1 CORE CU/MICA/XLEVA/LSHF 600/1000V (FRMI) (OCC-F6C01) Nominal crosssectional area
Approx. Overall Diameter
Approx. Cable Weight
Test Voltage
(mm2)
(mm)
(kg/km)
(kV/5min)
Maximum conductor DC resistance at 20°C (Ω/km)
Current Current Volt drop for rating based rating based 3 phase on enclosed on laid in air in conduit at at 40°C 30°C (Amp) (Amp) (V/A/km)
1.5
5.7
49
3.5
12.1
19
21
27
2.5
6.1
61
3.5
7.41
26
29
16
4
6.9
83
3.5
4.61
35
37
10
6
7.4
105
3.5
3.08
45
46
6.8
10
8.2
149
3.5
1.83
63
62
4.0
16
9.1
209
3.5
1.15
85
94
2.5
600/1000 V FRMI NON-ARMOURED FIRE RESISTANT CABLES
25
10.8
314
3.5
0.727
111
126
1.65
Application These cables offer enhanced circuit integrityover the same rated power cable.It is mainly used ininstallation where vital circuits are required to continue to operate in the event of a fire. It is s uited for use in public buildings like shopping complex, hospitals, theatres, mass transit utilities, oil & gas plants, etc.
35
12.0
411
3.5
0.524
138
156
1.15
50
13.5
542
3.5
0.387
168
190
0.90
Specification
70
15.3
749
3.5
0.268
214
246
0.65
95
17.3
1006
3.5
0.193
259
300
0.50
120
19.0
1253
3.5
0.153
299
350
0.42
150
20.9
1531
3.5
0.124
328
405
0.37
185
23.0
1903
3.5
0.0991
370
465
0.32
The conductor comprises of circular / compacted circular stranded plain annealed copper wires according toIEC 60228.
240
25.8
2461
3.5
0.0754
433
551
0.29
The insulation material consists of a layer ofextruded cross-linkable low smoke halogen free mineral filled polyolefin material (FRMI) as per IEC 60092/360, type HF90 with a temperature index of 300°C .
300
28.4
3052
3.5
0.0601
493
638
0.27
400
32.0
3875
3.5
0.0470
584
746
0.25
500
35.5
4922
3.5
0.0366
666
852
0.24
Mica fire barrier, cross-linked low smoke halogen free mineral insulated (XLEVA), low smoke halogen free outer sheathed Non-Armoured FRMI cables meets the following cable specifications : BS 6387 Performancerequirements for cables to maintain circuit integrity under fire conditions IEC 60331 Fire resisting characteristics of electric cables IEC 60332-1 Flame retardant characteristics of electric cables IEC 60332-3 Tests on electric cables under fire conditions Part 3: Tests on bunched wires orcables IEC 60754 Test on gases evolved during combustion of materials from cables IEC 61034 Measurement of smoke density of cables burning under defined conditions.
Construction
The core identificationis by coloured insulationFRMI or bicolour lining throughout the core length. For multicore cables, the cores may be laid up with the filler ( non-hygroscopic material ) and a layer of binder shall be applied over the laid up cores.
630
39.7
6301
3.5
0.0283
764
973
0.23
The innersheath shall consists ofa layer of extruded low smoke halogen free mineral filled (LSHF) compound applied over the FRMI insulation for single core cable and the binder around the laid up cores for multicore cables.
800
44.8
8025
3.5
0.0221
862
1105
0.22
The outer sheathing shall consist ofa layer of extruded LSHF compound in accordance with IEC60092-360. Special outer sheathing material such as LSHF with termite or rodent protection and UV protection are available upon request.
1000
48.6
9969
3.5
0.0176
934
1228
0.20
*The contentof this catalogue isprovided for information onlyand istothe best of our knowledge correctat the time of printing. The companymakesnorepresentationsor warrantiesaboutthe accuracy, reliability, completenessor timeless of the information in thiscatalogue. The companyin itssole discretion mayrevise the contained herein atanytime withoutprior notice. Usersshould independentlyevaluate the suitabilityof each productfor the desired application.
02
03 3 CORE CU/MICA/XLEVA/LSHF 600/1000V (FRMI) Nominal crosssectional area
1 CORE CU/MICA/LSHF/LSHF 600/1000V Maximum conductor DC resistance at 20°C (Ω/km) 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470
Current rating Volt drop for Current rating based based on a 3 phase perforated on clipped cable tray direct 25°C / free air at 30°C (Amp) (V/A/km) (Amp)
*The contentof this catalogue isprovided for information onlyand istothe best of our knowledge correctat the time of printing. The companymakesnorepresentationsor warrantiesaboutthe accuracy, reliability, completenessor timeless of the information in thiscatalogue. The companyin itssole discretion mayrevise the contained herein atanytime withoutprior notice. Usersshould independentlyevaluate the suitabilityof each productfor the desired application.
*The contentof this catalogue isprovided for information onlyand istothe best of our knowledge correctat the time of printing. The companymakesnorepresentationsor warrantiesaboutthe accuracy, reliability, completenessor timeless of the information in thiscatalogue. The companyin itssole discretion mayrevise the contained herein atanytime withoutprior notice. Usersshould independentlyevaluate the suitabilityof each productfor the desired application.
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.