FR-EE-403-00003-L

March 7, 2018 | Author: Talha Altaf | Category: Electrical Substation, Transformer, Electric Power System, Relay, Power Engineering
Share Embed Donate


Short Description

Relay coordination report...

Description

L

5-NOV-2014

Rev.

Date

Issued for COMPANY Review Description

TAT

NAS

MTH

Prep’d By

Chk’d By

Appr’d By

COMPANY

EPC CONTRACTOR

Abu Dhabi Polymers Company Limited (Borouge)

PROJECT

BOROUGE PO FLARE GAS RECOVERY PROJECT TITLE

RELAY SETTINGS & PROTECTION COORDINATION STUDY Contractor Project No.:6502

Contractor Doc No: 6502-10-100-M1380-005-01

Document Class: 1 BOROUGE Document Information: Project No.

Document Number

Page

Rev.

PE/000451

FR-EE-403-00003

1 OF 14

L

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

2 OF 14

L

Revision / Changes: Revision No.

Page No.

Section

Change(s)

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

3 OF 14

L

TABLE OF CONTENTS 1   I NT R O D U CTI O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4   2   S T U DY O BJ E C T I V E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4   3   R EFE RE NC E DO CUME NTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4   4   ET AP MO DEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5   5   B A SIS & AS S UMPTI O N S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6   6   N ET W O R K DE S C RIPTI O N FO R ST U DY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6   7   M O DEL SIM U L ATI O N CO N DI TION S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6   8   F A U LT C UR RE NT LEV ELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7   9   R EL AY TYP E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9   10   H V P ROTE CTI O N REL AY SE T TIN GS D A T A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9   11   TI ME CU RR E NT C URV ES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 0   12   C O N C L USIO N A N D RE CO MME ND A TI O NS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 4  

Attachments: Attachment A: ETAP SLD Attachment B: ETAP Report

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

4 OF 14

L

1 INTRODUCTION The intent of this study report is to carry out electrical power system analysis by performing protection coordination study of the electrical network under the scope of Borouge PO Flare Gas Recovery project (B3). 2 STUDY OBJECTIVE The main objectives of protection coordination study are as follows:   

To determine the characteristics, ratings, and settings of over current protective devices that minimizes plant outages and interrupts short circuits as rapidly as possible. To verify the existing protection device settings. To verify the proper margin between protective devices in series to enable a back-up protection system. That is, upstream devices are on a standby basis to act expeditiously in case the immediate device nearer to the fault location fails to operate.

Relay Coordination study is performed on the basis & recommendations of following international standards  

IEEE Std 399-1997. (IEEE Recommended Practice for Industrial & Commercial Power System Analysis) IEEE Std 242-2001. (IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems)

3 REFERENCE DOCUMENTS The documents listed below have been considered as the basis/reference for the relay settings & protection coordination study: Document Name Electrical Cable Schedule Electrical Load Summary (B3) Electrical One Line Diagram B3 PE5 Process Substation Unit N-42(11KV, 3.3 KV, 0.415 KV) 11 KV SWITCHGEAR 42-ES-9001 Protection and Metering One Line Diagram Electrical One Line Diagram B3 PP4 Process Substation UNIT N-45 11 KV SWITCHGEAR 45-ES-9001 Protection and Metering One Line Diagram 3.3 KV SWITCHGEAR 45-ES-9002 Protection and Metering One Line Diagram 3.3 KV SWITCHGEAR 42-ES-9002 Protection and Metering One Line Diagram BOR 3 PO SUBSTATION Protection and Metering Diagram 0.415 KV Switchgear Electrical One Line Diagram PE5 Extrusion Substation Unit N-42(11KV, 3.3 KV, 0.415 KV) Electrical One Line Diagram PP4 Extrusion Substation Unit N-42(11KV, 3.3 KV, 0.415 KV)

Borouge Document No. FR-EE-403-00006 STU-EE-FR-003

Contractor Document No. 6502-10-100-D1-1382-001-01 6502-10-100-D1381-002-01

TEC-EE-FR-0044

----

TEC-EE-FR-0045

----

TEC-EE-FR-0046

----

TEC-EE-FR-0047

----

TEC-EE-FR-0048

----

TEC-EE-FR-0050

----

TEC-EE-FR-0049

----

42-EE-153-920001

----

45-EE-153-920001

----

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

5 OF 14

L

4 ETAP MODEL As per Descon / Contractor scope (DOC: Electrical System Description and Scope Definition for EPC Package) in Borouge 3 expansion project, Descon has to analyze the impact of newly added loads (which are in Descon scope, DOC: Electrical Load Summary B3) on the electrical network of B3 by performing the protection coordination study. The details of ETAP model provided by Company are as follows: Name: ETAP-3583-PO This contains the following switchgears with associated electrical equipment (Motors, Transformers, and Cables etc). 80-ES-1802 (33 KV) 41-ES-9203 (3.3 KV) 42-ES-9213 (0.415 KV) 42-ES-9201 (11 KV) 42-ES-9203 (3.3 KV) 42-ES-9212 (0.415 KV) 44-ES-9202 (3.3 KV) 44-ES-9212 (0.415 KV) 45-ES-9202 (3.3 KV)

41-ES-9001 (11 KV) 41-ES-9011 (0.415) 41-ES-9212 (0.415 KV) 42-ES-9001 (11 KV) 42-ES-9011 (0.415 KV) 44-ES-9001 (11 KV) 44-ES-9011 (0.415 KV) 45-ES-9001 (11 KV) 45-ES-9011 (0.415 KV)

41-ES-9002 (3.3 KV) 41-ES-9211 (0.415 KV) 41-ES-9201 (11 KV) 42-ES-9002 (11 KV) 42-ES-9211 (0.415 KV) 44-ES-9002 (3.3 KV) 44-ES-9211 (0.415 KV) 45-ES-9002 (3.3 KV) 45-ES-9211 (0.415 KV)

Loads in Contractor’s scope have been modeled along with associated cables.

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

6 OF 14

L

5 BASIS & ASSUMPTIONS The basis and assumptions are listed below    

The protection data for motors i.e starting time, thermal withstand limits, thermal time constants etc are based on technical data provided by vendor and assumptions are made where vendor data is pending. Thermal overload settings of motors shall be performed at site during commissioning stage. For simulation purposes, exact Relay/ETU model is used as available in standard ETAP device library. In case of unavailability of particular model, nearest match having similar characteristics is used. In this report, following switchgears of Unit 42 (PE5) and Unit 45 (PP4) are under observation as most of the loads under contractor’s scope are being fed from theses switchgears. However attached ETAP report will reflect the results of other switchgears as well. 42-ES-9001 (11 KV)

45-ES-9001 (11 KV)

42-ES-9011 (0.415 KV)

45-ES-9011 (0.415 KV)

6 NETWORK DESCRIPTION FOR STUDY For the simulation, ETAP models have been updated as per the reference documents mentioned in section 3 of this report. The Network Description for the study is as follows:     

The main power sources for 11 KV switchgear 42-ES-9001 are 2 Nos. 33 KV feeders supplied by switchgear 80-EE-1802 through 31.5 MVA, 33/11.5 KV transformers (42-EP-9011, 42-EP-9012). 2 Nos. 11 KV feeders (from switchgear 42-ES-9001) are stepped down by 2 Nos. 3.15 MVA, 11/0.433 KV transformers (42-EP-9031, 42-EP-9032) to feed 0.415 KV switchgear 42-ES-9011. The main power sources for 11 KV switchgear 45-ES-9001 are 2 Nos. 33 KV feeders supplied by switchgear 80-EE-1803 through 31.5 MVA, 33/11.5 KV transformers (45-EP-9011, 45-EP-9012). 2 Nos. 11 KV feeders (from switchgear 45-ES-9001) are stepped down by 2 Nos. 2.5 MVA, 11/0.433 KV transformers (45-EP-9031, 45-EP-9032) to feed 0.415 KV switchgear 45-ES-9011. Following Generators are operating in Standby mode and considered OFF in the analysis. 42-EG-9201

42-EG-9001

45-EG-9001

45-EG-9201

7 MODEL SIMULATION CONDITIONS Following are the basis of model simulation conditions.        

Loads are categorized into Continuous, Intermittent and Stand by 100%, 50% & 0% loading respectively. All Lump Loads are considered as “Continuous” and operating at 80% loading. Loading Category is selected as Normal. Primary tap positions are set at +2.5% of nominal voltage, for all transformers (for Unit 42 & 45). 33kV Grid bus is considered as slack/swing bus. The by-pass switches for VFDs are closed to get maximum short circuit contribution from motors. Maximum short circuit power from utility to switchgears of unit 42 and 45 is considered 1257 MVA (3-phase) as per etap model/etap report submitted by Company described in section 5 of this report. Minimum short circuit power from utility to switchgears of unit 42 and 45 is considered 850 MVA (3-phase) as per etap model/etap report submitted by Company described in section 5 of this report.

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

7 OF 14

L

8 FAULT CURRENT LEVELS Initial Symmetrical Short Circuit Current (maximum):

Bus

Nominal Voltage (kV)

Rated Short Circuit (kA)

42-ES-9001 A 42-ES-9001 B 42-ES-9011 A 42-ES-9011 B 45-ES-9001 A 45-ES-9001 B 45-ES-9011 A 45-ES-9011 B

11 11 0.415 0.415 11 11 0.415 0.415

31.5 31.5 80 80 31.5 31.5 80 80

Initial Symmetrical RMS Current kA (Ik”) Double Line to Three Phase Line to Ground Line to Line Ground 26.3 0.4 23.1 23.2 26.3 0.4 23.1 23.2 54.2 47.3 46.8 52.8 54.2 47.3 46.8 52.8 25.1 0.4 21.8 21.9 25.1 0.4 21.8 21.9 47.7 42.8 41.2 46.8 47.7 42.8 41.2 46.8

Peak Short Circuit Current (maximum): Bus 42-ES-9001 A 42-ES-9001 B 42-ES-9011 A 42-ES-9011 B 45-ES-9001 A 45-ES-9001 B 45-ES-9011 A 45-ES-9011 B

Nominal Voltage (kV)

Rated Short Circuit (kA)

11 11 0.415 0.415 11 11 0.415 0.415

31.5 31.5 80 80 31.5 31.5 80 80

Peak Short Circuit Current kA (ip) Double Line to Three Phase Line to Ground Line to Line Ground 67.7 1.08 59.4 59.7 67.7 1.08 59.4 59.7 124.3 108.6 107.3 121.3 124.3 108.6 107.3 121.3 64.9 1.08 56.4 56.7 64.9 1.08 56.4 56.7 110.4 99.1 95.3 108.2 110.4 99.1 95.3 108.2

Symmetrical Short Circuit Breaking Current (maximum): Symmetrical Short Circuit Breaking Current kA (Ib) Nominal Rated Short Bus Voltage (kV) Circuit (kA) Line to Ground Line to Line Double Line to Ground 42-ES-9001 A 11 31.5 0.4 23.1 23.2 42-ES-9001 B 11 31.5 0.4 23.1 23.2 42-ES-9011 A 0.415 80 47.3 46.8 52.8 42-ES-9011 B 0.415 80 47.3 46.8 52.8 45-ES-9001 A 11 31.5 0.4 21.8 21.9 45-ES-9001 B 11 31.5 0.4 21.8 21.9 45-ES-9011 A 0.415 80 42.8 41.2 46.8 45-ES-9011 B 0.415 80 42.8 41.2 46.8

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

8 OF 14

L

Initial Symmetrical Short Circuit Current (minimum): Bus

Nominal Voltage (kV)

Rated Short Circuit (kA)

42-ES-9001 A 42-ES-9001 B 42-ES-9011 A 42-ES-9011 B 45-ES-9001 A 45-ES-9001 B 45-ES-9011 A 45-ES-9011 B

11 11 0.415 0.415 11 11 0.415 0.415

31.5 31.5 80 80 31.5 31.5 80 80

Initial Symmetrical RMS Current kA (I”k) Three Phase Line to Ground Line to Line 14.1 14.1 29.7 29.7 14.1 14.1 28.1 28.1

0.3 0.3 30.6 30.6 0.3 0.3 28.9 28.9

12.2 12.2 25.7 25.7 12.2 12.2 24.3 24.3

Double Line to Ground 12.3 12.3 30.2 30.2 12.3 12.3 28.5 28.5

Peak Short Circuit Current (minimum): Bus

Nominal Voltage (kV)

Rated Short Circuit (kA)

42-ES-9001 A 42-ES-9001 B 42-ES-9011 A 42-ES-9011 B 45-ES-9001 A 45-ES-9001 B 45-ES-9011 A 45-ES-9011 B

11 11 0.415 0.415 11 11 0.415 0.415

31.5 31.5 80 80 31.5 31.5 80 80

Peak Short Circuit Current kA (ip) Double Line to Three Phase Line to Ground Line to Line Ground 36.7 0.9 31.8 32 36.7 0.9 31.8 32 74.7 77.1 64.7 76 74.7 77.1 64.7 76 36.7 0.9 31.8 32 36.7 0.9 31.8 32 70.2 72.3 60.8 71.4 70.2 72.3 60.8 71.4

Symmetrical Short Circuit Breaking Current (minimum): Bus 42-ES-9001 A 42-ES-9001 B 42-ES-9011 A 42-ES-9011 B 45-ES-9001 A 45-ES-9001 B 45-ES-9011 A 45-ES-9011 B

Nominal Voltage (kV) 11 11 0.415 0.415 11 11 0.415 0.415

Rated Short Circuit (kA) 31.5 31.5 80 80 31.5 31.5 80 80

Symmetrical Short Circuit Breaking Current kA (Ib) Line to Ground Line to Line Double Line to Ground 0.3 12.2 12.3 0.3 12.2 12.3 30.6 25.7 30.2 30.6 25.7 30.2 0.3 12.2 12.3 0.3 12.2 12.3 28.9 24.3 28.5 28.9 24.3 28.5

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

9 OF 14

L

9 RELAY TYPE The relays used for HV motor feeder protection are ABB make REF630 with following protection functions. 50P 51P 50N 51N 87M 74 42R 86 46 38 49 49T 48 66

Motor Feeder REF 630

Phase definite time OC Phase inverse OC Earth definite time OC Earth inverse OC Differential protection Alarm Running CB Lockout Phase balance current relay Bearing protection Thermal protection Temperature protection Incomplete Sequence Relay

Jogging device

10 HV PROTECTION RELAY SETTINGS DATA Only over current protection function settings (50P, 50G, 51P, 51G) are proposed in this document. All other settings shall be performed at site during commissioning stage. Motor TAG Description Relay CT Ratio Pickup Value TMS Characteristic Curve Pickup Value Time Pickup Value Time

47-XK-921-KM-921 47-XK-931-KM-931 Motor feeder Motor feeder REF 630 REF 630 250-1 200-1 OVERCURRENT STAGE I> (51) Settings 0.9 0.9 3.5 2.11 IECIECExtremely Inverse Extremely Inverse OVERCURRENT INSTANTANEOUS I>> (50) Settings 6.71 6.41 0.05 0.05 RESIDUAL CURRENT INSTANTANEOUS I02 > (50N) Settings 0.21 0.18 0.05 0.05

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

10 OF 14

L

11 TIME CURRENT CURVES Time current curves (TCC) are plotted to verify the present state of coordination. a. 47-XK-921-KM-921 PE compressor motor relay phase TCC.

Figure 1

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

11 OF 14

L

b. 47-XK-921-KM-921 PE compressor motor relay earth time current curves

Figure 2

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

12 OF 14

L

c. 47-XK-931-KM-931 PP compressor motor relay phase time current curves

Figure 3

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

13 OF 14

L

d. 47-XK-931-KM-931 PP compressor motor relay earth time current curves

Figure 4

Abu Dhabi Polymers Company Limited (Borouge)

BOROUGE PO FLARE GAS RECOVERY PROJECT RELAY SETTINGS & PROTECTION COORDINATION STUDY Issued date

Project No.

Document Number

Page

Rev.

5-NOV-2014

PE/000451

FR-EE-403-00003

14 OF 14

L

12 CONCLUSION AND RECOMMENDATIONS Relay coordination study has been performed after incorporating protection settings of existing system and proposed protection settings of newly added loads. The study reflects that both HV & LV electrical systems are adequate and properly coordinated after the Borouge project load additions and no modification/update in protection settings of existing system is required at this stage.

^,KZd/Zh/d^dhz PROTECTION COORDINATION STUDY ETAP SLD ATTACHMENT A

ATTACHMENT A

One-Line Diagram - SCMAX (Star Sequence-of-Operation) 80-ES-1802 A

80-ES-1802 B ±

±

I> I>

42-EP-9011 31.5 MVA

42-EP-9012 31.5 MVA

±

±

R

R

CB336

CB339

± ±

R

42-ES-9001 A

R

±

±

CB331 ±

R

R

±

CB337 ±

R ±

CB332 ±

R

CB334 ±

R

R

R

47 1- EC 3/ CC 50 18 00 5 1

12:05:32

Oct 31, 2014

CB340

CB328

CB329

0 A

CB7 ±

R ±

1750 kVA Cable7 0 A

42-EP-9032 42-EP-9232 42-EP-9234 2-3/C 185

42-XE-705-EC-701A 42-XE-705-EC-701B

Project File: ETAP-3583-PO

4450 kW

C/42-ES-9001 B 42-XK-401-KM-401

1400 kW

C/42-ES-9001 A 42-XE-705-NM-701A

42-XK-402-KM-402 2300 kW

47-XK-921-KM-921 3300 kW

page 1

XC/42-ES-001A

±

42-EP-9233 42-EP-9231 42-XE-705-EP-701A 1750 kVA

CB327

±

CB338 Open

± ±

42-EP-9031

CB341

R

±

±

±

CB326

CB335

1400 kW

R ±

CB330

42-XE-705-NM-701B

±

CB17

XC/42-ES-001B

CB40

42 -X E70 5EP -7 01 B

42-ES-9001 B

ATTACHMENT A

One-Line Diagram - SCMAX (Star Sequence-of-Operation) 80-ES-1803 A

80-ES-1803 B

±

±

I>

I>

45-EP-9011 31.5 MVA

45-EP-9012 31.5 MVA ±

±

R

R

CB581

CB584

± ±

R

R

45-ES-9001 B

R

R

R

R

R

±

± ± ±

12:03:46

Oct 31, 2014

±

R ±

0 A

±

45-EP-9032

0 A

45-EP-9232

45-XE-705-NM-701

Project File: ETAP-3583-PO

±

R

±

R

±

R ±

7.85 MVA

2.6 MVA

C/45-ES-9001 A

45-EP-9031

3150 kW

45-XK-401-KM-401

47-XK-931-KM-931 2650 kW

45-EP-9231

XC/45-ES-9001A

47 -E C 1- C3/ 50 C 00 18 2 5

±

C/45-ES-9001 B

page 1

CB583 Open

±

±

±

2130 kW

R

45-XK-503-KM-503

±

CB35

CB72

45 -X E70 5EC -7 54

±

CB574

6350 kW

±

CB585

45-XE-705-NM-754

±

±

CB572

45 -X E70 5EP -7 54

R ±

CB586

CB571

CB580

45 -X E70 5EC -7 01

CB579

CB577

2100 kW

CB582

XC/45-ES-9001B

CB28

CB38

45 -X E70 5EP -7 01

45-ES-9001 A

^,KZd/Zh/d^dhz

PROTECTION COORDINATION STUDY ETAP REPORT ATTACHMENT B

Project:

BOROUGE #3

Location: LHR PAK

ETAP

Page:

1

12.5.0C

Date:

29-10-2014

Contract: 6502

Revision: Base

Engineer: DIPL

Overcurrent Relay Settings

Filename: ETAP-3583-PO

OCR: R_42-ES-9001-A1 MFR:

ABB

Model:

RE_630

Tag #:

CT

Base kV

If (kA)

Phase:

2500/1

24.70 3 ph, (User-Defined)

GND:

2500/1

0.40 LG, (User-Defined)

Phase:

250/1

24.70 3 ph, (User-Defined)

GND:

100/1

0.40 LG, (User-Defined)

OC Level: OC1 Range

Setting

Phase TOC IEC - Normal Inverse Pickup (Tap)

0.3 - 5 xCT Sec

Time Dial Phase INST Pickup Time Delay Ground INST Pickup Time Delay

0.790 0.150

0.01 - 35 xCT Sec

6.300

0.04 - 30 Sec

0.400

0.01 - 400 xCT Sec

0.100

0.01 - 300 Sec

0.600

OCR: R_42-ES-9001-KM-921 MFR:

ABB

Model:

RE_630

Tag #:

CT

Base kV

If (kA)

OC Level: OC1 Range

Setting

Phase TOC IEC - Extremely Inverse Pickup (Tap)

0.3 - 5 xCT Sec

Time Dial Phase INST Pickup Time Delay Ground INST Pickup Time Delay

0.900 3.500

0.01 - 35 xCT Sec

6.710

0.04 - 30 Sec

0.050

0.01 - 400 xCT Sec

0.210

0.01 - 300 Sec

0.050

ATTACHMENT B

Project:

BOROUGE #3

Location: LHR PAK

ETAP

Page:

2

12.5.0C

Date:

29-10-2014

Contract: 6502

Revision: Base

Engineer: DIPL

Overcurrent Relay Settings

Filename: ETAP-3583-PO

OCR: R_45-ES-9001-A1 MFR:

ABB

Model:

RE_630

Tag #:

CT

Base kV

If (kA)

Phase:

2500/1

23.90 3 ph, (User-Defined)

GND:

2500/1

0.40 LG, (User-Defined)

Phase:

200/1

23.90 3 ph, (User-Defined)

GND:

100/1

0.40 LG, (User-Defined)

OC Level: OC1 Range

Setting

Phase TOC IEC - Normal Inverse Pickup (Tap)

0.3 - 5 xCT Sec

Time Dial Phase INST Pickup Time Delay Ground INST Pickup Time Delay

0.790 0.150

0.01 - 35 xCT Sec

6.300

0.04 - 30 Sec

0.400

0.01 - 400 xCT Sec

0.100

0.01 - 300 Sec

0.600

OCR: R_45-ES-9001-KM-931 MFR:

ABB

Model:

RE_630

Tag #:

CT

Base kV

If (kA)

OC Level: OC1 Range

Setting

Phase TOC IEC - Extremely Inverse Pickup (Tap)

0.3 - 5 xCT Sec

Time Dial Phase INST Pickup Time Delay Ground INST Pickup Time Delay

0.900 2.110

0.01 - 35 xCT Sec

6.410

0.04 - 30 Sec

0.050

0.01 - 400 xCT Sec

0.180

0.01 - 300 Sec

0.050

ATTACHMENT B