Calculations of Short Circuit Currents (by Impedence Mathod) Parameters Rated System Voltage VCB
11 kV
Power Plant Aux. Distn Swgr
11000
UoM Volts
Source Fault Level
40
kA
Source Fault MVA
762
MVA
Voltage factor
1.1 1.05
VCB
Impedance
ZQ
0.175
Ω
Resistance
RQ
0.035
Ω
Reactance
XQ
0.171
Ω
Cable 1 No. of runs
Cable 1
3x240 3
Route Length
VCB 11 kV
CHP . Distn Swgr
VCB Cable 2
11/3.5 kV 4000 kVA
Cable Resistance Cable Reactance Net Cable Resistance
1.2
kM
0.16 0.085 0.0640
Ω/km Ω/km Ω
XC1
0.0340 0.245
Ω Ω
Isc
28.51
kA
Cable 2 No. of runs Route Length Cable Resistance Cable Reactance Net Cable Resistance
RC2
3x240 1 0.1 0.16 0.085 0.0160
kM Ω/km Ω/km Ω
Net Cable Reactance
XC2
0.0085
Ω
ST
MVA kV kV
Net Cable Reactance Total Impedance Symmetrical S/C Current (rms) at 11 kV SWGR Bus
RC1
Remarks Assumed in the absence of the information For MV System up to 35 kV (In Accordance with IEC 60909) For 415 V System (In Accordance with IEC 60909) RQ = 0.2 ZQ (In Accordance with IEC 60909)
As per Cable Sizing Calculations Estimated Route lengths as per Plant layout Taken from Polycab Datasheets
Taken from Polycab Datasheets
ONAN, OCTC
Power Transformer Rated Capacity Rated Primary Voltage Rated Secondary Voltage
VT
4 11 3.5
Dyn 1
Rated Secondary Current
IT
659.8
Amp
% Impedance
uT
6.25
%
Full Load Cu Loss
QT
27000
W
As per CBIP Guidelines
Transformer Impedance
ZT
0.1914
Ω
(uT / 100)*(VT2 / ST)
Transformer Resistance
RT
0.0207
Ω
(Q / (3 * IT2)
Main CHP Trafo
Tap ± 5% @ 2.5
XT 0.1903 Ω Transformer Reactance (ZT2 - RT2) As two identical transformers are connected in parallel, its Impedance, resistance & reactance shall be divided by 2. RT1 0.0103 Ω Equivalent Transformer Resistance Equivalent Transformer Reactance
XT1
0.0951
Ω
The reactance & resistance calculated for HV Section must be recalculated for the LV network via multiplication by square of the voltage ratio of the transformer. N1 0.101 Square of the voltage Ratio Equivalent reactance up to Power Trafo
X1
0.1168
(XQ + XC1 + XC2) * N1 + XT1
Equivalent resistance up to Power Trafo
R1
0.0220
(RQ + RC1 + RC2) * N1 + RT2
Equivalent reactance up to 3.3 kV SWGR Bus
X1
0.1168
Equivalent resistance up to 3.3 kV SWGR Bus
R1
0.0220
Busduct Neglected for the purpose of calculation
Busduct
VCB 3.3 kV
CHP . Distn Swgr
Total Impedance Symmetrical S/C Current (rms) at 3.3 kV SWGR Bus
VCB Cable 3
HT JB on Ground
0.119
Ω
Isc
18.71
kA
Cable 3 No. of runs Route Length Cable Resistance Cable Reactance Net Cable Resistance
RC3
3x185 1 0.35 0.21 0.075 0.0735
Ω/km Ω/km Ω
Net Cable Reactance
XC3
0.0263
Ω
Cable 4
3x70
Cable Up to Center Pit JB
Taken from Polycab Datasheets
Cable from Center Pit JB to SR LBS Rev 0
Calculations of Short Circuit Currents (by Impedence Mathod) Cable 5 Trailing Cable
SR Machine HT LBS
No. of runs Route Length Cable Resistance Cable Reactance Net Cable Resistance Net Cable Reactance
RC4
1 0.22 0.354 0.093 0.0779
Ω/km Ω/km Ω
XC4
0.0205
Ω
VT
NA 0.63 3.3 0.433
MVA kV kV
840.0
Amp
Taken from Nicco Datasheets
630 kVA
Distribution Transformer Rated Capacity Rated Primary Voltage Rated Secondary Voltage
Dry Type, OCTC
Rated Secondary Current
IT
% Impedance
uT
5
%
Full Load Cu Loss
QT
8500
W
As per CBIP Guidelines
Transformer Impedance
ZT
0.0149
Ω
(uT / 100)*(VT2 / ST)
Transformer Resistance
RT2
0.0040
Ω
(Q / (3 * IT2)
Transformer Reactance
XT2
0.0143
Ω
(ZT2 - RT2)
3.3/.433 kV
SR Trafo
Dyn 1
ACB
ST
The reactance & resistance calculated for HV Section must be recalculated for the LV network via multiplication by square of the voltage ratio of the transformer. 433 V
SR MCC
Square of the voltage Ratio
N2
0.017
Equivalent reactance up to SR MCC Bus
0.017
Ω
(X1 + XC3 + XC4 ) * N2 + XT2
Equivalent resistance up to SR MCC Bus Total Impedance Symmetrical S/C Current (rms) at SR MCC bus
0.007 0.019
Ω Ω
(R1 + RC3 + RC4 ) * N2 + RT2
14.18
kA
Isc
Note: Motor Contributions are neglected in this calculations.
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.