Generator Protection 1
May 14, 2018 | Author: Niketa Gupta | Category: N/A
Short Description
Download Generator Protection 1...
Description
Generator protection
Presented by
Bipasha Jash (PEE)
NTPC
Classification Classificat ion of Generator Protection
Stator Protection Generator Abnormal Operating conditions System back up protections Rotor protection GT protections UT protections
Classification Classificat ion of Generator Protection
Stator Protection Generator Abnormal Operating conditions System back up protections Rotor protection GT protections UT protections
Over view of type of fault Vs protection FAULT/ABNORMAL EFFECT CONDITION
PROTECTION
Thermal over loading
Over heating of stator winding/ insulation failure
Thermo couples/ Over current relays
External fault
Unbalanced loading stress
Over load/negative phase sequence relay
Stator fault Ph to Ph/Ph to E Inter turn
Winding burn out Welding of core lamination
Differential prot 100% E/F prot/95% E/F Inter turn prot
Rotor fault
Damage to shaft/bearing
2 stage rotor E/F protection
Motoring
LFPR/Rev power
O/V,O/F,U.F
Insulation failure,Heating of core failure of blades
O/V relay Volt/Hz relay U/F relay
Loss of field
Induction gen operation Absorb MVAR from system/damage to rotor wdg
Loss of field
Generator Connection Methods The protection scheme depends on the type of generator connection A) Unit scheme: In this scheme no switchgear is provided between the generator and generator transformer, which are treated as a unit; a unit transformer is tapped off the interconnection for supply of power to auxiliary plant. B) Generator circuit breaker scheme: In this scheme a generator circuit breaker is provided between the generator and generator transformer .
TRIP LOGIC OF GENERATOR PROTECTION TWO INDEPENDENT CHANNELS WITH INDEPENDENT CT/VT INPUTS/DC SUPPLY/TRIP RELAY CLASS A TRIP ALL ELECTRICAL TRIPS TRIP TURBINE, GENERATOR, GT, UT
CLASS-B TRIP MECHANICAL TRIPS AVOID OVER SPEEDING OF TURBINE DUE TO STEAM ENTRAPPED IN TURBINE. TURBINE TRIP SIGNAL IS GIVEN FIRST AND THE ACTIVE POWER, SENSED BY THE LOW FORWARD RELAY (32G) GIVES THE TRIP SIGNAL TO THE UNIT BREAKER & FIELD BREAKER AFTER A TIME DELAY
Class C TRIPS ONLY HV CB IN CASE OF GCB SCHEME
Typical Generator protection scheme
GENERATOR PROTECTIONS NTPC PRACTICES
DIFFERENTIAL PROTECTION UNIT TYPE PROTECTION INSTANTANEOUS IN OPERATION. COVERS THE STATOR WDG FOR PHASE TO PHASE FAULTS. SINGLE PHASE TO EARTH FAULTS ARE NOT COVERED IN HIGH IMP EARTHING SYSTEMS (EARTH CURRENT IS LOW) DUPLICATED DIFF USED FOR GCB SCHEME TYPICAL SETTING: HIGH IMP TYPE: 5% BIASED 10%
STATOR EARTH FAULT PROTECTION E/F CURRENT IS LIMITTED TO 10A THIS MINIMIZES THE DAMAGE FIRST FAULT LESS CRITICAL NEEDS CLEARANCE AS IT MAY DEVELOP INTO A PH TO PH FAULT SECOND FAULT WILL RESULT IN VERY HIGH CURRENT FIRE MAY RESULT FROM EARTH FAULT. TWO TYPES: 100 % E/F 95 % E/F
95 % STATOR E/F RESULTS IN VOLTAGE SHIFT OF GEN NEUTRAL W.R.T. GROUND DETECTED BY OVER VOLTAGE RELAY CONNECTED ACROSS GROUNDING RESISTOR PROTECTS APPROX 95% OF STATOR WDG TYP SETTING: 5V TIME DELAY OF MORE THAN 1 SEC(GEN IDMT RELAY WITH PMS 5.4 AND TMS 1 IS USED)
100% Stator E/F Protection THIRD HARMONIC PRINCIPLE A RELAY WHICH RESPONDS TO THE REDUCTION OF THE 3 RD HARMONIC COMPONENT A STATOR PHASE-TO-GROUND FAULT OCCURS AT OR NEAR THE GENERATOR NEUTRAL, THERE WILL BE AN INCREASE IN THIRD HARMONIC VOLTAGE AT THE GENERATOR TERMINALS, WHICH WILL CAUSE RELAY OPERATION. DISADVANTAGES DUE TO DESIGN VARIATIONS, CERTAIN GENERATING UNITS MAY NOT PRODUCE SUFFICIENT THIRD HARMONIC VOLTAGES THIS METHOD DOES NOT PROTECT THE M/C DURING STAND STILL CONDITIONS.
100 % Stator E/F protection LOW FREQUENCY INJECTION PRINCIPLE THIS SCHEME DETECTS THE GROUND FAULTS BY INJECTING A LOW FREQUENCY SIGNAL (SAY 20 HZ)AT THE NEUTRAL EARTHING TRFR OR LINE CONNECTED EARTHING TRFR AND MONITOR EITHER THE EARTH CURRENT IN THE WDG(INCREASES DURING A FAULT) OR THE STATOR EARTH RESISTANCE (REDUCES DURING FAULT) PROVIDES PROTECTION EVEN DURING SHUT DOWN SETTINGS TYPICAL FOR 500 MW UNIT 14 mA /1 sec (current setting ) OR Trip : 10 Ohm/1 sec Alarm : 20 ohm/10 sec( for Imp measuring relay SETTINGS ARE TO BE FINALISED DURING COMMISSIONING TEST IN LINE WITH INSTRUCTIONS OF RELAY CATALOGUE.
Rotor Earth Fault Protection FIRST ROTOR E/F DOES NOT CAUSE IMMEDIATE DAMAGE SECOND E/F RESULTS IN A WDG SC OF ROTOR CAUSE MAGNETIC UNBALANCE/MECH FORCES /DAMAGE METHODS OF DETECTION POTENTIOMETER METHOD A CENTRE TAPED RESISTOR IS CONNECTED ACROSS THE MAIN FIELD WINDING THE CENTRE TAP IS CONNECTED TO EARTH THROUGH A VOLTAGE RELAY AN EARTH FAULT ON THE FIELD WINDING WILL PRODUCE VOLTAGE IN THE RELAY, MAXIMUM VOLTAGE OCCURRING FOR END FAULTS A BLIND SPOT EXISTS AT THE TAPPING POINT, TO AVOID THIS , THE TAPPING POINT IS VARIED WITH A PUSH BUTTON OR SWITCH , AND IS TESTED PERIODICALLY TO DETECT BLIND ZONE
LOW FREQUENCY INJECTION METHOD
MODERN ROTOR EARTH FAULT PROTECTION RELAY OPERATES ON THE PRINCIPLE OF LOW FREQUENCY INJECTION INTO THE FIELD WINDING VIA CAPACITORS. IF AN EARTH FAULT OCCURS, THE CORRESPONDING CURRENT OR RESISTANCE IS DETECTED TYP SETTING (500 MW) ALARM 40 K OHM TIME = 10 SEC TRIP
5 K OHM
TIME = 1 SEC
ACTUAL VALUES OF SETTING SHALL BE DECIDED AT SITE DURING COMMISSIONING TO ACCERTAIN THE HEALTHY VALUE OF THE PARTICULAR M/C.
INTER TURN PROTECTION CURRENT BASED SYSTEM FOR GENERATORS WITH SPLIT NEUTRALS WITH ALL SIX TERMINALS BROUGHT OUT ON NEUTRAL SIDE DELAYED LOW-SET O/C RELAY WHICH SENSES THE CURRENT IN THE CONNECTION BETWEEN THE NEUTRALS OF THE STATOR WINDINGS VOLTAGE BASED SYSTEM RELAY COMPARES THE NEUTRAL NGT SEC VOLTAGE AND GEN TERMINAL OPEN DELTA VOLTAGE BALANCE DURING E/F OR NORMAL CONDITION DURING INTER TURN FAULT OPEN DELTA VOLTAGE WILL BE DEVELOPED AND NGT SEC VOLTAGE WILL BE ZERO, RESULTING IN A DIFFERENTIAL VOLTAGE WHICH MAKES THE RELAY OPERATE IDMT RELAYS WITH 5.4 PMS AND 1 TMS ARE ADOPTED.
O/V PROTECTION TYP SETTINGS OF A 3 STAGE O/V RELAY IS AS FOLLOWS ALARM 110 % 2 SEC TRIP 120 % 1 SEC 140 % INSTANTANEOUS
U/F O/F PROTECTION TYPICAL SETTING: ALARM - 47.8HZ 1 SEC TRIP - 47.4 HZ 2 SEC SETTING NEED TO BE CO-ORDINATED WITH THE RESPECTIVE RLDC AND THE ISLANDING SCHEME SETTINGS
Negative Sequence protection NEGATIVE SEQUENCE PROTECTION FOR GENERATOR PROTECTS THE GENERATOR FROM EXCESSIVE HEATING IN THE ROTOR RESULTING FROM UNBALANCED STATOR CURRENTS CAUSED DUE TO ONE POLE OPEN IN LINE ONE POLE OPEN OF A CIRCUIT BREAKER CLOSE IN UNCLEARED UNBALANCED FAULTS
THE NEGATIVE SEQUENCE PROTECTION RELAYS SHALL BE SET TO THE NPS CAPABILITY OF THE MACHINE WHICH IS K = I22* T TYP FOR 500 MW PERMISSIVE NEG SEQ CURRENT = 5 – 8 % OF STATOR CURRENT PERMISSIVE I22* T = 5 – 10 SETTINGS ADOPTED FOR NTPC I2 = = 7.5 % I22*T = 8.3
Loss of Field Protection ACTS AS AN INDUCTION GENERATOR INDUCED EDDY CURRENTS IN THE FIELD WINDING, ROTOR BODY, WEDGES AND RETAINING RINGS MW FLOW IN TO THE SYSTEM/MVAR FLOWS IN TO THE MACHINE. THE APPARENT IMP TRAVELS TO THE FORTH QUADRANT OF X-Y PLANE METHODS OF DETECTION: UNDER VOLTAGE + O/C MINIMUM IMPEDANCE WITH U/V SOME RELAYS ARE SET IN THE ADMITTANCE PLANE MATCHING WITH THE CAPABILITY CURVE OF THE MACHINE
BIG M/C WITH GOOD AVR
SMALL MACHINES
LOSS OF FIELD RELAY
OUT OF STEP PROTECTION MACHINE RUNS OUT OF SYNCHRONISM WITH THE NETWORK CYCLIC VARIATION OF ROTOR ANGLE CURRENT INCREASES HEAVILY FREQUENCY DEPEND ON THE RATE OF SLIP RESULT IN THE WINDING STRESS IT MAY ALSO DAMAGE THE AUXILIARIES OF THE AFFECTED UNIT DETECTED BY SENSING THE VARIATIONS IN IMP DISTINGUISH BETWEEN THE RECOVERABLE SWING AND THE IRRECOVERABLE SWING TWO BLINDERS(IMPEDANCE) + A SUPERVISORY MHO ELEMENT, TRIP WHEN IMP IS INSIDE THE MHO AND CROSED THE BLINDERS MINIMUM IMPEDANCE (MULTIPLE ZONE) + COUNTING NO. OF SWINGS
POLE SLIPPING CHARACTERISTIC
ACCIDENTAL BACK ENERGISATION CAUSE OPERATION AS AN INDUCTION MOTOR DAMAGE MACHINE AND TURBINE THE RAPID HEATING IRON PATHS NEAR THE ROTOR SURFACE DUE TO STATOR INDUCED CURRENT. DETECTED BY OVER CURRENT + CB AUXILIARY CONTACTS CHECKS FOR THE CURRENT WHEN THE GEN BREAKER CONTACTS ARE OPEN SET BELOW THE RATED CURRENT (50 –70%) O/C AND U/V MEASUREMENTS
Backup Impedance protection FOR UNCLEARED SYSTEM FAULT THE BACKUP PROTECTION IS TIME DELAYED TO COORDINATE WITH THE ZONE 3 SETTING OF LINES . DETECTED BY OVER CURRENT DISTANCE DISTANCE PREFFERED AS THE LINE IS PROVIDED WITH DISTANCE RELAYS SETTING SHOULD BE MADE TO COVER THE GT IMP AND THE LONGEST LINE IMP SETTING SHOULD TAKE CARE OF THE INFEED FROM OTHER GENERATORS CONNECTED TO THE SAME BUS ALSO TIME SETTING 1.5 –2 SEC
LOW FORWARD AND REVERSE POWER INTERLOCK
To protect the machine from motoring action Trip under class B after a short time delay in case the turbine is already tripped ( typ set at 2 sec) Trip under class A, after a long time delay if turbine is not tripped (typically set at 10 sec) Power setting typ 0.5 % of rated power
GEN TRANSFORMER PROTECTION DIFFERENTIAL BIASED DIFFERENTIAL 10 % BIAS SETTING (TO COVER TAP RANGE AND CT MISMATCH, IF ANY) TIME INSTANTANEOUS
BACK UP EARTH FAULT DEF TIME OR IDMT RELAY 20 % WITH 2 SEC TIME DELAY TO BE COORDINATED WITH DISTANCE PROT ZONE 3
UT PROTECTION DIFFERENTIAL BIASED DIFF USED BIASED SETTING 10%
BACK UP OVER CURRENT 2-3 TIMES THE FULL LOAD CURRENT DELAY 0.9 SEC TAKE CARE OF ANY LARGE MOTOR STARTING CASE
RESTRICTED E/F HIGH IMP DIFF SET TO 5%-7% IN HIGH IMP EARTHING
COMMONLY USED GEN/GEN TRFR RELAYS PROTECTI ALSTOM ON
ABB
HIGH IMP CAG 34 RADHA DIFF MICOM P343 REG 216
SIEMENS
7UM 62
REMARK In case of duplicated diff, one low imp & one high imp preferred For trfr biased relay preferred
BIASED DIFF
MBCH MICOM P 633
RADSB RET 316
7 UT
POWER RELAYS
RXPE
PPX
7 UM SERIES
Directional power relays
LOSS OF FIELD
RAGPC(DIR O/C+U/V)
YCGF
7UM SERIES
Impedance /
100% E/F
PVMM MICOM P343
GIX
PG871
95% E/F
VDG
BACK UP IMP
YCG15
admittance
REG 216
RAKZB
7UE22
Low frequency 7UM SERIES injection type
preferred over 3 rd harmonic principle
7UM SERIES
Open delta of gen sec VT
7UM 516
Minimum impedance
PROTECT ALSTOM ION
ABB
SIEMENS
Remarks
OVER FLUXING
GTTM
RATUB RALK
7RW
IDMT
POLE SLIPPING
ZTO+YTG RXZF+RXPE M15
7UM 516
IMPEDANCE IMP+ DIR O/C IMP+NO OF POWER SWINGS
ACC. BACK ENERG
CTIG
INTER TURN
VDG
NEG PH SEQ
CTN
REF
CAG/FAG
ROTOR E/F
VDG
RAGUA
RARIB RADHD
7UM SERIES
O/C +CB AUX CONTACT CURRENT ELEMENT+U/V
7UM SERIES
comp of open delta 0n gen term+ngt sec voltage
7UM SERIES
MEASUREMENT OF
7UM SERIES
HIGH IMP PREFFERED
7UR 22 7 UM SERIES
I2
Stator protections Type of fault
Protection
Channel
Recommendation
Short circuit
87 G1 87G2 87 GT
1 2 1&2
Stator Earth Fault
64G1 64G2
1 2
Inter turn
95G
1 &2
unbalance
46G
1&2
Over load
51G
Alarm
<
Loss of excitation
40G1 40G2
1 2
>100 MW
Out of step
98G
1&2
Motoring
32 G1/2 / 37 G1/G2
1/2
O/V,O/F U/F
59/99 81G1/81G1
1 /2 1/2
System back up
21G
1&2
Accidental energisation
50GDM
1 &2
Rotor E/F
64F
1 &2
Generator Transformer/Unit Transformer Protections
Fault Short ckt (GT)
Device no
87T 87 HV 51 GT Earth Fault(GT) 51 NGT 64GT(3 Ph GT) 64T Short 87 UT circuit(UT) 51UT Earth Fault UT 51 NUT 64 UT
Channel 1 2 2 1 1 1/2 1/2 1/2 1 2
Recommendation
View more...
Comments