IBC 2006 and ASCE 7-05.xls

December 22, 2017 | Author: Nguyen Duc Cuong | Category: Fire Sprinkler System, Snow, Lighting, Roof, Structural Engineering
Share Embed Donate


Short Description

Download IBC 2006 and ASCE 7-05.xls...

Description

Fire-resistance rating requirement for building elements: (T-601) Type V-B, Any materials permitted (602.5) Windows(T-715.5) Door&Shutter(T-715.3) a Structural frame 0 hours f Exterior bearing walls 0 hours 0 hours #N/A hours Interior bearing walls 0 hours 0 0 Floor construction 0 hours 0 Roof construction 0 hours Int. Non-bearing & partition NR Fire-resistance rating requirements for exterior walls based on fire separation distance. (T-602)* For Type V-B,Group R-3 Ext Wall Setback (ft)

North South West East

Max area of opening in percentage of the area of exterior wall.T-704.8

Fire Rating hrs

Windows (715.5) hrs

Doors (715.3) hrs

Unprotected

1 1 0 0

¾ ¾ 0 0

¾ ¾ 0 0

10 NP NL (g) NL (g)

5.1 4.5 10 30

Protected a,c,e,g,h,i a,c,g a,c,e,g,h,i a,d,g,i

25 15 NL (g) NL (g)

a,c,e,g,h,i a,c,g a,c,e,g,h,i a,d,g,b

*For special requirements for Group U occupancies see Section 406.12

Required Separation of Occupancies (T-508.3.3)* Between

S-2

&

M

=

2 hours, NS 1 hours, S

c, d

b

S = Buildings equipped throughout with an automatic sprinkler system installed in accordance withSection 903.3.1.1. NS = Buildings not equipped throughout with an automatic sprinkler system installed in accordance withSection 903.3.1.1.

Fire wall fire resistance rating, considered a separate building. (T-705.4 ) Occupancies Group 1 A-1 Type of construction 8 V-A Required fire resistance rating 2 hours Shaft enclosures (if required per 707.2) fire resistance rating 1 hours Opening protective fire rating for fire door and shutter assemblies (715.4) Type of Assembly Rating Minimum Opening Protection Smoke barriers 7 21 ⅓ hours The required locations for fire and smoke dampers: (716.5)

Location 1 Uses (FB) Incidental

Section

Fire Damper Nonspr Sprinkler

302.1.1.1

Yes (1)

Smoke Damper Nonspr Sprinkler

Yes (1)

No

No

Interior wall and ceiling finish requirement by occupancy T-803.5 Group R-3 SPRINKLERED UNSPRINKLERED k

Vertical exit & exit passageways a b Exit access corridors & other exitways

C C

C C

Room & enclosed space c

C

C

Fire Alarm and Detection Systems (907) Occupancy 5 E, Occupant load 50

Section System Type 907.2.3

Manual fire alarm system

Exception: Manual fire alarm boxes not required where six specific condition are met.

Group R-3, An automatic sprinkler system shall be provided where: 0

Minimum roof covering classification for type of construction T-1505.1 a b Type of construction V-B Class C(c) Roof covering

1 1 0 0

MINIMUM NUMBER OF REQUIRED PLUMBING FACILITIES PER T-2902.1

Water Closet

UBC 1997

A - Conference rooms, dining rooms, drinking establishments, exhibit rooms, gymnasiums, lounges,sq. stages andoccupant similar uses including ft per Occupancy Factor = 30 water close

A

Conference rooms, dining rooms, drinking establishments, exhibit rooms, gymnasiums, lounges, stages and similar uses including restaurants classifies as group B Occupancies. Total Area = 48,000 Sq. ft

M

Total Occupant = 1,600

Required water closet Male: 1:1-25, 2:26-75, 3:76-125,

4:126-200, 5:201-300, 6:301400, over 400, add one for each additional 200

Female: 1:1-25, 2:26-75, 3:76-125,

4:126-200, 5:201-300, 6:301400, over 400, add one for each additional 150

##

= 8 A

= 9 A A

Required lavatories Male: 1 for each water closet up to 4, = 6 then 1 for each two additional water closets

A

B

Female: 1 for each water closet up to 4, = 7 then 1 for each two additional water closets

Required bath or shower Total: 0

B E

= 0 E

Required drinking fountain Total: 1 per 150

E

= 11

E

MINIMUM NUMBER OF REQUIRED PLUMBING FACILITIES PER T-2902.1 IBC 2003 E - Educational facilities

E

Educational facilities

= 15

Total Occupant

Required water closet Male: 1 per 50

= 1

Female: 1 per 50

= Separate ficilities shall not be required

Required lavatories Male: 1 per 50 Female: 1 per 50

= 1 = Separate ficilities shall not be required

Required bath or shower Total: 0

= 0

Required drinking fountain Total: 1 per 100

= 1

Other

1 Service sink

Means of Egress, Floor Area 5,000 500

Area 1 Area 2

CHAPTER 10 Floor area per No of Occupancy occupant Occupant Exit Group T-1003.2.2.2 Loads 1004.2.1 240 gross 21 1 I-2 35 net 15 2 I-4 00 00 00 00 00 00 00 200

Use Inpatient treatment areas Day care

Other

Total occupant load No.of exits required Egress width (Inches) per occupant served, Table 1005.1 Occupant Occupancy Without sprinkler system With sprinkler system Load Group Stair way Other Egress Stair way Other Egress 0.3 0.2 0.2 0.15 15

R-2

5 (in)

3 (in)

3 (in)

Panic and fire exit hardware

Not required

Travel Distance, Table 1015.1

For Group R-2

Without sprinkler system With sprinkler system Common path of egress travel.1014.3

200 feet 250 feet

a,b

75 feet 125 feet, with sprinkler

Corridor fire-resistance rating, Table 1017.1 Without sprinkler system With sprinkler system When occupant load served by corridor

3 (in)

For Group R-2 NP hrs ½ hrs > 10

c

Building with 1 exit, Section 1019.2 Occupancy Max story ht. Max occupants (or dwelling units) per floor and travel distance R-2 1 story 10 occupants and 75 feet travel distance or 2 story 4 dwelling units occupants and 50 feet travel distance

36 2

1

Required water closet Used Group

Description

A-2

Restaurants, banquet halls and food courts

Male:

No. of Occupants 1 per 75

100

0

0

0

1

0

0

0

0

0

0

0

0

0

0

Total Occupants =

0

0

0

0

0

0

0

0

0

0

1

0

0

0

1 per 200

0

0

Female:

1

0

0

0

1 per 200

0

0

Male:

1

0

0

0

Female:

1 per 75

0

Required lavatories

0

0

0

0

0

0

Required bath or shower

Required drinking fountain

Total:

Total:

0

1 per 500

0

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

100

1

1

1

1

0

1

MINIMUM NUMBER OF REQUIRED PLUMBING FACILITIES PER T-2902.1

Other

1 Service sink

0

0

0

0

Required water closet Used Group

A-2

Description

Male: 1:1-100, 2:101-200, 3:201-400. Over 400, No. of add one fixture each Occupants additional 250.

Casino

901

0

0

0

0

0

0

0

0

0

0

0

Total Occupants =

0

0

0

0

0

0

3

0

0

0

1:1-200, 2:201-400, 3:401-750, Over 750, add one fixture for each additional 500

0

0

0

Female:

3

0

0

0

1:1-200, 2:201-400, 3:401-750, Over 750, add one fixture for each additional 500

0

0

0

Male:

9

0

0

0

0

3:1-50, 4:51-100, 6:101-200, 8:201400 Over 400, add one fixture each additional 150.

0

0

0

Female:

4

0

Required lavatories

0

0

0

0

0

0

Required bath or shower

Required drinking fountain

Total:

Total:

0

1 per 500

0

2

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

901

4

9

3

3

0

2

MINIMUM NUMBER OF REQUIRED PLUMBING FACILITIES PER T-2902.1 with SNBC amendments.

Other

1 Service sink

0

0

0

0

Lighting Application Worksheet 2006 IECC (SNBO) PROJECT: Name Section 1: Allowed Lighting Power Calculation

Building Type Auditorium

LPD (T-505.5.2) 1.8

Total Area =

Floor Area ft2 2000

2000

Adjust for Heights above the floor 14 ft

Allowed Watts 1.10

3960

Total Allowed Watts =

3960.0

Section 2: Actual Lighting Power Calculation

LAMP TYPE 48" T8 25W (Super T8)

Fixture ID A

Lamps/ Fixture

# of Fixtures

3

15

Fixture Watt 20

Incandescent 250 Total Actual Watts =

Total Watts 300 0 0 0 0 0 0 0 0 0 0 300

Section 3: Compliance Calculation Total Allowed Watts = Total Actual Watts = Project Compliance = Lighting PASSES: Design 92 % better than code

3,960 300 3,660

1607.11.2 MINIMUM ROOF LOAD Tributary area At = 300.0 R1 = 1.2-.001At = 0.90 Rise per feet, F = 4 :12 R2 = 1.00 = 1.00 Lr = 20R1R2

SQ.FT

##

Eq. 16-29

## Eq. 16-28 ##

Eq. 16-31

## Eq. 16-31

Eq. 16-24

= 20(0.9)(1) Min Design Roof Load Lr = 18.00 psf 1607.9 REDUCTION OF LIVE LOAD 1607.9.1 General 1/2 L = Lo[0.25+15/(KLLAT)] Lo = 40 KLL = 1

psf

AT = 2000.0

SQ.FT

Interior columns

Exterior columns without Edge columns with cantil Corner columns with can

(6-24)

Edge beams without can

T-1607.1

Interior beams

Cantilever beams

T-1607.9.1

Edge beams with cantilev Cantilever beams

L = 23.4 psf = 0.59 Lo L shall not be less than 0.50Lo for members supporting one floor and L shall not be less than 0.40Lo for members supporting two or more floors

r(A-150) 2000.0 0.08 60

## (16-25)

Horizontal member Vertical member

SQ.FT for floor 60% Max for vertical member

L = 16

psf

R = 23.1(1+D/Lo)

And

Members without provisio

Vertical member

1607.9.2 Alternate Live Load reduction for Lo = 40 psf R= A= r= R=

Two-way slabs

(16-26)

Dead load D = 75.0 psf R = 60.0 60% Max for vertical member L = 16.0 psf Min Design Live Load L = 16.0 psf ASCE 7.3 FLAT ROOF SNOW LOAD (slope ≤ 5o ) Flat-roof snow load, pf = 0.7CeCtIspg (7-1) Ground snow load, pg = 100

psf

##

Figure 7-1

Is

Terrain Category = Above the treeline in windswept mountainous areas Exposure of Roof = Fully Exposed

B (see Section 6.5.6) C (see Section 6.5.6)

Thermal Condition = Structures kept just above freezing and others with cold, ventilated roofs in which D (see 6.5.6) the Section thermal resista Snow load importance factor, Is = 1 Table 7-4 Above the treeline in wind Snow exposure factor, Ce = 0.7 Table 7-2 In Alaska, in areas where Thermal factor, Ct = 1.1 Table 7-3 ## Flat-roof snow load, pf = 53.9 psf All structures except as in Min pf = 20 psf Design pf = 53.90 psf 7.4 SLOPE ROOF SNOW LOAD (slope > 5o ) ps = Cspf Design pf = 53.90 Slope Θ = 25 Ct = 1.1 Slope factor Cs = 0.75

7.3

Unheated structures Continuously heated gree (7-2)

psf o

##

hdγ/S½

= 18.44

/3hdS½

= 3.91

See Figure 7.3 for Curved Roof See Figure 7.4 for Cont Beam See Figure 7-6 for Sawtooth Roof See Figure 7-8 for Snow Drifts

Unobstructed Slippery Su

Unobstructed Slippery Surfaces

All Other Surfaces 7.4.1, 7.4.2, 7.4.3 Figure 7.2a,b and c

ps = 40.43 psf Balanced and Unbalanced Snow Load for Hip and Gable Roof Snow Density γ = .13pg + 14 ≤ 30 pcf (7-3) = 27.00 pcf S =1/tanΘ = 2.14 Height of Snow Drift hd = 1 ft 8

Structures kept just above

### W = 15.00ft

## # # # #

Θ = 25

psf

Θ> ps = 40.43ft

ft BALANCED

W ≤ 20 W > 20

ps = 100.00ft

UNBALANCED W ≤ 20

3.91ft

UNBALANCED OTHER

Θ≤ ### ###

12.13ft

40.43ft

18.44psf

IBC2006 (1613), ASCE 7-05 CHAPTER 11, 12, 13 SEISMIC DESIGN CRITERIA Response Spectral Acc. (0.2 sec) Ss = 175.00%g Response Spectral Acc.( 1.0 sec) S1 = 75.00%g Soil Site Class D

= 1.750g

Figure 22-1 through 22-14

= 0.750g

Figure 22-1 through 22-14

Table 20-3-1, Default = D

Site Coefficient Fa = 1.000 Site Coefficient Fv = 1.500

Table 11.4-1 Table 11.4-2

Max Considered Earthquake Acc. SMS = Fa.Ss

= 1.750

(11.4-1)

Max Considered Earthquake Acc. SM1 = Fv.S1

= 1.125

(11.4-2)

@ 5% Damped Design SDS = 2/3(SMS)

= 1.167

(11.4-3)

= 2/3(SM1)

= 0.750

(11.4-4)

SD1

Building Occupancy Categories II, Standard

Table 1-1

Flexible Diaphragm Design Category Consideration: Seismic Design Category for 0.1sec D Seismic Design Category for 1.0sec D E S1 ≥ .75g

Since Ta < .8Ts (see below), SDC =

with dist. between seismic resisting system >40ft

Table 11.6-1 Table 11.6-2 Section 11.6

E T-R301.2.2.1.1

IRC, Seismic Design Category = D2

Comply with Seismic Design Category E 12.8 Equivalent lateral force procedure

A. BEARING WALL SYSTEMS

T-12.2-1

Seismic Force Resisting Systems 9. Ordinary reinforced masonry shear walls Ct = 0.02 x = 0.75 T-12.8-2 Building ht. Hn = 20 ft Limited Building Height (ft) = NP Cu = 1.400 for SD1 of 0.750g Table 12.8-1 Approx Fundamental period, Ta = Ct(hn)x

12.8-7

= 0.189

Calculated T shall not exceed ≤ Cu.Ta 0.8Ts = 0.8(SD1/SDS)

TL = .266 Sec

= 0.265

Use T = 0.265 0.265

= 0.600

Is structure Regular & ≤ 5 stories ? Yes Response Spectral Acc.( 0.2 sec) Ss = 1.500g Fa = 1.00

12.8.1.3 Max Ss ≤ 1.5g

@ 5% Damped Design SDS =

⅔(Fa.Ss)

Response Modification Coef. R =

2

Table-12.2-1

2 1 CsW

foot note g Table 11.5-1

Over Strength Factor  Importance factor I = Seismic Base Shear V = Cs = or need not to exceed, Cs = or Cs = Cs shall not be less than = Min Cs =

sec.

SDS R/I SD1 (R/I).T SD1TL

= 1.000g

(12.8-3)

= 1.416

For T≤ TL

N/A

For T > TL

= 0.188

For S1 ≥ 0.6g

T (R/I)

Use Cs = 0.583 Design base shear V = 0.583 W

(12.8-2)

=0.583

2

0.01 0.5S1I/R

(11.4-3)

(12.8-4) (12.8-5) (12.8-6)

Control T-12.14-1

12.14 Simplified Seismic base shear 2. Ordinary reinforced concrete shear walls @ 5% Damped Design SDS = 1.167 SDC = E F= 1.1 For two-story building FSDS(W) V= = 0.321 W R 13.3 Seismic Demands on Nonstructural Components Fp = 0.4apSDSW p(1+2z/h) (Rp/Ip) ap = 1 Ip = 1.0

Limitations: NP R= 4

Rp = 3

z = 10 ft Max Fp = 1.6SDSIpW p Min Fp = 0.3SDSIpW p

SDS = 1.167

(13.3-1)

T-13.5-1 or 13.6-1 13.1.3 Fp = 0.467 Wp

h = 10 ft = 1.867Wp

(13.3-2)

= 0.350Wp

(13.3-3)

Fp = 0.467 Wp 12.11.1 Structural Walls and Their Anchorage Fp = 0.40SDSIW w

12.11.1

= 0.467(W) 12.11.2 Anchorage of Concrete or Masonry structural Walls (flexible diaphragm) or Fp = 400SDSI shall be ≥ 280 #/ft = 467 Fp = 0.8SDSI(W w)

(12.11.1)

= 0.933 Wp Max Seismic Load EM = QE ± 0.2SDSD Where = 2 0.2SDSD = 0.234(D) Deflection Amplification factor Cd = 1.75 Nonbuilding structures, Section 15 Response Modification Coef. R = 3 Importance factor I = 1 For flexible nonbuilding, Cs = SDSI/R Min Cs = 0.03 or Cs= 0.8 S1I/R V = 0.389 W For rigid nonbuilding, Cs = 0.3 SDS I = 0.300 W

(12.4.4), (12.4.5), (12.4,6), (12.4.7)

T-15.4-1 or T-15.4-2 15.4.1.1 = 0.389 (15.4-1) = 0.200

(15.4-2) (15.4-5)

ASCE 7-05 (IBC 2006) WIND: BUILDING DATA: Basic wind speed (3 sec gust) = 90 MPH Exposure

B

Roof Pitch = Mean Roof Height h = Importance factor Iw =

4.00 :12 25 ft 1.00

T-6-1

6.4 METHOD 1- SIMPLIFIED PROCEDURE (LOW-RISE, 60 FT) Height Adjustment factor λ = 1.00 -10.70G -15.40E

-2.73D -4.92B

Fig 6-2

-7.97H -10.51F

-10.70G -15.40E

-6.80H -8.80F

θ= 18.4

11.52C 17.27A

All forces shown in psf

8.50C 12.80A

22.58333

=

29

=

TRANSVERSE ELEV. 12.80A

13.53 kips 6.77 k

10.1psf

10 % of least dimension=

2.9 ft

40 % of the eave height =

9.0 ft

4 % of least dimension or 3 ft=

3.0 ft

therefore a =

3.0 ft

9.3 psf

8.50C

49 ft All forces shown in psf

11.52C

49

LONGITUDINAL ELEV.

2a= 6.0ft

29 ft

H =27.4

Example: ps = λ KztIps30

(6-1)

Kzt =

1.00

6.5.7

horizontal load at end zone ps30 =

12.8

6.0ft

17.27A

PLAN VIEW

Height Adjustment factor λ =

1.00

Importance factor Iw =

1.00

FIGURE 6.2, Main Wind Force System

Fig 6-2 X

Fig 6-2

X

6.2

12.80psf

MWFRS Load

Roof

Horizontal Loads End Zone Interior zone

Direction

Angle 18.4 All

Wall (A) Roof (B) Wall (C ) Roof (D) 17.27 -4.92 11.52 -2.73 12.8 -6.7 8.5 -4

Transverse Longitudinal

End Zone WW (E) -15.40 -15.4

Vertical Loads Interior zone

LW (F) WW (G) LW (H) -10.51 -10.70 -7.97 -8.8 -10.7 -6.8

Overhang EOH GOH -21.60 -21.6

-16.90 -16.9

* If roof pressure under horizontal loads is less than zero, use zero Plus and minus signs signify pressures acting toward and away from projected surfaces, respectively. For the design of the longitudinal MWFRS use Ө = 0°, and locate the zone E/F, G/H boundary at the mid-length of the building

FIGURE 6-3, COMPONENT AND CLADDING sq. ft, = 18.4 Roof effective area = 30 Effective Area for wall element = 20 Sq. ft Interior Zone 1 = 9.45 -12.87 psf Wall, Interior Zone 4 = 13.90 -15.10 psf End Zone 2 = 9.45 -17.98 psf End Zone 5 = 13.90 -18.20 psf Conner Zone 3 = 9.45 -23.90 psf Roof Overhang effective area = 6 sq. ft Interior Zone 2 = -26.13 psf End Zone 3 = -36.71 psf IBC 1605.2.1(LRFD) U = 0.9D + 1.6W IBC 1605.3.1(ASD), U = 06D + W, increase in allowable shall not be used. IBC 1605.3.2(ASD), U = D + 1.3 W, allowable stress are permit to be increased.

ASCE7-05, 6.5.7 Topographic Effects x = 50

H = 80 = H/2

Lh = 320 Height above local ground z = Hill Shape Direction

45 ft 3-dimentional axisym Downwind of Crest

Exposure B Height of hill, H= Distance upwind of crest to where the difference in ground elevation is half the height of hill, Lh =

80 ft

##

320 ft

2-dimensional ridge

H/Ln =

0.25

calculate K1 by using H/Ln =

0.25

2-dimensional escarpments 3-dimentional axisym x/Lh =

0.16

0.95

K1 =

0.24

320 K2 = 1 - x/µLh

µ=

1.5

γ=

4

Distance from the crest to the building, x = Figure 6-4, K1/(H/Lh) =

50 ft

calculate K2, K3 by using Ln = K2 =

0.90

K3 = e-γz/Lh K3 = 0.57 Kzt = [1 +K1K2K3]2 Kzt =

1.26

(6-3) Back to Wind load

6.5.14 Design Wind Load on Solid Freestanding Walls and Solid Signs Per ASCE 7-05

F = qh G Cf As

(6-27)

qz= .00256 Kz Kzt Kd V2 I

(6-15)

Exposure coefficient Kz = Exposure Topography factor Kzt = 1.00

B =20.00

1.4 B (6.5.7.2)

Directionality factor Kd = 0.85 Wind Speed V= 90 Impotance factor I= 0.87 qz= 15.33 Kz

s = 10.00

(6.5.4.4)

0 to s

s to 2s

(6.5.5), T-6-1

Gust Effect factor G = 0.85

L1 = 0.00 ft

(6.5.8)

D1 = 1.00 ft

Balance Cf =1.40

B/s= 2.00 s/h = 1.00 Case A & B, Cf = 1.40

Fig 6-20

Since B/s ≥ 2 Case C must also be considered Total # of Segment with width = s =2 Balance, see Fig 6-20 = 0.00 Case C, Cf for Region

Vert. location of resultant force 5.5 ft from grade

L2 = 0.00 ft

D2 = 1.50 ft

ft

Total h =10.00

0 to s, = 2.25 s to 2s, = 1.50

L3 = 0.00 ft

Case C, Multiples factor (if applicable) Horizontal dim of return corner Lr = 0.0 ft when s/h > 0.8, (1.8-s/h) = for Lr/s = 0.00, = %openning = Reduction factor =

D3 = 2.00 ft

Free Standing Wall, Case B= 10.40PSF Free Standing Wall, Case C= 11.14PSF 1 0.9

0.80 1.00 0.0% 1.00

d = 6.77 ft Method A & B h 10.00 0.00 0.00 0.00

area As

Sign Balance, see Fig 6-20 = 0 to s, = s to 2s, =

h 10.00 10.00 10.00

area As

Pole

0.00 0.00 0.00

Sign Pole

Cf

200.0 0.0 0.0 0.0

Kz 1.40 1.2 1.2 1.2

qh 0.57 0.57 0.57 0.57

8.7 8.7 8.7 8.7 Total H=

F (lbs) 2080.2 0.0 0.0 0.0 2,080.2 5.50 ft

M (ft-lbs) 11441.4 0.0 0.0 0.0 11,441.4

F (lbs) 0.0 1337.3 891.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 2,228.8 5.00ft

M (ft-lbs) 0.0 6686.5 4457.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 11,144.2

3.00ft

Method C Cf

Kz

0.00 100.00 100.00

1.40 2.25 1.50

0.0 0.0 0.0

1.2 1.2 1.2

qh 0.57 0.57 0.57 0.57 0.57 0.57 0.57 0.57 0.57 0.57 0.57

IBC 1805.7: Design Employing Lateral Load Bearing Total Lateral Load, P = 2080.2 lbs Dist from ground to point of P, H = 5.50 ft *Allowable lateral soil-bearing, S = 100.00 lbs/sq ft/ft Allowable Increase = 2 x 100.00 lbs/sq ft/ft Dia of footing or diagonal of sq. footing, b = 3.00 ft Constrained at ground = No S1 = 866 lbs/sq ft ≤ 15 x 100 O.K. = 2.34P/S1 b d = 0.5A[1+(1+(4.36h/A))½]

d=

6.77 ft

8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 Total H=

PSF 13.37 8.92

Design Requirement by Category

Category A

Category B

Category C

Category D

Category E

Category F

For: 9. Ordinary reinforced masonry shear walls, see 14.4

Limit Building Height Table-12.2-1 Seismic load effect E, 12.4 25 % Increase in Force for Connection Horizontal Irregular

NL

NL

160

NP

NP

NP

QE ± 0.2DDSD

QE ± 0.2DDSD

QE ± 0.2DDSD

QE ± 0.2SDSD

QE ± 0.2SDSD

QE ± 0.2SDSD

0.40SDSIW w 400SDSI

0.40SDSIW w 400SDSI

1a,1b,2,3 or 4 4 0.40SDSIW w 400SDSI

1a,1b,2,3 or 4 4 0.40SDSIW w 400SDSI

1a,1b,2,3 or 4 4 0.40SDSIW w 400SDSI

Vertical Irregular 0.40SDSIW w 400SDSI

Anchorage of concrete or masonry walls

0.8SDSIE(W w)

0.8SDSIE(W w)

0.8SDSIE(W w)

0.8SDSIE(W w)

0.8SDSIE(W w)

1 0.4SDSIwpx

1 0.4SDSIwpx

1 0.4SDSIwpx

1.3 0.4SDSIwpx

1.3 0.4SDSIwpx

1.3 0.4SDSIwpx

0.2SDSIwpx

0.2SDSIwpx

0.2SDSIwpx

0.2SDSIwpx

0.2SDSIwpx

0.2SDSIwpx

QE

QE

Em=QE ± 0.2SDSD

Em=QE ± 0.2SDSD

QE

QE

Em=QE ± 0.2SDSD

QE .40IESDSW w 0.1W w

.40IESDSW w 0.1W w Em=QE ± 0.2SDSD

.40IESDSW w 0.1W w Em=QE ± 0.2SDSD

.40IESDSW w 0.1W w Em=QE ± 0.2SDSD

.40IESDSW w 0.1W w Em=QE ± 0.2SDSD

na na

na na

na na

y

y

y

1b 1b, 5a or 5b 5b not over 2-story y

1b 1b, 5a or 5b 5b not over 2-story y

Flexible Redundancy,  Diaphragm, 12.10

max min Collector element & connection, 12.10.2 Light frame Structural Walls and Their Anchorage, 12.11.1 min Element Supporting discontinuous Wall and Frame, 12.3.3.3 Horizontal Irregular Not Permit Vertical Irregular Not Permit, 12.3.3.1 Extrem Weak Stories 12.3.3.2 Building Separations, 12.12.3 Concrete Seismic-force-resisting systems

QE

.40ISDSW w 0.1Ww Em =QE ± 0.2SDSD na 5b 5b not over 2-story y

QE

QE

IBC 1908.1.4

IBC 19081.4

IBC 1908.1.4

IBC 1908.1.4

Discontinuous members.

IBC 1908.1.12

IBC 1908.1.12

IBC 1908.1.12

IBC 1908.1.12

Plain

IBC 1910.4.4

IBC 1910.4.4

IBC 1910.4.4

IBC 1910.4.4

Frame members not proportioned to resist forces induced by earthquake motions.

IBC 1908.1

Em =QE ± 0.2SDSD

n/a

n/a

n/a

IBC 1910.5.2

IBC 1910.5.2

IBC 1910.5.2

MSJC 1.14.3

IBC1911.1 IBC 2106.3 MSJC 1.14.4

IBC1911.1 IBC 2106.4 MSJC 1.15.5

IBC1911.1 IBC 2106.5 MSJC 1.14.6

IBC1911.1 IBC 2106.6 MSJC 1.14.7

IBC1911.1 IBC 2106.6 MSJC 1.14.7

IBC 2106.3.1

IBC 2106.3.1

IBC 2106.3.1

IBC 2106.3.1

IBC 2106.3.1

IBC 2106.4.1

IBC 2106.4.1

IBC 2106.4.1

IBC 2106.4.1

IBC 2106.5.1

IBC 2106.5.1

IBC 2106.5.1

IBC 2205.2.2 IBC 2205.3.1 IBC 2210.5

IBC 2205.2.2 IBC 2205.3.1 IBC 2210.5

IBC 2205.2.2 IBC 2205.3.1 IBC 2210.5

IBC2305

IBC2305

Slab on Grade

Masonry Seismic Design Requirement Wall not part of the lateral-force-resisting system

Design of discontinuous members that are part of the lateral-force-resisting system 1.5 times the forces Steel, AISC 341 Structural steel Composite Light frame Wood General Shear wall 2305 Structural wood panel, h/d ratio, 2305.3.3 Gypsum Board & Stucco Particleboard Fiberboard

Shear panel connections (2305.1.4)

IBC 2205.2.1

IBC 2205.2.1

IBC 2210.5

IBC 2210.5

IBC 2205.2.1 IBC 2205.3 IBC 2210.5

IBC 2305

IBC2305

IBC2305

31/2:1

31/2:1

31/2:1

2:1

11/2:1

11/2:1

2:1 11/2:1

2:1

11/2:1

NP

NP

31/2:1

31/2:1

31/2:1

NP

NP

NP

11/2:1

11/2:1

11/2:1

NP

NP

NP

NA

NA

NA

IBC 2305.1.4

IBC 2305.1.4

IBC 2305.1.4

IBC 2305.3.11

IBC 2305.3.11

IBC 2305.3.11

Sill Plate

MSJC = Masonry Standards Joint Committee (ACI 530.1-05/ASCE 6-05/TMS 602-05)

IBC2305

CONCRETE SLENDER WALL PER IBC-2006, ACI 318-05,Section 14.8 Compressive strength, f'c =

4500 psi

Yield strength of rebars, fy =

60000 psi 14 psf 0.467 W p

Wind Load, W = Seismic Load QE = Fp = Design response spectrum, SDS =

1.17 g

Wall unsupported height, lc =

27 ft 0 ft

Parapet Height, p = Eccentric, e = Design width, b = Effective thickness, t = Design, d = Weight of the wall, W p =

2.7 24 6 3.8

in in in in

75.0 psf

Reduction factor, Dead Load, D = Live Load, L = Vertical Rebars = Spacing = Horizontal rebars = Spacing = Wt. of the wall @ mid height Pw =

0.9 200 100 #5 24 #5 24

Ver 4/2006

0.2SDSD E = QE ± Q ± = 0.23 D E Load Combination, IBC 1605.2.1

12.4.2.3

U = 1.20 D + 1.6L

(16-3)

U = 1.20 D + 0.5L + 1.6W U = 1.43 D + 0.5L + 1.QE

(16-4) (16-5) (16-6)

U = 0.90 D + 1.6W U = 0.67 D + 1.QE

(16-7)

Concrete wt. = 150 pcf h/t = 54.0 n= 7.1 Ec = 4,066,840 psi β1 = 0.825

plf plf in in

2025 lbs

Load Combination For Strength Design: (16-3) (16-4) (16-5) (16-6)

(16-7)

Factored load from trib Floor/Roof , P uf =

800.0

580.0

673.3

360.0

266.7 lbs

Factored weight of wall @ mid Ht, Puw =

2430.0

2430.0

2902.5

1822.5

1350.0 lbs

=

3230.0

3010.0

3575.8

2182.5

1616.7 lbs

=

22.4

20.9

24.8

15.2

11.2 psi

44.8

70.0

44.8

70.0 plf

Factored axial load, Pu = Puf+Puw Pu/Ag = Max Factored distributed lateral load, wu =

24.8 ≤ 0.06f'c, OK, 14.8.2.6

=

As = 0.310 sq.in Ase = (Pu+As.fy)/fy

≤ 0.6b(b.d) OK

a = (Pu+As.fy)/(0.85.f'c.b) c = a/0.85 ε1 = (0.003/c)d - 0.003 ≥ 0.005 for tension conctrol Nominal strength, Mn = (Asefy)(d - a/2) Icr = n.Ase.(d-c)2+bc3/3

Mu obtained by iteration of deflection ∆u (10times) Strength check Deflection at service load

(14-7)

/2

e

Mua = wu.lc /8+Puf. 2

(14.8.2.3)

=

0.36

0.36

0.37

0.35

0.34 sq.in

= =

0.24 0.28

0.24 0.28

0.24 0.28

0.23 0.27

0.22 inch 0.26 inch

=

0.038

0.038

0.037

0.040

OK

OK

OK

OK

=

80,358

79,574

81,590

76,621

74,597 lb-in

=

32.33

32.05

32.76

30.99

30.26 in4

0.041 OK

=

1,080

49,772

77,454

49,475

76,905 lb-in

Mu = Mua + PuΔu

(14-4)

=

1,683

75,038

127,236

66,184

95,122 lb-in

u = (5.Mu.h2)/[.75(48.Ec.Icr)]

(14-5)

= Mn =

0.19

8.39

13.92

7.66

Mn shall not be less than Mu 72,323 71,617 73,431 Mn > Mu (14-3) OK NG NG Load combination = D + L +(W or 0.7E) (16-15) Seismic Wind

68,959 OK

Unfactored Load trib from floor/roof, P f =

600.0

600.0 lbs

Pw =

2,025.0

2,025.0 lbs

Ps = Pf + P w

2,625.0 49.0

2,625.0 lbs 28 plf

w= Ig = b.t3/12 Mcr = 7.5(f'c)1/2.Ig)/0.5.t

432

=

72,449

=

0.45

0.45 in

= =

0.20 0.24

0.20 in 0.24 in

(14-7)

=

28.15

28.15 in4

(14-10)

=

55,295

(9-8)

=

432.0

31,950 lb-in ≤ Ig 432.0

(14-9)

=

0.34

0.20 inch

14.8.4

=

2.16 OK

2.16 inch OK

cr = (5.Mcr.h2)/(48.Ec.Ic) a = As.fy/(0.85.f'c.b) c = a/0.85 Icr = n.As.(d-c)2+bc3/3 2 M = w.lc /8+Pf.e/2+(Ps).s Ie = (Mcr/M)3Ig + [1+(Mcr/M)3]Icr

s = (5.M.lc2)/(48.Ec.Ie) Allowable= lc/150 Check total reinforcement Horizontal reinforcement =

0.0022 Ag 0.0022 Ag

Total =

0.0043 Ag

Vertical reinforcement =

432 in4

= (9-9)

11.27 in 67,138 lb-in NG

72,449 lb-in

> øMn, NG

(14-2)

in4

`

MASONRY SLENDER WALL PER IBC-2006, MSJC-05, SECTION 3.3.5

Ver 5/2003 ###

Compressive strength, f'm =

1500 psi

Yield strength of rebars, fy =

60000 psi 5 psf 0.224 W p

Wind Load, W = Seismic Load QE = Fp = Design response spectral, SDS =

1.17 g

Wall unsupported height, h = Parapet Height, p =

35 ft 0 ft

Eccentric, e = Design width, b = Effective thickness, t = Design, d = Weight of the wall, W p =

7.3 12 7.63 3.81

in in in in

0.2SDSD E = QE ± = QE ± 0.23 D Load Combination, IBC 1605.2.1

Reduction factor,  =

(16-3)

###

(16-4)

###

(16-5) (16-6)

###

(16-7)

###

U = 0.90 D + 1.6W U = 0.67 D + 1.QE

### ###

h/t = n= Em =

55.0 27.6

# #

700 f'm

For clay masonry

#

= 1,050,000 psi MSJC 1.8.2 fr = 84.0 psi, per T-3.1.8.2.1

plf plf

# # # ###

in

###

in

1400 lbs (16-3)

Factored load from trib Floor/Roof , Puf = Factored weight of wall @ mid Ht, Puw = Factored axial load, Pu = Puw+Puf Pu/Ag = Max Factored distributed lateral load, wu =

Load Combinatio .2SDS

U = 1.20 D + 0.5L + 1.6W U = 1.43 D + 0.5L + 1.QE

0.9 MSJC 3.1.4.1 50 0 #5 24 #4 24

#

U = 1.20 D + 1.6L

80 psf

Tributary Dead Load, D = Tributary Live Load, L = Vertical Rebars Spacing = Horizontal rebars Spacing = Wt. of the wall @ mid height Pw =

12.4.2.3

(3-25)

22.7 ≤ 0.05 fm, OK

(3-23), 3.3.5.4

Load Combination For Strength Design: (16-4) (16-5) (16-6)

(16-7)

60.0

71.7

45.0

33.3 lbs

1680.0

1680.0

2006.7

1260.0

933.3 lbs

1740.0

1740.0

2078.3

1305.0

966.7 lbs

19.0

19.0

22.7

14.3

10.6 psi

8.0

17.9

8.0

17.9 plf

As =

0.155 sq.in Ase = (Pu+As.fy)/fy a = (Pu+As.fy)/(0.8.f'm.b) c = a/0.8 Nominal strength, Mn = (Asfy + Pu)(d - a/2)

###

=

0.18

0.18

0.19

0.18

0.17 sq.in

(3-28) 3.3.2(g)

= =

0.77 0.96

0.77 0.96

0.79 0.99

0.74 0.92

0.71 inch 0.89 inch

(3-27)

=

37,830

37,830

38,856

36,500

35,456 lb-in

=

44.85

44.85

45.57

43.88

43.09 in4

=

84

84

84

84

84 psi

=

444

444

444

444

444 in4

=

9,780

9,780

9,780

9,780

=

0.39

0.39

0.39

0.39

=

235

27,479

116,993

21,413

=

0.01

N/A

N/A

N/A

N/A inch

= Mn =

N/A

7.22

40.32

5.02

16.19 inch

32,850 OK

31,911 lb-in NG

Icr = n.Ase.(d-c)2+bc3/3 Modulus of Rupture fr = 84.0

psi, per T-3.1.7.2.1

Ig = b.t3/12 Mu obtained by iteration of deflection ∆u (10times)

Mcr = (fr.Ig)/0.5.t

3.3.5.4

δcr = (5.Mcr.h2)/(48.Em.Ig)

Applied ultimate strength, Mu = wu.h2/8+Puf.e/2+Pu.δu

###

60.0

(3-24)

Mu < Mcru = (5.Mu.h2)/(48.Em.Ig) Mcr < Mu < Mn,u = cr+ 5.(Mu-Mcr)h2/(48.Em.Icr)

Mn shall not be less than Mu 34,047 34,047 34,970 Mn > Mu (3-26) OK OK NG Deflection at service load Load combination = D + L + (W or 0.7E) (16-15) Seismic Wind Unfactored lateral load, w = 12.5 5.0 plf Unfactored Load from trib floor/roof, Pf = 50.0 50.0 lbs Pw = 1,400.0 1,400.0 lbs Strength check

P = Pf+Pw

9,780 lb-in 0.39 in 48,697 lb-in

`

Δs ###

=

1,450.0

1,450.0

lbs

###

=

0.18

0.18

in2

###

a = Ase.fy/(0.8.f'm.b) c = a/0.8

= =

0.75 0.93

0.75 0.93

in in

###

Icr = n.Ase.(d-c)2+bc3/3

=

44.20

44.20

in4

###

=

42,540

10,126

lb-in

###

(3-30)

=

N/A

N/A

inch

###

(3-31) (3-29)

= =

13.32 2.94 NG

0.52 2.94 OK

inch inch

###

Ase = (P+As.fy)/fy

Ms = w.h2/8+Pf.e/2+(Pf+Pw).s Ms < Mcrs = (5.Ms.h2)/(48.Em.Ig) Mcr < Ms < Mns = cr+5.(Ms-Mcr)h2/(48.Em.Icr) Allowable= .007(h) Check total reinforcement Vertical reinforcement = 0.0017 Ag Horizontal reinforcement = Total =

0.0011 Ag 0.0028 Ag

###

###

Wood member Design: IBC

Dense DF#1 a DF#1 DF#2

Design Live Load, L Design Dead Load, D Load Duration

20 Psf 10 Psf Deflection Limits L/ 360 1.25 (1 for Normal, 1.25 For Roof, 1.15 For Snow Loading) Allow soil bearing= 1000 psf L.B with 2x Ledger RAFTER / OR FLOOR JOIST (Table 1) HEADER (Table 2) Allowable load of L.B. in lbs 270 530 Size, Member Data Spacing Span Header Rafter/Floor joist Max Span Spacing(inch) (Inch) (ft) (Inch) Size Span(ft)*Overhang Ft - Inch 3/8"dia 5/8"Dia ### 2x6 ## DF#2 ## R=Repetitive ##

875 4x10

2x12 2x14 DF#2

12

14

13

6

40

0 ## ###

8

6

6

13

2x6

16

12

12

3

95 DF#2

41

0 ### #

8

5

6

12

b

19.2

12

11

7

1.6 S=Single

42

0 ## ###

8

4

6

12

d

1.2 Fb

24

11

10

9

875

43

0 ### #

8

3

6

12

CF

# 2x8

12

18

18

2

CF

1.200

44

0 ## ###

8

2

6

12

Cr

## DF#1

16

17

16

6

Cr

1.00

45

0 ### #

8

1

6

11

E

19.2

16

15

6

FOOTING (Table 3)

24

14

14

5

Rafter/Floor Joist

## R=Repetitive ## DF#2, Fb= CF= For 2x6DF#2 Fb= Fv= E=

875 psi 1.3 1309 95 1.6

w/o Load Duration

Cr= 1.15 psi psi psi

For 4x10DF#2 Fb= 875 psi CF= 1.2 Cr= 1.00 Fv= 95 psi E= 1.6 psi R=Repetitive member Used (not more than 24" o/c) S=Single member Used Lag Bolts shall be min of 5" long * For header with Rafter or Joist at both side, spacing (rafter's span) shall be double or average.

RAFTER SPAN PER TABLE 1

Span*

Fb Post Spacing

Overhang

12.8

1.5

13.8

1.5

14.8

1.5

Fv

10

11

12

ft

Int footing Ext footing Int footing Ext footing

240 240 254 254

19 14 20 14

20 14 21 15

21 15 21 15

Sq.In Sq.In Sq.In Sq.In

Int footing Ext footing

269 269

20 14

21 15

22 16

Sq.In Sq.In

3x6

Specie size ## DF#1

Patio may be supported on concrete slab, provided that the post

2x8 b d

do not support D+L in excess of 750 lbs.

CF

MINIMUM ROOF LIVE LOAD PER IBC 1607.11.2 Tributary area At = 300.0 R1 = 1.2-.001At = 0.90 Rise per feet, F = 5 :12 R2 = 1.2-.05F = 0.95 Lr = 20R1R2 = 20(0.9)(0.95) Min Design Roof Lr = 17.10

Cr E

SQ.FT Eq. 16-29 6x8 6x10

Eq. 16-32 size

Eq. 16-24 DF#2

psf b d CF

LAG BOLT, SIZE & SPACING PER TABLE 2

HEADER, PER TABLE 2

HEADER, PER TABLE 2 POST SPACING PER TABLE 3 FOOTING SIZE PER TABLE 3

Cr E Fb Fv

Allowable load for plate, headed and bent bar anchor bolt per ACI 530-05, Section 2.1.4.2 Ab = ⅝˝ Diameter of angle bolt = 0.307 in2 Edge distance lbe =

15''

Equivalent embedment length, le =

10''

f'm = fy = Ap =

B a =0 . 5 A p √ f 'm

1,500 psi 36,000 psi πle2 = 314.29

in2

(2-3, 2-4)

=

6086 lbs

(2-1)

Ba = 0.2Abfy =

2,210 lbs

(2-2)

Allowable in tension, Ba =

2210 lbs

4

B v =350 √ f m A b '

=

1,621

Reduction factor =

1.00

or Bv = 0.12Abfy =

1,326 lbs

Allowable in shear Bv =

1,326 lbs

(2-5) Bv =

1,621 lbs (2-6)

Strength design for plate, headed and bent bar anchor bolt per ACI 530-05, Section 3.1.6 Ab = ⅝˝ Diameter of angle bolt = 0.307 Edge distance lbe =

15''

Equivalent embedment length, lb =

10''

f'm = fy = Apt =

1,500 psi 36,000 psi πlb2 = 314.29

Ban = .5(4Apt(f'm)½) =

24,344

(3-1)

Or Ban = 0.9Abfy =

9,944

(3-2)

Capacity in tension Ban =

9,944 lbs

Apv = ½(πl ) =

353.57

(3-10)

Bvn = .5(4Apv(f ) ) =

27,388

(3-8)

Or Bvn = 0.9(.6Abfy) =

5,967

(3-9)

2 be

' ½ m

Capacity in shear Bvn =

5,967 lbs

The application is created by Yo Ratanapeanchai, SE. This spreadsheet is intended as an educational tool for learning and understanding of the IBC 2006 and ASCE 7-05. It will perform both Fire Life Safety (chapter 3, 5, 6, 7, 8, 9, 10, 15 and 29) and Structural (Snow, Wind and Earthquake Load, Chapter 16 and ASCE7-05) .The application is freeware, so feel free to distribute, modify or use in anyway you see fit. Password protection is in place on some of the Worksheets and will not be given due to data integrity of the original development. Report by fax or email any errors or suggestions you may have. This will be greatly appreciated.

To verify the accuracy of the formula in each cell, just copy the entire Worksheet and paste or follow each calculation process manually. The built-in reset and print function are required for Macro to be set to Enable. See built in Help in Excel for more information.

DISCLAIMER STATEMENT: The author is not responsible and liable for the accuracy of this application and any information contained in this spreadsheet to the full extent permitted by the law.

Date

Location

30-Apr-06

All Sheets

Note

22-Jun-06

EQ

Revise cell C39, B43 to display Cs value, when T>TL Min Cs =0.01

8-Aug-06

Arch

A-2, Sprinkler

Egress

Common path of travel

7-Sep-06

CMU-Slender-wall

12-Sep-06

EQ

Pu, 0.2fm & 0.05fm Max, Min Fp

12-Dec-06

Free standing sign

Add wind load calc for sign

19-Dec-07

EQ

Revise Limitation for T-12.14-1 Revise cell C41, S1≥ 0.6g

[email protected]

Download the latest edition at

[email protected] Fax: 702-380-9773

http://seaoc.org/software.html

Last Update 12/19/2007

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF