External Alarm Configuration Procedure-20110317

October 30, 2017 | Author: Samir Ah | Category: Boolean Algebra, Computer Networking, Computer Hardware, Telecommunications, Manufactured Goods
Share Embed Donate


Short Description

Download External Alarm Configuration Procedure-20110317...

Description

External Alarm Configuration Procedure

1 Introduction to Hardware Ports and Alarm Cables 1.1 Monitoring Ports on the BBU The UPEU on the BBU has two Boolean input ports, as shown in the following figure:

Boolean input ports on the UPEU in the upper part of the BBU: −

EXT-ALM0: port for Boolean inputs 0 to 3



EXT-ALM1: port for Boolean inputs 4 to 7

The BBU supports a maximum of 16 Boolean inputs. Each UPEU supports eight Boolean inputs. The BBU is configured with one UPEU in the lower part by default.

2011-03-17

Huawei Confidential

Page 1 of 5

External Alarm Configuration Procedure

1.2 Color Definitions for the Boolean Alarm Cables on the BBU RJ45 Pin/Color

Recommends Cable Leading Sequence for the BBU

Twisted Pair

1 Orange white

Boolean input 1+

1 and 2 twisted

2 Orange

Boolean input 1– (GND)

1 and 2 twisted

3 Green white

Boolean input 2+

3 and 6 twisted

4 Blue

Boolean input 3- (GND)

4 and 5 twisted

5 Blue white

Boolean input 3+

4 and 5 twisted

6 Green

Boolean input 2- (GND)

3 and 6 twisted

7 Brown white

Boolean input 4+

7 and 8 twisted

8 Brown

Boolean input 4- (GND)

7 and 8 twisted

2011-03-17

Huawei Confidential

Page 2 of 5

External Alarm Configuration Procedure

1.3 Hardware Connection of External Alarms For the detailed information about port numbers and slots, see the following table: Monitoring

Monitoring

Frame Position - Slot

Port

Device

Device Port

Position

Number

Name and BOM of

Core

the Monitoring

Number of

Cable

the Cable

BTS Type

4 UPEU (The

BTS3900

The UPEU is in slot 19 of

of a UPEU are

frame 0. The GTMU is in

reported on the

slot 6 of frame 0.

Orange white/orange

5

BBU Boolean

X1.3/X1.6

Green white/green

6

alarm cable

X1.5/X1.4

Blue white/blue

7

X1.7/X1.8

Brown white/white

0

X1.1/X1.2

Orange white/orange

1

BBU Boolean

X1.3/X1.6

Green white/green

2

alarm cable

X1.5/X1.4

Blue white/blue

X1.7/X1.8

Brown white/white

EXT-ALM0 3

2011-03-17

X1.1/X1.2

EXT-ALM1

Boolean alarms

GTMU)

Cable color

Huawei Confidential

Page 3 of 5

External Alarm Configuration Procedure

2 Setting the Boolean Alarm of the BBU 2.1 Setting the Boolean Alarm of the BBU on the BSC6900 Step 1: As shown in figure 1, set the alarm name, alarm level, and the gateway categories on the MML. The command used on the MML is SET ENVALMPARA. The alarm ID here is the alarm ID of the port to be set.

Figure 1

Step 2: In the MML input serial port, type the SET BTSENVALMPORT command to set the high and low voltage levels of the dry contacts on the UPEU.

Figure 2

Note: For the current BTS in the BSC6900, the numbers of the ports on the PEU in both upper and lower parts of the PEU are in range of 0 to 7.

Step 3: Use the MML command (LST BTSENVALMPORT) to check whether the numbers of the ports where dry contacts are set and the alarm levels are correctly set.

2011-03-17

Huawei Confidential

Page 4 of 5

External Alarm Configuration Procedure

2.2 Alarm ID of the Boolean Alarm The alarm ID of Boolean alarm which can be defined by the user starts from 65033 to 65533.

2011-03-17

Huawei Confidential

Page 5 of 5

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF