if certain modifications are undertaken. Power transmission circuits are typically bimodal in terms of power flow. Under normal operation, it is not unusual for power transformers and lines to operate at much less than half of their power flow capacity, only approaching their operational limits under relatively rare emergency events. There are basically three methods of increasing power flow: load control, improved modeling and monitoring, and physical modification of existing circuits. Improved models may allow operation of equipment with reduced safety factors without reducing safety and reliability. Examples are the “bottom oil” model in Annex G of the IEEE loading guide and the improved models for high-temperature sag of ACSR conductor.
Figure 1.2-3 Base system operating in response to a “single contingency” outage of line #1 between A and C while there is a power transfer of 2834 MW from A to B.
Similarly, monitoring of environmental factors (air temperature, wind speed, humidity, etc.) may allow the use of less conservative assumptions, again without reducing safety and reliability.
1-3
Chapter 1: Increased Power Flow Fundamentals and Principles
With monitors communicating data in real-time, it may be possible to run equipment at higher power levels most of the time by avoiding the use of “worst case” assumptions. This approach is called dynamic thermal ratings. It is unlikely that such real-time monitoring would allow any increase in non-thermal operating limits. Overhead transmission lines are the primary means of power transfer over long distances. They have thermal ratings just as power transformers, substation terminal equipment, and underground cables but, for long lines, power flow limits may also be necessary to avoid excessive voltage drop or system stability problems. In addition, since the public has access to the area under lines, there may also be limits on voltage and current related to environmental effects. This section concerns the relationship between the various types of power flow limits for overhead lines. 1.3.2
Surge Impedance Loading of Lines
Sometimes a power transmission line possesses a definite power flow limit based on the design parameters for the specific line, but at other times, the line as a component of the overall transmission system determines the limit. System limits can result from factors such as voltage drop, possibility of voltage collapse, and system stability, both steady state and transient. System limits are functions of transmission line reactances in relation to the overall power system. Series reactance, shunt admittance, and their combination, surge impedance, are relevant to system transfer limits. System planners have long recognized this relationship, particularly where there are prospects of changing the line surge impedance, either by adding equipment (e.g., series capacitors) or by modifying the line itself (e.g., reconductoring, voltage uprating, etc.). Transmission line series inductive reactance is determined by conductor size, phase spacing, number of conductors, relative phasing (double-circuit lines), and line configuration. In transmission lines the series reactance is significantly larger than the series resistance, and is the dominant factor in a first-order explanation of system behavior. For this reason, simple reconductoring of a transmission line results in only minor changes in system power flows. Power flow on a transmission line, neglecting resistance of the line, is given by Equation 1.3-1, which can be derived from a simple circuit consisting of sending and receiving end voltage sources connected by a series reactance.
1-4
Increased Power Flow Guidebook
V1 •V2 • sin(δ ) X 1.3-1 Where: P = Real power transfer on the transmission line. V1 = Magnitude of sending end bus voltage. V2 = Magnitude of receiving end bus voltage. X = Line series inductive reactance between V1 and V 2. δ = Phase angle difference between V1 and V2. P=
Increasing voltage magnitude for the same line voltage and same phase difference between ends increases the power flow. By increasing the voltages V 1 and V 2 together, the power transmitted increases by the square of the voltage for the same phase angle. Power flow increases for the same end voltage magnitudes are accommodated by an increase in the phase angle difference between the voltages at the two line ends. Equation 1.3-1 imposes a fundamental limit on the amount of power that can be carried by a transmission line corresponding to a phase difference between line ends of 90°. Further increases in angle result in decreases in power flow. This is an unstable situation that can be realized in practice in two ways. If the steady-state power flow were to slowly increase to the point that the angle reached 90°, an attempt to further increase power flow would actually decrease the power flow. An increase in the power angle δ when δ is in the range from 90° to 180° results in a decrease in sin(δ) and a consequent decrease in power flow. The condition trying to increase the flow on the line actually results in a decreased flow, and system instability. Secondly, a system disturbance—for example, tripping of a line—causes a redistribution of power flow among the remaining lines, and consequent changes in the bus voltage angles. It is insufficient that the new angle differences on all the lines are less than 90°, because the angle differences must remain lower than 90° during all the transient system swinging from the time of the disturbance until the system settles in its new operating state. If a line were to experience its angle difference momentarily passing 90°, it would try to accommodate the power requirement by opening up the angle beyond 90°, decreasing the power flow. This is an unstable situation, and would cause the line to pass through the electrical point where its relay protection would sense a fault (even though none exists on the line), and result in a line trip and probable system separation. Surge impedance loading (SIL), defined in Equation 1.3-2) provides a useful rule of thumb measure of trans-
Increased Power Flow Guidebook
Chapter 1: Increased Power Flow Fundamentals and Principles
mission line loading limitation as a result of the effects of series reactance.
SIL =
V2 ZS
1.3-2
Where V is the line voltage, and ZS is the surge impedance of the transmission line given by:
ZS =
L C
1.3-3
Surge impedance ZS is a resistance in ohms. L and C in Equation 1.3-3 are positive sequence inductance and capacitance in henries per mile and farads per mile, respectively. Surge impedance loading is that loading on a three-phase power transmission line that it would have if it were loaded by a Y-connected set of resistances of ZS ohms per phase. This is the same physical condition as a radio frequency transmission line impedance matched to its termination (72 ohm coaxial cable terminated in 72 ohms in television cable). In electromagnetic theory, it corresponds to a pure TEM wave. The reactive power (vars) generated in the line capacitance is exactly canceled by the vars absorbed in the line inductance in a power transmission line at surge impedance loading (neglecting line resistance and real power losses). Surge impedance loading thus is a loading value based on physical principles related to the line design itself. Surge impedance loading is a handy tool for estimating the relative loading capabilities of lines of different voltages, constructions, and lengths from a system standpoint (St. Clair 1953). SIL is oversimplified for use in specifying actual line ratings on an operating system. However, it is a useful guide both for assessing actual loading limits and for understanding the different factors that limit line loading. Figure 1.3-1 gives a curve of line loadability in per unit of SIL as a function of line length for heavy loading conditions. Slightly different versions of Figure 1.3-1 have been published, but they are all very similar (Dunlop et al. 1979, Gutman 1988). The fundamental observation from Figure 1.3-1 is that transmission line loadability decreases as length of the line increases. Three different regions come into play in derivation of Figure 1.3-1. Short lines tend to be thermally limited, irrespective of system conditions. As line length increases, voltage drop considerations frequently come into play. At longer line lengths, stability factors may dominate. Short lines are often loaded at 2 or 2.5 times SIL and thus need reactive power (var) support to maintain the voltage. Long lines may be limited to 1.0 times SIL or less.
An important observation from Equation 1.3-2 is that surge impedance loading is a function of the square of line voltage. This has been a driving force in increased transmission voltages over the years, especially for longer lines. For an overhead transmission line, typical surge impedance is on the order of 300 ohms, while for a cable it may be 50 ohms or less. At 345 kV, SIL of an overhead line is on the order of 400 MW. Short lines may be able to carry 800 MW or more, while long lines of exactly the same construction may be limited to less than 400 MW by system considerations. Because of limitations on heat dissipation, underground transmission cables always operate very far below SIL. A consequence is that underground transmission cables are a net source of vars to the system, a condition that must be considered in system design. 1.3.3
Voltage Drop Limitations
Voltage control on the power system is of concern as system loadings increase. The system voltage distribution is affected by the series inductance and shunt capacitance of the transmission lines, and is related to the flow of reactive power in the system. Depending on the relative real and reactive power flow on a given transmission line, the voltage may increase or decrease from one end to the other. It is not desirable for voltage to vary more than 5%, or at most 10%, from one end to
Figure 1.3-1 Line loadability in terms of surge impedance loading (Dunlop et al. 1979).
1-5
Chapter 1: Increased Power Flow Fundamentals and Principles
the other. In some cases, a voltage drop limit is placed on power flow corresponding to the maximum allowable decrease in voltage magnitude. The longer the line or cable, generally the lower the power flow required to reach a voltage drop limit. Voltage control is a system problem, and is not generally solved by modifications to any one transmission circuit. Methods to improve voltage control on transmission circuits may take a variety of forms: 1. In some cases, bundled conductors have been in overhead lines used for short lower voltage lines to reduce series reactance, where the use of bundled conductors is required neither for thermal or corona reasons. 2. Supply of vars at various points on the system can be used to control voltage. The supply can be fixed, switched, or adjustable. In former years synchronous condensers were used to supply vars in a continuously adjustable basis. Capacitor banks are commonly used, and may be switched on or off depending on the local voltage. Static var compensators (SVCs) are also used to control voltage on the bulk power system. 3. Shunt reactors may be used for long EHV lines where the var supply from the line capacitance is greater than the system can absorb. Because voltage drop is primarily a function of line reactance rather than resistance, simple reconductoring does very little to decrease the voltage drop per unit length. Reconductoring an existing 230-kV line by replacing the original 636 kcmil Hawk ACSR with a 954 kcmil Rail ACSR only increases the voltage drop limit by 5%. For an overhead line, adding a second conductor per phase to form two conductor bundles results in a more significant reduction in series reactance, and a greater improvement in voltage drop power limit.
Increased Power Flow Guidebook
ular transmission line may be limited in its power-handling capacity by system voltages and var flows irrespective of the thermal capacity of the line conductors. In some cases, it is possible to increase the line flows by addition of capacitors or similar measures. Flexible AC Transmission (FACTS) is a scheme where thyristor-controlled devices are arranged to provide realtime control of transmission line flows in excess of those that would normally be allowed by system voltage and stability considerations. While voltage drop has long been known as a transmission limitation, attention has also been focused in more recent years on voltage collapse, which is a system instability that can occur under heavy loading conditions. Figure 1.3-2 shows a voltage collapse condition following a system disturbance, where the 115-kV voltage drops to 50% of the nominal operating voltage (0.5 p.u.). Voltage collapse can occur for several reasons on a heavily loaded system where there is insufficient var support. An example is the geomagnetic storm of March 13, 1989, with its resulting voltage collapse and blackout. The March 1989 storm increased attention to system problems that result from solar activity. Utilities in areas subject to geomagnetic disturbances monitor solar activity (Lesher et al. 1994), and can re-dispatch generation to reduce loading on affected lines during times of high geomagnetic activity. However, geomagnetic disturbances are not the only cause of voltage collapse. 1.3.4
Thermal Limits
Thermal limits are discussed in considerable detail later in this guidebook (see, for example, Section 2.3). In brief, the current-carrying capacity (thermal rating) of an overhead transmission circuit is determined by the assumed “worst-case” weather conditions, assumed
Shunt reactors may be applied for reasons other than voltage control—for example, to control transient overvoltages during line switching. Series capacitors may be used to partially compensate for the line series reactance, but this is usually reserved for the longest lines in relation to system stability. Whenever capacitors are installed in series with the transmission line inductance, the possibility of a series resonant condition exists. Subsynchronous resonance has been the cause of generator/turbine shaft failure and is a serious consideration for a series capacitor installation. Other problems present themselves with series capacitors—for example, provision for passage of fault current without causing failure of the capacitors. The overall effect of the concern with system voltage is that a partic-
1-6
Figure 1.3-2 Voltage collapse condition following a system disturbance.
Increased Power Flow Guidebook
conductor parameters, and the maximum allowable conductor temperature. Some of the specific thermal rating parameters are:
• Conductor construction: outside diameter, conductor strand diameter, core strand diameter, number of conductor strands, and number of core strands.
• Conductor AC resistance, which itself is a function of the conductor temperature.
• Conductor surface condition: solar absorptivity and
Chapter 1: Increased Power Flow Fundamentals and Principles
as 5 minutes. Emergency ratings are typically calculated for higher temperatures, and allow for some equipment deterioration in order to avoid load interruptions under unusual operating conditions. Broader voltage tolerances may also be appropriate under contingency conditions compared to normal operation. Lower voltage may be acceptable for a short time. Likewise, conductor resistive power losses are inconsequential during emergencies.
emissivity.
• Line location: latitude, longitude, conductor inclina-
1.3.5
Environmental Limits
tion, conductor azimuth, and elevation above sea level.
The electric field produced by overhead power transmission lines is influenced by the following factors:
• Weather: incident solar flux, air temperature, wind
• Line voltage. • Height of conductors above ground. • Configuration of conductors (line “geometry,” con-
speed, and wind direction. The temperatures experienced by terminal equipment must also be limited. In certain circuits, the thermal rating of substation equipment, in series with an overhead line, may determine the “circuit” rating. Disconnect switches, wave traps, current transformers, and other substation equipment all have current ratings that can be lower than those of the line. An example of terminal equipment limitations on older lines is 600 A disconnect switches. At EHV, bundled conductors are employed to reduce the conductor surface electric field and consequent corona phenomena of radio, television, and audibl e n o i s e. B u n d l e d c o n d u c t o r s we re o ri g i n a l ly introduced to lower line reactance and increase the line loadability, and their use for noise reduction was recognized later. Especially at the higher transmission voltages of 500 and 765 kV, the thermal current-handling capacity of a bundled conductor may be far in excess of the ratings of the circuit breakers. In such cases, the thermal limit of the circuit is entirely dominated by the terminal equipment. A survey of utility 345-kV circuit thermal limits in New York State gave the following limitations:
• 41% of the circuits were limited by the line or cable. • 18% of the circuits were limited by current transformers.
• 4% of the circuits were limited by wave traps. • 4% of the circuits were limited by the bus-work. • 3% of the circuits were limited by disconnect
ductor spacing, relative phasing of multi-circuit lines, and use of bundled conductors).
• Lateral distance from the center line of the transmission line.
• Height above ground at the point of field measurement.
• Proximity of conducting objects (trees, fences, buildings) and local terrain. The electric field near ground level produced by an overhead transmission line induces voltages and currents in nearby conducting objects. These objects are typically the size of people, animals, motor vehicles, sheds, and similar-sized bodies. Electric field coupling is capacitive coupling, and can be represented by a current source in parallel with a high source impedance (Norton equivalent circuit). The allowable electric field is limited by the maximum allowed induced current and voltage. For example, the National Electrical Safety Code specifies a maximum of 5 mA short-circuit current induced into the largest vehicle that could be stopped under the line, based on human susceptibility to loss of muscular control (letgo). Thus, if an existing line induces 4.9 mA on a large tractor-trailer, it would not be possible to increase the voltage without taking other measures to limit the electric field.
switches.
• 4% of the circuits were limited by the circuit breakers. Lines and substation equipment may have different thermal ratings for normal and for emergency system conditions. Emergency ratings typically apply for a limited period of time, not exceeding 24 hours and as short
Electric field levels are limited by law in some jurisdictions. Some regulations are specified at the edge of the right-of-way for public exposure. Other regulations are maximum levels on the right-of-way based on induction to an assumed size object. These regulations may restrict
1-7
Chapter 1: Increased Power Flow Fundamentals and Principles
voltage increases on presently existing transmission lines without taking electric field reduction measures. Magnetic field is affected by the same variables as electric field, except line current replaces line voltage, and nearby objects generally have minimal impact on the magnetic field. Magnetic field coupling is generally of significance for objects that parallel the transmission line for a long distance. Such objects include pipelines, telephone and railway signal circuits, and metal fences. Because magnetic field is a function of line current, and current increases during fault conditions, it may be necessary to evaluate magnetic field effects under both normal operation and faults. Magnetic field coupling is inductive coupling, and generally produces low voltages with low source impedances. Increasing current on a transmission line increases the magnetic field, and thus increases magnetically induced voltages and currents. This may be significant in cases such as when a transmission line parallels a railroad right-of-way. This is the inductive coordination problem that has been around since the dawn of the power industry with respect to telephone and railroad signal facilities. Increasing current flow on existing lines may require coordination with parallel infrastructure. In some jurisdictions, maximum magnetic field levels are specified by regulation. If an existing transmission line is operating near the magnetic field limit set by regulation, the ability to increase line current may be impaired, unless measures are taken to reduce the magnetic field levels.
Increased Power Flow Guidebook
Electric fields can be shielded by conducting objects. Vegetation is sufficiently conductive to reduce electric field levels. Grounded wires can be strung under the phase conductors at road crossings to reduce electric field levels. Grounding measures can be taken for fixed objects to eliminate induced voltages. On the other hand, magnetic field shielding is significantly more difficult than electric field shielding. Shielding a transmission line by magnetic materials is impractical. Flux canceling loops have been developed, but incur power loss and complexity in actively driven loops. Shielding is less practical as a mitigation measure for magnetic fields than it is for electric fields. 1.3.6
Examples – Overhead Lines
Figure 1.3-3, adapted from (Gutman 1988), repeats the generalized SIL curve of Figure 1.3-1 with the addition of a curve for thermal limitation. Superimposed on the SIL curve are curves for:
• Thermal limit for a single 1414 kcmil conductor per phase.
• Voltage drop limitation of 5%. • Steady-state stability margin of 35%. The thermal and voltage drop limitation curves cross at a line length of approximately 110 miles. The voltage drop and stability limitation curves cross at a line length of approximately 190 miles. Based on the thermal, voltage, and stability curves, three regions are identified in Figure 1.3-3.
Figure 1.3-3 Three line loading limits: thermal limit, voltage drop, and steady-state stability.
1-8
Increased Power Flow Guidebook
Chapter 1: Increased Power Flow Fundamentals and Principles
• Less than approximately 110 miles line length, the line is thermally limited.
• Between approximately 110 and 190 miles line length, the line is limited by voltage drop.
• Beyond approximately 190 miles, the line is stability limited. Figure 1.3-3 thus illustrates the three regimes of lineloading limits. Figure 1.3-3 further illustrates that, for a specific transmission line example, the data points for the line fall near, but not on, the generalized SIL curve. The fact that the values are similar, but not identical, illustrates the point that the SIL curve is a handy reference for sanity checking and rule of thumb analysis, but is not to be considered exact for any specific line. Sample surge impedance and thermal loading values for transmission lines of different voltages are given in Table 1.3-1. For comparison with the 345-kV example in Figure 1.33, the 230-kV example in Table 1.3-1 has a thermal rating of 440 MW and surge impedance loading of 145 MW. Stability and voltage control limits for this line depend on the system to which it is connected. As an example of voltage drop, assume the 230-kV line is 100 miles long. Further assume that the sending end bus has a voltage of 1.0 per unit, and the receiving end bus has a voltage of 0.95 per unit, a 5% difference. Also assume the 230-kV line is at 1.0 power factor at the receiving end, neither taking nor supplying vars to the bus. In this case, the 230-kV line flow would be 220 MW, about 1.5 times SIL, but half the thermal rating. This result is in line with the 345-kV example given in Figure 1.3-3. Because SIL is primarily related to transmission line series reactance rather than resistance, simple reconductoring would produce only a minor effect on SIL limits such as voltage drop. In this 230-kV example of 5% voltage drop, reconductoring from Cardinal to Falcon ACSR would increase the loading from 220 MW to 230
MW, a minor difference. Adding a second Cardinal conductor per phase to make two conductor bundles would increase the loading to 310 MW. Adding a second conductor per phase has a greater impact on surge impedance, and thus on SIL and line loading. Full use of the 230-kV line’s thermal rating would require system changes to provide var support at the receiving end of the line. The thermal limit is determined by line current and line voltage. Equation 1.3-2 shows that surge impedance loading is proportional to the square of the line voltage. Doubling line voltage doubles the thermal rating of the line, but multiplies SIL by a factor of 4. This has been the driving force during the history of the electric power industry for increasing voltage levels, and sometimes a motivation for voltage upgrades of existing lines. 1.4
CHAPTER PREVIEW
1.4.1
Overhead Lines (Chapter 2)
Overhead transmission lines are the predominant method of transporting power in any but the most urbanized power systems such as the New York City area. Of all the types of power equipment, overhead lines offer the largest opportunities for increased power flow at modest cost. Limits are placed on power flow through overhead lines in order to limit electrical phase shift, avoid excessive voltage drop, and limit the temperature of the current-carrying conductors. The emphasis in this book is on the latter of these limits. Chapter 2 discusses the reasons for limiting the temperature of overhead lines and the consequences of exceeding such limits. The chapter also covers the techniques for modifying the clearance of existing lines, reconductoring them without rebuilding structures, and real-time monitoring of weather and line sag-tensions. A number of interesting case studies are included at the end of the chapter.
Table 1.3-1 Power Flow Limits on Lines and Cables System kV
XL (Ω/mi)
XC (Ω/km)
(MΩ-mi)
Surge Impedance
SIL
Thermal Rating
(Ω)
(MW)
(MW)
(MΩ-km)
Transmission Line Characteristics 230
0.75
0.47
0.18
0.29
367
145
440
345
0.60
0.37
0.15
0.24
300
400
1500
500
0.58
0.36
0.14
0.26
285
880
3000
765
0.56
0.35
0.14
0.26
280
2090
8000
39
3050
2100
Transmission Cable Characteristics 345
.25
.16
.0060
.0097
1-9
Chapter 1: Increased Power Flow Fundamentals and Principles
1.4.2
Underground Cables (Chapter 3)
Chapter 3 provides an overview on underground cable systems and a very brief background on each of the major transmission cable types. As with overhead lines, the discussion on underground cable considers aspects external to a specific cable circuit that may limit power flow regardless of the cable circuit’s rating. The chapter also includes an overview on cable system ampacity, including worked examples. The major barriers to increased underground cable rating are inherent to each cable system type or installation location. Methods for increasing the rating of underground cable—such as surveying the soil thermal resistivity along the route and removing thermal bottlenecks due to other cable circuits or external heat sources—are discussed in some detail. Given the relatively long thermal time constant of underground cables, dynamic rating methods are very attractive ways of increasing the rating. The chapter discusses monitoring methods and the necessary real-time data required for dynamic rating calculations with underground cable. Case studies are included for actual cable uprating projects, and the chapter provides a summary comparison of uprating methods. 1.4.3
Power Transformers (Chapter 4)
Power transformers represent a significant portion of capital investment costs. Under existing conditions in the industry, utility budgets are reduced and networks are being forced to support greater power transfer over existing transmission circuits than ever before. As such, there is increased interest in safely utilizing all available capacity of power transformers. In general, transformer load capacity is limited by equipment (winding and oil) temperatures. Industry standards (IEEE C57.12.00 in the U.S.) specify a maximum average winding rise that defines the rated load. In other words, when operating at rated nameplate current, the average winding rise shall not exceed the given value. Chapter 4 describes the general construction of power transformers, outlines short- and long-term risks related to the loading of transformers, provides an overview of heat transfer mechanisms and describes the four most prevalent thermal models, and discusses factors behind thermal ratings, including ambient air temperature, load, and maintenance considerations.
1-10
Increased Power Flow Guidebook
1.4.4
Substation Terminal Equipment (Chapter 5)
Substation terminal equipment consists of many different types and designs of power equipment. Included in this classification are line traps, oil circuit breakers, SF6 circuit breakers, rigid tubular bus, line disconnects, current transformers, bolted connectors, and insulator bushings. The increase in circuit rating, resulting from applying the various methods of increasing power flow in overhead transmission lines, underground cable, and power transformers is often limited by terminal equipment. In some cases, a large increase in circuit rating may be obtained for a very modest expenditure on terminal equipment rather than a relatively large investment in lines, cables, or transformers. Chapter 5 describes practical, rather simple methods of increasing the power flow through less capital-intensive equipment such as switches, bus, line traps, breakers, and power transformer auxiliary equipment. The chapter includes a summary of terminal equipment types, specific thermal models for each type of equipment, dynamic thermal rating of terminal equipment, and methods of determining specific thermal parameters from field test, laboratory test, and manufacturer heatrun tests. 1.4.5
Dynamic Rating and Monitoring (Chapter 6)
Since the mid-1980s, considerable attention has been paid to increasing the power flow of overhead lines, power transformers, underground cables, and substation terminal equipment by means of monitoring weather and the equipment thermal state and by developing more accurate thermal models. The resulting dynamic thermal rating techniques typically yield increases of 5 to 15% in capacity. Chapter 6 provides an overview of dynamic thermal rating methods. The chapter aims to present a balanced overall view of when dynamic rating methods are appropriate, how they are best implemented in a practical operational application, and how such methods can be applied to complex interconnections consisting of multiple circuits and many circuit elements. The chapter discusses concerns related to dynamic ratings; outlines the need for inspections and/or real-time monitors and the problems that may arise without them; provides an overview on models for overhead lines, transformers, underground cables, and substation terminal equipment; describes the use of DTCR software; identifies operating issues related to dynamic thermal ratings; and describes field studies of dynamic ratings used for overhead lines, transformers, underground cables, substation terminal equipment, and power circuits.
Increased Power Flow Guidebook
REFERENCES
Boteler, D. H. 1994. “Geomagnetically Induced Currents: Present Knowledge and Future Research.” IEEE Transactions on Power Delivery. Volume 9. Number 1. January. pp. 50-58. Dunlop, R. D., R. Gutman, and P. P. Marchenko. 1979. “Analytical Development of Loadability Characteristics for EHV and UHV Transmission Lines.” IEEE Transactions on Power Apparatus and Systems. Volume 98. Number 1. March/April. pp. 606-617. correction May/June. page 699. Federal Power Commission. 1964. National Power Survey. Part II-Advisory Reports. U. S. Government Printing Office. Washington, D. C. October.
Chapter 1: Increased Power Flow Fundamentals and Principles
Koessler, R. J. and J. W. Feltes. 1993. “Voltage Collapse Investigations with Time-Domain Simulation.” IEEE/NTUA Joint International Power Conference. Athens Power Tech Proceedings. Athens, Greece. September 5-8. Lesher, R. L., J. W. Porter, and R. T. Byerly. 1994. “Sunburst—A Network of GIC Monitoring Systems.” IEEE Transactions on Power Delivery. Volume 9. Number 1. January. pp. 128-137. North American Electric Reliability Council (NERC). 1995. “Transmission Transfer Capability.” St. Clair, H. P. 1953. “Practical Concepts in Capability and Performance of Transmission Lines.” AIEE Transactions on Power Apparatus and Systems. Volume 72. Part III. December. pages 1152-1157.
Gutman, R. 1988. “Application of Line Loadability Concepts to Operating Studies.” IEEE Transactions on Power Systems. Vol. 3. Number 4. November. pages 1426-1433.
1-11
Increased Power Flow Guidebook
CHAPTER 2
Overhead Transmission Lines
2.1
INTRODUCTION
The degree to which the maximum power flow can be increased on an existing overhead line depends on its length, the original design margins, environmental concerns, and many other issues. Because power flow on the transmission system is a function of the overall system topology (transmission lines, transformers, generation, series and shunt compensation, and load), system considerations can also limit the maximum power flow on a specific transmission line. Transmission line ratings are sometimes developed on a system basis rather than on an individual line basis. The overall limit may be between operating areas, irrespective of ownership or individual lines, and may change during a day based on system conditions. Sometimes a power transmission line possesses a definite power flow limit based on the design parameters for the specific line; at other times the line as a component of the overall transmission system determines the limit. System limits can result from factors such as voltage drop, possibility of voltage collapse, and system stability, both steady state and transient. Power system limits, on the power flow through individual overhead lines, are described in more detail in Chapter 1, which discusses power system limits on increased power flow. System limits are functions of transmission line reactances in relation to the overall power system. Series reactance, shunt admittance, and their combination, as well as surge impedance are relevant to system transfer limits. Transmission line series inductive reactance is determined by conductor size, phase spacing, number of conductors, relative phasing (double circuit lines), and line configuration. In transmission lines, the series reactance is significantly larger than the series resistance, and is the dominant factor in a first-order explanation of system behavior. For this reason, simple reconductoring of a transmission line results in only minor changes in system power flows. Critical factors related to power flow limits for overhead lines include:
• • • •
Surge impedance loading Voltage drop Thermal limits Environmental limits
2-1
Chapter 2: Overhead Transmission Lines
2.1.1
Increased Power Flow Guidebook
Surge Impedance Loading
• Conductor AC resistance, which itself is a function of
Surge impedance loading (SIL, defined in Equation 2.11) provides a useful rule-of-thumb measure of transmission line loading limitation as a result of the effects of series reactance.
SIL =
2.1-1
For an overhead transmission line, typical surge impedance is on the order of 300 ohms, while for a cable it may be 50 ohms or less. At 345 kV, SIL of an overhead line is on the order of 400 MW. Short lines may be able to carry 800 MW or more, while long lines of exactly the same construction may be limited to less than 400 MW by system considerations. 2.1.2
Voltage Drop
Voltage control on the power system is of concern as system loadings increase. The system voltage distribution is affected by the series inductance and shunt capacitance of the transmission lines. It is not desirable for voltage to vary more than 5%, or at most 10%, from one end to the other. In some cases, a voltage drop limit is placed on power flow corresponding to the maximum allowable decrease in voltage magnitude. The longer the line, generally the lower the power flow required to reach a voltage drop limit. Voltage control is a system problem, and is not generally solved by modifications to any one transmission line. Because voltage drop is primarily a function of line reactance rather than resistance, simple reconductoring does very little to decrease the voltage drop per unit length. Reconductoring an existing 230-kV line by replacing the original 636 kcmil (324 mm2) Hawk ACSR with a 954 kcmil (487mm2 ) Rail ACSR only increases the voltage drop limit by 5%. Adding a second conductor per phase, to form two conductor bundles, results in a significant reduction in series reactance, and yields an increase in the voltage drop power limit. 2.1.3
Thermal Limits
Thermal limits are discussed in considerable detail in this chapter. In brief, the current carrying capacity (thermal rating) of an overhead transmission circuit is determined by the assumed “worst case” weather conditions, assumed conductor parameters, and the maximum allowable conductor temperature. Some of the specific thermal rating parameters are:
• Conductor construction: outside diameter, conductor strand diameter, core strand diameter, number of conductor strands, and number of core strands.
2-2
• Conductor surface condition: solar absorptivity and emissivity.
• Line location: latitude, longitude, conductor inclination, conductor azimuth, and elevation above sea level.
2
V ZS
the conductor temperature.
• Weather: incident solar flux, air temperature, wind speed, and wind direction. 2.1.4
Environmental Limits
The electric field produced by overhead power transmission lines is influenced by the following factors:
• Line voltage • Height of conductors above ground • Configuration of conductors (line “geometry,” conductor spacing, relative phasing of multi-circuit lines, use of bundled conductors)
• Lateral distance from the center line of the transmission line
• Height above ground at the point of field measurement
• Proximity of conducting objects (trees, fences, buildings) and local terrain The electric field near ground level produced by an overhead transmission line induces voltages and currents in nearby conducting objects (St. Clair 1953, Federal Power Commission 1964, Dunlop et al. 1979, Koessler and Feltes 1993, Boteler 1994, Lesher et al. 1994, EPRI 2005). These objects are typically the size of people, animals, motor vehicles, sheds, and similar-sized bodies. Electric field coupling is capacitive coupling, and can be represented by a current source in parallel with a high source impedance (Norton equivalent circuit). Electric field levels are limited by law in some jurisdictions. Some regulations are specified at the edge of the right-of-way (ROW) for public exposure. Other regulations are maximum levels on the ROW based on induction to an assumed size object. These regulations may restrict voltage increases on presently existing transmission lines without taking electric field reduction measures. Magnetic field is affected by the same variables as electric field, except line current replaces line voltage, and nearby objects generally have minimal impact on the magnetic field. Magnetic field coupling is generally of significance for objects that parallel the transmission line for a long distance. Such objects include pipelines,
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
telephone and railway signal circuits, and metal fences. Because magnetic field is a function of line current, and current increases during fault conditions, it may be necessary to evaluate magnetic field effects under both normal operation and faults. Magnetic field coupling is inductive coupling, and generally produces low voltages with low source impedances (St. Clair 1953, Federal Power Commission 1964, Dunlop et al. 1979, Koessler and Feltes 1993, Boteler 1994, Lesher et al. 1994, EPRI 2005).
• Section 2.4, Effects of High-Temperature Operations,
Increasing current on a transmission line increases the magnetic field, and thus increases magnetically induced voltages and currents. This may be significant in cases such as when a transmission line parallels a railroad ROW. This is the inductive coordination problem that has been around since the dawn of the power industry with respect to telephone and railroad signal facilities. Increasing current flow on existing lines may require coordination with parallel infrastructure. In some jurisdictions maximum magnetic field levels are specified by regulation. If an existing transmission line is operating near the magnetic field limit set by regulation, the ability to increase line current may be limited, unless measures are taken to reduce the magnetic field levels.
• Section 2.7, Dynamic Monitoring and Line Rating,
Electric fields can be shielded by conducting objects. Vegetation is sufficiently conductive to reduce electric field levels. Grounded wires can be strung under the phase conductors at road crossings to reduce electric field levels. Grounding measures can be taken for fixed objects to eliminate induced voltages. On the other hand, magnetic field shielding is significantly more difficult than electric field shielding. Shielding a transmission line by magnetic materials is impractical. Flux canceling loops have been developed, but incur power loss and complexity in actively driven loops. Shielding is less practical as a mitigation measure for magnetic fields than it is for electric fields (St. Clair 1953, Federal Power Commission 1964, Dunlop et al. 1979, Koessler and Feltes 1993, Boteler 1994, Lesher et al. 1994, EPRI 1994, EPRI 2005). Chapter 2 includes seven sections:
• Section 2.2, Uprating Constraints, discusses constraints on electrical and mechanical safety, with information on sag-tension calculations, limiting high-temperature sag, constraints related to windinduced conductor motion, electrical clearance, loss of conductor strength, constraints on structural loads, and environmental effects.
• Section 2.3, Line Thermal Ratings, explores the calculation of line thermal ratings, and describes common heat balance methods.
describes annealing, calculation of sag and tension, thermal and creep elongation, and connectors and conductor hardware at high temperature.
• Section 2.5, Uprating without Reconductoring, discusses deterministic and probabilistic methods of uprating without reconductoring.
• Section 2.6, Reconductoring without Structural Modifications, reviews the various reconductoring choices using new commercially available conductors. introduces the principles of dynamic rating methods.
• Section 2.8, Case Studies, includes a number of uprating test cases and an economic comparison of line uprating alternatives. 2.2
UPRATING CONSTRAINTS
2.2.1
Introduction
Increasing the thermal rating of an existing line requires dealing with constraints on electrical and mechanical safety. The uprated line must remain safe under all electrical power flows up to its maximum without compromising the mechanical safety under severe ice and wind loads. This section discusses issues related to constraints on uprating, including determining what constitutes a constraint in various areas of design, operation, and the environment. 2.2.2
Sag-tension Calculations
Normally, “sag-tension” calculations are performed using numerical programs in order to determine the sag and the tension of a conductor catenary as a function of ice and wind loads, conductor temperature, and time. Calculation examples from a program like SAG10 are shown below to illustrate how tension limits are applied and how maximum conductor tension and maximum final high temperature sag are taken for the purposes of strain structure design and tower placement. Details of sag-tension calculation methods are not included, but examples and key references are cited. In the design, uprating, or simple maintenance of power transmission lines, the concern of primary importance is public safety. It is more important that a line be safe than it carry power. Other than designing the supporting structures such that they remain standing under even the most severe weather conditions, the safety of a line is essentially determined by the position of its energized conductors relative to nearby people, buildings, and vehicles. Maintaining minimum distances to nearby 2-3
Chapter 2: Overhead Transmission Lines
objects and people is primarily a matter of limiting the sag of the energized conductors under high mechanical loads and high temperature conditions. In addition to making lines safe, other important constraints are the level of electric and magnetic fields produced (e.g., electric fields increase as the conductor gets closer to the ground), the maximum structure loads during occasional high wind and ice loads, and the maximum temperature at which the energized conductors are allowed to operate. Given standard “worst-case” weather conditions, the thermal rating of an existing line is determined by the maximum allowable conductor temperature. Thus, uprating such lines without reconductoring normally requires finding ways to maintain electrical clearances while operating at a higher conductor temperature.
Increased Power Flow Guidebook
ture is the minimum attachment height, which determines structure height and spacing. In a detailed line design that has many different spans, this sort of sagclearance calculation must be developed for all spans (Ehrenburg 1935, Winkleman 1959). Definitions of the labels in Figure 2.2-1 are as follows:
• “Init” is the initial installed unloaded (with no ice or wind) sag of the conductor. It is typically at a conductor temperature of 10°C to 25°C (50°F to 80°F). This is also typically referred to as the line “ruling span stringing sag.”
• “Final–STC” is the final sag of the conductor at 15oC (60oF) after an ice/wind-loading event has occurred for a short time—typically an hour. STC stands for “short-time creep.”
• “Final–LTC” is the final sag of the conductor at 15oC Figure 2.2-1 is a basic sag-clearance diagram, which illustrates how minimum ground clearance must be maintained under both heavy loading and high temperature events over the life of both new and re-rated transmission lines. The figure shows ground clearance and line sags under normal conditions, high ice/wind load, and high temperature conditions for a ruling (or “equivalent”) span. Note that the sum of the minimum ground clearance, the buffer, and the sag at maximum tempera-
(60oF) after an extended period—typically 10 years— where the conductor simply persists at a conductor temperature on the order of 15°C (59°F) without ice or wind. “LTC” stands for “long-time creep,” which occurs even if heavy ice and wind loads never occur.
• “Max Load” is the sag of the conductor during the specified maximum ice and wind loading at a reduced temperature—typically 18°C to 0°C (0°F to 32°F). Note that the sag prior to this event is normally assumed to be the Init sag and the sag after this event is the Final–STC sag.
• “TCmax” is the sag of the conductor when its temperature is the maximum for which the line is designed—typically 50°C to 150°C. The final sag at 15oC (60oF), prior to this high temperature event, is assumed to be the larger of the Final–STC and the Final–LTC sags. Figure 2.2-1 shows typical behavior of transmission conductors where the sag under maximum ice and wind load conditions is less than that at the maximum temperature. For small or weak conductors experiencing heavy ice loads, this may not be true. Note that the diagram illustrates the “snapshot” nature of traditional sag-tension calculations. The actual conductor sag position at any time in the life of the line depends on the actual mechanical and electrical load history of the line. If the high load event is more severe or persists for a longer time than assumed in determining the Max Load condition, then the corresponding sag at Max Load and the sag increase will be greater. The use of buffers is required because of such uncertainties. Figure 2.2-1 Sag diagram showing sags for various times and loading conditions.
2-4
For transmission conductors made up primarily of aluminum strands under tension, sag never stops increasing
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
with both time and high loading events throughout the life of the line (Aluminum Association 1974, Harvey and Larson 1972, Harvey 1979). That is, the sag at a given conductor temperature (e.g., 15.5°C, or 60oF) increases steadily over the years after construction. However, with moderate unloaded and loaded conductor tensions (typically 15% and 50% of rated strength), the rate of change in sag with each such event decreases over the life of the line. Thus, if a heavy ice load event occurs 10 years after installation, the permanent increase in sag is much smaller than if it occurred in the first 6 months after construction. Similarly, under everyday unloaded conditions, the rate of change in sag will decrease with time, over the life of the line.
important to the correct calculation of maximum tension. Use of a linear modulus will result in an overestimate of the maximum tension.
Tension-Elongation Diagram (Normal) The “tension-elongation” diagram shown in Figure 2.2-2 shows how the conductor tension changes corresponding to the changes in sag position with load, time, and temperature shown in the preceding sag diagram.
The thermal elongation of stranded conductors is essentially the same as that of its component strands. Therefore, for an all aluminum or copper conductor, once the sag at “final” everyday conditions is established, the sag at high temperatures can be calculated and limited with relatively small uncertainty.
The initial unloaded (“Init”) sag corresponds to the initial unloaded (Init) tension. In the design of a new overhead line, increasing this initial tension decreases maximum temperature (Tcmax) sag and can allow the use of fewer and shorter structures. However, increased everyday tension levels also increase the maximum (“Max”) tension loads (and thus the cost) on angle and dead-end structures, and decrease the mechanical selfdamping of the conductor, which can lead to Aeolian vibration-induced fatigue damage unless dampers are applied.
High Temperature Sag with All Aluminum Conductors For example, consider a line section of an all-aluminum, 37 strand (Arbutus) conductor having a ruling span of 600 ft (183 m) installed to meet the following constraints: maximum tension of 50%, 33% initial unloaded at 15°F and 25% final unloaded at 15°F (-9.4 °C). An equally typical SAG10 program line design sag-tension run is shown in Table 2.2-1.
As the temperature of the conductor increases, its length and the resulting sag increase while the line tension decreases. Errors in modeling the conductor modulus at high temperatures have little or no effect on the calculated sag, but the thermal elongation behavior of conductors at high temperatures is very important. As is noted in Section 2.4, the thermal elongation of ACSR can be particularly complex. 2.2.3
Limiting High Temperature Sag
With an older existing line that has reached its final sag, increasing the conductor tension reinitiates creep (though at a reduced rate). It also increases angle and dead-end structure loads (though perhaps not higher than they were upon initial installation) and is likely to increase Aeolian vibration activity. When reconductoring an existing line, an increase in the maximum tension load may lead to the need for reinforcement or replacement of angle and dead-end structures and may be a critical factor in determining whether reconductoring is an economic uprating solution. The modulus (actually the spring constant) of the conductor determines the increase in tension between unloaded and loaded states. Figure 2.2-2 shows typical behavior for a transmission conductor where the difference in tension between unloaded and loaded states may result in a tension increase by a factor of two or more. Specification of a realistic, nonlinear conductor modulus (stress-strain behavior) under high tension loads is
Figure 2.2-2 Tension diagram showing conductor tension for various times and loading conditions.
2-5
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Table 2.2-1 Sag-Tension Calculations for 37 AAC (Arbutus) ALUMINUM COMPANY OF AMERICAN SAG AND TENSION DATA Conductor Arbutus
795.0 kcmil
37 Strands AAC
Area = 0.6234 sq in.
Dia + 1.026 in.
Wt = 0.746 lb/°F
RTS= 13900 lb
Span + 600.0 ft
Creep is a Factor
NESC Medium Load Zone
Design Points
Final
Initial
Temp (°F)
Ice (in.)
Wind (psf)
K (lb/°F)
Weight (lb/°F)
Sag (ft)
Tension (lb)
Sag (ft)
Tension (lb) 6140
15.
.25
4.00
.20
1.451
12.02
5446.
10.65
32.
.25
.00
.00
1.143
12.00
4294.
10.06
5118
0.
.00
.00
.00
.746
8.77
3833.
6.63
5067.
15.
.00
.00
.00
.746
9.67
3475.a
7.27
4621.
30.
.00
.00
.00
.746
10.58
3179.
7.98
4212.
60.
.00
.00
.00
.746
12.34
2727.
9.54
3524.
90.
.00
.00
.00
.746
13.99
2406.
11.19
3006.
120.
.00
.00
.00
.746
15.54
2167.
12.82
2624.
167.
.00
.00
.00
.746
17.78
1897.
15.24
2210.
212.
.00
.00
.00
.746
19.73
1711.
17.37
1941.
a. Design condition.
High Temperature Sag with ACSR Because steel elongates thermally at half the rate of aluminum, the thermal elongation rate of ACSR conductor is less than that of all aluminum conductor. Therefore, older lines (which often have relatively small conductors with high steel content) sag less than all aluminum conductors for the same change in temperature. The degree to which an ACSR conductor’s thermal expansion is less than that of an all aluminum conductor (AAC) is dependent on the ratio of the steel to aluminum area. This ratio, expressed as a percentage, is usually referred to as the ACSR “Type” number. Table 2.2-2 lists the composite thermal elongation of ACSR conductors with different type numbers. Typical values for the coefficient of thermal expansion (α) of an ACSR are shown in Table 2.2-2. Although we have listed composite thermal elongation coefficients for ACSR, in reality the aluminum strands elongate at twice the rate of the steel strands. The reduced thermal elongation coefficient of the composite Table 2.2-2 Coefficients of Thermal Expansion for Bare Stranded Conductors Conductor
Type Number
α (per degree C)
AAC
0
-6 23.0 x 10
36/1 ACSR
3
-6 22.0 x 10
18/1 ACSR
5
21.1 x 10
45/7 ACSR
7
-6 20.7 x 10
54/7 ACSR
13
-6 19.5 x 10
26/7 ACSR
16
-6 18.9 x 10
30/7 or 30/19 ACSR
23
17.5 x 10
2-6
-6
-6
is actually the result of both this difference in expansion with temperature and the change in component tensions that it produces.
Ignoring Aluminum Compression in ACSR at High Temperature Over the past 40 years, the Varney graphical method (Aluminum Company of America 1961) has been the basis of most sag-tension programs. The Alcoa SAG10 program is widely used. The sag-tension Table 2.2-3, taken from the SAG10 program, shows the sag and tension (total, aluminum, and steel component tensions) for initial and final conditions for 30/19, 795 kcmil (405 mm2) ACSR (Mallard) initially sagged so as not to exceed a final unloaded tension of 25% of Mallard’s Rated Breaking Strength at 60oF (15.5oC). NESC Medium Loading conditions and conductor temperatures up to 302oF (150oC) are included. Notice that the knee point temperature, where the aluminum tension goes to zero, under final conditions, occurs at only 90oF (32oC). Figure 2.2-3 shows final sag versus conductor temperature for ACSR (Mallard) in four different ruling span lengths. Note the change in slope of the curves below 50oC where the knee point is predicted to occur. Many older lines that are typical candidates for uprating were designed with high steel ACSR such as 30/19, 30/7, and 26/7. The low thermal elongation beyond the knee point temperature, illustrated in the preceding calculations, makes these older lines attractive candidates for operation at higher temperatures. In such design situations, the difference in predicted sag at high temperature can be very important.
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Table 2.2-3 Sag-Tension Calculations for 30/19, 795 kcmil ACSR (Mallard) ALUMINUM COMPANY OF AMERICAN SAG AND TENSION DATA Conductor Mallard
795.0 kcmil
30/19 ACSR
Area = .7669 sq. in.
Dia + 1.140 in.
Wt = 1.235 lb/°F
RTS = 38400 lb
Span + 600.0 ft
Creep is a Factor
NESC Medium Load Zone
Design Points
Final
Initial
Temp (°F)
Ice (in.)
Wind (psf)
K (lb/°F)
Weight (lb/°F)
Sag (ft)
Tension (lb)
Sag (ft)
Tension (lb)
15.
.25
4.00
.20
1.955
7.80
11283. 3423.A 7859.S
6.83
12880. 4986.A 7894.S
32.
.25
.00
.00
1.667
7.68
9773. 2377.A 7395.S
6.36
11804. 4462.A 7342.S
0.
.00
.00
.00
1.235
5.30
10495. 3193.A 7302.S
4.45
12499. 4972.A 7527.S
15.
.00
.00
.00
1.235
5.79
9600.a 2508.A 7092.S
4.69
11864. 4623.A 7242.S
30.
.00
.00
.00
1.235
6.34
8775. 1860.A 6914.S
4.95
11241. 4277.A 6963.S
60.
.00
.00
.00
1.235
7.56
7357. 693.A 6664.S
5.54
10039. 3605.A 6435.S
90.
.00
.00
.00
1.235
8.65
6432. 0.A 6432.S
6.23
8921. 2966.A 5955.S
120.
.00
.00
.00
1.235
9.26
6010. 0.A 6010.S
7.03
7910. 2373.A 5537.S
167.
.00
.00
.00
1.235
10.27
5422.S 0.A 5422.S
8.45
6580. 1553.A 5027.S
212.
.00
.00
.00
1.235
11.27
4939. 0.A 4939.S
9.94
5600. 894.A 4706.S
257.
.00
.00
.00
1.235
12.30
4528. 0.A 4528.S
11.45
4864. 343.A 4522.S
302.
.00
.00
.00
1.235
13.34
4178. 0.A 4178.S
12.80
4352. 0.A 4352.S
a. Design condition.
Figure 2.2-3 Sag for a “strong” 30/19 ACSR conductor (calculated ignoring aluminum strand compression) as a function of conductor temperature and ruling span length.
2-7
Chapter 2: Overhead Transmission Lines
Considering Aluminum Compression in ACSR at High Temperature Starting with the studies of Barrett at Ontario Hydro (Barrett et al. 1982), the assumption of zero compressive stress in ACSR beyond the knee point temperature has come into question. The question centers not on the correct calculation of the knee point temperature but on whether the aluminum strands can support compressive stresses above it. The Canadian Electrical Association’s STESS software program incorporated Barrett’s research. Inclusion of the compressive effects of the aluminum strands of high steel content conductors such as 26/7 ACSR (Drake) can add as much as 3 ft (0.91 m) to the sag at 150oC in a 1200 ft (366 m) span. The effect is less with smaller ruling spans and with lower conductor temperatures. Recent studies by Rawlins (Rawlins 1998) seem to confirm the existence of compressive effects as well as residual stresses (due to manufacturing) in aluminum strands at high temperatures. The effect on sag at high temperatures appears to be much smaller than those predicted by Barrett. The widely used SAG10 program has incorporated Rawlins’s studies as an optional calculation. In a 1200 ft (366 m) span, Rawlins’s method would add about 1 ft (30 cm) to the sag of a high steel conductor such as Drake at 150oC. Figure 2.2-4 shows a comparison of sag as a function of conductor temperature calculated with the following assumptions:
• The SAG10 computer program with an assumption
Increased Power Flow Guidebook
• The STESS computer program with the default assumption of 10 MPa (1450 psi) for maximum compressive stress and no residual stress. Figure 2.2-5 is a similar plot that shows the somewhat larger sag differences that occur in a 1200 ft (366 m) ruling span. At this point, there is no clear way to determine which of these methods is correct. Indeed, there is no way to be certain that the stress assumptions for any of the calculations is correct for all ACSR conductors installed in old and new lines. However, there is a distinct possibility that the original line design sag-tension calculations, assuming no compressive stress in the multiple aluminum layers, yielded sags above the kneepoint that were too small. The uncertainty centers on how much the sag should be increased to be certain that electrical clearances will be maintained at an increased maximum conductor temperature. 2.2.4
Uprating Constraints Related to WindInduced Conductor Motion
Transmission lines must be designed not only to provide adequate vertical clearance for electrical and safety considerations, but also to allow for adequate horizontal clearance to tall objects and buildings at the edge of the ROW under high wind conditions. This conductor displacement is termed conductor blowout and is normally at its maximum midway between conductor support points, as shown in Figure 2.2-6. Note that the horizontal displacement at midspan (XH) is determined in part by the conductor sag (D).
of zero compressive stress in the aluminum strands.
• The SAG10 computer program with the default assumption of 2500 psi (17.2MPa) residual stress and allowance for aluminum compression.
Figure 2.2-4 Sag at high temperatures calculated with and without aluminum compression.
2-8
The maximum displacement of the outermost conductors from the center of the ROW under high wind conditions can be one of the most important variables in
Figure 2.2-5 Final sags for Mallard ACSR in a 1200-ft span.
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
determining ROW width or for a given ROW width, determining the maximum structure spacing. In addition to blowout in strong cross-winds, wind can cause certain oscillatory conductor motions. See Table 2.2-4. By far the most common oscillatory windinduced motion is aeolian vibration since it occurs under low-speed everyday wind conditions. Unless it is controlled, aeolian vibration can accumulate millions of cycles, which cause fatigue failure of copper, aluminum, or steel strands. A less common, but more dramatic, form of wind-induced conductor motion is ice galloping. It occurs for strong winds in combination with ice on the conductors and can yield high amplitude, oscillatory conductor motions that result in repeated flashovers between the phase conductors or between a phase conductor and a shield wire. The amplitude of wind-induced conductor aeolian vibration is generally less than the conductor diameter. It can be measured with special monitors, but the calcu-
lation methods are complex. Two simple methods of control are widely used: (1) the tension of the line conductors under everyday conditions is limited and; (2) vibration dampers are clamped to the line conductors. In regions where aeolian vibration is a problem, transmission line conductor tensions are typically limited to between 15% and 20% of RBS during the coldest month of the year, and vibration dampers are routinely installed in every span. Ice galloping motions can be predicted in a crude way through the use of ice galloping ellipses. By comparing such ellipses to the spacing between the line conductors, the likelihood of flashovers from galloping can be minimized by providing sufficient phase spacing and by offsetting any vertical phases. Also, since the major axis of the galloping ellipse is proportional to the line conductor sag with ice and wind loading, the amplitude of ice galloping motions can be reduced by minimizing the sag of conductors in the typical span. Wind-induced subconductor oscillation only occurs for bundled phase conductors when wind speeds exceed a certain critical velocity. If uncontrolled, it can result in fatigue damage to spacers and suspension hardware. Oscillations are controlled by keeping bundled conductors at a spacing-to-diameter ratio of about 20 or more and by avoiding uniform spacer spacing. With regard to increasing maximum allowable power flow through existing lines, wind-induced conductor motions are a primary constraint on increasing the line operating voltage, on retensioning the existing conductors to allow operation at higher maximum conductor temperatures, on reconductoring the line with high– temperature, low-sag conductor, and on bundling (adding a second conductor per phase).
Figure 2.2-6 Illustration of midspan conductor blowout due to wind.
Table 2.2-4 Cyclic, Wind-induced Conductor Motions Aeolian Vibration
Ice Galloping
Subconductor Oscillation
Types of Overhead Lines Affected
All
All in regions with ice
Lines with bundled conductors
Approx. Frequency Range, Hz
3 to 150
0.08 to 3
0.15 to 10
Approx. Range of Vibration Amplitudes (Peak-topeak, Expressed in conductor diameters)
0.01 to 1.0
5 to 300
0.5 to 80
Weather Conditions Favoring Conductor Motion Wind Character: Wind Velocity: Conductor Surface: Damage Characteristics: Direct Causes of Damage:
Steady 1 to 7 m/sec (2 to 15 mph) Bare or uniformly iced
3 months to 20 years for damage to occur Conductor fatigue due to cyclic bending
Steady Steady 7 to 18 m/sec (15 to 40 mph) 4 to 18 m/sec (10 to 40 mph) Bare, Dry Asymmetrical, thin ice deposits 1 to 48 hours per occurrence 1 month to 8+ years for damage to occur Repeated Flashovers, High dynamic loads on structures, Conductor clashing, accelerated wear of hardware premature wear of hardware
2-9
Chapter 2: Overhead Transmission Lines
HTLS conductors such as ACSS are particularly advantageous in reconductoring if they are prestressed. When prestressed, ACSS has much higher self-damping than standard ACSR. It can be installed with smaller initial sag, which reduces ice galloping motions and may allow operation of an existing line at higher voltage as well as higher current levels. In lines without vibration dampers, the addition of dampers may allow the line’s existing conductors to be retensioned and operated to a higher maximum temperature without the need for reconductoring. When bundling new conductors with old, the use of a vertical bundle can eliminate the problem of subconductor oscillation while keeping the bundle spacing to no more than 9 to 12 inches. Regardless of the uprating method, wind-induced motions must be thoroughly considered as part of the redesign. 2.2.5
Electrical Clearance
The National Electric Safety Code (National Electric Safety Code 1997) specifies minimum spacings from energized conductors to ground, to objects passing under the line, to buildings nearby, and to other conductors (“underbuild”). These clearances must be maintained under “The maximum conductor temperature for which the line is designed to operate” (NESC 232.A.2). Failure to maintain such minimum distances is a public safety issue of primary importance. The National Electric Safety Code also specifies minimum horizontal spacings from energized conductors to other conductors and objects such as buildings at the edge of ROW. When subjected to transverse wind, the conductor catenaries “blow out,” and the horizontal spacing of energized conductors to buildings, etc. is reduced. This reduction in horizontal clearance can be limited by using heavier conductors or shorter span lengths; reducing energized conductor sag under blowout conditions; using insulators such as V strings, horizontal V, and posts that do not move with wind; and providing generous right-of-way widths. Reducing sag under horizontal blowout conditions is limited by concerns about vibration, but is complementary to uprating methods such as retensioning. Minimum electrical clearances must be maintained under all line loading and environmental conditions. Since the actual sag clearance of transmission lines is seldom monitored, sufficient allowance for this clearance must be included in the process of initial design or in rerating of existing lines. 2-10
Increased Power Flow Guidebook
Applicable Code Clearances In all cases, national codes may apply. In the United States, the National Electric Safety Code (NESC) is applicable. State codes may also apply. Minimum horizontal and vertical distances from energized conductor (“electrical clearances”) to ground, other conductors, vehicles, and objects such as buildings are a function of three things: the line-to-ground voltage, the use of ground fault relaying, and type of object or vehicles. The NESC Rules covers both vertical and horizontal clearances. That is, the code sets minimum spacing for energized conductors both above and next to people, vehicles, and buildings. This chapter considers only vertical clearances since our focus is on high temperature operations (see Tables 2.2-5 and 2.2-6). Horizontal clearances are typically specified for high winds where the transmission line catenaries are horizontally displaced by the wind. In such cases, the conductor temperature is low due to high convection cooling. Ground clearance minimums listed in the NESC code are primarily due to the height of the object or person that may pass beneath the span. For example, a person with an overhead umbrella extended overhead at arm’s length may physically reach 10 ft (3 m) above ground, whereas a railroad car may be as much as 20 ft (6 m) high. The NESC code calls for a minimum ground clearance of 27 ft (8.2 m) for a low-voltage conductor over a railroad and only 16.5 ft (5 m) over “spaces or ways” accessible only to pedestrians. The difference in minimum ground clearance is due primarily to the height of the object under the line. In each case, the clearance between the low-voltage conductor and the top of the conflicting object is approximately the same. Essentially, the minimum vertical ground clearance for any “supply” conductor (0 to 750 V) is defined by the NESC code as 16.5 ft (5 m) for lines going over places such as roads, streets, driveways, parking lots, and farmland, or any other type of land which can be traversed by vehicles. Conductors passing over waterways must generally meet greater clearance requirements. The Influence of Line Voltage on Clearance For those lines having a line-to-ground voltage of 750 to 22 kV, the ground clearance for the 0 to 750 V supply conductor is increased by 2 ft to 18.5 ft (0.6 m to 5.6 m). For lines at higher voltages, the vertical clearance is increased by 0.4 in. (1 cm) for every kV increase in lineto-ground voltage above 22 kV. Note that the voltage used in these calculations of added electrical clearance are based on the maximum operating voltage, which is typically 5% or 10% above nominal.
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Reduced Clearance for EHV Lines with Limited Switching Surge Levels For lines exceeding 98 kV line to ground, the code allows clearances to be calculated based on knowledge of switching surge levels. If the switching surge level is restrained to 2.2 p.u., the clearance at EHV voltages may be decreased. Power System Conditions when Clearances Apply It is impossible to be certain that clearances will be maintained under all foreseeable circumstances. For example, in certain regions, tornadoes may occur, which might cause conductors that are energized to fall to earth. However, it is irresponsible to design lines or line upgrades where clearance violations are likely to occur. The minimum ground clearances specified by the NESC code apply to energized conductors under the three conditions specified in Rule 232A where the temperatures specified are that of the conductor not the surrounding air:
• 50°C (122°F) with no wind displacement. • At the maximum operating temperature for which the line is designed to operate if greater than 50°C (122°F) with no wind displacement. Table 2.2-5 Minimum Vertical Ground Clearances According to NESC C2-1997, Rule 232C L-L/L-G
Basic Clearance @ 22 kV
kV
ft
m
69/40
18.5
5.6
138/80
18.5
161/93
18.5
Clearance Added for Voltage
m
0.7
19.2
5.8
5.6
2.1
20.6
6.3
5.6
2.5
21.0
6.4 6.8
230/133
18.5
5.6
3.9
22.2
18.5
5.6
7.0
25.5
7.8
500/290
18.5
5.6
9.9
28.4
8.7
765/440
18.5
5.6
15.5
34.0
10.4
Table 2.2-6 Minimum Vertical Ground Clearances According to NESC C2-1997, Rule 232D*
KV
Reference Minimum Height Listed in Alternate Clearance for Table 232-3 Clearance Adder Streets ft
m
ft
m
ft
m
69/40
-
19.2
5.9
138/80
-
20.6
6.3
21.0
6.4 6.4
161/93
ness of ice. Even in these days of heavily utilized transmission assets, it is unusual for lines to carry electrical loads that cause the energized conductors to be more than 5°C or 10°C above air temperature. However, given the relatively rare loss (outage) of a major generating station or EHV transmission circuit, electrical loading on HV lines can increase and cause much higher conductor temperatures. Thus, all lines are designed to meet clearances “at the maximum operating temperature for which the line is designed to operate” (see above). Heavy ice loads are also relatively rare events, but in any modern HV or EHV line, the energized conductor sag at 0°C (32°F) with maximum ice is typically less than the sag for high temperature, even when that maximum operating temperature is only 50°C (122°F). Thus, the assurance of adequate clearance involves the behavior of transmission conductors at high temperatures, not under heavy ice load. Transmission line operators typically meet minimum clearance requirements by limiting the current on the energized conductors. The specification of any relationship between the electrical current on the energized conductors and the conductor temperature is left to the discretion of the operator.
Streets ft
345/200
Nominal Voltage L-L/L-G
• 0°C (32°F), no wind displacement, with radial thick-
230/133
14
4.3
7.1
2.2
21.0
345/200
14
4.3
7.1
2.2
21.0
6.4
500/290
14
4.3
12.7
3.9
26.7
8.1
765/440
14
4.3
21.8
6.6
32.4
9.9
* In accord with Rule 232D4, the clearance calculated based on Rule 232D2-3 cannot be less than the clearance calculated for 98 kV under Rule 232C, which is 21.0 ft.
The NESC code describes the minimum clearances in considerable detail as a function of voltage and potentially conflicting activity. The code also prescribes the conditions under which the clearance minimums must be met. The code does not, however, specify: (1) how the temperature of the conductor is to be calculated; (2) how the physical position of the conductor above ground is to be related to this maximum operating temperature; nor (3) how adequate ground clearance can be confirmed under rare occasions of high electrical loading. Consequently, methods of ensuring adequate ground clearance vary widely between transmission line operators. Upgrading Buffers On older transmission lines, the structure placement along the ROW is fixed, and the final sag of the conductor is measurable. Thus any initial spacing buffer added because of uncertainties in structure placement and initial sag can be reduced in uprating. There are, however, certain irreducible uncertainties, and some clearance buffer must be maintained. The traditional method of determining clearances for existing transmission lines involves standard survey methods to determine the conductor attachment points and the sag at span mid-point for one or more spans in 2-11
Chapter 2: Overhead Transmission Lines
each line section. These measurements are typically taken with the line out of service so that the conductor is at air temperature plus some solar rise. Vertical position errors of up to a foot (0.3 m) are easily made in determining the catenary’s position and the attachment heights. Additional errors may be expected in determining the ground clearance since the ground profile is only checked at a few points along the line. In more recent years, several photographic and laserbased methods have been developed. These methods help determine all attachment points at all structures, and provide a complete description of catenary profiles for all three-phase conductors with much better accuracy than is possible with conventional survey methods. Such measurements are seldom done with the line out of service, so the conductor temperature at the time of the survey measurements must be calculated or measured. The result of such detailed survey activity is very impressive and can easily convince the novice that buffers can be eliminated or reduced when upgrading existing lines. This is not the case. Knowing the exact ground clearance with perfect certainty at the conclusion of a laser survey does not mean that one can be certain of adequate clearance under maximum electrical loading. There still remain several uncertainties. 2.2.6
Increased Power Flow Guidebook
Figure 2.2-7 shows the reduction in tensile strength with time and temperature for a sample of 0.081 in. (0.2 cm) diameter hard drawn copper wire, as described in (Hickernell et al. 1949). There are 8760 hours in a year, so the diagram clearly shows that sustained operation at 65οC yields no measurable reduction of tensile strength, sustained operation at 100oC yields a 10% reduction in 600 hours (25 days), and that only 40 hours at 125 o C reduces the wire tensile strength by 10%. Figure 2.2-8 shows similar tensile strength reduction data for 1350-H19 “EC” hard drawn aluminum wire. It
Figure 2.2-7 Annealing of 0.081 in. diameter hard drawn copper wire.
Loss of Conductor Strength
Construction codes also require that maximum conductor tension not exceed a certain percentage of the energized conductor’s breaking strength. A significant reduction in the breaking strength can weaken the energized conductor and lead to a tensile failure during subsequent high ice and wind loading events. To avoid this, the conductor must not operate at a high enough temperature for a long enough period of time so as to reduce its breaking strength more than 10%, and it must not be installed at such a high everyday “unloaded” tension that its strands fatigue due to wind vibration. The American Society for Testing and Materials (ASTM) or the International Engineering Consortium (IEC) standards specify the minimum tensile strength of aluminum and copper wires, which is the stress at which the wire breaks. At temperatures above 75°C, the tensile strength decreases with time. Temperatures below 300°C do not affect the tensile strength of galvanized, aluminum-clad, or copper-clad steel wires. Thus, extended exposure of conductors made up largely of aluminum or copper wires to temperatures above 75oC can eventually lead to tensile failures during high ice and/or wind loading events.
2-12
Figure 2.2-8 Annealing of 1350-H19 hard drawn aluminum wire (Aluminum Association 1989).
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
is taken from (Aluminum Association 1989). In general, tensile strength reduction of aluminum wires at temperatures of less than 90 o C is considered negligible. At 100oC, the tensile strength of the wire is reduced by 10% after 5000 hours, and at 125 oC the tensile strength is reduced 10% after 250 hours. When compared to copper, aluminum appears to anneal somewhat more slowly, though the difference is probably not important in transmission line applications. The source of the copper wire data also noted a significant amount of variation in the annealing rates for wire obtained from different manufacturers. In applying these equations, the cumulative strength reduction for multiple exposures at the same conductor temperature may be found by simply adding up all the hours and calculating the residual strength. However, for multiple exposures at different conductor temperatures, the calculation process is more complex. To determine the cumulative strength reduction for a series of high temperature exposures at different temperatures and times, all exposures must be expressed in equivalent time at the highest temperature before adding. Thus, if an all aluminum conductor consisting of 370.1466 in. diameter strands is raised to 125oC for 100 hours and then at a later time for 50 hours, then the strength reduction can be calculated for 150 hours at 125 oC. If the same conductor is raised to 125oC for 100 hours and then at a later time is raised to 150oC for 50 hours, then the following calculation must be performed: For 100 hours @125oC,
RS = 100 × 100
⎡ ⎛ 0.1 ⎞ ⎤ − ⎢ (0.125 − 0.095 )• ⎜ ⎟⎥ ⎝ 0.1466 ⎠ ⎦ ⎣
= 91.0%
Before undertaking any uprating project, a review of the existing structures and operating records of the line is required. If structural failures at angle or dead-end structures have occurred, any attempt at increasing everyday installed tension is unlikely to succeed. Similarly, if occasional high temperature operations have yielded splice failures, increasing operating temperature levels without replacing or inspecting the line is unwise. On the other hand, if a review of structure and foundation capacity indicates that the line was conservatively designed, and that it has operated for many years without any structural or foundation failures, it may be possible to replace the existing conductor with a new larger conductor without structure modifications. When a conductor span is ice covered and/or exposed to high winds, the effective conductor weight per unit length increases. During occasions of heavy ice and/or wind load, the conductor tension increases dramatically, along with the loads on angle and dead-end structures. Both the conductor and its supports can fail unless these high-tension conditions are considered in the line design. The National Electric Safety Code (NESC) suggests certain combinations of ice and wind corresponding to heavy, medium, and light loading regions of the United States.
2.2-1
At 150oC, RS = 91.0% after 7.2 hours, so the cumulative loss of strength over the two high temperature exposures is equal to the remaining strength after 50 + 7.2 hours. It is 82.1% 2.2.7
For tangent structures, the governing transverse loads are primarily a function of the conductor diameter. Thus the replacement conductor diameter must be within about 10% of the existing conductor to avoid tangent structure modification. For angle and dead-end structures, the governing loads are primarily related to maximum conductor tension. The replacement conductor’s maximum tension should not exceed the original conductor’s initial maximum conductor tension unless these structures are to be reinforced.
Constraints on Structural Loads
Existing structures and foundations were designed for certain maximum transverse wind loads and, for strain structures, for maximum tension loads. Unless the existing structures are to be replaced, retensioning the existing conductor, or reconductoring the line with a new conductor, must be done without greatly exceeding the original design limits on structure loading. If many of the line structures must be replaced, the design solution is not the sort of minimal capital investment solution that this guide emphasizes.
The NESC Code (National Electric Safety Code 1997) also suggests that increased conductor loads due to high wind loads but no ice should be considered as noted in the last column of Table 2.2-7. Certain utilities in very heavy ice areas use glaze ice thickness as much as 2 to 3 in. (5 to 7.6 cm) in order to calculate iced conductor weight. This is especially true if they have experienced extensive line failures due to ice loads in excess of those recommended by the NESC. Similarly, utilities in regions where hurricane winds occur may use wind loads as high as 0.236 psi (1630 Pa). Ice Loading The formation of ice on overhead conductors may take several physical forms such as glaze ice, rime ice, or wet
2-13
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Table 2.2-7 Definition of NESC Loading Areas Loading Districts
Therefore, small diameter conductors may need to have a higher elastic modulus and higher tensile strength than large conductors in heavy ice and wind loading areas to limit the sag.
Light
Extreme Wind Loading
6.5
0
0
318
165
0
0
Horizontal wind pressure (lb/ft2)
4
4
9
16 to 22
Horizontal wind pressure (Pa)
190
190
430
16 to 22
Temperature (°F)
0
+15
+30
+60
Temperature (°C)
-18
-10
-1
+15
angle suspension structures are often determined by infrequent high wind-speed loading.
Constant to be added to the resultant (all conductors) (lb/ft)
0.30
0.20
0.05
0.0
• Wind loading determines the permanent increase in
Constant to be added to the resultant (all conductors) (N/m)
4.40
Heavy Medium Radial thickness of ice (in.)
12.5
Radial thickness of ice (mm)
Wind Loading Wind loading on overhead conductors influences line design in a number of ways:
• The maximum span between structures may be determined by the need for horizontal clearance to the edge of the ROW during moderate winds.
• The maximum transverse loads for tangent and small
conductor sag in areas of light ice loads. 2.50
0.70
0.0
snow. The impact of lower density ice formation is usually considered in the design of line sections at high altitudes. The formation of ice on overhead conductors has the following influence on line design:
Wind pressure load on conductors, Pw, is commonly specified in lb/ft2. Equation 2.2-2 gives the relationship between Pw and wind velocity: Pw (lb / ft 2 ) = 0.00256 ⋅ [Vw ( mph )]
2
Pw ( Pascals ) = 0.0473 ⋅ [Vw ( km / h )]
2
2.2-2
Where Vw = the wind speed in miles per hour.
• Ice loads determine the maximum vertical conductor loads that structures and foundations must withstand.
• In combination with simultaneous wind loads, iced conductor may also yield the highest transverse design loads on structures.
• In regions of heavy ice loads, the maximum sags and the permanent increase in sag with time (difference between initial and final sags) may be due to ice loading. In addition to the NESC loading region, ice loads for use in designing lines may also derive from past experience, state regulations, and analysis of historical weather data. Mean recurrence intervals for heavy ice loadings are a function of local conditions along various routings. Line design software can be used to investigate the impact of a variety of assumptions concerning ice loading. The calculation of glaze ice loads on conductors is normally done with an assumed ice density of 57 lb/ft3 (913 kg/m3). The ratio of iced weight to bare weight depends strongly upon the conductor diameter. As shown in Table 2.2-8, for three different conductors covered with 0.5 in. (1.27 cm) radial glaze ice, this ratio ranges from 4.8 for #1/0 AWG to 1.6 for 1590 kcmil (811 mm 2 ) conductors.
2-14
The wind load per unit length of conductor, Ww, is equal to the wind pressure load, Pw, multiplied by the conductor diameter (including radial ice of thickness t, if any):
Ww (lb / ft ) = Pw ( psf ) Ww ( N / m ) = Pw
[Dc (in) + 2 ⋅ t(in)] 12
[D ( mm) + 2 ⋅ t( mm)] ( Pascals ) ⋅ c 1000
2.2-3
Combined Ice and Wind Loading If the conductor weight is to include ice and wind loading, the resultant magnitude of the loads must be deterTable 2.2-8 Ratio of Iced to Bare Conductor Weight ACSR Conductor
wbare+ wice --------wbare
D
wbare
wice
(in.)
(lb/ft)
(lb/ft)
#1/0AWG-6/1 “Raven”
0.398
0.1452
0.559
4.8
47-kcmil-26/7 “Hawk”
0.858
0.6570
0.845
2.3
1590-kcmil-54/19 “Falcon”
1.545
2.044
1.272
1.6
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
mined. Equation 2.2-4 gives the weight of a conductor under both ice and wind loading: w w +i = (w b + w i ) 2 + (Ww ) 2
2.2-4
Where wb = bare conductor weight per unit length. wi = weight of ice per unit length. ww = wind load per unit length. ww+i= resultant of ice and wind loads. 2.2.8
Environmental Effects
The public considers overhead transmission lines as very visible and, though most power engineers have difficulty in understanding why, unattractive. Thus, one of the primary environmental effects of any transmission line is their visual impact on their surroundings. A great deal of effort has been expended on making lines more visually acceptable with decidedly mixed results. Fortunately, when uprating existing lines, most of the normal opposition to new lines is avoided unless the appearance of the uprated line is significantly changed. Because lines are highly visible and perceived as unattractive, they can have a negative impact on property values. This is typically much less of an issue with the modification of existing lines than with new lines. Figure 2.2.9 shows a comparison of the relative importance of some of the major environmental issues involving overhead lines as deter mined by survey. It is interesting that the top three factors are primarily a matter of human perception or belief, while the three least important issues are matters of physics.
Figure 2.2-9 Median survey results as to why people oppose transmission lines.
Various attempts to reduce the visual impact of lines and the corresponding impact on property values have been made. There have been design competitions to find more visually acceptable structures and research into methods of compacting HV lines so they look more like distribution lines. Probably the most effective way to reduce public opposition to transmission lines concerns putting them away from where people live and work. Clearly, this is not always possible, but as shown in Table 2.2-9, it is quite effective. In the specific case of uprating, a variation on the classic physician’s ethic. “First, do no harm” makes sense. Specifically, uprating techniques that do not raise structure peaks or make conductors more visible from a distance are preferred. This guide emphasizes line uprating methods where the voltage of the line remains the same but current flow is increased. Most of the techniques covered herein will leave the original ground level electric field, electric induction, corona discharge levels and audible noise levels unchanged. However, the ground level magnetic field and magnetic induction levels will increase with the higher line currents. Both environmental effects are linear with current so that maximum original levels are easily estimated by scaling with the increase in rating. Table 2.2-9 The Impact of Distance on Public Opposition to Power Transmission Lines Distance from Line Feeling
Less than 1 mile
Like it
2.3%
3.2%
Don’t care
32.6%
71.3%
Dislike it
65.1%
25.3%
2.3
LINE THERMAL RATINGS
2.3.1
Introduction
More than 1 mile
The temperature and/or sag of overhead power transmission lines can be measured, but seldom are. Rather, in order to avoid excessive sag or loss of strength, a “maximum allowable conductor temperature” is typically specified, and the conductor temperature is kept below this maximum by placing limits on the level and duration of power transferred over the line (MVA or amperes). If such limits are based on worst-case weather conditions, they are called static ratings, and if based on actual weather conditions, they are called dynamic ratings. The calculation of thermal ratings for overhead lines is an essential part of the uprating process.
2-15
Chapter 2: Overhead Transmission Lines
The electrical power conductors of overhead transmission lines carry relatively large electrical currents, are self-supporting, and energized at high voltage. They are stranded from wires of aluminum or copper, which may be reinforced with a steel core. As the current flowing through a conductor increases, its temperature increases, and it elongates. This elongation increases the sag of the conductor between support points, decreasing the clearance to people, ground, other conductors, buildings, and vehicles under the line. Beyond a certain “maximum allowable” sag, the line may flashover, resulting in either a power supply outage or injury to the public. If the conductor temperature remains high for an extended period of time, the strength of the conductor and tensioned connectors may decrease, resulting in mechanical failure during the next occurrence of ice or high wind loading. In the design of a new transmission line, the thermal rating required for reliable system operation can be attained either by selecting a large conductor at a moderate maximum operating temperature or by using a smaller conductor at a higher maximum temperature. The higher sag resulting from higher operating temperatures can easily be accommodated by using taller or more closely spaced structures. In uprating an existing line, it is unusual if the existing conductor can be replaced by a significantly larger conductor since this would increase both transverse wind loads and maximum tension loads, and require costly and time-consuming rebuilding of existing structures. It is also unusual if the existing conductor can simply be operated at a significantly higher temperature without raising the existing attachment points or retensioning the line, since this would lead to unacceptable violations of minimum electrical clearances under maximum electrical loading. 2.3.2
Maximum Conductor Temperature
Modern transmission conductors are typically stranded from aluminum wires with a steel core added where increased strength is required. The temperature limit on all-aluminum or ACSR conductors is based on the maximum sag or maximum loss of strength in the aluminum. Temperature limits for normal ACSR conductors in use today range from 50°C to 150°C (122°F to 302°F). The temperature limit is normally selected at the time the line is designed. The higher this temperature, the higher the thermal capacity of the line, the maximum conductor sag, and the higher (or closer) the structures required to maintain ground clearance. If aluminum or copper conductor temperatures remain high (above 95 °C, or 203 °F) for an extended period of 2-16
Increased Power Flow Guidebook
time, the strength of the conductors and tensioned connectors may decrease, which eventually results in mechanical failure during ice or high wind occurrences. Generally, rating durations are kept short if maximum conductor temperatures are high (e.g., 4 hour maximum at 115 °C [239 °F] and 15 minutes at 125 °C [257 °F]). These high temperature effects on conductor, hardware, and fittings are discussed in detail in Section 2.4. 2.3.3
Weather Conditions for Rating Calculation
Traditionally, power utilities use fixed “worst-case” weather conditions in order to calculate (static) line ratings. The impact of changes in these weather parameters upon thermal line ratings depends on the specific rating situation. Consider an overhead line with 795 kcmil (402 mm2) of aluminum, 26/7, “Drake” ACSR conductor, whose static rating is based upon a maximum allowable conductor temperature of 100oC with an air temperature of 40oC, full summer sun, and a wind blowing perpendicular to the conductor axis at 2 ft/sec (0.61 m/sec). The static rating under these conditions is 1000 A. Clearly, if the current in this conductor is 1000 A with the assumed weather conditions, the conductor temperature is 100 o C. Table 2.3-1 shows how the conductor temperature is affected by small changes in weather conditions. For example, the conductor temperature drops to 92oC if there is no solar heating. The table also shows how the thermal rating (i.e., the current which yields a temperature of 100oC) changes with small changes in weather. Note that with the conductor at a reasonably high temperature and near “worst-case” heat transfer conditions, the overhead line rating and conductor temperature are very sensitive to wind direction, modestly sensitive to Table 2.3-1 Variation in Conductor Temperature and Rating with Weather Conditions (for 795 kcmil [404 mm2], 26/7, “Drake” ACSR conductor with a maximum allowable conductor temperature of 100°C, an air temperature of 40oC, full summer sun, and a wind blowing perpendicular to the conductor axis at 2 ft/sec) Range in Weather Conditions
Line Rating @ 100°C
Conductor Temperature at 1000 A
(amperes)
(°C)
(°F)
None
1000
100
212
Air temp = 39°C
1010
99
210
No sun
1070
92
198
3 ft/sec (0.91m/sec)
1090
90
194
Parallel wind
750
133
271
Increased Power Flow Guidebook
changes in wind speed and solar heating, and less affected by small changes in air temperature. Other minor factors are gradual changes in emissivity and absorptivity of the conductor with age, and seasonal shifts in solar heating. 2.3.4
How Line Design Temperature Affects Line Ratings
Chapter 2: Overhead Transmission Lines
sponds to an increase of 10oC in the line design temperature. For this ACSR conductor, the increase in sag for a 10oC increase in conductor temperature decreases with increasing line design temperature. It is clear from this table why simple physical line modifications (such as raising support points or using “floating” dead-ends) are an effective means of uprating older lines with relatively low design temperatures. Even modest increases in allowable sag result in relatively large increases in rating for such lines. It is also clear why such techniques are not usually helpful in uprating new lines having higher line design temperatures.
Line design temperature is the maximum allowable conductor temperature for a particular line. As noted previously, for normal conventional ACSR, it varies from 50oC to 150oC. The impact of changes in the line design temperature upon thermal line ratings depends on the specific rating situation, but certain observations are possible.
2.3.5
Until the early 1970s, the National Electric Safety Code (National Electric Safety Code 1997) suggested that minimum electrical clearances were to be met at conductor temperatures up to 120 ° F (49 o C). Line thermal capacity was typically calculated by conductor manufacturers for a conductor temperature of 75oC, a temperature sure to avoid possible annealing problems with aluminum and copper.
Around the world, utilities perform overhead line rating calculations in essentially the same way: by setting the heat input from Ohmic losses and solar heating equal to the heat loss due to convection and radiation (EPRI 1995). The specific formulas used to determine the heat balance terms vary somewhat, but normally one of three methods is used – the IEEE method (IEEE 1993), the CIGRE method (CIGRE 1992), or the EPRI DYNAMP method (Black et al. 1983).
In the 1970s, the NESC changed this position and stated that the electrical clearances listed were to be met at “the maximum conductor temperature for which the line was designed to operate, if greater than 50oC, with no wind displacement” (excerpted from Rule 232.A.2). Thus the maximum allowable conductor temperature (MACT) used in line rating calculations may vary from 50oC to 200oC according to available ground clearances, and consistency, with concerns about loss of tensile strength at temperatures above 90oC. Consider an existing overhead line with 795 kcmil (402 mm2) of aluminum, 26/7, “Drake” ACSR conductor, whose static rating is based upon an air temperature of 40oC, full summer sun, and a wind blowing perpendicular to the conductor axis at 2 ft/sec (0.61 m/sec). The rating of this existing line depends on the line design temperature as is shown in Table 2.3-2, where the line design temperature with this ACSR conductor ranges from 50°C to 150oC. For each line design temperature, the line rating is shown. Also shown is the increase in rating that corre-
Heat Balance Methods
Given the same assumed wind speed and direction, the same conductor temperature and the same conductor electrical and physical parameters, the thermal rating found with the three methods is similar if not identical. To illustrate typical values of the heat balance terms, the IEEE method is used in the following development for a Drake ACSR conductor at 100oC. Table 2.3-2 Variation in Line Rating with Design Temperature (for 795 kcmil [405 mm2], 26/7, “Drake” ACSR conductor with an air temperature of 35oC, full summer sun, and a wind blowing perpendicular to the conductor axis at 2 ft/sec [0.61 m/sec]) Increase in Line Rating for 10°C Change in Line Design Temperature
Line Design Temperature
Line Rating
(oC)
(amps)
(amps)
(%)
50
374
213
57
75
797
107
13
100
1039
78
7.5
125
1221
63
5.2
150
1370
54
3.9
2-17
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Radiation Radiation of heat from an overhead conductor is modeled in terms of the absolute temperature of the conductor and its surroundings (taken as the air temperature):
4⎤ ⎡ ⎢ ⎛⎜ T c + 273 ⎞⎟ ⎥ ⎢ ⎝ 100 ⎠ ⎥ qr = 0.0178⋅ D ⋅ ε ⋅ ⎢ ⎥ ⎢ ⎛ T a + 273 ⎞ 4⎥ ⎢−⎜ ⎟ ⎥ ⎢⎣ ⎝ 100 ⎠ ⎥⎦ 4⎤ ⎡ ⎢ ⎛⎜ T c + 273 ⎞⎟ ⎥ ⎢ ⎝ 100 ⎠ ⎥ qr = 0.138⋅ D ⋅ ε ⋅ ⎢ ⎥ ⎢ ⎛ T a + 273 ⎞ 4⎥ ⎢−⎜ ⎟ ⎥ ⎣⎢ ⎝ 100 ⎠ ⎦⎥
100 + 40 = 70DC 2
ρf = 1.029 kg/m (28.14)
W/m
Tfilm =
3
100 + 40 = 70oC 2
ρf = 0.0643 lb/ft3
qc = 0.0205 (1.029)
0.5
qc = 0.283 (0.0643)0.5
0.75
(1.108)0.75
(100–40)1.25
(100-40)1.25 = 12.9 W/ft
= 42.4 W/m
Forced Convection With the IEEE 738 and the CIGRE methods, forced convection is calculated with two separate formulas, and the larger of the two values for forced convection heat loss is used.
W / ft
2.3-1
As an example of radiation heat loss from a bare overhead conductor, consider Drake ACSR at 100oC and an air temperature of 40oC: ⎡ 4 4⎤ ⎢⎛⎜ 373 ⎞⎟ − ⎛⎜ 313 ⎞⎟ ⎥ ⎜ 100 ⎟ ⎥ q = 0.0178 ⋅ 28.14 ⋅ 0.5⋅⎢⎜⎝ 100 ⎟⎠ ⎝ ⎠ ⎥ r ⎢ ⎢⎣ ⎥⎦
⎦⎥
⎡ ⎛ D ⋅ ρ ⋅V ⎢ f w ⎜ q = ⎢1.01+ 0.0372⋅⎜ c1 μ ⎜ ⎢ f ⎝ ⎢⎣ ⋅ k ⋅ (T − T ) W / m f c a ⎡ ⎛ D ⋅ ρ ⋅V ⎢ f w ⎜ q = ⎢1.01+ 0.371⋅⎜ c1 μ ⎜ ⎢ f ⎝ ⎣⎢
⎡ 4 ⎛ 4⎤ ⎛ 373 ⎞ 313 ⎞ ⎥ ⎟ −⎜ ⎟ q = 0.138 ⋅1.108 ⋅ 0.5⋅⎢⎜⎜ ⎜ 100 ⎟ ⎥ ⎢⎝ 100 ⎟⎠ r ⎝ ⎠ ⎣⎢
T film =
⋅k 2.3-2
qr = 24.44 W/m qr = 7.461 W/ft Convection Natural Convection With zero wind speed, natural convection occurs, where the rate of heat loss is:
q c = 0.0205 ⋅ ρ f0.5 ⋅ D 0.75 ⋅ (T c - T a )1.25W / m q c = 0.283 ⋅ ρ f0.5 ⋅ D 0.75 ⋅ (T c - T a )1.25 W / ft
f
⋅ (T − T ) W / ft c a
⎛ D⋅ρ f ⋅Vw ⎞ q = 0.0119⋅⎜ ⎟ c2 μ f ⎝ ⎠
(
⋅k ⋅ T −T f c a
)
(
)
0.52 ⎤ ⎥ ⎥ ⎥ ⎦⎥
0.52 ⎤ ⎥ ⎥ ⎥ ⎦⎥ 2.3-5
0.6
W /m
⎛ D⋅ρ f ⋅Vw ⎞ q = 0.1695⋅⎜ ⎟ c2 μ f ⎝ ⎠ ⋅k ⋅ T −T f c a
⎞ ⎟ ⎟ ⎟ ⎠
⎞ ⎟ ⎟ ⎟ ⎠
0.6
W / ft 2.3-6
2.3-3
Taking our example of Drake ACSR at 100oC, the natural convection heat loss is:
q = 0.0205 ⋅ ρ 0.5 ⋅ D 0.75 ⋅(T −T )1.25 (5s ) c f c a 0 . 5 1 . 25 ⋅(T −T ) q = 0.283⋅ ρ c f c a where: D = 28.14 mm Tc = 100°C Ta = 40°C
2-18
where: D = 1.108 in. TC = 100oC Ta = 40oC
2.3-4
The first two equations apply at low winds, but are too low at high speeds. The last two equations apply at high wind speeds, being too low at low wind speeds. At any wind speed, the larger of the two calculated forced convection heat loss rates is used. The convective heat loss rate is multiplied by the wind direction factor, Kangle, where φ is the angle between the wind direction and the conductor axis:
K angle = 1.194 - c os (φ ) + 0.194 cos (2φ ) + 0.368 sin (2φ ) 2.3-7
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Referring once again to our example of Drake ACSR at 100oC we have: 0.52 ⎤ ⎡ ⎛ 28.14 ⋅1.029 ⋅ .6096 ⎞ ⎢ ⎥ ⎟ q c1 = ⎢1.01 + 0.0372 ⎜ ⎥ 5 − ⎜ ⎟ 2.04 ⋅10 ⎢ ⎥ ⎝ ⎠ ⎣ ⎦ .0295 ⋅ (100-40) = 82.295 W/m
According to the IEEE solar model, the maximum possible conductor solar temperature rise above air temperature is on the order of 15 o C (for still air). Field measurements of actual lines indicate that the typical solar rise is in the range of 5°C to 10°C.
0.52 ⎤ ⎡ ⎛ 1.108 ⋅ 0.643 ⋅ 7200 ⎞ ⎥ q c1 ⎢1.01 + 0.371⎜ ⎟ 0.0494 ⎢ ⎥ ⎝ ⎠ ⎣ ⎦ .00898 ⋅ (100-40) = 25.052 W/ft 2.3-8
⎛ 28.14 ⋅1.029 ⋅ .6096 ⎞ q c 2 = 0.0119 ⋅ ⎜ ⎟ ⎜ ⎟ 2.04 ⋅10 −5 ⎝ ⎠ .0295 ⋅ (100-40) = 76.88 W/m
0.6
⎛ 1.108 ⋅ 0.0643 ⋅ 7200 ⎞ q c 2 = 0.1695 ⋅ ⎜ ⎟ 0.0494 ⎝ ⎠ .00898 ⋅ (100-40) = 23.464 W/ft
0.6
With reference to Table 2.3-3, with a solar altitude of 70 degrees (noon in June in New York) and clear atmosphere, the solar heat flux to a surface perpendicular to the sun’s rays is approximately 1020 watts/ft 2 or 95 watts/m2. The maximum heat input to the conductor is therefore: qC = 0.5 ⋅1020 ⋅ 0.0281 = 14.3
2.3-9
Now select the larger of the two calculated convection heat losses. qc = 82.295 W/m
the angle of the solar beam relative to the line direction, and the conductor absorptivity (the fraction of incident solar radiation absorbed by the conductor). The resulting temperature rise above air temperature is a function of the conductor absorptivity and diameter as well as the wind speed and direction.
qc = 25.052 W/ft
Since the wind is perpendicular to the axis of the conductor, the wind direction multiplier, Kangle, is 1.0, and the forced convection heat loss is greater than the natural convection heat loss. Therefore, the forced convection heat loss will be used in the calculation of thermal rating. Notice that if the wind had been nearly parallel to the line at 10o from the line direction, the wind direction multiplier would be 0.517, and convection cooling would have been similarly reduced. Also, notice that the heat loss with no wind (natural convection) is much less than that for forced convection with even the low 2 ft/sec (0.61 m/sec) wind. Solar Heating Overhead conductors are typically 5oC to 10oC above air temperature due to solar heating alone, even if the current in the conductor is zero. The conductor heat balance described in these notes applies when there is only solar heat input as well as when the conductor carries electrical current. The solar heat into the conductor in direct sun is a function of the solar heat flux density,
W/m
qC = 0.5 ⋅ 95 ⋅ 0.092 = 4.4 W/ft
2.3-10
Ohmic Losses Conductor resistance per unit length and the electrical current on the line determine the Ohmic losses. The resistance of a stranded conductor is a function of the conductivity of the component wires, the frequency, the current density, the temperature of the wires, and the stranded construction. Resistance values at 25°C and 75oC are readily available from the manufacturer or the Aluminum Association.
The IEEE standard suggests that electrical resistance may be calculated solely as a function of conductor temperature, ignoring dependence on current density. For example, the values of conductor resistance at high temperature, Thigh, and low temperature, Tlow, may be taken from the tabulated values in the Aluminum Association Handbook (Aluminum Association 1989). The conduc-
Table 2.3-3 Total Heat Flux Received by a Surface at Sea Level Normal to the Sun’s Rays Solar Altitude, Hc
QS for a Clear Atmosphere
QS for an Industrial Atmosphere
Degrees
(w/m2)
(w/ft2)
(w/m2)
(w/ft2)
60
1000
92.9
771
71.6
70
1020
95.0
809
75.2
80
1030
95.8
833
77.4
90
1040
96.4
849
78.9
2-19
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
tor resistance at any other temperature, TC, is found by linear interpolation according to Equation 2.3-11. R(T c) =
⎡ R(T high) - R(T low)⎤ ⎢⎣ T high - T low ⎥⎦
* (T c - T low)+ R(T low)
2.3-11
This method of resistance calculation allows the user to calculate the high and low temperature resistance values by whatever means is appropriate. See, for example, references (Douglass and Rathbun 1985 and (Lewis and Tuttle 1958). In the example calculation, the resistance of the Drake ACSR conductor is calculated for a conductor temperature of 100oC:
⎛ R(75) − R( 25) ⎞⋅(100 − 25) R(100 ) = R( 25 ) +⎜ ⎟ 72 − 25 ⎝ ⎠ ⎡ 8.688⋅10 − 5 −7.283⋅10 − 5 ⎤ ⎥⋅ 75 =7.283⋅10 − 5 + ⎢ 50 ⎢ ⎥ ⎣ ⎦ −5 =9.390⋅10 Ω / m
⎛ R(75) − R( 25) ⎞⋅(100 − 25) ⎟ 72 − 25 ⎝ ⎠
R(100 ) = R( 25 ) +⎜
⎡ 2.648⋅10 −5 −2.220⋅10 −5 ⎤ =2.220⋅10 −5 + ⎢ ⎥⋅ 75 50 ⎣ ⎦ =2.862⋅10 −5 Ω / ft 2.3-12
Steady-State Thermal Rating Now that the radiation heat loss, the convective heat loss, the solar heat input and the resistance of the conductor have been determined, the steady-state thermal rating can be calculated as follows:
I=
qc + qr − qs R(100)
I=
qc + qr − qs R(100)
2.3-13
For the example case: qc = 82.295 W/m qr = 24.44 W/m qs = 14.0 W/m (from equations) R(100) = 9.390⋅10-5 Ω/m I=
82.295+ 24.44 −14.0 9.39010
= 994 A
2-20
−5
qc = 25.052 W/ft qr = 7.461 W/ft qs = 4.26 W/ft (from equations) R(100) =2.862·10-5Ω/ft I =
Thermal Rating – Dependence on Conductor Parameters The rating of bare overhead conductors depends on the various conductor parameters including (see Table 2.3-4):
• Outside diameter • Emissivity and absorptivity • Electrical resistance per unit length At the time of construction, the choice of conductor type and size defines the resistance and outside diameter. Normally, the emissivity and absorptivity of new aluminum conductor are initially in the range of 0.2 to 0.3 but increase to values close to 1.0 as the conductor ages. Figure 2.3-1 shows this increase in emissivity with time for energized conductors. The actual rate at which the conductor emissivity and absorptivity increase with time is a function of the line voltage and the density of particulates in the air. Two observations, however, can be made. The emissivity and absorptivity are correlated, so it is unlikely that one parameter will be high and the other low. Also, new conductors will have emissivity and absorptivity values in the range of 0.2 to 0.3, and old conductors will have values in excess of 0.5. As stated above, resistance and diameter are tightly correlated. Thus, aluminum stranded conductors of a given diameter will have a corresponding resistance per unit length. The exceptions to this are:
• The component strands have a different conductivity from that of standard aluminum (e.g., copper).
• Conducting strands are trapezoidal rather than round (e.g., TW conductor).
• The steel core strands are not used or are replaced by aluminum-clad steel wires (e.g., ACSR/AW). Table 2.3-4 Illustration of the Effect of Diameter, Resistance, Emissivity and Absorptivity on Thermal Rating Resistance Outside Emissivity Conductor Diameter @ 25 °C and Description (Ohms/mi) Absorptivity (in.)
Thermal Rating (A)
Drake
1.108
0.1170
0.5 & 0.5
996
Drake/TW
1.010
0.1170
0.5 & 0.5
976 (-2.0%)
Drake/AW
1.108
0.1129
0.5 & 0.5
1014 (+1.8%)
Arbutus AAC
1.026
0.1200
0.5 & 0.5
962 (-3.4%)
CU 500 kcmil
0.811
0.1196
0.5 & 0.5
909 (-8.7%)
Drake
1.108
0.1170
0.9 & 0.9
1046 (+5.0%)
Drake
1.108
0.1170
0.3 & 0.3
971 (-2.5%)
25.052 + 7.461 − 4.26 2.862 ⋅ 10 − 5
= 994 A
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Figure 2.3-1 Transmission line conductor emissivity as a function of time (House et al. 1963)
2.3.6
Thermal Ratings—Dependence on Weather Conditions
It is clear from the preceding discussion that the thermal rating of an overhead line depends on the weather conditions along it, as well as on the type of conductor and its maximum allowable operating temperature. Many utilities around the world adjust their line ratings for seasonal variation in air temperature, recognizing that air temperature is lower and ratings can be higher in the winter than in the summer. Of course, in areas where the seasonal change is small (near the equator), or where the fluctuations in any season are larger than the seasonal average difference, this does not make sense. Other utilities adjust thermal ratings for day and night by including or ignoring solar heating, and others adjust the wind speed, using a more conservative (lower) wind speed for continuous ratings than for emergency ratings, which tend to have a low probability of occurrence. Many utilities have installed real-time monitoring systems, adjusting their line ratings for actual real-time wind speed, wind direction, solar heating, and air temperature. This technique is discussed in more detail in Section 2.8.
Table 2.3-5 Effect of Weather Conditions on Thermal Ratings. (In all cases, the conductor is 26/7 795 kcmil (0.61 mm2) ACSR (Drake) with emissivity = absorptivity = 0.5, Direct sun on June 10, clear air, at sea level, latitude = 40° with the conductor at 100°C.)
Air Temperature (°C)
Wind Speed (ft/sec)
Wind Direction Relative to the Line (90 = Perpendicular)
40
2
90
2 PM
996
40
2
90
12 PM
986 (-0.8%)
40
2
90
6 PM
1045 (+4.9%
30
2
90
2 PM
1081 (+8.5%)
40
0
90
2 PM
838 (-15.6%)
40
3
90
2 PM
1183 (+18.7%)
40
6
10
2 PM
968 (-2.8%)
Time of Day
Thermal Rating Amperes
In order to illustrate the effect of changing weather conditions on ratings, consider Table 2.3-5.
2-21
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
By reviewing this limited series of rating calculations, a number of important aspects of line rating dependence on weather can be drawn:
solar heating equals the heat loss by convection and radiation.
• Rating variation due to solar heating changes
Immediately after the current step change (t = 0+), the conductor temperature is unchanged (as are the conductor resistance and the heat loss rate due to convection and radiation), but the rate of heat generation due to Ohmic losses has increased. Therefore, at time t = 0+, the temperature of the conductor begins to increase at a rate given by the non-steady-state heat balance equation.
throughout the day is less than 5%.
• Air temperature variation is important. A difference of 10°C in air temperature causes a line rating change of nearly 10%.
• Relatively small differences in wind speed, in the range of 0 to 3 ft/sec (0.91 m/sec) can make a big difference in the line rating, generally 10% to 20%.
• The wind direction relative to the line is as important as the speed. A 6 ft/sec (1.8 m/sec) wind blowing near parallel to the line (10°) yields a slightly lower line rating than a 2 ft/sec (0.61 m/sec) wind blowing perpendicular to the line. 2.3.7
Transient Thermal Ratings
The need for increased thermal capacity in overhead lines is often driven by occasional, sharp increases in load after certain system contingencies. For example, an HV line might only reach high current levels after the loss of an EHV line or a critical generating facility. Since these occasions of high load occur infrequently and may persist for short time periods, it is often useful to consider transient thermal ratings for lines. The temperature of an overhead power conductor is constantly changing in response to changes in electrical current and weather. In this method, however, weather parameters (wind speed and direction, ambient temperature, etc.) are assumed to remain constant, and any change in electrical current is limited to a step change from an initial current, Ii, to a final current, If, as illustrated in Figure 2.3-2. Immediately prior to the current step change (t = 0–), the conductor is assumed to be in thermal equilibrium. That is, the sum of heat generation by Ohmic losses and
As time passes, the conductor temperature increases, yielding higher heat losses due to convection and radiation, and somewhat higher Ohmic heat generation due to the increased conductor resistance. After a large number of “thermal time constants”, the conductor temperature approaches its final steady-state temperature (Tf). The transient thermal rating is normally calculated by repeating the preceding calculations of Tc(t) over a range of If values, then selecting the If value that causes the conductor temperature to reach its maximum allowable value in the allotted time.
q c + q r + mC p
dT c = q s + I 2R (T c ) dt
1 dT c ⎡⎣R(T c ) I 2 + q s - q c - q r ⎤⎦ = dt mC p The transient thermal rating of an overhead line is dependent on the duration of the elevated current, the maximum temperature that the conductor is allowed to attain during the rating period, and on the starting temperature of the conductor. For example, with the Drake ACSR that was used for rating calculations previously, the transient ratings for various rating durations, maximum temperatures, and starting temperatures are as shown in Table 2.3-6. The advantage to using transient ratings is that the line can be loaded above its continuous rating without violating the constraints on sag clearance or annealing, but Table 2.3-6 Transient Ratings Versus Rating Duration
Figure 2.3-2 Temperature response of a bare overhead conductor to a step-change in current.
2-22
Rating duration
Maximum temp
Starting Temp
(Minutes)
(oC)
(oC)
(A)
continuous
100
N/A
1040
60
100
50
1045
30
100
50
1090 (+4.8%)
15
100
50
1230 (+18.3%)
15
100
75
1135 (+9.1%)
Rating
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
the drawback is that the load must be reduced to the continuous rating or below within a short time (15 to 30 min). See, for example, (Black and Rehberg 1985) and (Davidson 1969). 2.4
EFFECTS OF HIGH-TEMPERATURE OPERATIONS
2.4.1
Introduction
For any given high-voltage conductor, there are usually at least two current limits specified—the conductor’s normal rating, and the emergency rating (see Section 2.3). The conductor’s normal rating specifies how much current may flow in the circuit on a continuous basis, whereas the emergency rating specifies how much current can flow under emergency conditions for a specified amount of time—e.g., 30 minutes. A typical emergency rating may be applicable in the case where there is an unexpected outage on a parallel circuit requiring a short-duration increase in the load flow. The above “normal” current flow that is required during emergency loading will, if it remains unchecked, result in a thermal overload of the circuit, or significantly reduced clearances leading to a flashover of the circuit. Regardless of the case, the two issues that require attention are the loss of conductor strength and increased conductor sag. Ideally, transmission line operators aim to maximize the load on a particular circuit while minimizing the annealing (softening) of the circuit’s conductor. Annealing causes a decrease in the conductor’s strength and performance, necessitating the eventual replacement of this component. Because of the difficulty associated with taking a line out of service, and the large expense associated with the replacement of a circuit’s conductor, the operator clearly needs to balance the need for increased load flow with the economic risk associated with the premature replacement of the component, and the loss of service life or the safety risk associated with providing inadequate clearances. This section reviews issues related to the effects of hightemperature operation, including annealing, calculation
of sag and tension, thermal and creep elongation, and connectors and conductor hardware at high temperature. 2.4.2
Annealing of Aluminum and Copper
The American Society for Testing and Materials (ASTM) standards and the International Engineering Consortium (IEC) standards specify the minimum tensile strength of aluminum and copper wires, which is the stress at which the wire breaks. For aluminum and copper wires, the tensile strength of the materials decreases with time if operated at temperatures above 75°C, while the tensile strength of galvanized, aluminum-clad, or copper-clad steel wires remains constant at temperatures below 300°C. Thus, the extended exposure of conductors made up largely of aluminum or copper wires to temperatures above 75oC can eventually lead to tensile failures during high ice and/or wind loading events. Table 2.4-1 shows experimental results for a test conducted by Troia (Troia 2000). The high-temperature simulation used an ACSR conductor “Raven” with a 6/1 stranding ratio. In this study, four sets of conductors and connectors, and three sample loops, were operated at a temperature of 100°C, and cycled for 125, 250, and 500 cycles, respectively. The fourth set of samples was continued to 1000 current cycles at the 100°C temperature rise. A second group of four sets of sample test loops were operated at 175 ° C, and the current cycle counts were 125, 250, 500, and 1000. Upon completion, a Rockwell H scale was used to measure the hardness of each sample, and as expected, the average hardness was determined to be directly proportional to the temperature and duration of heating. Conductors heated to 100 ° C exhibited a decrease in hardness of up to 22% after 1000 cycles, and conductors heated to 175 ° C showed a decrease in hardness of up to 92.5% after only 250 cycles. Thus, annealing of the conductor was extensive at the higher operating temperature, and hardness readings could not be measured for conductors having been cycled 500 or 1000 cycles. Clearly, the results of this and other studies indicate that the prolonged operation of high-voltage conductors including ACSR at very high temperatures reduces the
Table 2.4-1 Hardness Resultsa Conductor
ACSR (6/1) ‘Raven’
Cycle Temp Average Hardness % Difference Temp Average Hardness % Difference 0
-
33
-
-
37.3
-
125
100
23.6
28.5
175
15.9
57.4
250
100
19.4
41.2
175
2.8
92.5
500
100
20.8
37.0
175
0b
-
1000
100
22.6
31.5
175
0b
-
a. Rockwell H scale, 1/8 in. ball, 60 kgs. b. Material hardness too soft for accurate readings on Rockwell H scale.
2-23
Chapter 2: Overhead Transmission Lines
mechanical strength, integrity, and performance of the overhead system. It is also clear that the damage to the aluminum is of a cumulative nature and that the prolonged high temperature operation will significantly reduce the expected service life of the delivery system. Figure 2.4-1 shows the influence of prolonged hightemperature operation on the tensile strength of aluminum conductor. The graph shown has been developed based on test data of 1350-H19 “EC” hard drawn aluminum wires. In general, tensile strength reduction of aluminum wires at temperatures of less than 90 o C is considered negligible, and the effect of prolonged operation at this temperature will have very little effect on the service life of the aluminum conductor. At 100 oC, the
Increased Power Flow Guidebook
tensile strength of the wire is reduced by 10% after 5000 hours, equivalent to a little more than a half a year, and at 125oC, the tensile strength of the aluminum conductor is reduced 10% after 250 hours, a little more than 10 days of continuous operation. The effects of the hightemperature operation on the aluminum conductor are irreversible, and the damages experienced by the conductor are cumulative. Aluminum anneals at a slower rate than copper wire when exposed to identical conditions. Even though the use of copper conductors has significantly decreased over the years, a large number of low- to medium-voltage lines with copper conductors are still operated. The issues associated with the prolonged operation of these wires at very high temperatures are similar to the issues encountered with aluminum conductors. For example, Figure 2.4-2 shows the reduction in tensile strength with time and temperature for a sample of 0.081 in. (0.2 cm) diameter hard drawn copper wire. Since there are 8760 hours in a year, the logarithmic diagram clearly shows that the sustained operation of the copper wire at 65oC yields no measurable reduction in the tensile strength, while the sustained operation of a copper wire at 100 o C yields a 10% reduction in the tensile strength in 600 hours (25 days). More critically, the operation of the same wire at a temperature of 125oC for less than 40 hours reduces the wire tensile strength by 10%. The remaining strength of AAC, AAAC, ACAR, and ACSR conductor wires can be estimated with the following predictor equations. The use of these equations is acceptable even in the case in which several emergencyrating episodes have occurred.
Figure 2.4-1 Annealing of 1350-H19 hard-drawn aluminum wire.
2-24
Figure 2.4-2 Annealing of 0.081–in. diameter hard-drawn copper wire (Southwire).
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Definition of Terms:
Predictor Equations: (English)
RS1350 = Residual aluminum (1350 Alloy) strength as a percentage of initial strength [%].
AAC:
RS6201 = Residual 6201 Alloy strength as a percentage of initial strength [%]. RSCOM = Residual strength of composite conductor as a percentage of initial strength [%]. T
= Temperature [°C].
t
= Elapsed time [hours].
d
= Strand diameter [mm, in.].
A1350
= Area of aluminum (1350 Alloy) strands [sq mm, sq in.].
A6201
= Area of 6201 alloy strands [sq mm, sq in.].
AT = Total area [sq mm, sq in.]. STR1350= Calculated initial strength of the aluminum (1350 Alloy) strands [N, lbs]. STRST = Calculated initial strength of the steel core [N, lbs]. STRT
= Calculated initial strength of the conductor [N, lbs].
Predictor Equations: (Metric) AAC: ⎛ 2.54 ⎞ − (0.001 T - 0.095 )⎜⎜ ⎟⎟
⎝ d ⎠ RS1350 = (- 0.24 T + 134 ) t 2.4-1 If (-0.24T + 134) > 100, use 100 for this term.
AAAC: ⎛ 2.54 ⎞ − (0.0012 T - 0.118 )⎜ ⎟
⎝ d ⎠ RS 6201 = (- 0.52 T + 176 ) t If (-0.52T + 176) > 100, use 100 for this term.
2.4-2
ACAR: RSCOM
⎛A = (RS1350 )⎜⎜ 1350 ⎝ AT
⎛A ⎞ ⎞ ⎟⎟ + (RS6201 )⎜⎜ 6201 ⎟⎟ ⎝ AT ⎠ ⎠
⎛ STR1350 RSCOM = (RS1350 )⎜⎜ ⎝ STRT ACSR: ACSR:
⎛ STRST ⎞ ⎟⎟ + (109 )⎜⎜ ⎝ STRT ⎠
RSCOM = (134 - 0.24 ) t (0.241 - 0.00254T ) d
RSCOM = (134 - 0.24 ) t −(0.001T - 0.095 ) 2.4-6 If (-0.24T + 134) > 100, use 100 for this term. AAAC: 0.1 d
2.4-7 RSCOM = (- 0.52T + 176 ) t − (0.0012T - 0.118 ) If (-0.52T + 176) > 100, use 100 for this term. ACAR: 0.1 d
⎛A RSCOM = (RS1350 )⎜⎜ 1350 ⎝ AT ACSR:
⎛A ⎞ ⎞ ⎟⎟ + (RS 6201 )⎜⎜ 6201 ⎟⎟ ⎝ AT ⎠ ⎠
⎛ STR1350 RSCOM = (RS1350 )⎜⎜ ⎝ STRT
⎛ STRST ⎞ ⎟⎟ + (109 )⎜⎜ ⎝ STRT ⎠
2.4-8
⎞ ⎟⎟ ⎠
2.4-9
As previously shown, when applying these equations, the cumulative strength reduction for multiple exposures at the same conductor temperature is additive; however, this is not true for multiple exposures at different conductor temperatures. To determine the cumulative strength reduction for a series of high-temperature exposures at different temperatures and times, each of the exposures must be expressed in equivalent time at the highest temperature experienced by the conductor before finding the equivalent time. The following examples illustrate a possible scenario that an ACSR and AAC conductor might experience during one year of service. Example 2.4-1: The conductor is 795 kcmil (405 mm2)ACSR “Drake”. During one year of operation, it is subjected to 7500 hours at 75°C, 1200 hours at 100°C, 50 hours at 125°C, and 10 hours at 150°C. What is the remaining strength (RS) of the conductor?
Using Equation 2.4-5, we know the following equation: 2.4-3
⎞ ⎟⎟ ⎠ 2.4-4
ACSR:
RSCOM = (134-0.24) t(0.241 - 0.00254T)
⎛ 0.1 ⎞ ⎜ ⎟ ⎝ d ⎠
and, if (134 – 0.24T) >100, use 100; if (0.241- 0.00254T) > 0, use 0.
0.1
2.4-5
a) 7500 hours at 75°C 0.1
0.241 - 0.00254T ) d RSCOM = (134-0.24 ) t (
= (134 - (0.24 x 75)) x (7500)
⎛ 0.1 ⎞ -(0.241 0.00254T)⎜ ⎟ ⎝ 1.108 ⎠
= 100%
7500 hours at 75°C has 100% remaining, which equals 0 minutes at 150°C. 2-25
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
b) 1200 hours at 100°C ⎛ 0.1 ⎞ -(0.241 - 0.00254T)⎜⎝ 1.108 ⎟⎠
= (134 - (0.24 x 100)) x (1200) = 99.17%
RS1350
= (134 - 0.24 T) t
-(0.001 T - 0.095)⎛⎜ 0.1 ⎞⎟ ⎝ d ⎠
= (134 - (0.24 x 75)) x (7500) -(0.001(75) - 0.095)
⎛ 0.1 ⎞ ⎜ ⎟ ⎝ 1.026 ⎠
= 98.3%
1200 hours at 100°C has 99% remaining, which equals 20 minutes at 150°C. c) 50 hours at 125°C
7500 hours at 75°C has 98.3% remaining, which equals 1 hour at 150°C. b) 1200 hours at 100°C
= (134 - (0.24 x 125)) x (50)-(0.241 -
⎛ 0.1 ⎞ 0.00254T) ⎝⎜ 1.108 ⎠⎟
= (134 - (0.24 x 100)) x (1200) -((0.001 x 100) - 0.095) = 87.4%
= 99.17%
50 hours at 125°C has 99% remaining, which equals 2 hours at 150°C.
⎛ 0.1 ⎞ ⎜ ⎟ ⎝ 1.026 ⎠
1200 hours at 100°C has 87.4% remaining, which equals 125 hours at 150°C.
d) 10 hours at 150°C c) 50 hours at 125°C ⎛ 0.1 ⎞
= (134 - (0.24 x 150)) x (10) = 95.19%
-(0.241 - 0.00254T) ⎜⎝ 1.108 ⎟⎠
= (134 - (0.24 x 125)) x (50) -((0.001 x 100) - 0.095) = 91.95%
⎛ 0.1 ⎞ ⎜ ⎟ ⎝ 1.026 ⎠
10 hours at 150°C has 95% remaining. To calculate the total loss of conductor strength, the sum of the equivalent times (hours) at 150°C is found. In this example, the sum is:
50 hours at 125°C has 92% remaining, which equals 15 hours at 150°C. d) 10 hours at 150°C
D
0 + 0.3 + 2 + 10 = 12.3 hours at 150 C. RSCOM = (134 - 0.24T) t -(0.241 -
⎛ 0.1 ⎞ 0.00254T) ⎜⎝ d ⎟⎠
= (134 - (0.24 x 150)) x (12.3)-(0.241 - (0.00254 x 150))
⎛ 0.1 ⎞ ⎜ ⎟ ⎝ 1.108 ⎠
= 95% The remaining strength for the in-service conductor is 95%. Example 2.4-2 : The conductor is 37 kcmil (19 mm 2 ) AAC “Arbutus”. During one year of operation, it is subjected to 7500 hours at 75°C, 1200 hours at 100°C, 50 hours at 125°C, and 10 hours at 150°C. What is the remaining strength (RS) of the conductor?
Using Equation 2.4-6, AAC: RSCOM = (134-0.24 ) t
and, if (134 – 0.24T) >100, use 100. a) 7500 hours at 75°C
2-26
0.1
− ( 0.001T - 0.095 ) d
= (134 - (0.24 x 150)) x (10) -((0.001 x 100) - 0.095) = 92.8%
⎛ 0.1 ⎞ ⎜ ⎟ ⎝ 1.026 ⎠
10 hours at 150°C has 93% remaining. To calculate the total loss of conductor strength, the sum of the equivalent times at 150°C is found. In this example, the sum is:
1 + 125 + 15 + 10 = 151 hours at 150D C. RS1350 = (134 - 0.24 T) t -(0.001 T - 0.095)
⎛ 0.1 ⎞ ⎜ ⎟ ⎝ d ⎠
-(0.001(150) - 0.095) ⎛⎜
= (134 - (0.24 x 150)) x (151) = 86.9%
0.1 ⎞ ⎟ ⎝ 1.026 ⎠
The remaining strength for the in-service conductor is 87%. As expected, the example calculations predict that the continuous high-temperature operation will cause the tensile strength of the AAC conductor to deteriorate faster than in the case of the ACSR conductor. In Figure 2.4-1, the graph showing the loss of strength for
Increased Power Flow Guidebook
individual strands of aluminum indicates that after 150 hours the remaining strength of the hard-drawn aluminum wire is 82%. When compared to the remaining strength value calculated using the predictor equations, the AAC conductor appears to be 5% stronger than predicted by using the data of the individual aluminum strands. Much of this difference in the prediction of the strength loss in the AAC conductor can be attributed to differences in behavior between the stranded conductor and an individual strand of aluminum and to differences in the nominal and actual dimensions of the manufactured product. Similarly, using strand data, the prediction equations show the ACSR conductor to be approximately 13% stronger than the tensile strength predicted by using the individual aluminum strand data itself. The difference in the remaining tensile strength can be directly attributed to the presence of the steel reinforcing strands which are significantly stronger than a comparably sized aluminum strand and are also not affected by temperatures below 300°C. 2.4.3
Sag Tension Models for ACSR Conductors
The traditional sag and tension model used throughout the industry is the model developed and promoted by the Alcoa-Fujikura LLC (Alcoa) (Alcoa 2003). The Alcoa sag and tension prediction model and methods assume that the magnitude of the compression stresses resulting from the manufacturing process are negligible and therefore do not affect the behavior of the conductor regardless of the operating temperature. Therefore, the model ignores the effects of aluminum compression. The Alcoa sag and tension model focuses on the coefficient of ther mal expansion phenomenon, which accounts for the fact that the aluminum strands expand at nearly twice the rate of the steel strands for the same increase in temperature. Consequently, as the temperature of the conductor increases significantly, the aluminum strands expand more rapidly than the steel strands. This shifts a continuously increasing percentage of the catenary tension onto by the steel strands (i.e., the aluminum “unloads” its share of the original tension). At some point (i.e., commonly called the “knee point”) the tension in the aluminum strands approaches a value of zero. At this time, the steel strands of the conductor carry all of the catenary tension of the composite wire. Based on this premise, and once the knee point temperature has been exceeded, the sag of the ACSR conductor is proportional to the rate of thermal expansion of the steel strands. It should be noted that the Alcoa sag and tension prediction model was developed in the early part of the last century when the stranding of the most commonly used ACSR conductors was six aluminum
Chapter 2: Overhead Transmission Lines
strands to one steel strand. Nevertheless, the sags and tensions predicted by the Alcoa model generally correlate very well for most conductors operated at temperatures not exceeding 75°C to 100°C. Today, medium-to-large ACSR conductors may have as many as four layers of aluminum strands surrounding a multistranded steel core. Based on the construction methods used to manufacture these multilayered conductors, it is very likely that a significant number of aluminum strands are capable of supporting limited compression forces (as a result of the confinement provided by underlying and overlaying layers) and that the resulting conductor harbors noticeable built-in stresses. The EPRI technical report Conductor and Associated Hardware Impacts during High Temperature Operations – Issues and Problems, published in December 1997 by Shan and Douglass (EPRI, TR-109044) concluded that it is more likely that such multilayered conductors follow a sag and tension model originally proposed by Nigol (Nigol and Barrett 1980). The Nigol sag and tension model, as shown in Figure 2.4-3, assumes that the aluminum strands do not change from tension to compression until a fixed limiting value is reached. In Nigol’s sag and tension model, as the aluminum changes from tensile to compression stresses, the elastic modulus is assumed not to change. Nigol hypothesizes the existence of compression stresses in the aluminum below the “birdcaging” temperature but assumes that the outer layer of aluminum strands remains in tension. Therefore, Nigol assumes that the tension in the outer layer strands denies the inner layer to expand radially and buckle outward. Nigol concludes that, since the inner layer is in compression and the outer layer is in tension, and since the outer layer presses radially inwards against the expanding inner layer, the aluminum strands of the inner layer are pressed against the steel cores and birdcaging is effectively negated. Consequently, based on this hypothesis, Nigol concluded that the elastic modulus remains unchanged even though the net aluminum stresses change from tension to compression. Thus, Nigol’s sag-tension model assumes that, as the conductor temperature increases towards the birdcaging temperature, the tensions in the outer layers of aluminum strands and the corresponding inward directed radial forces decrease. At the same time, Nigol’s model assumes that there is an increase in the radial forces of the outer layer and also an increased axial compression in the strands of the inner layers. Nigol, therefore, concludes that at the time when the birdcaging temperature is reached, the inner and outer radial forces are
2-27
Chapter 2: Overhead Transmission Lines
balanced, and the compressive stresses that are created reach their limiting value. Barrett’s sag and tension prediction model (Barrett et al. 1982) departs from Nigol’s model at this point. Barrett hypothesizes that at the birdcaging temperature, the radial forces within each of the aluminum strand layers balance. Based on Barrett’s hypothesis, the aluminum strands of a layer move radially outward as the temperature rises, resulting in a different elastic modulus to be used for the aluminum strands. Therefore Barrett describes the use of two compression moduli—the first value to be used at temperatures below the “knee point” and the second to be used at temperatures above the birdcaging temperature. Contrary to Nigol and Barrett, Rawlins (Rawlins 1998) proposes that there are no compression stresses above the knee point, but rather promotes the idea of large built-in tensile stresses that are the result of the manufacturing process. In Rawlins’s sag and tension prediction model, the point at which the aluminum stresses become tensile is also the point when there is a change in the elastic modulus. Therefore, Rawlins proposes that these stresses cause permanent elongations when compared to the other sag and tension models at the same level of tension. Figure 2.4-3 shows graphical representations of the four hypotheses explaining the behavior of high temperature conductors. 2.4.4
Increased Power Flow Guidebook
the aluminum strands are capable of greatly contributing to the sag of conductors at high operating temperatures. A simplified illustration of the influence of compression stresses in the aluminum strands at high temperatures is illustrated in Figure 2.4-4. The first sketch (Sketch 1) shows a length of the conductor at ambient temperature where the lengths of all of the aluminum and steel strands are equal. The second sketch (Sketch 2) shows an instance of the behavior of the conductor once the conductor length is heated to a temperature above ambient conditions. Because of the differences in the coefficients of thermal expansion of the aluminum and the steel strands (discounting for now issues such as stranding, manufacturing, etc), the lengths of the aluminum and steel strands will differ by an amount proportional to the temperature difference and the difference in the coefficients of thermal expansion. Of course, this scenario assumes that each type of material would be free to expand and not restricted in any manner. Similarly, the third sketch (Sketch 3) shows the behavior of the same length of conductor heated to a temperature significantly above ambient conditions, with the difference that the two materials are restricted from expanding independently of each other. As a result of the differences in the coefficients of thermal expansion, the proportion of the stresses carried by each type of material will change.
Axial Compressive Stresses
Work performed previously by Nigol and Barrett (Barrett 1982) clearly showed that compression stresses in
Finally, the fourth sketch (Sketch 4) shows the conductor in the case at which the compression in the aluminum strands is balanced by a tensile load in the steel core (i.e., the phenomenon most commonly referred to as “aluminum compression”). As the conductor reaches the birdcaging temperature (i.e., the point at which the aluminum strands expand outward to compensate for the increase in length), the aluminum strands move outward, yielding to the inherent compression stress induced by the constrained thermal expansion. At this
Figure 2.4-3 Sag-tension models. Figure 2.4-4 Manufacturing effects of ACSR conductor.
2-28
Increased Power Flow Guidebook
point (i.e., the point in the loading at which birdcaging is first observed), the tensile stress in the steel core far exceeds the value of the compression stress in the aluminum strands. 2.4.5
Built–In Stresses
When multistranded conductors are manufactured using a combination of steel and aluminum wires, the temperatures of the individual wire strands during the manufacturing process may vary, especially that of the steel core when compared to the aluminum strands. Contrary to the manufacturing of these multimaterial conductors, the same problem is not encountered in the manufacturing of All Aluminum Conductors (AAC), since they are constructed from the same homogeneous material. For ACSR conductors, the variance in the temperatures of the different types of stranding materials contributes to the composite behavior of the conductor. Therefore, when the conductor is placed under load, the variance in the temperature during manufacturing is likely to impact the sag and tension characteristics of the conductor. Unfortunately, quantitative values useful in estimating these manufacturing effects are neither provided by the manufacturer nor otherwise published. For example, if one assumes that a cold steel core is stranded with hot aluminum wires around the outside, the resulting conductor’s steel core will be slightly longer than the outer aluminum layers once the conductor is allowed to reach thermal equilibrium. As a result of the temperature differences, the commonly named knee point (i.e., the point at which the temperature of the complete length and cross-section has increased to a level at which the stresses in the aluminum strands approach zero) will shift relative to the knee point of a conductor constructed with steel and aluminum strands at the same temperature. 2.4.6
Chapter 2: Overhead Transmission Lines
of the conductor is not exceeded and that the suggested minimum clearances are maintained. In this subsection the mechanical and thermal properties acquired in the EPRI Conductor High Temperature Project experiments are presented, and the calculated sags and tensions are compared to values predicted using traditional sag and tension prediction data, methods, and tools. For clarity, these comparisons have been separated into two parts; the first addresses sags of level spans, the second addresses sags for inclined spans. To illustrate the use of the results and to demonstrate the differences in the predicted sags and tensions, three ACSR conductors of varying stranding ratios (low, medium, and high aluminum- to-steel stranding ratios) have been analyzed at different temperatures. The conductor sag analyses and comparisons were made at room temperature (23ºC), at a temperature of 120ºC, and at a temperature of 150ºC. Also, sags computed at level spans are compared to values at an inclined span of 15° and 30°. The underlying principles behind sag tension calculations for both level and inclined spans are outlined in the following subsections. Sag and Tension of Level Spans The shape of a catenary of a conductor is a function of the conductor’s weight per unit length, w, the horizontal component of tension, H, the span length, S, and the conductor sag, D. Figure 2.4-5 shows an illustration relating all of these parameters for a level conductor span. The actual conductor length, L, constitutes the stretched length of conductor (Trash et al. 1994).
Sag Tension Calculations
Bare overhead conductors are flexible and uniform in weight. These characteristics allow conductors to assume a catenary shape when suspended between support points. The shape of the catenary assumed by the conductor changes continuously as a result of climatic changes such as ambient temperature, operating conditions such as the amount of current being transferred, service life, and weather-related loads such as wind, snow, and ice. Because of the threat to human life and property, it is critical to ensure adequate horizontal and vertical clearances under all circumstances. Therefore the line designer is challenged to consider all weather and electrical loading cases to ensure that the breaking strength
Figure 2.4-5 Catenary sag model – level span.
2-29
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
The exact catenary equation representing the height of the conductor, y(x), at its lowest point along the span is given by the following equation: y( x ) =
H wx [cosh( ) − 1] w H
2.4-10
For level conductor spans, the low point is in the center and the total sag, D, is found by substituting x = S/2 in Equation 2.4-10. The resulting hyperbolic catenary relation for sag then becomes: D=
H ws [cosh( ) − 1] 2H w
2.4-11
The horizontal component of tension, H, is located at the point in the span where the conductor slope is horizontal, or at the midpoint for level spans. The conductor tension, T, is found at the ends of the spans at the point of attachment and is calculated using the following equation. T = H + wD
⎞ ⎛ Sw ⎞ ⎟ sinh ⎜ 2H ⎟ ⎠ ⎝ ⎠
2.4-13
Therefore, in order to calculate the correct sag, it is necessary to separate the effects of conductor elongation due to tensile loading as well as thermal loading. This process requires an iterative procedure in which the mathematical formulas describing the conductor elongation caused by the temperature change are solved simultaneously with the tension and conductor length relationship. To calculate the change in length due to temperature loading, the following equation is used: REF
2-30
⎡⎣1 + α AS (T − Tr Re f ) ⎤⎦
= coefficient of linear thermal elongation for the AL/SW strands.
LT
= final length of the conductor.
LT REF
= reference length of the conductor.
(T − Tr Re f )
= change in temperature.
The NESC (National Electric Safety Code 1993) recommends limits on the tension of conductors based on a percentage of their Rated Breaking Strength (RBS). For example, the tension limits of an ACSR may be 60% under maximum ice and wind loading, 35% upon installation at 60ºF, and 25% final unloaded after maximum loading has occurred at 60ºF. Therefore, if the initial tension in a span is known along with the initial conductor length, the total elongation resulting from the tensile load is calculated as follows:
2.4-12
It should be noted that while the above equations describe the behavior of ideal (with perfectly elastic stress and strain characteristics) concentric-lay stranded conductors, actual conductors such as ACSR conductors exhibit nonlinear behavior when loaded from an initial tension to some final value due to ice, wind, or temperature loading. Permanent elongation from creep and heavy loading also affects the resulting sag. Also, hightemperature operations result in thermal elongation of the steel and aluminum strands, thus affecting sag.
LT = LT
α AS
LH = LH
Rearranging the hyperbolic catenary equation for a level span, along with the substitution of x = S /2 for level spans corresponds to a conductor length of: ⎛ 2H L=⎜ ⎝ w
where:
2.4-14
REF
⎡ H − H REF ⎤ ⎢1 + ⎥ Ec A ⎦ ⎣
2.4-15
where: LH
REF
= length of conductor under horizontal reference tension.
LH
= length of conductor under horizontal tension.
H
= horizontal tension.
H REF = length of conductor under horizontal reference tension. Ec
A
= modulus of elasticity of the conductor (psi). = cross-sectional area, in2.
It should be noted that the modulus E c in Equation 2.4-15 is the modulus of the steel and aluminum strands determined by the stress and strain relationship of the composite conductor. Since this relationship for a bimetallic construction of the conductor is quite complex, the relationship of ACSR conductors is typically described by a third or fourth order polynomial. In addition, the thermal and permanent elongation drastically affects the mechanical behavior of ACSR conductors at high temperatures, and this further complicates the analysis. Therefore, since ACSR conductors are nonhomogenous, the stress and strain characteristics are separated into their steel and aluminum components as shown in Figure 2.4-6. Numerical methods are used to calculate the resulting sags and tensions, with the aid
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Figure 2.4-6 Decomposed ACSR “Tern” conductor at 120°C.
of software programs such as Alcoa Fujikura’s Sag10 package (Alcoa 2003). 2.4.7
The same equation used to represent the height of the conductor, for a level span is valid for inclined spans and is given by the following equation (Trash el al. 1994):
Sag and Tension of Inclined Spans
For inclined spans, the length of the conductor between supports is divided into two separate sections for consideration. One is to the right of the lowest point of the conductor, and one is to the left (see Figure 2.4-7).
y( x ) =
H⎛ wx ⎞ cosh( ) − 1⎟ w ⎜⎝ H ⎠
2.4-16
In each part of the span, the sag is dependent upon the vertical distance between support points and can be described by the following equations:
h ⎞ ⎛ DR = D ⎜ 1 − ⎟ ⎝ 4D ⎠
2
h ⎞ ⎛ DL = D ⎜ 1 + ⎟ ⎝ 4D ⎠
2
2.4-17
2.4-18
The maximum tension is
TR = H + wDR
2.4-19
TL = H + wDL
2.4-20
Figure 2.4-7 Catenary sag model—inclined span.
2-31
Chapter 2: Overhead Transmission Lines
2.4.8
Calculation of Conductor High-Temperature Sag and Tension
Simplified Calculations Simplified calculations are used for demonstration using a hand calculator. While most sag and tension calculations are typically performed with an analysis software, the use of the simplified calculation clearly demonstrates the process and provides the reader some insight into how sags and tensions occur for overhead lines. Example 2.4-3: What is the sag (D) and slack for a 1000-ft level span of 795 kcmil (405 mm 2 ) ACSR “Drake” conductor at ambient temperature (25ºC, 77ºF). The weight per unit length is 1.094 lbs/ft (1.6 kg/m), the horizontal tension component, H, is 25% of the RBS.
H = 0.25 x 31,500 lbs = 7875 lbs (35,196 N)
Increased Power Flow Guidebook
At 50ºC, the length of the conductor is 1001.28 ft (305.2 m). At 150ºC, the length of the conductor is 1003.21 ft (305.8 m). Example 2.4-5: What is the sag of the conductor at the elevated temperature levels?
The following equation is rearranged to estimate the resulting sag, which only considers the change due to thermal effects, and ignoring any changes that are due to the changes in tension.
L=S+
hence
D(122 ) =
Use Equation 2.4.11,
H ws wS 2 D = [cosh( ) − 1] ≈ w 2H 8H wS 2 1.094 (1000 ) D= = = 17.37 ft ( 5.29 m ) 8H (8) 7875 2
The sag for this level span is 17.37 ft (5.3 m). The following equation is used to calculate the length of the conductor:
3S ( L − S ) 8D 2 becomes D = 3S 8
D(302 ) =
3 (1000 )(1.28) 8 3 (1000 )( 3.21) 8
= 21.9 ft ( 6.68 m ) = 34.7 ft (10.58 m )
Example 2.4-6: What is the tension of the conductor when subjected to the two temperatures?
Rearrange the following equation to obtain the resultant tension of the conductor.
D=
wS 2 wS 2 becomes H = 8H 8D
wS 2 1.094 (1000 ) H(122 ) = = = 6244 lbs (27,875 N) 8D 8 ( 21.9 ) 2
8D ⎛ 2H ⎞ ⎛ Sw ⎞ sinh ⎜ L=⎜ ≈S+ ⎟ ⎟ 3S ⎝ w ⎠ ⎝ 2H ⎠
2
8 (17.37 ) 8D 2 = 1000 + = 1000.80 ft ( 305.05 m ) 3S 3 (1000 ) 2
L=S+
The conductor slack is the length minus the span length, 0.80 ft (0.24 m). Example 2.4-4: What happens to the conductor length if the temperature increases from ambient to 50ºC (122ºF)? What about if it increases to 150ºC (302ºF)? The coefficient of linear thermal expansion is 10.7 x 10-6/ºF.
LT = LT
REF
⎡⎣1 + α AS (T − TREF ) ⎤⎦
L(122 ) = 1000.80 ⎡⎣1 + 10.7 × 10 −6 (122 − 77 ) ⎤⎦ = 1001.28 ft (305.2 m) L(302 ) = 1000.80 ⎡⎣1 + 10.7 × 10 −6 ( 302 − 77 ) ⎤⎦ = 1003.21 ft (305.8 m)
2-32
wS 2 1.094 (1000 ) H(302) = = = 3941lbs (17,594N) 8D 8 ( 34.7 ) 2
These values assume that the conductor has an infinite modulus of elasticity. Actually, the elastic modulus of the conductor is finite, and changes in the conductor tension do affect the length of the conductor. Therefore, these equations estimate sags that are greater than has been observed in the field. Estimating the actual change in sag due thermal effects is complex, because one needs to look at the combined thermal and elastic effects of conductors. The initial loads of concentrically stranded ACSR conductors result in elongation behavior that is different from that caused by loading several years later. Software such as Alcoa’s Sag10 program use numerical methods to estimate the resulting sags.
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
The following example uses an AAC, and the effects of the elevated temperature levels are estimated.
hence
D(122 ) =
Example 2.4-7: What is the sag (D) and slack for a 1000 ft. (305 m) level span of AAC “Arbutus” conductor at ambient temperature (25ºC, 77ºF). The weight per unit length is 0.746 lbs/ft (1.09 kg/m), the horizontal tension component, H, is 25% of the RBS.
H = 0.25 x 13,900 lbs = 3475 lbs. (15,513 N) wS 2 0.746 (1000 ) = = 26.8 ft ( 8.18 m ) 8H (8) 3475
D(302 ) =
3 (1000 )( 2.48) 8 3 (1000 )( 4.79 ) 8
= 30.5 ft ( 9.3 m ) = 69.2 ft ( 21.1 m )
Example 2.4-10: What is the tension of the conductor when subjected to the two temperatures?
2
D=
The sag for this level span is 26.8 ft (8.18 m). The following equation is used to calculate the length of the conductor: 8 ( 26.8) 8D2 = 1000 + = 1001.9 ft ( 305.38 m ) 3S 3 (1000 ) 2
L=S+
Rearrange the following equation to obtain the resultant tension of the conductor.
D=
wS 2 wS 2 becomes H = 8H 8D
wS 2 0.746 (1000 ) H(122 ) = = = 3057 lbs (13,647 N) 8D 8 ( 30.5 ) 2
The conductor slack is the length minus the span length, 1.9 ft (0.58 m). Example 2.4-8: What happens to the conductor length if the temperature increases from ambient to 50ºC (122ºF)? What about if it increases to 150ºC (302ºF)? The coefficient of linear thermal expansion is 12.8 x 10-6/ºF.
LT = LT
REF
⎡⎣1 + α AS (T − TREF ) ⎤⎦
L(122 ) = 1001.9 ⎡⎣1 + 12.8 × 10 −6 (122 − 77 ) ⎤⎦ = 1002.48 ft (305.56 m) L(302 ) = 1001.9 ⎡⎣1 + 12.8 × 10
−6
(302 − 77 )⎤⎦
= 1004.79 ft (306.26 m) At 50ºC, the length of the conductor is 1002.48 ft (305.56 m). At 150ºC, the length of the conductor is 1004.79 ft (306.26 m). Example 2.4-9: What is the sag at the elevated temperature levels?
The following equation is rearranged to estimate the resulting sag, which only considers the change due to thermal effects, and ignoring any changes that are due to the changes in tension.
D=
3S ( L − S ) 8
wS 2 0.746 (1000 ) = = 1348 lbs (6,018 N) 8D 8 ( 69.2 ) 2
H(302 ) =
These high readings reflect the thermal elongation assuming the strands have an infinite modulus of elasticity. Fortunately, the modulus is finite, and the changes in the tension levels do affect the conductor length. These equations are a useful way to get a rough idea of how an ACSR conductor behaves when compared to an AAC conductor. At 50ºC, the AAC elongates about 28% more than the ACSR, and at 150ºC, the AAC elongates approximately 50% more than the ACSR. Using Alcoa Fujikura’s Sag10 Software Software programs can be useful to obtain more accurate results, since they use an iterative procedure to obtain solutions to complex problems such as the sag and tension calculation of a conductor. This iterative process is commonly referred to as the “binary chop” technique, and it separates the thermal as well as plastic and elastic effects resulting from changes in the conductor’s tension.
Once the results of the iterative calculations have converged, the results reflect the conductor length that accounts for the elastic effects of an increased load as well as the thermal elongation effects. Since H, and H REF correspond to the first-, second-, third-, and fourth-order composite stress and strain curves that describe the initial and final conductor modulus, it is typically convenient to rearrange the equations in terms of strain elongation to permit the direct substitution of values into the polynomial equations.
2-33
Chapter 2: Overhead Transmission Lines
2.4.9
Results of High-Temperature Sag Tension Calculations
Three different ACSR conductors were selected to demonstrate the high-temperature behavior of conductors and the calculation of the sag and tension. The ACSR conductors have varying steel-to-aluminum ratios, hence the effects of the construction of the conductor on the sag and tension are demonstrated. The conductors selected for the examples are ACSR “Drake,” ACSR “Mallard,” and ACSR “Tern.” All of these ACSR conductors selected for the demonstration are commonly used by electric utilities. ACSR Mallard is constructed using 30 aluminum strands and 19 steel core strands. The ratio of the aluminum’s cross-sectional area to the conductor’s total crosssectional area for the ACSR Mallard conductor is 0.814, classifying this conductor as a wire with a “high” steel-to-aluminum ratio. Similarly, ACSR Drake is constructed using 26 aluminum strands and 7 steel strands. The ratio of the aluminum’s cross-sectional area to the ACSR Drake conductor’s total cross-sectional area is 0.860, classifying this conductor as a wire with a “medium” steel-to-aluminum ratio. Finally, ACSR Tern is constructed using 45 aluminum strands and 7 steel strands. The ratio of the aluminum’s cross sectional area to the ACSR Tern conductor’s total cross-sectional area is 0.935, classifying this conductor as a wire with a “low” steel-to-aluminum ratio. In support of the analysis and the illustration of the high-temperature behavior of standard ACSR conductors, stress and strain data acquired in the EPRI Conductor High Temperature Operation Project were used. The data used for the prediction of high-temperature sags included the stress and strain curves and coefficients of thermal elongation. In order to illustrate the differences in the results, sag analyses were performed for a level conductor span as well as for inclined spans of 15° and 30°. In each case, sags were calculated for each type of conductor using two different approaches at each of the selected conductor temperatures. The resulting sags are reported at the initial and final condition at each temperature. In addition, the span length was varied, and the sag analyses were performed for 500 ft, 1000 ft, and 1500 ft span lengths. Again, the results were reported at the initial and final condition at each temperature. In the first approach, sags were calculated using Alcoa Fujikura’s Sag10 sag tension analysis program using the provided stress and strain charts included in the soft-
2-34
Increased Power Flow Guidebook
ware. Values are reported for initial and final conditions, respectively. In the second approach, sags were calculated using Alcoa Fujikura’s Sag10 sag tension analysis program and data obtained in the EPRI Conductor High Temperature Operation Project. Values are reported for initial and final conditions, respectively. Tables 2.4-2 through 2.4-10 provide a summary and comparison of derived sags at each operating temperature. For ACSR Drake with the 500 ft (152 m) span, the results of the comparison show that final sags calculated using EPRI High Temperature Conductor data are less than 1ft (0.3 m) greater than comparable values calculated using Alcoa Fujikura’s Sag10 data. For the 15°inclined span, the differences in the final sag were also less than 1 ft (0.3 m). Similar results were obtained for the 30° incline, which resulted in increased final sags that were less than 1 ft (0.3 m). For ACSR Drake with the 1000 ft (305 m) span, the results of the comparison show that final sags calculated using EPRI High Temperature Conductor data generally differ by about 2 ft (0.61 m) at ambient, but was about 1 ft (0.3 m) higher for elevated temperatures when compared to Alcoa Fujikura’s Sag10 data. For the 15° inclined span, the difference in the final sags was less than 1 ft (0.3 m). Similar results were obtained in the case of the 30° incline, which resulted in increased final sags that were minimal. For ACSR Drake with the 1500 ft (457 m) span, the results of the comparison show that final sags calculated using EPRI High Temperature Conductor data was up to 3 ft (0.9 m) at ambient, and 1 ft (0.3 m) at the elevated temperatures when compared to Alcoa Fujikura’s Sag10 data. For the 15° inclined span, the difference in the final sags was less than a foot (0.3 m). Similar results were obtained for the 30° incline, which resulted in increased final sags that are less than 1 ft (0.3 m). For ACSR Tern with the 500 ft (152 m) span, the results of the comparison show that final sags calculated using EPRI High Temperature Conductor data are generally less by about half a foot (0.15 m) when compared to Alcoa Fujikura’s Sag10 data. For the 15° inclined span, the difference in the final sags was negligible, and similar results were obtained for the 30° incline. Good correlation of the data occurred for the 1000 ft (305 m) and 1500 ft (457 m) span, and the sag values were less than 1 ft (0.3 m) when compared to Alcoa data. In most cases, the predicted sag was less than expected by the Alcoa database curves.
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
For ACSR Mallard with the 500 ft (152 m) span, the results of the comparison show that final sags calculated using EPRI High Temperature Conductor data are generally 1 ft (0.3 m) higher than comparable values calculated using Alcoa Fujikura’s Sag10 data. For the 15° inclined span, the difference in the final sags was between 0 ft and 1.5 ft (0.46 m). For the 30° incline, the difference in the final sags was between 0 and 1.6 ft (0.49 m).
For ACSR Mallard with the 1500 ft (457 m) span, the results of the comparison show that final sags calculated using EPRI High Temperature Conductor data is an additional 4 ft (1.2 m) at ambient temperature and is about 2.5 ft (0.76 m) at elevated temperatures when compared to values calculated using Alcoa Fujikura’s Sag10 data. For the 15° inclined span, the difference in the final sags was negligible at ambient, and as high at 3 ft (0.9 m) and approached 4 ft (1.2 m) for elevated temperature levels. Similar results were obtained for the 30° incline.
For ACSR Mallard with the 1000 ft (305 m) span, the results of the comparison show that final sags calculated using EPRI High Temperature Conductor data are 3 ft (0.9 m) at ambient temperatures and about 2 ft (0.61 m) at elevated temperatures, when compared to values calculated using Alcoa Fujikura’s Sag 10 data. For the 15° inclined span, the difference in the final sags was negligible at ambient temperature but 2.5 ft (0.76 m) at elevated temperatures. For the 30° incline, the difference in the final sags was negligible at ambient temperature but up to 2.8 ft (0.85 m) at elevated temperatures.
Table 2.4-2 ACSR Drake, Span Length = 500 ft Alcoa Fujikura Sag 10 Software with Alcoa Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
3.26
4.35
3.26
3.37
3.26
3.76
120 Deg
8.61
8.61
8.61
8.30
8.61
9.26
150 Deg
9.21
9.61
9.21
9.52
9.21
10.62
Alcoa Fujikura Sag 10 Software with EPRI Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
3.26
5.23
3.26
3.37
3.26
3.76
120 Deg
8.64
9.26
8.64
8.93
8.64
9.96
150 Deg
9.81
10.29
9.81
10.14
9.81
11.31
Comparison: Alcoa to EPRI Conductor Temperature
Level
15%
30%
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
23 Deg
0
0.88
0.00
0
0
0.88
120 Deg
0.61
0.65
0.63
0.70
0.61
0.65
150 Deg
0.60
0.68
0.62
0.69
0.60
0.68
2-35
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Table 2.4-3 ACSR Drake, Span Length = 1000 ft Alcoa Fujikura Sag 10 Software with Alcoa Data Conductor Temperature
Level Initial Sag (ft)
15% Final Sag (ft)
Initial Sag (ft)
30% Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
13.05
16.27
13.05
13.05
13.05
15.05
120 Deg
22.48
25.32
22.48
23.22
22.48
25.89
150 Deg
25.62
26.94
25.62
26.45
25.62
29.49
Alcoa Fujikura Sag 10 Software with EPRI Data Conductor Temperature
Level Initial Sag (ft)
15% Final Sag (ft)
Initial Sag (ft)
30% Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
13.05
18.32
13.05
13.5
13.05
15.05
120 Deg
23.05
26.23
23.05
23.81
23.05
26.55
150 Deg
26.20
27.87
26.20
27.05
26.20
30.16
Difference (ft)
Difference (ft)
Comparison: Alcoa to EPRI Conductor Temperature
Level Difference (ft)
15%
Difference (ft)
Difference (ft)
30% Difference (ft)
23 Deg
0
2.05
0
0
0
0
120 Deg
0.57
0.91
0.57
0.59
0.57
0.66
150 Deg
0.58
0.93
0.58
0.60
0.58
0.67
Table 2.4-4 ACSR Drake, Span Length = 1500 ft Alcoa Fujikura Sag 10 Software with Alcoa Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
29.39
34.65
29.39
30.38
29.39
33.88
120 Deg
42.39
47.81
42.39
43.74
42.39
48.77
150 Deg
46.40
49.93
46.40
47.84
46.40
53.34
Alcoa Fujikura Sag 10 Software with EPRI Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
29.39
37.61
29.39
30.38
29.39
33.88
120 Deg
43.04
48.83
43.04
44.41
43.04
49.51
150 Deg
47.10
50.97
47.10
48.56
47.10
54.14
Comparison: Alcoa to EPRI Conductor Temperature
2-36
Level
15%
30%
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
23 Deg
0
2.96
0
0
0
0
120 Deg
0.65
1.02
0.65
0.67
0.65
0.74
150 Deg
0.70
1.04
0.70
0.72
0.70
0.80
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Table 2.4-5 ACSR Tern, Span Length = 500 ft Alcoa Fujikura Sag 10 Software with Alcoa Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
3.81
5.67
3.81
3.94
3.81
4.39
120 Deg
10.90
12.89
10.90
11.27
10.90
12.56
150 Deg
13.11
13.73
13.11
13.53
13.11
15.09
Alcoa Fujikura Sag 10 Software with EPRI Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
3.81
5.74
3.81
3.93
3.81
4.39
120 Deg
10.76
12.45
10.76
11.12
10.76
12.40
150 Deg
13.00
13.29
13.00
13.42
13.00
14.96
Comparison: Alcoa to EPRI Conductor Temperature
Level
15%
30%
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
23 Deg
0
0.07
0
-0.01
0
0
120 Deg
-0.14
-0.44
-0.14
-0.15
-0.14
-0.16
150 Deg
-0.11
-0.44
-0.11
-0.11
-0.11
-0.13
Table 2.4-6 ACSR Tern, Span Length = 1000 ft Alcoa Fujikura Sag 10 Software with Alcoa Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
15.24
19.84
15.24
15.76
15.24
17.58
120 Deg
27.30
34.46
27.30
28.17
27.30
31.41
150 Deg
30.84
35.78
30.84
31.80
30.84
35.45
Alcoa Fujikura Sag 10 Software with EPRI Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
15.24
19.98
15.24
15.76
15.24
17.58
120 Deg
27.17
33.7
27.17
28.04
27.17
31.27
150 Deg
30.67
35.04
30.67
31.63
30.67
35.26
Comparison: Alcoa to EPRI Conductor Temperature
Level
15%
30%
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
23 Deg
0
0.14
0
0
0
0
120 Deg
-0.13
-0.76
-0.13
-0.13
-0.13
-0.14
150 Deg
-0.17
-0.74
-0.17
-0.17
-0.17
-0.19
2-37
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Table 2.4-7 ACSR Tern, Span Length = 1500 ft Alcoa Fujikura Sag 10 Software with Alcoa Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
34.34
41.10
34.34
35.47
34.34
39.55
120 Deg
49.79
62.49
49.79
51.31
49.79
57.20
150 Deg
54.26
64.30
54.26
55.88
54.26
62.28
Alcoa Fujikura Sag 10 Software with EPRI Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
34.34
41.27
34.34
35.47
34.34
39.55
120 Deg
49.69
61.51
49.69
51.21
49.69
57.08
150 Deg
54.13
63.26
54.13
55.73
54.13
62.12
Comparison: Alcoa to EPRI Conductor Temperature
Level
15%
30%
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
0
0.17
0
0
0
0
120 Deg
-0.10
-0.98
-0.10
-0.10
-0.10
-0.12
150 Deg
-0.13
-1.04
-0.13
-0.15
-0.13
-0.16
23 Deg
Table 2.4-8 ACSR Mallard, Span Length = 500 ft Alcoa Fujikura Sag 10 Software with Alcoa Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
3.02
4.27
3.02
3.12
3.02
3.48
120 Deg
6.21
7.43
6.21
6.42
6.21
7.16
150 Deg
7.77
8.48
7.77
8.03
7.77
8.95
Alcoa Fujikura Sag 10 Software with EPRI Data Conductor Temperature
23 Deg
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
3.02
5.45
3.02
3.12
3.02
3.48
120 Deg
7.63
8.49
7.63
7.89
7.63
8.80
150 Deg
8.67
9.57
8.67
8.96
8.67
10.00
Comparison: Alcoa to EPRI Conductor Temperature
15%
30%
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
0
1.18
0
0
0
0
120 Deg
1.42
1.06
1.42
1.47
1.42
1.64
150 Deg
0.90
1.09
0.90
0.93
0.90
1.05
23 Deg
2-38
Level Difference (ft)
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Table 2.4-9 ACSR Mallard, Span Length =1000 ft Alcoa Fujikura Sag 10 Software with Alcoa Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
12.08
15.82
12.08
12.50
12.08
13.94
120 Deg
19.54
22.59
19.54
20.20
19.54
22.52
150 Deg
22.11
24.33
22.11
22.85
22.11
25.48
Alcoa Fujikura Sag 10 Software with EPRI Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
12.08
18.58
12.08
12.50
12.08
13.94
120 Deg
21.99
24.46
21.99
22.72
21.99
25.34
150 Deg
24.51
26.20
24.51
25.31
24.51
28.22
Comparison: Alcoa to EPRI Conductor Temperature
Level
15%
30%
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
23 Deg
0
2.76
0
0
0
0
120 Deg
2.45
1.87
2.45
2.52
2.45
2.82
150 Deg
2.40
1.87
2.40
2.46
2.40
2.74
Table 2.4-10 ACSR Mallard, Span Length = 1500 ft Alcoa Fujikura Sag 10 Software with Alcoa Data Conductor Temperature
Level Initial Sag (ft)
15% Final Sag (ft)
Initial Sag (ft)
30% Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
27.21
33.36
27.21
28.13
27.21
31.37
120 Deg
38.20
43.22
38.20
39.45
38.20
43.98
150 Deg
41.62
45.51
41.62
42.95
41.62
47.89
Alcoa Fujikura Sag 10 Software with EPRI Data Conductor Temperature
Level
15%
30%
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag (ft)
Initial Sag (ft)
Final Sag(ft)
23 Deg
27.21
37.38
27.21
28.13
27.21
31.37
120 Deg
40.74
45.76
40.74
42.05
40.74
46.89
150 Deg
45.07
48.03
45.07
46.48
45.07
51.82
Comparison: Alcoa to EPRI Conductor Temperature
Level
15%
30%
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
Difference (ft)
23 Deg
0
4.02
0
0
0
0
120 Deg
2.54
2.54
2.54
2.60
2.54
2.91
150 Deg
3.45
2.52
3.45
3.53
3.45
3.93
2-39
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
2.4.10 Effects of Wind Speed on Thermal Ratings
High-temperature operations are greatly affected by local wind conditions. This is discussed in Section 2.3 for its effect on clearances. Below, its effect on conductor strength is the focus. The following will demonstrate the effect of wind on the performance of the conductor. For the comparison, Power Technologies’ Ratekit was used. Ratekit is a software tool capable of evaluating the effects of wind speed and operating temperature independently. In the discussion, all conductor conditions are assumed steady state. Also, the angle of the wind relative to the conductor is 90°, the span is at sea level, and the time of year is summer. The coefficient of emissivity is 0.50, the coefficient of solar absorptivity is 0.50, the conductor resistance at 25ºC is 0.1200 ohms/mile (0.075 ohms/km), and the conductor resistance at 75ºC is 0.1442 ohms/mile (0.090 ohms/m). Atmospheric conditions are clear, and the orientation of the conductor relative to the north is 0°. The ambient temperature is 25°C , the ruling span is 1000 ft (305 m), and the conductors used in the comparisons are ACSR Drake and AAC Arbutus. The operating temperatures are 120°C and 150°C , and the wind speeds used are 0 ft/sec, 2 ft/sec (0.61 m/sec), and 4 ft/sec (1.2 m/sec). Table 2.4-11 shows the remaining strength Table 2.4-11 ACSR Drake Current (A)
Wind Speed (ft/sec)
Temperature (°C)
Remaining Strength (%)a
1180
0
150
2
110
4 1000
Initial Sag (ft)
Final Sag (ft)
98.64
36.1
39.6
100
32.3
36.1
85.7
100
29.8
33.8
0
120
100
33.3
36.9
2
85.8
100
29.8
33.8
4
68.5
100
28.0
32.1
a. The remaining strength is after 100-hours of high operating temperatures. Table 2.4-12 AAC Arbutus Temperature (°C)
Remaining Strength (%)a
0
150
2
108.5
4
Current (A)
Wind Speed (ft/sec)
1130
960
Initial Sag (ft)
Final Sag (ft)
70.12
47.4
49.0
92.11
43.5
45.2
84.6
100
41.2
43.0
0
120
85.89
44.6
46.3
2
84.9
100
41.2
43.0
4
68.1
100
39.5
41.3
a. The remaining strength is calculated when the conductor is exposed to the high temperature for 100 hours.
2-40
and sags for the ACSR Drake conductor, and Table 2.412 summarizes the results obtained for the AAC Arbutus. At 1180 A and 0 ft/sec wind, the operating temperature of the ACSR Drake conductor is 150ºC. If subjected to this high operating temperature for 100 hours, the remaining strength of the ACSR Drake conductor decreases by 1.4% to 98.64% of the rated tensile strength. If the weather conditions are favorable and the wind speed is 2 ft/sec (0.61 m/sec), the operating temperature of the ACSR Drake conductor is 110ºC, and the tensile strength of the conductor remains unaffected. If the wind speed is 4 ft/sec (1.22 m/sec), the temperature of the ACSR Drake conductor with 1180 A of current is nearly 86ºC, and the strength of the conductor remains unaffected. Similarly, the sag (final) of the ACSR conductor at 1180 A, and 0 ft/sec wind is 39.6 ft (12.1 m), while the sag of the ACSR Drake decreases by nearly 3.5 ft (1.1 m) if the wind speed increases from 0 ft/sec to 2 ft/sec. If the wind speed increases to 4 ft/sec (1.2 m/sec), the sag of the ACSR Drake conductor is 33.8 ft/sec (10.3 m/sec), nearly 6 ft (1.8 m) less than in the case where the wind is 0 ft/sec. If the ACSR Drake carries 1000 A and the wind speed is 0 ft/sec, the operating temperature of the conductor is 120ºC, resulting in no loss of tensile strength if operated for 100 hours. If the wind speed increases to 2 ft/sec (0.61 m/sec), the operating temperature decreases 86ºC and the sag decreases by approximately 2 ft (0.61 m). If the wind speed increases to 4 ft (1.2 m), the temperature decreases to 70ºC and the sag decreases an additional 2 ft (0.61 m). The temperature of an AAC Arbutus conductor carrying a current of 1130 A at a wind speed of 0 ft/sec is 150ºC. If the duration of this operation is 100 hours, the tensile strength of the conductor decreases by nearly 30% to 70.12% of the rated tensile strength. However, if the wind speed is 2 ft/sec (0.61 m/sec), the operating temperature of the AAC Arbutus conductor is 108ºC, and the operation at this condition for a period of 100 hours reduces the tensile strength of the conductor by only 9% instead of 30% at a wind speed of 0 ft/sec. The remaining strength at these conditions is 92.1% of the rated tensile strength, an acceptable value. At a wind speed of 4 ft/sec (1.2 m/sec), an AAC Arbutus conductor carrying a current of 1130 A will operate at a temperature of 85ºC, resulting in no loss of the tensile strength of the conductor. Also, a wind speed of 2 ft/sec (0.61 m/sec) reduces the sag by nearly 4 ft (1.2 m) compared to the sag calculated in the no wind scenario, and the sag is reduced an additional 2 ft (0.61 m) if the wind speed increases to 4 ft/sec (1.2 m/sec).
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
AAC Arbutus carrying a current of 960 A at a wind speed of 0 ft/sec operates at a temperature of 120ºC, resulting in a loss of 14% of the tensile strength if operated continuously for a period of 100 hours. The remaining tensile strength is reduced to 86% of the rated tensile strength of the conductor. If the wind speed increases to 2 ft/sec (0.61 m/sec), the sag of the conductor decreases by 3 ft (0.9 m), while an increase in the wind speed will decrease the sag by nearly 5 ft (1.5 m) when compared to the no wind case. 2.4.11 Thermal Elongation
Thermal elongation is a metallurgical phenomenon where the material increases in length in proportion to an increase in temperature. The rate of linear thermal expansion for the composite ACSR conductor is less than that of conductors that are made entirely of aluminum because the steel strands in the ACSR elongate at approximately half the rate of aluminum. The theoretical composite coefficient of linear thermal expansion (CTE) of a nonhomogenous conductor, such as the ACSR Drake may be found from the following equations: ⎛ E AL ⎞⎛ AAL ⎟⎜ ⎝ E AS ⎠⎝ ATOTAL
∂ AS = ∂ AL ⎜
⎞ ⎛ EST ⎞ ⎛ AST ⎞ ⎟ + ∂ ST ⎜ ⎟⎜ ⎟ ⎠ ⎝ E AS ⎠ ⎝ ATOTAL ⎠
⎛ 10 x106 ⎞ aAS = 12.8x10 −6 ⎜ 6 ⎟ ⎝ 12.8x10 ⎠ ⎛ 30x106 ⎞ +6.4 x10 −6 ⎜ 6 ⎟ ⎝ 12.8x10 ⎠ = 10.7 x10 −6 / °F
⎛ 0.6247 ⎞ ⎜ 0.7264 ⎟ ⎝ ⎠ ⎛ 0.1017 ⎞ ⎜ 0.7264 ⎟ ⎝ ⎠
A comparison of three different ACSR conductors of varying aluminum-to-steel ratios is used to demonstrate the effect of the steel reinforcing on the composite conductor behavior and coefficient of linear expansion. Table 2.4-13 summarizes calculated (ideal) and measured coefficients of linear thermal expansion. The measured coefficient of linear expansion of the ACSR Tern conductor (low steel-to-aluminum ratio) is 10.9% larger than the calculated value. The measured coefficient of linear expansion of the ACSR Drake conductor (medium steel-to-aluminum ratio) is approximately 6% higher than the calculated value and the measured coefficient of the ACSR Mallard (high steel-to-aluminum ratio) is only marginally larger than the calculated value. As the steel-to-aluminum ratio increases, the coefficient of linear expansion of the composite conductor approaches a limiting value equal to the coefficient of steel alone.
2.4-21
⎛ A ⎞ ⎛ A ⎞ E AS =E AL ⎜ AL ⎟ + EST ⎜ ST ⎟ ⎝ ATOTAL ⎠ ⎝ ATOTAL ⎠ 2.4-22 where EAL = modulus of elasticity of aluminum, psi. = modulus of elasticity of steel, psi. EST = modulus of elasticity of aluminum-steel EAS composite, psi. AAL = area of aluminum strands, square units. = area of steel strands, square units. AST ATOTAL = total cross sectional area, square units. αAL = aluminum coefficient of linear thermal expansion, per °F. αST = steel coefficient of thermal elongation, per °F. αAS = composite aluminum-steel coefficient of thermal elongation, per °F. Example 2.4-10: Using elastic moduli of 10 and 30 million psi (68,966 MPA and 206,897 Mpa) for aluminum and steel, find the elastic modulus for ACSR Drake is:
⎛ 0.6247 ⎞ 6 ⎛ 0.1017 ⎞ E AS = 10 x106 ⎜ ⎟ + 30 x10 ⎜ 0.7264 ⎟ ⎝ 0.7264 ⎠ ⎝ ⎠ 6 10 = 12.8x10 psi (8.83 x 10 Pa)
(
)
(
)
Note that the results of the EPRI High Temperature Conductor Project identifies the conductor’s knee point, and that the coefficient of linear expansion does not typically address the effect of the knee point on the sag and tension calculation. A typical set of test data is shown in Figure 2.4-8. The knee point is shown at approximately 120ºC. However, to accurately predict sags and tensions at high temperature, the effects of the knee point need to be considered and is discussed in more detail. The conditions under which calculations using a simple composite modulus and coefficient of linear thermal expansion fail may be illustrated by considering the tension distribution between steel and aluminum under normal and high temperature conditions. The preceding equations for composite modulus and CTE are derived based on the assumption that the aluminum and steel Table 2.4-13 Coefficient of Thermal Elongation for ACSR Conductors Measured Calculated ACSR Coefficient of Coefficient of Conductor (below 212°F, Thermal Elon- Thermal Elongation (CTE) gation (CTE) or 100°C) Tern 45/7
and the coefficient of linear thermal expansion is:
Drake 26/7 Mallard 30/19
Percent Difference
11.7 x 10-6
13.0 x 10-6
10.9
10-6
11.4 x 10-6
6.09
10.2 x 10-6
10.1 x 10-6
0.64
10.7 x
2-41
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
strands are of the same length. Based on this assumption, the total conductor tension (HAS) is equal to the sum of the component tensions, and the elongation of the steel and aluminum is equal: H AS = H AL + H ST HST H AL = AST ⋅ EST AAL ⋅ E AL
Figure 2.4-8 is 12.84 x 10-6 /ºC, while the corresponding value in Figure 2.4-9 is 13.74 x 10-6 /ºC, a difference of less than 7%. 2.4.12 Creep Elongation
2.4-23
2.4-24
For example, an ACSR Drake conductor installed in a 600 ft (183 m) span at an initial tension of 9450 lbs (42,188 N) carries 3124 lbs (13,946 N) of the tension in the steel core with the remainder of the tension being carried by the aluminum strands. Therefore, the tension carried by the steel is roughly 33% of the total tension. If the ACSR Drake conductor is heated to a temperature of 100oC, the sag of the conductor increases, and the total tension decreases to 4780 lbs (21,339 N), but the tension carried by the steel core increases from 3124 lbs (13,946 N) to 3305 lbs (14,754 N), or nearly 70% of the total tension. As the operating temperature of the conductor increases further, the tension in the aluminum eventually decreases to zero while the tension carried by the steel increases further. At some temperature, commonly referred to as the knee point temperature, the linear expansion of the conductor continues, but the stresses in the aluminum strands change from tension to compression (as shown in Figures 2.4-8 and 2.4-9). The knee point temperature of an ACSR conductor is directly proportional to the steel-to-aluminum ratio and is lower for ACSR conductors with high ratios and higher for conductors with low steel to aluminum ratios.
Once a conductor has been installed to an initial tension, it can elongate further. Such elongation results from three phenomena—permanent elongation due to high-tension levels resulting from ice and wind loads, creep elongation under everyday tension levels, and creep elongation due to thermal overloads. The creep resulting from thermal loading is discussed below. High-Temperature Creep Elongation The definition of “normal” creep is the accumulative nonelastic elongation of a conductor under low tension, over an extended period of time at modest operating temperatures. Normal operating temperatures are generally agreed upon as temperatures below 75°C. In any
Figure 2.4-8 ACSR Drake (26/7) composite thermal elongation, (30% of RBS Pre-Stressing, 10% of RBS Applied Tension, Manufacturer 2).
Conductors made by different manufacturers exhibit different knee-point temperatures because of differences in the manufacturing practices, processes, and machinery. For example, Figure 2.4-8 indicates that the ACSR Drake has a knee point at about 120ºC, while the data in Figure 2.4-8 suggests that the ACSR Drake has a knee point of only 70ºC. Disregarding experimental differences, built-in stresses, which are the result of manufacturing methods and tools, are the primary cause for this difference. In Figure 2.4-8, the coefficient of thermal expansion is 17.38 x 10-6 /ºC prior to the knee point, and the corresponding value in Figure 2.4-9 is 17.53 x 10-6 /°C, a difference of less than 1%. While the corresponding coefficient beyond the knee point is also fairly consistent, the temperature at which the knee point has been observed differs by nearly 50ºC or nearly 70%. The coefficient of thermal expansion beyond the knee point in
2-42
Figure 2.4-9 ACSR Drake (26/7) composite thermal elongation, (30% of RTS Pre-Stressing, 10% of RTS Applied Tension, Manufacturer 1).
Increased Power Flow Guidebook
case, a conductor under tension experiences a nonelastic elongation over a period of time. Time is usually measured in years. The magnitude and rate of creep are a function of the conductor's composition, stranding, line tension, and operating temperature. Conductors exhibit creep under everyday tension levels even if the tension level never exceeds normal operating conditions. Creep can be determined by long-term laboratory creep tests, and the results of the tests are used to generate charts that document the relationship of creep versus time. On the stress-strain graphs of conductors, creep curves are often shown for 6-month, 1-year, and 10-year time periods. Figure 2.4-10 shows a typical creep curve (experimental results) for an ACSR Drake conductor at room temperature. Generally, the creep elongation in aluminum conductors is quite predictable, it is a function of time and temperature, and the relationship is exponential. Thus, knowing the initial conditions of the conductor, the permanent elongation due to creep at everyday tension can be found for any period of time after the initial installation. Note that the creep elongation of copper and steel strands is minimal, and that the effects can essentially be ignored. High-temperature creep occurs when a conductor is operated for extended periods of time at operating temperatures in excess of approximately 75°C. Creep constitutes an irreversible, nonelastic elongation occurring in response to the molecular realignment in the conductor’s base material. Figure 2.4-10 shows the effects of creep on the conductor strain at an operating temperature of 120°C. Because aluminum exhibits a significantly higher rate of creep elongation than steel, the sag and tension behavior of all-aluminum type conductors such as AAC, AAAC, and ACAR is much more susceptible to high-temperature creep. Conversely, copper and steel wire strands supported aluminum conductors (Cu, ACSR, and AACSR) exhibit lower rates of creep, and the sag and tension behavior of these conductors is less affected by the high-temperature operation. Aluminum Conductor Steel Supported (ACSS) conductor, a conductor constructed using fully annealed aluminum strands and steel strands for the strength member, exhibits negligible creep rates since all of the tension is carried by the steel strength member, which is essentially not affected by creep. Creep, and the associated rate of creep, are directly proportional to the type of conductor, the steel-to-aluminum stranding ratio, the material characteristics of the conductor, and the tension and operating temperature. For example, using strands that are drawn from continuous-cast rod instead of hot-rolled rod reduces the creep
Chapter 2: Overhead Transmission Lines
elongation and the associated long-term sag and tension behavior of the conductor. Other important parameters required in the determination of the rate of creep and the cumulative effect include the conductor stress or strain, the operating temperature, the elapsed time, and for ACAR and ACSR type conductors, the ratio of the constitutive components. Figures 2.4-10 and 2.4-11 show experimentally derived creep elongation results for ACSR Drake at room temperature and at 120°C. In both experiments, the majority of the creep elongation occurred during the initial 100 hours, a settling phase, so to speak. Note that at ambient room temperature conditions (23°C), the final creep elongation after 1000-hours was 0.01%, while the final creep elongation measured at the increased operating temperature was 0.03%. Thus, an ACSR conductor operated at a high temperature will reach its “final” sag
Figure 2.4-10 ACSR Drake composite creep at 23°C, Manufacturer 1.
Figure 2.4-11 ACSR Drake composite creep at 120°C, Manufacturer 1.
2-43
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
approximately two to three times faster than a conductor operated at temperatures of 75°C or below. Creep Predictor Equations Harvey (Harvey 1969) developed mathematical models and associated equations that can be used to estimate the magnitude of creep elongation. The models and equations were empirically derived, and are able to predict the creep elongation of a conductor at room temperature, as well as at an elevated temperature. The required definitions, constants, and formulas are listed (see Tables 4-14 and 4-15), along with an example.
Definition of Terms: εc = Primary creep strain (units/unit) ε = Strain - increase in length/original (units/unit) ΣεT = Increase in conductor strain due to elevated temperature operations (units/unit) σ = Stress - tension/area (N/mm2, lbs/in2) α = Coefficient of thermal expansion (units/unit/C) t = Elapsed time (hours) T = Conductor temperature (C) ΔT = Temperature change value (C) AEC = Area of aluminum strands (sq. mm., sq. in.) AST = Area of steel strands (sq. mm., sq. in.) AT = Total conductor area (sq. mm., sq. in.) %RS = Tension as a percentage of the rated strength (%) Table 2.4-14 Formula Constants (Metric Units) K1
AAC:ε c = K σ 1.3 t 0.16 AAAC:ε c = G σ
1.3
t
2.4-25
0.16
2.4-26
ACAR:ε c = (0.19 + 1.36 A EC / A T ) (T
1.4
σ
1.3
t
AAC:ε c = K σ 1.3 t 0.16 AAAC:ε c = G σ
1.3
t
2.4-28
0.16
2.4-29
ACAR:ε c = (0.0003 + 0.0021 A EC / A T ) (T
1.4
σ 1.3 t 0.16 ) 2.4-30
All-Aluminum Conductors (Elevated Temperature, Metric) AAC:ε c = M T1.4 σ 1.3 t
0.16
2.4-31
AAAC: ε c = 0.0077 T
σ
1.4
1.3
t
0.16
2.4-32
ACAR: ε c = (0.0019 +0.012 A EC / A T ) (T
1.4
σ
61 Strands
1.36
1.29
1.23
1.16
AAAC: ε c = 0.000012 T ACAR: ε c =
0.77
0.77
0.71
0.0142
0.0136
0.0129
M2
0.0090
0.0090
0.0084
0.0077
G
0.71
0.65
0.77
0.61
Note: K1, K3, M1, and M3 are for wire bar rolled rod and K2, K4, M2, and M4 are for continuous cast (rolled) rod. Table 2.4-15 Formula Constants (English Units)
1.4
19 Strands
37 Strands
61 Strands
K3
0.0021
0.0020
0.0019
0.0018
K4
0.0013
0.0012
0.0012
0.0011
M3
0.000023
0.000022
0.000021
0.000020
M4
0.000014
0.000014
0.000013
0.000012
G
0.0011
0.0010
0.0012
0.00094
Note: K1, K3, M1, and M3 are for wire bar rolled rod and K2, K4, M2, and M4 are for continuous cast (rolled) rod.
2.4-34
σ
1.3
t
0.16
2.4-35
(0.000003 +0.000019 A EC / A T ) (T1.4 σ 1.3 t
0.16
2.4-36
Steel Reinforced Conductors (Room Temperature, English) Aluminum strands drawn from hot-rolled rod: ACSR: ε c = 2.4 (%RS)1.3 t
7 Strands
t 0.16 )
All-Aluminum Conductors (Elevated Temperature, English)
37 Strands
0.84
1.3
2.4-33
19 Strands
0.0148
)
All-Aluminum Conductors (Room Temperature, English)
7 Strands
M1
0.16
2.4-27
AAC: ε c = M T1.4 σ 1.3 t 0.16
K2
2-44
Predictor Equations: All-Aluminum Conductors (Room Temperature, Metric)
0.16
2.4-37
Aluminum strands drawn from continuous cast rod: ACSR: ε c = 1.1 (%RS)1.3 t
0.16
2.4-38
Steel Reinforced Conductors (Elevated Temperature, English) Only for conductors with less than 7.5% steel by area:
)
Increased Power Flow Guidebook
ACSR: ε c = 2.4 (%RS) T t
Chapter 2: Overhead Transmission Lines
Using Equation 2.4-37, the ambient temperature creep is:
0.16
2.4-39
Elevated creep in conductors with steel to aluminum ratios of greater than 7.5% can be ignored.
Temperature Change Value The equivalent temperature change value is a calculated temperature that approximates the net increase in the micro-strain due to elevated temperature creep above and beyond general creep. ∑ ε T = α ΔT or ΔT = ∑ ε T /α ∑ ε T = ε @high - ε @ambient
2.4-40 2.4-41
ε@ambient is the strain in the conductor due to room temperature creep only, and ε@high is the strain in the conductor attributed to the elevated temperature creep.
Method for Using the Predictor Equations The process of calculating the predicted elevated temperature creep is straightforward and can be accomplished using sags and tensions derived from graphical charts, long-hand calculations, or computer software predictions. The following procedure must be followed: 1. Use the standard graphical charting, long-hand calculations, or computer sag and tension methods to predict the sags and tensions without elevated creep for the given situation. 2. Compute the creep of the conductor at ambient temperature. 3. Compute the creep of the conductor at the first elevated temperature. 4. Compute the number of hours that would be required to accumulate an equivalent amount of conductor creep at the second elevated temperature. 5. Repeat steps 3 and 4 for each elevated temperature. 6. Calculate the value of the equivalent temperature change by subtracting the predicted creep elongation at the everyday temperature from the creep elongation at the elevated temperature. 7. Calculate the final sag of the conductor following elevated temperature creep by adding this temperature change value to the temperatures used in the standard sag and tension calculation.
ε c = 2.4 (%RS)1.3 t 0.16 where %RS is the Remaining Strength, and t is the time (hours) a)
Conductor creep produced for 20 hours at 60°F (16°C)
ε c = 2.4 x 0.25 1.3 x 20 0.16 ε c = 0.64 micro-in/in (1 in. = 2.54 cm) 20 hours at 60°F produces a creep of 0.64 micro-in./in. or the equivalent of operating the conductor for 0 hours at 212°F. Using Equation 2.4-39, the elevated temperature creep is:
ε c = 2.4 (%RS) T t 0.16 b) Conductor creep produced for 7500 hours at 167°F (75 C)
ε c = 2.4 x 0.25 x 167 x (7500) 0.16 ε c = 417.7 micro-in./in. 7500 hours at 167°F produces a creep of 417.7 microin./in. or the equivalent of operating the conductor for 1690 hours at 212°F (100°C).
c) Conductor creep produced for 1240 hours at 212°F (100 C)
ε c = 2.4 x 0.25 x 212 x (1240) 0.16 ε c = 397.6 micro-in./in. To calculate the total elongation due to creep, the sum of the equivalent times (hours) at 212°F (100 ° C ) is determined. In this example, the sum is:
0 + 1690 + 1240 = 2930 hours at 212°F (100°C).
ε c = 2.4 (%RS) T t 0.16 ε c = 2.4 x.25 x 212 x 2930 0.16 ε c = 456 micro-in./in. The temperature change value is calculated using Equation 2.4-40. ΔT = ∑ ε T /α
where Example 2.4-11 : A 795 kcmil (405 mm 2 )ACSR Tern conductor is subjected to 20 hours at 60°F (16°C), 7500 hours at 167°F (75 ° C ) and 1240 hours at 212°F (100°C). What is the sag and tension if creep is a factor? Use a ruling span equal to 1000 ft (305 m). Use Alcoa’s Sag10 program to directly calculate the result and compare it to the results of the Creep Predictor Equations. Assume Alcoa Heavy Loading applies.
∑ ε T = ε @high - ε @ambient ΔT = (456 − 0.64) /(11.8 × 10 −6 ) = 38.75°F(3.8°C)
The final sag following elevated temperature creep is determined by adding this temperature change value to 2-45
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
the temperatures used in the standard sag and tension software calculations. In this example, 60 ° F (16 ° C) becomes 98.75°F (37 ° C), 90°F (32 ° C) becomes 128.75 ° F (54 ° C), 120 ° F (49 ° C) becomes 158.75 ° F (70°C), etc. Table 2.4-16 provides a summary comparison of the calculated sags including the effects of creep at each of the reference temperatures. The differences in the sags predicted by each method can be mostly attributed to the empirical nature of the predictor equations and the creep data and numerical analysis methods deployed by the Alcoa software. Regardless, the use of the predictor equations has been illustrated to convey the process required whenever dealing with the effects of elevated temperature creep for conductors. While the predicted sags vary depending on which analysis method is used, the critical issue is the significant difference in the predicted sag that is directly attributed to the high-temperature operation of the conductor. As discussed, the results obtained by using the hand calculations are in close agreement to the values obtained using the software, and the percentage difference ranged from only 2.2 to 13%. Note that the correlation improves as the temperature is increased, with a difference of only 2.2% when the operating temperature is 212°F (100°C). 2.4.13 Connectors at High Temperature
Splices and compression fittings, which join sections of conductor and other components, must provide both structural and electrical integrity. Therefore, the integrity of these components is critical to the operation of a power line, particularly as the temperature of operation increases. Connector failures can become very costly to utilities, and the cost of failure can be attributed to one of four categories. First, there is the cost associated with potential damages and injuries to the public. Second, there is a cost for loss of revenue from rerouting power. Third is the cost of repairs, which depends heavily on the labor cost for using line crews and equipment, and
Table 2.4-16 Comparison of the Predictor Equations and Alcoa’s Software Results Temperature (°F)
2-46
Predictor Equations (ft)
Alcoa’s Sag 10 Percentage Software (ft) Difference (%)
60
27.5
31.6
90
29.5
33.4
13.0 11.8
120
31.4
35.2
10.8
167
34.2
36.6
6.3
212
36.8
37.6
2.2
fourth, there is the cost associated with the loss of competitive advantage in the marketplace. Transmission line operators use two types of tension connectors: limited-tension connectors and full-tension connectors. Limited-tension connectors are primarily designed to join conductors that are under little or no mechanical tension. These connectors are typically used to splice the ends of two conductors together in a lowtension application, tap a second conductor from a continuous run conductor, or terminate the end of a conductor in a low-tension application. Typical examples of limited-tension connectors are bolted connectors, compression connectors, formed-wire connectors, wedgetype connectors, and implosive connectors. Because these connectors exhibit a limited tensile strength, the part of the connector directly in contact with the current-carrying conductor is generally smaller in area than that of its full-tension counterpart. Full-tension connectors are designed to provide mechanical strength up to, or in excess, of the rated tensile strength of the conductor at all operating temperatures and also to provide a low-resistance conductive path for the current carried by the conductor. Thus, splice connectors are used to join the ends of the conductors in spans between supports, and dead-end (also referred to as terminations) connectors are used to join conductors to the attachment hardware at the end of each tension segment, or special heavy angle, or termination structures. Generally, full-tension connections can be achieved using one- and two-piece compression connectors, formed-wire splices, implosive connectors, and wedgetype connectors, but the compression-type connector appears to be the predominant method of creating a full-tension connection on high-voltage conductors. Although the term “full tension” is commonly used to specify the tensile strength of connectors to match the tensile strength of the conductor, the connectors are typically designed to exhibit a tensile strength of at least 95% of the conductor's rated breaking strength. The main consideration for connectors when evaluating elevated conductor temperature operations is its impact on the connector’s short- and long-term performance and the effect on the service life. Certainly, the hightemperature operation of a circuit greatly increases a connector’s electrical, mechanical, and thermal stresses. If operated unchecked, these stress increases are likely to lead to the premature deterioration of the integrity of the connector and the eventual failure of this critical component. Since the prediction of such a failure is
Increased Power Flow Guidebook
difficult, and the consequences are great, the successful high-temperature operation of a circuit requires a careful evaluation of all of the issues involved. Connector Breakdown Process A connector facilitates the transfer of current through numerous contact points between the connector and the conductor. High current densities and high operating temperatures tend to encourage the buildup of resistive compounds at these contact points, effectively reducing the size of the contact area, or in some cases completely restricting the current flow. Generally, the resulting increase in the temperature of the connector will then allow the formation of new contact points within the component at locations where the buildup of resistive compounds is small. The continuous cycle of closing and reopening of contact points within the connector can be thought of as an “aging” process in which the connector will continue to perform well as long as there are locations where contact points can be easily established.
Once the connector has aged sufficiently so that all locati ons for easi ly establi shin g contac t poi nts are exhausted, the connector is forced to maintain contact points at locations at which resistive compounds are present in order to reach the parent metal. This increases the overall resistance of the connector, its operating temperature, and current density within the remaining contact points. At this time, the higher current densities and operating temperatures cause further buildup of resistive compounds, which in turn further increases the current density and operating temperatures, leading to the eventual thermal failure of the connector. The thermal failure will eventually lead to the electrical failure of the connector, and eventually results in the mechanical failure of the component. Figure 2.4-12 shows typical compression deadend connectors as used on transmission lines, and Figure 2.4-13 shows an infrared image of the connector indicating an impeding failure as indicated by the significant temperature differences at the surface of the component.
Figure 2.4-12 Visual image of problem deadend.
Chapter 2: Overhead Transmission Lines
Elevated temperature operations of conductors will increase the current density and operating temperature of associated connectors. This increase in the associated thermal, electrical, and mechanical stresses will accelerate their aging process, effectively reducing service life. The amount of accelerated aging connectors experience is directly related to the magnitude and frequency of the elevated current and operating temperature operation experienced by the component. Unfortunately, the relationship between the aging of the connector and the loads served is nonlinear, and little success has been achieved in directly quantifying that relationship. EPRI is currently conducting research to assess the performance of transmission-line components when subjected to increases in operating temperatures. Preliminary results indicate that most conductor hardware appears to operate more efficiently when compared to the conductors as long as the components are installed correctly. Results show that failures occur mostly as a result of improper installation, and that many of these issues can be addressed effectively using an appropriate quality assurance strategy. Most well-designed connectors (when properly installed) are capable of operating at high current densities and high conductor temperatures while providing acceptable performance and service life. The current cycle test, an industry standard, is commonly used to evaluate these connector designs. Current cycling the connector results in the thermal expansion and contraction of the electrical contact interface and tends to break down the contact points between the connector and the conductor. Although this standard test identifies procedures and qualification criteria for connectors used under normal operating conditions, the application of this test does have its limitations. Figure 2.4-14 shows typical test results obtained from a standard heat cycling test.
Figure 2.4-13 IR image of problem deadend.
2-47
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Figure 2.4-14 Mechanical load data of a “new” Hawk conductor.
Connectors should be considered as approaching failure if the operating temperature approaches or exceeds the operating temperature of the conductor. Experiments show that the operating temperature of an adequately designed and correctly installed compression connector should be approximately 10 to 30% lower than the operating temperature of the conductor. The reduced operating temperature can be directly attributed to the significantly larger cross section of the compression connector relative to the cross-sectional area of the conductor, the increase in the surface area of the compression fitting relative to the surface area of a comparable unit length of conductor, and the increase in the convection to occur at any measurable wind speed. High-Temperature Effects on Connector Joint Compound Most aluminum connectors, especially compression type, employ a viscous compound in the interface between the connector and underlying conductor. The primary purpose of the joint compound is to provide a barrier that prevents moisture and other contaminants from leaching into the joint. The ingress of moisture and other contaminants is not desirable since this will lead to the internal corrosion of the connector, which is likely to affect not only the tensile strength of the steel strength member in the case of an ACSR conductor but
2-48
also deteriorate the connector’s ability to effectively transfer the current. The repeated high-temperature operation (connector temperatures above 200°F (95 ° C)) degrades the joint interface by causing the viscosity of the joint compound to decrease significantly, leading to the eventual outflow of the joint compound or the carbonization of the joint compound, leading to a reduction in the protection provided by the corrosion inhibitor. Thus, the later scenario leaves a shrunken and hardened residue that is no longer effective as a moisture barrier. The presence of moisture and contaminants in the joint accelerates the connector’s aging process and effectively shortens the connector’s service life. Figure 2.4-15 shows an infrared image of a compression splice on which the joint compound is leaking out of the fill hole located at the center of the component. New and Existing Connectors When designing overhead power lines for high-temperature operations or contemplating the refurbishment of existing facilities, a great deal of consideration should be given to the conductor temperatures at which the connectors were tested. Prudence dictates that connectors designed for high-temperature operation should be
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
high-temperature operation of a particular line can be shunted to reduce their electrical loading and to prolong their service life. Shunts provide an alternate path for the current flow, thereby reducing a connector’s current density and operating temperature. The reduction in the connector’s current density retards the aging process, and extends the long-term performance and service life. Similarly, shunting of marginal connectors can be used to extend the service life and to improve the performance of components.
Figure 2.4-15 Leakage of connector joint compound.
tested and qualified for temperatures well in excess of those expected in service. When evaluating existing connectors prior to the operation of a circuit at a higher operating temperature, it is recommended to evaluate the original performance specifications of the existing connectors. A review of the standards against which the connectors were designed and tested assists in evaluating whether these components are acceptable for operation at significantly increased operating temperatures. Operating electrical connectors at temperatures above those for which they were designed can be risky, and at the least, a standard current-cycle test should be performed to evaluate the performance of each connector. Mitigation of Effects of Connector High-Temperature Operations A cost-effective and frequently used method used to increase the operating life of connectors is by using reinforcing methods such as shunts. Typically, existing connectors that are suspected of being inadequate for the
Nondestructive Methods to Measure Connectors The degradation of a connector can be observed by increases in its resistance and temperature. The increased resistance is measured with devices such as an Ohmstik, developed by SensorLink Corp. The tool takes advantage of the increased resistance by measuring the ac voltage drop across the component that is caused by the current. Typically, resistance measurement devices such as the Ohmstick can operate at currents ranging from 2 to 1400 A and can measure resistances from 5 to 2500 micro-ohms. Figure 2.4-16 shows an infrared image of a defective conductor connection and a summary of the corresponding resistance measurements. 2.4.14 Conductor Hardware
Conductor hardware, as defined in this report, refers to noncurrent carrying devices attached directly to the conductor. Conductor hardware includes components such as suspension clamps (with or without armor rods), dampers, repair sleeves and splices, spacers and spacer dampers, shackles, pins, etc. Generally hardware is manufactured from cast or forged aluminum, but there are instances where metallic hardware has been used, and the issues associated with the use of metallic hardware are discussed.
Figure 2.4-16 Resistance measurement of connector.
2-49
Chapter 2: Overhead Transmission Lines
Metallic Conductor Hardware Metallic conductor hardware for aluminum conductors is fabricated primarily from aluminum alloys, while hardware for copper conductors is mostly fabricated from copper alloys. One of the reasons for the strict selection and use of similar metals is the recognition of the differences in the galvanic properties of these materials. When metals of different galvanic properties are permitted to react in the presence of moisture, the resulting reaction quickly deteriorates the lower ranked material, resulting in significant corrosion to an assembly. Nevertheless, galvanized ferrous hardware and components have been used extensively in the past because of the inherent high strength-to-weight ratio and the fact that the galvanized steel component is relatively inert to both aluminum and copper in a mild climate and environment.
High-Temperature Effects of Ferrous Conductor Hardware Ferrous hardware that either partially or completely surrounds a current-carrying conductor is subject to hysteresis and eddy current losses caused by the magnetic flux associated with the current flow. These eddy current losses manifest themselves in the form of significant heat gains within the hardware, and hence significantly increased operating temperatures. Thus, excessive heating of the hardware or greatly increased operating temperatures within the ferrous hardware at levels above the acceptable level of the conductor is likely to cause the annealing of any aluminum components. The excessive heating and increased temperatures conveyed by the ferrous hardware can anneal the conductor or other aluminum components, thereby reducing the tensile strength and the expected service life. While the effect of the heating is typically localized and adjacent to the ferrous component, the effect on the conductor can be detrimental and sufficiently destructive to mandate the eventual replacement. Heat gain due to hysteresis and eddy current losses in ferrous hardware is a function of the magnitude of the current in the conductor and the hardware’s thermal conductivity. Convection and radiation heat losses from the ferrous hardware are primarily a function of the hardware’s surface area and surrounding ambient conditions. Hence, the operating temperature of ferrous hardware fluctuates in response to changes in the circuit’s load and the ambient conditions. Conductor hardware is deployed in numerous configurations to support and protect the conductor, and is available in many different sizes and shapes. Smaller versions of ferrous hardware have a relatively low ratio of mass to surface area and usually operate at temperatures well below that of the conductor, regardless of cur-
2-50
Increased Power Flow Guidebook
rent. Conversely, larger versions of ferrous hardware have a mass-to-surface-area ratio that can result in hardware temperatures greater than the conductor’s allowable annealing temperature at higher currents. Hardware large enough to produce localized conductor temperatures of concern are usually confined to suspension and strain clamps, but can occasionally be caused by any ferrous device surrounding the conductor as long as they have a large mass-to-surface-area ratio. Published literature, which permits the calculation of the local temperature increase in a conductor’s temperature as a function of the load, is limited. The mitigation of the effects of localized heating under ferrous hardware usually involves either limiting the current rating of a line, limiting the cumulative time a conductor can operate at the elevated rating, or replacing the hardware with nonferrous hardware. Experience shows that the number of conductor and hardware configurations are extensive, requiring each utility to develop customized solutions to address this problem. Nonferrous conductor hardware does not internally generate any heat in response to a conductor’s current. Generally, nonferrous hardware operates at temperatures well below the conductor’s operating temperature because of the increased surface area and the corresponding increase in the convective cooling provided by the wind, if any. Nonmetallic Conductor Hardware Nonmetallic conductor hardware is generally limited to elastomeric compounds, which serve as compressive “bushings” within a hardware assembly. Compression bushings are typically used in spacers, spacer-dampers, and armor grip suspension clamps to provide a resilient interface between the conductor and the hardware.
Publications concerning the effects of high-temperature operations on elastomeric hardware components are limited. During and after high-temperature excursions, the elastomeric components must retain their resilient and semiconductive properties for long-term survival. Loss of such properties can result in component deterioration and/or component failure. High-Temperature Tests on ACSS Conductor Hardware Reynolds Aluminum performed high-temperature current cycle tests of ACSS conductors and associated fittings. Tests were performed on a loop of 1033.5 kcmil (527 mm2), with a 45/7 Stranding, “Ortolan” SSAC conductor with various fittings installed. In all cases, the temperatures measured at the conductor hardware were well below the conductor operating temperature. At a 200oC conductor operating temperature, the measured
Increased Power Flow Guidebook
full-tension splice temperatures ranged from 120o to 130oC. The operating temperature of the partial-tension splices was observed to be significantly higher, ranging from 160o to 170oC. On the contrary, the operating temperature at the suspension clamp was 84oC, and the temperature measured at the first insulator pin was 37oC. Operating temperatures at the AGS unit were 102oC on the armor rods, 46oC on the clamp surface, and 106oC beneath the neoprene sleeve. High-Temperature Tests of ACSR Conductor Hardware Detroit Edison conducted tests of ACSR conductors and hardware to determine if high-voltage power line hardware could be safely operated at temperatures up to 200oC. Tests were conducted over a temperature range from 75oC to 200oC. Hardware tested included aluminum body bolt-type strain clamps, aluminum body suspension clamps, armor rods, parallel groove clamps, line dampers, and full-tension splices. Hardware was tested with 477 kcmil (243 mm2) ACSR Hawk, 795 kcmil (405 mm2) ACSR Drake, 954 kcmil (487 mm2) ACSR Cardinal, and 1431 kcmil (730 mm2) ACSR Bobolink conductors. The aluminum strain clamp temperature ranged from 35 to 61% of the conductor operating temperature for the four conductors tested, while the suspension clamp temperature ranged from 29 to 43% of the conductor temperature. On the contrary, armor rod temperatures were 68 to 80% higher than the conductor’s temperature. High-Temperature Tests on Polymer Insulators Test results on polymer insulators indicate that most insulators are well equipped to handle high operating temperature loads. An EPRI report (EPRI 2002) describes the results of a typical conductor suspension assembly using a polymer insulator. In the test, temperatures were measured on the conductor, suspension clamp, shackle, link, insulator pin, and polymer insulator, as well as the ambient temperature. The temperatures of the test components at the maximum conductor operating temperature of 292oC (not referenced to ambient temperature) ranged from 163oC at the suspension clamp, to 88oC at the shackle, to 43oC at the link, to 32oC at the insulator pin, to 28oC at the insulator. The ambient temperature at the time of the test was measured at 17oC.
Another set of tests on polymer insulators had similar results. In these tests, temperatures were measured at the insulator end fitting near the fiberglass rod end, near the suspension fitting end, on the suspension fitting conductor keeper, on the suspension fitting body near the conductor groove, and on the conductor itself. The testing included the mechanical loading of the suspension assembly and current cycling of the conductor to a max-
Chapter 2: Overhead Transmission Lines
imum conductor core operating temperature of 250oC (not referenced to ambient temperature). Tests were conducted on high-voltage polymer suspension insulators of five different manufacturers. The measured insulator end fitting temperature, nearest the fiberglass rod, ranged from 47o to 61oC depending on the type of polymer insulator. The end fitting temperature nearest the conductor was slightly higher, ranging from 54o to 67oC. After the thermal testing, each insulator was tested mechanically to determine the residual strength. Results showed no measurable degradation of the mechanical performance of the five polymer insulators regardless of the manufacturer. A third set of tests reinforces the same conclusions for polymer suspension insulator assembly. In each test, thermocouples were used to measure the conductor temperature, the insulator end fitting temperature, and the ambient temperature. Sufficient current was applied to the conductor to generate a nominal operating temperature of 200oC. Tests generated end-fitting temperatures ranging from 38o to 46oC at ambient temperatures ranging from 19o to 27oC. 2.5
UPRATING WITHOUT RECONDUCTORING
2.5.1
Introduction
There are two overall strategies to uprating overhead transmission lines without reconductoring: using deterministic methods or probabilistic methods. With deterministic methods, line rating calculations are done using traditional tools, such as the EPRI DYNAMP program, and assumed ambient conditions. Physical alterations to the line can be made (such as retensioning the conductors or raising their support points) to increase the maximum allowed conductor temperatures, thereby increasing the ratings. Or, the assumed ambient conditions themselves can be changed (such as assuming a higher wind speed). With probabilistic methods, actual weather data is analyzed statistically to determine the most viable assumptions and the associated risks. 2.5.2
Deterministic Methods This subsection focuses on uprating methods that avoid reconductoring, involve minimal capital investment, and do not require field monitors. Typical increases in power flow resulting from these options range from 5% to 50%, depending on the original design conditions, the present rating assumptions, and the type of structure and conductor used in the existing line. These uprating choices are particularly effective for older lines, perhaps
2-51
Chapter 2: Overhead Transmission Lines
designed under the old 120oF (49oC) clearance temperature. Since the transmission conductors are not to be replaced, the result will be operation of the line’s existing conductors at increased temperature levels. Consequently, the conductor, its hardware, and its connectors need to be carefully inspected prior to uprating. Any questionable elements need to be replaced. In addition to a physical inspection, the line uprating process must verify that adequate electrical clearances will be maintained after the uprating is complete. Typically, this verification should consist of three steps: 1. Measurement of “everyday” sag clearance and support point locations by use of conventional survey equipment, or airborne digital imaging equipment, with the line out of service or at relatively low electrical load. 2. Calculation of maximum sag (minimum ground clearances) under electrical load equal to the proposed new thermal rating. 3. Experimental verification of electrical clearances under a combination of rated load and worst-case weather conditions through the use of sag or tension monitors. Since the maximum allowable temperature is to be increased, these steps are necessary to be certain that the additional sag does not violate minimum electrical clearance requirements and that any increased annealing of the conductor’s aluminum or copper strands does not reduce the line’s loading safety factors to an unacceptable level. Evaluating Sag Clearance Under “Everyday” Conditions As discussed in Section 2.3, new lines are designed to meet certain minimum electrical clearances under all weather conditions at electrical loads less than or equal to their thermal rating. They are also designed to limit the maximum tension under maximum ice and wind loads to the structure design values. To do this, initial unloaded conductor sags are specified such that the final sags at high temperatures and the maximum tensions under ice and/or wind loading are within these limiting values. By adjusting the initial sags to these “stringing sags” at the time of construction, minimum clearance and maximum tension limits are maintained throughout the life of the line. The “final” sags include an allowance for permanent elongation due to creep elongation of aluminum and to plastic elongation due to ice and wind loads. In addition, because of uncertainties in these calculations, new lines are typically designed with clearance buffers of at least 3 ft (1 m).
2-52
Increased Power Flow Guidebook
With existing lines that have been in service for 10 years or more, the measured sag may be assumed equal to “final” conditions. That is, the conductor has experienced most of the permanent elongation allowed in the original design. Unless the line is retensioned, the error in estimating final sag at the maximum design temperature is limited to questions about thermal elongation at high temperature. Also, since the structures have been located and the support point elevations determined, the initial sag buffer requirement may be less than that required for a new line. Many different techniques are available to determine the electrical clearance under everyday loadings where the conductor temperature is quite close to air temperature. These techniques range from the use of survey crews at selected spans, to flying the span by airplane or helicopter with digital recording devices. The latter provides more data than required and costs more. The former provides less data than one might wish for and costs less. Particularly with digital recording from the air, the data can be loaded directly into line profiling and design programs like PLS-CADD™ and TL-CADD™. This allows a span-by-span verification of sag and a relatively straightforward calculation of conductor sag at higher temperatures. While the accuracy of these measurements is in the range of a few inches (several centimeters), the determination of the corresponding conductor temperature at the time of measurement is less accurate. Generally, the conductor temperature is determined by use of a heat balance equation such as IEEE738 or DYNAMP with the line electrical load and local weather data. If the electrical load of the conductor is less than 0.25 A/kcmil (0.5 A/mm 2 ), then the difference between calculated conductor temperature and actual should be less than 5oC. If the electrical load is higher, then the difference can also be higher, depending on how the calculation is done and how the weather data (see Section 2.3) is determined. Raising Conductor Support Points The thermal elongation of stranded conductors is essentially the same as that of its component strands. Therefore, for an all-aluminum or copper conductor, once the sag at “final” everyday conditions is established, the sag at high temperatures can be calculated with relatively small uncertainty.
For example, consider a line section of an all-aluminum, 37 strand (Arbutus) conductor having a ruling span of 600 ft (183 m) installed to meet the following constraints: maximum tension of 50%, 33% initial unloaded
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
at 15°F (9.4°), and 25% final unloaded at 15°F (-9.4 °C). An equally typical SAG10 program line design sag-tension run is in Table 2.5-1.
In existing lines having longer ruling span sections, there are fewer structures per mile (km) to modify but greater sag increases required to offset increased sag at higher operating temperatures, as shown in Figure 2.5-2.
As an example, consider that the line was originally designed for a maximum conductor temperature of 120°F (49 °C) and the line structures were placed such that the minimum ground clearances are met with the ruling span final sag of 15.5 ft (4.7 m).
Retensioning Existing Conductors Rather than replacing existing conductors with new, it may be possible to increase the everyday tension of existing lines in order to reduce sag at high temperature and therefore increase the line rating. For example, consider the following case where an existing line with Mallard ACSR is to be uprated.
To operate the existing line at 167°F (75 °C), the attachment points must be raised approximately 2.2 ft (0.67 m). To operate at 212°F (100 °C), the attachment points must be raised approximately 4.2 ft (1.28 m).
Table 2.5-2, taken from the SAG10 program, shows the sag and tension (total, aluminum, and steel component tensions) for initial and final conditions for 30/19, 795 kcmil (405 mm2) ACSR (Mallard) initially sagged so as
Given rating conditions of 2 ft/sec crosswind, sun, and an air temperature of 35oC, the rating of the original line is 345 A. By raising the attachment points by 2.2 and 4.2 ft (0.67 and 1.28 m), to allow operation to 75oC and 100oC, the line’s thermal rating is increased to 775 and 1010 A, respectively. Note the large increase in thermal rating corresponding to modest increase in attachment height. Many lines built prior to 1970 originally utilized 49oC as the maximum conductor temperature for clearance estimates. With wood pole H-frame structures, increasing attachment height in order to increase the line thermal rating may be particularly attractive. Crossarm attachment points can be raised, hardware replaced, and shield wires placed on metal pole top extensions at minimal cost. Figure 2.5-1 is a photograph of a wood pole structure where the conductor attachment height has been raised.
Figure 2.5-1 Photograph of a wood pole H-frame structure with raised crossarm and pole-top extensions for shield wires.
Table 2.5-1 Sag-tension Calculations for 37 AAC (Arbutus) ALUMINUM COMPANY OF AMERICAN SAG AND TENSION DATA Conductor Arbutus
795.0 kcmil
37 Strands AAC
Area = 0.6234 sq in.
Dia + 1.026 in.
Wt = 0.746 lb/°F
RTS = 13900 lb
Span + 600.0 ft
Creep is a Factor
NESC Medium Load Zone
Design Points
Final
Temp (°F)
Ice (in.)
Wind (psf)
K (lB/°F)
Weight (lb/°F)
Initial
Sag (ft)
Tension (lb)
Sag (ft)
Tension (lb) 6140
15.
.25
4.00
.20
1.451
12.02
5446.
10.65
32.
.25
.00
.00
1.143
12.00
4294.
10.06
5118
0.
.00
.00
.00
.746
8.77
3833.
6.63
5067.
15.
.00
.00
.00
.746
9.67
3475.a
7.27
4621.
30.
.00
.00
.00
.746
10.58
3179.
7.98
4212.
60.
.00
.00
.00
.746
12.34
2727.
9.54
3524.
90.
.00
.00
.00
.746
13.99
2406.
11.19
3006.
120.
.00
.00
.00
.746
15.54
2167.
12.82
2624.
167.
.00
.00
.00
.746
17.78
1897.
15.24
2210.
212.
.00
.00
.00
.746
19.73
1711.
17.37
1941.
257.
.00
.00
.00
.746
21.54
1570.
19.33
1746.
302.
.00
.00
.00
.746
23.22
1457.
21.15
1598.
a. Design condition. 2-53
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
result from pulling the conductor to a higher everyday tension (up to 25% rather than 15% of RBS at 60 ° F [16°C]) can be offset by the addition of dampers. From Table 2.5-2, it can be seen that increasing the tension from 15% to 25% RBS will reduce the high-temperature sags at temperatures of 75oC to 150oC by about 4 ft (1.2 m). Therefore, the maximum design temperature can be increased to 150 o C or more without violating clearance limits. At the original line’s maximum allowable conductor temperature of 75oC, with an air temperature of 40oC, full summer sun, and a wind blowing perpendicular to the conductor axis at 2 ft/sec, the thermal rating was 735 A. If the retensioned line is rated at 150oC with the same weather conditions, the new thermal rating is 1345 A (83% higher).
Figure 2.5-2 Change in sag for all aluminum conductor as a function of span length.
Limitations on Retensioning Existing Conductor There are several concerns about this method of thermal uprating:
not to exceed a final unloaded tension of 15% of Mallard’s Rated Breaking Strength at 60oF (15.5oC). NESC Medium Loading conditions and conductor temperatures up to 302oF (150oC) are included, but the original line is rated at 75 o C, at which temperature electrical clearance to ground is near the NESC minimum values.
1. The maximum tension exerted on strain structures during maximum wind and ice loading has increased from 7800 to 11,300 lbs. (34.8 kN to 50.4 kN). As a result, it is likely that these structures would need to be replaced. An alternative solution may be to limit the increase in everyday tension so that the increase in tension loading of existing structures was acceptable without having to rebuild. This would, of course, reduce the allowable conductor temperature and the resulting increase in thermal rating.
Notice that the knee-point temperature, where the aluminum tension goes to zero, under final conditions, occurs at only 90oF (32oC). It is assumed that the existing conductor has been inspected, and that the increased vibration that will
Table 2.5-2 Sag-tension Calculations for 30/19, 795 kcmil ACSR (Mallard)a ALUMINUM COMPANY OF AMERICAN SAG AND TENSION DATA Conductor Mallard
795.0 kcmil
30/19 ACSR
Area = 0.7669 sq in.
Dia + 1.140 in.
Wt = 1.235 lb/°F
RTS = 38400 lb
Span + 600.0 ft
Creep is a Factor
NESC Medium Load Zone
Design Points Wind (psf)
15.
.25
4.00
.20
32.
.25
.00
.00
K (lb/°F)
Original Line
Sag (ft)
Tension (lb)
1.955
7.80
11283.
11.26
7823
1.667
7.68
9773.
11.39
6600 6202
Weight (lb/°F)
Sag (ft)
Tension (lb)
0.
.00
.00
.00
1.235
5.30
10495.
8.97
15.
.00
.00
.00
1.235
5.79
9600.
9.66
5760
30.
.00
.00
.00
1.235
6.34
8775.
10.35
5377
60.
.00
.00
.00
1.235
7.56
7357.
11.71
4755
90.
.00
.00
.00
1.235
8.65
6432.
12.57
4433
120.
.00
.00
.00
1.235
9.26
6010.
13.26
4204
167.
.00
.00
.00
1.235
10.27
5422.
14.33
3891
212.
.00
.00
.00
1.235
11.27
4939.
15.33
3637
257.
.00
.00
.00
1.235
12.30
4528.
16.32
3419
302.
.00
.00
.00
1.235
13.34
4178.
17.28
3230
a. Design condition.
2-54
Re-tensioned
Ice (in)
Temp (°F)
Increased Power Flow Guidebook
2. While the conductor in the existing line had reached its final sag condition, increasing the tension will cause additional creep elongation and must be allowed for in the uprating study (see Section 2.4). 3. The calculation of sag and tension for this Mallard ACSR ignored the problem of compression in the aluminum strands. If compression is considered, the sag at high temperature will be higher than that indicated in Table 2.5-2. This has two effects: the sag clearance of the original line may not have been adequate at 75oC, and the change in sag with temperature after retensioning will also be greater than indicated. 4. Conductors and structures that have been in place for many years will be mechanically and electrically stressed to increased levels. Unless the existing conductor, structures, hardware, and connectors are thoroughly inspected, there is a possibility that the reliability of the line will be less than that of a new line or one that was reconductored. Redefining Weather Assumptions Through a careful review of weather conditions, it may be possible to use less conservative weather assumptions for rating calculations. This increases the rating without the need for physical modification of the line. The technique is limited by the increased risk necessarily assumed by allowing higher current operation without increasing everyday clearances.
Figure 2.5-3 illustrates the difference between actual line ratings and static ratings. The rightmost bell-shaped curve represents the probability distribution of line thermal ratings calculated based upon real-time field measurements of weather data. Note that the ratings of the line typically vary over a range of more than 2:1. The
Chapter 2: Overhead Transmission Lines
very lowest ratings correspond to still air, maximum air temperatures, and full sun. A typical static thermal rating of 800 A is shown at the left tail of the rating distribution. A less conservative static rating of about 900 A is also shown. Clearly, the higher the static rating, the more frequently the actual line rating is less than the static. The leftmost distributions are line loadings (which vary as a result of varying customer load levels and system configuration changes) appropriate to each of the static ratings. Note that in this case, the line loadings approach, but do not exceed, the static ratings, and for each loading curve, the load may occasionally exceed the dynamic rating. This happens more frequently (larger overlap area) for the higher load distribution. Unless a dynamic line rating system is in use, the operator cannot know when the actual line rating is lower than the line load and therefore is unable to avoid occasional clearance infringements if the load distribution is high enough.
Actual Line Ratings are Normally Higher than Static Ratings It can be seen from Figure 2.5-3 that most of the time the line rating is well above the static rating and that under these conditions, the line current could safely be higher than the static limit. As long as line loads only rarely approach the line rating, it has been argued that the static rating can be increased with a negligible effect on electrical safety. This approach is investigated more thoroughly in Section 2.6. The method discussed here is much less scientific and much more common. Lines are sometimes uprated simply by using less conservative weather assumptions. Concerns About Using Less Conservative Weather Conditions In a regulated business environment, under ordinary operating conditions, power equipment was lightly loaded. High electrical loadings were rare; hence, the precise determination of high-temperature behavior was not critical. Some years ago, however, as the regulation of utility business began to decrease, many older highvoltage lines have been operated at higher and higher load levels. This might lead to increased failure rates and consequent service outages unless the mathematical models used to specify load limits were refined, and critical equipment parameters verified by measurement.
Figure 2.5-3 Probability density distributions for a typical circuit load and dynamic rating.
Driven by the advent of open transmission access and deregulation of the utility business, there has been a distinct trend toward the use of less conservative rating assumptions with little or no basis in science. Field test-
2-55
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
ing of dynamic thermal methods offered an opportunity both to evaluate the possible increase in ratings, and to detect the frequency of occurrences where existing equipment might be damaged due to less conservative rating assumptions. The calculation of thermal ratings for overhead lines is typically based upon heat balance methods such as that found in IEEE 738-1993. Given a maximum allowable conductor temperature, the corresponding maximum allowable current (the thermal rating) is determined for “worst-case” weather conditions. Maximum allowable conductor temperatures typically range from 50° C to 150°C. Typical “worst-case” weather conditions are a wind speed of 2 ft/sec (0.61 m/sec) perpendicular to the conductor, with full solar heating and an air temperature of 30°C to 40°C. Table 2.5-3 illustrates the advantage of assuming a higher wind speed and the consequence of doing so. Use of a higher wind speed for thermal rating calculations yields an increase in the line rating, even though the maximum conductor temperature (100°C) remains the same. For example, an increase in assumed wind speed from 2 to 3 ft/sec (0.61 m/sec to 0.91 m/sec) yields an increase in the rating from 990 to 1080 A and, since the assumed conductor temperature remains the same, no line modifications are required. The major advantage of this method of uprating is clear—it is very inexpensive. Since the maximum allowable conductor temperature remains the same (100°C), the corresponding maximum sag is unchanged and no line modifications are required. The major disadvantage of this approach is also clear from the rightmost column of Table 2.5-3. This column shows the temperature attained by the conductor for still air conditions , with a line load equal to the calcuTable 2.5-3 Effect of Assumed Wind Speed on Thermal Rating for Drake 795 kcmil ACSR at 100°C, Assuming Full Sun and an Air Temperature of 40°C. Assumed Wind Speed for Line Rating Calculation
Line Rating for 795 kcmil ACSR @ 100°C
Conductor Temperature When Current = Rating and Wind Speed = 0 ft/sec (0 m/sec) (°C)
(ft/sec)
(m/sec)
(A)
0
0
750
100
2
0.61
990
130
3
0.91
1080
145
4
1.22
1160
160
2-56
lated rating shown in column 2. Historically, the joint probability of maximum loading and worst-case weather was considered a rare event. Recent field studies indicate that, in certain areas, the probability of still air may be in excess of 10%. Combined with the previously noted increase in normal and emergency line loading, the temperatures indicated in the last column of Table 2.5-3 may be a real concern, and the use of a less conservative wind assumption may impact line reliability. 2.5.3
Probabilistic Methods
The probabilistic approach uses the actual weather data and conditions prevailing on the line to determine the likelihood or probability of a certain condition occurring. Such a condition could be, for example, the conductor temperature rising above the design temperature (the maximum allowed conductor temperature). These methods have been developed to include a measure of safety of the line. This can be used as a means of comparison of practices between utilities in all countries. The pros of probabilistic methods are that the risk is better known and can be quantified and defended if necessary. The designs can be consistent from a risk point of view in that, if localized weather conditions are used for different lines in different geographical areas, the lines can have different ratings, even though their design temperature and conductor types are the same. If there is a thermal rating limitation on a line, the probabilistic approach can ensure minimal or zero capital is used to uprate the line. The line designers also have far more parameters to vary in increasing the rating of a line. They could use the load profile, surge, or traffic patterns to increase the thermal rating of lines. This is not possible in the deterministic method. The cons of the probabilistic method are that significant amounts of data are required to determine the rating. This includes weather data as a minimum. If more sophisticated methods are required, the data needs to be determined on traffic patterns, surge patterns, and load profiles etc. Regarding the weather data, the variation of the data with time as well as with area needs to be taken into account. While the ambient temperature and solar radiation may be consistent over large areas, the wind speed and direction may vary within a few meters. It is also necessary to know how the parameters will vary into the future. This is particularly important with regard to the more complicated probabilistic methods where, for example, load profile is used. It is thus necessary to be aware of these issues in the determination of ratings.
Increased Power Flow Guidebook
Three main probabilistic methods are available at present: 1. Absolute Method The probability of an unsafe condition occurring can be quantified in this method. The benefit is that an absolute measure of safety can be achieved. The drawback is that the nature of the parameters is extremely difficult to determine. In addition, the correlation between the parameters—for example, the weather parameters—must be determined. This could vary from country to country. 2. Exceedence Method Historical weather data is used to determine the temperature of the line conductors for a given current flow. The amount of time that the temperature exceeds the line design temperature can be determined for each current level. The utility can then decide on the current level to use based on the percentage of excursion or “exceedence.” The advantage of this method is that it is relatively easy to determine the percentages and decide on a level by which to operate. The disadvantage is that there is no way of determining the difference in safety (to the public) between, for example, the 5% and 6% exceedence levels. An adaptation of the above method is to simulate the weather data and the current flow to determine the cumulative distribution of the conductor temperature as a function of current. This curve could be used to determine the current and excursion level. 3. Modified Exceedence Method The safety of a transmission line is estimated by incorporating all relevant factors. From this method, a measure of safety can be developed whereby the practices in different countries can be compared on an objective basis. The advantage of this method is that all factors are considered. The variation of the occurrence of objects under the line—for example, a traffic pattern—can be related to the safety of a line. Designers can use a wider range of methods, not generally used before, to increase the thermal rating of the line. Examples of this are the reduction of surge magnitudes or the number of surges per year, both of which can be used to increase the current-carrying capacity of a line. By using the measure of safety, system planners and line designers are in a position to determine the consequences of decisions in a more objective, rather than a subjective, way. Similarly by using the measure in conjunction with real-time monitoring systems to determine exact conductor temperature, operators can take more objective decisions. Utilities worldwide would also be in a position to determine the safety of their lines in relation to those of other utilities.
Chapter 2: Overhead Transmission Lines
The “Absolute Method” of Determining the Probability of an Accident Research to date has primarily been confined to attempts at determining the probability of an unsafe condition arising. This is determined by ascertaining the probability of each factor occurring and multiplying the probabilities. This is represented in Equation 2.5-1.
P(acc) = P(CT) • P(I) • P(obj) • P(surge)
2.5-1
Where: P(acc) is the probability of the accident occurring. P(CT) is the probability of a certain temperature being reached by the conductor, and is calculated from existing weather conditions, conductor types, and an assumed current. P(I) is the probability of the assumed current being reached, and is determined from the actual current being measured on a system. P(obj) is the probability of the electrical clearance being decreased by an object or person. P(surge) is the probability of a voltage surge occurring in the line and may be determined from fault records kept by the power utility as well as simulations on switching surge overvoltages on the system. If the surge occurs simultaneously with an object being under the line, the likelihood of a flashover is increased. Each of the above is considered to be determined independently. P(CT) is determined by the Monte Carlo simulation technique sampling from distributions of ambient temperature, wind speed, wind direction, and solar radiation to calculate the probability of a certain temperature being reached given a current transfer. The ambient temperature, solar radiation, wind speed, and wind direction are sampled independently to form a set of parameters from which the temperature of the conductor is determined. The problem with the above method is that it assumes no correlation between weather parameters or the current, object, and surge occurrences. This may not be correct in all cases. The correlation between the individual weather parameters, as well as the weather parameters and the surge occurrences and objects being under the line, needs to be ascertained. This problem can be partly overcome by using sets of weather parameters, nmeasured at the same time. These sets will be used to determine the P(CT). Since each set used is determined from actual recordings of ambient
2-57
Chapter 2: Overhead Transmission Lines
temperature, solar radiation, wind speed, and wind direction taken at the same time, the correlation between the parameters is taken care of. Determination of Line Rating by the “Standard Exceedence Method” This method assumes that the design temperature of the line may be exceeded for a small percentage of time, but that the line remains safe because of the low probability of other factors, such as high current levels and switching surge voltages. The amount of time the conductor exceeds the design temperature expressed as a percentage of total time is termed the exceedence level. By determining the exceedence level, and keeping it constant, the line ratings can be determined using different weather conditions or different geographical locations. This method is simpler to use than the absolute probabilistic method described earlier and does ensure consistent risk. The standard use of this method assumes that the full load current will flow at all times. A modified exceedence method uses the load profile of the line in question to increase the thermal rating above that of the standard method.
This (standard) method uses the weather data as well as the current and conductor characteristics to determine the frequency of occurrence of each temperature range attained for a given conductor current. Alternatively the current that would result in the templating or design temperature being reached can be calculated for each set of weather conditions. The frequency of occurrence of each current range can be determined. The weather data
Increased Power Flow Guidebook
used can be hourly readings, although the accuracy will increase with more frequent readings. The steady-state model can be used for the determination of the conductor temperature or the current required to reach a certain temperature. With reference to Figure 2.5-4, the exceedence levels have been calculated for the same conductor (Bersfort) in two separate locations in South Africa. The solid line represents the exceedence levels experienced in Bloemfontein, a hot semi-arid climate, compared to Volksrust, a small town in a more moderate climatic region. The number of lines for Volksrust indicates the differences in the weather data from year to year. The dashed line represents the average of the years. The graph indicates an interesting fact in that the operators utilize a single rating for both sites. The risk or exceedence experienced at both sites is likely to be different for the same current. The operators are therefore operating “blind” with regard to the risk. The exceedence method has the benefit of applying a uniform risk, or probability of exceeding the design temperature, by utilizing different ratings at the different locations. Difficulty often arises in setting the exceedence limit. One approach could be to determine the exceedence limits experienced at present for various geographical areas at different times of the year. This can be achieved by plotting graphs similar to those of Figure 2.5-4. The present current limit is used to determine the exceedence level. This level can then be used to determine the
Figure 2.5-4 Graph showing the results of the use of the exceedence method.
2-58
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
ampacity of different conductors at different design or line design temperatures.
the current is not at the maximum level all the time. These factors vary from area to area and line to line.
Benefits of Using Standard Exceedence Method The Standard Exceedence Method has been in use by the National Grid Company (UK) for some years. Table 2.5-4 gives an example for rating its transmission system. The percentage excursion time, now called “exceedence,” corresponds to the portion of time that the conductor would exceed the stated design temperature if it were operated continuously at the corresponding current. These values of current are compared in the table with their previous ratings assigned on a deterministic basis. The exceedence to which the deterministic ratings actually corresponded, which could not be identified or acknowledged previously, are seen to vary from approximately zero to 6%, depending on the rating, season, and the design temperature.
Instead of looking to the probability of an unsafe condition arising that relates directly to safety, it has been assumed that to exceed the design temperature is unsafe. No knowledge exists of exactly how unsafe it is. The next method, although more complex, goes some way to solve this problem.
Adopting a consistent 10% exceedence throughout the year led to increases in rating from 3% to 30%. More accurate meteorological studies may allow a rating increase without increasing the exceedance. The method also allows greater consistency compared to the other approach, since the exceedence can be made constant for all seasons. Note that the ratings given in Table 2.5-4 are post-contingency values, which are used only in emergency conditions. The risk of flashover depends on the coincident risk of a maximum voltage surge occurring while worstcase cooling conditions exist in the span with the critical clearance. This risk is many orders of magnitude less than the value of exceedence chosen. In addition to this,
Modified Exceedence Method The Standard Exceedence Method assumes that the line current is constant. For lines having a reasonably predictable electrical load cycle, the load cycle shape can be used. The calculation is then referred to as the Modified Exceedence Method.
Effect of the Load Profile on Thermal Rating The effect of a load profile on thermal rating can be quite pronounced. This can be shown in the following set of graphs (Figure 2.5-5) developed for conditions prevailing in Cape Town (moderate climate with strong winds). This load profile was used to generate the exceedence and modified exceedence curves. The conductor used in this case was 196 kcmil (100 mm2), 6/1, “Hare”. Figure 2.5-6 shows the increase in the ampacity of the conductor using the load profile and local weather data. The graph shows that the ampacity can be increased, if we are using an exceedence level of 5%, for example, from 230 A to 340 A. The two graphs using the load
Table 2.5-4 Comparison of Deterministic and Probabilistic Ratings for 4% - A1/S1 - 54/7 “ZEBRA” Design Exceedence Temp %
0.1 50
Summer Previous Deterministic Rating (A)
Probabilistic Rating (A)
Previous Deterministic Rating (A)
Probabilistic Rating (A)
Previous Deterministic Rating (A)
Probabilistic Rating (A)
610
683
770
789
950
847
745
861
925
6
769
888
954
10
790 795
826
912 896
910
980 1019
959
3
901
994
1046
6
930
1025
1079
10 0.1 75
Winter
3
0.1 65
Spring/Autumn
955 912
906
1053 1000
981
1109 1090
1025
3
989
1071
1118
6
1020
1105
1153
10
1048
1135
1185
2-59
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Figure 2.5-5 Load profile for exceedence rating example.
1. 2. 3. 4. 5. 6.
Figure 2.5-6 Results of exceedence rating probability example.
profile for HARE and HARE 95 result from different year’s data being used. This shows that in this type of evaluation it may not be necessary in Cape Town to use many years’ data to determine ampacity as each year is sufficiently variable. 2.5.4
Development of a “Measure of Safety” as a Basis for Line Rating
The above probabilistic methods—the absolute method, the standard exceedence method, and the modified exceedence method—do not make use of all the factors that affect the thermal rating of a line. The factors that affect the safety are:
2-60
Whether or not a surge exists on the line. The magnitude of the surge should one be present. Whether or not an object is present under the line. The size of the object should one be present. The position of the conductor. The probability of flashover as a function of spacing and shape.
Types of Accidents Occurring Relating to Transmission Lines Based on the research conducted to date in Eskom (South Africa), the area in which this probabilistic approach to the determination of conductor ampacity would be most beneficial is on lines above 132 kV. The objects that would result in an unsafe condition arising in this case are mainly vehicles. It should be noted that these findings may vary from country to country, and similar research may be required.
Simulations of transmission-line flashovers indicate that the correlation between the various factors make the calculation of probable safety difficult, if not impractical. It is not merely a matter of multiplying the probabilities of each of the factors together, but to include the correlation functions, which are extremely difficult to determine.
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Simulation using actual weather and data for each factor that affects the safety of a line measured at the same time eliminates the need for correlation evaluation. Simulation of Unsafe Conditions The simulation combines different models to determine whether a flashover occurs to a vehicle or how close the situation was to a flashover. At Eskom this is done by means of four modules. Each of the modules simulates the behavior of the particular parameter. These modules are:
required to cause a flashover from the surge generated at the time. The more positive the mean of the difference, the safer the line. This measure is felt to be the most valid since it takes into account not only the surges generated, but also the surges generated at the time the vehicle is under the line. The designer can readily determine the probability of an accident occurring since the integral (number of incidents) of the curve below zero would represent the number of accidents expected. The distribution of the new safety measure as a function of line design temperature is shown in Table 2.5-5.
• Surge Module. This module determines the month, day, hour, minute, and second in which a surge occurs. It then determines the magnitude of the surge.
• Object Module. This simulates the size and time that a vehicle will be under the line. If the vehicle is under the line at the same time as the simulated surge, the data containing the surge time and magnitude, as well as the vehicle data, is stored.
• Position Module. The position module determines the position of the conductor at the time of the surge.
• Accident Module. Using the gap-surge relationship, it is possible to determine the surge required to create a flashover. This module determines the difference between the surge required to cause a flashover with the actual simulated surge on the line. Developing a Measure of Safety Parameters Independent of Current and Line Design Temperature
The number of surges and vehicles in each category were analyzed based on the generation of 572 “counts,” or times at which the surge and the truck were simultaneously under the line.
• • • • • • • • •
Average counts per year
12.43
Number of cars
26.4% of vehicles
Number of small trucks
49.8%
Number of large trucks
23.8%
Surges of magnitude 1.6
30.6% of surges
Surges of magnitude 1.7
40.6%
Surges of magnitude 1.8
17.1%
Surges of magnitude 1.9
10.1%
Surges of magnitude 2.0
1.4%
The probability of surges follows the expected distribution, but the probability distribution for vehicles under the line is affected by the time span that the different vehicles remain under the line. Incorporating the surges generated on the line into the measure of safety is difficult. One method investigated was to subtract the surge
It appears that the statistical description of the safety measure as listed above is a valid and reliable means of determining the safety of a transmission line since the measure is valid for any line design temperature and takes into account every parameter dealt with in determining the likelihood of an accident. Uses of the Established Measure of Safety A statistical “signature” can now be established describing the safety of a particular line. This can be used as described in the above example to increase current by line design temperature or by reducing surge magnitude.
Utilities are now able to quantify the safety of a transmission line. This will enable presentation of the rationale behind any action taken. Uprating an existing line or establishing a power transfer rating for a new line can be justified in an objective rather than a subjective way. The advantage of the above method is that the probability of an accident occurring can be determined. The safety of the line can be quantified and compared with other risks such as that of nuclear facilities. This will assist with objective discussions with regulators. The model can be used to determine the reliability of lines by comparing statistical signatures of the difference between the surge present on the line and that required to cause a flashover with the insulator string swinging due to wind. The wind data as well as the surge modules can be used in this case. Lines in similar areas with difTable 2.5-5 Probability Distributions versus Line Design Temperature Line Design Temperature oC Mean Std. Dev Max. Min. % below 0
40°C
50°C
60°C
80°C
1.58 0.84 1.95 -1.9 4.3%
1.64 0.78 3.2 -0.37 4.0%
1.89 0.70 3.09 -0.19 0.8%
2.34 0.56 3.32 0.91 0%
2-61
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
ferent designs can be compared, and a measure of reliability relating to conductor swing can be developed. 2.5.5
Comparison of Probabilistic Rating Methods
Table 2.5-6 summarizes the main points of each probabilistic rating method. 2.5.6
Device for Mitigating Line Sag - SLiM
A new class of line hardware, SLiM (Sagging Line Mitigator) (Figure 2.5-7), can help solve problems where there may exist excessive line sag. SLiM reduces excessive sag in transmission lines and allows transmission owners to realize higher line ratings and increases transmission system performance, reliability, and asset utilization. The
passive design of SLiM and its ruggedness allow transmission owners to treat SLiM like typical transmission line hardware such as insulator strings. Its installation procedure is a relatively simple O&M activity. SLiM reduces excess sag and allows transmission owners to realize higher line ratings, permitting them to increase asset utilization and maintain safety and reliability in a very cost-effective manner. SLiM has multiple applications for both new and existing transmission lines to address a host of challenges for transmission owners. SLiM provides transmission planners, engineers, and asset managers another tool to help them manage transmission systems in an increasingly challenging environment. The SLiM can serve as an economic alternative to conventional solutions, such as:
• Replacing the existing conductor with a premium conductor that can operate at high temperatures without increased sag.
• Reinforcing line structures and foundations for increased mechanical loading, and either reconductor with a larger conductor or bundle with the existing size conductor.
• Raising towers and improving foundations at key line locations to provide for increased clearance.
• Adding intermediate towers at key line locations to increase ground clearances.
Figure 2.5-7 The SLiM device. Table 2.5-6 Comparison of Probabilistic Rating Methods Absolute Method
Std Exceedence Method
Modified Exceedence Method
Safety Method
Establishes the absolute probaUses relative comparison of bility of an unsafe condition risk. Cannot relate to an absoarising. Can be used to compare with other industries such lute probability. as nuclear safety standards.
Uses relative comparison of risk. Cannot relate to an absolute probability.
Uses relative comparison of risk. Cannot relate to an absolute probability.
Complex method that requires Uses simulation. Little explicit equations for the proba- advanced probabilistic theory bilities of current, surges, etc. required.
Uses simulation. Little advanced probabilistic theory required.
Uses simulation. Little advanced probabilistic theory required.
Takes into account all factors that affect thermal rating of lines.
Uses weather data and load profile.
Takes into account all factors that affect thermal rating of lines.
Takes only the weather data into account.
Automatically takes care of Requires analysis of correlation weather data correlation by between weather data and using actual wind speed, solar weather data and other factors radiation, wind direction, and such as surges and load. ambient
Can be used on its own.
Can be used in isolation, but may encounter difficulties in determining the exceedence limit to use without reference to an absolute risk
Uses simulation that automatiUses simulation taking care of cally takes care of correlation if correlation if sets of weather sets of weather data and load data are used. profile data are used. Can be used in isolation, but may encounter difficulties in determining the exceedence limit to use without reference to an absolute risk
Can be used as a comparison between two lines, but needs to refer to the risk level found in the absolute method to determine a reference level.
Analysis of data is required to Data can be used directly in the Data can be used directly in the Data can be used directly in the determine the probabilistic func- method without statistical analy- method without statistical analy- method without statistical analytions. sis of the data itself. sis of the data itself. sis of the data itself.
2-62
Increased Power Flow Guidebook
• Installing a sag monitoring system and the infrastructure to process this information. How SLiM Works SLiM uses a shape-memory alloy actuator that is activated by the same temperature changes that cause a conductor to change sag. The device is passive, with no motors or electronic controls. As increasing temperature increases conductor length, and hence its sag, SLiM changes its geometry to decrease line length. As conductor temperature returns to normal, SLiM returns to its original shape, keeping the conductor always within acceptable sag and tension limits (see Figures 2.5-8 and 2.5-9). Some Potential Applications Here is a bulleted list of situations where a SLiM device may offer a viable solution:
• A system contingency situation can cause loading on parallel transmission lines to exceed their thermal limits. These limits are often established to maintain conductor line-to-ground clearances. Thus, the action of SLiM, which mitigates the excess sag caused by high-temperature operation, can allow for safe line operation during these contingencies. Line capacity is increased by allowing operation beyond conventional thermal limits, and expensive line modification projects may not be required.
• Many older lines were constructed to 120°F maximum conductor temperature operation. Studies have shown that SLiM can enable operation of such lines at a conductor temperature of about 200°F without compromise of line clearances or tensions. This can represent a substantial increase of rated line capacity.
• System planning may project that certain lines will become overloaded as local growth increases demand. In this instance SLiM can delay the need for either a new line or considerable line modifications while the anticipated load materializes. Installation of SLiM is a simple O&M activity and can help bridge needs.
Chapter 2: Overhead Transmission Lines
to be as low-profile as possible. SLiM can be employed in a cost-effective fashion to minimize tower height for such installations while maintaining required ground clearances and higher power flows.
• Limitations on line ratings to maintain clearances over road or river crossings can be lifted by using SLiM while maintaining ground clearances and higher power flows.
• SLiM can be used on new line construction and allow for use of lower towers, mitigating visual impacts and community objections. SLiM Specifications
Electrical Connection The SLiM device carries the full line current, splitting the current between the actuator and the body of the device. Standard flexible connectors carry current between the transmission line and the SLiM device. The electrical connectors on the device terminate with 4-bolt NEMA paddles for easy connection to standard line hardware. Mechanical Connection The device is installed in series with the transmission line. Either end of the device is equipped with standard oval-eye end fittings. The mating attachment on the conductor is the choice of the utility. The device accepts any industry standard dead-end attachment with a 1 in. (2.54 cm) clevis pin. Options include dead-end compression fittings, preformed dead ends, and wedge dead ends. Installation The device can be installed at a dead end, or anywhere along a span using procedures similar to line-splicing techniques. During installation, a piece of conductor approximately the length of the SLiM device is removed and replaced by the device. The length of conductor to be removed as well as the number and locations of devices along a section of transmission line can be determined using line-sagging software for optimum performance.
• Line routing or line modifications near airports or other unique situations quite often require structures
Figure 2.5-8 SLiM is strong, maintenance-free, and designed to have a very long life. It is designed for easy installation using hot or cold procedures. Industry standard connectors can be used to attach SLiM to the line. Its operation is configurable to match specific line requirements, and has no negative effects on line electrical performance.
2-63
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Figure 2.5-9 The major components of the SLiM device in its “Dead-End Configuration” and its “In-Line Configuration.”
Operating Parameters Tables 2.5-7 and 2.5-8 list some of SLiM’s basic parameters and operating characteristics. The standard unit is targeted primarily to 115- and 230-kV lines, but can operate in 60- and 70-kV class, as well as 345-kV class lines. Standard units can also be configured to actuate at different temperature points based on individual requirements. Table 2.5-7 Operating Parameters for Standarda SLiM Criteria
Application
Voltage Rating
230 kV and below. Higher voltages (345 and 400 kV) possible.
Target Conductor
Conductors with a breaking load 40,000 lb (180 kN)
Range of Motion
Up to 8 in. (200 mm)
Line Tension @ 110°F
Up to 5,000 lbs (22.5 kN)
Functional Temperatures
~120–212°F (50-100°C) (conductor temperature)
Mechanical Failure Load
> 49,000 lbs (218 kN) – Tested per IEC at Kinectrics
Electrical Current Capacity
> 1400 A
Short Current Rating
40 kA (rms) – Tested per IEC at Kinectrics
Development and Testing of SLiM SLiM has been through several years of extensive R&D and testing including laboratory functionality and reliability testing as well as actual field demonstration.
Functionality testing was performed at PG&E’s training facility in Livermore, California. The sag differential between the test and control spans at the maximum temperature of 100°C was 44 in. (Figure 2.5-10), which closely matched the predicted effect of SLiM. Prior to and following the full functionality testing at PG&E, SLiM and its components were extensively tested for load and current-carrying capacity, fatigue, corrosion, and repeatability of performance. SLiM was also tested at Kinectrics and was subjected to a number of fault current events ranging from 21 kA to 40 kA (rms) for a minimum of 10 cycles. After current testing, SLiM was subjected to increasing load until its break links failed, as designed, at about 49 Kips, exceeding the target range (110% of the conductor breaking load).
Total Weight
~ 85 lbs (380 N) (Production Version)
End-to-end Dimension
~ 5 ft, 3½ in. (1610 mm) open, 4 ft, 7½ in. (1410 mm) closed
End Connectors
Any standard connector with 1 in. clevis pin (utility’s choice)
Installation
“Cold” using standard procedures – or – “Live” using live-line hand procedure (similar to splicing procedure). Detail procedure available upon request.
a. Custom sizes for special applications available.
The SLiM device was installed on the bottom phase of a 69-kV transmission line, in SDG&E’s service area in Escondido, California (Figure 2.5-11), and monitoring equipment was installed directly below the test span on a 12-kV distribution pole. The field demonstration was intended to prove both ease of installation and functionality and reliability. SDG&E crews called the installation “straightforward.” SLiM has successfully completed over a year of field demonstrations.
Table 2.5-8 Example Sag Mitigation for a Drake Conductor Conductor Temperaturea
Excess Sag due to Heating
Span ft / m
Initial ºF / ºC
Final ºF / ºC
Without SLiM ft / cm
750 / 230
110 / 43
212 / 100
1000/300
110 / 43
212 / 100
Reduction ft / cm
5.2 / 158
0.2 / 6
5.0 / 152
6.0 / 183
1.9 / 58
4.1 / 125
a. Tension at 40°F considered equal to 20% of tensile strength of conductor.
2-64
Sag
With SLiM ft / cm
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Figure 2.5-10 The sag differential being measured on a control span (bottom) and a test span (top).
2.6
RECONDUCTORING WITHOUT STRUCTURAL MODIFICATIONS
2.6.1
Introduction
By replacing the original line conductors, it is possible to employ modern conductors having lower resistance for the same diameter and/or having the same maximum sag as the original conductor but at greatly increased temperature. The use of certain new conductors can yield an increase in thermal capacity of as much as 100% at a cost of less than half that of a new line. This section concerns the application of commercially available conductors, but the analysis methods are applicable to new conductor types. Existing lines may be uprated using methods discussed in preceding sections of this chapter, all of which involve using the original conductor. In certain applications, it may make sense to replace the original conductor with a new one, usually having a diameter near the original and often capable of operation at higher temperatures. This section reviews the various reconductoring choices, and provides some insight into those line uprating applications where reconductoring is preferred. Given the low cost, high conductivity, and low density of aluminum, no other high conductivity material is presently used. Therefore, any “low-resistance” replacement conductor must have increased cross-sectional aluminum area, and increased wind/ice and tension loads on the existing structures. Figure 2.5-11 Field demonstration of the SLiM device at SDG&E.
Figure 2.6-1 shows how the thermal rating of an existing line may be increased by about 50% by using a replace-
2-65
Chapter 2: Overhead Transmission Lines
ment conductor with twice the original conductor’s aluminum area. Note that this doubles the original strain structure tension loads and increases transverse wind/ice conductor loads on suspension structures by about 40%. Such large load increases would typically require structure reinforcement or replacement. “High-Temperature, Low-Sag” (HTLS) conductors, capable of continuous operation at temperatures above 100oC with stable tensile strength and creep elongation properties, are commercially available or under development. Practical temperature limits of up to 200oC have been specified for some conductors. As is also shown in Figure 2.6-1, use of an HTLS conductor (having the same diameter as the original) at 180oC also increases the line rating by 50%, but without any significant change in structure loads. Raising the structures may also be avoided if the replacement conductor has a lower thermal elongation rate than the original. EPRI is presently engaged in a project to field-test long samples (several spans) of HTLS conductors in operating lines. This project is in its early stages at the printing of this guidebook, but some preliminary observations are discussed in the following sections. Future versions of this guidebook will be updated with the latest publishable results. The use of a lower-resistance conductor has two advantages—losses are reduced, and operating temperatures remain modest. The use of HTLS conductor has the primary advantage that structure modifications are minimized. In either case, the replacement of existing conductor should improve the mechanical reliability of the line since conductor, connectors, and hardware are all new.
Figure 2.6-1 Thermal rating as a function of conductor area and maximum temperature.
2-66
Increased Power Flow Guidebook
Sag Constraints for Reconductoring As shown in Figure 2.6-2, the original conductor’s “Initial installed sag” increases to a final “everyday” sag condition (typically at 60×F [16×C] with no ice and wind) as a result of both occasional wind/ice loading events and the “normal” creep elongation of tensioned aluminum strands over time. This everyday final sag increases further (but reversibly) due to ice/wind loading or high electrical loads. For most transmission lines, as shown, maximum final sag occurs as a result of electrical rather than mechanical loads.
Any replacement conductor must be installed such that, over time, its final sag under maximum electrical or mechanical load does not exceed the original conductor’s maximum final sag. Otherwise, existing structures will have to be raised or new structures added. HTLS replacement conductors are usually applied to existing lines where structure reinforcement or replacement is to be avoided. 2.6.2
TW Aluminum Wires – ACSR/TW or AAC/TW
While this conductor is limited to operation at moderate temperatures, the use of compact trapezoidal strands results in a resistance reduction of about 20% for the same diameter as the original conductor. The use of aluminum trapezoidal wire (TW) wires in place of round wires potentially increases the cross sectional area of a round wire conductor of the same diameter by approximately 20%. Therefore, the use of TW conductor in uprating offers a reduction in conductor resistance of 20% with no increase in structure transverse loading. If some increase in conductor diameter over the original is possible with limited structural reinforcement, the resis-
Figure 2.6-2 Typical transmission line sag as a function of time, load, and temperature.
Increased Power Flow Guidebook
tance reduction can be in excess of 20%, and the increase rating can be 20% or more. For example, consider an existing line with a 477 kcmil (243 mm2), 26/7 Aluminum Conductor Steel-Reinforced (ACSR) (Hawk) conductor operated to a line design temperature of 90oC. Given reasonably conservative rating weather conditions, the rating of the line is 650 A. If this original conductor is replaced by a Calumet/TW conductor (which has the same diameter) and operated to the same maximum temperature of 90o C, it would have approximately the same sag at 90oC, but its lower resistance would result in a rating that is on the order of 710 A (9% higher). The maximum tension on strain structures and for broken wire calculations would be about 10% higher. To get a larger increase in thermal capacity, a largerdiameter replacement conductor could be used, but this would require the existing structures to handle increased ice and wind transverse loads as well as even higher tension loads than Calumet/TW. Other advantages to this replacement conductor include reduced electrical losses over the life of the line, and since the conductor and connectors are new, one might argue that the reconductored line is capable of safe operation at temperatures above 90 o C and that installed tensions could be increased if dampers are used. In summary, reconductoring with ACSR/TW requires that structures, , especially strain structures, be reinforced. The probable increase in line rating will be modest, but the electrical losses over the life of the line will be less. These conductors are intended to be operated at usual temperatures, and are not part of the EPRI HTLS project. 2.6.3
ACSS and ACSS/TW
Many millions pounds of Aluminum Conductor Steel Supported (ACSS) have been installed and are operating successfully in the United States. However, for many it is still considered a relatively new conductor, and its performance is not well understood. As such, it is an integral part of EPRI’s HTLS conductor field test project. Most of the initial concerns about installation and surface roughness problems due to the use of annealed aluminum strands have passed. The main limitation with ACSS is its relatively low strength and modulus that may limit its application in regions experiencing high ice loads. The use of ACSS/TW can offset this problem to some extent, as can the use of extra-high-strength steel core wires. The conductor and special connectors designed for it allow continuous
Chapter 2: Overhead Transmission Lines
operation at temperatures up to 200oC with conventional galvanized steel core wires. The conductor can be operated above 200oC if Alumoweld or special zinc “Galfan” coated steel is used. ACSS is described in ASTM B 856-95. It consists of fully annealed strands of aluminum (1350-H0) stranded around stranded steel core. The steel core wires may be aluminized, galvanized, or aluminum clad, and are normally “high strength,” having a tensile strength about 10% greater than standard steel core wire. In appearance, ACSS conductors are essentially identical to standard ACSR conductors (see Table 2.6-1). By using annealed aluminum, the rated strength of ACSS is reduced by an amount dependent on the stranding (e.g., 35% for 45/7, 18% for 26/7, and 10% for 30/7). In fact, a 45/7 ACSS conductor has about the same rated breaking strength as a conventional all-aluminum conductor (e.g., 16,700 lbs (71.4 kN) for 954 kcmil (487 mm 2 ) 45/7 ACSS versus 16,400 lbs (73.2 kN) for 954 kcmil (487 mm2) 37 strand AAC [Magnolia]). The thermal elongation coefficient, creep rate, and maximum operating temperature are, however, quite different. ACSS Conductor Designs ACSS is typically available in three different designs: “Standard Round Strand ACSS,” “Trapezoidal Wire of Equal Area,” and “Trapezoidal Wire of Equal Diameter.” In addition, it is possible to obtain all three ACSS conductor designs with any of the standard types of steel core wire (galvanized, aluminized, and Alumoweld). Advantages and Disadvantages of ACSS ACSS provides a number of advantages in reconductoring. The combined effect of these factors can make it economically attractive in thermal uprating applications. It has higher self-damping than conventional ACSR. It has lower thermal elongation over a wide range of conductor temperatures. It can be operated at temperatures as high as 250 °C without damage. It can be installed at smaller initial sags without dampers if it is prestressed. With reference to the preceding discusTable 2.6-1 ACSS Equivalents to Standard Type 16, 795 kcmil, 26/7 ACSR (Drake) Conductor Name
OD (in.)
Alum Area
(mm) (kcmil)
AC Resistance (Ω/ (Ω/km) (Δ%) mile)
Drake ACSR
1.108
28.14
795
0.1170 0.0727
æ
Drake/ACSS
1.108
28.14
795
0.1137 0.0707
-3%
Suwannee/ ACSS/TW
1.108
28.14
960
0.0939 0.0584 -17%
Drake/ACSS/TW
1.010
25.65
795
0.1132 0.0704
-3%
2-67
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
sion of sag clearance, the conductor properties make it attractive for reconductoring applications as well as certain new line designs. In reconductoring existing lines, in comparison to conventional ACSR conductors, ACSS can yield a much larger increase in thermal capacity while minimizing the need for expensive structure modifications. In new lines, this conductor can yield designs with less environmental impact (shorter and/or fewer structures) with greatly increased thermal capacity for essentially no increase in cost. As discussed in the following, the key advantages of ACSS are:
• Operate to 250 °C with no loss in strength • No creep elongation over time • High self-damping (which yields low levels of Aeolian vibration)
• Lower thermal elongation than conventional conductor
• 63% IACS conductivity, not 61.2% • Equal OD and equal AREA options. Higher Maximum Temperature Typically aluminum stranded conductors can be operated at temperatures up to 95°C without significant loss of tensile strength. Aluminum conductors with a steelreinforcing core can be operated at temperatures of up to 150° C for limited periods. Because the aluminum in ACSS is fully annealed at the factory, it can be operated continuously at temperatures up to 250°C or, with special high-temperature-tolerant galvanizing coatings such as “Galfan,” even higher. Table 2.6-2 shows a comparison of continuous ampacity (with 2 ft/sec (0.61 m/sec) crosswind, 40 °C air temperature, and full sun) for ACSS and ACSR conductors. Note that the ampacity of an ACSS conductor operatTable 2.6-2 Continuous Ampacity of Equivalent ACSR and ACSS Conductors as a Function of Maximum Allowable Conductor Temperature
ing at 250°C is nearly twice that of an ACSR of the same cross-sectional area operating at 100°C.
Thermal Elongation Aluminum strands elongate thermally at twice the rate of steel. The sag increase of ACSR conductor is, therefore, less than it is for AAC. In the case of ACSS, the tension level in the aluminum strands is very small, and the conductor elongates thermally as though it were steel. Thus, the sag increase in going from 15°C to 150°C with ACSS may be the same as the sag increase from 15°C to 95°C with ordinary ACSR. As an example of this lower thermal elongation of ACSS, consider the data in Table 2.6-3. The ACSS conductor has the same sag at 150°C as the ACSR conductor of the same diameter has at 100°C. Therefore, for a clearance-limited line, by reconductoring with ACSS, the thermal capacity of the line increases by about 30% without the need to raise or reinforce structures.
Self-Damping The tension of conductors in overhead lines is normally determined by concern about Aeolian vibrationinduced fatigue. It is normal to limit initial tension to no more than 20% of the rated breaking strength in order to limit vibration levels. Because it has higher selfdamping than ordinary ACSR, ACSS may be installed to smaller initial sags, and because it has a lower modulus, it yields lower maximum tensions than ACSR. Low Creep Elongation When reconductoring, one must allow for creep elongation over time with ordinary ACSR. In addition, except for ACSR conductors with a high steel content, one must consider the possibility of accelerated creep at high operating temperatures. ACSS does not creep at any temperature, high or low. Thus, its final and initial sags are the same as shown in Figure 2.6-3. Not only is there little or no difference between the initial and final sag, but also the initial sag is less, and the change in sag due to temperature is less than it is for standard ACSR.
Conductor Temperature (oC)
Drake ACSRa
Suwannee ACSS/TW
Drake/ACSS or Drake/ACSS /TW
75
730
820
720
100
990
1110
980
150
--
1490
1320
Conductor Temp
200 250
---
1770 2000
Sag of Drake ACSR
Sag of Drake/ACSS
1560
(oC)
(ft)
(m)
(ft)
(m)
1740
15
31.0
9.4
31.0
9.4
--
100
37.6
11.5
35.3
10.8
1110
150
--
--
37.8
11.5
1490
a. For continuous loads, ACSR is normally limited to about 100oC to avoid annealing of the aluminum strands.
2-68
Table 2.6-3 Illustration of the Lower Thermal Elongation of ACSS Conductor Ampacity (A)
Increased Power Flow Guidebook
The novel characteristics of ACSS make it attractive as a replacement conductor for HV lines where thermal capacity is inadequate. ACSS can be substituted for existing ACSR of the same diameter. Although having nearly the same resistance and diameter as the conductor it replaces, ACSS can be operated at a much higher temperature without exceeding the original high-temperature sag levels. Since the aluminum strands of ACSS are fully annealed, it has a somewhat lower rated strength than the same stranding in ACSR. In areas where ice and wind loads permit, ACSS may be specified with a reduced steel content. The result is that, with ACSS, the maximum tension loads on angle and deadend structures may be no higher than those generated by the ACSR conductor that it replaces. As an example of the advantages of ACSS in reconductoring, consider Figure 2.6-4, which shows ampacity and sag as a function of maximum allowable tempera-
Chapter 2: Overhead Transmission Lines
ture. The original conductor in the existing line is assumed to be 477 kcmil (243 mm2) ACSR (Hawk). The proposed replacement conductors are 565.3 kcmil (288 mm2) ACSS/TW (Calumet), which has the same diameter as the original and 795 kcmil (405 mm 2 ) ACSR (Drake), which has a diameter that is 30% higher. For continuous operation, the 565.3 kcmil (288 mm 2 ) ACSS/TW (Calumet) conductor at 200 ° C has an ampacity about 25% higher than Drake at 100°C and lower maximum sag than the original or replacement ACSR conductors. ACSS/TW: Field Trial in the EPRI HTLS Conductor Project As part of the EPRI HTLS conductor project, an ACSS/TW conductor was spliced into a line segment of an operating 138-kV transmission line. This test segment consists of four spans, and is approximately 2880 ft in length, and includes five structures (two dead-end and three suspension towers). The test conductor was spliced into all three phases of one circuit of a doublecircuit vertical line. Various field data associated with conductor performance are intended to be collected over an extended period of time (about three years).
The conductor is classified as “Trapezoidal Shaped Wire Concentric-Lay Aluminum Conductor Steel Supported” (ACSS/TW). It is designated by the name “Suwannee,” and is 1.108 in. (2.814 cm) in diameter. Figure 2.6-5 shows photos of the conductor—the outside aluminum strands and steel center strands are indicated.
Figure 2.6-3 Typical behavior of ACSS conductor, illustrating that initial and final sags are nearly identical.
Figure 2.6-4 Ampacity and sag of original Drake ACSR and Calumet ACSS/TW replacement conductor as a function of maximum allowable temperature.
Figure 2.6-5 ACSS/TW cable, manufactured by SouthWire, installed on operating test line.
2-69
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
During the course of the project (ongoing for just over two years at this time), measurements and observations were made of the following quantities:
As a simple comparison, consider Table 2.6-4, a summary of the maximum operating temperatures of the various Japanese heat-resistant conductors.
• • • • • • • • •
High-Temperature Alloys of Aluminum Table 2.6-5 is a description of the heat-resistant alloys of aluminum.
Sag and Tension Weather Parameters Average Conductor Temperature Current Splice Resistances Hardware Temperatures via Infrared Measurements Corona Electric and Magnetic Fields Visual Inspections
This project is still ongoing, and final results are not yet available 2.6.4
High-Temperature Aluminum Alloy Conductors
T-Aluminum Conductor Steel Reinforced (TACSR) is a conductor widely used in Japan. A special type of steel core (“Invar”) adds expense but reduces thermal elongation. There is extensive laboratory test data on the Zirconium aluminum alloy wire materials (TAL and ZTAL). There appear to be no special problems with installation and termination of (Z)TACSR. TAC can be operated continuously up to 150oC and ZTAC to 210oC without loss of strength. The various Japanese manufacturers (e.g., Fujikura Ltd., Sumitomo Electric Industries, Ltd.) have developed a whole range of special high-temperature conductors. These conductors consist of special temperaturetolerant aluminum alloy wires combined with ordinary steel or a special low-thermal-elongation steel wire called “Invar.” The acronyms for these conductors indicate the type of aluminum alloy (TAC, GTA, UTA, XTA, and ZTA); the type of steel core wire (SR or IR); and whether the aluminum strands are trapezoidal; and whether there is a gap between the inner layer of aluminum and the steel core (e.g., GACSR or GTACIR). A partial list of the most common types includes the foll o wi n g n a m e s : TAC S R , G TAC S R , U TAC S R , GTACSR, UTACIR, XTACSR, XTACIR, ZTACSR, and ZTACIR. The acronyms refer to the type of hightemperature alloy, whether the conductor is “gapped,” and the type of steel core material.
2-70
The TAL alloy was developed in the 1960s. The other alloys were developed in a continuing attempt to keep the conductivity near that of ordinary electrical conductor grade aluminum (1350-H19). The relationship between conductivity and maximum continuous temperature is shown in Figure 2.6-6. 2.6.5
Special Invar Steel Core
ACSR conductors are manufactured with a variety of steel wire coatings to prevent corrosion. Normal steel core wire has a tensile strength of 170 to 190 psi (1170 to 1310 Mpa). Invar steel wires have a 15-20% lower tensile strength but also have a much lower coefficient of thermal expansion than conventional galvanized steel wire. The thermal expansion coefficient of conventional steel is 11.5 × 10-6 per-degree-C, whereas the thermal coefficient of Invar steel is only 2.8 × 10-6 per-degree-C. At high operating temperatures, the aluminum strands of any high-temperature conductor unload tension almost entirely to the steel core. With Invar, this happens at a lower (“knee point”) temperature. In addition, Table 2.6-4 Maximum Operating Temperatures (°C) for High-Temperature Alloys Made in Japan Description
Symbol
Max Temp Continuous
Max Temp Emergency
Super Heat Resistant
UTACSR
200
230
Super Heat Resistant
ZTACSR
210
240
Super Heat Resistant
XTACSR
230
310
Heat Resistant
TACSR
150
180
Normal
ACSR
95
125
Table 2.6-5 Conductivity of High-Temperature Alloys Made in Japan Aluminum Alloy
UTAL
% Conductivity
Max Temp Continuous
Min. Tensile Strength
(IACS)
(°C)
(kgf/mm2)
57.0
200
16.2 to 17.9
ZTAL
60.0
210
16.2 to 17.9
XTAL
58.0
230
16.2 to 17.9
TAL
60.0
150
16.2 to 17.9
1350-H19
61.0
95
16.2 to 17.9
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
the rate of increase in sag with further increases in conductor temperature is less with Invar steel cores. This is demonstrated in Figure 2.6-7.
is too early in the project to make any further meaningful conclusions at this time. The data shown in Table 2.6-6 show the physical properties of this conductor.
The EPRI HTLS project has begun the field testing of an Invar “Drake” conductor spliced into a five-span section of a 230-kV line. The installation process went well, but it
2.6.6
Gapped Construction
Gapped ACSR has been used both in Japan and England. The conventional steel core is surrounded by a layer of trapezoidal aluminum wires, and the gap filled with grease. Through the use of special terminations and suspension clamps and by preloading the steel core, the thermal elongation of the conductor is less than that of conventional ACSR, while maintaining the full strength of a conventional ACSR conductor under heavy ice conditions. The lower temperature range aluminum alloys are optionally supplied in a “gapped” construction, as shown in Figure 2.6-8—a picture taken from a Sumitomo Technical Data Sheet. In the gapped construction, the space between the steel core and the inner layer of the aluminum alloy strands is filled with high-temperature grease to prevent corrosion. In addition, the gapped construction conductors are installed with full tension on the steel core (and little or no load on the aluminum strands).
Figure 2.6-6 Plots of conductivity (top) and loss of strength (bottom) for high-temperature Japanese aluminum alloys.
It was noted in the preceding comparison of Invar with conventional steel wire that Invar has a reduced tensile strength. While it is conceivable that a gapped construction conductor could be made with an Invar steel core for use in a light-loading region such as Arizona, it is not commonly done in Japan, where heavy ice and wind loads commonly occur. Thus, as shown in Figure 2.6-8,
Figure 2.6-7 Comparison of ACSR-type conductors with Invar and conventional steel cores.
2-71
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Table 2.6-6 Physical Properties of a Drake Invar Conductor Item Cable designation Stranding wire composition Super thermal-resistant aluminum-alloy wire High tensile strength aluminum-clad invar wire Minimum rated tensile strength
Unit
Specifications
--
Hi-STACIR/AW 795kcmil (Drake)
Nos./mm Nos./mm
26/4.44 7/3.45
kgf
13,630
Calculated cross-section areaa Super thermal-resistant aluminum-alloy wire High tensile strength aluminum-clad invar wire Complete conductor
mm2 mm2 mm2
402.56 65.44 468.0
Calculated overall diametera High tensile strength aluminum-clad invar wire Complete conductor
mm mm
10.35 28.11
Calculated nominal weighta
kg/km
1,582
Calculated D.C. resistance at 20°Ca
ohms/km
0.0706
Typical modulus of elasticitya Up to transition point temperature Above transition point temperature
kgf/mm2 kgf/mm2
7,590 15,500
1/°C 1/°C 1/°C
17.5 x 10-6 3.7 x 10-6 10.8 x 10-6
Typical coefficient of linear expansiona Up to transition point temperature From transition point temperature to 230°C From 230°C to 290°C Maximum operating temperature
Continuous
°C
210
for emergency
°C
240
Calculated current carrying capacityb
Continuous
A
1,628
for emergency
A
1,752
The direction of lay of the outer most layer
--
Left-hand (S)
Standard length per reel
m
200 -0%/+1.0%
a. Tabulated values are for reference calculated on standard diameter and density. b. Current carrying capacity is calculated on the following conditions: Ambient air temperature (°C) 40 Maximum temperature (°C) 210 Frequency (Hz) 60 Wind velocity (m/s) 0.61 Total solar and sky radiated heat flux at sea level (W/cm) 0.10 Emissivity 0.50 Solar absorptivity 0.50
Figure 2.6-8 Summary table showing gapped and conventional constructions for Japanese high-temperature conductors.
2-72
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Gapped conductors are designed with conventional high-strength steel core wires. Gapped Conductor: Field Trial in the EPRI HTLS Conductor Project The EPRI HTLS project has begun the field testing of a Gap conductor spliced into a four-span section of a 230kV line. The installation process went well, but it is too early in the project to make any further meaningful conclusions at this time. The data shown in Table 2.6-7 show the physical properties of this conductor.
There are presently no other installations of this conductor in North America; however, there are many applications in other countries (e.g., Japan, UK, Saudi Arabia). Figure 2.6-9 shows a photo of a lineman from a North American utility being trained by a specialist from Japan on the splicing technique. The participants
In addition to a field trial on an operating transmission line, the EPRI HTLS project included a demonstration and training session on the installation of a Gap conductor on a full-scale test line at the EPRI Engineering and Test Center in Lenox, Massachusetts. The installation of a Gap conductor is somewhat unique, particularly in the need to strip back a sizeable amount of the aluminum outer strands in order to expose and splice the steel core separately from the aluminum layers in a “two-step” splice arrangement.
Figure 2.6-9 A lineman being trained on the installation of a Gap conductor.
Table 2.6-7 Physical Properties of a Drake Invar Conductor Item
Unit
Construction
Nos./mm
Proposal 16/4/4-ZTAI 10/TWa-ZTAI 7/3.2-Est
Direction of outer lay
--
Minimum breaking strength
kN
149.2
times
10-14 8-16
σ/km
0.0714
Outer layer Inner layer
Aluminum layer
Lay ratio (length/diameter)
Steel core
16-26
Maximum D.C. resistance at 20°C Calculated cross-sectional area
Z-Strand
Super thermal resistant aluminum alloy Steel
413.2 mm2
Total
56.29 469.5
Outer diameter
mm
27.8
Weight
kg/km
1614
Modulus of Elasticity
Conductor Steel Core
GPa
79.1 205.9
Coefficient of linear expansion
Conductor Steel Core
x 10-6/°C
19.4 11.5
Cross sectional view
a. TW Trapezoid wire
2-73
Chapter 2: Overhead Transmission Lines
of the training session generally believed that, although the installation and splicing technique is different than what they are accustomed to, it was easy to learn and very “do-able.” However, it is recommended that prior to an installation, linemen unfamiliar with the methods should be provided training on the techniques involved. 2.6.7
ACCR Conductor
The Aluminum Conductor Composite Reinforced (ACCR) is commercially available in limited quantities from the 3M Company. Reasonably extensive tests have been performed on several sizes of this conductor under laboratory conditions, and terminations and suspension clamps are available from Preformed Line Products. Xcel Energy, Hawaiian Electric Company, and Western Area Power Administration have successfully completed test installations. The installation of this conductor appears to be fairly straightforward, but may require special large blocks and careful handling. The key advantage of ACCR is that the composite core strands have a conductivity of about 40% International Annealed Copper Standard (IACS) and have the modulus and tensile strength of steel but are approximately the same density as aluminum. The ACCR conductor is about to be field tested in the EPRI HTLS conductor project. Future updates to this guidebook will provide more details as they become available. 2.6.8
Conductors with Exotic Cores
There are other less well-known conductors that are either still in the development stage, or in early trials compared to the other HTLS conductors. One is a fiberglass core conductor that was a popular topic of discussion in the power industry’s research community, but interest seems to have dwindled recently. Another has a carbon fiber core with a slightly negative coefficient of thermal expansion. Development of this conductor was supported by the National Science Foundation, and a patent has been issued. However, no significant laboratory or field tests have been reported thus far.
Increased Power Flow Guidebook
line. The installation process went well, but it is too early in the project to make any further meaningful conclusions at this time. Figure 2.6-10 shows a photo of the conductor’s cross section. The core has the look and feel of a rod that is somewhat rigid, but with some flexibility. This conductor requires some special hardware and installation techniques, and linemen would require some degree of training prior to installation. Also, as with any core that has a polymer component, there is some concern about long-term performance. 2.6.9
Comparing ACSS and High-Temperature Alloy Conductors
The major advantage of using ACSS is its cost (typically sold at a premium of less than 50%) and its wide availability outside of Japan. Also, ACSS has been used extensively, and most of the handling and installation difficulties are well understood. The major advantage of the High-Temperature Alloy conductors is that they can be used in regions experiencing heavy ice and wind loads (ACSS may not), and they are applicable to EHV lines, where surface roughness of ACSS may yield higher corona noise and radio noise levels. The cost of these conductors, however, appears to be relatively high (probably a premium in excess of 100% over conventional ACSR). The availability of these high-temperature alloy conductors outside of Japan is uncertain at this point, and shipping costs would simply worsen the cost issue. The selection process for HTLS replacement conductor is unique to each line uprating, but the most important aspect is sag as a function of temperature. Consider an existing line with 795 kcmil (405 mm 2 ) 26/7 Drake ACSR installed in a 1000 ft (305 m) ruling span to an initial unloaded tension equal to 20% of its rated breaking strength at 60°F. The everyday initial sag of 21.8 ft
Another conductor that involves a carbon and polymer fiber core, referred to as ACCC (aluminum conductor composite core), has received some press coverage recently. Very little laboratory test data have been published, and there is not much expertise in the industry on it. Apparently, there are other business-related issues about the ability to procure it at this time. The EPRI HTLS project has begun field testing a sample of the ACCC conductor in four spans of a 69-kV
2-74
Figure 2.6-10 Cross section of an ACCC conductor.
Increased Power Flow Guidebook
(6.6 m) increases to 25.7 ft (7.8 m) over the life of the line. The initial conductor tension is 15,300 lbs (68.3 kN) under maximum ice and wind load. At the original maximum conductor temperature of 100°C (212°F), the ruling span sag is 31.7 ft (9.7 m). To avoid raising the existing structures, any HTLS replacement conductor will also be limited to a sag of 31.7 ft (9.7 m) at its maximum temperature. The thermal rating of DRAKE at 100 ° C is 990 A for 2 ft/sec (0.61 m/sec) crosswind, 40° C air temperature, and solar heating for summer at noon. The sag behavior of HTLS replacement conductors (ACSS, ACSS/TW, ACCR(3M), GTACSR, and TACIR) are compared in Figure 2.6-11, where each of the HTLS alternatives has the same diameter as Drake and the same final unloaded sag at 60°F as the original conductor. From this figure, one can see that the ACCR conductor, with its very low thermal elongation, attains the highest operating temperature of 370°F (190°C). Given the relatively high conductivity of its composite core, the thermal rating is 1550 A. ACSS/TW reaches the maximum sag (31.7 ft (9.7 m)) at 120° C, given the thermal elongation of its steel core, which yields a thermal rating of 1270 A with its somewhat higher aluminum cross-sectional area. T-Aluminum Conductor Invar Reinforced (TACIR) reaches the maximum sag at 270°F (132°C) for a thermal rating of 1220 A. Gapped T-Aluminum Conductor Steel Reinforced (GTACSR) reaches the sag limit at 124°C for a thermal rating of 1170 A.
Chapter 2: Overhead Transmission Lines
For all of these replacement conductors, the conductor temperature at the maximum sag of 31.6 ft (9.6 m) is well below their continuous operating temperature limit. The thermal rating comparison could be quite different if the line were not clearance limited or limited to a higher sag. Similarly, the results could be quite different if the final everyday sags of the HTLS conductors were different due to differences in vibration damping or structure tension load limits. 2.7
DYNAMIC MONITORING AND LINE RATING
2.7.1
Introduction
If dynamic rating methods are applied to increase the effective rating of an overhead line, real-time weather data and, optionally, line temperature or sag-tension data must be communicated from multiple remote locations to the operations center where the line rating calculations are performed. In all such cases, the line rating is no longer constant but varies with weather conditions. This technology has been implemented at a number of EPRI member utilities and is worth considering in cases where there is a need for a modest increase in rating at minimum capital investment. The technology requires operational flexibility and available SCADA/EMS communications. 2.7.2
Dynamic Ratings Versus Static Ratings The calculation of thermal ratings for overhead lines is typically based upon heat balance methods such as that found in IEEE 738-1993 (see Section 2.3). For static ratings, given a maximum allowable conductor temperature, the corresponding maximum allowable current (the thermal rating) is determined for “worst-case” weather conditions.
As discussed in Section 2.2, for most existing transmission lines, the maximum allowable conductor temperatures typically range from 50°C to 150°C. In most cases, the maximum temperature is limited in order to avoid excessive conductor sag (referred to as a “clearance limited” line), or, in some cases, a loss in conductor strength (referred to as a “thermally limited” line).
Figure 2.6-11 Typical plot of sag versus temperature for various HTLS conductor types.
Also, as discussed in Section 2.5, most power utilities (both domestic and foreign) assume “worst-case” weather conditions that are not really worst, but rather conservative. Worst-case line rating conditions would be the peak 1-hour air temperature and still air with full solar heating. Conservative line rating conditions assume a wind speed of 2 to 3 ft/sec (0.6 to 1 m/sec) perpendicular to the conductor with full solar heating and
2-75
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
a reasonably high air temperature of 30°C to 40°C. As a result, dynamic line ratings are usually higher than static line ratings but can occasionally be less. Table 2.7-1 illustrates the advantage and consequence of various wind speed assumptions. Use of a higher wind speed for static thermal rating calculations yields an increase in the line rating, even though the maximum conductor temperature (100 °C) remains the same. For example, an increase in assumed wind speed from 2 to 3 ft/sec (0.61 m/sec to 0.91 m/sec) yields an increase in the rating from 990 to 1080 A and, since the assumed conductor temperature remains the same, no line modifications are required. The major advantage of this method of uprating is clear—it is very inexpensive. Since the maximum allowable conductor temperature remains the same (100 °C), the corresponding maximum sag is unchanged and no line modifications are required. The major disadvantage of this approach is also clear from the rightmost column of Table 2.7-1. This column shows the temperature attained by the conductor for still air conditions, with a line load equal to the calculated rating shown in column 2. Historically, the joint probability of maximum loading and worst-case weather was considered a rare event. Recent field studies indicate that, in certain areas, the probability of still air may be in excess of 10%. Combined with the previously noted increase in normal and emergency line loading, the temperatures indicated in the last column of Table 2.7-1 may be a real concern, and the use of a less conservative wind assumption may impact line reliability. 2.7.3
Advantages of Dynamic Rating
A Flexible Response to Uncertain Load Growth In a regulated utility environment, circuit load growth was reasonably predictable, and the corresponding need for increases in circuit capacity could be predicted years in advance. In the increasingly “open access” environTable 2.7-1 Effect of Assumed Wind Speed on Thermal Rating for Drake 795 kcmil ACSR at 100°C, Assuming Full Sun and an Air Temperature of 40°C Conductor Temperature Line Rating for Assumed Wind when current = 795 kcmil ACSR rating and wind speed = Speed for Line @ 100°C Rating Calculation 0 ft/sec (0 m/sec) (ft/sec)
(m/sec)
(A)
(°C)
0
0
750
100
2
0.61
990
130
3
0.91
1080
145
4
1.22
1160
160
2-76
ment, circuit load growth is much less certain, and providing appropriate increases in circuit capacity is much more difficult. Also, in our present economic state, large capital expenditures are unattractive, especially if those expenditures turn out to be unnecessary. Dynamic monitoring leading to modest practical increases in capacity for equally modest capital investment appears to be an attractive uprating alternative. Avoid Circuit Outage With those methods of uprating existing lines that require physical modification of the line—reconductoring, raising support points, retensioning—the line must be de-energized. This may be expensive if loss of service results in increased generation costs. Installation and calibration of some line monitoring devices do not require taking the line out of service for more than a few hours. With some noncontact monitors, the line may stay in service during installation. Monitoring Equipment May be Moved and Reused Monitoring equipment and communication links are, in general, reusable. Thus they may be applied to lines on a temporary basis, allowing postponement or avoidance of a more traditional uprating project. If the line is eventually physically modified, the monitors can be used at another location. This process is limited by the durability of monitors and the rate of change in communications equipment. Improved Clearance Accuracy One of the benefits of real-time line monitoring is the improved understanding of how existing transmission lines behave when subjected to heavy electrical loading. Such high loading events in a regulated environment were rare, and errors in clearance estimation were, therefore, of little concern. Given the difficulty in getting new lines approved and the increased utilization of existing lines under both normal and emergency conditions, accurate determination of electrical clearances along the line is becoming essential. Real-time monitors combined with direct communication links to SCADA allow the system operator to load existing circuits with confidence that minimum clearances are being met. This allows increased utilization (higher ratings) during most loading situations and the avoidance of dangerous clearance violations during those increasingly frequent times when the line is heavily loaded during a period of poor rating weather conditions (low wind speed, high solar heating, high air temperature). 2.7.4
Disadvantages of Dynamic Rating
Need for Real-time Communication to SCADA Transmission owners have not traditionally monitored overhead lines, especially in real-time. Whatever type of
Increased Power Flow Guidebook
monitoring device is used, communication of the measured values back to the system operator is essential. This requires two communication links, one from the monitor to a nearby substation, and a second from the substation to the operations center. These communication links must be set up and maintained if the dynamic monitoring and rating method is to be useful. Installation and Material Cost The cost of any dynamic monitoring system must be weighed against the cost of other uprating methods. Costs include monitors, communications equipment, software, and engineering as well as the cost of maintaining each. In general, the cost of real-time monitoring and rating should be significantly less than the cost of more conventional uprating methods. Operational Issues In contrast to the other line uprating methods discussed in this report, dynamic monitoring and rating methods require a change in the way system operators limit circuit loading. With such methods, the system operator sees a circuit load limit that varies significantly with time, and at certain times can be less than the present fixed line rating. This typically requires some mental adjustment by operators that is partly offset by normally higher line ratings. A culture change regarding line ratings needs to take place. This can be facilitated by performing some upfront dynamic rating studies. It can prove very useful to gather data offline for a period of time, then run real-time simulations on the data. This can help educate operators (and engineers and managers) about the technology and its usefulness. Also, this data itself can be very useful in identifying hidden power capacity in lines.
Chapter 2: Overhead Transmission Lines
the line current and weather conditions are known in real-time, the conductor temperature near the weather monitor can be calculated in real-time (EPRI 1995). Weather stations can include standard propeller-type anemometers, or the more sophisticated 3-D ultrasonic units. The latter are quite expensive, but have no moving parts and are therefore very reliable, are very accurate even at low wind speeds, and can measure vertical air movement. Figure 2.7-1 shows a photograph of a weather station with both anemometer types. Conductor Temperature Monitors Conductor temperature monitors incorporate a clampon thermocouple, attached directly to the energized conductor and linked to a ground station by radio. The accuracy of temperature monitors depends on how close the measured conductor temperature at one spot is to the average line section temperature. It has been observed that conductor temperature can vary significantly along its length due to large variations in wind speed and direction. Line Tension Monitors A load cell can be used to determine the line tension. The load cell is placed on the grounded side of dead-end insulator strings. The measurement of line tension can then be converted to the average temperature of the line section.
A base station is mounted on the structure and connected to the load cells by cable. Communication to a base station is usually by spread spectrum radio, and the units can be solar powered. The line is normally deenergized when the load cells are installed.
2.7.5
Real-time Monitors The maximum electrical power flow down an overhead transmission line is typically determined by the need to limit conductor sag and thus maintain minimum ground clearances that are specified by a maximum allowed conductor temperature. Various monitoring methods have been proposed and tested, all of which are typically applied to determine the line’s sags in all its spans and the maximum current that can be carried without violating minimum electrical clearance requirements in any span.
The following real-time monitors are either commercially available or have been field-tested at a number of locations: Weather Stations Weather stations generally measure wind speed and direction, air temperature, solar intensity, and rain. If
Figure 2.7-1 A weather station with a 3-D ultrasonic anemometer mounted next to a standard propeller-type anemometer.
2-77
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Sag Monitors EPRI recently developed a device for monitoring conductor sag in real-time. It is based on digital video technology, and is called the video sagometer (EPRI 2001).
logger. In addition to the sag/ground clearance data, the data logger also records the date, time, temperature, correlation factor, and other data described in the reference (EPRI 2001).
Figure 2.7-2 provides a very simple illustration of the basic concept and main components of the video sagometer system. The main components include a video camera based on highly light-sensitive charge coupled device (CCD) technology, a passive reflective target, a solid-state target illuminator, a communication system, and associated electronics.
Communication of the data back to a control center or engineering office is accomplished via cell phone and/or spread-spectrum radio. Data can be retrieved in archived blocks or provided in real time, although realtime transmission by cell phone is generally impractical. In addition, the system can be configured to transmit digitized images of the camera’s field of view.
The camera unit is typically mounted on one of the structures of the line being monitored, but it could be mounted on any appropriate structure in the vicinity. A small, passive, reflective target is placed on the conductor being monitored. A low-power solid-state illuminator (diode laser or LED-based device) is mounted with the camera to illuminate the target at night or when ambient light is not sufficient.
The systems can be powered by solar-cell/battery arrangements, or by standard ac distribution power if available at the site. The systems, including the targets, can readily be installed on energized EHV transmission lines, or readily removed and relocated.
Image recognition algorithms residing in local firmware determine the position of the target within the camera’s field of view. The target’s ground clearance is determined from that position through a calibration procedure performed during installation. The conductor’s sag and/or ground clearance is determined at any point along the span from the catenary equation. The systems have proved to be incredibly accurate. Readings are taken at user defined intervals—typically about every 10 minutes—and stored in an onboard data
Figure 2.7-2 A simplified illustration of the video sagometer concept.
2-78
Utilities have used these systems in a variety of ways. Some simply monitor the ground clearance in real time as a simplified means of rating their lines in real time. Others use the more sophisticated approach of using the real-time data in conjunction with EPRI’s Dynamic Thermal Circuit Rating (DTCR) software to perform realtime rating calculations. Some have used the data in uprating studies. Figure 2.7-3 is a photograph of an installation of a video sagometer on a wood pole. The communications and associated electronics are mounted in boxes near the base of the pole. The video sagometer underwent extensive testing at the EPRI-Lenox facility, and now has a proven performance record on operating transmission lines throughout North America, and over a line voltage range of 69 kV to 500 kV. The video sagometer offers several features:
Figure 2.7-3 The video sagometer mounted on a wood pole.
Increased Power Flow Guidebook
• It can easily be installed, or moved, without taking a line outage. In fact, of all the systems installed in North America, most were installed while the line was energized.
• It does not have to be installed at a dead-end structure. It can be installed on any of the transmission structures, on nearby poles, on its own pole, or mounted anywhere in the vicinity of the line.
• Because conductor sag depends on average conductor temperature, sag measurements are equivalent to temperature measurements (and tension measurements). This is important for lines that are thermally constrained, and makes it possible to use heat balance equations for rating computations.
• The system has proven to be incredibly accurate, providing sag measurements to better than quarter-inch accuracy.
• The system provides a direct indication of sag, which can be the most relevant quantity for line operation. The system can also be placed at the most critical span in the line.
• Its operation can be simply verified at any time by comparing the measured height of the conductor to the sagometer’s output. Comparative measurements can readily be made by any simple means (surveying equipment, range finder, tape measure, etc.).
• Because of the so-called ruling span effects, measurement of sag at one span provides the sag and temperature information for the entire line section.
• The systems can be powered by solar cells and battery pack, or by standard AC power if available at the site. Both types of systems have been installed in North America.
• On-board electronics store the information for later retrieval and/or provide the information in real-time.
• Information is transmitted back to a control center via cell phone or spread-spectrum radio. Both types of systems have been installed in North America.
• The system can also provide other information, such as ambient temperature, battery voltage, etc. Also, a new device has been developed that works in conjunction with the sagometer that can monitor load at the site. Load needs to be known in real-time in order to perform dynamic rating calculations.
• The system is able to transmit a digitized image of the line back to a control center for further scrutiny if needed. This feature could be used when there appears to be anomalous line behavior, such as icing events or other serious physical damage to the line.
Chapter 2: Overhead Transmission Lines
2.7.6
Dynamic Rating Calculations
There is a distinction to be made between the real-time monitoring and dynamic rating of overhead lines. Realtime monitoring is easier, but less useful in guiding operator actions than providing dynamic ratings. For example, the conductor temperature, sag clearance, or tension of an overhead line can be monitored with a temperature monitor, a video sagometer or a load cell, and the result reported to the system operator by a variety of communication methods. Such measurements can be very useful during periods of high electrical loading in guiding the operator as to the “real-time” state of the line. Such measurements can be used to avoid load shedding or load reduction that would be required by static rating methods. The limitations of such real-time monitoring involve the operator’s needing to know the specific limits on temperature, sag, or tension for the line section, and the operator’s needing to estimate how large the electrical load can be in order to meet physical limits. Dynamic thermal ratings require certain calculations based on the real-time sag, conductor temperature, or tension monitor data, however, since such ratings may be directly compared to electrical load to guide operator actions even where the operator does not have detailed knowledge of line design limits on temperature or sagtension. Dynamic thermal ratings are also useful prior to high post-contingency loadings and may therefore be utilized to maximize load flows and minimize the likelihood of clearance or over-temperature occurrences during emergencies. Dynamic thermal ratings are calculated on the basis of thermodynamic heat balance in the line conductors (Douglass and Edris 1996, 1999; EPRI 1995). If realtime tension or sag is monitored, the tension or sag must be converted into an equivalent conductor temperature in order to serve as the basis for dynamic rating calculations. With both tension and sag monitoring systems, the conductor temperature is not directly measured. Therefore, the temperature of the conductor must be inferred from other measurements. This process of relating conductor temperature to sag or tension is called “line calibration.” Figure 2.7-4 illustrates how a “line calibration” is done with a tension monitor (note that a very similar graph is used for sag measurements—i.e., sag versus temperature is plotted). The vertical axis is the line tension. The horizontal axis is the estimated conductor temperature. In this case, the conductor temperature is assumed equal to
2-79
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
The conductor temperature (and the sag and tension of the line) is predicted based on weather conditions, line current, and conductor parameters. Conductor temperature is used to determine the position of the conductor in light of the sag-tension line design data. Alternatively, the conductor temperature is compared to the line design maximum allowable conductor temperature, and it is assumed that if the design temperature is reached, then the safety limit is exceeded and there is risk to the public.
Figure 2.7-4 Example of “line calibration” from a previous EPRI field test at PECO Energy.
that reported by a “net radiation sensor,” which is a short length of aluminum rod, oriented in the direction of the line section and painted to approximate the emissivity of the line. This is a reasonable assumption during those times when the line current is low and the line conductor may be assumed to have nearly the same temperature as the painted aluminum rod. The symbols indicate 15-minute average tension and solar temperature data taken for the line during periods of low current. The curve shown in Figure 2.7-1 is taken from a normal sag-tension calculation (done with Alcoa’s SAG10 program), where the final unloaded tension at 15°C was set equal to about 6350 lbs (28 kN) in order to fit the tension field data. The curve has also been expressed as a polynomial, as shown by the fourthorder equation shown in the figure. Given the tension-temperature (or sag-temperature) equation for a line section, tension (or sag) measurements can be converted to equivalent conductor temperature and dynamic rating calculations performed. Weather-Based Ratings Instruments to measure wind speed, wind direction, solar intensity, and air temperature are placed at the approximate height of the transmission line conductor, preferably in the transmission right-of-way. Weather data from airports and other commercial stations is likely to be inappropriate for real-time monitoring of lines. As in most monitoring methods, the line current is obtained from conventional current transformer measurements at a nearby substation.
2-80
The highest conductor temperatures are obtained for the lowest wind speeds, and those winds that are nearly parallel to the line direction. Therefore, the wind anemometer must be of high quality, and be able to measure wind speeds below 3 ft/sec (1m/sec). The propeller type is more accurate than the cup type, but both are subject to start-up error after stalling at low wind speed. The best results are often obtained from the ultrasonic type (see Figure 2.7-1). The calculation of line ratings by weather monitoring does not require measurement of the line current. This method may therefore be used to supplement the other monitor based dynamic rating methods. This method may not cater for variation in parameters that could affect the conductor temperature. Variation in the value of the parameters can be caused by variability of the terrain or by the sheltering of a line by trees or buildings. In addition, wind speed and direction can differ from the point of measurement, (for example, an airport) to the actual line. To mitigate this, there may be a need to install a number of weather stations along the (long) lines; associated communication problems to transmit the readings may occur, together with uncertainty of the best location of weather stations. Conductor Temperature-Based Ratings The sensor is usually located at one position only. It is known that temperature varies along the span as well as between spans. To make a judgment based on this one reading is risky, since the temperature of the conductor can be very different from span to span, especially if the line changes direction or terrain (sheltered or unsheltered spans). The cooling is approximately 40% in a line section parallel to the wind compared to a section perpendicular to the wind.
Also, the temperature measured is the conductor surface temperature, not the average conductor temperature (that affects sag). Tension-Based Dynamic Ratings Over the last 5 years, use of line tension monitors has become widespread within the U.S. The first commer-
Increased Power Flow Guidebook
cially available device, known as the CAT-1, is installed at over 30 utilities. There are a number of reasons for the popularity of these devices. The tension-measuring device is a commercial load cell, which appears to be very reliable and exhibits little drift with varying weather and line load conditions. The device is mounted on the grounded side of a dead-end insulator string and thus is not subject to high electric fields. Line tension monitors are normally installed with the line taken out of service. Sag-Based Dynamic Ratings As an example of a typical sagometer installation, a recent field study at TVA is noted in the following (see Figure 2.7-5). The project involved one of the video sagometer’s unique features: the transmission of real-time images of the span being monitored. The development of firmware and the base-station software needed to implement this feature has been completed.
One of TVA’s primary objectives was to use these systems in real time—i.e., by communicating clearance measurements directly to the control center and determining real-time dynamic ratings for these lines. TVA’s ultimate goals are to connect the sagometers and the weather station to its SCADA system, which would make the data available throughout its EMS system, and to use the clearance and weather data, coupled with modified DTCR software, to calculate real-time ratings for the monitored lines that would be available to system operators.
Chapter 2: Overhead Transmission Lines
As such, these systems were set up and installed to function in real-time, and from the day the system went into operation, data has been collected at the base station in real-time. Spread-spectrum radios are used instead of cell phones to communicate between the base-station computer and the remote video sagometer sites. The sagometers are all within a radius of 10 miles from the base-station computer. A custom-made user interface to display clearance data, along with the available clearance margin, was written for the base-station computer (see Figure 2.7-6). The TVA’s system operators routinely access the display screen during contingency periods and monitor the available clearance margin, which blinks if it gets below 10%. Based on sag and weather measurements, DTCR was executed to compare actual ratings to the static rating. Figure 2.7-7 shows an example of the results that can be achieved. This is a 24-hour block of rating data. The 4-hour and 15-minute dynamic rating data were determined by DTCR operating in conjunction with realtime data from a video sagometer. As can be seen, the dynamic ratings are significantly greater than the static
Figure 2.7-6 Real-time display for TVA video sagometers.
Figure 2.7-5 The solar-powered Sagometer on a lattice structure at TVA.
Figure 2.7-7 A 24-hour block of rating data.
2-81
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
ratings. Note that, during the morning, the dynamic ratings became very high due to precipitation. Results such as these are typical of all DTCR/sagometer applications.
Comparison of Weather Monitor and Tension/Sag Monitor-Based Dynamic Line Ratings The main advantages of using weather-based line ratings are two-fold:
2.7.7
• The rating calculation is independent of the line
Field Test Results
EPRI sponsored a series of field tests of dynamic rating and monitoring techniques at several utility sites. The outcome of these field tests were significant, and EPRI refined both its DTCR circuit rating software and learned certain fundamental facts about how weather affects the rating of overhead transmission lines and how dynamic rating methods are best applied. 1. Dynamic thermal ratings for overhead lines may be calculated based on either real-time weather, or realtime sag or tension data in conjunction with real-time weather. For weather-based ratings, the wind angle should be assumed fixed and near parallel to the line direction to account for directional variation along the line section. 2. In rating longer lines with multiple ruling span sections, it is likely that the line rating (dynamic or static) decreases with line length and that dynamic rating of lines requires multiple monitoring locations, and the minimum number of monitors required must be based on field measurements. 3. Sag and tension monitors work well in lines having high current density (greater than approximately 1 amp/mm2) where they generally yield more accurate ratings than single-point weather monitors. However, in lines with low current density (less than 0.5 amps/mm2), weather-based dynamic ratings are more accurate than those based on sag-tension monitors 4. Sag and tension monitoring allows one to directly make measurements at high temperatures. Weather monitoring does not.
current.
• The monitoring equipment is modest in cost. Weather data may also be used to dynamically rate nearby substation equipment. The disadvantages are that the anemometers are quite fragile and prone to measurement error unless calibrated frequently and, being a measurement of weather conditions at a single location, may not truly represent the weather along the entire line section, especially the wind, which can be extremely variable from place to place. Field experiments conducted by Chisholm at Ontario Hydro (EPRI 1995) indicated considerable success in estimating average conductor temperature. The instruments were placed over a five span ruling span section, and the data was based on real-time line current and on weather monitors placed at a distance from the line, and it was assumed that the wind angle was fixed at an angle of 20° to 30°. Comparisons of weather-based and tension-based line ratings at three of the four field-test sites indicates that there is good agreement between minimum values of weather-based and line tension-based ratings when using a fixed wind angle of 22° relative to the conductor axis. This is illustrated in Figure 2.7-9.
For example, the data obtained in these field tests show that there is a great deal of fluctuation in both wind speed and direction along most line routes, particularly during periods of low wind activity. Figure 2.7-8 shows 15-minute average wind speeds at locations only 1.5 km apart along a line route in Philadelphia. The field tests confirm that not only the wind speed but also the wind direction varies along the line. This raises questions about the usefulness and accuracy of basing dynamic thermal line ratings on weather data from a single location within a line section. It would seem to imply that multiple weather monitor locations might be required, especially for long line sections.
2-82
Figure 2.7-8 Wind speed (15-min average) at two locations 1.5 km apart along a 230-kV line in the eastern U.S.
Increased Power Flow Guidebook
Based on such observations at each field test site, it appears that weather-based ratings based on a fixed line angle of the order of 20° are conservative under nearly all conditions and that such “weather-based” ratings can be used as a means of warning the operator during periods of “low rating” conditions. When combined with the use of less conservative fixed ratings for planning and low load operation, this weather-based dynamic rating method would be very cost-effective. Rating Variation in Adjacent Line Sections Figure 2.7-10 shows the variation in tension-based line rating with time for the 230-kV SRP line. Four ruling span sections are monitored. I2 is E-W, and the other three are oriented nearly N-S. Note that the E-W span generally has the lowest rating, but that this is not true for certain periods such as the three hours starting at 6 am.
Figure 2.7-9 Comparison of weather-based and tensionbased cumulative rating distributions.
Figure 2.7-10 Comparison of tension-based rating estimates for four separate line sections.
Chapter 2: Overhead Transmission Lines
Clearly, if the entire line were rated on the basis of a monitor in only one section, the rating would be too high some percentage of the time and therefore not conservative. Multiple monitoring locations are required to correctly calculate the real-time line rating; however, it appears that there is good agreement for the three line sections oriented in the same direction (N-S). It appears that the number of monitoring locations (either weather or tension) required to calculate the realtime line rating correctly must be empirically determined for each location. Daily Line Rating Variation Certain circuits experience a fairly regular daily load variation, others do not. For those circuits that experience a repeatable load cycle, the daily variation in line rating may or may not be coordinated with the load. Consider, for example, the rating variations shown in Figures 2.7-11 and 2.7-12.
Figure 2.7-11 Weather-based normal rating for SDGE 138kV line as a function of time of day for September 1997.
Figure 2.7-12 Weather-based normal rating for SDGE 138-kV line as a function of time of day for December 1997.
2-83
Chapter 2: Overhead Transmission Lines
2.7.8
Summary
The calculation of thermal ratings for overhead lines is typically based upon heat balance methods such as that found in IEEE 738-1993. Given a maximum allowable conductor temperature, the corresponding maximum allowable current (the static thermal rating) is determined for “worst-case” weather conditions. In most cases, the maximum temperature is limited in order to avoid excessive conductor sag or, in some cases, a loss in conductor strength. By using real-time monitors combined with communications, these measurements can be presented to the system operator, and/or can be used to perform dynamic rating computations whose results can also be provided. Results of several projects have demonstrated that it is possible both to increase the line rating under most conditions and to avoid electrical clearance violations under severe load and weather situations. The distinction between real-time line monitoring and dynamic ratings is explained and the various monitoring methods noted and analyzed. 2.8
CASE STUDIES
2.8.1
Introduction This section includes a general discussion of the major factors that need to be quantified in order to select an economic and reliable uprating method for overhead lines. No single method is most economic in all cases, nor are all the important factors economic. Nonetheless, the selection of an appropriate uprating method is never made without economic justification. Similarly, no method can be identified as the “best” method since the uprating decision depends on predictions of what will be, and involves certain irreducible uncertainties. In spite of these difficulties, the uprating of transmission lines, as described in the following, should be a logical process, flexible enough to use in most cases, and powerful enough to yield valuable insight into line behavior and operation. 2.8.2
Selecting a Line Uprating Method
As described in preceding sections of this chapter, there are many ways to increase the thermal rating of an existing line. As any experienced line designer knows, there are a lot of different ways to accomplish the same goal, and the cheapest way may not be the most sensible way to provide a reliable transmission system. Engineering judgment is often required in selecting the most appropriate method of uprating existing lines. Therefore, the goal here is to identify the major factors that should be
2-84
Increased Power Flow Guidebook
considered in line uprating, demonstrate a general method of viewing these factors simultaneously for a number of design cases, and perform a reasonably detailed application of such methods for a particular line uprating example. Basic Observations Certain observations about line uprating appear to be nearly universally accepted by utility designers:
• Public safety is most crucial, and litigation is to be avoided if at all possible. If litigation or public injury is a possible result, the chosen uprating approach is unacceptable.
• Frequent load shedding is painful, expensive, and makes distributed generation (DG) more attractive. A marginal line uprating method that results in the frequent need for operator intervention to drop customer loads, even interruptible ones, is a poor choice in the long run.
• Avoiding the use of vibration dampers and/or armor rod by keeping everyday conductor tension well below NESC Code or CIGRE safe limits is an expensive way to avoid conductor fatigue. However, a vibration assessment by damper manufacturers should precede any uprating decision that involves the use of high everyday conductor tensions.
• If the maximum design temperature of an older existing line is to be increased to more than 100oC, compression splices should be replaced or shunted, and loss of tensile strength in the aluminum strands must be carefully assessed.
• Sag clearance buffers are required in any transmission line because of uncertainties in weather and design. The buffer for an existing line may be somewhat less than for the design of a new line (since structure placement uncertainties do not exist, and conductor elongation uncertainties are less than for a new line), but reducing necessary sag buffers to zero is not a good idea.
• Before considering any uprating method, it must be determined if the existing structures are in reasonably good shape, having load capacities at least equal to the original design assumptions. If this is not true, then none of the uprating options discussed is appropriate. The transmission owner should consider replacing the existing line with a new facility that is both safe and reliable.
• Before considering any uprating method that does not involve reconductoring the line, the present condition of the conductors must be evaluated. When the conductor is not replaced, the increased rating will lead to higher conductor operating temperatures, and
Increased Power Flow Guidebook
such methods can only be considered practical when the existing conductors and compression splices are in “very good” condition or can be made so. Critical but Qualitative Issues In evaluating uprating options for an overhead transmission line, there are many issues to be considered. Some issues are hard to quantify. For example, the reuse of existing structures carries with it an uncertain, and to a certain degree unknowable, risk that there may be undiscovered structural flaws. This risk may be perfectly acceptable in most situations, but not acceptable in lines whose failure may have enormous consequences. These factors may be hard to put a price on, but their consideration is essential in deciding whether, and how, to uprate an existing line. Some risks that should be considered are:
• Corporate impact of negative publicity from injuries, death, property damage from downed conductors, or instances of excessive sag.
• Loss of residential or commercial customers due to service interruptions.
• Intervention by regulatory bodies in response to service interruptions.
• Criticality of line to overall system reliability. To what extent might an outage affect a broader regional service interruption.
• Certainty of projected electrical overload. • Certainty of financial return on capital investment. All of these issues exist and are part of the transmission owner’s uprating decision, but none is easy to quantify. A consideration of these issues is more likely to produce a sense of “comfortable risk” rather than a detailed decision on uprating method. Financial Consequence of Electrical Line Losses A very important and peculiar issue in line uprating concerns the matter of line losses over the life of the line. As is demonstrated in the final detailed uprating example in this section, when the value of line losses is considered in the uprating problem, the line designer may select a significantly different uprating method than if such losses are ignored.
In those cases where the rating of a moderately short transmission line is being increased in order to avoid load shedding during relatively infrequent post-contingency loadings, it is unlikely that electrical losses should be a factor in uprating. In those cases where the rating of a reasonably long line is being increased in order to allow increased daily load peaks throughout an entire season, it is likely that electrical losses should be consid-
Chapter 2: Overhead Transmission Lines
ered and that the designer should seek an uprating method that reduces them. Surely, occasional operation of lines at temperatures approaching 200oC may be smart engineering, but routine operation at high temperature is not. 2.8.3
Preliminary Selection of Uprating Methods
The “best” solution at one utility may differ from that at another because the line uprating decision involves a good deal of engineering judgment based on experience. Nonetheless, in every case, the selection of an appropriate uprating method depends heavily on the physical, electrical, and thermal characteristics of the existing line, and on the exact nature of the “need” for a higher capacity line. It is possible to identify certain existing line parameters and system analysis results that largely indicate the “best” uprating solutions. Since there are many factors that influence the selection of line uprating methods, it is helpful to list the most essential ones, and to develop a table summarizing those most likely to determine, or at least strongly influence, the line uprating method. The resulting “Uprating Analysis Table” is intended for use in the preliminary stages of developing an appropriate uprating solution. It is an aid to focusing the engineering inquiry on the most productive uprating methods. Given the large number of factors that influence the uprating of an existing overhead line, it is crucial to identify, and then quantify, the most important. These factors in line uprating (with the most important shown italicized and/or in bold) include the following: System Analysis The impetus for line uprating comes as a result power system analysis. Present electrical loads are projected into the future, and the impact of various component outages (i.e., contingencies) on the electrical loading of the existing line is determined. Specific probabilities are seldom associated with post-contingency loadings, and even the prediction of normal loads is often uncertain, particularly with the advent of “open access” to commercial power generators.
Nonetheless, even with such uncertainties, the system planner must determine:
• Criticality of the line to overall system reliability (marginal or absolutely critical).
• Certainty of projected electrical overload (very certain or not certain).
2-85
Chapter 2: Overhead Transmission Lines
• Frequency of high electrical loads (e.g., daily seasonal peak loading or rare post-contingency emergency loads).
• Magnitude of the electrical overload in 2 years (e.g., < 10% or > 50%). Structural Review Transmission structures and the conductors they support are the major cost components of any overhead line. (In comparison, the cost of insulators and hardware are almost always minor.) Therefore, the design limits and actual physical condition of the existing structures and foundations are a major factor in selecting a line uprating method. It is fair to say that if the line’s structures are in poor condition, no uprating alternative makes much sense, reliability-wise or financially. On the other hand, given their initial cost, if the structures are largely in their “as designed” condition, any uprating method that does not require their extensive modification is likely to be significantly cheaper than a new line with the same capability.
Increased Power Flow Guidebook
• Evaluation of broken wire loads and other conditions not considered in the original design. Conductor Review Other than transmission structures, the conductors they support are the major cost component of any overhead line. Therefore, the reuse of the existing conductors in a line uprating is very economically attractive. The option of reusing existing conductors hinges on their physical condition, which may not be easy to determine. The usual signs of conductor deterioration include corrosion of the steel core wires of ACSR, corrosion and fatigue within compression splices, and the fatigue of aluminum wires at, or near, the mouth of support clamps due to Aeolian vibration. None of these signs is easily determined in the field, yet there is little point in considering the reuse of existing conductor without establishing that it is in good condition.
Assuming that the existing conductor is in reasonably good condition, the following factors help in selecting an appropriate uprating method:
Given an existing line with structures in reasonably good condition, there is a large financial incentive to uprate the line without needing to make major changes in the structure geometry or load capability. As part of any preliminary uprating evaluation, for a line with structures in good condition, it is necessary to determine the limits of “low-cost” structure modifications. For example, in uprating an existing line, how much can the present structure attachment points be raised without incurring significant cost (where significant cost is that which exceeds 10% of the cost of new structures). Similarly, in considering the possibility of retensioning the line or reconductoring it, how much can the original maximum conductor tension be increased without incurring costs that exceed 10% of the cost of new structures. In performing such analysis, the following should be considered:
• Physical condition of the existing conductors (“as
• Physical condition of the existing structures (“as
Preliminary Uprating Analysis Tables To summarize the various key uprating parameters, the following simple “Uprating Analysis Table” has been developed. By defining the 11 parameters listed in the table, one can better understand which uprating methods are likely to meet system needs at minimum cost.
designed” or “10% or more in need of replacement”).
• Maximum increase in transverse load beyond which the cost of tangent structure reinforcement exceeds 10% of the cost of new structures.
purchased” or “remaining life” < 10 years).
• Unloaded final everyday tension of existing conductors (15% or 25% RBS).
• Existing conductor type (30/7 ACSR or 37 strand AAC).
• Existing line maximum temperature (49°C or 125°C). • Excess clearances at existing line maximum temperature (most spans < 1ft (3 m) or most > 5 ft (1.5 m)).
• Change
in sag with increased temperature (0.2 ft/10°C to 2 ft/10°C [0.06 m/°C to 0.6 m°C]).
• Probability of assumed weather conditions. • % change in line rating per 10°C change in line design temperature (50% to 5%).
• Maximum typical increase in tangent structure conductor attachment height beyond which the cost exceeds 10% of the cost of new structures.
• Number of strain structures per mile (km) (0.05 or 1.0).
• Maximum increase in maximum conductor tension load beyond which the cost of strain (and possibly tangent) structure reinforcement or replacement exceeds 10% of the cost of new structures.
2-86
Table 2.8-1 is an example. In this example, it is clear that:
• The predicted overload magnitude is probably too large to be accommodated by the use of dynamic rating methods, but not so large as to necessarily require reconductoring.
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
• The predicted high electrical loading will be infrequent, and the resultant cost of electrical losses will be low even if the existing conductor is reused.
• Modifying the existing conductor tension or replacing it with a larger conductor will require significant expensive structure modifications, but raising the conductor attachment points appears to be rather easy (low cost).
• The present line design temperature is moderate and could be increased without causing annealing by exceeding 100°C. This preliminary review seems to indicate that raising the existing conductor attachment height, while continuing to use the existing conductor and installed tension, may be an economic uprating method.
Uprating analysis tables were developed for each of the following uprating case studies in order to simply summarize those aspects of the existing line that are most important to the selection of uprating method. 2.8.4
Uprating Test Cases—Preliminary Uprating Study
Clearly, the uprating method applicable to a particular line depends on a number of different parameters that must be defined as part of the uprating process. However, certain aspects of the line design suggest certain uprating methods, or suggest avoiding certain approaches. This section includes a collection of typical candidate lines with appropriate line uprating methods identified (including references to the section describing the method) (see Table 2.8-2).
Table 2.8-1 Uprating Analysis Table
Table 2.8-2 List of Case Studies Considered Case Study # and Section Reference
Structure
Conductor
System
Promising Uprating Method(s)
1– Section 5
115-kV single ckt, wood pole H-Frame, I-string insulators
26/7 397.5 kcmil (203 mm2), clearance limited at 75°C
Normal load in summer reaches 50% of rating, fairly frequent emergency loads reach 110%
Raise attachment points by raising crossarm or using floating dead-end concept
2 – Section 3 & 4
69-kV single ckt, single wood pole with crossarm & post insulators, guyed pole angle and dead-ends
#2AWG copper with original splices, > 3 ft, (1 m) excess clearance at 75°C max
Normal load is 20% of thermal, rare emergency load to 120% rating
Inspect conductor and connectors, raise max temp of existing conductor to 90°C
3 – Section 5
230-kV double ckt, steel lattice self-supp, I string insul
18/1 477 kcmil (243 mm2), clearance limited at 75°C
Normal load in summer Retension existing reaches 50% of rating, ACSR conductor to allow fairly frequent emeroperation to 100°C gency loads reach 110%
4 – Section 5
132-kV double ckt, steel lattice self-supp, I string insul
30/7 250 mm2 (490 kcmil) ACSR
Normal load profile to exceed 100% rating. Load cycle is predictable.
5 – Section 7
138-kV double ckt, steel lattice, light loading, seacoast area
26/7 636 kcmil (324 mm2) ACSR
Statistical comparison of line rating with other lines in region of low wind and high air temp allows increased rating Install tension or sag monitors, and use dynamic rating methods
2-87
Chapter 2: Overhead Transmission Lines
To be useful, a detailed description of each case study is included to make at least some initial decisions about what approach to take, but a detailed plan profile or sag survey data is not included. Similarly, the lines include voltage ranges of 69 kV to 345 kV—the most common lines that need uprating. Case #1 – 115-kV Single-Circuit Wood Pole H-Frame 26/7 ACSR Conductors This 115-kV line has a thermal rating of 114 MVA (see Figure 2.8-1). During the preceding summer period, the load on this line reached 110 MVA during the hottest day, and system planners project the need for a 25% increase in capacity (to 140 MVA). The increasing load is likely to develop slowly over the next 10 years. The line experiences relatively high daily loads during the summer peak period. Post-contingency emergency loads are not a problem.
The line consists of older wood pole H-frame structures with 600 ft (180 m) spans. The structures are easily reinforced. Transverse load limits can be increased with a minimum of additional bracing. Vertical loading can be increased by hardware replacement, and dead-ends can be strengthened by use of additional guying. The line is in an NESC light loading area.
Figure 2.8-1 Case #1—115-kV line.
Increased Power Flow Guidebook
The existing conductor is 26/7, 397.5 kcmil (203 mm2) Ibis ACSR strung to a final unloaded tension of 20% of its rated strength at 32oF. The final everyday sag per 600 ft (180 m) span is about 9 ft (3 m) with an existing buffer (excess electrical clearance) that is typically 3 to 6 ft (1 to 2 m) at the present line design temperature of 75oC. Occasional fatigue breaks have been observed near clamps, and about half of the original galvanizing is left on the core wires. The summer rating conditions (the line load peaks in the summer) presently in use are an air temperature of 35oC and a crosswind speed of 3 ft/sec (0.91 m/sec).
Uprating Analysis – Case #1 The uprating alternatives for test case #1 (see Table 2.8-3) include the following: A. Revision of existing rating conditions based on the use of monitors (dynamic ratings - Section 7) or through a probabilistic analysis of the line rating (probabilistic ratings - Section 5). Given the required 25% increase in line rating and the nonconservative weather assumptions presently in use, it is unlikely that these methods will yield an increase that large. Also, given the high daily load cycle, electrical losses will be significant, and neither of these methods reduces losses. B. While the structures appear to be in good condition, there is evidence that the existing Ibis conductor has sustained some damage from vibration and that its steel core strands are certainly not in “like new” condition. Given the relatively low cost of structure reinforcement, one might consider retensioning the existing conductor (Section 5) and increasing the line design temperature to 100oC. Ibis ACSR at 100oC has a thermal rating of 145 MVA. Given the high normal line loads and the marginal conductor condition, however, this may not be advisable. C. If the capital is available, the line might be reconductored (Section 6) with a trapezoidal wire conductor
Table 2.8-3 Uprating Analysis for Case #1
2-88
Increased Power Flow Guidebook
such as Dove/TW, which has 40% lower resistance (and therefore lower losses), about the same sag as Ibis at 80°C, and a thermal rating 25% higher than the present line. The transverse structure loads will be 10% higher with Dove/TW, but the maximum tension loads will be nearly 40% higher, and dead-end structures will require extensive reinforcement. D. An alternative uprating solution may involve the use of a high-temperature, low-sag conductor such as ACSS or ACCR, though the relatively modest increase in line rating (25%) doesn’t require it. ACSS is particularly attractive in applications where the existing structures cannot easily, or economically, be reinforced. The structures in this case are easily and inexpensively reinforced. Case #2— 69-kV Single-Circuit Wood-Pole Copper Conductors Typical of the oldest lines in many systems, the desired increase in thermal line rating results from an attempt to deal with a relatively rare single contingency that would persist for up to 24 hours. The addition of a new 345-kV
Chapter 2: Overhead Transmission Lines
line section will remove the contingency within 5 years. (See Figure 2.8-2.)
Line Description—Case #2
• 69-kV system voltage, 4 suspension insulator bells. • No dampers, bolted dead-ends, no armor rod. • 7 strand, #4/0 AWG Copper conductor, original splices.
• Rating conditions—2 ft /sec (0.6 m/sec) perpendicular, 40°C air, sun, 60°C continuous/75°C emergency.
• Mild corrosion area, no broken strands found at clamp locations.
• Normal daily peak annual loading is only 30% of normal continuous rating. System analysis by planning needs a 50% increase in emergency rating (postcontingency loading).
• Span lengths range from 150 to 300 ft (45 to 90 m). Ruling span is 250 ft (76 m). Excess electrical clearance at 75°C ranges from 2 to 10 ft (0.6 to 3 m). Average clearance is 4 ft (1.2 m). The line length is 10 km (6 miles) with 15 line sections going in a predominantly east-west direction.
• NESC Medium loading area (0.25 in. (0.6 cm) ice with 4 psf wind). Everyday tension at 15 °C equal to 12% RBS (Rated Breaking Strength) final.
• Single wood pole structures with zig-zag cross-arms and suspension insulators.
• Built in 1935, 20% damaged poles (rot) replaced in 1962. Another 15% replaced in 1988. No extensive structural failures known. No broken conductors.
Figure 2.8-2 Photo of Case #2 69-kV line.
Uprating Analysis—Case #2 The thermal rating of the existing line is 47 MVA (395 A). The system analysis indicates a need for a 50% higher emergency rating of 70 MVA (590 A). The normal rating of the line remains at 33 MVA (280 A). (See Table 2.8-4.)
Table 2.8-4 Uprating Analysis for Case #2
2-89
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
The structures appear to be in reasonably good shape, yet they are quite old, and the possibility of reconductoring such old structures to meet a relatively rare emergency load event does not seem economic. The existing structures cannot be modified to raise the attachment points, nor can they be easily reinforced. Reconductoring the line would, therefore, be difficult since the conductor maximum tension and diameter could not be increased at all, and the sag could not be increased. The predicted occurrence of high, post-contingency electrical loading is relatively rare, being the result of an unusual contingency. The copper phase conductors could be operated at temperatures up to 100oC for short periods of time without any significant annealing, but the existing original splices would have to be replaced to ensure reliable operation. This is also true of existing hardware. The original conductor is installed at a relatively low tension in short spans and exhibits no evidence of fatigue damage. There is insufficient clearance at 75oC to allow operation of the existing line above that design temperature. Retensioning the existing conductor may be a low-cost uprating method to meet clearance requirements at a temperature above 75oC. The present rating weather assumptions are reasonably conservative. This suggests the possibility of using dynamic uprating methods, but as discussed in Section 2.7, such methods typically produce a usable increase of only 10 to 20% in the line rating. Assuming that samples taken from the existing copper conductor indicate that it retains its original tensile strength and that a 10% reduction in tensile strength over the remaining life of the conductor is acceptable, the annealing curves in Section 2.2 indicate that the existing #4/0 copper conductor can be operated at temperatures in excess of 100oC for brief time periods with the impact on tensile strength, as shown in Table 2.8-5. With the (emergency) design temperature of the line increased to 115oC, the emergency rating with the existing #4/0 copper conductor would be increased to 70 MVA, meeting the required emergency rating. At this temperature, the tensile strength of the #4/0 copper conductor would drop by 10% in approximately 100 hours. Table 2.8-5 Loss of Tensile Strength
2-90
At the present emergency design temperature of 75oC, the sag is 7.6 ft (2.3 m). If the unloaded sag of the conductor is decreased from 5.1 ft to 3.4 ft. (1.5 m to 1 m) by increasing the everyday tension at 60°F by about 500 lbs (2232 N), then the sag at 115oC will be 7.4 ft (2.2 m) and the clearances will be met. The increase in installed tension will cause an increase in the maximum conductor tension from 1570 lbs (7009 N) to 2120 lbs (9464 N) and will require reinforcement or replacement of deadends. The transverse loads on tangent structures are unchanged. Case #3— 230-kV, Double-Circuit Steel Lattice, 54/7 795 kcmil (405 mm2) Condor ACSR Typical of the moderately aged lines in many systems, this double-circuit 230-kV line was built in the 1960s using steel lattice self-supporting structures. The emergency thermal rating of the Condor ACSR conductor is 1170 A (465 MVA per circuit). The system analysis indicates that this short line needs to carry up to 800 MVA as a result of certain severe contingencies. Although the contingency is likely to occur only every few years, if it does occur at all, it is likely to persist for several weeks.
Line Description—Case #3
• 230-kV system voltage, double-circuit, 12 suspension insulator bells, aluminum clamps.
• Dampers on exposed sections, compression deadends, armor rod used at all clamps.
• Existing line has 54/7 strands, 795 kcmil (405 mm2) ACSR conductor, the condition of full tension splices is uncertain.
• Rating conditions—3ft/sec (1 m/sec) perpendicular, 30 °C air, sun, 75°C continuous/100°C emergency.
• Mild corrosion area, no broken strands found in routine climbing inspection.
• Normal daily peak annual loading is 40% of normal continuous rating. System analysis indicates that the emergency rating needs to be 800 MVA rather than 475 MVA, and that the increased post-contingency loading would be likely to persist for several days at the infrequent times when it occurs.
• Span lengths range from 800 to 1100 ft (240 to 330
Loss in tensile strength after 100 hours
Hours for a 10% Loss in Tensile Strength
100
3%
600
125
20%
40
Temperature
If the remaining life of the line is 20 years, and contingencies are limited to 24 hours when they occur every 5 years, then this is acceptable if the electrical clearance can be maintained.
m). Ruling span is 1000 ft (305 m). Electrical clearance at 100°C ranges from 1 to 3ft. (0.3 to 3 m). Average clearance at 100°C is 2 ft (0.6 m). The line length is 40 km (24 miles) with 20 line sections going in a predominantly north-south direction.
Increased Power Flow Guidebook
• NESC Heavy loading area (0.5 in. [1.3 cm] ice with 4 psf wind). Final everyday unloaded tension at 15 °C equal to 18% RBS (Rated Breaking Strength) final.
• Steel lattice, self-supporting structures. Galvanizing is in good shape. Concrete footing inspection indicates they are in “near-original” condition.
• Built in 1963, structures have been inspected by helicopter. No major line failures have occurred. One line section failure in 1972 due to a crane accident. Crossarm failure and conductor damaged.
Uprating Analysis—Case #3 Given the nonconservative nature of the rating weather assumptions and the need for a large increase in the line rating (465 to 800 MVA), neither the dynamic rating methods in Section 2.7 nor the probabilistic methods of Section 2.5 are applicable. (See Figure 2.8-3 and Table 2.8-6.)
Chapter 2: Overhead Transmission Lines
Similarly, given the small increase in rating (7%) per 10oC increase in the line design temperature, even if the line design temperature of the existing line (with Condor) were increased to 200 oC, the corresponding line rating (690 MVA) would not be sufficient to meet the system requirements (800 MVA). This reduces our options to reconductoring the line (see Section 2.6) with a conductor having less resistance than Condor and capable of operating at 200 o C for an extended period of several days. In addition, the replacement conductor will need to sag (at 200°C) no more than the original Condor ACSR did at 100oC, yet the maximum conductor tension cannot exceed that of Condor by more than 20%. As can be seen from the following sag-tension calculations for Condor in the original line design (Table 2.8-7), the final sag is 37 ft (11 m) at 100 o C, and the maximum tension is a little over 10,000 lbs (44.6 kN). As noted in the uprating analysis table, the clearance limits of the existing line are tight (i.e., excess clearance of Condor at 100oC is only 1 to 3 ft (0.3 to 1 m). Therefore the replacement conductor cannot have more than 37 ft (11 m) sag at 200oC. Also, the maximum tension load should not exceed that of the original Condor conductor by more than 20% or the costs of reinforcement will become prohibitive.
Figure 2.8-3 Photo of structure for Case #3.
One possible solution involves reconductoring with ACSS/TW. For example, 1033.5 kcmil (527 mm 2 ), Curlew/ACSS/TW would yield a rating of 803 MVA at a line design temperature of 200 o C as a result of its greater aluminum cross section and its ability to operate at 200oC for an extended period of time. The sag-tension calculations (of Table 2.8-8) indicate that it is also capable of meeting the 37 ft (11 m) sag constraint at 200oC and the 20% higher maximum tension constraint.
Table 2.8-6 Uprating Analysis for Case #3
2-91
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Table 2.8-7 Sag-tension Calculations for Case #3
Table 2.8-8 Sag-tension Calculations for Replacement Conductor of Case #3
Other ACSS conductor designs may also be reviewed to see if another design can also meet these constraints, but with in lower capital cost. Case #4—Double-Circuit 132-kV Line The existing 132-kV double-circuit line, according to projected load growth, will soon reach the thermal limit under normal operating conditions. The line is situated in an area with mild climate and strong winds. The phase conductor is “Bear” ACSR (30/7 250 mm2)—a British conductor similar to Hen ACSR.
The prediction of increased load is somewhat uncertain, and in order to conserve capital, uprating methods that require a minimum level of capital investment are strongly preferred by management. As shown in Table 2.8-9, two essential features of the existing line that make it a candidate for probabilistic uprating are that the present rating calculations are based on rather conservative weather conditions (40 ° C air temperature,
2-92
2 ft/sec [0.6 m/sec] wind, full sun), and the line design temperature of the existing line is only 60oC. This makes the rating of the line quite sensitive to changes in air temperature (> 30% per 10°C). Probabilistic uprating methods require little or no capital investment since the line is neither physically modified nor monitored. The modified exceedance method (described in Section 5) considers the electrical load profile of the line. The conductor temperature (and thus the ground clearance) is calculated over an entire season using weather data derived through monitoring along the line. The load profile is normalized based on the profile at the maximum load. This is assumed to be the likely profile at the time when the thermal rating is likely to be met. The present ratings for the existing line are based on the assumption of a flat load profile using weather data from a location some distance away from this line, in a
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
Table 2.8-9 Uprating Analysis for Case #4
semi-arid region. While it isn’t possible to determine the absolute probability of ground clearance for the line, the relative probability of ground clearance for this line could be calculated using more appropriate weather. When these relative probabilistic methods are applied, it is determined that the thermal capacity of the existing line can be increased from 529 to 863 A for normal, and 715 to 1240 A for emergency ratings. The risk is the same as long as the line integrity from a physical viewpoint is not jeopardized. It is necessary, therefore, to assess the temperatures that joints are likely to reach.
• This method of uprating must be carefully applied. The rating applies only to a particular line. All joints in the line must be tested via the resistance method for integrity. All joints that are the same or higher resistance than the conductor need to be replaced.
• If the resistance method is found to be too costly, each joint should have a wrap tie placed around it to prevent the conductor falling in case of failure. The joints then need to be regularly checked by infrared camera. All joints at the same, or hotter, temperature than the conductor need to be replaced.
airport weather station 20 miles (32 km) from one end of the line may not be useful for this. 2. The conclusion that the line can be uprated because it appears to be more conservatively rated than another line at another location depends on the assumption that the rating of the other line is safe. 3. The inclusion of line current variation over a typical day means that the resulting probability distribution of conductor temperatures may no longer be valid if the line’s daily load variation changes due to changes in the system configuration. 4. Finally, there is no absolute certainty that the resulting line rating is safe. The uprating decision is based on a comparison to another line, not on the establishment of an absolute clearance assurance probability. Case #5—169-kV double-circuit, steel lattice, medium loading area, 26/7 636 kcmil (324 mm2) ACSR
Line Description—Case #5
• 169-kV system voltage, double-circuit, 10 suspension insulator bells, aluminum clamps.
• Dampers on exposed sections, compression deadends, armor rod used at all clamps.
Given the managerial decision to seek the lowest cost uprating method, probabilistic methods of uprating are very attractive. The rating of the line can be increased sufficiently such that a major capital investment project might be postponed for several years. It may not even be necessary to increase the tension in the conductor or raise towers. It must be noted, however, that such methods must be used with care. Results are not generic and depend on the weather conditions at a specific area and the load profile of a specific line. There are several specific cautions to be observed: 1. The weather data used in the calculation of conductor must be appropriate to line ratings. Data from an
• Existing line has 26/7 strands, 636 kcmil (324 mm2) Grosbeak ACSR conductor. The condition of full tension splices is excellent.
• Rating conditions—2ft/sec (0.6 m/sec) perpendicular, 40°C air, sun, 75°C continuous/90°C emergency.
• Mild corrosion area, no broken strands found in routine climbing inspections.
• Normal daily peak annual loading is 30% of its present continuous rating. System analysis indicates that the emergency rating needs to be increased to 310 MVA rather than the existing line’s 293 MVA. The increased post-contingency loading would be
2-93
Chapter 2: Overhead Transmission Lines
likely to persist for no more than an hour at the infrequent times when it occurs.
• Despite the modest predicted overloads, system operations is particularly interested in finding a way to uprate this line without taking it out of service for more than short time periods. Extensive reconstruction is unacceptable.
• Span lengths range from 600 to 800 ft (180 to 240 m). Ruling span is 750 ft (225 m) Electrical clearance at 90°C ranges from 3 to 5 ft (1 to 1.5 m). Average clearance at 90°C is 4 ft (1.2 m). The line length is 15 km (9 miles) with 10 line sections going in a predominantly east-west direction.
• NESC Heavy loading area (0.5 in. (1.3 cm) ice with 4
psf wind). Final everyday unloaded tension at 15°C equal to 18% RBS (Rated Breaking Strength) final.
Increased Power Flow Guidebook
The following photograph (Figure 2.8-4) illustrates the installation of a sag monitor on a lattice structure. The primary advantage of this approach is that it meets the need for a modest increase in line rating without requiring a large capital investment. Also, if the predicted increase in post-contingency load does not occur, the monitor and communications equipment can be reused in another suitable installation. The primary concerns center around the need to educate system operations personnel in dealing with line ratings that are not constant. This can be challenging and, if this is the first application of dynamic rating methods in the utility, the necessary investment in engineering time and operator education should not be underestimated.
• Steel lattice, self-supporting structures. Galvanizing is in good shape. Concrete footing inspection indicates they are in “near-original” condition. Built in 1974, structures have been inspected by helicopter. No major line failures have occurred.
Uprating Analysis—Case #5 Given the conservative weather assumptions (see Table 2.8-10) used in calculating the rating of the existing line, the uncertainty of the predicted overload, and the modest magnitude by which the post-contingency load exceeds the present rating, the use of dynamic rating methods appears to be worth considering. Since system operations does not want this line taken out of service even to uprate it, noncontact or hot stick mounting of line monitors is attractive. Video sagometers could be installed at each end of the line, each near a substation where communications to the utility control center is simplest.
Table 2.8-10 Uprating Analysis for Case #5
2-94
Figure 2.8-4 A Video sagometer mounted on a lattice structure.
Increased Power Flow Guidebook
2.8.5
Chapter 2: Overhead Transmission Lines
Economic Comparison of Line Uprating Alternatives
This chapter discusses a wide variety of techniques that allow one to increase the capacity of existing transmission lines. In the preceding part of this section, test cases and methods are presented for performing a preliminary uprating assessment, the goal of this being to identify those methods most likely to apply to a particular line uprating problem. Typically, while several methods can be eliminated as yielding inadequate ratings increases, or requiring excessive capital investment, multiple uprating options are likely to survive such an initial review. In this subsection, it’s assumed that a preliminary analysis has been successfully completed and that the most likely uprating methods have been identified. The goal here is to prepare a more detailed cost/performance comparison of likely uprating methods. A test case will be developed to illustrate the essential features of such a detailed analysis.
at different points in time. The uprating alternatives appear to be economically equivalent. But it is clear that the distribution of annual costs—interest on capital and inflation—has been ignored. The concepts of present and future worth of money are explained in many texts and will be included in the following discussions. Line Costs and System Savings from Line Uprating With the exception of electrical losses, and possibly reduced maintenance from reconductoring, all of the benefits from line uprating accrue to the power system at large. In contrast, with the exception of certain dynamic rating methods, all of the costs associated with line uprating are specific to the line being modified.
The most significant economic benefits to be expected from uprating of existing lines include:
• Reduced power generation costs by increased access to low cost sources.
• Increased revenues from increased sales of low cost power to other utilities.
In comparing the total cost of viable uprating alternatives, the major cost and savings factors for each alternative need to be determined. The point of the exercise is to select the minimum cost uprating method that meets the need for safe and reliable operation, that is most likely to meet regulatory constraints on line modifications, and that minimizes systemwide costs. In many cases, the lowest-cost uprating solution may not be selected because of the many noneconomic constraints on line design. Present Worth Calculations Because line uprating costs can occur immediately, or over the life of the line, the total costs of each uprating method should be developed on a “present worth” basis.
• Avoidance of litigation involving clearances and environmental effects.
• Avoidance of extensive regulatory and public hearings required for new lines.
• Postponement of major capital investment. • Reduced maintenance. • Reduced electrical losses. The major cost components typical of line uprating include at least some of the following:
• Replacement and/or reinforcement of tangent/suspension structures.
• Replacement and/or reinforcement of tension/strain Consider two uprating schemes, which require the same total amount of capital but with different annual expenditure schedules, as shown in Table 2.8-11. In each case the total cost of uprating is the same, $15,000, if there is no difference in the value of a dollar Table 2.8-11 Comparison of Two Uprating Schemes Year
Uprating Method A ($)
Uprating Method B ($)
0
7,000
15,000
1
2,000
0
2
2,000
0
3
2,000
0
4
2,000
0
TOTAL
15,000
15,000
structures.
• Purchase of new conductors. • Stringing, sagging and clipping of new or existing conductors.
• Replacement or addition of insulators and hardware. • Addition of wind-motion control devices. • Purchase and installation of monitors and communications.
• Installation and repair of line monitoring devices and communications.
• Increased maintenance associated with higher operating temperatures.
• Increased cost of operator intervention to reduce line load.
2-95
Chapter 2: Overhead Transmission Lines
• Reduced maintenance access to heavily loaded lines and equipment. Some of these factors—structure reinforcement, conductor cost, etc.—can be quite readily estimated while others—increased levels of maintenance, operation complexities, etc.—can be difficult to quantify. This difficulty in estimating maintenance is particularly true for those uprating methods with which the utility has little or no experience. In choosing the “best” line uprating approach, the line engineer typically finds himself with several different ways to accomplish the same (or nearly the same) end result. Given the high level of uncertainty in the power transmission business today and the uncertainties about the long-term cost and viability of many of the possibilities, the choice of uprating method cannot be solely economic. Nonetheless, economic analysis helps to clarify the choices, and is necessary to get funds to do the modifications. Identifying Potential Power System Savings Many transmission line uprating projects are not justifiable on a purely economic basis (i.e., the present worth of savings over the life of the uprated line does not exceed the present worth of construction capital and maintenance). Considerations of safety or system reliability are as likely to prompt the decision to uprate a line, as is the opportunity to reduce electrical losses or to operate the transmission and generation grid at a marginally lower cost per kilowatt-hour. On “tie-lines” between systems or on radial feeds from low-cost generators, however, where major savings from the purchase of more low-cost power or increased income from the sale of same is at stake, economic justification of uprating is more likely.
Savings in Generation Dispatch The potential savings in electrical losses and/or improved economic generation dispatch associated with uprating an existing circuit by traditional means—such as reinforcing the towers and reconductoring—must offset the very real dollars spent in the rebuilding (typically in excess of $100,000 per mile, or $62,000 per km). Some of the lower-cost uprating alternatives—such as the use of dynamic thermal ratings, increased static thermal ratings based on weather studies, or the selective rebuilding of critical clearance spans—are more likely to prove economically justifiable since the capital investment is so much lower. Dynamic thermal uprating of all lines throughout a system on the basis of weather data monitoring has been economically justified in terms of reduced generation
2-96
Increased Power Flow Guidebook
costs in several references. The calculation of such cost savings involves load flow studies and is peculiar to each system. It has been noted, however, that for increases in capacity of any single line beyond about 10%, other lines serve to limit dispatch, and little is gained by further increases in the capacity of that particular line. Maximum improvement in economic dispatch is, rather, gained by systemwide increases in line capacity. Reference (Nabet 1986) is typical of the more general claims at economic justification of uprating procedures. Under a section of the paper called Benefits, G. Nabet writes “...the use of [systemwide] ambient temperature adjusted [dynamic thermal] ratings ....from January 1, 1979 to June 30, 1980 .... resulted in reduced off-cost generation requirements for transmission control ... [saving] ... 976 MWHR [worth] 1.2 million [dollars]. These savings reflect only those occasions in which offcost operation was invoked.” Reference (Hall and Deb 1987) presents a more detailed attempt at the economic justification of (again dynamically) uprating lines in the PG&E system. The point was to show that by increasing the thermal ratings of all the double-circuit lines shown in [their] Figures 8 and 9 from 800 to 1300 A, the total cost of generating power for loads and line losses decreased by some 18%. The authors do not attempt to justify the use of such a large increase in line ratings with dynamic ratings, nor do they present any cost estimates for the increased operation and maintenance expenses of the dynamic rating system. This paper does clearly illustrate the technique of economic justification of line uprating.
Savings in Electrical Losses The flow of electrical current on the phase conductors results in the loss of electrical energy due to conductor heating. As was noted previously in this section, the issue of whether electrical losses are included in an economic analysis of uprating can have a major impact of the selection of uprating method. For example, consider a 10-mile (16-km) long, 115-kV three-phase transmission line with Drake conductor. Assume that the current on the phases of the line is constant and equal to the static thermal rating of Drake ACSR conductor (995 A for a maximum allowable conductor temperature of 75oC without sun, 25oC ambient and a 2 ft/sec (0.6 m/sec) cross-wind). The thermal capacity is 198 MVA. At 75oC, the resistance of 795 kcmil (405 mm2) Drake ACSR is 0.1390 ohms/mile (0.09 ohms/km), and the total of losses in the three-phase conductors is 413 kW per mile (0.1390 * 9952 * 3/1000 = 413). At a power fac-
Increased Power Flow Guidebook
tor of 0.95, carrying its full thermal capacity, the 115-kV line is transmitting 198 MW (0.95 * 995 * 1.732 * 115) and the electrical losses amount to 0.22% of the real power transmitted per mile of line. If the 115-kV line were thermally uprated to 236 MVA (1185 A per phase) by increasing the line design temperature to 100 o C (by raising attachment points and/or retensioning the existing conductor), and if the line current again equaled its thermal rating, then the line losses would be increased by 53%, from 413 kW/mile to 632 kW/mile (256 to 392 kW/km). Assuming a wholesale electrical power cost of $0.03 per KW-hr, the cost of electrical losses increases from $123.39 per hour of operation at the thermal limit to $189.60 per hour. Clearly, if operation of the original, or uprated, 10-mile (16-km) long line is operated at or near its thermal limit for no more than 24 hours per year, the cost of losses is a minor consideration. If, on the other hand, the line is operated such that its electrical load is at or near its thermal capacity for 2 hours per day, the cost of losses ($189.60 * 2 * 365 = $138,000 annually) can be a major economic consideration in uprating. Of course, the comparison of electrical losses for various uprating alternatives is not quite this straightforward for a real transmission line. The line loading varies with the season, the weather, and the time of day. For many lines, even those that are candidates for uprating, the normal load may be well below the thermal capacity of the line (approaching the thermal capacity of the line only under occasional contingency loadings resulting from emergency operation). In order to account for the variation in line load over time, it is normally assumed that the “peak normal load” is that which occurs under normal operation of the transmission system. The “peak post-contingency load” is that line load that occurs only rarely, under emergency operation of the transmission system. The “average load” is the average line load over a certain period of normal operation. Since the “contingency peak load” only rarely occurs, the line losses that occur during such times will be neglected. The line load factor (LoadF) for each of those future years is defined as the ratio of average to peak line load over the year. In order to calculate the present worth of line losses, however, one needs to know the loss factor (LossF)—the ratio of average annual electrical losses to peak losses—rather than the load factor. If the average current on a conductor over one year is 500 A, and the peak current over the same period is 1000 A, then the load factor is 0.50. If the current is quite constant at 500
Chapter 2: Overhead Transmission Lines
A, except for brief excursions to 1000 A, then the loss factor for the conductor is 0.25. In many cases, the load factor and the loss factor are often empirically related by a formula such as: LossF = 0.15 ∗ LoadF + 0.85 ∗ LoadF2
2.8-1
Reduced Emergency Actions If the capacity of certain lines is increased, then the probability is reduced that the system operator will be forced to take emergency actions (e.g., “shedding” load or initiating “quick startup” generation). This increase in reliability of power supply to interruptible customers and reduced use of relatively expensive generation has a real cost that is very much a function of the particular system. The reduction of workload for the operator also has genuine value to the efficient functioning of the system. Naturally, if the operator has more work to do after the uprating than before, then this should be evaluated as a cost of uprating. This is particularly true for “instantaneous” dynamic thermal rating schemes.
Postponed Capital Investment The selection of uprating method, indeed the initiation of the uprating process itself, is the result of projected load growth. Clearly a number of unpredictable factors are involved in the prediction both of systemwide load, and even more so of the load on any particular line within the system. Every utility has seen this very clearly over the last decade as a result of large swings in fuel costs, generation construction costs, and conservation efforts. Decreases in peak contingency loads on the order of 20 to 30% have occurred with changes in oil prices. Such major shifts in predicted load render large capital commitments for uprating hazardous. Similarly large changes in projected loading of certain lines can result from wheeling decisions made by neighboring utilities or from additions of cogeneration. As a result of the unpredictability of future load growth, marginal uprating methods have real economic value. They are especially attractive if they can be applied and then supplemented or removed at a future date depending upon whether the projected load growth does or does not occur. During the short term, such methods would require only the minimum capital investment. During the long term, the capital investment in the line would more closely match the needs of the transmission system. A number of marginal methods of uprating have been discussed. The only commercially available method that is “portable” is some sort of weather-based dynamic
2-97
Chapter 2: Overhead Transmission Lines
thermal rating technique. The techniques of dynamic rating and selective rebuilding of critical clearance spans are complementary and could follow one another as required. Conductor temperature monitors, for example, could be removed and used on another circuit if the line load did not require them in the future. Estimating Line Uprating Costs In comparing alternative methods of line uprating, one must consider all of the cost components and the likelihood that each uprating method can meet the power system needs. Line uprating costs are very dependent on the design details of the existing line. For example, if the structures were designed to withstand much larger transverse and/or longitudinal forces than are produced by the existing conductors, reconductoring can be accomplished without the expense of structure modification. Similarly, if the original design allowed for ground clearances that greatly exceed the NESC minimums, it may be possible to operate the line at higher electrical loads without any physical modification or expense.
Structures and Foundation Modifications Modifications to existing structures should be considered in a two-part process. First, consider only the tangent structures, assuming that angle structures will have to be either rebuilt or replaced if the conductor diameter or tension levels are changed. Determine the cost of modifying the tangent structures on the line as a function of the conductor diameter accounting for changes in code or loading since the line was built. Second, if the uprating cost for tangent structures appears to be reasonable for the required increase in thermal rating or voltage, then consider the cost of modifying angle structures and dead-ends, and do a detailed clearance study of the line for the most economical conductor diameter.
Increased Power Flow Guidebook
Bundling of new and old conductor doubles loading on the structure. The cost of installing the second conductor in either a vertical or horizontal bundle costs only slightly more than installing a new conductor on the same structures. The added cost is due to the possible need to pre-stress the new conductor and the need to work “around” the existing conductor. Reconductoring with a larger conductor costs roughly what the stringing, sagging, and clipping of new conductor usually costs. The old conductor may have significant scrap value if it is all aluminum. In any event, if it can be reused, the cost of this operation should be reduced accordingly. Reconductoring with special conductors may cost somewhat more than using standard conductors. There is often a premium of 5 to 15% associated with conductors such as SDC or SSAC. Also the use of higher installation tensions and special handling may cause a contractor premium.
Operation and Maintenance Costs Uprating an existing line will inevitably lead to higher electrical loads. This can cause reduced life for conventional current-carrying components and/or the need for shorter inspection intervals. The use of real-time monitors may also increase the need for maintenance and problem-solving where none existed before. Also,
• Dynamic rating monitors are installed in a hostile electromagnetic environment. Though sometimes installable with the line in service, their removal from certain spans of the line can be a significant expense. It is essential that the manufacturer provides the user with the possibility of field correction, or at least detection of errors, so that recalibrations can be kept to a minimum.
As a rough rule of thumb, if the study of tangent structures shows that necessary structure modifications can be accomplished for less than 50% of the cost of replacing the existing structures with new, then a more detailed analysis is justified.
• Reconductoring with novel conductors may be very
Reconductoring Costs If the existing conductors are to be replaced, then a number of conductor options exist. A new conductor may be bundled with the existing conductor or the existing conductor can be replaced with:
Unless engineers have extensive experience with particular techniques of uprating, they should first move to gain experience with a pilot project. Based on this work, one should be certain to allow for any unforeseen problems that might develop years after the uprating occurs.
• A conductor having less electrical resistance. • A special conductor capable of higher unloaded ten-
If line ratings are to be only marginally increased, the need for operator intervention may increase. Dynamic ratings in particular offer added complexity to the system operator, both in assessing the adequacy of the transmission system, and in establishing contractual obligations for the transfer of power between systems.
sion.
• A special conductor capable of operating at higher temperatures with reduced sag.
2-98
attractive, but the aggressive utilization of new materials and products can add to maintenance and repair activities.
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
The operator must help to define his needs for display of variable thermal ratings. This need is likely to involve additional software and display hardware in the energy control center.
time of day. This is a very real cost, even though it is difficult to quantify.
If the interval between uprating reviews of lines is to be reduced in order to more closely match capital investment to capacity needs, the operator must be closely integrated into the process of review and uprating decisions. This implies an increase in the time that the system operator is to spend in communicating his experience to planners and engineering personnel.
Consider a 10-mile (16-km) long, 115-kV transmission line with 336.4 kcmil (172 mm2) Linnet ACSR conductor installed to a final unloaded tension of 16% UTS at 60°F. The wood pole H-frame structures are spaced quite uniformly at 600 ft (180 m). According to the utility operating this line, it is assumed that the conductor has a summertime thermal capacity of 430 A (75oC conductor, 40°C air, 2 ft/sec (0.6 m/sec) cross-wind, with sun) that corresponds to a thermal line capacity of 85 MVA. The sag-tension data for the original conductor is shown below in Table 2.8-12.
Miscellaneous Cost Issues If a particular method of uprating is applicable to many lines in a particular utility system, then the engineering cost can be spread over several upratings. Otherwise, the cost of engineering time is a real consideration in making some of the more complex uprating schemes work. Traditional uprating of lines by rebuilding with lines of the next higher voltage class or reconductoring with larger standard conductors means that the transmission system planner need only concern himself with certain lines at widely spaced intervals of time—at least 5 to 10 years. Marginal uprating techniques imply more frequent and more sophisticated studies of line capacity, including the possibility of small changes in capacity that must be reviewed for sufficiency frequently. Dynamic thermal uprating techniques offer particular challenges to the system planner. Standard software tools must be modified to consider the probabilistic aspect of thermal limits, which depend on weather and
2.8.6
Detailed Comparison of Uprating Alternatives—An Example
The existing structures are in good condition, and it is possible to reinforce strain structures to allow an increase in the present maximum conductor tension (6410 lbs or 28.6 kN) of up to 50% for a cost equal to less than 10% of rebuilding all structures. The transverse load capability of the existing tangent structures is such that the diameter of the replacement conductor can be up to 10% higher than that of the existing conductor (0.72 in., or 1.8 cm) without reinforcing or replacing tangent structures. The suspension structure conductor attachment height may not easily be increased, and the existing line’s ground clearances with a sag of 13.2 ft (4 m) at 75°C are barely adequate. Therefore this maximum high-temperature sag may not be exceeded in any of the uprating alternatives.
Table 2.8-12 ALCOA Sag and Tension Data
ALUMINUM COMPANY OF AMERICA SAG AND TENSION DATA 600 ft spans, 16% final, 75C max, w comp Conductor LINNET 336.4 Kcmil 26/ 7 Stranding ACSR Area = 0.3070 sq in. Dia = 0.720 in. Wt = 0.463 lb/°F RTS = 14100 lb Span = 600.0 ft NESC Heavy Load Zone Creep is a Factor Rolled Rod Design Points
Final
Initial
Temp
Ice
Wind
K
Weight
Sag
Tension
Sag
(°F)
(in.)
(psf)
(lb/°F)
(lb/°F)
(Ft)
(lb)
(Ft)
Tension (lb)
0.
.50
4.00
.30
1.650
12.58
5915.
11.61
6409.
-20.
.00
.00
.00
.463
5.85
3564.
4.13
5047.
0.
.00
.00
.00
.463
6.67
3124.
4.44
4695.
60.
.00
.00
.00
.463
9.55
2186.
5.75
3626.
120.
.00
.00
.00
.463
12.08
1729.
7.78
2679.
167.
.00
.00
.00
.463
13.23
1579.
9.78
2133.
212.
.00
.00
.00
.463
14.33
1458.
11.78
1772.
2-99
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
The existing Linnet conductor is in reasonably good condition with an expected life of at least 20 years. It is capable of operation at a temperature above the present limit of 75oC, but only if it can be operated at a higher temperature without exceeding the present sag of 13.2 ft (4 m) at 75oC. Because the line is short, stability problems are not of concern. The voltage drop per mile is considerable, however, with a current of 430 A, a conductor temperature of 75°C, and a 90% power factor is: ⎡100 • I • ( Rac cos φ + X sin φ ) ⎤⎦ %VoltDrop = ⎣ ⎡ kVLL ⎤ ⎢ ⎥ ⎣ 3 ⎦ ⎡100 • 430 • ( 0.328 • 0.90 + 0.336 • 0.436 ) ⎤⎦ =⎣ ⎡ 115 ⎤ ⎢ ⎥ ⎣ 3⎦ = 0.286% per mile 2.8-2
Setting a 10% voltage drop as a limit during emergency loadings, all lines of this construction, having a thermal limit of 85 MVA are voltage constrained at lengths greater than 35 miles (56 km). Note that as the thermal rating of the line is increased, the line length at which the line is voltage drop limited decreases. Thus increasing the thermal rating of a 25-mile (40-km) line of this design to 125 MVA would make it voltage drop rather than thermally limited. In the present example, however, the 10-mile-long line’s rating would have to be increased to 300 MVA before it became voltage-drop limited.
Preliminary Uprating Analysis A preliminary uprating assessment of the line has been performed, as shown in this Uprating Analysis Table (Table 2.8-13). Certain uprating methods seem inappropriate. For example, since the line is presently clearance limited with Linnet at 75oC and the tangent structures will not allow an increase in conductor attachment height, it is not possible to lift the conductor attachment points in order to increase the line design temperature. Alternatively, the relatively modest increase in thermal rating and its uncertainty indicates that dynamic rating methods may work well.
After considering the capabilities and conventions of the transmission owner, the following three alternative uprating methods are identified as possible: A. Reconductor the line with a lower resistance, trapezoidal wire, Hawk/TW ACSR conductor, reinforcing the strain structures. The 10% larger diameter of Hawk/TW can be accommodated by the existing structures. B. Install a dynamic thermal rating system based upon the use of conductor sag-tension monitors along the line. After some period of time depending upon the line load growth rate, remove the dynamic rating system, and increase the tension of the existing Linnet conductors to allow operation at higher temperature for the same maximum sag.
The projected growth of the peak emergency line loading is shown in Figure 2.8-5. Note that the thermal capacity of the line will be exceeded by the peak contingency loading in 2 to 5 years for the pessimistic (1%) and the optimistic (3%) projections, respectively.
Table 2.8-13 Uprating Analysis Table
2-100
Figure 2.8-5 Example of projected growth of peak emergency line loading.
Increased Power Flow Guidebook
C. Reconductor the line with Linnet ACSS without modifying either tangent or strain structures. Reconductoring with ACSR/TW Conductor Reconductoring with 477 kcmil (243 mm2), 26/7 Hawk ACSR/TW conductor will yield a thermal rating of 525 A (105 MVA) at 75oC and 700 A (139 MVA) at 100oC due to the reduced resistance of Hawk/TW. The increased thermal capacity with Hawk/TW will be adequate for at least 10 years under the least-conservative assumption of 3% annual load growth.
In order to meet the maximum sag limit of 13.2 ft (4 m) at 75 o C , Hawk/TW must be installed to an initial unloaded tension of 29% UTS at 0°F (-18°C) and a corresponding maximum tension under NESC Heavy loading conditions of 7750 lbs (35 kN) (21% above the existing Linnet ACSR). If the initial unloaded tension at 0°F (-18°C) is increased to 33%, the sag limit is met at 100oC, but the maximum tension increases to 8310 lbs (37 kN) (30% above the present line). In either case, the maximum tension is well within the 50% increase limit in maximum tension load. Hawk/TW has a diameter of 0.781 in. (2 cm) (8.5% greater than Linnet), so it is likely that the existing tangent structures will not require reinforcement. Having established the increase in thermal capacity possible by reconductoring with Hawk/TW, other substation equipment limits and replacement costs need to be reviewed. The total line construction cost (i.e., strain structure modifications, replacement conductor, vibration dampers, labor cost, etc.) is a weak function of maximum tension, since only strain structures need to be modified. It’s assumed that the reinforcement of strain structures costs 5% of the structures for a new 115-kV line. It is further assumed that this amounts to $5,000 per mile ($3k per km). In addition to the cost of upgrading structures, the most significant cost is that of the new conductor minus the scrap value of the old. Typically, one may obtain conductor costs and scrap value from a manufacturer. We will assume that the new Hawk/TW ACSR conductor costs $2.00 per ft ($6.70 per m) and that the scrap value of the old conductor is $0.50 per ft (1.50 per m). Reconductoring the line with Hawk/TW involves a total material cost of $24,000 per mile ($14,400 per km). Other costs include stringing, sagging, and clipping the new conductor, new hardware, and engineering design costs. We will assume that this cost equals that of the Hawk/TW material.
Chapter 2: Overhead Transmission Lines
Finally, the present worth of electrical losses over the life of the reconductored line should be calculated. It is assumed that the normal annual peak line load that is presently 50 MVA will increase to 65 MVA over an estimated 20-year useful life of the reconductored line. It is also assumed that the peak contingency load is 1.6 times the peak normal annual load of the line, and that the loss factor is 40%. Economic Parameters for Loss Calculation
• • • •
Years of Analysis: 20 years Interest Rate: 8% Energy charge: $0.020/kW-hour Energy charge Escalation Rate: 7%
Using the economic data in the preceding paragraph and in Table 2.8-14, the present worth of electrical losses with the existing Linnet conductor over the 20-year period is $610k. The resistance of Hawk/TW is approximately 70% (336.4/477 = 0.71) that of Linnet. Therefore, the savings in present worth of electrical losses for Hawk/TW is $18k/mile ($11k/km). During the reconductoring of the line, the system operator cannot use the circuit. Construction could take months and higher cost generation may have to be purchased during this period. The cost of this loss of the circuit could be determined by a system load flow analysis. The cost is primarily due to higher costs of generation due to non-optimum generation dispatch during construction and increased losses on other lines whose loads increase Table 2.8-14 summarizes the costs and savings associated with reconductoring the line with Hawk/TW conductor.
Table 2.8-14 Summary of Cost Savings Associated with Reconductoring Conductor Name OD (in.) Structures
Hawk/TW 0.782 $5,000/mi
Conductor
$24,000/mi
Conductor labor
$24,000/mi
Total construction
$53,000/mi
Cost of increased losses during construction
?
Savings in PW losses over 20-year life
$18,000/mi
Net PW cost of line operation over 20 years (ignore losses)
$53,000/mi
Net PW cost of line operation over 20 years (include losses)
$35,000/mi
2-101
Chapter 2: Overhead Transmission Lines
Dynamic Uprating Method If the existing Linnet conductor is in good condition, the line rating can be increased through the installation of sag-tension monitors along the line. Many papers have dealt with these techniques.
Before doing any economic calculations, it is essential that one determines just how much the use of a dynamic rating method increases the thermal rating of the line. As was discussed previously, the dynamic thermal rating of the line is both random and chronological—that is, there is a certain amount of uncertainty combined with a certain degree of predictability based on season and time of day. Based on reference (Hall and Deb 1987), for a line in upstate New York, one may expect that the dynamic thermal rating of the 115-kV line with Linnet conductor will be:
• 10 to 20% above the static rating 50% of the time. • Above the static rating 90% of the time. • Below the static rating 10% of the time (usually at night). One must decide how to interpret these numbers in terms of traditional planning criteria. One must recognize that the operator will have to intervene occasionally to reduce the loading of this line during times of peak loading and minimal rating. During these times when the load is high and the dynamic rating is low, the system will be operated in an uneconomic mode or load may need to be shed. It’s assumed that operating personnel feel that they can intervene during 10% of the peak loading events without incurring significant costs. Then one may credit the dynamic rating system with increasing the thermal rating of the line by 10%, or from 85 to 94 MVA. For a 2% annual growth rate, the peak contingency load will reach 94 MVA in 8 years. Therefore, one may assume that the useful life of this dynamic rating approach is 8 years, after which the line must be modified in some other manner to increase its thermal rating (e.g., raise structures, reconductor, etc). The installation of the dynamic rating system does nothing to reduce losses since the conductor resistance is unchanged. It may be assumed that the dynamic rating equipment costs about $100,000 for a 10-mile (6.2 km) line. The monitoring system is reusable on other lines after 8 years, or earlier if the load increases more rapidly than predicted. Line monitors are usually installed by bucket truck if terrain permits. Installation expenses vary widely since
2-102
Increased Power Flow Guidebook
they depend on terrain and accessibility along the line. This is also true for maintenance. The monitors presently available require periodic recalibration and probably should be checked annually. A guess for initial installation cost of the line monitors might be $10,000 with an annual maintenance cost of the order of $5,000. Prior to beginning the dynamic rating of the line, one must allow for a complete inspection of the structures and conductor to spot bad splices and impaired clearances. An inspection of the 10-mile (6.2-km) line is required for any of the three alternatives. The use of line monitors offers the unique advantage of establishing an experimental basis for high-temperature clearance. Any line outage required to install the line monitors is brief, typically less than 24 hours. For EPRI’s video sagometer, no outage is needed. Assume that at the end of 8 years the dynamic rating monitor system is worth 50% of its initial purchase price. After 8 years, the dynamic rating system will be removed and reused elsewhere in the system. The line would then be surveyed, certain critical spans selected for increase in clearance, the allowable conductor temperature increased, and 50 MVA of power transformer capacity added. The use of dynamic ratings would be discontinued at this point. It’s estimated that the cost of retensioning the existing Linnet ACSR to 20% UTS at 60°F will be equal to half that of installing new conductor or approximately $12,000/mile ($7,400/km). The increased everyday tension will require the use of dampers costing about $2,000/mile ($1240/km). The retensioned line will then have a line design temperature of 100oC and a rating of 575 A (115 MVA). If load growth is faster than anticipated, then this may not be adequate, and the line will have to be either reconductored or rebuilt. The present worth of $14,000/mile 8 years in the future is $10,000/mile, so the total present worth cost of this uprating approach is $21,000/mile. Reconductor with Linnet/ACSS Linnet/ACSS can be applied to the line without the need to rebuild or reinforce any of the structures. If the the Linnet/ACSS is installed to maximum NESC Code limits at 60oF, it reaches the sag limit of 13.2 ft (4 m) at about 150oC. The line rating is, therefore, 770 A (153 MVA).
The cost of reconductoring is limited to the conductor and its installation. Given the premium typical of ACSS of $2.00 per ft ($6/m) for the conductor and an equal
Increased Power Flow Guidebook
Chapter 2: Overhead Transmission Lines
amount for stringing, sagging, and clipping it in place of the original Linnet, the total cost is $63,000 per mile ($39k/km). Dampers will also be required because of the high initial tension levels. Therefore, the total estimated cost is $65,000 per mile ($40k/km). Economic Comparison of Uprating Alternatives The total present worth of construction and losses to meet the increased thermal rating requirements of this 10-mile line in the three different uprating methods are summarized in Table 2.8-15.
Clearly, the use of dynamic ratings followed by a retensioning of the existing conductor (if required by actual load growth) is the most flexible approach, and requires the least initial and total capital investment. The major drawbacks involve the need to modify standard operating procedures to utilize real-time ratings and the modest rating increase that results. The use of ACSS requires an absolute minimum of structure reinforcement since Linnet/ACSS has the same diameter as the original Linnet ACSR and yields reduced maximum tension because of its reduced modulus. There is no reduction in electrical losses since the Linnet/ACSS has nearly the same resistance as the original Linnet. In pursuing other alternatives, it is likely that an ACSS/TW conductor with a slightly larger diameter than Linnet would be a better choice. Table 2.8-15 Present Worth of Three Uprating Options Option A1 – Reinforcing strain structures, adding dampers, and reconductoring with Hawk/TW for a line design temperature of 100oC.
$53,000/mile (ignoring losses)
Option A2 – Same as A1 but include loss savings
$35,000/mile (allowing for loss savings)
Option B – Apply dynamic r ating monitors and retension existing Linnet ACSR if predicted load growth requires it.
$20,900/mile
Option C – Reconductor with Linnet/ACSS and go to a line design temperature of 125oC.
$65,000/mile
The uprating option requiring the largest capital investment is the reinforcement of strain structures and the aggressive use of vibration dampers in order to reconductor the line with Hawk/TW ACSR. This option is unique in that it reduces electrical losses as well as increasing the line rating. Review of other line uprating options and refinement of these three is clearly worthwhile. The means for identifying other possible uprating options and selecting the most appropriate has been presented in the preceding notes. 2.8.7
Conclusions
The impetus for line uprating comes as a result power system analysis. Present electrical loads are projected into the future, and the impact of various component outages (i.e., contingencies) on the electrical loading of the existing line is determined. Specific probabilities are seldom associated with post-contingency loadings, and even the prediction of normal loads is often uncertain, particularly with the advent of “open access” to commercial power generators. For uprating to be possible, the existing line must be in good condition. Having established this, the identification of possible uprating methods depends upon the physical, electrical, and thermal characteristics of the existing line. An “Uprating Analysis Table” is developed here that simplifies the analysis of the existing line and provides a basis for identifying promising uprating methods in each specific line. Once the most promising uprating methods have been identified, a detailed analysis comparing the costs and capabilities of each method is required. The final selection of an uprating method and its success in providing the necessary increase in line capacity while maintaining system reliability and minimizing capital cost involves a good deal of engineering judgment, as well as the application of suitable numerical tools.
2-103
Chapter 2: Overhead Transmission Lines
REFERENCES
Adams, H. W. 1974. “Steel Supported Aluminum Conductors (SSAC) for Overhead Transmission Lines.” IEEE Paper T 74 054-3. Presented at the IEEE PES Winter Power Meeting. Alcoa. 2003. “Alcoa Sag10 User’s Manual.” Aluminum Association. 1974. “Stress-Strain-Creep Curves for Aluminum Overhead Electrical Conductors.” Aluminum Association. 1989. “Aluminum Electrical Conductor Handbook.” Third Edition. Aluminum Company of America. 1961. “Graphic Method for Sag Tension Calculations for ACSR and Other Conductors.” Aronstein, J. 1990. “Conduction in Failing Aluminum Connections.” Proceedings of the Thirty-Sixth IEEE Holm Conference on Electrical Contacts. Montreal, Quebec. August. Barrett, J. S., P. Ralston, and O. Nigol. 1982. “Mechanical Behaviour of ACSR Conductors.” CIGRE International Conference on Large High Voltage Electric Systems. September 1-9. Beers, G. M., et al. 1963 “Transmission Conductor Ratings.” AIEE Transactions. Paper 63-86. Bennett, E. H. 1992. “Designing Compression Fittings for Long-Term Survival.” Bonneville Power Engineering Symposium. April. Black, W. Z., W. R. Byrd, R. A. Bush, and T. C. Champion III. 1983. “Experimental Verification of a RealTime Program for the Determination of Temperature and Sag of Overhead Lines.” Paper 83 WM 144-3. January.
Increased Power Flow Guidebook
Boteler, D. H. 1994. “Geomagnetically Induced Currents: Present Knowledge and Future Research.” IEEE Transactions on Power Delivery. Volume 9. Number 1. January. pp. 50-58. Braunovic, M. 1985. “Effect of Contact Aid Compounds on the Performance of Bolted Aluminum-toAluminum Joints Under Current Cycling Conditions.” 31st Annual Holm Conference. Chicago, IL. September. Cahill, T. 1973. “Development of Low-Creep ACSR Conductor,” Wire Journal. July. Campbell, H. E. and J. J. Burke. 1985. “Power Distribution Systems Course.” PTI Course. September. Chisholm, W. A. 1986. “Ampacity Field Studies on Line with Low Operating Temperature.” EPRI DTR Seminar. May. CIGRE. 1992. WG 05 – Conductors. “The Thermal Behaviour of Overhead Conductors.” 22-81 (WG05) – 06. December. CIGRE. 1997. WG 12-22. “Thermal State of Overhead Line Conductors.” Electra. No. 121. pp. 51-67. CIGRE. 2000. WG 22-12. “Description of State of the Art Methods to Determine Thermal Rating of Lines in Real-Time and Their Application in Optimising Power Flow.” Paper 22-304. Clapp, A. L. 1985. “Relationships of National Electrical Safety Code Vertical Clearances and Potentially Conflicting Activity.” IEEE Transactions on Power Apparatus and Systems. Vol. PAS-104. No. 11. November. pp. 3306-3312. Dalle, B. 1982. Size and Aging of Joints for Bare Conductors of Overhead Line. Electricite de France. December.
Black, W. Z. and W. R. Byrd. 1983. “Real Time Ampacity Model for Overhead Lines.” IEEE Transactions. Vol. PAS-102. No. 7. July. pp. 2289-2293.
Davidson, G. A., et al. 1969. “Short-time Thermal Ratings for Bare Overhead Conductors.” IEEE Transactions on Power Apparatus and Systems. Vol. PAS-88. No.3. March.
Black, W. Z. and R. L. Rehberg. 1985. “Simplified Model for Steady State and Real-time Ampacity of Overhead Conductors.” IEEE Transactions on Power Apparatus and Systems. Vol. 104. October. Pp. 29-42.
Davis, M. W. 1979. Development of Real Time Thermal Rating System. St. Louis, MO: Edison Electrical Institute T&D. May 19.
2-104
Increased Power Flow Guidebook
DeLuca, C. B. 1986. “Current Cycling Connectors in Tension.” Proceedings of Seminar on Effects of Elevated Temperature Operation on Overhead Conductors and Accessories. pp. 110-119. Atlanta, Georgia. May. Douglass, D.A. 1986. “Weather-Dependent Versus Static Thermal Line Ratings.” IEEE Paper No. 86 T&D 503-7. Presented at the IEEE T&D Conference. Anaheim, California. September. Douglass, D. A., I. S. Grant, et al. 1986. “Optimization of Line Uprating.” Presented at IEEE/PES T&D Special Session “Upgrading Transmission Lines.” Anaheim, California. September. Douglass, D. A. and L. S. Rathbun. 1984. “AC Resistance of ACSR - Magnetic and Temperature Effects.” IEEE Paper 84 SM 700-1. Douglass, D. A. and A. Edris. 1996. “Real-time Monitoring and Dynamic Thermal Rating of Power Transmission Circuits.” IEEE Transactions on Power Delivery. Vol. 11. No. 3. July. Douglass, D. A. and A. Edris. 1999. “Field Studies of Dynamic Thermal Rating Methods for Overhead Lines.” IEEE T&D Conference Report. New Orleans. April 7. New Orleans, LA. Dunlop, R. D., R. Gutman, and P. P. Marchenko. 1979. “Analytical Development of Loadability Characteristics for EHV and UHV Transmission Lines.” IEEE Transactions on Power Apparatus and Systems. Volume 98. Number 1. March/April. pp. 606-617. correction May/June. page 699.
Chapter 2: Overhead Transmission Lines
EPRI. 1995. Thermal Models for Real-Time Monitoring of Transmission Circuits. Report No. TR-105421. December. EPRI. 2001. Video Sagometer Application Guide. EPRI Report N0. 1001921. September. EPRI. 2002. Performance of Transmission Line Components at Increased Operating Temperatures. EPRI Interim Report. December. EPRI. 2005. Transmission Line Reference Book, 345 kV and Above, EPRI, Palo Alto, CA. Federal Power Commission. 1964. National Power Survey. Part II-Advisory Reports. U. S. Government Printing Office. Washington, D. C. October. Fink, D. G. and H. W. Beaty. 1993. Standard Handbook for Electrical Engineers. 13th Edition. McGraw-Hill. Foss, S. D., S. H. Lin, and R. A. Fernandez. 1983. “Dynamic Thermal Line Ratings—Part 1—Dynamic Ampacity Rating Algorithm.” IEEE Transactions on Power Apparatus and Systems. Vol. PAS-102. No. 6. pp. 1858-1864. June. Frank, W. 1959. “The Critical Aspects of Steel Hardware in Aluminum Connectors.” AIEE Transmission and Distribution Committee. June. Hall, J. F. and A. K. Deb. 1987. “Economic Evaluation of Dynamic Thermal Rating by Adaptive Forecasting.” IEEE Paper 87 SM 556-4. Presented at the IEEE Summer Power Meeting. July.
Dupre, H. 1951. The Problems Involved in Designing Connectors for Aluminum Cable. AIEE 51-325. September.
Harvey, J. R. 1969. Creep of Transmission Line Conductors. IEEE Transactions. Vol. PAS-88. No. 4. pp. 281-285. April.
Edris, A. 2000. “FACTS Technology Development: An Update.” IEEE Power Engineering Review. Vol. 20. No. 3. March.
Harvey, J. R. and R. E. Larson. 1972. “Creep Equations of Conductors for Sag-Tension Calculations.” IEEE Paper C72 190-2.
Ehrenburg, D. O. 1935. “Transmission Line Catenary Calculations.” AIEE Paper. Committee on Power Transmission & Distribution. July.
Harvey, J. R. and R. E. Larson. 1970. “Use of Elevated Temperature Creep Data in Sag-Tension Calculations.” IEEE Transactions. Vol. PAS-89. No. 3. pp. 380-386. March.
EPRI. 1994. Handbook of Shielding Principles for Power System Magnetic Fields: Volume 1: Introduction and Application Volume 2: Methods and Measurements. 103630. Palo Alto, CA.
Hickernell, L. F., A. A. Jones, and C. J. Snyder. 1949. “Hy-Therm Copper – An Improved Overhead Line Conductor.” AIEE Transactions. Vol. 68. pp. 22-27.
2-105
Chapter 2: Overhead Transmission Lines
Increased Power Flow Guidebook
Hiel, C. 2000. “Development of a Composite Reinforced Aluminum Conductor.” California Energy Commission Report. November.
Lewis, W. A. and P. D. Tuttle. 1958. “The Resistance and Reactance of Aluminum Conductors Steel Reinforced.” AIEE Transactions. Vol. 77. Part III.
House, H. E., W. S. Rigdon, R. J. Grosh, and W. B. Cottingham. 1963. “Emissivity of Weathered Conductors after Service in Rural and Industrial Environments.” AIEE Transactions. pp. 891-896. February.
Longo, V. J. and I. S. Grant. 1981. “Economic Incentives for Larger Transmission Conductors.” IEEE Paper 81 WM 208-8. Presented at the IEEE Winter PES Meeting, February.
Howitt, W. B. 1986. Elevated Temperature Performance of Conductor Accessories. Proceedings of Seminar on Effects of Elevated Temperature Operation on Overhead Conductors and Accessories. pp. 120-139. Atlanta, Georgia. May.
Nabet, G. 1986. “Thermal Ratings for Bare Overhead Conductors—Method Used by Pa-NJ-Maryland Interconnection.” Proceedings of Seminars on Effects of Elevated Temperature Operation on Overhead Conductors and Accessories. Atlanta, Ga. May. (Sponsored by Georgia Power and EPRI).
IEEE. 1993a. Standard 738-93. “IEEE Standard for Calculation of Bare Overhead Conductor Temperatures.” IEEE. 1993b. “IEEE Standard for Calculating the Current-Temperature Relationship of Bare Overhead Conductors.” PES. IEEE Standard 738-1993. IEEE. 1993c. “Guide to the Installation of Overhead Transmission Line Conductors.” IEEE Standard 5241993. New York, NY. IEEE. 1999. “Limitations on Stringing and Sagging Conductors,” Paper TP64-146. Working Group of the IEEE Towers, Poles, and Conductors Subcommittee of the Transmission and Distribution Committee of the IEEE Power Engineering Society. Johnson, D. 2001. “Composite Conductors—A New Overhead Conductor (ACCR).” IEEE Panel Session on Applications and Economics of New Conductor Types. Vancouver, B.C. July. Kikuta, T. 2001. “Low Sag Up-rating Conductor.” IEEE Panel Session on Applications and Economics of New Conductor Types. Vancouver, B.C. July. Koessler, R. J. and J. W. Feltes. 1993. “Voltage Collapse Investigations with Time-Domain Simulation.” IEEE/NTUA Joint International Power Conference. Athens Power Tech Proceedings. Athens, Greece. September 5-8. Lesher, R. L., J. W. Porter, and R. T. Byerly. 1994. “Sunburst—A Network of GIC Monitoring Systems.” IEEE Transactions on Power Delivery. Volume 9. Number 1. January. pp. 128-137.
2-106
National Electric Safety Code. 1993. 1993 edition. National Electric Safety Code. 1997. 1997 edition. C2-1997. Naybour, R. D. and T. Farrell. 1973. Degradation Mechanisms of Mechanical Connectors on Aluminum Conductors. PROC IEE. Vol. 120. No. 2. pp. 273-280. February. NEMA. 1973. Standard, EEOI-NEMA. Connectors for use Between Aluminum or Aluminum-Copper Overhead Conductors. NEMA Pub. No. CC 3-1973. August. Nigol, O. and J. S. Barrett. 1980. “Development of an Accurate Model of ACSR Conductors for Calculating Sags at High Temperatures.” Ontario Hydro Research Division. CEA. March. Rawlins, C. B. 1998. “Some Effects of Mill Practice on the Stress Strain Behavior of ACSR.” Presented at IEEE Winter Meeting. Tampa, FL. February. Reding, J. L. 1991. “Investigation of Thrasher Compression Fittings on BPA's Direct Current Transmission Line.” IEEE Trans. PWRD-6. No. 4. pp. 1616-1622. October. Reding, J. L. 1994. “A Method for Determining Probability Based Allowable Current Ratings for BPA’s Transmission Lines.” IEEE Transactions on Power Delivery. Vol. 9. No. 1. January. Rural Electrification Administration. 1992. REA Bulletin 1724E-200. “Design Manual for High Voltage Transmission Lines.” 9/3/92.
Increased Power Flow Guidebook
Sato, K., N. Mori, et al. 1981. “Development of Extremely-Low-Sag Invar Reinforced ACSR (XTACIR). IEEE Transactions on Power Apparatus and Systems. Vol. PAS-100. No. 4. April. Schmidt, N. 1997. “Comparison between IEEE and CIGRE Ampacity Standards.” IEEE PE-749-PWRD-006-1997. Berlin, Germany. July. Seppa. T. O., et al. 1998. “Use of On-Line Tension Monitoring Systems for Real Time Ratings, Ice Loads and Other Environmental Effects.” CIGRE Report 10222. September. Paris, France. Smith, J. 2001. (Applied Thermal Sciences). “Advanced Carbon Conductor Project Report.” National Science Foundation. August. St. Clair, H. P. 1953. “Practical Concepts in Capability and Performance of Transmission Lines.” AIEE Transactions on Power Apparatus and Systems. Volume 72. Part III. December. pages 1152-1157. Troia, G. D. 2000. “Effects of High Temperature Operation on Overhead Transmission Full-Tension Joints and Conductors.” IEEE WG 12. August.
Chapter 2: Overhead Transmission Lines
Trash, R. et al. (ed.) 1994. Overhead Conductor Manual. Southwire. Thrash, F. R. 1999. “ACSS/TW - An Improved Conductor for Upgrading Existing Lines or New Construction.” IEEE Paper 0-7803-5515. June. Tunstall, M. J., et al. 2000. “Maximizing the Ratings of National Grid’s Existing Transmission Lines Using High Temperature, Low-sag Conductor.” CIGRE Paper 22-202. Paris, France. August. Turner, D. K. and B. J. Belk. 1987. “Elevated Conductor Temperatures and Their Effect on Planning and Design.” Presented at the Transmission and Substation Design and Operation Symposium. Ft. Worth, Texas. September. Winkelman, P. F. 1959. “Sag-Tension Computations and Field Measurements of Bonneville Power Administration.” AIEE Paper 59-900. June. Wong, T. Y., J. A. Findlay, and A. N. McMurtie. 1982. “An On-Line Method for Transmission Ampacity Evaluation.” IEEE Transactions on Power Apparatus and Systems. Vol. PAS-101. No. 2. February.
2-107
Increased Power Flow Guidebook
CHAPTER 3
Underground Cables
3.1
INTRODUCTION
Many factors need to be considered when evaluating uprating and upgrading options for underground transmission cables. Chapter 3 provides a general description of concepts that a utility engineer should consider in understanding underground power cables and selecting uprating technologies that are appropriate. While this chapter focuses on transmission, many of the concepts are equally valid for distribution cables, although the costbenefit ratio of applying these techniques to distribution is less easy to justify. Chapter 3 includes nine sections:
• Section 3.2, Cable System Types, provides an overview on underground cable systems and a very brief background on each of the major transmission cable types.
• Section 3.3, Power Flow Limits and System Considerations, considers aspects external to a specific cable circuit that may limit power flow regardless of the cable circuit’s rating.
• Section 3.4, Underground Cable Ratings, provides an overview of cable system ampacity, including worked examples, to understand the basic approach to calculating ratings and the areas where uprating or upgrading could be applied.
• Section 3.5, Uprating and Upgrading Constraints, lists some of the major barriers to uprating that are inherent to each cable system type or installation location.
• Section 3.6, Increasing the Ampacity of Underground Cable, is the major focus of this chapter, describing how to increase capacity on existing circuits. Other sections of the chapter have been provided to support this chapter.
• Section 3.7, Reconductoring (Upgrading), discusses topics related to replacing cables to increase capacity, possibly combined with other uprating considerations.
• Section 3.8, Dynamic Ratings of Underground Cable Systems, includes information on the state-of-the-art methods used for optimizing the rating on a cable system, including topics on real-time monitoring and ratings.
• Section 3.9, Case Studies for Underground Cable Circuits, describes real-world uprating applications that have been implemented by utility-users, along with their respective experiences.
• Section 3.10, Summary of Uprating and Upgrading Approaches and Economic Factors, lists the various uprating and upgrading approaches with qualitative comparisons of each concept. While readers of this chapter are encouraged to have a background in underground cable systems, the various sections provide a general overview so that those readers who are unfamiliar with underground technologies may also come away with an understanding and be able to utilize some of the technologies discussed on their own cable systems. Readers are also encouraged to review appropriate industry standards and guides from
3-1
Chapter 3: Underground Cables
Increased Power Flow Guidebook
the Institute of Electrical and Electronics Engineers (IEEE), Association of Edison Illuminating Companies (AEIC), International Electrotechnical Commission (IEC), Insulated Cable Engineers Association (ICEA) and others. In addition to providing valuable background on cable manufacturing, rating and installation practices, these documents also include supporting information about testing (type, routine and commissioning) that may be done in conjunction with uprating activities. 3.2
CABLE SYSTEM TYPES
Underground transmission is often used to transfer power where overhead lines are impractical. Issues that affect the selection of underground cables vary but are generally focused around reduced rights-of-way requirements, aesthetics, and minimizing the environmental impact associated with installing transmission systems. There are three major types of cables systems:
• High-pressure fluid-filled (HPFF) or gas-filled (HPGF), pipe-type
• Extruded dielectric (XD), including cross-linked polyethylene (XLPE) and ethylene-propylene-rubber (EPR) cable types
• Self-contained liquid-filled (SCLF) or self-contained
When evaluating uprating and upgrading strategies for underground cable systems, it is first important to consider the unique characteristics of each of these cable system types. This section describes the construction features and operational characteristics of each cable system. 3.2.1
High-Pressure Pipe-Type (Fluid- and Gas-Filled)
Cable Construction Pipe-type cables incorporate three cable phases installed in a common steel pipe (see Figure 3.2-1). Each cable phase consists of a stranded copper or aluminum conductor, with a layer of metallic (steel or copper) binder tapes intercalated with a carbonized black paper tape. Larger conductors above 800 mm2 (1500 kcmil) may be segmented to reduce ac resistance, and hence reduce ac losses. Over the conductor shield is a laminated Kraft paper or, for higher voltages, a laminated paperpolypropylene insulation. The insulation thickness is governed by voltage. Typical AEIC insulation thicknesses are listed in Table 3.2-1. The insulation wall thickness is important when evaluating reconductoring options or for considering the free area within the pipe for circulating dielectric liquid. These concepts are discussed in Section 3.7.
oil-filled (SCOF)
Table 3.2-1 Typical Pipe Cable Insulation Thicknesses Rated kV Phase-to-Phase
Size of Conductors
Insulation Thickness
(kcmil)
(mm2)
Laminated Paper Polypropylenea mils (mm)
69
167.8-4000
85 – 2027
n.a.
270 (6.86) 300b (7.62b)
115
350-750 800-4000
177-380 405-2027
250 (6.35) 250 (6.35)
420 (10.67) 375 (9.53) 485b (12.32b)
120
350-750 800-4000
177-380 405-2,027
n.a.
435 (11.05) 405 (10.29)
500-900 1000-4000
253-456 507-2027
300 (7.62) 270 (6.86)
161
759-900 1000-4000
380-456 507-2027
n.a.
575 (14.61) 515 (13.08)
230
1000-2000 2250-4000
507-1013 1140-2027
450 (11.43)
745 (18.92) 605 (15.37)
345
1000-1250 1500-4000
507-633 760-2027
500
2000-4000
765
2000-4000
138
Paper mils (mm)
490 (12.45) 440 (11.18) 585b (14.86b)
600 (15.24)
1020 (25.91) 905 (22.99)
1013-2027
745 (18.92)
1100 (27.94)
1013-2027
1200 (30.48)
n.a.
a. Large conductor sizes using laminated paper polypropylene insulation may require increased insulation wall thicknesses to control the minimum electrical stress to 1750 volts/mil (68.9 kV/mm) so as not to exceed the design limits of terminals and splices. b. High-pressure gas-filled (HPGF) cable insulation thicknesses.
3-2
Increased Power Flow Guidebook
Over the insulation, it is common to see one or two metalized Mylar tapes applied over a carbonized black paper tape. The Mylar tape acts as a moisture seal to limit insulation contamination and dielectric liquid drainage prior to installation. Metal shield tapes are then applied over the Mylar tape. Over the shield and moisture barrier tapes is one or two helical metal skid wires, typically constructed of stainless steel, zinc, brass, or bronze. The skid wires provide mechanical protection when the three cables are pulled into the installed cable pipe. On a few cable designs, a plastic “compression jacket” is applied over the insulation shield (more often on HPGF cables than HPFF cables) to limit the insulation impregnate from draining from the insulation and mixing with the dielectric media within the cable pipe.
Chapter 3: Underground Cables
• Normal Joint. The cable conductors are connected through the casing, and hydraulic continuity is permitted (see Figure 3.2-3).
• Semi-Stop Joint. The cable conductors are connected through the casing and hydraulic flow is stopped for differential pressures below 350 kPa (50 psi). Valves may allow complete hydraulic isolation from one side of the joint to the other.
Cable Pipe The pipe is generally ASTM A-523 Schedule 20 or 40 line pipe, 6.35 mm (¼-in.) wall with flared ends to facilitate welding with chill rings. A cable trench is excavated for the installation of the cable pipe. Typically, the trench is usually backfilled with “thermal sand” or a Fluidized Thermal Backfill (FTB) that helps ensure good heat transfer away from the cable pipes (Figure 3.2-2). Joints Pipe cables may be 32 km (20 miles) long, but most installations are only a few kilometers (miles). Installation sections are on the order of 350-1000 m (12003300 ft) and require manholes and joints to connect cable sections. Cable pipes enter both ends of the manhole to facilitate joining the cables. Inside manholes, section casing lengths of 1-1.5 m (3-5 ft)— generally 1.53 times the cable pipe diameter—are used to connect pipe sections. Inside the casing, each cable phase is joined together using a compression connector and hand-applied paper or laminated-paper-polypropylene tapes. Joints may be one of three types:
Figure 3.2-1 Example of high-pressure fluidfilled (HPFF) pipe-type cable.
Figure 3.2-2 Pipe-type cable trench being backfilled with FTB.
Figure 3.2-3 Pipe-type cable manhole with joint casing.
3-3
Chapter 3: Underground Cables
• Full Stop Joint. The cable conductors are connected through the casing, but there is no hydraulic continuity as the full stop joint supports rated line pressure differential. Terminations (Potheads) The ends of a pipe-type circuit are terminated with a graded insulation that controls electrical stress from the paper-insulated cable to the air-insulated terminal. A “cone” of insulation is applied within a porcelain termination to provide hydraulic and electrical isolation for the cable end. Leading up to the terminations, the three cables within the common cable pipe are separated into individual stainless steel pipes through a trifurcating joint (see Figure 3.2-4). Nonmagnetic stainless steel pipes are used between the trifurcating joint and the termination to avoid the high circulating currents and eddy current heating that would otherwise result if conventional carbon steel pipe were used. Stand-off insulators are used at the base of the potheads to isolate the pothead from the support structure so that circulating currents are not induced in the riser pipes between the trifurcator joint and pothead. Fluid-Filled Cables High-pressure fluid-filled (HPFF, also known as highpressure oil-filled) cables are installed in cable pipes where the pipe is filled with very clean, very low mois-
Increased Power Flow Guidebook
ture dielectric fluid. Older HPFF cable systems (before 1970) typically used mineral oil for the pipe filling dielectric fluid. HPFF cable systems installed after 1970 have used alkyl benzene or polybutene dielectric fluid (polybiphenyl chlorine-based liquids were never used as an insulating liquid in pipe cables). The dielectric fluid is pressurized to 1400 kPa (200 psi) and is generally free to mix with the insulation impregnant, although this movement is limited. Gas-Filled Cables High-pressure gas-filled (HPGF) cables use pressurized dry nitrogen gas inside the cable pipe. HPGF cables still utilize dielectric-fluid impregnated into paper insulating tapes as insulation, but the dielectric fluid is generally of a much higher viscosity than fluid-filled cables to limit drainage. Also, the insulation thickness on HPGF cables is slightly greater than in HPFF cables as shown in Table 3.2-1. Nitrogen pressure is typically on the order of 1400 kPa (200 psig). Bottled nitrogen and a pressure regulator located near the terminal ends are used to maintain the pressure within the cable pipe. Low-pressure alarms are utilized to ensure that the cable pipes are maintained at the required pressure to avoid damaging the pipe cable. Other Equipment Pumping Plants As was mentioned above, pipe-type cables are pressurized with either dry nitrogen or dielectric liquid. For the liquid-filled cables, a “pumping plant” or “pressurization plant” is needed to maintain and regulate the typically 1400 kPa (200 psi) pressure within the cable pipe (Figure 3.2-5). Cathodic Protection Equipment The carbon steel pipe must be protected from corrosion to avoid leaks and deterioration of the pipe. The first level of protection is a corrosion protection layer that is applied over the outside of the pipe. Older cable systems used a hot applied tar coating or a somastic coating that is similar to concrete. More recent HPFF cable systems use pipe that is coated with a polymeric material such as high-density polyethylene. These corrosion protection coatings are effective in preventing corrosion if there are no holes (“holidays”) or cracks in the coatings. However, some damage inevitably occurs to the pipe coating during installation or subsequent digging after the cable system has been placed in service. Consequently, it is necessary to further protect the cable pipe with impressed current cathodic protection systems or sacrificial anodes.
Figure 3.2-4 Above ground trifurcator (spreader head) and pipe-type cable potheads.
3-4
Some HPFF cable system pipes are corrosion protected with magnesium sacrificial anodes that are connected to
Increased Power Flow Guidebook
the pipe at manhole locations as well as at the substations where the cable terminations are located. Impressed current cathode protection systems must provide enough current to maintain the cable pipe at a potential of –1.0 volt dc (or in some cases higher) with respect to the surrounding earth. The impressed current/pipe grounding system must also be designed to accommodate the maximum line-to-ground fault current while keeping the pipe potential close to ground potential. Several types of impressed current systems have been used to cathodically protect and ground the cable pipe. These are: Resistor/Rectifier Cathodic Protection. In this type of cathodic protection system, the ends of the pipe are grounded through low resistance connections (several milliohms), and a relatively high-capacity dc current supply forces enough current through the resistor to maintain the dc pipe potential at approximately -0.85 to -1.0 V. Polarization Cells with Rectifiers. In this type of cathodic protection system, a passive device called a polarization
Chapter 3: Underground Cables
cell is used to ground the cable pipe at the end point substations. A polarization cell, which is about the size of a car battery, is characterized by a relatively high resistance to dc voltages of several volts and a low resistance to ac currents. A relatively low-capacity dc rectifier then supplies enough current to the pipe to maintain the pipe potential at -0.85 to -1.0 V. Solid-State Pipe Grounding Devices with Rectifiers. The most recent development for pipe cathodic protection includes power electronic devices that are capable of conducting line-to-ground fault currents. These devices are direct replacements for the polarization cells described above. 3.2.2
Extruded Dielectric
Cable Construction Extruded dielectric cables are so named because the insulation is extruded onto the conductor core (Figure 3.2-6), as compared to paper-insulated cables (HPFF or SCFF), where the insulation is a laminar application of paper. The cables consist of a stranded copper or aluminum conductor. Larger conductors above 800 mm2 (1500 kcmil) may be segmented to reduce ac impedance, and
Figure 3.2-5 Pumping plant pressure charts and control system (left) and fluid reservoir (right).
3-5
Chapter 3: Underground Cables
hence reduce ac losses. The typical extruded insulation types are as follows:
• Cross-linked Polyethylene (XLPE). This cable insulation is the most common on modern XD cable systems with applications up to 500 kV. The insulation is cross-linked (vulcanized), forming long polymer chains that are joined to one another at intermediate carbon atoms. XLPE cable manufacturing is extremely sensitive to cleanliness and quality control during the manufacturing process. “True triple extrusion” process, where the conductor shield, insulation, and insulation shield are extruded together, is the standard extrusion process. This ensures that there is good adhesion between the insulation-shield boundaries and limits the likelihood that contaminants get into the insulation. XLPE insulation is extremely sensitive to the presence of moisture or water, which could lead to water and electrical trees.
• Ethylene-Propylene-Rubber (EPR). This insulation type is often considered for distribution cables and transmission cables up to 138 kV. The insulation is very “lossy” as compared to XLPE insulation, resulting in high dielectric losses and charging current. For this reason, EPR insulation is rarely considered for higher voltage cable systems. The insulation material is relatively forgiving about operation in the presence of water, so that the cable may not include a hermetic moisture barrier like the one required on XLPE cables.
• Linear Low or Medium Density Polyethylene (LLPE, MDPE). This insulation type is less common for new installations, although there are several installations,
Figure 3.2-6 Example extruded dielectric (XLPE) transmission cable.
3-6
Increased Power Flow Guidebook
predominantly in France. As compared to XLPE insulation, LLPE and MDPE were first used at the higher voltage levels because the extrudate could be raised to higher temperatures without forming crosslinking agents present. This permitted filtering the extrudate at higher temperatures with finer-grade mesh screens. The disadvantage is that the maximum normal operating temperature for cables with LLPE and MDPE is much lower, limiting the power transfer for a given conductor size as compared to an otherwise similar XLPE cable. Typical insulation thicknesses for extruded insulation are summarized in Table 3.2-2. After the conductor and insulation shields and insulation are applied, the outer layers of an extruded cable vary depending on the application. All XLPE cables and most other extruded transmission cables have some type of metallic sheath consisting of a lead extrusion, corrugated copper, aluminum or stainless steel, or copper or aluminum foil laminate. There may be additional copper or aluminum wires applied under the moisture barrier for additional fault current capability. Over the metallic moisture barrier is typically an extruded insulating jacket of linear low, medium, or high-density polyethylene. The jacket electrically isolates the metallic moisture barrier to control circulating currents and insulate to induced voltages. The jacket also provides corrosion protection. Extruded dielectric cables do not utilize any dielectric liquid, which has increased the use of this cable type as it represents a low-maintenance cable system with minimal potential for environmental impact. Installation Considerations Most extruded transmission cables are manufactured as single phases that are connected into three-phase systems (there are three-core extruded cables that may be used for transmission voltages, but these are less common). The cable phases may be installed directly buried in the ground or pulled into conduits. Direct buried installations are generally less expensive and have slightly better ampacity capability for a given conductor size, but require that the trench for an entire installation section be open, which is generally not possible with urban installations. Duct bank installations are installed in similar manners as pipe-type cables in that the conduit system is installed first and backfilled with concrete, thermal sand, or Fluidized Thermal Backfill (FTB) (Figure 3.2-7). The cables are then pulled into the conduits later. The cost for duct bank installations is normally greater than direct buried, both for materials and installation, but later changes to the cable system do not require surface excavation.
Increased Power Flow Guidebook
Chapter 3: Underground Cables
Table 3.2-2 Typical Extruded Cable Insulation Thicknesses Size of Conductors Rated kV Phaseto-Phase
(kcmil)
(mm2)
63-70
500-2000
110-120
474 4,000
Insulation Thickness XLPE mils (mm)
LLPE mils (mm)
EPR mils (mm)
253-1013
650 (16.5)a 433 (11.0)b
650 (16.5) 433 (11.0)
650 (16.5)
240 2000
800 (20.3)a 620 (15.7)b
709 (18) 630 (16)
800 (20.3)
(21.6)a
132-138
750-3000
380-1520
850 650 (16.5)b
150-161
592 3,947
300 2000
24.5 21.2
19.5 19.5
220-230
789 3,947
400 2,000
906 (23)c 866 (22)
906 (23) 866 (22)
850 (21.6)
330-400
1243-2368
630-1200
1063 (27)
1063 (27)
500
2000-4000
1013-2027
1260 (32)
1260 (32)
a. AEIC CS7-1993 “full wall” insulation thicknesses. b. Typical minimum insulation thicknesses used on commercial cable. c. Initial applications of 230-kV XLPE cable in North America used insulation thicknesses of approximately 29-mm (1142 mils).
Extruded dielectric cables may also be installed under water. The submarine installations often utilize a stranded armor around the outside of the cables but are otherwise similar in construction to land cables. Joints As with pipe-type cables, extruded cables are typically installed in sections of 300–850 m (1000-2800 ft) that must be joined together. For direct buried systems, the joints may be directly buried and backfilled with thermal sand. Duct bank installations utilize manholes similar to pipe-type cables. Older joint technology for XLPE cables utilized “field-molded” joints where unvulcanized polyethylene tapes were applied around a connector and cables and then heated and vulcanized
Figure 3.2-7 Duct bank installation for extruded dielectric cables.
using specialized equipment. This approach required additional time and was more sensitive to workmanship than the present technology that utilizes “prefabricated” joints where the cable ends are inserted into the factory-molded joint (Figure 3.2-8). Each cable phase is joined separately. Depending on the sheath bonding scheme (single-point bonded, crossbonded, or multi-point bonded—see Section 3.6.8 for a
Figure 3.2-8 Factory pre-molded joint for XLPE cable (“Click-Fit” joint from Pirelli).
3-7
Chapter 3: Underground Cables
detailed discussion), the joint may have sheath interrupts built into the joint. This allows electrical isolation of the sheath from one side of the joint to the other and permits transpositions of sheath connections in a crossbonding link box or connection of the ungrounded sheath end to a sheath voltage limiter.
Increased Power Flow Guidebook
support structure. For cable systems with cross-bonded or single-point bonded sheaths, the stand-off insulators control circulating currents. During maintenance, the stand-off insulators allow the cable jacket to undergo a 10-kV dc test to insure cable jacket integrity. 3.2.3
The cable joints are often placed on racks on the sides of the manhole and mechanically supported so that the joint does not move as a result of thermal-mechanical bending. One distinction between pipe-type cable manholes and manholes for other cable types is that parallel pipe circuits may pass through the same manhole while XLPE cables typically have individual manholes for each circuit unless all the XLPE circuits connect to a common bus at the terminals (e.g., as shown for the manhole in Figure 3.2-9). Pipe circuits can pass through a common manhole since utilities generally allow work on one pipe circuit while a parallel circuit is still energized. Extruded cables, lacking the robust steel cable pipe and joint casing, are generally not operated this way both for concerns about faults and the possibility of induced voltages and currents from nearby parallel circuits.
Self-Contained Liquid-Filled (SCLF)
Cable Construction Self-contained liquid-filled (SCLF) (also known as selfcontained oil-filled [SCOF] or low-pressure oil-filled [LPOF]) cables utilize the dielectric liquid-impregnated laminated-paper insulation similar to pipe-type cables, but three separate cables are installed for the three phases. The cable is called “fluid-filled” because there is a hollow fluid channel in the center of the conductor that allows dielectric liquid to move through the cable with thermal expansion and contraction (Figure 3.2-11). As compared to pipe-type cables, the SCLF cable typically operates at a lower pressure of 105– 525 kPa (15–75 psi). Two different methods are used to construct the stranded hollow conductors. Smaller conductors typically consist of a helical steel support for the fluid channel, over which is applied the conductor
Terminations Terminations (terminators) provide a means of grading the high electrical stress in the cable insulation to an airinsulation where the cable is connected to other equipment (Figure 3.2-10). Most termination designs for extruded dielectric transmission cables utilize a small amount (200–400 liters, 50–100 gallons) of silicone oil. The metallic and semiconducting shields are removed from the outside of the insulation, and the insulation is sanded smooth prior to installing a stress cone and placing a polymer or porcelain termination housing over the prepared cable end. The terminations typically have polymer or porcelain stand-off insulators that isolate the base plate from the
Figure 3.2-9 Extruded dielectric cable manhole.
3-8
Figure 3.2-10 Termination for a 145-kV class extruded dielectric cable.
Increased Power Flow Guidebook
strands (usually copper but may be aluminum). Larger conductors are manufactured by using “keystone” shaped copper strands to form the fluid channel, and the helically-applied round strands are then applied over the first layer of formed strands. Large conductors (i.e., 1000 mm2 or larger) are typically assembled with 4, 5, or 6 segments that are brought together around the fluid channel. For larger conductor sizes, a binder tape (metallized paper tape, carbon black tape, or copper or steel tape) is applied around the outside of the high-voltage conductors to maintain the circular construction, particularly around segmented conductors. A carbonized black paper tape may be intercalated with the binder tape for a conductor shield. Many layers of insulating tapes are then wound around the cable conductor using a tape “lapping” machine in a low-humidity environment (see Figure 3.2-12). Both conventional cellulose and laminated paper polypropylene (LPP) tapes are used to insulate SCLF cables. The cable cores are then impregnated with low-viscosity dielectric liquid, such as alkyl- or dodecyl-benzene. Over the insulation, carbon black paper tapes and metallic shield tapes are applied. A metallic sheath is then applied around the outside of the cable core to facilitate pressurization of the cable system and to exclude moisture. The cable sheaths are typically tubular lead or corrugated aluminum or copper. In some cases, lead sheaths must be reinforced with nonmagnetic metal tapes to withstand the cable fluid pressure. On some SCLF submarine cables, a concentric copper conductor may be installed to reduce induced sheath current and armor wire losses. This is common on submarine cables where there may be large phase spacing, resulting in induced currents that approach the magnitude of the phase currents. An insulating plastic jacket,
Figure 3.2-11 Example self-contained liquid-filled cable.
Chapter 3: Underground Cables
similar to extruded cables, is applied over the metallic sheath. Installation Considerations SCLF cables are typically installed directly buried or suspended from the walls of underground tunnels, particularly in Europe and Asia. Concrete-encased duct bank installations have been the most common installation method used in North America. SCLF cables are frequently used for submarine cable installations because SCFF cables can be manufactured in long lengths (greater than 15 km or 9 miles) without factory or field joints. One of the significant differences between the installation of SCLF cables and other types of transmission cables is that dielectric fluid pressure must be maintained at all times. The cables are shipped from the factory on reels with integral pressure reservoirs to maintain the fluid pressure during shipment and storage. Joints SCLF cable joints are, in general, more complicated than joints for other cable types. Two different types of joints are required for most SCLF transmission cable circuits that have elevation differences greater than 150 m (500 ft) or that are longer than 5 km (3 miles) in length. The normal, or straight-through, joint is designed to electrically connect the conductor between two adjacent cable sections and to provide hydraulic continuity between the two cable sections. The splice casing must also act as a pressure vessel and in some cases electri-
Figure 3.2-12 SCLF tape lapping machine for paper cable.
3-9
Chapter 3: Underground Cables
cally isolate the metallic cable sheaths to eliminate induced sheath currents. Stop joints are designed to withstand dielectric fluid pressure between the two sides of the joint in order to hydraulically isolate adjacent cable sections. In this case, the joints are fitted with hydraulic connections to nearby fluid pressurization reservoirs. The installation of SCLF cable joints requires a high level of skill by the cable jointer (Figure 3.2-13). These special skills include tape lapping and conductor joining (while maintaining a continuous flow of dielectric fluid). Lead wiping of the joint casing to the cable sheath also requires special skills. Terminations SCLF cable terminations require the installation of an impregnated paper stress cone similar to that of HPFF cables to maintain acceptable electrical stresses at the point where the cable insulation shield is terminated. The terminations typically have epoxy or porcelain stand-off insulators that isolate the base plate from the support structure. For cable systems with cross-bonded or single-point bonded sheaths, the stand-off insulators control circulating currents. During maintenance, the stand-off insulators allow the cable jacket to undergo a 10-kV dc test to ensure cable jacket integrity.
Figure 3.2-13 Jointing a self-contained liquidfilled cable.
3-10
Increased Power Flow Guidebook
Other Equipment Fluid Reservoirs SCLF cables commonly utilize fluid reservoirs on one or both ends of the circuit and sometimes at intermediate locations along the cable route. Pumping plants or pressurization plants similar to pipe-type systems are also used for very large installations. The fluid reservoirs consist of a nitrogen-pressurized bladder that expands or compresses against a sealed dielectric liquid container, allowing the dielectric liquid in the cables to expand and contract with load cycling. Reservoirs for SCLF cables are sometimes gravity fed, as shown in Figure 3.2-14. 3.2.4
Other Cable Types
There are other cable types, but most are less common for transmission applications than pipe-type, extruded dielectric, or self-contained. Mass Impregnated (MI) or Paper Insulated Lead Covered (PILC) cables are sometimes used up to 69 kV for ac systems, although they are not that common at this
Figure 3.2-14 SCLF fluid reservoirs.
Increased Power Flow Guidebook
voltage. Uprating approaches would be somewhat similar to those of extruded or self-contained cables. These cables have paper tapes that are impregnated with a high-viscosity dielectric fluid. They do not have external pressurization systems, as in the case of HPFF or SCLF cable systems. MI cables are used for ac applications but are more common for HVDC submarine applications where there may be a significant change in elevation along the cable route that would otherwise be complicated by hydrostatic head pressures. A moisture barrier on the outside of the MI cable prevents moisture ingress. Compressed Gas Insulated Transmission (CGIT) lines have many similarities to isolated phase bus or gas insulated substation (GIS) equipment. A system of SF6 gas and epoxy insulators are used to insulate a hollow, rigid aluminum conductor from a tubular aluminum enclosure. Factory-assembled elbows are required to accommodate turns in the cable route, and sections with bellows in the enclosure are required to accommodate expansion and contraction. A CGIT bus is generally not buried because the aluminum enclosure is highly susceptible to corrosion, although some manufacturers in the early 21st century are promoting an insulated enclosure for buried applications. The most common applications for CGIT lines are situations where very high ampacities are required (i.e., > 2000 A), usually to connect with overhead lines entering a station or as a high-capacity bus within a station. 3.3
POWER FLOW LIMITS AND SYSTEM CONSIDERATIONS
Generally, this section considers methods to improve the thermal capacity, and therefore the rating, of underground cable systems. However, transmission circuits may be limited by factors external to the cable circuit being considered. Specifically, system considerations may not allow a cable circuit to be fully loaded to its thermal capacity. This section describes these factors. 3.3.1
Thermal, Stability, and Surge Impedance Loading Limits
Transmission circuits, in general, may be constrained based upon one of three limits—thermal, stability, and surge impedance loading—each of which is summarized in the sections that follow. Thermal Limits All transmission cables are limited by thermal considerations. “Weak link” analysis applies to underground cable ratings where the section of cable that has the worst thermal conditions limits the overall circuit capacity. The causes of these thermal limits will be discussed in more detail in Section 3.4.5. Sections of the
Chapter 3: Underground Cables
route that result in the cable having a higher operating temperature for a given load condition will limit the overall line capacity. These limits may result from greater soil thermal resistivity, deeper burial depth, higher ambient soil temperature, or possibly mutual heating from multiple cables in the same trench or other external heat sources. Conceivably, conditions along a few meters of cable may limit the rating for several kilometers of an underground line. Cables also have much higher charging current per unit length as compared to overhead lines, and the charging current must pass through the conductor. Although the cable charging current is 90° out of phase from the current for real power transfer, it significantly reduces the amount of real power that may flow through the cable conductor for some underground lines. The cable charging current per unit length is given by Equation 3.3-1.
I Ch arg ing = 2πfCE 0 =
2πfεE 0 18 ln
DINSULATION DCONDUCTOR
× 10 −9 [Amperes] 3.3-1
Where: f is the power frequency. C is the capacitance in Farads per meter. E0 is the line-to-ground voltage. ε is the dielectric constant. The natural log term contains the insulation and conductor shield diameters. In determining the allowable real power transfer for a cable circuit, the square of the capacitive current (leads the real current by 90°) is subtracted from the square of the maximum allowable current (e.g., the normal rating or “ampacity”), as described in Equation 3.3-2. 2 2 I Re al = I Maximum − I Ch arg ing [ Amperes]
3.3-2
Cable circuits are always limited by thermal constraints, which is generally consistent with overhead lines that are less than 80 km (50 miles) in length. Although economic considerations constrain the lengths for underground cables, the maximum length ac cable circuits between shunt compensation reactors are technically limited by the charging current. The charging current increases proportionally with length and represents actual amperes that flow through the cable. Figure 3.3-1 shows the magnitude of the charging current for cable circuits with the charging from one end and from both ends of the line.
3-11
Chapter 3: Underground Cables
Increased Power Flow Guidebook
As the length of the underground line is increased, a point is reached where the total charging current equals the cable ampacity. This occurs at what is called the “critical length” of the cables, where no real power may be transferred without overloading the cable circuit. The critical length can be calculated from Equation 3.3-3.
Critical Length =
I Normal [Meters] I Ch arg ing
3.3-3
Where: INormal is equal to the normal ampacity. ICharging is equal to the charging current per meter. It is obvious that the maximum feasible line length must be significantly less than the critical length in order to transmit reasonable amounts of real power. However, the concept of critical line length quantifies the absolute maximum lengths between shunt compensation that can be achieved for different types of underground cables. Table 3.3-1 shows critical line lengths based on typical insulation thicknesses and parameters. In real situations, economic considerations, rather than the critical length considerations, limit the construction length for most land cables. However, charging current limitations have been a significant factor for long submarine cable circuits. In these cases, owners sometimes consider using HVDC cables where there are only resis-
tive losses to consider and the cost of the HVDC valves and convertor stations is more easily justified relative to the cable cost. In some other cases, shunt compensation reactors were installed on intermediate islands. Note that reactive compensation can mitigate cable charging current effects on the system to which the cables are connected, but the charging current still flows in the cables, potentially limiting the real power transfer. It is common practice to install shunt reactors at one or both ends of relatively long underground transmission lines to mitigate the effects of cable-generated charging current on the power system. The amount of shunt compensation depends upon the ability of the power system to “absorb” the reactive MVARs generated by the cables during light load conditions. The amount of leading reactive MVARs that generation units can absorb is generally less that the amount of lagging MVARs that they can generate. During normal and peak load conditions, the leading MVARs generated by the cable capacitance are typically offset by lagging power factor loads. Consequently, high-voltage load-switching devices (i.e., circuit switchers) are typically used to disconnect shunt compensation reactors during periods of relatively high load. The reactors are then connected to the power system during periods of light load. The reduction of transmission system losses is another consideration in sizing shunt compensation reactors for underground transmisTable 3.3-1 Critical Lengths for Underground Cable Circuits with Typical Insulation Thicknessesa
Voltage
Laminated Paper Polypropylene Kraft Paper
CrossLinked Polyethylene
EthylenePropyleneRubber
Critical Lengths, miles (km)
Figure 3.3-1 Charging current magnitude profile.
3-12
69 kV
63 (101)
n.a.b
163 (262)
120 (193)
115 kV
48 (77)
n.a.b
130 (209)
82 (132)
138 kV
45 (72)
n.a.b
120 (193)
70 (113)
161 kV
42 (67)
52 (84)
114 (183)
n.a.c
230 kV
30 (48)
36 (58)
81 (130)
n.a.c
345 kV-400 kV
20 (32)
29 (47)
53 (85)
n.a.c
500 kV
n.a.d
23 (37)
47 (76)
n.a.c
a. Assuming 3158 kcmil (1600 mm2) segmental copper conductor. b. Laminated paper-polypropylene is not generally used for voltages below 161 kV. c. The relatively high dielectric constant and dissipation factor for EPR insulation limit the application of these cables to 138 kV or below. d. At this voltage, with conventional Kraft paper insulation, the dielectric losses are so great that the ampacity is zero.
Increased Power Flow Guidebook
sion lines. Typically, the shunt reactors are chosen so that the lagging MVARs created by the shunt reactors are between 60% and 100% of the leading MVARs generated by the cable capacitance. In most cases, a series of load flow cases must be performed for light and heavy load conditions to determine the optimum amount and location for cable system shunt compensation. Voltage Profile and Stability Limits Some overhead lines may have voltage regulation problems (i.e., excessive voltage drop) when transmitting power to lagging power factor loads. As the line length increases, the voltage on the line tends to drop. This can cause problems in transferring power from the sending end to the receiving end of a line. The relatively high capacitance of cable circuits may have adverse effects on the voltage profile in the vicinity of underground transmission lines. Since a capacitive current flowing through an inductance causes a voltage rise across the inductor, the charging current created by the capacitance of a cable circuit can cause high system voltage by two related phenomena. The first and most common situation is for the cable charging current to cause voltage rises across the inductive impedances external to the cable circuits. This situation, which is worst during light load conditions, is illustrated in Figure 3.3-2. In this circuit, the reactances, X L and X T, represent inductive impedances of transmission lines and transformer impedances between the generator and the cable circuit. Since the voltages at the load must be held near rated voltage, the system voltages rise significantly above the rated voltage as the cable charging current flows through the inductive impedances, XL and XT, to the generation units. During light load conditions (assumed in Figure 3.3-2), this voltage rise may cause voltages above the maximum rated voltage that most power system components are designed for (105%) without shunt compensation.
Chapter 3: Underground Cables
Cable circuits are not generally associated with voltage stability problems because of their capacitive nature— they are generally shorter as compared to overhead lines, are naturally compensated, and generate voltagesupporting vars. Surge Impedance Loading (SIL) Limits Surge impedance loading (SIL) limits involve a greater than allowable phase shift in power frequency from one end of a transmission system to the other. As a result, the two ends of the system cannot remain synchronous, resulting in instability and outages. This system stability consideration is generally an issue on overhead transmission lines that are 80-320 km (50-200 miles) in length. The positive sequence surge impedance, ZS, of a transmission line is defined by Equation 3.3-4
ZS =
L C
Ohms 3.3-4
where, L and C are the positive sequence series inductance and shunt capacitance, respectively. Cables have lower series inductances and much higher shunt capacitances compared to overhead lines. Consequentially, cables have very low surge impedance relative to overhead lines. Typical surge impedances for overhead and underground lines are 375 ohms and 30 ohms, respectively. The SIL limit, based on the line-to-line voltage (VLL), is defined by Equation 3.3-5
SIL Limit =
V LL ZS
2
MVA 3.3-5
SIL power transfer limits are rarely a problem for underground transmission lines because of their low surge impedance and relatively short lengths.
Figure 3.3-2 Voltage rise due to cable charging current.
3-13
Chapter 3: Underground Cables
3.3.2
Increased Power Flow Guidebook
Load Flow Considerations
Low cable system series impedances, and the resulting unequal distribution of load flow between overhead and underground lines, are important considerations when evaluating the uprating potential on underground cable circuits. The reactive loading of various transmission lines in a power system is controlled by the magnitude of the voltages across the system and can be adjusted by generator excitation and transformer taps. The flow of real power over the lines is a function of the relative voltage angles around the system and the interconnecting impedances. Unfortunately, the distribution of real power flow is not as easily controlled as reactive power flow because the circuit impedances are fixed in most cases, and it is not economical to control power flows by changing angles at the generation units. Therefore, where transmission line loadings are not approximately equal to the thermal capacities of the circuits, the power transfer cannot be increased once a circuit is loaded to its thermal limit even though the other circuits may be lightly loaded. Because underground cables have much lower series impedances than overhead lines, a higher portion of power will flow over the underground lines compared to overhead lines in the same area. Figure 3.3-3 shows an extreme situation where an underground cable is connected electrically in parallel with an overhead line. The sending and receiving end phasor voltages are the same for both overhead and underground circuits. Then the power flow between the two buses along the cable and line is defined by Equations 3.3-6 and 3.3-7.
PCable =
V1V2 Sin(θ 2 − θ1 ) Z Cable
POH Line =
V1V2 Sin(θ 2 − θ 1 ) Z OH Line
Figure 3.3-3 Simplified power system network with parallel overhead and underground circuits.
3-14
3.3-6
3.3-7
Since the series impedance of cables is typically 25-30% of length compared to those for overhead lines, the power flow along the cable circuit is greater, perhaps exceeding the ampacity of the cable circuit or resulting in underutilization of the overhead line. While the above example is extreme, cables may be put in parallel with overhead lines indirectly in a conventional power system. Is some cases, relatively expensive phase shifting transformer must be placed in series with underground cables to more evenly distribute power flows with overhead lines in the same area. 3.3.3
Uprating Hybrid (Underground and Overhead) Circuits
Hybrid transmission circuits contain sections of both overhead lines and underground cables. The reasons for these types of installations are numerous (rights-of-way congestion, available ROW, water crossings, tunnels, airports, etc.), but the issues with uprating these types of circuits are complicated by considering all of the equipment along the circuit. Overhead lines are typically operating at only 30-40% of their rated capacity, and in hybrid circuits usually have a normal rating that is 4060% greater than the connected underground sections. As a result, the cable section is usually studied first from the standpoint of increasing a circuit’s capacity since the circuit will be limited by the section with the lowest rating – often the cable. From the standpoint of typical design limits, an overhead line usually can obtain 1 ampere of capacity for each kcmil (2 amperes per square millimeter), while a cable will generally have half that capacity. Also, overhead lines do not suffer from mutual heating effects among phases or circuits, but this is a significant consideration where cables are installed in the same trench. Therefore, additional overhead conductors added to increase capacity cannot be equally matched by the same number of underground conductors, since the buried cables will experience a net de-rating from mutual heating. While overhead lines typically have greater ampacity for normal operating conditions, the large thermal time constant of buried transmission cables – typically 50150 hours – compared with overhead lines (5-15 minutes) means that for short-duration emergencies, cables typically have a higher emergency rating. Also, because of the relatively short time constant of overhead lines, the load cycle on the overhead line does not have a significant impact on the normal or emergency capacity. However, with buried cables, the long thermal time constant has a big impact on ratings. This is factored into daily ratings by considering a 24-hour loss factor (essen-
Increased Power Flow Guidebook
Chapter 3: Underground Cables
tially, the daily load factor of the losses). This is discussed in greater detail in Section 3.4. 3.4
UNDERGROUND CABLE RATINGS
3.4.1
Introduction
This section provides a brief overview of the ampacity procedures used to determine cable ratings. While there are subtle differences in constructions among the various cable types, this section focuses on the most common constructions to provide the reader with enough background to understand how the uprating approaches discussed in later sections can be applied. Many ampacity calculations are based on a 1957 paper by Neher and McGrath (Neher and McGrath 1957). Later work by CIGRÉ documented an ampacity procedure into an international standard (International Electrotechnical Commission 1982, 1987) that provides a step-wise approach to calculating ampacity based upon cable construction. The two calculation approaches give similar results, although their treatment of daily load cycles is different. The paper by Neher and McGrath assumes a sinusoidal load shape and uses a 24-hour (daily) loss factor to account for an overall “averaging” effect of heat output from the cable beyond a certain diameter (called DX). Within this diameter, the temperature rise across the thermal resistances in the cable and nearby soil is proportional to the peak heat output from the cable. At distances greater than this diameter away from the cable center, the temperature rise is proportional to the average daily heat output. Many system planners are familiar with a “load factor,” which relates the peak load to the average daily load. In cable systems, the focus is on heat output—a function of I 2 R—so the term daily “loss factor” is used, which is essentially the load factor of the losses as defined by Equation 3.4-1.
Loss Factor =
i =1
2 i
2 24 ⋅ I max
3.4-1
The loss factor can be estimated from the load factor using an empirical relationship. One such relationship is as shown in Equation 3.4-2.
Loss Factor = 0.3(Load Factor ) + 0.7(Load Factor )
The approach described in this section is focused on the use of the IEC method—generally recognized as providing better accuracy for ac losses and being easier to follow—but accounts for cyclic loading by using the “loss factor” approach from the paper by Neher and McGrath. Chapter 3 does not specifically address emergency ratings, except conceptually in later sections. For the typical user of this chapter, both normal and emergency rating calculations can be handled by a computer program such as UTWorkstation and DTCR that are available from EPRI, as well as other commercial sources. For additional background on emergency rating calculations, the reader should review relevant references listed at the end of this chapter. 3.4.2
Concept of Ampacity
An underground cable circuit rating, or “ampacity,” is the solution to a basic heat transfer problem. Heat generated in the cable is removed by thermal conduction to ambient earth and, ultimately, air. Engineers familiar with Ohm’s Law know that electrical current flowing through an resistance will produce a voltage drop (or rise) according to Equation 3.4-3.
ΔVoltage = Current ⋅ R AC
24
∑I
Distribution cables sometimes follow a similar relationship, Loss Factor = 0.2 (Load Factor) + 0.8 (Load Factor)2 , but it is important to note that these load factor-to-loss factor relationships are specific to a given system and should not necessarily be applied arbitrarily. The IEC method in its basic form assumes that the load remains constant (e.g., a loss factor of 100%), but ratings by this method can be modified by a companion document, IEC-60853 (International Electrotechnical Commission 1989), to account for the daily load variations, particularly when the load is not closely sinusoidal. The IEC approach to account for load variations does not easily lend itself to hand calculations and generally gives close agreement to the “Neher and McGrath” method under typical loading patterns.
3.4-3
An analogous relationship may be used to describe thermal conduction where heat flowing through a thermal resistance produces a temperature drop (or rise) according to Equation 3.4-4.
ΔTemperature = Heat ⋅ RThermal
3.4-4
2
3.4-2
This basic concept is extended to model heat out of a buried cable through the various cable layers, trench backfill and native earth.
3-15
Chapter 3: Underground Cables
3.4.3
Increased Power Flow Guidebook
Losses
Electrical Losses
Losses (heat) from a cable are the source of temperature rise above ambient earth. Heat is generated from both dielectric heating and ac resistance heating, as described in the following sections. Dielectric Heating Dielectric heating comes from charging and discharging the insulating dielectric at 50 or 60 times per second. The dielectric heat loss, WDielectric, can be found from Equation 3.4-5.
W Dielectric = 2πfCV
2 l−g
=
2πfεVl 2− g tan δ ⋅10 −9 ⎛D 18 ln⎜⎜ insulation ⎝ DConductor
⎞ ⎟ ⎟ ⎠
DC Resistance Electrical losses are generated from current flowing through the resistance of the phase conductors, concentric metallic shields, sheaths or skid wires, and the pipes (depending on cable system type). The resistance is a function of the cross-sectional area of the material and is defined by Equation 3.4-6.
R dc 20 =
ρ Area ⋅10 − 6
[Ohms/meter] 3.4-6
Where: ρ = electrical resistivity of metal in ohm-m at 20°C. Area = cross-sectional area of metal in mm2.
[W/meter]
3.4-5
Where: C = Capacitance, Farads/meter. f = power frequency, Hz. ε = specific inductive capacitance (dielectric constant). tan δ = insulation dissipation factor. Vl-g = line to ground voltage applied across the insulation, volts. Some typical insulation parameters are listed in Table 3.4-1.
The dc resistance of the conductor is usually increased by 2.5% or so to account for the lay of the wires in the stranded conductor. The dc resistance can be adjusted to other temperatures, usually the rated conductor temperature, using Equation 3.4-7.
R dcT = R dc 20 ⋅
T −τ [Ohms/meter] 20 − τ
3.4-7
Where: τ = inferred temperature of zero resistance. T = temperature of the conductor.
Charging Current Dielectric losses are generated on a per-meter basis and affect the radial heat escaping from the cable, ultimately affecting normal ampacity. Charging current—energy used to charge and discharge the insulation at power frequency—is consumed when the cable is energized and ultimately limits the allowable real power transfer (see Section 3.3.1).
Some typical values of electrical resistivity are listed in Table 3.4-2, along with their temperature correction coefficients.
Table 3.4-1 Typical Cable Insulation Material Parametersa
Table 3.4-2 Electrical Resistivities and Temperature Factors for Common Cable Metals
Dielectric Constant
Dissipation Factor
Insulation Material
Range
Typical
Range
Typical
Impregnated Paper
3.3-3.7
3.5
0.0020.0025
0.0023
2.7-2.9
2.7
0.00070.0008
0.0007
Cross-linked Polyethylene 2.1-2.3
2.3
0.00010.0003
0.0001
Laminated PaperPolypropylene
Ethylene-PropyleneRubber
2.5-4.0
3.0
0.002-0.08 0.0035
a. Values from 1992 EPRI Underground Transmission Systems Reference Book.
3-16
AC Skin and Proximity Effects Losses in the conductor are affected by self and mutual inductance; the self inductance causes the current to concentrate near the conductor surface – called “conductor skin effect” – and the magnetic field of neighbor-
Material
Electrical Resistivity Inferred Temperature Ohm-meters of Zero Resistance, °C
Aluminum
2.8264 x 10-8
Brass
6.317 x 10-8
-912.0°C
Bronze
3.5 x 10-8
-564.0°C
Copper
1.7241 x 10-8
-234.5°C
Lead
21.4 x 10-8
-236.0°C
Stainless Steel
70 x 10-8
n.a.a
Zinc
6.633 x 10-8
-218.7°C
-228.1°C
a. There is almost no variation in the resistance of stainless steel with respect to temperature over the typical operating range of a cable.
Increased Power Flow Guidebook
Chapter 3: Underground Cables
ing conductors affects the distribution of current across the conductor – called “conductor proximity effect.” When the total losses from the cable conductor are being calculated, these two parameters must be determined. The impact of these effects on the dc resistance – called the “ac-dc ratio” – is a function of the conductor type and construction. Values of the conductor skin effect correction factor, ks, and proximity effect correction factor, kp (also known as the transverse conductivity factor) are listed in Table 3.4-3. The ac resistance increment for conductor skin effect, YCS, can be found from Equation 3.4-8, where kS is the skin effect factor based on the conductor construction.
3.4-8
The ac resistance increment for conductor proximity effect, YCP, can be found from Equation 3.4-9, where kP is the proximity effect factor based on the conductor construction.
YCP
8πfk P ⋅ 10 −7 RdcT
⎛ X P2 =⎜ ⎜ 192 + 0.8 ⋅ X 2 P ⎝
⎞ ⎛ DConductor ⎟⋅⎜ ⎟ ⎜ d phase ⎠ ⎝
⎛ ⎜ ⎜ ⎛D ⋅ ⎜ 0.312 ⋅ ⎜ Conductor ⎜ d phase ⎜ ⎝ ⎜ ⎜ ⎝
⎞ ⎟ ⎟ ⎠
2
⎞ ⎟ ⎟ ⎠
R acc = R dcT ⋅ (1 + YCS + YCP ) for cables in air or soil 3.4-10
R acc = R dcT ⋅ (1 + 1.5 ⋅ (YCS + YCP )) for cables in a steel pipe
3.4-11
Shield, Sheath and Skidwire Resistance Depending on the cable type, there are various metallic layers outside of the cable insulation. A summary of typical layers is as follows: Pipe-Type:helically applied metallic tape(s), helically applied skid wire(s).
X S2 8πfk S ⋅ 10 −7 YCS = XS = RdcT 192 + 0.8 ⋅ X S2
XP =
The conductor resistance including skin and proximity effects can be calculated using Equations 3.4-10 and 3.4-11.
2
⎞ ⎟ ⎟ 1.18 ⎟ + 2 ⎟ ⎛ DConductor ⎞ ⎜ ⎟ + 0.27 ⎟ ⎜ d phase ⎟ ⎟ ⎝ ⎠ ⎠ 3.4-9
Table 3.4-3 Skin and Proximity Effect Factors for Various Conductor Types Conductor Type
ks
kp
Concentric round, dry
1.0
1.0
Concentric round, in oil
1.0
0.8
Compact round, in oil
1.0
0.6
Compact segmental, dry
0.435
0.6
Compact segmental, in oil
0.435
0.37
Compact segmental, in oil
0.39
0.35 (trefoil), 0.46 (cradled)
Compact segmental (aluminum), in oil
0.35
0.29 (trefoil), 0.36 (cradled)
Hollow core, 6 segment, in oil
0.39
0.33
Hollow core, 6 segment (aluminum), in oil
0.26
0.19 (trefoil), 0.27 (cradled)
Hollow core, 4 segment, in oil
0.435
0.37
SCFF:
extruded lead, corrugated copper, or corrugated aluminum sheath, possibly with additional copper wires or tapes.
Extruded: concentric stranded copper or aluminum wires, copper or aluminum tapes, extruded lead, corrugated copper, corrugated aluminum or corrugated stainless steel. Regardless of the cable type, the resistance of the metallic layers outside of each cable phase must be evaluated. These resistance values are then be adjusted for the temperature of the respective layer. Three basic equations may be used. For a helical metallic layer (e.g., a helically applied tape or skid wire), Equation 3.4-12 can be used.
R dc 20 =
ρ Area ⋅10 − 6
⎛ π ⋅ D Layer ⋅ 1+ ⎜ ⎜ Lay Layer ⎝
2
⎞ ⎟ [Ohms/meter] ⎟ ⎠ 3.4-12
Where: ρ = electrical resistivity of layer in Ohmmeters. DLayer = average diameter of the helical layer. LayLayer = distance along the cable for one turn of the tape or wire (e.g., the “lay”). Area = cross-sectional area of the tape, wire or skid wire. For an extruded or welded metallic layer (e.g., the sheath on an extruded or self-contained cable), the area of the layer can be calculated by knowing the difference
3-17
Chapter 3: Underground Cables
Increased Power Flow Guidebook
in diameters above and below the layer, as shown in Equation 3.4-13. Area = R dc 20 =
2 2 ) π (DOuter − D Inner
ρ
4
Area ⋅10
−6
[mm 2 ]
[Ohms/meter] 3.4-13
For a stranded shield, the area of a single strand must be calculated and then multiplied by the number, N, of wire strands. The resistance can then be calculated as above by dividing the area into the electrical resistivity of the material (see Equation 3.4-14). 2 N ⋅ π ⋅ D strand Area = [mm 2 ] 4
Calculation of the circulating current increment requires determining the mutual reactance between adjacent cable phases and depends on the configuration of the phases. Equations 3.4-16, 3.4-17, and 3.4-18 should be applied appropriately, depending on the cable configuration that most closely matches the indicated cable positions. S, the center-to-center phase spacing, and, DS, the average diameter of the shield/sheath/skidwire layer are used in the equations. −7
3-18
3.4-17
3.4-18
The incremental increase in resistance from circulating currents can then be found using Equation 3.4-19. YSC =
RS ⋅ Racc
1 ⎛R ⎞ 1+ ⎜ S ⎟ ⎝ Xm ⎠
2
3.4-19
Shield Loss Increments for Eddy Currents Eddy current losses occur when a continuous concentric metallic layer exists around the cable core (e.g., a corrugated or extruded metal sheath or longitudinally taped metallic shield, but not to stranded shields). Also, eddy currents are negligible for pipe-type cables.
3.4-15
Shield Loss Increments for Circulating Currents Circulating currents exist when a cable metallic shield, sheath, neutral or skidwire is grounded at both ends (e.g., multi-point bonding – see Section 3.6.8). The phase currents induce a circulating current in these layers depending on the geometry and resistance of the layer that opposed the phase current according to Lenz’s Law. Circulating currents exist in pipe-type cables because the skidwire and metallic shield are continuously grounded to the cable pipe. Circulating currents also exist in single-core cables (e.g., extruded dielectric or self-contained cable types) when the metallic sheath is grounded at both ends or on cross-bonded systems where the minor section lengths are not equal in length.
⎛ 2⋅ S ⎞ Xm = 4π f ⋅10 ⋅ ln⎜ ⎟ [Ohms/meter] ⎝ Ds ⎠ for cables in equilateral (triangular) configuration
⎛ 2.52 ⋅ S ⎞ X m = 4π f ⋅10 −7 ⋅ ln ⎜ ⎟ [Ohms/meter] ⎝ Ds ⎠ for cables in flat/vertical configuration
3.4-14
Once the resistances for all of the shield layers are determined, they should be taken electrically in parallel to find the overall resistance, as shown in Equation 3.4-15.
1 1 1 1 = + + .... + RS Rs1 Rs 2 Rsn
⎛ 2.3 ⋅ S ⎞ X m = 4π f ⋅10 −7 ⋅ ln ⎜ ⎟ [Ohms/meter] ⎝ Ds ⎠ for cables in cradled configuration
The mechanics for calculating the eddy current losses is somewhat onerous but not particularly complicated. The equations to perform these calculations were derived empirically and are listed in Equations 3.4-20 through 3.4-24. For a more detailed explanation, see IEC-287 (International Electrotechnical Commission 1982). m=
2π f ⋅10 −7 RS '
3.4-20
⎛ m2 YSe 0 = 6 ⋅ ⎜ ⎜ 1 + m2 ⎝
⎞ ⎛ DS ⎞2 ⎟⎟ ⋅ ⎜ ⎟ ⎠ ⎝ 2 ⋅S ⎠ 1.4⋅m + 0.7
YSe1
⎛D ⎞ = 0.86 ⋅ m ⋅ ⎜ S ⎟ ⎝ 2 ⋅S ⎠ for flat formation 3.08
⎛ m2 YSe 0 = 3 ⋅ ⎜ 2 ⎜ ⎝ 1+ m
⎞ ⎛ DS ⎞ ⎟⎟ ⋅ ⎜ ⎟ ⎠ ⎝ 2 ⋅S ⎠
(
)
⎛D ⎞ YSe1 = 1.14 ⋅ m2.45 + 0.33 ⋅ ⎜ S ⎟ ⎝ 2⋅S ⎠ for trefoil formation
β1 =
0.92⋅m +1.66
3.4-22
8π 2 f
ρShield ⋅107 1.74
3.4-16
3.4-21 2
⎛t ⎞ gs = 1 + ⎜ Shield ⎟ ⎝ DS ⎠
(
⋅ β1 ⋅ DS ⋅10 −3 − 1.6
) 3.4-23
Increased Power Flow Guidebook
YEC
⎛ R =⎜ S ⎝ Racc
Chapter 3: Underground Cables
⎞ ⎛ ( β1 ⋅ tShield )4 ⎜ g Y Y 1 ⋅ ⋅ ⋅ + + ( ) ⎟ s Se 0 Se1 12 ⋅1012 ⎠ ⎝⎜
⎞ ⎟ ⎟ ⎠
3.4-24
where R S’ is the resistance of only the layer(s) where eddy currents may occur and tShield is the thickness of the shield layer. AC Resistance Including Circulating Current and Eddy Current Increments The conductor resistance including skin, proximity, circulating current, and eddy current effects can be calculated using Equations 3.4-25 and 3.4-26.
Racs = RdcT ⋅ (1 +YCS +YCP +YSC +YEC ) for cables in air or soil
3.4-25
Racs = RdcT ⋅ (1 + 1.5 ⋅ (YCS +YCP +YSC +YEC ) ) for cables in a steel pipe
3.4-26
Pipe Loss Increments for Pipe-Type Cables Pipe cables have additional losses from eddy current and hysteresis heating in the cable pipe as a result of the ac cables within the pipe. The increment losses associated with the pipe can be calculated using Equations 3.4-27 and 3.4-28.
YP =
3.4.4
Equivalent Thermal Circuit and Thermal Resistances
As was discussed in Section 3.4.2, thermal conduction is the principal means by which heat leaves a buried cable system. The thermal equivalent to Ohm’s Law is applied to this model by developing an “equivalent thermal circuit” that describes the various layers of cable materials and surrounding earth which heat must pass through to reach ambient. Thermal circuits for extruded/self-contained and pipe-type cables are shown in Figures 3.4-1 and 3.4-2. The thermal resistances and heat sources are shown, analogous to electrical resistances and current sources in a conventional Ohm’s Law circuit. The temperature of the conductor, Tc, is determined by adding up the temperature rises above the ambient earth tem-
0.0438 ⋅ DSkidwire + 0.0226 ⋅ IDPipe RdcT ⋅106
for cables in cradled configuration YP =
Other Losses Additional losses may be experienced in some cable installations. Single-core submarine cables may have steel or other armor wires that can have both circulating current and hysteresis (for iron-based armor) losses. Also, utilities use steel casings for road crossing or directionally drilled installations that can have significant hysteresis and eddy current losses. Neutral continuity conductors may generate heat if the phase currents are imbalanced, but this is most often an issue on distribution systems.
3.4-27
0.115 ⋅ DSkidwire − 0.01485 ⋅ IDPipe RdcT ⋅106
for cables in trefoil configuration
3.4-28
Note that the pipe loss increment is greater for cables in cradled configuration, so cradled configuration should generally be assumed unless the cables are known to lay in close trefoil configuration.
Figure 3.4-1 Equivalent thermal circuit for extruded dielectric and self-contained fluid-filled cable types.
Equations 3.4-27 and 3.4-28 are for 60 Hz. If the power system is 50 Hz, the values of YP should be multiplied by 0.76. Ac resistance including skin, proximity, circulating current, eddy current, and pipe loss effects is determined using Equation 3.4-29. Racp = RdcT ⋅ (1 + 1.5 ⋅ (YCS +YCP +YSC +YEC ) +YP ) 3.4-29
Figure 3.4-2 Equivalent thermal circuit for pipe-type cables.
3-19
Chapter 3: Underground Cables
Increased Power Flow Guidebook
perature, Tearth, as heat passes through the various thermal resistances. The thermal capacitances shown in the figures account for the fact that changing load (e.g., heat output) from the cable does not instantaneously result in a change in temperature. This is consistent with the Ohm’s Law analogy, where a change in applied voltage does not instantly change the voltage across an electrical capacitor. Temperature Rise To calculate the ampacity, the conductor temperature is determined for a given current and checked against the maximum allowable conductor temperature based on the insulation material. For the above thermal circuits, the temperature rise above ambient is found using Equation 3.4-30, where the ac losses (I2R) and dielectric heat losses (Wd) pass through the various thermal resistances to give a temperature rise:
(
)
Tmax = I 2 Rac + Wd × Rthermal + Tambient ΔT = Tmax − ΔTd − Tambient = I 2 Rac × Rthermal
ΔT
Rac ⋅ Rthermal
3.4-31
For layers where the inner and outer diameters are concentric (e.g., cable insulation, cable jackets or pipe coatings, or the thermal resistance of a conduit), the thermal resistances may be found using the Equation 3.4-32
3.4-33
Where: Tmean = mean temperature of the duct air, or nitrogen gas or dielectric liquid in the pipe. Dcable = outer diameter of the cable. n = number of cables within the conduit or pipe. U, V, and Y as defined in Table 3.4-5. Earth Thermal Resistances The cable thermal resistances describe components of the thermal circuit out to the interface with the surrounding soil. For direct buried cables, this is the pipe coating (on pipe-type cables) or the jacket on singleconductor cables. Single core cables installed in conduits have an earth interface at the outside of the conduit. At that point, the earth portion of the thermal circuit starts.
Three thermal resistances must be considered in the earth portion of the thermal circuit:
• Thermal resistance to heat escaping from the cable or pipe itself Table 3.4-4 Thermal Resistivities of Common Cable Materials Range (C°-m/Watt)
Typical (C°-m/Watt)
Impregnated Paper
5.0-6.0
6.0
Laminated Paper-Polypropylene
5.0-6.0
6.0
Crosslinked Polyethylene
3.5-4.0
3.5
Ethylene-Propylene-Rubber
4.5-5.0
4.5
Somastic
1.0
1.0
Transite
2.0
2.0
PVC
4.0-4.5
4.0
Neoprene
3.8-5.8
4.0
Epoxy
0.7-4.45
1.0
Thermoplastic Pipe Coating
3.5-4.5
4.0
Table 3.4-5 Pipe and Duct Thermal Resistance Constants 3.4-32
where n is the number of cables within the diameter, DInner.
3-20
n ⋅U [C ° − m /Watt ] 1 + 0.1(V +Y ⋅ Tmean ) ⋅ Dcable
Material
Cable Thermal Resistances The thermal resistances for each cable layer out to the earth interface – where the cable contacts the soil – must be determined to complete the thermal circuit. The thermal resistivities of common cable materials are listed in Table 3.4-4.
⎛D ⎞ ρ R= ⋅ n ⋅ ln ⎜ Outer ⎟ [C°-m/Watt] 2π ⎝ DInner ⎠
R=
3.4-30
Typical ampacity calculations assume that the voltage remains constant, so dielectric losses are fixed. Then, the only unknown in Equation 3.4-30 is the current as shown in Equation 3.4-31 (as a convention, thermal quantities are shown with an over-line to distinguish these values from electrical quantities):
I=
The thermal resistance between a cable and the inside of a conduit or pipe can be determined using Equations 3.4-33.
Configuration
U
V
Y
Fiber Duct or PVC in Concrete
5.2
0.91
0.010
Asbestos Cement in Concrete
5.2
1.1
0.011
Pipe-Type, HPGF
0.95
0.46
0.0021
Pipe-Type, HPFF
0.26
0.0
0.0026
Earthenware Ducts
1.87
0.28
0.0036
Increased Power Flow Guidebook
Chapter 3: Underground Cables
• Thermal resistance resulting from mutual heating among other cables or pipes
• Thermal resistance correction to account for native soil materials outside of the trench having a higher thermal resistivity than backfill materials The equations in this section describe each of these. The basis for these calculations is application of superposition of the heat fields generated by each buried cable and the assumption that the earth’s surface may be treated as an isotherm. These assumptions are substantiated by the Kennelly Hypothesis, and the reader is encouraged to review relevant references (Anders 1997) for more details. The thermal resistivity of the soil is an important parameter, which will be discussed in detail later. Table 3.4-6 summarizes some typical values of soils and backfills. Earth Thermal Resistance The earth thermal resistance is mainly a function of cable burial depth. For installations where the cable is installed in a special backfill, the thermal resistivity of the special backfill—directly in contact with the cable— should be used for the earth thermal resistance calculation. The fact that the native soil outside of the trench may have a greater thermal resistivity will be corrected, as shown in Equation 3.4-34.
Rearth
⎛ ⎛ Dx ⎞ ⎜ ln ⎜ ⎟ + LF ⎜ ⎝ Dearth ⎠ ρ = ⋅n⋅⎜ 2 2π ⎜ ⎛ 2 ⋅ L + 4 ⋅ L2 − Dearth ⎜ ⋅ ln ⎜ Dx ⎜ ⎜ ⎝ ⎝
⎞ ⎟ ⎟ ⎟ [C°-m/Watt] ⎞⎟ ⎟⎟ ⎟⎟ ⎠⎠ 3.4-34
Where:
L
= centerline burial depth of the center of the cable, pipe or conduit, mm. Dearth = diameter of the earth interface (cable OD, pipe OD, or conduit OD), mm. ρ = the thermal resistivity of the soil in contact with the cable, C°-m/Watt. n = number of cables within diameter, Dearth. LF = the 24-hour loss factor for the load on the cables, per-unit. Dx = diameter where average daily heat output applies, as defined below. Diameter, D x , is the diameter beyond which 24-hour average ac heat losses apply and is a function of the soil thermal diffusivity. An empirical relationship for finding the soil thermal diffusivity, α soil , as a function of the native soil thermal resistivity, ρ native , is as shown in Equation 3.4-35.
α soil =
(ρ
6.71× 10 4 native
⋅100
)
0.8
[mm 2 /hour] 3.4-35
From this, the diameter, D x, may be found (typically about 210 mm or 8.3 in.), using Equation 3.4-36. Dx = 1.02 α soil ⋅ 24 [mm]
3.4-36
Mutual Heating Thermal Resistance When multiple cables are installed in the ground, heat generated by each cable impacts the temperature of the other cables. For the purposes of this section, all cables are treated as though they are carrying equal loading such that the heat output from each cable is the same. With the assumption that the earth’s surface is an isotherm, a “method of images” is used to model the heat leaving each cable and its mutual heating effects on the other cables. Figure 3.4-3 shows examples for a two-pipe
Table 3.4-6 Typical Soil Thermal Resistivity Values Thermal Resistivity Soil Type
5% Moisture (C°-m/Watt)
0% Moisture (C°-m/Watt)
Fluidized Thermal Backfill
0.4
0.75
Concrete
0.6
0.8
Stone Screenings
0.4
1.0
Thermal Sand
0.5
1.0
Uniform Sand
0.7
2.0
Clay
1.0
2.5
Lake Bottom
1.0 (50% moisture)
>3.0
Highly Organic Soil
>3.0
>6.0
Figure 3.4-3 Illustration of mutual heating effects.
3-21
Chapter 3: Underground Cables
Increased Power Flow Guidebook
cable circuit (left) and for a single extruded dielectric or self-contained cable circuit (right). The mutual heating effect is evaluated knowing the distance from a given cable to the image of an adjacent cable divided by the actual distance separating the cables, as shown in Equation 3.4-37. ⎛d' ⎞ ⎛d' ⎞ ⎛d' ⎞ F = ⎜ 12 ⎟ ⋅ ⎜ 13 ⎟ ... ⎜ 1N ⎟ ⎝ d12 ⎠ ⎝ d13 ⎠ ⎝ d1N ⎠
3.4-37
with N being the number of conduits, cable pipes, or cable positions with energized cables. It is important to evaluate the mutual heating effect for the cable that will run at the highest temperature to ensure that none of the cables exceeds the maximum allowable temperature.
Then, if the center-line depth, Lb, of the backfill envelope is known, a geometric factor for the backfill can be calculated, as shown in Equation 3.4-40.
⎛ 2 ⋅ L + 4 ⋅ L 2 − D2 b b b Gb = ln ⎜ ⎜ Db ⎝
⎞ ⎟ ⎟ ⎠
3.4-40
The thermal resistance correction for native soil with different thermal resistivity, ρnative, than the backfill thermal resistivity, ρbackfill, can be calculated using the above geometric correction factor as shown in Equation 3.4-41. Rcorrection =
ρ native − ρbackfill 2π
⋅ n ⋅ N ⋅ LF ⋅ Gb [C ° − m /Watt ] 3.4-41
Then, the thermal resistance from mutual heating can be evaluated using Equation 3.4-38. Rmutual =
ρ n ⋅ LF ⋅ ln ( F ) [C ° − m /Watt ] 2π
3.4-38
where n is the number of energized cables at each location. For a pipe-type cable, n equals three. For direct buried cables or conduit installations of transmission cables, n generally equals one. If the cables are installed in special backfill, the thermal resistivity used to calculate the mutual heating thermal resistance should be that of the backfill. Thermal Resistance Correction for Native Soil Up to this point, the thermal resistances of the earth and mutual heating have used a value of the backfill thermal resistivity. However, in actual installations, the thermal resistivity of the soil outside of the trench is typically greater, and this must be factored into the ampacity calculations. To make this correction, an additional thermal resistance term is needed. The approach considers the length and width of the backfill envelope, as shown in Figure 3.4-4.
where n is the number of cables per pipe, conduit or location, and N is the number of pipes, conduits or locations within the backfill envelope. The procedure described above is valid as long as the ratio of the long dimension of special backfill to the short dimension of the special backfill is 3 or less. A paper by El-Kady and Horrocks (1995) describes geometry factors that may be used for special backfill envelopes with dimensions outside the acceptable range of the method used above. Temperature Rise from Dielectric Heating The ac and thermal resistances complete the equivalent thermal circuit so that ampacity can be calculated. However, it is also important to consider the temperature rise caused by dielectric heating. Losses are generated throughout the insulating dielectric, but for the purposes of ampacity calculations, the dielectric losses, Wd, are assumed to enter the thermal circuit half way through the insulation. This can be seen by referring back to the thermal circuit figures.
If the short, x, and long, y, dimensions of the backfill envelope are known, it is possible to determine a circumscribing circle having a diameter, Db, with the same volume of backfill material as the rectangular backfill envelope, as shown in Equation 3.4-39.
⎡⎛ 1 ⎞ ⎛ x ⎞⎛ 4 x ⎞ ⎛ y2 Db = exp ⎢⎜ ⎟ ⎜ ⎟⎜ − ⎟ ln ⎜ 1 + 2 ⎜ ⎣⎢⎝ 2 ⎠ ⎝ y ⎠⎝ π y ⎠ ⎝ x
⎤ ⎞ ⎟⎟ + ln ( x ) ⎥ ⎠ ⎦⎥ 3.4-39
3-22
Figure 3.4-4 Trench backfill width and height.
Increased Power Flow Guidebook
Chapter 3: Underground Cables
The thermal resistances used for dielectric temperature rise are calculated in the same manner as for ac losses, except that the loss factor is 100% (1.0 per unit) since the voltage is constant. Therefore, it is necessary to consider the thermal resistance values used for dielectric temperature separately from those used for ac losses, which are a function of the daily load variation.
resistances” are C°/ampere 2 ) is determined using the thermal circuit parameters, as shown in Equations 3.445 through 3.4-47. For extruded and self-contained cables in conduit:
(
ΣRAC ⋅ Rth = Racc Rinsulation
⎛ R jacket + R jacket −duct + Rduct ⎞ ⎟ +Racs ⎜ ⎜ +R ⎟ + + R R mutual correction ⎠ ⎝ earth 3.4-45
The temperature rise caused by dielectric heating can be determined as shown in Equations 3.4-42 through 3.4-44. For extruded and self-contained cables in conduit:
⎛ Rinsulation + R jacket ⎞ ⎜ ⎟ ⎟ ΔTd = Wd ⎜ + R jacket − duct + Rduct ⎜ ⎟ ⎜ + Rearth + Rmutual + Rcorrection ⎟ ⎝ ⎠
Table 3.4-7 Example Ambient Soil Temperatures at Typical Installation Depthsa
1 2
3.4-42
For direct buried extruded and self-contained cables:
⎛ Rinsulation + R jacket ⎞ ⎟ ΔTd = Wd ⎜ ⎜ +R ⎟ R R + + mutual correction ⎠ ⎝ earth 1 2
3.4-43
For pipe-type cables:
⎛ Rinsulation + R cable − pipe ⎞ ⎟ ΔTd = W d ⎜ ⎜+ R ⎟ pipe coating + R earth + R mutual + R correction ⎠ ⎝ 1 2
3.4-44
Ambient Soil Temperature “Ambient” soil temperature is the temperature at the burial depth of the cable in the absence of any nonnative heat sources. These temperatures are usually established during a route thermal survey (described in Section 3.6.1). Some typical values of ambient soil temperature are listed in Table 3.4-7. 3.4.5
)
Calculating Ampacity
Once the thermal circuit is complete and the dielectric temperature rise is known, it is possible to determine the allowable conductor temperature rise for ac loading (ampacity). The temperature at the conductor is highest, and the temperature of the insulation nearest the conductor limits the ampacity. Some industry-accepted maximum allowable conductor temperatures are listed in Table 3.4-8. The “summation of electrical and thermal resistances” (units of the “summation of electrical and thermal
Location
Maximum Summer
Maximum Winter
Atlanta
25°C
20°C
Boston
22°C
18°C
Chicago
22°C
18°C
Denver
22°C
17°C
Honolulu
30°C
15°C
Johannesburg
22°C
15°C
London
18°C
8°C
Miami
30°C
25°C
New York
25°C
18°C
Palo Alto
22°C
20°C
Singapore
30°C
25°C
a. E.g., 1.1 m (42 in.). Table 3.4-8 Industry-Accepted Maximum Conductor Temperatures
Insulation Material
Maximum Normal (Continuous) Temperature
Maximum Emergency Temperature
Impregnated Paper
85°C
105°C peak at end: up to 100 hours 100°C peak at end: 100-300 hours
Laminated Paper Polypropylene
85°C
105°C peak at end: up to 100 hours 100°C peak at end: 100-300 hours
Cross-Linked Polyethylene
90°C
105-130°Ca, 72 hours continuousb 105°C- peak at end of 100-300 hours
Ethylene Propylene Rubber
90°C
130°C
Linear Low Density Polyethylene
75°C
90°C
a. Depends on shield construction and agreement from manufacturer. b. Based on Association of Edison Illuminating Companies CS-7 standard.
3-23
Chapter 3: Underground Cables
Increased Power Flow Guidebook
For direct buried extruded and self-contained cables:
( (R
ΣRAC ⋅ Rth = Racc Rinsulation +Racs
jacket
)
+ Rearth + Rmutual + Rcorrection 3.4-46
For pipe-type cables:
( (R (R
ΣR AC ⋅ Rth = R acc Rinsulation + R acs
+ R acp
)
cable − pipe
)
pipe coating
+ R earth + R mutual + R correction
)
3.4-47
Then, the ampacity may be calculated, as shown in Equation 3.4-48. I=
Tmax imum − ΔTd − Tambient ΣR AC ⋅ Rth
[amperes] 3.4-48
Appendices 3.1 and 3.2 have worked examples for calculating ampacity of pipe-type and extruded dielectric cables. 3.4.6
Effect of Various Parameters on Ampacity
This section briefly highlights the effects of various cable and installation parameters on ampacity. The range of variation shown is not applicable to all installed cable systems, but the trend is generally consistent for all cable installations. Effect of Burial Depth As the burial depth increases, the thermal resistance to heat leaving the cable and reaching the earth’s surface also increases (see Equation 3.4-34). As a result, the ampacity declines with increasing burial depth. This is illustrated in Figure 3.4-5.
Figure 3.4-5 Graph of ampacity versus burial depth.
3-24
)
Barring other factors, it is generally better to have a more shallow burial depth to minimize the earth thermal resistance. However, ambient soil temperatures are generally greater near the surface (potentially reducing ampacity) and soils tend to be drier above the water table (potentially reducing soil moisture content and increasing thermal resistivity). So, although a shallow burial depth reduces thermal resistance, other installation factors must be considered when evaluating ampacity and placement of cables. Effect of Phase and Circuit Spacing Mutual heating among cable circuits and cable phases cause elevated temperatures that reduce the available temperature rise for ac current. As a result, increased phase and circuit spacing reduce mutual heating and tend to increase ampacity. Some considerations for the mutual heating might be the placement of cable phases within a duct bank. For example, if a 3x3 duct bank is being used, the outer duct positions should be filled first before the center ducts to minimize mutual heating. Figure 3.4-6 shows the effect of circuit spacing on ampacity.
A similar trend would apply to phase spacing except in the case of multi-point bonded cables. For multi-point bonded cables, metallic shield/sheath circulating currents are generally higher when the phase spacing is large, particularly for sheath constructions designed for high fault currents. For this reason, multi-point bonded cables (mostly at distribution voltages) are placed in a single conduit or in close-trefoil (triangular) configuration. Effect of Native Soil and Backfill Thermal Resistivity Except for conductor size, most of the cable construction is fixed based upon the voltage class of the cable. The native soil outside the cable trench is also fixed (and represents a large part of the total thermal resistance as seen in the examples at the back of this guide) but must be factored into the ampacity calculations. Higher soil thermal resistivity results in a higher thermal resistance to heat leaving the cable and lower ampacity.
Figure 3.4-6 Graph of ampacity versus circuit spacing.
Increased Power Flow Guidebook
Soils may also have great variability in soil conditions over a few meters of cable route, contrary to overhead lines where weather conditions may apply for a few kilometers. Therefore, it is important to find the worst conditions along the cable route – “weakest link” – and base ratings on that limiting location. From the standpoint of installations, the installer has control over the material put back into the trench. Figure 3.4-7 shows the effect of special backfill placed in the cable trench as a function of various native soil conditions. Using a good quality thermal backfill (thermal sand, Fluidized Thermal Backfill – FTB) can improve the allowable current carrying capacity. Section 3.6.1 describes soil testing and backfill materials. Effect of Ambient Soil Temperature Like native soil thermal resistivity, there is little control over the ambient soil temperature, but it must be factored into the cable ratings. One consideration about the ambient temperature is the burial depth. Greater temperature extremes are experienced close to the surface, so summer ambient temperatures will be more significant at shallow depths. Also, surface coverings have an impact on ratings. Soil ambient temperatures may be 35°C warmer below asphalt than other areas because of the increased solar absorptivity of the surface. Figure 3.4-8 shows the impact of ambient temperature on ampacity.
Chapter 3: Underground Cables
3.4.7
Emergency Ratings
Emergency ratings reflect a temporary increase in circuit capacity during a contingency. For cables, the emergency ratings take advantage of a higher allowable conductor temperature for a period of time (usually not longer than 300 hours) and the heat storage capacity – long thermal time constant – of the cable and soil around the cables. This is somewhat different from overhead transmission lines where the thermal time constant is measured in minutes. With buried transmission cables, the thermal time constant is 35 to 150 hours. Figure 3.4-10 shows an
Figure 3.4-8 Graph of ampacity versus ambient soil temperature.
Effect of Conductor Size and Sheath Bonding Conductor size directly impacts the allowable current carrying capacity of a circuit. Larger conductor sizes allow for more current. Also, the circulating currents from multi-point bonded cable sheaths cause significant losses (heat) that reduce ampacity by 20% or more (depending on factors like sheath construction and resistance and the phase spacing). Figure 3.4-9 shows the impact of these parameters on ampacity. Figure 3.4-9 Graph of ampacity versus conductor size as a function of sheath bonding mode.
Figure 3.4-7 Graph of ampacity versus native and special backfill thermal resistivity.
Figure 3.4-10 Graph of emergency ampacity versus emergency duration.
3-25
Chapter 3: Underground Cables
Increased Power Flow Guidebook
example of emergency ampacity versus duration for a 230-kV XLPE cable. The normal ampacity at 100% load factor is also shown on the graph.
including effects of moisture migration, etc.) over the in situ measurements or soil samples collected some distance away from the cables.
The calculation of emergency ratings is described in a paper by Neher (1963) and IEC-853 (International Electrotechnical Commission 1989). The reader is encouraged to review these documents or obtain suitable software such as EPRI’s ACE (Alternative Cable Evaluation) or DTCR (Dynamic Thermal Circuit Rating) to perform these calculations.
By using the equivalent thermal circuit to calculate the temperature at a location where measurements are made, the effective soil thermal resistivity can be adjusted until the calculated values match the measured values. The effective soil thermal resistivity, combined with historical load data—usually 2-4 weeks—can be used to find the temperature of a conductor in the trench. A more elegant approach is to use the dynamic rating model described in Section 3.8 of this chapter.
From the standpoint of uprating, the techniques described in this chapter apply to both normal and emergency ratings. 3.4.8
Inferring Conductor Temperatures from Measured Temperatures
Some cable installations have temperature monitoring using thermocouples or distributed fiber optic temperature sensing (DFOTS) (both described in Section 3.6.4). The temperature measurements are commonly available in one or more locations:
• Under the cable jacket (for DFOTS) • Outside of the cable jacket or cable pipe (for thermocouples) when direct buried
• Duct air temperature (either DFOTS or thermocouples)
• Parallel conduit or cable pipe (either DFOTS or thermocouples) The conductor temperature of a neighboring cable can be inferred by comparing the measured and calculated temperatures at one of the above locations until they agree, usually while varying the inferred native soil thermal resistivity. During in situ or laboratory soil thermal resistivity measurements using a thermal property analyzer (described in Section 3.6.2), a constant heat is injected into the soil (or soil sample) using a thermal probe. A sensitive thermistor is used to monitor changes in temperature over time while the heat is being injected into the soil. The slope of the change in temperature with respect to time shows the soil thermal resistivity. For a buried cable circuit, it is possible to infer the soil thermal resistivity using measured cable temperatures – essentially making the cable a thermal probe. Although the loading (heat input) is not constant, a reasonable assessment of the soil thermal resistivity can be determined and is often a better indication of the effective soil thermal resistivity “seen” by the power cable (e.g.,
3-26
3.5
UPRATING AND UPGRADING CONSTRAINTS
Underground cable systems have unique characteristics that must be considered when exploring uprating options. This section describes the characteristics of each cable system and installation conditions that may limit uprating options and that should be considered before exploring any of the uprating methods described later. 3.5.1
Direct Buried Cable Systems
Direct buried cable systems have several limitations for uprating and upgrading mainly due to the fact that the cable is relatively inaccessible, there is generally no opportunity to provide active cooling, and the civil works cost would eliminate most practical reconductoring options. A hot spot along the cable route that is identified and of relatively short length might be mitigated. Spot temperature monitoring might also be considered, but retrofitting continuous monitoring is just as impractical as reconductoring. Soil remediation using a lower thermal resistivity soil or, for very short distances, applying heat pipes, could mitigate a hot spot that is limiting a circuit. If overburden has developed above the cables and this is determined to be the cause of a hot spot, the overburden could be removed to reduce the cable burial depth and thereby improve ampacity. 3.5.2
Fluid-Filled Cable Systems
The pipe in a pipe-type cable system offers the greatest flexibility for uprating and upgrading an underground cable system of any cable type. While the pumping or pressurization plant generally requires greater maintenance than the other cable types, particularly extruded, the ability to circulate the dielectric liquid (for HPGF, fill the pipe with dielectric liquid and then circulate) allows for both thermal smoothing of a hot spot or forced cooling.
Increased Power Flow Guidebook
The pipe size may be a limiting factor because it can constrain the voltage upgrading (requiring thicker insulation wall), or ampere upgrading (requiring a larger conductor) may be limited. Note that mitigating a hot spot on a pipe-type or selfcontained fluid-filled cable system, allowing a greater overall ampacity, may mean that other sections of the circuit will be operating at a higher temperature. This would generally result in greater fluid expulsion in pipe type and, in particular, SCFF cables, which may require that the pressurization plant be recalibrated, that the fluid reservoir tanks be resized, or the nitrogen blanket pressure above the oil adjusted to accommodate the larger volume of dielectric liquid. Alarm settings might also need to be adjusted. 3.5.3
Duct Bank Installations
Duct bank installations do not offer significant options for uprating. The concrete encasement that is common to duct banks generally has good thermal resistivity. The impact of overburden on the circuit might be investigated and, in extreme cases, the native soil around a section of duct bank might be replaced with lower thermal resistivity material. Often a problem associated with duct banks is the relatively high congestion of cable circuits in those locations. Sometimes expensive transmission cables are significantly derated by a low-cost and relatively very low power transfer distribution cable. One possible remediation method could be to remove the distribution circuits entirely, or replace the distribution cables with a larger conductor or multiple cables per phase to reduce the heat output and mutual heating effects. Duct bank installations allow for upgrading options in that existing cables may be removed and new ones installed relatively easily. If a particular section of a cable route is found to limit overall ampacity and a section of cable with a larger conductor is available, that particular section could be replaced to mitigate the hot spot. Ducts may also be filled with water or grouted with a low-thermal resistivity grout to improve thermal conduction between the cable surface and conduit. 3.5.4
Trenchless Installations
Trenchless installations – horizontal directional drilling (HDD), pipe jacking, or microtunneling – have some of the limitations of the direct buried system such as being essentially inaccessible. However, trenchless installations typically use inner ducts – some with spare pipes or conduits – that may be used to mitigate hot spots and improve ampacity. The inner ducts allow a cable phase
Chapter 3: Underground Cables
to be removed and replaced, possibly with a larger conductor size. To improve ampacity, the casing in a trenchless installation may be filled with water or a lowthermal resistivity grout to improve heat transfer away from the cables and conduits. Filling the annular space between the inner ducts and the casing will allow heat to pass through a low thermal resistivity grout (0.8 C°m/Watt) or water (1.6 C°-m/Watt) rather than air (45 C°-m/Watt). 3.5.5
Other Installation Locations
Tunnels Tunnel installations offer some unique considerations from the standpoint of uprating. First, the cables are generally more accessible than for buried cable systems, so this more easily facilitates maintenance and repairs. However, tunnel installations do not benefit as much from the long thermal time constant of direct buried, pipe, or conduit installations because the cables are essentially installed in air. Some tunnel installations may be limited by the maximum allowable air temperature from the standpoint of work safety or heating/ventilation/air conditioning (HVAC) limits. Depending on the tunnel configuration, it may be difficult to add forced air ventilation to the tunnel to improve capacity. Also, extruded or self-contained cables that are racked in troughs or by mechanical supports could be subjected to damage from thermal-mechanical bending (TMB) effects during increased temperature operation. “Deep” Installations Including Water Crossings Somewhat like trenchless installations described above, “plowing in” cables or cable pipes in water crossings makes installation of a specialized thermal backfill impractical. Also, mitigating a hot spot at one of these locations is not easily accomplished because there is little control over the sedimentation that can build above the cables. The best approach is to properly account for the soil conditions – both thermal resistivity and ambient temperatures – in developing ratings. Overhead (In Air) Installations Cables installed in air, for example on bridges or risers, do not benefit from the long earth thermal time constant of buried cable systems. In most cases, the in-air normal ampacity is greater than the buried normal ampacity.
However, the cables may be exposed to high ambient air temperatures and possibly solar radiation and also lack the long earth thermal time constant of buried cables, possibly limiting the emergency rating capacity of in-air sections. Mitigating ampacity limits for in-air sections may be difficult, particularly if solar radiation is an issue since shielding the cables from solar heating can be impractical. 3-27
Chapter 3: Underground Cables
3.5.6
Hot Spot Identification
Hot spot identification is sometimes difficult to do because of restrictions on accessing the cables. Distributed temperature sensing (DTS) fiber—the state-of-theart for cable temperature monitoring—is often difficult to retrofit. More traditional approaches to finding hot spots involve studying plan and profile drawings and evaluating the impact of other known heat-producing services in the area around cables. If DTS can be applied, the hot spots can be readily identified, although the causes may not always be obvious. 3.5.7
Accessories
Joints For the most part, joints do not normally limit a cable circuit’s ampacity, particularly when the joints are installed in manholes that often run cooler than the direct buried soil sections. However, directly-buried joints on pipe-type cables may limit ampacity because of the added layers of hand-applied paper tape insulation that are used to construct the joint, adding additional thermal resistance to heat leaving the joint. Forcedcooled pipe-type cables may result in a thermal limit at joints. The forced-cooling fluid circulation essentially makes the surface of the cable an isotherm. With the added insulation applied over the joint resulting in increased thermal resistance, the connector may be running hotter, limiting the rating. Terminations In general, terminations are not the limiting factor for uprating cable systems except on forced-cooled pipetype cables or in areas with a very high ambient air temperature. In forced-cooled pipe systems, the dielectric liquid circulation cannot cool the termination, so the terminations rather than the cable sections become a limiting factor. EPRI report EL-2233 on high-capacity terminations gives additional details about this subject (EPRI 1982). 3.5.8
Hydraulic Circuit
In pipe-type cables, the hydraulic circuit may limit uprating opportunities under some circumstances. For example, if there is no return pipe or there is only one pipe circuit, it would not be possible to circulate dielectric liquid within the pipe. Some utilities are reluctant to use fluid circulation where the hydraulic circuit involves moving liquid down one energized cable pipe and back another, mainly because if a failure occurred, the “healthy” circuit could be contaminated from byproducts of the fault. Although there will be less mutual heating with the parallel circuit out of service,
3-28
Increased Power Flow Guidebook
the rating on the healthy circuit will probably drop because fluid circulation cannot continue. A small amount of fluid movement might be achieved by oscillating the dielectric liquid within the pipe using the 7500–11,000 liter (2000–3000 gallon) fluid reservoir tanks on either end of the circuit if at least 3,750 liters (1000 gallons) of additional dielectric fluid can be accommodated in the existing reservoirs on each end. The extent of pipe filling—degree to which the cables fill the free area of the pipe—may also limit dielectric liquid circulation rates because the pressure drop between pumping plants may be too great even when using a low viscosity dielectric liquid. 3.6
INCREASING THE AMPACITY OF UNDERGROUND CABLES
Once there is an understanding of the possible limitations associated with each cable type, it is necessary to consider how uprating might occur on a given circuit. This section describes various techniques that may be applied to investigate ampacity limitations and then ways to improve ampacity, or at least have a better understanding of what is limiting the ampacity. 3.6.1
Route Thermal Survey
A route thermal survey has traditionally involved evaluating the entire cable route in a detailed manner to understand ampacity limitations. Many North American utilities adhere to Association of Edison Illuminating (AEIC) standards regarding cable design. One of the principles of these standards is that if the soil characteristics are not well known, the design ampacity should be based upon a maximum operating temperature that is 10°C below the allowable operating temperature (e.g., values in Table 3.4-8). Regardless of following the AEIC standards or not, utilities have sometimes designed cable circuits without a good knowledge of the route characteristics, particularly on older circuits. In these cases, the ambient soil temperature and soil thermal resistivity were not well known, so assumed values were often incorporated into rating calculations. Those following the AEIC guidelines obtained some additional conservatism in the ratings by using the lower 10°C operating temperature in the event that the assumed parameters were inaccurate. However, as the circuits age and load growth continues, many utilities are revisiting the rating assumptions to see if additional transmission capacity is available without major investment in infrastructure. Also, during the process of uprating a cable circuit, hot spot mitigation may require removing existing trench
Increased Power Flow Guidebook
backfill materials and replacing it with a good quality thermal backfill. The following subsections discuss some of the techniques employed for a route thermal survey and describe soil and backfill characteristics that are important to consider in evaluating methods for uprating cable systems. Thermal Property Analysis In the equivalent thermal circuit, the earth thermal resistances are the largest component, typically representing over 50% of the total thermal resistance. They are also the least understood. As compared with overhead lines, where weather parameters (wind speed and direction, solar radiation, temperature) may be valid for 1-2 km of line length, soil characteristics along underground cable routes can vary over a few meters. If the cables are buried in city streets, there exists a strong possibility of encountering “borrowed fill” instead of native soils. These “fills” may satisfy civil/construction requirements, but if topsoil, cinders, or organic soils are used, the thermal performance may be very poor. For this reason, it is very important to test the soils so that appropriate values of thermal resistivity may be used in design calculations.
Chapter 3: Underground Cables
Essentially, an underground cable is a long distributed heat source. The “transient thermal needle” method takes advantage of this characteristic by using a “thermal probe,” which contains a heating coil throughout its length and a thermistor type temperature sensor at the mid-point of the heater. The length-to-diameter ratio of the probe is high enough so that end effects do not impact the measurements. An example thermal probe is shown in Figure 3.6-1. Once the probe is installed in the soil sample or in the native soil (field), the heater in the thermal probe is energized with a constant power while the change in temperature is recorded over time (usually 20–30 min). The slope of the log time-temperature curve is proportional to the thermal resistivity of the soil sample. A thermal property analyzer (TPA) was developed to automate this process and is commonly used for both field and laboratory measurements (Figure 3.6-2). The transient thermal probe method (e.g., IEEE Standard 442) is a relatively quick and accurate approach to measuring soil thermal properties, provided the theoretical assumptions are understood and care is taken in the test setup to stay within the limits of the theory. The test assumes various conditions:
Thermal property analysis based on transient heat flow was first suggested as early as 1888 (Wiedman 1888). During the mid-1900s, significant research and other work were conducted in North America (Mason and Kurtz 1952; Blackwell 1954; Carslaw and Jaeger 1959). This demonstrated the practical use of a thermal needle “line heat source” method. The Insulated Conductors Committee, organized in 1947, performed a special project on soil thermal resistivity in 1951. A special subcommittee (No. 14) headed by Professor H. F. Winterkorn of Princeton University continued work in this field for 10 years and published the AIEE Committee Report in 1960. In the 1970s, EPRI-sponsored research resulted in the design and development of the Thermal Property Analyzer. The basic approach was to develop a portable, fully automated test instrument with standardized testing procedure that could be employed for both field and laboratory with results that could be extended to power cable systems. Thermal Resistivity Thermal resistivity, sometimes call “rho,” is a property of a material. In the contents of cable installation and field measurements, the thermal resistivity is measured for a soil or trench backfill. The most common approach to thermal resistivity measurements now is the “transient thermal needle” method, which is based on the “line heat source theory.”
Figure 3.6-1 Thermal probe used for field thermal resistivity measurements. 3-29
Chapter 3: Underground Cables
Increased Power Flow Guidebook
for detailed laboratory analysis and to evaluate parameters such as dry-out curves (thermal resistivity as a function of moisture content under constant dry density; see Figure 3.6-3) or thermal stability that cannot be done effectively in the field. The samples are collected in thinwall Shelby tubes. If the soil is very loose or noncohesive (granular), a split spoon sampler or large diameter California sampler with liners is used to collect undisturbed samples. If soil conditions (granular, very hard or rocky) are such that undisturbed tube samples cannot be collected, either disturbed bulk samples or auger cuttings are taken. If bedrock is encountered, core samples of 5– 8 cm (2–3 in.) diameter are collected to be tested in the laboratory. Standard ASTM procedures should be implemented for soil boring, sampling, storage, and transportation.
Figure 3.6-2 Thermal Property Analyzer (TPA) used for field and laboratory thermal resistivity measurements.
• The probe is an instantaneous and constant heat source (no thermal capacitance).
• • • • •
Heat flow is radial.
Borehole logs, which characterize the soil types with depth, are often made so that if the cable burial depth varies, the type of native material – and its thermal resistivity – can be known for rating purposes. A typical bore hole log is shown in Figure 3.6-4. The borehole log information may also be used for other geotechnical purposes such as designing structural loads, laying out directional drilling route, etc. This geotechnical information is very useful for the civil contractor to determine the type of equipment required for excavation,
Conduction is the only mechanism of heat transfer. No contact resistance exists at the soil/probe interface. An infinite sample boundary exists. The test sample is homogeneous and at moisture and thermal equilibrium.
• No moisture migration occurs during the test. For these assumptions to be valid, it is important that the probe insertion and testing be performed carefully, usually by a qualified specialist, to ensure that the results are valid. Contact resistance is very important and a critical part of inserting the probe into the soil. Also, it is important to keep the probe temperature at reasonable values to avoid drying the soil. A drill rig with a hollow stem auger is used to drill down to the required depth for soil sampling and to perform in situ thermal resistivity measurement tests. Sometimes a backhoe or hand digging down to the required depth is also used to access the soil where testing will be done. In the case where the hole is advanced using a drill rig, the thermal probe is attached to an extension rod and then tapped into the native soil at the required depth. The testing is then performed from the surface (see Figure 3.6-1). In addition to field measurements, called in situ measurements, soil samples are collected during soil boring 3-30
Figure 3.6-3 Example thermal dry-out curves for various soil types with pores between soil grain particles saturated with water (A), and dry (B).
Increased Power Flow Guidebook
Chapter 3: Underground Cables
Figure 3.6-4 Example borehole log.
3-31
Chapter 3: Underground Cables
Increased Power Flow Guidebook
dewatering, backfilling, and other activities. The ambient temperature recorded at the start of an in situ thermal resistivity test is an important value to record for the cable designer. In the laboratory, a soil sample is prepared to evaluate thermal dry-out characteristic– the variation in thermal resistivity of the material as a function of moisture content. The results of these tests (dry-out curves) are presented on charts that show thermal resistivities at the in situ moisture content (if known), at “critical moisture content,” and in totally dry condition (worst case). Some degree of drying beyond the native moisture levels should be expected in the presence of energized power cables, so an adjusted soil thermal resistivity that factors in the drying should be incorporated into ampacity calculations. Once the soil thermal resistivity results are known, they can be used in ampacity calculations. For the case of installed cable systems, it may be necessary to do testing outside the cable trench to get native conditions, and within the cable backfill to characterize the special thermal backfill that may have been used around the cables. If the trench is known to have a common material throughout, testing of the backfill material may only be needed at a few selected locations. Thermal Diffusivity Although thermal diffusivity is not commonly recorded (typical transient needle TPA equipment can measure this parameter) for most applications, its application is in “transient” calculations. In simple terms it can be treated as the “inertia” in the heat and mass transfer equation. The three terms—resistivity (ρ), diffusivity (α) and heat capacity (C)—are related by Equation 3.6-1.
ρ ⋅ α ⋅C = 1
3.6-1
Thermal Stability Thermal stability is a system-driven parameter and is a soil characteristic that describes how well a soil maintains a constant thermal resistivity when exposed to cable heating. The main issue is to consider if the heat leaving a cable would result in the soil being below its critical moisture content, in which case the soil would experience net drying and an increase in thermal resistivity. Smaller diameter cables with direct contact to the soil are more likely to result in thermal instability because of a larger heat flux (temperature gradient) at the cable-soil interface.
A classic example of a thermally instable material is modeling clay. The clay can be dried at room temperature over time. If the dried sample is then placed in water, it does not readily reabsorb water to return to a
3-32
malleable substance. Some soils—including soils with high clay and silt contents—have these characteristics. A common situation where this may be an issue for power cables is the use of bentonite as a grout material either in trenchless casing installations or for cable conduits; pure bentonite has high thermal resistance and is prone to drying. Bentonite is prone to shrinkage and cracking (leaving voids) if drying does occur. A better solution is to use as much sand as possible while minimizing the bentonite content, and to seal the ends of the casing or ducts so that the grout cannot dry. Moisture Migration in the Soil For any given soil or backfill, the major influence on the thermal resistivity is the moisture content. In a dry state, the pore spaces between soil particles are filled with air (thermal resistivity of about 45°C-m/W). As water (thermal resistivity of about 1.65°C-m/W) replaces air, the soil resistivity decreases substantially by as much as 3 to 7 times, as the good heat conduction paths are expanded (additional thermal “thermal bridges”). This is illustrated by the “thermal dry-out curve” (thermal resistivity vs. soil moisture content) shown in Figure 3.6-3. A soil that is better able to retain its moisture, as well as being able to efficiently re-wet when dried, will have better thermal performance characteristics. The soil water content is expressed as a percentage of the weight of water to the dry weight of soil solids, as determined by oven drying at 105°C.
The heat generated by energized cable tends to cause soil moisture to migrate away from the cable/backfill interface. In unstable backfills or soils, this drying increases the resistivity substantially, inducing further heating of the cable and thus more drying of the soil. Eventually this cycle may create a totally dry zone of the backfill around the cable, resulting in excessive heating and potential thermal runaway. In a stable backfill, the heatinduced drying raises the resistivity marginally, thus minimizing the potential for thermal runaway. Thermal stability is best illustrated by means of thermal dry-out curves (Figure 3.6-3). The “critical moisture” is defined as the moisture content below which the relatively flat nature of the thermal dry-out curve gives way to a disproportionate increase in the thermal resistivity. Above the critical moisture a soil will resist thermal drying (by means of capillary suction), whereas below this value, thermal runaway is inevitable (unless soil moisture is externally replenished, (i.e., rain). Although some native soils at high moisture content (10–25%) may exhibit fairly low thermal resistivity (0.4 to 0.6 °C-m/W), this value may increase a few fold when dry. Well-graded sands and stone-dust containing 10–
Increased Power Flow Guidebook
Chapter 3: Underground Cables
15% fines (-200 Sieve size material) make good corrective thermal backfills.
thermal resistivity, heat transfer takes place by radiation instead of conduction that is much less efficient.
Cable Route Soil Test Spacing The soil testing and sampling frequency for thermal resistivity testing along the cable route can vary depending on the area and the length of the route. In rural areas, where the use of fills is minimal and historical construction has not been significant, sampling and insitu testing every 500 m might be done. In urban areas or locations where fill materials have been used, sampling might be done every 200–500 m. Known variations in geology or other conditions might affect how often along the route testing and sampling are done. The goal of testing is to capture test results for any unique soils and potential hot spots along the cable route while categorizing where each soil type is found.
Soil Texture and Dry Density The soil texture is also critically important to thermal resistivity. The grain size distribution and grain shape are evaluated by a sieve analysis (e.g., ASTM D422, etc.) to determine the variation in particles both in backfill materials and native soils. Figure 3.6-5 shows a sieve analysis for four materials and a band of “good” granular thermal backfill.
Factors Affecting Soil Thermal Resistivity
Soil Composition The soil composition is an important characteristic affecting soil thermal resistivity. Soils are typically a conglomerate of various materials, and the ratio of these materials within a soil affects the thermal resistivity. Table 3.6-1 summarizes the dry thermal resistivity values of various components.
Because the soil components are so important in affecting the thermal resistivity, a good understanding of the geology along a cable circuit is valuable to assessing where soil testing should be performed and how much variation might be expected along a given cable route. It is important to note from Table 3.6-1 and Figure 3.6-3 that dry soils have a much higher thermal resistance than moist soils because the thermal resistivity of water (1.65 C°-m/Watt) is much lower than that of air (~45 C°-m/Watt). In addition to the air having higher
Table 3.6-1 Thermal Resistivities of Soil Components Component
Dry Thermal Resistivity C°-m/Watt
Quartz
0.12
Granite
0.30
Limestone
0.40
Sandstone
0.50
Shale (sound)
0.60
Shale (highly friable)
2.00
Mica
1.70
Ice
0.45
Water
1.65
Organics (peat, etc.)
~5.00
Petroleum Oil
~8.00
Air
~45.00
Water Content and Ground Water Level As is seen in Figure 3.6-3, soils with higher moisture content generally speaking have better thermal resistivity. Some soils naturally retain water better than others. Certain soils may not retain water well—e.g., they have a high hydraulic porosity—but are below the water table so they remain saturated even though the dry density is low and dry thermal resistivity would otherwise be high. Dry Density The dry density of a soil determines its ideal ability to conduct heat away from the cables. Factors that influence the dry density are porosity, solids content, interparticle contacts and pore size distribution. Having a well-graded material with a range of particle sizes improves the dry density and minimizes pores and voids in the material. Other Subsurface Characteristics Concerns for solutes and hysterisis apply only in areas where significant fluctuation in the water table may “wash out” fines from the backfill, making it thermally poor. For most applications, this is not a concern for cable system uprating and, in any case, would be found during soil thermal resistivity testing. Surface Characteristics and Vegetation Surface conditions have an impact on soil thermal resistivity. For example, soils below asphalt roadways generally will not gain or loose moisture readily under normal conditions. However, in the presence of cables, the drying that does occur may not be mitigated by heavy rains since the water will not be easily reabsorbed.
Surface vegetation can be significant factor affecting soil thermal resistivity. The root systems on large trees and plants will draw moisture out of the soil, drying it. Also, the decaying components of plants and their root systems will tend to increase the organic component of soils, which tends to increase the soil thermal resistivity (see Table 3.6-1). Surface cover has strong influence over earth ambient temperatures, especially at shallower depths. A difference of 4–5°C has been measured between grasses versus asphalt cover over cables. 3-33
Chapter 3: Underground Cables
Increased Power Flow Guidebook
Engineered Thermal Backfills The general goal of engineered thermal backfills (ETB) is to enhance the removal of heat away from buried cables. In most cases, the native soil materials have a higher thermal resistivity than good quality backfills and, in any case, are difficult to reconstitute in the trench with the same density as the native soil. For this reason, special backfill materials are often designed for use in a cable trench. These include well-graded sands, stone screenings, and concrete or Fluidized Thermal Backfill. In addition to having excellent thermal properties, they are engineered to meet civil requirements (strength and ease of voids-free installation) that are associated with the particular application. The criteria considered for these ETB are:
• Low thermal resistivity over the expected range of operating conditions
• Low critical moisture content and high thermal stability limits
• No adverse affects on materials used for cable conduits, cable jackets, or pipe coatings
• Easy to install • Inexpensive and locally available to the location where the materials will be used Types of engineered thermal backfills are discussed in the following sections. Granular Backfill Materials These materials should be composed of hard, wellgraded, natural or crushed mineral aggregate (limestone, granite, quartz or other similar rock). The material should be sound (porosity less than 2%) and be free of any organic material (peat, root matter, topsoil, vegetation) and foreign matter (wood, rubble, cinders). The sieve analysis should match closely to that given in 3.6-5. The maximum particle size should be no larger than 1/4in. sieve size with a fines content (material finer than #200 sieve size) of 12% to 18%.
During supply and installation of this material, quality assurance is very important. Sieve analysis on the delivered materials should be performed periodically to check and verify its compliance with the above characteristics.
Figure 3.6-5 Grain size distribution for soil samples.
3-34
Increased Power Flow Guidebook
Fluidized Thermal Backfill (FTB) One of the difficulties with any granular backfill is that it must be installed properly, regardless of its ideal thermal properties. Granular backfills should be installed in shallow lifts 15 cm (6 in.) at a time and well compacted to give good density. This is labor intensive, and great care must be used when working close to directly-buried cables or conduits so as not to damage either.
Leading up to and during installation, FTB delivered to the project site should conform to the respective mix design and performance specifications of low-strength and/or high-strength FTB. This should be checked with samples collected during the project. When installed by pouring into the cable trench, the material should be free flowing and without any segregation. This will help ensure that the material completely surrounds the cables, conduits, or pipes. The amount of water in the FTB mix may be adjusted to increase or decrease the flow (slump) as directed by the field engineer. If lower slump FTB is required for a particular area, it is generally better to adjust the water content at the batch plant rather than as the material goes into the trench. Air content (natural trapped) should not be higher than 2%. Mixing at the batch plant and transportation to the project site should be done in accordance with ASTM or American Concrete Institute (ACI) specifications.
Chapter 3: Underground Cables
If trench shoring and sheathing is being used, these should be removed immediately after the installation of FTB, unless otherwise required by the field engineer. If FTB is installed in cold conditions, care should be taken to protect the installed FTB from freezing. This applies to both low-strength and especially high-strength FTB. ASTM or ACI specifications should be followed for such installations. Sampling and testing for quality control/assurance should be performed on FTB samples taken every 250 ft along the cable trench, or every 100 cubic yards of material installed, or as directed by the field engineer. Component materials from an FTB mix design are shown in Figure 3.6-6. Grouts for Cable Conduits and Trenchless Casings For extruded or self-contained cables in ducts or the space between inner-ducts and trenchless (directional drilling, pipe jacking, etc.) casings, the air space between the cable and conduit or conduit and casing is often filled with air, which is a poor thermal conductor. Filling the duct with a thermally conductive material improves the cable ampacity by 5–10%, depending on the configuration and the type of filler. The annular space is generally small, and utilities usually want to retain the ability to remove the cables from the conduits later in the event of a failure or for upgrading. Therefore, it is not practical to fill the annular space with a solid filler material (or one
Figure 3.6-6 Component materials used in a typical Fluidized Thermal Backfill.
3-35
Chapter 3: Underground Cables
Increased Power Flow Guidebook
that becomes solid over time), so a pumpable material that will not hard set is ideal.
locations of other underground utilities that may impact cable ratings.
IEC-60287 allows that cables with grouted conduits may be treated as direct-buried cables for the purposes of ampacity. Various materials that have been considered for conduit grouts are:
The plan drawings will show a variety of factors that may be relevant to determining the cable ampacity and possible locations where uprating could be considered:
• • • • •
Bentonite and sand/bentonite slurry Sand-cement grout Flyash-cement grout Grease and viscous oil, along with other compounds Water
Factors that must be considered when selecting a grout are the total length that must be filled and the amount of annular space. For trenchless installations, the potential softening of a plastic duct at elevated temperatures— including potentially the heat generated as cement-based grouts cure—could soften ducts and cause partial collapse. The safe pumping pressure for the grout material must therefore be considered when a grout is pumped on the outside of air-filled cable conduits. The grout material typically will have a thermal resistivity of 0.4 to 1.4 C°-m/Watt, which is much lower than air (45 C°-m/Watt) at the set moisture content. A sandbentonite slurry backfill with a thermal resistivity of approximately 0.7 C°-m/Watt is easy to formulate and generally easy to install. Varying the amount of sand, bentonite and water affects the pumpability of the grout. Bentonite tends to absorb a lot of water, so this must be factored into the mix. Mixing the sand/bentonite slurry also requires special equipment (i.e., colloidal mixer). The thermal resistivities of these components are as follows:
• Sand: 0.12-0.20 C°-m/Watt—optimizes the thermal resistivity but negatively affects pumpability.
• Phase and circuit or pipe spacing among the cables being studied, which would impact mutual heating effects.
• The locations of other utilities that cross the cables, especially other transmission or distribution cable circuits that could produce mutual heating effects. Also, steam lines may be present.
• Sections of the route that parallel other utilities, including power cables. Parallel cables within a certain range may produce sufficient mutual heating to cause derating. A general guideline is, if the horizontal spacing is within 25% of the depth, mutual heating may be a factor (e.g., if the cables being studied are at 4 m depth, parallel cables or other heat sources within 1 m horizontal spacing should be examined for mutual heating effects).
• Topographical profiles may show areas where overburden has accumulated above the cable route. Profile drawings mainly indicate the cable circuit’s depth of cover below grade and usually the locations of other utilities that cross the cable circuit. Areas that are important to note on the profile drawing are:
• Entry/exit to manholes since cables frequently dip to enter a manhole
• Road crossings where the cable burial depth may be increased to accommodate the required road bedding materials
• Directional drilling locations where the burial depth is significantly greater than conventionally-trenched sections
• Water: 1.65 C°-m/Watt—optimizes the flowability but negatively affects shrinkage.
• Bentonite: 3.50 C°-m/Watt—optimizes the pumpability but negatively affects thermal resistivity. These materials are combined by a soil specialist for use by the contractor or utility during installation. 3.6.2
Review Circuit Plan and Profile
A classical approach to performing uprating on underground cable circuits is to review the circuit plan and profile drawings, preferably the “as-built” versions, which may show additional details about the locations of the buried power cables, as well as better illustrate the
3-36
3.6.3
Evaluate Daily, Seasonal, or Other Periodic Load Patterns
Load shape is generally not that important for most transmission equipment, particularly overhead lines where the thermal time constant is relatively short. With underground transmission cables, the long thermal time constant—35–150 hours—can significantly impact loading patterns for both normal and emergency ratings, particularly for short-duration emergencies. In typical normal ampacity ratings on cables, daily load cycles are modeled by rating techniques through the application of a load factor or loss factor. The load fac-
Increased Power Flow Guidebook
tor relates the average daily load to the peak load, usually following a relationship similar to the following: Loss Factor, p.u. = 0.3 (Loss Factor, p.u.) + 0.7 (Loss Factor, p.u.)2 This relationship is graphed in Figure 3.6-7. As mentioned earlier, the loss factor (or load factor of the losses) considers the average daily heat output relative to the peak heat output. Consider Figure 3.6-8, which shows several load shapes that all have the same peak current but substantially different load and loss factors. All of the curves in Figure 3.6-8 have the same peak current (1000 A), but substantially different loss factors. On a daily basis, the different loads shown will release different amounts of energy into the surrounding soil. This has a significant impact on conductor sizing for a desired rating or on the available current for a given conductor size. Note that the loss factor is also the perunit power delivered on a daily basis.
Chapter 3: Underground Cables
If the cable construction and installation conditions are held constant and the loss factor is varied, the cable ratings will vary substantially. From the standpoint of uprating, increases in loss factor over time mean that the ampacity will tend to decrease. For example, on a recent uprating study for a New England utility, the loss factor in 1959 when the circuit was built was 57% but had grown to 83% in 2001. While the utility was able to increase capacity on the circuit with some extraordinary methods, the normal book rating actually decreased with respect to time because of the increasing loss factor. Load shape may also play an important role from the standpoint of emergency ratings. If the daily load cycle is such that the load during portions of the day (typically at night) is lower than at other times of the day (typically mid-afternoon), short duration emergencies can vary greatly. This is illustrated in Figure 3.6-9, where the normal ampacity (1.0 per unit), A, is determined for a peak temperature of 90°C, and two 4-hour emergency ratings are determined:
• Emergency Rating B: The peak temperature is 105°C with a rating of 2.6 per-unit (as compared to the normal rating). This emergency starts going into a lowload period, so the pre-emergency load temperature is about 73°C.
• Emergency Rating C: The peak temperature is also 105°C with a rating of only 1.3 per-unit (as compared to the normal rating). This emergency starts going into a peak load period, so the pre-emergency temperature is about 85°C. Figure 3.6-7 Ampacity as a function of loss factor.
Figure 3.6-8 Graph of load profiles showing the same peak current with different load and loss factors.
The above example illustrates that considering the load shape for emergency ratings is important. Dynamic ratings (see Section 3.8) is a main benefit for this type of analysis in optimizing—and generally increasing—the current carrying capacity of an underground cable circuit.
Figure 3.6-9 Temperature plots and ratings as a function of rating starting time.
3-37
Chapter 3: Underground Cables
3.6.4
Temperature Monitoring
Using Thermocouples Temperature measurements are an important part of verifying assumptions when calculating ampacity and studying ways to improve ratings. Ideally, one would want to measure the cable conductor temperature—the hottest location in the cable system—to be sure that insulation temperature limits are not exceeded. However, because the conductor is energized, this is typically difficult to do. Instead, it is common to measure the temperature on the outer surface of the cable either on the pipe coating of a pipe-type cable or the jacket of the other cable types. For conduit installations, temperatures might be measured in the conduits.
To perform these measurements, thermocouples are often used. Thermocouples are temperature sensors based on the principle that when two dissimilar metals are joined, a predictable voltage will be generated that relates to the difference in temperature between the measuring junction and the reference junction (connection to the measuring device). The types of metals that are used depend on the application (temperature range, location, cost, etc.). There are varieties of thermocouple types (T, F, N, J, etc.). For cable-related measurements, “Type-T” thermocouples are most often used because they have a temperature range most closely matched to typical cable operating temperatures. The Type-T thermocouple has a blue outer jacket in the United States, France and the United Kingdom (up until 1993) or dark brown outer jacket in the United Kingdom (since 1993) and Germany. Inside, the thermocouple wire consists of a copper electrode (positive, +) and a constantan electrode (negative, -). Each electrode has an insulating coating that varies in color depending on the country of origin (United States is blue on the positive and red on the negative; the United Kingdom is white on the positive and blue on the negative (pre-1993) or brown on the positive and white on the negative; France is yellow on the positive and blue on the negative; and Germany is red on the positive and brown on the negative). When connecting thermocouple wire to a meter, data logger, or other measuring device, it is important to verify that the polarity is correct. Otherwise, the schematic will essentially create three thermocouple junctions in series (rather than one), which could provide misleading results. Also, the thermocouple wire or extension grade thermocouple wire must also be run from the measurement location all the way to the test instrument. A thermocouple junction is created by joining the copper and constantan wires together as shown in Figure 3.6-10. The junction can be left bare, which minimizes thermal capacitance and increases temperature mea-
3-38
Increased Power Flow Guidebook
surement response. However, depending on the environment, the junction may need to be coated or soldered to protect the thermocouple junction from corrosion, etc. Laboratory-grade thermocouples are typically welded together. A thermocouple has an accuracy of typically less than 1 C°. A key advantage to thermocouple temperature measurement is that the wire itself and the equipment to measure thermocouple temperatures are both relatively inexpensive and minimal training is required to use the technology. Several companies including Telog Instruments, Omega, and Fluke make data loggers that cost less than US $1000 to read and possibly record thermocouple temperatures. Battery-powered recorders can log data for 6–18 months, recording temperatures every 15 minutes for an extended period. Once suspected or known cable circuit hot spots are identified, low-cost thermocouples and data loggers may be placed at these locations and checked periodically, particularly during periods of high load. By comparing measured temperatures with those predicted using load history and the equivalent thermal circuit from ampacity calculations, it is possible to evaluate the assumptions used in ampacity calculations. From an operations standpoint, monitoring the cable temperatures gives some assurance that the cables are not exceeding their allowable temperature during typical load cycles. The main disadvantage to thermocouple measurements is that they only take a temperature measurement at one location. It is, therefore, possible to miss hot spots if they are not already identified. Also, the practical lead length limit of thermocouples is about 300 m (1000 ft), and each thermocouple requires its own pair of wires to
Figure 3.6-10 Thermocouple wires (copper and constantan with U.S. color scheme – left) and completed junction (right).
Increased Power Flow Guidebook
make a measurement. Therefore, it is difficult to instrument more than a few tens of locations. Distributed Fiber Optic Temperature Sensing (DFOTS) Distributed fiber optic temperature sensing (DFOTS) uses a specialized optical time-domain reflectometer (OTDR) to measure the temperature along a multimode optical fiber. The process works by taking advantage of temperature-dependent reflections (called “backscatter” based on the Raman Effect) in the fiber. The special OTDR instrument, such as York Sensors (Sensa) DTS80 or SensorTran’s Model 5000 (see Figure 3.6-11), records the magnitude of the reflection (proportional to temperature) and the time for reflections to return after sending an incident 1080 nm laser pulse into the fiber, which, when combined with the fiber’s propagation velocity, gives the distance to the measurement location. By successively sending light pulses into the fiber, the special OTDR can scan the entire fiber and obtain a temperature trace along the fiber with a spatial resolution of approximately 1 m and a temperature accuracy of 1°C. The obvious advantage of DFOTS is that a continuous end-to-end temperature measurement is possible, allowing the ampacity study to reveal all of the hot spots along the cable route. Later, these hot spots could be instrumented with thermocouples for extended temperature measurements at key locations.
Chapter 3: Underground Cables
buried system is impractical unless there is a conduit (communications or power) within a meter or so of the energized cables in which the fiber may be installed. An example of fiber that might be installed directly buried or in a conduit is shown in Figure 3.6-12. The fiber optic cable typically consists of four to six 50 x 125 μm fibers, each with a 900 μm tight buffer (only 1 or 2 fibers are needed, but some may be damaged during installation so spares are desirable), Kevlar strength members to improve pulling strength (usually only 3000N, 675 lb), and a fire-retardant PVC jacket. Some XLPE cable manufacturers are embedding optical fibers under the jacket of the cable to facilitate temperature measurements (Figure 3.6-13). Since this is physically closer to the conductor—ultimately where we would like to know the temperature—this has some advantages. A disadvantage of DTS equipment is the cost of the electronics to measurement the fiber temperature, which may be upwards of US $60,000. Also, the equipment is
Depending on the configuration of the fiber (number of splices, etc.) and the temperature measurement mode (single or double ended), a fiber length of 5–10 km may be scanned. Equipment is also available that works with single-mode fiber and can measure up to 30 km. However, this equipment suffers from both lower spatial resolution (4–10 m) and lower accuracy (2–3°C). All fiber test loops are limited by the losses in the system, so fusion splicing is the preferred method for joining fibers. Fiber used for DTS measurements is typically installed in a parallel conduit or directly buried alongside an existing cable or pipe. Retrofitting a fiber on a direct-
Figure 3.6-11 Distributed temperature sensing equipment.
Figure 3.6-12 Optical fiber cable used for DTS measurements.
Figure 3.6-13 XLPE cable with integrated optical fiber under the jacket. 3-39
Chapter 3: Underground Cables
not well suited for operation in the field on an extended period of time, which makes “spot” measurements or extended measurements in manholes or stations difficult. Most of the equipment has an operating range of 10–35°C, which is fairly limited in particularly warm or cool climates. 3.6.5
Ampacity Audit
An “ampacity audit” involves investigating ampacity for a cable circuit by applying the various techniques described in this chapter. The basic concepts include performing a soil thermal survey to determine soil characteristics and ambient temperatures, evaluating load history, and then calculating ampacity. If AEIC guidelines are being followed on a circuit that previously had used assumed soil parameters, the 10°C increase in conductor temperature by itself generally allows a 20% increase in ampacity.
Increased Power Flow Guidebook
constructed using an alcohol-water or ammonia-water mixture in a partially filled copper tube. A partial vacuum is drawn on the tube to adjust the vapor pressure to the operating temperature range for the particular application. The heat pipe is then installed at an angle with the low point installed near the heat source (cable, steam main, etc.). Heat from the source is absorbed by the liquid alcohol-water or ammonia-water solution, causing a phase change to vapor, which rises, carrying the heat away. The gaseous vapor then condenses back to a liquid away from the hot spot and then drains back to the hot spot location. This continuous process removes heat from the location. The number and installation geometry of the heat pipes are typically designed by a specialist. An example of a heat pipe installation to mitigate the effects of crossing cable circuits is shown in Figure 3.6-14.
The ampacity audit is geared towards verifying the ampacity by whatever means are available and assessing which locations along the route limit the overall circuit ampacity. This might possibly include obtaining a DFOTS temperature trace for the route to find hot spots, or looking at route plan and profiles to find limiting installation conditions. These “hot spots” would then be investigated further to see how they might be mitigated. 3.6.6
Remediation of “Hot Spots”
Remediation of hot spots is sometimes possible if the scope of the hot spot is limited. If the hot spot is the result of overburden, or increased burial depth, it might be possible to remove some of the overburden above the cables. This reduces the thermal resistance to heat leaving the cable and may improve ampacity. Poor soil thermal resistivity can often lead to hot spots, particularly if a low quality thermal backfill was used – or not backfill at all. A hot spot may be eliminated or partially mitigated by excavating around the cables and installing a good quality thermal backfill. This will improve the heat transfer characteristics away from the cable, lowering the operating temperature for a given load condition. Heat Pipes In extreme cases, usually where one circuit experiences a hot spot from mutual heating of another circuit, the installation of heat pipes can help. The heat pipe is a passive device that takes advantage of the heat of vaporization to remove heat from a location. A heat pipe is
3-40
Figure 3.6-14 Heat pipes being installed to mitigate a hot spot where a steam main crosses a pipe-type cable.
3.6.7
Active Uprating
The following methods are mostly applicable to pipetype cables, although there are applications that could extend to extruded or self-contained cables.
Increased Power Flow Guidebook
Fluid Filling Gas-filled pipe-type cables may be uprated slightly by replacing the dry nitrogen gas with a dielectric liquid such as polybutene or alkylbenzene. Since a liquid is a more efficient heat transfer media than a gas, fluid-filling alone provides a small ampacity improvement (~23%). However, this allows for additional uprating methods to be applied. Fluid Circulation Fluid circulation is a relevant uprating technique when a short section, relative to the overall circuit length, is limiting the pipe-cable rating. By circulating the dielectric liquid within the cable pipe, the heat generated in the hot section will be transferred to other portions of the route, mitigating the hot temperatures at that location. One requirement for this to be implemented is to have a fluid return pipe or a parallel cable pipe that will permit a continuous circulation path as shown in Figure 3.6-15. Flow rates may be up to 800 liter/min (200 gpm), but slow circulation with only 20 liter/min (5 gpm) may be used for small hot spots or where the fluid viscosity limits the flow rate.
If no fluid return pipe or parallel cable pipe is present, fluid oscillation may be used. In this configuration, fluid is moved through the pipe at 4–40 liter/min (1–10 gpm) and cycled between the 4,000–11,000 liter (1000–3000 gallon) fluid reservoirs at either end of the pipe circuit. Major considerations for fluid circulation are the free area in the pipe and the viscosity of the dielectric liquid used in the pipe. As a result, the pressure rise when pumping dielectric fluid through a pipe could be too excessive for practical uses. If the flow rate is limited to a value below what is necessary to mitigate a hot spot, circulation may not be possible to mitigate a hot spot; the utility might consider changing to a lower viscosity dielectric liquid or re-examining pressure rise limitations.
Chapter 3: Underground Cables
The basic principle of fluid circulation is based on work done by CIGRÉ and discussed in Electra (CIGRÉ 1979). The approach is to evaluate sections of the fluid circulation route that have basically the same characteristics and then use boundary conditions to match the flow rate from one section to the next. Dielectric liquid (or water in parallel circulation/cooling tubes) is relatively noncompressible, although the density varies with temperature around the circulation loops. To consider this, the dielectric fluid characteristics—density and specific heat—are adjusted for each section that is being modeled. As fluid circulates through the pipes, the temperature of the fluid leaving one section is assumed to be the temperature entering the next section, satisfying the boundary conditions. To model each section, the “un-cooled” (temperature that would result absent of any cooling or circulation movement in the pipes) temperature is calculated based on circuit loading, the cable construction, and installation conditions at each section. Then, heat absorbed or removed would cause increases or decreases in the dielectric fluid temperature as it moves through the pipes. The temperature change with respect to distance is of the form shown in Equation 3.6-2. T ( x ) = TUN −COOLED − K ⋅ A ⋅ exp( P ⋅ x )
3.6-2
In the equation, x is the distance, K is a value proportional to the maximum change in temperature possible for a section of infinitively long length, A is a value relating the mutual heating affects among the pipes (either cabled or fluid return), and P is a value characterizing the rate of temperature change as air moves along the pipe section. There is one exponential term for each pipe in which fluid is circulating.
Figure 3.6-15 Example pipe cable dielectric fluid circulation loop with heat exchangers.
3-41
Chapter 3: Underground Cables
Increased Power Flow Guidebook
The “un-cooled” temperature is the steady-state temperature of the dielectric liquid inside the cable pipe that would result if the loading remained fixed on the energized cables and no fluid circulation was in place. As the flow rate is reduced, the value of K approaches zero. As the flow rate increases, the value of K approaches the difference between the inlet temperature of the dielectric liquid and the uncooled temperature for a given section. Changes in dielectric liquid temperature as it passes through the cable pipes provide an indication of the heat being removed in each section based on the mass flow through the section as defined by Equation 3.6-3. •
m = ρ ⋅ A ⋅υ
3.6-3
from the cable pipe, passed through a heat exchanger to remove heat, and then reintroduced to the cable pipe. This has the potential of increasing the ampacity by 50– 70%, although the cost and maintenance of these active systems can be high. Considerations for Active Uprating With fluid circulation or forced cooling in pipe-type cables, there are some cautions associated with using these uprating methods. Pressures along the hydraulic loop may become excessive as a result of hydrostatic head pressure, fluid flow restrictions near joints, and cross-over plumbing between feeders and fluid return pipes. The high pressures could cause the termination housing to fracture, potentially resulting in a cable failure, dielectric fluid leak, and fire.
Where: •
m is the mass flow rate in kg/sec. ρ is the density in kg/m3. A is the free area within the pipe in m2. υ is the velocity in m/sec. The heat removed, Watts, in a given section can then be found from Equation 3.6-4. •
q = m⋅ CP ⋅ (TOUT − TIN )
3.6-4
Where: CP is the specific heat in kJ/kg-°C. TOUT and TIN represent the outlet and inlet temperatures, respectively, of the dielectric liquid in a given section. By knowing the net heat absorbed or lost in a given section and the length of that section, it is possible to evaluate the net heat removed (or gained) in a given section. For a forced-cooled system (described next), the net heat gained by the system will assist with sizing the forced-cooling plant and heat exchangers. Fluid circulation could be applied to extruded dielectric or self-contained liquid-filled cables by installing parallel water cooling pipes next to the cables and then circulating water through those pipes. Although technically feasible, this is not often done. In addition, some utilities such as National Grid in the United Kingdom circulate the dielectric liquid in the fluid channel of self-contained liquid-filled cables. Again, this is relatively rare. Forced Cooling (Water or Oil) Forced cooling is an extension of fluid circulation. The main difference is that, rather than just moving heat around from “hot spots” to “cold spots” in the cable route, the dielectric liquid (or water in the case of water cooling of extruded or self-contained cables) is diverted
3-42
Pressure drop along long circulation loops must be considered. The degree of snaking of the cable phases within the pipe can affect the fluid flow and pressure drop, potentially limiting the flow rate. The pressure drop as a function of length can found by evaluating the Darcy-Weisbach equation, as shown in Equation 3.6-5. dP ν ⋅V 2 = f 2 ⋅ Dh dL
3.6-5
Where: f is the friction factor, empirically determined based upon the Reynolds Number cable-topipe inner diameter ratio. γ is the density, kg/m3. V is the flow velocity, m/sec. Dh is the hydrostatic diameter, m. The pumping plant, in particular the fluid circulation pump, must be able to accommodate the circulation pressure. The density and viscosity of the dielectric liquid will impact the allowable pressure drop, in addition to the free area within the pipe and the degree of cable snaking. On long circulation loops, multiple loops may be needed with intermediate fluid circulation stations to limit the pressure drop. Complex control systems, particularly in the event of a cable failure, must also be developed to manage the various cooling loops and to stop fluid circulation in the event of a fault. Fluid circulation is often considered for the buried pipe sections. However, when forced cooling is used, the riser sections—lengths of pipe between the trifurcator and termination—may become limiting and could require specialized plumbing to allow circulation in these areas. Diffusion chambers may also be necessary to avoid damaging the outer layers of insulation. A factor to consider for uprating older pipe circuits, where the riser
Increased Power Flow Guidebook
section may be limiting, is that installation of a diffusion chamber on a riser that is not so equipped can be difficult. This is because working “close in” on the riser pipe would be difficult with the cable already in place, and removing and installing a new termination to put in the diffusion chamber may be impractical. 3.6.8
Shield/Sheath Bonding Scheme
As discussed to some extent in Section 3.4, there are three methods for grounding the shield/sheath on singleconductor (extruded dielectric, self-contained fluidfilled) cable systems: multipoint bonding, single-point bonding and cross-bonding. Multipoint bonding involves tying the shield/sheath connections together and to local ground at both terminals and usually at intermediate manholes, resulting in a path for induced circulating currents but with minimal induced voltages. Single-point bonding involves grounding the shield/sheaths at only one location along a given section, preventing circulating currents but leaving the other end un-grounded where a standing voltage will appear. Cross-bonding involves dividing the cable sections into groups of three minor sections that are close to the same length and transposing sheath connections at the one-third and two-third locations, thereby eliminating net circulating currents and minimizing induced voltages. Generally, single-conductor transmission cables are designed with cross-bonding or single-point bonding to minimize shield/sheath circulating currents in the presence of relatively high phase currents. The one exception to this common practice is submarine cable installations, where multipoint bonding of the sheath is almost mandatory because of the long installation lengths and typically wide phase spacing. Contrary to transmission practice, most distribution circuits are multipoint bonded where the utility transformer and customer service panel are both grounded for safety and so the neutral can carry imbalance currents. The circulating currents in multipoint bonded systems generate additional I2R losses (heat) in the shield/sheath that impacts ampacity. Multipoint bonding systems generally have about 2030% lower ampacity than single-point bonded or crossbonded systems constructed with similar cable sizes. If the ampacity audit reveals that a circuit has lower ampacity than desired and happens to be multipoint bonded, the shield/sheath connections might be reconfigured for sectionalized single-point bonding or crossbonding to eliminate the circulating current and gain a significant improvement in ampacity. The reconfiguration may require changing out some or all joints since
Chapter 3: Underground Cables
the joints must have shield interrupts to provide for single-point bonding or to facilitate transposing the sheath connections for cross-bonding. If a system that was previously multipoint bonded is being reconfigured for single-point bonding, a ground continuity conductor should be installed to provide a low impedance path for fault current; the shield breaks will otherwise block the flow of fault current. Also, single-phase or three-phase link boxes or cross-bonding boxes will be needed. If uprating using a reconfigured sheath bonding scheme is being considered, and utility practice is typically with multipoint bonding systems, care should be used to clearly mark all manholes where standing voltages may appear. A shield that is not grounded locally, but is connected to ground at the adjacent manhole, may experience a significant voltage rise with respect to local ground during nearby system fault conditions from a combination of induced voltages and system potential shifts. This is not a phenomenon peculiar to single-point grounded arrangements, as any shielded cable is susceptible when the shield is connected to a remote ground yet remains ungrounded locally. The remedy for this situation is to provide secure, temporary shield grounding as appropriate. This has always been a recommended practice. This is particularly important when working on a de-energized single-point bonded circuit that parallels an energized circuit, since the parallel circuit can induce a voltage. Also, single-point bonded or cross-bonded cable systems require periodic maintenance to check the jacket integrity and ensure that there are no unexpected current circulation paths. Fault location efforts may also be complicated by single-point bonded or cross-bonded sheaths, possibly requiring that the bonding connections be reconfigured during cable fault location. Jacket fault location in duct bank installations is difficult unless the ducts are under the water table. Although not technically necessary, many cross-bonded cable systems are installed with a parallel ground continuity conductor. Induced currents in this parallel conductor can generate enough I ^ 2 x R losses to produce mutual heating that can affect ampacity of the phase conductors. 3.7
RECONDUCTORING (UPGRADING)
3.7.1
Introduction
In contrast to uprating, which is generally defined as improving the capacity of existing equipment, upgrading considers using available infrastructure to economically put in new cables, replacing existing conductors. This section discusses some of these issues.
3-43
Chapter 3: Underground Cables
Increased Power Flow Guidebook
A basic assumption for this section is that the cable system is either pipe-type or a duct installation. Reconductoring a direct buried cable is impractical and really should be considered a new installation, along with the installation of a parallel circuit when there is no existing infrastructure (pipe or conduits). Neither of these cases is covered by this chapter. One possible scenario might be reconductoring one of two parallel cable circuits. The condition of the older circuit should be evaluated to see if loss of life or higher operating temperatures might affect reliable performance. The upgrading topics in this guidebook would apply to the scenario, although the details of evaluating the impact on the older circuit or other connected equipment are beyond the scope of this chapter. 3.7.2
Larger Conductor Sizes
The main issue with considering a larger conductor size is whether the cable will fit within the same conduit or pipe. Paper-insulated insulation thicknesses are fairly standardized based upon voltage class, but the designer might consider using a larger conductor size combined with a switch from conventional Kraft paper insulation to laminated paper polypropylene paper (PPP) insulation, which has a higher dielectric strength and, therefore, a lower insulation wall thickness. With pipe-type cables, the issue is to maintain sufficient clearance in the cable pipe. The traditional guideline for new pipe installations is to have at least 12.5 mm (0.5 in.) of clearance in the pipe, as determined by Equation 3.7-1. However, with older pipes, where upgrading would more often be considered—either pipes that have cables to be replaced or old but unused empty pipes that might have new cables installed—a minimum clearance of 25 mm (1 in.) is often considered prudent to allow for the possibility that overburden or settling may have increased the ovality of the pipe that possibly could affect a successful installation. C=
D 1 ⎛ d ⎞ − 1.366d + ( D − d ) 1 − ⎜ ⎟ 2 2 ⎝ D−d ⎠
diameter of the conduit and the outer diameter of the cable. Again, it is typical to have 12.5–25 mm (0.5– 1.0 in.) of clearance in the conduits. If cables are not already in the conduits, a mandrel through the conduits should be used to check the maximum size cable that can pass through the pipe or conduit. For extruded cables in particular, the construction of the metallic moisture barrier and metallic shield could be adjusted to allow for a larger cable. As an example, Commonwealth Edison (now ComEd, An Exelon Company) removed 138-kV paper-insulated cables from ducts to be replaced by cross-linked polyethylene cables. If the typical 3.2 mm (0.125 in.) lead sheath moisture barrier and full-wall 138-kV insulation 21.6 mm (0.85 in.) were used, it would have meant the standard XLPE cable design could not fit in the existing conduits. Instead, the installation included a reduced insulation wall (16.5 mm, 0.65 in.), a copper laminate tape with copper shield wires, and a reduced jacket wall (as compared to typical industry practice for that size cable), greatly reducing the outer cable diameter and allowing the cable system to fit in the conduits. The relative effect of reconductoring on ampacity is discussed in Section 3.4. 3.7.3
Cupric Oxide Strand Coating
Some cable manufacturers have investigated using cupric oxide coated strands to make conductors. By coating the strands with cupric oxide, each strand has a slightly increased resistance (in the radial direction) to each adjacent strand. This improves the skin and proximity effect factors of the conductor—reportedly down to 0.3 for both values—over conventional copper stranded insulations. This reduction in ac incremental losses significantly improves the ac to dc resistance ratio and ampacity. To illustrate, the pipe-type cable example
2
3.7-1
Where: D is the inner diameter of the cable pipe. d is the diameter of the cable over the insulation, plus 1.5 times the height of a skidwire, all values in inches. Figure 3.7-1 shows the clearance in a pipe-type cable. For extruded or self-contained cables where normally a single phase would be installed in each conduit, the clearance is simply the difference between the inner
3-44
Figure 3.7-1 Clearance in a pipe-type cable.
Increased Power Flow Guidebook
in Appendix 3.1 would show an increase in ampacity by almost 3% if a cupric oxide strand coated conductor were used. 3.7.4
Voltage Upgrading
Voltage uprating, possibly combined with an increase in conductor size, would significantly improve the power transfer limits. As an example, an 8-in. cable pipe that is typically used for 138-kV cables with 11.2 mm (0.44 in.) of Kraft paper insulation might be reconductored with 11.4 mm (0.45 in.) of PPP insulation, allowing an increase to 230-kV cable with virtually no change in the outer cable diameter and a 67% increase in power transfer. Additional improvements in capacity might be possible if a larger conductor size can also be used. Section 3.2 lists typical insulation thicknesses for the various cable constructions and insulation materials.
Chapter 3: Underground Cables
• Sumitomo: 100 m of 66-kV cable with 1000 A. • Southwire: 30 m of 12.5-kV cable with 2600 A (operated in parallel to an overhead line on Southwire's property).
• NKT: 30 m of 30-kV cable with 3000 A (utility substation).
• Condumex: 5 m of 2000 A (Condumex test facility). • Nexans / American Superconductor / LIPA: 610 m circuit 138-kV cable with 2510 A is being developed for a new installation on Long Island.
The main issue with voltage upgrading is that, in addition to possibly significant costs in new cables, several pieces of substation equipment must also be replaced to accommodate the new voltage level. This is sometimes not so significant if the higher voltage level being considered for voltage upgrading already exists within both terminals. Otherwise, the cost and effort generally make voltage upgrading infeasible. 3.7.5
Superconducting Cables
At the time this chapter is being prepared, superconducting cables are largely in the research stage. Limited sections of cable have been installed in controlled settings (e.g., parallel to a 100% redundant overhead line, in a “laboratory” setting, or in a nonessential capacity underground). Several high-temperature superconducting (HTS) cable projects have been demonstrated largely with U.S. Department of Energy funding, using either warm or cold dielectric technology (Figure 3.7-2). As the names imply, the “warm dielectric” cable uses insulation that is at or above room temperature to support the energized line-to-ground voltage, while “cold dielectric” cable utilizes cryogenic (liquid nitrogen ~80°K) insulating medium. Examples of recent research in superconducting cables are summarized below: 1996-1999
• Pirelli/EPRI: 50 m of 115-kV cable with 2000 A. • Sumitomo/TEPCO: 30 m of 66-kV cable with 1000 A. 2000-2002
• Pirelli/Detroit Edison: 130 m of 24-kV with 2500 A (system could not be energized because of a vacuum leak in the cryostat).
Figure 3.7-2 Examples of superconducting cables (courtesy of American Superconductor Inc.).
3-45
Chapter 3: Underground Cables
While favorable results have been observed, the available technology is not yet practical for typical transmission voltages, and the operating lengths have not been increased sufficiently to allow “transmission” at what have typically been considered medium-voltage levels (e.g., transferring bulk power at high-current/low-voltage). At this point, superconducting cables do not yet offer a commercially viable means for uprating existing transmission circuits, though this is likely to change within the next decade.
Increased Power Flow Guidebook
tion aging and “acceptable loss of life” has not often been considered for underground cable ampacity. The main benefit to dynamic ratings is the ability to track the cables’ temperatures with time and changing load conditions and then base emergency ratings on the actual, rather than assumed, pre-emergency temperatures. The benefits of this type of evaluation were illustrated in Section 3.6.3 and Figure 3.6-9. 3.8.2
3.8
DYNAMIC RATINGS OF UNDERGROUND CABLE SYSTEMS
3.8.1
Background
As discussed in Section 3.3.1, the thermal time constants of underground transmission lines are significantly longer than those of overhead lines and power transformers. This is a result of the thermal inertia (or heat capacitance) of the earth that surrounds the cables. As a result of this thermal inertia, the dynamic rating of underground transmission lines significantly exceeds their steady-state ratings, provided that there are significant variations in the line loading. Conversely, the dynamic rating of underground transmission lines is not much higher than their steady-state ratings if the lines are consistently loaded near their steady-state ratings. The term “dynamic rating” means the present rating of a line, taking into account its load history and real-time measurement of parameters (mainly ambient earth temperature). In actuality, the “normal” ampacity of a circuit does not change, except for changing ambient temperature, since it is generally based on an assumed daily loss factor and installation conditions. Therefore, a “dynamic” normal rating remains relatively constant unless some decision about future loading is evaluated. Predicting future loading patterns is difficult since unplanned system changes may affect loading patterns, but the use of predicted load patterns, usually based on utility SCADA systems, does allow for some future load estimations (usually limited to 24 hours). Tracking the cable conductor temperature is the main goal of dynamic ratings, since this is ultimately what limits the power transfer on the circuit. For paper-insulated cables, tracking the conductor temperature also permits an assessment of insulation aging and ultimately the life of the cable system. EPRI funded a detailed investigation of paper-insulated pipe-type cables in the 1990s. Transformer ratings have been based on a variety of factors including the insulation aging and loss-of-life criteria. However, application of insula-
3-46
EPRI Dynamic Ratings on Cables
Development of the EPRI Dynamic Thermal Circuit Rating (DTCR) system was started in 1991 with advanced models for overhead transmission lines, power transformers, and underground cables. The cable model used in DTCR was initially based largely on the underground cable ampacity program “Alternative Cable Evaluation (ACE)” in the EPRI Underground Transmission Workstation (UTW) that was started in 1990. ACE was an off-line ampacity program that would determine normal and emergency ratings based on userspecified input data. The ratings generated by ACE were similar to what many utility engineers refer to as “book ratings” in that they were static ratings based on assumptions (usually worst-case) and then tabulated for reference by engineers and operators. As the utility industry changed dramatically during the 1990s, toward achieving higher profits, there was increased pressure to get more capacity from existing equipment while minimizing new construction whenever possible. To this end, DTCR was developed to take realtime data from “off the shelf ” monitoring hardware, and determine optimal ratings (not worst-case) for the conditions at the time the ratings were performed. Although this required some philosophical changes at utilities to consider circuit ratings as moving, changing entities rather than fixed parameters, the overall benefit was to demonstrate a greater capacity in transmission assets, including underground transmission cables. The general theory behind DTCR is that, probabilistically, there are relatively rare circumstances where the worst-case rating conditions occur at the same time that the greatest possible circuit loading is required or desired. As a result, by evaluating the ratings on a realtime basis using actual, rather than worst-case conditions, the real-time rating is much higher and the allowable power transfer is greater. This is illustrated graphically in Figure 3.8-1. In Figure 3.8-1, there is a relatively small region (rating regime) where the dynamic rating distribution overlaps the loading, indicating that at most times, the dynamic
Increased Power Flow Guidebook
Chapter 3: Underground Cables
Figure 3.8-1 Probabilistic view of dynamic ratings and actual circuit loads.
rating is greater than the “book” ampacity. DTCR allows the circuit to operate closer to the limit by performing a real-time rating evaluation using measured (rather than conservative or worst-case estimates) parameters. Cable Models One approach to dynamic ratings on cables—that used in the Underground Cable Module in DTCR—is based on the paper by Neher and McGrath (1957), and on the International Electrotechnical Commission (IEC) Publications 287 and 853 (International Electrotechnical Commission 1982, 1989). These same calculation methods are used in off-line rating tools such as EPRI’s UTWorkstation ACE program.
The numerical technique used in DTCR to track conductor temperatures is an “additive wave method,” whereby the temperature response to a constant heat input is tracked into the future. For cables, DTCR looks at “small” intervals (< 0.5 hours), over which the load can be treated as constant. The temperature response to the load with respect to time is a function of the heat input to the cable (either positive for increasing load or negative for decreasing load). Each time the load changes, a new temperature response “wave” is launched. As the load changes from interval to interval, the total temperature response at a given time is the summation of all the previous temperature response functions from each change in heat from the cable (as a function of load and the change in resistance with temperature). This basic concept is described in a paper by Neher (Neher 1963) and illustrated in Figure 3.8-3 with an arbitrary load. The numerical calculations are based on equations from IEC-287 and IEC-853 and make use of attainment fac-
tors for changes in heat output from the cables. The cable temperature changes with respect to time and changing load based on the thermal response of the cable and environment. The cable or pipe temperature response is defined by Equation 3.8-1.
θCable (t ) = Wi ⎡⎣ RA (1 − exp( −at ) ) + RB (1 − exp( −bt ) ) ⎤⎦ 3.8-1
Where: Wi is the heat output from the cable. RA, RB is the thermal resistance at steady state. a, b are time constants representing how the temperature changes with respect to time for a given heat input. For the temperature response of the environment, there are two models in DTCR: one that assumes all circuits/cables carry identical currents, and a second where two circuits may carry unequal loading. Equal Loading For the case of two three-phase circuits of extruded or self-contained cable, all six (6) cables are assumed to carry the same load even if the circuits are electrically disconnected. The temperature rise above ambient from ac loading is described by Equation 3.8-2, utilizing exponential integrals, for the cable that is identified to be the hottest cable in the trench.
⎡ ⎛ D2 ⎞ ⎛ L2 ⎞ ⎢ −Ei ⎜ − earth ⎟ + Ei ⎜⎜ − ⎟⎟ ⎜ 16δ t ⎟ ⎝ δt ⎠ ⎝ ⎠ ρs ⎢ θ HottestCable (t ) = Wi ⎢ ⎛ rj 2 ⎞ ⎛ r ' j2 4π ⎢ 6 ⎜ ⎟ ⎜− + − − + Ei Ei ⎢ ⎜ 4δ t ⎟ ⎜ 4δ t ⎢⎣ j = 2 ⎝ ⎠ ⎝
∑
⎤ ⎥ ⎥ ⎥ ⎞⎥ ⎟⎥ ⎟⎥ ⎠⎦ 3.8-2
3-47
Chapter 3: Underground Cables
Increased Power Flow Guidebook
Where: is the heat generated by each cable. Wi Ei is an exponential integral. Dearth is the earth diameter for the cable or conduit. L is the burial depth for the “hottest” cable among the group. is the actual distance between the hottest rj cable and adjacent cables. is the distance between the hottest cable and r’j the image of adjacent cables. The watts generated by each cable, Wi, are identical for all cables in the group. Unequal Loading For the case of two circuits with unequal loading, the heat output from the second circuit is defined separately from the first circuit. The mutual heating effects with respect to time are then evaluated as shown in Equation 3.8-3.
⎡ ⎛ D2 ⎞ ⎛ L2 ⎞ ⎢ − Ei ⎜ − earth ⎟ + Ei ⎜⎜ − ⎟⎟ ⎜ ⎟ ⎝ δt ⎠ ⎝ 16δ t ⎠ ρs ⎢ θ Pr imaryCable1 (t ) = Wi1 ⎢ ⎛ rj 2 ⎞ ⎛ r' 2 4π ⎢ 3 ⎟ + Ei ⎜ − j ⎢ + − Ei ⎜ − ⎜ 4δ t ⎟ ⎜ 4δ t ⎝ ⎠ ⎝ ⎣⎢ j = 2
∑
+Wi 2
⎤ ⎥ ⎥ ⎥ ⎞⎥ ⎟⎥ ⎟⎥ ⎠⎦
⎛ r2 ⎞ ⎛ r ' 2 ⎞⎤ ρs ⎡ 6 ⎢ − Ei ⎜ − j ⎟ + Ei ⎜ − j ⎟ ⎥ ⎜ 4δ t ⎟ ⎜ 4δ t ⎟ ⎥ 4π ⎢ j = 4 ⎣
∑
⎝
⎠
⎝
⎠⎦
3.8-3
Where: Wi1 , Wi2 are, respectively, the heat generated by each cable in circuit 1 and circuit 2. Cable Dynamic Rating Model The combined effects of the two temperature response functions gives the complete temperature response of the cable conductor to a given cable heat output. When there is changing load, typical of most transmission circuits, the accumulated temperature responses for each change in load will give the conductor temperature with respect to time. The general procedure and flow of the DTCR cable model are illustrated in Figure 3.8-2.
Graphically, the changing load is illustrated in Figure 3.8-3, where the top graph shows an arbitrary load pattern, with loads that are both increasing and decreasing over time. The bottom graph shows the individual temperature response waves to each change in load (fine lines) and the summation of all the temperature response waves (dark line). Also shown in the graph is the addition of the dielectric temperature rise, which remains constant with respect to time as long as the lineto-ground voltage remains constant (this is an assumption). As compared to other modules (overhead lines and power transformers) within DTCR, the cable model requires extensive computations since the long earth thermal time constant requires “looking back” hundreds of hours in the loading history. As a result, ratings are normally not performed more often than once every 15 minutes or so. Fortunately, the long thermal time
Figure 3.8-2 General flow of information in DTCR cable model. (“STE” means “Short Time Emergency” rating, and “LTE” means “Long Time Emergency” rating.)
3-48
Increased Power Flow Guidebook
constant also means that there are limited temperature changes over that time. Because of the considerable heat storage capacity of underground cables, the operating power levels prior to a contingency loading have a large effect on the actual thermal behavior during emergency loading events. EPRI’s DTCR technology allows continuous monitoring and establishment of such power equipment’s actual pre-contingency thermal state. As a result, load shedding during emergencies can often be avoided and capital investment in new equipment postponed. 3.8.3
Benefit of Dynamic Ratings
The thermal rating of underground cables is traditionally calculated using worst-case seasonal loads and soil temperatures. Underground cable thermal parameters are based on manufacturer’s data, installation assump-
Chapter 3: Underground Cables
tions, and industry standards. Rating calculations are typically performed “off-line” using worst-case assumptions to derive seasonal limits (maximum soil temperature, worst-case loss factors). With dynamic ratings, actual soil temperatures and load data are used in place of worst-case approximations, allowing higher operating limits under most conditions and more accurate thermal modeling under all conditions. Other than cable parameters and configuration, dynamic thermal rating calculations for underground cable require soil characteristics and temperature. The equipment parameters can be verified by comparing calculated to measured equipment temperatures, which in the case of high-voltage underground cable is the earth interface temperature, or a more general comparison between a measured temperature and calculated temperature in a location near the power cables. The measured temperature from a thermocouple or DFOTS can be compared to the dynamic rating system-calculated temperature, as described in Section 3.4.7. DTCR Circuit Ratings The DTCR software allows the user to calculate realtime equipment temperatures, multiple thermal ratings, and “remaining-time” (or “Time to Temperature Overload,” TTO) during emergency loadings, given real-time load and ambient ground temperature for underground cable circuits. “Circuit” ratings, rather than “equipment” ratings, are possible by modeling all of the power equipment on a given circuit (e.g., series-connected transformers, overhead lines, cables, etc.), or in the case of cables, each unique installation section along a given route, and then letting DTCR calculate ratings for all equipment and locations on a circuit. Then, DTCR selects the lowest rating for each category (normal, LTE, STE) and reports these values as circuit ratings. Utility Implementation of Dynamic Ratings Some dynamic rating systems interface directly with monitoring hardware. This has some disadvantages:
• The hardware is probably redundant to monitoring already done by the utility.
• The hardware is sometimes very specialized, meaning that the original vendor must be recalled for maintenance and repairs, usually at a high cost.
• Telemetry for any monitoring outside of a substation is often complex, expensive, and prone to interruption. Figure 3.8-3 “Additive Wave” model for temperature tracking in underground cables.
• The computer system used to perform rating calculations, by virtue of the direct connection to the moni-
3-49
Chapter 3: Underground Cables
Increased Power Flow Guidebook
time input data file on the dynamic rating system computer through use of “Network Access calls” or other operational programs.
toring hardware, must be located in the field where weather and security are difficult to manage.
• Any changes to the hardware usually require a
• The real-time input data on the dynamic rating sys-
new custom-designed interface to collect the monitored data.
tem is read from the ASCII file created by a SCADA Network Access call.
• There is an issue of getting calculation results from
• A specific “SCADA” input file containing real-time
the remote location back to the utility’s operations center, where it can be used by engineers and operators to optimize circuit capability.
temperatures and ratings is continually updated by the dynamic rating system and made available to the utility SCADA/EMS system. This allows dissemination of the calculation results to anywhere within the utility.
For these reasons, dynamic rating systems may be interfaced to the utility SCADA system so that the SCADA system can handle all of the utility-specific telemetry issues, and the dynamic rating system can concentrate on just the rating and temperature calculations. Some favorable characteristics are as follows:
All calculations can now be performed in an engineering office or operations center environment (rather than in a substation) without the need for special monitoring device communication links. Utility operations programmers need only develop simple SCADA Network Access calls to write ASCII input data files to the dynamic rating computer, rather than spending a lot of time writing equipment-specific interface programs. Figure 3.8-4 shows the general layout of EPRI’s dynamic rating system (DTCR), which utilizes this approach.
• The preferred mode of operation is one wherein remote monitors provide data to the SCADA/EMS database using utility-specific communication links, and the dynamic rating system obtains its real-time data from that database rather than directly from the remote monitors.
• The utility SCADA/EMS system must transfer realtime monitor data from the database to a simple real-
Monitor
PC in Engineering Office or Operations Center
Modem Cell or Land Line
Monitor
Wire or Fiberoptic (RS232)
Modem
Direct Monitor Input
Monitor
Input Data File*
Direct Connect Communications Program
Input Data File*
Radio Link Communications Program
wireless
Network Access Call
Telephone Communications Program
Input Data File* Input Data File*
* File with most recent realtime data appended.
DTCR Software Product User Interface
File Handler
Real-Time Historical Data File (mmddyy.###)
File
DTCR Calculation Algorithms
Real-Time Output File (ratings, temps., etc.)
Real-Time SCADA Output File (ratings, temps, etc.)*
Network Access Call
SCADA/EMS Database Output to Engineering or Operations Center
DTCR Functional Diagram
Figure 3.8-4 Schematic overview of DTCR’s location within the utility architecture.
3-50
Increased Power Flow Guidebook
3.8.4
Required Monitoring
Underground cable dynamic rating systems require various monitored parameters. Some of the parameters that could be evaluated are summarized as follows: Ambient Soil Temperature The ambient temperature is a fundamental parameter to be monitored since it directly affects the allowable temperature rise from ac loading. Soil temperature monitoring should be located where it is representative of the ambient conditions imposed on the cable system. Usually, this means being at least 10 m (30 ft) away from an energized cable circuit at typical installation depths. A thermocouple tree—a series of thermocouples installed at various depths at the same location—is ideally suited for this type of monitoring, since it gives a range of temperatures that may be used for the variation in burial depth encountered along the circuit. Load The load is also an important parameter to know, even if doing quasi-dynamic ratings (described in Section 3.8.4). The load serves two purposes. First, it allows the conductor temperature to be calculated as a function of load. Second, it allows a correlation between any measured temperatures and the circuit load (see Section 3.4.7). This is important for verifying ampacity capability. Soil Thermal Resistivity Real-time monitoring of soil thermal resistivity is not common, mostly because the soil thermal resistivity does not change rapidly. Some utilities permanently install a thermal probe so that additional thermal resistivity measurements can be made to account for seasonal variations or weather effects.
As discussed in Section 3.6, thermal resistivity is a very important parameter, since earth components of thermal resistance represent more than half of the total thermal resistance to heat leaving the cable. Pipe-Type Cable Monitoring Some parameters are uniquely important to pipe-type cable dynamic ratings, particularly those that utilize fluid circulation or forced cooling. Inlet and outlet pressure to a cooling loop, fluid flow rates through the cooling loop, inlet dielectric liquid temperature, and cooling system outlet temperature all may be monitored to evaluate the performance of a pipe-type cable system with active forced cooling. The capability of the cooling plant to remove heat from the dielectric liquid is very important, since this ultimately dictates how much forced cooling can be applied to the pipe-type system.
Chapter 3: Underground Cables
3.8.5
Quasi-Dynamic (Real-Time) Ratings
“Quasi-dynamic ratings” utilize many of the principles of real-time ratings except they may not be done on a continuous basis. For example, a utility may have a cable circuit that is only heavily loaded two months of the year. On that basis, the cost to implement a dynamic rating system may not be justified, but the ratings during that two-month window are still critical. Quasi-dynamic ratings might be applied by monitoring load and temperatures for a period of time and then calculating what the conductor temperature might be as a result of that load. From this, the temperature of the cable conductor at rated temperature can be extrapolated for rating purposes. For example, the earth interface temperature of a cable system may be monitored with thermocouples for several months until a period of high loading occurs. At that time, the utility may download measured temperatures from a thermocouple data logger and compare measured to calculated temperatures to evaluate the assumptions used for rating models, both real-time and off-line ratings. Quasi dynamic ratings may also apply to reviewing historical load profiles using dynamic rating algorithms. The load history on a circuit for a year or two—perhaps covering high-load periods during summer months— could be run through a dynamic rating tool to evaluate peak loading periods and study loss-of-life criteria (on paper cables). 3.9
CASE STUDIES FOR UNDERGROUND CABLE CIRCUITS
Section 3.9 describes uprating projects recently conducted at utilities. It is hoped that these case studies help to illustrate the general application of uprating techniques described in this chapter. 3.9.1
CenterPoint Energy
Description of Circuit and Summary of Rating Constraints and Utility Goals A 138-kV HPFF underground transmission line was constructed in 1969 from CenterPoint Energy’s Polk substation (located at the intersection of Polk and La Branch Streets in Houston, Texas) to CenterPoint’s Garrott Substation (located at the intersection of Garrott Street and Blodgett). The total length of this 138-kV underground transmission line is approximately 2.37 miles (12,500 ft). A 2500-kcmil, compact segmental copper, 138-kV HPFF cable with 505 mils of insulating tapes was used to construct the Polk – Garrott transmission line.
3-51
Chapter 3: Underground Cables
In March 2001, a loop feed to a new CenterPoint substation, Midtown Substation, was constructed by tapping into the existing Polk to Garrott underground transmission line. This loop feed to the Midtown Substation (located on La Branch Street between Taum and Drew Streets) segregated the Polk to Garrott underground transmission line into two parts with the lengths of 0.96 and 1.41 miles. CenterPoint wanted to evaluate the power transfer capabilities of the Polk-MidtownGarrott and Polk-Downtown 138-kV underground transmission lines in light of these changes and to optimize the current-carrying capacity of the circuits. The ampacity audit was based on an evaluation of recent and historical data including:
• Long-term load current, ambient soil temperatures, and cable pipe temperatures during summer operating conditions
• Distributed fiber optic temperature sensing (DFOTS) measurements performed on the circuits in February 2002 for hot spot identification
• As-built plan and profile drawings for the two cable circuits
• Cable manufacturing data CenterPoint Energy also wanted to evaluate the condition of the thirty-two-year-old Polk-Garrott HPFF cables in coordination with the ampacity analysis. Consequently, two investigations were performed for this purpose. First, Detroit Edison (DECo) performed dissolved gas analysis (DGA) and laboratory testing of cable paper tape samples obtained during construction of the loop feed to the new Midtown Substation. Power Delivery Consultants (PDC) also performed cable dissipation factor measurements at rated voltage using EPRI-developed instrumentation. A previous EPRI project (Transmission Cable Life Evaluation and Management) indicated that cable tape physical property measurements, DGA, and dissipation factor measurements are the best diagnostic tests to determine cable loss-of-life. The primary focus of the DTCR project was to examine the ratings on the Polk-Midtown-Garrott circuit. This circuit consists of two segments: 5,060 ft from Polk to Midtown Substation, and 7,440 ft from Midtown Substation to Garrott Substation. DTS measurements showed that the hotspot for the Polk-Midtown-Garrott underground line is a crossing with the Polk-Downtown 138-kV underground transmission line at the intersection of Polk and La Branch (just outside of the Polk Substation). The cable used for the Polk to Downtown 138-kV line is identical to the Polk to Garrott line. The depth of cover over the Polk-Midtown-Garrott line is approximately 11 ft-2 in. at the hot spot location, and 3-52
Increased Power Flow Guidebook
the vertical clearance to the Polk-Downtown line (above it) is approximately 3 ft. CenterPoint placed a thermocouple on the Polk to Garrott cable pipe near the intersection. Initially, the thermocouple temperature was monitored with a data logger, but this thermocouple is now connected directly to CenterPoint's SCADA system. A thermocouple was also placed on the PolkDowntown circuit at the location of the crossing and connected to SCADA. In 2000, CenterPoint Energy (Houston Lighting & Power) began this investigation (completed in December 2002 – EPRI Report 1007539) to increase the circuit capacity on the high-pressure fluid-filled (HPFF) pipetype cable connecting the Polk and Garrott Substations. Various studies were performed to evaluate uprating possibilities for this circuit, including the application of distributed fiber optic temperature sensing (DFOTS). Results of DFOTS revealed that a hot spot existed where another pipe-type cable (CenterPoint’s Polk-Downtown circuit) crossed over the Polk-Garrott circuit. Although an overall increase in ampacity was found for the general cable circuit, a net decrease in ampacity resulted from the modeling of the mutual heating of the two cable circuits where they cross. This was anticipated prior to beginning the project, so DTCR was implemented on the Polk-Garrott circuit in an effort to optimize available circuit capacity. The principal goal of the project was to investigate an optimized circuit rating in light of the interference temperature effects detected by DFOTS and experienced by the crossing pipes. A secondary objective was to demonstrate that, under normal loading patterns, the maximum normal temperature (85°C) of the conductor would infrequently be exceeded. Results of Uprating and Benefits to Utility The following conclusions may be reached from reviewing the application of DTCR at CenterPoint:
• The DTCR modifications and subsequent data analysis showed that CenterPoint Energy’s Polk-Midtown-Garrott and Polk-Downtown pipe-cable circuits can benefit from dynamic ratings. DTCR’s predicted load pattern assumes a typical 24-hour loss factor cycle consistent with static ratings. However, the emergency loading is a function of pre-load conditions, and DTCR accurately calculates the conductor pre-load temperature based on historical loading patterns. Also, DTCR uses the present loading to predict time to temperature overload (TTO).
• While a detailed ampacity study indicated there was effectively a reduction in the established book rating of 3.4%, applying DTCR allowed for a net increase in the normal rating of 20.7%, based on considering a
Increased Power Flow Guidebook
“dynamic” rating using summer 2000 load data for a “quasi-real-time” dynamic rating analysis.
• In summary, the real-time dynamic ratings of the
Chapter 3: Underground Cables
the harbor section. An additional goal was to consider means for increasing ampacity on the circuit.
Polk-Midtown-Garrott and Polk-Downtown underground transmission lines are expected to be significantly higher than the static ratings that were calculated under a separate project, assuming there is similar load pattern variability to that observed during the summer 2000.
Power Delivery Consultants, Inc. (PDC) was contracted in 2001 to perform a very detailed evaluation of the Bridgeport Harbor portion of UI’s 1710 and 1730 lines using sophisticated modeling and state-of-the-art technology to gather information about the installation and environment. The evaluation included several technologies:
The following conclusions are a result of the cable condition assessment testing performed on the Polk-Garrott 138 kV underground transmission line.
• Gyroscopic testing on the empty cable pipe to
• DGA testing of pipe fluid samples and laboratory
• Hydroscopic surveying of the harbor bottom to eval-
testing of a cable sample indicated that Polk-Garrott 138-kV cable offers an exceedingly long life, which is characteristic of HPFF cables.
uate the degree of siltation over the cable pipes since they were installed in 1961 and, ultimately, to determine the cable depth of cover.
• Results of the dissipation factor measurements con-
• Distributed temperature sensing (DTS) using EPRI’s
firmed that the Polk-Garrott 138-kV HPFF cables do not show any signs of insulation deterioration after more than 30 years of operation.
DTS equipment and fiber optic cable installed in the spare cable pipe
3.9.2
United Illuminating Company
Description of Circuit and Summary of Rating Constraints and Utility Goals In 1989, United Illuminating Company (UI) performed an engineering evaluation on the ampacity of the existing 1.4-mile-long UI 115-kV high-pressure gas-filled cable Circuits 1710 and 1730, which connect UI’s Pequonnock Substation to the Seaview Tap in Bridgeport, Connecticut, where the lines transition to overhead conductors. A 1600-ft section under Bridgeport Harbor, where the cables were buried approximately 25 ft under high-resistivity sediments, appeared to limit the overall circuit rating. UI’s construction records indicated that the cable configuration under the harbor consists of three pipes in a 5-ft trench, with a spare (empty) pipe centered between the two cabled pipes.
Results of the 1989 thermal tests showed that soil resistivity ranged widely, from 90º to 250º C-cm/Watt. This range of values produced a degree of uncertainty in the ratings. In addition, the degree of siltation and the actual pipe positions since the cable pipes were installed in 1961 was unknown. Because of the uncertainty of the pipes’ locations, 1989 soil tests were done at least 50 ft away from the expected pipe position to avoid possibly damaging the pipes with the soil-coring equipment. The uncertainty of some parameters from the 1989 study, the limiting of the entire circuit’s ampacity by the harbor section, combined with UI’s interest in increasing the total power transfer on the circuit, precipitated UI in undertaking a more thorough ampacity evaluation of
develop accurate cable pipe plan and profile information for the harbor crossing.
• Continuous thermocouple temperature monitoring using installed thermocouples and data loggers
• Updated soil sample testing to characterize the soils at the depths of interest
• Forced air ventilation to characterize possible uprating by removing heat from the cabled pipes An EPRI report (1007534) documents the results of these evaluations and a detailed ampacity study to determine the actual capacity of UI’s 1710 and 1730 lines under both normal and emergency ampacity conditions, and describes possible approaches for increasing the ampacity on the lines. In 2002, UI implemented two of the recommendations of the ampacity study:
• Applied forced-air cooling on the parallel cable pipe. • Implemented DTCR to monitor conductor temperature and evaluate real-time temperatures on the circuit as the result of circuit loading. Results of Uprating and Benefits to Utility The initial ampacity study resulted in several recommendations to mitigate the rating limits on UI’s cable circuits. These are summarized in Table 3.9-1. Two of the options, forced air cooling on a parallel empty cable pipe and dynamic ratings, were later implemented.
The forced-air cooling equipment is shown in Figure 3.9-1. The actual cost to install the forced-air cooling equipment was substantially higher than the initial esti-
3-53
Chapter 3: Underground Cables
Increased Power Flow Guidebook
Table 3.9-1 Summary of United Illuminating Pipe Cable Uprating Methods Forced Air Cooling Location
Reconditioning
Harbor only Harbor only
Fluid Filling
Circulation
Forced Cooling
Reconductoring
XLPE
Water Cooling
Dynamic Rating
Circuit
Circuit
Circuit
Circuit
Circuit
Harbor only
Circuit
Maximum estimated increase
4.0%a
5.6%b
120°C)
• Higher overloads result in prolonged arcing during break operation. Dragging the arc across the contacts could result in short-circuiting the regulating winding. Overload limits, as specified in C57.131-1995 (IEEE 1995a):
• 120°C contact temperature (higher is OK, but may result in greater maintenance).
• 2x LTC rated load current (limit breaking operations at high load level to few times/year).
The temperature rise of the contacts is calculated as shown in Equation 4.3-14 (IEEE 1995c) 4.3-14
Where: ΔθC is the LTC contact temperature rise over oil. ΔθC,R is the LTC contact temperature rise over oil at rated load. I is the LTC current in per unit of the rated LTC current. n is an exponent that varies from 1.6 to 1.85, with 1.8 as the default.
θ C = θ A + Kθ TO + Δθ C
4.3-15
Where: θC is the total contact temperature. θA is the ambient air temperature. θTO is the transformer top oil temperature. K is a constant to account for the difference between transformer top oil temperature and LTC compartment oil temperature. This is typically around 0.8. It is important to note that the main difficulty associated with elevated temperatures in LTCs is the increased tendency toward contact coking. Since coking increases the electrical resistance across the contact assembly, coking can result in even higher temperatures and possible thermal runaway. If frequent high loading periods are expected, the temperature differential between the main tank oil and the LTC compartment oil should be checked, if possible. In addition, the LTC oil should be clean oil with high interfacial tension (IFT) and low acidity. Reduced Capacity Taps The load dependent losses, and therefore the heating of the transformer windings, is a function of the winding current. Often the transformer load is expressed in terms of apparent power, or MVA, since this number is essentially the same for all windings (neglecting losses). However, in the case of rated MVA when taps are present, the rated current varies inversely proportional to the voltage. The consequence for loading is that, for lower voltage taps, the rating in MVA for a given size conductor decreases.
Often, to maintain the same MVA load capability for all taps, the conductors are sized according to the current at the lowest voltage time. However, occasionally, to reduce cost, the transformer may be specified with reduced capacity taps. In this case, the conductors are sized for the rated current at the neutral position. For higher-voltage taps, the transformer is capable of carrying full rated MVA. However, for lower voltage taps, the
4-19
Chapter 4: Power Transformers
Increased Power Flow Guidebook
transformer is capable of carrying only a reduced MVA, corresponding to the rated current at the neutral tap. Transformers with reduced capacity taps can easily be identified by referring to the table of tap positions, voltages, and rated currents on the nameplate. Transformers with reduced capacity taps have the same rated current for all taps at voltages below neutral. An example of this is shown in Table 4.3-4.
It is important to examine the nameplate when determining the load capability of a particular transformer to determine if the unit was designed with reduced capacity taps. If it was designed with reduced capacity taps, and the unit is operated at taps below neutral, the load capability in MVA will be lower than the nameplate MVA.
Table 4.3-4 Nameplate Showing Tap Positions, Voltages, and Currents CONNECTIONS CRT LOAD TAP CHANGER WINDING
“H” VOLTAGE WYE
CONNECTS IN EACH PHASE
VOLTAGE
MAXIMUM FOA AMPERES
PCS
P1 TO
P3 TO
R TO
120175
432
16L
11
11
3
119495
435
15L
11
10
3
118610
437
14L
10
10
3
118130
440
13L
10
9
3
117445
442
12L
9
9
3
116765
445
11L
9
8
3
116080
448
10L
8
8
3
115395
450
9L
8
7
3
114715
453
8L
7
7
3
114030
456
7L
7
6
3
113350
458
6L
6
6
3
112665
461
5L
6
5
3
111980
464
4L
5
5
3
111300
467
3L
5
4
3
110615
470
2L
4
4
3
109935
473
1L
4
3
3
109250
476
NEUT
11
11
11
108565
476
1R
11
10
11
107885
476
2R
10
10
11
107200
476
3R
10
9
11
106520
476
4R
9
9
11
105835
476
5R
9
8
11
105150
476
6R
8
8
11
104470
476
7R
8
7
11
103785
476
8R
7
7
11
103105
476
9R
7
6
11
102420
476
10R
6
6
11
101735
476
11R
6
5
11
101055
476
12R
5
5
11
100370
476
13R
5
4
11
99690
476
14R
4
4
11
99005
476
15R
4
3
11
98325
476
16R
3
3
11
NO LOAD TAP CHANGER
4-20
CONNECTS IN EACH PHASE
WINDING
VOLTAGE
AMPERES
A
B
“X” VOLTAGE WYE
59000
753
2
1 TO 19
13 TO 15
06000
787
1
1 TO 18
13 TO 14
POS
Increased Power Flow Guidebook
Bushing or Internal CTs Detailed evaluation of bushing CTs is difficult, if not impossible. The location of the CT can be in the bushing adapter or “turret,” or mounted on the active assembly in the tank. Bushing CTs are usually limited by transformer top oil temperature. Maintaining a top oil temperature of less than 110°C should avoid excessive temperatures. Aging rates should be lower than that of the winding insulation over the average of the loading conditions. De-Energized Tap Changers (DETCs) De-energized tap changers are similar, in a thermal sense, to on-load tap changers, albeit much simpler. The same general considerations and risks apply to DETCs as to LTCs. Coking may become a greater problem for DETCs, as they are seldom operated. It may be advisable to periodically operate the DETC over the range of taps to “wipe” the contacts clean of any deposits. Lead Heating Internal connecting leads may be a concern. The same hot spot limits, and associated risks, apply for leads as for windings. In general, it is impossible to evaluate lead heating without detailed design data. In a properly designed transformer, the connecting leads should not limit the overload capability. However, lead hot spots have been a limitation in the load carrying capability of many transformers because of lack of attention in the design stage or manufacturing practices that permitted or even encouraged liberal application of insulating tape at lead connection points.
Evaluation of lead heating problems outside of the factory is rather difficult. Even with dimensions of the leads and construction details, it is difficult to assess the oil flow conditions in the vicinity of the lead. The best method for assessing lead heating problems is by examining the DGA records for the unit for any hint of heating gases involving cellulose decomposition, particularly CO and CO2 , and eventually CH4 and C 2 H6 . If these gases are present in significant quantity or have a generation rate that increases sharply with load, load should be reduced immediately. At the earliest convenience, an internal inspection should be performed to locate the source of the gassing. In addition to DGA, partial discharge detection and perhaps Furan analysis may also yield useful information. Stray Flux Heating Heating of non-current carrying metal components by the leakage flux of the windings and leads is termed “stray flux heating.” The leakage flux induces eddy current in any conducting material that it passes through. This includes the steel clamping structure, tie rods or tie plates, metal core bands, and the tank wall itself. Since
Chapter 4: Power Transformers
leakage flux varies proportionally with load current, the stray flux heating increases roughly with the square of winding current. For larger power transformers and GSUs in particular, the problem of stray flux heating can be substantial. Special design measures must be taken to reduce the induced currents. The most common areas of stray flux heating problems are tie plates, used to connect the upper and lower core yoke clamping structure, and bushing penetrations. As with lead heating, evaluation of stray flux heating potential is difficult. The best method for assessing stray flux heating problems is by examining the DGA records for the unit for any hint of hot metal gases, specifically methane and ethane. Should either of these gases exceed 120 ppm or 65 ppm, respectively, high loading should be discontinued and the source of the gases investigated. In addition, sudden increases in these gas levels concurrent with increased loading should be considered additional cause for alarm. In addition to DGA, stray flux heating in the tank wall can be evaluated by examining the transformer with an infrared camera. Particular attention should be paid in the area of bushing penetrations and bushing adapters. A visual examination for discolored paint could also reveal stray flux heating. 4.4
THERMAL MODELING
Given the extreme complexities of heat transfer within a transformer, as well as the lack of information typically available, drastic simplifications must be made. It is important to recognize the simplifications and to know the areas in which these simplifying assumptions are not sufficiently accurate. Therefore, this section begins with a brief and somewhat academic overview of the various heat transfer mechanisms involved. Following this, the section describes available thermal models. 4.4.1
Mechanisms of Heat Transfer
In a power transformer, two heat transfer mechanisms are predominant: radiation and convection. Conduction plays a smaller role and will not be described at length here. It should also be noted that even the most modern treatments of the subject are largely empirical. This initial discussion parallels that of Montsinger in (Montsinger 1951), with additional emphasis on variables that may not be constant. Radiation All bodies at a temperature above their surroundings radiate heat energy to the surroundings. The mathematical relationship between heat lost due to radiation and
4-21
Chapter 4: Power Transformers
Increased Power Flow Guidebook
the temperature rise are fairly well known, as shown in Equation 4.4-1 (Cengel 1997)
Qrad = εσA(Tb − Ta ) 4
4
4.4-1
This relationship can be simplified to a simple power relationship of the form shown in Equation 4.4-2.
Qrad = KΔθ x
4.4-2
This relationship, for a given exponent x, is generally valid over a limited temperature range (Figure 4.4-1). The curve fits in Figure 4.4-1 are generally valid from a 0°C rise to about a 70°C rise. The exponents vary from 1.133 for a 0°C ambient to 1.117 for a 40° C ambient. Note that the emissivity will change the multiplicative constant but not the exponent. This relationship could also be expressed inversely as: m Δθ = CQrad
4.4-3
where m = 1/x. For the ranges of x derived above, m varies from 0.883 for a 0 ° C ambient to 0.895 for a 40 ° C ambient. The absorption rate in the infrared region for transparent liquids such as transformer oils is relatively high. Therefore, the radiant energy from transformers windings is absorbed by even a thin layer of oil, and is therefore negligible. Air, on the other hand, has a negligible absorption rate, and radiant energy loss must be considered when determining the heat loss from the tank, and therefore the oil.
Forced Convection When heat is transferred from a solid to a moving fluid medium, the adjacent fluid is heated by conduction. Since the fluid medium is moving, the heated fluid is quickly replaced by cooler fluid. This results in an increased rate of heat transfer than would occur by conduction alone. The heat loss due to convection can be expressed by Newton’s Law of Cooling, as shown in Equation 4.4-4 (Cengel 1997).
Q = hA(Tc − Ta ) 4.4-4 Where: Q is the rate of heat loss. h is the heat transfer coefficient. Tc is the temperature at the surface of the object (solid). Ta is the temperature of the surrounding fluid.
For cross-flow over a cylinder or similar-shaped object (Cengel 1997): ⎛ ρVD ⎞ k ⎟⎟ h = C ⋅ Re Pr ⋅ = C ⋅ ⎜⎜ D ⎝ μ ⎠ m
n
m
⎛ μC p ⎜ ⎜ k ⎝
⎞ ⎟ ⎟ ⎠
n
4.4-5
Where: C is a constant. Re is the Reynold’s Number. Pr is the Prandtl Number. k is the thermal conductivity of the fluid. D is the characteristic length of the immersed object (diameter of cylinder). ρ is the density of the fluid. V is the velocity of the fluid. μ is the viscosity of the fluid (varies with temperature). Cp is the specific heat of the fluid. m, n are constants. From this, it can be seen that h is a function of several parameters, including geometry, fluid velocity, and fluid viscosity. The exponent n is typically 1/3. The exponent m, determined empirically, ranges from about 0.3 to 0.8, depending upon the geometry. Note that if the exponents are equal, the viscosity cancels out and is no longer a factor. Summarizing, the heat loss can be expressed by: Q = KΔθ
4.4-6
or, solving for the temperature rise: Δθ = KQ Figure 4.4-1 Radiative heat transfer at various ambient temperatures.
4-22
4.4-7
Natural Convection Natural convection is slightly more complex than forced convection. The heat transfer is still a function of the
Increased Power Flow Guidebook
Chapter 4: Power Transformers
velocity of the fluid, as described above. However, now the velocity of the fluid is the result a varying fluid density with temperature. This is known as thermosiphon flow. The basic relationship is the same as for forced convection. Q = hA(Tc − Ta )
4.4-8
However, h is now a function of the temperature rise as well. For natural convection along a vertical plate (also applicable to a vertical cylinder), h is given by: h =C ⋅
k k m ⋅ (Gr ⋅ Pr ) = C ⋅ L L
⎛ gρ β (Tc − Ta )L μC p ⎞ ⎟ ⋅⎜ ⋅ ⎜ k ⎟⎠ μ2 ⎝ 2
3
forced convection, the viscosity is generally not a factor. For natural convection, the temperature rise is a function of viscosity as follows: 1 ( m + 1) Δθ = KQ nat ⋅ μ −m
4.4-14
Transient Formulation For any temperature rise, the temperature at any time, t, can be determined by equating the heat input to the sum of the change in heat storage and the heat loss:
Heat generated = Change in heat storage + Heat loss.
m
Q gen = mC p
dθ + KΔθ x dt
4.4-15
4.4-9
m varies from 1/3 to 1/4. Note that h is also a function of viscosity, μ, to the -m power.
Combining the temperature component of h with the equation for convection heat transfer: Q = KΔθ m + 1
4.4-10
Taking the inverse to solve for the temperature rise: 1 ( m + 1) Δθ = KQ nat
4.4-11
Since m varies from 1/3 to 1/4, the exponent in Equation 4.4-11 varies from 0.75 to 0.80. Combined Heat Transfer Summarizing the above discussion, the temperature rise (or, conversely, the heat loss) for a particular mechanism of heat transfer can be expressed in the following form:
Δθ = KQ x
4.4-12
or Q = K Δθ
1
x
4.4-13
Where: Δθ is the temperature rise above the surrounding medium. K is a constant. Q is the heat loss (or gain). x is an exponent that varies with mechanism as shown in Table 4.4-1. The constant K is generally constant over the range of temperatures and materials considered in transformer thermal modeling. The only variable that changes appreciably with temperature is the viscosity of oil. For
Traditionally, transient temperatures have been calculated by approximating an instant of time as a stepchange in load and calculating the temperature at the end of the time step as follows: − Δt ⎛ ⎞ Δθ = Δθ i + (Δθ u − Δθ i )⎜1 − e τ ⎟ ⎜ ⎟ ⎝ ⎠ 4.4-16 Where: Δθ is the calculated temperature at time t + Δt. Δθi is the initial temperature at time t. Δθu is the ultimate steady-state temperature. Δt is the time step. e is the time constant.
This closed form solution to the transient differential equation has several drawbacks. First, it is difficult to correct for the change in losses with temperature. The losses at the ultimate temperature rise are a function of the ultimate temperature. The ultimate temperature is, of course, a function of these losses, requiring an iterative calculation at each time step to find the ultimate temperature rise. In addition, the closed form solution above is only truly correct for heat transfer function with an exponent of 1.0 (i.e., forced convection). A more robust approach is to solve the differential equation using a finite difference approach, as taken by Pierce (Pierce 1994) and Lesieutre (Lesieutre et al. 1997) Table 4.4-1 Exponents for Radiation, and Forced and Natural Convection Mechanism
Exponent
Radiation
0.883-0.895
Forced Convection
1.0
Natural Convection
0.75-0.8
4-23
Chapter 4: Power Transformers
Increased Power Flow Guidebook
Referring to the differential equation above, the difference equation would take the form:
Q gen,2 = mC p 4.4.2
θ 2 − θ1 Δt
+ KΔθ x
temperature, the hot spot temperature, is located at the top of the winding. This hot spot temperature represents the hottest temperature endured by the insulation and therefore the highest aging rate (1995b).
4.4-17
Top Oil Model (IEEE C57.91-1995, Clause 7)
The following is an outline of the temperature calculation methods presented in Clause 7 of IEEE C57.911995 (IEEE 1995b) (Figure 4.4-2). The thermal mechanisms of a transformer are extremely complex and difficult to model. To reduce complexity, the transformer is analyzed as a lumped system, and several assumptions are made. The transformer is essentially reduced to two systems, the bulk oil and the winding, with an additional “hot spot” temperature located at the top of the winding.
The IEEE top oil method relates the steady-state oil temperature rises to the total losses by a power function. The steady-state winding rises are also related to the winding current by a power function. In addition, certain corrections are made to account for additional considerations such as increased mixing due to forced-oil cooling systems and change in winding resistance with temperature. The following is an outline of the temperature calculation method presented in IEEE C57.91-1995, Clause 7. Symbols:
C
The oil temperature is presumed to be lowest at the bottom of the winding. As the oil rises upward along the winding, the oil adjacent to the winding is heated at a constant rate. Therefore, the oil temperature is assumed to increase linearly from the bottom of the winding to the top of the winding, with the highest oil temperature located at the top of the winding. At rated load, the winding temperature distribution is assumed to be higher than the oil temperature distribution by a constant value, Δw, and thus parallel to the oil temperature distribution. Due to stray flux concentration near the top of the winding, a further increase in
is the thermal capacity (Watt-hours/deg C).
WCC is the weight of the core and coils (kg). WTank is the weight of the tank and fittings in contact with the oil (kg). VFluid is the volume of oil (L). τO
is the oil thermal time constant (min).
τw
is the winding time constant (min).
t
is the time (min.).
Δt
is the calculation time step (min).
ΔθTO is the top oil rise over ambient temperature (deg C).
Figure 4.4-2 Graph of temperature rises vs. height for IEEE Clause 7 Model. 4-24
Increased Power Flow Guidebook
Chapter 4: Power Transformers
ΔθHS is the hot spot rise over the top oil temperature (deg C). PT
is the total loss (W).
K
is the load (per unit of the nameplate rating).
R
is the ratio of load loss to no-load loss at the nameplate rating.
m
is the winding temperature rise exponent.
n
is the oil temperature rise exponent.
θHS
is the hot spot temperature (deg C).
θA
is the ambient temperature (deg C).
A combined thermal capacity can be calculated by combining the specific heats of the various component materials with the component weights. However, the components are not at a uniform temperature. The oil temperature varies from the bottom of the tank to the top. For OA (ONAN) and FA (ONAF), the assumption has been made that the mean oil temperature is 76% of the maximum top oil temperature. In addition, 2/3 of the tank weight is used. For OA and FA (ONAN and OFAF), the thermal capacity, C, equals:
C = 0.06 * WCC + 0.04 * WTank + 1.33 * VFluid
4.4-19
Subscripts:
For DFOA and NDFOA (ODAF and OFAF), the thermal capacity, C, equals:
R
indicates a rated quantity.
i
indicates an initial quantity.
U
indicates an ultimate or steady-state quantity.
C = 0.06 * WCC + 0.06 * WTank + 1.93 * VFluid
At top oil temperatures other than rated, the time constant must be corrected as follows:
Oil Thermal Time Constant:
In order to calculate the transient response of the bulk oil, it is necessary to calculate an oil thermal time constant. The thermal time constant of the bulk oil at rated temperature equals:
τO,R = C * ΔθTO,R / PT,R 4.4-18 Where: τO,R is the oil thermal time constant at rated load (min). C is the combined thermal capacity of the transformer (W-min/lbs-C). Δθ TO,R is the measured oil temperature rise over ambient at rated load (C). PT,R is the total loss at rated load (W). The thermal capacity, C , is the combined thermal capacity of all transformer components in contact with the bulk oil. This includes the core, windings, tank and fittings, and the oil itself. The specific heat for each component material is shown in Table 4.4-2.
τ O = τ O, R
⎛ Δθ TO ,U ⎜ ⎜ Δθ ⎝ TO , R ⎛ Δθ TO ,U ⎜ ⎜ Δθ ⎝ TO , R
⎞ ⎛ Δθ TO , i ⎟−⎜ ⎟ ⎜ Δθ ⎠ ⎝ TO , R 1
⎞ n ⎛ Δθ TO , i ⎟ −⎜ ⎜ Δθ ⎟ ⎝ TO , R ⎠
Table 4.4-2 Specific Heat for Copper, Steel, and Oil Specific Heat (W-min/lbs-C)
Copper
0.05
Steel
0.06
Oil
14.6
⎞ ⎟ ⎟ ⎠ 1
⎞n ⎟ ⎟ ⎠
4.4-21
Initial Temperatures:
The following equations are used to calculate the initial temperatures based upon the assumption that the load prior to the calculation period was constant long enough for the temperatures to reach their steady-state limits. This assumption is reasonable if the load is fairly constant for a period of time prior to the overload equal to two to three times the oil thermal time constant.
(
)
⎡ K 2R + 1 ⎤ Δθ TO , i = Δθ TO , R ⎢ i ⎥ ⎣⎢ (R + 1) ⎦⎥ Δθ HS , i = Δθ HS , R ⋅ K i2 m
Material
4.4-20
n
4.4-22
Transient Temperatures:
The following equations are used to calculate the transient temperature rises based upon the oil time constant calculated above, the user-determined winding time constant, load, losses, and initial and ultimate temperature rises. For a graphical representation of the various temperature rises, see Figure 4.4-2.
4-25
Chapter 4: Power Transformers
Increased Power Flow Guidebook
For all cooling modes: The top oil rise at time t2 = t1 + Δt is given by the following: Δθ TO ,U
(
)
⎡ K 2R +1 ⎤ = Δθ TO , R ⎢ U ⎥ ⎢⎣ (R + 1) ⎥⎦
Δθ TO ,2 = (Δθ TO ,U
n
4.4-23
Δt ⎛ − − Δθ TO ,1 )⎜1 − e τ ⎜ ⎝ O
⎞ ⎟ + Δθ TO ,1 ⎟ ⎠
4.4-24
The hot-spot rise over top oil at time t2 = t1 + Δt is given by the following: Δθ HS ,U = Δθ HS , R ⋅ K U2 m Δθ HS ,2 = (Δθ HS ,U
4.4-25
Δt ⎛ − τ ⎜ − Δθ HS ,1 ) 1 − e ⎜ ⎝ W
⎞ ⎟ + Δθ HS ,1 ⎟ ⎠
4.4-26
The hot-spot temperature at time t2 = t1 + Δt is given by:
θ HS ,2 = θ A,2 + Δθ TO ,2 + Δθ HS ,2
4.4-27
The above calculation is repeated for each time step of the overload period, with the initial temperatures rises equal to the temperature rises from the previous time step. In addition, loss-of-life calculations are performed at each time step (IEEE 1995b). 4.4.3
Bottom Oil Model (IEEE C57.91-1995, Annex G)
This model was originally developed by Linden Pierce with GE in the early 1990s based upon detailed temperature measurements on a model coil (Pierce 1992, 1994). The model was included in the 1995 revision of IEEE C57.91 as Annex G (IEEE 1995b). In the top oil model, the hot spot temperature consisted of three components: ambient temperature, top oil rise over ambient, and hot spot rise over top oil (Figure 4.4-3). In the bottom oil model, which is the approach that will be developed here, the hot spot temperature consists of four components: ambient temperature, bottom oil rise over ambient, top-of-duct oil to bottom oil gradient, and hot spot rise over top of duct oil. These components are shown schematically below. In addition to these components, the average winding rise over average duct oil needs to be developed, as the winding losses are a function of this temperature and not the hot spot temperature.
θ HS = θ A + Δθ BO + Δθ DO / BO + Δθ HS / DO
4-26
Average Winding Rise over Average Duct Oil It will be assumed that the temperatures of the winding and the duct oil vary linearly from bottom to top, and both are parallel. This results in a winding temperature rise over adjacent duct oil that does not vary over the height of the winding, and a constant heat flux from the winding to the duct oil. In line with the finite difference transient formulation described above, a heat balance will be developed for the winding-duct oil system.
The heat generated by the winding at time t2 = t1 + Δt is given by: Q gen,W = L2 (PI 2 R ⋅ K W + PE K W )
4.4-29
Where: Qgen,W is the average heat generated by the windings. L is the winding current, in per unit rated. PI2R is the Ohmic losses in the windings due to the winding current at rated current. is the eddy losses in the windings at rated PE current.
⎛ θW ,1 + θ K ⎞ ⎟ KW = ⎜ ⎜θ ⎟ + θ K ⎠ ⎝ W,R 4.4-30 Where: θW,1 is the average winding temperature calculated at the previous time step, t1. θW,R is the average winding temperature at rated load. θK is 234.5°C for copper windings and 225°C for aluminum windings. The heat lost by the windings to the duct oil is dependent upon the mechanism of heat transfer. For ONAN, ONAF, and OFAF, the predominant mode of heat
θDO θHS
θBO
θA
Figure 4.4-3 Components of bottom oil model. 4.4-28
Increased Power Flow Guidebook
Chapter 4: Power Transformers
transfer is natural convection. As outlined above, the heat loss for natural convection can be expressed by: m +1
m
⎛ θW ,1 − θ DO,1 ⎞ ⎛ μW , R ⎞ ⎟ (PI 2 R + PE ) ⎟ ⎜ Qloss ,W = ⎜ ⎟ ⎟ ⎜μ ⎜θ θ − DO , R ⎠ ⎝ W ,1 ⎠ ⎝ W ,R 4.4-31 Where: Qloss,Wis the average heat lost by the windings to the average duct oil. θW,1 is the average winding temperature at the previous time step. θDO,1 is the average duct oil temperature at the previous time step. θW,R is the average winding temperature at rated current. θDO,R is the average duct oil temperature at rated current. μW,R is the oil viscosity at a temperature equal to the average of the average winding temperature and average duct oil temperature at rated load. μW,1 is the oil viscosity at a temperature equal to the average of the average winding temperature and average duct oil temperature at the previous time step. m is a constant, usually between 1/3 and 1/4. For ODAF transformers (directed forced oil), the predominant mode of heat transfer is forced convection. The heat loss for OFAF can then be expressed by:
⎛ θW ,1 − θ DO,1 Qloss,W = ⎜ ⎜θ ⎝ W , R − θ DO, R
⎞ ⎟(PI 2 R + PE ) ⎟ ⎠
4.4-32
Note that it is assumed that the effect of the change in oil viscosity with temperature is negligible for this case. Completing the heat balance, the heat absorbed by the windings is given by:
Qabs ,W = mW C P ,W
(θ
W ,2
− θW ,1 )
Δt 4.4-33 Where: Qabs,W is the heat absorbed by the winding during incremental time step, Δt. mW is the mass of the windings. CP,W is the effective specific heat of the windings. θW,1 is the average winding temperature at time t1. θW,2 is the average winding temperature at time t2 = t1 + Δt. Δt is the incremental time step.
constant calculated from the winding cooldown curves taken during the factory heat run. From the definition of a thermal time constant:
mW C P ,W =
τ W (PI 2 R + PE ) (θW , R − θ DO, R )
4.4-34
Summing the three terms of the heat balance and solving for θW,2:
θW , 2 =
(Q
gen,W
− Qloss ,W )Δt
mW C P ,W
+ θW ,1 4.4-35
Duct Oil Gradient over Bottom Oil The oil entering the winding ducts is at a temperature equal to the bottom oil temperature. The oil is then heated as it rises up the winding duct, either by forced oil flow or natural thermosiphon flow. The temperature at the duct exit, for a constant heat flux along the duct, is dependent upon the mass flow rate, as follows:
Te = Ti +
q s As
ρVAcC P
4.4-36
Where: Te is the temperature of the fluid exiting the duct. Ti is the temperature of the fluid entering the duct. qs is the constant heat flux along the duct. As is the surface area of the duct. ρ is the density of the fluid. V is the fluid velocity (average). Ac is the cross-sectional area of the duct. Cp is the specific heat of the fluid. For ODAF, the mass flow rate through the duct remains essentially constant for varying load levels. For ONAN, ONAF, and OFAF, the oil flow through the duct is by natural thermosiphon flow. The flow rate through the duct in these cases is a complex function of the temperature rise in the duct, the temperature drop through the radiators, and the relative height of the windings and the radiators. The temperature rise in the duct, in turn, is a function of the mass flow rate through the duct (Figure 4.4-4). Lacking sufficient data, the following simple approach will be taken, relating the temperature rise through the vertical ducts (top-of-duct oil – bottom oil) to the loss by an exponent, y, as follows:
Δθ DO / BO,2 = H HS ⋅ Δθ TDO / BO, R * L2 y
4.4-37
Where: ΔθDO/BO is the duct oil rise over bottom oil.
The term mWCP,W is usually not known directly. Instead, this term can be calculated from a winding thermal time 4-27
Chapter 4: Power Transformers
Increased Power Flow Guidebook
that, for ONAN, ONAF, and ODAF, this value is equal to the rated top oil rise. For OFAF, Pierce suggests using the average winding rise. These recommendations appear to be based upon the tests of the model coil in (Pierce 1992). Hot Spot Rise over Top Duct Oil By following a development similar to the average winding rise over average duct oil, only considering an incremental portion of the winding at the hot spot (top of winding), the hot spot temperature rise over top duct oil can be calculated.
The heat generated by the winding at the hot spot at time t2 = t1 + Δt is given by: Figure 4.4-4 Oil flow throughout the duct.
Q gen, HS = L2 (PI 2 R ⋅ K HS + PE K HS )
4.4-38
is the height of the winding hot spot in per unit of the winding height (1.0 = top). ΔθTDO/BO,R is the top-of-duct oil rise over bottom oil at rated load (see discussion below). L is the per unit load. y is an exponent.
Where: Qgen,HS is the heat generated by the windings at the hot spot. L is the winding current, in per unit rated. PI2R is the Ohmic losses in the windings due to the winding current at rated current. PE is the eddy losses in the windings at rated current.
In almost all cases, it can be assumed that the hot spot is at the top of the winding, and hence adjacent to the top duct oil temperature, making HHS equal to 1.0. The data from tests done on model coils in Pierce (1994) suggests that, for most cases, the hot spot is within the top 10% of the winding. When the increased eddy loss at the top of the winding is factored in, the hot spot should be even closer to the top, most often within a few turns or disc sections. However, HHS has been included to allow the engineer to assume a hot spot position below the top of the winding.
⎛ θ HS ,1 + θ K ⎞ ⎟ K HS = ⎜ ⎟ ⎜θ + θ HS , R K ⎠ ⎝ 4.4-39 Where: θHS,1 is the winding hot spot temperature calculated at the previous time step, t1. θHS,R is the winding hot spot temperature at rated load. θK is 234.5°C for copper windings and 225°C for aluminum windings.
HHS
The exponent, y, is as yet undetermined. Lacking measured data, the values given by Pierce (1994) can be used. For ONAN, ONAF, and OFAF, y is given as 0.5. For ODAF, y is given as 1.0. Since the mass flow rate does not change for ODAF over varying loads and the heat flux is proportional to the losses, the exponent of 1.0 for ODAF should be correct. For the other cooling modes, however, the mass flow rate is a function of both the oil temperatures within the duct and the oil temperatures in the bulk oil and radiators. Therefore, a more complex relationship is needed. The temperature of the oil exiting the ducts, expressed as the rise over bottom oil ΔθDO/BO, at rated load is difficult to determine. It cannot be measured easily. Even when measurements are made, the values vary considerably for the various vertical ducts around the circumference of the winding (Pierce 1992). Pierce (1994) suggests
4-28
The heat lost by the windings to the duct oil is dependent upon the mechanism of heat transfer. For ONAN, ONAF, and OFAF, the predominant mode of heat transfer is natural convection. As outlined above, the heat loss for natural convection can be expressed by: Qloss , HS
⎛ θ HS ,1 − θ DO,1 =⎜ ⎜θ ⎝ HS , R − θ DO, R
⎞ ⎟ ⎟ ⎠
m +1
⎛ μ HS , R ⎜ ⎜μ ⎝ HS ,1
⎞ ⎟ ⎟ ⎠
m
(PI 2R
+ PE ) 4.4-40
Where: Qloss,HS is the heat lost by the winding hot spot to the top duct oil. θHS,1 is the winding hot spot temperature at the previous time step. θDO,1 is the duct oil temperature at the previous time step. θHS,R is the winding hot spot temperature at rated current.
Increased Power Flow Guidebook
Chapter 4: Power Transformers
θDO,R is the duct oil temperature at rated current. μHS,R is the oil viscosity at a temperature equal to the average of the winding hot spot temperature and top. μHS,1 is the oil viscosity at a temperature equal to the average of the winding hot spot temperature and top duct oil temperature at the previous time step. m is a constant, usually between 1/3 and 1/4.
For ODAF transformers (directed forced oil), the predominant mode of heat transfer is forced convection. The heat loss for OFAF can then be expressed by: ⎛ θ HS ,1 − θ DO,1 Qloss, HS = ⎜ ⎜θ ⎝ HS , R − θ DO, R
⎞ ⎟(PI 2 R + PE ) ⎟ ⎠
4.4-41
Note that it is assumed that the effect of the change in oil viscosity with temperature is negligible for this case. Completing the heat balance, the heat absorbed by the windings is given by: Q abs, HS = mW C P ,W
(θ
HS ,2
− θ HS ,1 ) Δt
4.4-42
Where, Qabs,HS is the heat absorbed by the winding during incremental time step, Δt. mW is the mass of the windings. CP,W is the effective specific heat of the windings. θHS,1 is the average winding temperature at time t1. θHS,2 is the average winding temperature at time t2 = t1 + Δt. θt is the incremental time step. Summing the three terms of the heat balance and solving for θHS,2:
θ HS ,2 =
(Q
gen , HS
)
− Qloss, HS Δt
mW C P ,W
+ θ HS ,1
The heat generated by the active assembly (core and coils) at the hot spot at time t2 = t1+ Δt is given by: Q gen, O = L2 (PI 2 R ⋅ K W + (PE + PS ) K W ) + PC
4.4-44
Where: Qgen,O is the heat generated within the transformer. L is the winding current, in per unit rated. PI2R is the Ohmic losses in the windings due to the winding current at rated current. PE is the eddy losses in the windings at rated current. PS is the stray loss. PC is the core (no-load) loss. ⎛ θW ,1 + θ K ⎞ ⎟ KW = ⎜ ⎜θ ⎟ + θ W , R K ⎝ ⎠ 4.4-45 Where: θW,1 is the average winding temperature calculated at the previous time step, t1. θW,R is the average winding temperature at rated load. θK is 234.5°C for copper windings and 225°C for aluminum windings.
The heat loss is given by: Qloss , AO
⎛ θ AO ,1 − θ A,1 =⎜ ⎜θ ⎝ AO, R − θ A, R
⎞ ⎟ ⎟ ⎠
1
y
PT 4.4-46
Where: Qloss,AO is the heat lost by the bottom oil to the surrounding air. θA,1 is the ambient temperature at the previous time step. θA,R is the ambient temperature during the heat run. θAO,1 is the average oil temperature at the previous time step. θAO,R is the average oil rise at rated load. y is an exponent equal to 0.8 for ONAN, 0.9 for ONAF and OFAF, 1.0 for ODAF.
4.4-43
Bottom and Top Bulk Oil Rise Pierce (1994) calculates the average oil rise and then applies a top-to-bottom oil gradient to that average oil rise. This gradient is calculated as a function of the losses raised to an exponent. This exponent is given by Pierce (1994) as 0.5 for ONAN and ONAF, and 1.0 for OFAF and ODAF.
Completing the heat balance, the heat absorbed by the bulk oil is given by: Qabs , AO = ∑ mC P
(θ
AO ,2
− θ AO ,1 )
Δt 4.4-47 Where: Qabs,AO is the heat absorbed by the average bulk oil during incremental time step, Δt. θAO,1 is the average bulk oil temperature at time t1. θAO,2 is the average bulk oil temperature at time t2 = t1 + Δt. Δt is the incremental time step.
4-29
Chapter 4: Power Transformers
Increased Power Flow Guidebook
The value ΣmCP is a sum of product of the masses of the transformer in contact with the oil, as well as the oil itself, and the specific heat of those components:
∑ mC
P
4.4.4
The IEC 354-1991 (McNutt 1992) model is similar to the IEEE Clause 7 model (Figure 4.4-5). The two models differ in a few important respects. First, the calculation of the rated hot spot rise is done by applying a “hot spot factor” to the average winding rise over average oil temperature gradient. This “hot spot factor” is a design specific constant that generally varies between 1.0 and 1.4, with 1.2 being typical for power transformers.
= C P , steel (WC & C + WTank ) + C P , fluidW fluid 4.4-48
Summing the three terms of the heat balance and solving for θAO,2:
θ AO ,2 =
(Q
gen , O
− Qloss, AO )Δt
∑ mC P
+ θ AO ,1
Note: The winding temperature rise exponent in this document differs slightly from that described in IEC 354. The equations listed below apply a multiple of 2 to this exponent, whereas in IEC 354, this multiple is included in the exponent definition. Therefore, the winding temperature rise exponent listed here is equal to half of the winding temperature rise exponent in IEC 354.
4.4-49
Once the average bulk oil temperature has been determined, a top-to-bottom bulk oil gradient must be calculated. This is done by the following equation:
θ TO / BO = (θ TO , R
⎛ Qloss , AO ⎞ ⎟ − θ BO , R )⎜ ⎜ Q gen, O Δt ⎟ ⎠ ⎝
z
Oil Thermal Time Constant: 4.4-50
Where, θTO/BO is the top-to-bottom bulk oil gradient, C. θTO,R is the top oil rise at rated load, C. θBO,R is the bottom oil rise at rated load, C. Δt is the incremental time step. z is an exponent (0.5 for ONAN, ONAF; 1.0 for OFAF, ODAF). The top and bottom oil temperatures are then solved for by adding and subtracting, respectively, half of the topto-bottom bulk oil gradient:
θ TO = θ AO +
θ BO = θ AO −
θ TO / BO 2
4.4-51
θ TO / BO 2
IEC Model (IEC 354-1991)
In order to calculate the transient response of the bulk oil, it is necessary to calculate an oil thermal time constant. Since IEC 354 does not include this information, the IEEE C57.91-1995 equations can be offered as an option:
(
0.1 ) 1.108
For OA and FA (ONAN and OFAF), the thermal capacity, C, equals: C = 0.0272 * WCC + 0.01814 * WTank + 5.034 * VFluid (1) (IEEE Clause 7) 4.4-53
For DFOA and NDFOA (ODAF and OFAF), the thermal capacity, C, equals: C = 0.0272 * WCC + 0.0272 * WTank + 7.305 * VFluid (2) (IEEE Clause 7) 4.4-54
4.4-52
Figure 4.4-5 Diagram illustrating assumed temperature profile within transformer for IEC model. 4-30
Increased Power Flow Guidebook
Chapter 4: Power Transformers
The thermal time constant of the bulk oil at rated temperature equals: τO,R = C * ΔθTO,R / PT,R (3) (IEEE Clause 7)
4.4-55
At top oil temperatures other than rated, the time constant must be corrected as follows:
τ O = τ O, R
⎛ Δθ TO ,U ⎜ ⎜ Δθ ⎝ TO , R
⎞ ⎛ Δθ TO , i ⎟−⎜ ⎟ ⎜ Δθ ⎠ ⎝ TO , R 1
⎛ Δθ TO ,U ⎞ n ⎛ Δθ TO , i ⎟ −⎜ ⎜ ⎜ Δθ ⎟ ⎜ Δθ ⎝ TO , R ⎝ TO , R ⎠ (4) (IEEE Clause 7)
⎞ ⎟ ⎟ ⎠ 1
⎞n ⎟ ⎟ ⎠
The top oil rise at time t2 = t1 + Δt is given by the following:
(
)
n
⎡ K 2R +1 ⎤ Δθ TO ,U = Δθ TO , R ⎢ U ⎥ ⎢⎣ (R + 1) ⎥⎦ (8) (IEC 2.4.1, Equation 1) Δt ⎛ − τO ⎜ Δθ TO ,2 = (Δθ TO ,U − Δθ TO ,1 ) 1 − e ⎜ ⎝ (9) (IEC 2.5)
4.4-60
⎞ ⎟ + Δθ TO ,1 ⎟ ⎠ 4.4-61
The hot-spot rise over top oil at time t2 = t1 + Δt is given by the following: 4.4-56
Initial Temperatures:
Δθ HS ,U = Hg R ⋅ K U2 m
(10) (IEC 2.4, Equation 1+2)
The following equations are used to calculate the initial temperatures based upon the assumption that the load prior to the calculation period was constant long enough for the temperatures to reach their steady-state limits. This assumption is reasonable if the load is fairly constant for a period of time prior to the overload equal to two to three times the oil thermal time constant. ⎡ K 2R + 1 ⎤ Δθ TO , i = Δθ TO , R ⎢ i ⎥ ⎢⎣ (R + 1) ⎥⎦ (5) (IEC 2.4.1, Equation 1)
(
)
n
⎡ K R +1 ⎤ Δθ BO , i = Δθ BO , R ⎢ ⎥ ⎣⎢ (R + 1) ⎦⎥
)
n
(
2 i
4.4-57
(6) (IEC 2.4.2, Equation 2)
In addition, for DFOA (ODAF) cooling modes a correction factor is applied to account for the change in winding Ohmic losses due to temperature as follows:
θ HS ,U ′ = θ HS ,U + 0.15(θ HS ,U − θ HS , R ) (11) (IEC 2.4.3, Equation 3)
4.4-63
For other types of cooling, the change in winding Ohmic losses is negligible. Note that the IEEE method neglects the change in winding resistance with temperature for all cases, assuming that this change is always offset by the change in oil viscosity with temperature. The transient hot spot rise is then:
4.4-58
Δθ HS , i = Hg R ⋅ K i2 m
(7) (IEC 2.4, Equation 1+2)
4.4-62
Δθ HS ,2 = (Δθ HS ,U
4.4-59
g is difference between average winding and average oil temperatures. H is a multiplier that equals 1.3.
Hg is the hot spot rise above top oil. Transient Temperatures:
The following equations are used to calculate the transient temperature rises based upon the oil time constant calculated above, the user-determined winding time constant, load, losses, and initial and ultimate temperature rises. For a graphical representation of the various temperature rises, see Figure 4.4.5. For OA and FA (ONAN and ONAF) cooling modes:
Δt ⎛ − τW ⎜ − Δθ HS ,1 ) 1 − e ⎜ ⎝
(12) (IEC 2.5)
⎞ ⎟ + Δθ HS ,1 ⎟ ⎠ 4.4-64
The equation form is the same as IEEE if the hot spot rise over top oil term is calculated with the IEC method. Note that the IEC method calculates the hot spot rise over top oil temperature at rated load through the use of a multiplier, H, applied to the difference between the average winding temperature from test and the average top oil temperature from test. For power transformers, H is typically approximately 1.3. The hot-spot temperature at time t2 = t1 + Δt is given by:
θ HS ,2 = θ A,2 + Δθ TO ,2 + Δθ HS ,2 (13) (IEC 2.4.1, Equation 1)
4.4-65
4-31
Chapter 4: Power Transformers
Increased Power Flow Guidebook
For NDFOA and DFOA (OFAF and ODAF) cooling modes: For forced-oil cooling modes, the increased mixing introduced by the forced circulation of the oil increases the complexity of the model. The top oil temperature leaving the winding is greater than the measured top oil. Therefore, the top oil temperature leaving the winding is calculated using the sum of the ambient temperature, the bottom oil temperature rise, and the difference between the top oil and the bottom oil rises. Note that this differs from the IEEE methodology. The IEEE method assumes that the measured top oil temperature is equal to the temperature of the oil leaving the top of the winding for all cooling modes. The bottom oil rise at time t2 = t1 + Δt is given by:
(
)
Rather than taking an analytical approach to the problem, as had been taken by Pierce with the IEEE Annex G model, the authors of the model took the approach of applying corrective factors and multiple time constants. The constants would be adjusted empirically to fit measured temperature data. Like the IEEE Clause 7 model, the revised IEC model lumps the hot spot temperature into a top oil rise over ambient and a hot spot rise over top oil.
θ HS = θ A + Δθ TO + Δθ HS / TO
4.4-71
n
⎡ K R +1 ⎤ Δθ BO ,U = Δθ BO , R ⎢ ⎥ ⎢⎣ (R + 1) ⎥⎦ (14) (IEC 2.4.2, Equation 2) Δt ⎛ − τO ⎜ Δθ BO ,2 = (Δθ BO ,U − Δθ BO ,1 ) 1 − e ⎜ ⎝ (15) (IEC 2.5) 2 U
this new model recognized that the hot spot temperature increases more rapidly initially than is currently predicted with traditional equations. This is commonly attributed to an increase in the duct oil that occurs more quickly than the increase in bulk oil. This phenomenon they have dubbed the "hot spot bump" (see Figure 4.4-6).
4.4-66
⎞ ⎟ + Δθ BO ,1 ⎟ ⎠ 4.4-67
The top-to-bottom oil rise at time t2 = t1 + Δt is given by the following: Δθ T − BO ,U = Δθ T − BO , R K U2 m
The computation of the constituent rises is a complex arrangement of factors and time constants. The intent of these factors is to simulate the “hot spot bump” by inclusion of an additional exponential term in the calculation of the hot spot rise over top oil. The calculation of the top oil temperatures proceeds in a similar fashion to the IEEE Clause 7 model. First, the ultimate top oil temperature for the given load level is calculated: x
(16) (IEC 2.4.2, Equation 2)
4.4-68
⎛ − Δθ T − BO ,2 = (Δθ T − BO ,U − Δθ T − BO ,1 )⎜1 − e τ W ⎜ ⎝ (17) (IEC 2.5)
Δt
⎞ ⎟ + Δθ T − BO ,1 ⎟ ⎠ 4.4-69
The hot-spot rise above top oil, ΔθHS, is calculated using the same equations as used for OA and FA cooling modes described above.
⎡ K 2 R + 1⎤ Δθ TO ,U = Δθ TO , R ⎢ ⎥ ⎣ R +1 ⎦ 4.4-72 Where: ΔθTO,U is the ultimate top oil temperature rise, C. ΔθTO,R is the rated top oil temperature rise, C. K is the per unit load. R is the ratio of load losses to no-load losses. x is a constant exponent.
The hot-spot temperature at time t2 = t1 + Δt is given by:
θ HS ,2 = θ A,2 + Δθ BO ,2 + Δθ T − BO ,2 + Δθ HS ,2 (18) (IEC 2.4.2, Equation 2)
4.4-70
The above calculation is repeated for each time step of the overload period, with the initial temperatures rises equal to the temperature rises from the previous time step. In addition, loss-of-life calculations are performed at each time step (IEEE 1995b). 4.4.5
Proposed IEC Model
The proposed IEC model (IEC 1991) takes a bit of a radical departure from the earlier models. The authors of 4-32
Figure 4.4-6 Example of “hot spot bump.”
Increased Power Flow Guidebook
Chapter 4: Power Transformers
The transient top oil rise is then calculated by the following equation (note the additional constant applied to the time constant): Δθ TO ,2 = Δθ TO ,1 + (Δθ TO ,U
− Δt ⎛ k 11τ O ⎜ − Δθ TO ,1 ) 1 − e ⎜ ⎝
⎞ ⎟ ⎟ ⎠
The hot spot rise over top oil is then calculated. The ultimate hot spot rise over top oil is calculated in the traditional manner: 4.4-74
Where: ΔθHS/TO,U is the ultimate hot spot rise over top oil, C. ΔθHS/TO,R is the rated hot spot rise over top oil, C (IEC defines this as H*g, where H is a hot spot factor between 1.1 and 1.5 and g is the average winding to average oil gradient). K is the load in per unit. y is a constant exponent. The most significant difference between this new IEC model and more traditional calculations is in the transient formulation of the hot spot rise over top oil. The new IEC model breaks the rise into two components with different time constant, one on the order of the winding time constant and the other on the order of the oil time constant. The transient hot spot rise over top oil is calculated as follows for increasing load: Δθ HS / TO ,2 = Δθ HS / TO ,1 + (Δθ HS / TO ,U − Δθ HS / TO ,1 ) − Δt ⎡ ⎛ ⎢k21 ⎜1 − e k 22τ W ⎢ ⎜ ⎣ ⎝
− Δt ⎞ ⎛ ⎟ − (k − 1)⎜1 − e τ O / k 22 21 ⎟ ⎜ ⎠ ⎝
⎞⎤ ⎟⎥ ⎟⎥ ⎠⎦
ONAN
ONAF
OFAF
Oil exponent, x
0.8
0.8
1.0
1.0
Winding exponent, y
1.3
1.3
1.3
2.0
4.4-75
Where: ΔθHS/TO,2 is the hot spot rise over top oil at the current time step, C. ΔθHS/TO,1 is the hot spot rise over top oil at the previous time step, C. k21 & k22 are transformer specific constants. Δt is the time step, minutes. τW is the winding thermal time constant, minutes. τO is the oil thermal time constant, minutes. For decreasing loads, the effects of thermal capacity are ignored, and the hot spot rise over top oil is taken as the
ODAF
Constant k11
0.5
0.5
1.0
1.0
Constant k21
2.0
2.0
1.3
1.0
Constant k22
2.0
2.0
1.0
1.0
Oil Time Constant (min)
210
150
90
90
Winding Time Constant (min)
10
7
7
7
4.4-73
Where: ΔθTO,2 is the top oil temperature rise at the current time step, C. ΔθTO,1 is the top oil temperature rise at the previous time step, C. Δt is the time step, minutes. k11 is a transformer specific constant. τO is the oil thermal time constant, minutes.
Δθ HS / TO ,U = Δθ HS / TO , R K y
Table 4.4-3 Suggested Values for Constants in Revised IEC Model
ultimate hot spot rise over top oil. The individual terms are then summed to give the hot spot temperature:
θ HS = θ A + Δθ TO + Δθ HS / TO
4.4-76
The various k-constants and the exponents x and y are transformer specific. The recommended method for determining these values is via extrapolation from the heating curves of a prolonged factory heat run test. This information would not be available for existing transformers, and it is unclear whether it could even be derived using standard factory heat run procedures. In lieu of measured values, Table 4.4-3 provides suggested values. 4.5
THERMAL RATINGS
To this point, this chapter has examined the risks of increased loading and determined ways to predict the pertinent equipment temperatures. Now a method for maintaining reasonable risk levels under everyday operation must be developed. The manner in which transformer ratings are calculated and communicated varies from utility to utility, depending upon operating procedures. Thermal ratings are used for various purposes, ranging from planning to operation. The form and complexity of the presentation of calculated ratings vary with the preference of the user. The loading of transformers is ultimately an economical decision. The increased risk of failure and reduced usable life must be balanced with the capital investment of the unit and, to a smaller degree, increased maintenance costs. In addition, the impact of the loss of the unit on the integrity of the system must be factored in. Therefore, the ultimate decision on rating limits is up to the individual utility. Presented here are general recommendations. Ratings can be viewed as a function of several factors:
• Ambient temperature —magnitude —diversity
• Load Shape (diversity) • Pre-Load 4-33
Chapter 4: Power Transformers
• Rating Duration Power transformer ratings are traditionally calculated over a 24-hour period. The general procedure is to calculate the temperatures and loss-of-life over the 24-hour period and compare these to pre-selected limits. The load is adjusted accordingly such that none of the limits is exceeded and one or more limits are met. This is then the definition of the rating. The steps to calculating the rating are as follows: 1. Determine initial temperatures. Since transformers have a significant thermal capacity, the initial temperatures prior to the rating become an important factor, particularly with rating durations less than twice the oil thermal time constant. Therefore, the initial operating temperatures of the transformer must be estimated by some means. The initial temperatures can be estimated directly (possibly from measured temperatures) or calculated by calculating the temperatures at the end of a 24-hour period of assumed loading. 2. Calculate equipment temperatures and loss-of-life for rating period. Using any available means, such as those outlined in Section 4.4, the operating temperatures, principally hot spot and top oil, are calculated throughout the rating period. In addition, loss-of-life is calculated. 3. Compare maximum temperatures and loss-of-life from Step 2 to selected limits. 4. Adjust load level and return to Step 2. 4.5.1
Ambient Air Temperature Obviously, the ambient air temperature is a major factor in the load capacity of a power transformer (Figure 4.5-1). Each degree that average 24-hour air temperature is below 30°C represents additional capacity. Therefore, seasonal variations in air temperature can be used to give higher thermal ratings for cooler periods.
Increased Power Flow Guidebook
Seasonal Variation Depending upon geographical location, the temperature can vary widely between seasons. This allows for increased capacity during cooler months. Depending upon the nature of the load, this can be a significant advantage, especially in cooler climates. If the load is largely heating and lighting loads, then the peak system loading tends to occur in the winter, when ambients are the lowest and thermal capacity the highest. On the flip side, in areas with summer peaking loads, the peak load coincides with the peak ambient temperatures and consequently the minimum capacity periods.
Often times, users produce thermal ratings based upon seasonal peak or average ambients. This allows the user to take advantage of the additional capacity during periods where the ambient is below the rated ambient. Ratings of this kind are simple and safe. Significant additional capacity can be realized without even exceeding the rated hot spot temperature of 110°C. Diurnal Variation Diurnal variations in ambient temperature are often predictable. Due to the thermal capacity of the transformer, cyclic variations in ambient temperature can be used to advantage. Measurement Ambient temperature should be measured as close as possible to the transformer. Ideally, one would want the temperature of the air in the vicinity of the radiators or heat exchangers. This is generally not practical. Temperatures measured within the substation should be sufficient. Weather bureau data may be used with the understanding that temperatures can vary significantly over a short distance.
For transformers located in any sort of enclosure such as a kiosk or vault, temperatures should be used that are measured in the vicinity of the transformer. If this is not possible, an offset should be added to the ambient temperature to account for the increased local temperatures. 4.5.2
Load
Pre-load For transient ratings, the thermal mass of the transformer makes the rating dependent upon the initial temperatures at the start of the rating period. These initial temperatures are governed by the loading for the previous 24 hours. Therefore, for rating durations less than approximately twice the oil thermal time constant, preload is a significant factor. An illustration of this is shown in Figure 4.5-2. Figure 4.5-1 Example plot of rating vs. air temperature for various durations with pre-load = 0.7 PU. 4-34
Load Shape Also due to the long thermal time constant of the transformer, load shape can be a factor in rating calculations.
Increased Power Flow Guidebook
Chapter 4: Power Transformers
A load shape that is flat will achieve higher temperatures than a diverse (large difference between minimum and maximum) load shape for a given peak magnitude. This can often be used to advantage if the loading on a particular unit is cyclic and predictable.
length of the oil time constant makes this definition a bit unclear given the cyclic variation in load and air temperature. For the sake of discussion and throughout this chapter, a long-term emergency rating is defined as a rating greater than 4 hours in duration.
4.5.3
Short-Term Emergency As with LTEs, the definition of short-term emergency ratings (STE) varies. Short-term ratings are usually defined as extremely short duration ratings that take advantage of the thermal capacity of the equipment. These ratings range from a few minutes in duration to a few hours. In this document, STEs are defined as ratings 4 hours and less. An example of a 4-hour STE rating is shown in Figure 4.5-3, demonstrating the pre-load, rating period, and post contingency period.
Rating Type and Duration
A thermal rating is a statement of the load capability of a transformer under a given set of conditions. These conditions represent various typical operating scenarios that a system operator may run into. The system operator then selects the rating scenario that most represents the current operating scenario to determine the load capability of the transformer for the current operating scenario. Depending upon the application of the transformer, the system conditions impacting the transformer, and company operating policies, various rating scenarios may be developed. However, these rating scenarios can generally be lumped into three categories: - Long-term emergency (LTE)
It is important to note here that short-duration ratings are highly sensitive to the inaccuracies in the transient temperature modeling of transformers. Therefore, caution should be exercised when calculating ratings less than 1 hour in duration.
- Short-term emergency (STE)
4.5.4
Normal Life-Expectancy Loading Normal life-expectancy loading represents the normal operating state of the transformer. A transformer represents a large capital investment, and therefore it makes good business sense to get a full life expectancy out of the unit. Increased temperatures result in accelerated aging rates, and therefore a lower return on investment. The “normal rating” represents the load limit for continuous operation.
As a guideline, the following procedure for initial rating or re-rating of a transformer is proposed.
- Normal life-expectancy loading
Long-Term Emergency The definition of a long-term emergency rating (LTE) varies within the industry. Typically, it denotes a rating where the thermal capacity of the equipment does not greatly impact the rating. For power transformers, the
Figure 4.5-2 Example plot of rating vs. pre-load for various rating durations.
Rating Procedure
1. Gather information Information essential to the loading calculations must be gathered. This information must include, at minimum, the factory test report and the nameplate drawing. It is highly recommended that maintenance history (DGA, oil quality, etc.) and loading history be obtained. Outline drawings may be of use as well. 2. Assess condition The full scope of this step is beyond this guide; however, it is important to recognize the importance of condition. Guidelines for condition assessment with regard to loading are given below.
Figure 4.5-3 Example 4 Hr STE rating.
4-35
Chapter 4: Power Transformers
Increased Power Flow Guidebook
3. Examine long-term risks When considering a particular loading event, the first things examined are the long-term risks. This mainly consists of evaluating the loss of insulation life outlined above. This is an economic decision, balancing the cost benefit of the increased load levels with the decreased return on capital investment. If the loading is short duration, the loss of life may be negligible, and therefore the only concern is avoiding immediate failure. 4. Examine short-term risks If the increased life consumption is acceptable, the concern then shifts to avoiding immediate failure. This means limiting operating temperatures, particularly hot spot temperature. 5. Check auxiliary equipment Most of the attention when presented with a potential overload scenario is on the oil and winding temperatures. However, the auxiliary equipment (bushing, LTCs, etc.) should not be neglected. While these should be sized properly to avoid limiting the transformer rating, this is not guaranteed. Before proceeding with increased loading, it is often advisable to verify the thermal capability of these devices. 6. Follow-up post loading Once the decision has been made to permit with increased loading, any significant overload events should be followed up with a site inspection and oil analysis. This should be done to verify that there were no unintended consequences of the increased loading event and to determine suitability for future overload. 4.5.5
Condition-Based Loading
Rather than proposing a static set of limits for various loading situations, a condition-based methodology is presented here. Limits are first given for healthy transformers. These are to be viewed as maximum limits.
These maximum limits are then reduced based upon the assessed condition of the unit. Conditions necessitating the reduction of the temperature limits include:
• • • •
moisture content of bulk insulation oxygen content gassing history criticality of service
For this guide, three condition categories are proposed: Good, Moderate, and Marginal. Transformers are placed in each category using the several different criteria outlined above. The lowest category for any particular criterion is the category for the unit. For example, if a unit has an Ethylene content of less than 36 ppm, but has a moisture content of 2%, the unit falls in the “Marginal” category (Table 4.5-1). Once the unit has been placed in a condition category, the criticality of service, or the impact of failure, should be considered. If the unit is crucial to system integrity, or is the only GSU for a generation plant with no spare, it may be advisable to use the rating limits for a “Moderate” or “Marginal” unit, even if the condition suggests “Good.” The rating limits for each condition category are given in Table 4.5-2. These should be taken as guideTable 4.5-1 Criteria for Condition Categories Used to Determine Rating Limits Good
Moderate
Moisture
< 0.5%
0.5%-1.5%
Marginal > 1.5%
Oxygen
< 3% TDG
3%-5% TDG
> 5% TDG
Methane
< 120 ppm
120-400 ppm
> 400 ppm
Ethane
< 65 ppm
65-100 ppm
> 100 ppm
Ethylene
< 50 ppm
50-100 ppm
>100 ppm
Table 4.5-2 Condition-Based Rating Limits for Transformers Condition
GOOD
MODERATE
MARGINAL
4-36
Normal
LTE (> 4 hrs)
Top Oil
95
105
STE (< 4 hrs) 110
Hot Spot
120
140
160
LOL (hrs)
24
-
STE (< 4 hrs)
Normal
LTE (> 4 hrs)
Top Oil
95
105
105
Hot Spot
120
130
140
LOL (hrs)
24
-
-
Normal
LTE (> 4 hrs)
STE (< 4 hrs)
Top Oil
95
100
100
Hot Spot
110
120
120
LOL (hrs)
24
-
-
Increased Power Flow Guidebook
lines and not necessarily as God-given rules. Each user has different policies and risk tolerances. 4.5.6
Maintenance Considerations
Given the multitude of unknowns in loading power transformers, it is essential that increased vigilance be exercised. The reasons for this are twofold. First, the assumptions made in evaluating the risks of loading need to be verified. Second, the unit must be maintained in top working order to prevent conditions that may be exacerbated by increased loading. Throughout the thermal rating process, assumptions are made to turn a problem of enormous complexity into a manageable process. This is what distinguishes engineering from science. The most important of these assumptions are the location of the ther mally limiting temperature near the top of the winding, adequately sized and applied leads, and proper construction and design. These assumptions need to be verified in some manner. Direct measurement of the temperatures of the winding is impossible unless fiber optic probes had been installed during manufacture. Even with the probes installed, this does not preclude the existence of an unintended hot spot elsewhere in the transformer. Increased Preventive Maintenance One often neglected consideration in the loading of transformers is the need for increased maintenance. The cooling equipment must be maintained in top working order. Loss of even partial cooling could be disastrous. If a unit were loaded to the nameplate rating of the highest cooling mode of an OA/FA/FA and all cooling fans were lost, the unit would be overloaded by roughly 66%, resulting in temperatures exceeding 200°C. In addition, various components will age or wear more quickly.
Prior to initial re-rating or increased load, a field inspection should be scheduled. At this time, the unit should be subjected to careful scrutiny. In particular, the following should be checked:
• Make sure all pumps and fans are operational. Manually switch the cooling on and off to ensure proper operation. Listen to the pumps, if possible, for sounds of cavitation. Occasionally, phases on the pumps are reconnected in the wrong phase order, causing the pump to run in reverse. Note the position of all radiator valves. If a radiator or bank of radiators is valved off, do not open the valve. Make a note of this, and derate the unit accordingly.
Chapter 4: Power Transformers
• Calibrate and check all gauges. This is particularly important if the cooling equipment is switched on/off by the temperature gauges. Oil temperature should be double-checked by placing a handheld thermocouple on the tank wall as close to the thermal well as safety allows. Once the oil gauge has been calibrated, the estimated hot spot temperature should be calculated for the measured top oil temperature and the given load. The ratio of the CT feeding the heating element of the analog WTI (winding temperature indicator) (if equipped) should be adjusted until the gauge reads the calculated value. Finally, check that all snap switches or setpoints for cooling switching and alarms are properly set. Be sure the alarm and trip settings coincide with appropriate rating limits. Calculated ratings do no good if the unit will trip at lower temperatures!
• Check the oil level. Make sure the oil is at the level specified in the operating manual for the measured oil temperature. As mentioned previously, oil will expand with increasing temperature. Too much oil will result in operating of the pressure relief device and expulsion of oil. Too little oil could result in exposing the active assembly upon cooling.
• Check all gasketed surfaces for leaks. Specifically, check the bushings, both at the tank cover and at the top of the bushing, and any other tank penetrations. Gaskets in particular will harden and become brittle more rapidly than at normal operating temperatures. As this happens, the gaskets can begin to leak, resulting in reduced oil levels and ingress of moisture and oxygen. Should this occur, the unit must then be taken out of service at some point to replace the gaskets. If this occurs with sufficient frequency, it may be advisable to replace the gaskets with a higher temperature material such as Viton.
• Check the tank wall for discolored paint. Areas of high temperatures due to stray flux heating in the tank wall may result in noticeable discoloration of the paint. Pay close attention to bushing penetrations.
• Check conservator and gas blanket systems. Make sure the oil conservator, if equipped, is filled to the proper level and all piping is leak free. Make sure any desiccant canisters are filled with a suitable desiccant. If equipped with an inert gas blanket system, make sure that the pressure regulator is operating properly and that sufficient gas quantity is available in the canister. Gas over-pressure can cause supersaturation of the oil at high temperatures. Upon cooling, the gas would come out of solution and free bubbles would form.
• Check the LTC for proper operation, if equipped. If possible, measure the temperature of the LTC compartment oil. If the differential between the LTC oil
4-37
Chapter 4: Power Transformers
and the main tank exceeds 15°C, consider scheduling an outage to investigate the cause. If system conditions permit, consider cycling the LTC throughout the tap range, in particular exercising the reversing switch.
• Draw an oil sample for DGA and oil quality. Safe overloading requires the oil to be in good condition. In addition, DGA provides a useful tool for spotting lead heating or stray flux heating problems, or any other unknown thermal conditions. In addition, units with possible incipient problems should never be considered for overload. If an evaluation of insulation condition with respect to thermal aging is desired, Furan analysis could be performed as well. The above checks should be repeated as part of a preventive maintenance program at the usual scheduled interval. If a unit is frequently loading near or above nameplate, and increased preventive maintenance schedule should be considered. In addition, following more severe emergency overloads, a site inspection should be scheduled at the earliest convenient time to ensure that no damage was done and that the unit is operating normally. 4.6
WINDING TEMPERATURE MEASUREMENT
Temperature monitoring and measurement is an important tool in loading power transformers. It provides feedback on the cooling performance of the transformer, confirmation of calculated temperatures, and a reliable assessment of the current operating condition of the transformer. That said, accurate temperature measurement is difficult and can be expensive. Depending upon the technology, it may not be economical for smaller units. Simulated WTI Simulated WTIs (winding temperature indicators) are by far the most common devices for measuring winding temperatures (Figure 4.6-1). In reality, however, these devices do not actually measure the winding temperature. They simply measure the temperature of a specially calibrated heating element that is immersed in the top bulk oil near the tank wall. These devices simulate the actual winding temperature.
These most common analog devices consist of a brass tube, or well, that is mounted on the side of the tank, such that it is immersed in the top oil. A separate heating element is the placed in the tube, and a current proportional to the winding current is passed through the heating element. This current produces a temperature rise that, at rate load, equals the expected hot spot temperature.
4-38
Increased Power Flow Guidebook
Since these devices do not directly measure the winding temperature, they are inherently inaccurate. The thermal characteristics of the devices do not exactly match that of the transformer windings. At higher loads, the error can be significant. In addition, these devices have a longer time constant, making them inaccurate during transient shifts in load (Teetsel 2003). This can be significant, especially if the cooling equipment is switched by the WTI temperature. Fiber Optic Temperature Measurement First introduced in the early 1980s, use of fiber optic temperature probes provides a method for direct temperature measurement of a point on the surface of the winding insulation. This is possible due to the inherent dielectric strength of the silica fiber optic material. There are essentially two viable competing technologies in this area: fluoroptic thermometry and abortion shift of GaAs semiconductor.
Fluoroptic thermometry probes utilize a phosphor coating at the tip. When the coating is excited with a pulse of light sent down the fiber optic, the coating fluoresces. The rate of decay of this fluorescence is temperature dependent. Therefore, by measuring the rate of decay at the far end of the fiber optic, the temperature of the probe tip can be determined. GaAs semiconductor devices utilize a GaAs semiconducting wafer topped with a reflective coating at the end of the probe. A pulse of white light is sent down the fiber, passing through the GaAs wafer. Some of the light is absorbed by the GaAs, while the remainder passes through and reflects off the reflective coating. The light then returns down the fiber where the magnitude of the received light is measured for the various wavelengths of the spectrum of the light pulse. Light at different wavelengths is absorbed by the GaAs, with the magnitude at a particular wavelength a function of temperature of the GaAs semiconductor. Therefore, the absorption spec-
Figure 4.6-1 Schematic drawing of winding temperature indicator.
Increased Power Flow Guidebook
Chapter 4: Power Transformers
trum is a function of the temperature of the GaAs. The characteristic curve of the absorption spectrum shifts toward higher wavelengths with increasing temperatures. By measuring the shift in the absorption spectrum, the temperature of the probe is determined.
• retrofit radiators or heat exchangers with higher cool-
Regardless of the technology used, fiber optic temperature probes have a few significant disadvantages. First, these probes must be installed during manufacture. The probes must be inserted in the winding at the expected hot spot location. Since this location is difficult to pinpoint, several probes at different locations must be used. In addition, hot spot locations can move with differing oil flow regimes, making precise hot spot determination impossible. These probes are also extremely delicate. Even with the newer, ruggedized probes, breakage often occurs. The manufacturer must take extra precautions during winding and final assembly not to break the fibers. This in turn increases the cost of manufacture for the unit as a whole. The measuring units for reading the probes are also rather expensive, making them economical only for larger, critical units.
All of the methods listed above increase the heat transfer from the oil to the surrounding environment. The effect would then be to decrease both the average oil rise and the top-to-bottom oil gradient. In non-directed flow designs, this reduction in oil temperature increases the thermal pressure of the natural thermosiphon flow through the windings. Assuming that the duct size is not limiting the oil flow in the area of the hot spot, the hot spot temperature is then decrease.
4.7
MODEST INCREASES IN CAPACITY FROM EXISTING TRANSFORMERS
When additional capacity is required, and higher temperatures are not practical or acceptable, there are limited options for increasing the rating of a transformer by adding additional cooling. This can be effective to some extent, but care must be taken to ensure that the winding hotspot is not excessive. There are essentially two ways to reduce transformer temperatures: reduce the losses or increase the heat transfer. The former would require a redesign and rewind of the transformer and is therefore not economical unless the unit is already being rewound following a failure. Even then, other design constraints will limit the amount of additional capacity. The only viable option is, therefore, to increase the heat transfer. To be cost effective, any cooling upgrades must be installable in the field. This precludes any internal modifications. Additional pumps and fans may be added, with limited increase in capacity. There is a practical maximum to pump flow rates or fan capacities, above which there will be no increase in heat transfer. For units employing heat exchangers, larger heat exchangers may be added if the cost of the retrofit is justified by the increased capacity. Methods of increasing the cooling capacity include:
• addition of fans, or higher flow rate fans, to radiators or heat exchangers
ing capacity units
• water spray cooling over radiator fins • retrofit with oil-water heat exchangers
However, this leads to a major caveat in the application of supplemental cooling: the drop in oil temperature does not necessarily give a corresponding drop in the hot spot temperature. In other words, if the oil temperature is reduced 10°C, the hot spot temperature will be reduced somewhere between 0 ° and 10 ° C. Without detailed design data or embedded fiber optics, it is impossible to determine the actual decrease in hot spot temperature. Therefore, the excess capacity, if any, gained by applying supplemental cooling should not be relied upon for planning or operating purposes unless the manufacturer has reviewed the application. 4.8
EXAMPLES
Example 1:
This first example will illustrate a simple 6 hr transient rating with a flat preload and load cycle, followed by a 6 hr transient rating with a cyclical preload and load cycle. The unit is a 220/69-kV autotransformer rated at 224 MVA with directed forced-oil cooling (DFOA). For this unit, the bottom oil temperature rise at rated load is known, so the more accurate IEEE Annex G model is used. The parameters for the thermal calculation are as shown in Table 4.8-1. As mentioned previously, the preload and load cycles are flat. A flat preload enforces a conservative assumption that the transformer temperatures have reached steady-state (and therefore the maximum) prior to the onset of the contingency. The contingency onset is assumed to occur at 12 pm to coincide with the peak ambient. The load shape during the contingency is also assumed to be flat, again giving a conservative answer (Figure 4.8-1). The ambient temperature used for the calculation is a representative peak day for the summer months measured at the substation. This represents the worst-case 4-39
Chapter 4: Power Transformers
Increased Power Flow Guidebook
scenario where the contingency occurs on the hottest day of the season (Figure 4.8-2). This particular unit was manufactured in 1997 and is in good working order. Therefore, the temperature limits Table 4.8-1 Parameters for Example 1 MVA Base for Loss Data
200
Temperature Base for Loss Data
75
C
525072
W
Winding I2R Losses
MVA
Winding Eddy Losses
0
W
Stray Losses
0
W
Core Losses
54560
W
Cooling Mode Type
ODAF
Nameplate MVA
224
MVA
Guaranteed Average Winding Rise
65
C
Rated Average Winding Rise
50.6
C
Rated Hot Spot Rise
62.2
C
Rated Top Oil Rise
32.2
C
Rated Bottom Oil Rise
29.2
C
30
C
Rated Ambient Temperature Winding Conductor
Copper
Per Unit Eddy Loss at Winding Hot Spot
0
Winding Time Constant
5
Per Unit Winding Height to Hot Spot
1
min
Weight of Core & Coils
225500
lbs
Weight of Tank & Fittings
102600
lbs
Fluid Type
Mineral Oil
Oil Volume
21696
for this LTE rating shall be set at 140 hot spot temperature and 110 ° C top oil temperature. Given the above load and air temperature cycles and the temperature limits, the load over the 6 hour rating interval is increased until either the hot spot temperature or the top oil temperature meets the temperature limit. This is demonstrated in Figure 4.8-3. The 6 hr LTE rating for this specific scenario is 278 MVA. In the above scenario, the conservative approximation of assuming a flat preload and load cycle was used. Where the load follows a predictable cyclical pattern, increased capacity can be safely realized by using the actual load shapes. Recalculating the rating above utilizing the preload and load cycles, shown in Figure 4.8-4, reveals a slight increase in the rating from 278 MVA to 291 MVA. Note that the preload in this example peaks higher at 0.88 pu than the flat preload of 0.7 pu assumed above. However, the preload is below 0.7 the majority of the 24 hour cycle, with an average load of 0.53. Given the thermal time constant of the transformer bulk oil, the operating temperatures with a diverse load shape will be fractionally less than the temperatures with a flat load shape (Figure 4.8-5).
gals
Load (Per Unit)
Load 1.4 1.2 1 0.8 0.6 0.4 0.2 0 0
10
20
30
40
50
60
Time (hrs)
Figure 4.8-3 Calculated transformer temperatures for Example 1.
Figure 4.8-1 Preload and load cycle for Example 1. Load 35
Load (Per Unit)
Ambient Temp (deg C)
Ambient Temperature 30 25 20 15 10 5
1 0.8 0.6 0.4 0.2 0 0
0
10
20
30
40
50
60
Time (hrs) 0
10
20
30
40
50
Time (hrs)
Figure 4.8-2 Air temperature cycles for Example 1.
4-40
1.4 1.2
60
Figure 4.8-4 Preload and load cycles for Example 1 with cyclical load.
Increased Power Flow Guidebook
Chapter 4: Power Transformers
Example 2
This second example will answer a question: A substation transformer is feeding a circuit in parallel with two other transformers. One of the three transformers must be removed from service for 48 hours. Can the remaining two units handle the increased load safely? The unit in this example is a 220/138-kV autotransformer rated at 180/240/300MVA OA/FA/FA. Again, the Annex G model is used with the parameters shown in Table 4.8-2. The predicted load for the days of the outage is shown in Figure 4.8-6. The lower curve shows the predicted load with all units in service. The upper curve shows the load with two units in service. Figure 4.8-7 shows the
predicted air temperatures in the vicinity of the substation for the 48 hour period under question. Figure 4.8-8 reveals that the hot spot temperature peaks at about 140 ° C and the top oil temperature reaches approximately 100°C. Given the short duration of the event, these temperatures should be safe, assuming the in-service units are in good working order.
Table 4.8-2 Parameters for Example 2 MVA Base for Loss Data
180
Temperature Base for Loss Data
65
C
146265
W
Winding Eddy Losses
0
W
Stray Losses
0
W
Core Losses
47894
W
Winding I2R Losses
Cooling Mode Type
FA
Nameplate MVA
336
Guaranteed Average Winding Rise
55
C
Rated Average Winding Rise
53.6
C
Rated Hot Spot Rise
68.6
C
Rated Top Oil Rise
38.2
C
Rated Bottom Oil Rise
12.4
C
40
C
Rated Ambient Temperature Winding Conductor
Figure 4.8-5 Calculated transformer temperatures for Example 1 with cyclical load.
Load (PU)
Load (Per Unit)
Load
Original Load
1.4 1.2 1 0.8
MVA
MVA
Copper
Per Unit Eddy Loss at Winding Hot Spot
0
Winding Time Constant
5
Per Unit Winding Height to Hot Spot
1
min
Weight of Core & Coils
190600
lbs
Weight of Tank & Fittings
145750
lbs
Fluid Type
Mineral Oil
Oil Volume
26973
gals
0.6 0.4 0.2 0 0
10
20
30
40
50
60
Time (hrs)
Figure 4.8-6 Predicted load during outage for Example 2.
Ambient Temp (deg C)
Ambient Temperature 50 40 30 20 10 0 0
10
20
30
40
50
Time (hrs)
Figure 4.8-7 Predicted air temperature for outage.
60
Figure 4.8-8 Calculated transformer temperatures during outage
4-41
Chapter 4: Power Transformers
Insulation Aging Age Acceleration Rate
250
25
200
20
150
15
100
10
50
5
0
0 0
10
20
30
40
50
Time (hrs)
Figure 4.8-9 Insulation aging during outage.
4-42
60
Age Acceleration Rate
Total Aging (hrs)
Cumulative Aging (hrs)
Figure 4.8-9 shows the cumulative aging during the outage, in hours, for the in-service units. The total aging over the 48 hour period is approximately 220 hours. If this event is relatively rare, this increased aging should be acceptable over the expected 180,000 hour life of the unit.
Increased Power Flow Guidebook
Increased Power Flow Guidebook
REFERENCES
Aubin, J. and T. Langhame. 1992. “Effect of Oil Viscosity on Transformer Loading Capability at Low Ambient Temperatures.” IEEE Trans. on Power Delivery. Vol. 7. No. 2. pp. 516-524. April. Cengel, Y. A. 1997. Introduction to Thermodynamics and Heat Transfer. McGraw-Hill. Boston, MA. Dakin, T. W. 1948. “Electrical Insulation Deterioration Treated as a Chemical Rate Phenomenon.” AIEE Transactions. Vol. 67. pp. 113-122. November. Emsley, A. M. and G. C. Stevens. 1994. “Review of Chemical Indicators of Degradation of Cellulosic Electrical Paper Insulation in Oil-filled Transformers.” IEE Proc. Sci. Meas. Technol. Vol. 141. No. 5. pp. 324-334. September. IEC. 1991. IEC 60354: 1991. Loading Guide for Oilimmersed Power Transformers. January. IEC. 2004. IEC 60076-7. Power Transformers – Part 7: Loading Guide for Oil-immersed Power Transformers. Committee Draft 2. IEEE. 1995a. Standard Requirements for Load Tap Changers. IEEE Standard C57.131-1995. March. IEEE. 1995b. Guide for Loading Mineral-Oil-Immersed Transformers. IEEE Standard C57.91-1995. June. IEEE. 1995c Guide for Application of Power Apparatus Bushings. IEEE Standard C57.19.100-1995. August.
Chapter 4: Power Transformers
Lesieutre, B. C. Hagman, W.H. and J. L Kirtley Jr. 1997. “An Improved Transformer Top Oil Temperature Model for Use in An On-Line Monitoring and Diagnostic System.” IEEE Trans. on Power Delivery. Vol. 12 No. 1. pp. 249-256. McNutt, W. J. 1992. “Insulation Thermal Life Considerations for Transformer Loading Guides.” IEEE Transactions on Power Delivery. Vol. 7. No. 1. pp 392401. January. Montsinger, V. M. 1930. “Loading Transformers by Temperature.” Trans. AIEE. Vol. 49. pp 776-790. Montsinger, V. M. 1951. Transformer Engineering. John Wiley & Sons. New York. pp. 275-351. Pierce, L. W. 1992.“An Investigation of the Thermal Performance of an Oil Filled Transformer Winding.” IEEE Trans. on Power Delivery. Vol. 7. No. 3. pp. 13471358. July. Pierce, L. W. 1994. “Predicting Liquid Filled Transformer Loading Capability.” IEEE Trans. on Industry Applications. Vol. 30. No. 1. pp. 170-178. January/February. Schroff, D. H. and A. W. Stannett. 1985. “A Review of Paper Ageing in Power Transformers.” IEE Proc. Vol. 132. Pt. C. No. 6. pp. 312- 319. November. Teetsel, M. 2003. “Winding Temperature Measurement: Techniques, Devices and Operation.” From presentation before IEEE/PES Transformers Committee. October.
Lundgaard, L., W. Hansen, D. Linhjell, and T. Painter. 2004. “Ageing of Oil Impregnated Paper in Power Transformers.” IEEE Trans. on Power Delivery. Vol. 19. No. 1. pp. 230-239. January.
4-43
Increased Power Flow Guidebook
CHAPTER 5
Substation Terminal Equipment
5.1
INTRODUCTION
In comparison to overhead lines, underground cables, and power transformers, substation terminal equipment is usually much less expensive to replace, and since terminal equipment is within the utility substation boundaries, its replacement does not require public hearings or regulatory approval. Nonetheless, in many cases, the benefits of increasing the rating of lines, cables, and transformers may be limited by one or more breakers, line traps, or current transformers, and replacement of such equipment can be both time consuming and disruptive due to required circuit outages. Finally, just as with lines, cables, and transformers, when relatively modest increases in terminal equipment rating are required, more detailed knowledge of thermal behavior can often be obtained quite easily. Substation terminal equipment consists of many different types and designs of power equipment. Included in this classification are line traps, oil circuit breakers, SF6 circuit breakers, rigid tubular bus, line disconnects, current transformers, bolted connectors, and insulator bushings. In a recent Electra article entitled “Dynamic Loading of Transmission Equipment – An Overview” (CIGRE 2002), representatives of Study Committee 23 concluded, “there is scope for implementing dynamic loading principles for a wide range of transmission assets.” The need for increased power flow in substation terminal equipment is illustrated in Figure 5.1-1 taken from (New York Power Pool 1982). It shows that the thermal rating of over 50% of the transmission circuits in New York State are thermally limited by substation equipment.
Figure 5.1-1 Thermally limiting transmission circuit equipment. 5-1
Chapter 5: Substation Terminal Equipment
The increase in circuit rating, resulting from applying the various methods of increasing power flow in overhead transmission lines, underground cable, and power transformers is often limited by terminal equipment, as shown in Figure 5.1-2. This figure illustrates the unexpected conclusion that relatively modest investments in terminal equipment (replacement of the CT in Circuit A) yields an increase in that circuit rating and a 50-MW increase in the rating of the complex interface. Here a large increase in circuit rating is obtained for a very modest expenditure on terminal equipment rather than a relatively large investment in lines, cables, or transformers. This chapter is limited to studying practical, rather simple methods of increasing the power flow through less capital-intensive equipment such as switches, bus, line traps, breakers, and power transformer auxiliary equipment. Because the substation equipment being uprated is generally less expensive to replace than lines, cables, and transformers, some of the more elaborate methods of monitoring are difficult or even impossible to justify economically. Also, because of the large number of switches, circuit breakers, etc., in any power system, and the variety of designs, both the thermal models that represent the equipment and the requirements for weather monitoring must be kept simple.
Increased Power Flow Guidebook
This chapter includes four sections:
• Section 5.2, Summary: Equipment Types and IPF Opportunities, is a summary of terminal equipment types, their thermal response to changes in weather and current, and the risks associated with high current loading.
• Section 5.3, Thermal Models for Terminal Equipment, describes specific thermal models for each type of equipment and suggests common limits on temperature.
• Section 5.4, Uprating of Substation Terminal Equipment, reviews dynamic thermal rating of terminal equipment, including a discussion of the need for weather and load data.
• Section 5.5, Thermal Parameters for Terminal Equipment, describes methods of determining specific thermal parameters from field test, laboratory test, and manufacturer heat-run tests. 5.2
SUMMARY—EQUIPMENT TYPES AND IPF OPPORTUNITIES
Substation terminal equipment includes a wide variety of equipment types with varying opportunities for increased power flow. This section provides a broad overview of the types of equipment that might limit power circuit thermal ratings. 5.2.1
Equipment Rating Parameters
For each type of terminal equipment, the following issues are compared:
• Primary reasons for temperature and deterioration limits
• • • • •
Type of thermal model used in rating calculations Consequences of over-temperature Degree of thermal interaction with other equipment Sensitivity to weather parameters Response to short-time emergency loads
The comparisons included here are not intended to be exhaustive, but rather to be an initial guide as to what can be expected to result from the various methods of increasing power flow.
Figure 5.1-2 Diagram showing the limiting element for each of multiple circuits making up a complex power flow interface. The total interface transfer limit is shown at the top labeled “Transfer (MW)”. Note that replacing the CT in Circuit A yields an increase in the transfer limit from 450 to 500 MW! (Diagram courtesy of N. Dag Reppen, Niskayuna Power Consultants, Inc.)
5-2
Temperature and Deterioration Limits Manufacturers of terminal equipment usually follow ANSI or IEEE or IEC standard recommendations with regard to maximum operating temperatures of substation terminal equipment. One clear exception is bus. While there are manufacturing standards for strain bus and tubular bus, temperature limits and thermal models are not typically included in the standards.
Increased Power Flow Guidebook
Chapter 5: Substation Terminal Equipment
One obvious way to increase the rating of substation terminal equipment involves the use of higher than recommended equipment component temperatures, especially when this is done for limited periods of time and when such events occur infrequently. However, when the exceedence of normally recommended maximum equipment temperatures are to be allowed, the consequence of such events on the life and proper function of terminal equipment must be known. Thermal Models Thermal models for substation terminal equipment fall into one of two categories. The first category is similar to the power transformer “top oil” model (see Chapter 4). In this “ambient-adjusted” model, the temperature rise above ambient for critical components of the equipment (e.g., switch contact temperature), determined by reference to the appropriate standard, by a manufacturer test report (if available), or by field or laboratory measurement, is specified for a known current (typically the rated current of the equipment). This “reference” temperature rise is then adjusted for other currents according to an equation of the form:
⎛ I2 ⎞ ⎟ ⎝ IR ⎠
2n
θ2 = θR ⎜
5.2-1
Where: θ2 is the temperature rise to be calculated. θR is the “reference” temperature rise. I2 is current for which the temperature rise is to be calculated. IR is the “reference” current which causes θR. n is an exponent, generally close to 1.0. The second category of thermal model consists of an actual heat balance similar to that used for overhead lines and underground cables. In this model, the temperature rise is calculated with a heat balance equation of the form:
I 2 R + qs = qr + qc
5.2-2
Where: I is current in amps. R is the ac resistance of the component. qs is the solar heat gain. qr is the radiation heat loss. qc is the convective heat loss. With either sort of thermal model, heat storage in the equipment can be included in order to simulate transient thermal response to changes in current flow. Circuit breakers, CTs, and line traps are usually modeled with the “ambient adjusted” thermal model. Strain
and tubular bus, bolted connectors are usually modeled with the heat balance approach. Switches and line traps can be modeled either way, but the heat balance approach usually requires too many dimensional and material parameters to be practical. Determination of Equipment Thermal Parameters As discussed in Section 5.5, the determination of other than default thermal parameters for substation terminal equipment is one of the most challenging parts of determining and increasing power flow through them. Unlike power transformers, for which certified heat run data is typically available, thermal test data from the manufacturer is seldom required by the utility and, if it was originally supplied, it may no longer be available for older equipment. For newer equipment, it should be possible to obtain documentation of a thermal design test. This documentation will contain measurements of the temperature rises above ambient of critical equipment parts at rated current. Thermal time constants and exponents are not typically available and must be determined by measurement or assumed. Estimate and Consequences of Over-temperature Unless one chooses to be extremely conservative, the magnitude and consequences of equipment over-temperature must be evaluated when rating substation equipment. For example, strain bus is seldom rated for still air conditions, because this would yield extremely low thermal ratings. But when strain bus is rated at 100oC on the basis of a 3-foot-per-second crosswind, then the temperature that it might obtain under still air conditions (the “temperature rise”) must be estimated, and the consequences of occasionally attaining such a temperature on bus strength and clearance evaluated. Degree of Thermal Interaction with Other Equipment Spacing of equipment in most substation designs is driven by electrical clearance considerations. At distances sufficient to meet these electrical clearance needs, there is little or no thermal interaction by means of convection or radiation. On the other hand, substation equipment is connected by electrical conductors that may conduct heat as well as current. The source of such heat may be either other electrically connected equipment or the conductor itself. Fortunately, the conduction of heat between equipment by means of typical bus conductors is unlikely to be significant. The impact of heat from conductors that are themselves hot, however, is a source of concern. Sensitivity to Weather The thermal rating of most substation equipment is sensitive to air temperature, solar heating, and wind speed and direction. Nonetheless, within the typical substation, because of the many equipment orientations and
5-3
Chapter 5: Substation Terminal Equipment
Increased Power Flow Guidebook
the degree of sheltering by other equipment and buildings, determination of reasonable values for solar heating, wind speed, and wind direction is very difficult. Air temperature, on the other hand, is easily determined for all equipment at a particular location. Therefore, with the possible exception of strain and rigid bus work, wind and solar effects are typically ignored. Response to Short Time Emergency Overloads In transmission power systems, normal power flows in most circuits are modest (i.e., less than 30% of the circuit thermal capacity). This occurs because the system must be capable of transmitting sudden increases in power flows due to the sudden loss (outage) of key components (e.g., generators and bulk transmission circuits). In order to limit the magnitude of such sudden “emergency” loads, the operator may intervene within a short period of time (e.g., 15 minutes) in order to reduce power flow levels to normal continuous ratings or below. In such situations, short-time emergency ratings of substation terminal equipment may be useful. Two factors determine the short-time emergency (STE) rating of substation terminal equipment (and other power equipment). These factors are the equipment’s thermal time constant and its ability to withstand occasional high temperature events with an acceptable degree of deterioration. The thermal time constant is defined as that time, after a sudden increase in electrical current, after which the equipment temperature rise equals 63% of that which will ultimately occur if the new higher load continues indefinitely. An example of with-
standing occasional high temperature exposure is the aging of free-standing current transformer insulation, which may shorten the life but not cause short-term catastrophic failure. Maximum Multiple of Nameplate Rating For short-time and long-time emergency ratings, the thermal rating calculation formulas may allow for operation at many times the continuous “nameplate” rating, but there may be perfectly good engineering reasons to limit these transient rating to a multiple of the nameplate rating. For example, this is done with power transformers, which are normally limited to 200% of nameplate regardless of the STE or long-time emergency (LTE) rating calculations. 5.2.2
Thermal Rating Parameter Comparison
Tables 5.2-1 and 5.2-2 compare thermal rating parameters of substation terminal equipment. 5.3
THERMAL MODELS FOR TERMINAL EQUIPMENT
As noted in the preceding section of this chapter, there are many types and designs of terminal equipment, and detailed thermal test data, particularly for older equipment, is unlikely to be available. As a result, simplicity is preferred in modeling terminal equipment. 5.3.1
Bus Conductors
Bus conductors in substations come in a wide variety of sizes and types. To keep things reasonably simple, three
Table 5.2-1 Summary of IPF Characteristics for Substation Terminal Equipment (Part I) Substation Terminal Equipment Type
Temperature or Temp Rise Limits (oC)
Thermal Models
Consequence of Over- Thermal Interaction with Temperature Other Equipment
Strain Bus
75 to 125 (cont.)
Heat balance
Loss of strength, sag clearance
Possible
Rigid Bus
75 to 125 (cont.)
Heat balance
Loss of strength
Possible
Switches (Air Disconnects)
70/93 rise normal 105/120 rise LTE
Ambient Adjusted
Contact damage, annealing of parts
None
Line Traps
90 to 115 rise (cont.)
Ambient Adjusted
Damage to Insulation or reduction in tensile strength of aluminum
None
Bushings
150 conductor temp
Adjusted for top oil of PT or OCB.
Reduction in insulation life, overpressure, gasket deterioration
Directly influenced by oil temp in OCB or PT
CTs - Bushing
120 hot spot
Adjusted for top oil of PT or OCB.
Decrease in insulation life
Can be directly influenced by oil temp in OCB or PT
CTs – Free-standing
45 rise oil 55 to 80 winding rise.
PT model, ambient adjusted
Decrease in insulation life
None
Circuit Breakers
90 (metal in oil) 80 (top oil)
Ambient Adjusted
Damage to contacts, annealing of parts
None
Current Limiting Reactors
55 or 80 rise
Ambient Adjusted
Damage to insulation
None
5-4
Increased Power Flow Guidebook
Chapter 5: Substation Terminal Equipment
Table 5.2-2 Summary of IPF Characteristics for Substation Terminal Equipment (Part II) Substation Terminal Equipment Type
Sensitivity of cont. rating to air temp. (% change per oC)
Practical Sensitivity to weather
Thermal Time Constant (min)
Strain Bus
Wind speed and direction, air temp, solar heating
5 to 15
0.6% to 0.8% 10% per fps wind
None
Rigid Bus
Wind speed and direction, air temp, solar heating
10 to 30
1.0% to 0.8% 10% per fps wind
None
Switches (Air Disconnects)
Air temp
30
0.8% for new 53oC rise 1.2% for older 30oC rise
200%
Line Traps
Air temp
15
0.2%
None
Bushings
Indirectly through transformer or breaker oil temperature
Adjusted for top oil of PT or OCB.
Reduction in insulation life
Directly influenced by oil temp in OCB or PT
CTs - Bushing
Air temp
15
Same as PT
Same as PT
Maximum Multiple of Nameplate
CTs – Free-standing
Air temp
15
Similar to PTs with OA cooling.
Circuit Breakers
Air temp
30
1%
200%
15 to 30
0.8% for 55oC rise 0.4% for 80oC rise
200%
Current Limiting Reactors (Dry-type)
Air temp
types of substation bus are recognized: rigid bus, strain bus, and jumpers:
• Rigid bus is normally tubular, functionally similar to copper or aluminum conduit or pipe, but some older rigid bus may be square or “L” shaped in cross-section.
• Strain bus is under tension (thus the name “strain”), and usually identical to stranded conductor used in overhead transmission lines. It usually is stranded aluminum wires with a steel wire core (i.e., ACSR).
• Jumpers are also made from stranded transmission
qs qr qc qcond
is the solar heat gain (W/m). is the radiation heat loss (W/m). is the convective heat loss (W/m). is heat loss/gain due to conduction (W/m).
One difference between substation bus and overhead lines is that reflected solar heating is negligible for lines, but not for substation bus, where the conductor are somewhat closer to the ground. There are other important thermal rating differences, even for the same conductor applied as substation strain
conductor but are not under tension. The three types of bus conductor are shown in Figure 5.3-1. The thermal model for these bus types are similar to that of an overhead line (CIGRE 1997, IEEE 1993), consisting of a heat balance between Ohmic and solar heat input and convective and radiation heat losses. The steady state temperature given a constant load, ambient temperature, and effective wind speed must be solved by iteration so as to satisfy the following heat balance equation:
I 2 R + qs = qr + qc + qcond
5.3-1
Where: I is current in amps. R is the ac resistance at temperature T in ohms/meter.
Figure 5.3-1 Three types of substation bus conductor.
5-5
Chapter 5: Substation Terminal Equipment
bus and as a phase conductor in an overhead line. These differences include:
• The decrease in electrical clearance at high temperature is less likely to be a problem for substation bus where strain bus spans are short.
• The issue of loss in strength due to annealing is less likely to be a concern in bus applications since the increase in tension under ice and wind load is less than for lines.
• High electrical losses in bus are not a concern because of the short length involved.
• Inspection of connectors is much simpler in a substation than in a line, which might be 50 or more miles in length. On the other hand, the temperature attained under high load conditions for both strain bus and line conductors is very sensitive to wind cooling (forced convection). Given these observations, it seems reasonable that substation bus could be rated “less conservatively” than overhead lines. Consider Drake ACSR used as both substation bus and as the phase conductor in a line. One end of the line terminates at the substation with the Drake bus conductor. Assume that both conductors are rated at 990 A for a conductor temperature of 100 o C, wind speed 2 ft/sec perpendicular to the conductor, air temperature of 40oC, and full sun. If the wind drops to 0 ft/sec, the conductor temperature with full rated load would increase to 130oC. This is acceptable in both applications. Now consider the impact of increasing the assumed wind speed from 2 ft/sec wind to 3 ft/sec. The risk associated with this change in the assumed rating conditions appears to be greater for the line than for the strain bus in the substation. Any possible deterioration in the physical conductor and associated hardware is easier to spot by a single trip to the substation. A line inspection is far more expensive, requiring more time and travel. Any permanent increase in sag is a genuine safety concern along the line, not within the substation. Any loss in conductor strength is more likely to result in a high tension failure of the line during the next severe ice storm than in the shorter substation span. Oddly enough, however, substation bus is normally rated more conservatively than lines in terms of weather assumptions. Thus, one simple possible approach to
5-6
Increased Power Flow Guidebook
increasing power flow in substation bus might be the use of less conservative weather assumptions. 5.3.2
Switch (Air Disconnect)
ANSI standards (ANSI 1979) specify certain requirements for high-voltage air disconnect switches. The standards specify the rated current (thermal rating) of the switch and the weather conditions and equipment temperatures under which the rating is calculated. For example, modern switches, produced after 1971, with silver contacts, are rated for continuous operation at a temperature rise of 53oC, whereas those manufactured after 1971 are rated for continuous operation at a rise of 30oC. In both cases, the continuous rating is calculated for an air temperature of 40oC. A typical, rather simple switch design is shown in Figure 5.3-2. The PJM Interconnection has published detailed rating data (PJM 1999) for air disconnects. The conclusions drawn in the PJM documents reflect the operating philosophy of PJM and should be considered by anyone utilizing the analysis. For example (New York Power Pool 1995), the NY Power Pool (presently NY ISO) utilizes limits of 93oC, 120oC, and 140oC in calculating the rating of pre-1971 air disconnects for normal continuous, long-time emergency (LTE) and short-time emerg e n c y ( S T E ) r a t i n g s. T h e m o s t r e c e n t P J M recommendations are 93oC, 115oC, and 125 oC for the same ratings. The PJM standard also considers the temperature of conducting material joints, switch terminals with bolted connections, and flexible connectors. The PJM discussion also considers annealing of copper and aluminum component parts as a factor in high-temperature limits, while the NY ISO discussion does not.
Figure 5.3-2 Typical air disconnect (switch).
Increased Power Flow Guidebook
Chapter 5: Substation Terminal Equipment
Simple Dynamic Rating Switch Model The adjustment of steady-state switch rating, IR, with air temperature, TA, may be approximated as follows: 1
⎛ T − TA ⎞ 2 I2 = IR ⋅ ⎜ R ⎟ ⎝ TR − 40 ⎠
5.3-2
Table 5.3-1 shows the variation of steady-state switch rating with air temperature, using this simple equation. Notice that the variation in the rating of the newer switches, having a higher allowable contact temperature rise over air temperature, is less. In any event, Table 5.3-1 indicates that the switch rating can be 5% to 20% higher on a cool day. The following, more general equations, are given in ANSI C37.30. They allow adjustment of manufacturer nameplate rating for both steady-state and transient loads. The critical contact temperature may also be tracked with these equations as load and air temperature vary over time.
θ2 is the contact temperature rise at the present time step, t2. TA is the ambient temperature. θ1 is the contact temperature rise at the previous time step, t1. Δt is the time step. τ is the switch thermal time constant (default 30.0 min). The switch rating can be determined by one of several “observable temperature” rises with different limiting temperatures. It seems likely that the switch contacts will most often be the limiting temperature. In addition, it must be assumed that the contacts are kept in good condition such that there is not an appreciable increase in contact resistance. Thermodynamic Dynamic Rating Switch Models As part of the development of the EPRI DTCR software, thermodynamic models of certain switches were developed (Coneybeer 1992) and verified through laboratory testing. For example, Figures 5.3-3, 5.3-4, and 5.3-5 show a comparison of contact temperature mea-
1
⎛ T − TA ⎞ 2 n I2 = IR ⋅ ⎜ R ⎟ ⎝ TR − 40 ⎠ ⎛ I2 ⎞ ⎟ ⎝ IR ⎠
5.3-3
2n
θU = θ R ⎜
5.3-4
θ 2 = θ1 + (θU − θ1 ) (1 − e
−Δt τ
)
5.3-5
T2 = TA + θ 2
5.3-6
Where: θU is the ultimate contact temperature rise. θR is the rated contact temperature rise. I2 is switch current at the present time step, t2. IR is the rated switch current. n is an exponent, generally between 0.7 and 1.0 (default 0.8).
Figure 5.3-3 Laboratory current step-sequence for switch tests.
Table 5.3-1 Impact of Air Temperature on the Normal Rating of Air Disconnects
Ambient Temperature (oC)
Thermal Rating (53°C rise in silver contact temp) %Nameplate (after 1971)
Thermal Rating (30°C rise in silver contact temp) %Nameplate (before 1971)
45
95
91
40
100
100
35
105
108
30
109
115
25
113
122
20
117
129
Figure 5.3-4 Comparison of laboratory measurements of contact segment temperature to IEEE/ANSI and EPRI Dynamp thermodynamic model with adjusted parameters.
5-7
Chapter 5: Substation Terminal Equipment
Increased Power Flow Guidebook
In addition, the laboratory testing of an old weathered switch with contacts that were in poor condition showed that the ANSI/IEEE model (or presumably the Dynamp thermal model with default parameters) underestimated the contact temperature, as shown in Figure 5.3-4. The good agreement between the measured temperature and the EPRI Dynamp thermal model was accomplished by noting the poor condition of the switch contacts and adjusting the parameters accordingly—hardly a practical solution to a “bad” switch. In reality, this switch should have been de-rated or replaced if part of a heavily loaded power circuit.
Figure 5.3-5 Comparison of laboratory test results to the ANSI/IEEE model and the EPRI Dynamp thermodynamic model.
sured in a laboratory to temperature calculated with a thermodynamic switch model. The thermodynamic switch model consists of modeling three switch segments separately—the contact segment, the bus bar segment, and the shunt. The model is basically a heat balance much like that used to model a bare overhead line. The detailed model had the advantage that it adjusted ratings for wind cooling, but it had a number of disadvantages, primarily consisting of the requirement for detailed geometrical dimensions and electrical and thermal parameters as illustrated by the following list:
• Outer and inner diameters of the bus segment. • Contact material and surface emissivity/absorptivity. • Switch rated current, contact temperature at rated current, and ratio of contact resistance to that of a new contact.
• Dimensions of contacts. • Shunt material and emissivity/absorptivity. • Shunt width and thickness.
Field Testing of Switches Both as part of the original series of substation terminal tests and as part of more recent field measurements of switch temperature in operating substations, it was concluded that even in heavily loaded circuits, switch temperatures rarely reach levels that allow for meaningful measurements. The older DTCR tests concluded that the temperature rise due to solar heating was generally higher than the temperature rise due to electrical current.
The more recent tests utilized infrared (IR) imaging cameras and prepared (white painted) switch surfaces. It was found that this approach to measurement provides a noncontact measurement of temperature with an accuracy of within 1° to 2° C. The camera used was not unusual, but the experience of the operator was. The primary impediment to field testing involves the relatively low current levels that most switches and other substation equipment experience. At a current equal to 30% of the switch's thermal rating, the temperature rise is only about 10% of the rated rise. 5.3.3
Air-core Reactor
Series-connected air-core reactors are governed by ANSI standards (ANSI 1996, 1965). The rating is limited by the hot-spot temperature rise of the conductor in contact with the insulation or encapsulation material. The limiting temperature varies depending upon the insulation material (as indicated by the temperature index). For specific limits, refer to Table 5.3-2. No therTable 5.3-2 Temperature Limits for Air-Core Reactors
Utility advisors on the project concluded that these requirements were onerous and impractical, given the number of switch designs being used in large utilities. In addition to these problems, the tests indicated that the switch contact temperature calculation was adequately modeled with the simpler ANSI/IEEE equations and with previously developed utility models (Bendo et al. 1979). This is illustrated in Figure 5.3-5.
5-8
Insulation Temperature Index (°C)
Average Winding Rise by Resistance Hottest-spot Winding (°C) Temperature Rise (°C)
105
55
85
130
80
110
155
100
135
180
115
160
220
140
200
Increased Power Flow Guidebook
Chapter 5: Substation Terminal Equipment
mal model is specifically outlined in the applicable standards. The following simple model should reflect a reasonable compromise between accuracy and efficiency. ⎛ I2 ⎞ ⎟ ⎝ IR ⎠
2n
θU = θ R ⎜
5.3-7
θ 2 = θ1 + (θU − θ1 ) (1 − e
−Δt τ
T2 = TA + θ 2
)
5.3-8 5.3-9
Where: θU is the ultimate winding hot spot temperature rise. θR is the rated winding hot spot temperature rise. I2 is winding current at the present time step, t2. IR is the rated current. n is an exponent, generally between 0.7 and 1.0 (default 0.8). θ2 is the winding hot spot temperature rise at the present time step, t2. θ1 is the winding hot spot temperature rise at the previous time step, t1. Δt is the time step. τ is the winding thermal time constant (default 5.0 min). T 2 is the winding hot spot temperature at the present time step, t2. TA is the ambient temperature. 5.3.4
Oil Circuit Breaker
ANSI standard (ANSI 1998) gives an expression for allowable continuous current at different ambients. This expression can be rearranged to give the temperature rise as a function of the current as follows:
The transient formulation is as follows:
θO ,U
⎛I ⎞ = θO ,R ⎜ 2 ⎟ ⎝ IR ⎠
m
(
θO ,2 = θO ,1 + (θO ,U − θO ,1 ) 1 − e ⎛ I2 ⎞ ⎟ ⎝ IR ⎠
−Δt τ O
5.3-11
)
5.3-12
n
θ HS ,U = θ HS ,R ⎜
(
θ HS ,2 = θ HS ,1 + (θ HS ,U − θ HS ,1 ) 1 − e −Δt τ THS ,2 = TA + θO ,2 + θ HS ,2
W
)
5.3-13 5.3-14 5.3-15
Where: θO,U is the ultimate oil temperature rise. θO,R is the rated oil temperature rise. I2 is current at the present time step, t2. IR is the rated current. m is an exponent, generally between 1.5 and 2.0 (default 1.8). θO,2 is the oil temperature rise at the present time step, t2. θO,1 is the oil temperature rise at the previous time step, t1. Δt is the time step. τO is the oil thermal time constant. θHS,U is the ultimate hot spot temperature rise over oil. θHS,R is the rated hot spot rise over oil. n is an exponent, generally between 1.5 and 2.0 (default 1.8). θHS,2 is the hot spot rise over oil at the present time step, t2.
1.8
⎛ I ⎞ ⎟ ⎝ IR ⎠
θC = θC ,R ⎜
5.3-10
Equation 5.3-10 is for steady state. To calculate the temperature during transient loading periods, it is necessary to break the contact temperature rise over ambient into two components with different time constants: contact rise over oil and oil rise over ambient (ANSI 1979). This may cause some difficulty in application, as the rated contact rise over oil may not be available. In addition, an expression or some guidance needs to be developed in estimating the time constant.
Figure 5.3-6 Oil circuit breaker.
5-9
Chapter 5: Substation Terminal Equipment
Increased Power Flow Guidebook
θ2
is the contact temperature rise at the present time step, t2. TA is the ambient temperature. θ1 is the contact temperature rise at the previous time step, t1. Δt is the time step. τ is the breaker contact thermal time constant (default 5.0 min). 5.3.6
Bushings (Oil-immersed Equipment Only)
This model (ANSI 1995a) applies to capacitance graded (condenser) bushings with oil-impregnated paper or resin-impregnated paper. Draw-lead bushing applications are not considered, because the temperature rises will depend upon the size of the draw lead conductor and the amount of insulation on the draw lead. Note that use of this model requires tested values for K1, K2, and n.
Figure 5.3-7 SF6 circuit breaker.
θHS,1 is the hot spot rise over oil at the previous τW THS,2 TA 5.3.5
time step, t1. is the winding thermal time constant (default 5.0 min). is hot spot temperature at the present time step, t2. is the ambient temperature.
SF6 Circuit Breaker
The equations given in (ANSI 1998) and (ANSI 1979) also apply to SF6 breakers. However, whereas it is necessary to divide the contact temperature rise into two components for oil circuit breakers, it should be sufficient to consider only the temperature rise of the contacts over ambient for SF6 breakers. There should be no appreciable thermal capacitance between the contacts and the ambient air.
⎛I ⎞ θU = θ R ⎜ 2 ⎟ ⎝ IR ⎠
2n
θ 2 = TA + θ1 + (θU − θ1 ) (1 − e
5.3-16 −Δt τ
)
5.3-17
Where: θU is the ultimate contact temperature rise. θR is the rated contact temperature rise. I2 is breaker current at the present time step, t2. IR is the continuous current rating of the breaker. n is an exponent, generally between 0.7 and 1.0 (default 0.8).
5-10
Figure 5.3-8 Bushings.
Increased Power Flow Guidebook
Chapter 5: Substation Terminal Equipment
The bushing model is as follows:
θTO ,U
⎛ ( I I )2 R + 1 ⎞ 2 E ,R ⎟ = θTO ,R ⎜ ⎜ ⎟ R +1 ⎝ ⎠
(
5.3.7 m
θTO ,2 = θTO ,1 + (θTO ,U − θTO ,1 ) 1 − e
−Δt τ O
)
5.3-18 5.3-19
Note: Equations 5.3-18 and 5.3-19 are for the calculation of the oil temperature that the bushing is immersed in, and are included for the sake of completeness. Equations 5.3-18 and 5.3-19 can be substituted by simply specifying the oil temperature.
θ HS ,U = K1 ( I 2 I B ,R )
Current Transformers
The rating of CTs can be complex. They are rated according to (ANSI 1993), but unlike other substation terminal equipment, the limits on current are a function of the tap selection and the secondary burden as well as the CT itself. No single set of rating factors can be specified for all applications, even in the same utility substation. To develop continuous ratings, the continuous thermal current rating factor (CTRCF), defined in (ANSI 1993), must be used. The standard does not consider LTE or STE ratings, so these must be determined by nonstandard methods, which should be different for free-standing and for bushing-type CTs.
n
(
θ HS ,2 = θ HS ,1 + (θ HS ,U − θ HS ,1 ) 1 − e −Δt τ THS ,2 = TA + K 2θTO ,2 + θ HS ,2
b
)
5.3-20 5.3-21 5.3-22
Where: θO,U is the ultimate oil temperature rise. θO,R is the rated oil temperature rise. I2 is current at the present time step, t2. IE,R is the rated current of the equipment (transformer, OCB, etc.). m is an exponent, generally between 0.7 and 1.0 (default 0.8). θTO,2 is the oil temperature rise at the present time step, t2. θTO,1 is the oil temperature rise at the previous time step, t1. Δt is the time step. τO is the oil thermal time constant. θHS,U is the ultimate bushing hot spot temperature rise over oil. K1 is constant equal to the rated bushing hot spot rise over oil (15-32). IB,R is the rated bushing current. n is an exponent, generally between 1.6 and 2.0 (default 1.8). θHS,2 is the bushing hot spot rise over oil at the present time step, t2. θHS,1 is the bushing hot spot rise over oil at the previous time step, t1. τb is the bushing thermal time constant (default 5.0 min). THS,2 is bushing hot spot temperature at the present time step, t2. TA is the ambient temperature. K2 is a bushing-specific constant between 0.6 and 0.8.
In general the rating of bushing-type CTs is considered equal to that of the circuit breaker or power transformer in which the CT is installed. If the tap setting on a bushing CT is less than its maximum ratio, then the thermal capacity may be greater than that of the CT when set to its full winding tap position. The adjustment of thermal capacity for tap position can allow operation at currents above the rating for full tap position. For example, at the 50% tap position, the CT rating would be 140% of its full winding position rating. The adjustment of a free-standing CT whose tap position rating is Itap, and whose rated maximum temperature rise is θR, the rating for air temperature (θair), can be obtained in much the standard ambient adjustment method using the tap rating as a basis: 1
⎡ 30 − θ R − θ air ⎤ 2 I = I tap * ⎢ ⎥ θR ⎣ ⎦
5.3-23
Noncontinuous ratings can be calculated based on the power transformer model loading guide with 55oC average winding rise and OA cooling mode parameters. The winding rise exponent of 2 is typically used to be conservative. 5.3.8
Line Traps
Line traps consist of an air-core inductance coil. They are described by reference (ANSI 1981), but the standard does not make rating adjustments terribly clear, and there is some disagreement between sources. Following the method and suggestions outlined in the PJM document on rating of line traps (PJM 1999), suitable temperature limits are a function of the manufacturer as shown in Table 5.3-3.
5-11
Chapter 5: Substation Terminal Equipment
Increased Power Flow Guidebook
Table 5.3-3 PJM Recommended Temperature Limits for Line Traps Line Trap Manufacturer
Limit of Rise for Rated Continuous Current (°C)
Normal Max Temperature (°C)
LTE (>24 hrs) Max Temperature (°C)
STE ( 2000 A), usually to connect with overhead lines entering a station or as a high-capacity bus within a station. (Chapter 3) Conductor Hardware. Noncurrent carrying devices
attached directly to the conductor. Conductor hardware includes components such as suspension clamps (with or without armor rods), dampers, repair sleeves and splices, spacers and spacer dampers, shackles, pins, etc. (Chapter 2) Continuous (Normal) Rating. Current at this level (MVA or amperes) may continue indefinitely without without exceeding agreed-upon maximum (Normal) temperatures for conductors or critical components in all types of power equipment. (Chapter 6)
Ampacity. The ampacity of a conductor is that maxi-
mum constant current that will meet the design, security, and safety criteria of a particular line on which the conductor is used. In this Guidebook, ampacity has the same meaning as “steady-state thermal rating.” (Chapter 2)
Core-Form Construction. Power transformer design constructed with windings that are in the general form of concentric cylinders. (Chapter 4)
G-1
Glossary
Increased Power Flow Guidebook
Creep Elongation . Creep constitutes an irreversible,
Exceedance Level. Amount of time a conductor exceeds
plastic elongation occurring in the aluminum strands of bare overhead conductor, which occurs as a result of tension over extended periods of time. Higher rates of creep occur when a conductor is operated for extended periods of time at operating temperatures in excess of approximately 50°C. (Chapter 2)
the design temperature expressed as a percentage of total time. (Chapter 2)
Cross-Linked Polyethylene (XLPE) Cables. Most common on modern XD cable systems with applications up to 500 kV. The insulation is cross-linked (vulcanized), forming long polymer chains that are joined to one another at intermediate carbon atoms. (Chapter 3) Deterministic Methods. Method of uprating overhead
transmission lines (without reconductoring) using tradit i o n a l c a l c u l at i o n m e t h o d s, s u c h a s t h e E P R I DYNAMP program, with fixed, worst-case weather condition assumptions. (Chapter 2) Direct Flow Design . Design of power transformer
employing forced oil cooling. The transformer internal assembly is designed with oil manifolds that direct the incoming cool oil to the lower part of the core and windings. A directed flow design is normally used with larger sizes of transformers equipped with heat exchangers rather than radiators. (Chapter 4)
Extruded Dielectric (XD) Cables. Cables are so named
because the insulation is extruded onto the conductor core, as compared to paper-insulated cables (HPFF or SCFF), where the insulation is a laminar application of paper tapes. Three types of XD cables include: crosslinked polyethylene (XLPE) cables, ethylene-propylenerubber (EPR) cables, and linear low- or medium-density polyethylene (LLPE, MDPE) cables. (Chapter 3) Factory Heat Run. A direct measurement of the thermal performance of a transformer at a particular benchmark, the nameplate rating. Two methods are used to perform factory heat runs: the “short-circuit” method and the “loading-back” method. (Chapter 4) Flexible AC Transmission System ( FACTS ). A power electronic-based technology for enhancing controllability and increasing power transfer capability of transmission circuits. FACTS controllers provide the system operator with the means of rapidly controlling loads on particular circuits in order to maximize power transfer capability of transmission corridors. (Chapter 6) Fluidized Thermal Backfill (FTB). Fill used in trenches for
DTCR.
See Dynamic Thermal Circuit Rating. (Chapter 3)
underground cable that helps ensure good heat transfer away from the cable pipes. (Chapter 3)
Dynamic Rating . Limits on the level and duration of
power carried by power equipment based on actual weather conditions. (Chapter 2) Dynamic Thermal Circuit Rating (DTCR). EPRI software developed to take real-time data from “off the shelf ” monitoring hardware, and determine optimal ratings (not worst-case) for the conditions at the time the ratings were performed. (Chapter 3) Emergency Rating. Conductor rating that specifies how much current can flow through power equipment under emergency conditions for a specified amount of time— e.g., 30 minutes. (Chapter 2) EPR.
See Ethylene-Propylene-Rubber. (Chapter 3)
Ethylene-Propylene-Rubber ( EPR ) Cables. Insulation type often considered for distribution cables and transmission cables up to 138 kV. The insulation is very “lossy” as compared to XLPE insulation, resulting in high dielectric losses and charging current. (Chapter 3)
G-2
Gapped ACSR (GTACSR). Type of high-temperature conductor invented in Japan, which consists of a conventional steel core surrounded by layers of trapezoidal zirconium aluminum wires, and the gap filled with grease. The zirconium aluminum does not anneal until reaching temperatures in excess of 200oC. Through the use of special terminations and suspension clamps and by preloading the steel core, the ther mal elongation of the conductor is less than that of conventional ACSR, while maintaining the full strength of a conventional ACSR conductor under heavy ice conditions. (Chapter 2) High-Pressure, Fluid-Filled ( HPFF ) Pipe-Type Cables . One of two kinds of pipe-type cables (the other being HPGF). HPFF cables are installed in cable pipes where the pipe is filled with very clean, very low moisture dielectric fluid. Older HPFF cable systems (before 1970) typically used mineral oil for the pipe filling dielectric fluid. HPFF cable systems installed after 1970 have used alkyl benzene or polybutene dielectric fluid. (Chapter 3)
Increased Power Flow Guidebook
High-Pressure, Gas-Filled (HPGF) Pipe-Type Cables. One
of two kinds of pipe-type cables (the other being HPFF). HPGF cables use pressurized dry nitrogen gas inside the cable pipe. (Chapter 3) High-Temperature, Low-Sag (HTLS) Conductors. Conductors capable of continuous operation at temperatures above 100oC with stable tensile strength and creep elongation properties. Such conductors are commercially available or under development. (Chapter 2) HPFF.
See High-Pressure, Fluid-Filled. (Chapter 3)
HPGF.
See High-Pressure, Gas-Filled. (Chapter 3)
See High-Temperature, Low-Sag Conductors. (Chapter 2)
HTLS .
Glossary
higher temperatures without forming cross-linking agents present. (Chapter 3) LLPE.
See Linear Low-Density Polyethylene. (Chapter 3)
Load Losses. Losses generated by transformers that vary with load current but not with excitation. (Chapter 4) Long-Term Emergency (LTE) Rating. A rating where the
thermal heat storage capacity of the equipment does not greatly impact the rating. For power transformers, the bulk oil time constant makes this definition a bit unclear given the cyclic variation in load and air temperature. Sometimes defined as a rating greater than 2 to 4 hours in duration. (Chapter 4) Mass Impregnated (MI) Cables. Cables sometimes used
Insulated Cable Engineers Association. (Chapter 3) ICEA.
Ice Galloping. Wind-induced conductor motion occurring with both single and bundled conductors, and requiring high winds and ice on the conductors. (Chapter 2)
International Electrotechnical Commission (Chapter 3) or International Engineering Consortium (Chapter 2)
up to 69 kV for ac systems, although they are not that common at this voltage. These cables have paper tapes that are impregnated with a high-viscosity dielectric fluid. MI cables are used for ac applications, but are more common for HVDC submarine applications where there may be a significant change in elevation along the cable route that would otherwise be complicated by hydrostatic head pressures. (Chapter 3)
IEC.
MDPE. MI.
One of several methods of modeling the winding temperature of power transformers. See also Top Oil Model and Bottom Oil Model. (Chapter 4)
Medium-Density Polyethylene. (Chapter 3)
See Mass Impregnated. (Chapter 3)
IEC Model 354-1991.
The Institute of Electrical and Electronics Engineers. (Chapter 3)
IEEE.
Invar Steel. A type of steel core wire used in transmission conductors, which has a high nickel content. It has a 15-20% lower tensile strength than conventional galvanized steel wire and a much lower coefficient of thermal expansion than regular high-strength steel wire. (Chapter 2)
NESC.
National Electric Safety Code. (Chapter 2)
No-Load Losses. Losses generated by transformers that do not vary with load current but rather vary with excitation or voltage. (Chapter 4) Normal Rating. Power equipment thermal rating that specifies how much current may flow in the circuit on a continuous basis. (Chapter 4)
Linear Low- or Medium-Density Polyethylene ( LLPE , MDPE ) Cables . Insulation type less common for new
ODAF (Directed FOA). One of four cooling configurations used by oil-immersed power transformers. Pumps are used to circulate the oil. Fans are used to force air over the radiators or heat exchangers. The forced circulation of the oil increases the convective heat transfer from the windings to the oil. The forced air increases the convective heat transfer from the oil to the air. With ODAF, ducts are added to direct the oil over the winding. This forces a significant portion of the forced oil to flow upward through the vertical winding ducts. (Chapter 4)
installations, although there are several installations, predominantly in France. As compared to XLPE insulation, LLPE and MDPE were first used at the higher voltage levels because the extrudate could be raised to
OFAF (Non-directed FOA). One of four cooling configurations used by oil-immersed power transformers. Pumps are used to circulate the oil. Fans are used to
Knee-point Temperature. The conductor temperature
above which the aluminium strands of an ACSR conductor have no tension or go into compression. (Chapter 2)
G-3
Glossary
force air over the radiators. The forced circulation of the oil increases the convective heat transfer from the windings to the oil. The forced air increases the convective heat transfer from the oil to the air. With OFAF, there are no ducts to direct the oil over the winding. In general, the bulk of the forced oil flow passes upward between the winding and the tank, bypassing the windings. (Chapter 4) One of four cooling configurations used by oil-immersed power transformers. No pumps are used to circulate the oil. Fans are used to force air over the radiators to increase heat transfer from the bulk oil to the surrounding air. As with ONAN, oil circulates upward through the windings and down through the radiators by natural thermosiphon flow. (Chapter 4)
Increased Power Flow Guidebook
Ruling (Effective) Span. Hypothetical level span length
wherein the variation of tension with conductor temperature is the same as in a series of suspension spans. (Chapter 2) Sagging Line Mitigator (SLiM). A new class of line hard-
ware that uses a shape-memory alloy actuator, activated by increased temperature, to reduce excessive sag in conductors. (Chapter 2)
ONAF (FA).
Sag-Tension Calculations . Calculations performed using numerical programs in order to determine the sag and the tension of a conductor catenary as a function of ice and wind loads, conductor temperature, and time. (Chapter 2) Self-Contained Liquid-Filled (SCLF) Cables. Cables uti-
One of four cooling configurations used by oil-immersed power transformers. Also referred to as self-cooled, no pumps are used to circulate oil, and no fans are used to increase airflow over the radiators. Oil circulates upward through the windings and down through the radiators by natural thermosiphon flow. (Chapter 4) ONAN (OA).
Paper Insulated Lead Covered ( PILC ) Cables . Cables sometimes used up to 69 kV for ac systems, although they are not that common at this voltage. Uprating approaches would be somewhat similar to those of extruded or self-contained cables. These cables have paper tapes that are impregnated with a high-viscosity dielectric fluid. (Chapter 3) PILC.
See Paper Insulated Lead Covered. (Chapter 3)
Probabilistic Line Rating Methods. Methods that use the
actual weather data and conditions prevailing on a conductor to determine the likelihood or probability of a certain condition occurring. Probabilistic methods include the Absolute Method, the Exceedance Method, the Modified Exceedance Method, and the Safety Method. (Chapter 2) Quasi-Dynamic (Real-Time) Ratings . Quasi-dynamic ratings are applied by monitoring load and temperatures for a period of time and then calculating what the conductor temperature might be as a result of that load. From this, the temperature of the cable conductor at rated temperature can be extrapolated for rating purposes. (Chapter 3) Rated Breaking Strength (RBS). Breaking strength of a
bare overhead conductor as calculated by the methods described in appropriate ASTM or IEC manufacturing standards. (Chapter 2)
G-4
lizing the dielectric liquid impregnated laminated paper insulation similar to pipe-type cables, but with three separate cables installed for the three phases. The cable is called “fluid-filled” because there is a hollow fluid channel in the center of the conductor that allows dielectric liquid to move through the cable with thermal expansion and contraction. Also known as self-contained oilfilled (SCOF) or low-pressure oil-filled (LPOF). (Chapter 3) Self-Contained Oil-Filled (SCOF) Cables. Cables utilizing the dielectric liquid impregnated laminated paper insulation similar to pipe-type cables, but with three separate cables installed for the three phases. Also known as self-contained liquid filled (SCLF). (Chapter 3) Shell-Form Construction. Power transformer design in
which windings are initially assembled flat with insulation and cooling ducts between sections. Complete phase assemblies are then clamped and oriented in a vertical direction so that the plane of the individual sections are upright. (Chapter 4) Short-Term Emergency ( STE ) Rating . Short-term ratings are usually defined as extremely short duration ratings that take advantage of the thermal capacity of the equipment. These ratings range from 5 to 30 minutes in duration. (Chapter 4) SIL.
See Surge Impedance Loading. (Chapter 3)
Simulated Winding Temperature Indicator ( WTI ). The most common device for measuring winding temperatures in power transformers. These devices simply measure the temperature of a specially calibrated heating element that is immersed in the top bulk oil near the tank wall. (Chapter 4)
Increased Power Flow Guidebook
SLiM. See Sagging Line Mitigator. (Chapter 2) Static Ratings . Limits on the level and duration of power transferred over a line based on specified worstcase weather conditions. (Chapter 2) Stray Flux Heating . Heating of non-current carrying
metal components by the leakage flux of the windings and leads. The leakage flux induces eddy current in any conducting material that it passes through. This includes the steel clamping structure, tie rods or tie plates, metal core bands, and the tank wall itself. Since leakage flux varies proportionally with load current, the stray flux heating increases roughly with the square of winding current. For larger power transformers and GSUs in particular, the problem of stray flux heating can be substantial. (Chapter 4)
Glossary
Time-To-Overload ( TTO ). Parameter indicating to the system operator how much time is left until equipment temperatures exceed safe limits. (Chapter 6) Top Oil Model. One of several methods of modeling the winding temperature of power transformers. Temperature calculation methods presented in Clause 7 of IEEE C57.91-1995. See also Bottom Oil Model and IEC Model 354-1991. (Chapter 4) Trapezoidal Wire (TW). Aluminum trapezoidal wire used
in conductors in place of round wires, which thereby potentially increases the cross-sectional area of a round wire conductor of the same diameter by approximately 20%. (Chapter 2) Upgrading. Using available infrastructure to economi-
cally put in new cables. (Chapter 3) Subconductor Oscillation . Wind-induced conductor
motion occurring with bundled phase conductors when wind speeds exceed a certain critical velocity. (Chapter 2)
Uprating. Improving the capacity of existing equipment. (Chapter 3)
Surge Impedance Loading (SIL) Limits. Limits involving a greater than allowable phase shift in power frequency from one end of a transmission system to the other. As a result, the two ends of the system cannot remain synchronous, resulting in instability and outages. This system stability consideration is generally an issue on overhead transmission lines that are 80-320 km (50-200 miles) in length. (Chapter 3)
Video Sagometer. EPRI device, based on digital video
TACSR.
See Thermal-resistant Aluminum Conductor Steel Reinforced. (Chapter 2)
Thermal Elongation. Metallurgical phenomenon in conductors where the material increases in length in proportion to an increase in temperature. (Chapter 2)
technology, for monitoring conductor sag in real time. (Chapter 2) Voltage Drop. Limit placed on power flow correspond-
ing to the maximum allowable decrease in voltage magnitude. (Chapter 2) “Worst-case” Weather Conditions for Line Rating Calculation. Weather conditions that yield the maximum or
near-maximum value of conductor temperature for a given line current. (Chapters 2 and 5) XD.
See Extruded Dielectric. (Chapter 3)
XLPE.
See Cross-Linked Polyethylene. (Chapter 3)
Thermal Property Analyzer (TPA). Device used for field
and laboratory measurement of thermal resistivity. (Chapter 3)
ZTACIR.
Thermal-resistant Aluminum Conductor Steel Reinforced (TACSR). Conductor widely used in Japan, with a
ZTAL
special type of aluminum strand capable of operating at temperatures up to 150 o C without losing tensile strength. (Chapter 2)
ZTAL aluminium alloy conductor reinforced by an Invar steel core. (Chapter 2) (“Super Thermal-resistant Aluminium”). An aluminium zirconium alloy that has stable mechanical and electrical properties after continuous operation at temperatures of up to 210oC. (Chapter 2)
G-5
Increased Power Flow Guidebook
Index All references are to section or subsection numbers.
A AAC Sag-tension calculations, 2.2.3 ACCR, 2.6.7 ACSR High-temperature sag, 2.2.3 Sag-tension models, 2.4.3 ACSS, 2.6.3 Air-core reactor, 5.3.3 Ampacity, 3.4.2 Ampacity audit, 3.6.5 Calculating ampacity, 3.4.5 Effect of various parameters, 3.4.6 Increasing ampacity (of underground cables), 3.6 Annealing, 2.4.2 B Bus conductors, 5.3.1 Bushings, 5.3.6 C Case studies Overhead, 2.8 Underground, 3.9 CGIT (Compressed Gas-Insulated Transmission) cables, 3.2.4 Compressed gas-insulated transmission cables, 3.2.4 Conductor blowout, 2.2.4 Conductor hardware, 2.4.14 Constraints on uprating overhead transmission lines, 2.2 Constraints on uprating underground cables, 3.5 Continuous (normal) rating, 6.6.1 Creep elongation, 2.4.12 Cross-linked polyethylene, 3.2.2 Current transformers, 5.3.7 D DTCR (Dynamic Thermal Circuit Rating), 2.7.5, 3.8.2, 3.8.3, 6.5 Dynamic monitoring, 2.7 Real-time monitors, 2.7.5 Video sagometer, 2.7.5
Dynamic ratings (overhead transmission), 2.3.1, 2.7.2 Advantages, 2.7.3, 3.8.3 Calculations, 2.7.6 Disadvantages, 2.7.4 Underground cables, 3.8 Dynamic ratings (underground cables), 3.8, 6.4.4 Benefits, 3.8.3 Dynamic Thermal Circuit Ratings, 3.8.2 Monitoring, 3.8.4 Quasi-dynamic ratings, 3.8.5 Dynamic Thermal Circuit Rating (DTCR), 2.7.5, 3.8.2, 3.8.3, 6.5 DTCR output, 6.5.2 Power circuit modeling, 6.5.1 Dynamic Thermal Ratings Condition assessment and real-time monitors, 6.3 Costs, 6.2.2 Field studies, 6.7 Models, 6.4 Accounting for heat storage, 6.4.1 Overhead lines, 6.4.2 Power Transformers, 6.4.3 Substation terminal equipment, 6.4.5 Underground cables, 6.4.4 Operating with dynamic thermal ratings, 6.6 E Electric field, 1.3.5 Electrical clearance, 2.2.5 Elongation Creep elongation, 2.4.12 Thermal elongation, 2.4.11 Emergency ratings, 2.4.1, 3.4.7 Environmental limits (for overhead transmission lines), 1.3.5, 2.1.4 EPR (Ethylene-Propylene-Rubber) cables, 3.2.2 Ethylene-Propylene-Rubber cables, 3.2.2 Extruded dielectric, 3.2.2 F FACTS (Flexible AC Transmission Systems), 1.3.3, 6.2.3 Flexible AC Transmission Systems, 1.3.3, 6.2.3
I-1
Index
G Gapped Construction, 2.6.6 H Heat balance methods, 2.3.5 Convection, 2.3.5 Ohmic losses, 2.3.5 Radiation, 2.3.5 Solar heating, 2.3.5 Steady-state thermal rating, 2.3.5 High-temperature operations (of overhead transmission lines), 2.4 Connectors at high temperature, 2.4.13 High-pressure fluid-filled cables, 3.2.1 High-pressure gas-filled cables, 3.2.1 High-pressure pipe-type cables, 3.2.1 Hot spots Identification (underground cables), 3.5.6 Remediation (underground cables), 3.6.6 HPFF (High-Pressure Fluid-Filled) cables, 3.2.1 HPGF (High-Pressure Gas-Filled) cables, 3.2.1 Hybrid (underground and overhead) circuits, 3.3.3 Hydraulic circuit, 3.5.8 I Ice loading, 2.2.7 Invar steel core conductor, 2.6.5 L Limiting conditions, 1.3 Circuit power flow limits, 1.3.1 Environmental limits, 1.3.5 Surge impedance loading of line, 1.3.2, 3.3.1 Thermal limits, 1.3.4, 3.3.1 Voltage drop limitations, 1.3.3 Linear low-density polyethylene cables, 3.2.2 Line traps, 5.3.8 LLPE (Linear Low-density Polyethylene) cables, 3.2.2 Long-time emergency rating, 6.6.1 Losses (underground cables), 3.4.3 M Magnetic field, 1.3.5 Mass impregnated cables, 3.2.4 MDPE (Medium-Density Polyethylene) cables, 3.2.2 Medium-density polyethylene cables, 3.2.2 MI (Mass Impregnated) cables, 3.2.4 Modeling Complex interfaces, 6.5.5 Power circuits, 6.5.1 Monitoring (underground cables), 3.8.4 N National Electric Safety Code, 2.2.5 NESC (National Electric Safety Code), 2.2.5 Normal rating, 2.4.1 I-2
Increased Power Flow Guidebook
O Ohmic losses, 2.3.5 Oil circuit breakers, 5.3.4 Operating with dynamic thermal ratings, 6.6 Overhead transmission lines Case studies, 2.8 Dynamic monitoring and line rating, 2.7 Disadvantages, 2.7.4 Dynamic rating calculations, 2.7.6 Dynamic ratings versus static ratings, 2.7.2 Real-time monitors, 2.7.5 Dynamic thermal rating models, 6.4.2 Effects of high-temperature operations, 2.4 Annealing of aluminum and copper, 2.4.2 Axial compressive stresses, 2.4.4 Built-in stresses, 2.4.5 Calculation of conductor high-temperature sag and tension, 2.4.8 Conductor hardware, 2.4.14 Connectors at high temperature, 2.4.13 Creep elongation, 2.4.12 Sag and tension of inclined spans, 2.4.7 Sag-tension calculations, 2.4.6 Sag-tension models for ACSR conductors, 2.4.3 Thermal elongation, 2.4.11 Wind speed effects on thermal ratings, 2.4.10 Line thermal ratings, 2.3 Heat balance methods, 2.3.5 Line design effects on line ratings, 2.3.4 Maximum conductor temperature, 2.3.2 Transient thermal ratings, 2.3.7 Weather conditions for rating calculations, 2.3.3, 2.3.6 Reconductoring without structural modifications, 2.6 ACCR conductor, 2.6.7 ACSS and ACSS/TW, 2.6.3 Gapped construction, 2.6.6 High temperature aluminum alloy conductors, 2.6.4 Invar steel core, 2.6.5 TW aluminum wires, 2.6.2 Uprating constraints, 2.2 Constraints on structural loads, 2.2.7 Electrical clearance, 2.2.5 Environmental effects, 2.2.8 High-temperature sag, 2.2.3 Loss of conductor strength, 2.2.6 Sag-tension calculations, 2.2.2 Wind-induced conductor motion, 2.2.4 Uprating without reconductoring, 2.5 Deterministic methods, 2.5.2 “Measure of Safety” as a basis for line rating, 2.5.4 Probabilistic methods, 2.5.3 Sagging Line Mitigator, 2.5.6
Increased Power Flow Guidebook
P Pipe-type cables, 3.2.1 Power flow example, 1.2 Power flow limits, 3.3 Load flow considerations, 3.3.2 Stability limits, 3.3.1 Surge impedance loading limits, 3.3.1 Thermal limits, 3.3.1 Uprating hybrid circuits, 3.3.3 Power system issues, 1.2 Power transformers Design, 4.2 Cooling types, 4.2.2 Core-form construction, 4.2.1 Directed flow designs, 4.2.1 Factory testing, 4.2.4 Losses, 4.2.3 Shell-form construction, 4.2.1 Dynamic thermal rating models, 6.4.3 Examples, 4.8 Modest increases in capacity, 4.7 Risks of increased loading, 4.3 Long-term risks, 4.3.2 Short-term risks, 4.3.1 Thermal modeling, 4.4 Bottom oil model, 4.4.3, 6.4.3 IEC model, 4.4.4, 6.4.3 Mechanisms of heat transfer, 4.4.1 Proposed IEC model, 4.4.5 Top oil model, 4.4.2, 6.4.3 Thermal ratings, 4.5 Ambient air temperature, 4.5.1 Condition-based loading, 4.5.5 Load, 4.5.2 Maintenance considerations, 4.5.6 Rating procedure, 4.5.4 Rating type and duration, 4.5.3 Winding temperature measurement, 4.6 Q Quasi-dynamic ratings (underground cables), 3.8.5 R Ratings Continuous (normal) rating, 6.6.1 Emergency ratings, 2.4.1, 3.4.7 Long-time emergency rating, 6.6.1 Short-time emergency rating, 6.6.1 Traditional rating definitions, 6.6.1 Underground cable ratings, 3.4 Reconductoring Overhead transmission lines, 2.6 Underground cables, 3.7 Resistances (underground cables), 3.4.4 Route thermal survey, 3.6.1
Index
S Sag High-temperature sag with aluminum conductors, 2.2.3 High-temperature sag with ACSR, 2.2.3 High-temperature sag-tension calculations, 2.4.9 SAG10, 2.2.2, 2.4.8, 2.4.9 Sag and tension of inclined spans, 2.4.7 Sag-tension calculations, 2.2.2, 2.4.6, 2.4.8, 2.5 Tension-elongation diagram, 2.2.2 Sag-tension models, 2.4.3 Sagging Line Mitigator, 2.5.5 SCLF (Self-Contained Liquid-Filled) cables, 3.2.3 Self-contained liquid-filled cables, 3.2.3 SF6 circuit breakers, 5.3.5 Shield/sheath bonding scheme, 3.6.8 Short-time emergency rating, 6.6.1 SIL (Surge Impedance Loading), 1.3.2, 2.1.1, 3.3.1 SLiM (Sagging Line Mitigator), 2.5.5 Stability limits, 3.3.1 Static ratings, 2.3.1 STESS software, 2.2.3 Substation terminal equipment Dynamic thermal rating models, 6.4.5 Equipment types and IPF opportunities, 5.2 Rating parameters, 5.2.1 Thermal models, 5.3 Air-core reactor, 5.3.3 Bus conductors, 5.3.1 Bushings, 5.3.6 Current transformers, 5.3.7 Line traps, 5.3.8 Oil circuit breaker, 5.3.4 SF6 circuit breaker, 5.3.5 Switch (air disconnect), 5.3.2 Thermal parameters, 5.5 Uprating, 5.4 Maintenance and inspection procedures, 5.4.2 Monitoring and communications, 5.4.1 Reliability and consequences of failure, 5.4.3 Superconducting cables, 3.7.5 Surge impedance loading, 1.3.2, 2.1.1, 3.3.1 Switches (air disconnect), 5.3.2 T T-Aluminum Conductor Steel Reinforced (TACSR), 2.6.4 Temperature monitoring (underground cables), 3.6.4 Tension-elongation diagram, 2.2.2 Thermal elongation, 2.4.11 Thermal limits, 1.3.4, 2.1.3, 3.3.1 Thermal models Substation terminal equipment, 5.2.1, 5.3 Underground cables, 4.4 I-3
Index
Thermal ratings Overhead transmission lines, 2.3 Dependence on weather conditions, 2.3.6 Dynamic ratings, 2.3.1 Heat balance methods, 2.3.5 Maximum conductor temperature, 2.3.2 Static ratings, 2.3.1 Transient thermal ratings, 2.3.7 Weather conditions for rating calculation, 2.3.3 Wind speed, 2.4.10 Power transformers, 4.5 Ambient air temperature, 4.5.1 Condition-based loading, 4.5.5 Load, 4.5.2 Maintenance considerations, 4.5.6 Rating procedure, 4.5.4 Rating type and duration, 4.5.3 Transformers. See Power transformers. TW aluminum wires, 2.6.2 U Underground cables Cable system types, 3.2 Compressed gas insulated transmission, 3.2.4 Extruded dielectric, 3.2.2 High-pressure pipe-type, 3.2.1 Mass impregnated, 3.2.4 Paper insulated lead covered, 3.2.4 Self-contained liquid-filled, 3.2.3 Case studies, 3.9 Dynamic ratings, 3.8, 6.4.4 Benefits, 3.8.3 Dynamic Thermal Circuit Ratings, 3.8.2 Monitoring, 3.8.4 Quasi-dynamic ratings, 3.8.5 Increasing ampacity, 3.6 Active uprating, 3.6.7 Ampacity audits, 3.6.5 Evaluation of load patterns, 3.6.3 Remediation of “hot spots,” 3.6.6 Review circuit plan and profile, 3.6.2 Route thermal survey, 3.6.1 Shield/sheath bonding scheme, 3.6.8 Temperature monitoring, 3.6.4 Power flow limits and system considerations, 3.3 Load flow considerations, 3.3.2 Stability limits, 3.3.1 Surge impedance loading limits, 3.3.1 Thermal limits, 3.3.1 Uprating hybrid circuits, 3.3.3 Ratings, 3.4 Ampacity, 3.4.2, 3.4.5, 3.4.6 Emergency ratings, 3.4.7 Equivalent thermal circuit and thermal resistances, 3.4.3
I-4
Increased Power Flow Guidebook
Inferring conductor temperatures from measured temperatures, 3.4.8 Losses, 3.4.3 Reconductoring, 3.7 Cupric oxide strand coating, 3.7.3 Larger conductor sizes, 3.7.2 Superconducting cables, 3.7.5 Voltage upgrading, 3.7.4 Uprating and upgrading constraints, 3.5 Accessories, 3.5.7 Direct buried cable systems, 3.5.1 Duct bank installations, 3.5.3 Fluid-filled cable systems, 3.5.2 Hot spot identification, 3.5.6 Hydraulic circuit, 3.5.8 Trenchless installations, 3.5.4 Uprating, active (underground cables), 3.6.7 Uprating case studies Overhead transmission lines, 2.8 Underground cables, 3.9 Uprating constraints (overhead transmission lines), 2.2 Constraints on structural loads, 2.2.7 Electrical clearance, 2.2.5 Environmental effects, 2.2.8 Limiting high-temperature sag, 2.2.3 Loss of conductor strength, 2.2.6 Sag-tension calculations, 2.2.2 Uprating constraints related to wind-induced conductor motion, 2.2.4 Uprating constraints (underground cables), 3.5 Direct buried cable systems, 3.5.1 Duct bank installations, 3.5.3 Fluid-filled cable systems, 3.5.2 Trenchless installations, 3.5.4 Uprating hybrid (underground and overhead) circuits, 3.3.3 Uprating substation terminal equipment, 5.4 Uprating without reconductoring (overhead transmission lines), 2.5 Deterministic methods, 2.5.2 Probabilistic methods, 2.5.3 Absolute method, 2.5.3 Exceedance method, 2.5.3 Modified exceedance method, 2.5.3 V Video sagometer, 2.7.5 Voltage drop, 1.3.3, 2.1.2 Voltage limits, 3.3.1 Voltage upgrading, 3.7.4 W Wind-induced conductor motion, 2.2.4 Wind loading, 2.2.7 Wind speed, effect on thermal ratings, 2.4.10
Increased Power Flow Guidebook
Index
X XD (Extruded Dielectric), 3.2.2 XLPE (Cross-Linked Polyethylene), 3.2.2
I-5
Export Control Restrictions
The Electric Power Research Institute (EPRI), with major
Access to and use of EPRI Intellectual Property is granted with the
locations in Palo Alto, California; Charlotte, North Carolina; and
specific understanding and requirement that responsibility for ensur-
Knoxville, Tennessee, was established in 1973 as an independent,
ing full compliance with all applicable U.S. and foreign export laws
nonprofit center for public interest energy and environmental
and regulations is being undertaken by you and your company. This
research. EPRI brings together members, participants, the Institute’s
includes an obligation to ensure that any individual receiving access
scientists and engineers, and other leading experts to work
hereunder who is not a U.S. citizen or permanent U.S. resident is
collaboratively on solutions to the challenges of electric power. These
permitted access under applicable U.S. and foreign export laws and
solutions span nearly every area of electricity generation, delivery,
regulations. In the event you are uncertain whether you or your com-
and use, including health, safety, and environment. EPRI’s members
pany may lawfully obtain access to this EPRI Intellectual Property, you
represent over 90% of the electricity generated in the United States.
acknowledge that it is your obligation to consult with your company’s
International participation represents nearly 15% of EPRI’s total
legal counsel to determine whether this access is lawful. Although
research, development, and demonstration program.
EPRI may make available on a case-by-case basis an informal assessment of the applicable U.S. export classification for specific EPRI
Together...Shaping the Future of Electricity
Intellectual Property, you and your company acknowledge that this assessment is solely for informational purposes and not for reliance purposes. You and your company acknowledge that it is still the obligation of you and your company to make your own assessment of the applicable U.S. export classification and ensure compliance accordingly. You and your company understand and acknowledge your obligations to make a prompt report to EPRI and the appropriate authorities regarding any access to or use of EPRI Intellectual Property hereunder that may be in violation of applicable U.S. or foreign export laws or regulations.
Program: Increased Transmission Capacity
© 2005 Electric Power Research Institute (EPRI), Inc. All rights reserved. Electric Power Research Institute, EPRI, and TOGETHER...SHAPING THE FUTURE OF ELECTRICITY are registered service marks of the Electric Power Research Institute, Inc.
Printed on recycled paper in the United States of America
1010627
Electric Power Research Institute 3420 Hillview Avenue, Palo Alto, California 94304-1338 • PO Box 10412, Palo Alto, California 94303-0813 USA 800.313.3774 • 650.855.2121 •
[email protected] • www.epri.com