Iec61850 Und Sicam

January 12, 2018 | Author: sahil4IND | Category: Scada, Electrical Substation, Web Server, Automation, Electric Power Transmission
Share Embed Donate


Short Description

sicam...

Description

Power Transmission and Distribution

IEC 61850 & SICAM PAS

Power Transmission and Distribution

ENERGY AUTOMATION No. 1 with Energy Automation

Welcome! GüntherFleischer Fleischer Günther

SiemensAG, AG,PTD PTDEA2 EA2BD3 BD3 Siemens BusinessDevelopment Development Business EnergyAutomation Automation Energy

Regionen:Mercosur Mercosurand andPortugal Portugal Regionen: Tel. +49(0)911 (0)911/ /433-8254 433-8254 Tel. +49

Mobil: +49 +49(0)172 (0)172/ /351 3511910 1910 Mobil: Email:[email protected] [email protected] Email:

Energy Automation Buenos Aires Nov ‘05

Page 2

Power Transmission and Distribution

Present Situation of communication protocols for Substations No. 1 with Energy Automation

Most protocols have origins of low data rates

Energy Automation Buenos Aires Nov ‘05

Page 3

Power Transmission and Distribution

Present Situation of communication protocols for Substations No. 1 with Energy Automation

There are over 50 protocols worldwide for substation automation.

Energy Automation Buenos Aires Nov ‘05

Page 4

Power Transmission and Distribution

IEC 60870-5-… has gained acceptance No. 1 with Energy Automation

Corporate Network TCP/IP

Control Center

IEC 60870-5-104

IEC 60870-5-101

IEC 60870-5-103 FO in star configuration

IEC 60870-5-103 RS485-Bus

...

Profibus FMS Lon-Bus ….

Substation Energy Automation Buenos Aires Nov ‘05

Page 5

Power Transmission and Distribution

Technological Trends – Overview No. 1 with Energy Automation

yesterday

Energy Automation Buenos Aires Nov ‘05

today

Page 6

Power Transmission and Distribution

Communication Standards outside of Substations No. 1 with Energy Automation

Market 195 TR 2 6 C IE Participant IEC 61970 EMSEC, EDI ISO 9735

Control Centre 2 IEC 60870-5-101, -104, IEC 60870-6 (TASE.2), ELCOM90, DNP3 Power Plant

IEC 60870-6 (TASE.2), ELCOM90, DNP3, IEC 60870-5-101, -104

Server IEC 61968 DMS Control Centre 1 IEC 60870-5-101, -104, IEC 60870-6 (TASE.2), ELCOM90, DNP3

IEC 0 87 60

IEC 60870-5-101, IEC 60870-5-104, DNP3

IEC 6 1400 25

70 8 0 6 IEC 5 PoleTop

PU

02 -1 -5

Substation

IEC IEC 6110 620 7 56

Metering Billing PU Substation

(IEC 60834, IEEE 1565) Energy Automation Buenos Aires Nov ‘05

Page 7

Power Transmission and Distribution

Possible trend in the future No. 1 with Energy Automation

Market 195 TR 2 6 C IE Participant

Control Centre 2

IEC 61970 EMSEC, EDI ISO 9735

Server IEC 61968 DMS Control Centre 1

IEC 60870-6 (TASE.2)

IEC 61850

IEC 62210

IEC 61850

Substation 1IEC

61850

0 185 6 IEC CT VT

PoleTop

Power Plant

IEC 61850 IEC 6 1400 -25 IEC 620 56

Substation 2

IEC 61850

CT VT

Metering Billing

IEC 61850 Energy Automation Buenos Aires Nov ‘05

Page 8

Power Transmission and Distribution

Communication Standards within Substations IEC 61850 SU

B&B ComU

IEC 61850-8-1, IEC 60870-5-103, Profibus, Modbus, LON, DNP3, UCA.2, etc.

brown colour: no meaning in the future for substation control

SB PU

CU

C/ P

Filter

No. 1 with Energy Automation

IEC 61850-9-2, IEC 61850-8-1, CT VT

SG

IEC 62271-003 CAN, MVB, etc.

SG

PB CT VT

CT VT

IEC 61850-9-2,

IEC 60044-1 (1A/5A) IEC 60044-2 (100V)

SU - Station Unit PU - Protection Unit CU - Control Unit

PU

IEC 61850-9-1, IEC 60044-8 C/P Control/Protection Unit CT,VT - Instrument Transformer ComU - Communication Unit

Energy Automation Buenos Aires Nov ‘05

SB - Station Bus PB - Process Bus SG - Switchgear Page 9

Power Transmission and Distribution

Requirements of utilities - worldwide No. 1 with Energy Automation

n Long-term expandability of a system n

Possibility of combining a variety of manufacturers

n

Long-term exchangeability of equipment for simpler stocking of parts

n Saving time and reducing costs n

Investment expenditure and operation costs

n

Costs and time for changes and expansion made in service

n

Execution time of Projects

n Manageable complexity n

seamless, self-describing engineering

n

etc.

Energy Automation Buenos Aires Nov ‘05

Page 10

Power Transmission and Distribution

Architecture of a modern Substation Automation System No. 1 with Energy Automation

Distributed Intelligence n No more bottlenecks and classical master / slave architecture n Intelligence moves closer to the process due to distributed functionality using enhanced bay controller

SCADA Engineering Browser

SCADA Communication

Corporate Network TCP/IP

HMI SCADA / WAN

Station Unit

HMI

Master Unit

Station Bus Ethernet IEC 61850

Slave

Slave

e.g. I/O Unit

e.g. I/O Unit

BU

PU

BU

PU

independent communication Process

Master / Slave Architecture Energy Automation Buenos Aires Nov ‘05

Client / Server Architecture providing distributed intelligence Page 11

Power Transmission and Distribution

IEC 61850 - The way to an international standard for Substation IT No. 1 with Energy Automation

IEC 61850

Only IEC 61850 is able to provide a complete solution for Substation IT

US approach UCA™ 2

All major vendors of substation technology are active members of the IEC 61850 Working Groups

The international agreed goal IEC 60870-5 IEC 60870-6 experience

one world one technology one standard

IEC 61850

Energy Automation Buenos Aires Nov ‘05

The US committee US TAG for Working Groups 10, 11 and 12 of IEC TC57 clearly reaffirms that they support IEC 61850 as the only living standard for substation automation SIEMENS promotes the IEC 61850 work with 6 active members and numerous pilot projects Siemens project Substation IT coordinates a seamless communication technology within Siemens PTD

Page 12

Power Transmission and Distribution

3 Working Groups - 60 Experts - 14 Countries No. 1 with Energy Automation

WG10: Functional architecture and general requirements WG11: Communication within and between unit and station levels WG12: Communication within and between process and unit level 6 Siemens Member, partly editors

WG – Working Group Energy Automation Buenos Aires Nov ‘05

Page 13

Power Transmission and Distribution

The Solution: IEC 61850 No. 1 with Energy Automation

IEC 61850 One World

One Technology One Standard

Energy Automation Buenos Aires Nov ‘05

Page 14

Power Transmission and Distribution

IEC 61850 – present areas of application No. 1 with Energy Automation

Gasisolierte Schaltanlagen Gas insulated substations

Highly integrated Hoch Integrierte Schaltanlage HIS®® Substation HIS

IEC 61850 Luftisolierte Schaltanlagen Air insulated substations

Energy Automation Buenos Aires Nov ‘05

Medium-voltage substations

Page 15

Power Transmission and Distribution

Application Areas of the standard IEC 61850 No. 1 with Energy Automation

Control Centre harmonisation with CIM (IEC 61970) Station level

EthernetBasis

Engineering

Communication between bay devices Process connection

Energy Automation Buenos Aires Nov ‘05

Page 16

Power Transmission and Distribution

What does IEC 61850 achieve? No. 1 with Energy Automation

System configuration

Standardised language for describing substation

Standard communication with TCP - IP

Energy Automation Buenos Aires Nov ‘05

Defines structure for protection and control

IEC 61850

Based on Ethernet standard

Communication between bay devices

Fault records in Comtrade format

Time synchronisation with SNTP

Page 17

Power Transmission and Distribution

Ethernet: A Data Highway for everything No. 1 with Energy Automation

Transmission system

100 Mbit/s Ethernet § § § §

Bay devices to station controller Inter-device communication Remote setting of parameters etc.

DIGSI

à One communication technology in the substation

Energy Automation Buenos Aires Nov ‘05

Page 18

Power Transmission and Distribution

IEC61850 runs on Ethernet and TCP/IP Siemens provides redundancy to it No. 1 with Energy Automation

STP 62,5µ or 50µ Fibre

100 Mbit/s Ethernetring with ring management

Siemens provides redundancy down to the devices

TP

TP

TP

Energy Automation Buenos Aires Nov ‘05

Page 19

Power Transmission and Distribution

IEC61850 – Ethernet validated components No. 1 with Energy Automation

Energy Automation Buenos Aires Nov ‘05

Page 20

Power Transmission and Distribution

New Architecture creates Advantages No. 1 with Energy Automation

Distributed Intelligence n No more classical Master/Slave configuration and bottlenecks Corporate Network TCP/IP

Engineering Browser

HMI

Station Unit SCADA – WAN

Station bus Ethernet IEC61850

independent communication Process

Client / Server Architecture with Distributed Intelligence Energy Automation Buenos Aires Nov ‘05

Page 21

Power Transmission and Distribution

Client-Server Architecture No. 1 with Energy Automation

• Client holds connections with several Servers

Energy Automation Buenos Aires Nov ‘05

Page 22

Power Transmission and Distribution

Client-Server Architecture No. 1 with Energy Automation

• Server supports connections with several Clients simultaneously Energy Automation Buenos Aires Nov ‘05

Page 23

Power Transmission and Distribution

Interoperability No. 1 with Energy Automation

What are required for Interoperability Uniform standardisation: § Service (Service model) § Language (Data model) § Protocol § Communication medium § Engineering date-exchange § Conformity testing IEC 61850 fulfils these Requirements

Energy Automation Buenos Aires Nov ‘05

Page 24

Power Transmission and Distribution

The idea behind IEC 61850: Separation No. 1 with Energy Automation

Separation of: Application

(e.g. Protection)

Service

(e.g. Control, Report)

Communication

(e.g. MMS/TCP/IP/Ethernet)

IEC 61850: Data DataModel Model

Services, Services,Rules Rules

Mapping Mapping

because Data did not change and will not change but the communication technology will Energy Automation Buenos Aires Nov ‘05

Page 25

Power Transmission and Distribution

IEC 61850 – GOOSE Principle A device sends information by Multicasting. Only devices which are subscribers receive this message. In the example, Receiver Z receives the message. Receiver Y is not a subscriber.

EXAMPLE:

GOOSE Receiver Device Y Ethernet

GOOSE Sender Device X

GOOSE message

No. 1 with Energy Automation

GOOSE Receiver Device Z

GOOSE (Generic Object Oriented Substation Event) Energy Automation Buenos Aires Nov ‘05

Page 26

Power Transmission and Distribution

IEC 61850 – GOOSE Principle No. 1 with Energy Automation

Priority Tagging of GOOSE Telegrams Ethernet-Switch Overtake lane for IEC GOOSE fast GOOSE

Normal Telegrams Buffer for normal telegrams

Only IEC 61850 benefits from the options of modern 100 Mbit-Ethernet. Not UCA2.0, not DNP, not T104 ! Energy Automation Buenos Aires Nov ‘05

Page 27

Power Transmission and Distribution

Engineering Process according to IEC 61850: Solution No. 1 with Energy Automation

Device description Manufacturer X System configuration

Siprotec device library

SIPROTEC

Device configuration System description

Device configuration Manufacturer X

Basic data Station controller Energy Automation Buenos Aires Nov ‘05

Page 28

Power Transmission and Distribution

First manufacturer worldwide with an IEC 61850 certificate from KEMA No. 1 with Energy Automation

Energy Automation Buenos Aires Nov ‘05

Page 29

Power Transmission and Distribution

IEC 61850: Interoperability No. 1 with Energy Automation

Interoperability is the ability of two or more IEDs from the same vendor, or different vendors, to exchange information and uses that information for correct co-operation.

Energy Automation Buenos Aires Nov ‘05

Page 30

Power Transmission and Distribution

IEC 61850: Main Interoperability Projects No. 1 with Energy Automation

The way to interoperable substation automation 2000

2001

2002

2003

2004

2005

IEC 61850

2006

First Products and Systems Interoperability “System” ABB, ALSTOM, SIEMENS Interoperability “Between Bay Devices” ABB, ALSTOM, SIEMENS

Interoperability “Extended” ABB, SIEMENS Interoperability “Sampled Values” ABB, SIEMENS, KEMA Interoperability “Between Bay Devices” ABB, OMICRON, SIEMENS Interoperability “Bay Devices and Station Controller” ABB, ALSTOM, SIEMENS

Energy Automation Buenos Aires Nov ‘05

Page 31

Power Transmission and Distribution

Configuration at Hanover Fair ‘04 No. 1 with Energy Automation

Station Unit

KEMA UNICA Analyser

100 Mbit/s Ethernet

ABB

Areva

SIEMENS

OMICRON

OMICRON - Stand, Halle 12 A65 Energy Automation Buenos Aires Nov ‘05

Page 32

Power Transmission and Distribution

The Key is Interoperability No. 1 with Energy Automation

Energy Automation Buenos Aires Nov ‘05

Page 33

Power Transmission and Distribution

IEC 61850 Ready to go! No. 1 with Energy Automation

Specification as an IEC-Standard

Users are active

Example: VDN-Projektgruppe IEC 61850 ....

Test tools

.... Developments by market leaders

Interoperability tests

Energy Automation Buenos Aires Nov ‘05

Page 34

Power Transmission and Distribution

IEC 61850 – Benefit of the User No. 1 with Energy Automation

• Time savings in projects, operations and maintenance of substations

• Cost savings through the use of Ethernet

• Internationally valid and checked interoperability gets rid of frustration arising from the system

Energy Automation Buenos Aires Nov ‘05

Page 35

Power Transmission and Distribution

IEC 61850 – Ready for Use No. 1 with Energy Automation

• IEC 61850 specification has been approved as international Standard • Tools for Analysis and Tests are available • Interoperability Tests were successfully carried out

Energy Automation Buenos Aires Nov ‘05

Page 36

Power Transmission and Distribution

IEC 61850 – Layout for station bus No. 1 with Energy Automation

Corporate Network TCP/IP

Control Center IEC T101

IEC T104 SCALANCE S Security-module Router

Serial Hub 103 over Ethernet

IEC61850 Stations - Bus

IEC 61850 (Ethernet) Protection - Control IEC 6087060870-5-103 for Protection

Energy Automation Buenos Aires Nov ‘05

Page 37

Power Transmission and Distribution

IEC 61850: Basic applications and possible extensions No. 1 with Energy Automation

§ Substation automation IEC 61850

§ Telecontrol of substations ‘Seamless Information/Automation Architecture’ in discussion, IEC TC57 / Ad Hoc Working Group 07

§ Addendum Power Quality, Monitoring under way, IEC 61850

§ Product standard for switchgear equipment under way, IEC 62271-003

§ Control and monitoring of wind power plants under way, IEC 61400-25

§ Control and monitoring of distributed energy resources under way, IEC 62350

§ Control and monitoring of hydroelectric power plants under way, IEC 62344

§ Settings for Protection, Logging and Disturbance Recorder IEEE PSRC H5 (some more groups dealing with IEC 61850, C3, H6, JTF4)

§ Metering (EPRI, IEEE), Gas, Water in discussion

Energy Automation Buenos Aires Nov ‘05

Page 38

Power Transmission and Distribution

Comparison of Different Standards/Protocols No. 1 with Energy Automation

IEC 608705-103

Profibus

DNP

Modbus

LON

IEC 61850

Control Centre Level

-

-

Yes

-

-

Yes (future)

Station Level

Yes

Yes

Yes

Yes

Yes

Yes

Bay Level

Yes

Yes

Yes

Yes

Yes

Yes

Process Level

no

no

no

no

no

Yes

Engineering Support

no

partly

no

no

no

Yes

partly

partly

no

no

no

Yes

Global Adoption

Energy Automation Buenos Aires Nov ‘05

Page 39

Power Transmission and Distribution

IEC 61850 – now already known worldwide No. 1 with Energy Automation

Energy Automation Buenos Aires Nov ‘05

Page 40

Power Transmission and Distribution

IEC61850 worldwide No. 1 with Energy Automation

Energy Automation Buenos Aires Nov ‘05

Page 41

Power Transmission and Distribution

www.61850.com No. 1 with Energy Automation

Energy Automation Buenos Aires Nov ‘05

Page 42

Power Transmission and Distribution

The way to IEC 61850 No. 1 with Energy Automation

Substation automation has always been complex n IEC 61850 provides a structure to give a more simple view n IEC 61850 does not change the functions of a substation n IEC 61850 does not change the functionality of the devices n IEC 61850 provides Interoperability To Kick-off your thinking about today‘s philosophies n Do some more research (www.61850.com) n Consider your next substation application n Evaluate the chances to reduce costs in your substations Energy Automation Buenos Aires Nov ‘05

Page 43

Power Transmission and Distribution

Energy Automation ~ Siemens has the solution

Power Transmission and Distribution

A long lasting experience is the basis of our Competence No. 1 with Energy Automation

1996

2010

Telecontrol and Station control for more than 70 years Power Automation for more then 20 years Energy Automation Buenos Aires Nov ‘05

Page 45

Power Transmission and Distribution

The SICAM family – For each application a fitting solution No. 1 with Energy Automation

SICAM PAS CC

SICAM eRTU SICAM PAS

SIPROTEC SICAM mini/micro RTU

Energy Automation Buenos Aires Nov ‘05

SICAM Diamond

Page 46

Power Transmission and Distribution

SICAM - A powerful ability to shape the future No. 1 with Energy Automation

SICAM system unit based on standard hard- and software components which provides numerous communication options and a universal automation system. SICAM eRTU miniRTU PAS 4 SIPROTEC

Direct process connection

Energy Automation Buenos Aires Nov ‘05

Page 47

Power Transmission and Distribution

SICAM - RTU portfolio No. 1 with Energy Automation

Functionality

SICAM eRTU

Enhanced

Automation

SICAM RTU

SICAM miniRTU

Gateway

SICAM microRTU

Amount of process information

Gas - Water Power Transmission - Distribution Energy Automation Buenos Aires Nov ‘05

Page 48

Power Transmission and Distribution

SICAM eRTU - powerful and future oriented No. 1 with Energy Automation

CPU CPU

MCP MCP

I/O I/O cards cards

Interface Interface module module IM IM

PS PS

Flash Flash EPROM EPROM Open Open front front connector connector

Backplane Backplane bus bus

Based on Simatic S7-400 PLC from Siemens Energy Automation Buenos Aires Nov ‘05

Page 49

Power Transmission and Distribution

SICAM eRTU - a communication engine No. 1 with Energy Automation

Diagnostic Centre (Diamond Client)

Control Centre IEC 60870-5-101 SINAUT 8-FW TG800, TG8979 DNP V3.00

WAN IEC 60870-5-104

Control Centre

Diamond Server Router

Ethernet TCP / IP

Modbus / Profibus DP IEC 60870-5-101/DNP 3.00 IEC 60870-5-103

..

Energy Automation Buenos Aires Nov ‘05

..

Page 50

Power Transmission and Distribution

SICAM eRTU - technical Highlights No. 1 with Energy Automation

n Remote control & monitoring of substations from up to 3 Control centres (dual channels) n Remote diagnostic, control & monitoring with SICAM Diamond n PLC (Simatic S7) functionality n Easy Automation n 2.5 kV isolation n Continuous self-test n High availability n Real-time acquisition of data n I/O modules with 1ms time resolution n Wide input voltage range modules n Easily expandable n Communication of up to 96 IEDs or satellite RTUs n SIMATIC communication (Profibus DP, Modbus)

Energy Automation Buenos Aires Nov ‘05

Page 51

Power Transmission and Distribution

What is Substation Automation? No. 1 with Energy Automation

n Replacement of conventional control panels n Use of numerical station and bay controllers with self monitoring & integrated functions

Corporate Network TCP/IP

SCADA HMI

SCADA/ WAN

Station Unit

n Replacement of mimic boards by PC based system with HMI n Automated operation by logic functions à interlocking, load shedding etc. Log. IN 1

n Modern communication using fibre optic links and bus systems

1100 F1 1530

Log. IN 2

1503 2173 F2

Log.IN3

1530

1530 8888 >1 2173

Log. OUT1

è Reduction of hardware and easy expansion Energy Automation Buenos Aires Nov ‘05

Page 52

Power Transmission and Distribution

Cost Reduction at Station Level No. 1 with Energy Automation

8 5

Distributed System using fibre optic cables 2 0

Increasing reliability Simple & easy mounting 9

6 3

Marshalling cubicle

Energy Automation Buenos Aires Nov ‘05

Faster Commissioning Simplified Documentation Easy troubleshooting Reduced total costs Page 53

Power Transmission and Distribution

SICAM PAS Configuration and functions No. 1 with Energy Automation

Control Center

IEC 60870-5-101 DNP V3.00

SICAM PAS Stand-alone

Control Center

system SICAM PAS CC

IEC 60870-5-104

Time signal Log.IN1

1100

F1

1530 1530

8888

Log.Out1

>1 1503 Log.IN2

2173

F2

2173

Log.IN3 1530

Distributed process interface Process visualization and archiving Telecontrol interface Automation function with CFC Online configuration

Ethernet

Modbus/Profibus DP IEC 60870-5-101/DNP V3.00

Profibus FMS/IEC 60870-5-103

Energy Automation Buenos Aires Nov ‘05

Page 54

Power Transmission and Distribution

SICAM PAS Distributed system with higher performance No. 1 with Energy Automation

Control Centre

SICAM PAS Distributed

Control Centre

System SICAM PAS CC

IEC 60870-5-101 DNP V3.00 IEC 60870-5-104 Log.IN1

Time signal

1100

F1

1530 1530

8888 Log.Out1

>1 1503 Log.IN2

F2

2173 2173

Log.IN3 1530

Ethernet

Profibus FMS IEC 60870-5-103

IEC 60870-5-101 DNP V3.00

Energy Automation Buenos Aires Nov ‘05

Modbus/Profibus DP

Page 55

Power Transmission and Distribution

SICAM PAS High availability by redundancy & IEC 61850 No. 1 with Energy Automation

SICAM PAS Redundant

Control Centre

System

HMI Clients

IEC 60870-5-104 Ethernet

Full Server

Full Server

Station bus

!N ew ! IEC 61850 Profibus FMS

Energy Automation Buenos Aires Nov ‘05

Page 56

Power Transmission and Distribution

SICAM PAS High flexibility through new interfaces No. 1 with Energy Automation

Maintenance

SICAM PAS IT-Welt

Control Centre

w! !Ne

SICAM PAS CC SIMATIC WinCC IEC 60870-5-104 TCP/IP

Time signal Log.IN1

1100

F1

1530 1530

8888

Log.Out1

>1 1503 Log.IN2

2173

F2

2173

Log.IN3 1530

Ethernet

OPC IEC 60870-5-101/DNP V3.00

!Ne w! SIMATIC

Profibus FMS/IEC 60870-5-103

Energy Automation Buenos Aires Nov ‘05

Page 57

Power Transmission and Distribution

SICAM PAS Communication Highlights No. 1 with Energy Automation

Communication to Control Centres

Corporate Network TCP/IP

SCADA

IEC 60870-5-101 IEC 60870-5-104 (Ethernet TCP/IP)

SCADA / WAN

Station Unit

DNP V3.00

Connection of IEDs and Satellite RTUs IEC 61850 IEC 60870-5-103, MODBUS, DNP V3.00 IEC 60870-5-101 (incl. dial-up traffic) Profibus FMS, Profibus DP SINAUT LSA protocol

Data exchange

Station Unit

BU

PU

BU

BU

Station Unit

with OPC Server and Client

One substation platform for all communication needs Energy Automation Buenos Aires Nov ‘05

Page 58

Power Transmission and Distribution

SICAM PAS a scalable system: Central Tasks: Fault Recording No. 1 with Energy Automation

SICAM Recpro Collector

SICAM Recpro Explorer and Comtrade Viewer

Automatic transmission of archives of the station units to a superior level fault record archive

SICAM Recpro PC

Ethernet TCP/IP

DIP

Full Server

IEC 61850 Profibus FMS

Full Server

IEC 60870 -5-103

= communication- specific fault recording archive = collected fault recording archives, higher level fault recording archives Energy Automation Buenos Aires Nov ‘05

Page 59

Power Transmission and Distribution

SICAM PAS = Automation No. 1 with Energy Automation

Open Programming Platform (IEC-61131 compatible) No software development on customer side needed Configuration of functionality

ST CFC Energy Automation Buenos Aires Nov ‘05

Page 60

Power Transmission and Distribution

SICAM PAS a scalable system: Software: SICAM PAS UI - Data exchange No. 1 with Energy Automation

SINAUT Spectrum Power CC Import of engineering data - IEC 60870-5-101 - IEC 60870-5-104

SICAM PAS Export of T101 / 104 (Slave)- engineering data

SICAM PAS Import of engineering data - IEC 61850 - Profibus FMS - IEC 60870-5-103 - IEC 60870-5-101

Export of T101 (Slave) engineering data SICAM plusTOOLS > V4.0 XMLExportfile SICAM PAS or PCC

XMLExportfile

Export of T103 engineering data for SIPROTEC 4 DIGSI 4

Energy Automation Buenos Aires Nov ‘05

DbaseExportfile

Export of Profibus FMS Engineering data for SIPROTEC 4 DIGSI 4

XMLExportfile

Export of IEC 61850 engineering data for SIPROTEC 4 DIGSI 4

SCDExportfile

Page 61

Power Transmission and Distribution

SICAM PAS Technical Highlights No. 1 with Energy Automation

Local visualisation, archiving and logging with SICAM PAS Control Centre (CC) based on SIMATIC WinCC

Data acquisition and transmission with real time stamp and 1 ms resolution

Complete substation automation functions Switching authority, bay and station blocking, and automation using CFC/ST

Substation redundancy (HOT-HOT) for the bay, station and HMI levels

True upgradeability from LSA to PAS AND from SAS to PAS

One substation platform meeting all functional needs Energy Automation Buenos Aires Nov ‘05

Page 62

Power Transmission and Distribution

SICAM PAS IEC 61850 – Communication with Bay Devices No. 1 with Energy Automation

n IEC 61850 (Version V5.1) The communication standard for the station bus based on Ethernet

IEC 61850

n We recommend the use of Ethernet components from Ruggedcom n Principle communication configuration

Station Unit 62,5µ or 50µ Fibre

Station Unit

TP

100 Mbit/s redundant switched Ethernet ring Bay Cubicle

TP TP

No Redundancy, Cost-optimized

TP Cu Twisted Pair (TP) Shielded cable max. 20m

Small medium voltage switchgear

n Inter-bay-Communication between bay devices independent of the Station Unit with IEC 61850-Goose-mechanism (e.g. for inter-bay-interlocks) Energy Automation Buenos Aires Nov ‘05

Page 63

Power Transmission and Distribution

IEC 61850: Solution for SIPROTEC No. 1 with Energy Automation

• Profibus DP • Profibus FMS

• IEC 60870-5-103 + VDEW Extension

• IEC 61850 • Modbus • DNP 3.0

• Substation Communication • Download Fault Records • Download and Upload Settings • IED Configuration Energy Automation Buenos Aires Nov ‘05

Page 64

Power Transmission and Distribution

IEC 61850 – System components No. 1 with Energy Automation

Ethernet-Switch for the substation ü ü ü ü

Ethernet-Switch, complies with IEC61850 requirements Redundant power supply Output relay Fan free operation

Energy Automation Buenos Aires Nov ‘05

Page 65

Power Transmission and Distribution

IEC 61850 – System components No. 1 with Energy Automation

Ethernet-Switch for the substation ü ü ü ü

Ethernet-Switch, complies with IEC61850 requirements Rail mounting. Output relay Fan free operation

Energy Automation Buenos Aires Nov ‘05

Page 66

Power Transmission and Distribution

SICAM PAS – IEC 61850 Convincing Performance No. 1 with Energy Automation

Results determined with Station Unit 6MD91 and 72 devices Monitoring direction è SICAM PAS CC n Transmission of a message n Transmission of a measured value

< 200msec < 200msec

Control direction ç SICAM PAS CC n Output time n Process feedback time

< 100msec < 200msec

Fault records n 30 fault records transferred and archived

Energy Automation Buenos Aires Nov ‘05

< 1sec

Page 67

Power Transmission and Distribution

SICAM PAS meets SICAM DIAMOND No. 1 with Energy Automation

Web Technology = Diamond V2 n Substation IT, communication and information availability is becoming increasingly important n standardised front end – use standard web browser n Browser based diagnostics tools allowing remote access & support n Economic web-based HMI n Event List n Single Line Diagram

Energy Automation Buenos Aires Nov ‘05

Page 68

Power Transmission and Distribution

SICAM Diamond No. 1 with Energy Automation

n One or more Full Servers to one SICAM Diamond n Test & Diagnostics … simple Monitoring & control n Communication via Ethernet n Exchange of configuration data (*.xml)

Full Server 1

Full Server 2

Full Server 3 Diamond Server – local HMI

Station Bus

Bay Controller/ IEDs

Energy Automation Buenos Aires Nov ‘05

Page 69

Power Transmission and Distribution

SICAM DIAMOND - Web Technology for Substation Automation No. 1 with Energy Automation

UMTS

ISDN/xDSL

Internet Internet

Home / Office

C tn C re tl ro C tn C re o tln ero

Intranet: Web Clients using standard brwoser

SCADA Protocol DNP or IEC 60870-5-104 over TCP/IP & HTTP for Web Access

Diamond on a separate Web Server – local HMI

Corporate Wide Area Network / Intranet

Diamond / Web Server running on station unit no local HMI

All in One Solution SICAM PAS & Diamond - local HMI

Station Bus

. . .

Station Bus

Bay Controller/ IED

Bay Controller/ IED S/S 1 Energy Automation Buenos Aires Nov ‘05

Two independent protocols via the Station Router

Station Bus Bay Controller/ IED

S/S 2

S/S nn Page 70

Power Transmission and Distribution

No. 1 with Energy Automation

SICAM PAS

We have already sold more than 180 Units world wide since release January 2004!!!!

Energy Automation Buenos Aires Nov ‘05

Page 71

Power Transmission and Distribution

The Solution: IEC 61850

IEC 61850

No. 1 with Energy Automation

One World

One Technology One Standard

APPLICATIONS

Energy Automation Buenos Aires Nov ‘05

Page 72

Power Transmission and Distribution

SICAM PAS application with IEC 61850: ATEL No. 1 with Energy Automation

Corporate Network TCP/IP

Control Centre

First I EC applic 61850 ation ru since Octob nning er 200 4

IEC60870-5-101 Ethernet TCP/IP

SICAM Station Unit

IEC60870-5-101

SICAM miniRTU for general I/O

Stationbus Ethernet TCP/IP with IEC61850

Connection bay devices SIPROTEC 4 with IEC61850

substation

Energy Automation Buenos Aires Nov ‘05

Page 73

Power Transmission and Distribution

IEC 61850: In Utilities in Europe No. 1 with Energy Automation

Trend: IEC61850

þ RWE Power (Germany): open cast coal-mine Garzweiler II, 180 bays HV-/MV þ ATEL (Switzerland) Pilot project Winznauschachen þ City council Winterthur (Switzerland) Substation Wülflingen þ EEM (Madeira Portugal): 2 Substations commissioned þ NEK (Bulgaria): 1 400kv Substation þ Transelectrica SA (Rumania) Main substation in the south of Bucarest þ Delta N.V. (Netherlands) 2 x HV substations

Energy Automation Buenos Aires Nov ‘05

Page 74

Power Transmission and Distribution

IEC 61850: Utilities in Latin America No. 1 with Energy Automation

þ ENEBAR (Venezuela): Transmission company Trend: IEC61850

þ CADAFE (Venezuela): Transmission company þ TRANSELECTRIC (Ecuador): 5 substation on order þ ISA (Columbia) 5 substations with SICAM PAS þ DISPAC (Columbia) 3 Substation for delivery early 2006 þ EMSA (Columbia) 1st SICAM PAS for delivery in O2.06

Energy Automation Buenos Aires Nov ‘05

Page 75

Power Transmission and Distribution

IEC 61850: Utilities in Latin America No. 1 with Energy Automation

þ CTEEP (Brazil) Large GIS substation Trend: IEC61850

þ CFE (Mexico) Redundant SICAM PAS þ ICE (Costa Rica) Transmission Substation þ Luz der Sur (Peru) 2 Substation in commission

Energy Automation Buenos Aires Nov ‘05

Page 76

Power Transmission and Distribution

IEC 61850: activities in Industry No. 1 with Energy Automation

Trend: IEC61850

þ Deutsche BP - Cologne (Germany) Refurbishment of Power Station þ SASOL (South Africa): Petrochemical plant using SICAM PAS þ VW Salzgitter (Germany): Refurbishment of Power Station in an Automobile factory þ PETROBRAS (Brazil): FAFEM Petrochemical plant þ YANBO (United Kingdom) Air Products þ RUSAL (Russia) Aluminium Smelter Substation þ ERZ (Switzerland) Substation for a waste incineration plant þ ASMENT (Morocco) Substation for a cement production facility

Energy Automation Buenos Aires Nov ‘05

Page 77

Power Transmission and Distribution

Pilot project: RWE Rheinbraun – Garzweiler II No. 1 with Energy Automation Anschluss BÜ

Engineering Arbeitsplatz

zentrales Stationsleitsystem SICAM PAS

IEC 60870-5-101

Zeitsynchronisation über GPS Antenne

Abgesetzter Bedienplatz Fernzugriff auf den EngineeringPC über Remote Desktop

Mobiles Visualisierungsger ät

SICAM PAS DIP 25/6kV HSA SICAM PAS DIP 110kV HSA 6 kV BSP Trafomonitoring IEC61850

SICAM PCC Full Server

ca. 10 km

AnlagenbusIEC61850 LWL-Ring mit Ringmanagement

4 Strecken IEC 60870-5-101

StationsbusIEC61850 25/6kV HSA Anlage LWL-Ring mit Ringmanagement

1) Anschluss von biszu 6 Feldger äten an ein Optical Switch Modul (OSM)

Entfernte Stationen 1 - 4 mit SICAM miniRTU Feldger äte1 - n (7SJ, Regler )

StationsbusIEC61850 110 kV HSA Anlage LWL-Ring mit Ringmanagement

1)

1)

Liefergrenze

Feldgerät 6MD63 für zentrale Ein -/Ausgaben

Feldgerät 6MD63 für zentrale Ein -/Ausgaben

Anbindungsm öglich keit für nicht IEC61850fähige Feldger äte (bei Bedarf)

Energy Automation Buenos Aires Nov ‘05

Feldger äte1 - n (7SJ, Regler )

Feldgerät 6MD63 für zentrale Ein -/Ausgaben

StationsbusIEC61850 6kV BSP Anlage LWL-Ring mit Ringmanagement

1)

Anbindungsm öglich keit für nicht IEC61850fähige Feldger äte (bei Bedarf)

Feldger äte1 - n (7SJ, Regler )

Anbindungsm öglich keit für nicht IEC61850fähige Feldger äte (bei Bedarf)

Page 78

Power Transmission and Distribution

Pilot project: RWE Rheinbraun – Garzweiler II – Station bus No. 1 with Energy Automation

m

Connection to Plant bus

Three independent Station busses: 110kV – Section (HSA) 25/6 kV- Section (HSA) 6kV – Section (BSP)

m

general indications

In summary 180 Protection and Bay Units. 7SJ63, 7SJ64, 6MD66 and 7SJ62: IEC61850 7UT6: IEC60870-5-103

Station bus IEC61850 FO-Ring with ring management

m

Connection to Transformer Controller using IEC61850

m

High Availability due to automatic Ring management using intelligent Switch modules

Seriell Hub

Connection to Bay Units using IEC61850

Connection to Bay units using IEC60870-5-103

Switchgear IEC61850 - RJ45 IEC61850 - LWL Energy Automation Buenos Aires Nov ‘05

IEC 60870-5-103- Cu

Page 79

Power Transmission and Distribution

Pilot project: RWE Rheinbraun – Garzweiler II – Control room No. 1 with Energy Automation

Prozessleitstelle IEC60870-5101

local HMI SICAM PASCC

remote HMI (Net Meeting)

m SICAM PAS-System,

consisting of: Full server 2xDIP (Device Interface Processor) SICAM PAS CC remote Control PC Mobile Control PC

SICAM PAS FS DIP

10 km

m Bay

controller via IEC61850 IEC 60870-5-103

DIP

Mobile Control-PC 4 times IEC 101

Plant bus IEC61850 FO-Ring with ring management

Connection to Station bus 25/6kV HSA

Connection Station bus 110kV HSA

IEC61850 - RJ45 IEC61850 - LWL Energy Automation Buenos Aires Nov ‘05

m Sub

station connection IEC60870-5-101

m Control

center connection IEC 60870-5-101

m Notebook

as mobile Control PC useful at every switch.

Connection Station bus 6kV BSP

IEC 60870-5-xxx- Cu

Page 80

Power Transmission and Distribution

Pilotprojekt: VW Salzgitter Control room No. 1 with Energy Automation

local HMI SICAM PAS CC

IEC61850 / IEC60870-5-103

Hall 1 IEC 61850

IEC 103/ RS485

OSM

SICAM PAS

1…5

Switchgear

Hall 2 Hall 3

Connection to Corporate Network

OSM ESM

Hall 4

general Station indications

OSM

Central heading

Ethernet

TCP/IP

IEC61850 / IEC60870-5-103

Station bus to production sections ESM

IEC61850 - RJ45 IEC61850 - LWL Energy Automation Buenos Aires Nov ‘05

ESM

ESM

IEC 60870-5-103- Cu Page 81

Power Transmission and Distribution

Pilot project: VW Salzgitter - 20 kV switchgear No. 1 with Energy Automation

Switchgear Switchgear20kV 20kV 33sections with sections with12 12Feeder Feedereach each Bay BayUnits Units6MD63/7SJ63 6MD63/7SJ63using usingIEC IEC61850 61850 Protection Units 7SD61 using IEC 103 Protection Units 7SD61 using IEC 103

Connection to plant bus app. 20 Meter

Due Duetotoshort shortdistances distancesaa RS RS485 485cooper cooperbus buswill willbe beused used

Station bus IEC61850 electrical ring

IEC61850

Seriell Hub IEC 103/ RS485

1 … 12

Switchgear Section 1 IEC61850 - RJ45 IEC61850 - LWL Energy Automation Buenos Aires Nov ‘05

section 2

section 3

IEC 60870-5-103- Cu Page 82

Power Transmission and Distribution

The Solution: IEC 61850

IEC 61850

No. 1 with Energy Automation

One World

One Technology One Standard

Thanks for the attention

Energy Automation Buenos Aires Nov ‘05

Page 83

View more...