Fujitsu Hybrid Flex Inverter HFI Mini Split Systems Design Manual

December 24, 2016 | Author: e-ComfortUSA | Category: N/A
Share Embed Donate


Short Description

Fujitsu HFI AOU48RLXZ Eight Zone Ductless Mini Split Heat Pump Outdoor Unit Ideal solution for multi-room system, you ca...

Description

DTR_BMU001E_05 VD014E/06

DESIGN & TECHNICAL MANUAL

Hybrid Flex Inverter System

FUJITSU GENERAL LIMITED

CONTENTS 1. GENERAL INFORMATION 2. MODEL SELECTION 3. OUTDOOR UNITS 4. INDOOR UNITS 5. CONTROL SYSTEM 6. SYSTEM DESIGN 7. OPTIONAL PARTS

Hybrid Flex Inverter System

1. GENERAL INFORMATION

DTR_BMU001E_03--CHAPTER01 2010.08.25

CONTENTS 1. GENERAL INFORMATION 1. FEATURES OF SYSTEM ............................................................. 01 - 01 1-1.HIGH EFFICIENCY & COMPACT ............................................................. 01 - 01 1-2.FLEXIBLE DESIGN & EASY INSTALLATION.......................................... 01 - 02 1-3. CENTRAL CONTROL ............................................................................... 01 - 05

2. MODEL LINE UP .......................................................................... 01 - 07 2-1.OUTDOOR UNIT ....................................................................................... 01 - 07 2-2.INDOOR UNIT ........................................................................................... 01 - 08 2-3.CONTROLLER .......................................................................................... 01 - 09 2-4.SEPARATION TUBE ................................................................................. 01 - 10 2-5.BRANCH BOX........................................................................................... 01 - 10 2-6.OTHERS ....................................................................................................01 - 11

GENERAL INFORMATION

GENERAL INFORMATION

1. FEATURES OF SYSTEM 1-1. HIGH EFFICIENCY & COMPACT  HIGH EFFICIENCY Adopting a large heat exchanger, high efficiency ventilation fan, DC twin rotary compressor, etc. realizes high efficiency operation. Cooling

SEER:17.0

Heating

HSPF:9.8

3.89

0.0

15.0

16.0

17.0

SEER

0.0

8.0

9.0

10.0

HSPF

TOP CLASS

 TOP CLASS COMPACT DESIGN Compact and lightweight outdoor unit is easy to carry in, it can be installed unnoticeably in various places. About 48000Btu class

New model

Height difference

29%

50-25/32in. (1290mm)

36in. (914mm)

 INNOVATIVE TECHNOLOGY High efficiency large fan: New high efficiency fan is mounted.

DC Fan motor: High performance and high efficiency has been realized by using a small DC fan motor.

Heat exchanger: Reduced compact size and energy saving has been realized by utilizing high density piping design and 3-Row heat exchanger.

7 segment display: Easy –to-read 7 segment LED display which explains operational and trouble status.

High efficiency DC twin rotary Compressor: A high perforamnce, low noise, large capacity DC twin rotary compressor is used.

- (01 - 01) -

1. GENERAL INFORMATION

 FLEXIBLE DESIGN ● 4 types, 12models of indoor units can be selected ranging from 7000BTU to 24000BTU in capacity. Compact Cassette

Slim Duct

Compact Wall Mounted

Wall Mounted

● Up to 8 indoor units can be connected to one outdoor unit. ● A maximum of 130% indoor unit connectable capacity. Match any room layout. Connectable indoor unit capacity

Connectable indoor unit

80 to 130%

2 to 8

For any room layout-connectable capacity of indoor units is max 130%

Total pipe length

Actual pipe length

377ft. max

230ft. max

(115m)

(70m)

Can be installed in high rise condominium or commercial building. • Height difference between O.U and I.U 98ft.(30m) max. • Height difference between I.U and I.U 49ft.

- (01 - 02) -

(15m)

max.

1. GENERAL INFORMATION

GENERAL INFORMATION

GENERAL INFORMATION

1-2. FLEXIBLE DESIGN & EASY INSTALLATION

GENERAL INFORMATION

GENERAL INFORMATION

 EASY INSTALLATION ● Corresponding to diverse installation environments by use of branch connection system.

Current model : 4 Rooms multi x 2

New model

Branch box

 BRANCH BOX ● Branch box has an electronic expansion valve built-in, so it can control the refrigerant flow to each indoor unit. ● Can be connected by flare connection and both ceiling suspension and wall mounting installation are available.

Primary type: UTP-PU03A Secondary type: UTP-PU03B

 Allowed branch box mounting direction Ceiling suspension

By reversing the electrical box position you can orient the inlet and outlet pipes into a left hand or right hand configuration,

Horizontal wall mounted

By reversing the electrical box position you can orient the inlet and outlet pipes into a left hand or right hand configuration.

- (01 - 03) -

Vertical wall mounted

You cannot reverse the electrical box position when mounting the branch box vertically.

1. GENERAL INFORMATION

GENERAL INFORMATION

GENERAL INFORMATION

 DECREASE OF INSTALLATION MISTAKE ● This operation allows the air conditioner to automatically check the status of the outdoor unit and check for wiring mistakes.

 Installation procedure Refrigerant piping and electrical wiring work All Flare connection Sealing test

Vacuum process Refrigerant piping & Electric wiring

Additional refrigerant charging

Indoor unit function setting

Check run

Test run

Installation mistakes and positions where errors are occurring are shown by the outdoor unit display indicators.

 Check item ● Check communication ● Check the number of connected indoor units ● Check wiring and piping connection

 SERVICE MAINTENANCE  7 segment LED display Operation mode

Error display

Operating information

Example

Easy –to-read 7 segment LED display which explains operating and trouble status.

- (01 - 04) -

1. GENERAL INFORMATION

Support comfort control system for the varied needs of the home and the condominium, etc.

● Central remote controller is connected directly to the branch box, making the installation process easier. ● Once the controller is connected, it can automatic register and display all the indoor units.

 CENTRAL REMOTE CONTROLLER (Option) Controllable 1 Multi system

Max. controllable 8 indoor units UTY-DMMUM ● Large and full-dot liquid crystal screen ● Screen with backlight can be seen even in the dark ● Wide and large keys easy to press, user-intuitive arrow key - (01 - 05) -

1. GENERAL INFORMATION

GENERAL INFORMATION

GENERAL INFORMATION

1-3. CENTRAL CONTROL

Air conditioning load factor

● Users can choose from 4 low noise levels, depending on the installation environment.

Heat load

100%

Down

Capacity 0 58dB

Operating sound

0

(time) Low noise operation

 Minimum heat (All) operation ● While this function is selected, all indoor units start the minimum heat operation when all the indoor units are stopped by operation of the [On/Off button]. ● When the room temperature is higher than 50°F (10°C), MIN. HEAT operation starts and maintains the room temperature at 50°F (10°C) when the temperature drops below 50°F (10°C). ● When “MIN, HEAT operation stops, the room set temperature quickly returns to the preset temperature.

All indoor units OFF “All MIN. HEAT” operation ON

70°F Indoor unit operation START

50°F

 Economy (All) operation Temp.

Example : Cooling operation

● If all the indoor and outdoor units are changed to economy mode, this can save more energy than setting of each indoor unit individually. ● Economy operation is energy saving, as the set temperature of indoor unit is shifted by 2°F (1°C) and the maximum electric value of the outdoor unit is suppressed.

Economy operation Shift setting temp

Set temperature

Nomal operation

Time

Control maxmum current

 Schedule timer Example Temp. Cool

PM12

Cool

PM5

Heat

Heat AM7

PM12 PM1

Cool

PM11 Time

AM8

Cool

PM1

Cool PM6

● Operation setting can be changed 4 times in each day of a week, and 2types of the schedule can be set to suit users' preference.

PM10 Time

Temp.

Cool AM7

Winter season pattern

Saturday~Sunday

Temp.

Monday~Friday

Summer season pattern

Heat

Heat PM11 Time

AM7

PM1

Heat PM6

- (01 - 06) -

Heat PM11 Time

1. GENERAL INFORMATION

GENERAL INFORMATION

 Outdoor unit low noise operation

Temp.

GENERAL INFORMATION

 VARIOUS OPERATION MODES SET BY REMOTE CONTROLLER

GENERAL INFORMATION

GENERAL INFORMATION

2. MODEL LINE UP 2-1. OUTDOOR UNIT  LINE UP HP

Capacity (BTU/h)

Model name

Connectable indoor unit

5

48000

AOU48RLXFZ

2 to 8

 MODEL DESIGNATION 1

2

3

4

5

6

7

8

9

10

A

O

U

4

8

R

L

X

F

Z

Function L: Inverter

Function X: Extended line set

Type AO : Outdoor unit

Destination U: FUJITSU

Model code (BTU/h) 48 : (48000)

Function R: Heat pump

- (01 - 07) -

Function F: Flexible

Function Z: Zoning

1. GENERAL INFORMATION

GENERAL INFORMATION

GENERAL INFORMATION

2-2. INDOOR UNIT  LINE UP Various combinations of types and capacity 4 types 12 models, ranging from 7000BTU to 24000BTU. Capacity BTU/h 7000

Compact Cassette

Model code 7

9000

9

12000

12

18000

18

24000

24

Slim Duct

Compact Wall Mounted Wall Mounted

Compact Cassette

Compact Wall Mounted

Slim Duct ARU9RLF ARU12RLF ARU18RLF ARU24RLF

AUU9RLF AUU12RLF AUU18RLF

ASU7RLF ASU9RLF ASU12RLF

Wall Mounted ASU18RLF ASU24RLF

 MODEL DESIGNATION 1

2

3

4

5

6

7

8

A

S

U

1

8

R

L

F

Function L: Inverter

Function F: Flexible

Type AU: Cassette AR: Duct AS: Wall Mounted

Destination U: FUJITSU

Model code (BTU/h) 7 (7000) 9 (9000) 12 (12000) 18 (18000) 24 (24000)

Function R: Heat pump

- (01 - 08) -

1. GENERAL INFORMATION

GENERAL INFORMATION

GENERAL INFORMATION

2-3. CONTROLLER  LINE UP

Central remote controller

Indoor units Compact Model Compact Wall Wall Cassette Slim Duct mounted mounted  *1  *1  *1  *1 UTY-DMMUM

Wired Remote Controller

UTY-RNNUM





 *2



UTY-LNHUM



-

-



AR-RAH1U

-

-



-

IR Receiver Unit

UTY-LRHUM

-



-

-

Simple Remote Controller

UTY-RSNUM





 *2



Type

Wireless Remote Controller

: Accessory, : Optional, -: It is not possible to connect it. *1: Central remote controller is connected to Branch Box. *2: Optional Communication kit (UTY-XCBXZ1) is necessary for the installation.

 CENTRAL CONTROL Central remote controller

 INDIVIDUAL CONTROL Wired Remote Controller

Simple Remote Controller

Wireless Remote Controller

UTY-LNHUM

AR-RAH1U

IR Receiver Unit

- (01 - 09) -

1. GENERAL INFORMATION

GENERAL INFORMATION

GENERAL INFORMATION

2-4. SEPARATION TUBE Separation tube Model : UTP-SX248A Liquid pipe

Gas pipe

2-5. BRANCH BOX Primary type Model : UTP-PU03A

Secondary type Model : UTP-PU03B

- (01 - 10) -

1. GENERAL INFORMATION

GENERAL INFORMATION

GENERAL INFORMATION

2-6. OTHERS  LINE UP Type

Model

Indoor units Compact Compact Wall Wall Cassette Slim Duct mounted mounted  -

Outdoor unit

Grill kit

UTG-CCGF

Air outlet shutter plate

UTR-YDZB



-

-

-

-

Insulation kit for high humidity

UTZ-KXGC



-

-

-

-

Fresh air intake kit

UTZ-VXAA



-

-

-

-

External control set

UTD-ECS5A

-



-

-

-

External connect kit

UTY-XWZX



-

 *1



-

External connect kit

UTY-XWZXZ3

-

-

-

-



External connect kit (For Base heater)

UTY-XWZXZ4

-

-

-

-



UTR-FA16

-

-



-

-

UTR-FA13-1

-

-

-



-

UTR-FA16-2

-

-



-

-

UTR-FA13-2

-

-

-



-

UTY-XCBXZ1

-

-



-

-

Apple catechin filter

Ion deodorisation filter Communication kit

-

: Optional, -: It is not possible to connect it. *1: Optional Communication kit (UTY-XCBXZ1) is necessary for the installation

- (01 - 11) -

1. GENERAL INFORMATION

GENERAL INFORMATION

GENERAL INFORMATION

 PARTS Grille kit

Air outlet shutter plate Model : UTG-CCGF

Models : UTR-YDZB

For Compact Cassette type For Compact Cassette type

Insulation kit for high humidity Model : UTZ-KXGC

Fresh air intake kit Model : UTZ-VXAA

Insulation Kit

For Compact Cassette type

For Compact Cassette type

External control set

External connect kit Model : UTD-ECS5A

(x1)

(x2)

(x1)

(x2)

Model : UTY-XWZX

(x1)

(x1)

For Compact Cassette / Compact Wall Mounted / Wall Mounted

For Slim Duct type

External connect kit Model : UTY-XWZXZ3

External connect kit (For Base heater)

For Outdoor unit

Model : UTY-XWZXZ4

For Outdoor unit

- (01 - 12) -

1. GENERAL INFORMATION

GENERAL INFORMATION

GENERAL INFORMATION

 PARTS Apple catechin filter

Apple catechin filter Model : UTR-FA16

Model : UTR-FA13-1

For Compact wall mounted type For Wall mounted type

Ion deodorisation filter

Ion deodorisation filter Model : UTR-FA16-2

Model : UTR-FA13-2

For Compact wall mounted type For Wall mounted type

Communication kit Model : UTY-XCBXZ1

For Compact wall mounted type

- (01 - 13) -

1. GENERAL INFORMATION

Hybrid Flex Inverter System

2. MODEL SELECTION

DTR_BMU001E_04--CHAPTER02 2010.10.04

CONTENTS 2. MODEL SELECTION 1. MODEL SELECTION PROCEDURE............................................ 02 - 01 2. MODEL LINE UP .......................................................................... 02 - 02 2-1.OUTDOOR UNIT ....................................................................................... 02 - 02 2-2.INDOOR UNIT ........................................................................................... 02 - 02 2-3.OPTIONAL PARTS.................................................................................... 02 - 02

3. MODEL SELECTION AND CAPACITY CALCULATION ............. 02 - 04 3-1.SELECTION PROCEDURE OF INDOOR UNIT AND OUTDOOR UNIT .. 02 - 04 3-2.THE EXAMPLE OF CALCULATION ......................................................... 02 - 05 3-2-1. COOLING EXAMPLE .............................................................................................. 02 - 05 3-2-2. HEATING EXAMPLE ............................................................................................... 02 - 09

4. CAPACITY TABLE ....................................................................... 02 - 13 4-1.COOLING CAPACITY ............................................................................... 02 - 13 4-2.HEATING CAPACITY ................................................................................ 02 - 15

5. CAPACITY COMPENSATION COEFFICIENT ............................. 02 - 17 5-1.COMPENSATION COEFFICIENT OF PIPE LENGTH .............................. 02 - 17 5-2.COMPENSATION COEFFICIENT OF FROSTING / DEFROSTING ......... 02 - 18

1. MODEL SELECTION PROCEDURE See 2-2.MODEL LINE UP(INDOOR UNIT) and 3-1. SELECTION PROCEDURE OF INDOOR UNIT AND OUTDOOR UNIT

Selection of required optional parts ● Grill kit for Compact Cassette type

See 2-3.MODEL LINE UP(OPTIONAL PARTS)

Selection of Branch box

See 2-3.MODEL LINE UP(OPTIONAL PARTS)

Selection of Separation tube See 2-3.MODEL LINE UP(OPTIONAL PARTS)

Selection of controller units ● Central Remote Controller ● Wired Remote Controller ● Simple Remote Controller ● Wireless Remote Controller ● IR Receiver Unit

Selection of other optional parts ● Air Outlet Shutter Plate ● Insulation Kit for High humidity ● Fresh air intake kit ● External Control Set ● External Connect Kit ● Apple catechin filter ● Ion deodorisation filter ● Communication kit

See 2-3.MODEL LINE UP(OPTIONAL PARTS)

See 2-3.MODEL LINE UP(OPTIONAL PARTS)

END

- (02 - 01) -

2. MODEL SELECTION

MODEL SELECTION

MODEL SELECTION

Selection of indoor units

2. MODEL LINE UP 2-1. OUTDOOR UNIT

5

Capacity (BTU/h) Cooling

Heating

48000

54000

Connectable indoor unit

Model name AOU48RLXFZ

Number

Capacity (%)

2 to 8

80 to 130

MODEL SELECTION

MODEL SELECTION

HP

2-2. INDOOR UNIT Rated capacity (BTU/h) Cooling Heating 9000 10200 Compact 12000 13500 Cassette 18000 20000 9000 10200 12000 13500 Slim Duct 18000 20000 24000 27000 7000 8100 Compact Wall 9000 10200 Mounted 12000 13500 18000 20000 Wall Mounted 24000 27000 Type

Model name AUU9RLF AUU12RLF AUU18RLF ARU9RLF ARU12RLF ARU18RLF ARU24RLF ASU7RLF ASU9RLF ASU12RLF ASU18RLF ASU24RLF

Remarks UTG-CCGF (Grille kit)

2-3. OPTIONAL PARTS  BRANCH BOX Items Primary type Secondary type

Model name UTP-PU03A UTP-PU03B

Remarks

Model name UTP-SX248A

Remarks

 SEPARATION TUBE Items Separation tube

 CONTROLLER Items Central Remote Controller Wired Remote Controller Simple Remote Controller Wireless Remote Controller IR Receiver Unit

Model name Remarks UTY-DMMUM UTY-RNNUM Accessory: Compact Cassette, Slim Duct UTY-RSNUM UTY-LNHUM Accessory: Wall Mounted AR-RAH1U Accessory: Compact Wall Mounted UTY-LRHUM

- (02 - 02) -

2. MODEL SELECTION

 OTHERS Model name

Grill kit

UTG-CCGF

Air outlet shutter plate

UTR-YDZB

Insulation kit for high humidity

UTZ-KXGC

Fresh air intake kit

UTZ-VXAA

External control set

UTD-ECS5A

External connect kit

UTY-XWZX

External connect kit

UTY-XWZXZ3

External connect kit (For Base heater)

UTY-XWZXZ4

Apple catechin filter

Ion deodorisation filter Communication kit

Remarks MODEL SELECTION

MODEL SELECTION

Items

Refer to "7. OPTIONAL PARTS"

UTR-FA16 UTR-FA13-1 UTR-FA16-2 UTR-FA13-2 UTY-XCBXZ1

- (02 - 03) -

2. MODEL SELECTION

3. MODEL SELECTION AND CAPACITY CALCULATION 3-1. SELECTION PROCEDURE OF INDOOR UNIT AND OUTDOOR UNIT MODEL SELECTION

MODEL SELECTION

Please select indoor units and outdoor units and make the capacity of each indoor unit be larger than cooling and heating load. 1 Calculate heat load of each room

2 Tentative selection of indoor units

3 Calculate the total cooling capacity or heating capacity of indoor units The total cooling capacity or heating capacity of indoor units = The sum of capacity of indoor units x Capacity change rate by suction temperature of indoor unit : Calculate by the value of the outdoor temperature 95°F when cooling, 47°F when heating.

4 Tentative selection of outdoor unit

5 Calculate the Maximum cooling capacity or heating capacity of outdoor unit The maximum cooling capacity or heating capacity of outdoor unit = Capacity of outdoor unit calculated from total of indoor unit rated capacity with capacity table x Capacity change rate by temperature conditions (Calculate by the value of indoor units connecting capacity in 100%) x Capacity change rate by indoor units connecting capacity : Calculate by the value of standard temperature conditions (When indoor units connecting capacity is only 100% or more) x Capacity change rate by refrigerant pipe length x Capacity change rate by frosting (Only heating operation)

6 Actual cooling capacity or heating capacity of system (Smaller one of 3 and 5)

7 Calculate the cooling capacity or heating capacity of each indoor unit The cooling capacity or heating capacity of each indoor unit = Rated capacity of each indoor unit x 6 System capacity / The sum of rated capacity of indoor units

8 Check the heat load and capacity of indoor unit of each rooms (Are you satisfied 7≥1 ?) Note: Outdoor unit is added and calculated again to lower the total rated capacity of indoor unit in case of capacity shortage.

- (02 - 04) -

2. MODEL SELECTION

3-2. THE EXAMPLE OF CALCULATION 3-2-1. COOLING EXAMPLE  EXAMPLE 1 (When the connecting capacity for indoor unit is 100% or more)

Branch box

Outdoor unit

Branch Piping length, L1=32.8ft. (10m)

Branch box

MODEL SELECTION

MODEL SELECTION

Main Piping length, L1=32.8ft. (10m)

Branch box

Indoor unit 1

Indoor unit 2

Indoor unit 3

Indoor unit 4

Indoor unit 5

Indoor unit 6

Indoor unit 7

Indoor unit 8

Room 1

Room 2

Room 3

Room 4

Room 5

Room 6

Room 7

Room 8

 Design conditions ● Design temperature Indoor : 75°F DB / 63°F WB (23.9°C DB / 17.2°C WB) Outdoor : 86°F DB (30°C DB) ● Pipe length Main piping length : L1=32.8ft. (10m) Branch piping length : L2=32.8ft. (10m) ● Operation mode: Cooling

 Selection of indoor unit A-1 Cooling heat load

Btu

A-2 Indoor unit models A-3 Rated capacity (TCin)r

Btu

Room 1

Room 2

Room 3

Room 4

Room 5

Room 6

Room 7

Room 8

5800

5800

5800

5800

5800

5800

5800

5800

ASU7

ASU7

ASU7

ASU7

ASU7

ASU7

ASU7

ASU7

7000

7000

7000

7000

7000

7000

7000

7000

A-4 Total rated capacity ∑(TCin)r Btu A-5

7000 x 8 = 56000

Connecting indoor unit capacity (Cp)

Cooling Sum of A-3

56000 / 48000 = 117% (80%≤Cp≤130%)

Capacity change rate by A-6 suction temperature of indoor unit A-7

Remark

Total capacity at design temperature ∑(TCin) d

Btu

46.1 / 48.0 = 0.960

See Fig.1

56000 x 0.960 = 53760

(A-4) x (A-6)

 Calculate the Maximum capacity of outdoor unit Remark

B-1 Outdoor unit model

AOU48RLXFZ

B-2 Rated capacity (TCout)r

Btu

48000

Cooling

B-3 Capacity change rate by temperature conditions

47.4 / 48.0 = 0.988

See Fig.1

B-4 Capacity change rate by indoor units connecting capacity

52.4 / 48.0 = 1.092

See Fig.2

0.98 x 0.942 = 0.923

See 5-1.

48000 x 0.988 x 1.092 x 0.923 = 47800

(B-2) x (B-3) x (B-4) x (B-5)

B-5 Compensation coefficient of pipe length B-6 Maximum capacity of outdoor unit (TCout)c

Btu

 Decide system capacity Remark

C-1 System capacity

Btu

Smaller one of (A-7) and (B-6)

47800

 Calculate actual capacity of each indoor unit Actual capacity of each indoor unit

Btu

Room 1

Room 2

Room 3

Room 4

Room 5

Room 6

Room 7

Room 8

Remark

5970

5970

5970

5970

5970

5970

5970

5970

(A-3) x (C-1) / (A-4)

Actual capacity of all indoor units is larger than cooling heat load of each room. - (02 - 05) -

2. MODEL SELECTION

 EXAMPLE 2 (When the connecting capacity for indoor unit is 100% or less)

Branch box

Outdoor unit

Branch Piping length, L1=32.8ft. (10m) MODEL SELECTION

MODEL SELECTION

Main Piping length, L1=32.8ft. (10m)

Branch box

Indoor unit 1

Indoor unit 2

Indoor unit 3

Indoor unit 4

Room 1

Room 2

Room 3

Room 4

 Design conditions ● Design temperature Indoor : 75°F DB / 63°F WB (23.9°C DB / 17.2°C WB) Outdoor : 86°F DB (30°C DB) ● Pipe length Main piping length : L1=32.8ft. (10m) Branch piping length : L2=32.8ft. (10m) ● Operation mode: Cooling

 Selection of indoor unit A-1 Cooling heat load

Btu

A-2 Indoor unit models A-3 Rated capacity (TCin)r

Btu

Room 1

Room 2

Room 3

Room 4

8000

8000

11000

11000

ASU9

ASU9

ASU12

ASU12

9000

9000

12000

12000

A-4 Total rated capacity ∑(TCin)r Btu A-5

9000 x 2 + 12000 x 2 = 42000

Connecting indoor unit capacity (Cp)

Cooling Sum of A-3

42000 / 48000 = 87.5% (80%≤Cp≤130%)

Capacity change rate by A-6 suction temperature of indoor unit A-7

Remark

Total capacity at design temperature ∑(TCin) d

Btu

46.1 / 48.0 = 0.960

See Fig.1

42000 x 0.960 = 40320

(A-4) x (A-6)

 Calculate the Maximum capacity of outdoor unit Remark

B-1 Outdoor unit model

AOU48RLXFZ

B-2 Rated capacity (TCout)r

Btu

B-3 Capacity change rate by temperature conditions

Btu

Cooling

47.4 / 48.0 = 0.988

See Fig.1

0.98 x 0.942 = 0.923

See 5-1.

48000 x 0.988 x 0.923 = 43770

(B-2) x (B-3) x (B-5)

B-5 Compensation coefficient of pipe length B-6 Maximum capacity of outdoor unit (TCout)c

48000

 Decide system capacity Remark

C-1 System capacity

Btu

40320

Smaller one of (A-7) and (B-6)

 Calculate actual capacity of each indoor unit Actual capacity of each indoor unit

Btu

Room 1

Room 2

Room 3

Room 4

Remark

8640

8640

11520

11520

(A-3) x (C-1) / (A-4)

Actual capacity of all indoor units is larger than cooling heat load of each room.

- (02 - 06) -

2. MODEL SELECTION

Indoor unit connecting capacity (%) ●●●

100

Outdoor temperature (°F) ●●● ●●● 23 32 41 50 59 68 77 86 95 104 115

70°F DB 60°F WB TC PI

75°F DB 63°F WB TC PI

●●● ●●● 45.0 45.0 45.0 45.0 45.0 44.0 43.0 41.6 39.9 38.2 35.5

●●● ●●● 49.5 49.5 49.5 49.5 49.5 49.1 48.5 47.4 46.1 42.7 37.5

●●● ●●● 2.00 2.08 2.12 2.16 2.21 2.45 2.80 3.81 4.67 5.01 4.75

(c)

Indoor temperature 80°F DB 85°F DB 67°F WB 71°F WB TC PI TC PI

●●● ●●● 2.11 2.14 2.19 2.25 2.40 2.63 3.20 4.15 4.95 5.12 4.97

●●● ●●● 53.2 53.2 53.2 53.2 53.2 52.9 52.2 51.9 48.0 44.4 39.2

(b)

●●● ●●● 2.25 2.30 2.40 2.50 2.75 3.00 3.50 4.41 5.19 5.21 5.05

●●● ●●● 59.7 59.7 59.7 59.7 59.7 59.4 58.7 58.0 53.2 48.5 42.7

●●● ●●● 2.40 2.45 2.50 2.60 2.80 3.10 3.90 4.70 5.26 5.32 5.10

90°F DB 73°F WB TC PI ●●● ●●● 64.8 64.8 64.8 64.8 64.8 64.8 62.8 60.4 54.6 51.2 44.0

●●● ●●● 2.50 2.55 2.65 2.80 3.00 3.20 4.00 5.00 5.34 5.41 5.15

(a)

A-6: Capacity change rate by suction temperature of indoor unit (b) / (a) = 46.1 / 48.0 = 0.960 B-3: Capacity change rate by temperature conditions (c) / (a) = 47.4 / 48.0 = 0.988

- (02 - 07) -

2. MODEL SELECTION

MODEL SELECTION

MODEL SELECTION

 Fig 1

y

i) Refer to 4. CAPACITY TABLE to find Y1 and Y2 using X1 and X 2. ii) Calculate capacity of outdoor unit using following equation:

(X2, Y2)

Y=(Y2-Y1) / (X 2-X1)  (X-X1) + Y1

(X, Y)

(X1, Y1)

x Capacity ratio of indoor units to outdoor unit, X (%)

Indoor unit connecting capacity (%)

120

X2

●●●

100

X1

Outdoor temperature (°F) 23 32 41 50 59 68 77 86 95 104 115 ●●● ●●● 23 32 41 50 59 68 77 86 95 104 115

70°F DB 60°F WB TC PI

75°F DB 63°F WB TC PI

53.2 53.2 53.2 53.2 53.2 53.2 50.8 47.8 45.0 41.6 36.8 ●●● ●●● 45.0 45.0 45.0 45.0 45.0 44.0 43.0 41.6 39.9 38.2 35.5

56.3 56.3 56.3 56.3 56.3 56.3 54.6 51.5 48.1 44.0 39.9 ●●● ●●● 49.5 49.5 49.5 49.5 49.5 49.1 48.5 47.4 46.1 42.7 37.5

2.50 2.56 2.61 2.70 2.90 3.55 4.20 4.76 5.24 5.20 4.94 ●●● ●●● 2.00 2.08 2.12 2.16 2.21 2.45 2.80 3.81 4.67 5.01 4.75

2.55 2.75 2.85 2.95 3.20 3.60 4.40 5.13 5.79 5.90 5.06 ●●● ●●● 2.11 2.14 2.19 2.25 2.40 2.63 3.20 4.15 4.95 5.12 4.97

Indoor temperature 80°F DB 85°F DB 67°F WB 71°F WB TC PI TC PI 59.7 59.7 59.7 59.7 59.7 59.7 58.0 55.3 53.2 47.1 Y2 41.3 ●●● ●●● 53.2 53.2 53.2 53.2 53.2 52.9 52.2 51.9 48.0 44.4 Y1 39.2

Capacity ratio of indoor units to outdoor unit Capacity of outdoor units (kBtu/h)

2.65 2.80 2.90 3.05 3.30 4.00 4.70 5.33 5.90 5.96 5.15 ●●● ●●● 2.25 2.30 2.40 2.50 2.75 3.00 3.50 4.41 5.19 5.21 5.05

64.8 64.8 64.8 64.8 64.8 64.8 63.5 61.4 55.3 49.1 44.0 ●●● ●●● 59.7 59.7 59.7 59.7 59.7 59.4 58.7 58.0 53.2 48.5 42.7

X1 = 100 % Y1 = 48.0

2.75 2.90 3.05 3.05 3.35 4.05 4.80 5.45 5.93 5.98 5.20 ●●● ●●● 2.40 2.45 2.50 2.60 2.80 3.10 3.90 4.70 5.26 5.32 5.10

90°F DB 73°F WB TC PI 68.6 68.6 68.6 68.6 68.6 68.6 65.2 63.1 57.0 53.6 45.4 ●●● ●●● 64.8 64.8 64.8 64.8 64.8 64.8 62.8 60.4 54.6 51.2 44.0

X = 117 % Y

2.80 2.95 3.10 3.20 3.40 4.10 4.85 5.51 5.96 5.98 5.28 ●●● ●●● 2.50 2.55 2.65 2.80 3.00 3.20 4.00 5.00 5.34 5.41 5.15

X2 = 120 % Y2 = 53.2

Y= (53.2-48.0) / (120-100)  (117-100) + 48.0 = 52.4 (kBtu/h) B-4 : Capacity change rate by indoor units connecting capacity Y / Y1 = 52.4 / 48.0 = 1.092

- (02 - 08) -

2. MODEL SELECTION

MODEL SELECTION

Capacity of outdoor unit, Y (kBtu/h )

MODEL SELECTION

 Fig 2

3-2-2. HEATING EXAMPLE  EXAMPLE 3 (When the connecting capacity for indoor unit is 100% or more)

Branch box

Outdoor unit

Branch Piping length, L1=32.8ft. (10m)

Branch box

MODEL SELECTION

MODEL SELECTION

Main Piping length, L1=32.8ft. (10m)

Branch box

Indoor unit 1

Indoor unit 2

Indoor unit 3

Indoor unit 4

Indoor unit 5

Indoor unit 6

Indoor unit 7

Indoor unit 8

Room 1

Room 2

Room 3

Room 4

Room 5

Room 6

Room 7

Room 8

 Design conditions ● Design temperature Indoor : 65°F DB (18.3°C DB) Outdoor : 50°F DB / 47°F WB (10.0°C DB / 8.3°C WB) ● Pipe length Main piping length : L1=32.8ft. (10m) Branch piping length : L2=32.8ft. (10m) ● Operation mode: Heating

 Selection of indoor unit A-1 Heating heat load

Btu

A-2 Indoor unit models A-3 Rated capacity (TCin)r

Btu

Room 1

Room 2

Room 3

Room 4

Room 5

Room 6

Room 7

Room 8

8000

8000

8000

8000

8000

8000

8000

8000

ASU7

ASU7

ASU7

ASU7

ASU7

ASU7

ASU7

ASU7

8100

8100

8100

8100

8100

8100

8100

8100

A-4 Total rated capacity ∑(TCin)r Btu A-5

8100 x 8 = 64800

Connecting indoor unit capacity (Cp)

Heating Sum of A-3

64800 / 54000 = 120%

Capacity change rate by A-6 suction temperature of indoor unit A-7

Remark

Total capacity at design temperature ∑(TCin) d

Btu

59.4 / 54.0 = 1.10

See Fig.3

64800 x 1.10 = 71280

(A-4) x (A-6)

 Calculate the Maximum capacity of outdoor unit Remark

B-1 Outdoor unit model

AOU48RLXFZ

B-2 Rated capacity (TCout)r

Btu

B-3 Capacity change rate by temperature conditions B-4 Capacity change rate by indoor units connecting capacity B-5 Compensation coefficient of pipe length

54000

Heating

59.7 / 54.0 = 1.106

See Fig.3

62.1 / 54.0 = 1.15

See Fig.4

0.996 x 0.962 = 0.958

See 5-1.

B-6 Capacity change rate by frosting B-7 Maximum capacity of outdoor unit (TCout)c

Btu

1.00

See 5-2.

54000 x 1.106 x1.15 x 0.958 x1.00 = 65800

(B-2) x (B-3) x (B-4) x (B-5) x (B-6)

 Decide system capacity Remark

C-1 System capacity

Btu

Smaller one of (A-7) and (B-7)

65800

 Calculate actual capacity of each indoor unit Actual capacity of each indoor unit

Btu

Room 1

Room 2

Room 3

Room 4

Room 5

Room 6

Room 7

Room 8

Remark

8220

8220

8220

8220

8220

8220

8220

8220

(A-3) x (C-1) / (A-4)

Actual capacity of all indoor units is larger than heating heat load of each room. - (02 - 09) -

2. MODEL SELECTION

 EXAMPLE 4 (When the connecting capacity for indoor unit is 100% or more)

Branch box

Outdoor unit

Branch Piping length, L1=32.8ft. (10m)

Branch box

MODEL SELECTION

MODEL SELECTION

Main Piping length, L1=32.8ft. (10m)

Branch box

Indoor unit 1

Indoor unit 2

Indoor unit 3

Indoor unit 4

Indoor unit 5

Indoor unit 6

Indoor unit 7

Indoor unit 8

Room 1

Room 2

Room 3

Room 4

Room 5

Room 6

Room 7

Room 8

 Design conditions ● Design temperature Indoor : 65°F DB (18.3°C DB) Outdoor : 41°F DB / 37°F WB (5.0°C DB / 2.8°C WB) ● Pipe length Main piping length : L1=32.8ft. (10m) Branch piping length : L2=32.8ft. (10m) ● Operation mode: Heating

 Selection of indoor unit A-1 Heating heat load

Btu

A-2 Indoor unit models A-3 Rated capacity (TCin)r

Btu

Room 1

Room 2

Room 3

Room 4

Room 5

Room 6

Room 7

Room 8

6500

6500

6500

6500

6500

6500

6500

6500

ASU7

ASU7

ASU7

ASU7

ASU7

ASU7

ASU7

ASU7

8100

8100

8100

8100

8100

8100

8100

8100

A-4 Total rated capacity ∑(TCin)r Btu A-5

8100 x 8 = 64800

Connecting indoor unit capacity (Cp)

Heating Sum of A-3

64800 / 54000 = 120%

Capacity change rate by A-6 suction temperature of indoor unit A-7

Remark

Total capacity at design temperature ∑(TCin) d

Btu

59.4 / 54.0 = 1.10

See Fig.3

64800 x 1.10 = 71280

(A-4) x (A-6)

 Calculate the Maximum capacity of outdoor unit Remark

B-1 Outdoor unit model

AOU48RLXFZ

B-2 Rated capacity (TCout)r

Btu

B-3 Capacity change rate by temperature conditions B-4 Capacity change rate by indoor units connecting capacity B-5 Compensation coefficient of pipe length

54000

Heating

55.3 / 54.0 = 1.024

See Fig.3

62.1 / 54.0 = 1.15

See Fig.4

0.996 x 0.962 = 0.958

See 5-1.

B-6 Capacity change rate by frosting B-7 Maximum capacity of outdoor unit (TCout)c

Btu

0.90

See 5-2.

54000 x 1.024 x1.15 x 0.958 x 0.90 = 54830

(B-2) x (B-3) x (B-4) x (B-5) x (B-6)

 Decide system capacity Remark

C-1 System capacity

Btu

Smaller one of (A-7) and (B-7)

54830

 Calculate actual capacity of each indoor unit Actual capacity of each indoor unit

Btu

Room 1

Room 2

Room 3

Room 4

Room 5

Room 6

Room 7

Room 8

Remark

6850

6850

6850

6850

6850

6850

6850

6850

(A-3) x (C-1) / (A-4)

Actual capacity of all indoor units is larger than heating heat load of each room. - (02 - 10) -

2. MODEL SELECTION

Indoor unit connecting capacity (%) ●●●

100

Outdoor temperature DB WB °F

°F

●●● ●●● 5 14 23 32 41 47 50 59 68 75

●●● ●●● 3 12 19 28 37 43 47 50 59 65

60°F DB TC PI

65°F DB TC PI

●●● ●●● 35.8 43.7 49.1 53.6 58.0 63.1 63.5 64.1 64.8 65.2

●●● ●●● 34.1 41.6 47.1 51.5 55.3 59.4 59.7 60.1 60.7 61.4

●●● ●●● 5.55 5.60 5.70 5.76 5.76 5.70 5.56 5.19 4.63 4.05

(c')

(c)

Indoor temperature 70°F DB 75°F DB TC PI TC PI

●●● ●●● 5.52 5.61 5.78 5.78 5.61 5.35 5.25 4.80 4.45 3.92

●●● ●●● 32.8 40.3 45.4 49.5 51.2 54.0 54.6 56.0 57.0 58.0

(b)

●●● ●●● 5.50 5.62 5.75 5.74 5.23 4.89 4.80 4.61 4.36 3.81

●●● ●●● 31.4 38.6 44.0 47.1 47.8 49.5 50.2 51.2 52.5 56.0

●●● ●●● 5.48 5.64 5.72 5.68 4.92 4.55 4.53 4.33 4.08 3.73

78°F DB TC PI ●●● ●●● 31.0 37.5 42.7 43.7 45.0 46.1 46.7 47.4 48.5 53.9

5.45 5.66 5.40 5.38 4.79 4.46 4.37 4.05 3.77 3.51

(a)

A-6: Capacity change rate by suction temperature of indoor unit (b) / (a) = 59.4 / 54.0 = 1.10 B-3: Capacity change rate by temperature conditions (c) / (a) = 59.7 / 54.0 = 1.106 (Example 3) (c’) / (a) = 55.3 / 54.0 = 1.024 (Example 4)

- (02 - 11) -

2. MODEL SELECTION

MODEL SELECTION

MODEL SELECTION

 Fig 3

y

i) Refer to 4. CAPACITY TABLE to find Y1 and Y2 using X1 and X 2. ii) Calculate capacity of outdoor unit using following equation:

(X2, Y2)

Y=(Y2-Y1) / (X 2-X1)  (X-X1) + Y1

(X, Y)

(X1, Y1)

x Capacity ratio of indoor units to outdoor unit, X (%)

Indoor unit connecting capacity (%)

120 X2

●●●

100 X1

Outdoor temperature DB WB °F

°F

5 14 23 32 41 47 50 59 68 75 ●●● ●●● 5 14 23 32 41 47 50 59 68 75

3 12 19 28 37 43 47 50 59 65 ●●● ●●● 3 12 19 28 37 43 47 50 59 65

60°F DB TC PI

65°F DB TC PI

38.9 49.5 53.2 57.3 60.7 63.8 66.2 68.6 69.6 70.3 ●●● ●●● 35.8 43.7 49.1 53.6 58.0 63.1 63.5 64.1 64.8 65.2

37.5 48.8 52.5 56.3 60.1 63.1 65.2 67.9 68.9 69.9 ●●● ●●● 34.1 41.6 47.1 51.5 55.3 59.4 59.7 60.1 60.7 61.4

5.57 5.62 5.71 5.80 5.92 5.98 5.98 5.10 4.37 4.14 ●●● ●●● 5.55 5.60 5.70 5.76 5.76 5.70 5.56 5.19 4.63 4.05

5.58 5.64 5.74 5.82 5.93 5.98 5.98 5.22 4.44 4.25 ●●● ●●● 5.52 5.61 5.78 5.78 5.61 5.35 5.25 4.80 4.45 3.92

Indoor temperature 70°F DB 75°F DB TC PI TC PI 36.2 47.8 51.5 55.6 59.4 62.1 64.5 Y2 66.9 68.6 69.3 ●●● ●●● 32.8 40.3 45.4 49.5 51.2 54.0 54.6 Y1 56.0 57.0 58.0

Capacity ratio of indoor units to outdoor unit Capacity of outdoor units (kBtu/h)

5.60 5.66 5.77 5.86 5.95 5.98 5.98 5.45 4.73 4.39 ●●● ●●● 5.50 5.62 5.75 5.74 5.23 4.89 4.80 4.61 4.36 3.81

34.8 46.7 50.8 54.9 58.7 61.4 63.8 66.2 67.9 68.6 ●●● ●●● 31.4 38.6 44.0 47.1 47.8 49.5 50.2 51.2 52.5 56.0

X1 = 100 % Y1 = 54.0

5.62 5.68 5.79 5.88 5.96 5.98 5.98 5.84 5.05 4.61 ●●● ●●● 5.48 5.64 5.72 5.68 4.92 4.55 4.53 4.33 4.08 3.73

78°F DB TC PI 33.8 45.7 49.8 54.3 58.0 60.4 63.1 65.2 67.2 67.9 ●●● ●●● 31.0 37.5 42.7 43.7 45.0 46.1 46.7 47.4 48.5 53.9

X = 120 % Y

5.64 5.70 5.81 5.90 5.97 5.98 5.98 5.98 5.17 4.88 ●●● ●●● 5.45 5.66 5.40 5.38 4.79 4.46 4.37 4.05 3.77 3.51

X2 = 120 % Y2 = 62.1

Y= (62.1-54.0) / (120-100)  (120-100) + 54.0 = 62.1 (kBtu/h) B-4 : Capacity change rate by indoor units connecting capacity Y / Y1 = 62.1 / 54.0 = 1.15

- (02 - 12) -

2. MODEL SELECTION

MODEL SELECTION

Capacity of outdoor unit, Y (kBtu/h )

MODEL SELECTION

 Fig 4

4. CAPACITY TABLE 4-1. COOLING CAPACITY COOLING CAPACITY

 MODEL : AOU48RLXFZ Indoor unit connecting capacity (%)

130

120

110

100

90

80

Outdoor temperature (°F) 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115 23 32 41 50 59 68 77 86 95 104 115

70°F DB 60°F WB TC PI

75°F DB 63°F WB TC PI

57.0 57.0 57.0 57.0 57.0 57.0 53.9 49.5 46.4 42.0 37.5 53.2 53.2 53.2 53.2 53.2 53.2 50.8 47.8 45.0 41.6 36.8 49.1 49.1 49.1 49.1 49.1 49.1 47.4 45.0 43.3 39.9 36.2 45.0 45.0 45.0 45.0 45.0 44.0 43.0 41.6 39.9 38.2 35.5 40.9 40.9 40.9 40.9 40.9 40.9 40.9 40.3 39.2 37.2 34.1 35.1 35.1 35.1 35.1 35.1 35.1 34.8 34.1 33.1 32.1 31.4

59.7 59.7 59.7 59.7 59.7 59.7 56.3 53.6 48.8 44.4 40.9 56.3 56.3 56.3 56.3 56.3 56.3 54.6 51.5 48.1 44.0 39.9 52.9 52.9 52.9 52.9 52.9 52.9 51.5 49.5 47.4 43.3 38.9 49.5 49.5 49.5 49.5 49.5 49.1 48.5 47.4 46.1 42.7 37.5 46.1 46.1 46.1 46.1 46.1 46.1 45.4 43.3 41.3 39.2 35.8 38.9 38.9 38.9 38.9 38.9 38.9 38.6 38.2 36.5 34.8 32.8

2.80 2.90 2.95 3.10 3.40 4.25 4.80 5.11 5.40 5.50 5.01 2.50 2.56 2.61 2.70 2.90 3.55 4.20 4.76 5.24 5.20 4.94 2.25 2.29 2.44 2.51 2.60 2.95 3.50 4.30 5.05 5.00 4.82 2.00 2.08 2.12 2.16 2.21 2.45 2.80 3.81 4.67 5.01 4.75 1.80 1.86 1.94 2.01 2.10 2.38 2.75 3.35 4.10 4.61 4.50 1.55 1.65 1.80 1.92 2.11 2.31 2.70 3.02 3.38 3.91 4.15

2.85 3.00 3.05 3.25 3.55 4.35 5.15 5.49 5.85 5.90 5.06 2.55 2.75 2.85 2.95 3.20 3.60 4.40 5.13 5.79 5.90 5.06 2.30 2.35 2.60 2.65 2.85 3.20 3.75 4.63 5.33 5.90 5.01 2.11 2.14 2.19 2.25 2.40 2.63 3.20 4.15 4.95 5.12 4.97 1.95 2.05 2.10 2.20 2.35 2.45 2.95 3.60 4.31 4.66 4.55 1.90 2.00 2.05 2.15 2.30 2.55 2.90 3.33 3.55 4.14 4.22

Indoor temperature 80°F DB 85°F DB 67°F WB 71°F WB TC PI TC PI 62.8 62.8 62.8 62.8 62.8 62.8 61.4 56.6 53.6 47.8 42.0 59.7 59.7 59.7 59.7 59.7 59.7 58.0 55.3 53.2 47.1 41.3 56.6 56.6 56.6 56.6 56.6 56.6 55.6 53.9 52.9 46.1 40.3 53.2 53.2 53.2 53.2 53.2 52.9 52.2 51.9 48.0 44.4 39.2 48.5 48.5 48.5 48.5 48.5 48.5 47.8 46.1 43.3 41.3 37.5 44.0 44.0 44.0 44.0 44.0 44.0 43.0 41.3 38.6 36.5 34.1

2.90 3.05 3.10 3.30 3.60 4.45 5.20 5.55 5.87 5.96 5.15 2.65 2.80 2.90 3.05 3.30 4.00 4.70 5.33 5.90 5.96 5.15 2.45 2.55 2.65 2.80 3.05 3.55 4.20 5.11 5.90 5.96 5.11 2.25 2.30 2.40 2.50 2.75 3.00 3.50 4.41 5.19 5.21 5.05 2.20 2.25 2.35 2.45 2.70 2.95 3.45 4.10 4.43 4.74 4.63 2.15 2.20 2.30 2.40 2.65 2.90 3.19 3.42 3.63 4.29 4.27

66.5 66.5 66.5 66.5 66.5 66.5 64.8 62.4 56.6 49.5 44.7 64.8 64.8 64.8 64.8 64.8 64.8 63.5 61.4 55.3 49.1 44.0 61.4 61.4 61.4 61.4 61.4 61.4 60.7 60.1 54.3 48.8 43.3 59.7 59.7 59.7 59.7 59.7 59.4 58.7 58.0 53.2 48.5 42.7 54.6 54.6 54.6 54.6 54.6 54.6 53.6 52.5 49.8 46.7 40.9 48.8 48.8 48.8 48.8 48.8 48.8 48.1 47.1 45.0 42.3 37.9

2.95 3.10 3.15 3.35 3.65 4.45 5.20 5.61 5.93 5.98 5.20 2.75 2.90 3.05 3.05 3.35 4.05 4.80 5.45 5.93 5.98 5.20 2.60 2.65 2.75 2.85 3.15 3.65 4.40 5.22 5.93 5.98 5.18 2.40 2.45 2.50 2.60 2.80 3.10 3.90 4.70 5.26 5.32 5.10 2.35 2.40 2.45 2.55 2.75 3.05 3.70 4.27 4.66 4.87 4.71 2.30 2.35 2.40 2.50 2.70 3.00 3.29 3.77 4.20 4.36 4.32

90°F DB 73°F WB TC PI 70.3 70.3 70.3 70.3 70.3 68.2 66.5 64.1 58.0 51.2 46.1 68.6 68.6 68.6 68.6 68.6 68.6 65.2 63.1 57.0 53.6 45.4 66.9 66.9 66.9 66.9 66.9 66.9 64.5 61.8 57.0 52.5 44.7 64.8 64.8 64.8 64.8 64.8 64.8 62.8 60.4 54.6 51.2 44.0 59.7 59.7 59.7 59.7 59.7 59.7 58.3 54.6 51.2 47.8 42.0 52.9 52.9 52.9 52.9 52.9 52.9 52.2 49.1 46.4 43.3 39.2

3.00 3.15 3.20 3.40 3.70 4.50 5.25 5.68 5.98 5.98 5.30 2.80 2.95 3.10 3.20 3.40 4.10 4.85 5.51 5.96 5.98 5.28 2.65 2.75 2.80 3.00 3.20 3.75 4.45 5.29 5.96 5.98 5.26 2.50 2.55 2.65 2.80 3.00 3.20 4.00 5.00 5.34 5.41 5.15 2.45 2.50 2.60 2.75 2.95 3.15 3.95 4.41 4.86 4.95 4.80 2.40 2.45 2.55 2.70 2.90 3.10 3.41 3.86 4.35 4.49 4.40

TC : Total Capacity kBtu/h. PI : Power Input kW. The data is based on the following conditions. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]. - (02 - 13) -

2. MODEL SELECTION

MODEL SELECTION

MODEL SELECTION

 Capacity in kBtu/h

COOLING CAPACITY

Indoor unit connecting capacity (%)

130

120

110

100

90

80

Outdoor temperature (°C) -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 46.1

21.1°CDB 15.6°CWB TC PI

23.9°CDB 17.2°CWB TC PI

16.7 16.7 16.7 16.7 16.7 16.7 15.8 14.5 13.6 12.3 11.0 15.6 15.6 15.6 15.6 15.6 15.6 14.9 14.0 13.2 12.2 10.8 14.4 14.4 14.4 14.4 14.4 14.4 13.9 13.2 12.7 11.7 10.6 13.2 13.2 13.2 13.2 13.2 12.9 12.6 12.2 11.7 11.2 10.4 12.0 12.0 12.0 12.0 12.0 12.0 12.0 11.8 11.5 10.9 10.0 10.3 10.3 10.3 10.3 10.3 10.3 10.2 10.0 9.7 9.4 9.2

17.5 17.5 17.5 17.5 17.5 17.5 16.5 15.7 14.3 13.0 12.0 16.5 16.5 16.5 16.5 16.5 16.5 16.0 15.1 14.1 12.9 11.7 15.5 15.5 15.5 15.5 15.5 15.5 15.1 14.5 13.9 12.7 11.4 14.5 14.5 14.5 14.5 14.5 14.4 14.2 13.9 13.5 12.5 11.0 13.5 13.5 13.5 13.5 13.5 13.5 13.3 12.7 12.1 11.5 10.5 11.4 11.4 11.4 11.4 11.4 11.4 11.3 11.2 10.7 10.2 9.6

2.80 2.90 2.95 3.10 3.40 4.25 4.80 5.11 5.40 5.50 5.01 2.50 2.56 2.61 2.70 2.90 3.55 4.20 4.76 5.24 5.20 4.94 2.25 2.29 2.44 2.51 2.60 2.95 3.50 4.30 5.05 5.00 4.82 2.00 2.08 2.12 2.16 2.21 2.45 2.80 3.81 4.67 5.01 4.75 1.80 1.86 1.94 2.01 2.10 2.38 2.75 3.35 4.10 4.61 4.50 1.55 1.65 1.80 1.92 2.11 2.31 2.70 3.02 3.38 3.91 4.15

2.85 3.00 3.05 3.25 3.55 4.35 5.15 5.49 5.85 5.90 5.06 2.55 2.75 2.85 2.95 3.20 3.60 4.40 5.13 5.79 5.90 5.06 2.30 2.35 2.60 2.65 2.85 3.20 3.75 4.63 5.33 5.90 5.01 2.11 2.14 2.19 2.25 2.40 2.63 3.20 4.15 4.95 5.12 4.97 1.95 2.05 2.10 2.20 2.35 2.45 2.95 3.60 4.31 4.66 4.55 1.90 2.00 2.05 2.15 2.30 2.55 2.90 3.33 3.55 4.14 4.22

Indoor temperature 26.7°CDB 29.4°CDB 19.4°CWB 21.7°CWB TC PI TC PI 18.4 18.4 18.4 18.4 18.4 18.4 18.0 16.6 15.7 14.0 12.3 17.5 17.5 17.5 17.5 17.5 17.5 17.0 16.2 15.6 13.8 12.1 16.6 16.6 16.6 16.6 16.6 16.6 16.3 15.8 15.5 13.5 11.8 15.6 15.6 15.6 15.6 15.6 15.5 15.3 15.2 14.1 13.0 11.5 14.2 14.2 14.2 14.2 14.2 14.2 14.0 13.5 12.7 12.1 11.0 12.9 12.9 12.9 12.9 12.9 12.9 12.6 12.1 11.3 10.7 10.0

2.90 3.05 3.10 3.30 3.60 4.45 5.20 5.55 5.87 5.96 5.15 2.65 2.80 2.90 3.05 3.30 4.00 4.70 5.33 5.90 5.96 5.15 2.45 2.55 2.65 2.80 3.05 3.55 4.20 5.11 5.90 5.96 5.11 2.25 2.30 2.40 2.50 2.75 3.00 3.50 4.41 5.19 5.21 5.05 2.20 2.25 2.35 2.45 2.70 2.95 3.45 4.10 4.43 4.74 4.63 2.15 2.20 2.30 2.40 2.65 2.90 3.19 3.42 3.63 4.29 4.27

19.5 19.5 19.5 19.5 19.5 19.5 19.0 18.3 16.6 14.5 13.1 19.0 19.0 19.0 19.0 19.0 19.0 18.6 18.0 16.2 14.4 12.9 18.0 18.0 18.0 18.0 18.0 18.0 17.8 17.6 15.9 14.3 12.7 17.5 17.5 17.5 17.5 17.5 17.4 17.2 17.0 15.6 14.2 12.5 16.0 16.0 16.0 16.0 16.0 16.0 15.7 15.4 14.6 13.7 12.0 14.3 14.3 14.3 14.3 14.3 14.3 14.1 13.8 13.2 12.4 11.1

2.95 3.10 3.15 3.35 3.65 4.45 5.20 5.61 5.93 5.98 5.20 2.75 2.90 3.05 3.05 3.35 4.05 4.80 5.45 5.93 5.98 5.20 2.60 2.65 2.75 2.85 3.15 3.65 4.40 5.22 5.93 5.98 5.18 2.40 2.45 2.50 2.60 2.80 3.10 3.90 4.70 5.26 5.32 5.10 2.35 2.40 2.45 2.55 2.75 3.05 3.70 4.27 4.66 4.87 4.71 2.30 2.35 2.40 2.50 2.70 3.00 3.29 3.77 4.20 4.36 4.32

32.2°CDB 22.8°CWB TC PI 20.6 20.6 20.6 20.6 20.6 20.0 19.5 18.8 17.0 15.0 13.5 20.1 20.1 20.1 20.1 20.1 20.1 19.1 18.5 16.7 15.7 13.3 19.6 19.6 19.6 19.6 19.6 19.6 18.9 18.1 16.7 15.4 13.1 19.0 19.0 19.0 19.0 19.0 19.0 18.4 17.7 16.0 15.0 12.9 17.5 17.5 17.5 17.5 17.5 17.5 17.1 16.0 15.0 14.0 12.3 15.5 15.5 15.5 15.5 15.5 15.5 15.3 14.4 13.6 12.7 11.5

3.00 3.15 3.20 3.40 3.70 4.50 5.25 5.68 5.98 5.98 5.30 2.80 2.95 3.10 3.20 3.40 4.10 4.85 5.51 5.96 5.98 5.28 2.65 2.75 2.80 3.00 3.20 3.75 4.45 5.29 5.96 5.98 5.26 2.50 2.55 2.65 2.80 3.00 3.20 4.00 5.00 5.34 5.41 5.15 2.45 2.50 2.60 2.75 2.95 3.15 3.95 4.41 4.86 4.95 4.80 2.40 2.45 2.55 2.70 2.90 3.10 3.41 3.86 4.35 4.49 4.40

TC : Total Capacity kW. PI : Power Input kW. The data is based on the following conditions. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]. - (02 - 14) -

2. MODEL SELECTION

MODEL SELECTION

MODEL SELECTION

 Capacity in kW

4-2. HEATING CAPACITY HEATING CAPACITY

 MODEL : AOU48RLXFZ Indoor unit connecting capacity (%)

Outdoor temperature DB WB

65°F DB TC PI

Indoor temperature 70°F DB 75°F DB TC PI TC PI

°F

°F

60°F DB TC PI

78°F DB TC PI

130

5 14 23 32 41 47 50 59 68 75

3 12 19 28 37 43 47 50 59 65

40.9 51.2 53.9 58.0 61.4 64.8 67.2 69.6 70.6 71.0

5.59 5.66 5.76 5.86 5.93 5.98 5.98 5.98 5.98 4.22

39.2 50.2 53.2 57.0 60.7 63.8 66.5 68.9 69.9 70.3

5.61 5.67 5.77 5.88 5.95 5.98 5.98 5.98 5.98 4.35

38.2 49.5 52.5 56.3 60.1 62.8 65.9 68.2 69.6 69.9

5.64 5.69 5.79 5.90 5.97 5.98 5.98 5.98 5.98 4.50

36.2 48.1 51.9 55.6 59.4 62.1 65.2 67.6 68.6 69.3

5.69 5.71 5.81 5.91 5.98 5.98 5.98 5.98 5.98 4.70

35.5 47.4 50.8 54.9 58.7 61.4 64.5 66.9 67.9 68.6

5.67 5.72 5.83 5.92 5.98 5.98 5.98 5.98 5.98 4.90

120

5 14 23 32 41 47 50 59 68 75

3 12 19 28 37 43 47 50 59 65

38.9 49.5 53.2 57.3 60.7 63.8 66.2 68.6 69.6 70.3

5.57 5.62 5.71 5.80 5.92 5.98 5.98 5.10 4.37 4.14

37.5 48.8 52.5 56.3 60.1 63.1 65.2 67.9 68.9 69.9

5.58 5.64 5.74 5.82 5.93 5.98 5.98 5.22 4.44 4.25

36.2 47.8 51.5 55.6 59.4 62.1 64.5 66.9 68.6 69.3

5.60 5.66 5.77 5.86 5.95 5.98 5.98 5.45 4.73 4.39

34.8 46.7 50.8 54.9 58.7 61.4 63.8 66.2 67.9 68.6

5.62 5.68 5.79 5.88 5.96 5.98 5.98 5.84 5.05 4.61

33.8 45.7 49.8 54.3 58.0 60.4 63.1 65.2 67.2 67.9

5.64 5.70 5.81 5.90 5.97 5.98 5.98 5.98 5.17 4.88

110

5 14 23 32 41 47 50 59 68 75

3 12 19 28 37 43 47 50 59 65

37.5 46.7 50.5 54.3 57.7 60.7 63.1 66.2 67.9 69.3

5.55 5.59 5.56 5.52 5.04 4.75 4.63 4.40 4.23 4.12

35.8 46.1 49.8 53.6 57.0 60.1 62.1 65.2 66.9 68.6

5.57 5.61 5.71 5.79 5.22 5.00 4.89 4.66 4.43 4.21

34.1 45.4 49.1 52.9 56.0 59.4 61.4 64.1 66.2 66.2

5.59 5.63 5.74 5.84 5.36 5.30 5.18 4.88 4.61 4.28

33.1 44.7 48.5 52.2 55.3 58.7 60.7 63.1 65.5 63.8

5.60 5.65 5.73 5.85 5.55 5.37 5.27 5.03 4.72 4.36

32.4 44.0 47.4 51.5 54.6 58.0 59.7 62.1 64.8 61.4

5.62 5.68 5.77 5.89 5.86 5.51 5.43 5.19 4.84 4.42

100

5 14 23 32 41 47 50 59 68 75

3 12 19 28 37 43 47 50 59 65

35.8 43.7 49.1 53.6 58.0 63.1 63.5 64.1 64.8 65.2

5.55 5.60 5.70 5.76 5.76 5.70 5.56 5.19 4.63 4.05

34.1 41.6 47.1 51.5 55.3 59.4 59.7 60.1 60.7 61.4

5.52 5.61 5.78 5.78 5.61 5.35 5.25 4.80 4.45 3.92

32.8 40.3 45.4 49.5 51.2 54.0 54.6 56.0 57.0 58.0

5.50 5.62 5.75 5.74 5.23 4.89 4.80 4.61 4.36 3.81

31.4 38.6 44.0 47.1 47.8 49.5 50.2 51.2 52.5 56.0

5.48 5.64 5.72 5.68 4.92 4.55 4.53 4.33 4.08 3.73

31.0 37.5 42.7 43.7 45.0 46.1 46.7 47.4 48.5 53.9

5.45 5.66 5.40 5.38 4.79 4.46 4.37 4.05 3.77 3.51

90

5 14 23 32 41 47 50 59 68 75

3 12 19 28 37 43 47 50 59 65

34.8 41.3 44.4 48.1 51.9 56.0 56.6 58.3 59.7 60.4

5.45 5.53 5.55 5.30 5.17 5.02 4.86 4.47 4.14 3.76

33.1 39.9 41.6 44.4 48.1 51.5 51.9 54.6 56.6 57.7

5.41 5.36 5.29 4.96 4.71 4.65 4.54 4.11 3.83 3.57

32.1 38.9 40.9 43.0 46.7 48.5 50.8 52.9 55.3 55.3

5.38 5.20 5.15 4.84 4.55 4.36 4.14 3.92 3.73 3.49

31.0 37.9 39.9 42.3 44.0 45.4 46.7 47.8 49.1 50.5

5.32 5.17 5.08 4.77 4.46 4.16 3.95 3.77 3.53 3.32

30.7 35.8 37.9 39.2 40.9 42.0 43.0 44.7 45.7 48.5

5.28 5.14 5.01 4.70 4.35 3.99 3.86 3.56 3.26 3.01

80

5 14 23 32 41 47 50 59 68 75

3 12 19 28 37 43 47 50 59 65

31.7 36.5 38.6 42.3 45.7 49.5 50.5 52.2 53.6 55.3

5.22 5.01 4.86 4.48 4.17 3.99 3.95 3.86 3.65 3.41

31.4 35.1 37.2 40.6 43.3 46.7 47.4 49.5 51.5 53.6

5.15 4.98 4.81 4.40 4.10 3.91 3.84 3.74 3.56 3.25

31.0 33.8 36.2 38.6 40.9 43.3 44.7 47.4 49.8 51.5

5.12 4.95 4.71 4.32 4.06 3.85 3.82 3.70 3.55 3.11

30.7 33.1 35.1 37.2 38.9 40.9 42.0 43.3 45.7 47.1

5.08 4.92 4.66 4.26 3.81 3.54 3.50 3.45 3.22 2.93

30.4 32.4 34.1 35.8 36.8 37.9 38.6 39.9 40.9 42.7

5.03 4.89 4.59 4.11 3.70 3.41 3.33 3.16 2.94 2.68

TC : Total Capacity kBtu/h. PI : Power Input kW. The data is based on the following conditions. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]. - (02 - 15) -

2. MODEL SELECTION

MODEL SELECTION

MODEL SELECTION

 Capacity in kBtu/h

HEATING CAPACITY Indoor unit connecting capacity (%)

Outdoor temperature DB WB

15.6°C DB TC PI

18.3°C DB TC PI

Indoor temperature 21.1°C DB 23.9°C DB TC PI TC PI

25.6°C DB TC PI

°C

°C

130

-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9

-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3

12.0 15.0 15.8 17.0 18.0 19.0 19.7 20.4 20.7 20.8

5.59 5.66 5.76 5.86 5.93 5.98 5.98 5.98 5.98 4.22

11.5 14.7 15.6 16.7 17.8 18.7 19.5 20.2 20.5 20.6

5.61 5.67 5.77 5.88 5.95 5.98 5.98 5.98 5.98 4.35

11.2 14.5 15.4 16.5 17.6 18.4 19.3 20.0 20.4 20.5

5.64 5.69 5.79 5.90 5.97 5.98 5.98 5.98 5.98 4.50

10.6 14.1 15.2 16.3 17.4 18.2 19.1 19.8 20.1 20.3

5.69 5.71 5.81 5.91 5.98 5.98 5.98 5.98 5.98 4.70

10.4 13.9 14.9 16.1 17.2 18.0 18.9 19.6 19.9 20.1

5.67 5.72 5.83 5.92 5.98 5.98 5.98 5.98 5.98 4.90

120

-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9

-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3

11.4 14.5 15.6 16.8 17.8 18.7 19.4 20.1 20.4 20.6

5.57 5.62 5.71 5.80 5.92 5.98 5.98 5.10 4.37 4.14

11.0 14.3 15.4 16.5 17.6 18.5 19.1 19.9 20.2 20.5

5.58 5.64 5.74 5.82 5.93 5.98 5.98 5.22 4.44 4.25

10.6 14.0 15.1 16.3 17.4 18.2 18.9 19.6 20.1 20.3

5.60 5.66 5.77 5.86 5.95 5.98 5.98 5.45 4.73 4.39

10.2 13.7 14.9 16.1 17.2 18.0 18.7 19.4 19.9 20.1

5.62 5.68 5.79 5.88 5.96 5.98 5.98 5.84 5.05 4.61

9.9 13.4 14.6 15.9 17.0 17.7 18.5 19.1 19.7 19.9

5.64 5.70 5.81 5.90 5.97 5.98 5.98 5.98 5.17 4.88

110

-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9

-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3

11.0 13.7 14.8 15.9 16.9 17.8 18.5 19.4 19.9 20.3

5.55 5.59 5.56 5.52 5.04 4.75 4.63 4.40 4.23 4.12

10.5 13.5 14.6 15.7 16.7 17.6 18.2 19.1 19.6 20.1

5.57 5.61 5.71 5.79 5.22 5.00 4.89 4.66 4.43 4.21

10.0 13.3 14.4 15.5 16.4 17.4 18.0 18.8 19.4 19.4

5.59 5.63 5.74 5.84 5.36 5.30 5.18 4.88 4.61 4.28

9.7 13.1 14.2 15.3 16.2 17.2 17.8 18.5 19.2 18.7

5.60 5.65 5.73 5.85 5.55 5.37 5.27 5.03 4.72 4.36

9.5 12.9 13.9 15.1 16.0 17.0 17.5 18.2 19.0 18.0

5.62 5.68 5.77 5.89 5.86 5.51 5.43 5.19 4.84 4.42

100

-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9

-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3

10.5 12.8 14.4 15.7 17.0 18.5 18.6 18.8 19.0 19.1

5.55 5.60 5.70 5.76 5.76 5.70 5.56 5.19 4.63 4.05

10.0 12.2 13.8 15.1 16.2 17.4 17.5 17.6 17.8 18.0

5.52 5.61 5.78 5.78 5.61 5.35 5.25 4.80 4.45 3.92

9.6 11.8 13.3 14.5 15.0 15.8 16.0 16.4 16.7 17.0

5.50 5.62 5.75 5.74 5.23 4.89 4.80 4.61 4.36 3.81

9.2 11.3 12.9 13.8 14.0 14.5 14.7 15.0 15.4 16.4

5.48 5.64 5.72 5.68 4.92 4.55 4.53 4.33 4.08 3.73

9.1 11.0 12.5 12.8 13.2 13.5 13.7 13.9 14.2 15.8

5.45 5.66 5.40 5.38 4.79 4.46 4.37 4.05 3.77 3.51

90

-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9

-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3

10.2 12.1 13.0 14.1 15.2 16.4 16.6 17.1 17.5 17.7

5.45 5.53 5.55 5.30 5.17 5.02 4.86 4.47 4.14 3.76

9.7 11.7 12.2 13.0 14.1 15.1 15.2 16.0 16.6 16.9

5.41 5.36 5.29 4.96 4.71 4.65 4.54 4.11 3.83 3.57

9.4 11.4 12.0 12.6 13.7 14.2 14.9 15.5 16.2 16.2

5.38 5.20 5.15 4.84 4.55 4.36 4.14 3.92 3.73 3.49

9.1 11.1 11.7 12.4 12.9 13.3 13.7 14.0 14.4 14.8

5.32 5.17 5.08 4.77 4.46 4.16 3.95 3.77 3.53 3.32

9.0 10.5 11.1 11.5 12.0 12.3 12.6 13.1 13.4 14.2

5.28 5.14 5.01 4.70 4.35 3.99 3.86 3.56 3.26 3.01

80

-15.0 -10.0 -5.0 0.0 5.0 8.3 10.0 15.0 20.0 23.9

-16.1 -11.1 -7.2 -2.2 2.8 6.1 8.3 10.0 15.0 18.3

9.3 10.7 11.3 12.4 13.4 14.5 14.8 15.3 15.7 16.2

5.22 5.01 4.86 4.48 4.17 3.99 3.95 3.86 3.65 3.41

9.2 10.3 10.9 11.9 12.7 13.7 13.9 14.5 15.1 15.7

5.15 4.98 4.81 4.40 4.10 3.91 3.84 3.74 3.56 3.25

9.1 9.9 10.6 11.3 12.0 12.7 13.1 13.9 14.6 15.1

5.12 4.95 4.71 4.32 4.06 3.85 3.82 3.70 3.55 3.11

9.0 9.7 10.3 10.9 11.4 12.0 12.3 12.7 13.4 13.8

5.08 4.92 4.66 4.26 3.81 3.54 3.50 3.45 3.22 2.93

8.9 9.5 10.0 10.5 10.8 11.1 11.3 11.7 12.0 12.5

5.03 4.89 4.59 4.11 3.70 3.41 3.33 3.16 2.94 2.68

TC : Total Capacity kBtu/h. PI : Power Input kW. The data is based on the following conditions. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit]. - (02 - 16) -

2. MODEL SELECTION

MODEL SELECTION

MODEL SELECTION

 Capacity in kW

5. CAPACITY COMPENSATION COEFFICIENT 5-1. COMPENSATION COEFFICIENT OF PIPE LENGTH The figures give the compensation coefficient of pipe length owing to installation position.

Main piping length Change rate in cooling capacity Change rate in heating capacity

ft.

16.4

32.8

49.2

65.6

82.0

98.4

114.8

131.2

147.6

164.0

180.4

m

5

10

15

20

25

30

35

40

45

50

55

%

100

98.0

96.0

94.0

92.0

90.0

88.0

86.0

84.0

82.0

80.0

%

100

99.6

99.2

98.9

98.5

98.1

97.7

97.3

97.0

96.6

96.2

100 Heating 95

90

85

Cooling

80

75 0

16.4

32.8

49.2

65.6

82.0

98.4

114.8

131.2

147.6

164.0

180.4

ft.

0

5

10

15

20

25

30

35

40

45

50

55

m

Main piping length

 CAPACITY CHANGE RATE BY BRANCH PIPING LENGTH  Change rate in capacity ● Refrigerant piping connection diameter: Liquid ø1/4in. (6.35mm) , Gas ø3/8in. (9.52mm) Main piping length Change rate in cooling capacity Change rate in heating capacity

ft.

9.8

16.4

32.8

49.2

m

3

5

10

15

%

100

98.3

94.2

90.0

%

100

98.9

96.2

93.5

● Refrigerant piping connection diameter: Liquid ø1/4in. (6.35mm) , Gas ø1/2in. (12.70mm) Main piping length Change rate in cooling capacity Change rate in heating capacity

ft.

9.8

16.4

32.8

49.2

m

3

5

10

15

%

100

99.2

97.1

95.0

%

100

99.5

98.3

97.0

● Refrigerant piping connection diameter: Liquid ø1/4in. (6.35mm) , Gas ø5/8in. (15.88mm) Main piping length Change rate in cooling capacity Change rate in heating capacity

ft.

9.8

16.4

32.8

49.2

m

3

5

10

15

%

100

99.6

98.5

97.5

%

100

99.9

99.5

99.0

- (02 - 17) -

2. MODEL SELECTION

MODEL SELECTION

 Change rate in capacity

Change rate in capacity (%)

MODEL SELECTION

 CAPACITY CHANGE RATE BY MAIN PIPING LENGTH

5-2. COMPENSATION COEFFICIENT OF FROSTING / DEFROSTING To take the effects of accumulated frost and defrosting operation on heating capacity into consideration, the capacity of outdoor units should be corrected by compensation coefficient shown in the table below. Actual heating capacity = The value of capacity table x Capacity change rate by frosting

 CAPACITY CHANGE RATE BY FROSTING Outdoor temperature Capacity change rate by frosting

°FDB / °FWB °CDB / °CWB %

5.0 / 3.0

23.0 / 19.0

32.0 / 28.0

41.0 / 37.0

47.0 / 43.0

-15.0 / -16.1

-5.0 / -7.2

0.0 / -2.2

5.0 / 2.8

8.3 / 6.1

90.4

88.8

80.0

90.0

100

- (02 - 18) -

2. MODEL SELECTION

MODEL SELECTION

MODEL SELECTION

(HEATING OPERATION)

Hybrid Flex Inverter System

3. OUTDOOR UNIT & BRANCH BOX

DTR_BMU001E_04--CHAPTER03 2010.10.04

CONTENTS 3. OUTDOOR UNIT & BRANCH BOX 1. SPECIFICATIONS ......................................................................... 03 - 01 1-1.OUTDOOR UNIT ....................................................................................... 03 - 01 1-2.ENERGY EFFICIENCIES .......................................................................... 03 - 02 1-3.BRANCH BOX........................................................................................... 03 - 03

2. DIMENSIONS ................................................................................ 03 - 04 2-1.OUTDOOR UNIT ....................................................................................... 03 - 04 2-2.BRANCH BOX........................................................................................... 03 - 05

3. INSTALLATION SPACE ................................................................ 03 - 06 3-1.OUTDOOR UNIT ....................................................................................... 03 - 06 3-1-1. SINGLE OUTDOOR UNIT INSTALLATION ............................................................ 03 - 06 3-1-2. MULTIPLE OUTDOOR UNIT INSTALLATION ........................................................ 03 - 07 3-1-3. OUTDOOR UNITS INSTALLATION IN MULTI ROW .............................................. 03 - 07

3-2.BRANCH BOX........................................................................................... 03 - 08 3-2-1. HORIZONTAL INSTALLATION ............................................................................... 03 - 08 3-2-2. VERTICAL INSTALLATION .................................................................................... 03 - 09

4. REFRIGERANT CIRCUIT ............................................................. 03 - 10 5. WIRING DIAGRAM ....................................................................... 03 - 12 5-1.OUTDOOR UNIT ....................................................................................... 03 - 12 5-2.BRANCH BOX........................................................................................... 03 - 13

6. OPERATION RANGE .................................................................... 03 - 14 7. NOISE LEVEL CURVE .................................................................. 03 - 15 8. ELECTRIC CHARACTERISTICS .................................................. 03 - 17 8-1.OUTDOOR UNIT ....................................................................................... 03 - 17 8-2.BRANCH BOX........................................................................................... 03 - 17

9. SAFETY DEVICES ........................................................................ 03 - 18 9-1.OUTDOOR UNIT ....................................................................................... 03 - 18 9-2.BRANCH BOX........................................................................................... 03 - 18

1. SPECIFICATIONS Model name Power source Available Voltage Range Connectable indoor unit Cooling

Max

Capacity

OUTDOOR UNITS

Heating Cooling Input power *1 Heating Cooling Current *1 Heating

Fan

Type × Q'ty Airflow rate Motor

Sound pressure level

Heat exchanger

Enclosure

Weight

Net Gross Net Gross Size

Connection pipe

Operation range

Max Rated Max. Rated Max. Rated Max. Rated Max.

kW

A

CFM (m3/h) W Rated Rated

dB(A)

Type (Material) Surface treatment W W Type Charge Type Material Color

Refrigerant oil

Rated

in.(mm) FPI

Type × Q'ty Motor output Crankcase heater

Refrigerant

Dimensions

Cooling Heating Type × Q'ty Output Cooling Heating

Dimension Fin pitch Rows × Stages Pipe type (Material) Fin

Compressor

Rated

Number Capacity Btu/h kW Btu/h Btu/h kW Btu/h

(H x W x D)

lbs(g)

in. (mm) lbs (kg)

Liquid Gas

Method Max. length (Total) Max.length (BP-IN) Max. height difference between Outdoor Unit and each Indoor Units. Max. height difference between Indoor Units. Cooling Heating

in. (mm)

ft (m)

AOU48RLXFZ 1ø 208/230V 60Hz 187-264V 2 to 8 80 to 130% 48,000 14.1 51,100 54,000 15.8 57,000 5.27 5.98 4.83 5.98 23.4 26.5 21.4 26.5 Propeller ×1 2,737 (4,650) 2,825 (4,800) DC motor ×1 111 56 58 34-3/4 × 37-9/16 × 1-1/2 (882×955×38.1) 18 3 × 42 Grooved H-pin (Copper) Corrugate (Aluminium) Corrosion resistance (Blue Fin) DC TWIN ROTARY ×1 2700 25 R410A 7.6 (3450) PVE Painted galvanized steel Beige (10YR 7.5/1.0NN) 36 × 38-1/4 × 14-5/8 (914 x 970 x 370) 41-1/4 × 41-7/8 × 18-27/32 (1048 x 1064 x 479) 216 (98) 234 (106) 3/8 (9.52) 5/8 (15.88) Flare 377 (115) 49 (15) 98 (30) 49 (15)

°F (°C)

23 to 115 (-5 to 46) 5 to 75 (-15 to 24)

Note : Specifications are based on the following conditions. *1: In case of connecting four indoor units (12kBtu class), Electrical data is only for outdoor unit. Power source of specifications : 230V Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].

- (03 - 01) -

3. OUTDOOR UNIT & BRANCH BOX

OUTDOOR UNITS

1-1. OUTDOOR UNIT

Combination of indoor unit Capacity Cooling

Input power Current EER SEER Capacity

OUTDOOR UNITS

Heating

Input power Current COP HSPF

Btu/h kW kW A Btu/h/W Btu/h kW kW A W/W -

non-Duct ASU12 x 4 48,000 14.1 5.19 23.0 9.25 17.0 54,000 15.8 4.89 21.7 3.23 9.8

Duct ARU12 x 4 48,000 14.1 5.52 24.5 8.70 14.7 54,000 15.8 5.02 22.3 3.15 9.3

Mix 48,000 14.1 5.35 23.7 8.97 15.8 54,000 15.8 4.96 22.0 3.19 9.5

Note : Specifications are based on the ARI Standard 210/240. Power source of specifications : 230V Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].

- (03 - 02) -

3. OUTDOOR UNIT & BRANCH BOX

OUTDOOR UNITS

1-2. ENERGY EFFICIENCIES

Model name Casing color Connectable indoor unit Max. combination Min. combination Power source Available voltage range Power consumption Running current Refrigerant type Net Dimensions (H × W × D) Gross Net Weight Gross Connection pipe Operation range

Size

Btu/h Btu/h

W A in. (mm) lbs (kg) Liquid Gas

in. (mm)

Method °F (°C) %RH

UTP-PU03A (Primary) Paintingless 1 to 3 Units 62,000 7,000 1ø 208/230V 60Hz 187-264V 10 0.05 R410A 7-5/8 × 17 × 14-5/8 (195×433×370) 10 × 36-5/8 × 17-1/8 (255×929×434) 20 (9) 29 (13) Main : 3/8 (9.52) ×1, Branch : 1/4(6.35)×3 Main : 5/8(15.88)×1, Branch : 1/2(12.7)×3 Flare 5 to 115 (-15 to 46) 80 or less

UTP-PU03B (Secondary) Paintingless 1 to 3 Units 62,000 7,000 1ø 208/230V 60Hz 187-264V 10 0.05 R410A 7-5/8 × 17 × 14-5/8 (195×433×370) 10 × 36-5/8 × 17-1/8 (255×929×434) 20 (9) 29 (13) Main : 3/8 (9.52) ×1, Branch : 1/4(6.35)×3 Main : 5/8(15.88)×1, Branch : 1/2(12.7)×3 Flare 5 to 115 (-15 to 46) 80 or less

Note : Specifications are based on the following conditions. Power source of specifications : 230V.

- (03 - 03) -

3. OUTDOOR UNIT & BRANCH BOX

OUTDOOR UNITS

OUTDOOR UNITS

1-3. BRANCH BOX

2. DIMENSIONS 2-1. OUTDOOR UNIT  MODEL : AOU48RLXFZ 6-1/16 (154)

1-9/16 (40)

14-9/16 (370) 15/16 (24)

1-7/8 (48)

2 (51): Gas 16-5/32 (410)

25-19/32 (650)

1-11/16 (43): Liquid

6-17/32 (166)

Unit : inch (mm)

1-13/32 (36)

15/16 (24)

OUTDOOR UNITS

OUTDOOR UNITS

Top view

14-9/16 (370) 15/32 (12)

13-7/16 (341) 12-5/8 (321) 12-13/32 (315) 12 (305) 11-21/32 (296) 8-15/16 (227) 5-1/2 (140)

Front view

5-19/32 (142) 2-3/4 (70)

ø1-3/32 (28): Cable port ø1-3/32 (28): Cable port

Side view

1-31/32 (50)

4-3/8 (111) 13/16 (21) 2-5/32 (55)

6-3/32 (155)

20-23/32 (526)

4-23/32 (120) 1-31/32 (50)

3-1/2 (89)

1-31/32 (50) 11 (279) 3-3/4 (95) 11-11/16 (297)

1 (25)

5-5/32 (131) ø1-3/32 (28) 3-7/16 : Cable port (87)

5/16 (8)

13/16 (21)

36 (914)

38-3/16 (970)

13/16 2-9/16 (21) (65)

ø1-3/32 (28): Cable port ø1-3/32 (28): Cable port

Rear view

1-31/32 9/16 (14) (50)

2-9/16 19/32 (65) (15)

1-9/16 (40) 1-31/32 (50) 3 (76) 10-15/16 (278) 17-1/4 (438) 20-23/32 (526) 24-1/2 (622) 27-5/32 (690)

Detail A

Bottom view

- (03 - 04) -

3. OUTDOOR UNIT & BRANCH BOX

2-2. BRANCH BOX  MODELS : UTP-PU03A, UTP-PU03B 8-7/16 (214)

Unit : inch (mm)

6-27/32 (174)

OUTDOOR UNITS

OUTDOOR UNITS

6-1/16 (154)

5-9/32 (134)

4-11/32 (110)

6-15/16 (176) 8-1/2 (216) 10-3/32 (256)

2-3/4 (70)

18-15/32 (469)

7-11/16 (195)

Ceiling hanging

18-15/32 (469)

2-15/16 (75)

2-15/16 (75)

Outdoor unit side

1 (25)

Indoor unit side

17-1/16 (433)

5-13/16 (148)

2-11/16 (68)

3-3/4 (95)

14-21/32 (372)

10-3/32 (256) 3-11/32 (85)

15/16 (24)

2-1/4 (57)

3-3/4 (95) 3-3/4 (95)

17 (432)

Wall hanging

- (03 - 05) -

3. OUTDOOR UNIT & BRANCH BOX

Caution ● The installation space shown in the following examples is based on an ambient temperature under cooling operation of 95 °F DB (35 °C DB) at the air intake of the outdoor unit. Provide more space around the air intake than shown in the examples if the ambient temperature exceeds 95 °F DB (35 °C DB) or if the thermal load of all of the outdoor units exceeds the capacity. ● Consider the transportation route, installation space, maintenance space, and access, and install the unit in a location with sufficient space for the refrigerant piping. ● Observe the installation space specifications that are shown in the figures. Provide the same space for the air intake at the rear of the outdoor unit. If the installation is not performed according to the specifications, it could cause a short circuit and result in a lack of operating performance. As a result, the outdoor unit might easily be stopped by high-pressure protection. Air intake

Rear view

● Installation methods not shown in the following examples are not recommended. Performance may drop significantly.

3-1-1. SINGLE OUTDOOR UNIT INSTALLATION  WHEN THE UPWARD AREA IS OPEN

Unit : inch (mm)

 Obstacles at rear and sides only

 Obstacles at rear only

5-29/32 (150)

7-7/8 (200) 11-13/16 (300) 7-7/8 (200)

 Obstacles at front and rear only

 Obstacles at front only

5-29/32 (150) 39-3/8 (1000) or more

39-3/8 (1000) or more

 WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA  Obstacles at rear and above only

 Obstacles at rear, sides, and above only 59-1/16 (1500)

39-3/8 (1000)

11-13/16 (300) 9-27/32 (250)

Max. 19-11/16 (500)

9-27/32 (250)

- (03 - 06) -

19-11/16 (500) Max. 19-11/16 (500)

3. OUTDOOR UNIT & BRANCH BOX

OUTDOOR UNITS

OUTDOOR UNITS

3. INSTALLATION SPACE 3-1. OUTDOOR UNIT

3-1-2. MULTIPLE OUTDOOR UNIT INSTALLATION ● Provide at least 1inch (25mm) of space between the outdoor units if multiple units are installed. ● When routing the piping from the side of an outdoor unit, provide space for the piping. ● No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following example when an obstruction is present also in the upward area.

 WHEN THE UPWARD AREA IS OPEN OUTDOOR UNITS

Obstacles at front only Obstacles at front and rear only

OUTDOOR UNITS

 Obstacles at rear only

59-1/16 (1500) or more 11-13/16 (300)

19-11/16 (500) 59-1/16 (1500) or more

 WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD AREA  Obstacles at rear and above only

59-1/16 (1500)

59-1/16 (1500) 19-11/16 (500) Max. 11-13/16 (300)

3-1-3. OUTDOOR UNITS INSTALLATION IN MULTI ROW  Single parallel unit arrangement

 Multiple parallel unit arrangement

5-29/32 (150) 19-11/16 (500)

78-3/4 (2000) or more

118-1/8 (3000) or more

23-5/8 (600)

23-5/8 (600) 59-1/16 (1500)

39-3/8 (1000)

- (03 - 07) -

3. OUTDOOR UNIT & BRANCH BOX

3-2. BRANCH BOX ● The branch box can be installed onto the wall or hanging from the ceiling. ● The branch box can be installed and set horizontally or vertically. ● Provide a service access for maintenance and inspection purposes as shown in the figure below. ● It is not necessary to provide drainage for the branch box. ● The slope of the top side must be within ±5° in all directions of the horizontal plane. ● Use M8 or M10 (5/16" or 3/8") for the bolt size when hanging.

OUTDOOR UNITS

OUTDOOR UNITS

3-2-1. HORIZONTAL INSTALLATION

10-3/32 (256)

(13 (304))

Hanger bolt pitch

15/16 (24)

Be sure to install so that the top side faces up.

Top side 1-9/16 (40)

1-9/16 (40) 1-3/4 (44)

3-3/4 (95)

6-1/16 (154)

17-1/16 (433)

3-3/4 (95)

9-7/8 (251)

3-3/4 (95)

(13 (304))

Outdoor unit side

2-1/4 (57)

2-23/32 (69) Indoor unit side

Wall installation

(Service space)

12 (300) or more

Service access

28 (700) or more

63/64 (25)

Installation dimensions

5-53/64 (148)

2-15/16 (75)

7-11/16 (195)

4-3/4 (120)

(33 (838))

1-5/8 (42) 3-11/32 (85)

UNIT B

UNIT A

Top side

UNIT C

18-15/32 (469) Hanger bolt pitch

34 (850) or more

15 (360) or more

21 (530) or more

(Service space)

(Service space)

- (03 - 08) -

3. OUTDOOR UNIT & BRANCH BOX

3-2-2. VERTICAL INSTALLATION ● A vertical installation can only be performed when mounting on the wall. (A vertical installation cannot be hung from the ceiling.) ● Be sure to install the control box so that the top side faces up. ● The positioning of the control box cannot be changed when performing a vertical installation.

OUTDOOR UNITS

Top side

UNIT B UNIT C

18-15/32 (469) Hanger bolt pitch

Indoor unit side

15 (360) or more (Service space)

(Service space)

Installation dimensions

12 (300) or more

21 (530) or more (Service space)

31-1/2 (800) or more 15-3/4 (400) Service access

7-7/8 (200)

19-11/16 (500) or more

Outdoor unit side

UNIT A

15/16 (24) 10-3/32 (256)

OUTDOOR UNITS

Top side

- (03 - 09) -

3. OUTDOOR UNIT & BRANCH BOX

4. REFRIGERANT CIRCUIT Branch box 1 (primary type)

Outdoor unit

TH11

TH10 3WV

0

TH10

Strainer

4WV HP-SW

Strainer

HEX 0

TH11

TH12 EEV4

HEX

OS

Indoor unit 2

Indoor unit 3

0

TH1

Strainer

Comp ressor

EEV1 TH2

TH8

SCHEX

HEX

TH6

SV

EEV3

Strainer 3WV

Strainer

EEV3

TH12

TH9

OUTDOOR UNITS

OUTDOOR UNITS

TH11

TH12

TH10

HPS

Indoor unit 1

HEX

Strainer TH9 Strainer

TH5 TH4

TH3 LPS

TH7

EEV3 TH9 EEV2

Branch box 2 (secondary type) Accumu lator

TH11

HEX

TH10

0

TH12

TH10

Strainer

Indoor unit 4

TH11

HEX

TH10

0

TH12 EEV4

TH11

HEX

Indoor unit 5

Indoor unit 6

0

Strainer EEV3 Strainer

EEV3

EEV3

TH12

TH9 Strainer TH9 Strainer TH9

Branch box 3 (secondary type)

TH11

Indoor unit 7

HEX

TH10

0

TH12

TH10

Strainer

TH11

HEX

TH10

Indoor unit 8

0

TH12 EEV4

Strainer EEV3 Strainer

EEV3

EEV3

- (03 - 10) -

TH9 Strainer TH9 Strainer TH9

3. OUTDOOR UNIT & BRANCH BOX

 SYMBOL DESCRIPTION MARK HEX OS SCHEX HPS HP-SW LPS 4WV 3WV EEV 1 EEV 2 SV TH 1 TH 2 TH 3 TH 4 TH 5 TH 6 TH 7 TH 8

DESCRIPTION Heat exchanger Oil separator Sub-cool heat exchanger High pressure sensor High pressure sensor switch Low pressure sensor 4-way valve 3-way valve Electric expansion valve 1 Electric expansion valve 2 Solenoid valve Discharge temperature thermistor Compressor temperature thermistor Suction temperature thermistor Outdoor temperature thermistor Heat exchanger (outlet) thermistor Sub-cool heat exchanger (inlet) thermistor Sub-cool heat exchanger (outlet) thermistor Liquid temperature thermistor

OUTDOOR UNITS

OUTDOOR UNITS

 Outdoor unit

 Branch box MARK EEV 3 EEV 4 TH 9 TH 10

DESCRIPTION Electric expansion valve 3 Electric expansion valve 4 Branch box liquid temperature thermistor Branch box gas temperature thermistor

 Indoor unit MARK DESCRIPTION HEX Heat exchanger TH 11 Heat exchanger (middle) thermistor TH 12 Room temperature thermistor

- (03 - 11) -

3. OUTDOOR UNIT & BRANCH BOX

5. WIRING DIAGRAM 5-1. OUTDOOR UNIT

OUTDOOR UNITS

OUTDOOR UNITS

 MODELS : AOU48RLXFZ

- (03 - 12) -

3. OUTDOOR UNIT & BRANCH BOX

5-2. BRANCH BOX

OUTDOOR UNITS

OUTDOOR UNITS

 MODEL : UTP-PU03A (Primary)

 MODEL : UTP-PU03B (Secondary)

- (03 - 13) -

3. OUTDOOR UNIT & BRANCH BOX

6. OPERATION RANGE Operation mode Cooling / Dry

Heating

Operation range Indoor unit Outdoor unit 64 to 90°F DB 23 to 115°F DB (18 to 32°C DB) (-5 to 46°C DB) R.H. 80% or less 60 to 88°F DB 5 to 75°F DB (16 to 31°C DB)

(-15 to 24°C DB)

OUTDOOR UNITS

OUTDOOR UNITS

R.H. : Relative Humidity.

- (03 - 14) -

3. OUTDOOR UNIT & BRANCH BOX

7. NOISE LEVEL CURVE  MODEL : AOU48RLXFZ  Heating

 Cooling 80

80

70

70

N C -65

60 N C -60

N C -55 50 N C -50

N C -45 40 N C -40

N C -35 30 N C -30

N C -25 20 N C -20

60 N C -60

N C -55 50 N C -50

N C -45 40 N C -40

N C -35 30 N C -30

N C -25 20 N C -20

N C -15

N C -15

10

10

0

0 63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

- (03 - 15) -

3. OUTDOOR UNIT & BRANCH BOX

OUTDOOR UNITS

Octave band sound pressure level, dB:(0dB=0.0002μbar)

Octave band sound pressure level, dB:(0dB=0.0002μbar)

OUTDOOR UNITS

N C -65

 SOUND LEVEL CHECK POINT

Air flow

OUTDOOR UNITS

OUTDOOR UNITS

Microphone

39-3/8in. (1 m)

- (03 - 16) -

3. OUTDOOR UNIT & BRANCH BOX

8. ELECTRIC CHARACTERISTICS 8-1. OUTDOOR UNIT Power Supply

Model name

OUTDOOR UNITS

AOU48RLXFZ

Hz

60

Electric Characteristics Full Load Characteristics

Voltage

MCA

TOCA

MSC

(V)

(A)

(A)

(A)

208/230

26.5

45

23.4

Comp

Wiring Specifications *1 MOCP

Power Cable

Earth Cable

MFA

AWG size

AWG size

(A)

Cross-section

Cross-section

40

8

8

resser

Outdoor Fan Motor

Limited Wiring

RLA

Output

FLA

Length*2

(A)

(kW)

(A)

21

0.11

0.9

49/55 (ft.) 15/17 (m)

8-2. BRANCH BOX

Model name UTP-PU03A (Primary) UTP-PU03B (Secondary)

Rated Value Electric Characteristics Power Supply Full Load Characteristics Wiring Specifications *1 Power Cable Earth Cable MOCP Voltage MCA TOCA MFA Hz AWG size AWG size (V) (A) (A) (A) Cross-section Cross-section 60

208/230

3

10

15

14

14

60

208/230

3

10

15

14

14

● Select the breaker based on MOCP of the table above. ● Select the wire size based on the larger value of MCA or MOCP of the table above. *1 Wiring Spec : These values are recommended data. Please select the wiring spec in accordance with local rules. *2 Limited Wiring Length : This wiring length is in case voltage drop less than 2%. When wiring length extend longer, select the wiring size of larger diameter. RLA : Rated Load Amp of compressor under the standard condition. MCA : Min Circuit Amp = Max Operating Current (Full Load) MSC : Max Starting Current TOCA : Total Value of Each Over Current Set MFA : Main Fuse (Circuit Breaker) Current MOCP : Maximum Over Current Protection

- (03 - 17) -

3. OUTDOOR UNIT & BRANCH BOX

OUTDOOR UNITS

Rated Value

9. SAFETY DEVICES 9-1. OUTDOOR UNIT Safety device

Protector

Main PCB

AC 250V 3.15A

INV PCB

DC 400V 5A

Filter

AC 250V 10A AC 250V 3.15A

Filter

AC 500V 50A

OUTDOOR UNITS

Compressor Protector High Pressure Protection Low Pressure Protection

Overcurrent protection Temperature protection Off : 239°F (115°C) On : 158°F (70°C) Off : 609psi (4.2MPa)

On : 464psi (3.2MPa)

Off : 7.25psi (0.05MPa)

9-2. BRANCH BOX Safety device Fuse

UTP-PU03A, UTP-PU03B AC 250V 3.15A x 2 AC 250V 10A x 1

PCB

- (03 - 18) -

3. OUTDOOR UNIT & BRANCH BOX

OUTDOOR UNITS

Fuse

AOU48RLXFZ

Hybrid Flex Inverter System

4. INDOOR UNITS

DTR_BMU001E_05--CHAPTER04 2010.11.12

CONTENTS 4. INDOOR UNITS 1. FEATURES ................................................................................... 04 - 01 1-1. COMPACT CASSETTE TYPE ................................................................ 04 - 01 1-2. SLIM DUCT TYPE................................................................................... 04 - 02 1-3. COMPACT WALL MOUNTED TYPE ..................................................... 04 - 03 1-4. WALL MOUNTED TYPE ........................................................................ 04 - 04

2. SPECIFICATIONS ........................................................................ 04 - 05 2-1. COMPACT CASSETTE TYPE ................................................................ 04 - 05 2-2. SLIM DUCT TYPE................................................................................... 04 - 06 2-3. COMPACT WALL MOUNTED TYPE ...................................................... 04 - 07 2-4. WALL MOUNTED TYPE ......................................................................... 04 - 08

3. ELECTRIC CHARACTERISTICS ................................................. 04 - 09 4. DIMENSIONS ............................................................................... 04 - 10 4-1. COMPACT CASSETTE TYPE ................................................................ 04 - 10 4-2. SLIM DUCT TYPE................................................................................... 04 - 12 4-3. COMPACT WALL MOUNTED TYPE ...................................................... 04 - 17 4-4. WALL MOUNTED TYPE ........................................................................ 04 - 19

5. WIRING DIAGRAMS .................................................................... 04 - 21 5-1. COMPACT CASSETTE TYPE ................................................................ 04 - 21 5-2. SLIM DUCT TYPE................................................................................... 04 - 22 5-3. COMPACT WALL MOUNTED TYPE ...................................................... 04 - 23 5-4. WALL MOUNTED TYPE ......................................................................... 04 - 24

6. AIR VELOCITY AND TEMPERATURE DISTRIBUTIONS ........... 04 - 25 6-1. COMPACT CASSETTE TYPE ................................................................ 04 - 25 6-2. COMPACT WALL MOUNTED TYPE ...................................................... 04 - 31 6-3. WALL MOUNTED TYPE ......................................................................... 04 - 34

7. FAN PERFORMANCE CURVE ..................................................... 04 - 36 7-1. SLIM DUCT TYPE................................................................................... 04 - 36

8. AIR FLOW .................................................................................... 04 - 44

CONTENTS 4. INDOOR UNITS 9. NOISE LEVEL CURVE .................................................................. 04 - 46 9-1. COMPACT CASSETTE TYPE ................................................................ 04 - 46 9-2. SLIM DUCT TYPE................................................................................... 04 - 48 9-3. COMPACT WALL MOUNTED TYPE ...................................................... 04 - 50 9-4. WALL MOUNTED TYPE ......................................................................... 04 - 52 9-5. SOUND LEVEL CHECK POINT ............................................................. 04 - 53

10.

SAFETY DEVICES ................................................................... 04 - 55

1. FEATURES 1-1. COMPACT CASSETTE TYPE  MODELS : AUU9RLF, AUU12RLF, AUU18RLF

 FEATURES

 Quiet quality

High efficiency design by 2 stage structure Wind velocity

INDOOR UNITS

Fast

Previous turbo fan

2-stage turbo fan

In the case of a conventional fan, the air outlet range was narrow as the airflow moved to the motor side which meant the velocity of air passing through the heat exchanger was uneven.

A evenly spread air distribution across the heat exchanger is possible due to the new 2 stage turbo fan which produces two separate airflow streams. 1-stage

Optimization of wing form (laminar wing type) and wing number (7 blades each) Designed by CFD-analysis (fluid) simulations Laminar wing

Quiet

Airflow runs through smoothly along the laminar wing

INDOOR UNITS

 2-stage turbo fan

+

2-stage 2 stage

Slow

No airflow separation

Heat exchange efficiency:

Quiet Adoption of laminar wing

20%UP Spin direction

Airflow direction

 Easy maintenance 1Maintenance of fan motor and fan Maintenance of the fan motor and fan can be done easily after taking off the panel as the bell mouth of the fan can be removed easily. A : Fan motor B : 2-stage turbo fan 1 C : Bell-mouth D : Panel A

2Long life filter

B C

: standard equipment

3Adaptation of transparent drainage parts During installation, maintenance and operation, the drain pump and kit can be checked easily.

D

3

2

Grille cover

 Compact design Easy installation by taking off ceiling panel of 23-5/8in. x 23-5/8in.(600mm x 600mm) size 22-7/16in. (570mm) 22-7/16in. (570mm)

 High lift drain pump

27-9/16in. (700mm)

- (04 - 01) -

4. INDOOR UNITS

1-2. SLIM DUCT TYPE  MODELS : ARU9RLF, ARU12RLF, ARU18RLF, ARU24RLF

Slim design and wide range of static pressure for flexible installation.

 FEATURES  Slim design

 Flexible installation

This model is slim design, it can install at the place where a ceiling is narrow.

Ceiling concealed

INDOOR UNITS

INDOOR UNITS

Drain port Height

7-25/32 in. (198mm)

Drain pump

Drain pump built-in

Wall concealed

 Compact design Condensate lift-up to 33-15/32in. (850mm)

Max. 33-15/32 in. (850mm) Drain hose is standard accessory

 Selectable with a wide range of static pressure

 Filter (Accessory) Filter (ARU09/12/18: 2pcs.) ARU24: 3pcs.)

Static pressure range

By using DC fan motor, it is possible to change of static pressure range 0 to 0.36in. WG (0 to 90Pa). The change of static pressure range is possible by remote controller. [in.WG (P a)] 0.36 (90)

0 A ir flow rate

[CFM (m3/h)]

*24 model is 0 to 0.20in.WG (0 to 50Pa)

 Air - intake Air intake direction can be selected to match the installation site.

Bottom side

Back side

- (04 - 02) -

4. INDOOR UNITS

1-3. COMPACT WALL MOUNTED TYPE  MODELS : ASU7RLF, ASU9RLF, ASU12RLF Compact and Stylish design indoor unit

 FEATURES  High density heat transfer tube arrangement Ø5

Making the tube Thin:

7mm→5mm

 Easy maintenance Removable & washable panel

Volume reduction of heat exchanger:

Dry operation

30%

Dry operation removes moisture and keeps the air conditioner clean.

Improved the heat exchanger effectiveness

 Filter features Long-life* Ion deodorization filter The filter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra-fine particle ceramic. *The filter can be used for approx. 3 years if it is washed under water to restore it's surface action when it is dirty.

Apple-catechin filter

 Quiet operation

INDOOR UNITS

INDOOR UNITS

Even temperature

Cooling mode (07/09/12 TYPE) Fan speed

Noise level

Quiet

25dB(A)

 Auto swing louvre The Auto Swing Louvre function ensures that the air direction corresponds to the mode selected.

Step

Fine dust, invisible mold spores, and harmful microorganisms are absorbed onto the filter by static electricity, and further growth is inhibited and deactivated by the polyphenol ingredient extracted from apples.

Swing

Deodorizing effect (Odor reduction rate) (ppm) 160 120 80 40 0 0

Ammonia With no filter New filter 30

60

120 (min.)

(ppm) 160 120 80 40 0 0

Trimethylamine With no filter

Swing (Cooling)

New filter

30

60

120 (min.)

Swing (Heating) (ppm) 160 120 80 40 0 0

Hydrogen sulfate With no filter New filter

Testing organization : Environmental Sanitary Inspection Center

 Wired control compatible

Test method : Deodorization Test

* 30

60

120 (min.)

Wired and wireless remote controller are acceptable. SET TEMP.

START/STOP

* Optional communication kit is neccesary for the installation.

Wired remote controller

- (04 - 03) -

Simple remote controller

4. INDOOR UNITS

1-4. WALL MOUNTED TYPE  MODELS : ASU18RLF, ASU24RLF Simple & Elegant Appearance Design

 FEATURES  Compact & Slim design

39-9/32in. (998 mm)

 “ Vertical airflow” provides powerful floor level heating ft.(m) 7 (2.1)

16

(24/30)

0 10 (3)

46

o

Outside Outsid de air condition conditions: 35.6oF (2o C) 60% Operation contents: Heating Opera Set te temperature (Max set temp) 86oF (30oC), Air flow Hi Vertical flap : Downward Horizontal flap : Center

20 (6)

92

90

88

86

33

32

31

30

30 (9)

40 (12) ft.(m)

84 (oF) 29 (oC)

Power diffuser (full open)

 “ Horizontal airflow” does not blow cool air directly at the occupants in the room ft.(m) 7 (2.1)

3 (1)

0 10 (3) Power diffuser

Outside air conditions: 95oF (35oC) 40% Operation contents: Cooling Set temperature (Min set temp) 64oF (18oC), Air flow Hi Vertical flap : Upward Horizontal flap : Center

20 (6)

58

60

62

64 (oF)

15

16

17

18 (oC)

 Air conditioner filter features Ion Deodorization Filter Organic coating fin used heat exchanger

Apple-catechin Filter Pre Filter

30 (9)

40 (12) ft.(m)

Long-life* Ion deodorization filter The filter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra-fine-particle ceramic. (*The filter can be used for approx. 3 years if it is washed under water to restore its surface action when it is dirty.) 䚷䚷䚷

ὺᴾ

Using different filters at both sides

Antibacterial deodorizing pre-filter with special ceramic powder

Apple-catechin filter

 Easy maintenance Simplification of drain pan cleaning improves maintenance-ability.

Fine dust, invisible mold spores, and harmful microorganisms are absorbed onto the filter by static electricity, and further growth is inhibited and deactivated by the polyphenol extracted from apples.

- (04 - 04) -

4. INDOOR UNITS

INDOOR UNITS

INDOOR UNITS

3 (1)

2. SPECIFICATIONS 2-1. COMPACT CASSETTE TYPE AUU9RLF

Btu/h kW Btu/h kW pints/h(l/h) W A

Cooling Rated Capacity Heating Rated Moisture removal Power consumption Running current Cooling

Fan

Airflow rate Heating

High Med Low Quiet High Med Low Quiet

INDOOR UNITS

Fan Type × Q'ty Fan Motor Output Cooling Sound pressure level Heating

W High Med Low Quiet High Med Low Quiet

Dimension (H×W×D) Heat exchanger

Enclosure

Dimensions ( H×W×D )

Fin pitch Rows × Stages Pipe type Fin Type Material

Net Gross Net Gross

Drain pipe

dB(A)

in. (mm) FPI

Color

Weight

Connection pipe

CFM (m3/h)

Size

Unit Panel Unit Panel Unit Panel Unit Panel Liquid Gas

in.(mm)

lb. (kg)

in.(mm)

Method Material size

Operation range

in. Cooling Heating

Remote controller type

°F (°C) %RH °F (°C)

AUU12RLF AUU18RLF 1ø 208/230V 60Hz 187-264V 9,000 12,000 18,000 2.64 3.51 5.28 10,200 13,500 20,000 3.00 3.96 5.85 2.5 (1.2) 3.2 (1.5) 4.2 (2.0) 18 23 39 0.15 0.19 0.30 318 (540) 359 (610) 441 (750) 288 (490) 312 (530) 359 (610) 259 (440) 277 (470) 306 (520) 230 (390) 241 (410) 241 (410) 318 (540) 359 (610) 471 (800) 288 (490) 312 (530) 418 (710) 259 (440) 277 (470) 353 (600) 230 (390) 241 (410) 265 (450) Turbo × 1 42 42 42 33 37 42 31 33 37 29 31 33 27 28 29 34 37 44 32 33 40 29 31 37 27 28 30 8-9/32 × 51-9/16 × 17/32 + 8-9/32 × 49-7/32 × 17/32 (210×1310×13.3 + 210×1250×13.3) 21 2×10 Copper tube Aluminium PS White (Approximate color of Mansell N9.25 /) 9-21/32 × 22-7/16 × 22-7/16 (245×570×570) 1-15/16 × 27-9/16 × 27-9/16 (49 × 700 × 700) 10-7/16 × 28-3/4 × 24-19/32 (265×730×625) 4-23/32 × 30-1/8 × 29-23/32 (120 × 765 × 755) 33 (15) 5.7(2.6) 40 (18) 10(4.5) 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) Flare HARD PVC Outer Diameter : 1-1/16 Inner Diameter : 3/4 64 to 90 (18 to 32) 80 or less 60 to 88 (16 to 31) Wired [Wireless(option)]

Note : Specifications are based on the following conditions. Power source of specifications : 230V Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].

- (04 - 05) -

4. INDOOR UNITS

INDOOR UNITS

Model name Power source Available voltage range

2-2. SLIM DUCT TYPE ARU9RLF

Cooling Rated Capacity Heating Rated

INDOOR UNITS

Moisture removal Power consumption Running current High Med Cooling Low Quiet Airflow rate High Fan Med Heating Low Quiet Fan type ×Q'ty Fan motor output Recommended static pressure High Med Cooling Low Quiet Sound pressure level High Med Heating Low Quiet Dimension (H×W×D) Heat exchanger

Enclosure

Fin pitch Rows × Stages Pipe type Fin Type Material Color

Btu/h kW Btu/h kW pints/h(l/h) W A

CFM (m3/h)

W in.WG(Pa)

dB(A)

in (mm) FPI

Net Dimensions ( H×W ×D )

in. (mm) Gross

Weight Connection pipe

Drain pipe

Net Gross Size

lb. (kg) Liquid Gas

in. (mm)

Method Material size

Operation range

in. Cooling Heating

Remote controller type

°F (°C) %RH °F (°C)

ARU12RLF ARU18RLF ARU24RLF 1ø 208/230V 60Hz 187-264V 9,000 12,000 18,000 24,000 2.64 3.51 5.28 7.02 10,200 13,500 20,000 27,000 3.00 3.96 5.85 7.92 2.7 (1.3) 3.8 (1.8) 4.6 (2.2) 5.3 (2.5) 49 58 73 111 0.30 0.35 0.44 0.66 353 (600) 383 (650) 554 (940) 783 (1330) 324 (550) 353 (600) 518 (880) 730 (1240) 294 (500) 324 (550) 483 (820) 648 (1100) 265 (450) 283 (480) 442 (750) 607 (1030) 353 (600) 383 (650) 554 (940) 783 (1330) 324 (550) 353 (600) 518 (880) 730 (1240) 294 (500) 324 (550) 483 (820) 648 (1100) 265 (450) 283 (480) 442 (750) 607 (1030) Sirocco × 2 Sirocco × 3 Sirocco × 4 81 81 96 96 0 to 0.36 (0 to 90) 0 to 0.36 (0 to 90) 0 to 0.36 (0 to 90) 0 to 0.20 (0 to 50) 28 29 32 33 27 28 31 32 26 27 30 30 25 26 29 29 28 29 33 35 26 28 32 34 25 27 31 32 24 24 29 29 11-9/16 × 27-9/16 × 11-9/16 × 35-7/16 × 11-9/16 × 19-11/16 × 1-9/16 1-9/16 1-9/16 (294×500×39.9) (294×900×39.9) (294×700×39.9) 20 3 × 14 Copper tube Aluminium GALVANIZED STEEL SHEET 7-25/32 x 35-7/16 x 7-25/32 x 43-5/16 x 7-25/32 x 27-9/16 x 24-13/32 24-13/32 24-13/32 (198 × 700 × 620) (198 × 900 × 620) (198 × 1100 × 620) 10-7/8 x 53-27/32 x 10-7/8 x 38-1/8 x 29-3/4 10-7/8 x 46 x 29-3/4 29-3/4 (276 × 968 × 756) (276 × 1168 × 756) (276 × 1368 × 756) 41 (19) 50 (23) 59 (27) 58 (26) 67 (30) 75 (34) 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) 5/8 (15.88) Flare HARD PVC Outer Diameter : 1-1/16 Inner Diameter : 3/4 64 to 90 (18 to 32) 80 or less 60 to 88 (16 to 31) Wired [Wireless(option)]

Note : Specifications are based on the following conditions. Power source of specifications : 230V Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Standard static pressure : 0.10in.WG (25Pa) Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].

- (04 - 06) -

4. INDOOR UNITS

INDOOR UNITS

Model name Power source Available voltage range

2-3. COMPACT WALL MOUNTED TYPE

Cooling Rated Capacity Heating Rated

INDOOR UNITS

Moisture removal Power consumption Running current High Med Cooling Low Quiet Airflow rate High Fan Med Heating Low Quiet Fan type × Q'ty Fan motor output High Med Cooling Low Quiet Sound pressure level High Med Heating Low Quiet Dimension (H×W×D) Heat exchanger

Enclosure

Fin pitch Rows × Stages Pipe type Fin Type Material

ASU7RLF

Btu/h kW Btu/h kW pints/h(l/h) W A

CFM (m3/h)

W

dB(A)

in. (mm) FPI

Color

Dimensions Net ( H×W ×D ) Gross Net Weight Gross

in.(mm) lb.(kg)

Liquid Connection Size Gas pipe Method Material Drain pipe size Operation range

Cooling

Heating Remote controller type

in. (mm)

in. (mm) °F (°C) %RH °F (°C)

ASU9RLF ASU12RLF 1ø 208/230V 60Hz 187-264V 7,000 9,000 12,000 2.04 2.64 3.51 8,100 10,200 13,500 2.37 3.00 3.96 1.7 (0.8) 2.7 (1.3) 3.8 (1.8) 15 17 22 0.13 0.15 0.19 330 (560) 353 (600) 388 (660) 294 (500) 306 (520) 330 (560) 253 (430) 253 (430) 265 (450) 200 (340) 200 (340) 200 (340) 330 (560) 353 (600) 388 (660) 294 (500) 306 (520) 330 (560) 253 (430) 253 (430) 277 (470) 206 (350) 206 (350) 206 (350) Cross Flow ×1 30 30 30 36 37 40 32 33 36 29 29 30 25 25 25 36 37 40 32 33 36 29 29 31 25 25 25 Main: 12-19/32 x 24-13/16 x 25/32 (320 x 630 x 20) Sub: 3-5/16 x 24-13/16 x 17/32 (84 x 630 x 13.3) Main: 23, Sub: 18 Main: 2 x 20, Sub: 1 x 4 Copper tube Aluminium Polystyrene White (Approximate color of Mansell N9.25 /) 11-1/16 × 31-1/16 × 8 (280×790×203) 10-3/8 × 33-1/16 × 14-3/4 (263×840×375) 18 (8) 23 (10.5) 1/4 (6.35) 3/8 (9.52) Flare PP + LLDPE Outer Diameter : 5/8 to 21/32 (15.8 to 16.7) Inner Diameter : 17/32 (13.8) 64 to 90 (18 to 32) 80 or less 60 to 88 (16 to 31) Wireless [Wired(option)]

Note : Specifications are based on the following conditions. Power source of specifications : 230V Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].

- (04 - 07) -

4. INDOOR UNITS

INDOOR UNITS

Model name Power source Available voltage range

2-4. WALL MOUNTED TYPE Model name Power source Available voltage range Capacity Heating Rated

INDOOR UNITS

Moisture removal Power consumption Running current High Med Cooling Low Quiet Airflow rate High Fan Med Heating Low Quiet Fan type × Q'ty Fan motor output High Med Cooling Low Quiet Sound pressure level High Med Heating Low Quiet Dimension (H×W×D) Heat exchanger

Enclosure

Fin pitch Rows × Stages Pipe type Fin Type Material

Btu/h kW Btu/h kW pints/h(l/h) W A

CFM (m3/h)

W

dB(A)

in.(mm) FPI

Color

Dimensions Net ( H×W ×D ) Gross Net Weight Gross

mm lb.(kg)

Liquid Connection Size Gas pipe Method Material Drain pipe size Operation range

Cooling

Heating Remote controller type

ASU24RLF 1ø 208/230V 60Hz 187-264V

in.(mm)

in.(mm) °F (°C) %RH °F (°C)

18,000 5.28 20,000 5.85 5.3 (2.5) 41 0.32 542 (920) 436 (740) 365 (620) 324 (550) 542 (920) 436 (740) 365 (620) 324 (550)

24,000 7.02 27,000 7.92 5.9 (2.8) 69 0.53 659 (1120) 530 (900) 436 (740) 365 (620) 647 (1100) 530 (900) 436 (740) 365 (620)

Cross flow ×1 64 64 43 49 37 42 33 37 31 33 44 48 37 42 33 37 31 33 Main:15-7/8 x 33-3/4 x 1-1/16 (378 x 832 x 26.6) Sub:3-5/16 x 33-3/4 x 17/32 (84 x 832 x 13.3) Main:21, Sub:18 Main:2 x 18, Sub:1 x 4 Copper tube Aluminium Polystyrene White (Approximate color of Mansell N9.25 /) 12-5/8 x 39-1/4 x 9 (320×998×228) 12-9/16 x 42-15/16 x 16-7/8 (319×1090×429) 31 (14) 31 (14) 40 (18) 40 (18) 1/4 (6.35) 1/2 (12.7) 5/8 (15.88) Flare PVC Outer diameter : 5/8 (16) Inner diameter : 15/32 (12) 64 to 90 (18 to 32) 80 or less 60 to 88 (16 to 31) Wireless [Wired(option)]

Note : Specifications are based on the following conditions. Power source of specifications : 230V Cooling : Indoor temperature of 80°F(26.7°C)DB/67°F(19.4°C)WB,and outdoor temperature of 95.0°F(35°C)DB/75°F(23.9°C)WB. Heating : Indoor temperature of 70°F(21.1°C)DB/60°F(15.6°C)WB,and outdoor temperature of 47°F(8.3°C)DB/43°F(6.1°C)WB. Pipe length : 16.4ft.(5m) [Outdoor unit - Branch box], 9.8ft. (3m) [Branch box - Indoor unit] Height difference : 0 ft.(0m) [Outdoor unit - Indoor unit].

- (04 - 08) -

4. INDOOR UNITS

INDOOR UNITS

Cooling Rated

ASU18RLF

3. ELECTRIC CHARACTERISTICS Type Compact Wall Mounted Wall Mounted Compact Cassette

ASU7RLF ASU9RLF ASU12RLF ASU18RLF ASU24RLF AUU9RLF AUU12RLF AUU18RLF ARU9RLF ARU12RLF ARU18RLF ARU24RLF

60 60 60 60 60 60 60 60 60 60 60 60

Indoor Rated Input Power FLA (W) (A) 15 / 15 0.14 / 0.13 17 / 17 0.16 / 0.15 22 / 22 0.20 / 0.19 40 / 41 0.34 / 0.32 68 / 69 0.57 / 0.53 17 / 18 0.15 / 0.15 22 / 23 0.19 / 0.19 38 / 39 0.32 / 0.30 47 / 49 0.32 / 0.30 56 / 58 0.37 / 0.35 71 / 73 0.47 / 0.44 109 / 111 0.71 / 0.66

INDOOR UNITS

Hz

MCA (A) 0.18 / 0.17 0.20 / 0.19 0.25 / 0.24 0.42 / 0.40 0.71 / 0.66 0.19 / 0.19 0.24 / 0.24 0.41 / 0.38 0.40 / 0.38 0.47 / 0.44 0.59 / 0.55 0.89 / 0.83

INDOOR UNITS

Slim Duct

Model name

Power Supply Voltage (V) 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230 208 / 230

MCA : Min Circuit Amps = Max Operating Current (Full Load). MFA : Main Fuse (Circuit breaker) Amps.

- (04 - 09) -

4. INDOOR UNITS

4. DIMENSIONS 4-1. COMPACT CASSETTE TYPE  MODELS : AUU9RLF, AUU12RLF, AUU18RLF Unit : in. (mm)

• Decoration panel mounting state

□ 22-27/32 to 26 (580 to 660) : Ceiling openings

5-29/32 to 7-7/8 (150 to 200)

INDOOR UNITS

Top view

Maintenance space

Be sure to leave maintenance space for future service at the designated position.

27-9/16 (700)

1-3/16 (30) 2-9/32 (58)

Ceiling

Side view

4-27/32 (123)

Control box

10-5/16 (262)

4-1/32 (102) Drain port

1-3/16 (30)

8-15/32 (215)

1-3/16 (30)

1-3/16 (30)

(Drain hose)

1-15/16 (49)

4-1/4 (108)

5-3/4 (146)

9-21/32 (245)

3-29/32 (99)

4-1/2 (114)

Min. 17-23/32 (450) Drain port 4-1/32 (102) 1-9/16 (40)

Side view 27-9/16 (700)

Bottom view

1 2 3

Refrigerant pipe flare connection Drain hose connection

Liquid Gas Drain hose

AUU9RLF, AUU12RLF AUU18RLF ø 1/4 in. (6.35 mm) ø 1/4 in. (6.35 mm) ø 3/8 in. (9.52 mm) ø 1/2 in. (12.70 mm) I.D. 3/4 in. , O.D. 1-1/16 in. - (04 - 10) -

4. INDOOR UNITS

INDOOR UNITS

9-27/32 (250) Min. 17-23/32 (450)

5-5/16 (135)

□ 22-7/16 (570): Indoor unit

21-1/4 (540): Hanging bolt position

2-15/16 (75)

20-7/8 (530): Hanging bolt position

 INSTALLATION PLACE Unit : in. (mm)

Strong and durable ceiling

10-5/16 (262) or more

H

39-3/8 (1000) or more

39-3/8 (1000) or more

94-1/2 (2400) or more

INDOOR UNITS

INDOOR UNITS

Obstruction Floor

Model name Standard mode High Ceiling mode

H (The maximum height from floor to ceiling) Unit: in. (mm) AUU9 AUU12 AUU18 106-5/16 106-5/16 106-5/16 (2700) (2700) (2700) -

118-1/8

118-1/8

(3000)

(3000)

 3-way directions setting

* 3-15/16 (100) or more

To set “3-way directions”, the air outlet shutter plate (UTR-YDZB) sold separately must be installed and “outlet-direction” switched to “3-way” by remote controller. *When installing the indoor unit, be careful about the maintenance space. - (04 - 11) -

4. INDOOR UNITS

4-2. SLIM DUCT TYPE  MODELS : ARU9RLF, ARU12RLF

2 (51)

6 (152)

6-27/32 (174)

22-19/32 (574)

Unit : in. (mm)

View A

2-25/32 (71)

Rear view

1-3/16 (30)

1-27/32 (47)

25-19/32 (650)

2-5/32 (55)

28-29/32 (734)

3-1/16 (78)

3-1/2 (89) 1-7/8 (48)

4-11/16 (119)

3-7/32 (82)

6-9/16 (167)

Side view

2-5/32 (55)

1-11/16 (43)

3-1/16 (78)

5-15/16 (151)

6-5/8 (168)

7-25/32 (198)

Top view

25/32 (20) 25-19/32 (650) 26-5/32 (664) 27-9/16 (700)

Front view Bottom view

1 2 3

Refrigerant pipe flare connection Drain hose connection

ARU9, ARU12 ø 1/4 in. (6.35 mm) ø 3/8 in. (9.52 mm) I.D. 3/4 in. , O.D. 1-1/16 in.

Liquid Gas Drain hose

- (04 - 12) -

4. INDOOR UNITS

INDOOR UNITS

24-13/32 (620)

14-19/32 (371)

10-13/32 (264)

2-23/32 (69)

13/32 (10) 3-15/16 (100) x 6 = 23-5/8 (600)

5-21/32 (144)

Drain port

INDOOR UNITS

14-27/32 (377)

(Drain hose)

 MODELS : ARU18RLF

2-25/32 (71)

6 (152)

2 (51)

6-27/32 (174)

30-15/32 (774)

Unit : in. (mm)

Rear view

1-3/16 (30)

View A

(Drain hose)

2-5/32 (55)

3-1/16 (78)

3-7/16 (87) 2-7/32 (56)

3-1/16 (78) 2-5/32 (55)

5-15/16 (151)

Top view

6-5/8 (168)

4-11/16 (119) 6-9/16 (167)

Side view

1-11/16 (43)

25/32 (20) 33-15/32 (850) 34-1/32 (864) 35-7/16 (900)

Front view

Bottom view

1 2 3

Refrigerant pipe flare connection Drain hose connection

ARU18 ø 1/4 in. (6.35 mm) ø 1/2 in. (12.70 mm) I.D. 3/4 in. , O.D. 1-1/16 in.

Liquid Gas Drain hose

- (04 - 13) -

4. INDOOR UNITS

INDOOR UNITS

24-13/32 (620)

14-19/32 (371)

3-1/2 (89)

36-25/32 (934)

7-25/32 (198)

10-13/32 (264)

1-27/32 (47)

33-15/32 (850)

5-21/32 (144)

3-15/16 (100) x 8 = 31-1/2 (800)

2-23/32 (69)

13/32 (10)

INDOOR UNITS

14-27/32 (377)

Drain port

 MODELS : ARU24RLF

2 (51)

6 (152)

6-27/32 (174)

2-25/32 (71)

38-11/32 (974)

Unit : in. (mm)

View A

1-3/16 (30)

Rear view

14-27/32 (377)

(Drain hose)

3-15/16 (100) x 10 = 39-3/8 (1000)

2-5/32 (55)

3-7/16 (87)

4-11/16 (119)

2-7/32 (56)

6-9/16 (167)

Side view

1-11/16 (43)

25/32 (20) 43-5/16 (1100)

Front view

Bottom view

1 2 3

Refrigerant pipe flare connection Drain hose connection

ARU24 ø 1/4 in. (6.35 mm) ø 5/8 in. (15.88 mm) I.D. 3/4 in. , O.D. 1-1/16 in.

Liquid Gas Drain hose

- (04 - 14) -

4. INDOOR UNITS

INDOOR UNITS

24-13/32 (620)

14-19/32 (371)

3-1/16 (78)

3-1/2 (89)

Top view

2-5/32 (55) 3-1/16 (78)

5-15/16 (151)

44-21/32 (1134)

6-5/8 (168)

5-21/32 (144)

1-27/32 (47)

41-11/32 (1050)

7-25/32 (198)

10-13/32 (264)

INDOOR UNITS

13/32 (10)

2-23/32 (69)

Drain port

Unit : in. (mm)

 INSTALLATION PLACE 11-13/16 (300) or more 9-7/16 (240) or more

Strong and durable ceiling

Right side

25/32 (20) or more

11-13/16 (300) or more

3-15/16 (100) or more

Service access

Ceiling

(When no ceiling)

Left side

25/32 (20) or more

98-7/16 (2500) or more

Indoor unit

13/32 (10) or less

13/32 (10) or less

Left side

INDOOR UNITS

INDOOR UNITS

Floor

Right side (PIPE side)

Grill

Inlet air

5-29/32 (150)

or more 3-15/16 (100) or more

Strong and durable floor

5-29/32 (150) or more

Strong and durable floor 11-13/16 (300) or more

25/32 (20) or more

Dact

Right side (PIPE side)

Left side

25/32 (20) or more

Grill

Inlet air

5-29/32 (150) or more 3-15/16 (100) or more

Strong and durable floor

5-29/32 (150) or more

Strong and durable floor

11-13/16 (300) or more

- (04 - 15) -

25/32 (20) or more

25/32 (20) or more

4. INDOOR UNITS

Unit : in. (mm)

 MAINTENANCE SPACE Provide a service access for inspection purposes as shown below. Do not place any wiring or illumination in the service space, as they will impede service.

Service access

Unit

3-15/16 (100) or more

11-13/16 (300) or more

Control box

11-13/16 (300) or more INDOOR UNITS

INDOOR UNITS

Service space

- (04 - 16) -

4. INDOOR UNITS

4-3. COMPACT WALL MOUNTED TYPE  MODELS : ASU7RLF, ASU9RLF, ASU12RLF Unit : in. (mm) 8-1/16 (205) : Installed state 31-3/32 (790)

11-1/32 (280)

8 (203)

7-1/4 (184)

23/32 (18)

2-7/16 (62)

9-11/32 (237) 12-23/32 (323)

1-27/32 (47)

3-7/32 (82)

2-1/16 (52)

8-7/32 (209) 12-7/8 (327)

3-1/16 (78)

13-29/32 (353): Gas pipe ø2-9/16 (65) for pipe inlet

16-11/32 (415): Liquid pipe

ø2-9/16 (65) for pipe inlet

1 2

Refrigerant pipe flare connection

Liquid Gas

ASU7RLF, ASU9RLF, ASU12RLF ø 1/4 in. (6.35 mm) ø 3/8 in. (9.52 mm)

3

Drain hose connection

Drain hose

I.D. 17/32 in. (13.8 mm), O.D. 5/8 to 21/32 in. (15.8 to 16.7 mm) Drain hose : L=20-15/32 in. (520mm)

- (04 - 17) -

4. INDOOR UNITS

INDOOR UNITS

3-11/16 (94)

17-23/32 (450)

8-15/32 (215)

Outline of unit

23/32 (18)

*1: Vertical flap is downward

1-27/32 (47)

INDOOR UNITS

5-23/32 (145) *1

13/32 (10) *1

5-1/2 (140) *1

 INSTALLATION PLACE 2-15/32 (63) or more

1-25/32 (45) or more

Unit : in. (mm)

1-7/8 (48) or more

2-3/4 (70) or more

3-15/16 (100) or more

59-1/16 (1500) or more

- (04 - 18) -

4. INDOOR UNITS

INDOOR UNITS

2-1/16 (52) or more

70-7/8 (1800) or more

INDOOR UNITS

Outline of unit

4-4. WALL MOUNTED TYPE  MODELS : ASU18RLF, ASU24RLF Unit : in. (mm)

12-19/32 (320)

39-9/32 (998)

20-15/32 (520) 23-7/32 (590) 28-3/8 (721)

8-31/32 (228)

INDOOR UNITS

ø1-1/4 (32) ø5/8 (16) ø15/32 (12)

20-15/32 (520)

2-15/16 (75)

15-3/4 (400)

9-9/16 (243)

4-7/16 (113)

6-11/16 (170) 5-1/8 (130) 2-15/16 (75)

4-13/16 (122) 6-25/32 (172)

5-1/4 (133) 4-31/32 (126)

23/32 x 7/16 (18 x 11) hole 1-1/32 x 7/16 (26 x 11) hole 13/16 x 6/32 (21 x 5): 14holes

1-6/32 (30)

10-19/32 (269)

6/32 x 23/32 (5 x 18): 14holes

15-1/4 (387)

1-23/32 (44) 5-7/8 (149) 7-3/4 (197) 10-23/32 (272)

23/32 x 7/16 (18 x 11) hole

5/8 (16)

1/2 (13)

1-1/32 x 7/16 (26 x 11) hole

25/32 (20) Unit center 17-9/32 (439)

15/32 (12)

1-15/32 (37)

12-19/32 (320): Unit size

INDOOR UNITS

1 (25)

1-6/32 (30) ø3-5/32 (80) hole Piping inlet

17-1/4 (438)

15-5/8 (397) 39-3/8 (1000): Unit size

6/32 x 1-31/32 (5 x 50): 3holes ø6/32 (5): 65holes for tapping screw

1 2

Refrigerant pipe flare connection

Liquid Gas

3

Drain hose connection

Drain hose

ø3-5/32 (80) hole Piping inlet 1/2 x 6/32 (13 x 5): 4holes

ASU18RLF ASU24RLF ø 1/4 in. (6.35 mm) ø 1/4 in. (6.35 mm) ø 1/2 in. (12.70 mm) ø 5/8 in. (15.88 mm) I.D. 15/32 in. (12 mm) , O.D. 5/8 in. (16 mm) Drain hose : L=26-3/8 in. (670mm)

- (04 - 19) -

4. INDOOR UNITS

 INSTALLATION PLACE

3-5/32 (80) or more

2-15/32 (63) or more

Unit : in. (mm)

2-3/32 (53) or more

3-5/32 (80) or more

4-23/32 (120) or more

59-1/16 (1500) or more

- (04 - 20) -

4. INDOOR UNITS

INDOOR UNITS

2-1/16 (52) or more

70-7/8 (1800) or more

INDOOR UNITS

Outline of unit

5. WIRING DIAGRAMS 5-1. COMPACT CASSETTE TYPE

INDOOR UNITS

INDOOR UNITS

 MODELS : AUU9RLF, AUU12RLF, AUU18RLF

- (04 - 21) -

4. INDOOR UNITS

5-2. SLIM DUCT TYPE

INDOOR UNITS

INDOOR UNITS

 MODELS : ARU9RLF, ARU12RLF, ARU18RLF, ARU24RLF

- (04 - 22) -

4. INDOOR UNITS

5-3. COMPACT WALL MOUNTED TYPE

INDOOR UNITS

INDOOR UNITS

 MODELS : ASU7RLF, ASU9RLF, ASU12RLF

- (04 - 23) -

4. INDOOR UNITS

5-4. WALL MOUNTED TYPE

INDOOR UNITS

INDOOR UNITS

 MODELS : ASU18RLF, ASU24RLF

- (04 - 24) -

4. INDOOR UNITS

6. AIR VELOCITY AND TEMPERATURE DISTRIBUTIONS 6-1. COMPACT CASSETTE TYPE Conditions

Fan speed : High Operation mode : FAN

 MODEL : AUU9RLF  Air velocity distribution Top view Vertical flap : Up (ft.) (m) 13

4

10

3

7

2

3

1

Unit : ft./s (m/s)

1 (0.25)

2 (0.5)

7 (2.0)

0

2 (0.5)

0

1 (0.25)

2 (0.5)

1 (0.25)

7 (2.0)

7 (2.0)

3 (1.0) 3

3 (1.0)

7 (2.0)

INDOOR UNITS

INDOOR UNITS

3 (1.0)

1

3 (1.0)

7

2

2 (0.5)

10

3

1 (0.25)

13

4 4

3

2

1

0

1

2

3

4

(m)

13

10

7

3

0

3

7

10

13

(ft.)

Side view Vertical flap : Up (ft.) (m) 9

Unit : ft./s (m/s)

2.7

7 (2.0) 7

2

3 (1.0) 2 (0.5)

3

1

0

0

2 (0.5)

1 (0.25)

1 (0.25)

4

3

2

1

0

1

2

3

4

(m)

13

10

7

3

0

3

7

10

13

(ft.)

- (04 - 25) -

4. INDOOR UNITS

Note: Reference data Conditions Fan speed : High Operation mode : Heating Vertical flap: Downward (4Way)

 Air velocity distribution Side view Vertical flap : Down (ft.) (m) 2.7

8

2.5

7

2

Unit : ft./s (m/s)

7 (2.0)

7 (2.0)

5 (1.5)

5 (1.5)

3 (1.0)

3 (1.0)

2 (0.5)

2 (0.5)

1 (0.25) 1

0

0

INDOOR UNITS

3

4 13

3

2

10

7

1 (0.25)

1 3

0 0

1 3

2

3

7

10

4

(m)

13

(ft.)

 Air temperature distribution Side view Vertical flap : Down (ft.) (m) 9

2.7

8

2.5

7

2

Unit : °F (°C)

86 (30)

86 (30)

82 (28)

82 (28)

79 (26)

79 (26)

75 (24) 3

75 (24)

1

72 (22)

0

72 (22)

0 4 13

3 10

2 7

1 3

0 0

- (04 - 26) -

1 3

2 7

3 10

4

(m)

13

(ft.)

4. INDOOR UNITS

INDOOR UNITS

9

Conditions Fan speed : High Operation mode : FAN

 MODEL : AUU12RLF  Air velocity distribution Top view Vertical flap : Up (ft.) (m) 13

Unit : ft./s (m/s)

4

1 (0.25)

10

3

7

2

3

1

2 (0.5)

7 (2.0)

0

0

3 (1.0)

7 (2.0)

2 (0.5)

INDOOR UNITS

INDOOR UNITS

3 (1.0)

1 (0.25)

2 (0.5)

1 (0.25)

7 (2.0)

7 (2.0)

3 (1.0) 3

1

3 (1.0)

2 (0.5) 7

2

10

3

1 (0.25) 13

4 4

3

2

1

0

1

2

3

4

(m)

13

10

7

3

0

3

7

10

13

(ft.)

Side view Vertical flap : Up (ft.) (m) 9

2.7

7

2

Unit : ft./s (m/s)

7 (2.0) 3 (1.0) 2 (0.5)

2 (0.5) 3

1

1 (0.25)

0

1 (0.25)

0 4

3

2

1

0

1

2

3

4

(m)

13

10

7

3

0

3

7

10

13

(ft.)

- (04 - 27) -

4. INDOOR UNITS

Note: Reference data Conditions Fan speed : High Operation mode : Heating Vertical flap: Downward (4Way)

 Air velocity distribution (ft.) (m) 9

2.7

8

2.5

7

2

Unit : ft./s (m/s)

5 (1.5)

5 (1.5)

3 (1.0)

3 (1.0)

2 (0.5) 3

2 (0.5)

1

1 (0.25)

0 4

3

2

1

0

1

2

3

4

(m)

13

10

7

3

0

3

7

10

13

(ft.)

INDOOR UNITS

INDOOR UNITS

0

1 (0.25)

 Air temperature distribution (ft.) (m) 9

2.7

8

2.5

7

2

Unit : °F (°C)

86 (30)

86 (30)

82 (28)

82 (28)

79 (26)

79 (26)

75 (24) 3

75 (24)

1

72 (22)

0

72 (22)

0 4

3

2

1

0

1

2

3

4

(m)

13

10

7

3

0

3

7

10

13

(ft.)

- (04 - 28) -

4. INDOOR UNITS

Conditions Fan speed : High Operation mode : FAN

 MODEL : AUU18RLF  Air velocity distribution Top view Vertical flap : Up (ft.) (m) 13

Unit : ft./s (m/s)

4

1 (0.25)

10

3

7

2

2 (0.5)

3

INDOOR UNITS

INDOOR UNITS

3 (1.0) 1

7 (2.0)

7 (2.0) 1 (0.25)

0

2 (0.5)

0

3 (1.0)

1 (0.25) 3

3 (1.0)

7 (2.0)

2 (0.5)

7 (2.0)

1

3 (1.0)

7

2

2 (0.5)

10

3

1 (0.25) 13

4 4

3

2

1

0

1

2

3

4

(m)

13

10

7

3

0

3

7

10

13

(ft.)

Side view Vertical flap : Up (ft.) (m) 9

Unit : ft./s (m/s)

2.7

7 (2.0) 7

2

3 (1.0)

2 (0.5) 2 (0.5) 3

1

1 (0.25)

1 (0.25)

0

0 4

3

2

1

0

1

2

3

4

(m)

13

10

7

3

0

3

7

10

13

(ft.)

- (04 - 29) -

4. INDOOR UNITS

Note: Reference data Conditions Fan speed : High Operation mode : Heating Vertical flap: Downward (4Way)

 Air velocity distribution (ft.) (m) 9

2.7

8

2.5

7

2

Unit : ft./s (m/s)

7 (2.0)

7 (2.0)

5 (1.5)

5 (1.5)

3 (1.0)

3 (1.0)

2 (0.5) 3

2 (0.5)

1

1 (0.25)

0 4

3

2

1

0

1

2

3

4

(m)

13

10

7

3

0

3

7

10

13

(ft.)

INDOOR UNITS

INDOOR UNITS

0

1 (0.25)

 Air temperature distribution (ft.) (m) 9

2.7

8

2.5

7

2

Unit : °F (°C)

86 (30)

86 (30)

82 (28)

82 (28)

79 (26) 3

0

1

79 (26)

75 (24)

75 (24)

72 (22)

72 (22)

0 4

3

2

1

0

1

2

3

4

(m)

13

10

7

3

0

3

7

10

13

(ft.)

- (04 - 30) -

4. INDOOR UNITS

6-2. COMPACT WALL MOUNTED TYPE Conditions Fan speed : High Operation mode : Fan

 MODELS : ASU7RLF

Unit : ft./s (m/s)

(ft.) (m)

Top view Vertical flap : Up Horizontal flap : Center

7

2

3

1

0

0

3

1

7

2

2 (0.5)

3 (1.0)

7 (2.0)

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

10

3

7

2

3

1

INDOOR UNITS

INDOOR UNITS

(ft.) (m)

7 (2.0)

Top view Vertical flap : Up Horizontal flap : Right & Left

2 (0.5)

3 (1.0) 0

0

3 (1.0) 3

1

7

2

10

3

2 (0.5)

7 (2.0)

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

(ft.) (m)

Side view Vertical flap : Up Horizontal flap : Center

10

3

7

2

3

1

0

0

3 (1.0)

2 (0.5)

7 (2.0)

0

1

2

3

4

5

6

7

8

(m)

0

3

7

10

13

16

20

23

26

(ft.)

(ft.) (m)

Side view Vertical flap : Down Horizontal flap : Center

10

3

7

2

3

1

7 (2.0) 3 (1.0) 2 (0.5)

0

0 0

1

2

3

4

5

6

7

8

(m)

0

3

7

10

13

16

20

23

26

(ft.)

- (04 - 31) -

4. INDOOR UNITS

Conditions Fan speed : High Operation mode : Fan

 MODELS : ASU9RLF

Unit : ft./s (m/s)

(ft.) (m)

Top view Vertical flap : Up Horizontal flap : Center

7

2

3

1

0

0

3

1

7

2

3 (1.0)

7 (2.0)

2 (0.5)

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

Top view Vertical flap : Up Horizontal flap : Right & Left

10

3

7

2

3

1

0

0

INDOOR UNITS

INDOOR UNITS

(ft.) (m)

7 (2.0) 2 (0.5)

3 (1.0)

2 (0.5)

3 (1.0) 3

1

7

2

10

3

7 (2.0)

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

(ft.) (m)

Side view Vertical flap : Up Horizontal flap : Center

10

3

7

2

3

1

0

0

3 (1.0)

7 (2.0)

2 (0.5)

0

1

2

3

4

5

6

7

8

(m)

0

3

7

10

13

16

20

23

26

(ft.)

(ft.) (m)

Side view Vertical flap : Down Horizontal flap : Center

10

3

7

2

3

1

7 (2.0) 3 (1.0) 2 (0.5)

0

0 0

1

2

3

4

5

6

7

8

(m)

0

3

7

10

13

16

20

23

26

(ft.)

- (04 - 32) -

4. INDOOR UNITS

Conditions Fan speed : High Operation mode : Fan

 MODELS : ASU12RLF

Unit : ft./s (m/s)

(ft.) (m)

Top view Vertical flap : Up Horizontal flap : Center

7

2

3

1

0

0

3

1

7

2

3 (1.0)

7 (2.0)

2 (0.5)

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

Top view Vertical flap : Up Horizontal flap : Right & Left

10

3

7

2

3

1

0

0

INDOOR UNITS

INDOOR UNITS

(ft.) (m)

7 (2.0) 2 (0.5)

3 (1.0) 3 (1.0) 3

1

7

2

10

3

2 (0.5)

7 (2.0)

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

(ft.) (m)

Side view Vertical flap : Up Horizontal flap : Center

10

3

7

2

3

1

0

0

3 (1.0) 7 (2.0)

2 (0.5)

0

1

2

3

4

5

6

7

8

(m)

0

3

7

10

13

16

20

23

26

(ft.)

(ft.) (m)

Side view Vertical flap : Down Horizontal flap : Center

10

3

7

2

3

1

7 (2.0)

3 (1.0) 2 (0.5)

0

0 0

1

2

3

4

5

6

7

8

(m)

0

3

7

10

13

16

20

23

26

(ft.)

- (04 - 33) -

4. INDOOR UNITS

6-3. WALL MOUNTED TYPE Conditions Fan speed : High Operation mode : Fan

 MODEL : ASU18RLF (ft.) (m)

Top view Vertical flap : Up Horizontal flap : Center

7

2

3

1

0

0

3

1

7

2

Unit : ft./s (m/s)

3 (1.0)

7 (2.0)

2 (0.5)

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

3

7

2

3

1

0

0

3

1

Unit : ft./s (m/s)

INDOOR UNITS

INDOOR UNITS

(ft.) (m) 10

2 (0.5)

7 (2.0)

Top view Vertical flap : Up Horizontal flap : Right & Left

(m)

0

3 (1.0)

3 (1.0) 2 (0.5)

7 (2.0) 7

2

10

3

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

(ft.) (m)

Side view Vertical flap : Up Horizontal flap : Center

10

3

7

2

3

1

0

0

Unit : ft./s (m/s)

7 (2.0) 3 (1.0)

2 (0.5)

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

(ft.) (m)

Side view Vertical flap : Down Horizontal flap : Center

10

3

7

2

3

1

Unit : ft./s (m/s)

7 (2.0) 3 (1.0) 2 (0.5)

0

0

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

- (04 - 34) -

4. INDOOR UNITS

 MODEL : ASU24RLF

Conditions Fan speed : High Operation mode : Fan

(ft.) (m)

Top view Vertical flap : Up Horizontal flap : Center

7

2

3

1

0

0

3

1

7

2

Unit : ft./s (m/s)

7 (2.0)

2 (0.5)

3 (1.0)

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

3

7

2

Unit : ft./s (m/s)

INDOOR UNITS

INDOOR UNITS

(ft.) (m) 10

2 (0.5)

7 (2.0)

Top view Vertical flap : Up Horizontal flap : Right & Left

3

1

0

0

3

1

7

2

10

3

(m)

0

3 (1.0)

3 (1.0) 2 (0.5)

7 (2.0)

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

(ft.) (m)

Side view Vertical flap : Up Horizontal flap : Center

10

3

7

2

3

1

0

0

Unit : ft./s (m/s)

7 (2.0) 3 (1.0)

2 (0.5)

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

(ft.) (m)

Side view Vertical flap : Down Horizontal flap : Center

10

3

7

2

3

1

Unit : ft./s (m/s)

7 (2.0)

3 (1.0) 2 (0.5) 0

0

(m)

0

1

2

3

4

5

6

7

8

0

3

7

10

13

16

20

23

26 (ft.)

- (04 - 35) -

4. INDOOR UNITS

7. FAN PERFORMANCE CURVE 7-1. SLIM DUCT TYPE  MODEL : ARU9RLF 0.44 (110) SP mode09 upper limit

0.32 (80) 0.28 (70)

Quiet (SP mode09) SP mode09 lower limit

0.24 (60) 0.20 (50) 0.16 (40) 0.12 (30) 0.08 (20) 0.04 (10)

Normal SP upper limit

Hi (Normal SP)

SP mode00 upper limit Quiet (Normal SP) Hi (SP mode00)

Quiet (SP mode00)

177 (300)

INDOOR UNITS

External Static Pressure [in.WG (Pa)]

Hi (SP mode09)

0.36 (90)

0 (0)

235 (400)

294 353 (500) (600) Air Flow [CFM (m3/h)]

412 (700)

471 (800)

Available air flow rate range (High level)

0.44 (110) 0.40 (100) External Static Pressure [in.WG (Pa)]

INDOOR UNITS

0.40 (100)

0.36 (90) 0.32 (80) Hi (SP mode09)

0.28 (70) Hi (SP mode08)

0.24 (60) Hi (SP mode07)

0.20 (50) Hi (Normal SP)

Hi (SP mode06)

0.16 (40) 0.12 (30)

Hi (SP mode02) Hi (SP mode05) Hi (SP mode01)

0.08 (20) 0.04 (10)

Hi (SP mode04) Hi (SP mode00) Hi (SP mode03)

0 (0) 177 (300)

235 (400)

294 353 (500) (600) Air Flow [CFM (m3/h)]

- (04 - 36) -

412 (700)

471 (800)

4. INDOOR UNITS

120

60.8 (16)

Capacity (%)

100

59.0 (15)

Capacity

80

57.2 (14)

60

55.4 (13)

40

53.6 (12) Outdoor temperature

20

51.8 (11) 50.0 (10)

0 294 353 (500) (600) Air Flow [CFM (m3/h)]

412 (700)

471 (800) INDOOR UNITS

235 (400)

INDOOR UNITS

177 (300)

Output temperature [°F (°C)]

 Cooling

120

113.0 (45) Capacity

Capacity (%)

100

111.2 (44)

80

109.4 (43)

60

107.6 (42)

40

105.8 (41) Outdoor temperature

20

104.0 (40)

0

102.2 (39) 471 (800)

177 (300)

235 (400)

294 353 (500) (600) Air Flow [CFM (m3/h)]

- (04 - 37) -

412 (700)

Output temperature [°F (°C)]

 Heating

4. INDOOR UNITS

 MODEL : ARU12RLF 0.44 (110)

0.32 (80) 0.28 (70)

Quiet (SP mode09)

0.24 (60) 0.20 (50)

Normal SP upper limit

0.16 (40)

Quiet (Normal SP)

0.12 (30) 0.08 (20)

SP mode09 lower limit Hi (Normal SP)

SP mode00 upper limit

Hi (SP mode00) INDOOR UNITS

External Static Pressure [in.WG (Pa)]

0.36 (90)

0.04 (10) Quiet (SP mode00)

0 (0) 177 (300)

235 (400)

294 353 (500) (600) Air Flow [CFM (m3/h)]

412 (700)

471 (800)

Available air flow rate range (High level)

0.44 (110) 0.40 (100) External Static Pressure [in.WG (Pa)]

INDOOR UNITS

Hi (SP mode09)

SP mode09 upper limit

0.40 (100)

0.36 (90) 0.32 (80) 0.28 (70)

Hi (SP mode09)

0.24 (60)

Hi (SP mode08)

0.20 (50)

Hi (Normal SP)

Hi (SP mode07)

0.16 (40)

Hi (SP mode02)

Hi (SP mode06)

0.12 (30)

Hi (SP mode01)

Hi (SP mode05)

0.08 (20)

Hi (SP mode00)

Hi (SP mode04)

0.04 (10)

Hi (SP mode03)

0 (0) 177 (300)

235 (400)

294 353 (500) (600) Air Flow [CFM (m3/h)]

- (04 - 38) -

412 (700)

471 (800)

4. INDOOR UNITS

60.8 (16)

120 Capacity (%)

100

59.0 (15)

Capacity

80

57.2 (14)

60

55.4 (13)

40

53.6 (12) Outdoor temperature

20

50.0 (10)

0 294 353 (500) (600) Air Flow [CFM (m3/h)]

412 (700)

471 (800) INDOOR UNITS

235 (400)

INDOOR UNITS

177 (300)

51.8 (11)

Output temperature [°F (°C)]

 Cooling

120

113.0 (45) Capacity

Capacity (%)

100

111.2 (44)

80

109.4 (43)

60

Outdoor temperature

107.6 (42)

40

105.8 (41)

20

104.0 (40)

0

102.2 (39)

177 (300)

235 (400)

294 353 (500) (600) Air Flow [CFM (m3/h)]

- (04 - 39) -

412 (700)

Output temperature [°F (°C)]

 Heating

471 (800)

4. INDOOR UNITS

 MODEL : ARU18RLF 0.44 (110)

0.32 (80)

Quiet (SP mode09)

0.28 (70) SP mode09 lower limit

0.24 (60) Normal SP upper limit Quiet (Normal SP)

0.20 (50) 0.16 (40)

Hi (Normal SP)

0.12 (30) SP mode00 upper limit 0.08 (20) 0.04 (10)

INDOOR UNITS

External Static Pressure [in.WG (Pa)]

0.36 (90)

0 (0)

Hi (SP mode00) Quiet (SP mode00)

353

412

471

530

589

(600)

(700)

(800) (900) (1000) 3 Air Flow [CFM (m /h)]

647

706

(1100)

(1200)

Available air flow rate range (High level)

0.44 (110) 0.40 (100) External Static Pressure [in.WG (Pa)]

INDOOR UNITS

Hi (SP mode09)

SP mode09 upper limit

0.40 (100)

0.36 (90) 0.32 (80) 0.28 (70) Hi (SP mode09)

0.24 (60) Hi (SP mode08)

0.20 (50)

Hi (Normal SP)

0.16 (40)

Hi (SP mode02)

0.12 (30)

Hi (SP mode01)

0.08 (20)

Hi (SP mode00)

Hi (SP mode07) Hi (SP mode06) Hi (SP mode05) Hi (SP mode04)

0.04 (10)

Hi (SP mode03)

0 (0) 353

412

471

530

(600)

(700)

(800) (900) (1000) 3 Air Flow [CFM (m /h)]

- (04 - 40) -

589

647

706

(1100)

(1200)

4. INDOOR UNITS

120

60.8 (16) Capacity

Capacity (%)

100

59.0 (15)

80

57.2 (14)

60

55.4 (13) 53.6 (12)

40 Outdoor temperature

20

51.8 (11) 50.0 (10)

0 471

530

589

(600)

(700)

(800) (900) (1000) Air Flow [CFM (m3/h)]

647

706

(1100)

(1200) INDOOR UNITS

412

INDOOR UNITS

353

Output temperature [°F (°C)]

 Cooling

120

113.0 (45) Capacity

Capacity (%)

100

111.2 (44)

80

109.4 (43)

60

107.6 (42)

40 20

105.8 (41) Outdoor temperature

104.0 (40) 102.2 (39)

0 353

412

471

(600)

(700)

(800) (900) (1000) 3 Air Flow [CFM (m /h)]

530

589

- (04 - 41) -

647

706

(1100)

(1200)

Output temperature [°F (°C)]

 Heating

4. INDOOR UNITS

 MODEL : ARU24RLF

0.24 (60)

Hi (SP mode05)

Quiet (SP mode05) Hi (Normal SP)

0.20 (50) 0.16 (40)

Normal SP upper limit Quiet

0.12 (30) (Normal SP) 0.08 (20) SP mode00 upper limit

SP mode05 lower limit Hi (SP mode00)

0.04 (10) Quiet (SP mode00)

471

530

589

(800)

(900)

(1000)

647

706

765

(1100) (1200) (1300) Air Flow [CFM (m3/h)]

824

883

942

(1400)

(1500)

(1600)

Available air flow rate range (High level)

0.32 (80) 0.28 (70)

Hi (SP mode05)

0.24 (60)

Hi (SP mode04)

0.20 (50)

Hi (SP mode03) Hi (Normal SP)

0.16 (40)

Hi (SP mode02)

0.12 (30)

Hi (SP mode01)

0.08 (20)

Hi (SP mode00)

0.04 (10) 0 (0) 471

530

589

(800)

(900)

(1000)

647

706

765

(1100) (1200) (1300) Air Flow [CFM (m3/h)]

- (04 - 42) -

824

883

942

(1400)

(1500)

(1600)

4. INDOOR UNITS

INDOOR UNITS

External Static Pressure [in.WG (Pa)]

SP mode05 upper limit

0.28 (70)

0 (0)

External Static Pressure [in.WG (Pa)]

INDOOR UNITS

0.32 (80)

120

60.8 (16) Capacity

Capacity (%)

100

59.0 (15)

80

57.2 (14)

60

55.4 (13)

40

53.6 (12)

Outdoor temperature

51.8 (11)

20

50.0 (10)

0 589

(800)

(900)

(1000)

647

706

765

(1100) (1200) (1300) Air Flow [CFM (m3/h)]

824

883

942

(1400)

(1500)

(1600) INDOOR UNITS

530

INDOOR UNITS

471

Output temperature [°F (°C)]

 Cooling

120

113.0 (45)

Capacity (%)

100

111.2 (44)

Capacity

80

109.4 (43)

60

107.6 (42)

40

105.8 (41)

20

104.0 (40)

Outdoor temperature

102.2 (39)

0 471

530

589

(800)

(900)

(1000)

647

706

765

(1100) (1200) (1300) Air Flow [CFM (m3/h)]

- (04 - 43) -

824

883

942

(1400)

(1500)

(1600)

Output temperature [°F (°C)]

 Heating

4. INDOOR UNITS

Type

Model

Operation mode

Cooling

AUU9RLF Heating

Cooling Compact Cassette

AUU12RLF Heating

Cooling

AUU18RLF INDOOR UNITS

Heating

Cooling

ARU9RLF Heating

Cooling

ARU12RLF Heating Slim Duct Cooling

ARU18RLF Heating

Cooling

ARU24RLF Heating

Fan speed

m3/h

Air flow l/s

CFM

High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet

540 490 440 390 540 490 440 390 610 530 470 410 610 530 470 410 750 610 520 410 800 710 600 450 600 530 440 380 600 530 440 380 600 530 440 380 600 530 440 380 930 860 790 640 930 860 790 640 1330 1180 990 700 1330 1180 990 700

150 136 122 108 150 136 122 108 169 147 131 114 169 147 131 114 208 169 144 114 222 197 167 125 167 147 122 106 167 147 122 106 167 147 122 106 167 147 122 106 258 239 219 178 258 239 219 178 369 328 275 194 369 328 275 194

318 288 259 230 318 288 259 230 359 312 277 241 359 312 277 241 441 359 306 241 471 418 353 265 353 312 259 224 353 312 259 224 353 312 259 224 353 312 259 224 547 506 465 377 547 506 465 377 783 695 583 412 783 695 583 412

INDOOR UNITS

8. AIR FLOW

Conversion Factor 1 m3/h = 0.2778 l/s = 0.5886 CFM 3.6 m3/h = 1 l/s 1.699 m3/h = 1 CFM

- (04 - 44) -

4. INDOOR UNITS

Model

Operation mode

Cooling

ASU7RLF Heating

Cooling Compact Wall Mounted

ASU9RLF Heating

Cooling

INDOOR UNITS

ASU12RLF Heating

Cooling

ASU18RLF Heating Wall Mounted Cooling

ASU24RLF Heating

Fan speed

m3/h

Air flow l/s

CFM

High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet High Med Low Quiet

560 500 430 340 560 500 430 350 600 520 430 340 600 520 430 350 660 560 450 340 660 560 470 350 920 740 620 550 920 740 620 550 1120 900 740 620 1100 900 740 620

156 139 119 94 156 139 119 97 167 144 119 94 167 144 119 97 183 156 125 94 183 156 131 97 256 206 172 153 256 206 172 153 311 250 206 172 306 250 206 172

330 294 253 200 330 294 253 206 353 306 253 200 353 306 253 206 388 330 265 200 388 330 277 206 542 436 365 324 542 436 365 324 659 530 436 365 647 530 436 365

INDOOR UNITS

Type

Conversion Factor 1 m3/h = 0.2778 l/s = 0.5886 CFM 3.6 m3/h = 1 l/s 1.699 m3/h = 1 CFM

- (04 - 45) -

4. INDOOR UNITS

9. NOISE LEVEL CURVE 9-1. COMPACT CASSETTE TYPE  MODEL : AUU9RLF Heating

 Cooling 80

80

70

70

N C -55 50 N C -50

N C -45

H igh 40

N C -40

N C -35 30 N C -30

Quiet

N C -25

20 N C -20

60 N C -60

N C -55 50 N C -50

N C -45 H igh

40

N C -40

N C -35

INDOOR UNITS

N C -60

N C -65

Octave band sound pressure level, dB:(0dB=0.0002μbar)

Octave band sound pressure level, dB:(0dB=0.0002μbar)

60

30 N C -30

Quiet

N C -25

20 N C -20

N C -15

N C -15

10

10

0

0 63

125

250

500

1,000

2,000

4,000

8,000

63

125

Octave band center frequency, Hz

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

 MODEL : AUU12RLF Heating

 Cooling 80

80

70

70

N C -65

Octave band sound pressure level, dB:(0dB=0.0002μbar)

N C -65

Octave band sound pressure level, dB:(0dB=0.0002μbar)

INDOOR UNITS

N C -65

60 N C -60

N C -55 50 N C -50 H igh N C -45 40 N C -40

N C -35 30 N C -30

Quiet

N C -25

20 N C -20

60 N C -60

N C -55 50 N C -50

N C -45 H igh 40 N C -40

N C -35 30 N C -30

Quiet

N C -25

20 N C -20

N C -15

N C -15 10

10

0

0 63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

- (04 - 46) -

4. INDOOR UNITS

 MODEL : AUU18RLF Heating

 Cooling 80

80

70

70

N C -65

N C -60

N C -55 50

H igh N C -50

N C -45 40 N C -40

N C -35 30 N C -30 Quiet N C -25 20 N C -20

60 N C -60

N C -55 50 N C -50 H igh N C -45 40 N C -40

N C -35

INDOOR UNITS

Octave band sound pressure level, dB:(0dB=0.0002μbar)

Octave band sound pressure level, dB:(0dB=0.0002μbar)

INDOOR UNITS

N C -65 60

30 N C -30

Quiet

N C -25

20 N C -20

N C -15

N C -15

10

10

0

0 63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

- (04 - 47) -

4. INDOOR UNITS

9-2. SLIM DUCT TYPE  MODEL : ARU9RLF Heating

 Cooling 80

80

70

70

N C -65

N C -55 50 N C -50

N C -45 40 N C -40

N C -35 30 H igh

N C -30

N C -25 20

Quiet

N C -20

60 N C -60

N C -55 50 N C -50

N C -45 40 N C -40

N C -35 30 N C -30

H igh

N C -25 20

Quiet

N C -20

N C -15

N C -15 10

0

0 63

125

250

500

1,000

2,000

4,000

63

8,000

125

Octave band center frequency, Hz

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

 MODEL : ARU12RLF Heating

 Cooling 80

80

70

70

N C -65

Octave band sound pressure level, dB:(0dB=0.0002μbar)

N C -65 60 N C -60

N C -55 50 N C -50

N C -45 40 N C -40

N C -35 30

H igh

N C -30

N C -25 20

Quiet

N C -20

60 N C -60

N C -55 50 N C -50

N C -45 40 N C -40

N C -35 30

H igh

N C -30

N C -25 20

Quiet

N C -20

N C -15

N C -15 10

10

0

0 63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

- (04 - 48) -

4. INDOOR UNITS

INDOOR UNITS

Octave band sound pressure level, dB:(0dB=0.0002μbar)

Octave band sound pressure level, dB:(0dB=0.0002μbar)

N C -60

10

Octave band sound pressure level, dB:(0dB=0.0002μbar)

INDOOR UNITS

N C -65 60

 MODEL : ARU18RLF Heating

 Cooling 80

80

70

70

60 N C -60

N C -55 50 N C -50

N C -45 40 N C -40

N C -35 H igh

30

N C -30

Quiet

N C -25

20 N C -20

60 N C -60

N C -55 50 N C -50

N C -45 40 N C -40

H igh

30 N C -30

N C -25

Quiet

20 N C -20

N C -15

N C -15 10

0 63

N C -35

INDOOR UNITS

Octave band sound pressure level, dB:(0dB=0.0002μbar)

Octave band sound pressure level, dB:(0dB=0.0002μbar)

N C -65

10

0 125

250

500

1,000

2,000

4,000

8,000

63

125

Octave band center frequency, Hz

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

 MODEL : ARU24RLF Heating

 Cooling 80

80

70

70

N C -65

Octave band sound pressure level, dB:(0dB=0.0002μbar)

N C -65

Octave band sound pressure level, dB:(0dB=0.0002μbar)

INDOOR UNITS

N C -65

60 N C -60

N C -55 50 N C -50

N C -45 40 N C -40 H igh

N C -35 30 N C -30 Quiet

N C -25 20 N C -20

60

N C -60

N C -55 50

N C -50

N C -45 40

N C -40 H igh

N C -35 30

N C -30

Quiet

N C -25 20 N C -20

N C -15

N C -15 10

10

0

0 63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

- (04 - 49) -

4. INDOOR UNITS

9-3. COMPACT WALL MOUNTED TYPE  MODEL : ASU7RLF Heating

 Cooling 80

80

70

70

N C -65

N C -55 50 N C -50

N C -45 H igh

40

N C -40

N C -35 30 N C -30

N C -25 20 N C -20

Quiet

60 N C -60

N C -55 50 N C -50

N C -45 40

H igh

N C -40

N C -35 30 N C -30

N C -25 20

Quiet

N C -20

N C -15

N C -15 10

0

0 63

125

250

500

1,000

2,000

4,000

63

8,000

125

Octave band center frequency, Hz

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

 MODEL : ASU9RLF Heating

 Cooling 80

80

70

70

N C -65

Octave band sound pressure level, dB:(0dB=0.0002μbar)

N C -65 60 N C -60

N C -55 50 N C -50

N C -45

H igh 40

N C -40

N C -35 30 N C -30

N C -25 20 N C -20

Quiet

60 N C -60

N C -55 50 N C -50

N C -45 40

H igh N C -40

N C -35 30 N C -30

N C -25 20

Quiet N C -20

N C -15

N C -15 10

10

0

0 63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

- (04 - 50) -

4. INDOOR UNITS

INDOOR UNITS

Octave band sound pressure level, dB:(0dB=0.0002μbar)

Octave band sound pressure level, dB:(0dB=0.0002μbar)

N C -60

10

Octave band sound pressure level, dB:(0dB=0.0002μbar)

INDOOR UNITS

N C -65 60

 MODEL : ASU12RLF Heating

 Cooling 80

80

70

70

N C -65

N C -60

N C -55 50 N C -50 H igh N C -45 40 N C -40

N C -35 30 N C -30

N C -25 20 N C -20

Quiet

60 N C -60

N C -55 50 N C -50

N C -45 H igh 40 N C -40

N C -35 30 N C -30

N C -25 20

Quiet N C -20

N C -15

N C -15

10

10

0

0 63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

- (04 - 51) -

4. INDOOR UNITS

INDOOR UNITS

Octave band sound pressure level, dB:(0dB=0.0002μbar)

Octave band sound pressure level, dB:(0dB=0.0002μbar)

INDOOR UNITS

N C -65 60

9-4. WALL MOUNTED TYPE  MODEL : ASU18RLF Heating

 Cooling 80

80

70

70

N C -65

N C -55 H igh 50 N C -50

N C -45 40 N C -40

N C -35 30 N C -30

Quiet

N C -25 20 N C -20

60 N C -60

N C -55 50 N C -50

H igh

N C -45 40 N C -40

N C -35

INDOOR UNITS

Octave band sound pressure level, dB:(0dB=0.0002μbar)

Octave band sound pressure level, dB:(0dB=0.0002μbar)

N C -60

30 N C -30 Quiet N C -25 20 N C -20

N C -15

N C -15 10

10

0

0 63

125

250

500

1,000

2,000

4,000

63

8,000

125

Octave band center frequency, Hz

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

 MODEL : ASU24RLF Heating

 Cooling 80

80

70

70

N C -65

Octave band sound pressure level, dB:(0dB=0.0002μbar)

N C -65

Octave band sound pressure level, dB:(0dB=0.0002μbar)

INDOOR UNITS

N C -65 60

60 N C -60

N C -55 H igh 50 N C -50

N C -45 40 N C -40

N C -35 30 N C -30 Quiet N C -25 20 N C -20

60 N C -60

N C -55 50 N C -50

H igh

N C -45 40 N C -40

N C -35 30 N C -30 Quiet N C -25 20 N C -20

N C -15

N C -15 10

10

0

0 63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

- (04 - 52) -

4. INDOOR UNITS

9-5. SOUND LEVEL CHECK POINT  COMPACT CASSETTE TYPE

INDOOR UNITS

4ft. 11-1/16in. (1.5m)

INDOOR UNITS

Microphone

Microphone

- (04 - 53) -

4. INDOOR UNITS

 SLIM DUCT TYPE

Microphone

Microphone

Center

Center

Side view

Front view

 COMPACT WALL MOUNTED AND WALL MOUNTED TYPE

Microphone

Microphone

3ft. 3-3/8in. (1m)

- (04 - 54) -

4. INDOOR UNITS

INDOOR UNITS

Measuring duct

2ft. 7-1/2in. (0.8m)

INDOOR UNITS

Measuring duct

3ft. 3-3/8in. (1m)

4ft. 11-1/16in. (1.5m)

6ft. 6-3/4in. (2m)

10. SAFETY DEVICES Model and type

PCB fuse

AUU9RLF Compact Cassette

AUU12RLF

250V 3.15A

AUU18RLF

Compact Wall Mounted

ASU24RLF

250V 3.15A

250V 3.15A

275 ± 59°F (135 ± 15°C)

Float switch









248 ± 59°F

216°F OFF

(120 ± 15°C)

(102°C OFF)

302 ± 59°F

216°F OFF

(150 ± 15°C)

(102°C OFF)





INDOOR UNITS

Wall Mounted

250V 3.15A

Terminal thermal fuse

INDOOR UNITS

Slim Duct

ARU9RLF ARU12RLF ARU18RLF ARU24RLF ASU7RLF ASU9RLF ASU12RLF ASU18RLF

Fan motor thermal protector 266 + 63°F - 48°F (130 +17°C -9°C)

- (04 - 55) -

4. INDOOR UNITS

Hybrid Flex Inverter System

5. CONTROL SYSTEM

DTR_BMU001E_04--CHAPTER05 2010.10.04

CONTENTS 5. CONTROL SYSTEM 1. CONTROL SYSTEM...................................................................... 05 - 01 1-1. LINE UP OF CONTROLLERS ............................................................... 05 - 01 1-2. CONTROL SYSTEM DESIGN ............................................................... 05 - 02 1-3. SYSTEM CONFIGURATION EXAMPLES ............................................. 05 - 03 1-4. CONTROL EQUIPMENT DESIGN LIMITATION .................................... 05 - 05

2. CONTROL UNITS.......................................................................... 05 - 06 2-1. CENTRAL REMOTE CONTROLLER .................................................... 05 - 07 2-2. WIRED REMOTE CONTROLLER ......................................................... 05 - 13 2-3. SIMPLE REMOTE CONTROLLER ........................................................ 05 - 19 2-4. WIRELESS REMOTE CONTROLLER................................................... 05 - 25 2-5. IR RECEIVER UNIT ............................................................................... 05 - 30 2-6. GROUP CONTROL METHOD ............................................................... 05 - 33 2-7. COMPARISON TABLE OF CONTROLLERS ........................................ 05 - 34

1. CONTROL SYSTEM 1-1. LINE UP OF CONTROLLERS  FEATURES OF CONTROL SYSTEM Air Conditioning Central Control

Air Conditioning Individual Control

Central controller specially designs for centralized control.

A range of remote controllers suitable for range of individual control situations, using various built-in timers.

Central Remote Controller

Wired Remote Controller

UTY-DMMUM UTY-RNNUM

Control of indoor units with simple operation and weekly timer.

The room temperature can be controlled and detected accurately with built-in thermo sensor.

Simple Remote Controller

Compact remote controller concentrates on the basic functions such as Start/Stop, Fan Control, Temperature Setting and Operation mode.

Wireless Remote Controller

Simple and sophisticated operations with a choice of 4 daily timers. UTY-LNHUM AR-RAH1U

IR Receiver Unit UTY-LRHUM Wireless remote controller for duct type

- (05 - 01) -

5. CONTROL SYSTEM

CONTROL SYSTEM

CONTROL SYSTEM

UTY-RSNUM

1-2. CONTROL SYSTEM DESIGN  ADVANCED INTEGRATED CONTROL SYSTEM Air Conditioning Central Control

Air Conditioning Individual Control

System Outdoor Unit

Branch box (Primary)

Wired Remote Controller UTY-RNNUM

Central Remote Controller UTY-DMMUM

Simple Remote Controller UTY-RSNUM Branch box (Secondary 1)

CONTROL SYSTEM

CONTROL SYSTEM

Wireless Remote Controller

Transmission line UTY-LNHUM

AR-RAH1U

Remote controller line Central remote controller line

Branch box (Secondary 2)

IR Receiver Unit UTY-LRHUM

- (05 - 02) -

5. CONTROL SYSTEM

1-3. SYSTEM CONFIGURATION EXAMPLES  INDIVIDUAL CONTROL Wired Remote Controller ● Wired, simple, and wireless remote controllers can be used jointly. ● Two remote controllers can be connected with single indoor unit.

Branch box (Primary)

Branch box (Secondary 1)

Branch box (Secondary 2)

Outdoor unit

Wired Remote Controller

Simple Remote Controller ● Enables easy control of basic functions by the hotel or office guest. ● Two remote controller can be connected with single indoor unit.

Branch box (Primary)

Branch box (Secondary 1)

Branch box (Secondary 2)

Outdoor unit

Simple & Wired Remote Controller

● Wired, simple, and wireless remote controllers can be used jointly.

Branch box (Primary)

Branch box (Secondary 1)

Branch box (Secondary 2)

Outdoor unit

Wireless & Wired Remote Controller

 CENTRAL CONTROL Central Remote Controller ● Up to 8 indoor units can be controlled with one central remote controller. ● The central remote controller can be used simultaneously with wired, simple, and wireless remote controller. ● Only one can be used for one system.

Branch box (Primary)

Branch box (Secondary 1)

Branch box (Secondary 2)

Outdoor unit

Central Remote Controller

- (05 - 03) -

5. CONTROL SYSTEM

CONTROL SYSTEM

CONTROL SYSTEM

Wireless Remote Controller

 INDOOR UNIT TYPE AND THE APPLICABLE CONTROL METHOD Type

Indoor units Compact Slim Duct Wall Mounted  *1  *1

Model

Compact Cassette

UTY-DMMUM

 *1

UTY-RNNUM





 *2



UTY-LNHUM









AR-RAH1U









IR Receiver Unit

UTY-LRHUM









Simple Remote Controller

UTY-RSNUM





 *2



Central Remote Controller Wired Remote Controller Wireless Remote Controller

Wall Mounted  *1

: Accessory, : Optional, –: It is not possible to connect it. *1: Central remote controller is connected with Branch box.

CONTROL SYSTEM

CONTROL SYSTEM

*2: Optional Communication kit (UTY-XCBXEZ1) is necessary for the installation.

- (05 - 04) -

5. CONTROL SYSTEM

1-4. CONTROL EQUIPMENT DESIGN LIMITATION

Central Controller

Central Remote Controller

Model

The number that can be connected

UTY-DMMUM

1 / Multi system

UTY-LNHUM Wireless Remote Controller

AR-RAH1U

Controller Wired Remote Controller

UTY-RNNUM

Simple Remote Controller

UTY-RSNUM

IR Receiver Unit

UTY-LRHUM

2 / Indoor unit

CONTROL SYSTEM

1 / Indoor unit

CONTROL SYSTEM

Individual Controller

- (05 - 05) -

5. CONTROL SYSTEM

2. CONTROL UNITS The following types of controllers are available with the FUJITSU GENERAL LIMITED Hybrid Flex Inverter System :

 Central Remote Controller  Wired Remote Controller  Simple Remote Controller  Wireless Remote Controller  IR Receiver Unit

Central Control

CONTROL SYSTEM

CONTROL SYSTEM

Central Remote Controller

Individual Control Wired Remote Controller

Simple Remote Controller

Wireless Remote Controller

IR Receiver Unit

- (05 - 06) -

5. CONTROL SYSTEM

2-1. CENTRAL REMOTE CONTROLLER  MODEL : UTY - DMMUM ● Large and full-dot liquid crystal screen ● Screen with backlight can be seen even in the dark ● Wide and large keys easy to press, user-intuitive arrow key

 FEATURES Batched control of up to 8 indoor units. The temperature, airflow volume, and remote control prohibition settings of all indoor units can be batched.

 User-friendly operation ● Large backlight LED screen ● Large easy-to-see operation panel

 Easy installation ● Central remote controller is connected directly to the branch box, making the installation process easier. ● Once the controller is connected, it can automatic register and display all the indoor units.

- (05 - 07) -

5. CONTROL SYSTEM

CONTROL SYSTEM

CONTROL SYSTEM

 Central & Individual Control

 MAIN FUNCTIONS  Outdoor unit low noise operation Air conditioning load factor

● Users can choose from 4 low noise levels, depending on the installation environment.

Heat load

100%

Down

Capacity 0 58dB

Operating sound

0

(time) Low noise operation

● While this function is selected, all indoor units start the minimum heat operation when all the indoor units are stopped by operation of the [On/Off button]. ● When the room temperature is higher than 50°F (10°C), MIN. HEAT operation starts and maintains the room temperature at 50°F (10°C) when the temperature drops below 50°F (10°C). ● When “MIN, HEAT operation stops, the room set temperature quickly returns to the preset temperature.

All indoor units OFF “All MIN. HEAT” operation ON

70°F Indoor unit operation START

CONTROL SYSTEM

50°F

 Economy (All) operation Temp.

Example : Cooling operation

● If all the indoor and outdoor units are changed to economy mode, this can save more energy than setting of each indoor unit individually. ● Economy operation is energy saving, as the set temperature of indoor unit is shifted by 2°F (1°C) and the maximum electric value of the outdoor unit is suppressed.

Economy operation Shift setting temp

Set temperature

Nomal operation

Time

Control maxmum current

 Schedule timer Example Temp. Cool

Temp.

PM12

Cool

PM5

Heat

Heat AM7

Cool

PM11 Time

AM8

Cool

PM1

Cool PM6

● Operation setting can be changed 4 times in each day of a week, and 2types of the schedule can be set to suit users' preference.

PM10 Time

Temp.

Cool AM7

Winter season pattern

Saturday~Sunday

Temp.

Monday~Friday

Summer season pattern

Heat

PM12 PM1

Heat PM11 Time

AM7

PM1

Heat PM6

Heat PM11 Time

 Prohibited Settings The remote controller operation of all indoor units comes with a lock function to prevent unapproved operations in the various rooms. The central remote controller also has a key lock function to prevent children from playing with it, etc - (05 - 08) -

5. CONTROL SYSTEM

CONTROL SYSTEM

 Minimum heat (All) operation

 FUNCTIONS

1

2

6 7

3

8

5

9

1 Display panel (with backlight)

6 Screen switch button (Right)

2 Screen switch button (Left)

7 Power indicator

3 Menu button

8 On / Off button

4 Cancel button

9 Enter button

5 Cursor button

 ELECTRICAL WIRING Example: Wiring diagram when 3 units of branch boxes are connected Branch box (Primary)

Branch box (Secondary 1)

Branch box (Secondary 2)

REMOTE CONTROL

REMOTE CONTROL

REMOTE CONTROL

1 2 3

1 2 3

1 2 3

Remote controller cable 1 2 3

• Total remote controller cable length: MAX. 500 m (1640 ft.) Central remote controller

- (05 - 09) -

5. CONTROL SYSTEM

CONTROL SYSTEM

CONTROL SYSTEM

4

 INSTALLATION 1) Remove the insulation of the remote controller cable. 55 (2-5/32) 45 (1-25/32) 30 (1-3/16) Unit : mm (in.)

8 (5/16) 8

8 (5/16) 1. 12V (Red)

(5/16)

2. Signal (White) 3. COM (Black)

2) Insert the flat-blade screwdriver and remove the front case and rear case by twisting it slightly. Hooks (2 places)

Rear case

Front case

3) Install the rear case to the wall, box, etc. with 2 screws (M4 × 16 mm). Fix the 2 screws in either horizontal or vertical position. A. When mounting on the box:

B. When the cable is along the wall:

● Attach the case after leading the cable.

● Mount the rear case on the wall. ● Cut off a hole for cabling in the front case.

Remote controller cable

Cut off

Box Screws Rear case

Front case

CAUTION ● When connecting the remote controller cable, take measures to prevent the water or insects coming into the remote controller through the cable, such as to provide the trap or close the hole for cabling with the putty. Putty Trap

Putty

Putty Trap Trap

4) Setting up the DIP switch. Refer to "6. SYSTEM DESIGN".

- (05 - 10) -

5. CONTROL SYSTEM

CONTROL SYSTEM

CONTROL SYSTEM

Flat screwdriver

5) Connect the cable to the terminals on the front case. Fix the cable together with the sheath with the binder. Cut off the excess binder. Tightening torque Terminal screw 0.8 to 1.2N • m (7 to 10 lbf • in)

Binder 1. 12V (Red)

Remote controller cable (sheath)

2. Signal (White)

Hole for binder Good

3. COM (Black)

2 mm (3/32 in.)

No good

No good

CAUTION

6) Attach the front case.

CONTROL SYSTEM

CONTROL SYSTEM

● Be careful to avoid breaking the cable by over-tightening the binder. ● When connecting the remote controller cables, do not over-tighten the screws.

● Insert after adjusting upper part of front case. ● When insert the front case, do not pinch the cable. Front case

Click!

Good

No good

No good

No good

CAUTION ● Insert the upper case firmly. If improperly attached, it will cause the upper case to fall off.

- (05 - 11) -

5. CONTROL SYSTEM

 DIMENSIONS

Unit : in. (mm)

Side View

11/32 (9)

2-1/2 (63.5)

1/2 (12.5)

3/16 (4.5)

3/16 (4.5)

1-25/32 (45.3)

4-23/32 (120)

Front View

29/32 (23)

3/16 (4.5)

3-9/32 (83.5)

27/32 (21.3)

4-23/32 (120)

1-5/16 (33.5)

19/32 (15.3)

1-3/16 (30)

Rear View

 PACKING LIST Quantity

Remote controller cable

1

Screw (M4 x 16mm)

2

Binder

1

Installation manual

1

Operating manual

1

Application For connecting the remote controller For installing the remote controller For remote controller and remote controller cable binding

 WIRING SPECIFICATIONS Use Remote controller cable

Cable size 22AWG ( 0.33 mm2 )

Remarks Use sheathed PVC cable, Polar 3 core

 SPECIFICATIONS Dimensions [H x W x D]: in.(mm)

4-23/32 (120) x 4-23/32 (120) x 27/32 (21.3)

Weight: oz. (g)

7.8 (220)

- (05 - 12) -

5. CONTROL SYSTEM

CONTROL SYSTEM

CONTROL SYSTEM

Name and shape

2-2. WIRED REMOTE CONTROLLER  MODEL : UTY - RNNUM  FEATURES

● Various timer setup (ON / OFF / WEEKLY) are possible. ● Equipped with weekly timer as standard function. (Start / Stop function is twice per day for a week) ● When setting up a timer, start / stop and a temperature setup can be changed. ● When a failure occurs,the error code is displayed. ● Error history.(Last 16 error codes can be accessed.) ● The room temperature can be controlled by being detective the temperature accurately with Built-in thermo sensor.

 Powerful features and compact size Thermo sensor

Weekly timer

Wired remote controller

Setback timer

CONTROL SYSTEM

 Accurate and comfortable

Sensor part

Indoor temperature can be detected accurately by the inclusion of a thermo sensor in the body of the wired controller. Our system can correspond to various scenes. This wired remote controller and the optional remote sensor allows flexibility in sensor location, and suitable for all requirements.

Thermo sensor display Control part for changing the thermo sensor

 Built-in timers Weekly timer

Setback timer

Possible to set ON/OFF time to operate twice each day of the week.

Possible to set temperature for two time spans and for each day of the week.

Easy-to-understand time bar display Screen after setup

Example : setup screen (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)

Example : setup screen (Set to Wednesday: 8:00 to 20:00.)

84°F (28°C)

76°F (24°C) 0 time 12

3 3

6 6 AM

9 9

12 12

15 3

18 6

21 9

0 time 12

O'clock

3 3

6 6

9 9

12 12

AM

PM

At "Weekly timer" + "Set back timer" setup 76°F (24°C)

76°F 24°C

84°F 28°C

76°F 24°C

0 time 12

3 3

6 6 AM

 Easy-to-understand operation

9 9

15 3

18 6

21 9

O'clock

PM

84°F (28°C)

12 12

15 3

18 6

21 9

O'clock

PM

 Simple installation Components are compatible with standard switch boxes. Flat back surface allows equipment to be installed wherever it is needed.

Timer area

Operation area

European switch box

[Variable timer control] The operation/display sections are zoned according to time and operation, enabling variable programming to match application. - (05 - 13) -

JIS box

5. CONTROL SYSTEM

CONTROL SYSTEM

Individual control

 FUNCTIONS 1

START/STOP button Pressed to start and stop operation.

7

2 Display

SET TEMP. button Selects the setting temperature.

3 2 8 9 10 11

1 3 4 6 5

12

14 15

13

MODE button Selects the operating mode (AUTO , COOL , DRY , FAN , HEAT ).

16

4

FAN button Selects the fan speed (AUTO , HIGH , MED LOW , QUIET ).

5

,

Vertical air flow direction and swing button Press for two seconds to change the swing mode

6

Horizontal air flow direction and swing button

7

Built-in thermo sensor

8

TIMER MODE (CLOCK ADJUST) button

Press for two seconds to change the swing mode. Detect room temperature.

Display panel

Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.

9 17

20 21 19

18

DAY (DAY OFF) button Temporarily cancels of one day timer.

10 SET BACK button Pressed select the set back timer.

11 SET TIME button

27 25 26 23 24 22

The schedule of a weekly timer is deleted.

13 TIME SET button Sets the date, hour, minute and on-off time.

14 ECONOMY (THERMO SENSOR) button 15 FILTER RESET button 16 Operation lamp Lights during operation and when the timer is on.

17 Timer and clock display 18 Operation mode display 19 Fan speed display 20 Operation lock display 21 Temperature display Displayed temperature is set temperature.

22 Defrost display Indicates during the oil recovery and defrosting operation.

23 Vertical swing display 24 Horizontal swing display 25 Economy display 26 Thermo sensor display 27 Filter display Note: Functions will be different due to type of indoor unit. For details, please see operation manual.

- (05 - 14) -

5. CONTROL SYSTEM

CONTROL SYSTEM

CONTROL SYSTEM

Pressed to select the set back timer.

12 TIMER DELETE button

 SYSTEM DIAGRAM 2 remote controllers

 1 remote controller Indoor unit

Indoor unit

A

B

C

Primary

Remote controller

A , B , C : Remote controller cable. A< =1640ft (500m) ; B+C < =1640ft (500m)

Secondary

Remote controllers

 ELECTRICAL WIRING 2 remote controllers

 1 remote controller

REMOTE CONTROLLER

1 2 3

1 2 3

1 2 3

1 2 3

Primary

Remote controller

1 (RED) : 12V 2 (WHITE) : Signal 3 (BLACK) : COM

1 2 3

Secondary

Remote controllers

 DIMENSIONS

Front View

Side View

- (05 - 15) -

Rear View

5/16 (8)

3/16 (4.5)

3-9/32 (83.5)

3/16 (4.5) 1/2 (12.5)

3/16 (4.5)

1-25/32 (45.3)

4- 23/32 (120)

29/32 (23)

Hole

21/32 (17)

2-1/2 (63.5)

1-3/16 (30) 1-5/16 (33.5) 4- 23/32 (120)

19/32 (15.3)

Unit : in. (mm)

4- 23/32 (120)

CONTROL SYSTEM

REMOTE CONTROLLER

1/4 (6) Hole x 2 Hole x 3

5. CONTROL SYSTEM

CONTROL SYSTEM

Indoor unit

Indoor unit

 INSTALLATION  Connection Pattern Note: Connection pattern is different according to type of Indoor unit. Indoor unit types Compact Cassette type Slim Duct type Compact Wall Mounted type Wall Mounted type

Connection Pattern Pattern A Pattern B Pattern C

 Pattern A Connect the end of remote controller cable directly to the exclusive terminal block. M4 screw Remote controller terminal block

Remote controller cable

Indoor unit

Outdoor unit / Power supply terminal block

PCB

Terminal block

Note: It may be failed if it is connected to the outdoor unit or the terminal block for power supply.

● Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. ● Connect the remote controller cable and connecting cable as shown in Fig. ● Be sure to insulate the connection between the cables. Connecting cable White Red Black

White Red Remote controller cable

Insulated connection Black

2) Method of connecting remote controller cable ● Connecting cable made by above-mentioned 1) is connected with terminal (CN305) of optional communication kit (UTY-XCBXZ1). ● Cable connected with terminal (CN301) of communication kit (UTY-XCBXZ1) is connected with PCB of Indoor unit.

Remote controller cable

Connecting cable

Terminal (CN301) Terminal (CN305)

Communication kit (UTY-XCBXZ1)

- (05 - 16) -

Indoor unit PCB

5. CONTROL SYSTEM

CONTROL SYSTEM

1) Modify the remote controller cable as per below methods.

25/32 in. (20 mm)

CONTROL SYSTEM

 Pattern B

 Pattern C 1) Modify the remote controller cable as per below methods. ● Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. ● Connect the remote controller cable and connecting cable as shown in Fig. ● Be sure to insulate the connection between the cables. 25/32 in. (20 mm)

Connecting cable White Red Black

White Red Remote controller cable

Insulated connection Black

2) Method of connecting remote controller cable

Remote controller cable

Connecting cable

CONTROL SYSTEM

CONTROL SYSTEM

● Connecting cable made by above-mentioned 1) is connected with PCB of Indoor unit.

CN6

Indoor unit PCB

- (05 - 17) -

5. CONTROL SYSTEM

 PACKING LIST Name and shape

Quantity

Remote controller cable

1

Application For connecting the remote controller

[33ft(10m)] 2

Binder

1

Connecting cable *1

1

CONTROL SYSTEM

Screw *1 (M4 x 14mm)

1

Cable clamper *1

1

Installation manual

1

Operating manual

1

For installing the remote controller For remote controller and remote controller cable binding For connecting the remote controller cable to the Compact wall mounted type and Wall mounted type indoor unit

For installing the remote controller cable to the indoor unit For installing the remote controller cable to the indoor unit

CONTROL SYSTEM

Screw (M4 x 16mm)

*1: Use only if the remote controller cable must be modified for the indoor unit model.

 WIRING SPECIFICATIONS Use Remote controller cable

Cable size 22AWG ( 0.33 mm2 )

Remarks Use sheathed PVC cable, Polar 3 core

 SPECIFICATIONS Dimensions [H x W x D]: in.(mm)

4-23/32 (120) x 4-23/32 (120) x 21/32 (17)

Weight: oz. (g)

5.6 (160)

- (05 - 18) -

5. CONTROL SYSTEM

2-3. SIMPLE REMOTE CONTROLLER  MODEL : UTY - RSNUM  FEATURES ● Easy operation. ● Built-in background light function. ● Easy installation with a slim shape with no bulge in the back. ● Error history.(Last 16 error codes can be accessed.) ● Can be installed onto SW-BOX. (applies to European and other country's standard)

 User-friendly operation ● Provides access to basic operations, such as Start / Stop, Fan speed, operation mode and room temperature setting. ● A large Start / Stop button is provided in the centre of the remote controller unit for easy operation. ● Following an error display, diagnostics can be carried out on the controller.

 Simple installation Can be mounted on the European switch Box (installation dimension: 60mm) or the JIS Built-in Box (installation dimension: 83.5mm)

2-3/8in. (60mm) European switch box

JIS Built-in box

- (05 - 19) -

5. CONTROL SYSTEM

CONTROL SYSTEM

● Background light enables easy operation in a darkened room. ● Background light activates during all button operations, and lasts 10 seconds in operating mode and 5 seconds in stop mode after a button is pressed.

3-9/32in. (83.5mm)

CONTROL SYSTEM

 Background light

 FUNCTIONS 1

START/STOP button

2

Display background light

3

Operation lamp

Pressed to start and stop operation. Lights during operation. Lights during operation. 2

4

3 4

5

6

FAN button Selects the fan speed (AUTO LOW

1

5

, HIGH , MED , QUIET ).

,

SET TEMP. button Selects the setting temperature.

6

MODE button Selects the operating mode (AUTO

7

Standby display

8

Power source display

9

Central control display

, COOL

, DRY ,FAN

, HEAT

).

Indicates during the oil recovery and defrosting operation. Indicates the main power ON.

Display panel

Indicates when function is locked. 7

8

13

9

10 Fan speed display 11 Set temperature

10

Indicates Error history number. *1 Indicates Indoor unit address. *2

11

CONTROL SYSTEM

12

13 (Upper) Indicates the error code *1 *3 / the refrigerant

system address. *2 (Lower) Indicates the remote controller address. *1 *2 *3

*1: during Error code history display mode. *2: during address display mode. *3: during self Diagnosis mode.

 SYSTEM DIAGRAM  1 remote controller

2 remote controllers

Indoor unit

A

Indoor unit

B

C

Primary Remote controller

Secondary

Remote controllers

A , B , C : Remote controller cable. A< =1640ft (500m) ; B+C < =1640ft (500m)

- (05 - 20) -

5. CONTROL SYSTEM

CONTROL SYSTEM

12 Operating mode display

 ELECTRICAL WIRING  2 remote controllers

 1 remote controller Indoor unit

Indoor unit

REMOTE CONTROLLER

REMOTE CONTROLLER

1 2 3

1 2 3

1 2 3

1 2 3

Secondary

Primary Remote controller

1 (RED) : 12V 2 (WHITE) : Signal 3 (BLACK) : COM

1 2 3

Remote controllers

 DIMENSIONS 7/16 (11) 23/32 (18)

11/32 (9)

1/4 (6)

1/2 (12.5)

3/16 (4.5)

2-3/8 (60)

3-9/32 (83.5)

1-7/8 (47.5)

15/16 (23.5)

hole x 2

5/32 (4)

CONTROL SYSTEM

9/16 (14)

4-23/32 (120)

CONTROL SYSTEM

Unit : in. (mm) 2-15/16 (75) 1-15/16 (49) 1-17/32 (39)

5/16 (8)

hole x 2

Front View

Side View

- (05 - 21) -

Rear View

5. CONTROL SYSTEM

 INSTALLATION  Connection Pattern Note: Connection pattern is different according to type of Indoor unit. Indoor unit types Compact Cassette type Slim Duct type Compact Wall Mounted type Wall Mounted type

Connection Pattern Pattern A Pattern B Pattern C

 Pattern A Connect the end of remote controller cable directly to the exclusive terminal block. M4 screw Remote controller terminal block

Remote controller cable

Indoor unit

Outdoor unit / Power supply terminal block

PCB

Terminal block

Note: It may be failed if it is connected to the outdoor unit or the terminal block for power supply.

● Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. ● Connect the remote controller cable and connecting cable as shown in Fig. ● Be sure to insulate the connection between the cables. Connecting cable White Red Black

White Red Remote controller cable

Insulated connection Black

2) Method of connecting remote controller cable ● Connecting cable made by above-mentioned 1) is connected with terminal (CN305) of optional communication kit (UTY-XCBXZ1). ● Cable connected with terminal (CN301) of communication kit (UTY-XCBXZ1) is connected with PCB of Indoor unit.

Remote controller cable

Connecting cable

Terminal (CN301) Terminal (CN305)

Communication kit (UTY-XCBXZ1)

- (05 - 22) -

Indoor unit PCB

5. CONTROL SYSTEM

CONTROL SYSTEM

1) Modify the remote controller cable as per below methods.

25/32 in. (20 mm)

CONTROL SYSTEM

 Pattern B

 Pattern C 1) Modify the remote controller cable as per below methods. ● Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. ● Connect the remote controller cable and connecting cable as shown in Fig. ● Be sure to insulate the connection between the cables. 25/32 in. (20 mm)

Connecting cable White Red Black

White Red Remote controller cable

Insulated connection Black

2) Method of connecting remote controller cable

Remote controller cable

Connecting cable

CONTROL SYSTEM

CONTROL SYSTEM

● Connecting cable made by above-mentioned 1) is connected with PCB of Indoor unit.

CN6

Indoor unit PCB

- (05 - 23) -

5. CONTROL SYSTEM

 PACKING LIST Name and shape

Quantity

Application For connecting the remote controller

Remote controller cable

1

[33ft(10m)] Screw (M4 x 16mm)

2

Binder

1

Connecting cable *1

1

1

Cable clamper *1

1

Installation manual

1

Operating manual

1

For remote controller and remote controller cable binding For connecting the remote controller cable to the Compact wall mounted type and Wall mounted type indoor unit

For installing the remote controller cable to the indoor unit For installing the remote controller cable to the indoor unit

*1: Use only if the remote controller cable must be modified for the indoor unit model.

CONTROL SYSTEM

CONTROL SYSTEM

Screw *1 (M4 x 14mm)

For installing the remote controller

 WIRING SPECIFICATIONS Use Remote controller cable

Cable size 22AWG ( 0.33 mm2 )

Remarks Use sheathed PVC cable, Polar 3 core

 SPECIFICATIONS Dimensions [H x W x D]: in. (mm)

4-23/32 (120) x 2-15/16 (75) x 9/16 (14)

Weight: oz. (g)

3.2 (90)

- (05 - 24) -

5. CONTROL SYSTEM

2-4. WIRELESS REMOTE CONTROLLER  MODEL : UTY - LNHUM / AR-RAH1U  FEATURES ● Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible. ● Can be used jointly with wired remote controllers . ● Easy to change custom code (4 patterns).

 Built-in timers Select from four different timer programs (On / Off / Program / Sleep).

 Program timer The program timer operates the ON and OFF timer once within a 24 hour period.

 Sleep timer

Cooling operation / dry operation

Heating operation

When the sleep timer is set, the set temperature automatically rises 2°F (1°C) every hour. The set temperature can rise up to a maximum of 4°F (2°C).

When the sleep timer is set, the set temperature automatically drops 2°F (1°C) every 30 minutes. The set temperature can drop to a maximum of 8°F (4°C).

Timer setting

2°F (1°C) 4°F (2°C)

60min.

6°F (3°C)

8°F (4°C)

30min. 60min. 4°F (2°C)

2°F (1°C)

90min. Timer setting

 Switching remote controller signal code After code change I.U.

Mixed-up I.U. I.U.

I.U.

A I.U.

B

C

D

I.U.

I.U.

I.U.

A

B

C

D

• Code selector switch eliminates unit being wrongly switched. (Up to 4 codes can be set.) *I.U.=Indoor unit

- (05 - 25) -

5. CONTROL SYSTEM

CONTROL SYSTEM

CONTROL SYSTEM

The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping.

 FUNCTIONS (UTY-LNHUM) 1

MODE button Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT). /Start / end R.C. custom code change. (Max 4 types)

16

2

MIN.HEAT button

3

Set temp. button ( ▲ / ▼ ) Set remote controller custom code buttons Sets the indoor temp./ Sets R.C. custom code.

4

ECONOMY button

5

SLEEP button Pressed to select sleep timer.

6 1

6

3

7

2

8

4

9

5

10

FAN button Selects the fan speed (AUTO, HIGH, MED, LOW, QUIET).

7

START/STOP button

8

SET button (Vertical)

Pressed to start and stop operation. Air flow direction vertical set button.

9

SET button (Horizontal) Air flow direction horizontal set button.

10 SWING button 11 13

Air flow direction swing button. 14 12 15

11 TIMER MODE button Pressed to select the timer mode. (OFF TIMER, ON TIMER, PROGRAM TIMER, TIMER RESET)

12 TIMER SET ( + / - ) button CONTROL SYSTEM

CONTROL SYSTEM

Sets the current time and on-off time.

13 CLOCK ADJUST button Sets the current time.

14 RESET button Used when replacing batteries.

15 TEST RUN button Used when testing the air conditioner after installation.

Display panel

16 Signal transmitter 17 Temperature set display

17 20

18 Operating mode display 19 Sleep display 20 Transmit indicator

18

21

21 Fan speed display 22 Swing display

22

23 Timer mode display 24 Clock display

19

23

24

Note: Functions will be different due to type of indoor unit. For details, please see operation manual.

- (05 - 26) -

5. CONTROL SYSTEM

 FUNCTIONS (AR-RAH1U) 1

MODE button Selects the operating mode (AUTO, COOL, DRY, FAN, HEAT). /Start / end R.C. custom code change. (Max 4 types)

15

2

MIN.HEAT button

3

Set temp. button ( ▲ / ▼ ) Set remote controller custom code buttons Sets the indoor temp./ Sets R.C. custom code.

4

ECONOMY button

5

SLEEP button Pressed to select sleep timer.

6 1

6

3

7

FAN button Selects the fan speed (AUTO, HIGH, MED, LOW, QUIET).

7

START/STOP button

8

SET button (Vertical)

Pressed to start and stop operation. 2 4

8

5

9

Air flow direction vertical set button.

9

Air flow direction swing button.

10 TIMER MODE button

10 12

SWING button

Pressed to select the timer mode. (OFF TIMER, ON TIMER, PROGRAM TIMER, TIMER RESET) 13 11 14

11 TIMER SET ( + / - ) button Sets the current time and on-off time.

12 CLOCK ADJUST button

Used when replacing batteries.

14 TEST RUN button Used when testing the air conditioner after installation.

15 Signal transmitter 16 Temperature set display

Display panel

17 Operating mode display 18 Sleep display

16 19

19 Transmit indicator 20 Fan speed display

17

21 Swing display 20

22 Timer mode display 23 Clock display

21

18

22

23

Note: Functions will be different due to type of indoor unit. For details, please see operation manual.

- (05 - 27) -

5. CONTROL SYSTEM

CONTROL SYSTEM

CONTROL SYSTEM

Sets the current time.

13 RESET button

 SYSTEM DIAGRAM

Signal transmitter

Signal receiver window

● Control signal might not be recognized in following cases: (i) A curtain or a wall, etc. exists between transmitter and receiver. (ii) There is an instant-start type (inverter type, etc.) fluorescent lamp in the room. ● Air conditioner might not work correctly when strong light hits the signal receiver window. Shut off the direct sunlight and also make illuminator far away from the receiver window.

 DIMENSIONS  Controller Unit : in. (mm)

CONTROL SYSTEM

6-11/16 (170)

CONTROL SYSTEM

Top View

3/4 (19)

2-7/32 (56)

Front View

Side View

Rear View

 Holder 1 (25.5)

2-3/8 (60.4) 1-3/16 (30.2)

6-3/32 (154.7)

3-3/4 (95)

Ø1/8 (3.5) (HOLE)

1/8 x 1/4 (3.5 x 6.5) (HOLE)

1-1/32 (26.2)

Front View

Side View

- (05 - 28) -

Bottom View

5. CONTROL SYSTEM

 PACKING LIST Name and shape

Quantity

Installation manual

1

Operating manual

1

Remote controller holder

1

Tapping screw

2

Battery [ 1.5V (R03 / AAA) ]

2

Application

Use as remote controller holder For remote controller holder installation

For remote controller

 SPECIFICATIONS Weight : oz. (g)

3 (85) [w/o batteries]

CONTROL SYSTEM

6-11/16 (170) x 2-7/32 (56) x 3/4 (19)

CONTROL SYSTEM

Dimensions [H x W x D]: in. (mm)

- (05 - 29) -

5. CONTROL SYSTEM

2-5. IR RECEIVER UNIT  MODEL : UTY - LRHUM  FEATURES Duct type indoor unit can be controlled with wireless remote controller if the IR receiver unit is used.

 FUNCTIONS Wireless remote controller IR Receiver

MANUAL AUTO SIGNAL RECEIVER Refer to 2-4.WIRELESS REMOTE CONTROLLER for details.

 SYSTEM DIAGRAM  ATTACHMENT RANGE 1)

L

L

1)

1) Connection cable length L Cable A (standard accessory) : 16ft. (5 m) Cable C (Optional parts) : 33ft. (10 m)

 SIGNAL ANGLE

120

120

16ft. (5m)

16ft. (5m)

- (05 - 30) -

5. CONTROL SYSTEM

CONTROL SYSTEM

CONTROL SYSTEM

OPERATION LAMP TIMER LAMP ECONOMY LAMP

 ELECTRICAL WIRING Connected to CN13 of PCB

PCB CN13

Connection cable B [L = 7-7/8in. (0.2m)] ...Standard accessory

Connection cable A [L = 16ft. (5m)]...Standard accessory Connection cable C [L = 33ft. (10m)]...Optional service parts

2-3/8in. x 4-3/4in. (60mm x 120mm) hole

Connected to Connection cable Connected to IR Receiver Unit

IR Receiver Unit

 DIMENSIONS Unit : in. (mm)

/32

Side View

Rear View

21/32 (17)

CONTROL SYSTEM

3-9

Front View

(83

.5)

5-23/32 (145)

2-3/8 (60)

CONTROL SYSTEM

9/32 (7.2)

4-21/32 (118.4)

9/32 (7.2)

3-17/32 (90)

17/32 (13.6) 29/32 (22.9)

2-1/4 (57.4)

2-27/32 (72.4)

17/32 (13.6)

2-9/32 (57.6)

7/16 23/32 (11.5) (18.5) 11/32 (8.5)

- (05 - 31) -

5. CONTROL SYSTEM

 PACKING LIST Quantity

Application

Installation manual

1

Operating manual

1

Cover

1

For covering receiver unit

Insulation

1

For protecting PCB from dust

Connection cable A [16ft. (5m)]

1

For connecting PCB of indoor unit to receiver unit

Connection cable B [7-7/8in. (0.2m)]

1

For connecting PCB of indoor unit to receiver unit

Bracket (cover)

1

For fixing receiver unit to the wall or ceiling

Screw (M3 x 12mm)

2

For installing remote control unit holder to the wall

Screw (M4 x 20mm)

2

For installing receiver unit to the wall or ceiling

Battery (R03/LR03)

2

For remote controller

Remote controller holder

1

Use as remote controller holder

 SPECIFICATIONS (IR Receiver) Dimensions [H x W x D]: in. (mm)

5-23/32 (145) x 3-17/32 (90) x 1-3/16 (30)

Weight: oz. (g)

5.3 (150)

 OPTIONAL SERVICE PARTS Please use the parts number shown below to order the cable from your sales representative. Select shielded type conncetion cable in accordance with the standard of the country. Name and shape Connection cable C [33ft. (10m)]

Parts No. 9707598025

- (05 - 32) -

5. CONTROL SYSTEM

CONTROL SYSTEM

CONTROL SYSTEM

Name and shape

2-6. GROUP CONTROL METHOD  REMOTE CONTROLLER GROUP Wired, Simple and Wireless Remote Controllers can be used jointly in the following combinations.

CONTROL SYSTEM

CONTROL SYSTEM

Example of combination for "Remote controller group"

- (05 - 33) -

5. CONTROL SYSTEM

2-7. COMPARISON TABLE OF CONTROLLERS

Item

Central Remote Controller

Wired Remote Controller

Simple Remote Controller

Wireless Remote Controller

Model

UTY-DMMUM

UTY-RNNUM

UTY-RSNUM

UTY-LNHUM AR-RAH1U

8

1

1

1

Room temp. setting

● ● ● ●

Test operation



● ● ● ● ●

Up / down air direction flap setting



● ● ● ● ● ● ●

● ● ● ● ● ● ● / – *1



Max. controllable indoor units

Display

Operation mode setting Fan speed setting



RC prohibition

● ● ●













● ●

Low noise mode setting for outdoor unit (Outdoor Unit Quiet)









Failure

● –

● ●



Defrosting Current time

● ● ●





Min. heat setting Economy setting





● ● ● ● ● ● ●





On / Off per day

2

2





On / Off per week

14

14





On / Off timer







Sleep timer







Program timer







● ● ●

Day off









Status monitoring system









Error history









Day of week Address display Weekly timer

Timer



Right / left air direction flap setting

RC prohibition

Control

CONTROL SYSTEM

Air conditioning control function

Start/Stop









● ●

– –

*1: This function is not provided in AR-RAH1U.

- (05 - 34) -

5. CONTROL SYSTEM

CONTROL SYSTEM

 LIST OF CONTROLLER FUNCTION

Hybrid Flex Inverter System

6. SYSTEM DESIGN

DTR_BMU001E_04--CHAPTER06 2010.10.04

CONTENTS 6. SYSTEM DESIGN 1. SYSTEM DESIGN ......................................................................... 06 - 01 1-1. SYSTEM OUTLINE ................................................................................ 06 - 01 1-2. REFRIGERANT SYSTEM ...................................................................... 06 - 02 1-3. WIRING SYSTEM................................................................................... 06 - 07 1-4. MOUNTING POSITION .......................................................................... 06 - 08

2. PIPING DESIGN ............................................................................ 06 - 10 2-1. IMPORTANT ITEMS WHEN USING NEW REFRIGERANT (R410A) ... 06 - 10 2-2. PIPING LIMITATION .............................................................................. 06 - 12 2-3. PIPE SIZE............................................................................................... 06 - 14 2-4. SELECTION OF PIPE HEAT INSULATING MATERIAL ....................... 06 - 16 2-5. ADDITIONAL CHARGE CALCULATION .............................................. 06 - 17 2-6. EXAMPLE OF PIPING DESIGN ............................................................ 06 - 18

3. INSTALLATION ............................................................................. 06 - 26 3-1. OUTDOOR UNIT .................................................................................... 06 - 26 3-2. SEPARATION TUBE .............................................................................. 06 - 29 3-3. BRANCH BOX ....................................................................................... 06 - 31

4. WIRING DESIGN ........................................................................... 06 - 37 4-1. ELECTRICAL WIRING ........................................................................... 06 - 37 4-2. POWER SUPPLY CABLE WIRING ........................................................ 06 - 39 4-3. TRANSMISSION LINE ........................................................................... 06 - 43 4-4. CONTROLLER CABLE WIRING ........................................................... 06 - 46

5. FUNCTION SETTING .................................................................... 06 - 50 5-1. OUTDOOR UNIT .................................................................................... 06 - 50 5-2. INDOOR UNIT (setting by jumper wire)............................................... 06 - 54 5-3. INDOOR UNIT (setting by wireless remote controller) ...................... 06 - 55 5-4. INDOOR UNIT (setting by wired remote controller) ........................... 06 - 60 5-5. INDOOR UNIT (setting by simple remote controller) ......................... 06 - 64 5-6. FUNCTION DETAILS ............................................................................. 06 - 68 5-7.

CENTRAL REMOTE CONTROLLER .................................................... 06 - 71

5-8. WIRED REMOTE CONTROLLER.......................................................... 06 - 74 5-9. SIMPLE REMOTE CONTROLLER ........................................................ 06 - 77

CONTENTS 6. SYSTEM DESIGN 5-10. DUCT STATIC PRESSURE SETTING ................................................... 06 - 80

6. CHECK RUN .................................................................................. 06 - 81 6-1. PRECAUTIONS & PREPARATION ....................................................... 06 - 81 6-2. CHECK RUN CHECK ITEMS AND PROCEDURE ................................ 06 - 83 6-3. CHECK RUN EXAMPLES ..................................................................... 06 - 84 6-4. RELOCATION AND INCREASE OF UNIT............................................. 06 - 88

7. EXTERNAL INPUT & OUTPUT..................................................... 06 - 89 7-1. OUTDOOR UNIT .................................................................................... 06 - 89 7-2. INDOOR UNIT ........................................................................................ 06 - 98

8. DRAIN CONNECTION ................................................................. 06 - 104 8-1. OUTDOOR UNIT ................................................................................... 06 - 104 8-2. INDOOR UNIT ....................................................................................... 06 - 105

9. STANDARD ACCESSORIES ....................................................... 06 - 111 9-1. OUTDOOR UNIT ................................................................................... 06 - 111 9-2. INDOOR UNIT ....................................................................................... 06 - 112

10.

OPTIONAL PARTS INSTALLATION....................................... 06 - 115

10-1. FRESH AIR INTAKE KIT ...................................................................... 06 - 115

11.

REFRIGERANT LEAKAGE CAUTION ................................... 06 - 126

11-1. INTRODUCTION ................................................................................... 06 - 126 11-2. CHECKING CONCENTRATION LIMIT ................................................. 06 - 127

12.

INSTALLATION PRECAUTIONS ............................................ 06 - 129

12-1. INDOOR UNIT INSTALLATION PRECAUTIONS ................................. 06 - 129 12-2. OUTDOOR UNIT INSTALLATION PRECAUTIONS ............................. 06 - 132

1. SYSTEM DESIGN 1-1. SYSTEM OUTLINE Branch box 3 (Secondary)

8 Indoor units

6 Circuit breaker (over current) Earth leakage breaker Power supply

Branch box 2 (Secondary)

6 Circuit breaker (over current) Earth leakage breaker Power supply

8

Branch box 1 (Primary)

2

6 Circuit breaker (over current)

Outdoor unit

Earth leakage breaker

Central remote controller

7

3 1

5

Circuit breaker (over current)

Power supply

4

SYSTEM DESIGN

SYSTEM DESIGN

Power supply

Earth leakage breaker

) 1: Transmission line [O.U. - B.B.(primary)] ( ) 2: Transmission line [B.B.(primary) - B.B.(secondary] ( 3: Central remote controller line [Central remote controller - B.B.] ( ) 4: Power supply and Transmission line [B.B. - I.U.] ( ) 5: Power supply [Outdoor Unit] ( ) 6: Power supply [Branch Box] ( ) 7: Remote controller line [I.U. - R.C.] ( ) 8: Piping (

- (06 - 01) -

)

6. SYSTEM DESIGN

1-2. REFRIGERANT SYSTEM  CONNECTABLE UNIT WITHIN 1 REFRIGERANT SYSTEM Unit

Quantity

Remarks

Outdoor unit

1 unit

Indoor unit

2 to Max. 8 units

Connectable indoor unit capacity : 80% to 130%

Branch box

1 to Max. 3 units

One Branch box of primary type is always necessary

 Caution

SYSTEM DESIGN

SYSTEM DESIGN

● When all indoor units are operating at maximum capacity, individual indoor unit operate at a slightly lower capacity. (When connecting more than 100%) ● Do not exceed both of "connectable capacity range" and "maximum connectable indoor unit", otherwise it may cause hinder the return of the refrigerant oil and cause a compressor breakdown.

- (06 - 02) -

6. SYSTEM DESIGN

 EXAMPLE OF REFRIGERANT SYSTEM  Example 1 (OK) Branch box 1 (Primary type) Outdoor unit

Capacity ratio 88%

Indoor unit 1 Indoor unit 2

Model Outdoor unit AOU48 Indoor unit 1 ARU24 Indoor unit 2 ARU18 Branch box 1 UTP-PU03A

Capacity (BTU/h) 48000 24000 18000 -

Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000 2 80% 3 130% 1 42000 -

Judgement 2≤ 1≤ 3

38400

62400

38400 < 42000 < 62400 → OK

-

-

-

 Example 2 (OK) Branch box 1 (Primary type)

Capacity ratio 125%

SYSTEM DESIGN

Indoor unit 1 Indoor unit 2 Indoor unit 3

Model Outdoor unit AOU48 Indoor unit 1 ARU24 Indoor unit 2 ARU24 Indoor unit 3 ARU12 Branch box 1 UTP-PU03A

Capacity (BTU/h) 48000 24000 24000 12000 -

Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000 2 80% 3 130%

Judgement

2≤ 1≤ 3

1 60000

38400

62400

38400 < 60000 < 62400 → OK

-

-

-

-

- (06 - 03) -

6. SYSTEM DESIGN

SYSTEM DESIGN

Outdoor unit

 Example 3 (OK)

Outdoor unit

Indoor unit 1

Model Outdoor unit AOU48 Indoor unit 1 ARU18 Indoor unit 2 ARU12 Indoor unit 3 ARU9 Indoor unit 4 ARU9 Indoor unit 5 ARU9 Branch box 1 UTP-PU03A Branch box 2 UTP-PU03B

Branch box 1

Branch box 2

(Primary type)

(Secondary type)

Indoor unit 2

Capacity (BTU/h) 48000 18000 12000 9000 9000 9000 -

Indoor unit 3

Indoor unit 4

Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000 1 57000

Capacity ratio 119%

Indoor unit 5

Judgement

2 80%

3 130%

2≤ 1≤ 3

38400

62400

38400 < 57000 < 62400 → OK

-

-

-

-

-

Outdoor unit

Indoor unit 1

Branch box 1

Branch box 2

Branch box 3

(Primary type)

(Secondary type)

(Secondary type)

Indoor unit 2

Indoor unit 3

Indoor unit 4

Indoor unit 5

Indoor unit 6

Indoor unit 7

Indoor unit 8

Capacity ratio 117% Model Outdoor unit AOU48 Indoor unit 1 ASU7 Indoor unit 2 ASU7 Indoor unit 3 ASU7 Indoor unit 4 ASU7 Indoor unit 5 ASU7 Indoor unit 6 ASU7 Indoor unit 7 ASU7 Indoor unit 8 ASU7 Branch box 1 UTP-PU03A Branch box 2 UTP-PU03B Branch box 3 UTP-PU03B

Capacity (BTU/h) 48000 7000 7000 7000 7000 7000 7000 7000 7000 -

Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000

1 56000

-

Judgement

2 80%

3 130%

2≤ 1≤ 3

38400

62400

38400 < 56000 < 62400 → OK

-

-

-

- (06 - 04) -

-

6. SYSTEM DESIGN

SYSTEM DESIGN

SYSTEM DESIGN

 Example 4 (OK)

 Example 5 (Not good) Branch box 1 (Primary type) Outdoor unit

Indoor unit 1

Model

Capacity (BTU/h)

Outdoor unit

AOU48

48000

Indoor unit 1

ARU24

24000

Branch box 1 UTP-PU03A

Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000 2 80% 3 130% 1 24000 -

-

38400

62400

-

-

Judgement Not good → Because only one indoor unit is connected -

 Example 6 (Not good) Branch box 1 (Primary type) Outdoor unit

SYSTEM DESIGN

Model Outdoor unit AOU48 Indoor unit 1 ARU24 Indoor unit 2 ARU12 Branch box 1 UTP-PU03A

Capacity (BTU/h) 48000 24000 12000 -

Total Connectable indoor capacity unit capacity (BTU/h) Min. Max. (BTU/h) 48000 2 80% 3 130% 1 36000 -

Judgement 1
View more...

Comments