ANNEXURE-I ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS
Different cases are analyzed depending on the fault location. The values for various impedances which will restrict the fault current are calculated first and after determining the parameters the following net work for 132kV and 66kV system is obtained. 132kV Bus at Gharafa (Fault Level 17.48kA), ZS= 0.878 + j 4.267
Case- II (0.114 kA on 132kV side) (0.228 kA on 66kV side)
X
X
66kV bus at Duhail (Fault level 9.38kA)
X X
Case- III (4.69 kA on 132kV side) (9.38 kA on 66kV side)
X
66kV Outgoing feeder
66kV Outgoing feeder
Source fault level at 132kV bus = 3996 MVA (17.48kA) (As informed by Client)
1 of 13
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS
Source X/R ratio
= 4.86 (informed by the client)
Source Impedance (p.u.) = Base MVA / Fault MVA Base MVA
= 160MVA
Positive sequence impedance (Z s1) = System Voltage √3 x 17480 = 132000 (√3x 17480)
Min. Source resistance R s1
Rs1 Min. Source reactance X s1
=
( Zs1 )2 1 + (Xs1 / Rs1)2
=
(4.36)2 1+ (4.86)2
= 4.36 Ohms
= 0.878 Ohms = 4.86 x Rs = 4.86 x 0.878 = 4.267 Ohms
132kV power cable data (According to cable data) Positive sequence resistance (R L1) = 0.085 Ohms/Km Positive sequence reactance (X L1) = 0.106 Ohms/Km Line length = 2.466 km Positive sequence resistance (R L1) Positive sequence reactance (X L1)
= 0.209 Ohms = 0.261 Ohms
Transformer Data Voltage Ratio = 132/66 kV Rating = 160 MVA Zpu = 0.12 (at 96MVA) Zpu = 0.22 (at 160MVA)
Actual Impedance Z T = Zpu X Base kV2 X 1000 Base kVA
2 of 13
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS
= 0.22 X 132 2 X 1000 160 X 1000 = 23.96 Ohms XT = Reactance of the transformer RT = Resistance of the transformer XT / RT = 69.33 (According to Transformer data)
RT
=
( ZT )2 1 + (XT / RT)2
=
(23.96)2 1+ (69.33) 2
= 0.34 Ohm XT
= 69.33 x R T = 69.33 x 0.34 = 23.57 Ohms
Detail calculations Source
0.878 4.267
0.209 0.261
0.34 23.57
0.209 0.261 0.34
23.57
3 of 13
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS
Equivalent
Source
0.878
4.267
0.889
0.209 0.261
47.401
Equivalent Source
0.878 4.267
0.169 0.259
4 of 13
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS
Three Phase fault condition Fault current will be limited by Source impedance (132kV Bus at Gharafa), impedance of both of 160MVA transformers and Line #2 Impedance. Reactance X = Source reactance X s1 + (Line reactance X L2 + 2 X Trafo. Reactance XT) in parallel with (Line reactance X L1) = 4.267 + (0.261 + 2X23.57)//0.261 = 4.526 Ohms Resistance R = Source resistance R s1 + (Line resistance R L2 + 2 X Trafo. resistance R T) in parallel with (Line resistance R L1) = 0.878 + (0.209 + 2X.345)//0.209 = 1.047 Ohms Impedance
= 1.047 + j 4.526
Impedance Z 1 = √X2 + R2 = √(4.526) 2 + (1.047)2 = 4.645Ohms Fault current at the end of Feeder = 132000 ( If ) (√3x 4.645)
= 16407.4 Amp.
Say 16.407 kA Fault current in Case-1 Fault current through line 1
= I f * (47.409) (0.334 + 47.409) = 16.407 * (47.409) 47.743 = 16.292 kA (132kV base)
Fault current in Case-2 Fault current through line 2
= I f * (0.334) (0.334 + 47.409) = 16.407 * (.334) 47.743
5 of 13
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS = 0.114 KA (132kV base)
Case III: - Fault on the 66kV Bus of Duhail and Fault contribution from Source from Gharafa (Through fault current seen by 160 MVA transformers) Fault current will be limited by Source impedance (132kV Bus at Gharafa), Impedance of both the Lines and impedance of both the160MVA transformers (Impedance of both the lines and transformers will act in parallel). Source
Rs
Xs
RL+RT
RL+RT
XL+XT
XL+XT
Three phase fault current calculation for 66kv Bus Reactance X= Source reactance X s + Line reactance X L /2+Transformer Reactance X T /2 = 4.267+ 0.261/2+ 23.57/2 = 16.183 Ohms Resistance R= Source resistance R s +Line resistance R L/2+Transformer Resistance R T/2 = 0.878 + 0.209/2 + 0.345/2 = 1.155 Ohms Impedance
= 1.155 + j16.183
Impedance Z 1
= √X2 + R2 = √ (16.183) 2 + (1.155)2
6 of 13
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS = 16.224 Ohms Fault current at the end of Feeder = 132000 = 4697.5Amp. (√3x 16.224) Say 4.69 kA Fault current seen by 66kV side CTs = 132000 x 4.69 = 9.38 kA 66000 132kV and 66kV systems are solidly grounded system. Therefore the current magnitude obtained above for phase fault current shall be used for earth fault relay settings also. Impedance for downstream of 66kV feeder is calculated based on 66kV Base voltage and 40MVA Base MVA and the following net work is obtained.
66kV Bus at Duhail (Fault level 9.38 kA), ZS= 0.289+ j 4.048 Line # 1 Impedance neglected due to small length
Case V (2.96 kA on 66kV side) (17.76 kA on 11kV side)
X
11kV Outgoing feeder
11kV Outgoing feeder
7 of 13
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS
Source fault level at 66kV bus = 1072 MVA (9.38kA) Source X/R ratio
=14.01(Derived from the calculations performed above in Case-III)
Base MVA
= 40MVA
Positive sequence impedance (Z s) = System Voltage √3 x 9380 = 66000 (√3x 9380)
Min. Source resistance R s
Rs Min. Source reactance X s
=
( Zs1 )2 1 + (Xs1 / Rs1)2
=
(4.062) 2 1+ (14.01)2
= 4.062 Ohms
= 0.289 Ohms = 14.01 x R s = 14.01 x 0.2 89 = 4.048 Ohms
Transformer Data Voltage Rat io = 66/11 kV Rating = 40 MVA Zpu = 0.13 p.u. (at 32 MVA base) Impedance at 4 0 MVA base = 0.13 x 40/32 = 0.1625p.u. Actual Impedance Z T = Zpu X Base kV2 X 1000 Base kVA = 0.1625 X 662 X 1000 40 X 1000 = 17.69 Ohms
XT = Reactance of the transformer RT = Resistance of the transformer
8 of 13
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS
XT / RT = 46 RT
=
( ZT )2 1 + (XT / RT)2
=
(17.69) 2 1+ (46)2
= 0.383 Ohm XT
= 46 x RT = 46 x 0.383 = 17.618 Ohms
Case IV :- Fault on the 11kV Bus of Duhail and Fault contribution from Source (Through fault current seen by both of the 40 MVA transformers) Fault current will be limited by Source impedance (66kV Bus at Duhail) and parallel impedance of both of the 40MVA transformers. Source
Rs Xs
RT
RT
XT
XT
9 of 13
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS Three phase fault current calculation for 11kV Bus Reactance X= Source reactance X s + Transformer Reactance X T /2 = 4.048+ 17.618/2 = 12.857 Ohms Resistance R= Source resistance R s +Transformer Resistance R T /2 = 0.289 + 0.383/2 = 0.4805 Ohms Impedance
Fault current at the end of Feeder = 66000 (√3x 12.86)
= 2963.1 Amp.
Say 2.96 kA (66KV base)
Fault at 11KV bus
= 66000 x 2.96 = 17.76 kA 11000
Earth fault current magnitude for 11kV system is limited to 750A due to Earthing transformer. The same will be used for relay settings. Various impedances for 11kV system are calculated based on 11kV Base voltage and 500 kVA Base kVA and the following network is obtained.
10 of 13
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS
11kV Bus at Duhail (Fault level 17.76kA), ZS= 0.013+ j 0.348
Source fault level at 11kV bus = 338 MVA (17.76 kA) Source X/R ratio
= 26.76(Derived from the calcula tions performed above in Case-IV)
Base MVA
= 500kVA
Positive sequence impedance (Z s) = System Voltage √3 x 17760 = 11000 (√3x 17760)
11 of 13
= 0.357 Ohms
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS
Min. Source resistance R s
Rs Min. Source reactance X s
=
( Zs1 )2 1 + (Xs1 / Rs1)2
=
(0.357)2 1+ (26.76) 2
= 0.013 Ohms = 26.76 x R s = 26.76 x 0.013 = 0.348 Ohms
Transformer Data Voltage Ratio = 11/0.415 kV Rating = 500kVA Zpu = 0.096 p.u. Actual Impedanc e ZT = Z pu X Base k V2 X 1000 Base kVA = 0.096 X 11 2 X 1000 0.5 X 1000 = 23.23 Ohms
XT = Reactance of the transformer RT = Resistance of the transformer XT / RT = 35.37
RT
=
( ZT )2 1 + (XT / RT)2
=
(23.23)2 1+ (35.37) 2
= 0.6565 Ohm XT
= 35.37 x R T
12 of 13
s
ANNEXURE-I for Doc. 13-3/14/SIE/16/0606
FAULT CURRENT CALCULATIONS FOR RELAY SETTINGS = 35.37 x 0.6565 = 23.22 Ohms
Case V: - Fault on the 415V Bus of Duhail and Fault contribution from Source (Through fault current seen by 500 kVA transformer) Fault current will be limited by Source impedance (11kV B us at Duhail) and impedance of 500kVA transformer.
Three phase fault current calculation for 415V bus Reactance X= Source reactance X s + Transformer Rea ctance XT = 0.348+ 23.22 = 23.568 Ohms Resistance R= Source resistance R s +Transformer Resistance R T = 0.013 + 0.6565 = 0.669 Ohms Impedance
= 0.669 + j23.5 68
Impedance Z 1
= √X2 + R2 = √(23.568 )2 + (0.669)2 = 23.577 Ohms
Fault current at the end of Feeder = 11000 = 269.45 Amp, say 270 Amp (√3x 23.57)
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.