installation and MaintenanCe instruCtions

12 Clintonville Road Northford, CT 06472-1653 Phone: 203.484.7161

FCM-1-rel r C M speCiFiCations

SLC

Normal Operating Voltage: Average Av erage Operating Current: Maximum Activation Current:

15 to 32 VDC Nominal 700µA (LED flashing) 9.0 mA (red LED on)

External Supply

Normal Operating Voltage: Maximum Line Loss: Minimum Operating Voltage to Activate Solenoid: Standby Current: Activation Current: Maximum Activation Current:

24 VDC Nominal 2.3 VDC (total allowable loss from power supply to module and from module to solenoid) 18 VDC (at solenoid) 6.4 mA 10 mA 2A

Solenoid

Supervisory Loop Voltage: Supervisory Loop Current (Normal): Maximum Activation Current: Temperature Range: Humidity: Dimensions: Accessories:

3.3 V 30 mA 2A 32°F to 120°F (0°C to 49°C) 10% to 95% RH Non-condensing 41/2˝ H × 4˝ W × 11/4˝ D; (106 mm H × 108 mm W × 31 mm D) Walll cover plate (included); SMB500 Surface Mount Electrical Box (for indoor dry applications only) Wal

BeFore installing

Wiring

This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.

NOTE: All wiring must conform to applicable local codes, ordinances, and regulations.

NOTICE: NOTIC E: This manual should be left with the owner/user of this equipment. general desCription

FCM-1-REL Releasing Control Modules are intended for use in intelligent, twowire systems, where the individual address of each module is selected using the built-in rotary switches. This module is used to switch an external power supply, which can be a DC power supply to a solenoid. It also supervises the wiring to the connected load and reports the status to the panel as NORMAL, OPEN, or SHORT CIRCUIT. CIRCUIT. The FCM-1-REL has h as two pairs of output out put termination terminatio n points available for fault-tolerant wiring and a panel-controlled LED indicator.

1.

Install module wiring wiring in accordance with the job drawings drawings and appropriate wiring diagrams.

2.

Set the address on the module per job job drawings. drawings.

3.

Secure module to electrical box (supplied by installer), as shown in Figure 2.

IMPORTANT: When using the FCM-1-REL for Class B applications, remove  Jumper (J1) and discard. The Jumper is located on the back as shown in Figure 1B. Figure 2. Module Mounting:

CoMpatiBility requireMents

To ensure proper operation, this module shall be connected to a compatible Notifier system control panels only (list available from Notifier). In addition, please refer to Notifier Device Compatibility document number 15378 for the list of compatible solenoids. Mounting

The FCM-1-REL mounts directly to 4-inch square electrical boxes (see Figure 2). The box must have a minimum depth of 21/8 inches. Surface mounted electrical boxes (SMB500) are available (for indoor dry applications only). Figure 1a. Controls and indiCators:

Figure 1B. JuMper loCat loCation: ion: J1

C1059-00

NO-460-002

C0910-00

C1060-00

1

I56-2992-004

Trusted by over 1 million members

Try Scribd FREE for 30 days to access over 125 million titles without ads or interruptions! Start Free Trial Cancel Anytime.

Trusted by over 1 million members

Try Scribd FREE for 30 days to access over 125 million titles without ads or interruptions! Start Free Trial Cancel Anytime.

Figure 3. typiCal Class B, solenoid ConFiguration: ConFiguration:

24 VDC CIRCUIT DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. 24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70. UL 864 LISTED FOR RELEASING DEVICE SERVICE USE WITH BATTERY BACKUP.

CONNECT MODULES TO LISTED COMPATIBLE COMPA TIBLE NOTIFIER NOTI FIER CONTROL PANELS ONLY

RELEASING CONTROL MODULE

  )  -  (

  )  -  (   )   +   (

  )  -  (

  )   +   (

POWER SUPPLY SUPERVISION BY MODULE

  )   +   (

FROM PANEL OR PREVIOUS DEVICE

SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMMENDED

OUTPUT TO A UL LISTED FIRE ALARM RELEASING SOLENOID (REFER TO PANEL MANUFACTURER'S INSTALLATION DOCUMENT)

(-) (+) TO NEXT MODULE

TO NEXT DEVICE

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED C0996-00

Figure 4. typiCal Class a, solenoid ConFiguration: ConFiguration:

24 VDC POWER S UPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70. UL 864 LISTED FOR RELEASING DEVICE SERVICE USE WITH BATTERY BACKUP.

24 VDC CIRCUIT DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.   )   –   (

CONNECT MODULES TO LISTED COMPATIBLE NOTIFIER CONTROL PANELS ONLY

RELEASING CONTROL MODULE

  )   +   (

  )   –   (   )   +   (

  )   –   (   )   +   (

POWER SUPPLY SUPERVISION BY MODULE

FROM PANEL OR PREVIOUS DEVICE

SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMMENDED

OUTPUT TO A UL LISTED FIRE ALARM RELEASING SOLENOID (REFER TO PANEL MANUFACTURER'S MANUFACTURER'S INSTALLATION DOCUMENT)

(–) (+) TO NEXT MODULE

TO NEXT DEVICE

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED C0997-00