HIMAP ServiceManual E

Share Embed Donate


Short Description

HIMAP ServiceManual E...

Description

HIMAP- BC HYUNDAI HEAVY INDUSTRIES CO. LTD

BAY CONTROLLER Service Manual

HEAVY INDUSTRIES CO., LTD.

Service Manual

Version: File:

14.04.2005 (Du.) HIMAP_ServiceManual_E.doc

Firmware: -

HYUNDAI HIMAP

CU: MU: RU:

HIMAP_ServiceManual_E.doc

1.10 / 03.12.2004 1.10 / 25.10.2004 1.10 / 15.04.2004

- 2/149 -

Service Manual 1 Parameter settings introduction 5 1.1. Change of settings ........................................................................................................... 5 1.2. Event system introduction............................................................................................... 5 2. System settings....................................................................................................................... 6 2.1. Codes ............................................................................................................................... 7 2.2. General Parameter ........................................................................................................... 8 2.3. Nominal Ratio Values ................................................................................................... 13 2.4. Communication ............................................................................................................. 16 2.5. Analog Inputs ................................................................................................................ 19 2.5.1. PT100 Inputs ......................................................................................................... 22 2.6. Binary Inputs ................................................................................................................. 24 2.7. Analogous Outputs ........................................................................................................ 25 2.8. Binary Outputs .............................................................................................................. 27 2.8.1. Shunt #1 output ..................................................................................................... 27 2.8.2. Shunt #2 output ..................................................................................................... 28 2.8.3. Lockout relay......................................................................................................... 29 2.8.4. Synchron ON output.............................................................................................. 30 2.8.5. Function outputs ................................................................................................... 31 2.9. Event Builder................................................................................................................. 32 2.10. Power management ................................................................................................... 33 2.10.1. General PM Parameter .......................................................................................... 34 2.10.2. Power management ............................................................................................... 39 2.10.3. Load sharing.......................................................................................................... 42 2.10.4. Frequency controller ............................................................................................. 45 2.10.5. Voltage regulator................................................................................................... 47 2.10.6. Power factor controller.......................................................................................... 49 2.10.7. Big consumer request (BCR) ................................................................................ 51 2.10.8. Blackout ................................................................................................................ 53 2.10.9. Diesel control ........................................................................................................ 56 2.10.10. Starting phase ........................................................................................................ 58 2.10.11. Stopping phase ...................................................................................................... 61 2.10.12. Preferential trip limits / Abnormal bus condition.................................................. 65 2.10.13. Additional limits.................................................................................................... 67 3. Relay settings ....................................................................................................................... 69 3.1. ANSI 15 - Matching device (motorpoti) ....................................................................... 70 3.2. ANSI 24 - Overexcitation Relay ................................................................................... 71 3.3. ANSI 25 /A – Automatic Synchronizing ...................................................................... 72 3.4. ANSI 27 - Undervoltage Relay ..................................................................................... 80 3.5. ANSI 27B - Bus undervoltage relay ............................................................................. 82 3.6. ANSI 32 - Overload Relay ........................................................................................... 83 3.7. ANSI 37 - Undercurrent Relay (motor) ........................................................................ 84 3.8. ANSI 40Q - Loss of Excitation Relay........................................................................... 85 3.9. ANSI 46 - Negative Sequence Relay ............................................................................ 87 3.10. ANSI 47 - Phase sequence voltage relay .................................................................. 90 3.11. ANSI 49 - Thermal Overload.................................................................................... 91 3.11.1. Thermal overload I (general)................................................................................ 91 3.11.2. Thermal overload II (user) .................................................................................... 94 3.11.3. Thermal overload III (interval).............................................................................. 96 3.12. ANSI 50BF – Breaker Failure................................................................................... 97 3.13. ANSI 50 – Instantaneous overcurrent relay .............................................................. 98 3.14. ANSI 50G/N – Instantaneous ground overcurrent relay......................................... 100 HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 3/149 -

Service Manual 3.15. ANSI 51 – AC time overcurrent relay .................................................................... 102 3.16. ANSI 51G/N – AC time ground overcurrent relay ................................................. 105 3.17. ANSI 51LR – Locked Rotor ................................................................................... 107 3.18. ANSI 59 – Overvoltage relay................................................................................. 109 3.19. ANSI 59B – Bus overvoltage relay......................................................................... 111 3.20. ANSI 64 / 59N – Overvoltage ground relay ........................................................... 112 3.21. ANSI 66 – Start Inhibit for Motors ......................................................................... 113 3.22. ANSI 67 – AC directional overcurrent relay .......................................................... 114 3.23. ANSI 67GS/GD – AC directional ground overcurrent relay .................................. 118 3.24. ANSI 78 – Vector surge/ dF/dt supervision relay .................................................. 120 3.25. ANSI 78 S Out of step tripping............................................................................... 122 3.26. ANSI 79 – AC reclosing relay ................................................................................ 123 3.27. ANSI 81 – Frequency relay..................................................................................... 126 3.28. ANSI 81B – Bus frequency relay............................................................................ 129 3.29. ANSI 86 – Lockout relay ........................................................................................ 131 3.30. ANSI 87 – Differential protective relay.................................................................. 132 3.31. ANSI 87N – Restrict earth fault relay..................................................................... 135 3.32. ANSI 94 – Supervision relay .................................................................................. 137 3.33. ANSI 95i – Inrush blocking relay ........................................................................... 141 3.34. ANSI FF – Fuse failure (voltages) .......................................................................... 143 4. Alarm controller settings .................................................................................................. 145 5. Special parameter.............................................................................................................. 148

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 4/149 -

Service Manual

1 Parameter settings introduction 1.1. Change of settings All settings can be easily set or changed directly with the front panel keys of HIMAP without any additional programming device or laptop computer. A menu tree structure offers easy access to the functions. To change a setting or to set new settings, first select the parameter with the updown keys (↑↓), and then press “ENTER.” The requested digit can be selected by using the leftright keys (←→). The digit can be changed by pressing the up-down keys (↑↓). After finishing the change of values (numbers) or text declaration, such as ON or OFF, press the “ENTER” key. The next parameter may now be selected by pressing the up-down keys (↑↓). 1.2. Event system introduction The event system of the device gives the user the possibility to realise his own applications. With events all functions of the device can be activated or deactivated. An event is a internal logical representation of a device process. The event system offers sources and sinks of events. The event sources have fixed unique event numbers. These event numbers became active (logically “True”) if the condition related to this event is fullfilled (e.g. a limit is reached), otherwise inactive (logically “False”). The event sinks are linked to fixed processes or fixed functions and can be programmed by the user. The user can build a link between the source and the sink by setting an event source number to an event sink number. The sink (function) became active if the related source became also active. Note: some modules are sinks and sources at the same time, e.g. all binary outputs are sinks and will be activated by source events. But every binary output produces himself again source events when he becomes active. The same is valid for alarms and all event builder elements. The source events can be combined over logic modules (event builder) which produces new source events. Examples: • The ANSI 25 /A Synchronizing unit 1 should be activated by a binary input (FUNC 20). The binary input is an event source and the Sync. unit is an event sink. The event number related to the input is 521. This number must be set on parameter 1000 (SYNC. UNIT 1 acitve by: 521) by the user. Then FUNC.20 activates the Sync. unit 1. • The ANSI 50 Overcurrent device should open a circuit breaker over a binary output (Shunt#1). ANSI 50 is an event source and the binary output an event sink (respectively a source). One event number related to ANSI 50 is 1402 (1.limit reached and delay passed). This number must be set on Shunt#1 (e.g. 01: 1402). Then a measured current value will open a circuit breaker.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 5/149 -

Service Manual

2. System settings The following figure shows the different system parameter groups. HIMAP system parameter groups: SYSTEM PARAMETER 00 01 02 03 04 05 06 07 08 09

Codes General parameter Nominal ratio values Communication Analogous inputs Binary inputs Analogous outputs Binary outputs Event builder Power management

RELAY

AL.CTRL

HYUNDAI HIMAP

EXIT

HIMAP_ServiceManual_E.doc

- 6/149 -

Service Manual 2.1. Codes The system codes are used to define access levels for the user. HIMAP parameters: Codes

Setting range:

0001. Breaker/system control : 0002. Settings w/o ev.builder: 0003. Master password :

1111 1111 1111

BACK

0…9999 0…9999 0…9999

EXIT

Parameter description: [0001. Breaker/system control :] Only for breaker or system control, not for change of settings. [0002. Settings w/o ev.builder :] For breaker or system control and for change of settings, but without codes and event builder. [0003. Master password :] Access without restrictions. Note: the default codes have all the value 1111.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 7/149 -

Service Manual 2.2. General Parameter The general parameters of HIMAP contains the setting of the on-board real time clock, the selection of the graphic mimic for the LC-Display and the definition of the corresponding circuitbreaker feedback signals. HIMAP Parameter: Setting range:

General Parameter 0100. 0101. 0102. 0103. 0104. 0105. 0106. 0107. 0108. 0109. 0110. 0111. 0112.

TIME setting

- hours : 16 - minutes: 47 DATE setting - year : 2003 – month : 10 - day : 21 – format : YY.MM.DD LANGUAGE - select : ENGLISH GRAPHIC TYPE – select :1B ES.F-O reserved: reserved: reserved: Meters average builder : 10,0 sec Check control access : ON ! BACK EXIT

0……24 0……60 2002…2040 0……12 0……31 D.M.Y, Y.M.D, M.D.Y ENGLISH/GERMAN/FRENCH/RUSSIAN

(see Appendix A3)

0,0...999,9 sec OFF/ON

Figure: GeneralParameter-1

Setting range:

General Parameter "

0113. 0114. 0115. 0116. 0117. 0118. 0119. 0120. 0121. 0122. 0123. 0124. 0125.

BREAKER 1 –ON feedback : –OFF feedback: - ON->OFF control event - OFF->ON control event - IN feedback : - OUT feedback : - OUT->IN control event - IN->OUT control event – EARTH ON feedback : – EARTH OFF feedback : - EARTH->OFF ctrl.event - OFF->EARTH ctrl.event – ctrl. time (fail ev.): BACK

500 0 0 0 0 0 15,0 sec! EXIT

0…9999 Event 0…9999 Event event display only event display only 0…9999 Event 0…9999 Event event display only event display only 0…9999 Event 0…9999 Event event display only event display only 0,0…9999,9 sec

Figure: GeneralParameter -2

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 8/149 -

Service Manual Setting range:

General Parameter 0126. 0127. 0128. 0129. 0130. 0131. 0132. 0133. 0134. 0135. 0136. 0137. 0138.

BREAKER 2 –ON feedback : –OFF feedback: - ON->OFF control event - OFF->ON control event - IN feedback : - OUT feedback : - OUT->IN control event - IN->OUT control event – EARTH ON feedback : – EARTH OFF feedback : - EARTH->OFF ctrl.event - OFF->EARTH ctrl.event – ctrl. time (fail ev.): BACK

502 0

"

0 0 504 0 15,0 sec EXIT

!

0…9999 Event 0…9999 Event event display event display 0…9999 Event 0…9999 Event event display event display 0…9999 Event 0…9999 Event event display event display 0,0…999,9 sec

only only only only only only

Figure: GeneralParameter -3

Setting range:

General Parameter "

0139. 0140. 0141. 0142. 0143. 0144. 0145. 0146. 0147. 0148. 0149. 0150. 0151.

BREAKER 3 –ON feedback : –OFF feedback: - ON->OFF control event - OFF->ON control event - IN feedback : - OUT feedback : - OUT->IN control event - IN->OUT control event – EARTH ON feedback : – EARTH OFF feedback : - EARTH->OFF ctrl.event - OFF->EARTH ctrl.event – ctrl. time (fail ev.): BACK

0 0 0 0 0 0 15,0 sec EXIT

0…9999 Event 0…9999 Event event display event display 0…9999 Event 0…9999 Event event display event display 0…9999 Event 0…9999 Event event display event display 0,0…999,9 sec

only only only only only only

Figure: GeneralParameter –4

Setting range:

General Parameter "

0152. 0153. 0154. 0155. 0156. 0157. 0158. 0159. 0160. 0161. 0162. 0163.

COUNTER - Working hours: 0 h reserved: – Active power(fwd) P+ : 0 – Active power(rev) P- : 0 – React. power(cap) Q+ : 0 – React. power(ind) Q- : 0 – Breaker 1 ON cycles : 0 – EARTH cycles : 0 – Breaker 2 ON cycles : 0 – EARTH cycles : 0 – Breaker 3 ON cycles : 0 – Breaker 1 ON max.cyc.: 10000 BACK

0…999999 hours 0……4294967280 0……4294967280 0……4294967280 0……4294967280 0…… 65535 0…… 65535 0…… 65535 0…… 65535 0…… 65535 0…… 65535

EXIT

Figure: GeneralParameter –5

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 9/149 -

Service Manual Setting range:

General Parameter 0164. 0165. 0166. 0167. 0168. 0169. 0170. 0171. 0172. 0173.

– EARTH max.cyc.: – Breaker 2 ON max.cyc.: – EARTH max.cyc.: – Breaker 3 ON max.cyc.: – kWh-pulses (P+) : – kWh/pulse : – pulse duration: Switchgeardoor feedback: REMOTE – ACK : Switch op.mode(loc/rem): BACK

10000 10000 10000 10000 ON 10 0,05 sec 0 526 0

0……65535 0……65535 0……65535 0……65535 ON / OFF 0-9999 0,01…99,99 sec 0…9999 Event 0…9999 Event 0…9999 Event

EXIT

Figure: GeneralParameter-6

Parameter description: [0100. Time setting - hours :] Setting of hours of the integrated real time clock (RTC). Note: if devices are conneceted over the CAN1-bus they will synchronize their RTCs automatically. [0101. - minutes :] Setting of minutes of the integrated real time clock (RTC). [0102. Date setting - year :] Setting of year of the integrated real time clock (RTC). [0103. - month :] Setting of month of the integrated real time clock (RTC). [0104. - day :] Setting of day of the integrated real time clock (RTC). [0105. - format :] Selection of shown format of the date. [0106. LANGUAGE - select :] Actually available: english, german, french, russian. Only for the user menu, not for the settings menu section. [0107. GRAPHIC TYPE – select :] Selection of the shown graphic (bus bar and breaker arrangement). For details refer to the appendix A3. [0111. Meters average builder :] This parameter is valid for all meter values displayed on all pages and on the 7-segment displays. If the changing of a value is below the deadband limit (parameter 74, see chapter 5.) the average builder will plane the value (Exception: on the current meters page the column “average” is build always even if the value is higher than the deadband limit). [0112. Check control access :] OFF = free breaker control over the front panel. ON = password protected breaker control over the front panel.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 10/149 -

Service Manual

[0113. BREAKER 1 -ON feedback :] Assignment of the belonging function input of the breaker no. 1 ON feedback. [0114. -OFF feedback :] Assignment of the belonging function input of the breaker no. 1 OFF feedback. [0115. - ON->OFF control event :] Control event of the ON => OFF switching cycle of breaker no. 1. [0116. - OFF->ON control event :] Control event of the OFF => ON switching cycle of breaker no. 1. [0117. - IN feedback :] Assignment of the belonging function input of the breaker no. 1 IN position feedback. [0118. - OUT feedback :] Assignment of the belonging function input of the breaker no. 1 OUT position feedback. [0119. - OUT->IN control event :] Control event of the OUT => IN position movement of breaker no. 1. [0120. - IN->OUT control event :] Control event of the IN => OUT position movement of breaker no. 1. [0121. - EARTH ON feedback :] Assignment of the belonging function input of the breaker no. 1 EARTH ON position feedback. [0122. - EARTH OFF feedback :] Assignment of the belonging function input of the breaker no. 1 EARTH OFF position feedback. [0123. - EARTH->OFF ctrl. event :] Control event of the EARTH => OFF position movement of breaker no. 1. [0124. - OFF->EARTH ctrl. event :] Control event of the OFF => EARTH position movement of breaker no. 1. [0125. - ctrl. time (fail ev.) :] Setting of supervision time (control time) of the maximum operation time of a switching cycle or position movement of breaker 1. If the breaker does not reach the desired position within this time event 125 will become active (until ACK). Use this event to trigger an alarm for an error message. [0126. BREAKER 2 -ON feedback :] to [0138. - control time :] See description of Breaker 1 (events 113 to 125). [0139. BREAKER 3 -ON feedback :] to [0151. - control time :] See description of Breaker 1 (events 113 to 125). [0152. COUNTER – Working hours :] Setting of the counter of working hours. [0154. - Active power(fwd) P+ :] Setting of the counter of active power (forward) Pw+ in kWh. [0155. - Active power(rev) P:] Setting of the counter of active power (reverse) Pw- in kWh. [0156. - React. power(cap) Q+ :] Setting of the counter of reactive power (capacitive) Pq+ in kvarh. HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 11/149 -

Service Manual

[0157. - React. power(ind) Q:] Setting of the counter of reactive power (inductive) Pq- in kvarh. [0158. - Breaker 1 ON cycles :] Setting of the cycle counter of disconnecting switch no. 1. [0159. - EARTH cycles :] Setting of the cycle counter of the earth switch no. 1. [0160. - Breaker 2 ON cycles :] Setting of the cycle counter of disconnecting switch no. 2. [0161. - EARTH cycles :] Setting of the cycle counter of the earth switch no. 2. [0162. - Breaker 3 ON cycles :] Setting of the cycle counter of disconnecting switch no. 3. [0163. - Breaker 1 ON max.cyc. :] Setting of maximum cycles of disconnecting switch no. 1 before next inspection. [0164. - EARTH max.cyc. :] Setting of maximum cycles of earthing switch no. 1 before next inspection. [0165. - Breaker 2 ON max.cyc. :] Setting of maximum cycles of disconnecting switch no. 2 before next inspection. [0166. - EARTH max.cyc. :] Setting of maximum cycles of earthing switch no. 2 before next inspection. [0167. - Breaker 3 ON max.cyc. :] Setting of maximum cycles of disconnecting switch no. 3 before next inspection. [0168. - kWh-pulses (P+) :] Selection if the kWh-pulse function is switched ON or OFF. [0169. – kWh/pulse :] Setting of kWh per counter pulse. [0170. – pulse duration :] Setting of the pulse duration. Use the event 170 to drive an binary output. [0171. Switchgeardoor feedback :] Assignment of the belonging function input of the switchgeardoor feedback. [0172. REMOTE – ACK :] Assignment of the belonging function input of the remote acknowlegement. [0173. Switch op.mode(loc/rem) :] Assignment of the belonging function input of the local / remote mode switch.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 12/149 -

Service Manual 2.3. Nominal Ratio Values With the nominal ratio values the user can select the different external transformer types. NOMINAL RATIO VALUES 0200. 0201. 0202. 0203. 0204. 0205. 0206. 0207. 0208. 0209. 0210. 0211. 0212. 0213. 0214. 0215. 0216. 0217. 0218. 0219. 0220. 0221. 0222. 0223.

NOMINAL RATED – Current: – Voltage : - Active Power : – Frequency : CT Feeder –primary side: PT Feeder –primary side: –secondary side: PT BUS1 –primary side: –secondary side: PT BUS2 –primary side: –secondary side: PT GND1 –primary side: –secondary side: PT GND2 –primary side: –secondary side: CT GND1 -primary side: –secondary side: CT GND2 -primary side: –secondary side: CT DIFF -primary side: –Winding ratio: Uaux nominal input : Shunt#1 nominal input : Shunt#2 nominal input : BACK

Permissible setting range: 1000 A 25400 V 35195 kW 60 Hz 1000 A 25400 V 100 V 25400 V 100 V 25400 V 100 V 25400 V " 100 V ! 0 V 0 V 1000 A 5 A 0 A 0 A 0 A 1.00 110Vac 110Vac 110Vac

0……65535 A 0……65535 V 0……65535 kW 50 / 60 Hz 0……65535 A 0……65535 V 0……65535 V 0……65535 V 0……65535 V 0……65535 V 0……65535 V 0……65535 V 0……65535 V 0……65535 V 0……65535 V 0……65535 A 0……65535 A 0……65535 A 0……65535 A 0……65535 A 0.01……99.99 24 Vdc……230 24 Vdc……230 24 Vdc……230

Wprim/Wsec Vac Vac Vac

EXIT

Figure 1. 2. 3-1: Nominal Ratio Values-1

[0200. NOMINAL RATED - Current :] Setting of the nominal rated current of the feeder, generator, motor or transformer primary side. [0201. - Voltage :] Setting of the nominal rated voltage of the feeder, generator, motor or transformer primary side. [0202. - Active Power :] Setting of the nominal rated active power of the feeder, generator, motor or transformer primary side. [0203. - Frequency :] Setting of the nominal rated frequency of the feeder, generator, motor or transformer. [0204. CT Feeder -primary side :] Setting of the nominal rated current from the primary side of the feeder current measuring current transformer (CT).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 13/149 -

Service Manual [0205. PT Feeder -primary side :] Setting of the nominal rated voltage from the primary side of the feeder voltage measuring voltage transformer (PT). Note: Event 205 is activated if a negative sequence of the feeder voltage is detected. This supervision is always active. [0206. -secondary side :] Setting of the nominal rated voltage from the secondary side of the feeder voltage measuring voltage transformer (PT). [0207. PT BUS1 -primary side :] Setting of the nominal rated voltage from the primary side of the busbar #1 voltage measuring voltage transformer (PT). Note: Event 207 is activated if a negative sequence of the bus 1 voltage is detected. This supervision is always active. [0208. -secondary side :] Setting of the nominal rated voltage from the secondary side of the busbar #1 voltage measuring voltage transformer (PT). [0209. PT BUS2 -primary side :] Setting of the nominal rated voltage from the primary side of the busbar #2 voltage measuring voltage transformer (PT). Note: Event 209 is activated if a negative sequence of the bus 2 voltage is detected. This supervision is always active. [0210. -secondary side :] Setting of the nominal rated voltage from the secondary side of the busbar #2 voltage measuring voltage transformer (PT). [0211. PT GND1 -primary side :] Setting of the nominal rated voltage from the primary side of the ground #1 voltage measuring voltage transformer (PT). [0212. -secondary side :] Setting of the nominal rated voltage from the secondary side of the ground #1 voltage measuring voltage transformer (PT). [0213. PT GND2 -primary side :] Setting of the nominal rated voltage from the primary side of the ground #2 voltage measuring voltage transformer (PT). [0214. -secondary side :] Setting of the nominal rated voltage from the secondary side of the ground #2 voltage measuring voltage transformer (PT). [0215. CT GND1 -primary side :] Setting of the nominal rated current from the primary side of the ground1 current measuring current transformer (CT). [0216. -secondary side :] Setting of the nominal rated current from the secondary side of the ground1 current measuring current transformer (CT).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 14/149 -

Service Manual [0217. CT GND2 -primary side :] Setting of the nominal rated current from the primary side of the ground2 current measuring current transformer (CT). [0218. -secondary side :] Setting of the nominal rated current from the secondary side of the ground2 current measuring current transformer (CT). [0219. CT DIFF -primary side :] Setting of the nominal rated current from the primary side of the differential current measuring current transformer (CT). [0220. – Winding ratio :] In case of transformer differential protection, the winding ratio of the transformer (WPrimary to WSecondary ) can be adjusted. [0221. Uaux nominal input :] Setting of nominal rated voltage of the power supply of the device. [0222. Shunt#1 nominal input :] Setting of nominal rated voltage of the shunt#1 trip circuit. [0223. Shunt#2 nominal input :] Setting of nominal rated voltage of the shunt#2 trip circuit.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 15/149 -

Service Manual 2.4. Communication HIMAP provides five communication ports. The RS232 port on the front panel is always available. Use it to upload the firmware or to communicate with the HIMAP PC-tools. The other ports are on the backside, and they are programmable by the user with the parameters shown in Figure 1.2.4. Please note, that the PROFIBUS and CAN ports only optional. Refer to the order list for detailed information. COMMUNICATION PARAMETER 0300. 0301. 0302. 0303. 0304. 0305. 0306. 0307. 0308. 0309. 0310. 0311. 0312. 0313. 0314. 0315. 0316. 0317. 0318. 0319. 0320. 0321. 0322. 0323. 0324.

Permissible setting range:

SERIAL PORT 1 (ASC1) : OFF – address : 0 – baud rate : 57600 Bd – protocol : PC TOOLS PROFIBUS - com.port : OFF – address : 0 – first byte : LOW – application: none CAN 1 - com. port : OFF – number of nodes: 2 – identifier : 01 – identifier size: standard – baud rate :1000.0 kBd reserved: CAN 2 - com. port : ON – number of nodes: 1 – identifier : 1 – identifier size: standard – baud rate : 125.0 kBd – application :MDEC303 V1 – MDEC override : 0 reserved: SERIAL PORT 2 (ASC2) : OFF – address : 0 – baud rate : 625000 Bd

BACK

OFF / RS485 / RS422 0………255 9600/19200/38400/57600/62500 PC TOOLS/MODBUS/KUHSE/REMOTE OFF / ON 0………125 LOW / HIGH none ON / OFF 1………14 1………14 standard/extended 15.6kBd ………1000.0kBd OFF / ON 1………32 0………65535 standard/extended 15.6kBd ………1000.0kBd none,MDEC303 V1,MDEC303 all 0…..9999 OFF / ON 0…65535 9600……625000 Bd

EXIT

Figure 1.2.4: Communication parameters

[0300. SERIAL PORT 1 (ASC1)] Setting of the physical layer for this communication port. Use the Terminals 26 (-) and 27 (+) of plug X2.2 for the RS485 communication. For RS422 use the Terminals 26 (RxD -), 27 (RxD +), 28 (TxD -) and 29 (TxD+) of the same plug. If you do not want to use one of these communications, set this parameter to OFF. [0301. - address :] Setting of the communication address of this device for RS 422/485. [0302. - baud rate :] Selection of the transmission speed for RS232/422/485. If there are some problems with the communication, it may be useful to lower the speed. HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 16/149 -

Service Manual [0303. - protocol :] Selection of the protocol type. The table below shows the possible applications the device provides. For more details, please see Appendix A1. Parameter [303] PC TOOLS MODBUS KUHSE REMOTE

Description used for the HIMAP PC-tools for communication with a main control unit special protocol for communication between two HIMAP devices

[0304. PROFIBUS – com. port :] ON / OFF switch for the PROFIBUS port. The standard PROFIBUS DP V1 is fulfilled. The Parameters [0304] to [0307] work only with this communication port. Note: Event 304 is active if the device is exchanging data with the master. [0305. - address :] Setting of the communication address of this device for PROFIBUS communication. Make sure that there is only one specific address in the communication. [0306. -first byte :] Selection of the transmission sequence of a word (16 bit = 2 bytes) or of a long word (32 bit = 4 bytes). Choose “HIGH” to transmit the high byte first; or choose “LOW” to transmit the low byte first. [0307. - application :] Reserved for special applications.

[0308. CAN 1 – com. port :] ON / OFF switch for the CAN 1 port. The Parameters [0308] to [0313] work only with this first CAN-communication port. Note: if devices are connected over the CAN1-bus they will synchronize their RTCs (real time clocks) automatically. In this case, the RTC of the node with the smallest CANIdentifier (310) is the reference for all other RTCs. [0309. - number of nodes :] This parameter shows the number of devices connected to the CAN communication. If there are less nodes than this number detected on the CAN1-bus, system failure 3019 (“CAN1 node error”) will be activated. [0310. - identifier :] Setting of the communication identifier of this device for CAN communication. Make sure that there is only one specific identifier in the communication. [0311. - identifier size :] Selection of the identifier format. Choose “standard” for the 11 bit identifier; or choose “extended” for the 29 bit identifier. [0312. - baud rate :] Selection of the transmission speed for CAN communication. If there are some problems with the communication, it may be useful to lower the speed.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 17/149 -

Service Manual

[0314. CAN 2 – com. port :] ON / OFF switch for the CAN 2 port. The Parameters [0314] to [0319] work only with this second CAN-communication port. [0315. - number of nodes :] This parameter shows the number of devices connected to the CAN communication. [0316. - identifier :] Setting of the communication identifier of this device for CAN communication. Make sure that there is only one specific identifier in the communication. [0317. - identifier size :] Selection of the identifier format. Choose “standard” for the 11 bit identifier; or choose “extended” for the 29 bit identifier. [0318. - baud rate :] Selection of the transmission speed for CAN communication. If there are some problems with the communication, it may be useful to lower the speed. [0319. - application :] This parameter defines the application of the second CAN bus port. The table below shows the possible applications the device provides. Parameter [319] none MDEC303 V1 MDEC303 all

Description CAN2 port switched off Special communication protocol for MDEC controller (MTU). If MDEC application is in use, then the baud rate of 125kbaud will be set internally, as well as the identifier, 6, and the identifier size, standard. In version V1 only the most important data will be displayed. With option “all”, all data of the protocol will be shown on LCD.

[0320. - MDEC override :] Only for CAN2 application: MDEC 303. If the set event number is active, the MDEC function “override” also becomes active. Note: this means that the MTU-diesel will not stop if any engine trouble occurs. [0322. SERIAL PORT 2 (ASC2)] This port is only available for special differential protection applications. [0323. - address :] Setting of the communication address of this device. [0324. - baud rate :] Selection of the transmission speed.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 18/149 -

Service Manual 2.5. Analog Inputs Within the main device, there are four analog inputs available. The selection of two physical standards and many measuring types is possible. It is also possible to get customer-specialized measuring types – please ask the manufacturer. The description below shows an example of the parameter setting for analog input #1. With the change of the measuring type, the unit of the measuring input will be adapted. Thus the unit of the following parameter will be changed automatically. The settings for the other analog inputs are the same with the exception of the parameter / event numbers. The parameter / event numbers for the other analog inputs are listed at the end of this chapter. HIMAP Parameter: ANALOG INPUT – Select:

0400. 0401. 0402. 0403.

CURRENT INPUT 1 -X2.4/54,55 - Function : 0-20 - Measuring type[unit]: mA - Full scale : 0.0 - Zero scale : 0.0 – 1.Limit : 0.0 - 1.Limit high/low : LOW – 1.Limit delay time : 0.0 – 2.Limit : 0.0 - 2.Limit high/low : LOW – 2.Limit delay time : 0.0 - Hysteresis : 5,0 BACK

Permissible setting range:

01 mA mA mA mA sec mA sec %

OFF/0-20mA/4-20mA/0-10V see Table below 0.0……999.9 0.0……999.9 0.0……999.9 LOW/HIGH 0.0……999.9 sec 0.0……999.9 LOW/HIGH 0.0……999.9 sec 0.0……999.9 %

EXIT

Figure125-1: Analogous Input-1

Parameter description: [ [

CURRENT INPUT 1 -X2.4/54,55:] Name of the analog input with plug number and terminal numbers. Function :] Selection of the physical standard for this special input.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 19/149 -

Service Manual [

Measuring type[unit] :] This parameter defines the setting of the measuring type or the measuring unit. The following table shows all possible selections: Setting mA B1-Gas[bar] B1-Gas[g/l] B2-Gas[bar] B2-Gas[g/l] S1-Gas[bar] S1-Gas[g/l] S2-Gas[bar] S2-Gas[g/l] Gas[bar] Gas[g/l] Temp.[C] Temp.[F] Load [%]

RPM [%] Fuel [l] Fuel [m3] Voltage [V] Percent [%] bar CUR-OUT 1 CUR-OUT 2 CUR-OUT 3 CUR-OUT 4

Description The unit of the input is mA

Special application for GIS (Note: for this application, the parameter “function” must be set to: 4-20mA)

The unit of the input is °C The unit of the input is Fahrenheit The input can be used in combination with the asymmetric load controller (HIMAP XG/BCG only). If Parameter 0935 (analog input) is set, the measured value is the setpoint for the asymmetric load controller. The range of the input is 0-100%. With the help of full and zero scale adjustment, the range can be limited. The input can be used as a tacho input (HIMAP XG/BCG only). If parameter 265 (see 2.10.9.) is set, the measured value will be taken as a speed signal. The unit of the input is liter The unit of the input is m3 The unit of this input is V Can be used for any measuring The unit of the input is bar With this types, the analog outputs can be feed back to the analog inputs in order to use the limit events of the analog inputs. (The unit for this types are mA).

Figure125-2: Measuring types for analogous Inputs

[

Full scale :] Adjustment of the full scale point (20 mA = ?). [ Zero scale :] Adjustment of the zero scale point (0 or 4 mA = ?). [0400. 1. Limit :] Setting of the first limit event of this analog input. If the actual measured value is higher or lower than this limit, event 0400 will be set. [ 1. Limit high/low :] Selection of high or low level limit for Parameter 0400. In case of high limit, the actual measured value has to exceed the limit of Parameter 0400, in case of low limit, the actual value has to fall below the limit to set the corresponding event. HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 20/149 -

Service Manual [0401. 1. Limit delay time :] If Event 0400 is active and this delay time is passed, the Event 0401 will be activated as long as the actual value falls below the limit of Parameter 0400. Please use this parameter for the alarm controller. [0402. 2. Limit :] Setting of the second limit event of this analog input. If the actual measured value is higher or lower than this limit, event 0402 will be set. [ 2. Limit high/low :] Selection of high or low level limit for Parameter 0402. In case of high limit, the actual measured value has to exceed the limit of Parameter 0402. In case of low limit, the actual value has to fall below the limit to set the corresponding event. [0403. 2. Limit delay time :] If Event 0402 is active and this delay time is passed, the Event 0403 will be activated as long as the actual value falls below the limit of Parameter 0402. Please use this parameter for the alarm controller. [

Hysteresis :] Setting of the hysteresis for both limits.

analogue Event number Event number 1. Limit 1. Limit delay time 01 (CURRENT INPUT1) 0400 0401 02 (CURRENT INPUT2) 0404 0405 03 (CURRENT INPUT3) 0408 0409 04 (CURRENT INPUT4) 0412 0413

Number input

of

Event number Event number 2. Limit 2. Limit delay time 0402 0403 0406 0407 0410 0411 0414 0415

Figure: Event numbers for the current inputs

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 21/149 -

Service Manual 2.5.1.

PT100 Inputs

The following temperature measuring inputs are only available with the listed extension boards (with the main device there are no PT100 inputs): Number of analog input

CMA210 Connectors (16 PT100 inputs)

CMA211 Connectors (5 PT100 inputs)

05 (PT100-1) 06 (PT100-2) 07 (PT100-3) 08 (PT100-4) 09 (PT100-5) 10 (PT100-6) 11 (PT100-7) 12 (PT100-8) 13 (PT100-9) 14 (PT100-10) 15 (PT100-11) 16 (PT100-12) 17 (PT100-13) 18 (PT100-14) 19 (PT100-15) 20 (PT100-16)

-X40: 1,2,3 -X40: 4,5,6 -X40: 7,8,9 -X40: 10,11,12 -X40: 13,14,15 -X40: 16,17,18 -X40: 19,20,21 -X41: 25,26,27 -X41: 28,29,30 -X41: 31,32,33 -X41: 34,35,36 -X41: 37,38,39 -X41: 40,41,42 -X41: 43,44,45 -X41: 46,47,48 -X41: 49,50,51

-X44: 48,49,50 -X44: 51,52,53 -X44: 54,55,56 -X44: 57,58,59 -X44: 60,61,62 not available not available not available not available not available not available not available not available not available not available not available

Figure: Connectors for temperature measuring inputs

The description shows an example of the parameter setting for PT100-1. The settings for the other temperature measuring inputs are the same with the exception of the parameter / event numbers. ANALOG INPUT – Select:

0416. 0417. 0418. 0419.

05

PT100- 1 ext.board –X40/1,2,3 - Function : OFF - Measuring type[unit]: PT100 [C] - Full scale : 320.0 C - Zero scale : - 40.0 C – 1.Limit : + 0.0 C - 1.Limit high/low : LOW – 1.Limit delay time : 0.0 sec – 2.Limit : + 0.0 C - 2.Limit high/low : LOW – 2.Limit delay time : 0.0 sec - Hysteresis : 5,0 % BACK EXIT

Permissible setting range: OFF / ON PT100 / PT1000 0.0°C……999.9°C -999.9°C……+999.9°C -999.9°C……+999.9°C LOW / HIGH 0.0………999.9 sec -999.9°C……+999.9°C LOW / HIGH 0.0………999.9 sec 0.0………99.9 %

Figure: Analogous Input-5

Parameter description: [ [ [

PT100-1 ext.board -X40/1,2,3:] Name of the analogous input with plug number and terminal numbers. Function :] Selection of using this special input (ON / OFF switch). Measuring type[unit] :] Setting of the physical sensor (Up to now only PT100 possible).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 22/149 -

Service Manual [

[ [0416. [

[0417.

[0418. [

[0419.

[

Full scale :] Adjustment of the full scale point (for calibration only; the range of the input is depending on the hardware and not changeable with this parameter; for other ranges please contact the manufacturer). Zero scale :] Adjustment of the zero scale point (for calibration only; the range of the input is depending on the hardware and not changeable with this parameter). 1. Limit :] Setting of the first limit event of this analog input. If the actual measured value is higher or lower than this limit, event 0416 will be set. 1. Limit high/low :] Selection of high or low level limit for Parameter 0416. In case of high limit, the actual measured value has to exceed the limit of Parameter 0416. In case of low limit, the actual value has to fall below the limit to set the corresponding event. 1. Limit delay time :] If Event 0416 is active and this delay time is passed, the Event 0417 will be activated as long as the actual value falls below the limit of Parameter 0416. Please use this parameter for the alarm controller. 2. Limit :] Setting of the first limit event of this analog input. If the actual measured value is higher or lower than this limit, event 0418 will be set. 2. Limit high/low :] Selection of high or low level limit for Parameter 0418. In case of high limit, the actual measured value has to exceed the limit of Parameter 0418. In case of low limit, the actual value has to fall below the limit to set the corresponding event. 2. Limit delay time :] If Event 0418 is active and this delay time is passed, the Event 0419 will be activated as long as the actual value falls below the limit of Parameter 0418. Please use this parameter for the alarm controller. Hysteresis :] Setting of the hysteresis for both limits. Number of analogue input

Event number Event number Event number Event number 1. Limit 1. Limit delay 2. Limit 2. Limit delay time time

05 (PT100-1) 06 (PT100-2) 07 (PT100-3) 08 (PT100-4) 09 (PT100-5) 10 (PT100-6) 11 (PT100-7) 12 (PT100-8) 13 (PT100-9) 14 (PT100-10) 15 (PT100-11) 16 (PT100-12) 17 (PT100-13) 18 (PT100-14) 19 (PT100-15) 20 (PT100-16)

0416 0420 0424 0428 0432 0436 0440 0444 0448 0452 0456 0460 0464 0468 0472 0476

0417 0421 0425 0429 0433 0437 0441 0445 0449 0453 0457 0461 0465 0469 0473 0477

0418 0422 0426 0430 0434 0438 0442 0446 0450 0454 0458 0462 0466 0470 0474 0478

0419 0423 0427 0431 0435 0439 0443 0447 0451 0455 0459 0463 0467 0471 0475 0479

Figure: Event numbers for the temperature measuring inputs

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 23/149 -

Service Manual 2.6. Binary Inputs HIMAP provides with its basic unit 14 function inputs for user defined applications. In combination with an external board, the number of function inputs can be extended. HIMAP Parameter: BINARY INPUT EVENT – Select:

500

Setting range:

FUNC.10 INPUT –X2.3/30 0500. 0501.

– Condition : NORM.OPEN – Time delay: 0,0 sec BACK

NORM.OPEN … N.C.+W.F. 0,0…999,9 sec

EXIT

Figure: Binary Inputs-1

[ - Select] Selects an binary input. [ - Condition] Condition of the input. If the input is active event 500 will be set. Conditions: • NORM.OPEN: the input is normally open. • NORM.CLSD: the input is normally closed. • N.O.+W.F.: the input is normally open and the wirefault supervision is active. • N.C.+W.F.: the input is normally closed and the wirefault supervision is active. Note: the wirefault supervision is only available for the function inputs 10-23. Every input has a unique wirefault event number (3321-3334). These events can be used for alarming. Refer to the event list in the Appendix A2. [ - Time delay] If the input is active and the delay is passed event 501 will be set. The following shows the function inputs which can be used. All function inputs have the same parameters with exception of the event and terminal numbers. Function Input

Event number

Event number Plug / after delay Terminals

10 11 12 13 14 15 16 17 18 19 20 21 22 23

500 502 504 506 508 510 512 514 516 518 520 522 524 526

501 503 505 507 509 511 513 515 517 519 521 523 525 527

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

X2.3/30 X2.3/31 X2.3/32 X2.3/33 X2.3/34 X2.3/35 X2.3/36 X2.3/37 X2.3/38 X2.3/39 X2.3/40 X2.3/41 X2.3/42 X2.3/43

- 24/149 -

Service Manual 2.7. Analogous Outputs The basic unit of HIMAPprovides four analogous outputs. For each output, parameters for the function, the physical range and calibration are available.

Setting range:

ANALOGOUS OUTPUTS 0600. 0601. 0602. 0603. 0604. 0605. 0606. 0607. 0608. 0609. 0610. 0611. 0612. 0613. 0614. 0615. 0616. 0617. 0618. 0619.

CUR-OUT 1

CUR-OUT 2 ´ CUR-OUT 3

CUR-OUT 4

– – – – – – – – – – – – – – – –

function : U12-VOLT. range : 4-20 mA zero scale: 0,0 % full scale: 100,0 % adjust : 100,0 % function : U-average range : 4-20 mA zero scale: 0,0 mA full scale: 100,0 % adjust : 100,0 % function :I1-current range : 4-20 mA zero scale: 0,0 mA full scale: 100,0 % adjust : 100,0 % function :I-GND1-cur range : 4-20 mA zero scale: 0,0 mA full scale: 100,0 % adjust : 100,0 % BACK

↑ ↓

See func.selec.table OFF / 0-20mA / 4-20mA 0,0…999,9 % 0,0…999,9 % 0,0…999,9 % See func.selec.table OFF / 0-20mA / 4-20mA 0,0…999,9 % 0,0…999,9 % 0,0…999,9 % See func.selec.table OFF / 0-20mA / 4-20mA 0,0…999,9 % 0,0…999,9 % 0,0…999,9 % See func.selec.table OFF / 0-20mA / 4-20mA 0,0…999,9 % 0,0…999,9 % 0,0…999,9 %

EXIT

Figure: Analogous Outputs-1

The analogous outputs can be used to convert measuring and processed values to analogous outputs such as 0..20mA or 4..20mA. The following table shows the selection possibilities of analogous output function Parameters (600,605,610 & 615): Parameter symbol

Description

OFF I1-current I2-current I3-current I-average U12-Volt U23-Volt U31-Volt U-average U-Bus1 av. U-Bus2 av. reserved I-GND1-Cur I-GND2-Cur reserved UGND1-Volt. UGND2-Volt

The output is disabled Actual current of phase 1. Actual current of phase 2. Actual current of phase 3. Average current of phase 1-3. Line voltage U1 to U2. Line voltage U2 to U3. Line voltage U3 to U1. Average voltage of all line voltages. Average bus1 voltage of all line voltages. Average bus2 voltage of all line voltages.

HYUNDAI HIMAP

Ground current 1 Ground current 2 Ground voltage 1 Ground voltage 2 HIMAP_ServiceManual_E.doc

- 25/149 -

Service Manual Active power Reactive power HIMAP XG/BCG only: relative net power HIMAP XG/BCG only: the relative net spinning reserve Active ground power of Ignd1 and Ugnd1 Active ground power of Ignd2 and Ugnd2 Frequency of feeder system Frequency of bus 1 system Frequency of bus 2 system Power factor of feeder system Voltage U1 to ground Voltage U2 to ground Voltage U3 to ground HIMAP XG/BCG only: corresponds to ANSI 15 - speed matching device HIMAP XG/BCG only: corresponds to ANSI 15 - voltage matching device MDEC speed (nominal = 3000 rpm) MDEC injection quantity (nominal = 100%) MDEC Temperature lube oil (nominal = 100 °C) MDEC Temperature coolant (nominal = 100 °C) MDEC Temperature charge air (nominal = 100 °C) MDEC Temperature fuel (nominal = 100 °C) MDEC Temperature coolant intercooler (nominal = 100 °C) MDEC Pressure lube oil (nominal = 10.0 bar) MDEC Pressure charge air (nominal = 5.0 bar) MDEC Pressure fuel (nominal = 15.0 bar) MDEC Pressure fuel rail (nominal = 1600 bar) HIMAP XG/BCG only: the diesel speed in rpm

Pw Pq Net load SPIreserve Pw-GND1 Pw-GND2 Frequency Bus1-Freq. Bus2-Freq PF pow.fac. U1-Volt U2-Volt U3-Volt Speed ctrl Volt. ctrl MTU speed MTU inject MTU T-lube MTU T-cool MTU T-air MTU T-fuel MTU T-intc MTU P-lube MTU P-air MTU P-fuel MTU Prfuel Speed rpm

Each analogous output provides five parameters for adjustment. The following parameters refer to analogous output 1, which are representative for all analogous outputs. [0600. CUR-OUT 1 – function :] Output selection for analogous output number 1 (X2.4 49,50) [0601. - range :] Selection of the output range: 0-20mA, 4-20mA or OFF [0602. - zero scale :] The zero point adustment (0 or 4 mA = #.# %). [0603. - full scale :] Full scale adjustment (20 mA = #.# %). [0604. - adjust :] Total linear scale adjustment (calibration). Terminals of analogous outputs: Anal. output 1 2 3 4

Plug - Terminals X2.4 - 49, 50 (+) X2.4 - 49, 51 (+) X2.4 - 49, 52 (+) X2.4 - 49, 53 (+)

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 26/149 -

Service Manual 2.8. Binary Outputs The basic unit of HIMAP provides 12 binary outputs. The outputs are organized as follows: No. 1 2 3 4 5-12 2.8.1.

Output name Shunt #1 Shunt #2 Lockout relay CB synchron ON Function 1--8

Event number 700 701 702 & 703 704 & 705 706-720

Description used for breaker trip events special relay for lock-out purpose used for synchronizing unit free programmable outputs

Shunt #1 output

BINARY OUTPUT EVENT – Select: Events: 01:1402 02:1405 03:1408 04: 0 05: 0 06: 0 07: 0 08: 0 09: 0 10: 0

700

Shunt #1 -X2.1/18,19

OFF: If event of PM-switch is active, power management will be switched off. OFF -> ON: If event of PM-switch is active, power management will be switched on. [0902. START – check limits :] Checking single or average start limits. This parameter is valid for [0903], [0905] and [0909]. All limits can be disabled by setting them to zero. SINGLE: When passing limit parameters [0903], [0905] or [0909] the start order will be given depending on the load / current of each diesel engine. If a generator passes the limit while the others do not, a start order will be given. AVERAGE: Start order given if average load / current of Parameter [0903], [0905] or [0909] is passed. Average load / current means the average of load / current of all diesel engines running on the mains in one net. [0903. – 1. load limit :] First start limit for load-depending start of an additional diesel engine. [0904. – delay :] Delay time for first start limit Parameter [0903]. [0905. – 2.load limit :] Second start limit for load-depending start of an additional diesel engine. [0906. – delay :] Delay time for second start limit Parameter [0905]. [0907. – low frequency:] Passage of a low frequency limit also starts a diesel engine. Coordinate with Parameters [2007] and [2010]. [0908. – delay :] Delay time for low frequency start limit Parameter [0907]. [0909. – high current :] Start limit for current-depending start of an additional diesel engine. [0910. – delay :] Delay time for current start limit Parameter [0909]. [0911. STOP – with priority :] Sequence for stop order. LOW: Load-depending stop works in a sequence so that the aggregate with the lowest priority will be stopped first. HIGH:: Load-depending stop works in a sequence so that the aggregate with the highest priority will be stopped first. [0912. – block by event :] By activating this event on any device in one net, load-depending stop of the diesel engines can be blocked (this affects also the second P.M. function (P2430-2449). [0913. – remaining load :] Stop limit for load-depending stop of operating diesel engine. The entered percentage limit is the load value remaining on the mains after disconnecting the diesel engine. [0914. – remaining curr.:] Stop limit for current-depending stop of operating diesel engine. The entered percentage limit is the current value remaining on the mains after disconnecting the diesel engine. If zero is setted, the limitcheck will be disabled. HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 40/149 -

Service Manual [0915.

– delay :] Delay time for current and load stop limit Parameters [0913] and [0914]. Note that both conditions must be fullfilled to start the delay. If only load stop is to be used, the current limit (914) must be set to zero. Both limits can be disabled by setting them to zero, if PMstop is not to be used. Current stop [914] is only available in connection with load stop, never alone. [0916. Stop without runn. down] If this parameter is set to “YES”, the stopped gen. will only open the CB (after load reduction), and than remain running. [0917. Block own start by event] By activating this event, the start of the own diesel engine through the power management system can be blocked. The blocking does not affect other start sources (e.g. blackout, start next…). A message will be displayed on the power management page if the blocking is active.

[2430. LOAD RANGES – by event] Event switch for the second power management function. This switch affects only the parameters 2431-2449. All devices in one net must have this switch enabled for activation! [2431. – change to upper range] If the actual net power changes from one range to a higher range, the higher range will be taken as the valid range after this delay time has passed. [2432. – change to lower range] If the actual net power changes from one range to a lower range, the lower range will be taken as the valid range after this delay time has passed. [2432. – load range hysteresis] This hysteresis is valid if the actual net power changes from one range to a higher range. The power must fall below this hysteresis in order to return to the previous (lower) range. [2434. – 1. load range] [2435. – priority] …… [2448. – 8. load range] [2449. – priority] With this parameters up to eight ranges can be defined. Each range starts at the previous range and ends at the setted kW value. For every range up to five gen. (identified in the net by the priorities) can be assigned, which should be connected to the bus bar. Note: the starting and stopping will begin when a new range becomes valid (after the delays P2431 or 2432 are passed). The system will first start all the needed generators. After all the needed generators are connected to the bus bar, the system will begin to stop the unnecessary generators. If one generator needed for the actual load range is not available (in MANUAL and stopped), the system will search for another generator with the same nominal power. If the search is without result, the next standby generator will be started. The stopping is blocked in this case. The system will start or stop only generators which priority is defined in one of the load ranges (parameters 2435-2449). The stopping is automatically blocked if the PM stop is blocked (see P912) or if a “big consumer request” is active in the net (see 2.10.7.). If parameter 2430 is setted to a value greater than zero, an supervision becomes active. This supervision checks if all the gen. defined within the parameters 2435-2449 are available (in AUTOM.). In this case event 2430 will be active. Event 2431 will be active if P2430 is set (to a value greater zero) and the gen. needed for the actual range are all in AUTOM. This events can be used for alarming or to control processes (e.g. to switch to the classical PM if gen. are not available).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 41/149 -

Service Manual 2.10.3. Load sharing The load sharing parameter includes the settings that regulate the load within the bus bar section. The load sharing regulator works as a three-point controller. After a certain break time, the difference between the load set point and the actual measured load value will be calculated. With this load difference the pulse time for speed higher and lower will be calculated. The set point in the symmetrical load sharing mode for the load regulator is the average net load. The set point in the asymmetrical load sharing mode is Parameter [0934]). If the load difference (set point to actual load) is lower then the dead band, the load-sharing regulator is blocked.

0925. 0926. 0927. 0928. 0929. 0930. 0931. 0932. 0933. 0934. 0935. 0936. 0937. 0938. 0939. 0940. 0941. 0942. 0943.

LOAD SHARING SYM. – switch by event: 0 – characteristic : ON->OFF – break time : 3.0 sec - pulse time : 3.0 sec – deadband : 2.0 % – higher event – lower event ASYM. – switch by event: 501 - characteristic : ON->OFF – setpoint : 80 % – analog input : OFF – range minimum : 40 % – range maximum : 90 % – next attempt : 60 sec Allowed load difference: 20.0 % – delay : 60 sec REGUL.- switch by event: 0 – 2. break time : 0.0 sec – 2. pulse time : 0.0 sec BACK

Setting range: 0…9999 (Event number) ON->OFF/OFF->ON 0.0…999.9 0.0…999.9 0.0…999.9 --- (Event reminder) --- (Event reminder) 0…9999 (Event number) ON->OFF/OFF->ON 0…9999 OFF / CURR.1 – CURR.4 0…9999 0…9999 0…9999 0.0…999.9 0…9999 0…9999 (Event number) 0.0…999.9 0.0…999.9

EXIT

[0925. SYM. – switch by event :] The function for balancing the load through the load-sharing regulator can be switched on and off by this event. All devices in one net must have this switch enabled for activation! [0926. – characteristic :] Switch characteristic of load-sharing ON/OFF switch Parameter [0925]: ON -> OFF: If event of load-sharing switch is active, load-sharing function will be switched off. OFF -> ON: If event of load-sharing switch is active, load-sharing function will be switched on. [0927.

– break time :] Break time for the load-sharing regulator. The break time is the interval or cycle time for the regulator. At the beginning of the break time, the pulse duration for the speed control will be calculated and started. [0928. –pulse time :] Pulse time of the load-sharing regulator. The pulse time depends on the difference between the set point and the actual measured load of the generator. The speed control

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 42/149 -

Service Manual Event [0930] or [0931] will be activated as long as the pulse time is running. The pulse time will be calculated as follows: Pulse time = load difference* Parameter [0928] / 100 Set this parameter to the max. time the engine needs to reach nominal speed. [0929.

– deadband :] Dead band of the regulator: If the load difference (set point to actual measured load of the generator) is under the dead-band limit, the regulator is idle.

[0930.

–higher event :] Event for speed higher control. This event will be set by the system in case the pulse time of the regulator is active in combination with the demand to increase the speed. This event can be used to activate a function output. [0931. – lower event :] Event for speed lower control. This event will be set by the system in case the pulse time of the regulator is active in combination with the demand to decrease the speed. This event can be used to activate a function output. [0932. AYM. – switch by event :] Special application for load-sharing regulator. ON/OFF switch of asymmetrical load sharing function. The function for this asymmetrical mode for the load-sharing regulator can be switched on and off by setting this event. In the asymmetrical load sharing mode, the regulator uses a fixed-load set point Parameter [0934], instead of the average net load. The asymmetrical load mode is allowed, if a minimum of two generator sets feeding the bus bar and the load limits of Parameters [0936] and [0937] are not exceeded. In case of mains parallel operation Parameter [0190], asymmetrical load-sharing mode is always allowed. [0933. – characteristic :] Switch characteristic of asymmetrical load-sharing ON/OFF switch Parameter [0932]: ON -> OFF: If the event of the asymmetrical load-sharing switch set in Parameter [0932] is active, asymmetrical load-sharing function will be switched off. OFF -> ON: If the event of the asymmetrical load-sharing switch set in Parameter [0932] is active, asymmetrical load-sharing function will be switched on. [0934. – setpoint :] Set point for the asymmetrical load sharing regulator. The range for this set point is 0--100% of the nominal load of the generator. This parameter can be changed also on the load page (Asymm. load). [0935. –analog input :] Analogous setpoint for the asymmetrical load-sharing regulator. The set point for asymmetrical load limit can be set by the analogous input. One of the four analogous inputs of the basic unit can be used to modify the setpoint for the asymmetrical load sharing (refer to chapter 2.5. to enable the selected analog input). Note: If this parameter is enabled the setpoint of parameter 934 is inactive. [0936. [0937.

–range minimum :] –range maximum :] Minimum and maximum limit for the asymmetrical load-sharing mode. If the asymmetrical load-sharing is switched on (Parameters [0932] and [0933]) and if the load of the other generators feeding the same bus bar is within the minimum and maximum range limit, then the asymmetric mode will be allowed.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 43/149 -

Service Manual [0938.

– next attempt :] If the asymmetrical load-sharing mode is active and one of the other generators that is feeding the same bus bar exceeds the limits of Parameters [0936] and [0937], then the load-sharing mode is switching from asymmetric to symmetrical load-sharing mode. After the delay time set in Parameter [0938 ], the load-sharing regulator tries to switch again into the asymmetrical load-sharing mode.

[0939. Allowed load difference :] If the difference from the set point to the measured generator load exceeds this limit, then Event [0939] will be activated. (DNV load sharing supervision rule). [0940. – delay :] Delay time for Parameter [0939]. Use this event [0940] to activate an alarm channel. [0941. REGUL. – switch by event] With this function the load sharing regulator can be switched to another break and pulse time. This can be used to change the regulator characteristic for different operations. [0942. – 2. break time] This second break time is valid for the regulator if the event from parameter 941 is active (Refer to parameter 927). [0943. – 2. pulse time] This second pulse time is valid for the regulator if the event from parameter 941 is active (Refer to parameter 928).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 44/149 -

Service Manual 2.10.4. Frequency controller The frequency controller parameter contains the settings for regulating the frequency within the bus bar section. The frequency controller works as a three-point controller. After a certain break time, the difference between the frequency set point and the actual measured frequency will be calculated. With this frequency difference, the pulse time for the speed control will be calculated. The set point for the frequency controller will be calculated from the frequency-load static given by the parameter: idle and full-load frequency. If the frequency difference (set point to actual measured frequency) is lower then the dead-band limit, then the frequency controller will be blocked. FREQUENCY CONTROLLER 0945. – switch by event: 0946. – characteristic : 0947. – idle speed : 0948. - full load : 0949. – break time : 0950. – pulse time : 0951. – deadband : 0952. – higher event 0953. – lower event 0954.RANGE – maximum : 0955. – minimum : 0956.REGUL. - switch by event: 0957. – 2. break time : 2420. – 2. pulse time : 2421.REMOTE – higher event : 2422. – lower event : BACK

0 ON->OFF 61.00 Hz 59.00 Hz 20.0 sec 100.0 sec 0.2 % 58.00 62.00 0 0.0 0.0 0 0

Hz Hz sec sec

Setting range: 0…9999 (Event number) ON->OFF/OFF->ON 0.00…99.99 0.00…99.99 0.0…999.9 0.0…999.9 0.0…999.9 --- (Event reminder) --- (Event reminder) 0.00…99.99 0.00…99.99 0…9999 (Event number) 0.0…999.9 0.0…999.9 0…9999 (Event number) 0…9999 (Event number)

EXIT

[0945.

– switch by event :] The function for the frequency control can be switched on and off by activating this event. All devices in one net must have this switch enabled for activation! [0946. – characteristic :] Switch characteristic of frequency control ON/OFF switch Parameter [0945]: ON -> OFF: If event of Parameter [0945] is activated, the frequency controller will be switched off. OFF -> ON: If event of Parameter [0945] is activated, the frequency controller will be switched on. [0947. [0948.

– idle speed :] – full load :] Set point for frequency control. Either a constant frequency (for this, enter the same value in both Parameters [0947] and [0948]) or a load-depending speed droop can be entered in accordance with the speed controller of the diesel engine.

[0949.

– break time :] Break time for the frequency controller. The break time is the interval or cycle time for the controller. At the beginning of the break time, the pulse duration for the speed control will be calculated and started.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 45/149 -

Service Manual

[0950.

–pulse time :] Pulse time of the frequency controller. The pulse time depends on the difference between the set point and the actual measured frequency of the generator. The speed control Events [0952] and [0953] will be activated as long as the pulse time is running. The pulse time will be calculated as follows: Pulse time = frequency difference * Parameter [0950] / 100. Set this parameter to the max. time the engine needs to reach nominal speed.

[0951.

– deadband :] Dead band of the controller. If the frequency difference (set point to actual measured frequency the generator) is under the dead-band limit, the controller will be blocked.

[0952.

–higher event :] Event for speed higher control. This event will be set when the pulse time of the regulator is active in combination with the demand to increase the speed. Use this event to activate a function output. [0953. – lower event :] Event for speed lower control. This event will be set when the pulse time of the regulator is active in combination with the demand to decrease the speed. Use this event to activate a function output. [0954. RANGE –maximum :] [0955. – minimum :] Operating range for frequency controller, load sharing and load reduction. If the frequency of the bus bar exceeds the frequency range given by these parameters, then these functions will be blocked. [0956. REGUL. – switch by event] With this function the frequency regulator can be switched to another break and pulse time. This can be used to change the regulator characteristic for different operations. [0957. – 2. break time] This second break time is valid for the regulator if the event from parameter 956 is active (Refer to parameter 949). [2420. – 2. pulse time] This second pulse time is valid for the regulator if the event from parameter 956 is active (Refer to parameter 950). [2421. REMOTE – higher event] [2422. – lower event] Over this events the speed can be remotely controlled (e.g. over binary inputs, or communication).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 46/149 -

Service Manual 2.10.5. Voltage regulator The voltage regulator parameter contains the settings for regulating the voltage within the bus bar section. The voltage regulator works as a three-point controller. After a certain break time the difference between the voltage set point and the actual measured voltage will be calculated. With this voltage difference, the pulse time for the voltage regulator will be calculated. If the voltage difference (set point to actual measured voltage) is lower then the dead-band limit, then the voltage regulator will be blocked. VOLTAGE REGULATOR 0958. – switch by event: 1000 0959. – characteristic : ON->OFF 0960. – setpoint : 100.0 % 0961. – break time : 4.0 sec 0962. – pulse time : 3.0 sec 0963. – deadband : 2.0 % 0964. – higher event 0965. – lower event 0966.REMOTE – higher event : 0 0967. – lower event : 0 BACK

Setting range: 0…9999 (event number) ON->OFF/OFF->ON 0.0…999.9 0.0…999.9 0.0…999.9 0.0…999.9 0…9999 (event number) 0…9999 (event number)

EXIT

[0958.

– switch by event :] The function for the voltage control can be switched on and off by activating this event. All devices in one net must have this switch enabled for activation! [0959. – characteristic :] Switch characteristic of voltage regulator ON/OFF switch Parameter [0958]: ON -> OFF: If event of Parameter [0958] is activated, the voltage regulator will be switched off. OFF -> ON: If event of Parameter [0958] is activated, the voltage regulator will be switched on. [0960.

– setpoint :] Set point for voltage regulator. [0961. – break time :] Break time for the voltage regulator. The break time is the interval time for the controller. At the beginning of the break time, the pulse duration for the voltage control will be calculated and started. [0962. –pulse time :] Pulse time of the voltage regulator. The pulse time depends on the difference between the set point and the actual measured voltage of the generator. The voltage control Events [0964] and [0965] will be activated as long as the pulse time is running. The pulse time will be calculated as follows: Pulse time = voltage difference * Parameter [0962] / 100. Set this parameter to the max. time the generator needs to reach the setpoint.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 47/149 -

Service Manual [0963.

– deadband :] Dead band of the controller. If the voltage difference (set point to actual measured generator voltage) is under the dead-band limit, the controller will be blocked.

[0964.

–higher event :] Event for voltage higher control. This event will be set regulator is active in combination with the demand to generator. This event is used to activate a function output. [0965. – lower event :] Event for voltage lower control. This event will be set regulator is active in combination with the demand to generator. This event is used to activate a function output.

when the pulse time of the increase the voltage of the when the pulse time of the decrease the voltage of the

[0966. REMOTE – higher event] [0967. – lower event] Over this events the voltage can be remotely controlled (e.g. over binary inputs, or communication).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 48/149 -

Service Manual 2.10.6. Power factor controller The parameters of the power factor contain the settings for balancing the reactive power load within the bus bar section. The power factor controller works as a three-point controller. After a certain break time, the difference between the power factor set point and the actual measured power factor will be calculated. With this power factor difference, the pulse time for voltage higher and lower control will be calculated. The set point for the power factor regulator is the average net reactive power when the generators are operating in symmetrical load-sharing mode. When the generators are in the asymmetrical load-sharing mode, the set point for the power factor regulation is fixed by the setting of Parameter [0979]. If the power difference (set point to actual power factor) is lower then the dead band, then power factor control is blocked.

0970. 0971. 0972. 0973. 0974. 0975. 0976. 0977. 0978. 0979. 0980.

POWER FACTOR CONTROLLER – switch by event: 0 – characteristic : ON->OFF – break time : 5.0 sec - pulse time : 3.0 sec – deadband : 2.0 % – higher event – lower event ASYM. – switch by event: 0 – characteristic : ON->OFF – setpoint : 0.80 cap Controller condition : CAP BACK

Setting range: 0…9999 ON->OFF/OFF->ON 0…9999 0…9999 0.0…999.9 0…9999 ON->OFF/OFF->ON 0.00…9.99 CAP / IND

EXIT

[0970.

– switch by event :] ON/OFF switch of power factor control function. All devices in one net must have this switch enabled for activation! [0971. – characteristic :] Switch characteristic of power factor control ON/OFF switch Parameter [0970]: ON -> OFF: If the switch event of Parameter [0970] turns to active, power factor control function will be switched off. OFF -> ON: If the switch event of power factor control turns to active, power factor control function will be switched on.

[0972.

– break time :] Break time for the power factor controller. The break time is the interval time for the controller. At the beginning of the break time, the pulse duration for the power factor control will be calculated and started.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 49/149 -

Service Manual [0973.

– pulse time :] Pulse time of the power factor controller. The pulse time depends on the difference between the set point and the actual measured power factor of the generator. The voltage Control Events [0975] and [0976] will be activated as long as the pulse time is running. Voltage Control Event [0975] is to increase the voltage (increase the ind. load); and Event [0976], to decrease the voltage (increase the capacitive load). The pulse time will be calculated as follows: Pulse time = power factor difference * Parameter [0973] / 100. Set this parameter to the max. time the generator needs to reach the nominal voltage.

[0974.

– deadband :] Dead band of the controller. If the power factor difference (set point to actual measured power factor of the generator) is under the dead-band limit, the controller will be blocked.

[0975.

– higher event] Event for voltage higher control. This event will be set when the pulse time of the controller is active in combination with the demand to increase the voltage. This event should be used to activate a function output. See parameter 980 to invert this event.

[0976.

– lower event] Event for voltage lower control. This event will be set when the pulse time of the controller is active in combination with the demand to decrease the voltage. This event should be used to activate a function output. See parameter 980 to invert this event.

[0977. AYM. – switch by event:] Special application for power factor controller. ON/OFF switch of asymmetrical power factor function. The function for this asymmetrical mode for the power factor controller can be switched on and off by activating this event. In the asymmetrical mode the power factor controller uses a fixed power factor set point Parameter [0979], instead of the average power factor of the net. The asymmetrical PF mode is allowed if at minimum two generator sets feed the bus bar. [0978.

– characteristic :] Switch characteristic of asymmetrical power factor ON/OFF switch Parameter [0977]: ON -> OFF: If event of asymmetrical power factor turns to active, asymmetrical power factor function will be switched off. OFF -> ON: If event of asymmetrical power factor turns to active, asymmetrical load power factor function will be switched on.

[0979.

– setpoint :] Set point for the asymmetrical power factor controller. The range for this set point is 0--100, which is equal to a power factor of 0.00--1.00 (ind). This parameter can be changed also on the load page (Asymm. PF).

[0980. Controller condition] This parameter defines the regulator direction of the power factor controller (both the symmetrical and the asymmetrical). It simply inverts the output events 975 and 976.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 50/149 -

Service Manual 2.10.7. Big consumer request (BCR) Within the power management function a load controller is available to manage big consumer requests. The load controller parameters contain the settings for the request and the control and the release of big consumers within the same bus bar section. A maximum of four big consumers are managed by one device. After the request of a big consumer, the system checks the spinning reserve (valid load) of the corresponding net. Depending on the value of the spinning reserve, the load controller will start another diesel aggregate or release the big consumer directly. As long as the big consumer request is active, load depending stop of the power management will be blocked.

0984. 0985. 0986. 0987. 0988. 0989. 0990. 0991. 0992. 0993. 0994. 0995. 0996. 0997. 0998. 0999.

BIG CONSUMER REQUEST (BCR) REQUEST 1 by event : 511 – requested load : 655 – analog feedback: OFF – reserved : REQUEST 2 by event : 513 – requested load : 850 – analog feedback: OFF – reserved : REQUEST 3 by event : 0 – requested load : 0 – analog feedback: OFF – reserved : REQUEST 4 by event : 0 – requested load : 0 – analog feedback: OFF – reserved : BACK

kW

Setting range: 0…9999 0…99999 OFF / CURR.1-4

kW

0…9999 0…99999 OFF / CURR.1-4

kW

0…9999 0…99999 OFF / CURR.1-4

kW

0…9999 0…99999 OFF / CURR.1-4

EXIT

The load controller of the system operates in the following way. After a consumer request, the load controller evaluates the load of the bus bar section, in which the consumer has been requested. Depending on the load situation, the load controller will release the big consumer directly or after it has started one or more engines. The following parameter description refers to Big Consumer Request 1, since each consumer requests (1...4) or to have similar parameters with the exception of the event numbers. [0984. REQUEST 1 by event :] Request load-depending connection to Big Consumer 1. Select event number (normally a function input) and via it, enter request. The event must be active steadily until the big consumer has been switched on. Should the signal remain on at the input, diesel stop will be blocked. (Use for bow thruster operation.) [0985.

- requested load :] Enter power of Consumer 1. If there is sufficient reserve power, Event [0984] will be set without a delay. If there isn’t sufficient power, one or more diesel engines will be started. If after switching on the additional diesel engines, sufficient power becomes available, Event [0984] will be set after the load balancing delay time (set with Parameter [0189]). Event [0984] should be put on an output relay. If the power is not available, event 986 will be activated (for alarm).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 51/149 -

Service Manual [0986.

- analog feedback:] (future function: not prepared yet) Load state of big consumer during operation. Via an analogous input, the load state of the big consumer (actual load referring to nominal load) can be sent to the load controller. With this additional information, the load controller can reserve the required load at the bus bar. If the reserved load of the big consumer is higher than the valid load within the bas bar section, one or more engines will be started, if available. This additional function of the load controller works when the request event (Event [0984]) is active. Use one of the four analogous inputs of the basic unit of the system (CURR1…4). Example: If a 4…20mA input is selected, then an analogous signal of 4mA means that no power of the consumer is in use. 20mA means the total power of the consumer Parameter [0985] is in use.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 52/149 -

Service Manual 2.10.8. Blackout The blackout module offers a powerful supervisory system, which is capable of managing all emergency situations in one net.

0230. 0231. 0232. 0233. 0234. 0235. 0236. 0237. 0238. 0239. 0240. 0241. 0242. 0243. 0244. 0245. 0246.

BLACKOUT BUS 1 – blackout by : 0 – mains monitor : REDUNDANT – voltage limit: 40.0 % – start delay : 2.0 sec – start diesel : NEXT – stop enable by : 2957 – stop delay : 0 sec BUS 2 – blackout by : 0 – mains monitor : ON – voltage limit: 40.0 % – start delay : 2.0 sec - stop enable by : 2957 – stop delay : 0 sec STOP BUS 1,2 blocked by: 522 STOP preliminary output START BUS 1 blocked by : 0 START BUS 2 blocked by : 0 BACK

Setting range: 0…9999 event OFF/SINGLE/REDUNDANT 0.0…999.9 0.0…999.9 ALL/NEXT/OWN/SEQUENCE 0…9999 event 0…9999 0…9999 event OFF / ON 0.0…999.9 0.0…999.9 0…9999 event 0…9999 0…9999 event 0…9999 event 0…9999 event

EXIT

[0230. BUS 1 – blackout by] Blackout 1 will be recognized if this event is active (e.g. function input). [0231. – mains monitor] Blackout recognition via mains monitor. The mains monitor supervises the Bus 1 voltage when this parameter is set to SINGLE or REDUNDANT. Redundancy means that all devices in one net must recognize the Bus 1 voltage limit. [0232. – voltage limit] If Parameter [0231] is enabled and one of the 3 lines of Bus 1 voltage is lower than the limit of Parameter [0232], then the mains monitor condition is fulfilled and Event [0232] will be set. [0233. – start delay] The delay will start if the blackout event condition [0230] or the mains monitor condition [0232] occurs. If the delay is passed, blackout Bus 1 start condition is fulfilled and Event [0233] will be set. [0234. – start diesel] The starting mode can be set by this parameter. All devices in one net should have this parameter set to the same value. There are several possibilities according to the mode: • ALL: all standby diesels will start and close their CBs. • NEXT: the first standby diesel will start. • OWN : the own diesel (if in standby) will start. • SEQUENCE: all standby diesels will start, but only the generator with the highest priority will close its CB. After that, the other generator will cancel the startphase and remain running. If the first generator fails to close its CB within 3 seconds, the generator with the next highest priority has the permission to close its CB.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 53/149 -

Service Manual Note: if more than one generator is started (by any source) and no CB is closed in the net, a special interlock function becomes active. This function assures that only one generator at the same time has the permission to close the CB. The permission time is limited to 3 seconds. The other generator will remain waiting with blocked synchron -Events [1023],[1053],[1083]. [0235. [0236.

– stop enable by] – stop delay] The stop delay gets activated if Parameter [0235] is activated, the diesel is running, and Blackout 1 is inactive. If the delay is passed, and if Automatic has been selected, and if Event [243] is inactive, then the “own” diesel will be stopped.

[0237. BUS 2 – blackout by] Blackout 2 will be recognized if this event is active (e.g. function input). [0238. – mains monitor] Blackout recognition via mains monitor. The mains monitor supervises the Bus 2 voltage if Parameter [0238] is switched to ON. [0239. – voltage limit] If Parameter [0231] is activated and one of the three lines of Bus 2 voltage is lower than the limit of Parameter [0239], then the mains monitor condition will be fulfilled and Event [0239] will be set. [0240. – start delay] The delay will start if the Blackout Event Condition [0237] or the Mains Monitor Condition [0239] occurs. If the delay is over, Event [0240] will be set and the device will start the “own” diesel (if in standby). [0241. [0242.

– stop enable by] – stop delay] The stop delay gets activated if Event [0241] is activated, the diesel is running, and if Blackout 2 is inactive. If the delay is over and Automatic and [243] is inactive, the device will stop the “own” diesel.

[0243. STOP BUS 1,2 blocked by] The stopping of Blackout 1 or 2 can be blocked with this event. [0244. STOP preliminary output] The Event [0244] will be activated if the Delay [0236] or [0242] is passed and the stop is blocked by Event [0243] or manual mode. [0245. START BUS 1 blocked by] The starting of Blackout 1 can be blocked with this event. [0246. START BUS 2 blocked by] The starting of Blackout 2 can be blocked with this event. Note: For an automatic stop after blackout, it is advisable to use the Event [2957] (blackout start source) on Parameter [0235] or [0241], because the Event [2957] will be set on blackout start and will remain active until the engine is stopped by any source. For details related to the blackout function, refer to the logic on the next page.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 54/149 -

Service Manual

P[234]: OWN P[230]: by event

AUTOM.

E[233]

P[231]: SINGLE / REDUNDANT

START OWN

&

≥1 &

P[232]:

E[245] (start blocked by)

&

Limit reached

1

All net nodes

P[234]: ALL / NEXT / SEQUENCE

& CAN 1 - Bus

P[234]: NEXT

&

START NEXT STANDBY

&

START ALL STANDBYS

One node by P[230] All nodes with REDUNDANT: Limit reached One node with SINGLE limit

Bus 1

Master

≥1

P[234]: ALL/SEQUENCE

P[237]: by event E[240]

≥1

P[238]: ON P[239]:

&

AUTOM.

Limit reached

START OWN

E[246] (start blocked by)

2

Bus 2

&

E[235] (stop enable by) AUTOM.

Engine running

P[236]

&

P[234]: OWN

&

1

& ≥1

STOP OWN

≥1

P[234]: ALL/NEXT No net node with Blackout 1

&

≥1

Preliminary Output event

E[243] (stop blocked by) E[241] (stop enable by) Engine running

Stop 1/2

2

E 244

P[242]

&

& AUTOM.

Figure: Blackout logic

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 55/149 -

Service Manual 2.10.9. Diesel control The diesel control unit of the system controls and supervises the starting and stopping sequences of the aggregate. The diesel control group contains the general parameter for speed adjustment and prelubricating interval.

0260. 0261. 0262. 0263. 0264. 0265. 0266. 0267. 0268. 0269. 0270. 0271. 0272. 0273.

DIESEL CONTROL Diesel control : ON SPEED – nominal : 1800 rpm – ignition : 15.0 % – running up : 85.0 % – overspeed : 150.0 % TACHO - input : OFF PICKUP - input : ON – impuls / rev. : 4 LIMITS – n max. diff. : 10.0 % – n high limit : 105.0 % – n low limit : 95.0 % PRELUBRICATE -pulsetime: 20 sec -breaktime: 500 sec Alarmblocking delay : 5.0 sec BACK

Setting range: OFF / ON 0…99999 0.0…999.9 0.0…999.9 0.0…999.9 OFF / CURR.1-4 OFF/ON/IGNITION 0…9999 0.0…999.9 0.0…999.9 0.0…999.9 0…99999 0…99999 0.0…999.9

EXIT

[0260. Diesel control :] Main switch for diesel control. By setting this parameter to ON, the diesel control functions (starting and stopping of the aggregate) will be activated. [0261. SPEED - nominal :] Nominal speed of the engine. The nominal speed of the engine should be given in revolutions per minute (RPM). [0262.

- ignition :] Ignition speed limit. The ignition speed limit will be used within the starting phase to switch off the start valve when the speed signal exceeds this limit.

[0263.

- running up :] Running-up speed limit. The running-up speed limit will be used within the starting phase to recognize that the engine is ready to take load.

[0264.

- overspeed :] Overspeed limit. The overspeed limit can be used for the alarm system. This event number should be used to activate an alarm channel. [0265. TACHO - input :] Analogous input for speed measurement. If a tacho generator gives the speed signal of the engine, one of the four analogous inputs of the basic unit should be used. The adjustment setting of the analogous inputs is done within the parameter group “analog inputs” (see 2.5.).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 56/149 -

Service Manual [0266. PICKUP - input :] [0267. - impuls /rev. :] Pick-up input for speed measurement. If a pick-up system provides the speed signal, set Parameter [0266] to ON. The number of impulses the pick-up system recognizes during one revolution has to be set with Parameter [0267]. If Parameter [0266] is set to IGNITION and at the pickup input is a high-signal, the device will take the limit from Parameter [0262] as the pickup speed value. [0268. LIMITS - n max. diff. :] The speed signal can be measured via three speed channels: tacho generator, pick-up system and via the generator voltage signal. Depending on which speed measuring system is active, the speed signals of the respective channel are compared among themselves. When the measured speed signal differs more than this limit, Event [0268] will be activated. Use this event number to activate a alarm (with delay). The following two parameters are speed limit events. These events will be activated when the speed signal fulfills the corresponding conditions. They can be used for alarming. [0269. - n high limit :] High speed limit. Event [0269] will be activated if the speed signal is higher then this limit. [0270. - n low limit :] Low speed limit. Event [0270] will be activated if the speed signal is lower then this limit. [0271. PRELUBRICATE -pulsetime:] [0272. -breaktime:] Prelubricating interval. For prelubricating the engine a pulse and a break time can be defined. During the prelubricating pulse time, Event [0271] is activated. This event has to be used to activate prelubrication via a function output. After the pulse time is passed, the break time will be started. Prelubrication works only in automatic mode. If the mode is started from manual to automatic, then prelubricating process will be introduced and started with the pulse time. The following events introduce the prelubrication process: [0273. Alarmblocking delay :] For diesel engines it is necessary to block some alarm channels which are related to engine warnings. The alarm blocking event 273 will be activated immediately when the speed signal falls below the ignition limit or the running down stopphase is active. If the speed signal reaches the ignition limit again, event 273 will be deactive after the setted delay is over.

E[262] n > ignition E[658]

P[273]

Running down time

≥1

E[273]

Figure: Alarmblocking logic

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 57/149 -

Service Manual 2.10.10. Starting phase The parameters of the starting phase contain the settings for control and supervision of the engine during the starting phase.

DIESEL STARTING PHASE 0630.PREGLOWING - max time : 4.0 0631. – shorten by: 0 0632.START VALVE – max trials: 3 0633. – fuel valve: NO 0634. – at RPM=0 : NO 0635. – max time : 5.0 0636. – BREAKTIME : 10.0 0637.RUNNING UP - max time *: 20.0 0638. – min volt. : 90.0 0639.READY TO TAKE LOAD time : 3.0 0640.SYNCHRONIZING max time *: 120.0 0641.Start next after 1 trial: NO 0642.Cancel if n > ignition : NO 0643.Cancel start by event : 0 BACK

sec

sec sec sec % sec sec

Setting range: 0.0…999.9 0…9999 0…9999 NO/YES NO/YES 0.0…999.9 0.0…999.9 0.0…999.9 0.0…999.9 0.0…999.9 0.0…999.9 NO/YES NO/YES 0…9999

EXIT

The starting sequence includes a maximum of five phases (See also diagram starting procedure of diesel aggregate). 1. Preglowing time The first phase of the start procedure is used to preglow the engine. This phase can be shortened by an event. 2. Start time After pre-glowing the engine, the start time is activated. During this period the start valve will be activated to run up the engine. This phase can be shortened by reaching the ignition speed. After reaching the ignition speed, the start valve will be reset. 3. Running-up time The running-up time is a supervision time. If during this period the engine can not reach the running-up speed and minimum voltage limit, a fail event will be issued. 4. Ready-to-take-load time After reaching running-up conditions, the ready-to-take-load phase will be started. During this time the engine has to stabilize the speed before starting synchronization; or in case of blackout, the engine has to take the load immediately. 5. Synchronizing period During the synchronizing time, the speed and voltage controller try to synchronize the diesel generator to the bus bar. In case both systems are synchronized, the circuit breaker on command will be issued.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 58/149 -

Service Manual [0630. PREGLOWING – max time :] Pre-glowing of the engine. This time defines the pre-glowing period of the engine. The starting phase of the aggregate begins with the pre-glowing period. After this period the starting valve will be set. If no pre-glowing time is required, the time should be set to zero. If the pre-glowing time is running, Event [0630] will be set by the system. This Event [0630] is used to activate a function output. [0631. – shorten by :] The pre-glowing period (See Parameter [0630]) can be interrupted by an event. If the event (defined with this parameter) is active, the pre-glowing period will be interrupted and the start valve will be activated. [0632. START VALVE – max trials :] Number of start attempts. If the engine speed is below the ignition limit, the start procedure will be separated into three phases.: 1. pre-glowing, 2. the start time (start valve) and, if the engine has not reached the ignition speed, 3.the break time. The number of starts to be attempted should be entered here. At the end of the last unsuccessful start attempt, a start fault event will be activated. Note: in MANUAL mode and by pressing the front key “START”, only one start trial will be executed. [0633. – fuel valve :] If a fuel oil valve is in use, this parameter has to set to “ON.” During start or operation of the diesel engine, this event number is always active. This event becomes inactive within the stopping phase or if the engine is stopped. E[262] n > ignition Startphase

≥1 &

E[635]

E[660] Stop valve Figure: Fuel oil valve logic

[0634.

– at RPM=0 :] When the engine speed reaches 0 rpm, the start valve can be set. “YES”: Start process is initialised here when the speed = 0. With this, break time may be prolonged (for electro starters). “NO” : Start process is initialized at the end of break time even if the diesel engine still operates below ignition speed.

[0635.

– max time :] Maximum energizing time of start relay during start phase. Use Event [0635] to set the function output for the start relay.

[0636.

– BREAKTIME:] Break time between start attempts during start phase.

[0637. RUNNING UP – max time * :] [0638. – min volt. :] Running-up supervision time. The maximum supervising time allowed between rising above ignition speed and reaching running-up speed should be entered here. The diesel HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 59/149 -

Service Manual generator is run up if the speed signal is above the running-up limit Parameter [0263] and the voltage of the generator is higher than the minimum voltage of Parameter [0638]. [0639. READY TO TAKE LOAD time :] After the diesel generator reaches the run-up conditions (See Parameters [0637] and [0638]), the ready-to-take-load delay will operate. This time delay is used to stabilize the speed of the engine. After this delay time the next phase of the starting procedure will be introduced (e.g. switch on the synchronizing unit). [0640. SYNCHRONIZING max time * :] Synchronizing supervision time. If the diesel generator is ready to take load, event 640 will be activated. With this event one of the 3 synchronizing units can be activated. To supervise the synchronizing phase, a time limit can be entered. If after this time, the circuit breaker is not connected to the bus bar, a start failure will be issued. [0641. Start next after 1.trial :] After the first unsuccessful start attempt (See Parameter [0632]), the next available diesel engine of the same bus bar section will be started. [0642. Cancel if n > ignition :] With this parameter an additional condition for the startphase cancellation can be defined: • NO: cancel the startphase if the CB is closed. • YES: cancel the startphase if the CB is closed and if the speed reaches the ignition limit. [0643. Cancel start by event :] If this event is active, any start will be cancelled or blocked.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 60/149 -

Service Manual 2.10.11. Stopping phase The parameters of the stopping phase include the settings for control and supervision of the engine during the stopping phase. DIESEL STOPPING PHASE 0650.Stop abort if last gen. : NO 0651.ALARM DELAY – max time : 120.0 sec 0652.LOAD REDUCT. – by event : 511 0653. – loadlimit: 5.0 % 0654. – max time : 20.0 sec 0655. – CB OFF 0656.COOLING DOWN – time : 120.0 sec 0657. – if alarm : NO 0658.RUNNING DOWN – max time : 30.0 sec 0659.FIXED DELAY - time : 10.0 sec 0660.Stop valve event 0661.Emergency stop by event : 517 0662.Stop interlock by event : 519 0663.Cancel stop by event : 0 BACK

Setting range: YES / NO 0.0…999.9 0…9999 0.0…999.9 0.0…999.9 event number 0.0…999.9 YES / NO 0.0…999.9 0.0…999.9 event number 0…9999 Event number 0…9999 Event number 0…9999

EXIT

The stopping sequence includes at maximum four phases (See also diagram stopping procedure of diesel aggregate). 6. Alarm stop delay This phase will be used to start and connect another diesel aggregate to the bus bar before the engine is stopped. 7. Off with load reduction Within this phase, the load of the diesel generator is reduced with the speed lower signal. If the load is under a certain limit, the circuit breaker will be disconnected. 8. Running down phase The running-down phase is a supervision period. During this period, the speed of the engine is reduced via the stop valve output. If the speed signal does not fall below the ignition speed during that time, an alarm event will be issued. 9. Stop delay fixed time During the stop delay fixed time, the event for the stop valve will be set. This event is used to ensure that the engine reaches zero speed. [0650. Stop abort if last gen. :] Block stop order supervision. This parameter should be set to “YES,” if you want to block the stop order when the corresponding diesel generator is the last aggregate loading the bus bar. Stop orders introduced by alarms with any priority and the immediate stop order from the keyboard or by event [661] will stop the engine regardless of this parameter. [0651. ALARM DELAY – max time :] Stop delay time. If an alarm (see 1.3.) with priority 2, 6, 8 or 9 introduces a stop of the engine, the beginning of the stopping phase can be delayed with this delay time. This period of time is used to start and connect another diesel generator to the bus bar. The

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 61/149 -

Service Manual alarm delay maximum time can be shortened if another diesel generator is connected to the bus bar before this time has passed. [0652. LOAD REDUCT. – by event :] The load-reduction phase will be introduced automatically within the stopping phase. If another event activates the load-reduction function (e.g. off-switch at the front door of the cubical), then the event number should be set here. [0653. - loadlimit :] Load limit for load-reduction function. During the off with load reduction phase, the speed lower event will be set by the system until the load of the diesel generator is below this limit. Then the circuit breaker will be disconnected. [0654. – max time :] Maximum time for load-reduction phase. If the load-reduction phase is not finished within this supervision time, a failure event will be issued. [0655. – CB OFF ] Event for circuit breaker OFF command. This event number can be used to give out the circuit breaker OFF command. [0656. COOLING DOWN – time :] If the load-reduction phase is finished, the cooling down of the engine will be introduced. A period of time in which the engine should cool down with nominal speed should be entered here. [0657. – if alarm :] If an alarm with priority 2, 6 or 8 activates the stopping of the engine, the user can decide whether or not the cooling down period of the engine will also be activated. [0658. RUNNING DOWN – max time:] Running-down supervision time. A supervision period in which the speed of the engine should fall below the ignition speed limit while the stop valve is active should be entered here. [0659. FIXED DELAY - time :] Stop delay fixed time. If the speed signal is lower then the ignition speed limit, the stop delay fixed time starts. During this period the stop valve will be activated. [0660. Stop valve event ] Event number for stop valve. This event number is used to activate a function output that is connected to the stop valve (relay). [0661. Emergency stop by event ] If the event (e.g. a function input) becomes active, an emergency stop will be introduced. [0662. Stop interlock by event ] If the event (e.g. a function input) is active, all stop sources will be blocked (even alarm stops), with the exception of emergency stops by key or by Event [0661]. [0663. Cancel stop by event :] If this event is active, any stop (even emergency stops) will be cancelled or blocked.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 62/149 -

Service Manual Starting procedure of the diesel generator

. HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 63/149 -

Service Manual Stopping procedure of the diesel generator

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 64/149 -

Service Manual 2.10.12. Preferential trip limits / Abnormal bus condition With the parameter group “preferential trip limits,” the conditions for non-essential consumer trip and abnormal bus situation can be defined.

0670. 0671. 0672. 0673. 0674. 0675. 0676. 0677. 0678. 0679. 0680. 0681. 0682. 0683. 0684. 0685. 0686. 0687.

PREFERENTIAL TRIP LIMITS HIGH CURRENT – 1. limit: 70.0 – delay: 30.0 – 2. limit: 75.0 – delay: 15.0 – 3. limit: 80.0 – delay: 5.0 – 4. limit: 0.0 – delay: 0.0 LOW FREQUENCY – limit: 0.0 – delay: 0.0 HIGH LOAD – limit: 0.0 – delay: 0.0 BUS1 ABNORM.- overfreq.: 51.50 - underfreq: 48.50 – overvolt.: 105.0 – undervolt: 95.0 - delay: 10.0 PREF.TRIP –check limits: NET BACK

% sec % sec % sec % sec % sec % sec Hz Hz % % sec

Setting range: 0.0…999.9 % 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec / 0.00…99.99 Hz 0.00…99.99 Hz 0.0…999.9 % 0.0…999.9 % 0.5…999.9 sec / OWN / NET

0.5sec steps 0.5sec steps 0.5sec steps 0.5sec steps 0.5sec steps 0.5sec steps

0.5sec steps

EXIT

Preferential trip settings [670--681]: [0670. HIGH CURRENT – 1. limit:] Setting of the first current limit event for preferential trip purpose. If the actual measured current reaches this limit, Event 0670 will be activated. [0671. - delay :] If Event 0670 is active and this delay time is passed, Event 0671 will be activated and remains active as long as the actual value falls below the limit of Parameter [0670] (including 1% hysteresis). This parameter should be used for the alarm controller. [0672. – 2. limit:] Setting of the second current limit event for preferential trip purpose. If the actual measured current reaches this limit, Event 0672 will be activated. [0673. - delay :] If Event 0672 is active and this delay time is passed, Event 0673 will be activated and remains active as long as the actual value falls below the limit of Parameter [0672] (including 1% hysteresis). This parameter should be used for the alarm controller. [0674. – 3. limit:] Setting of the third current limit event for preferential trip purpose. If the actual measured current reaches this limit, Event 0674 will be activated. [0675. - delay :] If Event 0674 is active and this delay time is passed, Event 0675 will be activated and remains active as long as the actual value falls below the limit of Parameter [0674] (including 1% hysteresis). This parameter should be used for the alarm controller. HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 65/149 -

Service Manual [0676. [0677.

[0678.

[0679.

[0680. [0681.

[0687.

– 4. limit:] Setting of the fourth current limit event for preferential trip purpose. If the actual measured current reaches this limit, Event 0676 will be activated. - delay :] If Event 0676 is active and this delay time is passed, Event 0677 will be activated and remains active as long as the actual value falls below the limit of Parameter [0676] (including 1% hysteresis). This parameter should be used for the alarm controller. LOW FREQUENCY – limit:] Setting of the low frequency limit event for preferential trip purpose. This limit will only be checked if the CB is closed. If the actual measured frequency falls below this limit, Event 0678 will be activated. - delay :] If Event 0678 is active and this delay time is passed, Event 0679 will be activated and remains active as long as the actual value exceeds the limit of Parameter [0678] (including 0.1% hysteresis). This parameter should be used for the alarm controller. HIGH LOAD – limit:] Setting of the high load limit event for preferential trip purpose. If the actual measured power reaches this limit, Event 0680 will be activated . - delay :] If Event 0680 is active and this delay time is passed, Event 0681 will be activated and remains active as long as the actual value falls below the limit of Parameter [0680] (including 1% hysteresis). This parameter should be used for the alarm controller. PREF.TRIP – check limits:] This parameter is related to the limits [670-681], not to the abnormal bus limits. OWN: check only the own device. NET : check all devices in the same net.

Abnormal bus1 settings [682--686]: [0682. BUS1 ABNORM.– overfreq.:] Setting of the overfrequency limit event for abnormal bus1 purpose. If the actual measured bus1 frequency reaches this limit, Event 0682 will be activated. [0683. – underfreq:] Setting of the underfrequency limit event for abnormal bus1 purpose. If the actual measured bus1 frequency falls below this limit, Event 0683 will be set. [0684. – overvolt.:] Setting of the overvoltage limit event for abnormal bus1 purpose. If the actual measured bus1 voltage reaches this limit, Event 0684 will be activated. [0685. – undervolt:] Setting of the undervoltage limit event for abnormal bus1 purpose. If the actual measured bus1 voltage falls below this limit, Event 0685 will be activated . [0686. – delay:] If one of the above conditions (Event 0682-0685) is active and this delay time is passed, then Event 0686 will be activated. Use this event number for abnormal bus alarm.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 66/149 -

Service Manual 2.10.13. Additional limits With these additional limits, the user can define further events for his own applications. The time delays of these limits are not as exact as the delay time of the ANSI devices. 0280. 0281. 0282. 0283. 0284. 0285. 0286. 0287. 0288. 0289. 0290. 0291. 0292. 0293. 0294. 0295. 0296. 0297. 0298. 0299.

ADDITIONAL LIMITS OVERSPEED – limit: 105.0 % – delay: 0.5 sec OVERVOLTAGE – limit: 115.0 % – delay: 2.5 sec OVERCURRENT – limit: 90.0 % – delay: 2.5 sec OVERLOAD (OWN) – limit: 95.0 % – delay: 0.5 sec OVERLOAD (NET) – limit: 85.0 % – delay: 0.5 sec PF CAP. LOW – limit: 0.75 – delay: 4.0 sec PF IND. LOW – limit: 0.75 – delay: 4.0 sec REVERSE POWER – limit: 10.0 % – delay: 0.5 sec REACT.POWER IND.– limit: 40.0 % – delay: 0.5 sec NETLOAD excl.OWN- limit: 10.0 % – delay: 0.5 sec BACK EXIT

Setting range: 0.0…999.9 % 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec / 0.00…1.00 0.5…999.9 sec / 0.00…1.00 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec / 0.0…999.9 % 0.5…999.9 sec /

0.5sec steps 0.5sec steps 0.5sec steps 0.5sec steps 0.5sec steps 0.5sec steps 0.5sec steps 0.5sec steps 0.5sec steps 0.5sec steps

[0280. OVERSPEED – limit:] Setting of an additional overspeed limit. If the actual measured speed signal exceeds this limit, Event 0280 will be activated. [0281. - delay :] If Event 0280 is active and this delay time is passed, Event 0281 will be activated and remains active as long as the actual value falls below the limit of Parameter [0280] (including 1% hysteresis). This event number should be used for control functions. [0282. OVERVOLTAGE – limit:] Setting of an additional overvoltage limit. If the actual measured voltage exceeds this limit, Event 0282 will be activated. [0283. - delay :] If Event 0282 is active and this delay time is passed, Event 0283 will be activated and remains active as long as the actual value falls below the limit of Parameter [0282] (including 1% hysteresis). This event number should be used for control functions. [0284. OVERCURRENT – limit:] Setting of an additional overcurrent limit. If the actual measured current exceeds this limit, Event 0284 will be activated. [0285. - delay :] If Event 0284 is active and this delay time is passed, Event 0285 will be activated and remains active as long as the actual value falls below the limit of Parameter [0284] (including 1% hysteresis). This event number should be used for control functions. [0286. OVERLOAD (OWN)– limit:] Setting of an additional overload limit. If the actual measured load of the feeder exceeds this limit, Event 0286 will be activated. HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 67/149 -

Service Manual [0287.

[0288. [0289.

[0290. [0291.

[0292. [0293.

[0294. [0295.

[0296. [0297.

[0298.

[0299.

- delay :] If Event 0286 is active and this delay time is passed, Event 0287 will be activated and remains active as long as the actual value falls below the limit of Parameter [0286] (including 1% hysteresis). This event number should be used for control functions. OVERLOAD (NET)– limit:] Setting of an additional overload limit. If the actual measured load of the bus bar section (net) exceeds this limit, Event 0288 will be activated. - delay :] If Event 0288 is active and this delay time is passed, Event 0289 will be activated and remains active as long as the actual value falls below the limit of Parameter [0288] (including 1% hysteresis). This event number should be used for control functions. PF CAP. LOW – limit:] Setting of a capacitive power factor limit. If the actual measured capacitive power factor falls below this limit, Event 0290 will be activated. - delay :] If Event 0290 is active and this delay time is passed, Event 0291 will be activated and remains active as long as the actual value exceeds the limit of Parameter [0290] (including 1% hysteresis). This event number should be used for control functions. PF IND. LOW – limit:] Setting of a inductive power factor limit. If the actual measured inductive power factor falls below this limit, Event 0292 will be activated. - delay :] If Event 0292 is active and this delay time is passed, Event 0293 will be activated and remains active as long as the actual value exceeds the limit of Parameter [0292] (including 1% hysteresis). This event number should be used for control functions. REVERSE POWER – limit:] Setting of an additional reverse power limit. If the actual measured reverse power exceeds this limit, Event 0294 will be activated. - delay :] If Event 0294 is active and this delay time is passed, Event 0295 will be activated and remains active as long as the actual value falls below the limit of Parameter [0294] (including 1% hysteresis). This event number should be used for control functions. REACT.POWER IND.– limit:] Setting of a reactive inductive power limit. If the actual measured reactive power (inductive area only) exceeds this limit, Event 0296 will be activated. - delay :] If Event 0296 is active and this delay time is passed, Event 0297 will be activated and remains active as long as the actual value falls below the limit of Parameter [0296] (including 1% hysteresis). This event number should be used for control functions. NETLOAD excl.OWN- limit :] Setting of an special overload limit. If the actual measured load of the bus bar section (net), without the own load, exceeds this limit, event 0298 will be activated. This event can be used to cancel a stopping phase, if the future net load becomes to high, during load reduction. For this purpose set event 298 on parameter 187 (remote start) and the device will make a restart of the engine. - delay :] If Event 0298 is active and this delay time is passed, Event 0299 will be activated.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 68/149 -

Service Manual

3. Relay settings The following figure shows the ANSI device list, a list of the relay protection functions of which HIMAP is capable. HIMAP ANSI-Devices: ANSI-DEVICE LIST 15 Matching device (motorpoti) 24 Overexcitation relay 25 /A Synchronizing relay 27 Undervoltage relay 27 B Bus undervoltage relay 32 Overload relay 37 Undercurrent relay (motor) 40 Q Loss of excitation relay 46 Reverse phase relay 47 Phase sequence voltage relay 49 Thermal overload 50BF Breaker failure 50 Instantaneous overcurrent 50G/N Instant. ground overcurrent 51 AC time overcurrent 51G/N AC time ground overcurrent 51LR Locked rotor (motor) 59 Overvoltage relay 59 B Bus overvoltage relay 64/59N Overvoltage ground relay 66 Start inhibit (motor) 67 AC directional overcurrent 67GS/GD AC directional ground relay 78 Vector surge supervision 78 S Out of step tripping 79 AC reclosing relay 81 Frequency relay 81 B Bus frequency relay 86 Lockout relay 87 Differential protection 87N Restrict earth fault relay 94 Supervision relay 95i Inrush blocking relay -- FF Fuse failure (voltages)

↑ ↓

Figure: ANSI-DEVICE LIST-1

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 69/149 -

Service Manual 3.1. ANSI 15 - Matching device (motorpoti) This ANSI function is only operating with HIMAP XG/BCG. HIMAP parameters for matching device: ANSI 15

Matching device (motorpoti)

1025. SPEED device enable : 1026. – convert pulse: 1 sec= 1027. – preset analog output: 1028. – activate preset by: 1055. VOLTAGE device enable : 1056. – convert pulse: 1 sec= 1057. – preset analog output: 1058. – activate preset by:

ON 1.0 50.0 500 OFF 1.5 45.0 503

mA % mA %

Permissible setting range: ON/OFF 0.0……999.9 0.0……99.9 0…………9999 ON/OFF 0.0……999.9 0.0……99.9 0…………9999

mA % mA %

Figure: ANSI 15_1

Parameter description: [1025. SPEED device enable] Fixed switch to enable the device. To use the speed device also an analog output must be set to “Speed ctrl” (see chapter 2.7.). [1026. - convert pulse] Converts a pulse of 1 sec to mA according to this parameter. The pulses for the speed device comes from several functions. These functions are: the sync. units, load sharing, freq. controller, load reduction and the load page (manual speed control). [1027. - preset analog output] [1028. - activate preset by] As long as the event (parameter 1028) is active, the analog output will be set to parameter 1027. Note: also on Power-ON this preset will be executed, so parameter 1027 should be set to a significant value (if the speed device is to be used). [1055. VOLTAGE device enable] Fixed switch to enable the device. To use the voltage device also an analog output must be set to “Volt. ctrl” (see chapter 2.7.). [1056. - convert pulse] Converts a pulse of 1 sec to mA according to this parameter. The pulses for the voltage device comes from several functions. These functions are: the sync. units, voltage controller and the power factor controller. [1057. - preset analog output] [1058. - activate preset by] See 1027, 1028.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 70/149 -

Service Manual 3.2. ANSI 24 - Overexcitation Relay HIMAP parameters for overexcitation relay:

ANSI 24

Overexcitation relay

1090. Overexcitation relay : 1091. - dU/dF Limit value : 1092. - delay time(definite): 1093. – min. voltage :

ON 25.0 % 2.0 sec 70.0 %

Permissible setting range: ON/OFF 0.0……99.9 % 0.0……999.9 sec 0.0……99.9 %

Figure: ANSI 24_1

Parameter description: [1090. Overexcitation relay :] If the overexcitation relay should be activated, set it to ON; if not, to OFF. [1091. - dU/dF Limit value :] Limit setting of overexcitation relay. If the relation between voltage and frequency exceeds this limit, Event [1091] will be activated. Example: If the voltage of the generator is 100% of the nominal rated voltage and the generator frequency is 98% of nominal rated frequency, then the difference is 2%, which will be compared with this parameter. If the actual measured difference exceeds the limit value of Parameter [1091], then Event [1091] will be activated. [1092. - Delay time (definite) :] Time delay of Event [1901]. If Event [1091] is active and this delay time is passed, then Event [1092] will be activated as long as the actual value falls below the limit of Parameter [1091]. Please use this parameter for the alarm or output controller. [1093. - min. voltage :] Minimum voltage for relay operation. To secure a reliable relay function, the voltage limit of this parameter must exceed the limit to enable the protection function.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 71/149 -

Service Manual 3.3. ANSI 25 /A – Automatic Synchronizing Automatic synchronizing operates when two AC circuits are within the desired limits of frequency, phase angle and voltage range, allowing these two circuits to parallel one another. There are three automatic synchronizing units. Number 1 is responsible for the synchronization of the feeder bus to bus bar No.1; Number 2, of the feeder bus to bus bar No.2, and Number 3, between bus bar No.1 and bus bar No.2. The synchronizing units are laid out redundant. Two processor systems are responsible for the control and the supervision of the main breaker-on contact of the synchronizing unit. If HIMAP is used for ANSI 25 check synchronizing, only the following parameters are required for setup: Sync. Unit No. 1: 1000…1007 and 1023 Sync. Unit No. 2: 1030…1037 and 1053 Sync. Unit No. 3: 1060…1067 and 1076

HIMAP parameters for Synchronizing Unit 1 (feeder to bus bar1): ANSI 25 /A Synchronizing relay 1000. Sync. unit 1 active by : 0 1001. - MAX phase angle : 8 deg 1002. - MAX frequency diff. : 200 mHz 1003. - MIN frequency : 99,0 % 1004. - MAX frequency : 101,0 % 1005. - MAX voltage diff. : 5,0 % 1006. - MIN voltage : 95,0 % 1007. - MAX voltage : 105,0 % 1008. - freq.set.pulse time : 100,0 sec 1009. - freq.set.break time : 2,0 sec 1010. – speed push after 10s : 500 ms 1011. – volt.set.pulse time : 10,0 sec 1012. – volt.set.break time : 2,0 sec! 1013. – freq. higher event 1014. – freq. lower event 1015. – volt. higher event Figure: ANSI 25-1 1016. – volt. lower event 1017. – phase regu.active at : 30 mHz 1018. – phase 360 deg pulse : 0.10 sec " 1019. – closing direction : DOWN 1020. – CB closing delay : 50 ms 1021. – live/dead cond. check: ON 1022. – min voltage level : 10,0 % 1023. – CB sync. ON event 1024. – abnormal bus 1 event BACK

Permissible setting range: Event no. 0…………… 30 deg 0…………2000 mHz 70,0…100,0 % 100,0…130,0 % 0,1……30,0 % 70,0……100,0 % 100,0…130,0 % 0,1…999,9 sec 0,1…999,9 sec 0…………9999 ms 0,1…999,9 sec 0,1…999,9 sec event reminder for event reminder for event reminder for event reminder for 0 … 9999 mHz 0.01 … 655.34 sec UP/DOWN/BOTH 0…………1000 ms ON/OFF 0,0-99,9 % event reminder for event reminder for

output output output output

output output

EXIT

Figure: ANSI 25-1

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 72/149 -

Service Manual HIMAP parameters for Synchronizing Unit 2 (feeder to bus bar2): ANSI 25 /A Synchronizing relay

Permissible setting range: "

1030. Sync. unit 2 active by : 0 1031. - MAX phase angle : 8 deg 1032. - MAX frequency diff. : 200 mHz 1033. - MIN frequency : 99,0 % 1034. - MAX frequency : 101,0 % 1035. - MAX voltage diff. : 5,0 % 1036. - MIN voltage : 95,0 % 1037. - MAX voltage : 105,0 % 1038. - freq.set.pulse time : 100,0 sec 1039. - freq.set.break time : 2,0 sec 1040. – speed push after 10s : 500 ms 1041. – volt.set.pulse time : 10,0 sec 1042. – volt.set.break time : 2,0 sec 1043. – freq. higher event 1044. – freq. lower event 1045. – volt. higher event Figure: ANSI 25-3 1046. – volt. lower event 1047. – phase regu.active at : 30 mHz 1048. – phase 360 deg pulse : 0.10 sec 1049. - closing direction : DOWN 1050. – CB closing delay : 50 ms 1051. – live/dead cond. check: ON 1052. – min voltage level : 10,0 % 1053. – CB sync. ON event ! 1054. – abnormal bus 2 event BACK

Event no. 0…………… 30 deg 0…………2000 mHz 70,0…100,0 % 100,0…130,0 % 0,1……30,0 % 70,0……100,0 % 100,0…130,0 % 0,1…999,9 sec 0,1…999,9 sec 0…………9999 ms 0,1…999,9 sec 0,1…999,9 sec event reminder for event reminder for event reminder for event reminder for 0 … 9999 mHz 0.01 … 655.34 sec UP/DOWN/BOTH 0…………1000 ms ON/OFF 0,0-99,9 % event reminder for event reminder for

output output output output

output output

EXIT

Figure: ANSI 25-2

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 73/149 -

Service Manual HIMAP parameters for Synchronizing Unit 3 (bus bar1 to bus bar 2): Permissible setting range:

ANSI 25 /A Synchronizing relay "

1060. Sync. unit 3 active by : 0 1061. - MAX phase angle : 8 deg 1062. - MAX frequency diff. : 200 mHz 1063. - MIN frequency : 99,0 % 1064. - MAX frequency : 101,0 % 1065. - MAX voltage diff. : 5,0 % 1066. - MIN voltage : 95,0 % 1067. - MAX voltage : 105,0 % 1068. - freq.set.pulse time : 100,0 sec 1069. - freq.set.break time : 2,0 sec 1070. – speed push after 10s : 500 ms 1071. – volt.set.pulse time : 10,0 sec 1072. – volt.set.break time : 2,0 sec! 1073. – freq. higher event : 1074. – freq. lower event : 1075. – volt. higher event : Figure: ANSI 25-5 1076. – volt. lower event : 1077. – phase regu.active at : 30 mHz 1078. – phase 360 deg pulse : 0.10 sec 1079. - closing direction : DOWN 1080. – CB closing delay : 50 ms " 1081. – live/dead cond. check: ON 1082. – min voltage level : 10,0 % 1083. – CB sync. ON event 1084. – abnormal bus 2 event BACK

Event no. 0…………… 30 deg 0…………2000 mHz 70,0…100,0 % 100,0…130,0 % 0,1……30,0 % 70,0……100,0 % 100,0…130,0 % 0,1…999,9 sec 0,1…999,9 sec 0…………9999 ms 0,1…999,9 sec 0,1…999,9 sec event reminder for event reminder for event reminder for event reminder for 0 … 9999 mHz 0.01 … 655.34 sec UP/DOWN/BOTH 0…………1000 ms ON/OFF 0,0-99,9 % event reminder for event reminder for

output output output output

output output

EXIT

Figure: ANSI 25-3

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 74/149 -

Service Manual The following parameter description corresponds to Synchronizing Unit 1 (feeder to bus bar 1). Synchronizing Units 2 and 3 have the same parameters and differ only in their parameter and event numbers. (See also description of synchronizing page within the users manual.) [1000. Sync. Unit 1 active by :] To activate the Synchronizing Unit No.1, an event number (e.g. binary input event) must be set. If this event number is active, the synchronizing window appears and the synchronizer with its frequency and voltage controller is operative. [1001. - MAX phase angle :] The maximum phase angle (positive and negative angle) appears in the window in which the closing order for the switching device (breaker) is given. [1002. - MAX frequency diff. :] If the difference of frequency is higher than the set point, then the synchron closing is blocked until the difference of frequency drops below the set point. [1003. - MIN frequency :] Minimum frequency limit for “abnormal bus” check. If the frequency of bus bar1 is below the minimum frequency limit, then the frequency controller will be deactivated. That means the output to send speed lower signals will be blocked. [1004. - MAX frequency :] Maximum frequency limit for “abnormal bus” check. If the frequency of bus bar1 is above the maximum frequency limit, then the frequency controller will be deactivated. That means the output to send speed higher signals will be blocked. [1005. - MAX voltage diff. :] If the difference in voltages is higher than the set point, the synchron closing will be blocked until the difference in voltages drops below the set point. [1006. - MIN voltage :] Minimum voltage limit for “abnormal bus” check. If the voltage of bus bar1 is below the minimum voltage limit, then the voltage controller will be deactivated. That means the output to send voltage lower signals will be blocked. [1007. - MAX voltage :] Maximum voltage limit for “abnormal bus” check. If the voltage of bus bar1 is above the maximum voltage limit, then the voltage controller will be deactivated. That means the output to send voltage higher signals will be blocked. [1008. - freq.set.pulse time :] The pulse time for frequency adjustment during synchronization is set here. The pulse time is defined at 100 percent frequency difference. The pulse time, which the frequency controller calculates after the break time, is modified by the difference between the two frequency inputs. The formula for the pulse is:

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 75/149 -

Service Manual Calculation for pulse time: pulse [sec] = Parameter [1008] / 100 * ∆F [%] Whereby: Parameter [1008] : pulse time set point at 100% frequency difference. ∆F [%] : frequency difference between feeder and bus bar 1 in percent. Example:

Parameter [1008] = 100sec means: If the frequency difference between feeder and bus bar 1 is 100%, a pulse of 100 seconds will be set. If the frequency difference is 1% (0.5Hz at 50Hz nominal-rated frequency), then a pulse of 1 sec will be set, and so on.

[1009. - freq.set.break time :] The break time between pulse times for speed adjustment during synchronization is set here. After a break time is passed, the frequency controller will calculate the next pulse time to control the pulse event (Event 1008). [1010. - speed push after 10s :] If the difference between the electrical angles of the generator and bus bar does not become zero within 10 seconds, then an impulse of the set time in this parameter will be given. Note: instead of the speed push, the phase regulator can be used. [1011. - volt.set.pulse time :] The pulse time for voltage adjustment during synchronization is set here. Pulse time is modified by the difference between the voltages inputs. [1012. - volt.set.break time :] The break time between pulse times for voltage adjustment during synchronization is set here. [1013. - freq. higher event :] Use this event to activate a digital output in order to increase the frequency synchronization. [1014. - freq. lower event :] Use this event to activate a digital output in order to lower the frequency synchronization. [1015. - volt. higher event :] Use this event to activate a digital output in order to increase the voltage synchronization. [1016. - volt. lower event :] Use this event to activate a digital output in order to lower the voltage synchronization.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

during during during during

- 76/149 -

Service Manual [1017. – phase regu.active at] The phase regulation can be used to regulate the phase to zero if the two frequencies becomes nearly equal and the phase angle is nearly constant. If this parameter is set to 0 the phase regulator will be always inactive. Otherwise, if this parameter is set to a value > 0, the speed push (P1010) will be always inactive, and the phase regulator will be activated in the following way: if the difference between the two frequencies reaches this low limit (P1017), the phase regulator becomes active. The regulator will remain active until the difference exceeds the “MAX frequency diff.” (P1002). [1018. – phase 360 deg pulse ] The pulse time for phase regulation is set here. The pulse time, which the phase regulator calculates after the break time (P1009), is modified by the actual phase angle. The formula for the pulse is: pulse [sec] = (Parameter [1018] * deg) / 360. [1019. - closing direction :] The main breaker closing command will be given only when the engine speed is higher (UP), lower (DOWN) or in both directions. See also figure 25-5 and 25-6. [1020. - CB closing delay :] The main breaker closing delay is the mechanical delay time caused by the closing time of contactors, relays and the main breaker itself. This delay time can reduce the time period of “breaker synchron on command” Event 1023). [1021. - live/dead cond. check :] ON/OFF-switch for dead condition check. If the synchronizing unit recognizes one side (feeder or bus bar) without voltage (dead system), then the Event 1023 (CB sync.ON) will be activated without checking synchronization. Note: if HIMAP- XG/BCG is selected, only the bus bar will be checked for live/dead condition. [1022.

- min. voltage level :] If the live/dead condition check (Event 1021) is active and the voltage of one side (feeder or bus bar) is below this voltage limit, the synchronizing unit recognizes dead condition.

[1023. - CB sync. ON event ] Use this event to send the main breaker close signal. This event will be set if the pointer of the synchronization unit is within the synchron window and the synchronization unit is not blocked. [1024. - abnormal bus 1 event ] Use this event to indicate bus abnormal situation. If during synchronization the main conditions for voltage and frequency are not fulfilled for the bus bar, then bus abnormal event will be set and the corresponding controller for voltage and frequency will be blocked. (See Parameters 1003, 1004, 1006, 1007).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 77/149 -

Service Manual The following diagram shows the conditions that have to be fulfilled during synchronizing to set the “CB synchron event” (Event 1023). The parameter and event numbers correspond to Synchronizing Unit 1 (feeder to bus bar 1).

Main condition for MB ON command

SYNCHR. UNIT 1 ON

MB close command Event [1023]

Parameter [1000]

UBus 1 > UMIN

Freq. Ctrl. ON Volt. Ctrl. ON

UBus 1 < UMIN

UBus 1 - feed < Parameter [1005]

Parameter [1006]

Parameter [1007]

&

FBus 1 > FMIN

&

UBus 1 - feed

Parameter [1003]

< Parameter [1002]

FBus 1 < FMIN

act. Phase angle within synchr. window Parameter [1001]

Parameter [1004]

≥1

abnormal bus Event [1024]

Figure: ANSI 25-4

Note: in the case that the voltages of both systems are “alive” and one system has negative sequence, the synchronizer will be internally blocked, and event 2949 gets active (use this event for an alarm). If both systems have negative sequence the synchronizing process is not blocked.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 78/149 -

Service Manual The following diagrams shows the closing direction philosophy. If closing direction “down” (Parameter 1019) is selected and if the feeder frequency is higher then the bus bar frequency, then the main breaker synchron close command will be given.

HIMAP LC – display:

Synchronizing window

Frequency

For closing direction: DOWN the cursor has to move in the shown direction (F feeder > F bus)

CB ON-command

CB ON-command

actual Bus frequency closing direction: DOWN [Parameter 1019]

no CB on command Feeder frequency

CB: Circuit breaker

t

Figure: ANSI 25-5

If closing direction “up” (Parameter 1019) is selected and if the feeder frequency is lower then the bus bar frequency, then the main breaker synchron close command will be given, as the diagram below shows.

HIMAP LC – display:

Synchronizing window

For closing direction: UP the cursor has to move in the shown direction (F feeder < F bus)

Frequency

CB ON-command

CB ON-command

actual Bus frequency closing direction: UP [Parameter 1019]

no CB ON command Feeder frequency

CB: Circuit breaker

t

Figure: ANSI 25-5

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 79/149 -

Service Manual 3.4. ANSI 27 - Undervoltage Relay The undervoltage relay is a relay that operates when its input voltage is less than a predetermined value. Undervoltage protection detects and reports abnormally low voltage conditions, some of which could be related to system stability problems (voltage collapse, etc.). Undervoltage protection is generally used for load shedding and loss of phase purposes. HIMAP parameters: ANSI 27 1100. 1101. 1102. 1103. 1104. 1105. 1106. 1107.

Undervoltage relay

Undervoltage relay : - Undervoltage 1.limit: - Delay time(definite): - Undervoltage 2.limit: - Delay time(definite): – Min. start voltage : – Min. frequency : reserved:

BACK

Permissible setting range:

OFF 95,0 2,00 93,0 3,00 90,0 55,0

% sec % sec % Hz

ON / OFF / 0,0… 99,9 0,03…99,99 0,0… 99,9 0,03…99,99 0,0… 99,9 0,0… 99,9

CB ON % sec % sec % Hz

EXIT

Figure: ANSI 27

Parameter description: [1100. Undervoltage relay :] This parameter activates the undervoltage supervision, whereby: OFF: deactivates, ON: activates and CB ON: activates the undervoltage supervision only if the circuit breaker is switched on. [1101. - Undervoltage 1. limit :] First limit of the set point for undervoltage. [1102. - Time delay (definite ) :] Time delay of Event [1101]. Use this event to activate an output. [1103. - Undervoltage 2. limit :] Second limit of the set point for undervoltage. [1104. - Time delay (definite ) :] Time delay of Event [1103]. Use this event to activate an output. [1105. - MIN start voltage :] This parameter depends on the device type.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 80/149 -

Service Manual Device type BC or X: During the startup sequence, this limit must be reached in order to activate the undervoltage protection. Device type BCG or XG: This parameter is not active, since the undervoltage relay works when the main breaker is on; otherwise, it is blocked. [1106. - MIN frequency :] This parameter depends on the device type. Device type BC or X: When the feeder frequency is lower than this setting, the undervoltage protection function is disabled. Device type BCG or XG: This parameter is not active, since the undervoltage relay works when the main breaker is on; otherwise, it is blocked. [1107. - reserved …

ANSI 27

:]

off E 1100

27 active

„1“

P 1105

Setting

on

Startup

U>

&

3~

P 1106

Setting

Minimum

f> 3~

E 1101 Limit reached

U<

&

0 |

T |

E 1102

27-1 Trip

E 1103 Limit reached

3~

P 1104

P 1103 27-2 Pickup

U

S1 Q R

3~

& P 1202

Reset

E 1201 Limit reached

P 1201 46-TOC Pickup 3~

ANSI 79 Reclose

TMS

P 1203 IDMT Curve

&

E 1202 46-TOC Trip

on/off

VR_EN

Reclose

E 1205 Limit reached P 1205 46-1 Pickup 3~

&

P 1206 46-1 Delay 0 |

T |

E 1206 46-1 Trip on/off

VR_EN

Reclose

E 1207 Limit reached P 1208 46-2 Delay P 1207 46-2 Pickup 3~

VR_EN Voltage Restrain

&

0 |

T |

E 1208

46-2 Trip

on/off Reclose

on/off

Figure: Logic diagram for the reverse phase / balance protection

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 89/149 -

Service Manual 3.10. ANSI 47 - Phase sequence voltage relay The phase sequence voltage relay is a relay that functions upon a predetermined value of polyphase voltage in the desired phase sequence. HIMAP parameters: ANSI 47 Phase sequence voltage relay 1300. 1301. 1302.

Phase sequence relay : - Limit value : - Delay time(definite):

BACK

OFF 20,0 % 2,00 sec

Permissible setting range: ON / OFF 1,0...199,9 0,01..99,99

% sec

EXIT

Figure: ANSI 47

Parameter description: [1300. Phase sequence relay :] The normal voltage phase sequence is right rotating, that means L1-L2-L3. If the sequence turns to left rotating or one phase is missing, the relay becomes active. If the negative sequence relay should be activated, set it to ON; if not, to OFF. [1301. –Limit value :] If the left rotating field exceeds the limit, the phase sequence relay will be activated. [1302. - Delay time (definite ) :] Time delay for Event 1301. Use this event to activate an output.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 90/149 -

Service Manual 3.11. ANSI 49 - Thermal Overload The thermal overload relay is divided in 3 independent sections. Any of the sections can be activated and used independently of each other. 3.11.1. Thermal overload I (general) This section calculates a thermal image in accordance to the current. Parameters: Permissible setting range:

ANSI 49 Thermal overload 1340. 1341. 1342. 1343. 1344. 1345. 1346.

THERMAL OVERLOAD : – Rated current[ 1000]A: - Cold limit at 6*In : - Hot limit at 6*In : – tc / th : – Trip time reset delay: - Event for trip time - tc (calculated) = - th (calculated) = - Preload at 6*In (T6h)= BACK

OFF 20,0 10,0 20,0 5,0 10,0

% sec sec sec

16,7 min 11,1 min 67,0 % EXIT

ON / OFF 0,1.999,9 % 0,1…999,9 sec (0,25s steps) 0,1…999,9 sec (0,25s steps) 0,1… 99,9 0,1…999,9 sec Event only Calculated from [1342]&[1344] Calculated from [1342] Calculated from [1343]

Figure: ANSI 49

Parameter description: [1340. THERMAL OVERLOAD :] ON/OFF-switch for thermal overload protection. [1341. – Nominal rated current [ xxxx]A :] Overload current of the nominal rated current of the motor. Pickup value for thermal motor protection 49. If the current reaches this limit event 1341 will be set. [1342. – Cold limit at 6*In :] This parameter is required to calculate τh. This trip time is taken from the cold curve of the motor. The trip time in the curve is taken from 6*In. [1343. – Hot limit at 6*In :] This parameter is required to set the characteristic of the hot curve and limit the thermal image value. [1344. – tc/th :] The relationship between τ of the hot and the cold curve is required to calculate τc. [1345. – Trip time reset delay :] If the trip time is active and the actual current is below the nominal rated (set with Parameter 1341), the time value will be held for this time before reset. [1346. – Event for trip time :] If the trip time is passed according to the thermal overload conditions, Event 1346 will be set. Choose this event to initiate a trip signal by using a binary output.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 91/149 -

Service Manual [

tc (calculated) :] Calculated value τc. Result of the formula:

τ c = parameter [1344]*τ h [

th (calculated) :] Calculated value τh . Result of the formula:

τh =

t

⎛ (I / In )2 ⎞ ⎟ ln⎜⎜ 2 2 ⎟ ( ) I / In k − ⎝ ⎠

The time t will be taken from the cold curve of the motor at six times the nominal rated current. The threshold factor k is fixed with 1.03. The result of τh is calculated as follows:

τh =

[

T 6c ( param [1342]) 2 ⎛ ⎞ ( 6) ⎜ ⎟ ln⎜ 2 2 ⎟ ( ) − 6 ( 1 . 03 ) ⎝ ⎠

Preload at 6*In (T6h):] Calculated maximum preload value with the formula:

⎛ (I / In )2 − ( I Pr e / In) 2 t = τ h * ln⎜⎜ (I / In )2 − k 2 ⎝

t

⎞ ⎟ ⇒ ( I Pr e / In) 2 = ( I / In) 2 − e τ h * ( I / In) 2 − k 2 ⎟ ⎠

(

)

The time will be taken from the hot curve of the motor at six times the nominal rated current. The threshold factor k is fixed with 1.03. The result is the maximum preload value which will be limited by the hot curve of the motor.

( I Pr e / In) = (6) − e 2

2

⎛ T 6 h [1343 ]) ⎞ ⎟ ⎜ ⎟ ⎜ τh ⎠ ⎝

(

* (6) 2 − 1.03 2

)

( I Pr e / In) 2 relates to Θ which is the thermal image of the motor

The relationship is:

Θ Pr e = k * ( I Pr e / In) 2 The thermal image of the motor will be calculated all the time and follows the formula:

Θ(%) = Θ S + (Θ C − Θ S ) * e

⎛ −t ⎞ ⎜ ⎟ ⎜τ ⎟ ⎝ ⎠

whereby ΘC: The current motor image, ΘS : Thermal status destination, which will be calculated with (Iactual/In)². τ: Tau. During heating τh and during cooling, τc will be used. HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 92/149 -

Service Manual If the actual motor current exceeds the limit of Parameter [1341] (rated current), the trip time integrator will be activated. The tripping time t of the thermal overload relay is calculated according to the following formula and to the corresponding Preload value (IPre/IN)²:

⎡ (I / I N )2 − ( I Pr e / I N ) 2 ⎤ t = τ c * ln ⎢ ⎥ (I / I N )2 − k ² ⎦⎥ ⎣⎢ Whereby: I: The actual measured current. IN: The thermal overload (set with Parameter 1341). k: The threshold factor (1.03).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 93/149 -

Service Manual

3.11.2. Thermal overload II (user)

This section gives the user the possibility to define his own curve with 10 current / time points. Between these points, the time values are linear interpolated. ANSI 49 Thermal overload 1350. THERMAL OVERLOAD (user): ON 1351. - integrator reset mode: depending 1352. - integrator hold time : 300.0 sec 1353. - current limit : 110.0 % 1354. - time:3600.0 sec 1355. - current point 1: 111.0 % 1356. - time:1800.0 sec 1357. - current point 2: 114.0 % 1358. - time: 900.0 sec 1359. - current point 3: 123.0 % 1360. - time: 300.0 sec 1361. - current point 4: 145.0 % 1362. - time: 120.0 sec 1363. - current point 5: 180.0 % 1364. - time: 30.0 sec 1365. - current point 6: 230.0 % 1366. - time: 10.0 sec 1367. - current point 7: 400.0 % 1368. - time: 3.0 sec 1369. - current point 8: 0.0 % 1370. - time: 0.0 sec 1371. - current point 9: 0.0 % 1372. - time: 0.0 sec BACK EXIT

Permissible setting range: OFF / ON hold time / depending 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5 0.0……6553.5

Figure: ANSI 49

[1350. THERMAL OVERLOAD (user) :] OFF/ON-switch for this relay section. If the relay is tripped, Event [1350] will be set. [1351. - integrator reset mode] Defines the reset mode of the time integrator if the current falls below the limit of Parameter [1353]: • Hold time: the integrator will be reset if the time of Parameter [1352] has passed. • Depending: the integrator will be integrated downwards with the last excitation time. This time can be limited with Parameter [1352]. [1352. – integrator hold time] Hold time for the integrator if the current falls below the limit of Parameter [1353]. [1353. – current limit] Excitation limit for the time integration and the starting point of the curve. If the current reaches this limit, the time integration will be activated. [1354. – time] The max. trip time for limit Parameter [1353]. HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 94/149 -

Service Manual [1355. – current point 1] [1356. – time] …… [1371. – current point 9] [1372. – time] Every point consists of one current limit and the related time (max. trip time for the current at this point). If the current is between two limits the related time will be linearly calculated. The limits must be ascending, beginning at the first point. If a limit is 0, the curve will be truncated at the previous limit.

Example: I [%] 400

300

200

100

3

HYUNDAI HIMAP

10

30

120

300

900

HIMAP_ServiceManual_E.doc

1800

3600

t [sec]

- 95/149 -

Service Manual 3.11.3. Thermal overload III (interval)

This section gives the user the possibility to define a interval time in which the current has a defined allow time for remaining above a limit. Permissible setting range:

ANSI 49 Thermal overload 1373. INTERVAL PROTECTION : 524 1374. - current limit: 110.0 % 1375. - allow time : 60 min 1376. - interval time: 12 h BACK

0…9999 Event 0.1……999.9 1…999 1…24

EXIT

Figure: ANSI 49

[1373. INTERVAL PROTECTION] Event-switch for this relay section. • Event active: the function will be activated. • Event inactive: the function will be reset. If the relay is tripped, Event [1373] will be activated. [1374. – current limit] If the current reaches this limit, the time integration will be activated. [1375. – allow time] If the integration reaches this time limit, the relay will trip and the Event [1373] will be activated. [1376. – interval time] The allow time is only valid within this interval time. If one of the integrated periods overlaps this interval, the integrated time will be decreased by the period (if the current is below the limit of Parameter [1374]).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 96/149 -

Service Manual 3.12. ANSI 50BF – Breaker Failure

Breaker failure relay supervises the circuit breaker. HIMAP parameters: Permissible setting range:

ANSI 50BF Breaker failure relay 1380 Breaker failure relay : 1381. – Current limit(CB:OFF): 1382. - Delay time (definite):

BACK

ON 10,0 % 2 sec

ON / OFF 0…9999 % 0…9999 sec

EXIT

Figure: ANSI 50BF

Parameter description: [1380. Breaker failure relay :] ON/OFF – switch for breaker failure protection. [1381. – Current limit (CB:OFF) :] If the circuit breaker is off (feedback of circuit breaker or trip command) and a current is higher then the limit in Parameter 1381, the breaker failure relay will be activated. [1382. – Delay time (definite) :] Delay time of breaker failure relay.

CB: off (feedback)

>1

Trip command

&

Manual OFF

Event 1382

50BF

Act. current value > Current limit (1381)

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 97/149 -

Service Manual 3.13. ANSI 50 – Instantaneous overcurrent relay

Instantaneous overcurrent or rate-of-rise relay is a relay that functions instantaneously on excessive value of current or on an excessive rate of current. HIMAP parameters:

1400. 1401. 1402. 1403. 1404. 1405. 1406. 1407. 1408. 1409. 1410.

ANSI 50 Instantaneous overcurrent

Permissible setting range:

Instantaneous overcurr.: ON - 1. limit [ 3000]A: 300.0 % - Delay time (definite): 100 ms reserved: - 2. limit [ 3000]A: 300.0 % - Delay time (definite): 250 ms reserved: - Rev. limit [ 3000]A: 300.0 % - Delay time (definite): 200 ms reserved: - Inrush blocking : OFF

ON / OFF / reclose 2.0…2999.9 % 30………9999 ms

BACK

2.0…2999.9 % 30………9999 ms 2.0…2999.9 % 30………9999 ms ON / OFF

EXIT

Figure: ANSI 50

Parameter description: [1400. Instantaneous overcurr. :] If the instantaneous overcurrent relay should be activated, set it to ON; if not, to OFF. If it is set to RECLOSE, it closes the breaker according to the setting of ANSI 79. [1401. - 1. limit [ xxxx]A :] First limit setting of instantaneous overcurrent. If the actual measured value exceeds this limit, Event 1401 will be set. [1402. - Delay time (definite) :] Time delay of Event 1401. If Event 1401 is active and this delay time is passed, the Event 1402 will be activated as long as the actual value falls below the limit of Parameter 1401. Please use this parameter for the alarm or output controller. [1403. - reserved

:]

[1404. - 2. limit [ xxxx]A :] Second limit setting of instantaneous overcurrent. If the actual measured value exceeds this limit, Event 1404 will be set. [1405. - Delay time (definite) :] Time delay of Event 1404. If Event 1404 is active and this delay time is passed, the Event 1405 will be activated as long as the actual value falls below the limit of Parameter 1404. Please use this parameter for the alarm or output controller. [1406. - reserved :] HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 98/149 -

Service Manual [1407. - Rev. limit [ xxxx]A :] Limit setting of instantaneous overcurrent is active only if the current direction is going into the reverse direction. If the actual measured value exceeds this limit, Event 1407 will be set. [1408. - Delay time (definite) :] Time delay of Event 1407. If Event 1407 is active and this delay time is passed, the Event 1408 will be activated as long as the actual value falls below the limit of Parameter 1407. Please use this parameter for the alarm or output controller. [1409. - reserved

:]

[1410. - Inrush blocking :] The delay times of Parameters 1402, 1405 & 1408 can be extended, if inrush conditions referring to ANSI 95i are detected.

ANSI 50 off on reclose

„1“

or

E 1400

E 1401 Limit reached P 1401

≤1

50 active

ANSI 79 Reclose

P 1402 50-1 Delay

50-1 Pickup

&

I> 3~

0 |

T |

E 1402 50-1 Trip

on/off Reclose

Inrush EN

E 1404 Limit reached P 1404 1404 Pickup I >> 3~

&

P 1405 50-2 Delay 0 |

T |

E 1406 50-2 Trip on/off

Inrush EN

Reclose

E 1407 Limit reached P 1408 50-Rev Delay P 1407 50-Rev Pickup I >Rev 3~

&

0 |

T |

E 1408 50-Rev Trip on/off Reclose

Inrush EN

on/off „1“ Inrush Blocking

Figure: Logic diagram for the instantaneous overcurrent protection

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 99/149 -

Service Manual 3.14. ANSI 50G/N – Instantaneous ground overcurrent relay

Instantaneous ground overcurrent or ground rate-of-rise relay is a relay that functions instantaneously on excessive value of current or on an excessive rate of current. The permissible setting range of this relay depends on the ordered hardware. Refer to the order information to get the appropriate internal current transformers. Required measuring inputs (pick up) for ANSI50G/N protection: - Ground current input “Ignd1” Required parameters for ANSI50G/N protection: ANSI 50G/N Instant. ground overcurrent 1420. 1421. 1422. 1423. 1424.

Inst. ground overcurr. : ON - Limit [ 2000]A: 200.0 % – Delay time (definite): 30 ms - Pickup type (50G/N) :meas.Ignd1 - Inrush blocking : OFF

BACK

Permissible setting range: ON / OFF 2.0…2999.9 % or 0.1…6000.0 mA 30………9999 ms

meas.Ignd1/meas.Ignd2/meas.Ig1+2

ON / OFF

EXIT

Figure 3.14.1: parameter group for ANSI 50G/N

Parameter description: [1420. Inst. ground overcurr. relay :] If the instantaneous ground overcurrent relay should be activated, set it to ON; if not, to OFF. [1421. - Limit [ xxxx]A :] Limit setting of instantaneous ground overcurrent. If the actual measured value exceeds this limit, Event [1421] will be activated.

The unit of the limit value can be set between “%” and “mA” via Parameter[0053]. (See PC Parameter tool special parameter). “%”: If the unit is set to “%”, the limit value refers to the nominal-rated current (primary side) of the feeder (Parameter[0200]). The setting range is 2.0…999.9%. “mA”: If the unit “mA” is selected, the parameters for the nominal-rated value of the feeder current and the ground current transformer values have no influence on the measured current. HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 100/149 -

Service Manual

[1422. - Delay time (definite) :] Time delay of Event[1421]. If Event [1421] has been activated and the set delay time is passed, then Event[1422] will be activated until the measured value falls below the limit of Parameter[1421]. This parameter should be used for the alarm or output controller. [1423. - Pickup type (50G/N) :] Three different pickup types for instantaneous ground overcurrent can be selected. “meas.Ig1+2”: default setting. Please don’t change this parameter. “meas.Ignd1”: reserved. “meas.Ignd2”: reserved. [1424. - Inrush blocking :] The delay time of Parameter 1422 can be extended if inrush conditions referring to ANSI95i are detected.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 101/149 -

Service Manual 3.15. ANSI 51 – AC time overcurrent relay

AC time overcurrent relay is a relay that operates when its AC input current exceeds a predetermined value, and when the input current and operating time are inversely related through a substantial portion of the performance range. HIMAP parameters:

1500. 1501. 1502. 1503. 1504. 1505. 1506. 1507. 1508. 1509. 1510. 1511. 1512. 1513.

ANSI 51 AC time overcurrent

Permissible setting range:

Time overcurrent relay : – Limit [ 1000]A: - Time multiplier (TMS): - Curve shape : - Reset characteristic : - 1.limit [ 1200]A: – Delay time (definite): - 2.limit [ 1400]A: – Delay time (definite): - 3. limit [ 1800]A: – Delay time (definite): – Reset character (Th) : – Volt. restrain [51VR]: – Volt. low limit:

ON / OFF / reclose 2.0……2999.9 % 0.03…10.00 sec 8 curve shapes (IDMT) none,def./Th,dep.,curve D-F 2.0……2999.9 % 0.1……999.9 sec 2.0……2999.9 % 0.1……999.9 sec 2.0……2999.9 % 0.1……999.9 sec 0…………99 sec ON / OFF 10……90 %

BACK

ON 100.0 % 1.00 s very inv. def./Th 110.0 % 10.0 s 140.0 % 5.0 s 180.0 % 1.0 s 0 s OFF 10 % EXIT

Figure: ANSI 51-1

Parameter description: [1500. Time overcurrent relay :] If the AC time overcurrent relay should be activated, set it to ON; if not, to OFF. If it is set to RECLOSE, it closes the breaker according to the setting of ANSI 79. [1501. - Limit [ xxxx]A :] Limit setting of AC time overcurrent. If the actual measured value exceeds this limit, Event 1501 will be set. [1502. - Time multiplier (TMS) :] Time multiplier setting for the corresponding curve shape (see Parameter1503). If Event 1501 is active and the delay time calculated with the time multiplier and the chosen curve shape is passed, the Event 1502 will be activated as long as the actual value falls below the limit of Parameter 1501. Please use this parameter for the alarm or output controller. [1503. - Curve shape :] Curve shape selection of AC time overcurrent. Eight curve shapes (normal inverse, very inverse, extremely inverse, curve D-F, INV-K and VINV-K) can be selected (see appendix XXL). [1504. - Reset characteristic :] Reset characteristic of time overcurrent relay. If the calculated delay time is in process and the actual measured current value falls below the limit of Parameter 1501, then a HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 102/149 -

Service Manual special reset characteristic for the actual calculated delay time can be set with this parameter. The following characteristics are available: none, def./Th, depending, curve DF (see also appendix XXs). In addition to the AC time overcurrent relay operating with inverse curve shapes, three further limits with definite times can be used (Parameters 1505–1510). [1505. - 1. limit [ xxxx]A :] First additional current limit. If the actual measured value exceeds this limit, Event 1505 will be set. [1506. - Delay time (definite) :] Time delay of Event 1505. If Event 1505 is active and this delay time is passed, the Event 1506 will be activated as long as the actual value falls below the limit of Parameter 1505. Please use this parameter for the alarm or output controller. [1507. - 2. limit [ xxxx]A :] Second additional current limit. If the actual measured value exceeds this limit, Event 1507 will be set. [1508. - Delay time (definite) :] Time delay of Event 1507. If Event 1507 is active and this delay time is passed, the Event 1508 will be activated as long as the actual value falls below the limit of Parameter 1507. Please use this parameter for the alarm or output controller. [1509. - 3. limit [ xxxx]A :] Third additional current limit. If the actual measured value exceeds this limit, Event 1509 will be set. [1510. - Delay time (definite) :] Time delay of Event 1509. If Event 1509 is active and this delay time is passed, the Event 1510 will be activated as long as the actual value falls below the limit of Parameter 1509. Please use this parameter for the alarm or output controller. [1511. - Reset character (Th) :] Holding time for reset characteristic if Parameter 1504 is set to “def./Th”. If the calculated delay time is in process and the actual measured current value falls below the limit of Parameter 1501, then the calculated delay time is hold for this time. [1512. - Volt. restrain [51VR] :] The Parameter 1512 activates the voltage restrain function. If voltage restrain function is active, the Current limits (1501, 1505, 1507, 1509) will be reduced proportional to the relationship actual voltage to nominal voltage, as shown in the Figure 51-1 on the following page. [1513. - Volt. low limit :] The low voltage parameter limits the voltage restrain function to a minimum value (see Figure 51-1).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 103/149 -

Service Manual

1 0,9

Curve Pickup Multiplier

0,8 0,7 0,6 0,5 0,4 P

1513

0,3 0,2 0,1 0 0 P

1513

10

20

30

40

50

60

70

80

90

100 %

Voltage

Voltage low limit for ANSI 51

Figure 51-1: Pickup value calculation curve of the voltage restrain function

ANSI 51 off on reclose

„1“

E 1500

51 active

P 1502

or E 1501 Limit reached

P 1501 51-TOC Pickup

3~

&

t

1504 Reset Char.

E 1505 Limit reached

51-1 Pickup 3~

& E 1507 Limit reached

3~

Reclose

P 1508 51-2 Delay

&

E 1508 51-2 Trip 1511 Reset Char.

VR_EN

on/off Reclose

E 1509 Limit reached P 1509 51-3 Pickup 3~

Voltage Restrain

E 1506 51-1 Trip

on/off

VR_EN

VR_EN

Reclose

P 1506 51-1 Delay

1511 Reset Char.

P 1507 51-2 Pickup

ANSI 79 Reclose

E 1502 51-TOC Trip

on/off

I

VR_EN

P 1505

≤1

TMS

P 1503 IDMT Curve

P 1510 51-3 Delay

&

E 1510 1511 Reset Char.

51-3 Trip

on/off Reclose

on/off

Figure51-2: Logic diagram for the AC time overcurrent protection

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 104/149 -

Service Manual 3.16. ANSI 51G/N – AC time ground overcurrent relay

Inverse time overcurrent protection 51G/N contains ANSI characteristic curves (IDMT). The permissible setting range of this relay is depending on the ordered hardware. Refer to the order information to get the right internal current transformers for your application. HIMAP parameters: ANSI 51G/N AC time ground overcurrent 1520. 1521. 1522. 1523. 1524. 1525. 1526. 1527. 1528.

Time ground overcurrent: ON – Limit [ 1000]A: 100.0 % - Time multiplier (TMS): 1.00 s - Curve shape : very inv. - Reset characteristic : def./Th – Reset character (Th) : 0 s - Pickup type (51G/N) :meas.Ignd1 reserved reserved

BACK

Permissible setting range: ON / OFF 2.0……999.9 % 0.01…10 sec 8 curve shapes (IDMT) none,def./Th,dep.,curve D-F 0…………99 sec meas.Ignd1/meas.Ignd2/calculated

EXIT

Figure 51-3: ANSI 51G/N

Parameter description: [1520. Time ground overcurrent :] If the AC time ground overcurrent relay should be activated, set it to ON; if not, to OFF. [1521. - Limit [ xxxx]A :] Limit setting of AC time ground overcurrent. If the actual measured value exceeds this limit, Event 1521 will be set. [1522. - Time multiplier (TMS) :] Time multiplier setting for the corresponding curve shape (see Parameter1523). If Event 1521 is active and the delay time calculated with the time multiplier and the chosen curve shape is passed, the Event 1522 will be activated as long as the actual value falls below the limit of Parameter 1521. Please use this parameter for the alarm or output controller. [1523. - Curve shape :] Curve shape selection of AC time ground overcurrent. Eight curve shapes (normal inverse, very inverse, extremely inverse, curve D-F, INV-K and VINV-K) can be selected (see appendix XXL). [1524. - Reset characteristic :] Reset characteristic of time overcurrent relay. If the calculated delay time is in process and the actual measured current value falls below the limit of Parameter 1521, then a special reset characteristic for the actual calculated delay time can be set with this parameter. The following characteristics are available: none, def./Th, depending, curve DF (see also appendix XXs). HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 105/149 -

Service Manual

[1525. - Reset character (Th) :] Holding time for reset characteristic if Parameter 1524 is set to “def./Th”. If the calculated delay time is in process and the actual measured current value falls below the limit of Parameter 1521, then the calculated delay time is hold for this time. [1526. - Pickup type (51G/N) :] Two different types of the AC time ground overcurrent pickup can be selected. The first one is measured and the second is calculated. [1527. - reserved

:]

[1528. - reserved

:]

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 106/149 -

Service Manual 3.17. ANSI 51LR – Locked Rotor

HIMAP parameters: ANSI 51LR 1540. 1541. 1542. 1543. 1544.

– – – –

Locked rotor (motor)

Locked rotor relay : ON Starting current : 300.0 % Starting time : 10.0 s Locked rotor current: 200.0 % Locked rotor time : 8.0 s Tm (calculated)= 1.00 sec

BACK

Permissible setting range: ON / OFF 10…999.9 % 0.1…999.9 sec 10…999.9 % 0.1…999.9 sec calculated from [1541] & [1542]

EXIT

Figure 51-4: ANSI 51LR

Parameter description: [1540. Locked rotor relay :] If the locked rotor protection should be activated, set it to ON; if not, to OFF. [1541. – Starting current :] During starting phase of the motor, the current will be limited with extremely inverse characteristic. The time multiplier Tm (see figure51-5 below) will be calculated with the starting current (1541) and the starting time (1542). The trip time formula for the extremely inverse characteristic is:

( parameter[1541] / In ) − 1 80 t = Tm * ⇒ Tm = parameter[1542] * 2 80 (I / In ) − 1 2

Tm value will be displayed in the last line. [1542. – Starting time :] Because of the starting time, the time multiplier will be calculated. (see Parameter 1542). The stating phase will be limited by two times this setting. Use the event 1542 for a binary output or an alarm. [1543. – Locked rotor current :] During the running state of the motor, the trip time characteristic is definite. If the actual measured value exceeds this limit, Event 1543 will be set. [1544. – Locked rotor time :] Time delay of Event 1543. If Event 1543 is active and this delay time is passed, the Event 1544 will be activated as long as the actual is higher than the limit of Parameter 1543. Use this parameter for an alarm or output controller.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 107/149 -

Service Manual

Extremely Inverse Trip Time Characteristic t[ S]

100000 10000

51 LR Motor state: Starting

1000 100 10 Starting time Param. [1542]

1

0,1 0,01 1

2

Start current Param. [1541]

10

20

P.U

Figure 51-5: Inverse time characteristic during starting phase. The extremely inverse curve for trip time will be defined by Parameters [1541] & [1542].

51LR Trip Time Characteristics 10000

1000 51 LR Motor state: Running

100

10 51 LR current Param.[1543]

1

0,1

0,01 1

2

51LR time Param. [1544]

6

PU

Figure 51-6: Definite time characteristic during running state of the motor. The time characteristic will be defined by Parameters [1543] & [1544].

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 108/149 -

Service Manual 3.18. ANSI 59 – Overvoltage relay

The overvoltage relay operates when the actual measured voltage is more than a predetermined value. It prevents insulation failure by protecting against abnormally high voltage levels. Abnormally high voltages often occur in low-loaded long distance transmission lines, in isolated systems when generator voltage regulation fails, or after full-load shutdown of a generator from the system. HIMAP parameters:

1600. 1601. 1602. 1603. 1604. 1605. 1606. 1607.

ANSI 59 Overvoltage relay

Permissible setting range:

Overvoltage relay : ON - 1. Limit value : 110.0 % - Time multiplier (TMS): 1.00 sec - Curve shape : definite reserved : - 2. Limit value : 110.0 % - Delay time (definite): 1.00 sec reserved :

ON / OFF / reclose 1……999.9 % 0.01…10 sec normal inverse / definite

BACK

1……999.9 % 0.01…999.99 sec

EXIT

Figure59-1: ANSI 59

Parameter description: [1600. Overvoltage relay :] If the overvoltage relay should be activated, set it to ON; if not, to OFF. If it is set to RECLOSE, it will close the breaker according to the setting of ANSI 79. [1601. - 1. Limit value :] First overvoltage limit. The activation of this limit value depends on the curve shape selection of Parameter [1603]: “normal inverse”: If the actual measured voltage value plus 5% (k-factor) exceeds this limit, Event [1601] will be set. “definite”: If the actual measured voltage value exceeds this limit, Event [1601] will be set. No k-factor will be calculated. [1602. - Time multiplier (TMS) :] Delay time setting for overvoltage 1. limit. The characteristic of the delay time depends on the curve shape selection of Parameter [1603]: “normal inverse”: If normal inverse curve shape is selected, this parameter will be used as time multiplier. “definite”: if the curve shape is set to definite and if Event [1601] is active, then a definite delay time will be activated. Please use this parameter for the alarm or output controller. HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 109/149 -

Service Manual [1603. - Curve shape :] Curve shape selection of overvoltage. One curve shape (normal inverse) and one definite limit can be selected. Parameter [1602] is the time multiplier if the normal inverse curve is selected. If this parameter is set to “definite,” then a definite time delay can be activated. [1604. - reserved

:]

[1605. - 2. Limit value :] Second overvoltage limit. If the actual measured value exceeds this limit, Event [1605] will be set. [1606. - Delay time (definite) :] Time delay of Event [1605]. If Event [1605] is active and this delay time is passed, the Event [1606] will be activated as long as the actual value falls below the limit of Parameter [1605]. Please use this parameter for the alarm or output controller. [1607. - reserved :]

ANSI 59 off on reclose

„1“

or

E 1600

P 1602

59 active E 1601 Limit reached

or

TMS

ANSI 79 Reclose

P 1603 IDMT Curve

P 1601 59-1 Pickup

&

U>

E 1602 59-1 Trip

on/off

3~

Reclose

E 1605 Limit reached

P 1606 59-2 Delay

P 1605 59-2 Pickup

&

U >>

0 |

T |

E 1606 59-2 Trip on/off

3~

Reclose

ANSI 59N off on reclose

„1“

or

E 1610

59N active

E 1611 Limit reached

P 1612 59N Delay

P 1611 59N Pickup

U>

&

0 |

3~

T |

E 1612

59-N Trip

on/off Reclose

Figure59-2: Logic diagram for the overvoltage protection

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 110/149 -

Service Manual 3.19. ANSI 59B – Bus overvoltage relay

There are two independent overvoltage relays for the Bus 1 and Bus 2 measure inputs available. The overvoltage relay operates when the actual measured voltage is more than a predetermined value. It prevents insulation failure by protecting against abnormally high voltage levels. Abnormally high voltages often occur in low-loaded long distance transmission lines, in isolated systems when generator voltage regulation fails, or after full-load shutdown of a generator from the system. HIMAP parameters: ANSI 59B Bus overvoltage relay 1610. BUS1 overvoltage relay : 1611. - Overvoltage 1.limit : 1612. - Delay time(definite): 1613. - Overvoltage 2.limit : 1614. - Delay time(definite): 1620. BUS2 overvoltage relay : 1621. - Overvoltage 1.limit : 1622. - Delay time(definite): 1623. - Overvoltage 2.limit : 1624. - Delay time(definite): BACK

ON 103.0 % 8.0 sec 110.0 % 3.0 sec OFF 103.0 % 8.0 sec 110.0 % 3.0 sec EXIT

Permissible setting range: ON / OFF 0.0……999.9 0.0……999.9 0.0……999.9 0.0……999.9 ON / OFF 0.0……999.9 0.0……999.9 0.0……999.9 0.0……999.9

The parameters for the Bus 1 and Bus 2 relay differs only in the parameter numbers, so in the following only the Bus 1 parameters are described: [1610. BUS1 overvoltage relay :] The enable switch for the overvoltage relay. [1611. - Overvoltage 1. limit :] First limit of the set point for overvoltage. This event number can be used for an alarm prewarning. [1612. - Delay time (definite ) :] Time delay of Event 1611. Use the event 1612 to activate an binary output and an alarm. [1613. - Overvoltage 2. limit :] Second limit of the set point for overvoltage. This event number can be used for an alarm prewarning. [1614. - Delay time (definite ) :] Time delay of Event 1613. Use the event 1614 to activate an binary output and an alarm.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 111/149 -

Service Manual 3.20. ANSI 64 / 59N – Overvoltage ground relay

Ground detector relay is a relay that operates on failure of machine or other apparatus insulation to ground. Sensitive ground fault detection may be used in isolated or compensated systems to detect ground faults. In solidly or low-resistance grounded systems, sensitive ground fault detection is used to detect high impedance ground faults. Sensitive ground fault detection may be used for alarming and acoustic signaling, or may be allowed to initiate tripping. Programmable timers are supplied to supervise the alarming and tripping. For this protection function, HIMAP must be equipped with a sensitive input transformer. Because of its high sensitivity, ground fault detection is not suited for detection of high magnitude ground faults. The directional and nondirectional overcurrent protection functions are preferred for this application. ANSI 64/59N Overvoltage ground relay 1700. 1701. 1702. 1703. 1704. 1705. 1706. 1707. 1708. 1709. 1710.

Ground detector relay : OFF - Limit value Ugnd1 : 100,0 % - Delay time (definite): 10,0 sec reserved: - Limit value Ugnd2 : 100,0 % - Delay time (definite): 10,0 sec reserved: Overvoltage relay [59N]: OFF - 1.Limit value : 110,0 % - Delay time (definite): 1,00 sec reserved: BACK

Permissible setting range: ON / OFF / reclose 0,1…999,9 % 0,1…999,9 sec 0,1…999,9 % 0,1…999,9 sec ON / OFF / reclose 0,1……999,9 % 0,01…999,99 sec

EXIT

Figure: ANSI 64

Parameter description: [1700. Ground detector relay :] If the ground detector relay should be activated, set it to ON; if not, to OFF. [1701. - Limit value Ugnd1 :] First limit setting of ground overvoltage. [1702. - Delay time (definite) :] Time delay of Event 1701. Use this event to activate an output. [1704. - Limit value Ugnd2 :] Second limit setting of ground overvoltage. [1705. - Delay time (definite) :] Time delay of Event 1704. Use this event to activate an output. [1707. Overvoltage relay [59N] :] If the overvoltage relay should be activated, set it to ON; if not, to OFF. [1708. - 1. Limit value :] Limit setting of definite residual overvoltage. The voltage will be calculated from the measured three-phase system. [1709. - Delay time (definite) :] Time delay of Event 1708. Use this event to activate an output.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 112/149 -

Service Manual 3.21. ANSI 66 – Start Inhibit for Motors ANSI 66 Start inhibit for motors 1720. 1721. 1722. 1723. 1724. 1725.

Start inhibit relay : - Allow time : - Allowed starts : - Limit time : - Thermal limit (0d): – Event for SI

OFF 30,0 min 2 20,0 min 55 %

BACK

Permissible setting range: ON / OFF 1…999 min 1…50 1…999 min 1…100 %

EXIT

Figure: ANSI 66

[1720. Start inhibit relay :] If the start inhibit relay should be activated, set it to ON; if not, to OFF. [1721. - Allow time :] Defines the period of time in which a number of start attempts are allowed. [1722. - Allowed starts :] Number of starts which are allowed within the period of time (Parameter 1712). [1723. - Limit time :] After the last motor start, the limit time has to be passed before a new start is allowed. [1724. - Thermal limit (0d) :] If the thermal load of the motor is higher then this thermal limit, no further start attempt is allowed. [1725. - Event for SI :] If one of the above conditions for start inhibit (setting 1721-1723) is fulfilled, Event [1725] start inhibit will be activated and the [SI] – window in the LCD-display will appear.

Notice: The Events 1721, 1723 and 1724 are only listed in the event history after Event 1725 is active and the “ON”- key is pressed.

Actual number of starts ≥ Allowed starts / allow time

≥1

Start Inhibit [SI] Event[1725]

Limit time (1723) after last start attempt active Actual thermal load > thermal limit (1724)

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 113/149 -

Service Manual 3.22. ANSI 67 – AC directional overcurrent relay

AC directional overcurrent relay is a relay that functions on a desired value of AC overcurrent flowing in a predetermined direction. When the directional overcurrent stage exceeds the current setting (Parameter [1801]) and if the directional operation has been selected, then the directional criteria should activate Event [1801]. After the time delay, Event [1802] will be activated. These events can be used to activate the alarm controller and the binary outputs. The operation of the directional overcurrent stage is based on a definite time or inverse time characteristic. This mode of operation is set with Parameter [1803]. At definite time mode of operation, the operating time is set in 10msec steps. At inverse time mode of operation (I.D.M.T.), six internally standardized and two special type time/current characteristics are available. The operation stage starts if the current on one of the phases exceeds the setting value and if the phase angle between the current and base angle falls within the operation sector +/- 60° if the phase angle is selected at Parameter [1807]. The directional control is based on measuring the phase current and the phase voltage. The phase voltage is recalculated from the line voltage, which means that earth influences at the phase voltage are eliminated. HIMAP parameters: ANSI 67 AC directional overcurrent 1800. 1801. 1802. 1803. 1804. 1805. 1806. 1807. 1808.

AC dir.overcurrent [67]: ON – Limit value [ 1000]A: 100,0 % - Time multiplier (TMS): 1,00 s - Curve shape : very inv. - Reset characteristic : def./Th – Reset character. (Th): 0 sec – Current direction : reverse – Phase angle :0 ° – Voltage low limit : 8 %

BACK

Permissible setting range: ON / OFF 0,1……999,9 % 0,01…10 sec normal inverse…curve F +definite none,def./Th,dep.,curve D-F 0…………99 sec reverse / forward / angle -180…+180° 0…999 %

EXIT

Figure: ANSI 67_1

Parameter description: [1800. AC dir. overcurrent [67] :] If the AC directional overcurrent relay should be activated, set it to ON; if not, to OFF. [1801. - Limit value [xxxx]A :] Limit setting of AC directional overcurrent relay. If one of the three phase currents (I1-I3) exceeds this limit, Event [1801] will be activated.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 114/149 -

Service Manual [1802. - Time multiplier (TMS) :] Delay time for directional overcurrent. Depending on Parameter [1803], this parameter can be used as time multiplier for inverse time characteristics or for definite delay time. Time multiplier: If Event [1801] is active and the delay time calculated with the time multiplier and the chosen curve shape (Parameter [1803] )is passed, then Event [1802] will be activated as long as the actual value falls below the limit of Parameter [1801]. Definite delay time: If Event [1801] is active and this definite delay time is passed, then Event [1802] will be activated as long as the actual value falls below the limit of Parameter [1801]. Please use Parameter [1802] for the alarm or output controller. [1803. - Curve shape :] Curve shape selection of AC directional overcurrent. Eight curve shapes (normal inverse, very inverse, extremely inverse, curve D-F, INV-K and VINV-K) can be selected (see appendix XXL). [1804. - Reset characteristic :] Reset characteristic of AC directional overcurrent relay. If the calculated delay time has been activated and the actual measured current value falls below the limit of Parameter [1801], then a special reset characteristic for the actual calculated delay time can be set with this parameter. The following characteristics are available: none, def./Th, depending, curve D-F (see also appendix XXs). [1805. - Reset character. (Th) :] Holding time for reset characteristic if Parameter [1804] is set to “def./Th”. If the calculated delay time has been activated and the actual measured current value falls below the limit of Parameter [1801], then the calculated delay time will be on hold for this time. [1806. - Current direction :] The operational direction of the directional stage can be selected to be “forward,” “reverse” or “angle,” which means the operational sector will be defined with the angle definition of Parameter [1807] +/-60°. U1

Non operational

U2

IL1

U1

Forward direction

Sector

Reverse direction

U3

Figure 67_2: Operation sector when Parameter [1806] is set to “reverse”

HYUNDAI HIMAP

IL1

U2

Non operational Sector

U3

Figure 67_3: Operation sector when Parameter [1806] is set to “forward”

HIMAP_ServiceManual_E.doc

- 115/149 -

Service Manual

-60°

U3

U1

IL1

Non operational Sector

φParam.[1807] = -45°

+60°

U2

Figure 67_4: Operational sector when Parameter [1806] is set to “angle” and Parameter [1807] is set to -45°

[1807. - phase angle :] If the operational direction of the directional stage is selected with “angle”. The operational sector is defined with this parameter +/- 60°. [1808. – voltage low limit :] Minimum voltage for relay operation. To secure a reliable relay function, the voltage limit of this parameter must be exceeded to activate the protection function and to determine the angle between voltage and current.

Trip criteria for ANSI 67 Phase current > Parameter [1801]

≥1

Phase current within operating area Parameter [1806] Phase voltage > Parameter [1808]

Delay time Parameter [1802]

ANSI67 tripped Event[1802]

Figure 67_5: criteria for ANSI 67 trip

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 116/149 -

Service Manual

ANSI 67-TOC off

„1“

on

P 1801

67-TOC Pickup

P 1806

67-TOC Direction

3~

E 1800 67-TOC active

P 1802

E 1801 Limit reached

P 1803 IDMT Curve

TMS

&

E 1802 67-TOC Trip

VR_EN

„1“ Voltage Restrain

P 1804 Reset Char.

on/off

P 1805 Reset Char. Th

ANSI 67 N/G/Gs off on

„1“

E 1808 67 N/G/Gs active

P 1809 67 N/G/Gs Pickup

P 1810

P 1814 67 N/G/Gs Direction P 1815

67 N/G/Gs Type

E 1809 Limit reached

TMS

P 1811 IDMT Curve

&

E 1810

67 N/G/Gs Trip

3~

P 1812 Reset Char. P 1813 Reset Char. Th

Figure 67_6: Logic diagram for the AC directional overcurrent protection

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 117/149 -

Service Manual 3.23. ANSI 67GS/GD – AC directional ground overcurrent relay

The AC directional ground overcurrent relay is a relay that functions on a desired value of AC ground overcurrent flowing in a predetermined direction. HIMAP parameters: ANSI 67GS/GD AC dir. ground overcurrent

Permissible setting range:

1810.AC 1811. 1812. – 1813. 1814. – 1815. – 1816.AC 1817. 1818. – 1819. 1820. – 1821. –

ON / OFF 0.1……6000.0 0.1……6000.0 0.01…99.99 1……999 0……360° ON / OFF 1……9999 1……9999 0.01…99.99 1……999 0……360°

direction. [67GS] : ON Limit value [Ignd1] : 1.5 mA Max. limit (no dir.) : 4.0 mA Delay time (definite): 1,00ec Volt. low limit [Vo1]: 10 % Phase angle [+/-60] :55 deg direction. [67GD] : ON Limit value [Ignd2] : 80 mA Max. limit (no dir.) : 120 mA Delay time (definite): 1,00ec Volt. low limit [Vo1]: 10 % Phase angle [+/-60] : 55 deg BACK

mA mA sec % mA mA sec %

EXIT

Figure: ANSI 67GS_1

Parameter description: [1810. AC direction.[67GS/GD] :] If the AC dir. ground overcurrent relay should be activated, set it to ON; if not, to OFF. [1811. - Limit value [Ignd1] :] Limit setting of AC directional ground overcurrent. The unit of this limit is [mA] instead of a percentage. Through this unit very small values can be set (e.g. if a ZCT is in use). If the ground current exceeds this limit value, Event [1811] will be activated. [1812. - Max. limit value [no dir.] :] Maximum limit setting of AC directional ground overcurrent. If the ground current exceeds this limit value, Events [1811] and [1812] will be activated. These events will in turn activate the Delay Timer [1813] without checking the directional conditions. To disable the maximum limit supervision set this parameter to zero. [1813. - Delay time (definite) :] The delay timer for the directional ground overcurrent relay will be activated if the following criteria are fulfilled: o The ground (neutral) current exceeds the limit value of Parameter [1811]. o The ground (residual) voltage exceeds the limit value of Parameter [1814]. o The phase angle φ is within the operating range given with Parameter [1815] +/-60°. The timer will also be activated when the ground current exceeds the limit value of Parameter [1812]. If the delay time is passed, then Event [1813] will be activated as long

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 118/149 -

Service Manual as the above criteria are fulfilled. Please use this parameter for the alarm or output controller. [1814. – volt. Low limit [Vo1] :] Limit setting for ground voltage. If the ground voltage exceeds this limit, the protection relay will be activated. To secure reliable relay operation at extremely low ground voltage, a memory function has been implemented. At sudden loss of ground voltage in a fault situation, this memory function gives the directional stage an additional 3 seconds time to operate after loss of voltage (ground voltage below Parameter [1814]). [1815. – Phase angle [+/-60°] :] Definition of the operating area of the directional ground current relay. The operating area is defined by this phase angel (Io to Uo) plus 60° degrees in both directions. If the actual phase angle of the ground current in relation to the ground voltage is within the operating area, then the protection relay will be activated (see also following diagram ).

ANSI 67 [DGR/SGR] Operation area U0

U0 I0 φ p[1815]

φ non operational Sector

I0

±60°

I0 LIMIT [1811]

±60° non operational Sector

Figure 67GS_2: Operation characteristic when the phase angle φp = +90°

I0 LIMIT [1811]

Figure 67GS_3: Operation characteristic when the phase angle φp = 0°

[1816 –1821]

These parameters are not available at present.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 119/149 -

Service Manual 3.24. ANSI 78 – Vector surge/ dF/dt supervision relay

HIMAP parameters: ANSI 78 Vector surge supervision 1840. Vector surge superv. : 1841. - limit for phase jump : 1842. - current increase : 1843. reserved: 1844. – minimum voltage : 1845.dF/dt supervision dF/sec: 1846. – delay time (definite):

BACK

Permissible setting range:

ON

ON / OFF 0………360 deg 0.0…999.9 %

90.0 % 5.00 Hz 0.10 sec

0.0……99.9 % 0.00…99.99 Hz 0.00…99.99 sec

0 deg 0.0 %

EXIT

Figure: ANSI 78

Parameter description: [1840. Vector surge superv. :] To activate the vector surge supervision, set Parameter [1840] to ON; otherwise, to OFF. [1841. - limit for phase jump :] If a phase jump higher than the limit set in Parameter [1841] is detected, than Event [1841] will be activated. This event triggers the current flow check. Do not use this event to activate a relay output, since the active state of this event is too short. If no current increase check is needed, use Event [1842] for activating a relay output. In this case, set Parameter 1842 to zero. [1842. - current increase :] After a phase jump (Event [1841]) is detected, the current flow check will be activated. If this parameter is set to zero, Event [1842] will be activated immediately. Otherwise if the current flow after the following cycle exceeds the limit set in Parameter [1841], then Event [1842] will be activated. Use this event number to activate a relay output. [1843. reserved Not in use.

:]

[1844. - minimum voltage :] If the feeder voltage exceeds the limit set in Parameter [1844], then the vector surge supervision (Parameters [1841 & 1842]) and the dF/dt supervision (Parameters [1845 & 1846]) will be activated after a two seconds delay.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 120/149 -

Service Manual [1845. dF/dt supervision dF/sec: :] Limit value for the dF/dt supervision. If the frequency changes per second exceed the limit value set in Parameter [1845], Event [1845] will be activated as long as the frequency changes are below this limit. The dF/dt supervision can be switched off if this value is set to zero. Example: The allowed frequency change per 100msec is 0.5 Hz. That means the frequency change per second is 5Hz. This limit value should be set with Parameter [1845]. [1846. - Delay time (definite) :] Time delay of Event [1845]. If Event [1845] is active and this delay time is passed, the Event [1846] will be activated as long as the actual value falls below the limit of Parameter [1845]. Please use this parameter for the alarm or output controller.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 121/149 -

Service Manual 3.25. ANSI 78 S Out of step tripping

1850. 1851. 1852. 1853. 1854. 1855. 1856. 1857. 1857.

ANSI 78 S Out of step tripping

Permissible setting range:

Out of step tripping : – min. active power Po : reserved: – pick up value P-Po : – reserved: – number of periods : – reserved: –Holding time of pickup: –Time integrator for Po:

ON 20,0 %

ON / OFF 0,0…99,9 %

5,0 %

0,0…99,9 %

4

0…10

BACK

60,0 sec 60,0 sec

0,1…999,9 sec 0,1…999,9 sec

EXIT

Figure: ANSI 78 P

[1850. Out of step tripping] The relay enable switch.

HYUNDAI HIMAP

(in preparation)

HIMAP_ServiceManual_E.doc

- 122/149 -

Service Manual 3.26. ANSI 79 – AC reclosing relay

AC reclosing relay is a relay that controls the automatic reclosing and locking out of an AC circuit breaker. From experience, the majority of faults associated with overhead distribution feeders are temporary in nature. Therefore, to maximize service availability, it is desirable to employ a system that will close the circuit breaker shortly after it is tripped. This is accomplished in the HIMAP via the automatic reclosing system. When the automatic reclosing system is used, if the fault still exists after the circuit breaker has been reclosed, then the protective elements will retrip the circuit breaker. Depending on the number of reclosing attempts programmed for the automatic reclosing system (up to nine are possible), the circuit breaker will either be reclosed again, or it will remain open. The automatic reclosing function is typically utilized only in situations in which the occurrence of temporary faults is anticipated. Therefore, the automatic reclosing system is not applied when the HIMAP is used to protect generators, motors, transformers, and cables. The automatic reclosing function can also be initiated by an external protection relay. For this application, an output contact from the tripping relay must be wired to a binary input of the HIMAP. It is also possible to allow the HIMAP to work in conjunction with an external reclosing device. Initiation of the automatic reclosing function can be caused by internal protective functions or externally using a binary input. Each of the following elements may initiate the automatic reclosing function: ANSI 50-1, 50-2, 50-r, 51, 46-1, 46-2, 46-TOC The automatic reclosing system can be programmed so that any of the elements above can initiate, not initiate, or block reclosing. If an element initiates reclosing, the appropriate reclosing program is executed. HIMAP parameters: Permissible setting range:

ANSI 79 AC reclosing relay 1900. AC reclosing relay : 1901. - Reclaim time : 1902. - Reclosing trials : 1903. - 1. Reclosing time : 1904. - 2. Reclosing time : 1905. - 3. Reclosing time : 1906. - 4. Reclosing time : 1907. - 5. Reclosing time : 1908. - 6. Reclosing time : 1909. - 7. Reclosing time : 1910. - 8. Reclosing time : 1911. - 9. Reclosing time : 1913. – Blocking via event : 1913. - Initiate via event : 1914. – CB reclose event 1915. –Reclose event duration: 1916. –Reclose success event 1917. –Reclose fail event BACK

ON 20,0 3 250 3,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0 0

sec ms sec sec sec sec sec sec sec sec

100 ms

ON / OFF 0,1…999,9 0………999 0………9999 0,1…999,9 0,1…999,9 0,1…999,9 0,1…999,9 0,1…999,9 0,1…999,9 0,1…999,9 0,1…999,9 Event no. Event no.

sec ms sec sec sec sec sec sec sec sec

0……9999 ms

EXIT

Figure: ANSI 79

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 123/149 -

Service Manual Parameter description: [1900. AC reclosing relay :] If the AC reclosing relay should be activated, set it to ON; if not, to OFF. [1901. - Reclaim time :] The reclaim time is the setting of the maximum time of the whole reclosure attempt. [1902. - Reclosing trials :] Setting of the maximum numbers of reclosure shots. [1903. - 1. Reclosing time :] Setting of the first reclosing time. [1904. - 2. Reclosing time :] Setting of the second reclosing time. [1905. - 3. Reclosing time :] Setting of the third reclosing time. [1906. - 4. Reclosing time :] Setting of the forth reclosing time. [1907. - 5. Reclosing time :] Setting of the fifth reclosing time. [1908. - 6. Reclosing time :] Setting of the sixth reclosing time. [1909. - 7. Reclosing time :] Setting of the seventh reclosing time. [1910. - 8. Reclosing time :] Setting of the eighth reclosing time. [1911. - 9. Reclosing time :] Setting of the ninth reclosing time. [1912. - Blocking via event :] The breaker reclosure command can be blocked by entering the belonging event number. All other functions of ANSI 79 are active. [1913. - Initiate via event :] A reclosure shot can be initiated by entering the selected event number. That is only possible when the reclose time is active only. [1914. - CB reclose event :] This event will drive the breaker over a binary output. [1915. - Reclose event duration :] The duration is responsible for the length of pulse time of the reclosure shot.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 124/149 -

Service Manual

Trip Command CLOSE

Breaker Status

OPEN

Reclosing Command 1. Reclosing Time

duration [1915] 2. Reclosing Time

ReclaimTime

Figure: Timing diagram for a second successful reclosure

Trip Command CLOSE

Breaker Status

OPEN

Reclosing Command 1. Reclosing Time

duration [1915] 2. Reclosing Time

ReclaimTime

Figure: Timing diagram for two unsuccessful reclosing shots

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 125/149 -

Service Manual 3.27. ANSI 81 – Frequency relay

Frequency relay is a relay that responds to the frequency of an electrical quantity and operates when the frequency or rate of change of frequency exceeds or is less than a predetermined value. The frequency is measured from the feeder voltage. The frequency protection function detects abnormally high and low frequencies in the system. If the frequency lies outside the allowable range, appropriate actions are initiated, such as load shedding or separating a generator from the system. A decrease in system frequency occurs when the system experiences an increase in the real power demand, or when a malfunction occurs with a generator governor or automatic generation control (AGC) system. An increase in system frequency occurs when large blocks of load are removed from the system, or again when a malfunction occurs with a generator governor or AGC system. Through the use of filters and repeated measurements, the frequency evaluation is free from harmonic influences and very accurate. Frequency protection consists of four frequency elements. Two given frequency element can be set to pickup for overfrequency and two for underfrequency conditions. Each element can be independently set, and utilized to perform different functions within the system. The frequency can be determined as long as the positive sequence voltages are present and of sufficient magnitude. If the measurement voltage drops below a settable value, Parameter [2012], then frequency protection is blocked. For elements used in an underfrequency protection mode, as soon as the frequency of the measured voltage decreases below the setting, the element picks up and remains picked up until the system frequency increases above the setting. For elements used in an overfrequency protection mode, as soon as the frequency of the measured voltage increases above the setting, the element picks up and remains picked up until the frequency decreases below the setting. HIMAP parameters:

2000. 2001. 2002. 2003. 2004. 2005. 2006. 2007. 2008. 2009. 2010. 2011. 2012.

ANSI 81 Frequency relay

Permissible setting range:

Frequency relay : OFF Overfreq. 1.step limit : 102,0 % - Delay time (definite): 4,0 sec reserved: Overfreq. 2.step limit : 104,0 % - Delay time (definite): 2,0 sec reserved: Underfreq. 1.step limit: 98,0 % - Delay time (definite): 4,0 sec reserved: Underfreq. 2.step limit: 86,0 % - Delay time (definite): 2,0 sec Undervoltage blocking : 0,0 % !

ON / OFF 100,0…199,9 % 0,1…999,9 sec

BACK

100,0…199,9 % 0,1…999,9 sec 0,1……99,9 % 0,1…999,9 sec 0,1……99,9 % 0,1…999,9 sec 0,1……99,9 %

EXIT

Figure: ANSI 81-1

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 126/149 -

Service Manual Parameter description: [2000. Frequency relay :] This parameter activates the frequency supervision, whereby: OFF: deactivates, ON: activates and CB ON: activates the frequency supervision only if the circuit breaker is switched on. [2001. Overfreq. 1.step limit :] Limit setting of definite overfrequency. [2002. - Delay time (defnite) :] Time delay of Event 2001. Use this event to activate an output. [2003. - reserved …

:]

[2004. Overfreq. 2.step limit :] Limit setting of definite overfrequency. [2005. - Delay time (defnite) :] Time delay of Event 2004. Use this event to activate an output. [2006. - reserved :] ... [2007. Underfreq. 1.step limit :] Limit setting of definite underfrequency. [2008. - Delay time (defnite) :] Time delay of Event 2007. Use this event to activate an output. [2009. - reserved ...

:]

[2010. Underfreq. 2.step limit :] Limit setting of definite underfrequency. [2011. - Delay time (defnite) :] Time delay of Event 2010. Use this event to activate an output. [2012. Undervoltage blocking :] This parameter depends on the device type. Device type BC or X: When the feeder voltage is lower than this setting, the underfrequency protection function is disabled. Device type BCG or XG: This parameter is not active, since the underfrequencye relay works when the main breaker is on; otherwise, it is blocked.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 127/149 -

Service Manual

ANSI 81 „1“

off on

P 2012

or

Setting

E 2000

81 active

Startup

U> Reset

3~

S1 R

Q E 2001 Limit reached

P 2001 81-1 Pickup

f>

&

P 2002 0 |

81-1 Delay T |

E 2002

81-1 Trip

3~

E 2004 Limit reached

P 2004 81-2 Pickup

f >>

&

P 2005 0 |

81-2 Delay T |

E 2005

81-2 Trip

3~

E 2007 Limit reached

P 2007 81-3 Pickup

f<

&

P 2008 0 |

81-3 Delay T |

E 2008

81-3 Trip

3~

P 2010 81-4 Pickup

f

E 2230 Limit reached

&

P 2232 94-3 Undervoltage Pickup

U<

0 |

E 2232 Limit reached

&

P 2231 94-3 U> Delay T |

E 2231 94-3 U> Trip

P 2233 94-3 U< Delay 0 |

T |

E 2233 94-3 U< Trip

Figure: Logic diagram for the aux. power supervision

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 140/149 -

Service Manual 3.33. ANSI 95i – Inrush blocking relay When the SYMAP® is installed to protect a power transformer, large magnetizing inrush currents will flow when the transformer is energized. These inrush currents may be several times the nominal transformer current, and, depending on the transformer size and design, may last from several milliseconds to several seconds. Although pickup of the relay elements is based only on the fundamental harmonic component of the measured currents, false device pickup due to inrush is still a potential problem since, depending on the transformer size and design, the fundamental harmonic comprises a large component of the inrush current. The SYMAP® features an integrated inrush restraint function that may be utilized when the device is installed at or near a transformer. It supervises the “normal” tripping of all directional and non-directional overcurrent relay elements with the exception of the ANSI67 and ANSI67GSGD relay elements. For example, when a transformer is energized the current levels may exceed the normal pickup of the overcurrent elements set in the device. If inrush conditions are identified (the 2nd harmonic content of current exceeds the value of setting at Parameter 2302), special inrush messages are created within the device that will block tripping of the overcurrent elements. Note, that only the tripping elements are affected by harmonic inrush detection, the pickup values and corresponding timers continue to operate normally. Inrush current contains a relatively large second harmonic component which is nearly absent during a short-circuit fault. Inrush current detection, therefore, is based on the evaluation of the second harmonic component present during inrush conditions. For frequency analysis, digital filters are used to conduct a Fourier analysis of all three phase currents and the ground current. As soon as the second harmonic component of the current flowing in a specific phase or ground relay element exceeds a set value, tripping is blocked for that element (does not apply ANSI67, and ANSI67GSGD elements). Since quantitative analysis of the harmonic components of the current flowing through a specific relay element cannot be completed until a full cycle of inrush current has been measured, inrush restraint blocking, and the associated inrush detection message, is automatically delayed by one cycle. It is important to note, however, that the tripping time delays associated with the relay elements are started immediately after pickup of the relay element, even if the inrush conditions are detected. If inrush blocking drops out during the time delay, tripping will occur when the time delay of the element elapses. If inrush blocking drops out after the time delay has elapsed, tripping will occur immediately. Therefore, utilization of the inrush restraint feature will not result in any additional tripping delays. If a relay element drops out during inrush blocking, the associated time delay will reset.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 141/149 -

Service Manual HIMAP parameters: ANSI 95i Inrush blocking relay 2300. Inrush blocking relay 2301.- limit of DC-portion 2302.– 2. harmonic content 2303.– Te extension time 2304.– Tmax blocking time 2305.– Imax blocking inrush

: OFF : 100,0 % : 30 % : 100 ms : 0,20 sec : 1600 %

BACK

Permissible setting range: ON / OFF 1,0…. 99,9 1…... 99 30…….9999 0,03…99,99 1…...2999

% % ms sec %

EXIT

Figure: ANSI 95i

Parameter description:

[2300. Inrush blocking relay :] If the inrush blocking relay should be activated, set it to ON; if not, to OFF. [2301. - limit of DC-portion :] Limit setting of DC-portion of the measured current value. [2302. - 2. harmonic content :] Limit setting of 2nd. harmonic content of the measured current value. [2303. - Te extension time :] Measuring interval for inrush check. [2304. - Tmax blocking time :] Maximum inrush blocking time. [2305. - Imax blocking inrush :] If the measured current exceeds this limit, the inrush blocking function will be switched off.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 142/149 -

Service Manual 3.34. ANSI FF – Fuse failure (voltages) There are three independent Fuse failure relays for the Gen., Bus 1 and Bus 2 voltage measure inputs available. The Fuse failure protection monitors the displacement voltage Uo and the phase voltages U1, U2 and U3. For every relay three independent limits are available. The user can define own combinations of these three limits. Limits which are not used should be set to zero. The delay will only start to run if all enabled limits are reached. Note: The Fuse failure relays should not be used for ungrounded systems.

FF Fuse failure (voltages) 2310. GENERATOR fuse failure : ON 2311. – Uo limit : 22.5 % 2312. – min voltage limit: 8.3 % 2313. – max voltage limit: 95.6 % 2314. - delay (definite) : 3.0 sec 2320. BUS 1 fuse failure : OFF 2321. – Uo limit : 30.0 % 2322. – min voltage limit: 12.0 % 2323. – max voltage limit: 97.0 % 2324. - delay (definite) : 8.0 sec 2330. BUS 2 fuse failure : OFF 2331. – Uo limit : 35.0 % 2332. – min voltage limit: 20.0 % 2333. – max voltage limit: 98.0 % 2334. - delay (definite) : 7.5 sec BACK EXIT

Permissible setting range: ON / OFF 0.0……999.9 0.0……999.9 0.0……999.9 0.0……999.9 ON / OFF 0.0……999.9 0.0……999.9 0.0……999.9 0.0……999.9 ON / OFF 0.0……999.9 0.0……999.9 0.0……999.9 0.0……999.9

The parameters for the Gen., Bus 1 and Bus 2 relay differs only in the parameter numbers, so in the following only the Gen. parameters are described: [2310. GENERATOR fuse failure] The enable switch for this Fuse failure relay. [2311. - Uo limit] This limit will be supervised if the setted value is unequal zero. The displacement voltage is calculated from the phase voltages U1, U2 and U3. The percentage is calculated from parameter 201. Example: P2311(22.5%) × P201(400V) / √3 = 51.9 V Event 2311 is activated if the displacement voltage reaches this limit and all other enabled limits are reached. [2312. - min voltage limit] This limit will be supervised if the setted value is unequal zero. The percentage is calculated from parameter 201. Example: P2312(8.3%) × P201(400V) / √3 = 19.1 V Event 2312 is activated if one of the three phase voltages U1, U2 or U3 reaches this limit and all other enabled limits are reached.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 143/149 -

Service Manual [2313. - max voltage limit] This limit will be supervised if the setted value is unequal zero. The percentage is calculated from parameter 201. Example: P2313(95.6%) × P201(400V) / √3 = 220.7 V Event 2313 is activated if one of the three phase voltages U1, U2 or U3 reaches this limit and all other enabled limits are reached. [2314. - delay (definite)] Use this event to activate an binary output and an alarm. This event is active if a combination of the three limits is logically true and the delay is passed. The enabled limits are logically ANDed. In the following all seven possible combinations of enabled limits are listed: 1 2 3 4 5 6 7

HYUNDAI HIMAP

Uo limit X

Min limit

Max limit

X X X X X

X X X

HIMAP_ServiceManual_E.doc

X X X

- 144/149 -

Service Manual

4. Alarm controller settings The alarm controller has 79 independent free-programmable alarm channels. ALARM CHANNEL EVENT – Select: - 1.line: 2.line:

LED CONTROL - ALARM : X - TRIP : - red : X - amber : - green :

06.ANSI 50-1 - Inst.1.Overcur - mode : UNLATCHED - trigger : 1402 - block by: 508 - delay 0.7sec - 1. group: 87 - 2. group: none - priority: 2 - option : none - beeper : OFF

SYSTEM

RELAY

Setting range: 1 - 79

0006

Max. 17 characters Max. 17 characters OFF,LATCHED,UNLATCHED,NO ACK

0…9999 0…9999 0.0…999.9 sec none, 80…99 none, 80…99 none,1-9 option 1-4 OFF / ON

EXIT

Figure: Alarm parameter mask

[ALARM CHANNEL EVENT – Select] Selects an alarm channel for editing. Up to 79 alarm channels can be used. [1. and 2. line] This free programmable alarm text will appear on the alarm page if the alarm is active. [mode] The following alarm modes are available: OFF: The alarm channel is disabled. LATCHED: The alarm EVENT [1-79] is active until the alarm disappears and the ACK key is pressed. UNLATCHED: The alarm EVENT [1-79] is active until the trigger event is active. NO ACK : The alarm EVENT [1-79] is active until the trigger event is active. The alarm text in the LCD disappears without ACK, if the trigger event is not longer active. [trigger] The alarm channel will be activated by this event. [block by] The alarm channel is blocked if this event is active. [delay] The alarm channel can be delayed with this time. The following logic diagram shows the context of the trigger event, the block event, the delay, and the ACK. trigger event block event

delay

&

S ACK

R

SR FF

Q

alarm active

Figure: Alarm channel logic

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 145/149 -

Service Manual [1. and 2. group] Each alarm channel can be assigned to one or two alarm groups. If one of the alarms belonging to this group is active, the corresponding group event will also be activated. A maximum of twenty alarm groups (80-99) can be created. [priority] Note: only for HIMAP XG/BCG (power management) Through the priority settings, useful attributes can be set to the corresponding alarm channels. Additional operations such as “change to manual mode,” “start the next diesel” or “stop own aggregate” will activated after the alarm appears. The following table shows all alarm priorities and the corresponding operations that are activated after appearance of the alarm.

1

2

Alarm priority 3 4 5 6

Change to manual mode Start next standby engine

X X

X X

X

Immediately Stop

X

Operation after the alarm appears

none

X

X X

X X

8

9

X X

X X

X

Normal Stop Immediately Stop after started engine tries to synchronize Normal Stop after next C.B. is closed Only open Breaker after started engine tries to synchronize Only open Breaker with load reduction after next C.B. is closed

7

X X X X

[option] (not in use yet) [beeper] • OFF: No sound when the alarm appears. • ON: When the alarm appears, the beeper will be active until the ACK key is pressed. Note: There is a special beeper Event [2918], which can be used to drive external signal devices over an binary output. [LED CONTROL] The LED control box defines the action of the alarm LEDs if the alarm occurs: • ALARM: the main alarm LED will be activated. • TRIP: the trip LED will be activated. • red, amber, green (only HIMAP BC/BCG): the multi-colored LEDs left side of the LCD screen (where the alarm text is shown) will be activated. If more than one color is marked, the LED will blink alternately in these colors.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 146/149 -

Service Manual The following graphic shows the context of the latched and unlatched conditions of the alarm channel: Alarm trigger event Alarm channel event

UNLATCHED

Alarm output Beeper Acknowledgement Alarm trigger event Alarm channel event

LATCHED

Alarm output Beeper Acknowledgement Alarm trigger event Alarm channel event

LATCHED

Alarm output Beeper Acknowledgement

The “alarm trigger event” is the event number which activates the alarm channel. The “alarm channel event” will be active as long as the alarm is acknowledged. If the “alarm channel event ” is linked to a binary output, this output will be activated in accordance to the “latched/unlatched” condition set within the alarm channel settings. The “beeper” will be activated by the “alarm trigger event” and reset after alarm acknowledgement. Note: There is a special event [2936], which becomes active if a new alarm occurs. After that this event can be reset with ACK.

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 147/149 -

Service Manual

5. Special parameter This parameter group comprises some special parameters which are only accessible through the PC – Parameter tool (Button: EXTRAS -> Special parameter). Nr. 0074 0075 0090 0091 0092 0055 0084 0054 0057 0078 0088 0060 0082 0058 0032 0033 0034

Name

Default

DISPLAY FILTER Deadband filter Frequency filter FILTER -RPM nominal/dt - analog inputs - PT 100 BINARY INPUTS Wirefault limit Oscillation limit COMMUNICATION SERIAL PORT1 -Stopbits Modbus FC3 Byte count LOCAL / REMOTE MODE Select breaker mode Change to TEST mode SPECIAL PARAMETER

2.5 20000 10.0 10.0 60.0 20 150

Unit % mHz/sec sec sec sec LSB n/sec

0.0…20.0 0…65535 0.0…999.9 0.0…999.9 0.0…6553.5 0…255 0…65535

-

1…2 1…2

Loc/Rem MANUAL

-

none…Test…Loc/Rem MANUAL…AUTOM.

-

forward…reverse none…CMA212-1

Analog inp.4-add. low limit

forward none 0.0

0.0…6553.5

CALIBRATION PARAMETER Uaux CAL. -X3/ 1, 2 Shunt1 CAL.-X2.1/18,19 Shunt2 CAL.-X2.1/20,21

100.0 100.0 100.0

% % %

0.0…999.9 0.0…999.9 0.0…999.9

Current direction(gen.)

Select extension board

1 1

Range

[0074. Deadband filter] This parameter is valid for all measure data which are outputted over the LCD, the analogous outputs and which are transferred through all communication ports. If any value falls below the setted deadband limit, the value will be reset to zero. Furthermore, if the changing of any value is below the deadband limit, the average builder (parameter 111, see chapter 2.2.) will plane the value. [0075. Frequency filter] This parameter filters the Gen., Bus 1 and 2 frequencys. Only frequency changes below the setted value (in mHz/sec) are accepted by the measuring system. [0090. FILTER -RPM nominal/dt] Note: only for HIMAP XG/BCG (power management) With this parameter the measuring system builds an average of the diesel speed. [0091. FILTER – analog inputs] With this parameter the measuring system builds an average of the analog inputs values, except the PT 100 inputs (see 2.5.). [0092. FILTER –PT 100] With this parameter the measuring system builds an average of the PT100 inputs (see 2.5.1.).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 148/149 -

Service Manual [0055. Wirefault limit] If the measured LSB value of a binary input falls below this limit, wirefault is detected (see 2.6.). [0084. Oscillation limit] If the changings of a binary input per seconds exceeds this limit, system fail 3012 will be activated (see Appendix A2). [0054. SERIAL PORT 1 - Stopbits] With this parameter the number of stopbits (1 or 2) in the transfered bytes through serial port 1 can be adjust (see 2.4.). [0057. Modbus FC3 Byte count] With this parameter the number of bytes (1 or 2) of the byte count field in function code 3 of the Modbus protocol can be adjust (see Appendix A1). [0078. Select breaker mode] With this parameter the operating (breaker) modes for the device can be selected (see chapter 2.5. in the Users manual). The following modes are available: • none: no modes selected. This can be used for HIMAP XG/BCG, because for Power management usually only the AUTO/MANU. modes are used. • Loc/Rem: the valid modes are “Local” and “Remote”. • Test: the valid modes are “Local”, “Remote”, “Test Local” and “Test Remote”. [0088. Change to TEST mode] If this parameter is setted to AUTOM. and parameter 78 to “Test” the device will switch automatically to the test mode (“Test Local” or “Test Remote”) if one breaker changes the position from IN->OUT (see chapter 2.5. in the Users manual). [0060. Current direction (gen.)] This parameter defines the direction of the generator current. [0082. Select extension board] This parameter enables the software for various extension boards. [0058. Analog input 4 – additional low limit] With this parameter the user has the possibility to set an additional low limit for analog input 4 (see chapter 2.5.). The limit is disabled if the setted value equals zero. If the value reaches this low limit, event 2935 will be set. [0032. Uaux CAL.] This parameter calibrates the Uaux measure input (see chapter 3.32.). [0033. Shunt1 CAL.] This parameter calibrates the Shunt 1 measure input (see chapter 3.32.). [0034. Shunt2 CAL.] This parameter calibrates the Shunt 2 measure input (see chapter 3.32.).

HYUNDAI HIMAP

HIMAP_ServiceManual_E.doc

- 149/149 -

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF