GU 3 2 0 A C o n t r o l l e r

Ma n u a l

CONTENT 1 . I n t r o d u c t i o n …………………………………………………………………… . ……. 2 2 . S h a p e a n d c o n n e c t i o n o f t h e c o n t r o l l e r ………………………………………. . 2 3 . O p e r a t i o n p a n e l ……………………………………………………………………. . . 5 4 . I n s t a l l a t i o n g u i d e . ……………………………………………………………. ……6 5 . I n s t r u c t i o n o f c o n t r o l a n d o p e r a t i o n ………………………………………. …. 7 6 . Me a s u r i n g d a t a ……………………………………………………………………. …. 9 7 . Wa r n i n g , P r e - a l a r m a n d St S t o p F a u l t ……………………………………………. . 1 0 8 . P a r a me t e r s s e t t i n g ……………. ……………………………………………. ……. 11 9 . L CD C D d i s p l a y a n d me me n u s y s t e m…………………………………………………. …. 1 3 1 0 . C o mm mmu n i c a t i o n f u n c t i o n ………………………………………………………. ……1 5 1 1 . P r e p a r a t i o n b e f o r e u s e ………………………………………………………. …. . 19 1 2 . T r o u b l e s h o o t i n g …………………………………………………………………. …. 22

1

PDF created with pdfFactory Pro trial version www.pdffactory.com

GU 3 2 0 A C o n t r o l l e r

1.

Ma n u a l

Introduction:

GU320a is a kind of intelligent controller of generator which adopt high grade CMOS chip. It can configure the control procedure and protection parameters of the generator, including lots of function such as measuring, controlling, protection, three remote and so on, which completely satisfied the automatic controlling requirement of different generator sets for the generator user or factory. The controller measure and display all parameters the generator output, and the rotating speed, oil pressure, temperature, DC source voltage, running time of the engine and so on. All of the voltage measured in real virtual value to ensure the accuracy of the data. Including big LCD display and menu selection for Chinese and English. The keys on the control panel are used to select the control mode, start the running procedure, display data, and modify the running protection parameters. The LED indicates the operating mode of the controller and the running state of the generator sets. LCD display each measured parameter and state. The controller is integrated closely by aluminum alloy panel and steel shell which has been spurt powder. All connection of  the controller are connected by pin-like terminal with lock, such device can be connected 、moved 、maintained and replaced easily easil y and conveniently. conveniently.

This manual is available for the generator intelligent controller cont roller GU320a GU320a only, which you should carefully read before use 2

Shape and wiring of the controller: controller:

2.1 Detail size Control panel Hatch for installation Thickness

W205mm×H156mm W186m ×H137m D68mm(unconnected)

A

1

2

3

4

B

5

6

7

8

R S - C ON ON N E C T OR OR

C

NOTE

9 1 0 11 1 2 1 3 14 1 5 1 6

D

17 1 8 1 9 20 2 1 2 2 23 2 4 2 5 26 2 7 28

The shell of the controller should be grounded to earth, surge of the electricity system and transient shock to the meter can be reduced by the perfect low ground impedance. Running temperature of the controller controller -20~50 ℃ Storage temperature temperature of the controller controller -40~80 ℃ 2

PDF created with pdfFactory Pro trial version www.pdffactory.com

GU 3 2 0 A C o n t r o l l e r

Ma n u a l

2.2 Connection port : Pin NO.

Function Function

Signal

Line

A1

phase A V input

0-300VAC 0-300 VAC

1mm² line

A2

Phase B V input

0-300VAC 0-300 VAC

1mm² line

A3

Phase C V input

0-300VAC 0-300 VAC

1mm² line

A4

N zero line

B5

A phase A input {S1}

0-5A(AC)

1mm² line

B6

B phase A input {S1}

0-5A(AC)

1mm² line

B7

C phase A input {S1}

0-5A(AC)

1mm² line

B8

Current input common common {S2}

0-5A(AC)

1mm² line

C9

Relay output common common

C10

Fuel electromagnetic valve relay output

N.O dry contact, 10A/30VDC

1.5mm² line

C11

Start relay output

N.O dry contact, 10A/30VDC

1.5mm² line

C12

Exciter source of charger output

Forbid to cathode when no use

1mm² line

C13

Gen. Set running output

N.O dry contact,3A/30VDC

1mm² line

C14

Fault alarm output

N.O dry contact,3A/30VDC

1mm² line

C15

Pre-alarm output

N.O dry contact,3A/30VDC

1mm² line

C16

Idle output

N.O dry contact,3A/30VDC

1mm² line

D17

Pressure detection

P-sensor

1mm² line

D18

Temperature detection

T-sensor

1mm² line

D19

standby

Measure 0~5Vdc

1mm² line

D20

Pressure signal

Low potential valid

1mm² line

D21

Temperature signal

Low potential valid

1mm² line

D22

E.stop signal

Low potential valid

1mm² line

D23

Start (external control) signal

Low potential valid

D24

Standby signal measure

Low potential valid

1mm²line

D25

Magnetic sensor signal{+}

1-35Vac

Two-core

D26

Magnetic sensor signal{-}

connected to cathode of the DC source

shield

1mm² line

1.5mm² line

inside D27

Operating source {+}

D28

Operating source {-}

12V/24V (8-35VDC)

3

PDF created with pdfFactory Pro trial version www.pdffactory.com

1mm² line 1mm² line

GU 3 2 0 A C o n t r o l l e r

Ma n u a l

2.3 Typical wiring diagram     r     o     s     n      )      e      P     s      U        d      K     e      C     e      I     p      P      S      ( 

   R    O    T   C   E   N   N    O    C   S   R

    y      l     r     e     p     o     r     p

     6      2      5      2

     9      1

     h     t     r     a     e

   )   c  d   V  5      ~   0       (   y  b  d  n  a t   S

     8      1

  r  o  s  n  e  s  -   T

     7      1

    o     t

  r  o  s  n  e  s  -   P      4      2

   )   y  b  d  n  a t  s      (

     3      2

 t  r  a t  s   e t  o   m  e   R

     2      2

  p  o t  s .   E

     1      2

    t     s     u     m

  e  r  u  s  s  e  r   P

     6      1

   E  L   D I

    e      b

  e  r  u t  a  r  e  p   m  e   T

     0      2

    r     e      l      l     o     t     n     o     c

     5      1

   M    R    A  L   A .   E    R   P

     4      1

   T  L   U   A   F

     3      1

   G    N I   N    N   U    R

     d     e      d     n     u     o     r     g

    e      h     t

     1      1      )       k

     动     n     a      起     r

     0      1

     f     o

     C      (       )       l

     机      电      充

     2      1

    e      门     u      F      油

     l      l     e      h     s

     ( 

     d     n     a      )       A

     9

     ( 

     ) 

      )

     Y      L      C      P      D      P      V      U      5      S      3        X      8      U      A

      (

     1

    r     o     t     a     r     e     n     e      G

     1      F

     2

     2      F

     3

     4

     5

6

     7      2

     8      2

    y     r     e     t     t     a      b

     5     0      F     1

     4     A      F     2

   +

     ( 

     V      C      D

    e      h     t

  -

     f     o

7      8

    t     u     p     t     u     o

     3      F

    g     )      n     N      i      &      d     P      3     a     (      o      L

     G

4

PDF created with pdfFactory Pro trial version www.pdffactory.com

    e      d     o      h     t     a     c     :     e     t     o      N

GU 3 2 0 A C o n t r o l l e r

3

Ma n u a l

Operation panel

The whole Operation panel is divided into three parts: LED display for measuring parameters 、operating keys and runningstatus LED indicate。 3.1 LCD and its controlling keys

LCD with 128×64mm lattice can display multiple multiple lines of data information simultaneo simultaneously usly and additive background-light function which make operators read information whenever day or night. To turnoff the background-light, just keep pressing any key for a while. LCD and its control keys provide a friendly operating interface for operators, operators can read information and setting running parameters conveniently. conveniently.

3.2 LCD display of menu system and running state Name

Function

Entering submenu/modify submenu/modify/confirming /confirming modification Scroll up menu/ value ascend Scroll down menu/ value descend

3.3 Operating keys and LED Name

Function

AUTO key/LED The key is used for “auto-operate mode”. Running in this mode, the LED above the button will illuminate. According to the “remote control startup input signal”, the controller determines whether the generator startup or not.

MAN Key / Indicator Light The key is used for “manual-operation mode”. Running in this mode, the LED above the button will illuminate. By pressing “START” and “STOP” key, the controller will start or stop the generator.

TEST Key/ Indicator Light The key is used for testing operation mode settings. Running in this mode, the indicator light on the key on. Here, when the

remote control startup input



signal” simulated by the controller is valid, the generator startup. When it switch other mode, the generator stops.

START Key/LED The key is used for generators manually startup. And when the controller is in manual-operation manual-operation mode”, press this key to start the generator. Till the controller



performing the start procedure to the Gen set run in normal, the LED above the key on. After the Gen set running normally, the LED above the key on.

5

PDF created with pdfFactory Pro trial version www.pdffactory.com

GU 3 2 0 A C o n t r o l l e r

Ma n u a l

STOP/RESET key /LED Used to stop the generator by hand, when the controller set in “MAN” mode, this key could stop the generator. Press this key more than 2 seconds can release the fault stop lock if there is fault output. (When the controller performing the stop procedure, the indicator light above the key illuminate. If failed to stop, the light flash.)

LAMP TEST / MUTE key Alarm mute and lamp test key. Press the key more than 2 seconds, all LEDs on the panel will light. It used to test all LEDs on the panel. When Pre-alarm Pre-alarm or fault alarm occur, press this key can mute the buzzer. At the same time the light above the key illuminate. Press it again will cancel mute. If the controller still in fault, the buzzer will keep alarm.

4

Installation guide

4.1 Hatch size for for panel installation as the figure attached. Four special screws fix the controller. If the shell of the controller is installed on the body of a generator directly or other violent vibratory device, preventing device must be installed.

4.2 Connection for control line line please refer to the diagram attached and the typical wiring diagram 2.3 above. 4.3 Oil pressure and temperature sensor installation of the engine:

D1 7

D1 7 D1 8 (

D1 8

GU320a CONTROLLER

)

6

PDF created with pdfFactory Pro trial version www.pdffactory.com

GU 3 2 0 A C o n t r o l l e r

5

Ma n u a l

Control and Operation Instruction

There are three control modes: “AUTO”、 “MANUAL” and “TEST”。 5.1 Configuration for operating mode: Operation

Description

Press “AUTO” (for 2 seconds), the LED above illuminate, the controller then operating in “AUTO”

Press“MAN”key(for 2 seconds), the LED on the button will illuminate, then the controller runs in this mode.

Press “TEST” (for 2 seconds), the LED above illuminate, the controller then operating in “TEST”

NOTE: you can choose only one of the three modes. When the controller is ready Operation

Description

When the controller can’t detect the running speed, pressure, temperature of the engine, the related data will be 0, and the LCD display:

U=0V

I=0A 

P=0kW

F=0Hz

SP=0rpm

OP=0kPa

TEMP=0

Bat=24V

RUN 5.2 Start and control process Operation

Description

When the controller run in TEST, or the remote control start signal able in Auto, or press “START” in MAN, the controller begin to delay the start procedure, the light above the key will bicker.

The LCD display the count for start delay (not in “MAN” )

START

Fuel relay action, the fuel electromagnetic valve of the engine open. After delay for 200 milliseconds, the start relay active and crank begin. When the running speed of the engine reach the crank cutout speed, the controller will stop the start output and begin the safety-on delay.

CRANK

After the controller has detected the normal running speed, output voltage, pressure, temperature has been setup, and no other fault the same time, then display the parameters as right. (Scroll page for detail)

00:09 1

SAFETY-ON SAFETY-ON DELAY  00:08 U=380V

I=0A 

P=0kW

F=50Hz

SP=1500rpm

OP=465kPa

TEMP=70

Bat=24V

RUN 7

PDF created with pdfFactory Pro trial version www.pdffactory.com

GU 3 2 0 A C o n t r o l l e r

Ma n u a l

When the remote control start signal valid, the start delay will active and begin to time. During the delay, if the remote start signal invalid, start delay will instantaneously stop, the controller will stop the start procedure, and return to original state“READY ” after the time for fail to start out. During cranking or idle, if the remote control start input signal is invalid, the controller stop the followed start procedure and close all output for relay control, then stop the start process and return to original state “READY” after the time for fail to start out. Note: when cranking, the engine ignited, while the alternator output frequency reach the preset frequency, the start motor de-energized: Or de-energized the motor through the following way a、 The magnetism speed pickup device mounted on the flywheel of the engine has detected the frequency reached preset. b、 The output voltage of the alternator reach 80% of the rated voltage. c、 The low oil pressure switch of the engine open. 5.3 Fail to Start and Restart Condition: Operation

Description

During the cranking time, engine igniting is forbidden, and the controller

remains remains crank intermission, intermission, it will will not output outpu t starting signal. FAIL

CRK-RST 00:04

TO START indicator light flash.

Once the crank intermission reach, the controller will attempt to start the engine again.

CRANK

2

The phenomena above repeat again and again, until the engine reach the normal nor mal running running parameters. While starting, if any stop fault occurs, the controller cont roller will will stop controll contro lling ing output instantly until the fault eliminated eliminated and reset, then it can be operated again. 5.4 Fail to start condition: Operation

Description

When the phenomena above repeat again and again, the starting attempts exceed preset , the controller will stop controlling output. Then the LCD display:

 ALARM: START FAILURE

NOTE:

If it occurs FAIL TO START fault, the operator must check the whole “Genset” system. and confirm the fault and eliminate them, then press “ STOP/RESET ” key to unlock the fault-locking state, and reset the controller again.

5.5 Auto stop process Operation

Description

COOL When the remote start input signal is invalid, the cooling delay begin to count down, the running signal cut and the LCD then display: While the cooling delay timeout, the controller disconnect the fuel valve, and STOP count down for Fail To Stop, then the t he LCD display: While the Fail To Start timeout, if the engine still run, the controller will  ALARM: sent an alarm, and the LCD display: STOP FAILURE If the engine stop during the fail to stop permission delay, the LCD will display: READY 

02:34 00:24

When the remote control start input signal is invalid, the cool delay begin, if the remote control start input signal is valid during the delay, the cooling delay time stop instantaneously, the controller monitor each parameter again, and reset Auto running state if normal. 5.6 Stop by “MAN”

8

PDF created with pdfFactory Pro trial version www.pdffactory.com

GU 3 2 0 A C o n t r o l l e r

Ma n u a l

Operation

Description

The generator running normally, when press “STOP/RESET ” key for a while in “MAN” mode, the controller begin cooling delay to stop as the Auto stop. Press the “STOP/RESET ” key again for a while will disconnect the fuel valve, and the generator sets stop.

STOP

The The Fail To Stop time begin, the LCD display:

00:24

When the stop failed time beyond, the engine still run, the controller will  ALARM: send an alarm, the LCD will display: STOP FAILURE

The engine stop slowly during the Fail To Start permission time, and the LCD display:

READY 

5.7 The oil electromagnetic valve is the start running and stop process of the generator of normal open type.( Different from normal closed type). Start control process

When start running, oil relay of the controller take no action, no power in the oil electromagnetic valve, namely the oil electromagnetic magnet take no action. Stop control process

The control at the begging of the stop control process output oil electromagnetic valve source, oil electromagnetic valve action, the engine begin to stop. Then powered down after for the delay according to the fail to start delay setting. Other control process is the same to the engine of normal closed oil electromagnetic valve.

5.8 Idle Function While READY, the idle relay open, controller runs the start procedure, start delay begin to count down, the idle relay active the same time. When startup and the start motor open, idle delay begin to countdown (if IDLE DELAY is set 0, the idle relay will open, then begin to safety-on delay, namely the controller has no idle function). When delay time out, the idle relay will open, the safety-on time begin and after each parameter run in normal, the generator sets run.

6

Measuring display data

6.1 Electricity measuring data G e n . P h a s e  V

L1-N

L2-N

L3-N

G e n . L i n e  V

L1-L2

L2-L3

L3-L1

G e n .  A 

L1

L2

L3

Gen. HZ

HZ

G e n . K V A 

Sum of phase L1 L2 L3

Gen. KW

Sum of phaseL1 L2 L3

Gen. PF G e n . KVAr

 Average of L1 L2 L3 Sum of phase L1 L2 L3

Gen. KWh G e n . KVArh As the frequency measuring is from L1 phase of the generator, ensure no fault with this part before use.

9

PDF created with pdfFactory Pro trial version www.pdffactory.com

GU 3 2 0 A C o n t r o l l e r

Ma n u a l

6.2 Other measuring data Oi l p r e s s u r e K P a Coolant temperature Rotating speed R P M Total running time of the oil engine Battery voltage (V )

7

Obtain the data from an external sensor Obtain the data from an external sensor Obtain the data from speed sensor

h

Warning and Fault Stop

7.1 Warning (NOTE: warning is a very serious alarm state, it won’t affect the generator system operation, only

remind remind the operato o peratorr of the t he improper improper condition. When warning warning occurs, the state stat e indicator light illum illuminate, inate, but the buzzer won’t alarm and the fault won’t lock. Once the fault has been eliminated, the warning light off  automatically. C h a r g e f a i l u r e The controller detect the voltage lower than the “LOW battery pre-alarm setting” from the aux AC charger, “CHARGE FAILURE ” indicator light illuminate, and the buzzer alarm.

Ba t e r r y l o w

The controller detect the battery voltage lower than the “Low battery pre-alarm value”, the state LCD

will display “WARNING

Low pr essur e

BATTERY LOW”, and the buzzer warn.

After the safety-on delay timeout, and the controller detect the output pressure of the engine lower than

the low pressure alarm value preset, the buzzer warn. The state LCD will display “WARNING H temperature

The controller detect the coolant temperature of the engine higher than the high temperature preset alarm

value, and then the buzzer warn, the state screen display“WARNING Overspeed

LOW OILPRESS”

COOLANT TEMP” ,the buzzer warn.

If the running speed of the engine over the preset alarm value, the LCD will display “WARNING

OVER SPEED”,and the buzzer warn. Underspeed

“WARNING High voltage

If the running speed of the engine descend to alarm level preset, then the state LCD display UNDER SPEED”,and the buzzer warn.

If the controller detects the output voltage of the generator over the alarm value preset, the state LCD

will display “WARNING Low voltage

“WARNING Overcurrent

“WARNING Standby input

“WARNING

V HIGH”,and the buzzer warn.

If the controller detects output voltage lower than the alarm value preset, then the state LCD will display V LOW”,and the buzzer warn.

If the controller detects the output current over the alarm value preset, then the state LCD display I HIGH”,and the buzzer warn.

If set the aux input to a warning input, then if the signal at the input is valid, the LCD will display EXT. ALARM”,and the buzzer warn.

7. 2

St o p F a ul t (Note: “Stop fault” can lock the control system and stop the generator running. After the fault is eliminated, eliminated, by pressing press ing the “reset” key unlocking unlocking the fault lock, then t hen you can operate operat e the controller co ntroller again.) Fail to Start

If the engine starting times over the preset value, the engine still does not run, namely it occurs “Fail to

Start.” The LCD will display“ALARM

START FAILURE”, The indicator light Fail to Start illuminate, and the

buzzer warns. Fail to Stop

“ALARM

If the generator fail to stop after the stop delay timeout, then the buzzer warn and the LCD display STOP FAILURE”。

Emergency stop When the emergency stop input signal is valid, the controller stop all output of the relay except the alarm,

the LCD display “ALARM

E.STOP”,“EMERGENCY STOP” indicator light illuminate, and the buzzer warn.

Low Oil Pressure After the safety-on time-delay timeout, the controller detects the oil pressure switch closed, the engine

stop instantaneously, and the LCD display “ALARM

LOW OILPRESS”, the fault indicator light “LOW OIL

PRESSURE”, the buzzer warn.

10

PDF created with pdfFactory Pro trial version www.pdffactory.com

GU 3 2 0 A C o n t r o l l e r

H Temperature

Ma n u a l

The controller has detected the T-sensor switch of the engine closed, the engine stop instantaneously, the

LCD display “ALARM

COOLANT TEMP”,and the indicator light“HIGH TEMPERATURE” illuminate, the

buzzer warn. The controller has detected the running speed of the engine beyond the overspeed fault setting value, the

Overspeed

engine stop instantaneously, the LCD display “ALARM

OVER SPEED””,and the indicator light

“OVERSPEED” illuminate, the buzzer warn. Under Speed

The controller detects the running speed of the engine lower than the low speed fault value, the engine

stop instantaneoussly, and the LCD display “ALARM High Voltage

UNDER SPEED”,the buzzer warn.

The controller detect the output voltage of the generator higher than the high voltage fault value, the

engine will stop after confirming the delay, and LCD display “ALARM Low Voltage

After the safety-on delay timeout, the controller detect the output voltage of the generator lower than t han the

low voltage fault value, the LCD will display “ALARM Overcurrent

V HIGH”,the buzzer warn.

V LOW””after confirming the delay,and the buzzer warn.

The controller detect the output current of the controller higher than the over current fault value, the

engine will stop after confirming the delay, and the LCD display “ALARM Standby Output

I HIGH”,the buzzer warn.

If set the aux input to fault stop, then when the signal at the input is valid, the engine will stop

instantaneously, and the LCD display “ALARM

EXT. ALARM”,the buzzer warn.

NOTE: u

u

The data of low oil pressure pre-alarm is from the measuring of the oil pressure sensor, and the data of low pressure stop fault is from the measuring of the oil pressure sensor (set for no use at factory) or the oil pressure switch state. The data of high temperature pre-alarm is the water position from the measuring of the temperature sensor, and the data of high temperature stop fault is the water position from the measuring of the temperature sensor (set for no use at factory) or the temperature switch state .

u

The rotating speed of the engine typically from the measuring frequency of the speed sensor mounted on the flywheel of the engine, if no speed sensor equipped in the system, the controller will take the voltage frequency of  the generator output as the controlling and fault fault protection parameter. par ameter. To be convenient for for the user, part of the data is rotating speed, RPM=HZ*30.

u

Generator fault during the running of the generator: stop instantaneously after the high temperature , or low pressure, or overspeed, or under speed occur. But the low speed and low pressure required the idle delay set to 0 (without idle function) to active protection, or it won't be active.

8 Parameter Setting 8.1 SYSTEM NO. 1.0 1.1 1.2 1.3 1.4 1.5 1.6

Item

QUIT) ( CT) VT) Comm Address) (Default settings) Language> English/ 

Preset

Range

60 1 1

1~5000 1~100 1~255  /English

English

Firmware update

8.2 GENERATOR NO.

Item

2.0

QUIT

2.1

V Low Alarm V Low preALM

2.2

Preset

0V 198V

Range

AC45~20000V AC45~20000V

11

PDF created with pdfFactory Pro trial version www.pdffactory.com

0 (no setting) setting) 0 (no setting) setting)

GU 3 2 0 A C o n t r o l l e r

Ma n u a l

2.3

V High preALM

2.4

V High Alarm I High preALM pr eALM I High Alarm Alarm delay

2.5 2.6 2.7

253V 29999

AC45~20000V

29999 (no setting) setting)

9999A

AC45~20000V 0~9999A

29999 (no setting) setting) 9999 (no setting) setting)

9999A 10s

0~9999A 0~600s

9999 (no setting) setting)

8.3 ENGINE NO.

Item

Preset

Range

3.0 3.1

QUIT Nominal speed

1500

99-9999 99-99 99 RPM

3.2

Pickup frequency

3000

1-9999 1-999 9 Hz

3.3

Set pickup now

3.4

Pair of Poles

2

1~4

3.5

Fuel mode

0

0~1

0(NC)

3.6

T-sensor mode

0

0~8

0 (no use)

3.7

P-sensor mode

0

0~9

0 (no use)

3.8

H-sensor mode

0

0~1

0 (no use) 1 (use)

3.9

Start delay

3.10

Crank attempt

3

1~10s

3.11

Crank time

8s

0~30 s

3.12

Crank reset

15s

0~300 s

3.13

Crank disconnect

3.14

Idle delay

0秒

0~9999s

3.15

Safety-on Safety-on delay

60s

0~600s

3.16

Cooling delay

300s

0~600 s

3.17

Stop delay

20s

0~60s

3.18

Under SP Alarm

3.19

10s

300RPM

1 (NO)

0~300 s

1-9999 1-999 9 RPM

0 RPM

0-9999 0-999 9 RPM

0 (no setting)

Under SP preALM

1440 RPM

0-9999 0-999 9 RPM

0 (no setting)

3.20

Over SP preALM

1600 RPM

0-9999 0-999 9 RPM

9999 (no setting)

3.21

Over SP Alarm

1710 RPM

0-9999 0-999 9 RPM

9999 (no setting)

3.22

Oil-P low Alarm

140KPa

50~300Kpa

0 (no setting)

3.23

Oil-P low preALM

220KPa

50~300Kpa

0 (no setting)

3.24

Coolant preALM

95℃

70~160℃

9999 (no setting)

3.25

Coolant Alarm

105℃

70~160℃

9999 (no setting)

3.26

Batt low preALM

8.0V

3.27

External. Alarm

0

3.28

External analog

2

1~25V 0 (no setting) 0 unit V, 1 unit %, measuring 0-5v signal. 2 unit %, self determine the input according to the resistance type and sensor data.

8.4 Note for pressure and temperature sensor Different type of P-sensor and T-sensor according to the table followed, if the sensor available is not in the table, then write the sensor parameter into the controller through the software, and the sensor setting in the parameter setting should be the last type “user define” Pressure sensor NO. 0 1 2 3 4

Type

NOT USE VDO 10 bar VDO 5 bar Datcon 10 bar Datcon 7 bar 12

PDF created with pdfFactory Pro trial version www.pdffactory.com

GU 3 2 0 A C o n t r o l l e r

5 6 7 8 9

Ma n u a l

Datcon 5 bar Murphy 7 bar CMB 812 KP-YV01 User define

Temperature sensor NO. 0 1 2 3 4 5 6 7 8

9

Type

NOT USE VDO 120 degrees C Datcon high Datcon low Murphy Commis TS120 KP-T01 User define

LCD and menu system Display several lines of information at the same time according to the 128 ×64 lattice. LCD has background light.

Press any key for a while to turn off the background light. Set a different parameter in every page and controlled upon it, each electricity parameter of load displayed in main page, press

and

scroll to display each electricity

parameter and measuring data. If there is no fault occur, LCD hold the main page, and when fault fault occur, LCD display the fault information in the state screen s creen instantaneously. When more than one fault occur, LCD display one fault state of them. Press

and

refer to the running parameters.

Increase and decrease by degrees to set and adjust the parameter. When press the increase or decrease key for a while, the ones digit changes one by one, and then the tens digit change after ten changes, the rest may be deduced by analogy. Press

in the main page two seconds to enter setting state, then press

of the same level, and press

and

to look over in the menu

to enter next submenu to select and adjust the item, press

indicate to enter password, enter

then press

to adjust. When two seconds to quit setting state.

9 . 1 St St a t i c L C D d i s p l a y : When the controller is ready Operation

Description

While the controller hasn’t detected the running speed of the engine, if the Psensor and T-sensor disconnect , the related data will display “OPEN”, and the LCD display:

U=0V

I=0A 

P=0kW

F=0Hz

SP=0rpm

OP=0kPa

TEMP= OPEN

Bat=24V

RUN Set the controller without without T-sensor and P-sensor Operation

Description

The controller won’t check the data data such as pressure and temperature of the engine, the related data will display “—  ”in ready or running, and the LCD display:

U=0V

I=0A 

P=0kW

F=0Hz

SP=0rpm

OP=---kPa

TEMP= ---

Bat=24V

RUN 13