EXXON IP-03!02!07 Manual Sampling Systems

October 16, 2017 | Author: nadeemyaiman | Category: Pipe (Fluid Conveyance), Tap (Valve), Valve, Fluidization, Water
Share Embed Donate


Short Description

Download EXXON IP-03!02!07 Manual Sampling Systems...

Description

IP 3-2-7

Manual Sampling Systems

Page 1 of 12

INTERNATIONAL PRACTICE

(This practice is appropriate for attachment to Inquiry or Purchase Document)

Rev. 0

June 1997

Changes shown by ➧

SCOPE I

1.1

I

1.2

This practice covers the design and installation of facilities to obtain samples of liquid and gaseous materials from piping and process equipment, and fluidized solids particles from regenerator catalyst and coke transfer lines. It does not cover laboratory sampling facilities which are part of analyzer sampling systems for obtaining analyzer validation samples. An asterisk (✶) indicates that additional information is required. If the job is contracted, this additional information is furnished in the Job Specification.

SUMMARY OF ADDITIONAL REQUIREMENTS

➧ I

2.1



Table 1 lists the practices and standard which shall be used with this practice. TABLE 1 PRACTICES IP 3-6-1 IP 3-10-1

IP 3-18-1

Piping for Instruments Piping Selection and Design Criteria

Piping Fabrication Shop or Field

CODES AND STANDARDS ANSI Standard B31.3

Process Piping

SYSTEM DESIGN S



3.1

The types of sampling facilities will be specified per the following: SYSTEM TYPE (4)

USE Gas

Liquid

Fluidized Solids Particles



AUXILIARIES

A

Fig. 1 (1)

Fig. 5

— Sample Tap

B

Fig. 2 (1)

Fig. 5

— Sample Tap

C

Fig. 3

Fig. 5

— Sample Tap

Fig. 6

— Sample Discharge

Fig. 7

— Sampling Funnel (2)

D

Fig. 4

— Sample Tap * (Details to be specified) Fig. 6

— Sample Discharge

Fig. 9

— Sample Enclosure (3)

SAMPLE COOLER OR HEATER As required. Cooler to be commercially available type or per Fig. 8. Heater to be commercially available type or designed for the specific duty.

Not required

Notes: (1) The dimensions of the piping arrangement given in Figure 1 and Figure 2 are designed to accommodate a 3 300 cm sample cylinder. (2) The dimensions for the funnel given in Figure 7 is designed to accommodate a 1-quart bottle [approximately 3-3/4 in. diam. by 8-3/16 in. high (95 mm diam. by 210 mm high)]. (3) The dimensions for the enclosure given in Figure 9 are designed to accommodate a 5 gal container [approximately 12 in. diam. by 14 in. high (300 mm diam. by 350 mm high)]. (4) Sample system types are defined as follows: A - Gas B - Liquids that could vaporize or that are hazardous C - Liquids that will not vaporize and are not hazardous D - Fluidized solids If the size of the sample containers to be used is different from those specified in Notes (1), (2) and (3) above, the dimensions shall be altered accordingly.



C

REFERENCE

3.2

The use of proprietary type sampling valves will be specified. Installation details shall be submitted for review by the Owner’s Engineer. Note:

Proprietary type valves and systems for special applications include: interlocked valves, “ram-type” piston valves, samplers that use a septum on the sample bottle, and samplers that use a reciprocating sampling piston. If a “ram-type” valve is specified: (1) the piston shall extend approximately 1 in. (25 mm) into the pipe or vessel; (2) the valve shall have an indicator to show the position of the piston; (3) no block or check valves shall be installed in the sampling line for asphalt or materials of like viscosity.

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

IP 3-2-7

Manual Sampling Systems

Page 2 of 12 Rev. 0

June 1997

(This practice is appropriate for attachment to Inquiry or Purchase Document)

INTERNATIONAL PRACTICE

COOLING/HEATING FOR LIQUID AND GAS SAMPLES S

3.3

S

3.4

R

3.5

R



3.6

Sample coolers shall be designed for the pressure/temperature conditions of the stream being sampled. Materials of construction shall be suitable for the process fluid. Sample coolers shall be used as required to cool the sample to 140°F (60°C) or lower, but: (1) not below a temperature that would result in a viscosity greater than 500 cP, and (2) not to a temperature less than 25°F (14°C) above the pour point and the freezing point of the sample. Coolers for tar, asphalt, and residuum shall use co-current flow of water and the fluid being sampled, and a water preheater, to avoid plugging of the cooler. Sample system heaters. With fluids having a pour point or a freezing point above the lowest ambient design temperature, or having a viscosity greater than 500 cP at the lowest ambient design temperature, facilities shall be provided to heat the sampling system to 25°F (14°C) above the pour point and the freezing point of the sample to assure its flow into the sample container.

LIGHTING O

3.7



A minimum in-service illumination level of 20 ft candles (215 lux) shall be provided for sampling facilities. If lighting is provided specifically for the sampling system, a local switch shall be provided.

SAMPLE CONNECTIONS S,O

4.1

O

4.2

O

4.3

S O

4.4 4.5

The final locations of sample points shall be governed by the following considerations for personnel safety and accessibility: a. They shall be convenient to normal operating locations as far as practicable. b. The sample points shall preferably be accessible from ground level. If this is not practical, they shall be accessible from permanent platforms. c. At least two escape routes shall be available for personnel. d. They shall allow personnel to stand upwind, based on the prevailing wind pattern. e. They are not to be in areas of possible contamination if a spill of a hazardous material should occur (e.g., they shall not be in areas inside pump toewalls). Sample tap positioning shall be per the following: a. Liquid or gas streams. Sample taps shall not be closer than 20 pipe diameters downstream or 10 pipe diameters upstream from the junction of two streams. Where two-phase flow can exist, sample taps shall be no closer than 12 pipe diameters downstream from a pressure reducer. b. Fluidized solids streams. Sample taps shall not be closer than 8 pipe diameters downstream or 2 pipe diameters upstream from a junction of two fluidized solids streams, an elbow, valve, or other flow disruption. Sample tap orientation shall be per the following: a. Sample taps should be installed in vertical lines with upward liquid flow and downward vapor flow. b. When sample taps are installed in horizontal lines, side entry of probe is preferred. Process vents and drains shall not be used as sample connections. Sample connections shall not be used for the installation of indicators or other instruments that are extraneous to the sampling operation.

PIPING DESIGN S

5.1

S

5.2

Sample piping shall be as short as possible and shall be adequately supported and braced to minimize the probability of it being damaged by vibration, accidental impact, or reaction forces caused by valve operation. Soft sealed ball and plug valves shall not be used as block valves on lines discharging to the atmosphere.

MATERIALS R



5.3

All valves in liquid and gas sampling systems shall be Type 304 or Type 316 stainless steel, unless other materials of construction are required because of the fluid to be sampled. Valves in fluidized solids sampling systems are described in Figure 4. THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

Manual Sampling Systems

Page 3 of 12

INTERNATIONAL PRACTICE

S



5.4

IP 3-2-7

(This practice is appropriate for attachment to Inquiry or Purchase Document)

Rev. 0

June 1997

Where the temperature of the stream being sampled can be below -20°F (-29°C), including when the cold temperature results from flashing, all piping, valves, and fittings shall have suitable low-temperature properties.

TESTING S

6.1

S

6.2

Hydrostatic testing: a. All piping shall be hydrostatically tested per ANSI B31.3. b. Austenitic stainless steel piping and tubing shall be tested and flushed with water having less than 500 ppm (500 mg/L) of chlorides. Potable water will meet this requirement. The piping and tubing shall be drained immediately after flushing and residual water removed by blowing with air. A leakage test shall be conducted on the entire system, at the specified design pressure. Maximum permissible leakage rates are as follows: a. Gas Systems: 5% change per hour. b. Liquid Systems: No visible leakage. c. Fluidized Solids Systems: No visible dust plume.

INSULATING FOR PERSONNEL PROTECTION S

7.1

S

7.2

Equipment surfaces operating above 150°F (65°C) and located within 1 ft (300 mm) horizontally of a normal access, walkway, or work area shall be insulated to protect personnel. Where insulation is not permitted, personnel shall be protected by open guards, shields, or railing.

SAMPLE POINT IDENTIFICATION S



8.1

Sample points shall be identified with a permanent, corrosion resistant tag securely fastened (adhesive fastening is not acceptable). Each tag is to include the following information: a. Unit name. b. Unit sample identification. c. Sample identification for accounting purposes. d. Physical state (liquid, vapor or solid). e. Temperature. f. Pressure.

Revision Memo 1/83 1/85 12/92 6/97

Original Issue of Basic Practice Revision 1 Revision 2 Revision 0 - Original Issue of International Practice General technical and editorial revision to BP 3-2-7, Revision 2, to align the IP with other company practices. Specific revision include: Deleted Old Pars. 1.2, 2.1, 2.3, 2.9, 3.1, 2.5, 2.8, 4.2, 4.3, 4.5, 4.6, 4.7, 4.9, 4.10. Added section 2, summary of additional requirements, section 2.1, Table 1, list of International Practices & Standards to be used with this practice. Par. 3.7 changes minimum illumination level for lighting to 20 ft candles (215 lux). Figure 1, note 1, reordered sentence to move examples of differential pressure. Figure 1 added note 8, requiring the specification of take-off orientation. Figure 2, note 1, reordered sentence to move examples of differential pressure. Figure 1, added note 11, requiring the specification of take-off orientation. Figure 3, note 1 reordered sentence to move examples of differential pressure. Figure 3, added note 9 requiring specification of take-off orientation. Figure 8, note 5 was added to specify CSO valves in cooling water outlet lines. Renumbered Pars. 2.2 to 3.1, 2.4 to 3.2, 2.5 to 3.3, 2.6 to 3.4, 2.7 to 3.5, 2.8 to 3.6, 2.10 to 3.7, 3.2 to 4.1, 3.3 to 4.2 ,3.4 to 4.3, 3.6 to 4.4, 3.7 to 4.5, 4.1 to 5.1, 4.4 to 5.2, 4.8 to 5.3, 4.11 t o5.4, 5.1 to 6.1, 5.2 to 6.2, 6.1 to 7.1, 6.2 to 7.2, 7.1 to 8.1.

Exxon Research & Engineering Company, 1992, 1997

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

IP 3-2-7

Manual Sampling Systems

Page 4 of 12 Rev. 0

June 1997

INTERNATIONAL PRACTICE

(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 1 SAMPLING FACILITIES FOR GASES-TYPE A B re a k F la n g e s 3 / 4 in . N P S N o te s (2 ) & (5 )

N o te (8 )

Min.

S a m p le T a p ( F ig u r e 5 )

3 / 4 in . N P S N o te s (2 ) & (5 )

Min.

S o u rc e o f ∆ P N o te (1 ) P r o c e s s P ip in g o r E q u ip m e n t

F lo w

B r e a k F la n g e s P xxx I

N o te (3 )

N o te (4 ) N o te (6 )

(approx.)

1 / 4 in . N P S 42 in.

N o te (6 )

G L 1 5 - 1 / 4 in . (a p p ro x .)

1 /4 in . N P S

S p a c e f o r R e m o v a b le S a m p le C y lin d e r (S e e d e ta il b e lo w )

G r a d e o r P la t fo r m

F ix e d p a r t o f S a m p lin g S y s t e m

V a lv e

P R V a lv e 300 cm

3

c y li n d e r

N o te (7 ) 9 - 1 / 2 in . 1 5 - 1 /4 in . ( a p p r o x . )

030207F1

Notes:





(1) (2) (3)





(4) (5) (6) (7) (8)

Any conveniently located source of differential pressure (heat exchanger, pumps, control valve, etc.) with the exception of orifice plates. Sealweld threaded connections. Threaded female connections to mate with male connections of sample cylinder. Connections shall not put torque on the tubing or piping. PI shall be located and positioned for reading by person collecting sample. Brace block valve in two planes. Install when block valves at sample takeoff and return points are not easily accessible. Install flexible tubing from globe valve to sample cylinder. Orientation of take-off connection will be specified. Connections, with the exception of "ram-type" piston valves shall not be installed on the bottom of pipes, vessels or tanks. ACCEPTABLE METRIC EQUIVALENTS in. mm.

1/4 NPS

3/4 NPS

9-1/2

15-1/4

42

8

20

240

385

1050

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

IP 3-2-7

Manual Sampling Systems

Page 5 of 12

INTERNATIONAL PRACTICE

(This practice is appropriate for attachment to Inquiry or Purchase Document)

Rev. 0

June 1997

FIGURE 2 SAMPLING FACILITIES FOR LIQUIDS-TYPE B B r e a k F la n g e s 3 / 4 in . N P S N o te s (2 ) & (5 )

N o te (1 1 )

Min.

S a m p le T a p ( F ig u r e 5 ) S o u rc e o f ∆ P N o te (1 )

F lo w

M in .

B re a k F la n g e s

Min.

Min.

1 /4 in . N P S

15-1/4 in.

(approx.)

F lo w S ig h t G la s s N o te (8 )

N o te (3 )

S p a c e f o r R e m o v a b le S a m p le C y lin d e r ( S e e d e t a il b e lo w )

G L 1 / 4 in . N P S

Min.

P xxx I

(approx.)

42 in.

N o te (4 )

N o te (7 )

3 -W a y V a lv e

F ix e d p a r t o f S a m p lin g S y s t e m

3 /4 in . N P S N o te s (2 ) & (5 )

Min.

P r o c e s s P ip in g o r E q u ip m e n t

V a lv e

P R V a lv e 300 cm

N o te (9 )

G ra d e o r P la tfo rm

N o te (6 )

3

c y lin d e r

N o te (1 0 ) 9 - 1 /2 in . 1 5 - 1 / 4 in . ( a p p ro x .)

030207F2

Notes:





(1) (2) (3) (4) (5) (6)







(7) (8) (9) (10) (11)

Any conveniently located source of differential pressure (heat exchanger, pumps, control valve, etc.) with the exception of orifice plates. Sealweld threaded connections. Threaded female connections to mate with male connections of sample cylinder. Connections shall not put torque on the tubing or piping. PI shall be located and positioned for reading by person collecting sample. Brace block valve in two planes. Return loop not required if distance from sample takeoff to sample discharge into sample cylinder is 24 in. or less. Return to process, or drain to a designated closed system, as specified. If purge is returned to process, line and sight glass must be suitable for the line service classification of the process equipment to which they are connected. Install flexible tubing from globe valve to sample cylinder. Sample cylinder should have outage dipleg to allow for thermal expansion. Orientation of take-off connection will be specified. Connections, with the exception of "ram-type" piston valves shall not be installed on the bottom of pipes, vessels or tanks. ACCEPTABLE METRIC EQUIVALENTS in. mm.

1/4 NPS

3/4 NPS

9-1/2

15-1/4

24

42

8

20

240

385

600

1050

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

IP 3-2-7

Manual Sampling Systems

Page 6 of 12 Rev. 0

June 1997

(This practice is appropriate for attachment to Inquiry or Purchase Document)

INTERNATIONAL PRACTICE

FIGURE 3 SAMPLING FACILITIES FOR LIQUIDS-TYPE C B re a k F la n g e s 3 /4 i n . N P S N o te s (2) & (5 )

N o te (9 )

S a m p le T a p (F ig u re 5 ) S o u rc e o f ∆ P N o te (1 )

F lo w

P xxx I

N o te (4 )

Min.

P ro c e s s P ip in g o r E q u ip m e n t

3 /4 i n . N P S N o te s (2) & (5 ) B re a k F la n g e s

3 -W a y V a lv e

Min.

(approx.)

N o te (6 ) 1 /4 i n . N P S S a m p le D is c h a r g e E v a lu a tio n (F ig u re 7 ) N o te (8 )

G L

S p la s h P r o te c tio n Funnel (F ig u re 7 )

48 in.

(approx.)

N o te (3 )

3 /4 in . N P S M in . N o te (7)

G ra d e o r P l a tfo rm 030207F 3

Notes:













(1) (2) (3) (4) (5) (6) (7) (8) (9)

Any conveniently located source of differential pressure (heat exchanger, pumps, control valve, etc.) with the exception of orifice plates. Sealweld threaded connections. Minimum required clearance to permit placement and removal of sample containers without spilling contents. PI shall be located and positioned for reading by person collecting sample. Brace block valve in two planes. Return loop not required if distance from sample takeoff to sample discharge into sample cylinder is 24 in. or less. Drain to a designated closed system. Sample discharge elevation to be approximately 46 in. above grade or platform for convenience. Orientation of take-off connection will be specified. Connections, with the exception of "ram-type" piston valves shall not be installed on the bottom of pipes, vessels or tanks. ACCEPTABLE METRIC EQUIVALENTS in. mm.

1/4 NPS

3/4 NPS

24

48

8

20

600

1200

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

IP 3-2-7

Manual Sampling Systems

Page 7 of 12

INTERNATIONAL PRACTICE

(This practice is appropriate for attachment to Inquiry or Purchase Document)

Rev. 0

June 1997

FIGURE 4



S A M P L IN G F A C IL IT IE S F O R F L U ID IZ E D S O L ID S P A R T IC L E S – T Y P E D ( F O R R E G E N E R A T E D C A T A L Y S T A N D C O K E T R A N S F E R L IN E S ) P u r g e , L o c a te a s c lo s e to fl a n g e a s p r a c ti c a b l e (N o te 2 ) S a m p le T a p (N o te 1 ) R O xxx

P u rg e , V a lv e b o d y c o n n e c tio n p o s iti o n A o r C p e r A N S I B 1 6 .3 4 F ig . 1 (N o te 2 )

1 - 1 /2 x 1 i n . N PS

n 33 i

F u ll p o rt g a te v a l v e s

. mi n.

TR AN SFER L IN E

R O xxx

F u ll p o rt p lu g v a lv e P

1 -1 /2 in . N P S p e r lin e c l a s s ific a tio n M A T E R IA L SPEC BREAK 1 -1 /2 i n . N P S C la s s 1 5 0 , C S , 1 /8 in . C A , e x c e p t C la s s 3 0 0 m a tin g fla n g e

S a m p le E n c lo s u re ( F ig u r e 9 )

E v a lu a tio n o f S u p p o rt G ra ti n g fo r s a m p le c o n ta in e r a p p r o x . 4 2 in . a b o v e w o r k p l a tfo r m

O v e rflo w p ip e , s iz e 3 in . N P S V e n t p ip e , s iz e 2 in . N P S R e p l a c e a b l e D u s t F i l te r , s i z e 1 m ic r o n a b s o lu te D u s t ti g h t s l ip fi ttin g ( N o t e 3 ) D u s t ti g h t c o v e r O v e rflo w c o n ta in e r a p p r o x . 5 5 g a l v o lu m e (N o te 4 ) G r a d e o r P l a t fo r m 030207F 4

Notes: ✶

(1) (2) (3) (4)



Location and orientation of Sample Tap will be specified. Steam or nitrogen purge, as specified, designed for 10 to 14 fps purge velocity in sample line. LR Elbow, Sample Enclosure, Overflow Pipe to be readily removable from cover of container. Design shall permit easy removal of overflow container from system. ACCEPTABLE METRIC EQUIVALENTS

in. mm.

1/8

18

42

NPS 1-1/2 X 1

1

2

3

10-14 fps

55 gal

3

450

1050

40 X 25

25

50

80

3-4 m/s

220 L

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

IP 3-2-7

Manual Sampling Systems

Page 8 of 12 Rev. 0

June 1997



(This practice is appropriate for attachment to Inquiry or Purchase Document)

INTERNATIONAL PRACTICE

FIGURE 5 SAMPLE TAP FOR PIPES IN LIQUID AND GAS SERVICES

A

A V IE W L O O K IN G U P S T R E A M

o

F la n g e d C o n n e c t io n

Flow

45 P ip e S iz e

Im m e r s io n D e p t h " X " N o te (3 )

< 2 0 in . > 2 0 in

M id p o in t o f P ip e 1 0 in .

S c h e d . 1 6 0 P ip e N o te s (1 ) & (2 )

P r o b e m a r k e d f o r lo c a t in g p r o p e r t y in lin e

"X " 030207F5

S E C T IO N A - A

Notes: (1) For process system piping less than 2 in. NPS, a Tee shall be installed in a vertical piping run for sampling purposes. If no vertical run is available, the Tee shall be oriented so that the sample is drawn from the top of the pipe. A reducer shall be used to connect the 3/4 in. NPS circulating loop pipe to the process pipe at the Tee. (2) Sample taps shall not be located on low points of piping runs. (3) If the pipe will operate partly filled, locate the sample tap approximately at the centroid of the stream. ACCEPTABLE METRIC EQUIVALENTS in.

10

20

3/4 NPS

2 NPS

mm.

250

500

20

50

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

Manual Sampling Systems INTERNATIONAL PRACTICE

IP 3-2-7 Page 9 of 12

(This practice is appropriate for attachment to Inquiry or Purchase Document)



Flow

FIGURE 6 SAMPLE DISCHARGE

S a m p le D is c h a rg e : F o r L iq u id s - 1 /4 in . N P S ( 8 m m ) F o r F lu id iz e d S o lid s - 1 - 1 /2 in . N P S ( 4 0 m m )

T o p o f S a m p le C o n ta i n e r

C h a m fe r e n d

M i n i m u m to a l l o w r e m o v a l o f c o n ta i n e r w ith o u t s p ill in g c o n te n ts 030207F6

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

Rev. 0

June 1997

IP 3-2-7

Manual Sampling Systems

Page 10 of 12 Rev. 0

June 1997

(This practice is appropriate for attachment to Inquiry or Purchase Document)

FIGURE 7 SPLASH PROTECTION FUNNEL FOR LIQUID SAMPLES

INTERNATIONAL PRACTICE

(1)

F ix e d p e rfo ra te d p la te N o te (2 )

C u to u t D ir e c to ry u n d e r s a m p le d is c h a rg e N o te (3 ) S E C T IO N A - A H a n d le

B

CO VER FO R FUNNEL

S A M P L IN G RATE

A

FUNNEL D IA M .-A in . m m

0 .5 g p m ( 1 .9 L /m )

8 12 16 20

2 3 4 5

0 0 0 0

8 8 6 2

1 .0 g p m ( 3 .8 L /m )

12 16 20

300 400 500

12 12 12

A

0 0 0 0

A

✶ ✶

M IN . S ID E H E IG H T - B in . m m 2 2 1 5

00 00 50 0

300 300 300

030207F7

Notes: (1) Funnel and cover shall be fabricated of material suitable for the process fluid handled and sized to accommodate all specified sample containers. Both dimensions A and B shall be 12 in. (300 mm) for 1 quart bottles. Cover shall be chained to funnel. (2) Perforated plate shall be designed to support the weight of the largest specified sample container filled with sample. Assume that a 1 quart bottle filled with sample weights 5 lbs (2.3 kg). (3) Cutout shall be the maximum size that will allow the smallest specified sample container to rest securely on the perforated plate when under the sample discharge. The cutout diameter shall be 1-1/2 in. (40 mm) for 1 quart bottles.

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

IP 3-2-7

Manual Sampling Systems INTERNATIONAL PRACTICE

Page 11 of 12 (This practice is appropriate for attachment to Inquiry or Purchase Document)



Rev. 0

June 1997

FIGURE 8 SAMPLE COOLER C o o li n g W a t e r O u tle t N o te (4 ) M in .

C o o lin g W a te r In le t

4 in . N P S p ip e

1 - 1 / 2 in .

1 - 1 / 2 in .

S a m p le In le t 8 in . N P S p ip e SAM PLE TEM PERATUR E (° F )

1 /2 in . N P S o r 5 /8 in . O D tu b in g (F o rm e d a ro u n d a 5 in . N P S p ip e )

NUM BER OF TURNS O F C O IL

400 350 300 250 200 150

1 - 1 /2 in .

1 - 1 /2 in .

16 15 13 12 9 3

M IN . S IZ E O F C O O L IN G W A T E R C O N N E C T IO N S (N P S , in .) In le t

O u tle t

1 1 1 3 /4 1 /2 1 /2

2 2 2 1 -1 /2 1 -1 /2 1 -1 /2

S a m p le O u tle t

A c c e p ta b le M e tr ic E q u iv a le n ts

1 in . N P S D r a in ( c a p p e d o r p lu g g e d ) G e n e ra l N o te s : ( 1 ) C o m m e r c ia lly a v a ila b le c o o le r s a r e a c c e p t a b le fo r u s e in t h e c ir c u la t io n lo o p s c o m m e r c ia lly a v a ila b le c o o le r s t h a t a r e s e lf d r a in in g a r e a c c e p ta b le , in lie u o f t h e d e s ig n s h o w n , fo r u s e in th e d is c h a r g e lin e . ( 2 ) P i p i n g t h i c k n e s s a n d m a t e r i a l s h a l l b e c o n s i s t e n t w i t h t h e p ip i n g c la s s ific a tio n fo r th e flu id h a n d le d . ( 3 ) C o o lin g w a te r r a t e s h a ll b e b a s e d o n c o o lin g r e q u ir e m e n t s . * ( 4 ) A s s p e c i f i e d , t h e c o o l in g w a t e r o u t l e t s h a l l b e c o n n e c t e d t o t h e c o o lin g w a te r r e tu r n lin e o r p ip e d to s e w e r. If c o n n e c te d t o th e r e t u r n lin e , a f l o w s ig h t g la s s a n d v a lv e s h a ll b e in s t a lle d in t h e o u t le t lin e . T h e d is c h a r g e p ip in g s h a l l b e p r o t e c t e d f r o m f r e e z in g . ( 5 ) B e c a u s e o f p o t e n t i a l f o r t h e r m a l e x p a n s i o n , a v a l v e i f in s t a l l e d i n t h e c o o lin g w a t e r o u t le t lin e s h o u ld b e c a r s e a le d o p e n ( C S O ) .

NPS or O D a s in d ic a t e d in .

m m

°F

°C

1 /2 5 /8 3 /4 1 1 -1 /2 2 4 5 8

12 16 20 25 40 50 100 125 200

150 200 250 300 350 400

65 93 120 150 175 200

030207F8

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

IP 3-2-7

Manual Sampling Systems

Page 12 of 12 June 1997

(This practice is appropriate for attachment to Inquiry or Purchase Document)

INTERNATIONAL PRACTICE

FIGURE 9 SAMPLE ENCLOSURE FOR FLUIDIZED SOLIDS SERVICE (DIMENSIONS SHOWN FOR 5 GAL. CONTAINER)

F i x e d g r a ti n g . 1 x 4 in . o p e n in g s N o te (3 ) S a m p le In l e t

20 in.

Rev. 0

TO P

S E C T IO N A - A

2 0 in . 1 6 in . 1 -1 /2 in . N o te (1) N o te (2 )

30o A

A

3 in . FRO NT

030207F 9

Notes: (1) Sample enclosure to be fabricated from carbon steel. (2) Spring hinged and latched, dust tight door. (3) Grating and supports shall be designed to support the weight of the largest specified sample container filled with sample. ACCEPTABLE METRIC EQUIVALENTS in.

1

4

16

20

1-1/2 NPS

3 NPS

5 gal

mm.

25

100

400

500

40

80

20 L

THIS INFORMATION FOR AUTHORIZED COMPANY USE ONLY EXXON RESEARCH AND ENGINEERING COMPANY — FLORHAM PARK, N.J.

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF