IET Lecture - LV Circuit Design September 2014
Short Description
LV wWiring design and circuit configuration...
Description
Cable Sizing Fundamentals and E l e c t r i c a l LV S t a n d a r d Armada Hotel, Petaling Jaya 2 3 rd A u g u s t 2 0 1 4
Cable Sizing For Safe Power System Based on IEC Standards I r . H . P. L o o i ( m e k t r i c o n @ g m a i l . c o m ) B.Eng (Hons), FIEM, Jurutera Gas
Part
1
–Circuit
Design
2
SYNOPSIS
‘Cable sizing is a fundamental skill set required of the design engineer. Unfortunately the theory and empirical basis on which cable sizing rest on is not well understood amongst practicing engineers. Such gaps in knowledge may have implication in the design of wiring systems particularly on the safety of wiring systems (particularly thermal safety). This Presentation provides an introduction to basic concepts in sizing of cables in electrical (LV) system based on the IEC standards. The presentation is based on the handbook published and is in the following logical procession: 1.
Introduction
2.
Scope
3.
General Design Procedure (design road map)
4.
Earthing system
5.
Cable types & installation method
6.
Circuit configuration 23 r d August 2014
7.
Conductor sizing
3
THE SPONSOR – WIRING HANDBOOK
‘The International Copper Association Ltd. (ICA) is a non-profit organization promoting the use of copper worldwide . ICA increases awareness and usage of copper by communicating its unique attributes as a sustainable element an essential to life, science and technology, and a higher standard of living. ICA Southeast Asia established by ICA in 1992 acts as a strategic and networking base for regional copper and associated industries’ associations.
This handbook is distributed FREE courtesy of the sponsor 23 r d August 2014
5
INTRODUCTION – ROAD MAP TO IEC60364
Protection Device
Load Estimation
Cable Selection L.V. Wiring Design
Circuit Configuration
Installation Method
Earthing Verification Equipment Selection
23 r d August 2014
23 r d August 2014
8
VOLTAGE STANDARD
Malaysian Standard Voltages It is a misconception that Malaysia Standard Voltage is at 415V/240V !
As of 1st January 2008, Malaysia Standard Voltage is declared at 400V/230V Refer ST link for the official notification.
Rationalisation of voltage is to bring Malaysia in line with other member countries of the IEC. Singapore and the UK has already converted to 400V/230V from the old 415V/240V. Other IEC member countries which have yet to convert are Germany / China (380V/220V) and India (415V/240V). Practitioners must therefore design power distribution system to 400V/230V. 23 r d August 2014
9
VOLTAGE STANDARD
Malaysian Standard Voltages at 400V/230V +10%, -6% Electrical power distribution system should be designed to 400V/230V ! Change all reference in specifications to 400V/230V. Specify transformers at nominal 11kV/420V (not 11kV/433V). Check cable sizing as 400V/230V incur about 4% higher current.
Major reasons for rationalising to 400V/230V Standardisation among IEC countries. Multiple certification due to different voltage levels is avoided or minimised. Most motors and fluorescent light fittings works most efficiently within the voltage band of 210V to 220V. Thus reducing to 220V will Save energy Prolong life-span of electrical equipment. 23 r d August 2014
10 VOLTAGE STANDARD
Version 3 Published in 2013! 23 r d August 2014
23 r d August 2014
11 THE DESIGN WORK FLOW
23 r d August 2014
13 EARTHING SYSTEM 60364 - Part 1; 312 – 2 Letters definition:
23 r d August 2014
14 EARTHING SYSTEM
23 r d August 2014
15 EARTHING SYSTEM Network / Operation Criteria Service Criteria
System Chosen / Preferred
Competent Maintenance
Continuity of service critical
Available
IT System preferred
Continuity of service critical
Not consistently available
No satisfactory solution IT system preferred as discriminitive trippings are easier to implement and damages less with respect to TN system
Continuity of service NOT critical
Available
TN-S system preferred (rapidrepairs and extension easily performed.
Continuity of service NOT critical
Not available
No satisfactory solution. IT system preferred.
Fire hazard critical
Available
IT system and use of 5mA RCD or TT system preferred.
Special feature, very long networks
Assumed available
TT preferred
Special feature, standby power supply
Assumed available
TT preferred
Special feature, load sensitive to high currents (e.g. motors)
Assumed available
TT preferred; IT can be acceptable
Special feature, low natural insulation (furnace) OR very large HF filters (computers)
Assumed available
TN-S preferred
Special feature, control and monitoring systems
Assumed available
23 r d August 2014
IT for continuity of services; TT for enhanced equipotential
16 EARTHING SYSTEM – SIZING OF P.E. (TT)
60364-5-54, 312 : For TT system, PE need for exceed 25mm² (copper) 35mm² (aluminium)
As TT system effectively DO NOT have PE cables within the distribution system, this may presumably mean the earth electrode or frame earth system.
23 r d August 2014
17 EARTHING SYSTEM – SIZING OF P.E. (TNS) 60364-5-54, 543 For TN-S system (method 1): Cross sectional areas of line conductors S (mm²)
If the protective conductor is of the same material as the line conductor
If the protective conductor is not of the same material as the line conductor
S < 16
S
K1/K2 x S
16 < S < 35
16 a
K1/K2 x 16
S > 35
Minimum cross sectional area of the corresponding protective conductor (mm²)
S/2
a
K1/K2 x S/2
Where K1 is the value of k for the line conductor, selected from table A54.1 or from the tables of IEC50364-4-43 according to the resistance of the conductor and insulation. K2 is the value of k for the conductor selected from tables A 54.2 to A54.6 as applicable a
for a PEN conductor the reduction of the cross section area is permitted only in accordance with the rules for sizing of the neutral conductor (see IEC 23 r d August 60364-5-52).
2014
18 EARTHING SYSTEM – SIZING OF P.E. (TNS) 60364-5-54, 543 For TN-S system where the protective device afford disconnecting time NOT exceeding 5 seconds, the following formula may apply:
S = PE size (mm²); I = prospective fault current rms; t = operating time of protection device; k = factor based on conductor material and insulation.
23 r d August 2014
19 EARTHING SYSTEM – SIZING OF P.E. (TNS) 4x16mm² PVC + 1x16mm² PVC (PE)
Case :
SCI=10kA
Calculating I² t for PE:
70°C PVC cables
30A CB
k= 115
30A MCB class C, trip time
SC I=
3 kA
5 kA
6 kA
10 kA
15 kA
25 kA
t=
0.1 s
0.01 s
0.01 s
0.01 s
0.01 s
0.01 s
8.25
4.3
5.2
8.7
13.0
21.7
0.01 s
0.01 s
0.01 s
0.01 s
0.01 s
0.01 s
2.61
4.3
5.2
8.7
13.0
21.7
S min size of PE cable (mm²) 32A gG Fuse, trip time S min size of PE cable (mm²)
t=
From the above, we note that for up 15kA rating table 54.3 sizing for PE cable will be acceptable in terms of “energy-let-through” for both gG fuses and MCB class C and B types. 23 r d August 2014
23 r d August 2014
21 CABLE TYPES Cable types and installation methods have implication for cable sizing and Ampere capacity. IEC60364-5-52 : Cable Selection can be summarised:
23 r d August 2014
22 CABLE TYPES – ASSESSING CONDITIONS Part 5-51 defines environmental classes for use in defining installation and equipment selection criteria:
A A 2 Number – severity index 2nd alphabet – Specific conditions
A = Environment B = Utilisation C = Building
Specific conditions of environment usage etc are coded. Later prescription in standards specify technical conditions concerning conditions code.
23 r d August 2014
23 CABLE TYPES – ASSESSING CONDITIONS
External influences
Selection considerations
AA4, and AA5
Normal cable insulation PVC, or XLPE
AD5 to AD7
Ambient temp. -5ºC to +40ºC Presence of water
AE5 and AE6
Dusty atmosphere
AG3
Mechanical stress
AH2
Vibrations
AM1
Harmonics
Cable jointing glands to be IPX5 and better, extruded inner sheath for cables for AD7 (submerged) Cable jointing glands to be IP6X, bare conductor on insulator not recommended. Underground cables, mechanical protection of cables, sheathing of cables, armouring of cables, cable in ducts Connections to motor; termination lugs, cable slack to allow for vibration Mitigations for harmonics; Annex D in 60364-5-52 23 r d August 2014
24 CABLE TYPES – ASSESSING CONDITIONS
External influences
Selection considerations
AN3
Solar radiation
AP3 and AP4
Seismic effect
BD2 and BD4
Emergency evacuation; difficult exit Fire risk
Cable sheath or insulation which are immune against UV radiation (PVC sheath or insulation not permitted). Cable tray preferred over conduit, slack in cable run etc. Low smoke (LSZH) cables
BE2 CA2 CA2 and BE2
Presence of combustibles Combustibles and explosion risk
Fire rated cables for essential services; LSZH cables Fire rated cables for essential services; LSZH cables Design to IECEx standard IEC 60079 series. 23 r d August 2014
25 CABLES FOR FIRE & SMOKE CONDITIONS Flame retardant cables do not promote or propagate the spread of fire. Flame retardant cable installation is specified under conditions of emergency evacuation (BD2 and BD4 external influences). These conditions of emergency evacuation also apply in building spaces designated as fire escape routes or emergency evacuation routes under “life safety” standards for building design.
The ‘degree’ of flame retardant required will depend on the designed ‘evacuation-time’ of the escape routes. The test for compliance to flame retardant properties are defined in the IEC 60332 series: IEC 60332-1 & 60332-2; flame propagation test on single cable is the most basic flame retardant test (whilst Part 1 specify 1kW flame for general insulated cables, Part 2 specify ‘diffuse’ flame for single insulated small cables); IEC 60332-3; specify more stringent flame propagation test on bunched cables.
23 r d August 2014
26 CABLES FOR FIRE & SMOKE CONDITIONS
Low Smoke, Zero Halogen (LSZH) cables reduces smoke with zero halogen emission. Classes of cables listed as Low Smoke Flame Retardant (LSFR) or Low Smoke Zero Halogen (LSZH) are defined by the following test standards: The test for Low Smoke is the smoke density test of IEC 61034; The test for halogen emission is specified in IEC 60754-1; and The test for degree of acidity of is specified in IEC 60754-2.
23 r d August 2014
27 CABLES FOR FIRE & SMOKE CONDITIONS Fire Resistant (FR) cables can maintain circuit integrity even in the presence of a fire. The test for fire resistive behaviour is specified in IEC 60331 fire integrity tests. FR cables are mandatory where essential services (e.g. fire fighting services, fire lifts etc) require ‘circuit survivability’ even during a fire emergency). 1. LSFR, LSZH sheath 2. Binder tape 3. Filler, non-hygroscopic
4. Insulation, XLPE-FR 5. Mica tape (fire resistant barrier) 6. Conductor, solid or stranded.
23 r d August 2014
28 CABLES FOR FIRE & SMOKE CONDITIONS
23 r d August 2014
29 CABLES FOR FIRE & SMOKE CONDITIONS
23 r d August 2014
30 CABLE TYPES
23 r d August 2014
31 CABLE TYPES – COMMON DEFECTS Conductors and cables
Bare conductors
Insulated conductors
Sheathed cables (including armoured and mineral insulated) Multi core Single core NA
Method of Installation
Without fixings Clipped direct Conduit systems Cable trunking systems (including skirting trunking, flush floor 1 trunking) Cable ducting systems Cable ladder, cable tray, cable brackets On insulators NA NA Support wire – permitted – not permitted NA – not applicable or not normally used in practice 23 r d August 2014 Table 5A – Cable installation method and cable types from IEC 60364-5-52
32 CABLE TYPES – COMMON DEFECTS Some Common Defects 1. PVC conduit system are substandard and are NOT certified to electrical grade. 2. PVC conduit and/or cables laid in condition where continuous sunlight occurs (PVC will deteriorate in the presence of UV light). 3. Conduit embedded in concrete are of the wrong grade (conduit not properly graded will crack when laid in concrete).
4. No proper junction boxes and/or terminal boxes. 5. Trunking and/or conduit ‘overloaded’. 6. Splicing/jointing of cables without proper terminal box.
No proper evaluation on firerating of cables in complying with fire properties.
PVC products should NOT be installed exposed to sunlight. 23 r d August
2014
23 r d August 2014
34 CIRCUIT CONFIGURATION – EARTHING
23 r d August 2014
35 CIRCUIT CONFIGURATION
23 r d August 2014
36 CIRCUIT CONFIGURATION
23 r d August 2014
37 CIRCUIT CONFIGURATION
23 r d August 2014
38 CIRCUIT CONFIGURATION
23 r d August 2014
39 CIRCUIT CONFIGURATION
23 r d August 2014
40 CIRCUIT CONFIGURATION
23 r d August 2014
Cable Sizing Fundamentals and E l e c t r i c a l LV S t a n d a r d Armada Hotel, Petaling Jaya 2 3 rd A u g u s t 2 0 1 4
Cable Sizing For Safe Power System Based o n I E C S t a n d a r d s I r . H . P. L o o i ( m e k t r i c o n @ g m a i l . c o m ) B.Eng (Hons), FIEM, Jurutera Gas
Part
1
–Circuit
Design
Intermission-Continue to Part 2,,,
View more...
Comments