PROJECT : PARAS T.P.S EXPANSION PROJECT 2 X 250 MW PLANT
: 1000 m3/hr EFFLUENT TREATMENT PLANT
DOC. NO. : HT(PCD)-MSPG-PARAS-E-15 Rev. 0 TITLE A)
: LIGHTING FIXTURES CALCULATION
INTERNAL ILLUMINATION ASSUMPTIONS
:-
1
Following legends are used in the lighting Design Calculations
i)
R.I =
Room Index
ii)
F.L.=
Surface Reflection on Floor
= 10
%
iii)
C.L.=
Surface Reflection on Ceiling
= 70
% %
iv)
(For Clean Area)
v)
W.L. = Surface Reflection on wall
= 50
vi)
M.F. = Maintenance Factor
= 0.65
vii) COU = Coefficent of Utilisation a)
= 0.48
CALCULATION OF ROOM INDEX LxB H x ( L+B)
Room Index (R.I.) = where,
L
=
Length of room in meters
B H
= =
Breadth of room in meters Mounting height of fittings in meters
PARAMETER
SYMBOL
Length (Mtr.)
L
MCC ROOM 8.76
Breadth of Room in mtr.
B
6.5
6.5
Mounting Height of fitting in mtrs.
H
5.0
5.0
LxB H(L+B)
0.75
0.95
Room Index (RI)
b)
=
PUMP HOUSE 17.98
Calculation of Lighting fittings required 2
No. of lighting fittings required =
Area (A) in m x Lux Level Desired No. of Lamps x Lamp Lumens x COU x MF
Where, MF =
Maintenance facture
COU = Coefficient of Utilisation
2/3
PROJECT : PARAS T.P.S EXPANSION PROJECT 2 X 250 MW PLANT
: 1000 m3/hr EFFLUENT TREATMENT PLANT
DOC. NO. : HT(PCD)-MSPG-PARAS-E-15 Rev. 0 TITLE Sr. No.
: LIGHTING FIXTURES CALCULATION
Parameter
Symbol
Pump House
MCC room
1
Length in Mtr
L
17.98
8.76
2
Width in Mtr
W
6.5
6.5
3 Area Sq. Mtr
A
116.87
56.94
2 * 36 W Industrial with Reflector
2 * 36 W Industrial with Reflector
l
2 * 3200
2 * 3200
Lx
200
200
COU
0.48
0.48
MF
0.65
0.65
11.71
5.70
12
6
4
Type of fixture
5
Lumen O/P of tube Rod
6
Lux level required
7
Coeff. Of Utilisation
8
Maint. Factor
9
No. of fittings required = (A x Lx)/ (lxCOUxMF)
10 No of fittings provided TOTAL FIXTURES PROVIDED
= 12+ 6 + 2 Nos for staircase
(INTERNAL ILLUMINATION)
=
20
=
2 x 36 x 20
W
=
1440
W
Total load of internal illumination
B)
Nos
EXTERNAL ILLUMINATION ON TANK & PERIPHERY TOTAL NO OF FIXTURES PROVIDED = 15 x 125 HPMV LAMPS
1875 W
TOTAL NO OF FIXTURES PROVIDED = 15 x 250 HPMV LAMPS
3750 W
INTERNAL & EXTERNAL ILLUMINATION LOAD =
1400+1875+3750 =
7065 W
TOTAL NO OF RECEPTACLES PROVIDED W ITH PLUG ( INDUSTRIAL TYPE) = 3 Nos ( 63 Amp two nos. in Pump House & one no. in MCC room) TOTAL NO OF RECEPTACLES PROVIDED WITH PLUG ( DECORATIVE TYPE) = 1 No. MCC room = 6 Nos 5 Amp in Pump House