External Alarm Schematic
Short Description
Download External Alarm Schematic...
Description
External Alarms Connection:
There are two types of environment monitoring configurations for the BTS3012: A DEMU is built in the common sub rack and connects to the external sensor through a cabinet top cable. Environment alarm box (EAC-2), communicates with the DTMU through CBUS3. Here in V7 project, we use the first type to configure the external alarm. When installing the DEMU of the BTS3012, we need to configure a DDF box for the DEMU. The configuration procedure is as shown below figure.
Figure 11-1 Installing a DDF box for the built-in DEMU
All alarm signals are collected from rectifier cabinet, fire alarm control panel, generator system, air-condition, HVAC control panel and door switch sensor, ect. And firstly all this signals will be connected to the DDF as a group. The picture below shows the blocks used inside HUAWEI DDF cabinet.
Figure 11-2 External alarm socket
Extended alarm socket resource allocation can be seen from below table: 0
1
2
3
4
5
6
7
Telecom shelter air condition #1 fault
Telecom shelter air condition #2 fault
Telecom/ General shelter fire alarm
Telecom/ General shelter door alarm
Telecom shelter high temperature alarm
Telecom shelter minor power fail(minor)
Telecom shelter tower light alarm
X2
Generator #1 fault
Telecom shelter power fail major
Generator low fuel – day tank
Generator low fuel – storage tank
Telecom shelter commercial power fail
Generator #2 fault
X3
Telecom/ Generator shelter FM200 released/ FA fault
Telecom shelter high humidity alarm
Generato r #1 running(i ndication ) Telecom shelter battery/ AC failaccess control
Telecom shelter battery discharge/ commercial power Generator #2 running(indic ation)
Telecom shelter OPP alarm
DSX Fuse
Micor Wave Major
Micor Wave Minor
X1
Micor Wave Remote
Table 11-1 External alarm socket resource allocation table
The below table shows the function of the DMLC connector on the top of cabinet: Printscreen
Type
Description
BOM Code of the Cable
SWIN
MD68 female connector
32 Boolean value inputs
4047251 Single Cable,Alarm Input Signal Cable, 10.0m, D68M-IV, CC32P0.4P430U(S)-I, BTS3012
SWOUT
DB15 female
6 Boolean value outputs
4047250 Single Cable,Boolean Value Output
Printscreen
Type
Description
connector AIN
DB44 female connector
BOM Code of the Cable Signal cable, 10.0m, D15M-I, CC8P0.4P430U(S)-I, BTS3012
4 analog inputs, smoke/water/door access control/ infrared/temperature and humidity sensor signal input
4047252 Single Cable,Analog Signal And Dedicated Signal Cable, 10.0m, D44M-I, CC16P0.4P430U(S)-I, BTS3012
Table 11-2 Function of the DMLC connector
The following table shows the definition of the cable for the sensors at the cabinet top. BOM Code of Cable 4047250 Single Cable,Boolean Value Output Signal Cable,10.0m,D15MI,CC8P0.4P430U(S)I,BTS3012
4047252 Single Cable,Analog Signal And Dedicated Signal Cable,10.0m,D44MI,CC16P0.4P430U(S) -I,BTS3012
Connector to the DMLC at the Cabinet Top / Cable Signal Definition
4047251 Single Cable,Alarm Input Signal Cable,10.0m,D68MIV,CC32P0.4P430U( S)-I,BTS3012
Boolean value input ports 1–8 and 9–16:
Boolean value input ports 17–24 and 25–32:
Figure 11-3 Function of the DMLC connector
The following table shows the connections between DDF sockets and SWIN pins. Alarm ID 6438
Connecto r Pin
Core Color
Connecto r Pin
Core Color
Alarm Name
DDF
X1.2
White
X1.36
Blue
Telecom shelter air condition #1 fault
PIN NO. X1-0
6440 6442 6444 6446 6448 6450 6452
X1.3 X1.4 X1.5 X1.6 X1.7 X1.8 X1.9
White White White White Red Red Red
X1.37 X1.38 X1.39 X1.40 X1.41 X1.42 X1.43
Orange Green Brown Grey Blue Orange Green
6454 6456 6458 6460 6462 6464 6466 6422 6424
X1.10 X1.11 X1.12 X1.13 X1.14 X1.15 X1.16 X1.17 X1.18
Red Red Black Black Black Black Black Black White
X1.44 X1.45 X1.46 X1.47 X1.48 X1.49 X1.50 X1.51 X1.52
Brown Grey Blue Orange Green Brown Grey Blue Blue
6426 6428 6430 6432 6434 6436 6468 6470 6472 6474 6476 6478 6480 6482 6484
X1.19 X1.20 X1.21 X1.22 X1.23 X1.24 X1.25 X1.26 X1.27 X1.28 X1.29 X1.30 X1.31 X1.32 X1.33
White White White White Red Red Red Red Red Black Black Black Black Black Black
X1.53 X1.54 X1.55 X1.56 X1.57 X1.58 X1.59 X1.60 X1.61 X1.62 X1.63 X1.64 X1.65 X1.66 X1.67
Orange Green Brown Grey Blue Orange Green Brown Grey Blue Orange Green Brown Grey Blue
Telecom shelter air condition #2 fault Telecom/General shelter fire alarm Telecom/General shelter door alarm Telecom shelter high temperature alarm Telecom shelter minor power fail(minor) Telecom shelter tower light alarm Telecom shelter battery discharge/ commercial power Generator #1 fault Telecom shelter power fail major Generator #1 running(indication) Generator low fuel – day tank Generator low fuel – storage tank Telecom shelter commercial power fail Generator #2 fault Generator #2 running(indication) Telecom/ Generator shelter FM200 released/ FA fault Telecom shelter high humidity alarm Telecom shelter battery/ AC fail-access control Telecom shelter OPP alarm DSX Fuse Micro Wave Major Micro Wave Minor Micro Wave Remote TTA Alarm Boolean Value Alarm on Path 26 Boolean Value Alarm on Path 27 Boolean Value Alarm on Path 28 Boolean Value Alarm on Path 29 Boolean Value Alarm on Path 30 Boolean Value Alarm on Path 31 Boolean Value Alarm on Path 32
Table 11-3 connections between DDF sockets and DDFpins
There are three type cable between DMLC and DDF, BOM:4047251 Single Cable,Alarm Input Signal Cable, 10.0m, D68M-IV, CC32P0.4P430U(S)-I, BTS3012 BOM:4047250 Single Cable,Boolean Value Output Signal cable, 10.0m, D15M-I, CC8P0.4P430U(S)-I, BTS3012 BOM:4047252 Single Cable,Analog Signal And Dedicated Signal Cable, 10.0m, D44M-I, CC16P0.4P430U(S)-I, BTS3012
X1-1 X1-2 X1-3 X1-4 X1-5 X1-6 X1-7 X2-0 X2-1 X2-2 X2-3 X2-4 X2-5 X2-6 X2-7 X3-0 X3-1 X3-2 X3-3 X3-4 X3-5 X3-6 X3-7 X4-1 Future Future Future Future Future Future Future