Fujitsu Hybrid Flex Inverter HFI Mini Split Systems Design Manual
December 24, 2016 | Author: e-ComfortUSA | Category: N/A
Short Description
Fujitsu HFI AOU48RLXZ Eight Zone Ductless Mini Split Heat Pump Outdoor Unit Ideal solution for multi-room system, you ca...
Description
DTR_BMU001E_05 VD014E/06
DESIGN & TECHNICAL MANUAL
Hybrid Flex Inverter System
FUJITSU GENERAL LIMITED
CONTENTS 1. GENERAL INFORMATION 2. MODEL SELECTION 3. OUTDOOR UNITS 4. INDOOR UNITS 5. CONTROL SYSTEM 6. SYSTEM DESIGN 7. OPTIONAL PARTS
Hybrid Flex Inverter System
1. GENERAL INFORMATION
DTR_BMU001E_03--CHAPTER01 2010.08.25
CONTENTS 1. GENERAL INFORMATION 1. FEATURES OF SYSTEM ............................................................. 01 - 01 1-1.HIGH EFFICIENCY & COMPACT ............................................................. 01 - 01 1-2.FLEXIBLE DESIGN & EASY INSTALLATION.......................................... 01 - 02 1-3. CENTRAL CONTROL ............................................................................... 01 - 05
2. MODEL LINE UP .......................................................................... 01 - 07 2-1.OUTDOOR UNIT ....................................................................................... 01 - 07 2-2.INDOOR UNIT ........................................................................................... 01 - 08 2-3.CONTROLLER .......................................................................................... 01 - 09 2-4.SEPARATION TUBE ................................................................................. 01 - 10 2-5.BRANCH BOX........................................................................................... 01 - 10 2-6.OTHERS ....................................................................................................01 - 11
GENERAL INFORMATION
GENERAL INFORMATION
1. FEATURES OF SYSTEM 1-1. HIGH EFFICIENCY & COMPACT HIGH EFFICIENCY Adopting a large heat exchanger, high efficiency ventilation fan, DC twin rotary compressor, etc. realizes high efficiency operation. Cooling
SEER:17.0
Heating
HSPF:9.8
3.89
0.0
15.0
16.0
17.0
SEER
0.0
8.0
9.0
10.0
HSPF
TOP CLASS
TOP CLASS COMPACT DESIGN Compact and lightweight outdoor unit is easy to carry in, it can be installed unnoticeably in various places. About 48000Btu class
New model
Height difference
29%
50-25/32in. (1290mm)
36in. (914mm)
INNOVATIVE TECHNOLOGY High efficiency large fan: New high efficiency fan is mounted.
DC Fan motor: High performance and high efficiency has been realized by using a small DC fan motor.
Heat exchanger: Reduced compact size and energy saving has been realized by utilizing high density piping design and 3-Row heat exchanger.
7 segment display: Easy –to-read 7 segment LED display which explains operational and trouble status.
High efficiency DC twin rotary Compressor: A high perforamnce, low noise, large capacity DC twin rotary compressor is used.
- (01 - 01) -
1. GENERAL INFORMATION
FLEXIBLE DESIGN ● 4 types, 12models of indoor units can be selected ranging from 7000BTU to 24000BTU in capacity. Compact Cassette
Slim Duct
Compact Wall Mounted
Wall Mounted
● Up to 8 indoor units can be connected to one outdoor unit. ● A maximum of 130% indoor unit connectable capacity. Match any room layout. Connectable indoor unit capacity
Connectable indoor unit
80 to 130%
2 to 8
For any room layout-connectable capacity of indoor units is max 130%
Total pipe length
Actual pipe length
377ft. max
230ft. max
(115m)
(70m)
Can be installed in high rise condominium or commercial building. • Height difference between O.U and I.U 98ft.(30m) max. • Height difference between I.U and I.U 49ft.
- (01 - 02) -
(15m)
max.
1. GENERAL INFORMATION
GENERAL INFORMATION
GENERAL INFORMATION
1-2. FLEXIBLE DESIGN & EASY INSTALLATION
GENERAL INFORMATION
GENERAL INFORMATION
EASY INSTALLATION ● Corresponding to diverse installation environments by use of branch connection system.
Current model : 4 Rooms multi x 2
New model
Branch box
BRANCH BOX ● Branch box has an electronic expansion valve built-in, so it can control the refrigerant flow to each indoor unit. ● Can be connected by flare connection and both ceiling suspension and wall mounting installation are available.
Primary type: UTP-PU03A Secondary type: UTP-PU03B
Allowed branch box mounting direction Ceiling suspension
By reversing the electrical box position you can orient the inlet and outlet pipes into a left hand or right hand configuration,
Horizontal wall mounted
By reversing the electrical box position you can orient the inlet and outlet pipes into a left hand or right hand configuration.
- (01 - 03) -
Vertical wall mounted
You cannot reverse the electrical box position when mounting the branch box vertically.
1. GENERAL INFORMATION
GENERAL INFORMATION
GENERAL INFORMATION
DECREASE OF INSTALLATION MISTAKE ● This operation allows the air conditioner to automatically check the status of the outdoor unit and check for wiring mistakes.
Installation procedure Refrigerant piping and electrical wiring work All Flare connection Sealing test
Vacuum process Refrigerant piping & Electric wiring
Additional refrigerant charging
Indoor unit function setting
Check run
Test run
Installation mistakes and positions where errors are occurring are shown by the outdoor unit display indicators.
Check item ● Check communication ● Check the number of connected indoor units ● Check wiring and piping connection
SERVICE MAINTENANCE 7 segment LED display Operation mode
Error display
Operating information
Example
Easy –to-read 7 segment LED display which explains operating and trouble status.
- (01 - 04) -
1. GENERAL INFORMATION
Support comfort control system for the varied needs of the home and the condominium, etc.
● Central remote controller is connected directly to the branch box, making the installation process easier. ● Once the controller is connected, it can automatic register and display all the indoor units.
CENTRAL REMOTE CONTROLLER (Option) Controllable 1 Multi system
Max. controllable 8 indoor units UTY-DMMUM ● Large and full-dot liquid crystal screen ● Screen with backlight can be seen even in the dark ● Wide and large keys easy to press, user-intuitive arrow key - (01 - 05) -
1. GENERAL INFORMATION
GENERAL INFORMATION
GENERAL INFORMATION
1-3. CENTRAL CONTROL
Air conditioning load factor
● Users can choose from 4 low noise levels, depending on the installation environment.
Heat load
100%
Down
Capacity 0 58dB
Operating sound
0
(time) Low noise operation
Minimum heat (All) operation ● While this function is selected, all indoor units start the minimum heat operation when all the indoor units are stopped by operation of the [On/Off button]. ● When the room temperature is higher than 50°F (10°C), MIN. HEAT operation starts and maintains the room temperature at 50°F (10°C) when the temperature drops below 50°F (10°C). ● When “MIN, HEAT operation stops, the room set temperature quickly returns to the preset temperature.
All indoor units OFF “All MIN. HEAT” operation ON
70°F Indoor unit operation START
50°F
Economy (All) operation Temp.
Example : Cooling operation
● If all the indoor and outdoor units are changed to economy mode, this can save more energy than setting of each indoor unit individually. ● Economy operation is energy saving, as the set temperature of indoor unit is shifted by 2°F (1°C) and the maximum electric value of the outdoor unit is suppressed.
Economy operation Shift setting temp
Set temperature
Nomal operation
Time
Control maxmum current
Schedule timer Example Temp. Cool
PM12
Cool
PM5
Heat
Heat AM7
PM12 PM1
Cool
PM11 Time
AM8
Cool
PM1
Cool PM6
● Operation setting can be changed 4 times in each day of a week, and 2types of the schedule can be set to suit users' preference.
PM10 Time
Temp.
Cool AM7
Winter season pattern
Saturday~Sunday
Temp.
Monday~Friday
Summer season pattern
Heat
Heat PM11 Time
AM7
PM1
Heat PM6
- (01 - 06) -
Heat PM11 Time
1. GENERAL INFORMATION
GENERAL INFORMATION
Outdoor unit low noise operation
Temp.
GENERAL INFORMATION
VARIOUS OPERATION MODES SET BY REMOTE CONTROLLER
GENERAL INFORMATION
GENERAL INFORMATION
2. MODEL LINE UP 2-1. OUTDOOR UNIT LINE UP HP
Capacity (BTU/h)
Model name
Connectable indoor unit
5
48000
AOU48RLXFZ
2 to 8
MODEL DESIGNATION 1
2
3
4
5
6
7
8
9
10
A
O
U
4
8
R
L
X
F
Z
Function L: Inverter
Function X: Extended line set
Type AO : Outdoor unit
Destination U: FUJITSU
Model code (BTU/h) 48 : (48000)
Function R: Heat pump
- (01 - 07) -
Function F: Flexible
Function Z: Zoning
1. GENERAL INFORMATION
GENERAL INFORMATION
GENERAL INFORMATION
2-2. INDOOR UNIT LINE UP Various combinations of types and capacity 4 types 12 models, ranging from 7000BTU to 24000BTU. Capacity BTU/h 7000
Compact Cassette
Model code 7
9000
9
12000
12
18000
18
24000
24
Slim Duct
Compact Wall Mounted Wall Mounted
Compact Cassette
Compact Wall Mounted
Slim Duct ARU9RLF ARU12RLF ARU18RLF ARU24RLF
AUU9RLF AUU12RLF AUU18RLF
ASU7RLF ASU9RLF ASU12RLF
Wall Mounted ASU18RLF ASU24RLF
MODEL DESIGNATION 1
2
3
4
5
6
7
8
A
S
U
1
8
R
L
F
Function L: Inverter
Function F: Flexible
Type AU: Cassette AR: Duct AS: Wall Mounted
Destination U: FUJITSU
Model code (BTU/h) 7 (7000) 9 (9000) 12 (12000) 18 (18000) 24 (24000)
Function R: Heat pump
- (01 - 08) -
1. GENERAL INFORMATION
GENERAL INFORMATION
GENERAL INFORMATION
2-3. CONTROLLER LINE UP
Central remote controller
Indoor units Compact Model Compact Wall Wall Cassette Slim Duct mounted mounted *1 *1 *1 *1 UTY-DMMUM
Wired Remote Controller
UTY-RNNUM
*2
UTY-LNHUM
-
-
AR-RAH1U
-
-
-
IR Receiver Unit
UTY-LRHUM
-
-
-
Simple Remote Controller
UTY-RSNUM
*2
Type
Wireless Remote Controller
: Accessory, : Optional, -: It is not possible to connect it. *1: Central remote controller is connected to Branch Box. *2: Optional Communication kit (UTY-XCBXZ1) is necessary for the installation.
CENTRAL CONTROL Central remote controller
INDIVIDUAL CONTROL Wired Remote Controller
Simple Remote Controller
Wireless Remote Controller
UTY-LNHUM
AR-RAH1U
IR Receiver Unit
- (01 - 09) -
1. GENERAL INFORMATION
GENERAL INFORMATION
GENERAL INFORMATION
2-4. SEPARATION TUBE Separation tube Model : UTP-SX248A Liquid pipe
Gas pipe
2-5. BRANCH BOX Primary type Model : UTP-PU03A
Secondary type Model : UTP-PU03B
- (01 - 10) -
1. GENERAL INFORMATION
GENERAL INFORMATION
GENERAL INFORMATION
2-6. OTHERS LINE UP Type
Model
Indoor units Compact Compact Wall Wall Cassette Slim Duct mounted mounted -
Outdoor unit
Grill kit
UTG-CCGF
Air outlet shutter plate
UTR-YDZB
-
-
-
-
Insulation kit for high humidity
UTZ-KXGC
-
-
-
-
Fresh air intake kit
UTZ-VXAA
-
-
-
-
External control set
UTD-ECS5A
-
-
-
-
External connect kit
UTY-XWZX
-
*1
-
External connect kit
UTY-XWZXZ3
-
-
-
-
External connect kit (For Base heater)
UTY-XWZXZ4
-
-
-
-
UTR-FA16
-
-
-
-
UTR-FA13-1
-
-
-
-
UTR-FA16-2
-
-
-
-
UTR-FA13-2
-
-
-
-
UTY-XCBXZ1
-
-
-
-
Apple catechin filter
Ion deodorisation filter Communication kit
-
: Optional, -: It is not possible to connect it. *1: Optional Communication kit (UTY-XCBXZ1) is necessary for the installation
- (01 - 11) -
1. GENERAL INFORMATION
GENERAL INFORMATION
GENERAL INFORMATION
PARTS Grille kit
Air outlet shutter plate Model : UTG-CCGF
Models : UTR-YDZB
For Compact Cassette type For Compact Cassette type
Insulation kit for high humidity Model : UTZ-KXGC
Fresh air intake kit Model : UTZ-VXAA
Insulation Kit
For Compact Cassette type
For Compact Cassette type
External control set
External connect kit Model : UTD-ECS5A
(x1)
(x2)
(x1)
(x2)
Model : UTY-XWZX
(x1)
(x1)
For Compact Cassette / Compact Wall Mounted / Wall Mounted
For Slim Duct type
External connect kit Model : UTY-XWZXZ3
External connect kit (For Base heater)
For Outdoor unit
Model : UTY-XWZXZ4
For Outdoor unit
- (01 - 12) -
1. GENERAL INFORMATION
GENERAL INFORMATION
GENERAL INFORMATION
PARTS Apple catechin filter
Apple catechin filter Model : UTR-FA16
Model : UTR-FA13-1
For Compact wall mounted type For Wall mounted type
Ion deodorisation filter
Ion deodorisation filter Model : UTR-FA16-2
Model : UTR-FA13-2
For Compact wall mounted type For Wall mounted type
Communication kit Model : UTY-XCBXZ1
For Compact wall mounted type
- (01 - 13) -
1. GENERAL INFORMATION
Hybrid Flex Inverter System
2. MODEL SELECTION
DTR_BMU001E_04--CHAPTER02 2010.10.04
CONTENTS 2. MODEL SELECTION 1. MODEL SELECTION PROCEDURE............................................ 02 - 01 2. MODEL LINE UP .......................................................................... 02 - 02 2-1.OUTDOOR UNIT ....................................................................................... 02 - 02 2-2.INDOOR UNIT ........................................................................................... 02 - 02 2-3.OPTIONAL PARTS.................................................................................... 02 - 02
3. MODEL SELECTION AND CAPACITY CALCULATION ............. 02 - 04 3-1.SELECTION PROCEDURE OF INDOOR UNIT AND OUTDOOR UNIT .. 02 - 04 3-2.THE EXAMPLE OF CALCULATION ......................................................... 02 - 05 3-2-1. COOLING EXAMPLE .............................................................................................. 02 - 05 3-2-2. HEATING EXAMPLE ............................................................................................... 02 - 09
4. CAPACITY TABLE ....................................................................... 02 - 13 4-1.COOLING CAPACITY ............................................................................... 02 - 13 4-2.HEATING CAPACITY ................................................................................ 02 - 15
5. CAPACITY COMPENSATION COEFFICIENT ............................. 02 - 17 5-1.COMPENSATION COEFFICIENT OF PIPE LENGTH .............................. 02 - 17 5-2.COMPENSATION COEFFICIENT OF FROSTING / DEFROSTING ......... 02 - 18
1. MODEL SELECTION PROCEDURE See 2-2.MODEL LINE UP(INDOOR UNIT) and 3-1. SELECTION PROCEDURE OF INDOOR UNIT AND OUTDOOR UNIT
Selection of required optional parts ● Grill kit for Compact Cassette type
See 2-3.MODEL LINE UP(OPTIONAL PARTS)
Selection of Branch box
See 2-3.MODEL LINE UP(OPTIONAL PARTS)
Selection of Separation tube See 2-3.MODEL LINE UP(OPTIONAL PARTS)
Selection of controller units ● Central Remote Controller ● Wired Remote Controller ● Simple Remote Controller ● Wireless Remote Controller ● IR Receiver Unit
Selection of other optional parts ● Air Outlet Shutter Plate ● Insulation Kit for High humidity ● Fresh air intake kit ● External Control Set ● External Connect Kit ● Apple catechin filter ● Ion deodorisation filter ● Communication kit
See 2-3.MODEL LINE UP(OPTIONAL PARTS)
See 2-3.MODEL LINE UP(OPTIONAL PARTS)
END
- (02 - 01) -
2. MODEL SELECTION
MODEL SELECTION
MODEL SELECTION
Selection of indoor units
2. MODEL LINE UP 2-1. OUTDOOR UNIT
5
Capacity (BTU/h) Cooling
Heating
48000
54000
Connectable indoor unit
Model name AOU48RLXFZ
Number
Capacity (%)
2 to 8
80 to 130
MODEL SELECTION
MODEL SELECTION
HP
2-2. INDOOR UNIT Rated capacity (BTU/h) Cooling Heating 9000 10200 Compact 12000 13500 Cassette 18000 20000 9000 10200 12000 13500 Slim Duct 18000 20000 24000 27000 7000 8100 Compact Wall 9000 10200 Mounted 12000 13500 18000 20000 Wall Mounted 24000 27000 Type
Model name AUU9RLF AUU12RLF AUU18RLF ARU9RLF ARU12RLF ARU18RLF ARU24RLF ASU7RLF ASU9RLF ASU12RLF ASU18RLF ASU24RLF
Remarks UTG-CCGF (Grille kit)
2-3. OPTIONAL PARTS BRANCH BOX Items Primary type Secondary type
Model name UTP-PU03A UTP-PU03B
Remarks
Model name UTP-SX248A
Remarks
SEPARATION TUBE Items Separation tube
CONTROLLER Items Central Remote Controller Wired Remote Controller Simple Remote Controller Wireless Remote Controller IR Receiver Unit
Model name Remarks UTY-DMMUM UTY-RNNUM Accessory: Compact Cassette, Slim Duct UTY-RSNUM UTY-LNHUM Accessory: Wall Mounted AR-RAH1U Accessory: Compact Wall Mounted UTY-LRHUM
- (02 - 02) -
2. MODEL SELECTION
OTHERS Model name
Grill kit
UTG-CCGF
Air outlet shutter plate
UTR-YDZB
Insulation kit for high humidity
UTZ-KXGC
Fresh air intake kit
UTZ-VXAA
External control set
UTD-ECS5A
External connect kit
UTY-XWZX
External connect kit
UTY-XWZXZ3
External connect kit (For Base heater)
UTY-XWZXZ4
Apple catechin filter
Ion deodorisation filter Communication kit
Remarks MODEL SELECTION
MODEL SELECTION
Items
Refer to "7. OPTIONAL PARTS"
UTR-FA16 UTR-FA13-1 UTR-FA16-2 UTR-FA13-2 UTY-XCBXZ1
- (02 - 03) -
2. MODEL SELECTION
3. MODEL SELECTION AND CAPACITY CALCULATION 3-1. SELECTION PROCEDURE OF INDOOR UNIT AND OUTDOOR UNIT MODEL SELECTION
MODEL SELECTION
Please select indoor units and outdoor units and make the capacity of each indoor unit be larger than cooling and heating load. 1 Calculate heat load of each room
2 Tentative selection of indoor units
3 Calculate the total cooling capacity or heating capacity of indoor units The total cooling capacity or heating capacity of indoor units = The sum of capacity of indoor units x Capacity change rate by suction temperature of indoor unit : Calculate by the value of the outdoor temperature 95°F when cooling, 47°F when heating.
4 Tentative selection of outdoor unit
5 Calculate the Maximum cooling capacity or heating capacity of outdoor unit The maximum cooling capacity or heating capacity of outdoor unit = Capacity of outdoor unit calculated from total of indoor unit rated capacity with capacity table x Capacity change rate by temperature conditions (Calculate by the value of indoor units connecting capacity in 100%) x Capacity change rate by indoor units connecting capacity : Calculate by the value of standard temperature conditions (When indoor units connecting capacity is only 100% or more) x Capacity change rate by refrigerant pipe length x Capacity change rate by frosting (Only heating operation)
6 Actual cooling capacity or heating capacity of system (Smaller one of 3 and 5)
7 Calculate the cooling capacity or heating capacity of each indoor unit The cooling capacity or heating capacity of each indoor unit = Rated capacity of each indoor unit x 6 System capacity / The sum of rated capacity of indoor units
8 Check the heat load and capacity of indoor unit of each rooms (Are you satisfied 7≥1 ?) Note: Outdoor unit is added and calculated again to lower the total rated capacity of indoor unit in case of capacity shortage.
- (02 - 04) -
2. MODEL SELECTION
3-2. THE EXAMPLE OF CALCULATION 3-2-1. COOLING EXAMPLE EXAMPLE 1 (When the connecting capacity for indoor unit is 100% or more)
Branch box
Outdoor unit
Branch Piping length, L1=32.8ft. (10m)
Branch box
MODEL SELECTION
MODEL SELECTION
Main Piping length, L1=32.8ft. (10m)
Branch box
Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 4
Indoor unit 5
Indoor unit 6
Indoor unit 7
Indoor unit 8
Room 1
Room 2
Room 3
Room 4
Room 5
Room 6
Room 7
Room 8
Design conditions ● Design temperature Indoor : 75°F DB / 63°F WB (23.9°C DB / 17.2°C WB) Outdoor : 86°F DB (30°C DB) ● Pipe length Main piping length : L1=32.8ft. (10m) Branch piping length : L2=32.8ft. (10m) ● Operation mode: Cooling
Selection of indoor unit A-1 Cooling heat load
Btu
A-2 Indoor unit models A-3 Rated capacity (TCin)r
Btu
Room 1
Room 2
Room 3
Room 4
Room 5
Room 6
Room 7
Room 8
5800
5800
5800
5800
5800
5800
5800
5800
ASU7
ASU7
ASU7
ASU7
ASU7
ASU7
ASU7
ASU7
7000
7000
7000
7000
7000
7000
7000
7000
A-4 Total rated capacity ∑(TCin)r Btu A-5
7000 x 8 = 56000
Connecting indoor unit capacity (Cp)
Cooling Sum of A-3
56000 / 48000 = 117% (80%≤Cp≤130%)
Capacity change rate by A-6 suction temperature of indoor unit A-7
Remark
Total capacity at design temperature ∑(TCin) d
Btu
46.1 / 48.0 = 0.960
See Fig.1
56000 x 0.960 = 53760
(A-4) x (A-6)
Calculate the Maximum capacity of outdoor unit Remark
B-1 Outdoor unit model
AOU48RLXFZ
B-2 Rated capacity (TCout)r
Btu
48000
Cooling
B-3 Capacity change rate by temperature conditions
47.4 / 48.0 = 0.988
See Fig.1
B-4 Capacity change rate by indoor units connecting capacity
52.4 / 48.0 = 1.092
See Fig.2
0.98 x 0.942 = 0.923
See 5-1.
48000 x 0.988 x 1.092 x 0.923 = 47800
(B-2) x (B-3) x (B-4) x (B-5)
B-5 Compensation coefficient of pipe length B-6 Maximum capacity of outdoor unit (TCout)c
Btu
Decide system capacity Remark
C-1 System capacity
Btu
Smaller one of (A-7) and (B-6)
47800
Calculate actual capacity of each indoor unit Actual capacity of each indoor unit
Btu
Room 1
Room 2
Room 3
Room 4
Room 5
Room 6
Room 7
Room 8
Remark
5970
5970
5970
5970
5970
5970
5970
5970
(A-3) x (C-1) / (A-4)
Actual capacity of all indoor units is larger than cooling heat load of each room. - (02 - 05) -
2. MODEL SELECTION
EXAMPLE 2 (When the connecting capacity for indoor unit is 100% or less)
Branch box
Outdoor unit
Branch Piping length, L1=32.8ft. (10m) MODEL SELECTION
MODEL SELECTION
Main Piping length, L1=32.8ft. (10m)
Branch box
Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 4
Room 1
Room 2
Room 3
Room 4
Design conditions ● Design temperature Indoor : 75°F DB / 63°F WB (23.9°C DB / 17.2°C WB) Outdoor : 86°F DB (30°C DB) ● Pipe length Main piping length : L1=32.8ft. (10m) Branch piping length : L2=32.8ft. (10m) ● Operation mode: Cooling
Selection of indoor unit A-1 Cooling heat load
Btu
A-2 Indoor unit models A-3 Rated capacity (TCin)r
Btu
Room 1
Room 2
Room 3
Room 4
8000
8000
11000
11000
ASU9
ASU9
ASU12
ASU12
9000
9000
12000
12000
A-4 Total rated capacity ∑(TCin)r Btu A-5
9000 x 2 + 12000 x 2 = 42000
Connecting indoor unit capacity (Cp)
Cooling Sum of A-3
42000 / 48000 = 87.5% (80%≤Cp≤130%)
Capacity change rate by A-6 suction temperature of indoor unit A-7
Remark
Total capacity at design temperature ∑(TCin) d
Btu
46.1 / 48.0 = 0.960
See Fig.1
42000 x 0.960 = 40320
(A-4) x (A-6)
Calculate the Maximum capacity of outdoor unit Remark
B-1 Outdoor unit model
AOU48RLXFZ
B-2 Rated capacity (TCout)r
Btu
B-3 Capacity change rate by temperature conditions
Btu
Cooling
47.4 / 48.0 = 0.988
See Fig.1
0.98 x 0.942 = 0.923
See 5-1.
48000 x 0.988 x 0.923 = 43770
(B-2) x (B-3) x (B-5)
B-5 Compensation coefficient of pipe length B-6 Maximum capacity of outdoor unit (TCout)c
48000
Decide system capacity Remark
C-1 System capacity
Btu
40320
Smaller one of (A-7) and (B-6)
Calculate actual capacity of each indoor unit Actual capacity of each indoor unit
Btu
Room 1
Room 2
Room 3
Room 4
Remark
8640
8640
11520
11520
(A-3) x (C-1) / (A-4)
Actual capacity of all indoor units is larger than cooling heat load of each room.
- (02 - 06) -
2. MODEL SELECTION
Indoor unit connecting capacity (%) ●●●
100
Outdoor temperature (°F) ●●● ●●● 23 32 41 50 59 68 77 86 95 104 115
70°F DB 60°F WB TC PI
75°F DB 63°F WB TC PI
●●● ●●● 45.0 45.0 45.0 45.0 45.0 44.0 43.0 41.6 39.9 38.2 35.5
●●● ●●● 49.5 49.5 49.5 49.5 49.5 49.1 48.5 47.4 46.1 42.7 37.5
●●● ●●● 2.00 2.08 2.12 2.16 2.21 2.45 2.80 3.81 4.67 5.01 4.75
(c)
Indoor temperature 80°F DB 85°F DB 67°F WB 71°F WB TC PI TC PI
●●● ●●● 2.11 2.14 2.19 2.25 2.40 2.63 3.20 4.15 4.95 5.12 4.97
●●● ●●● 53.2 53.2 53.2 53.2 53.2 52.9 52.2 51.9 48.0 44.4 39.2
(b)
●●● ●●● 2.25 2.30 2.40 2.50 2.75 3.00 3.50 4.41 5.19 5.21 5.05
●●● ●●● 59.7 59.7 59.7 59.7 59.7 59.4 58.7 58.0 53.2 48.5 42.7
●●● ●●● 2.40 2.45 2.50 2.60 2.80 3.10 3.90 4.70 5.26 5.32 5.10
90°F DB 73°F WB TC PI ●●● ●●● 64.8 64.8 64.8 64.8 64.8 64.8 62.8 60.4 54.6 51.2 44.0
●●● ●●● 2.50 2.55 2.65 2.80 3.00 3.20 4.00 5.00 5.34 5.41 5.15
(a)
A-6: Capacity change rate by suction temperature of indoor unit (b) / (a) = 46.1 / 48.0 = 0.960 B-3: Capacity change rate by temperature conditions (c) / (a) = 47.4 / 48.0 = 0.988
- (02 - 07) -
2. MODEL SELECTION
MODEL SELECTION
MODEL SELECTION
Fig 1
y
i) Refer to 4. CAPACITY TABLE to find Y1 and Y2 using X1 and X 2. ii) Calculate capacity of outdoor unit using following equation:
(X2, Y2)
Y=(Y2-Y1) / (X 2-X1) (X-X1) + Y1
(X, Y)
(X1, Y1)
x Capacity ratio of indoor units to outdoor unit, X (%)
Indoor unit connecting capacity (%)
120
X2
●●●
100
X1
Outdoor temperature (°F) 23 32 41 50 59 68 77 86 95 104 115 ●●● ●●● 23 32 41 50 59 68 77 86 95 104 115
70°F DB 60°F WB TC PI
75°F DB 63°F WB TC PI
53.2 53.2 53.2 53.2 53.2 53.2 50.8 47.8 45.0 41.6 36.8 ●●● ●●● 45.0 45.0 45.0 45.0 45.0 44.0 43.0 41.6 39.9 38.2 35.5
56.3 56.3 56.3 56.3 56.3 56.3 54.6 51.5 48.1 44.0 39.9 ●●● ●●● 49.5 49.5 49.5 49.5 49.5 49.1 48.5 47.4 46.1 42.7 37.5
2.50 2.56 2.61 2.70 2.90 3.55 4.20 4.76 5.24 5.20 4.94 ●●● ●●● 2.00 2.08 2.12 2.16 2.21 2.45 2.80 3.81 4.67 5.01 4.75
2.55 2.75 2.85 2.95 3.20 3.60 4.40 5.13 5.79 5.90 5.06 ●●● ●●● 2.11 2.14 2.19 2.25 2.40 2.63 3.20 4.15 4.95 5.12 4.97
Indoor temperature 80°F DB 85°F DB 67°F WB 71°F WB TC PI TC PI 59.7 59.7 59.7 59.7 59.7 59.7 58.0 55.3 53.2 47.1 Y2 41.3 ●●● ●●● 53.2 53.2 53.2 53.2 53.2 52.9 52.2 51.9 48.0 44.4 Y1 39.2
Capacity ratio of indoor units to outdoor unit Capacity of outdoor units (kBtu/h)
2.65 2.80 2.90 3.05 3.30 4.00 4.70 5.33 5.90 5.96 5.15 ●●● ●●● 2.25 2.30 2.40 2.50 2.75 3.00 3.50 4.41 5.19 5.21 5.05
64.8 64.8 64.8 64.8 64.8 64.8 63.5 61.4 55.3 49.1 44.0 ●●● ●●● 59.7 59.7 59.7 59.7 59.7 59.4 58.7 58.0 53.2 48.5 42.7
X1 = 100 % Y1 = 48.0
2.75 2.90 3.05 3.05 3.35 4.05 4.80 5.45 5.93 5.98 5.20 ●●● ●●● 2.40 2.45 2.50 2.60 2.80 3.10 3.90 4.70 5.26 5.32 5.10
90°F DB 73°F WB TC PI 68.6 68.6 68.6 68.6 68.6 68.6 65.2 63.1 57.0 53.6 45.4 ●●● ●●● 64.8 64.8 64.8 64.8 64.8 64.8 62.8 60.4 54.6 51.2 44.0
X = 117 % Y
2.80 2.95 3.10 3.20 3.40 4.10 4.85 5.51 5.96 5.98 5.28 ●●● ●●● 2.50 2.55 2.65 2.80 3.00 3.20 4.00 5.00 5.34 5.41 5.15
X2 = 120 % Y2 = 53.2
Y= (53.2-48.0) / (120-100) (117-100) + 48.0 = 52.4 (kBtu/h) B-4 : Capacity change rate by indoor units connecting capacity Y / Y1 = 52.4 / 48.0 = 1.092
- (02 - 08) -
2. MODEL SELECTION
MODEL SELECTION
Capacity of outdoor unit, Y (kBtu/h )
MODEL SELECTION
Fig 2
3-2-2. HEATING EXAMPLE EXAMPLE 3 (When the connecting capacity for indoor unit is 100% or more)
Branch box
Outdoor unit
Branch Piping length, L1=32.8ft. (10m)
Branch box
MODEL SELECTION
MODEL SELECTION
Main Piping length, L1=32.8ft. (10m)
Branch box
Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 4
Indoor unit 5
Indoor unit 6
Indoor unit 7
Indoor unit 8
Room 1
Room 2
Room 3
Room 4
Room 5
Room 6
Room 7
Room 8
Design conditions ● Design temperature Indoor : 65°F DB (18.3°C DB) Outdoor : 50°F DB / 47°F WB (10.0°C DB / 8.3°C WB) ● Pipe length Main piping length : L1=32.8ft. (10m) Branch piping length : L2=32.8ft. (10m) ● Operation mode: Heating
Selection of indoor unit A-1 Heating heat load
Btu
A-2 Indoor unit models A-3 Rated capacity (TCin)r
Btu
Room 1
Room 2
Room 3
Room 4
Room 5
Room 6
Room 7
Room 8
8000
8000
8000
8000
8000
8000
8000
8000
ASU7
ASU7
ASU7
ASU7
ASU7
ASU7
ASU7
ASU7
8100
8100
8100
8100
8100
8100
8100
8100
A-4 Total rated capacity ∑(TCin)r Btu A-5
8100 x 8 = 64800
Connecting indoor unit capacity (Cp)
Heating Sum of A-3
64800 / 54000 = 120%
Capacity change rate by A-6 suction temperature of indoor unit A-7
Remark
Total capacity at design temperature ∑(TCin) d
Btu
59.4 / 54.0 = 1.10
See Fig.3
64800 x 1.10 = 71280
(A-4) x (A-6)
Calculate the Maximum capacity of outdoor unit Remark
B-1 Outdoor unit model
AOU48RLXFZ
B-2 Rated capacity (TCout)r
Btu
B-3 Capacity change rate by temperature conditions B-4 Capacity change rate by indoor units connecting capacity B-5 Compensation coefficient of pipe length
54000
Heating
59.7 / 54.0 = 1.106
See Fig.3
62.1 / 54.0 = 1.15
See Fig.4
0.996 x 0.962 = 0.958
See 5-1.
B-6 Capacity change rate by frosting B-7 Maximum capacity of outdoor unit (TCout)c
Btu
1.00
See 5-2.
54000 x 1.106 x1.15 x 0.958 x1.00 = 65800
(B-2) x (B-3) x (B-4) x (B-5) x (B-6)
Decide system capacity Remark
C-1 System capacity
Btu
Smaller one of (A-7) and (B-7)
65800
Calculate actual capacity of each indoor unit Actual capacity of each indoor unit
Btu
Room 1
Room 2
Room 3
Room 4
Room 5
Room 6
Room 7
Room 8
Remark
8220
8220
8220
8220
8220
8220
8220
8220
(A-3) x (C-1) / (A-4)
Actual capacity of all indoor units is larger than heating heat load of each room. - (02 - 09) -
2. MODEL SELECTION
EXAMPLE 4 (When the connecting capacity for indoor unit is 100% or more)
Branch box
Outdoor unit
Branch Piping length, L1=32.8ft. (10m)
Branch box
MODEL SELECTION
MODEL SELECTION
Main Piping length, L1=32.8ft. (10m)
Branch box
Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 4
Indoor unit 5
Indoor unit 6
Indoor unit 7
Indoor unit 8
Room 1
Room 2
Room 3
Room 4
Room 5
Room 6
Room 7
Room 8
Design conditions ● Design temperature Indoor : 65°F DB (18.3°C DB) Outdoor : 41°F DB / 37°F WB (5.0°C DB / 2.8°C WB) ● Pipe length Main piping length : L1=32.8ft. (10m) Branch piping length : L2=32.8ft. (10m) ● Operation mode: Heating
Selection of indoor unit A-1 Heating heat load
Btu
A-2 Indoor unit models A-3 Rated capacity (TCin)r
Btu
Room 1
Room 2
Room 3
Room 4
Room 5
Room 6
Room 7
Room 8
6500
6500
6500
6500
6500
6500
6500
6500
ASU7
ASU7
ASU7
ASU7
ASU7
ASU7
ASU7
ASU7
8100
8100
8100
8100
8100
8100
8100
8100
A-4 Total rated capacity ∑(TCin)r Btu A-5
8100 x 8 = 64800
Connecting indoor unit capacity (Cp)
Heating Sum of A-3
64800 / 54000 = 120%
Capacity change rate by A-6 suction temperature of indoor unit A-7
Remark
Total capacity at design temperature ∑(TCin) d
Btu
59.4 / 54.0 = 1.10
See Fig.3
64800 x 1.10 = 71280
(A-4) x (A-6)
Calculate the Maximum capacity of outdoor unit Remark
B-1 Outdoor unit model
AOU48RLXFZ
B-2 Rated capacity (TCout)r
Btu
B-3 Capacity change rate by temperature conditions B-4 Capacity change rate by indoor units connecting capacity B-5 Compensation coefficient of pipe length
54000
Heating
55.3 / 54.0 = 1.024
See Fig.3
62.1 / 54.0 = 1.15
See Fig.4
0.996 x 0.962 = 0.958
See 5-1.
B-6 Capacity change rate by frosting B-7 Maximum capacity of outdoor unit (TCout)c
Btu
0.90
See 5-2.
54000 x 1.024 x1.15 x 0.958 x 0.90 = 54830
(B-2) x (B-3) x (B-4) x (B-5) x (B-6)
Decide system capacity Remark
C-1 System capacity
Btu
Smaller one of (A-7) and (B-7)
54830
Calculate actual capacity of each indoor unit Actual capacity of each indoor unit
Btu
Room 1
Room 2
Room 3
Room 4
Room 5
Room 6
Room 7
Room 8
Remark
6850
6850
6850
6850
6850
6850
6850
6850
(A-3) x (C-1) / (A-4)
Actual capacity of all indoor units is larger than heating heat load of each room. - (02 - 10) -
2. MODEL SELECTION
Indoor unit connecting capacity (%) ●●●
100
Outdoor temperature DB WB °F
°F
●●● ●●● 5 14 23 32 41 47 50 59 68 75
●●● ●●● 3 12 19 28 37 43 47 50 59 65
60°F DB TC PI
65°F DB TC PI
●●● ●●● 35.8 43.7 49.1 53.6 58.0 63.1 63.5 64.1 64.8 65.2
●●● ●●● 34.1 41.6 47.1 51.5 55.3 59.4 59.7 60.1 60.7 61.4
●●● ●●● 5.55 5.60 5.70 5.76 5.76 5.70 5.56 5.19 4.63 4.05
(c')
(c)
Indoor temperature 70°F DB 75°F DB TC PI TC PI
●●● ●●● 5.52 5.61 5.78 5.78 5.61 5.35 5.25 4.80 4.45 3.92
●●● ●●● 32.8 40.3 45.4 49.5 51.2 54.0 54.6 56.0 57.0 58.0
(b)
●●● ●●● 5.50 5.62 5.75 5.74 5.23 4.89 4.80 4.61 4.36 3.81
●●● ●●● 31.4 38.6 44.0 47.1 47.8 49.5 50.2 51.2 52.5 56.0
●●● ●●● 5.48 5.64 5.72 5.68 4.92 4.55 4.53 4.33 4.08 3.73
78°F DB TC PI ●●● ●●● 31.0 37.5 42.7 43.7 45.0 46.1 46.7 47.4 48.5 53.9
5.45 5.66 5.40 5.38 4.79 4.46 4.37 4.05 3.77 3.51
(a)
A-6: Capacity change rate by suction temperature of indoor unit (b) / (a) = 59.4 / 54.0 = 1.10 B-3: Capacity change rate by temperature conditions (c) / (a) = 59.7 / 54.0 = 1.106 (Example 3) (c’) / (a) = 55.3 / 54.0 = 1.024 (Example 4)
- (02 - 11) -
2. MODEL SELECTION
MODEL SELECTION
MODEL SELECTION
Fig 3
y
i) Refer to 4. CAPACITY TABLE to find Y1 and Y2 using X1 and X 2. ii) Calculate capacity of outdoor unit using following equation:
(X2, Y2)
Y=(Y2-Y1) / (X 2-X1) (X-X1) + Y1
(X, Y)
(X1, Y1)
x Capacity ratio of indoor units to outdoor unit, X (%)
Indoor unit connecting capacity (%)
120 X2
●●●
100 X1
Outdoor temperature DB WB °F
°F
5 14 23 32 41 47 50 59 68 75 ●●● ●●● 5 14 23 32 41 47 50 59 68 75
3 12 19 28 37 43 47 50 59 65 ●●● ●●● 3 12 19 28 37 43 47 50 59 65
60°F DB TC PI
65°F DB TC PI
38.9 49.5 53.2 57.3 60.7 63.8 66.2 68.6 69.6 70.3 ●●● ●●● 35.8 43.7 49.1 53.6 58.0 63.1 63.5 64.1 64.8 65.2
37.5 48.8 52.5 56.3 60.1 63.1 65.2 67.9 68.9 69.9 ●●● ●●● 34.1 41.6 47.1 51.5 55.3 59.4 59.7 60.1 60.7 61.4
5.57 5.62 5.71 5.80 5.92 5.98 5.98 5.10 4.37 4.14 ●●● ●●● 5.55 5.60 5.70 5.76 5.76 5.70 5.56 5.19 4.63 4.05
5.58 5.64 5.74 5.82 5.93 5.98 5.98 5.22 4.44 4.25 ●●● ●●● 5.52 5.61 5.78 5.78 5.61 5.35 5.25 4.80 4.45 3.92
Indoor temperature 70°F DB 75°F DB TC PI TC PI 36.2 47.8 51.5 55.6 59.4 62.1 64.5 Y2 66.9 68.6 69.3 ●●● ●●● 32.8 40.3 45.4 49.5 51.2 54.0 54.6 Y1 56.0 57.0 58.0
Capacity ratio of indoor units to outdoor unit Capacity of outdoor units (kBtu/h)
5.60 5.66 5.77 5.86 5.95 5.98 5.98 5.45 4.73 4.39 ●●● ●●● 5.50 5.62 5.75 5.74 5.23 4.89 4.80 4.61 4.36 3.81
34.8 46.7 50.8 54.9 58.7 61.4 63.8 66.2 67.9 68.6 ●●● ●●● 31.4 38.6 44.0 47.1 47.8 49.5 50.2 51.2 52.5 56.0
X1 = 100 % Y1 = 54.0
5.62 5.68 5.79 5.88 5.96 5.98 5.98 5.84 5.05 4.61 ●●● ●●● 5.48 5.64 5.72 5.68 4.92 4.55 4.53 4.33 4.08 3.73
78°F DB TC PI 33.8 45.7 49.8 54.3 58.0 60.4 63.1 65.2 67.2 67.9 ●●● ●●● 31.0 37.5 42.7 43.7 45.0 46.1 46.7 47.4 48.5 53.9
X = 120 % Y
5.64 5.70 5.81 5.90 5.97 5.98 5.98 5.98 5.17 4.88 ●●● ●●● 5.45 5.66 5.40 5.38 4.79 4.46 4.37 4.05 3.77 3.51
X2 = 120 % Y2 = 62.1
Y= (62.1-54.0) / (120-100) (120-100) + 54.0 = 62.1 (kBtu/h) B-4 : Capacity change rate by indoor units connecting capacity Y / Y1 = 62.1 / 54.0 = 1.15
- (02 - 12) -
2. MODEL SELECTION
MODEL SELECTION
Capacity of outdoor unit, Y (kBtu/h )
MODEL SELECTION
Fig 4
4. CAPACITY TABLE 4-1. COOLING CAPACITY COOLING CAPACITY
MODEL : AOU48RLXFZ Indoor unit connecting capacity (%)
130
120
110
100
90
80
Outdoor temperature (°F) 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115
70°F DB 60°F WB TC PI
75°F DB 63°F WB TC PI
57.0 57.0 57.0 57.0 57.0 57.0 53.9 49.5 46.4 42.0 37.5 53.2 53.2 53.2 53.2 53.2 53.2 50.8 47.8 45.0 41.6 36.8 49.1 49.1 49.1 49.1 49.1 49.1 47.4 45.0 43.3 39.9 36.2 45.0 45.0 45.0 45.0 45.0 44.0 43.0 41.6 39.9 38.2 35.5 40.9 40.9 40.9 40.9 40.9 40.9 40.9 40.3 39.2 37.2 34.1 35.1 35.1 35.1 35.1 35.1 35.1 34.8 34.1 33.1 32.1 31.4
59.7 59.7 59.7 59.7 59.7 59.7 56.3 53.6 48.8 44.4 40.9 56.3 56.3 56.3 56.3 56.3 56.3 54.6 51.5 48.1 44.0 39.9 52.9 52.9 52.9 52.9 52.9 52.9 51.5 49.5 47.4 43.3 38.9 49.5 49.5 49.5 49.5 49.5 49.1 48.5 47.4 46.1 42.7 37.5 46.1 46.1 46.1 46.1 46.1 46.1 45.4 43.3 41.3 39.2 35.8 38.9 38.9 38.9 38.9 38.9 38.9 38.6 38.2 36.5 34.8 32.8
2.80 2.90 2.95 3.10 3.40 4.25 4.80 5.11 5.40 5.50 5.01 2.50 2.56 2.61 2.70 2.90 3.55 4.20 4.76 5.24 5.20 4.94 2.25 2.29 2.44 2.51 2.60 2.95 3.50 4.30 5.05 5.00 4.82 2.00 2.08 2.12 2.16 2.21 2.45 2.80 3.81 4.67 5.01 4.75 1.80 1.86 1.94 2.01 2.10 2.38 2.75 3.35 4.10 4.61 4.50 1.55 1.65 1.80 1.92 2.11 2.31 2.70 3.02 3.38 3.91 4.15
2.85 3.00 3.05 3.25 3.55 4.35 5.15 5.49 5.85 5.90 5.06 2.55 2.75 2.85 2.95 3.20 3.60 4.40 5.13 5.79 5.90 5.06 2.30 2.35 2.60 2.65 2.85 3.20 3.75 4.63 5.33 5.90 5.01 2.11 2.14 2.19 2.25 2.40 2.63 3.20 4.15 4.95 5.12 4.97 1.95 2.05 2.10 2.20 2.35 2.45 2.95 3.60 4.31 4.66 4.55 1.90 2.00 2.05 2.15 2.30 2.55 2.90 3.33 3.55 4.14 4.22
Indoor temperature 80°F DB 85°F DB 67°F WB 71°F WB TC PI TC PI 62.8 62.8 62.8 62.8 62.8 62.8 61.4 56.6 53.6 47.8 42.0 59.7 59.7 59.7 59.7 59.7 59.7 58.0 55.3 53.2 47.1 41.3 56.6 56.6 56.6 56.6 56.6 56.6 55.6 53.9 52.9 46.1 40.3 53.2 53.2 53.2 53.2 53.2 52.9 52.2 51.9 48.0 44.4 39.2 48.5 48.5 48.5 48.5 48.5 48.5 47.8 46.1 43.3 41.3 37.5 44.0 44.0 44.0 44.0 44.0 44.0 43.0 41.3 38.6 36.5 34.1
2.90 3.05 3.10 3.30 3.60 4.45 5.20 5.55 5.87 5.96 5.15 2.65 2.80 2.90 3.05 3.30 4.00 4.70 5.33 5.90 5.96 5.15 2.45 2.55 2.65 2.80 3.05 3.55 4.20 5.11 5.90 5.96 5.11 2.25 2.30 2.40 2.50 2.75 3.00 3.50 4.41 5.19 5.21 5.05 2.20 2.25 2.35 2.45 2.70 2.95 3.45 4.10 4.43 4.74 4.63 2.15 2.20 2.30 2.40 2.65 2.90 3.19 3.42 3.63 4.29 4.27
66.5 66.5 66.5 66.5 66.5 66.5 64.8 62.4 56.6 49.5 44.7 64.8 64.8 64.8 64.8 64.8 64.8 63.5 61.4 55.3 49.1 44.0 61.4 61.4 61.4 61.4 61.4 61.4 60.7 60.1 54.3 48.8 43.3 59.7 59.7 59.7 59.7 59.7 59.4 58.7 58.0 53.2 48.5 42.7 54.6 54.6 54.6 54.6 54.6 54.6 53.6 52.5 49.8 46.7 40.9 48.8 48.8 48.8 48.8 48.8 48.8 48.1 47.1 45.0 42.3 37.9
2.95 3.10 3.15 3.35 3.65 4.45 5.20 5.61 5.93 5.98 5.20 2.75 2.90 3.05 3.05 3.35 4.05 4.80 5.45 5.93 5.98 5.20 2.60 2.65 2.75 2.85 3.15 3.65 4.40 5.22 5.93 5.98 5.18 2.40 2.45 2.50 2.60 2.80 3.10 3.90 4.70 5.26 5.32 5.10 2.35 2.40 2.45 2.55 2.75 3.05 3.70 4.27 4.66 4.87 4.71 2.30 2.35 2.40 2.50 2.70 3.00 3.29 3.77 4.20 4.36 4.32
90°F DB 73°F WB TC PI 70.3 70.3 70.3 70.3 70.3 68.2 66.5 64.1 58.0 51.2 46.1 68.6 68.6 68.6 68.6 68.6 68.6 65.2 63.1 57.0 53.6 45.4 66.9 66.9 66.9 66.9 66.9 66.9 64.5 61.8 57.0 52.5 44.7 64.8 64.8 64.8 64.8 64.8 64.8 62.8 60.4 54.6 51.2 44.0 59.7 59.7 59.7 59.7 59.7 59.7 58.3 54.6 51.2 47.8 42.0 52.9 52.9 52.9 52.9 52.9 52.9 52.2 49.1 46.4 43.3 39.2
3.00 3.15 3.20 3.40 3.70 4.50 5.25 5.68 5.98 5.98 5.30 2.80 2.95 3.10 3.20 3.40 4.10 4.85 5.51 5.96 5.98 5.28 2.65 2.75 2.80 3.00 3.20 3.75 4.45 5.29 5.96 5.98 5.26 2.50 2.55 2.65 2.80 3.00 3.20 4.00 5.00 5.34 5.41 5.15 2.45 2.50 2.60 2.75 2.95 3.15 3.95 4.41 4.86 4.95 4.80 2.40 2.45 2.55 2.70 2.90 3.10 3.41 3.86 4.35 4.49 4.40
TC : Total Capacity kBtu/h. PI : Power Input kW. The data is based on the following conditions. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]. - (02 - 13) -
2. MODEL SELECTION
MODEL SELECTION
MODEL SELECTION
Capacity in kBtu/h
COOLING CAPACITY
Indoor unit connecting capacity (%)
130
120
110
100
90
80
Outdoor temperature (°C) -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1
21.1°CDB 15.6°CWB TC PI
23.9°CDB 17.2°CWB TC PI
16.7 16.7 16.7 16.7 16.7 16.7 15.8 14.5 13.6 12.3 11.0 15.6 15.6 15.6 15.6 15.6 15.6 14.9 14.0 13.2 12.2 10.8 14.4 14.4 14.4 14.4 14.4 14.4 13.9 13.2 12.7 11.7 10.6 13.2 13.2 13.2 13.2 13.2 12.9 12.6 12.2 11.7 11.2 10.4 12.0 12.0 12.0 12.0 12.0 12.0 12.0 11.8 11.5 10.9 10.0 10.3 10.3 10.3 10.3 10.3 10.3 10.2 10.0 9.7 9.4 9.2
17.5 17.5 17.5 17.5 17.5 17.5 16.5 15.7 14.3 13.0 12.0 16.5 16.5 16.5 16.5 16.5 16.5 16.0 15.1 14.1 12.9 11.7 15.5 15.5 15.5 15.5 15.5 15.5 15.1 14.5 13.9 12.7 11.4 14.5 14.5 14.5 14.5 14.5 14.4 14.2 13.9 13.5 12.5 11.0 13.5 13.5 13.5 13.5 13.5 13.5 13.3 12.7 12.1 11.5 10.5 11.4 11.4 11.4 11.4 11.4 11.4 11.3 11.2 10.7 10.2 9.6
2.80 2.90 2.95 3.10 3.40 4.25 4.80 5.11 5.40 5.50 5.01 2.50 2.56 2.61 2.70 2.90 3.55 4.20 4.76 5.24 5.20 4.94 2.25 2.29 2.44 2.51 2.60 2.95 3.50 4.30 5.05 5.00 4.82 2.00 2.08 2.12 2.16 2.21 2.45 2.80 3.81 4.67 5.01 4.75 1.80 1.86 1.94 2.01 2.10 2.38 2.75 3.35 4.10 4.61 4.50 1.55 1.65 1.80 1.92 2.11 2.31 2.70 3.02 3.38 3.91 4.15
2.85 3.00 3.05 3.25 3.55 4.35 5.15 5.49 5.85 5.90 5.06 2.55 2.75 2.85 2.95 3.20 3.60 4.40 5.13 5.79 5.90 5.06 2.30 2.35 2.60 2.65 2.85 3.20 3.75 4.63 5.33 5.90 5.01 2.11 2.14 2.19 2.25 2.40 2.63 3.20 4.15 4.95 5.12 4.97 1.95 2.05 2.10 2.20 2.35 2.45 2.95 3.60 4.31 4.66 4.55 1.90 2.00 2.05 2.15 2.30 2.55 2.90 3.33 3.55 4.14 4.22
Indoor temperature 26.7°CDB 29.4°CDB 19.4°CWB 21.7°CWB TC PI TC PI 18.4 18.4 18.4 18.4 18.4 18.4 18.0 16.6 15.7 14.0 12.3 17.5 17.5 17.5 17.5 17.5 17.5 17.0 16.2 15.6 13.8 12.1 16.6 16.6 16.6 16.6 16.6 16.6 16.3 15.8 15.5 13.5 11.8 15.6 15.6 15.6 15.6 15.6 15.5 15.3 15.2 14.1 13.0 11.5 14.2 14.2 14.2 14.2 14.2 14.2 14.0 13.5 12.7 12.1 11.0 12.9 12.9 12.9 12.9 12.9 12.9 12.6 12.1 11.3 10.7 10.0
2.90 3.05 3.10 3.30 3.60 4.45 5.20 5.55 5.87 5.96 5.15 2.65 2.80 2.90 3.05 3.30 4.00 4.70 5.33 5.90 5.96 5.15 2.45 2.55 2.65 2.80 3.05 3.55 4.20 5.11 5.90 5.96 5.11 2.25 2.30 2.40 2.50 2.75 3.00 3.50 4.41 5.19 5.21 5.05 2.20 2.25 2.35 2.45 2.70 2.95 3.45 4.10 4.43 4.74 4.63 2.15 2.20 2.30 2.40 2.65 2.90 3.19 3.42 3.63 4.29 4.27
19.5 19.5 19.5 19.5 19.5 19.5 19.0 18.3 16.6 14.5 13.1 19.0 19.0 19.0 19.0 19.0 19.0 18.6 18.0 16.2 14.4 12.9 18.0 18.0 18.0 18.0 18.0 18.0 17.8 17.6 15.9 14.3 12.7 17.5 17.5 17.5 17.5 17.5 17.4 17.2 17.0 15.6 14.2 12.5 16.0 16.0 16.0 16.0 16.0 16.0 15.7 15.4 14.6 13.7 12.0 14.3 14.3 14.3 14.3 14.3 14.3 14.1 13.8 13.2 12.4 11.1
2.95 3.10 3.15 3.35 3.65 4.45 5.20 5.61 5.93 5.98 5.20 2.75 2.90 3.05 3.05 3.35 4.05 4.80 5.45 5.93 5.98 5.20 2.60 2.65 2.75 2.85 3.15 3.65 4.40 5.22 5.93 5.98 5.18 2.40 2.45 2.50 2.60 2.80 3.10 3.90 4.70 5.26 5.32 5.10 2.35 2.40 2.45 2.55 2.75 3.05 3.70 4.27 4.66 4.87 4.71 2.30 2.35 2.40 2.50 2.70 3.00 3.29 3.77 4.20 4.36 4.32
32.2°CDB 22.8°CWB TC PI 20.6 20.6 20.6 20.6 20.6 20.0 19.5 18.8 17.0 15.0 13.5 20.1 20.1 20.1 20.1 20.1 20.1 19.1 18.5 16.7 15.7 13.3 19.6 19.6 19.6 19.6 19.6 19.6 18.9 18.1 16.7 15.4 13.1 19.0 19.0 19.0 19.0 19.0 19.0 18.4 17.7 16.0 15.0 12.9 17.5 17.5 17.5 17.5 17.5 17.5 17.1 16.0 15.0 14.0 12.3 15.5 15.5 15.5 15.5 15.5 15.5 15.3 14.4 13.6 12.7 11.5
3.00 3.15 3.20 3.40 3.70 4.50 5.25 5.68 5.98 5.98 5.30 2.80 2.95 3.10 3.20 3.40 4.10 4.85 5.51 5.96 5.98 5.28 2.65 2.75 2.80 3.00 3.20 3.75 4.45 5.29 5.96 5.98 5.26 2.50 2.55 2.65 2.80 3.00 3.20 4.00 5.00 5.34 5.41 5.15 2.45 2.50 2.60 2.75 2.95 3.15 3.95 4.41 4.86 4.95 4.80 2.40 2.45 2.55 2.70 2.90 3.10 3.41 3.86 4.35 4.49 4.40
TC : Total Capacity kW. PI : Power Input kW. The data is based on the following conditions. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]. - (02 - 14) -
2. MODEL SELECTION
MODEL SELECTION
MODEL SELECTION
Capacity in kW
4-2. HEATING CAPACITY HEATING CAPACITY
MODEL : AOU48RLXFZ Indoor unit connecting capacity (%)
Outdoor temperature DB WB
65°F DB TC PI
Indoor temperature 70°F DB 75°F DB TC PI TC PI
°F
°F
60°F DB TC PI
78°F DB TC PI
130
5 14 23 32 41 47 50 59 68 75
3 12 19 28 37 43 47 50 59 65
40.9 51.2 53.9 58.0 61.4 64.8 67.2 69.6 70.6 71.0
5.59 5.66 5.76 5.86 5.93 5.98 5.98 5.98 5.98 4.22
39.2 50.2 53.2 57.0 60.7 63.8 66.5 68.9 69.9 70.3
5.61 5.67 5.77 5.88 5.95 5.98 5.98 5.98 5.98 4.35
38.2 49.5 52.5 56.3 60.1 62.8 65.9 68.2 69.6 69.9
5.64 5.69 5.79 5.90 5.97 5.98 5.98 5.98 5.98 4.50
36.2 48.1 51.9 55.6 59.4 62.1 65.2 67.6 68.6 69.3
5.69 5.71 5.81 5.91 5.98 5.98 5.98 5.98 5.98 4.70
35.5 47.4 50.8 54.9 58.7 61.4 64.5 66.9 67.9 68.6
5.67 5.72 5.83 5.92 5.98 5.98 5.98 5.98 5.98 4.90
120
5 14 23 32 41 47 50 59 68 75
3 12 19 28 37 43 47 50 59 65
38.9 49.5 53.2 57.3 60.7 63.8 66.2 68.6 69.6 70.3
5.57 5.62 5.71 5.80 5.92 5.98 5.98 5.10 4.37 4.14
37.5 48.8 52.5 56.3 60.1 63.1 65.2 67.9 68.9 69.9
5.58 5.64 5.74 5.82 5.93 5.98 5.98 5.22 4.44 4.25
36.2 47.8 51.5 55.6 59.4 62.1 64.5 66.9 68.6 69.3
5.60 5.66 5.77 5.86 5.95 5.98 5.98 5.45 4.73 4.39
34.8 46.7 50.8 54.9 58.7 61.4 63.8 66.2 67.9 68.6
5.62 5.68 5.79 5.88 5.96 5.98 5.98 5.84 5.05 4.61
33.8 45.7 49.8 54.3 58.0 60.4 63.1 65.2 67.2 67.9
5.64 5.70 5.81 5.90 5.97 5.98 5.98 5.98 5.17 4.88
110
5 14 23 32 41 47 50 59 68 75
3 12 19 28 37 43 47 50 59 65
37.5 46.7 50.5 54.3 57.7 60.7 63.1 66.2 67.9 69.3
5.55 5.59 5.56 5.52 5.04 4.75 4.63 4.40 4.23 4.12
35.8 46.1 49.8 53.6 57.0 60.1 62.1 65.2 66.9 68.6
5.57 5.61 5.71 5.79 5.22 5.00 4.89 4.66 4.43 4.21
34.1 45.4 49.1 52.9 56.0 59.4 61.4 64.1 66.2 66.2
5.59 5.63 5.74 5.84 5.36 5.30 5.18 4.88 4.61 4.28
33.1 44.7 48.5 52.2 55.3 58.7 60.7 63.1 65.5 63.8
5.60 5.65 5.73 5.85 5.55 5.37 5.27 5.03 4.72 4.36
32.4 44.0 47.4 51.5 54.6 58.0 59.7 62.1 64.8 61.4
5.62 5.68 5.77 5.89 5.86 5.51 5.43 5.19 4.84 4.42
100
5 14 23 32 41 47 50 59 68 75
3 12 19 28 37 43 47 50 59 65
35.8 43.7 49.1 53.6 58.0 63.1 63.5 64.1 64.8 65.2
5.55 5.60 5.70 5.76 5.76 5.70 5.56 5.19 4.63 4.05
34.1 41.6 47.1 51.5 55.3 59.4 59.7 60.1 60.7 61.4
5.52 5.61 5.78 5.78 5.61 5.35 5.25 4.80 4.45 3.92
32.8 40.3 45.4 49.5 51.2 54.0 54.6 56.0 57.0 58.0
5.50 5.62 5.75 5.74 5.23 4.89 4.80 4.61 4.36 3.81
31.4 38.6 44.0 47.1 47.8 49.5 50.2 51.2 52.5 56.0
5.48 5.64 5.72 5.68 4.92 4.55 4.53 4.33 4.08 3.73
31.0 37.5 42.7 43.7 45.0 46.1 46.7 47.4 48.5 53.9
5.45 5.66 5.40 5.38 4.79 4.46 4.37 4.05 3.77 3.51
90
5 14 23 32 41 47 50 59 68 75
3 12 19 28 37 43 47 50 59 65
34.8 41.3 44.4 48.1 51.9 56.0 56.6 58.3 59.7 60.4
5.45 5.53 5.55 5.30 5.17 5.02 4.86 4.47 4.14 3.76
33.1 39.9 41.6 44.4 48.1 51.5 51.9 54.6 56.6 57.7
5.41 5.36 5.29 4.96 4.71 4.65 4.54 4.11 3.83 3.57
32.1 38.9 40.9 43.0 46.7 48.5 50.8 52.9 55.3 55.3
5.38 5.20 5.15 4.84 4.55 4.36 4.14 3.92 3.73 3.49
31.0 37.9 39.9 42.3 44.0 45.4 46.7 47.8 49.1 50.5
5.32 5.17 5.08 4.77 4.46 4.16 3.95 3.77 3.53 3.32
30.7 35.8 37.9 39.2 40.9 42.0 43.0 44.7 45.7 48.5
5.28 5.14 5.01 4.70 4.35 3.99 3.86 3.56 3.26 3.01
80
5 14 23 32 41 47 50 59 68 75
3 12 19 28 37 43 47 50 59 65
31.7 36.5 38.6 42.3 45.7 49.5 50.5 52.2 53.6 55.3
5.22 5.01 4.86 4.48 4.17 3.99 3.95 3.86 3.65 3.41
31.4 35.1 37.2 40.6 43.3 46.7 47.4 49.5 51.5 53.6
5.15 4.98 4.81 4.40 4.10 3.91 3.84 3.74 3.56 3.25
31.0 33.8 36.2 38.6 40.9 43.3 44.7 47.4 49.8 51.5
5.12 4.95 4.71 4.32 4.06 3.85 3.82 3.70 3.55 3.11
30.7 33.1 35.1 37.2 38.9 40.9 42.0 43.3 45.7 47.1
5.08 4.92 4.66 4.26 3.81 3.54 3.50 3.45 3.22 2.93
30.4 32.4 34.1 35.8 36.8 37.9 38.6 39.9 40.9 42.7
5.03 4.89 4.59 4.11 3.70 3.41 3.33 3.16 2.94 2.68
TC : Total Capacity kBtu/h. PI : Power Input kW. The data is based on the following conditions. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]. - (02 - 15) -
2. MODEL SELECTION
MODEL SELECTION
MODEL SELECTION
Capacity in kBtu/h
HEATING CAPACITY Indoor unit connecting capacity (%)
Outdoor temperature DB WB
15.6°C DB TC PI
18.3°C DB TC PI
Indoor temperature 21.1°C DB 23.9°C DB TC PI TC PI
25.6°C DB TC PI
°C
°C
130
-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9
-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3
12.0 15.0 15.8 17.0 18.0 19.0 19.7 20.4 20.7 20.8
5.59 5.66 5.76 5.86 5.93 5.98 5.98 5.98 5.98 4.22
11.5 14.7 15.6 16.7 17.8 18.7 19.5 20.2 20.5 20.6
5.61 5.67 5.77 5.88 5.95 5.98 5.98 5.98 5.98 4.35
11.2 14.5 15.4 16.5 17.6 18.4 19.3 20.0 20.4 20.5
5.64 5.69 5.79 5.90 5.97 5.98 5.98 5.98 5.98 4.50
10.6 14.1 15.2 16.3 17.4 18.2 19.1 19.8 20.1 20.3
5.69 5.71 5.81 5.91 5.98 5.98 5.98 5.98 5.98 4.70
10.4 13.9 14.9 16.1 17.2 18.0 18.9 19.6 19.9 20.1
5.67 5.72 5.83 5.92 5.98 5.98 5.98 5.98 5.98 4.90
120
-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9
-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3
11.4 14.5 15.6 16.8 17.8 18.7 19.4 20.1 20.4 20.6
5.57 5.62 5.71 5.80 5.92 5.98 5.98 5.10 4.37 4.14
11.0 14.3 15.4 16.5 17.6 18.5 19.1 19.9 20.2 20.5
5.58 5.64 5.74 5.82 5.93 5.98 5.98 5.22 4.44 4.25
10.6 14.0 15.1 16.3 17.4 18.2 18.9 19.6 20.1 20.3
5.60 5.66 5.77 5.86 5.95 5.98 5.98 5.45 4.73 4.39
10.2 13.7 14.9 16.1 17.2 18.0 18.7 19.4 19.9 20.1
5.62 5.68 5.79 5.88 5.96 5.98 5.98 5.84 5.05 4.61
9.9 13.4 14.6 15.9 17.0 17.7 18.5 19.1 19.7 19.9
5.64 5.70 5.81 5.90 5.97 5.98 5.98 5.98 5.17 4.88
110
-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9
-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3
11.0 13.7 14.8 15.9 16.9 17.8 18.5 19.4 19.9 20.3
5.55 5.59 5.56 5.52 5.04 4.75 4.63 4.40 4.23 4.12
10.5 13.5 14.6 15.7 16.7 17.6 18.2 19.1 19.6 20.1
5.57 5.61 5.71 5.79 5.22 5.00 4.89 4.66 4.43 4.21
10.0 13.3 14.4 15.5 16.4 17.4 18.0 18.8 19.4 19.4
5.59 5.63 5.74 5.84 5.36 5.30 5.18 4.88 4.61 4.28
9.7 13.1 14.2 15.3 16.2 17.2 17.8 18.5 19.2 18.7
5.60 5.65 5.73 5.85 5.55 5.37 5.27 5.03 4.72 4.36
9.5 12.9 13.9 15.1 16.0 17.0 17.5 18.2 19.0 18.0
5.62 5.68 5.77 5.89 5.86 5.51 5.43 5.19 4.84 4.42
100
-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9
-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3
10.5 12.8 14.4 15.7 17.0 18.5 18.6 18.8 19.0 19.1
5.55 5.60 5.70 5.76 5.76 5.70 5.56 5.19 4.63 4.05
10.0 12.2 13.8 15.1 16.2 17.4 17.5 17.6 17.8 18.0
5.52 5.61 5.78 5.78 5.61 5.35 5.25 4.80 4.45 3.92
9.6 11.8 13.3 14.5 15.0 15.8 16.0 16.4 16.7 17.0
5.50 5.62 5.75 5.74 5.23 4.89 4.80 4.61 4.36 3.81
9.2 11.3 12.9 13.8 14.0 14.5 14.7 15.0 15.4 16.4
5.48 5.64 5.72 5.68 4.92 4.55 4.53 4.33 4.08 3.73
9.1 11.0 12.5 12.8 13.2 13.5 13.7 13.9 14.2 15.8
5.45 5.66 5.40 5.38 4.79 4.46 4.37 4.05 3.77 3.51
90
-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9
-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3
10.2 12.1 13.0 14.1 15.2 16.4 16.6 17.1 17.5 17.7
5.45 5.53 5.55 5.30 5.17 5.02 4.86 4.47 4.14 3.76
9.7 11.7 12.2 13.0 14.1 15.1 15.2 16.0 16.6 16.9
5.41 5.36 5.29 4.96 4.71 4.65 4.54 4.11 3.83 3.57
9.4 11.4 12.0 12.6 13.7 14.2 14.9 15.5 16.2 16.2
5.38 5.20 5.15 4.84 4.55 4.36 4.14 3.92 3.73 3.49
9.1 11.1 11.7 12.4 12.9 13.3 13.7 14.0 14.4 14.8
5.32 5.17 5.08 4.77 4.46 4.16 3.95 3.77 3.53 3.32
9.0 10.5 11.1 11.5 12.0 12.3 12.6 13.1 13.4 14.2
5.28 5.14 5.01 4.70 4.35 3.99 3.86 3.56 3.26 3.01
80
-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9
-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3
9.3 10.7 11.3 12.4 13.4 14.5 14.8 15.3 15.7 16.2
5.22 5.01 4.86 4.48 4.17 3.99 3.95 3.86 3.65 3.41
9.2 10.3 10.9 11.9 12.7 13.7 13.9 14.5 15.1 15.7
5.15 4.98 4.81 4.40 4.10 3.91 3.84 3.74 3.56 3.25
9.1 9.9 10.6 11.3 12.0 12.7 13.1 13.9 14.6 15.1
5.12 4.95 4.71 4.32 4.06 3.85 3.82 3.70 3.55 3.11
9.0 9.7 10.3 10.9 11.4 12.0 12.3 12.7 13.4 13.8
5.08 4.92 4.66 4.26 3.81 3.54 3.50 3.45 3.22 2.93
8.9 9.5 10.0 10.5 10.8 11.1 11.3 11.7 12.0 12.5
5.03 4.89 4.59 4.11 3.70 3.41 3.33 3.16 2.94 2.68
TC : Total Capacity kBtu/h. PI : Power Input kW. The data is based on the following conditions. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]. - (02 - 16) -
2. MODEL SELECTION
MODEL SELECTION
MODEL SELECTION
Capacity in kW
5. CAPACITY COMPENSATION COEFFICIENT 5-1. COMPENSATION COEFFICIENT OF PIPE LENGTH The figures give the compensation coefficient of pipe length owing to installation position.
Main piping length Change rate in cooling capacity Change rate in heating capacity
ft.
16.4
32.8
49.2
65.6
82.0
98.4
114.8
131.2
147.6
164.0
180.4
m
5
10
15
20
25
30
35
40
45
50
55
%
100
98.0
96.0
94.0
92.0
90.0
88.0
86.0
84.0
82.0
80.0
%
100
99.6
99.2
98.9
98.5
98.1
97.7
97.3
97.0
96.6
96.2
100 Heating 95
90
85
Cooling
80
75 0
16.4
32.8
49.2
65.6
82.0
98.4
114.8
131.2
147.6
164.0
180.4
ft.
0
5
10
15
20
25
30
35
40
45
50
55
m
Main piping length
CAPACITY CHANGE RATE BY BRANCH PIPING LENGTH Change rate in capacity ● Refrigerant piping connection diameter: Liquid ø1/4in. (6.35mm) , Gas ø3/8in. (9.52mm) Main piping length Change rate in cooling capacity Change rate in heating capacity
ft.
9.8
16.4
32.8
49.2
m
3
5
10
15
%
100
98.3
94.2
90.0
%
100
98.9
96.2
93.5
● Refrigerant piping connection diameter: Liquid ø1/4in. (6.35mm) , Gas ø1/2in. (12.70mm) Main piping length Change rate in cooling capacity Change rate in heating capacity
ft.
9.8
16.4
32.8
49.2
m
3
5
10
15
%
100
99.2
97.1
95.0
%
100
99.5
98.3
97.0
● Refrigerant piping connection diameter: Liquid ø1/4in. (6.35mm) , Gas ø5/8in. (15.88mm) Main piping length Change rate in cooling capacity Change rate in heating capacity
ft.
9.8
16.4
32.8
49.2
m
3
5
10
15
%
100
99.6
98.5
97.5
%
100
99.9
99.5
99.0
- (02 - 17) -
2. MODEL SELECTION
MODEL SELECTION
Change rate in capacity
Change rate in capacity (%)
MODEL SELECTION
CAPACITY CHANGE RATE BY MAIN PIPING LENGTH
5-2. COMPENSATION COEFFICIENT OF FROSTING / DEFROSTING To take the effects of accumulated frost and defrosting operation on heating capacity into consideration, the capacity of outdoor units should be corrected by compensation coefficient shown in the table below. Actual heating capacity = The value of capacity table x Capacity change rate by frosting
CAPACITY CHANGE RATE BY FROSTING Outdoor temperature Capacity change rate by frosting
°FDB / °FWB °CDB / °CWB %
5.0 / 3.0
23.0 / 19.0
32.0 / 28.0
41.0 / 37.0
47.0 / 43.0
-15.0 / -16.1
-5.0 / -7.2
0.0 / -2.2
5.0 / 2.8
8.3 / 6.1
90.4
88.8
80.0
90.0
100
- (02 - 18) -
2. MODEL SELECTION
MODEL SELECTION
MODEL SELECTION
(HEATING OPERATION)
Hybrid Flex Inverter System
3. OUTDOOR UNIT & BRANCH BOX
DTR_BMU001E_04--CHAPTER03 2010.10.04
CONTENTS 3. OUTDOOR UNIT & BRANCH BOX 1. SPECIFICATIONS ......................................................................... 03 - 01 1-1.OUTDOOR UNIT ....................................................................................... 03 - 01 1-2.ENERGY EFFICIENCIES .......................................................................... 03 - 02 1-3.BRANCH BOX........................................................................................... 03 - 03
2. DIMENSIONS ................................................................................ 03 - 04 2-1.OUTDOOR UNIT ....................................................................................... 03 - 04 2-2.BRANCH BOX........................................................................................... 03 - 05
3. INSTALLATION SPACE ................................................................ 03 - 06 3-1.OUTDOOR UNIT ....................................................................................... 03 - 06 3-1-1. SINGLE OUTDOOR UNIT INSTALLATION ............................................................ 03 - 06 3-1-2. MULTIPLE OUTDOOR UNIT INSTALLATION ........................................................ 03 - 07 3-1-3. OUTDOOR UNITS INSTALLATION IN MULTI ROW .............................................. 03 - 07
3-2.BRANCH BOX........................................................................................... 03 - 08 3-2-1. HORIZONTAL INSTALLATION ............................................................................... 03 - 08 3-2-2. VERTICAL INSTALLATION .................................................................................... 03 - 09
4. REFRIGERANT CIRCUIT ............................................................. 03 - 10 5. WIRING DIAGRAM ....................................................................... 03 - 12 5-1.OUTDOOR UNIT ....................................................................................... 03 - 12 5-2.BRANCH BOX........................................................................................... 03 - 13
6. OPERATION RANGE .................................................................... 03 - 14 7. NOISE LEVEL CURVE .................................................................. 03 - 15 8. ELECTRIC CHARACTERISTICS .................................................. 03 - 17 8-1.OUTDOOR UNIT ....................................................................................... 03 - 17 8-2.BRANCH BOX........................................................................................... 03 - 17
9. SAFETY DEVICES ........................................................................ 03 - 18 9-1.OUTDOOR UNIT ....................................................................................... 03 - 18 9-2.BRANCH BOX........................................................................................... 03 - 18
1. SPECIFICATIONS Model name Power source Available Voltage Range Connectable indoor unit Cooling
Max
Capacity
OUTDOOR UNITS
Heating Cooling Input power *1 Heating Cooling Current *1 Heating
Fan
Type × Q'ty Airflow rate Motor
Sound pressure level
Heat exchanger
Enclosure
Weight
Net Gross Net Gross Size
Connection pipe
Operation range
Max Rated Max. Rated Max. Rated Max. Rated Max.
kW
A
CFM (m3/h) W Rated Rated
dB(A)
Type (Material) Surface treatment W W Type Charge Type Material Color
Refrigerant oil
Rated
in.(mm) FPI
Type × Q'ty Motor output Crankcase heater
Refrigerant
Dimensions
Cooling Heating Type × Q'ty Output Cooling Heating
Dimension Fin pitch Rows × Stages Pipe type (Material) Fin
Compressor
Rated
Number Capacity Btu/h kW Btu/h Btu/h kW Btu/h
(H x W x D)
lbs(g)
in. (mm) lbs (kg)
Liquid Gas
Method Max. length (Total) Max.length (BP-IN) Max. height difference between Outdoor Unit and each Indoor Units. Max. height difference between Indoor Units. Cooling Heating
in. (mm)
ft (m)
AOU48RLXFZ 1ø 208/230V 60Hz 187-264V 2 to 8 80 to 130% 48,000 14.1 51,100 54,000 15.8 57,000 5.27 5.98 4.83 5.98 23.4 26.5 21.4 26.5 Propeller ×1 2,737 (4,650) 2,825 (4,800) DC motor ×1 111 56 58 34-3/4 × 37-9/16 × 1-1/2 (882×955×38.1) 18 3 × 42 Grooved H-pin (Copper) Corrugate (Aluminium) Corrosion resistance (Blue Fin) DC TWIN ROTARY ×1 2700 25 R410A 7.6 (3450) PVE Painted galvanized steel Beige (10YR 7.5/1.0NN) 36 × 38-1/4 × 14-5/8 (914 x 970 x 370) 41-1/4 × 41-7/8 × 18-27/32 (1048 x 1064 x 479) 216 (98) 234 (106) 3/8 (9.52) 5/8 (15.88) Flare 377 (115) 49 (15) 98 (30) 49 (15)
°F (°C)
23 to 115 (-5 to 46) 5 to 75 (-15 to 24)
Note : Specifications are based on the following conditions. *1: In case of connecting four indoor units (12kBtu class), Electrical data is only for outdoor unit. Power source of specifications : 230V Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].
- (03 - 01) -
3. OUTDOOR UNIT & BRANCH BOX
OUTDOOR UNITS
1-1. OUTDOOR UNIT
Combination of indoor unit Capacity Cooling
Input power Current EER SEER Capacity
OUTDOOR UNITS
Heating
Input power Current COP HSPF
Btu/h kW kW A Btu/h/W Btu/h kW kW A W/W -
non-Duct ASU12 x 4 48,000 14.1 5.19 23.0 9.25 17.0 54,000 15.8 4.89 21.7 3.23 9.8
Duct ARU12 x 4 48,000 14.1 5.52 24.5 8.70 14.7 54,000 15.8 5.02 22.3 3.15 9.3
Mix 48,000 14.1 5.35 23.7 8.97 15.8 54,000 15.8 4.96 22.0 3.19 9.5
Note : Specifications are based on the ARI Standard 210/240. Power source of specifications : 230V Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].
- (03 - 02) -
3. OUTDOOR UNIT & BRANCH BOX
OUTDOOR UNITS
1-2. ENERGY EFFICIENCIES
Model name Casing color Connectable indoor unit Max. combination Min. combination Power source Available voltage range Power consumption Running current Refrigerant type Net Dimensions (H × W × D) Gross Net Weight Gross Connection pipe Operation range
Size
Btu/h Btu/h
W A in. (mm) lbs (kg) Liquid Gas
in. (mm)
Method °F (°C) %RH
UTP-PU03A (Primary) Paintingless 1 to 3 Units 62,000 7,000 1ø 208/230V 60Hz 187-264V 10 0.05 R410A 7-5/8 × 17 × 14-5/8 (195×433×370) 10 × 36-5/8 × 17-1/8 (255×929×434) 20 (9) 29 (13) Main : 3/8 (9.52) ×1, Branch : 1/4(6.35)×3 Main : 5/8(15.88)×1, Branch : 1/2(12.7)×3 Flare 5 to 115 (-15 to 46) 80 or less
UTP-PU03B (Secondary) Paintingless 1 to 3 Units 62,000 7,000 1ø 208/230V 60Hz 187-264V 10 0.05 R410A 7-5/8 × 17 × 14-5/8 (195×433×370) 10 × 36-5/8 × 17-1/8 (255×929×434) 20 (9) 29 (13) Main : 3/8 (9.52) ×1, Branch : 1/4(6.35)×3 Main : 5/8(15.88)×1, Branch : 1/2(12.7)×3 Flare 5 to 115 (-15 to 46) 80 or less
Note : Specifications are based on the following conditions. Power source of specifications : 230V.
- (03 - 03) -
3. OUTDOOR UNIT & BRANCH BOX
OUTDOOR UNITS
OUTDOOR UNITS
1-3. BRANCH BOX
2. DIMENSIONS 2-1. OUTDOOR UNIT MODEL : AOU48RLXFZ 6-1/16 (154)
1-9/16 (40)
14-9/16 (370) 15/16 (24)
1-7/8 (48)
2 (51): Gas 16-5/32 (410)
25-19/32 (650)
1-11/16 (43): Liquid
6-17/32 (166)
Unit : inch (mm)
1-13/32 (36)
15/16 (24)
OUTDOOR UNITS
OUTDOOR UNITS
Top view
14-9/16 (370) 15/32 (12)
13-7/16 (341) 12-5/8 (321) 12-13/32 (315) 12 (305) 11-21/32 (296) 8-15/16 (227) 5-1/2 (140)
Front view
5-19/32 (142) 2-3/4 (70)
ø1-3/32 (28): Cable port ø1-3/32 (28): Cable port
Side view
1-31/32 (50)
4-3/8 (111) 13/16 (21) 2-5/32 (55)
6-3/32 (155)
20-23/32 (526)
4-23/32 (120) 1-31/32 (50)
3-1/2 (89)
1-31/32 (50) 11 (279) 3-3/4 (95) 11-11/16 (297)
1 (25)
5-5/32 (131) ø1-3/32 (28) 3-7/16 : Cable port (87)
5/16 (8)
13/16 (21)
36 (914)
38-3/16 (970)
13/16 2-9/16 (21) (65)
ø1-3/32 (28): Cable port ø1-3/32 (28): Cable port
Rear view
1-31/32 9/16 (14) (50)
2-9/16 19/32 (65) (15)
1-9/16 (40) 1-31/32 (50) 3 (76) 10-15/16 (278) 17-1/4 (438) 20-23/32 (526) 24-1/2 (622) 27-5/32 (690)
Detail A
Bottom view
- (03 - 04) -
3. OUTDOOR UNIT & BRANCH BOX
2-2. BRANCH BOX MODELS : UTP-PU03A, UTP-PU03B 8-7/16 (214)
Unit : inch (mm)
6-27/32 (174)
OUTDOOR UNITS
OUTDOOR UNITS
6-1/16 (154)
5-9/32 (134)
4-11/32 (110)
6-15/16 (176) 8-1/2 (216) 10-3/32 (256)
2-3/4 (70)
18-15/32 (469)
7-11/16 (195)
Ceiling hanging
18-15/32 (469)
2-15/16 (75)
2-15/16 (75)
Outdoor unit side
1 (25)
Indoor unit side
17-1/16 (433)
5-13/16 (148)
2-11/16 (68)
3-3/4 (95)
14-21/32 (372)
10-3/32 (256) 3-11/32 (85)
15/16 (24)
2-1/4 (57)
3-3/4 (95) 3-3/4 (95)
17 (432)
Wall hanging
- (03 - 05) -
3. OUTDOOR UNIT & BRANCH BOX
Caution ● The installation space shown in the following examples is based on an ambient temperature under cooling operation of 95 °F DB (35 °C DB) at the air intake of the outdoor unit. Provide more space around the air intake than shown in the examples if the ambient temperature exceeds 95 °F DB (35 °C DB) or if the thermal load of all of the outdoor units exceeds the capacity. ● Consider the transportation route, installation space, maintenance space, and access, and install the unit in a location with sufficient space for the refrigerant piping. ● Observe the installation space specifications that are shown in the figures. Provide the same space for the air intake at the rear of the outdoor unit. If the installation is not performed according to the specifications, it could cause a short circuit and result in a lack of operating performance. As a result, the outdoor unit might easily be stopped by high-pressure protection. Air intake
Rear view
● Installation methods not shown in the following examples are not recommended. Performance may drop significantly.
3-1-1. SINGLE OUTDOOR UNIT INSTALLATION WHEN THE UPWARD AREA IS OPEN
Unit : inch (mm)
Obstacles at rear and sides only
Obstacles at rear only
5-29/32 (150)
7-7/8 (200) 11-13/16 (300) 7-7/8 (200)
Obstacles at front and rear only
Obstacles at front only
5-29/32 (150) 39-3/8 (1000) or more
39-3/8 (1000) or more
WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA Obstacles at rear and above only
Obstacles at rear, sides, and above only 59-1/16 (1500)
39-3/8 (1000)
11-13/16 (300) 9-27/32 (250)
Max. 19-11/16 (500)
9-27/32 (250)
- (03 - 06) -
19-11/16 (500) Max. 19-11/16 (500)
3. OUTDOOR UNIT & BRANCH BOX
OUTDOOR UNITS
OUTDOOR UNITS
3. INSTALLATION SPACE 3-1. OUTDOOR UNIT
3-1-2. MULTIPLE OUTDOOR UNIT INSTALLATION ● Provide at least 1inch (25mm) of space between the outdoor units if multiple units are installed. ● When routing the piping from the side of an outdoor unit, provide space for the piping. ● No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following example when an obstruction is present also in the upward area.
WHEN THE UPWARD AREA IS OPEN OUTDOOR UNITS
Obstacles at front only Obstacles at front and rear only
OUTDOOR UNITS
Obstacles at rear only
59-1/16 (1500) or more 11-13/16 (300)
19-11/16 (500) 59-1/16 (1500) or more
WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA Obstacles at rear and above only
59-1/16 (1500)
59-1/16 (1500) 19-11/16 (500) Max. 11-13/16 (300)
3-1-3. OUTDOOR UNITS INSTALLATION IN MULTI ROW Single parallel unit arrangement
Multiple parallel unit arrangement
5-29/32 (150) 19-11/16 (500)
78-3/4 (2000) or more
118-1/8 (3000) or more
23-5/8 (600)
23-5/8 (600) 59-1/16 (1500)
39-3/8 (1000)
- (03 - 07) -
3. OUTDOOR UNIT & BRANCH BOX
3-2. BRANCH BOX ● The branch box can be installed onto the wall or hanging from the ceiling. ● The branch box can be installed and set horizontally or vertically. ● Provide a service access for maintenance and inspection purposes as shown in the figure below. ● It is not necessary to provide drainage for the branch box. ● The slope of the top side must be within ±5° in all directions of the horizontal plane. ● Use M8 or M10 (5/16" or 3/8") for the bolt size when hanging.
OUTDOOR UNITS
OUTDOOR UNITS
3-2-1. HORIZONTAL INSTALLATION
10-3/32 (256)
(13 (304))
Hanger bolt pitch
15/16 (24)
Be sure to install so that the top side faces up.
Top side 1-9/16 (40)
1-9/16 (40) 1-3/4 (44)
3-3/4 (95)
6-1/16 (154)
17-1/16 (433)
3-3/4 (95)
9-7/8 (251)
3-3/4 (95)
(13 (304))
Outdoor unit side
2-1/4 (57)
2-23/32 (69) Indoor unit side
Wall installation
(Service space)
12 (300) or more
Service access
28 (700) or more
63/64 (25)
Installation dimensions
5-53/64 (148)
2-15/16 (75)
7-11/16 (195)
4-3/4 (120)
(33 (838))
1-5/8 (42) 3-11/32 (85)
UNIT B
UNIT A
Top side
UNIT C
18-15/32 (469) Hanger bolt pitch
34 (850) or more
15 (360) or more
21 (530) or more
(Service space)
(Service space)
- (03 - 08) -
3. OUTDOOR UNIT & BRANCH BOX
3-2-2. VERTICAL INSTALLATION ● A vertical installation can only be performed when mounting on the wall. (A vertical installation cannot be hung from the ceiling.) ● Be sure to install the control box so that the top side faces up. ● The positioning of the control box cannot be changed when performing a vertical installation.
OUTDOOR UNITS
Top side
UNIT B UNIT C
18-15/32 (469) Hanger bolt pitch
Indoor unit side
15 (360) or more (Service space)
(Service space)
Installation dimensions
12 (300) or more
21 (530) or more (Service space)
31-1/2 (800) or more 15-3/4 (400) Service access
7-7/8 (200)
19-11/16 (500) or more
Outdoor unit side
UNIT A
15/16 (24) 10-3/32 (256)
OUTDOOR UNITS
Top side
- (03 - 09) -
3. OUTDOOR UNIT & BRANCH BOX
4. REFRIGERANT CIRCUIT Branch box 1 (primary type)
Outdoor unit
TH11
TH10 3WV
0
TH10
Strainer
4WV HP-SW
Strainer
HEX 0
TH11
TH12 EEV4
HEX
OS
Indoor unit 2
Indoor unit 3
0
TH1
Strainer
Comp ressor
EEV1 TH2
TH8
SCHEX
HEX
TH6
SV
EEV3
Strainer 3WV
Strainer
EEV3
TH12
TH9
OUTDOOR UNITS
OUTDOOR UNITS
TH11
TH12
TH10
HPS
Indoor unit 1
HEX
Strainer TH9 Strainer
TH5 TH4
TH3 LPS
TH7
EEV3 TH9 EEV2
Branch box 2 (secondary type) Accumu lator
TH11
HEX
TH10
0
TH12
TH10
Strainer
Indoor unit 4
TH11
HEX
TH10
0
TH12 EEV4
TH11
HEX
Indoor unit 5
Indoor unit 6
0
Strainer EEV3 Strainer
EEV3
EEV3
TH12
TH9 Strainer TH9 Strainer TH9
Branch box 3 (secondary type)
TH11
Indoor unit 7
HEX
TH10
0
TH12
TH10
Strainer
TH11
HEX
TH10
Indoor unit 8
0
TH12 EEV4
Strainer EEV3 Strainer
EEV3
EEV3
- (03 - 10) -
TH9 Strainer TH9 Strainer TH9
3. OUTDOOR UNIT & BRANCH BOX
SYMBOL DESCRIPTION MARK HEX OS SCHEX HPS HP-SW LPS 4WV 3WV EEV 1 EEV 2 SV TH 1 TH 2 TH 3 TH 4 TH 5 TH 6 TH 7 TH 8
DESCRIPTION Heat exchanger Oil separator Sub-cool heat exchanger High pressure sensor High pressure sensor switch Low pressure sensor 4-way valve 3-way valve Electric expansion valve 1 Electric expansion valve 2 Solenoid valve Discharge temperature thermistor Compressor temperature thermistor Suction temperature thermistor Outdoor temperature thermistor Heat exchanger (outlet) thermistor Sub-cool heat exchanger (inlet) thermistor Sub-cool heat exchanger (outlet) thermistor Liquid temperature thermistor
OUTDOOR UNITS
OUTDOOR UNITS
Outdoor unit
Branch box MARK EEV 3 EEV 4 TH 9 TH 10
DESCRIPTION Electric expansion valve 3 Electric expansion valve 4 Branch box liquid temperature thermistor Branch box gas temperature thermistor
Indoor unit MARK DESCRIPTION HEX Heat exchanger TH 11 Heat exchanger (middle) thermistor TH 12 Room temperature thermistor
- (03 - 11) -
3. OUTDOOR UNIT & BRANCH BOX
5. WIRING DIAGRAM 5-1. OUTDOOR UNIT
OUTDOOR UNITS
OUTDOOR UNITS
MODELS : AOU48RLXFZ
- (03 - 12) -
3. OUTDOOR UNIT & BRANCH BOX
5-2. BRANCH BOX
OUTDOOR UNITS
OUTDOOR UNITS
MODEL : UTP-PU03A (Primary)
MODEL : UTP-PU03B (Secondary)
- (03 - 13) -
3. OUTDOOR UNIT & BRANCH BOX
6. OPERATION RANGE Operation mode Cooling / Dry
Heating
Operation range Indoor unit Outdoor unit 64 to 90°F DB 23 to 115°F DB (18 to 32°C DB) (-5 to 46°C DB) R.H. 80% or less 60 to 88°F DB 5 to 75°F DB (16 to 31°C DB)
(-15 to 24°C DB)
OUTDOOR UNITS
OUTDOOR UNITS
R.H. : Relative Humidity.
- (03 - 14) -
3. OUTDOOR UNIT & BRANCH BOX
7. NOISE LEVEL CURVE MODEL : AOU48RLXFZ Heating
Cooling 80
80
70
70
N C -65
60 N C -60
N C -55 50 N C -50
N C -45 40 N C -40
N C -35 30 N C -30
N C -25 20 N C -20
60 N C -60
N C -55 50 N C -50
N C -45 40 N C -40
N C -35 30 N C -30
N C -25 20 N C -20
N C -15
N C -15
10
10
0
0 63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
- (03 - 15) -
3. OUTDOOR UNIT & BRANCH BOX
OUTDOOR UNITS
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
OUTDOOR UNITS
N C -65
SOUND LEVEL CHECK POINT
Air flow
OUTDOOR UNITS
OUTDOOR UNITS
Microphone
39-3/8in. (1 m)
- (03 - 16) -
3. OUTDOOR UNIT & BRANCH BOX
8. ELECTRIC CHARACTERISTICS 8-1. OUTDOOR UNIT Power Supply
Model name
OUTDOOR UNITS
AOU48RLXFZ
Hz
60
Electric Characteristics Full Load Characteristics
Voltage
MCA
TOCA
MSC
(V)
(A)
(A)
(A)
208/230
26.5
45
23.4
Comp
Wiring Specifications *1 MOCP
Power Cable
Earth Cable
MFA
AWG size
AWG size
(A)
Cross-section
Cross-section
40
8
8
resser
Outdoor Fan Motor
Limited Wiring
RLA
Output
FLA
Length*2
(A)
(kW)
(A)
21
0.11
0.9
49/55 (ft.) 15/17 (m)
8-2. BRANCH BOX
Model name UTP-PU03A (Primary) UTP-PU03B (Secondary)
Rated Value Electric Characteristics Power Supply Full Load Characteristics Wiring Specifications *1 Power Cable Earth Cable MOCP Voltage MCA TOCA MFA Hz AWG size AWG size (V) (A) (A) (A) Cross-section Cross-section 60
208/230
3
10
15
14
14
60
208/230
3
10
15
14
14
● Select the breaker based on MOCP of the table above. ● Select the wire size based on the larger value of MCA or MOCP of the table above. *1 Wiring Spec : These values are recommended data. Please select the wiring spec in accordance with local rules. *2 Limited Wiring Length : This wiring length is in case voltage drop less than 2%. When wiring length extend longer, select the wiring size of larger diameter. RLA : Rated Load Amp of compressor under the standard condition. MCA : Min Circuit Amp = Max Operating Current (Full Load) MSC : Max Starting Current TOCA : Total Value of Each Over Current Set MFA : Main Fuse (Circuit Breaker) Current MOCP : Maximum Over Current Protection
- (03 - 17) -
3. OUTDOOR UNIT & BRANCH BOX
OUTDOOR UNITS
Rated Value
9. SAFETY DEVICES 9-1. OUTDOOR UNIT Safety device
Protector
Main PCB
AC 250V 3.15A
INV PCB
DC 400V 5A
Filter
AC 250V 10A AC 250V 3.15A
Filter
AC 500V 50A
OUTDOOR UNITS
Compressor Protector High Pressure Protection Low Pressure Protection
Overcurrent protection Temperature protection Off : 239°F (115°C) On : 158°F (70°C) Off : 609psi (4.2MPa)
On : 464psi (3.2MPa)
Off : 7.25psi (0.05MPa)
9-2. BRANCH BOX Safety device Fuse
UTP-PU03A, UTP-PU03B AC 250V 3.15A x 2 AC 250V 10A x 1
PCB
- (03 - 18) -
3. OUTDOOR UNIT & BRANCH BOX
OUTDOOR UNITS
Fuse
AOU48RLXFZ
Hybrid Flex Inverter System
4. INDOOR UNITS
DTR_BMU001E_05--CHAPTER04 2010.11.12
CONTENTS 4. INDOOR UNITS 1. FEATURES ................................................................................... 04 - 01 1-1. COMPACT CASSETTE TYPE ................................................................ 04 - 01 1-2. SLIM DUCT TYPE................................................................................... 04 - 02 1-3. COMPACT WALL MOUNTED TYPE ..................................................... 04 - 03 1-4. WALL MOUNTED TYPE ........................................................................ 04 - 04
2. SPECIFICATIONS ........................................................................ 04 - 05 2-1. COMPACT CASSETTE TYPE ................................................................ 04 - 05 2-2. SLIM DUCT TYPE................................................................................... 04 - 06 2-3. COMPACT WALL MOUNTED TYPE ...................................................... 04 - 07 2-4. WALL MOUNTED TYPE ......................................................................... 04 - 08
3. ELECTRIC CHARACTERISTICS ................................................. 04 - 09 4. DIMENSIONS ............................................................................... 04 - 10 4-1. COMPACT CASSETTE TYPE ................................................................ 04 - 10 4-2. SLIM DUCT TYPE................................................................................... 04 - 12 4-3. COMPACT WALL MOUNTED TYPE ...................................................... 04 - 17 4-4. WALL MOUNTED TYPE ........................................................................ 04 - 19
5. WIRING DIAGRAMS .................................................................... 04 - 21 5-1. COMPACT CASSETTE TYPE ................................................................ 04 - 21 5-2. SLIM DUCT TYPE................................................................................... 04 - 22 5-3. COMPACT WALL MOUNTED TYPE ...................................................... 04 - 23 5-4. WALL MOUNTED TYPE ......................................................................... 04 - 24
6. AIR VELOCITY AND TEMPERATURE DISTRIBUTIONS ........... 04 - 25 6-1. COMPACT CASSETTE TYPE ................................................................ 04 - 25 6-2. COMPACT WALL MOUNTED TYPE ...................................................... 04 - 31 6-3. WALL MOUNTED TYPE ......................................................................... 04 - 34
7. FAN PERFORMANCE CURVE ..................................................... 04 - 36 7-1. SLIM DUCT TYPE................................................................................... 04 - 36
8. AIR FLOW .................................................................................... 04 - 44
CONTENTS 4. INDOOR UNITS 9. NOISE LEVEL CURVE .................................................................. 04 - 46 9-1. COMPACT CASSETTE TYPE ................................................................ 04 - 46 9-2. SLIM DUCT TYPE................................................................................... 04 - 48 9-3. COMPACT WALL MOUNTED TYPE ...................................................... 04 - 50 9-4. WALL MOUNTED TYPE ......................................................................... 04 - 52 9-5. SOUND LEVEL CHECK POINT ............................................................. 04 - 53
10.
SAFETY DEVICES ................................................................... 04 - 55
1. FEATURES 1-1. COMPACT CASSETTE TYPE MODELS : AUU9RLF, AUU12RLF, AUU18RLF
FEATURES
Quiet quality
High efficiency design by 2 stage structure Wind velocity
INDOOR UNITS
Fast
Previous turbo fan
2-stage turbo fan
In the case of a conventional fan, the air outlet range was narrow as the airflow moved to the motor side which meant the velocity of air passing through the heat exchanger was uneven.
A evenly spread air distribution across the heat exchanger is possible due to the new 2 stage turbo fan which produces two separate airflow streams. 1-stage
Optimization of wing form (laminar wing type) and wing number (7 blades each) Designed by CFD-analysis (fluid) simulations Laminar wing
Quiet
Airflow runs through smoothly along the laminar wing
INDOOR UNITS
2-stage turbo fan
+
2-stage 2 stage
Slow
No airflow separation
Heat exchange efficiency:
Quiet Adoption of laminar wing
20%UP Spin direction
Airflow direction
Easy maintenance 1Maintenance of fan motor and fan Maintenance of the fan motor and fan can be done easily after taking off the panel as the bell mouth of the fan can be removed easily. A : Fan motor B : 2-stage turbo fan 1 C : Bell-mouth D : Panel A
2Long life filter
B C
: standard equipment
3Adaptation of transparent drainage parts During installation, maintenance and operation, the drain pump and kit can be checked easily.
D
3
2
Grille cover
Compact design Easy installation by taking off ceiling panel of 23-5/8in. x 23-5/8in.(600mm x 600mm) size 22-7/16in. (570mm) 22-7/16in. (570mm)
High lift drain pump
27-9/16in. (700mm)
- (04 - 01) -
4. INDOOR UNITS
1-2. SLIM DUCT TYPE MODELS : ARU9RLF, ARU12RLF, ARU18RLF, ARU24RLF
Slim design and wide range of static pressure for flexible installation.
FEATURES Slim design
Flexible installation
This model is slim design, it can install at the place where a ceiling is narrow.
Ceiling concealed
INDOOR UNITS
INDOOR UNITS
Drain port Height
7-25/32 in. (198mm)
Drain pump
Drain pump built-in
Wall concealed
Compact design Condensate lift-up to 33-15/32in. (850mm)
Max. 33-15/32 in. (850mm) Drain hose is standard accessory
Selectable with a wide range of static pressure
Filter (Accessory) Filter (ARU09/12/18: 2pcs.) ARU24: 3pcs.)
Static pressure range
By using DC fan motor, it is possible to change of static pressure range 0 to 0.36in. WG (0 to 90Pa). The change of static pressure range is possible by remote controller. [in.WG (P a)] 0.36 (90)
0 A ir flow rate
[CFM (m3/h)]
*24 model is 0 to 0.20in.WG (0 to 50Pa)
Air - intake Air intake direction can be selected to match the installation site.
Bottom side
Back side
- (04 - 02) -
4. INDOOR UNITS
1-3. COMPACT WALL MOUNTED TYPE MODELS : ASU7RLF, ASU9RLF, ASU12RLF Compact and Stylish design indoor unit
FEATURES High density heat transfer tube arrangement Ø5
Making the tube Thin:
7mm→5mm
Easy maintenance Removable & washable panel
Volume reduction of heat exchanger:
Dry operation
30%
Dry operation removes moisture and keeps the air conditioner clean.
Improved the heat exchanger effectiveness
Filter features Long-life* Ion deodorization filter The filter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra-fine particle ceramic. *The filter can be used for approx. 3 years if it is washed under water to restore it's surface action when it is dirty.
Apple-catechin filter
Quiet operation
INDOOR UNITS
INDOOR UNITS
Even temperature
Cooling mode (07/09/12 TYPE) Fan speed
Noise level
Quiet
25dB(A)
Auto swing louvre The Auto Swing Louvre function ensures that the air direction corresponds to the mode selected.
Step
Fine dust, invisible mold spores, and harmful microorganisms are absorbed onto the filter by static electricity, and further growth is inhibited and deactivated by the polyphenol ingredient extracted from apples.
Swing
Deodorizing effect (Odor reduction rate) (ppm) 160 120 80 40 0 0
Ammonia With no filter New filter 30
60
120 (min.)
(ppm) 160 120 80 40 0 0
Trimethylamine With no filter
Swing (Cooling)
New filter
30
60
120 (min.)
Swing (Heating) (ppm) 160 120 80 40 0 0
Hydrogen sulfate With no filter New filter
Testing organization : Environmental Sanitary Inspection Center
Wired control compatible
Test method : Deodorization Test
* 30
60
120 (min.)
Wired and wireless remote controller are acceptable. SET TEMP.
START/STOP
* Optional communication kit is neccesary for the installation.
Wired remote controller
- (04 - 03) -
Simple remote controller
4. INDOOR UNITS
1-4. WALL MOUNTED TYPE MODELS : ASU18RLF, ASU24RLF Simple & Elegant Appearance Design
FEATURES Compact & Slim design
39-9/32in. (998 mm)
“ Vertical airflow” provides powerful floor level heating ft.(m) 7 (2.1)
16
(24/30)
0 10 (3)
46
o
Outside Outsid de air condition conditions: 35.6oF (2o C) 60% Operation contents: Heating Opera Set te temperature (Max set temp) 86oF (30oC), Air flow Hi Vertical flap : Downward Horizontal flap : Center
20 (6)
92
90
88
86
33
32
31
30
30 (9)
40 (12) ft.(m)
84 (oF) 29 (oC)
Power diffuser (full open)
“ Horizontal airflow” does not blow cool air directly at the occupants in the room ft.(m) 7 (2.1)
3 (1)
0 10 (3) Power diffuser
Outside air conditions: 95oF (35oC) 40% Operation contents: Cooling Set temperature (Min set temp) 64oF (18oC), Air flow Hi Vertical flap : Upward Horizontal flap : Center
20 (6)
58
60
62
64 (oF)
15
16
17
18 (oC)
Air conditioner filter features Ion Deodorization Filter Organic coating fin used heat exchanger
Apple-catechin Filter Pre Filter
30 (9)
40 (12) ft.(m)
Long-life* Ion deodorization filter The filter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra-fine-particle ceramic. (*The filter can be used for approx. 3 years if it is washed under water to restore its surface action when it is dirty.) 䚷䚷䚷
ὺᴾ
Using different filters at both sides
Antibacterial deodorizing pre-filter with special ceramic powder
Apple-catechin filter
Easy maintenance Simplification of drain pan cleaning improves maintenance-ability.
Fine dust, invisible mold spores, and harmful microorganisms are absorbed onto the filter by static electricity, and further growth is inhibited and deactivated by the polyphenol extracted from apples.
- (04 - 04) -
4. INDOOR UNITS
INDOOR UNITS
INDOOR UNITS
3 (1)
2. SPECIFICATIONS 2-1. COMPACT CASSETTE TYPE AUU9RLF
Btu/h kW Btu/h kW pints/h(l/h) W A
Cooling Rated Capacity Heating Rated Moisture removal Power consumption Running current Cooling
Fan
Airflow rate Heating
High Med Low Quiet High Med Low Quiet
INDOOR UNITS
Fan Type × Q'ty Fan Motor Output Cooling Sound pressure level Heating
W High Med Low Quiet High Med Low Quiet
Dimension (H×W×D) Heat exchanger
Enclosure
Dimensions ( H×W×D )
Fin pitch Rows × Stages Pipe type Fin Type Material
Net Gross Net Gross
Drain pipe
dB(A)
in. (mm) FPI
Color
Weight
Connection pipe
CFM (m3/h)
Size
Unit Panel Unit Panel Unit Panel Unit Panel Liquid Gas
in.(mm)
lb. (kg)
in.(mm)
Method Material size
Operation range
in. Cooling Heating
Remote controller type
°F (°C) %RH °F (°C)
AUU12RLF AUU18RLF 1ø 208/230V 60Hz 187-264V 9,000 12,000 18,000 2.64 3.51 5.28 10,200 13,500 20,000 3.00 3.96 5.85 2.5 (1.2) 3.2 (1.5) 4.2 (2.0) 18 23 39 0.15 0.19 0.30 318 (540) 359 (610) 441 (750) 288 (490) 312 (530) 359 (610) 259 (440) 277 (470) 306 (520) 230 (390) 241 (410) 241 (410) 318 (540) 359 (610) 471 (800) 288 (490) 312 (530) 418 (710) 259 (440) 277 (470) 353 (600) 230 (390) 241 (410) 265 (450) Turbo × 1 42 42 42 33 37 42 31 33 37 29 31 33 27 28 29 34 37 44 32 33 40 29 31 37 27 28 30 8-9/32 × 51-9/16 × 17/32 + 8-9/32 × 49-7/32 × 17/32 (210×1310×13.3 + 210×1250×13.3) 21 2×10 Copper tube Aluminium PS White (Approximate color of Mansell N9.25 /) 9-21/32 × 22-7/16 × 22-7/16 (245×570×570) 1-15/16 × 27-9/16 × 27-9/16 (49 × 700 × 700) 10-7/16 × 28-3/4 × 24-19/32 (265×730×625) 4-23/32 × 30-1/8 × 29-23/32 (120 × 765 × 755) 33 (15) 5.7(2.6) 40 (18) 10(4.5) 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) Flare HARD PVC Outer Diameter : 1-1/16 Inner Diameter : 3/4 64 to 90 (18 to 32) 80 or less 60 to 88 (16 to 31) Wired [Wireless(option)]
Note : Specifications are based on the following conditions. Power source of specifications : 230V Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].
- (04 - 05) -
4. INDOOR UNITS
INDOOR UNITS
Model name Power source Available voltage range
2-2. SLIM DUCT TYPE ARU9RLF
Cooling Rated Capacity Heating Rated
INDOOR UNITS
Moisture removal Power consumption Running current High Med Cooling Low Quiet Airflow rate High Fan Med Heating Low Quiet Fan type ×Q'ty Fan motor output Recommended static pressure High Med Cooling Low Quiet Sound pressure level High Med Heating Low Quiet Dimension (H×W×D) Heat exchanger
Enclosure
Fin pitch Rows × Stages Pipe type Fin Type Material Color
Btu/h kW Btu/h kW pints/h(l/h) W A
CFM (m3/h)
W in.WG(Pa)
dB(A)
in (mm) FPI
Net Dimensions ( H×W ×D )
in. (mm) Gross
Weight Connection pipe
Drain pipe
Net Gross Size
lb. (kg) Liquid Gas
in. (mm)
Method Material size
Operation range
in. Cooling Heating
Remote controller type
°F (°C) %RH °F (°C)
ARU12RLF ARU18RLF ARU24RLF 1ø 208/230V 60Hz 187-264V 9,000 12,000 18,000 24,000 2.64 3.51 5.28 7.02 10,200 13,500 20,000 27,000 3.00 3.96 5.85 7.92 2.7 (1.3) 3.8 (1.8) 4.6 (2.2) 5.3 (2.5) 49 58 73 111 0.30 0.35 0.44 0.66 353 (600) 383 (650) 554 (940) 783 (1330) 324 (550) 353 (600) 518 (880) 730 (1240) 294 (500) 324 (550) 483 (820) 648 (1100) 265 (450) 283 (480) 442 (750) 607 (1030) 353 (600) 383 (650) 554 (940) 783 (1330) 324 (550) 353 (600) 518 (880) 730 (1240) 294 (500) 324 (550) 483 (820) 648 (1100) 265 (450) 283 (480) 442 (750) 607 (1030) Sirocco × 2 Sirocco × 3 Sirocco × 4 81 81 96 96 0 to 0.36 (0 to 90) 0 to 0.36 (0 to 90) 0 to 0.36 (0 to 90) 0 to 0.20 (0 to 50) 28 29 32 33 27 28 31 32 26 27 30 30 25 26 29 29 28 29 33 35 26 28 32 34 25 27 31 32 24 24 29 29 11-9/16 × 27-9/16 × 11-9/16 × 35-7/16 × 11-9/16 × 19-11/16 × 1-9/16 1-9/16 1-9/16 (294×500×39.9) (294×900×39.9) (294×700×39.9) 20 3 × 14 Copper tube Aluminium GALVANIZED STEEL SHEET 7-25/32 x 35-7/16 x 7-25/32 x 43-5/16 x 7-25/32 x 27-9/16 x 24-13/32 24-13/32 24-13/32 (198 × 700 × 620) (198 × 900 × 620) (198 × 1100 × 620) 10-7/8 x 53-27/32 x 10-7/8 x 38-1/8 x 29-3/4 10-7/8 x 46 x 29-3/4 29-3/4 (276 × 968 × 756) (276 × 1168 × 756) (276 × 1368 × 756) 41 (19) 50 (23) 59 (27) 58 (26) 67 (30) 75 (34) 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) 5/8 (15.88) Flare HARD PVC Outer Diameter : 1-1/16 Inner Diameter : 3/4 64 to 90 (18 to 32) 80 or less 60 to 88 (16 to 31) Wired [Wireless(option)]
Note : Specifications are based on the following conditions. Power source of specifications : 230V Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Standard static pressure : 0.10in.WG (25Pa) Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].
- (04 - 06) -
4. INDOOR UNITS
INDOOR UNITS
Model name Power source Available voltage range
2-3. COMPACT WALL MOUNTED TYPE
Cooling Rated Capacity Heating Rated
INDOOR UNITS
Moisture removal Power consumption Running current High Med Cooling Low Quiet Airflow rate High Fan Med Heating Low Quiet Fan type × Q'ty Fan motor output High Med Cooling Low Quiet Sound pressure level High Med Heating Low Quiet Dimension (H×W×D) Heat exchanger
Enclosure
Fin pitch Rows × Stages Pipe type Fin Type Material
ASU7RLF
Btu/h kW Btu/h kW pints/h(l/h) W A
CFM (m3/h)
W
dB(A)
in. (mm) FPI
Color
Dimensions Net ( H×W ×D ) Gross Net Weight Gross
in.(mm) lb.(kg)
Liquid Connection Size Gas pipe Method Material Drain pipe size Operation range
Cooling
Heating Remote controller type
in. (mm)
in. (mm) °F (°C) %RH °F (°C)
ASU9RLF ASU12RLF 1ø 208/230V 60Hz 187-264V 7,000 9,000 12,000 2.04 2.64 3.51 8,100 10,200 13,500 2.37 3.00 3.96 1.7 (0.8) 2.7 (1.3) 3.8 (1.8) 15 17 22 0.13 0.15 0.19 330 (560) 353 (600) 388 (660) 294 (500) 306 (520) 330 (560) 253 (430) 253 (430) 265 (450) 200 (340) 200 (340) 200 (340) 330 (560) 353 (600) 388 (660) 294 (500) 306 (520) 330 (560) 253 (430) 253 (430) 277 (470) 206 (350) 206 (350) 206 (350) Cross Flow ×1 30 30 30 36 37 40 32 33 36 29 29 30 25 25 25 36 37 40 32 33 36 29 29 31 25 25 25 Main: 12-19/32 x 24-13/16 x 25/32 (320 x 630 x 20) Sub: 3-5/16 x 24-13/16 x 17/32 (84 x 630 x 13.3) Main: 23, Sub: 18 Main: 2 x 20, Sub: 1 x 4 Copper tube Aluminium Polystyrene White (Approximate color of Mansell N9.25 /) 11-1/16 × 31-1/16 × 8 (280×790×203) 10-3/8 × 33-1/16 × 14-3/4 (263×840×375) 18 (8) 23 (10.5) 1/4 (6.35) 3/8 (9.52) Flare PP + LLDPE Outer Diameter : 5/8 to 21/32 (15.8 to 16.7) Inner Diameter : 17/32 (13.8) 64 to 90 (18 to 32) 80 or less 60 to 88 (16 to 31) Wireless [Wired(option)]
Note : Specifications are based on the following conditions. Power source of specifications : 230V Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].
- (04 - 07) -
4. INDOOR UNITS
INDOOR UNITS
Model name Power source Available voltage range
2-4. WALL MOUNTED TYPE Model name Power source Available voltage range Capacity Heating Rated
INDOOR UNITS
Moisture removal Power consumption Running current High Med Cooling Low Quiet Airflow rate High Fan Med Heating Low Quiet Fan type × Q'ty Fan motor output High Med Cooling Low Quiet Sound pressure level High Med Heating Low Quiet Dimension (H×W×D) Heat exchanger
Enclosure
Fin pitch Rows × Stages Pipe type Fin Type Material
Btu/h kW Btu/h kW pints/h(l/h) W A
CFM (m3/h)
W
dB(A)
in.(mm) FPI
Color
Dimensions Net ( H×W ×D ) Gross Net Weight Gross
mm lb.(kg)
Liquid Connection Size Gas pipe Method Material Drain pipe size Operation range
Cooling
Heating Remote controller type
ASU24RLF 1ø 208/230V 60Hz 187-264V
in.(mm)
in.(mm) °F (°C) %RH °F (°C)
18,000 5.28 20,000 5.85 5.3 (2.5) 41 0.32 542 (920) 436 (740) 365 (620) 324 (550) 542 (920) 436 (740) 365 (620) 324 (550)
24,000 7.02 27,000 7.92 5.9 (2.8) 69 0.53 659 (1120) 530 (900) 436 (740) 365 (620) 647 (1100) 530 (900) 436 (740) 365 (620)
Cross flow ×1 64 64 43 49 37 42 33 37 31 33 44 48 37 42 33 37 31 33 Main:15-7/8 x 33-3/4 x 1-1/16 (378 x 832 x 26.6) Sub:3-5/16 x 33-3/4 x 17/32 (84 x 832 x 13.3) Main:21, Sub:18 Main:2 x 18, Sub:1 x 4 Copper tube Aluminium Polystyrene White (Approximate color of Mansell N9.25 /) 12-5/8 x 39-1/4 x 9 (320×998×228) 12-9/16 x 42-15/16 x 16-7/8 (319×1090×429) 31 (14) 31 (14) 40 (18) 40 (18) 1/4 (6.35) 1/2 (12.7) 5/8 (15.88) Flare PVC Outer diameter : 5/8 (16) Inner diameter : 15/32 (12) 64 to 90 (18 to 32) 80 or less 60 to 88 (16 to 31) Wireless [Wired(option)]
Note : Specifications are based on the following conditions. Power source of specifications : 230V Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].
- (04 - 08) -
4. INDOOR UNITS
INDOOR UNITS
Cooling Rated
ASU18RLF
3. ELECTRIC CHARACTERISTICS Type Compact Wall Mounted Wall Mounted Compact Cassette
ASU7RLF ASU9RLF ASU12RLF ASU18RLF ASU24RLF AUU9RLF AUU12RLF AUU18RLF ARU9RLF ARU12RLF ARU18RLF ARU24RLF
60 60 60 60 60 60 60 60 60 60 60 60
Indoor Rated Input Power FLA (W) (A) 15 / 15 0.14 / 0.13 17 / 17 0.16 / 0.15 22 / 22 0.20 / 0.19 40 / 41 0.34 / 0.32 68 / 69 0.57 / 0.53 17 / 18 0.15 / 0.15 22 / 23 0.19 / 0.19 38 / 39 0.32 / 0.30 47 / 49 0.32 / 0.30 56 / 58 0.37 / 0.35 71 / 73 0.47 / 0.44 109 / 111 0.71 / 0.66
INDOOR UNITS
Hz
MCA (A) 0.18 / 0.17 0.20 / 0.19 0.25 / 0.24 0.42 / 0.40 0.71 / 0.66 0.19 / 0.19 0.24 / 0.24 0.41 / 0.38 0.40 / 0.38 0.47 / 0.44 0.59 / 0.55 0.89 / 0.83
INDOOR UNITS
Slim Duct
Model name
Power Supply Voltage (V) 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230
MCA : Min Circuit Amps = Max Operating Current (Full Load). MFA : Main Fuse (Circuit breaker) Amps.
- (04 - 09) -
4. INDOOR UNITS
4. DIMENSIONS 4-1. COMPACT CASSETTE TYPE MODELS : AUU9RLF, AUU12RLF, AUU18RLF Unit : in. (mm)
• Decoration panel mounting state
□ 22-27/32 to 26 (580 to 660) : Ceiling openings
5-29/32 to 7-7/8 (150 to 200)
INDOOR UNITS
Top view
Maintenance space
Be sure to leave maintenance space for future service at the designated position.
27-9/16 (700)
1-3/16 (30) 2-9/32 (58)
Ceiling
Side view
4-27/32 (123)
Control box
10-5/16 (262)
4-1/32 (102) Drain port
1-3/16 (30)
8-15/32 (215)
1-3/16 (30)
1-3/16 (30)
(Drain hose)
1-15/16 (49)
4-1/4 (108)
5-3/4 (146)
9-21/32 (245)
3-29/32 (99)
4-1/2 (114)
Min. 17-23/32 (450) Drain port 4-1/32 (102) 1-9/16 (40)
Side view 27-9/16 (700)
Bottom view
1 2 3
Refrigerant pipe flare connection Drain hose connection
Liquid Gas Drain hose
AUU9RLF, AUU12RLF AUU18RLF ø 1/4 in. (6.35 mm) ø 1/4 in. (6.35 mm) ø 3/8 in. (9.52 mm) ø 1/2 in. (12.70 mm) I.D. 3/4 in. , O.D. 1-1/16 in. - (04 - 10) -
4. INDOOR UNITS
INDOOR UNITS
9-27/32 (250) Min. 17-23/32 (450)
5-5/16 (135)
□ 22-7/16 (570): Indoor unit
21-1/4 (540): Hanging bolt position
2-15/16 (75)
20-7/8 (530): Hanging bolt position
INSTALLATION PLACE Unit : in. (mm)
Strong and durable ceiling
10-5/16 (262) or more
H
39-3/8 (1000) or more
39-3/8 (1000) or more
94-1/2 (2400) or more
INDOOR UNITS
INDOOR UNITS
Obstruction Floor
Model name Standard mode High Ceiling mode
H (The maximum height from floor to ceiling) Unit: in. (mm) AUU9 AUU12 AUU18 106-5/16 106-5/16 106-5/16 (2700) (2700) (2700) -
118-1/8
118-1/8
(3000)
(3000)
3-way directions setting
* 3-15/16 (100) or more
To set “3-way directions”, the air outlet shutter plate (UTR-YDZB) sold separately must be installed and “outlet-direction” switched to “3-way” by remote controller. *When installing the indoor unit, be careful about the maintenance space. - (04 - 11) -
4. INDOOR UNITS
4-2. SLIM DUCT TYPE MODELS : ARU9RLF, ARU12RLF
2 (51)
6 (152)
6-27/32 (174)
22-19/32 (574)
Unit : in. (mm)
View A
2-25/32 (71)
Rear view
1-3/16 (30)
1-27/32 (47)
25-19/32 (650)
2-5/32 (55)
28-29/32 (734)
3-1/16 (78)
3-1/2 (89) 1-7/8 (48)
4-11/16 (119)
3-7/32 (82)
6-9/16 (167)
Side view
2-5/32 (55)
1-11/16 (43)
3-1/16 (78)
5-15/16 (151)
6-5/8 (168)
7-25/32 (198)
Top view
25/32 (20) 25-19/32 (650) 26-5/32 (664) 27-9/16 (700)
Front view Bottom view
1 2 3
Refrigerant pipe flare connection Drain hose connection
ARU9, ARU12 ø 1/4 in. (6.35 mm) ø 3/8 in. (9.52 mm) I.D. 3/4 in. , O.D. 1-1/16 in.
Liquid Gas Drain hose
- (04 - 12) -
4. INDOOR UNITS
INDOOR UNITS
24-13/32 (620)
14-19/32 (371)
10-13/32 (264)
2-23/32 (69)
13/32 (10) 3-15/16 (100) x 6 = 23-5/8 (600)
5-21/32 (144)
Drain port
INDOOR UNITS
14-27/32 (377)
(Drain hose)
MODELS : ARU18RLF
2-25/32 (71)
6 (152)
2 (51)
6-27/32 (174)
30-15/32 (774)
Unit : in. (mm)
Rear view
1-3/16 (30)
View A
(Drain hose)
2-5/32 (55)
3-1/16 (78)
3-7/16 (87) 2-7/32 (56)
3-1/16 (78) 2-5/32 (55)
5-15/16 (151)
Top view
6-5/8 (168)
4-11/16 (119) 6-9/16 (167)
Side view
1-11/16 (43)
25/32 (20) 33-15/32 (850) 34-1/32 (864) 35-7/16 (900)
Front view
Bottom view
1 2 3
Refrigerant pipe flare connection Drain hose connection
ARU18 ø 1/4 in. (6.35 mm) ø 1/2 in. (12.70 mm) I.D. 3/4 in. , O.D. 1-1/16 in.
Liquid Gas Drain hose
- (04 - 13) -
4. INDOOR UNITS
INDOOR UNITS
24-13/32 (620)
14-19/32 (371)
3-1/2 (89)
36-25/32 (934)
7-25/32 (198)
10-13/32 (264)
1-27/32 (47)
33-15/32 (850)
5-21/32 (144)
3-15/16 (100) x 8 = 31-1/2 (800)
2-23/32 (69)
13/32 (10)
INDOOR UNITS
14-27/32 (377)
Drain port
MODELS : ARU24RLF
2 (51)
6 (152)
6-27/32 (174)
2-25/32 (71)
38-11/32 (974)
Unit : in. (mm)
View A
1-3/16 (30)
Rear view
14-27/32 (377)
(Drain hose)
3-15/16 (100) x 10 = 39-3/8 (1000)
2-5/32 (55)
3-7/16 (87)
4-11/16 (119)
2-7/32 (56)
6-9/16 (167)
Side view
1-11/16 (43)
25/32 (20) 43-5/16 (1100)
Front view
Bottom view
1 2 3
Refrigerant pipe flare connection Drain hose connection
ARU24 ø 1/4 in. (6.35 mm) ø 5/8 in. (15.88 mm) I.D. 3/4 in. , O.D. 1-1/16 in.
Liquid Gas Drain hose
- (04 - 14) -
4. INDOOR UNITS
INDOOR UNITS
24-13/32 (620)
14-19/32 (371)
3-1/16 (78)
3-1/2 (89)
Top view
2-5/32 (55) 3-1/16 (78)
5-15/16 (151)
44-21/32 (1134)
6-5/8 (168)
5-21/32 (144)
1-27/32 (47)
41-11/32 (1050)
7-25/32 (198)
10-13/32 (264)
INDOOR UNITS
13/32 (10)
2-23/32 (69)
Drain port
Unit : in. (mm)
INSTALLATION PLACE 11-13/16 (300) or more 9-7/16 (240) or more
Strong and durable ceiling
Right side
25/32 (20) or more
11-13/16 (300) or more
3-15/16 (100) or more
Service access
Ceiling
(When no ceiling)
Left side
25/32 (20) or more
98-7/16 (2500) or more
Indoor unit
13/32 (10) or less
13/32 (10) or less
Left side
INDOOR UNITS
INDOOR UNITS
Floor
Right side (PIPE side)
Grill
Inlet air
5-29/32 (150)
or more 3-15/16 (100) or more
Strong and durable floor
5-29/32 (150) or more
Strong and durable floor 11-13/16 (300) or more
25/32 (20) or more
Dact
Right side (PIPE side)
Left side
25/32 (20) or more
Grill
Inlet air
5-29/32 (150) or more 3-15/16 (100) or more
Strong and durable floor
5-29/32 (150) or more
Strong and durable floor
11-13/16 (300) or more
- (04 - 15) -
25/32 (20) or more
25/32 (20) or more
4. INDOOR UNITS
Unit : in. (mm)
MAINTENANCE SPACE Provide a service access for inspection purposes as shown below. Do not place any wiring or illumination in the service space, as they will impede service.
Service access
Unit
3-15/16 (100) or more
11-13/16 (300) or more
Control box
11-13/16 (300) or more INDOOR UNITS
INDOOR UNITS
Service space
- (04 - 16) -
4. INDOOR UNITS
4-3. COMPACT WALL MOUNTED TYPE MODELS : ASU7RLF, ASU9RLF, ASU12RLF Unit : in. (mm) 8-1/16 (205) : Installed state 31-3/32 (790)
11-1/32 (280)
8 (203)
7-1/4 (184)
23/32 (18)
2-7/16 (62)
9-11/32 (237) 12-23/32 (323)
1-27/32 (47)
3-7/32 (82)
2-1/16 (52)
8-7/32 (209) 12-7/8 (327)
3-1/16 (78)
13-29/32 (353): Gas pipe ø2-9/16 (65) for pipe inlet
16-11/32 (415): Liquid pipe
ø2-9/16 (65) for pipe inlet
1 2
Refrigerant pipe flare connection
Liquid Gas
ASU7RLF, ASU9RLF, ASU12RLF ø 1/4 in. (6.35 mm) ø 3/8 in. (9.52 mm)
3
Drain hose connection
Drain hose
I.D. 17/32 in. (13.8 mm), O.D. 5/8 to 21/32 in. (15.8 to 16.7 mm) Drain hose : L=20-15/32 in. (520mm)
- (04 - 17) -
4. INDOOR UNITS
INDOOR UNITS
3-11/16 (94)
17-23/32 (450)
8-15/32 (215)
Outline of unit
23/32 (18)
*1: Vertical flap is downward
1-27/32 (47)
INDOOR UNITS
5-23/32 (145) *1
13/32 (10) *1
5-1/2 (140) *1
INSTALLATION PLACE 2-15/32 (63) or more
1-25/32 (45) or more
Unit : in. (mm)
1-7/8 (48) or more
2-3/4 (70) or more
3-15/16 (100) or more
59-1/16 (1500) or more
- (04 - 18) -
4. INDOOR UNITS
INDOOR UNITS
2-1/16 (52) or more
70-7/8 (1800) or more
INDOOR UNITS
Outline of unit
4-4. WALL MOUNTED TYPE MODELS : ASU18RLF, ASU24RLF Unit : in. (mm)
12-19/32 (320)
39-9/32 (998)
20-15/32 (520) 23-7/32 (590) 28-3/8 (721)
8-31/32 (228)
INDOOR UNITS
ø1-1/4 (32) ø5/8 (16) ø15/32 (12)
20-15/32 (520)
2-15/16 (75)
15-3/4 (400)
9-9/16 (243)
4-7/16 (113)
6-11/16 (170) 5-1/8 (130) 2-15/16 (75)
4-13/16 (122) 6-25/32 (172)
5-1/4 (133) 4-31/32 (126)
23/32 x 7/16 (18 x 11) hole 1-1/32 x 7/16 (26 x 11) hole 13/16 x 6/32 (21 x 5): 14holes
1-6/32 (30)
10-19/32 (269)
6/32 x 23/32 (5 x 18): 14holes
15-1/4 (387)
1-23/32 (44) 5-7/8 (149) 7-3/4 (197) 10-23/32 (272)
23/32 x 7/16 (18 x 11) hole
5/8 (16)
1/2 (13)
1-1/32 x 7/16 (26 x 11) hole
25/32 (20) Unit center 17-9/32 (439)
15/32 (12)
1-15/32 (37)
12-19/32 (320): Unit size
INDOOR UNITS
1 (25)
1-6/32 (30) ø3-5/32 (80) hole Piping inlet
17-1/4 (438)
15-5/8 (397) 39-3/8 (1000): Unit size
6/32 x 1-31/32 (5 x 50): 3holes ø6/32 (5): 65holes for tapping screw
1 2
Refrigerant pipe flare connection
Liquid Gas
3
Drain hose connection
Drain hose
ø3-5/32 (80) hole Piping inlet 1/2 x 6/32 (13 x 5): 4holes
ASU18RLF ASU24RLF ø 1/4 in. (6.35 mm) ø 1/4 in. (6.35 mm) ø 1/2 in. (12.70 mm) ø 5/8 in. (15.88 mm) I.D. 15/32 in. (12 mm) , O.D. 5/8 in. (16 mm) Drain hose : L=26-3/8 in. (670mm)
- (04 - 19) -
4. INDOOR UNITS
INSTALLATION PLACE
3-5/32 (80) or more
2-15/32 (63) or more
Unit : in. (mm)
2-3/32 (53) or more
3-5/32 (80) or more
4-23/32 (120) or more
59-1/16 (1500) or more
- (04 - 20) -
4. INDOOR UNITS
INDOOR UNITS
2-1/16 (52) or more
70-7/8 (1800) or more
INDOOR UNITS
Outline of unit
5. WIRING DIAGRAMS 5-1. COMPACT CASSETTE TYPE
INDOOR UNITS
INDOOR UNITS
MODELS : AUU9RLF, AUU12RLF, AUU18RLF
- (04 - 21) -
4. INDOOR UNITS
5-2. SLIM DUCT TYPE
INDOOR UNITS
INDOOR UNITS
MODELS : ARU9RLF, ARU12RLF, ARU18RLF, ARU24RLF
- (04 - 22) -
4. INDOOR UNITS
5-3. COMPACT WALL MOUNTED TYPE
INDOOR UNITS
INDOOR UNITS
MODELS : ASU7RLF, ASU9RLF, ASU12RLF
- (04 - 23) -
4. INDOOR UNITS
5-4. WALL MOUNTED TYPE
INDOOR UNITS
INDOOR UNITS
MODELS : ASU18RLF, ASU24RLF
- (04 - 24) -
4. INDOOR UNITS
6. AIR VELOCITY AND TEMPERATURE DISTRIBUTIONS 6-1. COMPACT CASSETTE TYPE Conditions
Fan speed : High Operation mode : FAN
MODEL : AUU9RLF Air velocity distribution Top view Vertical flap : Up (ft.) (m) 13
4
10
3
7
2
3
1
Unit : ft./s (m/s)
1 (0.25)
2 (0.5)
7 (2.0)
0
2 (0.5)
0
1 (0.25)
2 (0.5)
1 (0.25)
7 (2.0)
7 (2.0)
3 (1.0) 3
3 (1.0)
7 (2.0)
INDOOR UNITS
INDOOR UNITS
3 (1.0)
1
3 (1.0)
7
2
2 (0.5)
10
3
1 (0.25)
13
4 4
3
2
1
0
1
2
3
4
(m)
13
10
7
3
0
3
7
10
13
(ft.)
Side view Vertical flap : Up (ft.) (m) 9
Unit : ft./s (m/s)
2.7
7 (2.0) 7
2
3 (1.0) 2 (0.5)
3
1
0
0
2 (0.5)
1 (0.25)
1 (0.25)
4
3
2
1
0
1
2
3
4
(m)
13
10
7
3
0
3
7
10
13
(ft.)
- (04 - 25) -
4. INDOOR UNITS
Note: Reference data Conditions Fan speed : High Operation mode : Heating Vertical flap: Downward (4Way)
Air velocity distribution Side view Vertical flap : Down (ft.) (m) 2.7
8
2.5
7
2
Unit : ft./s (m/s)
7 (2.0)
7 (2.0)
5 (1.5)
5 (1.5)
3 (1.0)
3 (1.0)
2 (0.5)
2 (0.5)
1 (0.25) 1
0
0
INDOOR UNITS
3
4 13
3
2
10
7
1 (0.25)
1 3
0 0
1 3
2
3
7
10
4
(m)
13
(ft.)
Air temperature distribution Side view Vertical flap : Down (ft.) (m) 9
2.7
8
2.5
7
2
Unit : °F (°C)
86 (30)
86 (30)
82 (28)
82 (28)
79 (26)
79 (26)
75 (24) 3
75 (24)
1
72 (22)
0
72 (22)
0 4 13
3 10
2 7
1 3
0 0
- (04 - 26) -
1 3
2 7
3 10
4
(m)
13
(ft.)
4. INDOOR UNITS
INDOOR UNITS
9
Conditions Fan speed : High Operation mode : FAN
MODEL : AUU12RLF Air velocity distribution Top view Vertical flap : Up (ft.) (m) 13
Unit : ft./s (m/s)
4
1 (0.25)
10
3
7
2
3
1
2 (0.5)
7 (2.0)
0
0
3 (1.0)
7 (2.0)
2 (0.5)
INDOOR UNITS
INDOOR UNITS
3 (1.0)
1 (0.25)
2 (0.5)
1 (0.25)
7 (2.0)
7 (2.0)
3 (1.0) 3
1
3 (1.0)
2 (0.5) 7
2
10
3
1 (0.25) 13
4 4
3
2
1
0
1
2
3
4
(m)
13
10
7
3
0
3
7
10
13
(ft.)
Side view Vertical flap : Up (ft.) (m) 9
2.7
7
2
Unit : ft./s (m/s)
7 (2.0) 3 (1.0) 2 (0.5)
2 (0.5) 3
1
1 (0.25)
0
1 (0.25)
0 4
3
2
1
0
1
2
3
4
(m)
13
10
7
3
0
3
7
10
13
(ft.)
- (04 - 27) -
4. INDOOR UNITS
Note: Reference data Conditions Fan speed : High Operation mode : Heating Vertical flap: Downward (4Way)
Air velocity distribution (ft.) (m) 9
2.7
8
2.5
7
2
Unit : ft./s (m/s)
5 (1.5)
5 (1.5)
3 (1.0)
3 (1.0)
2 (0.5) 3
2 (0.5)
1
1 (0.25)
0 4
3
2
1
0
1
2
3
4
(m)
13
10
7
3
0
3
7
10
13
(ft.)
INDOOR UNITS
INDOOR UNITS
0
1 (0.25)
Air temperature distribution (ft.) (m) 9
2.7
8
2.5
7
2
Unit : °F (°C)
86 (30)
86 (30)
82 (28)
82 (28)
79 (26)
79 (26)
75 (24) 3
75 (24)
1
72 (22)
0
72 (22)
0 4
3
2
1
0
1
2
3
4
(m)
13
10
7
3
0
3
7
10
13
(ft.)
- (04 - 28) -
4. INDOOR UNITS
Conditions Fan speed : High Operation mode : FAN
MODEL : AUU18RLF Air velocity distribution Top view Vertical flap : Up (ft.) (m) 13
Unit : ft./s (m/s)
4
1 (0.25)
10
3
7
2
2 (0.5)
3
INDOOR UNITS
INDOOR UNITS
3 (1.0) 1
7 (2.0)
7 (2.0) 1 (0.25)
0
2 (0.5)
0
3 (1.0)
1 (0.25) 3
3 (1.0)
7 (2.0)
2 (0.5)
7 (2.0)
1
3 (1.0)
7
2
2 (0.5)
10
3
1 (0.25) 13
4 4
3
2
1
0
1
2
3
4
(m)
13
10
7
3
0
3
7
10
13
(ft.)
Side view Vertical flap : Up (ft.) (m) 9
Unit : ft./s (m/s)
2.7
7 (2.0) 7
2
3 (1.0)
2 (0.5) 2 (0.5) 3
1
1 (0.25)
1 (0.25)
0
0 4
3
2
1
0
1
2
3
4
(m)
13
10
7
3
0
3
7
10
13
(ft.)
- (04 - 29) -
4. INDOOR UNITS
Note: Reference data Conditions Fan speed : High Operation mode : Heating Vertical flap: Downward (4Way)
Air velocity distribution (ft.) (m) 9
2.7
8
2.5
7
2
Unit : ft./s (m/s)
7 (2.0)
7 (2.0)
5 (1.5)
5 (1.5)
3 (1.0)
3 (1.0)
2 (0.5) 3
2 (0.5)
1
1 (0.25)
0 4
3
2
1
0
1
2
3
4
(m)
13
10
7
3
0
3
7
10
13
(ft.)
INDOOR UNITS
INDOOR UNITS
0
1 (0.25)
Air temperature distribution (ft.) (m) 9
2.7
8
2.5
7
2
Unit : °F (°C)
86 (30)
86 (30)
82 (28)
82 (28)
79 (26) 3
0
1
79 (26)
75 (24)
75 (24)
72 (22)
72 (22)
0 4
3
2
1
0
1
2
3
4
(m)
13
10
7
3
0
3
7
10
13
(ft.)
- (04 - 30) -
4. INDOOR UNITS
6-2. COMPACT WALL MOUNTED TYPE Conditions Fan speed : High Operation mode : Fan
MODELS : ASU7RLF
Unit : ft./s (m/s)
(ft.) (m)
Top view Vertical flap : Up Horizontal flap : Center
7
2
3
1
0
0
3
1
7
2
2 (0.5)
3 (1.0)
7 (2.0)
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
10
3
7
2
3
1
INDOOR UNITS
INDOOR UNITS
(ft.) (m)
7 (2.0)
Top view Vertical flap : Up Horizontal flap : Right & Left
2 (0.5)
3 (1.0) 0
0
3 (1.0) 3
1
7
2
10
3
2 (0.5)
7 (2.0)
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
(ft.) (m)
Side view Vertical flap : Up Horizontal flap : Center
10
3
7
2
3
1
0
0
3 (1.0)
2 (0.5)
7 (2.0)
0
1
2
3
4
5
6
7
8
(m)
0
3
7
10
13
16
20
23
26
(ft.)
(ft.) (m)
Side view Vertical flap : Down Horizontal flap : Center
10
3
7
2
3
1
7 (2.0) 3 (1.0) 2 (0.5)
0
0 0
1
2
3
4
5
6
7
8
(m)
0
3
7
10
13
16
20
23
26
(ft.)
- (04 - 31) -
4. INDOOR UNITS
Conditions Fan speed : High Operation mode : Fan
MODELS : ASU9RLF
Unit : ft./s (m/s)
(ft.) (m)
Top view Vertical flap : Up Horizontal flap : Center
7
2
3
1
0
0
3
1
7
2
3 (1.0)
7 (2.0)
2 (0.5)
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
Top view Vertical flap : Up Horizontal flap : Right & Left
10
3
7
2
3
1
0
0
INDOOR UNITS
INDOOR UNITS
(ft.) (m)
7 (2.0) 2 (0.5)
3 (1.0)
2 (0.5)
3 (1.0) 3
1
7
2
10
3
7 (2.0)
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
(ft.) (m)
Side view Vertical flap : Up Horizontal flap : Center
10
3
7
2
3
1
0
0
3 (1.0)
7 (2.0)
2 (0.5)
0
1
2
3
4
5
6
7
8
(m)
0
3
7
10
13
16
20
23
26
(ft.)
(ft.) (m)
Side view Vertical flap : Down Horizontal flap : Center
10
3
7
2
3
1
7 (2.0) 3 (1.0) 2 (0.5)
0
0 0
1
2
3
4
5
6
7
8
(m)
0
3
7
10
13
16
20
23
26
(ft.)
- (04 - 32) -
4. INDOOR UNITS
Conditions Fan speed : High Operation mode : Fan
MODELS : ASU12RLF
Unit : ft./s (m/s)
(ft.) (m)
Top view Vertical flap : Up Horizontal flap : Center
7
2
3
1
0
0
3
1
7
2
3 (1.0)
7 (2.0)
2 (0.5)
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
Top view Vertical flap : Up Horizontal flap : Right & Left
10
3
7
2
3
1
0
0
INDOOR UNITS
INDOOR UNITS
(ft.) (m)
7 (2.0) 2 (0.5)
3 (1.0) 3 (1.0) 3
1
7
2
10
3
2 (0.5)
7 (2.0)
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
(ft.) (m)
Side view Vertical flap : Up Horizontal flap : Center
10
3
7
2
3
1
0
0
3 (1.0) 7 (2.0)
2 (0.5)
0
1
2
3
4
5
6
7
8
(m)
0
3
7
10
13
16
20
23
26
(ft.)
(ft.) (m)
Side view Vertical flap : Down Horizontal flap : Center
10
3
7
2
3
1
7 (2.0)
3 (1.0) 2 (0.5)
0
0 0
1
2
3
4
5
6
7
8
(m)
0
3
7
10
13
16
20
23
26
(ft.)
- (04 - 33) -
4. INDOOR UNITS
6-3. WALL MOUNTED TYPE Conditions Fan speed : High Operation mode : Fan
MODEL : ASU18RLF (ft.) (m)
Top view Vertical flap : Up Horizontal flap : Center
7
2
3
1
0
0
3
1
7
2
Unit : ft./s (m/s)
3 (1.0)
7 (2.0)
2 (0.5)
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
3
7
2
3
1
0
0
3
1
Unit : ft./s (m/s)
INDOOR UNITS
INDOOR UNITS
(ft.) (m) 10
2 (0.5)
7 (2.0)
Top view Vertical flap : Up Horizontal flap : Right & Left
(m)
0
3 (1.0)
3 (1.0) 2 (0.5)
7 (2.0) 7
2
10
3
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
(ft.) (m)
Side view Vertical flap : Up Horizontal flap : Center
10
3
7
2
3
1
0
0
Unit : ft./s (m/s)
7 (2.0) 3 (1.0)
2 (0.5)
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
(ft.) (m)
Side view Vertical flap : Down Horizontal flap : Center
10
3
7
2
3
1
Unit : ft./s (m/s)
7 (2.0) 3 (1.0) 2 (0.5)
0
0
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
- (04 - 34) -
4. INDOOR UNITS
MODEL : ASU24RLF
Conditions Fan speed : High Operation mode : Fan
(ft.) (m)
Top view Vertical flap : Up Horizontal flap : Center
7
2
3
1
0
0
3
1
7
2
Unit : ft./s (m/s)
7 (2.0)
2 (0.5)
3 (1.0)
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
3
7
2
Unit : ft./s (m/s)
INDOOR UNITS
INDOOR UNITS
(ft.) (m) 10
2 (0.5)
7 (2.0)
Top view Vertical flap : Up Horizontal flap : Right & Left
3
1
0
0
3
1
7
2
10
3
(m)
0
3 (1.0)
3 (1.0) 2 (0.5)
7 (2.0)
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
(ft.) (m)
Side view Vertical flap : Up Horizontal flap : Center
10
3
7
2
3
1
0
0
Unit : ft./s (m/s)
7 (2.0) 3 (1.0)
2 (0.5)
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
(ft.) (m)
Side view Vertical flap : Down Horizontal flap : Center
10
3
7
2
3
1
Unit : ft./s (m/s)
7 (2.0)
3 (1.0) 2 (0.5) 0
0
(m)
0
1
2
3
4
5
6
7
8
0
3
7
10
13
16
20
23
26 (ft.)
- (04 - 35) -
4. INDOOR UNITS
7. FAN PERFORMANCE CURVE 7-1. SLIM DUCT TYPE MODEL : ARU9RLF 0.44 (110) SP mode09 upper limit
0.32 (80) 0.28 (70)
Quiet (SP mode09) SP mode09 lower limit
0.24 (60) 0.20 (50) 0.16 (40) 0.12 (30) 0.08 (20) 0.04 (10)
Normal SP upper limit
Hi (Normal SP)
SP mode00 upper limit Quiet (Normal SP) Hi (SP mode00)
Quiet (SP mode00)
177 (300)
INDOOR UNITS
External Static Pressure [in.WG (Pa)]
Hi (SP mode09)
0.36 (90)
0 (0)
235 (400)
294 353 (500) (600) Air Flow [CFM (m3/h)]
412 (700)
471 (800)
Available air flow rate range (High level)
0.44 (110) 0.40 (100) External Static Pressure [in.WG (Pa)]
INDOOR UNITS
0.40 (100)
0.36 (90) 0.32 (80) Hi (SP mode09)
0.28 (70) Hi (SP mode08)
0.24 (60) Hi (SP mode07)
0.20 (50) Hi (Normal SP)
Hi (SP mode06)
0.16 (40) 0.12 (30)
Hi (SP mode02) Hi (SP mode05) Hi (SP mode01)
0.08 (20) 0.04 (10)
Hi (SP mode04) Hi (SP mode00) Hi (SP mode03)
0 (0) 177 (300)
235 (400)
294 353 (500) (600) Air Flow [CFM (m3/h)]
- (04 - 36) -
412 (700)
471 (800)
4. INDOOR UNITS
120
60.8 (16)
Capacity (%)
100
59.0 (15)
Capacity
80
57.2 (14)
60
55.4 (13)
40
53.6 (12) Outdoor temperature
20
51.8 (11) 50.0 (10)
0 294 353 (500) (600) Air Flow [CFM (m3/h)]
412 (700)
471 (800) INDOOR UNITS
235 (400)
INDOOR UNITS
177 (300)
Output temperature [°F (°C)]
Cooling
120
113.0 (45) Capacity
Capacity (%)
100
111.2 (44)
80
109.4 (43)
60
107.6 (42)
40
105.8 (41) Outdoor temperature
20
104.0 (40)
0
102.2 (39) 471 (800)
177 (300)
235 (400)
294 353 (500) (600) Air Flow [CFM (m3/h)]
- (04 - 37) -
412 (700)
Output temperature [°F (°C)]
Heating
4. INDOOR UNITS
MODEL : ARU12RLF 0.44 (110)
0.32 (80) 0.28 (70)
Quiet (SP mode09)
0.24 (60) 0.20 (50)
Normal SP upper limit
0.16 (40)
Quiet (Normal SP)
0.12 (30) 0.08 (20)
SP mode09 lower limit Hi (Normal SP)
SP mode00 upper limit
Hi (SP mode00) INDOOR UNITS
External Static Pressure [in.WG (Pa)]
0.36 (90)
0.04 (10) Quiet (SP mode00)
0 (0) 177 (300)
235 (400)
294 353 (500) (600) Air Flow [CFM (m3/h)]
412 (700)
471 (800)
Available air flow rate range (High level)
0.44 (110) 0.40 (100) External Static Pressure [in.WG (Pa)]
INDOOR UNITS
Hi (SP mode09)
SP mode09 upper limit
0.40 (100)
0.36 (90) 0.32 (80) 0.28 (70)
Hi (SP mode09)
0.24 (60)
Hi (SP mode08)
0.20 (50)
Hi (Normal SP)
Hi (SP mode07)
0.16 (40)
Hi (SP mode02)
Hi (SP mode06)
0.12 (30)
Hi (SP mode01)
Hi (SP mode05)
0.08 (20)
Hi (SP mode00)
Hi (SP mode04)
0.04 (10)
Hi (SP mode03)
0 (0) 177 (300)
235 (400)
294 353 (500) (600) Air Flow [CFM (m3/h)]
- (04 - 38) -
412 (700)
471 (800)
4. INDOOR UNITS
60.8 (16)
120 Capacity (%)
100
59.0 (15)
Capacity
80
57.2 (14)
60
55.4 (13)
40
53.6 (12) Outdoor temperature
20
50.0 (10)
0 294 353 (500) (600) Air Flow [CFM (m3/h)]
412 (700)
471 (800) INDOOR UNITS
235 (400)
INDOOR UNITS
177 (300)
51.8 (11)
Output temperature [°F (°C)]
Cooling
120
113.0 (45) Capacity
Capacity (%)
100
111.2 (44)
80
109.4 (43)
60
Outdoor temperature
107.6 (42)
40
105.8 (41)
20
104.0 (40)
0
102.2 (39)
177 (300)
235 (400)
294 353 (500) (600) Air Flow [CFM (m3/h)]
- (04 - 39) -
412 (700)
Output temperature [°F (°C)]
Heating
471 (800)
4. INDOOR UNITS
MODEL : ARU18RLF 0.44 (110)
0.32 (80)
Quiet (SP mode09)
0.28 (70) SP mode09 lower limit
0.24 (60) Normal SP upper limit Quiet (Normal SP)
0.20 (50) 0.16 (40)
Hi (Normal SP)
0.12 (30) SP mode00 upper limit 0.08 (20) 0.04 (10)
INDOOR UNITS
External Static Pressure [in.WG (Pa)]
0.36 (90)
0 (0)
Hi (SP mode00) Quiet (SP mode00)
353
412
471
530
589
(600)
(700)
(800) (900) (1000) 3 Air Flow [CFM (m /h)]
647
706
(1100)
(1200)
Available air flow rate range (High level)
0.44 (110) 0.40 (100) External Static Pressure [in.WG (Pa)]
INDOOR UNITS
Hi (SP mode09)
SP mode09 upper limit
0.40 (100)
0.36 (90) 0.32 (80) 0.28 (70) Hi (SP mode09)
0.24 (60) Hi (SP mode08)
0.20 (50)
Hi (Normal SP)
0.16 (40)
Hi (SP mode02)
0.12 (30)
Hi (SP mode01)
0.08 (20)
Hi (SP mode00)
Hi (SP mode07) Hi (SP mode06) Hi (SP mode05) Hi (SP mode04)
0.04 (10)
Hi (SP mode03)
0 (0) 353
412
471
530
(600)
(700)
(800) (900) (1000) 3 Air Flow [CFM (m /h)]
- (04 - 40) -
589
647
706
(1100)
(1200)
4. INDOOR UNITS
120
60.8 (16) Capacity
Capacity (%)
100
59.0 (15)
80
57.2 (14)
60
55.4 (13) 53.6 (12)
40 Outdoor temperature
20
51.8 (11) 50.0 (10)
0 471
530
589
(600)
(700)
(800) (900) (1000) Air Flow [CFM (m3/h)]
647
706
(1100)
(1200) INDOOR UNITS
412
INDOOR UNITS
353
Output temperature [°F (°C)]
Cooling
120
113.0 (45) Capacity
Capacity (%)
100
111.2 (44)
80
109.4 (43)
60
107.6 (42)
40 20
105.8 (41) Outdoor temperature
104.0 (40) 102.2 (39)
0 353
412
471
(600)
(700)
(800) (900) (1000) 3 Air Flow [CFM (m /h)]
530
589
- (04 - 41) -
647
706
(1100)
(1200)
Output temperature [°F (°C)]
Heating
4. INDOOR UNITS
MODEL : ARU24RLF
0.24 (60)
Hi (SP mode05)
Quiet (SP mode05) Hi (Normal SP)
0.20 (50) 0.16 (40)
Normal SP upper limit Quiet
0.12 (30) (Normal SP) 0.08 (20) SP mode00 upper limit
SP mode05 lower limit Hi (SP mode00)
0.04 (10) Quiet (SP mode00)
471
530
589
(800)
(900)
(1000)
647
706
765
(1100) (1200) (1300) Air Flow [CFM (m3/h)]
824
883
942
(1400)
(1500)
(1600)
Available air flow rate range (High level)
0.32 (80) 0.28 (70)
Hi (SP mode05)
0.24 (60)
Hi (SP mode04)
0.20 (50)
Hi (SP mode03) Hi (Normal SP)
0.16 (40)
Hi (SP mode02)
0.12 (30)
Hi (SP mode01)
0.08 (20)
Hi (SP mode00)
0.04 (10) 0 (0) 471
530
589
(800)
(900)
(1000)
647
706
765
(1100) (1200) (1300) Air Flow [CFM (m3/h)]
- (04 - 42) -
824
883
942
(1400)
(1500)
(1600)
4. INDOOR UNITS
INDOOR UNITS
External Static Pressure [in.WG (Pa)]
SP mode05 upper limit
0.28 (70)
0 (0)
External Static Pressure [in.WG (Pa)]
INDOOR UNITS
0.32 (80)
120
60.8 (16) Capacity
Capacity (%)
100
59.0 (15)
80
57.2 (14)
60
55.4 (13)
40
53.6 (12)
Outdoor temperature
51.8 (11)
20
50.0 (10)
0 589
(800)
(900)
(1000)
647
706
765
(1100) (1200) (1300) Air Flow [CFM (m3/h)]
824
883
942
(1400)
(1500)
(1600) INDOOR UNITS
530
INDOOR UNITS
471
Output temperature [°F (°C)]
Cooling
120
113.0 (45)
Capacity (%)
100
111.2 (44)
Capacity
80
109.4 (43)
60
107.6 (42)
40
105.8 (41)
20
104.0 (40)
Outdoor temperature
102.2 (39)
0 471
530
589
(800)
(900)
(1000)
647
706
765
(1100) (1200) (1300) Air Flow [CFM (m3/h)]
- (04 - 43) -
824
883
942
(1400)
(1500)
(1600)
Output temperature [°F (°C)]
Heating
4. INDOOR UNITS
Type
Model
Operation mode
Cooling
AUU9RLF Heating
Cooling Compact Cassette
AUU12RLF Heating
Cooling
AUU18RLF INDOOR UNITS
Heating
Cooling
ARU9RLF Heating
Cooling
ARU12RLF Heating Slim Duct Cooling
ARU18RLF Heating
Cooling
ARU24RLF Heating
Fan speed
m3/h
Air flow l/s
CFM
High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet
540 490 440 390 540 490 440 390 610 530 470 410 610 530 470 410 750 610 520 410 800 710 600 450 600 530 440 380 600 530 440 380 600 530 440 380 600 530 440 380 930 860 790 640 930 860 790 640 1330 1180 990 700 1330 1180 990 700
150 136 122 108 150 136 122 108 169 147 131 114 169 147 131 114 208 169 144 114 222 197 167 125 167 147 122 106 167 147 122 106 167 147 122 106 167 147 122 106 258 239 219 178 258 239 219 178 369 328 275 194 369 328 275 194
318 288 259 230 318 288 259 230 359 312 277 241 359 312 277 241 441 359 306 241 471 418 353 265 353 312 259 224 353 312 259 224 353 312 259 224 353 312 259 224 547 506 465 377 547 506 465 377 783 695 583 412 783 695 583 412
INDOOR UNITS
8. AIR FLOW
Conversion Factor 1 m3/h = 0.2778 l/s = 0.5886 CFM 3.6 m3/h = 1 l/s 1.699 m3/h = 1 CFM
- (04 - 44) -
4. INDOOR UNITS
Model
Operation mode
Cooling
ASU7RLF Heating
Cooling Compact Wall Mounted
ASU9RLF Heating
Cooling
INDOOR UNITS
ASU12RLF Heating
Cooling
ASU18RLF Heating Wall Mounted Cooling
ASU24RLF Heating
Fan speed
m3/h
Air flow l/s
CFM
High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet
560 500 430 340 560 500 430 350 600 520 430 340 600 520 430 350 660 560 450 340 660 560 470 350 920 740 620 550 920 740 620 550 1120 900 740 620 1100 900 740 620
156 139 119 94 156 139 119 97 167 144 119 94 167 144 119 97 183 156 125 94 183 156 131 97 256 206 172 153 256 206 172 153 311 250 206 172 306 250 206 172
330 294 253 200 330 294 253 206 353 306 253 200 353 306 253 206 388 330 265 200 388 330 277 206 542 436 365 324 542 436 365 324 659 530 436 365 647 530 436 365
INDOOR UNITS
Type
Conversion Factor 1 m3/h = 0.2778 l/s = 0.5886 CFM 3.6 m3/h = 1 l/s 1.699 m3/h = 1 CFM
- (04 - 45) -
4. INDOOR UNITS
9. NOISE LEVEL CURVE 9-1. COMPACT CASSETTE TYPE MODEL : AUU9RLF Heating
Cooling 80
80
70
70
N C -55 50 N C -50
N C -45
H igh 40
N C -40
N C -35 30 N C -30
Quiet
N C -25
20 N C -20
60 N C -60
N C -55 50 N C -50
N C -45 H igh
40
N C -40
N C -35
INDOOR UNITS
N C -60
N C -65
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
60
30 N C -30
Quiet
N C -25
20 N C -20
N C -15
N C -15
10
10
0
0 63
125
250
500
1,000
2,000
4,000
8,000
63
125
Octave band center frequency, Hz
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
MODEL : AUU12RLF Heating
Cooling 80
80
70
70
N C -65
Octave band sound pressure level, dB:(0dB=0.0002μbar)
N C -65
Octave band sound pressure level, dB:(0dB=0.0002μbar)
INDOOR UNITS
N C -65
60 N C -60
N C -55 50 N C -50 H igh N C -45 40 N C -40
N C -35 30 N C -30
Quiet
N C -25
20 N C -20
60 N C -60
N C -55 50 N C -50
N C -45 H igh 40 N C -40
N C -35 30 N C -30
Quiet
N C -25
20 N C -20
N C -15
N C -15 10
10
0
0 63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
- (04 - 46) -
4. INDOOR UNITS
MODEL : AUU18RLF Heating
Cooling 80
80
70
70
N C -65
N C -60
N C -55 50
H igh N C -50
N C -45 40 N C -40
N C -35 30 N C -30 Quiet N C -25 20 N C -20
60 N C -60
N C -55 50 N C -50 H igh N C -45 40 N C -40
N C -35
INDOOR UNITS
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
INDOOR UNITS
N C -65 60
30 N C -30
Quiet
N C -25
20 N C -20
N C -15
N C -15
10
10
0
0 63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
- (04 - 47) -
4. INDOOR UNITS
9-2. SLIM DUCT TYPE MODEL : ARU9RLF Heating
Cooling 80
80
70
70
N C -65
N C -55 50 N C -50
N C -45 40 N C -40
N C -35 30 H igh
N C -30
N C -25 20
Quiet
N C -20
60 N C -60
N C -55 50 N C -50
N C -45 40 N C -40
N C -35 30 N C -30
H igh
N C -25 20
Quiet
N C -20
N C -15
N C -15 10
0
0 63
125
250
500
1,000
2,000
4,000
63
8,000
125
Octave band center frequency, Hz
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
MODEL : ARU12RLF Heating
Cooling 80
80
70
70
N C -65
Octave band sound pressure level, dB:(0dB=0.0002μbar)
N C -65 60 N C -60
N C -55 50 N C -50
N C -45 40 N C -40
N C -35 30
H igh
N C -30
N C -25 20
Quiet
N C -20
60 N C -60
N C -55 50 N C -50
N C -45 40 N C -40
N C -35 30
H igh
N C -30
N C -25 20
Quiet
N C -20
N C -15
N C -15 10
10
0
0 63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
- (04 - 48) -
4. INDOOR UNITS
INDOOR UNITS
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
N C -60
10
Octave band sound pressure level, dB:(0dB=0.0002μbar)
INDOOR UNITS
N C -65 60
MODEL : ARU18RLF Heating
Cooling 80
80
70
70
60 N C -60
N C -55 50 N C -50
N C -45 40 N C -40
N C -35 H igh
30
N C -30
Quiet
N C -25
20 N C -20
60 N C -60
N C -55 50 N C -50
N C -45 40 N C -40
H igh
30 N C -30
N C -25
Quiet
20 N C -20
N C -15
N C -15 10
0 63
N C -35
INDOOR UNITS
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
N C -65
10
0 125
250
500
1,000
2,000
4,000
8,000
63
125
Octave band center frequency, Hz
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
MODEL : ARU24RLF Heating
Cooling 80
80
70
70
N C -65
Octave band sound pressure level, dB:(0dB=0.0002μbar)
N C -65
Octave band sound pressure level, dB:(0dB=0.0002μbar)
INDOOR UNITS
N C -65
60 N C -60
N C -55 50 N C -50
N C -45 40 N C -40 H igh
N C -35 30 N C -30 Quiet
N C -25 20 N C -20
60
N C -60
N C -55 50
N C -50
N C -45 40
N C -40 H igh
N C -35 30
N C -30
Quiet
N C -25 20 N C -20
N C -15
N C -15 10
10
0
0 63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
- (04 - 49) -
4. INDOOR UNITS
9-3. COMPACT WALL MOUNTED TYPE MODEL : ASU7RLF Heating
Cooling 80
80
70
70
N C -65
N C -55 50 N C -50
N C -45 H igh
40
N C -40
N C -35 30 N C -30
N C -25 20 N C -20
Quiet
60 N C -60
N C -55 50 N C -50
N C -45 40
H igh
N C -40
N C -35 30 N C -30
N C -25 20
Quiet
N C -20
N C -15
N C -15 10
0
0 63
125
250
500
1,000
2,000
4,000
63
8,000
125
Octave band center frequency, Hz
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
MODEL : ASU9RLF Heating
Cooling 80
80
70
70
N C -65
Octave band sound pressure level, dB:(0dB=0.0002μbar)
N C -65 60 N C -60
N C -55 50 N C -50
N C -45
H igh 40
N C -40
N C -35 30 N C -30
N C -25 20 N C -20
Quiet
60 N C -60
N C -55 50 N C -50
N C -45 40
H igh N C -40
N C -35 30 N C -30
N C -25 20
Quiet N C -20
N C -15
N C -15 10
10
0
0 63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
- (04 - 50) -
4. INDOOR UNITS
INDOOR UNITS
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
N C -60
10
Octave band sound pressure level, dB:(0dB=0.0002μbar)
INDOOR UNITS
N C -65 60
MODEL : ASU12RLF Heating
Cooling 80
80
70
70
N C -65
N C -60
N C -55 50 N C -50 H igh N C -45 40 N C -40
N C -35 30 N C -30
N C -25 20 N C -20
Quiet
60 N C -60
N C -55 50 N C -50
N C -45 H igh 40 N C -40
N C -35 30 N C -30
N C -25 20
Quiet N C -20
N C -15
N C -15
10
10
0
0 63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
- (04 - 51) -
4. INDOOR UNITS
INDOOR UNITS
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
INDOOR UNITS
N C -65 60
9-4. WALL MOUNTED TYPE MODEL : ASU18RLF Heating
Cooling 80
80
70
70
N C -65
N C -55 H igh 50 N C -50
N C -45 40 N C -40
N C -35 30 N C -30
Quiet
N C -25 20 N C -20
60 N C -60
N C -55 50 N C -50
H igh
N C -45 40 N C -40
N C -35
INDOOR UNITS
Octave band sound pressure level, dB:(0dB=0.0002μbar)
Octave band sound pressure level, dB:(0dB=0.0002μbar)
N C -60
30 N C -30 Quiet N C -25 20 N C -20
N C -15
N C -15 10
10
0
0 63
125
250
500
1,000
2,000
4,000
63
8,000
125
Octave band center frequency, Hz
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
MODEL : ASU24RLF Heating
Cooling 80
80
70
70
N C -65
Octave band sound pressure level, dB:(0dB=0.0002μbar)
N C -65
Octave band sound pressure level, dB:(0dB=0.0002μbar)
INDOOR UNITS
N C -65 60
60 N C -60
N C -55 H igh 50 N C -50
N C -45 40 N C -40
N C -35 30 N C -30 Quiet N C -25 20 N C -20
60 N C -60
N C -55 50 N C -50
H igh
N C -45 40 N C -40
N C -35 30 N C -30 Quiet N C -25 20 N C -20
N C -15
N C -15 10
10
0
0 63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
63
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency, Hz
- (04 - 52) -
4. INDOOR UNITS
9-5. SOUND LEVEL CHECK POINT COMPACT CASSETTE TYPE
INDOOR UNITS
4ft. 11-1/16in. (1.5m)
INDOOR UNITS
Microphone
Microphone
- (04 - 53) -
4. INDOOR UNITS
SLIM DUCT TYPE
Microphone
Microphone
Center
Center
Side view
Front view
COMPACT WALL MOUNTED AND WALL MOUNTED TYPE
Microphone
Microphone
3ft. 3-3/8in. (1m)
- (04 - 54) -
4. INDOOR UNITS
INDOOR UNITS
Measuring duct
2ft. 7-1/2in. (0.8m)
INDOOR UNITS
Measuring duct
3ft. 3-3/8in. (1m)
4ft. 11-1/16in. (1.5m)
6ft. 6-3/4in. (2m)
10. SAFETY DEVICES Model and type
PCB fuse
AUU9RLF Compact Cassette
AUU12RLF
250V 3.15A
AUU18RLF
Compact Wall Mounted
ASU24RLF
250V 3.15A
250V 3.15A
275 ± 59°F (135 ± 15°C)
Float switch
―
○
―
○
248 ± 59°F
216°F OFF
(120 ± 15°C)
(102°C OFF)
302 ± 59°F
216°F OFF
(150 ± 15°C)
(102°C OFF)
―
―
INDOOR UNITS
Wall Mounted
250V 3.15A
Terminal thermal fuse
INDOOR UNITS
Slim Duct
ARU9RLF ARU12RLF ARU18RLF ARU24RLF ASU7RLF ASU9RLF ASU12RLF ASU18RLF
Fan motor thermal protector 266 + 63°F - 48°F (130 +17°C -9°C)
- (04 - 55) -
4. INDOOR UNITS
Hybrid Flex Inverter System
5. CONTROL SYSTEM
DTR_BMU001E_04--CHAPTER05 2010.10.04
CONTENTS 5. CONTROL SYSTEM 1. CONTROL SYSTEM...................................................................... 05 - 01 1-1. LINE UP OF CONTROLLERS ............................................................... 05 - 01 1-2. CONTROL SYSTEM DESIGN ............................................................... 05 - 02 1-3. SYSTEM CONFIGURATION EXAMPLES ............................................. 05 - 03 1-4. CONTROL EQUIPMENT DESIGN LIMITATION .................................... 05 - 05
2. CONTROL UNITS.......................................................................... 05 - 06 2-1. CENTRAL REMOTE CONTROLLER .................................................... 05 - 07 2-2. WIRED REMOTE CONTROLLER ......................................................... 05 - 13 2-3. SIMPLE REMOTE CONTROLLER ........................................................ 05 - 19 2-4. WIRELESS REMOTE CONTROLLER................................................... 05 - 25 2-5. IR RECEIVER UNIT ............................................................................... 05 - 30 2-6. GROUP CONTROL METHOD ............................................................... 05 - 33 2-7. COMPARISON TABLE OF CONTROLLERS ........................................ 05 - 34
1. CONTROL SYSTEM 1-1. LINE UP OF CONTROLLERS FEATURES OF CONTROL SYSTEM Air Conditioning Central Control
Air Conditioning Individual Control
Central controller specially designs for centralized control.
A range of remote controllers suitable for range of individual control situations, using various built-in timers.
Central Remote Controller
Wired Remote Controller
UTY-DMMUM UTY-RNNUM
Control of indoor units with simple operation and weekly timer.
The room temperature can be controlled and detected accurately with built-in thermo sensor.
Simple Remote Controller
Compact remote controller concentrates on the basic functions such as Start/Stop, Fan Control, Temperature Setting and Operation mode.
Wireless Remote Controller
Simple and sophisticated operations with a choice of 4 daily timers. UTY-LNHUM AR-RAH1U
IR Receiver Unit UTY-LRHUM Wireless remote controller for duct type
- (05 - 01) -
5. CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM
UTY-RSNUM
1-2. CONTROL SYSTEM DESIGN ADVANCED INTEGRATED CONTROL SYSTEM Air Conditioning Central Control
Air Conditioning Individual Control
System Outdoor Unit
Branch box (Primary)
Wired Remote Controller UTY-RNNUM
Central Remote Controller UTY-DMMUM
Simple Remote Controller UTY-RSNUM Branch box (Secondary 1)
CONTROL SYSTEM
CONTROL SYSTEM
Wireless Remote Controller
Transmission line UTY-LNHUM
AR-RAH1U
Remote controller line Central remote controller line
Branch box (Secondary 2)
IR Receiver Unit UTY-LRHUM
- (05 - 02) -
5. CONTROL SYSTEM
1-3. SYSTEM CONFIGURATION EXAMPLES INDIVIDUAL CONTROL Wired Remote Controller ● Wired, simple, and wireless remote controllers can be used jointly. ● Two remote controllers can be connected with single indoor unit.
Branch box (Primary)
Branch box (Secondary 1)
Branch box (Secondary 2)
Outdoor unit
Wired Remote Controller
Simple Remote Controller ● Enables easy control of basic functions by the hotel or office guest. ● Two remote controller can be connected with single indoor unit.
Branch box (Primary)
Branch box (Secondary 1)
Branch box (Secondary 2)
Outdoor unit
Simple & Wired Remote Controller
● Wired, simple, and wireless remote controllers can be used jointly.
Branch box (Primary)
Branch box (Secondary 1)
Branch box (Secondary 2)
Outdoor unit
Wireless & Wired Remote Controller
CENTRAL CONTROL Central Remote Controller ● Up to 8 indoor units can be controlled with one central remote controller. ● The central remote controller can be used simultaneously with wired, simple, and wireless remote controller. ● Only one can be used for one system.
Branch box (Primary)
Branch box (Secondary 1)
Branch box (Secondary 2)
Outdoor unit
Central Remote Controller
- (05 - 03) -
5. CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM
Wireless Remote Controller
INDOOR UNIT TYPE AND THE APPLICABLE CONTROL METHOD Type
Indoor units Compact Slim Duct Wall Mounted *1 *1
Model
Compact Cassette
UTY-DMMUM
*1
UTY-RNNUM
*2
UTY-LNHUM
–
–
AR-RAH1U
–
–
–
IR Receiver Unit
UTY-LRHUM
–
–
–
Simple Remote Controller
UTY-RSNUM
*2
Central Remote Controller Wired Remote Controller Wireless Remote Controller
Wall Mounted *1
: Accessory, : Optional, –: It is not possible to connect it. *1: Central remote controller is connected with Branch box.
CONTROL SYSTEM
CONTROL SYSTEM
*2: Optional Communication kit (UTY-XCBXEZ1) is necessary for the installation.
- (05 - 04) -
5. CONTROL SYSTEM
1-4. CONTROL EQUIPMENT DESIGN LIMITATION
Central Controller
Central Remote Controller
Model
The number that can be connected
UTY-DMMUM
1 / Multi system
UTY-LNHUM Wireless Remote Controller
AR-RAH1U
Controller Wired Remote Controller
UTY-RNNUM
Simple Remote Controller
UTY-RSNUM
IR Receiver Unit
UTY-LRHUM
2 / Indoor unit
CONTROL SYSTEM
1 / Indoor unit
CONTROL SYSTEM
Individual Controller
- (05 - 05) -
5. CONTROL SYSTEM
2. CONTROL UNITS The following types of controllers are available with the FUJITSU GENERAL LIMITED Hybrid Flex Inverter System :
Central Remote Controller Wired Remote Controller Simple Remote Controller Wireless Remote Controller IR Receiver Unit
Central Control
CONTROL SYSTEM
CONTROL SYSTEM
Central Remote Controller
Individual Control Wired Remote Controller
Simple Remote Controller
Wireless Remote Controller
IR Receiver Unit
- (05 - 06) -
5. CONTROL SYSTEM
2-1. CENTRAL REMOTE CONTROLLER MODEL : UTY - DMMUM ● Large and full-dot liquid crystal screen ● Screen with backlight can be seen even in the dark ● Wide and large keys easy to press, user-intuitive arrow key
FEATURES Batched control of up to 8 indoor units. The temperature, airflow volume, and remote control prohibition settings of all indoor units can be batched.
User-friendly operation ● Large backlight LED screen ● Large easy-to-see operation panel
Easy installation ● Central remote controller is connected directly to the branch box, making the installation process easier. ● Once the controller is connected, it can automatic register and display all the indoor units.
- (05 - 07) -
5. CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM
Central & Individual Control
MAIN FUNCTIONS Outdoor unit low noise operation Air conditioning load factor
● Users can choose from 4 low noise levels, depending on the installation environment.
Heat load
100%
Down
Capacity 0 58dB
Operating sound
0
(time) Low noise operation
● While this function is selected, all indoor units start the minimum heat operation when all the indoor units are stopped by operation of the [On/Off button]. ● When the room temperature is higher than 50°F (10°C), MIN. HEAT operation starts and maintains the room temperature at 50°F (10°C) when the temperature drops below 50°F (10°C). ● When “MIN, HEAT operation stops, the room set temperature quickly returns to the preset temperature.
All indoor units OFF “All MIN. HEAT” operation ON
70°F Indoor unit operation START
CONTROL SYSTEM
50°F
Economy (All) operation Temp.
Example : Cooling operation
● If all the indoor and outdoor units are changed to economy mode, this can save more energy than setting of each indoor unit individually. ● Economy operation is energy saving, as the set temperature of indoor unit is shifted by 2°F (1°C) and the maximum electric value of the outdoor unit is suppressed.
Economy operation Shift setting temp
Set temperature
Nomal operation
Time
Control maxmum current
Schedule timer Example Temp. Cool
Temp.
PM12
Cool
PM5
Heat
Heat AM7
Cool
PM11 Time
AM8
Cool
PM1
Cool PM6
● Operation setting can be changed 4 times in each day of a week, and 2types of the schedule can be set to suit users' preference.
PM10 Time
Temp.
Cool AM7
Winter season pattern
Saturday~Sunday
Temp.
Monday~Friday
Summer season pattern
Heat
PM12 PM1
Heat PM11 Time
AM7
PM1
Heat PM6
Heat PM11 Time
Prohibited Settings The remote controller operation of all indoor units comes with a lock function to prevent unapproved operations in the various rooms. The central remote controller also has a key lock function to prevent children from playing with it, etc - (05 - 08) -
5. CONTROL SYSTEM
CONTROL SYSTEM
Minimum heat (All) operation
FUNCTIONS
1
2
6 7
3
8
5
9
1 Display panel (with backlight)
6 Screen switch button (Right)
2 Screen switch button (Left)
7 Power indicator
3 Menu button
8 On / Off button
4 Cancel button
9 Enter button
5 Cursor button
ELECTRICAL WIRING Example: Wiring diagram when 3 units of branch boxes are connected Branch box (Primary)
Branch box (Secondary 1)
Branch box (Secondary 2)
REMOTE CONTROL
REMOTE CONTROL
REMOTE CONTROL
1 2 3
1 2 3
1 2 3
Remote controller cable 1 2 3
• Total remote controller cable length: MAX. 500 m (1640 ft.) Central remote controller
- (05 - 09) -
5. CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM
4
INSTALLATION 1) Remove the insulation of the remote controller cable. 55 (2-5/32) 45 (1-25/32) 30 (1-3/16) Unit : mm (in.)
8 (5/16) 8
8 (5/16) 1. 12V (Red)
(5/16)
2. Signal (White) 3. COM (Black)
2) Insert the flat-blade screwdriver and remove the front case and rear case by twisting it slightly. Hooks (2 places)
Rear case
Front case
3) Install the rear case to the wall, box, etc. with 2 screws (M4 × 16 mm). Fix the 2 screws in either horizontal or vertical position. A. When mounting on the box:
B. When the cable is along the wall:
● Attach the case after leading the cable.
● Mount the rear case on the wall. ● Cut off a hole for cabling in the front case.
Remote controller cable
Cut off
Box Screws Rear case
Front case
CAUTION ● When connecting the remote controller cable, take measures to prevent the water or insects coming into the remote controller through the cable, such as to provide the trap or close the hole for cabling with the putty. Putty Trap
Putty
Putty Trap Trap
4) Setting up the DIP switch. Refer to "6. SYSTEM DESIGN".
- (05 - 10) -
5. CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM
Flat screwdriver
5) Connect the cable to the terminals on the front case. Fix the cable together with the sheath with the binder. Cut off the excess binder. Tightening torque Terminal screw 0.8 to 1.2N • m (7 to 10 lbf • in)
Binder 1. 12V (Red)
Remote controller cable (sheath)
2. Signal (White)
Hole for binder Good
3. COM (Black)
2 mm (3/32 in.)
No good
No good
CAUTION
6) Attach the front case.
CONTROL SYSTEM
CONTROL SYSTEM
● Be careful to avoid breaking the cable by over-tightening the binder. ● When connecting the remote controller cables, do not over-tighten the screws.
● Insert after adjusting upper part of front case. ● When insert the front case, do not pinch the cable. Front case
Click!
Good
No good
No good
No good
CAUTION ● Insert the upper case firmly. If improperly attached, it will cause the upper case to fall off.
- (05 - 11) -
5. CONTROL SYSTEM
DIMENSIONS
Unit : in. (mm)
Side View
11/32 (9)
2-1/2 (63.5)
1/2 (12.5)
3/16 (4.5)
3/16 (4.5)
1-25/32 (45.3)
4-23/32 (120)
Front View
29/32 (23)
3/16 (4.5)
3-9/32 (83.5)
27/32 (21.3)
4-23/32 (120)
1-5/16 (33.5)
19/32 (15.3)
1-3/16 (30)
Rear View
PACKING LIST Quantity
Remote controller cable
1
Screw (M4 x 16mm)
2
Binder
1
Installation manual
1
Operating manual
1
Application For connecting the remote controller For installing the remote controller For remote controller and remote controller cable binding
WIRING SPECIFICATIONS Use Remote controller cable
Cable size 22AWG ( 0.33 mm2 )
Remarks Use sheathed PVC cable, Polar 3 core
SPECIFICATIONS Dimensions [H x W x D]: in.(mm)
4-23/32 (120) x 4-23/32 (120) x 27/32 (21.3)
Weight: oz. (g)
7.8 (220)
- (05 - 12) -
5. CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM
Name and shape
2-2. WIRED REMOTE CONTROLLER MODEL : UTY - RNNUM FEATURES
● Various timer setup (ON / OFF / WEEKLY) are possible. ● Equipped with weekly timer as standard function. (Start / Stop function is twice per day for a week) ● When setting up a timer, start / stop and a temperature setup can be changed. ● When a failure occurs,the error code is displayed. ● Error history.(Last 16 error codes can be accessed.) ● The room temperature can be controlled by being detective the temperature accurately with Built-in thermo sensor.
Powerful features and compact size Thermo sensor
Weekly timer
Wired remote controller
Setback timer
CONTROL SYSTEM
Accurate and comfortable
Sensor part
Indoor temperature can be detected accurately by the inclusion of a thermo sensor in the body of the wired controller. Our system can correspond to various scenes. This wired remote controller and the optional remote sensor allows flexibility in sensor location, and suitable for all requirements.
Thermo sensor display Control part for changing the thermo sensor
Built-in timers Weekly timer
Setback timer
Possible to set ON/OFF time to operate twice each day of the week.
Possible to set temperature for two time spans and for each day of the week.
Easy-to-understand time bar display Screen after setup
Example : setup screen (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
Example : setup screen (Set to Wednesday: 8:00 to 20:00.)
84°F (28°C)
76°F (24°C) 0 time 12
3 3
6 6 AM
9 9
12 12
15 3
18 6
21 9
0 time 12
O'clock
3 3
6 6
9 9
12 12
AM
PM
At "Weekly timer" + "Set back timer" setup 76°F (24°C)
76°F 24°C
84°F 28°C
76°F 24°C
0 time 12
3 3
6 6 AM
Easy-to-understand operation
9 9
15 3
18 6
21 9
O'clock
PM
84°F (28°C)
12 12
15 3
18 6
21 9
O'clock
PM
Simple installation Components are compatible with standard switch boxes. Flat back surface allows equipment to be installed wherever it is needed.
Timer area
Operation area
European switch box
[Variable timer control] The operation/display sections are zoned according to time and operation, enabling variable programming to match application. - (05 - 13) -
JIS box
5. CONTROL SYSTEM
CONTROL SYSTEM
Individual control
FUNCTIONS 1
START/STOP button Pressed to start and stop operation.
7
2 Display
SET TEMP. button Selects the setting temperature.
3 2 8 9 10 11
1 3 4 6 5
12
14 15
13
MODE button Selects the operating mode (AUTO , COOL , DRY , FAN , HEAT ).
16
4
FAN button Selects the fan speed (AUTO , HIGH , MED LOW , QUIET ).
5
,
Vertical air flow direction and swing button Press for two seconds to change the swing mode
6
Horizontal air flow direction and swing button
7
Built-in thermo sensor
8
TIMER MODE (CLOCK ADJUST) button
Press for two seconds to change the swing mode. Detect room temperature.
Display panel
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.
9 17
20 21 19
18
DAY (DAY OFF) button Temporarily cancels of one day timer.
10 SET BACK button Pressed select the set back timer.
11 SET TIME button
27 25 26 23 24 22
The schedule of a weekly timer is deleted.
13 TIME SET button Sets the date, hour, minute and on-off time.
14 ECONOMY (THERMO SENSOR) button 15 FILTER RESET button 16 Operation lamp Lights during operation and when the timer is on.
17 Timer and clock display 18 Operation mode display 19 Fan speed display 20 Operation lock display 21 Temperature display Displayed temperature is set temperature.
22 Defrost display Indicates during the oil recovery and defrosting operation.
23 Vertical swing display 24 Horizontal swing display 25 Economy display 26 Thermo sensor display 27 Filter display Note: Functions will be different due to type of indoor unit. For details, please see operation manual.
- (05 - 14) -
5. CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM
Pressed to select the set back timer.
12 TIMER DELETE button
SYSTEM DIAGRAM 2 remote controllers
1 remote controller Indoor unit
Indoor unit
A
B
C
Primary
Remote controller
A , B , C : Remote controller cable. A< =1640ft (500m) ; B+C < =1640ft (500m)
Secondary
Remote controllers
ELECTRICAL WIRING 2 remote controllers
1 remote controller
REMOTE CONTROLLER
1 2 3
1 2 3
1 2 3
1 2 3
Primary
Remote controller
1 (RED) : 12V 2 (WHITE) : Signal 3 (BLACK) : COM
1 2 3
Secondary
Remote controllers
DIMENSIONS
Front View
Side View
- (05 - 15) -
Rear View
5/16 (8)
3/16 (4.5)
3-9/32 (83.5)
3/16 (4.5) 1/2 (12.5)
3/16 (4.5)
1-25/32 (45.3)
4- 23/32 (120)
29/32 (23)
Hole
21/32 (17)
2-1/2 (63.5)
1-3/16 (30) 1-5/16 (33.5) 4- 23/32 (120)
19/32 (15.3)
Unit : in. (mm)
4- 23/32 (120)
CONTROL SYSTEM
REMOTE CONTROLLER
1/4 (6) Hole x 2 Hole x 3
5. CONTROL SYSTEM
CONTROL SYSTEM
Indoor unit
Indoor unit
INSTALLATION Connection Pattern Note: Connection pattern is different according to type of Indoor unit. Indoor unit types Compact Cassette type Slim Duct type Compact Wall Mounted type Wall Mounted type
Connection Pattern Pattern A Pattern B Pattern C
Pattern A Connect the end of remote controller cable directly to the exclusive terminal block. M4 screw Remote controller terminal block
Remote controller cable
Indoor unit
Outdoor unit / Power supply terminal block
PCB
Terminal block
Note: It may be failed if it is connected to the outdoor unit or the terminal block for power supply.
● Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. ● Connect the remote controller cable and connecting cable as shown in Fig. ● Be sure to insulate the connection between the cables. Connecting cable White Red Black
White Red Remote controller cable
Insulated connection Black
2) Method of connecting remote controller cable ● Connecting cable made by above-mentioned 1) is connected with terminal (CN305) of optional communication kit (UTY-XCBXZ1). ● Cable connected with terminal (CN301) of communication kit (UTY-XCBXZ1) is connected with PCB of Indoor unit.
Remote controller cable
Connecting cable
Terminal (CN301) Terminal (CN305)
Communication kit (UTY-XCBXZ1)
- (05 - 16) -
Indoor unit PCB
5. CONTROL SYSTEM
CONTROL SYSTEM
1) Modify the remote controller cable as per below methods.
25/32 in. (20 mm)
CONTROL SYSTEM
Pattern B
Pattern C 1) Modify the remote controller cable as per below methods. ● Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. ● Connect the remote controller cable and connecting cable as shown in Fig. ● Be sure to insulate the connection between the cables. 25/32 in. (20 mm)
Connecting cable White Red Black
White Red Remote controller cable
Insulated connection Black
2) Method of connecting remote controller cable
Remote controller cable
Connecting cable
CONTROL SYSTEM
CONTROL SYSTEM
● Connecting cable made by above-mentioned 1) is connected with PCB of Indoor unit.
CN6
Indoor unit PCB
- (05 - 17) -
5. CONTROL SYSTEM
PACKING LIST Name and shape
Quantity
Remote controller cable
1
Application For connecting the remote controller
[33ft(10m)] 2
Binder
1
Connecting cable *1
1
CONTROL SYSTEM
Screw *1 (M4 x 14mm)
1
Cable clamper *1
1
Installation manual
1
Operating manual
1
For installing the remote controller For remote controller and remote controller cable binding For connecting the remote controller cable to the Compact wall mounted type and Wall mounted type indoor unit
For installing the remote controller cable to the indoor unit For installing the remote controller cable to the indoor unit
CONTROL SYSTEM
Screw (M4 x 16mm)
*1: Use only if the remote controller cable must be modified for the indoor unit model.
WIRING SPECIFICATIONS Use Remote controller cable
Cable size 22AWG ( 0.33 mm2 )
Remarks Use sheathed PVC cable, Polar 3 core
SPECIFICATIONS Dimensions [H x W x D]: in.(mm)
4-23/32 (120) x 4-23/32 (120) x 21/32 (17)
Weight: oz. (g)
5.6 (160)
- (05 - 18) -
5. CONTROL SYSTEM
2-3. SIMPLE REMOTE CONTROLLER MODEL : UTY - RSNUM FEATURES ● Easy operation. ● Built-in background light function. ● Easy installation with a slim shape with no bulge in the back. ● Error history.(Last 16 error codes can be accessed.) ● Can be installed onto SW-BOX. (applies to European and other country's standard)
User-friendly operation ● Provides access to basic operations, such as Start / Stop, Fan speed, operation mode and room temperature setting. ● A large Start / Stop button is provided in the centre of the remote controller unit for easy operation. ● Following an error display, diagnostics can be carried out on the controller.
Simple installation Can be mounted on the European switch Box (installation dimension: 60mm) or the JIS Built-in Box (installation dimension: 83.5mm)
2-3/8in. (60mm) European switch box
JIS Built-in box
- (05 - 19) -
5. CONTROL SYSTEM
CONTROL SYSTEM
● Background light enables easy operation in a darkened room. ● Background light activates during all button operations, and lasts 10 seconds in operating mode and 5 seconds in stop mode after a button is pressed.
3-9/32in. (83.5mm)
CONTROL SYSTEM
Background light
FUNCTIONS 1
START/STOP button
2
Display background light
3
Operation lamp
Pressed to start and stop operation. Lights during operation. Lights during operation. 2
4
3 4
5
6
FAN button Selects the fan speed (AUTO LOW
1
5
, HIGH , MED , QUIET ).
,
SET TEMP. button Selects the setting temperature.
6
MODE button Selects the operating mode (AUTO
7
Standby display
8
Power source display
9
Central control display
, COOL
, DRY ,FAN
, HEAT
).
Indicates during the oil recovery and defrosting operation. Indicates the main power ON.
Display panel
Indicates when function is locked. 7
8
13
9
10 Fan speed display 11 Set temperature
10
Indicates Error history number. *1 Indicates Indoor unit address. *2
11
CONTROL SYSTEM
12
13 (Upper) Indicates the error code *1 *3 / the refrigerant
system address. *2 (Lower) Indicates the remote controller address. *1 *2 *3
*1: during Error code history display mode. *2: during address display mode. *3: during self Diagnosis mode.
SYSTEM DIAGRAM 1 remote controller
2 remote controllers
Indoor unit
A
Indoor unit
B
C
Primary Remote controller
Secondary
Remote controllers
A , B , C : Remote controller cable. A< =1640ft (500m) ; B+C < =1640ft (500m)
- (05 - 20) -
5. CONTROL SYSTEM
CONTROL SYSTEM
12 Operating mode display
ELECTRICAL WIRING 2 remote controllers
1 remote controller Indoor unit
Indoor unit
REMOTE CONTROLLER
REMOTE CONTROLLER
1 2 3
1 2 3
1 2 3
1 2 3
Secondary
Primary Remote controller
1 (RED) : 12V 2 (WHITE) : Signal 3 (BLACK) : COM
1 2 3
Remote controllers
DIMENSIONS 7/16 (11) 23/32 (18)
11/32 (9)
1/4 (6)
1/2 (12.5)
3/16 (4.5)
2-3/8 (60)
3-9/32 (83.5)
1-7/8 (47.5)
15/16 (23.5)
hole x 2
5/32 (4)
CONTROL SYSTEM
9/16 (14)
4-23/32 (120)
CONTROL SYSTEM
Unit : in. (mm) 2-15/16 (75) 1-15/16 (49) 1-17/32 (39)
5/16 (8)
hole x 2
Front View
Side View
- (05 - 21) -
Rear View
5. CONTROL SYSTEM
INSTALLATION Connection Pattern Note: Connection pattern is different according to type of Indoor unit. Indoor unit types Compact Cassette type Slim Duct type Compact Wall Mounted type Wall Mounted type
Connection Pattern Pattern A Pattern B Pattern C
Pattern A Connect the end of remote controller cable directly to the exclusive terminal block. M4 screw Remote controller terminal block
Remote controller cable
Indoor unit
Outdoor unit / Power supply terminal block
PCB
Terminal block
Note: It may be failed if it is connected to the outdoor unit or the terminal block for power supply.
● Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. ● Connect the remote controller cable and connecting cable as shown in Fig. ● Be sure to insulate the connection between the cables. Connecting cable White Red Black
White Red Remote controller cable
Insulated connection Black
2) Method of connecting remote controller cable ● Connecting cable made by above-mentioned 1) is connected with terminal (CN305) of optional communication kit (UTY-XCBXZ1). ● Cable connected with terminal (CN301) of communication kit (UTY-XCBXZ1) is connected with PCB of Indoor unit.
Remote controller cable
Connecting cable
Terminal (CN301) Terminal (CN305)
Communication kit (UTY-XCBXZ1)
- (05 - 22) -
Indoor unit PCB
5. CONTROL SYSTEM
CONTROL SYSTEM
1) Modify the remote controller cable as per below methods.
25/32 in. (20 mm)
CONTROL SYSTEM
Pattern B
Pattern C 1) Modify the remote controller cable as per below methods. ● Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. ● Connect the remote controller cable and connecting cable as shown in Fig. ● Be sure to insulate the connection between the cables. 25/32 in. (20 mm)
Connecting cable White Red Black
White Red Remote controller cable
Insulated connection Black
2) Method of connecting remote controller cable
Remote controller cable
Connecting cable
CONTROL SYSTEM
CONTROL SYSTEM
● Connecting cable made by above-mentioned 1) is connected with PCB of Indoor unit.
CN6
Indoor unit PCB
- (05 - 23) -
5. CONTROL SYSTEM
PACKING LIST Name and shape
Quantity
Application For connecting the remote controller
Remote controller cable
1
[33ft(10m)] Screw (M4 x 16mm)
2
Binder
1
Connecting cable *1
1
1
Cable clamper *1
1
Installation manual
1
Operating manual
1
For remote controller and remote controller cable binding For connecting the remote controller cable to the Compact wall mounted type and Wall mounted type indoor unit
For installing the remote controller cable to the indoor unit For installing the remote controller cable to the indoor unit
*1: Use only if the remote controller cable must be modified for the indoor unit model.
CONTROL SYSTEM
CONTROL SYSTEM
Screw *1 (M4 x 14mm)
For installing the remote controller
WIRING SPECIFICATIONS Use Remote controller cable
Cable size 22AWG ( 0.33 mm2 )
Remarks Use sheathed PVC cable, Polar 3 core
SPECIFICATIONS Dimensions [H x W x D]: in. (mm)
4-23/32 (120) x 2-15/16 (75) x 9/16 (14)
Weight: oz. (g)
3.2 (90)
- (05 - 24) -
5. CONTROL SYSTEM
2-4. WIRELESS REMOTE CONTROLLER MODEL : UTY - LNHUM / AR-RAH1U FEATURES ● Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible. ● Can be used jointly with wired remote controllers . ● Easy to change custom code (4 patterns).
Built-in timers Select from four different timer programs (On / Off / Program / Sleep).
Program timer The program timer operates the ON and OFF timer once within a 24 hour period.
Sleep timer
Cooling operation / dry operation
Heating operation
When the sleep timer is set, the set temperature automatically rises 2°F (1°C) every hour. The set temperature can rise up to a maximum of 4°F (2°C).
When the sleep timer is set, the set temperature automatically drops 2°F (1°C) every 30 minutes. The set temperature can drop to a maximum of 8°F (4°C).
Timer setting
2°F (1°C) 4°F (2°C)
60min.
6°F (3°C)
8°F (4°C)
30min. 60min. 4°F (2°C)
2°F (1°C)
90min. Timer setting
Switching remote controller signal code After code change I.U.
Mixed-up I.U. I.U.
I.U.
A I.U.
B
C
D
I.U.
I.U.
I.U.
A
B
C
D
• Code selector switch eliminates unit being wrongly switched. (Up to 4 codes can be set.) *I.U.=Indoor unit
- (05 - 25) -
5. CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping.
FUNCTIONS (UTY-LNHUM) 1
MODE button Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT). /Start / end R.C. custom code change. (Max 4 types)
16
2
MIN.HEAT button
3
Set temp. button ( ▲ / ▼ ) Set remote controller custom code buttons Sets the indoor temp./ Sets R.C. custom code.
4
ECONOMY button
5
SLEEP button Pressed to select sleep timer.
6 1
6
3
7
2
8
4
9
5
10
FAN button Selects the fan speed (AUTO, HIGH, MED, LOW, QUIET).
7
START/STOP button
8
SET button (Vertical)
Pressed to start and stop operation. Air flow direction vertical set button.
9
SET button (Horizontal) Air flow direction horizontal set button.
10 SWING button 11 13
Air flow direction swing button. 14 12 15
11 TIMER MODE button Pressed to select the timer mode. (OFF TIMER, ON TIMER, PROGRAM TIMER, TIMER RESET)
12 TIMER SET ( + / - ) button CONTROL SYSTEM
CONTROL SYSTEM
Sets the current time and on-off time.
13 CLOCK ADJUST button Sets the current time.
14 RESET button Used when replacing batteries.
15 TEST RUN button Used when testing the air conditioner after installation.
Display panel
16 Signal transmitter 17 Temperature set display
17 20
18 Operating mode display 19 Sleep display 20 Transmit indicator
18
21
21 Fan speed display 22 Swing display
22
23 Timer mode display 24 Clock display
19
23
24
Note: Functions will be different due to type of indoor unit. For details, please see operation manual.
- (05 - 26) -
5. CONTROL SYSTEM
FUNCTIONS (AR-RAH1U) 1
MODE button Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT). /Start / end R.C. custom code change. (Max 4 types)
15
2
MIN.HEAT button
3
Set temp. button ( ▲ / ▼ ) Set remote controller custom code buttons Sets the indoor temp./ Sets R.C. custom code.
4
ECONOMY button
5
SLEEP button Pressed to select sleep timer.
6 1
6
3
7
FAN button Selects the fan speed (AUTO, HIGH, MED, LOW, QUIET).
7
START/STOP button
8
SET button (Vertical)
Pressed to start and stop operation. 2 4
8
5
9
Air flow direction vertical set button.
9
Air flow direction swing button.
10 TIMER MODE button
10 12
SWING button
Pressed to select the timer mode. (OFF TIMER, ON TIMER, PROGRAM TIMER, TIMER RESET) 13 11 14
11 TIMER SET ( + / - ) button Sets the current time and on-off time.
12 CLOCK ADJUST button
Used when replacing batteries.
14 TEST RUN button Used when testing the air conditioner after installation.
15 Signal transmitter 16 Temperature set display
Display panel
17 Operating mode display 18 Sleep display
16 19
19 Transmit indicator 20 Fan speed display
17
21 Swing display 20
22 Timer mode display 23 Clock display
21
18
22
23
Note: Functions will be different due to type of indoor unit. For details, please see operation manual.
- (05 - 27) -
5. CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM
Sets the current time.
13 RESET button
SYSTEM DIAGRAM
Signal transmitter
Signal receiver window
● Control signal might not be recognized in following cases: (i) A curtain or a wall, etc. exists between transmitter and receiver. (ii) There is an instant-start type (inverter type, etc.) fluorescent lamp in the room. ● Air conditioner might not work correctly when strong light hits the signal receiver window. Shut off the direct sunlight and also make illuminator far away from the receiver window.
DIMENSIONS Controller Unit : in. (mm)
CONTROL SYSTEM
6-11/16 (170)
CONTROL SYSTEM
Top View
3/4 (19)
2-7/32 (56)
Front View
Side View
Rear View
Holder 1 (25.5)
2-3/8 (60.4) 1-3/16 (30.2)
6-3/32 (154.7)
3-3/4 (95)
Ø1/8 (3.5) (HOLE)
1/8 x 1/4 (3.5 x 6.5) (HOLE)
1-1/32 (26.2)
Front View
Side View
- (05 - 28) -
Bottom View
5. CONTROL SYSTEM
PACKING LIST Name and shape
Quantity
Installation manual
1
Operating manual
1
Remote controller holder
1
Tapping screw
2
Battery [ 1.5V (R03 / AAA) ]
2
Application
Use as remote controller holder For remote controller holder installation
For remote controller
SPECIFICATIONS Weight : oz. (g)
3 (85) [w/o batteries]
CONTROL SYSTEM
6-11/16 (170) x 2-7/32 (56) x 3/4 (19)
CONTROL SYSTEM
Dimensions [H x W x D]: in. (mm)
- (05 - 29) -
5. CONTROL SYSTEM
2-5. IR RECEIVER UNIT MODEL : UTY - LRHUM FEATURES Duct type indoor unit can be controlled with wireless remote controller if the IR receiver unit is used.
FUNCTIONS Wireless remote controller IR Receiver
MANUAL AUTO SIGNAL RECEIVER Refer to 2-4.WIRELESS REMOTE CONTROLLER for details.
SYSTEM DIAGRAM ATTACHMENT RANGE 1)
L
L
1)
1) Connection cable length L Cable A (standard accessory) : 16ft. (5 m) Cable C (Optional parts) : 33ft. (10 m)
SIGNAL ANGLE
120
120
16ft. (5m)
16ft. (5m)
- (05 - 30) -
5. CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM
OPERATION LAMP TIMER LAMP ECONOMY LAMP
ELECTRICAL WIRING Connected to CN13 of PCB
PCB CN13
Connection cable B [L = 7-7/8in. (0.2m)] ...Standard accessory
Connection cable A [L = 16ft. (5m)]...Standard accessory Connection cable C [L = 33ft. (10m)]...Optional service parts
2-3/8in. x 4-3/4in. (60mm x 120mm) hole
Connected to Connection cable Connected to IR Receiver Unit
IR Receiver Unit
DIMENSIONS Unit : in. (mm)
/32
Side View
Rear View
21/32 (17)
CONTROL SYSTEM
3-9
Front View
(83
.5)
5-23/32 (145)
2-3/8 (60)
CONTROL SYSTEM
9/32 (7.2)
4-21/32 (118.4)
9/32 (7.2)
3-17/32 (90)
17/32 (13.6) 29/32 (22.9)
2-1/4 (57.4)
2-27/32 (72.4)
17/32 (13.6)
2-9/32 (57.6)
7/16 23/32 (11.5) (18.5) 11/32 (8.5)
- (05 - 31) -
5. CONTROL SYSTEM
PACKING LIST Quantity
Application
Installation manual
1
Operating manual
1
Cover
1
For covering receiver unit
Insulation
1
For protecting PCB from dust
Connection cable A [16ft. (5m)]
1
For connecting PCB of indoor unit to receiver unit
Connection cable B [7-7/8in. (0.2m)]
1
For connecting PCB of indoor unit to receiver unit
Bracket (cover)
1
For fixing receiver unit to the wall or ceiling
Screw (M3 x 12mm)
2
For installing remote control unit holder to the wall
Screw (M4 x 20mm)
2
For installing receiver unit to the wall or ceiling
Battery (R03/LR03)
2
For remote controller
Remote controller holder
1
Use as remote controller holder
SPECIFICATIONS (IR Receiver) Dimensions [H x W x D]: in. (mm)
5-23/32 (145) x 3-17/32 (90) x 1-3/16 (30)
Weight: oz. (g)
5.3 (150)
OPTIONAL SERVICE PARTS Please use the parts number shown below to order the cable from your sales representative. Select shielded type conncetion cable in accordance with the standard of the country. Name and shape Connection cable C [33ft. (10m)]
Parts No. 9707598025
- (05 - 32) -
5. CONTROL SYSTEM
CONTROL SYSTEM
CONTROL SYSTEM
Name and shape
2-6. GROUP CONTROL METHOD REMOTE CONTROLLER GROUP Wired, Simple and Wireless Remote Controllers can be used jointly in the following combinations.
CONTROL SYSTEM
CONTROL SYSTEM
Example of combination for "Remote controller group"
- (05 - 33) -
5. CONTROL SYSTEM
2-7. COMPARISON TABLE OF CONTROLLERS
Item
Central Remote Controller
Wired Remote Controller
Simple Remote Controller
Wireless Remote Controller
Model
UTY-DMMUM
UTY-RNNUM
UTY-RSNUM
UTY-LNHUM AR-RAH1U
8
1
1
1
Room temp. setting
● ● ● ●
Test operation
–
● ● ● ● ●
Up / down air direction flap setting
–
● ● ● ● ● ● ●
● ● ● ● ● ● ● / – *1
–
Max. controllable indoor units
Display
Operation mode setting Fan speed setting
–
RC prohibition
● ● ●
–
–
–
–
●
–
● ●
Low noise mode setting for outdoor unit (Outdoor Unit Quiet)
●
–
–
–
Failure
● –
● ●
–
Defrosting Current time
● ● ●
–
●
Min. heat setting Economy setting
–
●
● ● ● ● ● ● ●
–
–
On / Off per day
2
2
–
–
On / Off per week
14
14
–
–
On / Off timer
–
●
–
Sleep timer
–
–
–
Program timer
–
–
–
● ● ●
Day off
●
●
–
–
Status monitoring system
●
–
–
–
Error history
–
●
●
–
Day of week Address display Weekly timer
Timer
–
Right / left air direction flap setting
RC prohibition
Control
CONTROL SYSTEM
Air conditioning control function
Start/Stop
–
–
–
–
● ●
– –
*1: This function is not provided in AR-RAH1U.
- (05 - 34) -
5. CONTROL SYSTEM
CONTROL SYSTEM
LIST OF CONTROLLER FUNCTION
Hybrid Flex Inverter System
6. SYSTEM DESIGN
DTR_BMU001E_04--CHAPTER06 2010.10.04
CONTENTS 6. SYSTEM DESIGN 1. SYSTEM DESIGN ......................................................................... 06 - 01 1-1. SYSTEM OUTLINE ................................................................................ 06 - 01 1-2. REFRIGERANT SYSTEM ...................................................................... 06 - 02 1-3. WIRING SYSTEM................................................................................... 06 - 07 1-4. MOUNTING POSITION .......................................................................... 06 - 08
2. PIPING DESIGN ............................................................................ 06 - 10 2-1. IMPORTANT ITEMS WHEN USING NEW REFRIGERANT (R410A) ... 06 - 10 2-2. PIPING LIMITATION .............................................................................. 06 - 12 2-3. PIPE SIZE............................................................................................... 06 - 14 2-4. SELECTION OF PIPE HEAT INSULATING MATERIAL ....................... 06 - 16 2-5. ADDITIONAL CHARGE CALCULATION .............................................. 06 - 17 2-6. EXAMPLE OF PIPING DESIGN ............................................................ 06 - 18
3. INSTALLATION ............................................................................. 06 - 26 3-1. OUTDOOR UNIT .................................................................................... 06 - 26 3-2. SEPARATION TUBE .............................................................................. 06 - 29 3-3. BRANCH BOX ....................................................................................... 06 - 31
4. WIRING DESIGN ........................................................................... 06 - 37 4-1. ELECTRICAL WIRING ........................................................................... 06 - 37 4-2. POWER SUPPLY CABLE WIRING ........................................................ 06 - 39 4-3. TRANSMISSION LINE ........................................................................... 06 - 43 4-4. CONTROLLER CABLE WIRING ........................................................... 06 - 46
5. FUNCTION SETTING .................................................................... 06 - 50 5-1. OUTDOOR UNIT .................................................................................... 06 - 50 5-2. INDOOR UNIT (setting by jumper wire)............................................... 06 - 54 5-3. INDOOR UNIT (setting by wireless remote controller) ...................... 06 - 55 5-4. INDOOR UNIT (setting by wired remote controller) ........................... 06 - 60 5-5. INDOOR UNIT (setting by simple remote controller) ......................... 06 - 64 5-6. FUNCTION DETAILS ............................................................................. 06 - 68 5-7.
CENTRAL REMOTE CONTROLLER .................................................... 06 - 71
5-8. WIRED REMOTE CONTROLLER.......................................................... 06 - 74 5-9. SIMPLE REMOTE CONTROLLER ........................................................ 06 - 77
CONTENTS 6. SYSTEM DESIGN 5-10. DUCT STATIC PRESSURE SETTING ................................................... 06 - 80
6. CHECK RUN .................................................................................. 06 - 81 6-1. PRECAUTIONS & PREPARATION ....................................................... 06 - 81 6-2. CHECK RUN CHECK ITEMS AND PROCEDURE ................................ 06 - 83 6-3. CHECK RUN EXAMPLES ..................................................................... 06 - 84 6-4. RELOCATION AND INCREASE OF UNIT............................................. 06 - 88
7. EXTERNAL INPUT & OUTPUT..................................................... 06 - 89 7-1. OUTDOOR UNIT .................................................................................... 06 - 89 7-2. INDOOR UNIT ........................................................................................ 06 - 98
8. DRAIN CONNECTION ................................................................. 06 - 104 8-1. OUTDOOR UNIT ................................................................................... 06 - 104 8-2. INDOOR UNIT ....................................................................................... 06 - 105
9. STANDARD ACCESSORIES ....................................................... 06 - 111 9-1. OUTDOOR UNIT ................................................................................... 06 - 111 9-2. INDOOR UNIT ....................................................................................... 06 - 112
10.
OPTIONAL PARTS INSTALLATION....................................... 06 - 115
10-1. FRESH AIR INTAKE KIT ...................................................................... 06 - 115
11.
REFRIGERANT LEAKAGE CAUTION ................................... 06 - 126
11-1. INTRODUCTION ................................................................................... 06 - 126 11-2. CHECKING CONCENTRATION LIMIT ................................................. 06 - 127
12.
INSTALLATION PRECAUTIONS ............................................ 06 - 129
12-1. INDOOR UNIT INSTALLATION PRECAUTIONS ................................. 06 - 129 12-2. OUTDOOR UNIT INSTALLATION PRECAUTIONS ............................. 06 - 132
1. SYSTEM DESIGN 1-1. SYSTEM OUTLINE Branch box 3 (Secondary)
8 Indoor units
6 Circuit breaker (over current) Earth leakage breaker Power supply
Branch box 2 (Secondary)
6 Circuit breaker (over current) Earth leakage breaker Power supply
8
Branch box 1 (Primary)
2
6 Circuit breaker (over current)
Outdoor unit
Earth leakage breaker
Central remote controller
7
3 1
5
Circuit breaker (over current)
Power supply
4
SYSTEM DESIGN
SYSTEM DESIGN
Power supply
Earth leakage breaker
) 1: Transmission line [O.U. - B.B.(primary)] ( ) 2: Transmission line [B.B.(primary) - B.B.(secondary] ( 3: Central remote controller line [Central remote controller - B.B.] ( ) 4: Power supply and Transmission line [B.B. - I.U.] ( ) 5: Power supply [Outdoor Unit] ( ) 6: Power supply [Branch Box] ( ) 7: Remote controller line [I.U. - R.C.] ( ) 8: Piping (
- (06 - 01) -
)
6. SYSTEM DESIGN
1-2. REFRIGERANT SYSTEM CONNECTABLE UNIT WITHIN 1 REFRIGERANT SYSTEM Unit
Quantity
Remarks
Outdoor unit
1 unit
Indoor unit
2 to Max. 8 units
Connectable indoor unit capacity : 80% to 130%
Branch box
1 to Max. 3 units
One Branch box of primary type is always necessary
Caution
SYSTEM DESIGN
SYSTEM DESIGN
● When all indoor units are operating at maximum capacity, individual indoor unit operate at a slightly lower capacity. (When connecting more than 100%) ● Do not exceed both of "connectable capacity range" and "maximum connectable indoor unit", otherwise it may cause hinder the return of the refrigerant oil and cause a compressor breakdown.
- (06 - 02) -
6. SYSTEM DESIGN
EXAMPLE OF REFRIGERANT SYSTEM Example 1 (OK) Branch box 1 (Primary type) Outdoor unit
Capacity ratio 88%
Indoor unit 1 Indoor unit 2
Model Outdoor unit AOU48 Indoor unit 1 ARU24 Indoor unit 2 ARU18 Branch box 1 UTP-PU03A
Capacity (BTU/h) 48000 24000 18000 -
Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000 2 80% 3 130% 1 42000 -
Judgement 2≤ 1≤ 3
38400
62400
38400 < 42000 < 62400 → OK
-
-
-
Example 2 (OK) Branch box 1 (Primary type)
Capacity ratio 125%
SYSTEM DESIGN
Indoor unit 1 Indoor unit 2 Indoor unit 3
Model Outdoor unit AOU48 Indoor unit 1 ARU24 Indoor unit 2 ARU24 Indoor unit 3 ARU12 Branch box 1 UTP-PU03A
Capacity (BTU/h) 48000 24000 24000 12000 -
Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000 2 80% 3 130%
Judgement
2≤ 1≤ 3
1 60000
38400
62400
38400 < 60000 < 62400 → OK
-
-
-
-
- (06 - 03) -
6. SYSTEM DESIGN
SYSTEM DESIGN
Outdoor unit
Example 3 (OK)
Outdoor unit
Indoor unit 1
Model Outdoor unit AOU48 Indoor unit 1 ARU18 Indoor unit 2 ARU12 Indoor unit 3 ARU9 Indoor unit 4 ARU9 Indoor unit 5 ARU9 Branch box 1 UTP-PU03A Branch box 2 UTP-PU03B
Branch box 1
Branch box 2
(Primary type)
(Secondary type)
Indoor unit 2
Capacity (BTU/h) 48000 18000 12000 9000 9000 9000 -
Indoor unit 3
Indoor unit 4
Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000 1 57000
Capacity ratio 119%
Indoor unit 5
Judgement
2 80%
3 130%
2≤ 1≤ 3
38400
62400
38400 < 57000 < 62400 → OK
-
-
-
-
-
Outdoor unit
Indoor unit 1
Branch box 1
Branch box 2
Branch box 3
(Primary type)
(Secondary type)
(Secondary type)
Indoor unit 2
Indoor unit 3
Indoor unit 4
Indoor unit 5
Indoor unit 6
Indoor unit 7
Indoor unit 8
Capacity ratio 117% Model Outdoor unit AOU48 Indoor unit 1 ASU7 Indoor unit 2 ASU7 Indoor unit 3 ASU7 Indoor unit 4 ASU7 Indoor unit 5 ASU7 Indoor unit 6 ASU7 Indoor unit 7 ASU7 Indoor unit 8 ASU7 Branch box 1 UTP-PU03A Branch box 2 UTP-PU03B Branch box 3 UTP-PU03B
Capacity (BTU/h) 48000 7000 7000 7000 7000 7000 7000 7000 7000 -
Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000
1 56000
-
Judgement
2 80%
3 130%
2≤ 1≤ 3
38400
62400
38400 < 56000 < 62400 → OK
-
-
-
- (06 - 04) -
-
6. SYSTEM DESIGN
SYSTEM DESIGN
SYSTEM DESIGN
Example 4 (OK)
Example 5 (Not good) Branch box 1 (Primary type) Outdoor unit
Indoor unit 1
Model
Capacity (BTU/h)
Outdoor unit
AOU48
48000
Indoor unit 1
ARU24
24000
Branch box 1 UTP-PU03A
Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000 2 80% 3 130% 1 24000 -
-
38400
62400
-
-
Judgement Not good → Because only one indoor unit is connected -
Example 6 (Not good) Branch box 1 (Primary type) Outdoor unit
SYSTEM DESIGN
Model Outdoor unit AOU48 Indoor unit 1 ARU24 Indoor unit 2 ARU12 Branch box 1 UTP-PU03A
Capacity (BTU/h) 48000 24000 12000 -
Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000 2 80% 3 130% 1 36000 -
Judgement 1
View more...
Comments