LARSEN & TOUBRO LIMITED

GENERATOR PROTECTION TYPICAL SCHEMES L&T SOLUTIONS

R.SESHADRI MPS Business Unit Mysore Works

Generator Protection Typical Schemes and L&T Solutions 1.0

With increasing complications in the power system, utility regulations , stress on cost reduction and trend towards automation, Generator protection has become a high focus area. State of the art , microcontroller based protection schemes from L&T offer a range of solutions to customers to address the basic protections and control requirements depending upon the size and plant requirements.

2.0

Generators - size less than 300 KVA Normally these generators are controlled by MCCBs, which offer O/C and short circuit protections. It is advisable to have following protections in addition to MCCB (Fig.1): E/F protection (51N) : This will protect the generator from hazardous leakages and ensure operator safety. Many SEBs have already made E/F protection as mandatory. L&T Relay for this is MC12A. 

MCCB

MC12A

5 1

G 3.0

51 N

Fig. 1 – Protection of Generators less than 300 kVA

Generators - size 300 to 1 MVA There are two major differences when compared with the small machines considered in section 2.0. a)

IDMT Over current + E/F relay will be required addition to normal MCCB or ACB releases – since the generator may need shorter trip

times for faults in the range 100% to 400% level. L&T Relay MC61A will be the ideal choice. b)

By virtue of larger power level, any faults inside the stator or fault between the neutral of the machine and the breaker terminals can reach very high intensity. ……………2 -2Such internal faults must be cleared instantaneously. Normal IDMT over current / E/F relays are not adequate to monitor this internal fault condition. A separate relay scheme is required to monitor this internal fault status - otherwise the machine can circulate very high fault currents resulting in severe damage. A high impedance differential relay scheme, with L&T relay SC14S (3 nos) is the best suited for this purpose (Fig.2). If the neutral is formed inside the machine, the differential relay scheme will not be possible – in this case a Restricted E/F scheme , with same SC14S relay (1 No.) is the solution. Care should be taken to provide adequate no. of CTs as shown in the diagram.

c)

Machines of this size are likely to have external controls for frequency and excitation – so that they can be run in parallel with other power sources (other generators on the same bus or the local grid). This necessitates voltage and frequency related protections as well. L&T Relays UM30A is the best solution for this purpose. Alternately Relay MV12A (4 Nos) can be used if frequency protection is built in the engine. MV12A / UM30A



27/ 59 51

50N

51

81

51N MC61A

G

87/ 87 N

-3-

3 x SC14S (Diff.) 1 x SC14S (REF) Fig. 2 – Protection of Generators 300 kVA – 1 MVA

………………..3 -3-

4.0

Generators – Size 1 MVA to 10 MVA Being a medium sized generator, it will need more comprehensive protection both for the stator side and the rotor side.

4.1

Stator side protections : a)

Voltage restrained Over Current Protection (50V / 51V) : Normal IDMT O/C will not work here – when a over current fault occurs, due to higher current levels, there would be a drop in terminal voltage. For the same fault impedance, the fault current will reduce (with respect to terminal voltage) to a level below the pick up setting. Consequently normal IDMT may not pick up. It is necessary to have a relay whose pick up setting will automatically reduce in proportion to terminal voltage. Hence the over current protection must be voltage restrained. Two levels of Over current protection is required – low set and highest ( for short circuit protection).

b)

Thermal Overload (49) : This protection is a must – it monitors the thermal status of machine for currents between 105% to the low set O/C level ( normally 150%).

c)

Current Unbalance (46) : Generators are expected to feed unbalanced loads – whose level has to be monitored. If the unbalance exceeds 20%, it may cause over heating of the windings. This heating will not be detected by the thermal overload relay - since the phase currents will be well within limits. A two level monitoring for unbalance is preferred – first level for alarm and the second level for trip.

d)

Loss of excitation(40) : When excitation is lost in a running generator, it will draw reactive power from the bus and get over heated. This condition is detected from the stator side CT inputs – by monitoring the internal impedance level & position of the generator.

e)

Reverse Power (32) : Generators of this size may operate in parallel with other sources, which may cause reverse power flow at certain times ( during synchronization or when there is a PF change due to load / grid fluctuation or when there is a prime mover failure). When reverse power happens, the generator along with prime mover will undergo violent mechanical shock – hence reverse power protection is absolute must.

f)

Under power (37) : It may not be economical to run generators below a

certain load level. This protection will monitor the forward power ……………..4 -4delivered by the machine and give alarm when the level goes below a set point. g)

Under / Over Voltage (27 / 59 ) : This will protect the machine from abnormal voltage levels, particularly during synchronization and load throw off conditions.

h)

Under / Over frequency (81) : This will protect the machine from abnormal frequency levels, particularly during synchronization and load throw off conditions. This will also help in load shedding schemes for the generator.

i)

Breaker Failure Protection : This protection detects the failure of breaker to open after receipt of trip signal. Another trip contact is generated under breaker fail conditions , with which more drastic measures (like engine stoppage, opening of bus coupler etc) can be taken. Multifunction relay IM3GV from L&T, as a single unit protects the generator for all above listed faults (a) to (h)– giving at the same time the benefit of small panel space, simple wiring and user friendly operation.

j)

Stator Earth fault (64S): L&T relay MC12A will do this job.

k)

Differential Protection (87G) : This protection is very important – since the machines of this size have to be protected for severe damages that may occur due to internal faults. Considering the large power levels, it is necessary to have a percentage biased, low impedance differential relay – L&T’s relay MD32G is the ideal solution. MD32G has following advantages : - it provides percentage biased differential protection with dual slope characteristics - it has a built in REF protection element (87N), which will monitor the generator for internal earth faults. - It has a built in O/C protection, as a back up

l)

PT Fuse Failure Protection : This relay will detect any blowing of PT secondary fuse – and give a contact which can be used to block the under voltage trip. L&T relay PTF03, with less than 7 ms response, will be ideal for this purpose.

……………5 4.2

-5Rotor side protections : Generators of this size, will need rotor side protections listed below : a)

Rotor Excitation Under Current : This is a DC under current relay ( UBC/A/37), which will monitor the excitation current.

b)

Rotor Excitation U/V(80) : This is a DC under voltage relay (UBC / 80), which will monitor rotor voltage.

c))

Diode failure Relay : Brushless excitation systems will have rotor mounted diodes, which can become short or open during operation. Diode Failure relay (RHS) will monitor the condition of these diodes , for both open circuit and short, and give alarm.

d)

Rotor Earth Fault(64R) : Relay UBO/CR will monitor the rotor winding status for the Earth fault.

Please see Fig 3 for the scheme with relays as above.

…………..6 -6-

5.0

Generators above 10 MVA For large generators above 10 MVA size, the philosophy of main protection and back up protection has to be followed. In addition to the protections listed in Section 4.0, following extra protections are to be considered: a)

100% Earth Fault Protection : This will help in sensing earth faults close to neutral.

b)

Inadvertent Breaker Closure : This will avoid closing of generator to bus during coasting to stop, or when stand still or before synchronism.

c)

Under Impedance : This will be required as a back up protection for the whole system including the generator transformer and the associated transmission line. If the distance relay fails to pick for some reason, this under impedance function will pick up and save the generator.

d)

Over Excitation : This will protect the generator from Over fluxing conditions.

Please see Fig. 4 for the SLD.

…………7 -7-

6.0

Generator connected in parallel to grid : Whenever generators are running parallel to grid, a comprehensive Auto Synchronising & Grid Islanding Scheme will be required. This scheme will help in synchronizing the generator to the bus and opening the incomer breaker of the plant whenever there is a severe grid disturbance, thus protecting the generator from ill effects of disturbed grid. L&T Relays SPM21, UFD34 , MW33 and MRP11 are ideal for this scheme. Please see Fig. 5.

7.0

Generators connected in parallel on a common bus : Whenever more than one generator is operating in parallel , it is necessary to see that the plant load is equally shared by the generators in parallel. If there is unequal sharing, there would severe hunting amongst the generators and eventually this will lead to cascaded tripping of all generators, causing a total black out. L&T relays RRS (two relays per generator) provide the most effective, online load sharing system for generators in parallel. Please see Fig 6 for a representative scheme of load sharing for three generators.

…………..8 -8-

8.0

Summary : The sections above describe the actual requirements and various options available from L&T towards protection and management of generators of various sizes. For generators above 1 MVA size, it is also recommended to have complete data acquisition & control through PC. L&T supplies MSCOM software for this purpose. The relays like IM3GV, MG30, MD32T,UM30A can all communicate to a PC and provide all management data. A comprehensive scheme as shown below will be the most desirable one.