Grounding Fundamentals Course Presentation
Short Description
Descripción: Grounding Fundamentals Course Presentation...
Description
Grounding Fundamentals Instructor: Allan Bozek, P.Eng. www EngWorks ca www.EngWorks.ca
1. 1 5 EICCEUs
Introduction • •
•
• •
•
Introductions Please introduce yourself – name, job title and experience Sign-in sheet circulated, everyone please sign in and return Emergency response requirements Please turn off all cell phones or turn to silent mode Washrooms and Breaks
www.EngWorks.ca
Grounding Fundamentals
2
Safety Topic Static Electricityy and Refuelling g
www.EngWorks.ca
Grounding Fundamentals
3
Safety Topic Static Electricityy and Refuelling g
Some statistics Petroleum Equipment Institute reports 175 fires since 1992 50% of the accidents occurred when the refueler returned to their vehicle Women account for 75% of all static ignition fires
Safety Guidelines when refueling
Turn off engine D 't smoke Don't k Never re-enter your vehicle while refueling. Do not overfill or top off your tank
If a fire starts Do not remove the nozzle from the vehicle or try to stop the flow of g gasoline. Immediately y leave the area and call for help
www.EngWorks.ca
Grounding Fundamentals
4
Learning Objectives 1. To understand why we ground 2 To describe the difference between grounding and 2. bonding 3. To apply the safety requirements as defined by the Canadian Electrical Code and the IEEE as they relate to grounding 4. To select the appropriate systems grounding scheme for an industrial facility
Sizing of components How it impacts the overall design of a facility
www.EngWorks.ca
Grounding Fundamentals
5
Learning Objectives 5. To implement a static electricity control and lightning g gp protection system y 6. To avoid the problems typically associated with the grounding g g of sensitive electronic systems y
Ground loops Methods of noise mitigation
7. To design a ground grid for a high voltage industrial substation
Concept of ground potential rise and touch and step potential
www.EngWorks.ca
Grounding Fundamentals
6
Agenda Overview 1. History of Grounding 2 System grounding 2. Generator and UPS systems grounding
3. 3 4. 5 5. 6.
Equipment bonding Static Protection Lightning Protection Grounding of Electronic and Instrumentation Systems 7. Station Ground Grid Systems Design 8 Tutorial 8. T t i l www.EngWorks.ca
Grounding Fundamentals
7
Introduction Section 1
Edison's Pearl Street Generation Station
www.EngWorks.ca
Pearl Street Generation station was initially constructed in 1882 to provide DC current for lighting systems in New York's financial district
Grounding Fundamentals
9
Edison’s Floating Approach to DC Systems y
Original design used an earth ground for DC lighting systems Several incidents associated with “stray currents” forced Edison to revise his plan currents One dead horse Workers W k nearby b the th generating ti station t ti could ld ffeell the current Believed the there was a “devil devil in the wire wire”
www.EngWorks.ca
Grounding Fundamentals
10
Edison’s Floating Approach to DC Systems y Current Flow + G Gen -
Intended Return Path
L
L
Unintended Return Path
www.EngWorks.ca
Grounding Fundamentals
11
Human Sensitivity to Electricity
Physiological y g Reaction to Electric Current Range from minor muscular contraction to ventricular fibrillation Function of body y weight g Current magnitude Current duration
H Human b body d can b be considered id d a 1000Ω resistor i t www.EngWorks.ca
Grounding Fundamentals
12
Human Sensitivity to Electricity Human Response
Direct Current (ma)
Alternating g Current (ma)
Men
Women
Men
Women
1
0.6
0.4
0.3
“Let Go” Threshold
6.2
3.5
1.1
0.7
Shock – Not Painful
9
6
1.8
1.2
Painful Shock – Muscular Control Loss
62
41
9
6
Severe Shock – Breathing Difficult
90
60
23
15
Slight Sensation on Hand
www.EngWorks.ca
Grounding Fundamentals
13
Edison's’ Isolated 3 Wire System
Edison later adopted a 3wire system y that did not rely on a earth path for return
Positive
+ 100V
G1
Allowed two circuits to be run with three wires + Circuit was isolated from ground 100V G2 All currents within the circuit could be measured and accounted for
www.EngWorks.ca
Grounding Fundamentals
L
L Neutral
L
200V
L
Negative
14
Shock Current Path
A shock current path requires q two p points
Single point of contact
One point for the current to enter and the second to exit Voltage difference is required for current to flo flow An isolated system under normal operating conditions insures a single point of contact
www.EngWorks.ca
L
G1 N Neutral l
Isolated Ground S t System No Shock Current Exists
Grounding Fundamentals
15
Shock Current Path
Under fault conditions, an isolated system ground creates a shock hazard
Single point of contact t t
Accidental A id t l Ground
L
G1 Neutral
Alternate circuit path leads to shock hazard
www.EngWorks.ca
Grounding Fundamentals
16
Ground Fault Detection An isolated system cannot detect the presence of a ground fault
Circuit protection cannot detect the accidental ground
Accidental Ground
Fuse
L
G1 Neutral
www.EngWorks.ca
Grounding Fundamentals
17
System Overvoltage and Surges
An isolated system cannot dissipate a high voltage surge Usually results in equipment damage
Equipment insulation is stressed as the high voltage surge finds its way to ground
www.EngWorks.ca
Fuse
Lightning Strike
L
G1 Neutral
Grounding Fundamentals
18
The Intentional Grounding of Circuits
Elihu Thompson Founder of Thompson-Houston Industries Later merged with Edison General and became General Electric
Author of over 700 patents
Advocated AC systems should be intentionally earthed Proposed as a safeguard against a breakdown in insulation of a primary circuit conductor Proposal created a large amount of controversyy
www.EngWorks.ca
Grounding Fundamentals
19
Grounding Premise
An intentionally grounded circuit provides a circuit path back to the source in the event of an p accidental ground Allows the circuit p protective devices to function preventing the circuit from becoming a safety hazard
Low Impedance path to source allows fuse to operate
www.EngWorks.ca
Accidental Ground
Fuse
L
G1 Neutral
Grounding Fundamentals
20
History of Grounding
Practice of earthing the secondary (neutral) conductor was banned by the New York Board of Fire Underwriters Speculation p that Thomas Edison was behind the scenes with his patented 3 wire un-grounded circuit
AIEE (Precursor to the IEEE) recommended that low voltage AC systems be grounded where a reliable ground connection could be secured Advocated a solid connection without a fuse on the neutral t l wire i
www.EngWorks.ca
Grounding Fundamentals
21
History of Grounding
NFPA later resolved that grounding the secondary circuit was the only way of absolutely insuring the safety f t off the th circuit i it The debate continued from 1903 – 1913 when it was passed into law Secondaries of all circuits 550V or less must be grounded Recommended that all circuits 300V or less be grounded
Original rule has not been changed in substance since the original 1913 rule in the NEC Section 10 of the CEC Part 1 also adheres to the fundamental premise of the rule
www.EngWorks.ca
Grounding Fundamentals
22
Canadian Electrical Code - Part 1 CSA C22.1-06
Minimum safety standards for installation and maintenance of electrical equipment Compliance will ensure a safe installation
Section 10 deals specifically with grounding and bonding Significant re-write in 2006 Minor updates p in 2009
www.EngWorks.ca
Grounding Fundamentals
23
Canadian Electrical Code - Part 1 CSA C22.1-06
Scope and object: Rules 10-000 and Rule 10-002 Protect life from the danger g of shock Limit the voltage on a circuit Facilitate operation of protective devices
System and circuit grounding: Rules 10-100 to 10-116 All circuits must be grounded with the exception of: Electric Arc furnaces Cranes installed in Class III locations Isolated systems in patient care areas Circuits less than 50V
www.EngWorks.ca
Grounding Fundamentals
24
CEC Handbook
Provides background information and commentary on the th Rules R l off th the Canadian C di Electrical Code, Part I Intended to provide a clearer understanding of the safety requirements of the Code I Incorporates t information i f ti on: Rational Intent Field Considerations
www.EngWorks.ca
Grounding Fundamentals
25
IEEE Standard 142 ((Green Book))
Recommended practices and methods associated with grounding
Systems grounding Equipment grounding and bonding Static and lightning protection Grounding electrode design Grounding of electronic equipment
Applies to industrial and commercial power systems Utility grounding methods are not covered
www.EngWorks.ca
Recommended Purchase Grounding Fundamentals
26
Commonly Used Grounding Terms and Definitions Neutral Conductor
Neutral Point
Neutral Ground Device Grounding Conductor Grounding Electrode www.EngWorks.ca
Metallic Enclosure Bonding Conductor
Stray Current
Earth Grounding Fundamentals
27
Earth
Conducting body of varying resistance Earthing – A connection to earth Interchangeable with the term ground
Earth www.EngWorks.ca
Grounding Fundamentals
28
Ground
A conducting connection by which an electrical circuit is connected to earth Grounding Electrode – a conductor buried in earth and used for collecting or dissipating ground current to earth Grounding g Conductor – conductor used to connect the service equipment to a ground electrode
Grounding G g Conductor Grounding Electrode www.EngWorks.ca
Grounding Fundamentals
29
Bonding
Low impedance path created by joining all noncurrent-carrying metal parts to ensure electrical continuity ti it Bonding Conductor – conductor that connects the noncurrent carrying parts of electrical equipment, raceways or enclosures
B di Conductor Bonding C d t (Equipment ground conductor)
www.EngWorks.ca
Grounding Fundamentals
30
Neutral Point
The point of a symmetrical system which is normally at zero voltage g Neutral Conductor – a system conductor, other than a phase conductor that provides a return path for current to the source Neutral Point
Neutral Ground Device
www.EngWorks.ca
Neutral Conductor
Grounding Fundamentals
31
Definitions
Ground Fault Current – ground current resulting from anyy p phase-conductor-to-earth fault Normal – brief flow of current that occurs until the protective device opens Abnormal – continuous flow of current from a phase conductor to ground Often referred to as the Zero Sequence Current
Neutral grounding devices include grounding resistors, grounding transformers, ground-fault ground fault neutralizers, reactors, capacitors, or a combination of these components
www.EngWorks.ca
Grounding Fundamentals
32
Ground Fault Current
Neutral Ground Device
Metallic Enclosure Intended G Ground dF Fault lt Current Path Ground Fault
Earth www.EngWorks.ca
Grounding Fundamentals
33
Stray Current
The uncontrolled flow of current over and through the earth results in undesired safety and system performance characteristics
Stray Current Earth www.EngWorks.ca
Grounding Fundamentals
34
Systems Grounding Section 2
Purpose of a Systems Ground “System grounding, or the intentional connection off a phase h or neutral t l conductor d t to t earth, th is i for f the purpose of controlling the voltage to earth, or ground ground, within predictable limits” limits IEEE 142 Green Book
Most system faults are ground fault related
www.EngWorks.ca
Grounding Fundamentals
36
Systems Ground
A systems ground will: Control the voltage g to g ground to p prevent stressing g equipment insulation Allow the operation of ground fault detection protection d i devices Reduce the risk of fire and shock hazard to persons who might come in contact with live conductors In some cases provide service continuity Allow the ground fault to be isolated and repaired at a convenient time ti
www.EngWorks.ca
Grounding Fundamentals
37
Concept of a System Ground
A grounding system consists of all interconnected grounding connections in a specific power system and is isolated from adjacent; grounding systems through a high impedance Isolation occurs via an ungrounded transformer winding connection
www.EngWorks.ca
Systems Ground 1
Y
Systems Ground 2
Y Y
Y
Systems Ground 3
Y
M
Grounding Fundamentals
PP
M
M
Systems Ground 4
38
Transformer Winding Connections
∆ (delta) Connections Isolates the p power system y from ground Important is creating “zones of protection”
Y (wye) Connections Y point provides a neutral point for managing ground faults Opportunity for multiple voltages
www.EngWorks.ca
Grounding Fundamentals
39
System Grounding Classifications
Ungrounded
Resistance Ground
www.EngWorks.ca
Solid Ground
Reactance Ground
Grounding Fundamentals
40
System Grounding Classifications Systems Grounding Ungrounded
Grounded
Impedance Grounded Resistance Low Resistance
www.EngWorks.ca
High Resistance
Solid Grounded Reactance Reactance
Tuned Reactance
Grounding Fundamentals
41
Ungrounded
Historically was used on power systems where a high g level of p process continuity y was required q Exists in many process facilities designed prior to 1980
Advantages g Single ground fault does not does not allow current to flow Allowed for a controlled shutdown for fault repairs
Eliminates the need for f elaborate protection schemes Grounding system cost is minimized A N G
B C
www.EngWorks.ca
Grounding Fundamentals
42
Ungrounded
Disadvantages On a g ground faults,, the voltage g to g ground for the remaining g phases is elevated by 73% Higher insulation rating required for system components
Transient T i t overvoltages lt can be b a problem bl Voltages up to 6X system voltage stresses insulation eventually leading to a second ground fault and subsequently a phase to phase fault
www.EngWorks.ca
Grounding Fundamentals
43
Ground Fault Voltage Shift Normal Operating Conditions
A
A
VAG
IA
IA
N
IB
VCG
B IB CA
CB
C
C CC
IC
VCN
IC
B A
VAN N
VAG
G
VAB
VCA VCG
VBN
If CA = CB = CC then IA+ IB + IC = 0 www.EngWorks.ca
VBG
Grounding Fundamentals
C
N G VBG VBC
B
44
Ground Fault Voltage Shift Ground Fault Phase C
A
IG VAG
A
IB
IA
IA
N
C G VCG=0
B IB
IG
CA
C
VBN
N
VAN
A
CB VCA
VCN
G
www.EngWorks.ca
B
VBG
IA + IB = IG
VAG
VAB
N
VCG=0
C G Grounding Fundamentals
VBC VBG
B
45
Intermittent Ground Faults A IA
N B IB
IG G
CA
C
CB
Breakdown in insulation results in phase to phase fault IG = ISC
www.EngWorks.ca
Intermittent or restriking type yp g ground faults on isolated grounded systems can cause severe system overvoltages Up to 6 or 8 times line to line voltage Will eventually lead to an g in insulation failure resulting a phase to phase fault Must be detected and corrected ASAP
Grounding Fundamentals
46
Ungrounded System Ground Fault Detection Scheme 10-106 Alternating-current systems (see Appendix B) ((2)) Wiring g systems y supplied pp by y an ungrounded g supply pp y shall be equipped with a suitable ground detection device to indicate the presence of a ground fault.
Ground Fault
L
L
L
0V
Light Dims Or Extinguishes
Ground fault Detection Scheme www.EngWorks.ca
Grounding Fundamentals
47
Solid Ground
A solid grounded system is one in which the neutral points have been intentionally connected to earth ground with a conductor having no intentional impedance Often referred to as effective grounding
A N G
B C
www.EngWorks.ca
Grounding Fundamentals
48
Solid Ground
Uniground System Used in Industrial Systems
www.EngWorks.ca
Multi-grounded System Used by Utilities in Rural Distribution Systems
Grounding Fundamentals
49
Solid Ground
Advantages Partially reduces the problem of transient over-voltages Reduced R d d insulation i l ti llevell required i d
Ground faults do not shift the system neutral Simple ground relay schemes provide for circuit protection
Disadvantages Damage at the fault may be excessive Arc flash hazard due to high ground fault current levels Difficult to coordinate ground fault protection Magnitude of the fault current is unknown
www.EngWorks.ca
Grounding Fundamentals
50
CEC Definition
Effective Grounding - a path to ground from circuits, equipment, q p , or conductor enclosures that is permanent and continuous and has carrying capacity ample to conduct safely any currents liable to be imposed upon it CEC Rule 10-500 in Appendix B states that the complete fault path of the circuit conductor conductor, together with the bonding return return, should have an impedance that allows at least five times the current setting of the overcurrent device to flow when a fault of negligible impedance occurs
www.EngWorks.ca
Grounding Fundamentals
51
Solid Ground A N B C
O/C fuse may not clear arcing ground fault
IG G
www.EngWorks.ca
High Impedance Ground fault
Grounding Fundamentals
VBN
N
VAN
VCN
52
High Resistance Ground
System is grounded through a high-impedance resistor High-impedance grounding typically limits ground fault current to 25 A or less Typically used on low voltage (600V or less) systems under 3000 Amps A N 2 - 25A
www.EngWorks.ca
G
B C
Grounding Fundamentals
53
High Resistance Ground Scheme
1000 KVA Xfmr 25kV – 600V 5.75% Z
AL
51G
Y
5 Amp NGR
NGR 5A
M 150HP Cooling Ground Fan
Fault www.EngWorks.ca
LP
U/H
45kVA
Lighting Panel
30kW Unit Heater
Grounding Fundamentals
Starter
75kVA
X2
HTP Heat Trace Panel
M
M
75HP Recycle Pump
25HP Injection u p Pump
X2
54
High Resistance Ground
Advantages Allows system y to operate p under a g ground fault condition Reduces arc flash energy associated with a ground fault Insures a ground fault of a known magnitude Aids in protective relay coordination and limiting equipment damage
Reduces transient ground fault overvoltages Allows easy identification and isolation of the ground fault location
Disadvantages Neutral shift on ground fault
www.EngWorks.ca
Grounding Fundamentals
55
Low Resistance Ground
System is grounded through a low-impedance resistor Low-resistance grounding typically limits ground fault current to 400A or less for a short period of time (10 sec) Typically used on medium and high voltage industrial power distribution systems A N 25 - 400A
www.EngWorks.ca
G
B C
Grounding Fundamentals
56
Low Resistance Ground
Advantages Allows p protective relay y devices to q quickly y clear a g ground fault Limits damage to equipment and reduces overheating and mechanical h i l stress t on conductors d t
Disadvantages Neutral Ne tral voltage oltage shift of limited d duration ration
www.EngWorks.ca
Grounding Fundamentals
57
Low Resistance Ground Scheme Trip Upstream Breaker 51 NGR 400A
Trip setting ~ 20% of NGR rating
Y
Trip Downstream Breaker
400A NGR 13.8kV
M
51 XFMR
SGR (Secondary Ground Resistor)
Y 5A NGR
600V
Alternate Arrangement M
www.EngWorks.ca
Grounding Fundamentals
M
58
LR Grounding Resistor Connection to Neutral Point on Transformer
Connection to ground
Resistors Current Transformer
51 NGR 400A
www.EngWorks.ca
Grounding Fundamentals
59
LR Grounding Transformer Ground resistor
51 XFMR
SGR (Secondary Ground Resistor)
Grounding Transformer
www.EngWorks.ca
Grounding Fundamentals
60
Alternate Grounding Schemes
Corner-of-the-Delta System Applicable pp to low-voltage g systems Not widely used in industrial systems t
A
I B C
I
Delta One Phase Grounded at Midpoint Applicable to single phase 120/240V loads
240V 120V
120V G
www.EngWorks.ca
Grounding Fundamentals
240V
61
Reactance Grounding
Ground fault current is a function of the neutral reactance Typically results in higher ground fault currents than a resistance grounded system 25 5 – 60% of o three t ee phase p ase fault au t current
Primarily used by Utilities on multi grounded systems on multi-grounded systems above 5kV Seldom used in industrial plant applications www.EngWorks.ca
Grounding Fundamentals
N
51 Reactor
IG
62
Resonant Grounding
Tuning reactor is used to ground the neutral point to ground Reactor is tuned to match the system capacitance
N
Results in a very low value of ground fault current 75% of line to ground faults are selfextinguishing
C Complex l controls t l are required i d tto constantly match the reactance to the system capacitance Primarily Pi il used d on overhead h d and d transmission lines above 15kV Rarely used in industrial applications
www.EngWorks.ca
51 Reactor Ground Fault Neutralizer
Grounding Fundamentals
IG
63
Grounding System Comparison Ung grounded
Solid Ground
Low Resistance
High Resistance
Immunity to transient overvoltages
Worst
Good
Good
Best
Arc Fault Damage Protection
Worst
Poor
Better
Best
Safety to Personnel
Worst
Better
Good
Best
Service Reliability
Worst
Good
Better
Best
Continued operation after initial ground fault
Better
Poor
Poor
Best
Not Possible
Good
Better
Best
Condition
Ground fault locating
www.EngWorks.ca
Grounding Fundamentals
64
Ground Fault Sensing
www.EngWorks.ca
Grounding Fundamentals
65
Ground Fault Sensing
Ground Return Ground fault current is measured in the neutral to ground connection Applicable only at a source transformer or 51G generator g Often used for ground fault alarm sensing on LV di t ib ti systems distribution t
www.EngWorks.ca
Grounding Fundamentals
Phase A Neutral Phase B Phase C
66
Ground Fault Sensing
Zero Sequence Relay Measures zero sequence or ground currents by sensing the magnetic fields surrounding th phase the h and d neutral t l conductors
Phase A Neutral Phase B Phase C
Should cancel under normal conditions
Often used in motor protection and feeder breaker relays
www.EngWorks.ca
Grounding Fundamentals
51G
67
Ground Fault Sensing
Differential Phase current and neutral current values are measured and ground fault current is calculated l l t d as th the diff difference Used in applications where current transformers are required for phase overcurrent relays High Hi h accuracy iin d detecting t ti ground faults
www.EngWorks.ca
Grounding Fundamentals
Phase A Neutral Phase B Phase C
51G
68
High Resistance Ground Detection Scheme
NGR 5A
Pulsing reading on phase indicates ground fault
AL
Y Pulsing Resistor
Clamp On CT
45kVA M
150HP Cooling Ground Fan
Fault www.EngWorks.ca
1000 KVA Xfmr 25kV – 600V 5.75% Z
5 Amp NGR
LP
U/H
51G
Lighting Panel
30kW Unit Heater
Grounding Fundamentals
Starter
75kVA
X2
HTP Heat Trace Panel
M
M
75HP Recycle Pump
25HP Injection u p Pump
X2
69
High Resistance Ground fault Detection System y
www.EngWorks.ca
Grounding Fundamentals
70
Ground Fault Relay Settings
Alarm only on continuous rated ground resistor applications pp Alarm setting at 80% of maximum current level allowed by ground resistor Above system charging current level
Trip on short time duty ground resistor applications High resistance ground applications Trip at 80% of maximum current level allowed by resistor
Low resistance g ground applications pp Trip at 20% of maximum current level allowed by ground resistor
www.EngWorks.ca
Grounding Fundamentals
71
Low Resistance Ground Detection Scheme Trip p Upstream p Breaker 51G
NGR 400A
Trip setting ~ 20% of NGR rating
Y Trip Downstream Breaker
400A NGR
Trip
ZCT
51G
13.8kV Trip
Trip ZCT
51G
Trip ZCT
ZCT - Zero Sequence CTs
www.EngWorks.ca
Grounding Fundamentals
51G
Trip ZCT 51G
ZCT
51G M
M
72
GF Relay Time Coordination Curves
Settings for ground-fault relays can be determined during the relayy coordination studyy GF curves are plotted on the coordination diagrams Set parameters include ti time and d currentt llevell Ground Fault coordination curves
www.EngWorks.ca
Grounding Fundamentals
73
CEC Requirements Associated with Systems Grounding
www.EngWorks.ca
Grounding Fundamentals
74
CEC Code Requirements 10-1102 – Installation of Neutral Grounding Devices 1) Neutral grounding devices can only be installed on systems where line to neutral loads are not served No single phase loads from a resistance grounded system
2) S Systems t with ith voltages lt > 5kV shall h ll b be d de-energized i d on detection of a ground fault a)) Electrical systems y operating p g at 5 kV or less are p permitted to remain energized if the ground fault current is controlled at 10A or less i.
Audible alarm is required
www.EngWorks.ca
Grounding Fundamentals
75
CEC Code Requirements 3) Where line-to-neutral loads are served, the system must be de de-energized energized on occurrence of a: 1) Ground fault 2) Grounded neutral on the load side of the NGR 3) Break in the continuity of the conductor connecting the NGR to ground Apparent conflict between subsection 1) and subsection 3)
www.EngWorks.ca
Grounding Fundamentals
76
NGR with Isolated System Neutral A Trip main breaker
HT Ckt
HT Ckt
HT Ckt
HT Ckt
HT Ckt
HT Ckt
N HT Ckt
B C
51
NGR IG
www.EngWorks.ca
Rule 10-1102 requires the system to g on detection of be de-energized ground current
Grounding Fundamentals
77
Neutral Ground Devices 10-1104 NGRs must be approved for the application CAN/CSA-C22.2 No. 0.4 – Bonding and Grounding of Electrical E i Equipment (P (Protective i G Grounding) di ) CAN/CSA-C22.2 No.14 – Industrial Control Equipment CAN/CSA-C22.2 No. 94 – Special Purpose Enclosures
Must be continuously rated where provisions are not made to interrupt the fault Maximum temperature allowed is 375°C
Where not continuously rated, the time rating of the device y must be coordinated with the protective devices of the system Must have an insulation voltage equal to the line-to-neutral system voltage
www.EngWorks.ca
Grounding Fundamentals
78
Location of Grounding Devices 10-1106 All live parts must be enclosed Must be placed in a location accessible to qualified personnel Must be placed in a location where it can dissipate the heat under ground fault conditions Warning g signs g must be p provided indicating g the system is impedance grounded and located at: Transformer or generator, or both Consumers service switchgear Supply authorities metering equipment
www.EngWorks.ca
Grounding Fundamentals
79
Grounding Conductors
System grounding conductors must be copper Solid g grounded systems y sized as p per CEC Table 17 Based on the ampacity of the largest service conductor
No splicing is permitted
www.EngWorks.ca
Grounding Fundamentals
80
CEC Code Requirements
www.EngWorks.ca
Grounding Fundamentals
81
NGR Conductors 10-1108 conductors connecting the NGR to the Neutral point of the system p y must be identified as white or grey Must not be grounded Sized to conduct the rated current of the device No less than #8 AWG
Conductor connecting the NGR to the system ground electrode may be insulated green or bare Made of copper pp
www.EngWorks.ca
Grounding Fundamentals
82
NGR Conductors
www.EngWorks.ca
Grounding Fundamentals
83
Bonding of Conduit Enclosing a Grounding g or Bonding g Conductor
Magnetic effect of metal conduit can increase the impedance of the grounding circuit by a factor of 40! Not an issue with PVC or aluminium conduits
Problem can be mitigated by bonding the grounding conductor to the metal conduit at both ends Allow the metal conduit to carry a portion of the ground current New CEC rule 10-806 makes this mandatory
www.EngWorks.ca
Grounding Fundamentals
84
Sizing and Specification of Neutral Ground Resistors
NGR Sizing Criteria
NGRs are sized based on the following criteria Charging current HRG - Maximum ground current must be greater than 3X the charging current for the system LRG – Charging current not a factor
Temperature rise Based on how long the fault is allowed to persist – Continuous – Extended E t d d titime (1 minute) i t ) – 10 seconds
www.EngWorks.ca
Grounding Fundamentals
86
NGR Sizing Criteria RNGR =
51 NGR
IG
VLL √ G √3I
XCO RNGR ≤ 3 IG ≥ 3ICO WNGR = IG2RNGR RNGR = Resistor Size ((Ohms)) IG = Maximum Ground Current (Amps) ICO = System Charging Current (Amps) WNGR = Resistor Size (Watts)
www.EngWorks.ca
Grounding Fundamentals
87
NGR Sizing Criteria Secondaryy Ground Resistor
51 XFMR
SGR
RNGR RSGR = N2 VLN(Pri) N= VLN(Sec) ISGR = NIG KVA = PNGR = IGVLN(Pri)
RNGR = Equivalent Primary Resistance (Ohms) RNGR = Equivalent Primary Resistance (Ohms) IG = Maximum M i G Ground dC Currentt (Amps) (A ) ISGR = Maximum Ground Current (Amps) N = Turns ratio PNGR = Resistor Power Rating (Watts) www.EngWorks.ca
Grounding Fundamentals
88
Charging Current - Estimation
Resistor must be sized to ensure that the ground fault current limit is g greater than the system's y total capacitance-to-ground charging current System Voltage
Charging Current (3ICO) Amps per 1000 kVA of System Capacity
480
0.1 – 2.0
600
0.1 – 2.0
2400
2.0 – 5.0
4160
2.0 – 5.0
13800
5.0 – 10.0
Typical Charging Currents based on Voltage Level www.EngWorks.ca
Grounding Fundamentals
89
Charging Current – More Detailed Analysis System Voltage 600V
4160V
13800V
Component Cable
Type
Typical Charging Current
3/C - 250 – 500MCM
0.15A/1000ft
3/C - #1 – 4/0AWG
0.02A/1000ft
Transformers
0.02A/MVA
Motors
0.01A/1000HP
Cable
3/C - 500–1000MCM Shielded
0.58A/1000ft
3/C – 1/0 – 350MCM Shielded
0.23/1000ft
Non Shielded
0.1A/1000ft
T Transformers f
0 05A/MVA 0.05A/MVA
Surge Suppressor.
1.35A per Set
Motors
0.1A/1000HP
Cable
3/C - 600–1000MCM Shielded
0.65A/1000ft
3/C – 250 – 350MCM Shielded
0.75/1000ft
3/C - #1 – 4/0AWG Shielded
0.65A/1000ft
Transformers
0.05A/MVA
Surge Suppressor
2 25A per Set 2.25A
Motors
0.15A/1000HP
www.EngWorks.ca
Grounding Fundamentals
90
Charging Current Calculation Example p ROT → IG ≥ 3ICO IG ≥ 3(4.78A) 3(4 78A) = 14.34A 14 34A Qty
Total Ch i Charging Current
Transformer
0.05A /MVA
17.5
500MCM Cable
0.58A /1000ft
4200 ft 2.43A
250MCM Cable
0.23A /1000ft
600 ft
Surge Suppressor
1.35A /Set
1
T t l Total www.EngWorks.ca
Y
12 MVA
10A NGR
0.875A
4160V 1500ft 500MCM
Charge C Current t
Surge Suppressor
1500ft 500MCM
Component
15A 5 NGR G more oe appropriate size
0.13A Y
2MVA
Y
2A NGR
1.35A
4 78A 4.78A
2MVA
600V
Y
1200ft 500MCM
600ft 250MCM 1 5MVA 1.5MVA
Surge Suppressor M
3000HP M
Grounding Fundamentals
M
91
Charging Current Test Procedure
A IA
N B IB CA
CB
C CC
IC
A Ammeter 0-10A 0 10A
Ammeter will indication charging current (3ICO)
G
www.EngWorks.ca
Connect an ammeter to ground g a resistance,, switch and through a fuse Increase the resistance to maximum level and close the di disconnect t Slowly reduce the resistance to zero All three phases should be g used measured and the average as the system charging current
Grounding Fundamentals
92
Cable Insulation Ratings on Resistance Grounded Systems y
Low Voltage Systems (≤ 600V) 100% % insulation rating g acceptable p for all applications pp Refer to Standata CEC 12
Medium Voltage g Systems y ((IEEE Recommendations)) 100% insulation level required where clearing time will not exceed one minute 133% insulation level required where clearing time will not exceed one hour 173% insulation level required where clearing time exceeds one hour
www.EngWorks.ca
Grounding Fundamentals
93
NGR Ratings
Based on the criteria defined in IEEE 32 - Standard Requirements, Terminology, and Test Procedure for Neutral Grounding Devices Current Current through the device during a ground fault condition
Voltage V = IR at 25ºC May need to be de-rated at elevations above 1000m
Frequency Circuit Voltage of System
Service NEMA Type 1 for Indoor Applications NEMA Type 3 for Outdoor Applications www.EngWorks.ca
Grounding Fundamentals
94
NGR Ratings
Basic Impulse Insulation Level System Insulation Class
www.EngWorks.ca
Class
BIL
1.2kV 2 5kV 2.5kV 5kV 8 7kV 8.7kV 15kV 23kV
45 60 75 95 100 150 Grounding Fundamentals
95
NGR Ratings
Time Rating and Permissible Temperature Rise under fault conditions Permissible Temperature Rise (Rise Above 30ºC Ambient)
Time Rating Ten Seconds (Short Time) (NGRs
760ºC 760 C
used with Protective Relay)
One Minute (Short Time)
760ºC
Ten Minutes (Short Time) (seldom
610ºC
specified)
Extended Time
(GF
610ºC 610 C
allowed to persist > 10min)
Steady State (Continuous)
385ºC*
*CSA permissible rise is 375ºC over 40ºC Ambient www.EngWorks.ca
Grounding Fundamentals
96
NGR Monitoring
Broken Spot Weld
NGR Thermal Failure Broken Resistor Wire www.EngWorks.ca
Grounding Fundamentals
97
NGR Monitor
The NGR monitor measures changes in NGR resistance, current in the neutral, and neutral-toground voltage g g Anomalies are detected and an alarm or trip signal is activated
www.EngWorks.ca
Grounding Fundamentals
98
NGR Sizing Tutorial
NGR Sizing Tutorial
Modular Substation incorporating 5 kV Switchgear and MCCs 600 V Switchgear and MCCs
Grounding system consists of: Power Distribution System Ground 5kV L Low resistance i t ground d system t 600V High resistance ground system
Objective Size the grounding resistors for the 5kV LRG system and the 600V HRG system Assume 1.5A charging current for the 600V System Assume 8A charging current for the 5kV System
www.EngWorks.ca
Grounding Fundamentals
100
Substation Single Line
LRG NGR
Y 5kV
M
HRG NGRY
M
M
600V ~=
M
M
=
~
UPS PP
www.EngWorks.ca
Grounding Fundamentals
101
NGR Sizing Tutorial Answers
Sizing the NGRs RNGR =
51 NGR
IG
VLL √ G √3I
XCO RNGR ≤ 3 IG ≥ 3ICO WNGR = IG2RNGR RNGR = Resistor Size ((Ohms)) IG = Maximum Ground Current (Amps) ICO = System Charging Current (Amps) WNGR = Resistor Size (Watts)
www.EngWorks.ca
Grounding Fundamentals
103
HRG Sizing ROT → IG ≥ 3ICO
ICO = 1.5A
IG ≥ 4.5 → Choose 5A as the HRG Current Rating RNGR = RNGR =
VLL √3IG 600V √3 x 5A
RNGR = 69.3Ω
www.EngWorks.ca
WNGR = IG2RNGR WNGR = 5A2 x 69.3Ω WNGR = 1733watts
Grounding Fundamentals
104
LRG Sizing ROT → IG-Trip Setting ≥ 3ICO to avoid nuisance tripping
ICO = 8A
Trip T i setting i is i roughly hl 20% off the h LRG resistor i size i IG-Trip Setting ≥ 24A to avoid nuisance tripping IG ≥ 120A → Choose Ch 125A as the h LRG Current C Rating R i RNGR = RNGR =
VLL √ G √3I 4160V
√3 x 125A
RNGR = 19.2Ω www.EngWorks.ca
WNGR = IG2RNGR WNGR = 125A2 x 19.2Ω WNGR = 300kW Grounding Fundamentals
105
System Grounding Application Summary
Solid Systems Ground Industrial applications pp 208V or less Commercial Applications 600V or less
High g Resistance Ground ((5-15A)) Industrial applications 600V or less CEC allows HRG to be used on applications up to 5kV
Low Resistance Ground (100 – 400A) Industrial applications 5kV – 34.5kV Ground G d ffaultlt protection t ti provided id d by b Z Zero Sequence S CTs CT on individual equipment items GF relays set to trip at 10 -20% of maximum ground fault current
www.EngWorks.ca
Grounding Fundamentals
106
Obtaining a Systems Neutral Application of Grounding Transformers
Obtaining a Systems Neutral
Often there are cases where a systems neutral point must be established for the purposes of:
Y
Servicing line to neutral loads Establishing a systems ground d point i t tto ground d th the system through a HRG, LRG or solid ground connection ti
13.8kV
M
Example: Conversion of a isolated ground system to a high resistance ground system www.EngWorks.ca
Grounding Fundamentals
108
Grounding Transformers
Grounding transformers are the standard means of obtaining a systems neutral Provide a low impedance path for ground fault currents
Zig-Zag transformer Often Oft referred f d to t as a grounding di transformer t f Specialized transformer with no secondary winding
Wye-delta Wye delta transformer configuration Delta winding is left unconnected
www.EngWorks.ca
Grounding Fundamentals
109
Grounding Transformer Schemes A B C
I
I G
Zig Zag Transformer
www.EngWorks.ca
I G
Wye-Delta Transformer
Grounding Fundamentals
110
Transformer Connection
The grounding transformer is connected to the main bus and serves as the return path for any unbalanced or ground fault currents
Y
A NGR is then connected to th neutral the t l point i t off th the grounding transformer establishing a connection to ground d
13.8kV
M
LRG www.EngWorks.ca
Grounding Fundamentals
111
Specifying a Grounding Transformer
Parameters for specifying a grounding transformer Primaryy Voltage g BIL (Basic Impulse Level) rating Defined by IEEE standards (refer to IEEE 141 Red book)
Transformer impedance Typically very high (up to 100%) to minimize magnetizing current flows
Continuous neutral current rating Applicable to four wire application
Fault F l current and dd duration i If a LRG scheme of limited duration is used, ( typically 10 – 60 seconds) the grounding transformer does not need a continuous duty rating www.EngWorks.ca
Grounding Fundamentals
112
G Grounding di off Generators G t Section 3
Generator Grounding
Generators differ from transformers in several ways Less able to withstand the heating g and mechanical effects of a short circuit Will have a higher initial ground fault current than three phase h ground d currentt Can develop third harmonic voltages and currents Less able to withstand voltage surges
www.EngWorks.ca
Grounding Fundamentals
114
Objective of Generator Neutral Grounding
Minimize the damage associated with internal ground faults Limit mechanical stresses in the generator for external ground faults Limit temporary and transient overvoltages on the generator t insulation i l ti system t Provide a means of system ground fault protection
www.EngWorks.ca
Grounding Fundamentals
115
Systems Ground Incorporating Generation System Ground #1 NGR
Y 5kV
System Ground #2
M G
Y
G
600V Normal Bus
System Ground #3
M
M
G
600V Emergency Bus
www.EngWorks.ca
Grounding Fundamentals
116
Generator Ground Fault IGF 400A NGR 2 X IGF IGF
400A NGR
Stator Ground Fault near Generator terminals Breaker Closed
Initial ground fault current results in 2 X 400A flowing into fault
www.EngWorks.ca
Grounding Fundamentals
117
Generator Ground Fault IGF 400A NGR IGF 400A NGR Stator Ground Fault near Generator terminals Breaker Open
Upon breaker trip, ground fault current continues to flow due to the residual magnetism and inertia of the machine www.EngWorks.ca
Grounding Fundamentals
118
Ground Fault Magnitude
Magnitude of a ground fault is determined by the impedance p of the g generator or transformer winding g Maximum ground fault will occur on the system bus Maximum theoretical ground fault current in the generator will occur at the generator terminals Closer the stator fault is to the generator terminals, the higher the fault
Resulting damage is a function of current and time
www.EngWorks.ca
Grounding Fundamentals
119
Solid System and Generator Ground
NOT RECOMMENDED Results in very high ground fault currents resulting in g extensive damage Risk of abnormal third-harmonic currents when more than one generator is connected in parallel Increased magnetic core losses in both generator and transformer
www.EngWorks.ca
Grounding Fundamentals
120
Low Voltage Emergency Generator Scheme
Bonding Conductor
Normal Bus
Emergency Bus Gnd
www.EngWorks.ca
Grounding Fundamentals
Gnd
121
Single Unparalleled Generator Grounding Solid Grounded with Neutral Equipment Ground conductor 3 pole Transfer Switch
Normal Bus
Neutral Conductor Zero Sequence CT is bypassed resulting in false ti trip www.EngWorks.ca
51G N
Neutral Connected To ground
Solid Neutral
Emergency Bus Gnd
Grounding Fundamentals
N
Gnd
122
Single Unparalleled Generator Grounding Solid Grounded with Neutral
Connection of the neutral to ground at the generator can cause problems p Allows stray current to flow between the neutral and the ground conductors Allow zero sequence (ground fault current) to flow in the neutral causing nuisance tripping of the main breaker Prevent ground fault relays from detecting a ground fault
A neutral should not be connected to ground on the load side of a service disconnect
www.EngWorks.ca
Grounding Fundamentals
123
Option 1 – Switch Neutral Equipment Ground conductor 4 Pole Transfer Switch
Normal Bus
Neutral Conductor
GFP N
www.EngWorks.ca
Neutral Connected To ground Neutral Switched With load conductors
Emergency Bus Gnd
Grounding Fundamentals
N
Gnd
124
Option 2 – Connect Generator Neutral with Transformer Neutral Equipment Ground conductor 3 pole Transfer Switch
Normal Bus
Neutral Conductor Zero Sequence CT read full neutral current value l www.EngWorks.ca
51G N
Generator G t Neutral connected to transformer neutral in transfer switch
Emergency Bus Gnd
Grounding Fundamentals
N
Gnd
125
Additional References
IEEE 446 Orange Book Provides application pp information for the system grounding and transfer switching of standby generators 600V or less
www.EngWorks.ca
Grounding Fundamentals
126
Single Unparalleled Generator Grounding High g Resistance Grounded HRG Bonding Conductor
HRG
Normal Bus
Emergency Bus Gnd
www.EngWorks.ca
Grounding Fundamentals
Gnd
127
HRG Source and Generator Grounding HRG HRG
Advantages Ground fault current limited to a veryy low value
Disadvantage Selective tripping on downstream breakers is not practical
www.EngWorks.ca
Grounding Fundamentals
128
LRG Source and Generator Grounding LRG LRG
Advantages Allows selective tripping of downstream feeders
Disadvantage Damage can occur to the generator from high ground fault currents Variations in fault current can cause relay coordination problems
www.EngWorks.ca
Grounding Fundamentals
129
LRG Source and HRG Generator Grounding g HRG LRG
Advantages Allows selective tripping of downstream feeders Reduced R d d level l l off fault f lt currentt to t the th generators t minimizing i i i i d damage
Disadvantage System is high resistance grounded when the generator is operating alone – makes selective tripping impossible
www.EngWorks.ca
Grounding Fundamentals
130
Source and Generator Grounded with Artificial Neutral
LRG
Advantages Allows selective tripping of downstream feeders Allows All either ith source or generator t to t provide id power
Disadvantage Damage can occur to the generator from restriking and intermittent ground faults
www.EngWorks.ca
Grounding Fundamentals
131
LRG Source and Hybrid LRG/HRG Generator Grounding g LRG LRG
HRG
Ground fault will cause generator t breaker b k to t trip and open LRG circuit
Advantages Allows selective tripping of downstream feeders Allows generator to operate without the source transformer energized
Disadvantage Additional complexity in the grounding and relaying system
www.EngWorks.ca
Grounding Fundamentals
132
Unit Connected Generator Grounding HRG
LRG LRG
Advantages Allows selective tripping of downstream feeders Allows generator to operate without the source transformer energized
Disadvantage Cost of the additional transformer
www.EngWorks.ca
Grounding Fundamentals
133
E i Equipment tB Bonding di Section 4
System Grounding
Grounding and bonding have distinct meanings within the context of the CEC Grounding refers to a conductive path direct to the grounding g g electrode Low impedance path to ground Conductors are sized to carry the expected fault current Insure the operation of protective devices in the circuit should a fault occur
www.EngWorks.ca
Grounding Fundamentals
135
Equipment Bonding
Refers to the interconnection and connection to earth of all normallyy non-current carrying y g metal p parts Insures that all metal parts remain at ground potential Reduces the shock hazard to personnel Provides a low impedance return path for ground currents Allows the circuit protection device to operate
Minimize the fire and explosion hazard Reduce accumulated static charges
www.EngWorks.ca
Grounding Fundamentals
136
Ground Return Path through Earth Insufficient current to operate protection device Line
~
S
Metallic Enclosure Ground Fault
V Neutral
Short circuit must take high impedance path to source High Impedance Ground Path
www.EngWorks.ca
Grounding Fundamentals
137
Ground Return with Metallic Path High Current Operates Protection Device Line ~ Metallic Enclosure
S
Ground Fault
V Neutral
Low Impedance Path through Bonding Conductor High Impedance Ground Path
www.EngWorks.ca
Grounding Fundamentals
138
Bonding Fundamentals
To reduce electrical shock exposure: the impedance p of the bonding g conductor must be capable p of carrying the fault current Must provide a lower impedance than all other parallel paths th
For fire protection: M Must st be able to conduct cond ct the available a ailable gro ground nd fa fault lt ccurrent rrent without excessive temperature rise or arcing Joints and connections are critical components
Overcurrent Protection Operation: Provide a low impedance current path back to the source
www.EngWorks.ca
Grounding Fundamentals
139
Bonding – CEC Requirements 10-400
All exposed non-current carrying metal parts of fixed equipment q p Supplied by a conduit wiring system Supplied by a wiring system that contains a bonding conductor Located in a wet location In a hazardous location Operates at more than 150V to ground
Examples Distribution equipment, motor and generator frames Lighting fixtures housings
www.EngWorks.ca
Grounding Fundamentals
140
Bonding Methods
Bonding conductor in a cable or raceway Rigid metal conduit Bonding conductor is required if the conduit is in underground service or installed in concrete slabs
EMT conduit Bonding conductor required if installed in concrete or masonry slabs
Sheath of a mineral insulated cable if manufactured of copper or aluminum CEC Not acceptable Metal armor of liquid tight flex or cable assemblies Conduit made of stainless steel
www.EngWorks.ca
Grounding Fundamentals
141
Bonding Methods - Effectiveness Cable or Conduit
DC Resistance Ω/1000ft
Voltage Drop V/1000A/100ft
1-1/4” Rigid Steel Conduit
0.0108
11
1-1/4” EMT
0.0205
22
0.435
436
1-1/4” Flexible Conduit 3/C St Steell A Armored dC Cable bl
55
3/C Steel Armored Cable with Ground Conductor
11
3/C Aluminum Armored Cable
0.286
3/C Aluminum Armored Cable with Ground Conductor www.EngWorks.ca
151 12
Grounding Fundamentals
142
Bonding Conductors
Bonding conductors may be: Be copper or other corrosion resistant material Aluminium conductors are acceptable May be insulated or bare Insulated bonding g conductors shall be coloured g green
May be spliced or tapped as required If installed to supplementary bond a raceway: Must be insulated Must be run in the same raceway
M st be protected against mechanical inj Must injury r ifif: Copper - Smaller than #6 AWG Aluminum – Smaller than #4 AWG
www.EngWorks.ca
Grounding Fundamentals
143
Bonding Conductors Equipment q p and Raceways y
www.EngWorks.ca
Grounding Fundamentals
144
Bonding of Cable Trays
Rule 12-2208 of the CEC requires that cable trays be bonded to ground g If the metal supports for cable tray are in good contact with the grounded structural metal frame of a building, the tray shall h ll b be d deemed d tto b be b bonded d d tto ground d If not in direct contact, a bonding conductor must be installed and the tray bonded to the conductor at intervals not exceeding 15m Sized as per CEC table 16 based on the largest ungrounded conductor in the tray
A bonding conductor may also be required in the cases that the tray supports single conductor cables of a three phase system www.EngWorks.ca
Grounding Fundamentals
145
Bonding of Single Conductor Cables
Separate ground conductor required to bond the metallic equipment at either end Must follow the same routing as the phase conductors
www.EngWorks.ca
Grounding Fundamentals
146
Bonding Considerations
Bonding connections require a clean surface Paint must be removed from connection points
Connections between dissimilar metals should be avoided Potential for deterioration of the connection due to galvanic action
Mechanical strength may often determine the size of conductor d t Electrical continuity of expansion joints Cable tray connections
www.EngWorks.ca
Grounding Fundamentals
147
Equipotential Bonding
Practice of bonding all exposed and extraneous conductive p parts ((Ref CEC 10-406)) Purpose is to ensure that under fault conditions, all conductive parts remain at the same potential
Applies to
Metallic water and sewer piping G piping Gas HVAC ducting Exposed metal equipment and structures Raised computer floors
www.EngWorks.ca
Grounding Fundamentals
148
Equipotential Bonding
CEC requires a minimum #6 AWG conductor
www.EngWorks.ca
Grounding Fundamentals
149
Bonding of Portable Equipment
Non-current carrying metal parts of portable equipment q p must be bonded when:
Equipment is used in a hazardous location Equipment is used in wet or damp locations Equipment operates at more than 150V to ground When the equipment is provided with a grounding means Three Th prong plug l with ith ground d
www.EngWorks.ca
Grounding Fundamentals
150
Grounding of Portable Equipment
Exceptions apply to double insulated equipment p products Additional insulation barrier added to the electrical device Will be marked with a double insulated symbol
Ground may omitted if a Class A ground fault circuit interrupter is used
www.EngWorks.ca
Grounding Fundamentals
151
GFCI Schematic
Designed to provide protection against electric shock from leakage current flowing to ground Provide supplementary pp yp protection but are not a substitute for insulation and grounding protection
www.EngWorks.ca
Grounding Fundamentals
152
Ground Fault Circuit Interrupters
GFCI Class A Primarily used for personnel protection Typically trip at 5ma Time to trip based on the formula T=
20 I
1.43
T in seconds I fault current between 4mA and 260 mA
GFCI Class B (Ground Fault Equipment Protectors) Used for equipment protection Heat trace circuits in hazardous locations
30ma trip level
www.EngWorks.ca
Grounding Fundamentals
153
GFCI – Where Required
Outdoor receptacles Wet locations Health care facilities Panels supplying power for buildings or projects under construction Heat trace systems
www.EngWorks.ca
Grounding Fundamentals
154
Static Grounding Section 5
Did the Cellphone Cause the Ignition?
www.EngWorks.ca
Grounding Fundamentals
156
Static Hazards in Industry
Aviation Industry Static charges are built up during flight and on the ground
Manufacturing Paper and Printing Power P and d conveyor b belts lt moving i over pulleys ll
Paint operations Transfer of fluids
Coal, Flour and Grain Industry Movement and accumulation of dust and particles
Petrochemical P h i lP Processing, i R Refining fi i and d Transportation Movement of materials
www.EngWorks.ca
Grounding Fundamentals
157
Reasons for Static Grounding
Reduce the risk of fires and explosions Improve process and quality control Reduce the operating costs associated with storing flammable materials Minimize the potential for damage to sensitive electronic equipment q p Loss of electronic data
Comply p y with hazardous g goods transport p and storage g regulations Reduce the cost of insurance
www.EngWorks.ca
Grounding Fundamentals
158
Energy from a Static Discharge CH4/Air
Ignition Energy (mJ))
10
H2/Air
E = CV2 X 10-9
Typical range of spark discharge energy from a human body
Where C = Capacitance in pF V = Voltage in V E = Energy in mJ
1.0
Stoichiometric CH4/Air Mixture 0.274 mJ
0.1
Stoichiometric Air/H2 Mixture 0.017 mJ 0
www.EngWorks.ca
60 20 40 Fuel (% Volume)
80
Material
Dust Cloud
Dust Layer
Coal
60 mJ
560 mJ
Grain
30 mJ
-
Sulfur
15 mJ
1.6 mJ
Energy Required for Dust Ignition Grounding Fundamentals
159
Typical Values of Static Voltages and Capacitances p Equipment
Voltage
Object
Capacitance
Carpet Walk
12 kV
Human Being
200 pF
28.8 mJ
Fabric on Fabric
25 kV
Automobile
500 pF
312.5 mJ
Tank Truck
25 kV
Tank Truck
1000 pF
625 mJ
Tank Truck
25 kV
3.6m Tank with Insulated Lining
www.EngWorks.ca
100000 pF
Grounding Fundamentals
Energy
62,500 mJ
160
Static Charge Generation
Static electricity is generated by the movement of dissimilar poor conducting materials in close contact Non conductive fluids or powders in motion are a frequent cause of static
Static charge increases as the velocity of movement is increased. Anything which generates eddies, turbulence or discontinuities in flow Filters Changes in piping cross sectional area
www.EngWorks.ca
Grounding Fundamentals
161
Static Charge Generation
Triboelectric Effect contact electrification in which certain materials become electrically charged when coming into contact with another and are then separated
www.EngWorks.ca
Grounding Fundamentals
162
Electrostatic Charge Dissipation
Electrostatic charges continually leak away from a charged g body y Termed electrostatic dissipation Determined by a materials conductivity Measured in pS/m (picosiemens per meter) for petroleum products
Electrostatic charges accumulate when they are generated at a higher rate than they are dissipated Function of the relaxation time constant Time required for a charge to dissipate to approximately 37% of its original i i l value l
www.EngWorks.ca
Grounding Fundamentals
163
Conductivity and Time Constants for Typical yp Materials Product
Conductivity (pS/m)
Relaxation Time (Seconds)
Benzene
0.005
>>100
Toluene
1
21
Gasoline
10 – 3000
0.006 - 1.8
0.5 – 50
0.36 - 36
50 - 1000
0 018 – 0.36 0.018 0 36
Crude Oil
> 1000
< 0.018
www.EngWorks.ca
Grounding Fundamentals
Diesel Fuel Oil
164
Static Discharge
For an electrostatic charge to be a source of ignition, four conditions must be present: p A means of generating an electrostatic charge A means of accumulating an electrostatic charge capable of producing an incendiary spark A spark gap An ignitable vapor vapor-air air mixture in the spark gap
www.EngWorks.ca
Grounding Fundamentals
165
Static Charge Generation
www.EngWorks.ca
Grounding Fundamentals
166
Static Discharge Spark discharges occur between conductive objects that are at different voltages g Brush discharges can occur between a grounded conductive object j and a charged g low conductivity y material Incendive discharge is a discharge that has enough energy to cause ignition
www.EngWorks.ca
Grounding Fundamentals
167
Industrial Materials Prone to Static Electricityy Nonconductive glass Nonconductive conveyor belts Rubber Plastic resins Dry gases Paper Petroleum fluids
Oil water mixtures
www.EngWorks.ca
Grounding Fundamentals
168
Sources of Static Electricity Dry materials handling equipment Flammable liquid pumps and handling equipment
Charge Separation in a Pipe
Multiphase flow enhances charge generation
Liquid filling operations Plastic piping systems Conveyor Belts Liquid motion in tanks
www.EngWorks.ca
Grounding Fundamentals
169
Sources of Static Electricity
API 2003 www.EngWorks.ca
Grounding Fundamentals
170
Spark Promoters
A spark promoter will provide the necessary conditions for a spark gap to occur Loose floating conductive objects Conductive downspouts Gage tapes, thermometers or sample p containers lowered into a tank “tank gauging rod, high-level sensor,, or other conductive device that projects into the cargo space of a tank truck” API 2003
www.EngWorks.ca
Grounding Fundamentals
171
Static Sparks in Kanses
www.EngWorks.ca
Grounding Fundamentals
172
Static Control Ignition hazards from static sparks can be eliminated by y controlling g the g generation or accumulation of static charges Static removal involves recombining g separated p charges
Usually met by bonding all electrically conducting parts
www.EngWorks.ca
Grounding Fundamentals
173
Methods of Static Control
Piping Systems Keep fluid velocities low Max 15 ft/sec
Filling Operations Eliminate splash filling and free fall of materials Reduce filling velocity to less than 3 ft/sec
Fluid Storage Non Non-conductive conductive material storage containers are not allowed for NFPA Class I, Class II and Class III materials
www.EngWorks.ca
Grounding Fundamentals
174
Methods of Static Control
Humidity Control 65% or higher will prevent static discharge
Antistatic treatments Addition Additi off carbon b bl black k tto materials t i l
Use bonding and grounding to prevent build-up build up of potential differences between conductive parts Small gauge conductors generally sufficient to prevent the b ild p of static build-up
www.EngWorks.ca
Grounding Fundamentals
175
Static Grounding
Vehicle Connected to Ground
Vehicle Bonded Together
Vehicle Bonded together and To Ground
www.EngWorks.ca
Grounding Fundamentals
176
Static Grounding
Drum Container Storage Scheme
www.EngWorks.ca
Grounding Fundamentals
177
Static Grounding
Bulk Fluid Transfer Operation
www.EngWorks.ca
Grounding Fundamentals
178
Static Grounding
Bonding connections should be less than 10Ω for static control www.EngWorks.ca
Grounding Fundamentals
179
Railcar Loading Bonding Scheme
www.EngWorks.ca
Grounding Fundamentals
180
API RP 2003
www.EngWorks.ca
Provides guidance on how to protect against hydrocarbon ignition from static, lightning and stray current discharges Discusses how static charges are accumulated and how they can be safely dissipated Lightning protection for metallic tanks equipment and structures Identification and mitigation of stray currents resulting from fault currents and cathodic protection applications
Grounding Fundamentals
181
NFPA 77
www.EngWorks.ca
Applies to the identification, assessment,, and control of static electricity for purposes of preventing fires and explosions Provides guidelines for controlling t lli static t ti electricity l t i it iin selected industrial applications
Grounding Fundamentals
182
Lightning Protection Section 6
Lightning Strikes
www.EngWorks.ca
Grounding Fundamentals
184
Lightning
No such thing as a standard lightning strike Highly g y complex p p phenomenon Described by statistical means + + + + - - - - - -
+
Charge Separation in Cloud
High electric field causes ionization of air Corresponding charge + Induced in ground + Current flow in metallic pathways + + + + +
www.EngWorks.ca
Grounding Fundamentals
185
Lightning Strike Initiation
+ + + + + + + + + + + + + + - - - - - - - - - - - - - - - - - Downward leader --Upwards Charge flows - leader meets - to ground + downwards leader - through Upward leader + structure + + + + + + + + + + + + + + + + - + -
+
www.EngWorks.ca
Grounding Fundamentals
186
Lightning Discharge
Direct effects of lightning
Lightning Stroke
Heat energy and large mechanical h i l fforces Direct ignition of flammable materials
Indirect effects of lightning
Incendive sparks Electromagnetic pulse Earth current transients Bounded charges
Subsequent kA
98%
95%
4
80%
50%
20 46 4.6
5% 90
12
Typical Lightning Current Value
C Current
First negative kA
Cumulative Frequency
Time Typical Lightning Discharge www.EngWorks.ca
Grounding Fundamentals
187
Difference between Lightning and High Voltage Electricity Factor
Lightning
High Voltage
Energy Level
25 kA typical, millions of volts
Usually much lower
Time of Exposure
Brief, instantaneous
Prolonged
y Pathway
Flashover,, orifice
Deep, p, internal
Burns
Superficial and minor
Deep with major injury j y
Cardiac
Primary & secondary arrest, asystole
Fillibration
www.EngWorks.ca
Grounding Fundamentals
188
Incidence of Lightning
Lighting varies with
Terrain Altitude Latitude Time of the year
Number of flashes per square kilometre per year
www.EngWorks.ca
Grounding Fundamentals
189
Lightning Protection
Lightning strikes cannot be stopped but their energy can be diverted in a controlled manner Strike frequency goes up with the square of the height above the average terrain Damage g is caused by y the lightning g g energy gy taking g a random – high g impedance path to ground
3 components to a lightning protection system Air terminal or electrode the intercepts the surge Low impedance conductor system to ground Ground electrode to dissipate the energy
If all equipment within an elevated potential area is bonded together, the potential for damage is minimized
www.EngWorks.ca
Grounding Fundamentals
190
Inherent Grounding
Inherent grounding Metallic equipment, tanks and structures in direct contact with the ground do not require additional grounding if: The thickness of tanks, vessels and process equipment is greater than 5mm and are capable of withstanding a direct lightning strike without damage Indirect contact with the ground (self grounded) Sealed to prevent the escape of liquids, vapours or gas
Mostt petrochemical M t h i l ffacilities iliti are iinherently h tl grounded d d and d require no additional lightning protection Equipment that may require special consideration Open floating roof tanks Tank farms incorporating a containment liner
www.EngWorks.ca
Grounding Fundamentals
191
Bounded Charge Dissipation
Bounded Charges Occurs when a storm cell induces an electrical charge on everything beneath it Consideration with open floating roof tanks
--------------Teflon seal isolates + roof from tank + + + + +
Bounded Charge
++++++++++++++ Flammable Product
Floating Roof tank + + + + + +
+++++++++++++++++++++++++++++ www.EngWorks.ca
Grounding Fundamentals
192
Bounded Charge Dissipation
-
Bounded Charge
++++++++++++++ Flammable Product
Floating Roof tank -
Incendive discharge to ground
--------------------------------------------------- -
www.EngWorks.ca
Grounding Fundamentals
193
Protection against Lightning
Floating Roof Lightning Protection Floating roof cable connection Grounding Shunts (Not Recommended)
-------Cable connection to floating roof
Bounded charge Dissipated with Lightning strike Grounding shunt
Flammable Product
www.EngWorks.ca
Grounding Fundamentals
194
Methods of Lightning Protection
Conventional air terminal Provides a low impedance path to ground
+ + + + - - - - - --
+
Lightning rods (sometimes called Franklin rods) Conducting masts Overhead wires
RA = 0.84 x
h0.6
x
RA
I0.74
RA = Attractive Att ti radius di iin meters t h = height of lightning mast in meters I = Peak lightning current in kA
www.EngWorks.ca
RA
Grounding Fundamentals
+
+
+ + + +
+
195
Dissipative Array System (DAS)
Claim of the technology is to dissipate a charge before a lightning strike occurs No scientific proof that this in fact occurs Renamed the Charge Transfer System (CTS) technology in recent years Still considered ineffective
www.EngWorks.ca
Grounding Fundamentals
196
Early Stream Emission Air Terminals
Consist of lightning rods incorporating a device that triggers the early initiation of a lightning strike Effectiveness is also questioned
www.EngWorks.ca
Grounding Fundamentals
197
Lightning Surge Protection
Transient Overvoltages can damage electrical equipment Result in insulation breakdown and eventual failure
Mitigated g by y Surge arrestors Equipment insulation standards
Lightning Strike EMF Travelling Wave
Surge Voltage Wave
Line www.EngWorks.ca
Grounding Fundamentals
198
Surge Protection
Diminished Surge Voltage Wave 35kV
Transient Voltage Surge 70kV
13 8kV 13.8kV 25kV
Surge Arrestor
Is Surge Voltage is Surge suppressor Induced on secondary reduces surge g voltage g winding by capacitive to below BIL of transformer coupling effect
www.EngWorks.ca
Grounding Fundamentals
199
Equipment Insulation Voltage Withstand Requirements q
Basic Impulse Level (BIL) is used to describe the insulation class of electrical equipment q p Based on the voltage rating of the equipment Based on specified p crest value kV Specified in the various equipment standards
Surge Voltage and Current Wave www.EngWorks.ca
Grounding Fundamentals
200
Surge Arrestors
Surge arrestor must have a high resistance i t under d normall conditions diti and a very low resistance under surge conditions Metal oxide arrestor is the industry standard Consist of a series connection of zinc oxide elements
www.EngWorks.ca
Grounding Fundamentals
201
Surge Arrestors
Class of Surge Arrestors (IEEE Std C62.11)
Station Class Intermediate Class Distribution Class – Heavy duty Distribution Class – Normal duty y Secondary
600V Secondary Surge Arrestor www.EngWorks.ca
Distribution Class Surge Arrestor
Grounding Fundamentals
202
Surge Arrestor Installation Considerations
Should be mounted as close as possible to the transformer bushings Arrestor must be coordinated with the BIL of the equipment it is protecting A dedicated “down down lead” lead conductor to ground required for each arrestor Down lead conductor should be mechanicallyy and thermallyy capable of handling the surge voltage to ground Down lead should be as short as possible with no changes in direction Minimum radius of 200mm No bends greater than 90º
www.EngWorks.ca
Grounding Fundamentals
203
Lightning Arrestors – CEC Requirements 10-1000 Lightning Arrestors on Secondary Services 1) Grounding conductor shall be as short (and straight) as possible 2) The lightning arrestor grounding conductor may connected to the: a) b) c) d)
Grounded service conductor Common grounding conductor Service equipment grounding conductor Separate grounding conductor
Common ground conductor Grounded service conductor
Service i equipment i grounding di conductor d www.EngWorks.ca
Grounding Fundamentals
204
Lightning References
NFPA 780 “Standard for the Installation of Lightning g g Protection Systems” provides detailed guidance on the design of lightning protection systems” API 2003 “Protection against I iti Ignitions A Arising i i outt off St Static, ti Lightning and Stray Currents” IEC 61024 “P “Protection t ti off St Structures t Against Lightning – Part 1”
www.EngWorks.ca
Grounding Fundamentals
205
NFPA 780
Installation standard for lightning protection systems for building structures and facilities handling flammable vapors p g gases and liquids q Does not apply to electric generating, transmission and d di distribution t ib ti systems t
www.EngWorks.ca
Grounding Fundamentals
206
Electronic Equipment Grounding
Section 7
History
Grounding principles for communication systems were developed to meet the operational characteristics h t i ti off th the equipment i t Early telegraph systems used a two wire circuit path Later systems used the earth return as the signal path
Morse Landline Telegraph System www.EngWorks.ca
Grounding Fundamentals
208
History
Earth return offered several advantages Iron wire was used for telegraph conductors The use of an “earth” ground doubled the distance a circuit could be run
Eliminated one wire from the circuit
Problems endured: Quality of the signal was effected by weather Leakage current to ground during wet weather Resistance of the return ground path varied with soil conditions Presence of “foreign” voltages
www.EngWorks.ca
Grounding Fundamentals
209
History
Early development of the telephone system also relied on the th solid lid DC reference f ground as the return path lines were p particularly y noisy, y, picking up electrical noise from power lines, adjacent telephone lines, telegraph g p lines, streetcars, and machinery
The grounded system was later replaced with a system employing two wires per telephone line eliminating most of the noise
www.EngWorks.ca
Grounding Fundamentals
210
Electronic Equipment Grounding Terms
Signal Common Grounding referred to as the “DC Signal Common” Zero reference system for data lines Very sensitive to transient voltages
DC Power Supply Reference Ground Bus -ve terminal on a DC power Supply
Equipment Ground Bus Used for equipment chassis bonding Often referred to as the safety ground bus
Variety of other terms used (depending on manufacturer) AC Safety Ground, Computer Reference Ground, DC Signal Common, Earth Common, DC Ground Bus
www.EngWorks.ca
Grounding Fundamentals
211
Electronic Systems Grounding
Most electronic computer systems employ a DC reference ground Required for logic circuits
Problems occur when the DC reference ground is tied to the AC safety ground With the logic circuits referenced to the equipment chassis ground, any small amount of chassis potential caused by current flow in the grounding of the device could cause reference error in the equipment.
www.EngWorks.ca
Grounding Fundamentals
212
Noise in Sensitive Circuits
Errors result when the noise is greater than the actual signal g Results in parity check errors signal is ignored if check fails
30-50V L i Logic Signal Noise does not impact signal Noise cause parity check errors 3-5V Logic Signal
www.EngWorks.ca
Grounding Fundamentals
213
Circuit Noise Sensitivity Measurement
Signal to Noise Ratio
Measure of the interference in a communications circuit Measured in dB SNR = 10log S dB N Bit Error Rate Measure of the number of bits received to those in error Bit E Error Rate
10-66 10-7 10-88 10-9
0 www.EngWorks.ca
10
20
30
40
50
60
SNR (dB)
Grounding Fundamentals
214
Categories of Noise
Traverse Mode Noise A disturbance that appears pp between two active conductors in an electrical system Measurable between two line conductors or from line to neutral t l Originates from within the power system A B
V
C N G
www.EngWorks.ca
Grounding Fundamentals
215
Categories of Noise
Common Mode Noise Appears pp simultaneously y in each active conductor The term "common" refers to the fact that identical noise appears on both the active and neutral wires Generally involves the ground conductor A B C
V
N G
www.EngWorks.ca
Grounding Fundamentals
216
Typical Problems Associated with Electronic Systems y Grounding g Electronic Equipment Symptoms
Electrical Condition
Temporary or chronic data hang-ups Slow data transfers, multiple retries I/O Damage
Different signal reference levels I d Induced d currents t on cable bl
Intermittent lock-ups Corrupted Signals I/O damage
Transient voltages and currents
Random data errors Slow transfer in analog circuits
Stray currents and common mode noise in equipment gro nding cond grounding conductor ctor
www.EngWorks.ca
Grounding Fundamentals
217
Electronic Equipment Grounding
Computers require a “quiet” ground where no voltage transients or electromagnetic g noise occurs Stabilize input voltage levels Act as a zero voltage reference point for circuits
Led to the practice of installing an “Isolated Ground” system specifically for electronic equipment This practice was in direct conflict with the CEC which requires that all grounding systems be i t interconnected t d CEC is concerned with safety – not with performance
www.EngWorks.ca
Grounding Fundamentals
218
Principles of Noise Mitigation
For noise to be a problem Requires q a noise source of sufficient magnitude g Some means of communicating the unwanted noise to the electronic circuit Galvanic coupling Electrostatic / Capacitive coupling Magnetic g or Inductive coupling p g
Solving the problem involves either reducing the amplitude of the noise voltage or effectively isolating the circuit from the noise source
www.EngWorks.ca
Grounding Fundamentals
219
Source of Electrical Noise
Motor starts High g current in-rush is impressed p on the communications circuit
Fluorescent lighting High frequency noise associated with the ballast operation
Switching power supplies or VFD systems High frequency noise associated with switching power supplies
High Hi h voltage lt surges d due tto lilightning ht i strikes t ik and d electrical faults
www.EngWorks.ca
Grounding Fundamentals
220
Galvanic Coupling
Occurs when two circuits share a common conductor Examples: Telephone circuits that used the same common return t path th as DC ttram lilines iin the early days
Easily solved by separating the circuits by using separate return conductors
www.EngWorks.ca
Grounding Fundamentals
221
Electrostatic/Capacitive Coupling
Form of coupling that is proportional p p to the capacitance between the noise source and the signal wires Function of: Distance from the noise source to the signal wires Length g of the signal g wires Strength of the noise voltage Frequency of the noise voltage
www.EngWorks.ca
R1 I1 C1 I2 R2 Noise source
Grounding Fundamentals
I3
RL
C2 E
dV dT
222
Electrostatic/Capacitive Coupling
Mitigation
Shielding g of the signal g wires Separating the source from the noise Reducing the amplitude of the noise voltage Reducing the frequency of the noise voltage Twisting of the signal wires
www.EngWorks.ca
Grounding Fundamentals
223
Shielding
Conductor shield provides a lower impedance path for the noise current to flow I2 R1
Copper braid (85% coverage) provides a noise reduction ratio of 100:1 Aluminum Mylar tape with drain wiren provides a noise reduction ratio of 6000:1
C3
I3 I5
I4
RL
C4
R2 I1 C1
C3 and C4 are 1/100 C1 and C2
www.EngWorks.ca
Noise source E
Grounding Fundamentals
C2 dV dT 224
Shield Grounding
Shielding on instrumentation and communication circuits eliminates the electrostatic induction into wires carrying low signal voltages Shielding g method may y be Braided copper wire Metalized foil, with a copper drain wire Metal conduit (if steel conduit, this also serves as a magnetic shield)
Shields must be grounded One end only for frequencies up to 1 Mhz Two or more locations for frequencies > 1 Mhz
www.EngWorks.ca
Grounding Fundamentals
225
Magnetic or Inductive Coupling Depends of the rate of change and the mutual inductance between the source of noise and the signal g wires Influenced by: Magnitude of the noise current Frequency of the noise current Area A enclosed l db by the h signal i l wires Distance between the noise sources and d th the wires i www.EngWorks.ca
Grounding Fundamentals
226
Magnetic or Inductive Coupling
Mitigation Twist the signal g conductors This results in lower noise due to the smaller area for each loop. This means less magnetic flux to cut through the loop and consequently a lower induced noise voltage Noise voltage that is induced in each loop tends to cancel out the noise voltages from the next sequential loop
Inductive coupling is reduced by ratios varying from 14:1 for a fourinch lay to 141:1 for one-inch lay
www.EngWorks.ca
Grounding Fundamentals
227
Magnetic or Inductive Coupling
Mitigation Enclose the signal g wires with a magnetic g shield The magnetic flux generated from the noise currents induces small eddy currents in the magnetic shield which then create an opposing magnetic flux Ø1 to the original flux Ø2 Galvanized steel conduit is an effective magnetic shield Placing parallel (untwisted) wires into a steel conduit will provide a noise reduction of approximately 22:1
www.EngWorks.ca
Grounding Fundamentals
228
Physical Segregation
Separate the noise sources from the noise sensitive equipment q p Cable spacing based on susceptibility levels defined by IEEE 518 Level 1 – High: Analog signals less than 50V and digital signals less than 15V Level 2 – Medium: analog signals greater than 50V Level 3 – Low: Switching signals greater than 50V Level 4 – Power: Voltages g 0 – 1000V;; Currents 20–800A
www.EngWorks.ca
Grounding Fundamentals
229
Physical Segregation Level Level
Separation
1
2
2 – 30mm 30
1
3
3 – 160mm
1
4
4 – 670mm
Cables Contained in Separate Trays
Level Level Separation 1 2 2 – 30mm 1 3 3 – 110mm 1 4 4 – 460mm One Cables in Conduit and the other In Trayy
Level Level Separation 1 2 2 – 30mm 1 3 3 – 80mm 1 4 4 – 310mm Both Cables in Conduits www.EngWorks.ca
Grounding Fundamentals
230
Electrical Segregation
Y
Y
Y Shielded Isolation Transformer
M
M
M
M
UPS M
M
~
Y
Sensitive Loads
Worst Case Sensitive Loads are subject to voltage fluctuations caused by motor loads
=
=
~
Better Best
www.EngWorks.ca
Grounding Fundamentals
231
Separately Derived AC Power Distribution System y using g an Isolation Transformer
Isolates power to the control system from the rest of the AC distribution system y Provides good line regulation and transient filtering
Transformers should be of a shielded design g Provide superior noise isolation using the same concepts used for shielded cables
Input power to the transformers should be sourced from the highest line voltage available K factor f t transformers t f should h ld be b considered id d if th the control system load employs a large number of switching power supplies
www.EngWorks.ca
Grounding Fundamentals
232
Isolation Transformer Grounding
www.EngWorks.ca
Grounding Fundamentals
233
Separately Derived AC Power Distribution System y using g an UPS
Provides a continuous power supply to the control system y in the event of a p power interruption p Protects the control system from power system surges g Isolation transformers cannot prevent surge events from being transmitted to the load without additional surge protection
Provides a “conditioned” AC power supply to the control system Completely disconnects the control system power supply from the source providing superior isolation from power system transients and noise
www.EngWorks.ca
Grounding Fundamentals
234
1 Phase UPS
www.EngWorks.ca
Grounding Fundamentals
235
3 phase UPS
www.EngWorks.ca
Grounding Fundamentals
236
UPS Grounding
UPS configuration with common source for UPS and bypass yp circuit Does not meet the definition of a separately derived circuit Common mode noise attenuation may be a problem
www.EngWorks.ca
Grounding Fundamentals
237
UPS Grounding
Addition of a bypass transformer meets the definition of a separately derived source Improved common mode noise attenuation Neutrals in UPS and bypass transformer are connected Power distribution center must be within 15m of the UPS
www.EngWorks.ca
Grounding Fundamentals
238
UPS Grounding
Best configuration for common mode noise attenuation No restriction on distances Allows more flexibility in UPS voltages
www.EngWorks.ca
Grounding Fundamentals
239
Multiple UPS Grounding Scheme
www.EngWorks.ca
Grounding Fundamentals
240
Ground Loops
Occurs when there is more than one ground connection path between two pieces of equipment ground current may take more than one path to return to the grounding electrode form the equivalent of a loop antenna which very efficiently picks up interference currents Conductor lead resistance transform the currents into voltage fluctuations
Consequences Ground reference in the system is no longer a stable potential Signals ride on the noise Noise becomes part of the program signal
Example Audible 60hz noise in your stereo system
www.EngWorks.ca
Grounding Fundamentals
241
Ground Loop U it A Unit Internal Connection
+ Output -
Unit B
Communication Cable
+
Input -
Power Ground
Power Ground
1A Current Flowing 0.1V
0.2V Low Resistance 0.1Ω
Stray Current in Ground Causes Current to Flow in communication conductors
www.EngWorks.ca
Grounding Fundamentals
242
Ground Loop – Motor Start Unit A Internal Connection
+ Output -
Communication Cable
Unit B +
Input -
Power Ground
From Electrical Sources
Power Ground
M Motor Start
Motor frame bonded To ground www.EngWorks.ca
Grounding Fundamentals
243
Ground Loop Mitigation
Add one or more separate grounds Not N t CEC code d compliant li t Unit A Internal Connection
+ Output -
Communication Cable
Unit B +
Input -
Power Ground
C Current t Fl Flowing i Mi Minimized i i d High Resistance
www.EngWorks.ca
Separate p Instrumentation Ground
Grounding Fundamentals
Motor frame bonded 244 To ground
Ground Loop Mitigation
Interrupting the continuity of the grounding conductor Shielded communication cables
Unit A + Output -
Communication Cable
Unit B +
Input -
Power Ground
www.EngWorks.ca
Interrupt ground path here
Power Ground
Grounding Fundamentals
245
Ground Loop Mitigation •
Control the path of the ground current • Use an insulated ground receptacle Unit A + Output Power Ground
Unit B
Communication Cable
+
Input -
Isolated Instrument ground
Power Ground
Insulated ground conductor Single point ground
www.EngWorks.ca
Grounding Fundamentals
246
Isolated Ground Receptacle
Helps to limit electrical noise introduced into a circuit via the grounding conductor Establishes a dedicated ground path connected to ground at one point only
Conventional Receptacle www.EngWorks.ca
Isolated Ground Receptacle Grounding Fundamentals
247
Isolated Ground Receptacle
Power Transformer
Branch B h Ci Circuit it Panelboard Junction Box
NEMA IG#5-15R2 Isolated Ground Receptacle
Metal Device Box
System Ground
www.EngWorks.ca
Insulated Isolated Ground wire
Conduit or Cable
Bare Bonding Conductor or Conduit
Grounding Fundamentals
248
Concept of a Single Point Ground System
Poor or faulty grounds are the most common causes of control system y faults The best way of insuring the performance and reliabilityy of a control system y is to employ p y a single g point ground network system Consists of an organized system of ground wiring that t terminates i t in i a single, i l d dedicated di t d point i t on th the plant l t ground d grid Provides a clean reference for control signals
www.EngWorks.ca
Grounding Fundamentals
249
Single Point Ground System
www.EngWorks.ca
Grounding Fundamentals
250
Single Point Ground System Multiple Enclosures
www.EngWorks.ca
Grounding Fundamentals
251
Instrument Tri-Ground System Main Transformer
Ground C d t Conductor NGR
Lightning Arrestor Connection to system ground may be temporarily disconnected to isolate ground loop
System Ground AC Ground
Instrument Tri Ground www.EngWorks.ca
Grounding Fundamentals
252
Intrinsically Safe Circuit Grounding H Hazardous d A Area
Field Device IS Apparatus
Non Hazardous Area IIntrinsic i i Safe Barrier
Controll C System Interface
Associated pp Apparatus Interconnecting Wiring System
www.EngWorks.ca
Grounding Fundamentals
253
Intrinsic Safety – Simple Field Devices Non Hazardous
Hazardous Location Th Thermocouple l
Controller Simple Device
Internal Fault Controller
Internal Fault Controller
Explosion IS Barrier
IS Ground www.EngWorks.ca
Grounding Fundamentals
Device is Considered Safe under Fault C di i Conditions 254
Intrinsic Safe Barrier Circuit Protects Zener from Destruction Limits input current
Limits the output currentt
Hazardous Area
Safe Area Fuse
Control System Interface
Zener Z Diodes
Limits the output voltage lt www.EngWorks.ca
Current Limiting Resistor
Field Device
IS Ground
Grounding Fundamentals
255
Intrinsic Safety - Grounding
Incorrect Ground Scheme
www.EngWorks.ca
Correct Ground Scheme
Grounding Fundamentals
256
Intrinsic Safety - Grounding
Extremely important for the safe operation of an IS wiring systems M t be Must b visibly i ibl id identified, tifi d secure and d accessible ibl Must be capable of carrying the maximum fault current #12 AWG minimum conductor size
Total resistance must not exceed 1Ω Must be insulated from f ground in all places except at the point of connection to the ground electrode Duplicate up ca e g ground ou d co conductors duc o s required equ ed
Aluminium must not be used as a ground conductor material Potential for electrolytic corrosion
www.EngWorks.ca
Grounding Fundamentals
257
IEEE Standard 1100 ((Emerald Book))
Recommended engineering principles and p practices for p power and g grounding g sensitive electronic equipment Provides consensus in an area where conflicting information has prevailed Excellent reference that describes the many challenges associated with grounding electronic equipment Power related noise control Signal related noise control
www.EngWorks.ca
Grounding Fundamentals
258
Station Electrode Design Section 8
Ground Grid Design
www.EngWorks.ca
Grounding Fundamentals
260
Ground Grid Design Fundamentals
In the event of a fault or transient phenomena ((lightning g g or switching g transients)) the g ground g grid must Ensure personnel safety Protect equipment against damage
Design Considerations Grid must be able to withstand the maximum ground current without damage Limit the ground potential rise between two points to a safe value
www.EngWorks.ca
Grounding Fundamentals
261
CEC Code Requirements
Section 10 “Grounding and Bonding” addresses grounding g g electrodes for facilities operating p g at less than 750V to ground Requirements are minimal
Section 36 “High Voltage Installations” addresses the grounding of facilities operating at more than 750V to ground d Requirements are in addition to those defined in Section 10 More substantial in nature and therefore require a deeper understanding of ground electrode theory
www.EngWorks.ca
Grounding Fundamentals
262
CEC Section 10 Requirements
CEC Section 10 does not specify a minimum ground resistance for a g g grounding g electrode but specifies the acceptable methods of obtaining a grounding electrode
NEC specifies a ground resistance of 25Ω or less
10-700 Grounding G Electrodes shall consist off a) Manufactured grounding electrodes b) Field Fi ld assembled bl d grounding di electrodes l t d c) In-situ grounding electrodes
www.EngWorks.ca
Grounding Fundamentals
263
Manufactured Ground Electrode
Must be certified to CSA C22.2 No.41 “Grounding and Bonding g Equipment” q p Rods must be driven to their full length and separated by a minimum of 3m Connected by a bonding conductor sized by Table 17
R d El Rod Electrode t d www.EngWorks.ca
Plate Electrode Grounding Fundamentals
264
Field Assembled Ground Electrode
Min 6m bare copper conductor buried or encased in concrete
conductor must be encased within the bottom 50 mm of a concrete foundation footing, with the footing in direct contact with the earth,, at not less than 600 mm below finished grade Field Assembled Ground Electrode www.EngWorks.ca
Grounding Fundamentals
265
In-situ Ground Electrode
Copper water pipe Metal reinforcement of concrete slabs, concrete pilings, and concrete foundations Iron pilings, when they are in significant contact with earth 600 mm or more below finished grade
In-situ Grounding Electrode www.EngWorks.ca
Grounding Fundamentals
266
10-700 Grounding Electrodes (5) Where local conditions such as rock or permafrost prevent a rod or g p grounding gp plate from being g installed at the required burial depth, a lesser depth shall be permitted
Horizontal Ground Rod Installation www.EngWorks.ca
Grounding Fundamentals
267
Other Section 10 Requirements
Lightning rod systems must be connected to ground using g a separate p g grounding g electrode that is not used as the grounding electrode for any other system Where a facilityy incorporates p more than one g ground electrode for lightning, communication or other systems Must be separated by a minimum of 2m Bonded together by a minimum #6AWG conductor
www.EngWorks.ca
Grounding Fundamentals
268
CEC Section 36 Requirements 36-302 Station ground electrode Every outdoor station shall be grounded by means of a station ground electrode that shall meet the requirements of Rule 36-304 and shall a)
consist of a minimum of four driven ground rods not less than 3 m long and 19.0 mm in diameter spaced at least the rod length apart and, where practicable, located adjacent to the equipment to be grounded;
b) have the ground rods interconnected by ground grid conductors not less than No. 2/0 AWG bare copper buried to a maximum depth of 600 mm below the rough station grade and a minimum depth of 150 mm below the finished station grade; and c) have the station ground grid conductors in Item (b) connected to all non-current-carrying non current carrying metal parts of equipment and structures www.EngWorks.ca
Grounding Fundamentals
269
Distribution Utility Standard Ground Electrode Design g
www.EngWorks.ca
Grounding Fundamentals
270
Distribution Utility Standard Ground Electrode Design g
www.EngWorks.ca
Grounding Fundamentals
271
CEC Requirements for Station Ground Resistance 36-304 Station ground resistance (see Appendix B) 1) The maximum permissible resistance of the station ground electrode shall be determined by the maximum available g ground fault current injected j into the ground by the station ground electrode or by the maximum fault current in the station, and the ground d resistance i t shall h ll b be such h th thatt under d allll soilil conditions that exist in practice (e.g., wet, dry, and frozen conditions) …..
www.EngWorks.ca
Grounding Fundamentals
272
CEC Section 36 – Ground Potential Rise 36-304 Station ground resistance ….the the maximum ground fault current conditions shall limit the potential rise of all parts of the station ground g g grid to 5000V 2) In addition to subrule (1), the touch and step voltage at the edge, within, and around the station grounding electrode…..shall not exceed the tolerable values specified in Table 52
www.EngWorks.ca
Grounding Fundamentals
273
CEC Section 36 – Tolerable Touch and Step p Voltages g
www.EngWorks.ca
Grounding Fundamentals
274
IEEE Standard 80
IEEE Standard 80 Defines the safe limits for touch and step potentials Provides guidance on the design of ground systems for outdoor substations Primarily Pi il used db by utilities tiliti for grounding on high g substations voltage
www.EngWorks.ca
Grounding Fundamentals
275
Ground Potential Rise (GPR)
Ground potential rise is a function of the current g injected j into the earth and the soil magnitude resistivity Measured with respect to a remote point May vary from a few meters to several hundred meters away
5000V criteria specified in the CEC is based on the maximum GPR communication circuits are d i designed d tto h handle dl
GPR = IG X Rg
IG = Maximum Grid Current Rg = Grid Resistance www.EngWorks.ca
Grounding Fundamentals
276
Ground Potential Rise 3 wire i ttransmission i i with ith no Metallic return path
G
∆
A
∆
N
N G
B C
Generator Transformer
Ground Fault
IG
NGR
EG
GPR
E th Earth Rg Ground Path
www.EngWorks.ca
Grounding Fundamentals
277
System Ground Fault Return Path Non Metallic conduit With no bonding conductor
Y
0.1Ω 500V
Ig=5kA Ground Return Path
Lack of bonding conductor forces ground fault return path through the earth creating personnel hazard www.EngWorks.ca
Grounding Fundamentals
278
System Ground Fault Return Path Metallic conduit with bonding conductor Low Impedance Ground Return Path
Y Ig=5kA
High Impedance Ground Return Path
Bonding conductor provides low impedance path to source: Stray current is minimized with improved safety www.EngWorks.ca
Grounding Fundamentals
279
Current GF Path with Local Source
Y
Y
Multiple low impedance ground paths limit the ground potential rise within th station the t ti www.EngWorks.ca
Grounding Fundamentals
280
Current GF Path with Remote Source
Overhead ground wire current path
Y
Y
Stray Current Paths
Multiple high impedance ground current paths back to source www.EngWorks.ca
Grounding Fundamentals
281
Ground Potential Rise (GPR)
Grid system must limit the ground potential rise (GPR) between two points to a safe value GPR can cause hazardous voltage in the form of Step & Touch Potentials May occur in location remote to the actual fault
Safe values of GPR, Touch and Step Voltages are determined by the human tolerance to shock currents Function of current magnitude, g , duration and frequency q y
GPR = IG X Rg IG= Maximum Grid Current Rg = Grid Resistance
www.EngWorks.ca
Grounding Fundamentals
282
Step Voltage ESTEP
Potential Rise above remote earth during short circuit R1
IF
ESTEP
IF RF RK
R2 R0
RF
RK
R1 www.EngWorks.ca
R2
R0 Grounding Fundamentals
283
Touch Voltage ETOUCH
Potential Rise above remote earth during short circuit
IF
ETOUCH
IF
RF
R1
RK
RF/2 RK R0 RF/2
R1 www.EngWorks.ca
R0 Grounding Fundamentals
284
Touch and Step Potential IEEE 80
ρ = resistivity of earth beneath surface ρs = surface material resistivity (Ω . m) hs = thickness of surface material in m www.EngWorks.ca
Grounding Fundamentals
285
Relationship between GPR, Touch and Step p Potentials
Y
Es
Et
Emesh
GPR
Remote Earth
www.EngWorks.ca
Grounding Fundamentals
286
Mesh Voltage
Defined as the maximum surface voltage g p potential difference between a grid conductor and and a point between two grid conductors Th Theoretical ti l maximum i touch voltage found within a ground grid
www.EngWorks.ca
Grounding Fundamentals
287
Touch and Step Potential 1 1.
2.
Two ways of making a grounding system safe Minimize the touch and step voltages that may appear at any point within the substation and around its perimeter p Increase the tolerable touch and step voltages by placing a high resistivity material over rough grade
Asphalt Crushed rock
Both methods are typically used together
www.EngWorks.ca
Grounding Fundamentals
288
Ground Surface Potential Gradients
High ground resistance increases step potential
10kA
Ground Rod
R1 Re1
Gn nd Surface Potential P
30kV
R = R1+Re1 = 3 ohm 0 Volts Infinite Earth
8kV Step Potential 0
www.EngWorks.ca
Distance from Rod Grounding Fundamentals
289
Ground Surface Potential Gradients Multiple ground rods reduce the ground surface potential low resistance surface reduces step potential
10kA
Gn nd Surface Potential P
R1+Re1 = 3 ohms
R1 4kA
R2
0 ohms
Re1
6kA
Re2
R2+Re2 = 2 ohms 0 Volts Infinite Earth
12kV 0
www.EngWorks.ca
Infinite Earth (0V) Grounding Fundamentals
290
Symmetrical Grid Current
The current that causes the ground potential rise in a grid is from a remote source g Only a portion of the current is responsible for the ground p g potential rise Multiple return paths include Overhead ground conductors Cable shields
The current flowing into the ground that is responsible for the GPR is adjusted by a split factor to incorporate the effect of the multiple paths
www.EngWorks.ca
Grounding Fundamentals
291
Symmetrical Grid Current Ig = Sf x If Ig = RMS Symmetrical Grid Current Sf = Split factor (Current Division Factor) If = RMS value of the symmetrical ground fault current Sf may be estimated using computer programs or by graphical analysis Typically ranges between 10 – 70% of If Refer to IEEE 80 for more information www.EngWorks.ca
Grounding Fundamentals
292
Split Factor Split factor accounts for the multiple current paths that will occur in a fault situation Overhead ground wire current path
Y
Y
If
Ig = Sf x If
www.EngWorks.ca
Grounding Fundamentals
293
Split Factor Graphical Estimate IEEE 80 Annex C Curve most likely to be used for a single circuit customer owned substation
28%
The symmetrical grid current (Ig ) would be approximately 28% of the total fault current for a substation with a 2.5Ω grid resistance
2.5Ω Substation www.EngWorks.ca
Grounding Fundamentals
294
Grid Current for Design IG = Cp x Df x Ig IG = Maximum Grid Current Cp = Estimated growth factor during station life span Cp = 1 ffor zero growth g Df = Decrement factor for the duration of the fault Ig = RMS value off the symmetrical y ground g fault f current
www.EngWorks.ca
Grounding Fundamentals
295
Decrement Factor Decrement factor accounts for the total asymmetric fault current flowing between the grounding system and the surrounding earth Df Fault Duration tf Sec 0.008 01 0.1 0.25 0.5
Subtransient S b i T Transient i Network N k Network (0-5 cycles) (5-30 cycles) www.EngWorks.ca
Cycles 0.5 6 15 30
1.65 1 25 1.25 1.1 1.0
S Steady State S Network (>30 ( 30 cycles))
Industrial Power System Protection and Control
296 296
Design Information Provided by Utility Current values to be used in the design of the station ground d grid id
www.EngWorks.ca
Grounding Fundamentals
297
Ground Resistance
The “WildCard” in the grounding design Ground grid resistance varies with soil conditions and may change over time Changing Ch i water t ttable bl Resistivity of the ground will change in drying or drought conditions
Chemical content of soil Presence of salts decrease resistivity
Frozen ground or permafrost conditions Consideration in all Canadian g grounding g situations www.EngWorks.ca
Grounding Fundamentals
298
Soil Resistivity (Ω . cm) = 100 x (Ω . M) Medium
Resistivity (Ω . cm) Minimum
Surface Soil, Loam
100
Clay, Shale, Gumbo
300
Sand and Gravel Limestone
Average
Maximum 5,000
4,000
20,000
5 000 5,000
10 000 10,000
500
400,000
Granite, basalt
1,000,000
Low Hills, Rich Soil
3,000
Medium hills, Medium Soil
20,000
St Steep Hills, Hill R Rocky k S Soilil
50 000 50,000
Sandy, dry coastal country
30,000
50,000
500,000
Freshwater Lake
10,000
20,000
20,000,000
Sea water
2,000
10,000
20,000
www.EngWorks.ca
Grounding Fundamentals
299
Effects of Moisture on Resistivity Moisture Content 0 2.5 5 10 15 20 30
www.EngWorks.ca
Resistivity Ω Ω-cm cm Top Soil Sandy Loam > 109 > 109 250,000 150,000 165,000 43,000 53,000 18,500 19,000 10,500 12,000 6,300 6,400 4,200
Grounding Fundamentals
300
Effects of Temperature on Resistivity for Sandyy Loam
www.EngWorks.ca
Temperature ºC 20
Resistivity Ω cm Ω-cm 7,200
10
9,900
0 (Water)
13,800
0 (Ice)
30,000
-5
79,000
-15
330,000 Grounding Fundamentals
301
Seasonal Variation in Earth Resistance
19mm Rod in Stony Clay Soil Curve 1 – 1m below surface C Curve 2 – 3m 3 b below l surface f
Moisture and temperature p is more stable at g greater depths p below the surface
www.EngWorks.ca
Grounding Fundamentals
302
Effect of Chemicals on Earth Resistivity for Sandyy Loam Effect of Salt on Resistivity of Soil ((Moisture 15% Temp p 17ºC)) Added Salt % by Weight of Moisture
Resistivity (Ω-cm)
0
Effect of Temperature on Resistivity of Soil with Salt (20% Moisture 5% Salt) Temperature C ºC
Resistivity (Ω-cm)
10,700
20
110
0.1
1,800
10
142
1.0
460
0
190
5
190
-5 5
312
10
130
-13
1,440
20
100
www.EngWorks.ca
Grounding Fundamentals
303
Electrode Resistance
ρ(Ω.cm) Ω Rg (rod) = 335 cm Applies to 3m ground rod and is accurate within 15% www.EngWorks.ca
Grounding Fundamentals
304
Multiple Ground Rod Resistance
Resistance of a grounding system of 2-24 rods placed on rod length p g apart p will p provide a g grounding g resistance divided by the number of rods multiplied by the factor F taken from Table 14 IEEE Std 142
www.EngWorks.ca
Grounding Fundamentals
305
Alternate Formulas for Ground Rod Resistance Contact resistance of one ground rod ρ 4L - 1 R= Ln X 2πL a ρ = Soil resistivity in Ω Ω-cm cm L = rod length in cm a = rod diameter in cm
Ground Rod Separation D = 2.2 X L
Contact resistance of multiple ground rods Rn =
R n
X 2 – e-0.17(n - 1)
n = number of ground rods
www.EngWorks.ca
Grounding Fundamentals
306
Smoking Ground Rod
Current loading capacity of a ground rod is a factor Current p passing g through g an electrode will have a direct impact on the temperature and moisture conditions immediately surrounding the ground rod Must M t be b checked h k d I=
34,800 X d X L
√ ρXt
I = Current loading gp per foot of rod length g d = rod diameter in meters L = Length in meters ρ = ohm meter t = seconds (3 (3.0 0 seconds is the value recommended by IEEE) www.EngWorks.ca
Grounding Fundamentals
307
Ground Rod Resistance to Earth Tutorial
Ground Rod Resistance to Earth Tutorial 1. Determine the resistance to earth for a ground rod system y consisting g of Qty y 4 – 10 foot long g 5/8” (16mm) ground rods spaced at 10’ intervals and interconnected connected together and placed in clay soil 2. Calculate the resistance to earth for a ground rod system t consisting i ti off Qty Qt 4 – 20 ffoott 5/8” (16mm) (16 ) ground rods interconnected together and placed in clay soil 3. Calculate the current loading capacity of the system
www.EngWorks.ca
Grounding Fundamentals
309
Ground Rod Resistance to Earth Tutorial Answers
4 - 10’ Ground Rods ρ(Ω.cm) Ω Rg (rod) = 335 cm Rg (rod) =
Average ρ for clay soil = 4000 Ω·cm
4000 Ω.cm = 11.94 Ω 335 cm
For 4 ground rods 11.94Ω 11 94Ω Rg (4 rods) = 4
X 1.36 = 4Ω
IEEE 142 Table 14
www.EngWorks.ca
Grounding Fundamentals
311
4 – 20’ Ground Rods Contact resistance of one ground rod ρ = Soil resistivity in Ω-cm ρ 4L - 1 L = rod length in cm R= Ln X 2πL a a = rod diameter in cm 4000 4(610) - 1 R= Ln X = 6.649Ω 1.6 2π(610) Contact resistance of multiple ground rods Rn = Rn = www.EngWorks.ca
R n
X 2 – e-0.17(n - 1)
6.649 4
X
n = number of ground rods
2 – e-0.17(4 - 1) = 2.32Ω
Grounding Fundamentals
312
Current Carrying Capacity of Ground Rod System y I=
34,800 X d X L
√ ρXt
I = Current loading of the ground rod system d = rod diameter in meters L = Length in meters ρ = ohm meter t = seconds (3.0 seconds typical value)
34,800 34 800 X 0.016 0 016 X 3.048 3 048 X 4 = 620 Amps 4 – 10ft Ground Rods I = 40 X 3
√
4 – 20ft Ground Rods I =
www.EngWorks.ca
34,800 X 0.016 X 6.1 X 4
√ 40 X 3 Grounding Fundamentals
= 1240 Amps
313
Primary and Auxiliary Ground Electrodes
Primary Ground Electrode Installed specifically p y for g grounding gp purposes p Ground rods Interconnecting wire mesh
A ili Auxiliary G Ground d El Electrode d Installed for purposes other than grounding Typically T picall ha have e limited ccurrent rrent carr carrying ing capacit capacity Examples Steel building gp piles Steel reinforced concrete foundations Rebar grounding
www.EngWorks.ca
Grounding Fundamentals
314
UFER Ground
First used by the US Army to ground a series of bomb storage vaults in the vicinity of Flagstaff, Arizona Dry desert conditions made for a very poor ground electrode system Herbert Ufer developed an alternate electrode system based on using the steel rebar used to reinforce concrete
Concrete is inherently alkaline and hydroscopic (absorbent) in nature The high pH provides a supply of ions to conduct current soil around concrete becomes “doped” by the concrete
has an effective resistance of 3000 Ω-cm
Bases for the development of concrete encased electrodes
www.EngWorks.ca
Grounding Fundamentals
315
Concrete Encased Electrodes
Can be used as part of an effective low resistance grounding system Will typically lower the overall resistance of the ground
Very cost effective! Adds very little cost to the installation Reduces the amount of buried conductor required for an installation Aids in reducing the amount of construction re-work Buried B i d ground d conductors d t are a popular l it item tto dig di up d during i ttrenching hi operations
The 2006 NEC requires that rebar encased in concrete be incorporated into the system ground No equivalent CEC requirement
www.EngWorks.ca
Grounding Fundamentals
316
Methods of Connecting Rebar to Building Steel
Option 1 – Connect structural steel and rebar using ground wire Requires electrical trade to be on on-site site during pouring of foundations
Bolted Connection to Steel C Copper Wi Wire
Ground Well
Grounding Compression p Connection or Cadweld
To ground grid
www.EngWorks.ca
Grounding Fundamentals
317
Methods of Connecting Rebar to Building Steel
Option 2 - Tie the vertical rebar to anchor bolts and the steel columns are g grounded through g the bolts and nuts
Rebar welded To anchor bolts
Ground Well
To ground grid
www.EngWorks.ca
Grounding Fundamentals
318
Rebar Grounding Installation Considerations
Rebar must be bare or zinc coated Minimum length – 6m Minimum diameter 13mm I t ll d iin a minimum Installed i i off 50mm of concrete
Surge Current Conductivity of Rebar in Concrete Rebar Diameter (in.)
Surge Ampere per Foot
0 375 0.375
3400
Preferably y located near the bottom of the foundation
0.5
4500
Concrete must be in direct contact with earth
0.625
5500
0.75
6400
10 1.0
8150
www.EngWorks.ca
Grounding Fundamentals
319
Ground Conductors
For a given application, ground rods are more effective than g ground g grid conductors Ground rods will penetrate the frost level injecting current into unfrozen ground
Basic Requirements for the selection of a Ground Grid conductor H Have sufficient ffi i t conductivity d ti it Resist fusing and mechanical deterioration under fault conditions Be mechanically reliable and rugged Resist corrosion
www.EngWorks.ca
Grounding Fundamentals
320
Ground Grid Conductor Options
Copper
Highest g conductivity y Highest cost Subject to theft Commercial hard drawn specification most often used
Copper-clad steel Good option where theft is a problem
Aluminum Not recommended as is subject to corrosion
Steel Poor conductivity limits use
www.EngWorks.ca
Grounding Fundamentals
321
Sizing of Grid Conductors
Based on the design ground fault current and the fault duration time
Akcmil = I · Kf √tc Akcmil = area of conductor in kcmil I = Fault current in kA tc = current duration in seconds (IEEE recommends 3.0 seconds) Kf = constant based on the material (Refer to table 2 IEEE 80)
www.EngWorks.ca
Grounding Fundamentals
322
Material Constants ((Excerpt p from Table 2 IEEE 80))
Material
Conductivity
Kf
Copper, Annealed Soft Drawn
100%
7.00
C Copper, C Commercial i lH Hard dD Drawn
97%
7 06 7.06
Copper Clad Steel Wire
40%
10.45
Aluminum 6201 Alloy
52.5%
12.47
Steel 1020
10.8%
15.95
Stainless Steel 304
2.4%
30.05
www.EngWorks.ca
Grounding Fundamentals
323
Grid Conductor Sizing Example
Fault current is estimated at 6kA Commercial hard drawn copper selected as the grid conductor What size of grid conductor is appropriate to handle the maximum fault current for 3.0 seconds? Akcmil = I · Kf √tc Akcmil = 6 · 7.06 √3.0 Akcmil = 73.37kcmil → #1 AWG
www.EngWorks.ca
Grounding Fundamentals
324
Grid Conductor Sizing Table Current Carrying Capacity (kA) kcmil
AWG
pp HD Copper
Copper pp Clad Steel Wire
Steel 1020
500
-
40
27.62
18.1
250
-
20 4 20.4
13 81 13.81
9 05 9.05
212
4/0
17.34
11.71
7.67
133
2/0
10.88
7.35
4.81
83.7
#1
6.84
4.62
3
66.4
#2
5.43
3.67
2.4
Based on a 3.0 Second Fault Duration
www.EngWorks.ca
Grounding Fundamentals
325
Grounding Connections
All grounding connections must be selected to withstand the short circuit forces and heating effects associated with an extended groung fault Resist the effects of corrosion High pullout resistance Time-current curves for ground grid conductors and connectors
www.EngWorks.ca
Grounding Fundamentals
326
Typical Connections found within a Grid Design g
Conductor to Ground Rod
Conductor to Conductor www.EngWorks.ca
Substation F Fence to t Grid G id Conductor Grounding Fundamentals
Equipment to G id C Grid Conductor d t 327
Cadweld Connections Thermite welding process is used to fuse the connection Suitable for high current applications Will meet the requirements of IEEE 837 ““IEEE Standard for Qualifying Permanent Connections Used in Substation Grounding Grounding”
Cadweld Connection
www.EngWorks.ca
Grounding Fundamentals
328
Grounding Connections
Compression Connections Acceptable p alternative to Cadweld connections in substation applications
Compression Tool www.EngWorks.ca
Grounding Fundamentals
329
Corrosion Considerations
A basic corrosion cell consists of the following: Anode – An electrode losing g metal Cathode – An electrode gaining metal Electrolyte – chemicals in solution in contact with the anode and cathode 0.78V Connecting conductor -
V
+
IRON Anode
Earth
COPPER Cathode
G l Galvanic i C Cellll www.EngWorks.ca
Grounding Fundamentals
330
Corrosion Considerations
When iron or steel is connected to copper with a low impedance p conductor,, it corrodes Rate of corrosion is dependent on the current flow Each ampere-year of current flow will result in 20lbs of steel being lost μ –5 μA 5A + A
IRON IRON Anode
www.EngWorks.ca
COPPER Earth
Cathode
Soil Corrosivity Ohm-Cm Corrosivity Etouch = 734V Go to step 8 and Calculate Mesh Voltage www.EngWorks.ca
Grounding Fundamentals
393
Step 8A Calculate Mesh Voltage
Calculate the MESH voltage for the grid design Em =
ρ · Km· Ki · IG LM
=
60 · Km· Ki · 400 LM
EM = Mesh Voltage ρ = Soil resistivityy in Ω·m Km = Geometrical correction factor for grids of varying dimension Ki= Correction factor for grid geometry IG = Maximum grid current LM = Effective length of grid conductors and ground rods in m
www.EngWorks.ca
Grounding Fundamentals
394
Km = Geometrical correction factor 1
D2 Km = · ln l 16 · h · d 2·π
+
D+2·h2 8·D·d
-
h 4·d
+
Kii
8 · lln π(2 · n – 1)
Kh
For grids with ground rods along the perimeter and thoughout the grid area: Kii = 1
Kh =
1+ h √
ho
ho = 1m (grid reference depth) =
1 + 0.45 = 1.2 √
1
D = Spacing between parallel conductors in m = 3.5m h = Depth of ground grid conductors in m = 0.45m d = Diameter of grid conductor in m = 0.0093m n = Effective number of parallel conductors in a given grid
www.EngWorks.ca
Grounding Fundamentals
395
Km = Geometrical correction factor LC = is the total length of the conductor in the horizontal grid in m = 120m Lp = is the peripheral length of the grid in m = 48m A = Area of Grid = 140m2
n = na · n b · n c · n d na =
nb =
2 · LC Lp
=
Lp
2 · 120 48 =
=5
48 = 1.01 1 01 4 · √140
4 · √A nc = 1 for square and rectangular grids nd = 1 for square, rectangular and L – shaped grids
n = 5 · 1.01 · 1 · 1 = 5.05 Ki= Correction C ti factor f t for f grid id geometry t Ki = 0.644 + 0.148 · n = 0.644 + 0.148 · 5.05 = 1.39 www.EngWorks.ca
Grounding Fundamentals
396
LM = Length of Grid Conductors and Ground Rods For grids with ground rods in the corners, as well as along the perimeter and throughout the grid
Lr LM = LC + 1.55 + 1.22 √Lx2 · Ly2
• LR
Lr = is the length of each ground rod in meters Lx = is the maximum length of the grid in the x direction in m Ly = is the maximum length of the grid in the y direction in m LC = is i the th length l th off conductors d t in i the th grid id in i m LR = is the length of rods in the grid in m
LM = 120 + 1.55 + 1.22
www.EngWorks.ca
3 √102 · 142
Grounding Fundamentals
• 39 = 181.46
397
Mesh Voltage 1
3.52 Km = · ln + 16 · 0.45 · 0.0065 2·π
3.5 + 2 · 0.45 2 8 · 3.5 · 0.0065
0.45 4 · 0.0065
-
1
8 + · ln π(2 · 5.05 – 1) 12 1.2
Km = 0.70 0 70 Ki = 1.39 LM = 121.57 121 57 Em =
www.EngWorks.ca
ρ · Km· Ki · IG LM
=
60 · 0.7· 1.39 · 400 181.46
Grounding Fundamentals
= 128.7V
398
Step 8B Calculate Step Voltage Es =
ρ · Ks· Ki · IG LS
Es = Step Voltage ρ = Soil resistivity = 60 Ω·m Ki= Correction ffactor for f grid g geometry g y = 1.39 IG = Maximum grid current = 400A LS = Effective buried conductor length m Ks = Spacing factor for step voltage
LS = 0.75 · LC + 0.85 · LR LC = is the total length of the conductor conducto in the horizontal ho i ontal grid g id in m = 1200 LR = is the total length of all ground rods = 39m
LS = 0.75 0 75 · 120 + 0.85 0 85 · 39 = 123.15 123 15
www.EngWorks.ca
Grounding Fundamentals
399
Step 8B Calculate Step Voltage KS =
1 π
1 1 1 n-2 1 – 0.5 + + 2·h D+h D
D = Spacing between parallel conductors in m = 3.5 h = Depth of ground grid conductors in m = 0.45 d = Diameter of grid conductor in m = 0.0065 n = Effective number of parallel conductors in a given grid = 5.05
1 KS = π
Es =
www.EngWorks.ca
1 1 1 5 05 2 5.05-2 + + 1 – 0.5 2 · 0.45 3.5 + 0.45 3.5
ρ · Ks· Ki · IG LS
=
= 0.513
60 · 0.513 · 1.39 · 400 123.15
Grounding Fundamentals
= 139V
400
Step 9 Em < Etouch? Emesh = 128.7V < 734V = Etouch YES go to step 10
www.EngWorks.ca
Grounding Fundamentals
401
Step 10 Es < Estep? Es = 139V < 2446V = Estep YES go to Detailed Design
www.EngWorks.ca
Grounding Fundamentals
402
Detailed Design 2/0 AWG Insulated Gnd Wire
3.3m
3.3m
600V MCC DCS Eqpt Gnd Bus Isolated Inst. Gnd Bus
600V Swgr 5A NGR
33m groundd rods d (16 in total)
600V XFMR
UPS
5kV MCC
Ground rods with Inspection well
5 kV Swgr
5kV XFMR Surge Arrestor
Intergrid Grounding Conductors Bare 2/0 AWG
125A NGR 2/0AWG to Xo Terminal
Gnd Conductor as short as possible www.EngWorks.ca
Grounding Fundamentals
403
Substation Ground System
Instrumentation Ground Designed to insure that all components of the control system operate at the same potential Eliminate potential ground loops Isolate system noise on the ground system Allow ground to be accessible for disconnect to assist in isolating ground loops
www.EngWorks.ca
Grounding Fundamentals
404
Control System Grounding Scheme SWGR
UPS
UPS PNL
N
Main Transformer
Ground Conductor Lightning A Arrestor t
Instrument Panel Bonding Conductors
Bonding Conductor
NGR
System Ground
Isolated Ground Bus
CP
CP
CP
Insulated Instrument Ground conductors
www.EngWorks.ca
Grounding Fundamentals
405
Computer Analysis GPR < Touch Summer Conditions
www.EngWorks.ca
Grounding Fundamentals
406
Computer Analysis GPR < Touch Summer Conditions
www.EngWorks.ca
Grounding Fundamentals
407
Computer Analysis GPR < Touch Winter Conditions
www.EngWorks.ca
Grounding Fundamentals
408
Computer Analysis IEEE 80
www.EngWorks.ca
Grounding Fundamentals
409
Computer Analysis IEEE 80
www.EngWorks.ca
Grounding Fundamentals
410
Computer Analysis Optimized
www.EngWorks.ca
Grounding Fundamentals
411
Computer Analysis Optimized
www.EngWorks.ca
Grounding Fundamentals
412
Summary and Wrap up
Section 10
Learning Objectives Review 1. To understand why we ground Protect life from the danger of shock Limit the voltage on a circuit Facilitate operation of protective devices
www.EngWorks.ca
Fuse
Low Impedance path to source allows fuse to operate
Accidental Ground
L
G1 Neutral
Grounding Fundamentals
414
Learning Objectives Review 2. To describe the difference between grounding and bonding g System grounding refers to the intentional connection of a phase or neutral conductor to earth for the purpose of controlling t lli th the voltage lt tto ground, d within ithi predictable di t bl lilimits it Bonding or equipment grounding refers to the interconnection and connection to earth of all normally non-current carrying metal parts Insures that all metal parts remain at ground potential Reduces the shock hazard to personnel Provides a low impedance return path for ground currents – Allows the circuit protection device to operate
Minimize the fire and explosion hazard www.EngWorks.ca
Grounding Fundamentals
415
Learning Objectives Review 3. To apply the safety requirements as defined by the Canadian Electrical Code and the IEEE as theyy relate to grounding
CEC Section 10
Defines when a system should be grounded and when equipment should be bonded Describes the acceptable methods for grounding and bonding and stipulates the size of grounding and bonding conductors Defines what an acceptable grounding electrode shall be
CEC Section 36
Describes the grounding and bonding requirements for high voltage substations – –
www.EngWorks.ca
GPR < 5000\v Touch and Step potential as per table 52 Grounding Fundamentals
416
Learning Objectives Review 3. To apply the safety requirements as defined by the Canadian Electrical Code and the IEEE as theyy relate to grounding
IEEE 142 (Green Book)
IEEE 1100 (Emerald Book)
Recommended Practice for the Grounding of Industrial and Commercial Power Systems Recommended Practice for Powering and Grounding Electronic Equipment
IEEE 80
Guide for Safety in AC Substation Grounding Primarily concerned with outdoor AC substations
www.EngWorks.ca
Grounding Fundamentals
417
Learning Objectives 4. To select the appropriate systems grounding scheme for an industrial facilityy Ungrounded
Solid Ground
Low Resistance
High Resistance
Immunity to transient overvoltages
Worst
Good
Good
Best
Arc Fault Damage Protection
Worst
Poor
Better
Best
Safety to Personnel
Worst
Better
Good
Best
Service Reliability
Worst
Good
Better
Best
Continued operation after initial ground fault
Better
Poor
Poor
Best
Not Possible
G d Good
B tt Better
B t Best
Condition
Ground fault locating g
www.EngWorks.ca
Grounding Fundamentals
418
Learning Objectives 5. To implement a static electricity control and lightning g gp protection system y Static Control Bond together and to ground
Lightning Protection Lightning strikes cannot be stopped but their energy can be diverted in a controlled manner Requires a low impedance path to ground
www.EngWorks.ca
Grounding Fundamentals
419
Learning Objectives 6. To avoid the problems typically associated with the grounding g g of sensitive electronic systems y
Ground loops - use the single point grounding concept Methods of Noise Mitigation
Physical Separation Electrical Segregation Harmonic Filtering Shielding or screening of noise sources
www.EngWorks.ca
Grounding Fundamentals
420
Learning Objectives 7. To design a ground grid for a high voltage industrial substation Limit the ground potential rise between two points to a safe value Limit the touch and step potentials to a safe value Must be able to withstand the maximum ground current without damage Important part of a safe and reliable electrical systems design
www.EngWorks.ca
Grounding Fundamentals
421
View more...
Comments