ABB Power Technologies

Training Course EXERCISE 3

ABB-INDIA

PCM 600 EXERCISE 3

Objective: Purpose of this Exercise is to learn and understand: -

Input, output Assigning using Signal Matrix tool Indication LED assigning in SMT tool Parameter Setting Tool and its interface with the Application Configuration Tool (CAP 531) Getting familiar to SMT & PST download and Upload possibilities.

The Protection Device is connected to line according to the following diagram

.

Substation Automation and Protection Training - 1 -

ABB Power Technologies ABB-INDIA

Training Course EXERCISE 3

VIRTUAL INPUT AND OUTPUT ASSIGNING Now you can find the SIGNAL MATRIX & GRAPHICAL DISPLAY EDITOR when you Right click on the Plant structure.

Analog Input has to be mapped as shown in figure .

Substation Automation and Protection Training - 2 -

ABB Power Technologies ABB-INDIA

Training Course EXERCISE 3

Binary output assigning: You will be having 12 output contacts in your Input Output module, out of that which contact you want to make high for which output can be mapped with the help of signal matrix.

Binary Input Assigning:

Similarly, Input what you want take to the relay can also be mapped with the help of signal matrix tool. NOTE: In our Exercise we have not used any Binary INPUT.

Substation Automation and Protection Training - 3 -

ABB Power Technologies ABB-INDIA

Training Course EXERCISE 3

You can also assign LED for your particular output. Totally 15 User configurable LEDs available for ANNUNCIATION purpose

You can also Read the INPUTS and OUTPUTS which is already assigned in the IED by clicking the READ FROM IED icon shown in the figure.

Substation Automation and Protection Training - 4 -

ABB Power Technologies ABB-INDIA

Training Course EXERCISE 3

Similarly after modifying your input and output, you can write these changes to the IED with the help of WRITE TO IED icon as shown in figure

Substation Automation and Protection Training - 5 -

ABB Power Technologies ABB-INDIA

Training Course EXERCISE 3

Start the Parameter setting for the IED that you have used in the Previous Exercise.

ANALOG CHANNEL CT/PT RATIOS:

Goto Setting  General setting  Analog modules  Analog Input 6I and 6U Right click on Analog Input 6I and 6U, and then select the Parameter Setting.

Substation Automation and Protection Training - 6 -

ABB Power Technologies

Training Course EXERCISE 3

ABB-INDIA

CT Ratios Primary and Secondary In this Exercise out of 12 Analog channels first four channels (Current Channels) we have used for used for Overcurrent function.

For first four channels set CT ratio as 1000/1A as shown in figure.

Substation Automation and Protection Training - 7 -

ABB Power Technologies ABB-INDIA

Training Course EXERCISE 3

HMI LED INDICATION: There 15 users Configurable LED are available, that can be programmed by end user through Signal Matrix tool. LED 1 to 6 Red color LED LED 7 to 15 Yellow color LED. In SMT tool we have mapped first 4 LEDs out of that 15 LEDS. LED 1 – General Trip LED 2 – Rph O/C Trip LED 3 – Yph O/C Trip LED 4 – Bph O/C Trip

Substation Automation and Protection Training - 8 -

ABB Power Technologies

Training Course EXERCISE 3

ABB-INDIA

To get this indication During a Fault it has to be enabled in the Parameter setting which is shown below.

You can set the LED in different mode. In this Example we have set LED in LatchedReset S. It means until you reset the LED, it will glow and indicate that Relay has tripped on O/C.

Enable the HMI LED Function

Set the LEDs in Latched Reset-S Mode.

Substation Automation and Protection Training - 9 -

ABB Power Technologies

Training Course EXERCISE 3

ABB-INDIA

Disturbance Recording Setting: Enable the Disturbance Recorder function to capture the Waveforms of the Analog signal and to view the Binary channels Triggered during the Fault.

Set the PRE_ FAULT AND POST_ FAULR recording time here.

Analog signal that is used as phase reference from Disturbance Recorder in its Report (RPH_CU).

Substation Automation and Protection Training - 10 -

ABB Power Technologies ABB-INDIA

Training Course EXERCISE 3

Setting the Binary signals of Disturbance recorder Function:

Set now general trio signal OC_TRIP to trigger Disturbance recorder, other signals will just be shown on the HMI. Example here for signal one.

Set as shown above

Substation Automation and Protection Training - 11 -

ABB Power Technologies ABB-INDIA

Training Course EXERCISE 3

Setting the Analog signals of Disturbance recorder Function: Set the analog signals that you want to be recorded (the first four).

Set the setting for analog triggering as indicated here.

Substation Automation and Protection Training - 12 -

ABB Power Technologies

Training Course EXERCISE 3

ABB-INDIA

Setting for Overcurrent Function:

Set 1. IBase as 1000A 2. OpMode – 1 out of 3 3. IP>> as 200% If the Current exceeds 2000 A in Primary Overcurrent relay will TRIP.

Substation Automation and Protection Training - 13 -

ABB Power Technologies ABB-INDIA

Training Course EXERCISE 3

UPLOAD AND DOWNLOAD OF PARAMETERS: Right click on REL 670 IEC in the plant structure, and then click ‘PARAMETER SETTING’

You can read the parameter FROM the relay with help of READ PARAMETER FROM IED icon as shown in figure.

Substation Automation and Protection Training - 14 -

ABB Power Technologies ABB-INDIA

Training Course EXERCISE 3

You will be getting Read parameters from REL 670 IEC pop up window as shown in figure. Click OK to Read setting from the IED.

The changes you want to make can be made in the PC field as shown in figure.

After modifying the setting you can write these values to the IED with the help of WRITE PARAMETERS TO THE IED as shown in figure.

Substation Automation and Protection Training - 15 -

ABB Power Technologies

Training Course EXERCISE 3

ABB-INDIA

You will be getting Write parameters to REL 670 IEC Pop up window as shown in figure.

Click ok to Download Parameter to the IED.

***End of Exercise 3*** Substation Automation and Protection Training - 16 -