EuroChiller Instructions Manual

February 28, 2019 | Author: anon_385650136 | Category: High Voltage, Refrigeration, Leak, Valve, Switch
Share Embed Donate


Short Description

Download EuroChiller Instructions Manual...

Description

GC LT INSTRUCTIONS MANUAL

PROCESSING WATER CHILLER

EUROCHILLER S.r.l. INTERNATIONAL COOLING

Via Milano, 69 27030 CASTELLO D’AGOGNA (PV) ITALIA TEL. 0384-298985 - FAX 0384-298984 SERVICE 0384-298981 e-mail [email protected]

REVISION DATE VERSION

3 15/10/2004 1

Model GC

Processing water chiller

HOW TO READ AND USE THIS OPERATING HANDBOOK This handbook is supplied in one copy when buying the machine. In case the customer requires more copies, he must order them to the Builder, stating the model and the machine serial number (the data are printed on the machine identification plate) The user of this machine must be a professionally skilled operator with a good experience on similar machines. On the contrary, the user must attend a training course for the machine use at the Builder's or reseller's or a training course held by the Builder's qualified personnel. This handbook must be regarded as an integrating part of the machine and therefore it must be always available for reading and must be kept in a dry and safe place far from sunbeams. The builder authorises the User to produce some copies of this document for internal use only. With the term ATTENTION is used to identify any actions which could compromise the machine condition and which could cause a danger, risk for the operator. These warnings are printed in Italics and sometimes in bold script.

Attention: The machine manufacturer, EUROCHILLER S.r.l. reserves the right to change the measurements, shape and characteristics of the machine at any time without prior notice.

Instruction, use and maintenance manual –

©02_10/02

Page 2

Model GC

Processing water chiller

MACHINE CODES SERIES

TYPE A – Axial ventilation / internal accumulation / pump C – Centrifugal ventilation / internal accumulation / pump A\E – Axial ventilation / delivery pump to the evaporator / without accumulation C\E – Centrifugal ventilation / delivery pump to the evaporator / without accumulation A\P – Axial ventilation without accumulation / without pump

GC

C\P – Centrifugal ventilation without accumulation / without pump LTA – Low-temperature version(-30°C) / axial ventilation / internal accumulation / pump LTC – Low-version temperature(-30°C) / centrifugal ventilation / internal accumulation / pump LTA\E – Low temperature version(-30°C) / axial ventilation / delivery pump to the evaporator / without accumulation LTC\E – Low-temperature version(-30°C) / centrifugal ventilation / delivery pump to the evaporator / without accumulation LTA\P – Low-temperature version(-30°C) / axial ventilation / without accumulation / without pump LTC\P – Low-temperature version(-30°C)/ centrifugal ventilation / without accumulation / without pump B – Low-temperature version(0°C)

Page 3

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

MAIN WARNINGS It is compulsory to carefully read the operating handbook before performing any operation on the machine: if the machine is started by unskilled operators it could cause serious damages to people and things. The operators responsible for the refrigerator use must be well trained. Therefore, the customer must check that the personnel training is suitable and when necessary, ask the builder to hold special training sessions. Each single machine component undergoes quality and dimensioning controls during the production process. All maintenance, adjustment setting and replacement operations described in this Instruction manual must be carried out ONLY AFTER having switched off the machine and disconnected the machine plug from the main line socket. While using the antifreeze liquid (if present) and the gas contained in the refrigeration circuit, the operator must wear special protective gloves and masks to avoid any sort of danger typical of their nature. The operator must wear special anti-slip and resistant shoes. The protection systems on the machine have been provided by the manufacturer to protect the operator during his work on the machine. These protection guards must NEVER be removed for any reason whatsoever while the machine is running. Never use the machine, which is equipped with an electric motor, in the presence of natural gas, petrol vapours or other inflammable vapours. No unauthorised operator must pass or stop near the lifting and handling area of the machine elements, while the operators responsible for such operations will have to keep at a suitable distance to avoid being hit by the elements hanging in the air. The electric and earth connection must be carried out by qualified and skilled operators according to the regulations in force. It is strongly advised to protect the user’s main line from overloading by installing a safety switch (magnetothermal switches) on the line.

The pressure value in the water tank must never exceed the atmospheric pressure value. The presence of magnetic or electromagnetic fields near the machine could compromise the correct function of the electrical or electronic parts. The ideal temperature and humidity levels for correct machine performance is standard room temperature. Check that the electric circuit is duly protected and that it corresponds to the motor features: the machine is equipped with an identification plate indicating the power, the frequency and the supply voltage. Check that the machine is provided with an earth connection and with a differential switch compliant with the regulations in force on top of the supply cable. The Builder will not accept any responsibility for the damages caused to people and things by a wrong ground connection. Only use the recommended types of gas and liquid: in case a different type is used, the Customer must first check the physical-chemical characteristics (included in the documentation attached to the element) and check the similarities with the recommended one: in case they are not similar, the Customer must contact the Builder about the product use.

Before any adjustment, maintenance and replacement operation the operator must wait for a while since the machine has been stopped, so that the parts subject to heating during the normal machine functioning can cool down.

Instruction, use and maintenance manual –

©02_10/02

Page 4

Model GC

Processing water chiller

INSTRUCTION MANUAL CONTENTS CHAPTER 1- GENERAL INFORMATION CONCERNING THE INSTRUCTION MANUAL 7 1.1 Introduction ............................................................................................................................. 7 1.2 Reference to standards........................................................................................................... 7 1.3 Aim of this document............................................................................................................... 7 1.4 Machine marking data and identification plate ........................................................................ 7 1.5 Use and conserving of this manual ......................................................................................... 7 1.6 Respecting current legislation ................................................................................................. 8 1.7 Information for the machine user ............................................................................................ 8

CHAPTER 2- PROTECTION SYSTEMS PROVIDED FOR THE OPERATOR’S SAFETY.. 9 2.1 Protection systems on the machine ........................................................................................ 9 2.2 Identification plate ................................................................................................................... 9

CHAPTER 3- EVENTUAL ADDITIONAL DANGER RISKS............................................... 10 3.1 Information concerning safety conditions and additional risks .............................................. 10

CHAPTER 4- CORRECT AND INCORRECT MACHINE USE........................................... 12 4.1 Warning advice against danger as a result of incorrect use ................................................. 12

CHAPTER 5- GENERAL DESCRIPTION OF THE MACHINE........................................... 13 5.1 Tables for the calculation of the refrigerating yield................................................................ 14 5.1.1 “GC LT”Tables for the calculation of the refrigerating yield................................................ 15 5.2 Operating principle................................................................................................................ 17 5.2.1 Cooling circuit .................................................................................................................... 17 5.2.2 Cooling circuit with hot gas (OPTIONAL)........................................................................... 17 5.2.3 Hydraulic circuit.................................................................................................................. 19

CHAPTER 6- MOVING AND TRANSPORTING THE MACHINE....................................... 21 6.1 Transporting the machine ..................................................................................................... 21 6.2 Weights ................................................................................................................................. 21

CHAPTER 7- MACHINE INSTALLATION ......................................................................... 22 7.1 Max machine size ................................................................................................................. 22 7.2 Area to be left free around the machine................................................................................ 23 7.3 Positioning for air canalization .............................................................................................. 24

CHAPTER 8- ASSEMBLAGE AND PREPARATION OF THE MACHINE TO WORK ...... 26 8.1 Preliminary control checks .................................................................................................... 26 8.2 Control check on any damage the machine may have suffered during transport ................. 26 8.3 Power supply connection ...................................................................................................... 27 8.3.1 Power supply connection ................................................................................................... 28 8.4 Hydraulic connection............................................................................................................. 32 8.4.1 Water pipes connection ..................................................................................................... 33 8.4.2 In-out connection sizes ...................................................................................................... 34 8.4.3 Hydraulic attacks position gc-lt........................................................................................... 35 8.5 Use of antifreeze in the process water.................................................................................. 36 8.5.1 % Glycol Yield diagram – Evaporator power..................................................................... 36 8.5.2 Ratio between the cooling and concentration points of water solutions in glycol............... 37 8.5.3 Antifreeze liquid filling system FILL-CHILL (Optional, for version GC 9 to GC 55 only) .... 37 8.5.4 Water content in the tank ................................................................................................... 38 8.5.5 Water pipes capacity.......................................................................................................... 38

Page 5

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

CHAPTER 9- CONTROL PANEL ...................................................................................... 39 9.1 Control panel for models GC 2 to GC 6 ................................................................................ 39 9.2 Display and functions ............................................................................................................ 39 9.2.1 Set point programming....................................................................................................... 40 9.3 Control panel for models GC 9 to GC 55 .............................................................................. 40 9.4 Display and functions ............................................................................................................ 41 9.4.1 Modifyng the temperature setting....................................................................................... 41 9.4.2 Resetting the alarm ............................................................................................................ 42 9.4.3 Modifyng the configuration parameters.............................................................................. 42

CHAPTER 10- MACHINE USE .......................................................................................... 43 10.1 Start-up and work cycle(for models GC 9 to GC 55 version excluded GC-E)..................... 43 10.2 Unforeseen stopping due to a power cut ............................................................................ 44 10.3 Stopping the machine manually .......................................................................................... 44 10.4 Reset thermomagnetic protection (for version GC 9 to GC 55 only)................................... 44

CHAPTER 11- MACHINE MAINTENANCE ....................................................................... 45 11.1 Programmed maintenance.................................................................................................. 45 11.2 Maintenance operations for axial fans (VER. GC-A)........................................................... 46 11.3 Cleaning the filters panel..................................................................................................... 46 11.4 Reset of the gas high pressure gauge .........................Errore. Il segnalibro non è definito. 11.4.1 Reset of the gas high pressure gauge (for version GC 2 to GC 6 only).................Errore. Il segnalibro non è definito. 11.4.2 Reset of the gas high pressure gauge (for version GC 9 to GC 55 only)......................... 47 11.5 Maintenance ON-OFF level switches.................................................................................. 48 11.6 Maintenance pumps............................................................................................................ 48 11.7 Maintenance an regulating differential by-pass valve (for versions GC 9 to GC 55 only)... 48 11.8 Amount of coolant. Type of oil. .......................................................................................... 48 11.9 Cleaning the control instruments (perform with machine switched off)............................... 48

CHAPTER 12- MODIFYNG THE PROTECTED PARAMETER (FOR VERSIONS GC 9 TO GC 55 ONLY) ..................................................................................................................... 49 12.1 gc lt Programme parameters............................................................................................... 50 12.2 IN / OUT list ........................................................................................................................ 51 12.3 Parameters programming (for versions GC 2 to GC 6)....................................................... 52 12.4 Programmable parameters ................................................................................................. 53 12.4.1 Parameters table.............................................................................................................. 53 12.5 Parameters description ....................................................................................................... 54 12.6 Errors signalling .................................................................................................................. 55 12.7 Cleaning .............................................................................................................................. 55

CHAPTER 13- TROUBLESHOOTING ............................................................................... 56 13.1 LED H1 / H2 – (par 9.3) ...................................................................................................... 56 13.2 LED H3 ............................................................................................................................... 57 13.3 LED H4 ............................................................................................................................... 58 13.4 LED H5 / H7 / H10 .............................................................................................................. 59 13.5 LED H8 / H9 ........................................................................................................................ 60

CHAPTER 14- LIST OF COMPONENTS ........................................................................... 61 CHAPTER 15- SPARE PARTS REQUESTS ..................................................................... 69 CHAPTER 16- MACHINE DEMOLITION ........................................................................... 75

Instruction, use and maintenance manual –

©02_10/02

Page 6

Model GC

Processing water chiller

CHAPTER 1- GENERAL INFORMATION CONCERNING THE INSTRUCTION MANUAL 1.1 INTRODUCTION This manual is very important for learning to know and operate the machine correctly. It is essential that the manual be read carefully before using the machine. Each machine is sold together with its own instruction manual. The machine user is responsible for keeping the manual for reference during the total machine life, making sure that the manual is not lost or destroyed until the machine has been demolished. The EUROCHILLER S.r.l. will not be held responsible for any tampering with this manual or for any changes made on the machine after its delivery, which have not been included and described in this manual. This causes the termination of the warranty The manufacturer reserves all technical and intellectual rights to the contents of this manual and all reproduction is prohibited, whether total or partial, and in any form whatsoever (printing, photocopying, microfilm, or other means). Reproduction is also forbidden using electronic systems, or transmission to third parties without the approval and registration by the manufacturer.

1.2 REFERENCE TO STANDARDS The indications contained in the following documents have been used in this handbook: Directive 98/37/EEC dated 22/06/1998 (that replaces the directive 89/392/EEC implemented in Italy by the Presidential Decree 459/96) Directive 73/23/EEC dated 19/02/1973. Directive 92/31/EEC of 28/04/1992, implementing the Directive 89/336/EEC. Directive 97/23/EC on the use of pressure equipment (PED) – (of the 01/06/02) UNI EN 292 -1 Nov. 92 Machine safety: Terminology UNI EN 292 - 2 Nov. 92 Machine safety: Specifications and technical principles CEI EN 60204-1 Apr. 98 Machine safety: Machine electric equipment

1.3 AIM OF THIS DOCUMENT The aim of this document is to provide the user with all information and instructions necessary for correct machine use and for the protection of the operator from all danger while working on the machine. All instructions must be obeyed carefully. For this reason the user is bound to the following: keep this document handy and accessible to the work area, making it available to the operator. The machine operator must read the manual before using the machine. the manual must be transferred to the following owner if the machine is sold or transferred.

1.4 MACHINE MARKING DATA AND IDENTIFICATION PLATE The Builder data, the machine model and serial number are indicated on the machine plate. Always refer to the data indicated on this plate for any communication about the machine (troubles, servicing during the warranty period, spare parts, etc.). The plate also shows the EC marking assuring the machine compliance with EEC regulations in force. All the warning notices present on the machine must be strictly observed and never removed.

1.5 USE AND CONSERVING OF THIS MANUAL This manual has been written for the machine user, the personnel responsible for handling and transport, the operator, the control and maintenance personnel, and those responsible for its final demolition. The manual was drawn up to provide all necessary information concerning the machine design, technical features, instructions for handling, adequate and safe installation, assembly, setting and use; it provides information on maintenance, ordering spare parts, and on any possible danger risks on the machine. In particular, the manual must be readily available for the following : conditions necessary for machine installation operator’s work position instructions concerning: • set up, • use, • transport, • installation, • assembly and disassembly, • setting interventions, • maintenance and repairs, • any necessary training instructions.

Page 7

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

1.6 RESPECTING CURRENT LEGISLATION As well as the rules and instructions contained in this manual, the user must apply all current legislation and standards concerning safety in work environments to prevent injury to personnel.

1.7 INFORMATION FOR THE MACHINE USER 123-

4-

5-

The manufacturer reserves the right to update any successive production and manuals without the necessity to update previous machines and manuals. Materials may be changed at any time according to technical evolution without prior notice. In any cases where the electrical protection controls are removed from the installation ( the electrical panel on the machine) the Manufacturer will not assume any responsibility for problems concerning safety measures as a result of electrical parts which do not comply with current standards and regulations. In any case, all responsibility for ensuring that the appropriate standards and legislation for electrical equipment attached to the machine lies with the customer, who must control that this work has been carried out correctly to standard. The manufacturer will not be held responsible for damage caused by any of the following: ¾ incorrect machine use ¾ use by untrained personnel ¾ use not in compliance with current standards ¾ use with faulty main line supplies ¾ lack of maintenance and repairs as advised in this manual ¾ non-authorised changes and /or modifications. Changes must receive the manufacturer’s written permission ¾ use with non original spare parts, or parts not designed for the machine ¾ use with the partial or complete disregard for the instructions contained in this manual The general sales guarantee is not considered as valid in the following cases: • incorrect machine use • Tampering with the machine • bad machine conservation • problems arising from incorrect machine use • use by untrained personnel • exceeding the machine’s performance limits • excessive use of all mechanical, electrical and/or pneumatic parts • machine use in unsuitable or dangerous conditions as described in point 4.

Any requests for extra copies of this manual must be made from the manufacturer demonstrating the proof of purchase. Copies are obtainable from EUROCHILLER S.r.l.

Instruction, use and maintenance manual –

©02_10/02

Page 8

Model GC

Processing water chiller

CHAPTER 2- PROTECTION SYSTEMS PROVIDED FOR THE OPERATOR’S SAFETY 2.1 PROTECTION SYSTEMS ON THE MACHINE The manufacturer has provided mechanical protection systems on the machine to protect the operator from any contact, even accidental, with any of the machine parts which can cause danger: 1. The perimeter has been marked by safety panels made of sheet, fixed by clamping screws, wrench required for opening. ƒ An IP54 door protecting the electric board is assembled on the front part: it is closed by the main switch and a series of hexagonal screws that can be opened only with a wrench; ƒ The rear side is equipped with a filter made of synthetic material; it is used to filter the capacitor operating air. 2. The fan, positioned on the refrigerator upper side, is equipped with a fixed protection grid IP 2X for the fingers covering it completely. 3. All the elements subject to heating during the normal production cycle have been covered with insulating material, so that the outer surface cannot overheat. Attention: The protection systems on the machine have been provided by the manufacturer to protect the operator during his work on the machine. These protection guards must NEVER be removed for any reason whatsoever while the machine is running.

2.2 IDENTIFICATION PLATE An identification plate fixed to the structure in a well visible way indicating the machine main data is applied to the machine: - CE mark, - The mark and the address of the manufacturer, - The model of machine, - Matriculation number, - The year of construction, - The machine electric data: • Voltage (VOLT) Power supply frequency (Hz) • Installed power (KW) Maximum power drain (A) • Auxiliary voltage (Vaux) Insulation voltage (Vi) • Protection index (IP) Type of gas (GAS) • Cooling flow rate (water 15°C – air 25°C) KW The identity plate shown below refers to machinery that does not require the application of Directive 97/23/EC on highpressure equipment; for other machines, the Manufacturer provides a booklet attached to the manual.

Figure paragraph 2.2

Page 9

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

CHAPTER 3- EVENTUAL ADDITIONAL DANGER RISKS 3.1 INFORMATION CONCERNING SAFETY CONDITIONS AND ADDITIONAL RISKS This equipment has been conceived by reducing all the sources and situations of danger to the minimum. Danger conditions can occur only if the installation rules are not observed or because of a wrong use of the product. DANGER DERIVING FROM CONTACT BETWEEN PRODUCTS AND OBJECTS OR PERSONS The movement of the fan poses a danger. The protection grill has a utility pitch of less than 12 mm IP 2X between wires. A further hazard is posed by accidental contact with the capacitor whose aluminium winglets can cause cuts. The capacitor is protected by filtering panels, which guarantee adequate safety levels under normal conditions. The utmost care must be taken when removing or repositioning the filter. SAFETY REGULATIONS FOR ELECTRICAL EQUIPMENTS The causes of electrical risks are well known and prevention is not difficult if attention is constant. To reduce the number of incidents of an electrical origin, personnel must be informed of potential danger and instructed on safety procedures. MANAGERS RESPONSABILITIES Managers must be informed of potential risks of the system and keep electrical equipment personnel under control. Control consists in locating possible risk conditions and investigating problems found by personnel during maintenance operations. Any defective components must be repaired or replaced immediately. The manager must make sure that safety measures are observed without tolerating or accepting deviations, in as much as damage to persons or apparatus may occur. HIGH VOLTAGE Contact with high voltage circuits can provoke burns, shock, unconsciousness or death by electrocution. This may be caused by a scarce knowledge of dangers connected to use of electric apparatus. SAFETY REGULATIONS WHILE CARRYING OUT MAINTENENCE WITH MACHINE ON - personnel must not carry out operations alone; - whenever possible operations must be carried out using only one hand; - check instruments and conducting wires periodically; - check that personnel is fully aware of the apparatus components and maintenance procedures before carrying out any work; - use protective gloves; - open all apparatus power supply contacts before taking resistance values; - check that in the low voltage circuit high voltage is not present; - do not use magnetic utensils near strong magnetic fields.. - If there’s a dangerous situation. NOXIOUS SUBSTANCES (XN) This unit contains and uses R22/R407c/R404a gas up to a maximum of 17 kg; the circuit is completely sealed. If a sudden leakage of refrigerant occurs, operators must move out of the vicinity and the room must be ventilated and don’t use free flames.

Instruction, use and maintenance manual –

©02_10/02

Page 10

Model GC

Processing water chiller

SAFETY REGULATIONS TO FOLLOW WHILE OPERATIONS ARE CARRIED OUT - if constant functioning is not required, the system must be turned off; - before carrying out electrical maintenance observe the following: ƒ check that the maintenance technician does not have objects that can act as conductors on his person; ƒ inspect the work area and check that it is clean and that the floor is dry; ƒ check that the work instruments to be used are suitable and in a good state for safe intervention; - measurement instruments must be periodically calibrated; - check the procedure of the operation to be carried out before starting, checking the electric diagram to see how the system is structured; - while maintenance operations are carried out it is necessary that: ƒ the technician knows which circuits are high voltage ƒ no resistance measures are carried out in the live circuits ƒ one hand is used to carry out operations on powered circuits ƒ the instrument terminal must be earthed before carrying out operations on powered circuits - maintenance operations can be considered concluded only when all components have been reinstalled on the unit. SAFETY MEASURES ON REFRIGERATING CIRCUITS The refrigerant used for this apparatus can be dangerous if not used correctly, and it is therefore necessary to take the following precautions when handling this substance. - Never unload, stock or use the refrigerating liquid in the presence of flames, since the combustion produces a noxious gas (phosgene) if it gets in contact with the flame. - The cooling liquid must not come into contact with the eyes; - The cooling liquid must not come into contact with the skin, if contact occurs, the wounds must be treated in the same way as frostbite; - Avoid high concentrations of cooling liquid that can cause suffocation; if this happens, the person suffocating must be evacuated from the area and artificial respiration must be provided. DANGERS DERIVING FROM GAS LEAKAGE IN CASE OF FIRE Since the machine is typically installed away from heat sources and inflammable/explosive materials, there is a very remote possibility that it may be involved in a fire. Overheating due to natural events, such as sunlight cannot raise the temperature beyond 60° C inside the refrigerating circuit, and therefore below the TS and PS set. Full observance of the machine positioning instructions given herein is highly recommended. DANGER DERIVING FROM CIRCULATING FLUIDS WITH BASE OF WATER If fluid leaks, it poses the danger of coming into contact with electric parts that are not suitably protected against contact with the fluid. Tubes inside the refrigerator unit are capable of supporting up to 6 bar pressure; the used pump can reach a pressure max. of 5 bar. If regular maintenance is not carried out on the fixing system of the tubes, fluid can leak. WHEN TO DISCONNECT THE ELECTRICAL POWER SUPPLY Disconnect the power supply immediately using the switch at the top of the power line when: - the electrical power cable is worn or damaged; - maintenance operations or repairs are being carried out to the machine; - the machine is being cleaned. SAFETY ADVANCE FOR MAINTENANCE - wear protective gloves to carry out maintenance work; - always disconnect the electrical power supply before opening the protection panels; - wait a few minutes for the internal parts of the machine to cool before opening the protection panels; - do not meddle with the faucets on the gas/water circuit; - use appropriate warning signs when the machine is off for maintenance or repairs; - only use original spare parts; - use appropriate electric and hydraulic connections.

Page 11

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

CHAPTER 4- CORRECT AND INCORRECT MACHINE USE The machine of EUROCHILLER S.r.l., is a processing water chiller. If the machine is used in a wrong way, this condition could give some damages to the work and become a serious danger for the operator.

4.1 WARNING ADVICE AGAINST DANGER AS A RESULT OF INCORRECT USE ƒ

It is absolutely forbidden to hold metal objects near protection grid of ventilator because they could tumble and make dangerous situations.

ƒ

The machine is tested before the selling.

ƒ

Only the Builder qualified operators can modify, adjust or replace all the elements that are not described in this handbook.

ƒ

For any use not foreseen or described for this machine, or for any intervention, which the user wishes to carry out on the machine, it is essential that the user contact the manufacturer for advice concerning any possible damage as a result of incorrect machine use.

ƒ

Never use antifreeze liquids and inflammable, obnoxious and polluting gases: once exhausted they will have to be eliminated in compliance with the safety regulations in force.

ƒ

The machine must not be installed in an explosive room.

Instruction, use and maintenance manual –

©02_10/02

Page 12

Model GC

Processing water chiller

CHAPTER 5- GENERAL DESCRIPTION OF THE MACHINE The machines making up the series GC, built by EUROCHILLER S.r.l., are water coolers for industrial process. The main components of the machine are the following: - The self-bearing structure made of very thick sheet, treated and varnished with anti-corrosion varnishes and epoxy powders. It can be equipped with pivoting wheels or feet. - The tank is made of INOX steel, max. seal: 1,5 bar - The pump made of INOX steel for models from GC 6 to GC 55 - The evaporator made of AISI 316 with braze welded plates. - The capacitor made of copper tubes directly connected to a group of sheets made of corrugated rigid aluminium to optimise their performance. The tubes are mechanically expanded inside the finned group. - The compressor can be rotative, with pistons or SCROLL, - The fan can be axial or centrifugal. - The air filter to collect the impurities. - The automatic by-pass for process water (for models 6 to 55). These coolers have been planned and built to guarantee both high-level performances and simplicity of use: they are equipped with a special control panel the operator will only have to use to set the production and supervision cycle. The coolers model GC, are highly automated machines and do not require the constant presence of the operator during their functioning.

Page 13

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

5.1 TABLES FOR THE CALCULATION OF THE REFRIGERATING YIELD

Model GC

Version 1.0

Revision 00

of 11-04-2001

GC Standard max air temperature = +40°C GC Standard water max temperature = +25°C GC Standard water min temperature = +5°C ( with ethylene -7°C) Supertropicalised version

Instruction, use and maintenance manual –

©02_10/02

Page 14

Model GC

Processing water chiller

5.1.1 “GC LT”TABLES FOR THE CALCULATION OF THE REFRIGERATING YIELD

Model Temp. -10°C H2O Temp. Ambient +25°C +35°C +45°C

Kw 2.8 2.07 1.3

Model Temp. -10°C H2O Temp. Ambient +25°C +35°C +45°C

Kw 4.3 3.2 2.1

Model Temp. -10°C H2O Temp. Ambient +25°C +35°C +45°C

Page 15

Kw 9 7.6 4.9

GC LT 1,5 -20°C -25°C Kw 2.1 1.8 1.2

-30°C

Kw 1.6 1.4 0.9

Kw 1.1 0.9 0.6

GC LT 3 -20°C -25°C

-30°C

Kw 3.4 2.9 2.0

Kw 2.5 2.1 1.4

GC LT 5 -20°C -25°C Kw 7.3 6.4 4.4

Kw 5.3 4.5 2.9

Kw 1.8 1.5 1.0

-30°C Kw 3.6 3.0 1.8

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

Model Temp. -10°C H2O Temp. Ambient +25°C +35°C +45°C

Kw 12.5 10 7.6

Model Temp. -10°C H2O Temp. Ambient +25°C +35°C +45°C

Kw 18.6 15 9.7

Model Temp. -10°C H2O Temp. Ambient +25°C +35°C +45°C

Kw 25.6 20.0 13.2

Model Temp. -10°C H2O Temp. Ambient +25°C +35°C +45°C

Kw 38.4 31.0 24.2

Instruction, use and maintenance manual –

GC LT 7,5 -20°C -25°C Kw 9.8 8.5 5.9

-30°C

Kw 7.2 6.2 4.0

Kw 5.1 4.2 2.5

GC LT 11 -20°C -25°C

-30°C

Kw 14.6 12.8 8.8

Kw 10.6 9.0 6.0

Kw 7.2 6.0 3.6

GC LT 15 -20°C -25°C

-30°C

Kw 20.0 17.0 12.0

Kw 14.4 12.2 8.0

Kw 10.0 8.4 5.0

GC LT 22 -20°C -25°C

-30°C

Kw 30.0 27.0 22.0 ©02_10/02

Kw 23.0 20.0 17.0

Kw 18.0 16.0 13.0 Page 16

Model GC

Processing water chiller

5.2 OPERATING PRINCIPLE 5.2.1 COOLING CIRCUIT The machine is equipped with a refrigerating circuit using a particular gas to cool down the water; please find below a list of the gases that can be used:

TYPE OF GAS R407c

Standard

R22

Upon demand

R404a

Only version LT

The gas contained in the circuit is pushed by the compressor inside the capacitor, where it releases heat. The gas becomes liquid inside the capacitor. Heat is removed from the gas and passes from a gaseous state to a liquid state. At this point the gas in a liquid form is forced towards the expansion valve and injected into the evaporator where it cools (expanding) and returns to the gaseous state. During this phase the water present in the evaporator yields heat to the cold gas. The compressor takes in the gas and the cycle recommences. In the standard version, the gas condensation takes place through an exchange of heat, by means of the air aspired by one or more fan through the condensing battery. The fan can be: • of the axial type (mod. GC-A) • or centrifuge type (mod. GC-C).

5.2.2 COOLING CIRCUIT WITH HOT GAS (OPTIONAL) The cooling circuit fitted with the HOT GAS optional varies from the standard circuit in that it regulates the temperature of the water supplied to the evaporator by means of a solenoid valve, which regulates the passage of hot gas and mixes it with the cold gas discharged from the expansion valve directed towards the evaporator. This system enables the compressor to remain switched on at all times and only stops when the heat load is very low and the temperature reaches the set-point value.

Warning: The exhausted gas must be collected separately from any other waste material, not to damage the environment: once collected, it must be eliminated by a specialised company, in compliance with the regulations in force in the country where the machine is installed.

Only and EXCLUSIVELY use the type of gas indicated on the Builder plate.

Page 17

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

REFRIGERATING CIRCUIT DIAGRAM

POS. ELEMENT 1

Compressor

2

High pressure switch

3

Condenser

4

Fan

5

Fan control (optional)

6

Gas filter

7

Liquid pilot light

8

Expansion valve

9

Evaporator

10

Low pressure switch

11

Solenoid valve *

12

Spherical cock *

* Only present in HOT GAS version Instruction, use and maintenance manual –

©02_10/02

Page 18

Model GC

Processing water chiller

5.2.3 HYDRAULIC CIRCUIT 1. Standard version: the evaporator is made of braze welded plates, insulated by made of expanded ball neoprene. The water pump can suck from an internal tank and pushes the water towards the process The water pump sucks the water from the internal tank and pushes it through the process before returning through the evaporator to the chiller and into the tank once more. A by-pass compensates for any lack in water capacity to the evaporator.

Figure A Paragraph 5.2.3 _ Hydraulic diagram for standard version fitted with automatic loading accessories.

POS

ELEMENT

POS

ELEMENT

1

Pump

9

Expansion tank (optional) *

2

Temperature probe

10

Air valve *

3

Pressure gauge

11

Float

12

Safety valve *

13

Discharge for open tank **

4 5

By-pass valve (only for versions from GC 9 to GC 55) Cock (only for versions from GC 9 to GC 55)

6

Evaporator

14

Tank

7

Solenoid valve *

15

Pressure differential automatic device ***

8

Manual load

16

Flow switch ****

* ** *** ****

Only present in automatic water filling versions. Only present for manual water filling. (standard version) Only present for versions from GC 2 to GC 6 (optional) Only present for versions from GC 9 to GC 55 (optional)

Page 19

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

2. Version for external tank : the evaporator is composed of insulated braze welded plates with closed cell expanded neoprene. The pump forces the water sucked from an EXTERNAL tank into the plate evaporator, from which it then returns cooled.

Figure B Paragraph 5.2.3 _ Hydraulics diagram for external tank version

POS

ELEMENT

1

Pump

2

Probe

3

Pressure gauge

4

Evaporator

5

Water outlet

6

Water inlet

7

Flow switch

8

Y Filter

Instruction, use and maintenance manual –

©02_10/02

Page 20

Model GC

Processing water chiller

CHAPTER 6- MOVING AND TRANSPORTING THE MACHINE 6.1 TRANSPORTING THE MACHINE The transit area, the machine is going to be moved over must first be inspected, to identify and eliminate any possible dangers. Lifting the machine or parts of it must be carried out be qualified personnel; Use suitable pallet transporter, fork lift or crane to move the packaged machine. Sling, lifting and transportation devices must take the volume, weight and shape of the load to be moved into account

Figure paragraph 6.1

6.2 WEIGHTS

Attention:

Model GC-A (Axial ventilation)

Weight (Kg)

3 5 7.5 11 15 22

139 215 279 302 342 390

No one except for the operators responsible for the machine handling will have to pass through or stop near the handling area of the machine elements while the operators in charge of such operations will have to stay at a suitable distance, not to be hit by the elements hanging in the air. While handling the machine elements, a second operator must be present besides the operator driving the lift truck or the crane, to check that the distance to be covered is free from any obstacle and that during the machine handling it does not intercept anyone or anything. Only use chains or nylon belts duly dimensioned to lift a weight equal or superior to the sum of the element and belts weights.

Page 21

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

CHAPTER 7- MACHINE INSTALLATION 7.1 MAX MACHINE SIZE

Figure paragraph 7.1 GC-A dimensions

MODEL GC GC LT 3 GC LT 5 GC LT 7.5 GC LT 11 GC LT 15 GC LT 22

Height (H) GC-A 1170 1416 1707 1707 1707 1707

Instruction, use and maintenance manual –

Figure paragraph 7.1 GC-C dimensions

Lenght (L) GC-A 702 922 1222 1222 1222 1222

©02_10/02

Depth (P) GC-A 770 808 908 908 908 908

Page 22

Model GC

Processing water chiller

7.2 AREA TO BE LEFT FREE AROUND THE MACHINE

1 00 0

The refrigerator unit must be positioned according to the minimum space requirements indicated in the figure. The surrounding space allows correct use of the unit and maintenance operations to be carried out.

1000

1 5 00

1000

Figure paragraph 7.2

Attention:

It is advisable to mark with varnish or adhesive tape the distance to be observed by the machine elements on the floor, so that : - the limited area is free and is not occupied by other machines or objects; - no one except for the machine operator stays or passes through that area when the machine is running.

Do not position the machine near sources of heat or containers holding inflammable and/or explosive liquids or materials.

Failure to respect minimum distances may require the machine to be disconnected during routine and occasional maintenance operations.

Page 23

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

7.3 POSITIONING FOR AIR CANALIZATION

AXIAL OR CENTRIFUGAL VENTILATION Internal location with no air pipe. Respect the minimum distances indicated.

AXIAL OR CENTRIFUGAL VENTILATION External location with no air pipe. Respect the minimum distances indicated

Instruction, use and maintenance manual –

AXIAL OR CENTRIFUGAL VENTILATION IT IS FORBIDDEN TO POSITION THE MACHINE OUTDOORS WITHOUT SUITABLE SHELTER

AXIAL OR CENTRIFUGAL VENTILATION. Internal location with no air pipe. Respect the minimum distances indicated

©02_10/02

Page 24

Model GC

Processing water chiller

CENTRIFUGAL VENTILATION External location with air pipe over or under a roof Respect the maximum distances indicated

CENTRIFUGAL VENTILATION Internal location with air pipe over or under a roof Respect the maximum distances indicated

Attention: In case of canalization (exclusively for GCC versions), it is necessary to eliminate the “FLAP” located overhead the centrifugal fan, as indicated in the figure below.

Page 25

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

CHAPTER 8- ASSEMBLAGE AND PREPARATION OF THE MACHINE TO WORK 8.1 PRELIMINARY CONTROL CHECKS Upon receipt of the machine, it is advisable to check all the elements composing it. Please find below a brief list of the elements to be checked: 1. Check that the machine completely assembled 2. Control the presence of possible accessories and the option required 3. Control that there are all the mechanic protection

8.2 CONTROL CHECK ON ANY DAMAGE THE MACHINE MAY HAVE SUFFERED DURING TRANSPORT In order to check whether the machine has been subject to any damage during transport, check all protruding machine parts as described above: • The control panel with the relevant control organs, • the mechanic safety devices. If any of the machine packing has been damaged, proceed as follows: ‰

Easily recognizable damage on exterior or on machine parts: these must be signalled immediately after delivery to the transport company, and confirmed in writing by the transporter.

‰

Damage not immediately recognizable: This must be declared to the transport company within the period prescribed by law.

‰

Serious damage: All damage must be assessed by a qualified technician charged by the transport company or the insurance company.

Attention: Any complaint concerning a possible lack in the material supplied with the machine must be notified within 10 days upon receipt.

Instruction, use and maintenance manual –

©02_10/02

Page 26

Model GC

Processing water chiller

8.3 POWER SUPPLY CONNECTION The electric board, insulated and built in compliance with the regulations in force, is contained in the machine and can be reached by removing the control panel present on the front side. Use a quality cable whose section complies with the refrigerator rating (see table in Chap. 8.3.1). Before use, check that the electric cable is undamaged. Position the cable in the electric board through the special input, until reaching the connection points on the main switch body A. Connect L1 – L2 – L3 to the main switch. Connect the external end of the electric cable to the main supply line.

A

Figure 1 paragraph 8.3

Warning: The machine models 25-35-45-55 are equipped with a device controlling the correct sequence of the supply phases. If the device (K/F) cuts off the power supply, it is necessary to exchange 2 wires of the cable connected to the main switch.

The electric and earth connection must be carried out by qualified and skilled operators according to the regulations in force.

If a resistance is present for the compressor oil casing, it is necessary to connect a preferential line to the “Q/R” thermal-magnetic switch.

Page 27

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

8.3.1 POWER SUPPLY CONNECTION Electrical data – Monophase version 200V 2605 3170 1,5 9,14 1,5 20 A

208V 2605 3170 8,53 8,71 1,5 20 A

2605 50 HZ 3170 60 HZ 8,95 50 HZ Total A 10,04 60 HZ Recommended cable section (PVC) 1,5 Recommended protection (D/MA Curve) 20 A

2605 3170 8,53 9,61 1,5 20 A

1405 1720 7,85 8,82 1,5 20 A

2605 3170 7,43 8,4 1,5 20 A

2605 / 6,63 7,39 1,5 20 A

2630 50 HZ 3240 60 HZ 11,37 50 HZ Total A 13,35 60 HZ Recommended cable section (PVC) 2,5 Recommended protection (D/MA Curve) 25 A

2630 3240 10,94 12,8 2,5 25 A

1930 2290 9,98 11,73 2,5 25 A

2630 3240 9,43 11,16 2,5 25 A

2630 3240 8,42 9,92 1,5 20 A

2995 50 HZ 3655 60 HZ 18,2 50 HZ Total A 22,65 60 HZ Recommended cable section (PVC) 4 Recommended protection (D/MA Curve) 32 A

2995 3655 17,36 21,7 4 32 A

2995 3655 16 19,9 4 25 A

2995 3655 14,1 19 4 25 A

2995 3655 13,4 16,9 2,5 25 A

50 HZ Total W 60 HZ 50 HZ Total A 60 HZ Recommended cable section (PVC) Recommended protection (D/MA Curve)

Total W

Total W

Total W

220/230V 240V 1385 2685 1370 3170 7,05 7,43 7,22 7,4 1,5 1,5 20 A 20 A

270V 2685 3170 6,63 6,59 1,5 20 A

GC A2

GC A3

GC A4

GC A6

N.B.: The values shown refer to standard versions.

Instruction, use and maintenance manual –

©02_10/02

Page 28

Model GC

Processing water chiller

Electrical data – Tri-phase version

200V 4450 50 HZ Total W 4930 60 HZ 17 50 HZ Total A 18,7 60 HZ Recommended cable section (PVC) 2,5 Recommended protection (D/MA Curve) 25 A

208V 4450 4930 16,4 18 2,5 25 A

50 HZ 60 HZ 50 HZ Total A 60 HZ Recommended cable section (PVC) Recommended protection (D/MA Curve)

6030 7280 22,9 26,9 4 32 A

6030 7280 22,1 25,9 4 32 A

50 HZ 60 HZ 50 HZ Total A 60 HZ Recommended cable section (PVC) Recommended protection (D/MA Curve)

7330 7280 27,5 26,7 4 32 A

50 HZ 60 HZ 50 HZ Total A 60 HZ Recommended cable section (PVC) Recommended protection (D/MA Curve)

8030 8880 29,9 32,5 10 40 A

220/230 380/400 V V 415 V 4450 4450 4450 4930 4930 / 15,4 8,8 8,5 17 9,45 / 2,5 1,5 1,5 16 A 16 A 16 A

440 V 4450 4930 7,96 8,56 1,5 16 A

460/480 V / 4930 / 7,85 GC A9 1,5 16 A

6030 7280 20,1 23,6 4 25 A

6030 7280 11,55 14,1 2,5 16 A

6030 / 11,08 / 1,5 16 A

6030 7280 10,52 12,5 1,5 16 A

/ 7280 / 11,75 GC A12 1,5 16 A

7330 7280 24,8 24,1 4 25 A

7330 7280 13,9 13,5 2,5 16 A

7330 / 13,3 / 1,5 16 A

7330 7280 12,6 12,4 1,5 16 A

/ 7280 / 11,7 GC A15 1,5 16 A

8030 8880 28,8 31,2 10 40 A

8030 8880 27,0 29,4 6 32 A

8030 8880 15,1 16,4 2,5 25 A

8030 / 14,5 / 2,5 25 A

8030 8880 13,7 15,0 2,5 25 A

/ 8880 / 14,2 2,5 25 A

10050 50 HZ 9450 60 HZ 36,7 50 HZ Total A 34,5 60 HZ Recommended cable section (PVC) 10 Recommended protection (D/MA Curve) 50 A

10050 9450 35,0 33,2 10 50 A

10050 9450 33,4 31,4 10 40 A

10050 9450 18,4 17,3 4 25 A

10050 / 17,7 / 4 25 A

10050 9450 16,7 15,7 2,5 25 A

/ 9450 / 15,0 2,5 25 A

10050 50 HZ 11050 60 HZ 36,7 50 HZ Total A 39,8 60 HZ Recommended cable section (PVC) 10 Recommended protection (D/MA Curve) 50 A

10050 11050 35,3 38,3 10 50 A

10050 11050 33,4 36,2 10 40 A

10050 11050 18,4 19,9 4 25 A

10050 / 17,7 / 4 25 A

10050 11050 16,7 18,1 2,5 25 A

/ 11050 / 17,3 GC A25 2,5 25 A

Total W

Total W

Total W

Total W

Total W

7330 7280 26,5 25,7 4 32 A

GC A18

GC A23

N.B.: For centrifuge versions refer to the identification plate on the machine.

Page 29

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

Electrical data – Tri-phase version 13900 50 HZ 15100 60 HZ 41,3 50 HZ Total A 42,3 60 HZ Recommended cable section (PVC) 16 Recommended protection (D/MA Curve) 63 A

13900 15100 39,7 40,7 16 63 A

13900 15100 37,5 38,5 10 63 A

13900 15100 20,7 21,2 6 32 A

13900 / 19,9 / 4 32 A

13900 15100 18,8 19,2 4 32 A

/ 15100 / 18,4 GC A35 4 25 A

18400 50 HZ 17900 60 HZ 66,8 50 HZ Total A 62,1 60 HZ Recommended cable section (PVC) 25 Recommended protection (D/MA Curve) 80 A

18400 17900 64,2 59,7 25 80 A

18400 17900 60,7 56,5 25 80 A

18400 17900 33,4 31,1 10 40 A

18400 / 32,2 / 10 40 A

18400 17900 30,4 28,2 10 40 A

/ 17900 / 27,0 GC A45 6 40 A

23900 50 HZ 23900 60 HZ 84,8 50 HZ Total A 80,5 60 HZ Recommended cable section (PVC) 35 Recommended protection (D/MA Curve) 100 A

23900 23900 81,5 77,4 35 100 A

23900 23900 77,1 73,2 35 100 A

23900 23900 42,4 40,3 16 63 A

23900 / 40,9 / 16 63 A

23900 23900 38,5 36,6 10 63 A

/ 23900 / 35,0 GC A55 10 63 A

Total W

Total W

Total W

N.B.: For centrifuge versions refer to the identification plate on the machine. The values shown refer to standard versions.

Instruction, use and maintenance manual –

©02_10/02

Page 30

Model GC

Processing water chiller

GC LT Electrical data – Tri-phase version + neutral 50 HZ 60 HZ 50 HZ Total A 60 HZ Recommended cable section (PVC) Recommended protection (D/MA Curve) Total W

50 HZ 60 HZ 50 HZ Total A 60 HZ Recommended cable section (PVC) Recommended protection (D/MA Curve) Total W

GC LT 3

8100

8100

8100

8100

8100

8100

8100

33

32

29,5

17

16

15

14

12560

12560

12560

12560

12560

40.5

23.3

22.46

21.2

19.8

12560 12560 50 HZ 60 HZ 46.6 44.8 50 HZ Total A 60 HZ Recommended cable section (PVC) Recommended protection (D/MA Curve) Total W

20900 50 HZ 60 HZ 74 50 HZ Total A 60 HZ Recommended cable section (PVC) Recommended protection (D/MA Curve)

20900

20900

20900

20900

20900

20900

71

66

38

35,5

33,5

31,5

27600 50 HZ 60 HZ 101,5 50 HZ Total A 60 HZ Recommended cable section (PVC) Recommended protection (D/MA Curve)

27600

27600

27600

27600

27600

27600

97,5

90

52

49

46

43

Total W

Total W

Page 31

Instruction, use and maintenance manual –

GC LT 5

GC LT 7.5

GC LT 15

GC LT 22

©02_10/02

Model GC

Processing water chiller

8.4 HYDRAULIC CONNECTION The machine can be hydraulically connected through rigid or flexible tubes to be connected to the rigid tubes on the machine right side: The rated pressure the tubes and line unions must withstand must be higher than 6 bar. If the operating water is sent to various operating machines, it is possible to assemble a multy-way manifold on the connection tube of the refrigerator. A closing cock must be assembled on the inlet and outlet unions of the refrigerator. For a correct functioning, it is advisable to use a filter at the entry of the refrigerator to keep all the system impurities. N.B.: The filter must have a diameter at least the same size as the diameter of the refrigerator connection (the Manufacturer recommends the use of a filter one size lager than the inlet section) with a degree of filtration of at least 200 microns.

Fig.1 Par.8.4 Modelli dal GC2 al GC4

Fig. 2 Par.8.4 Modello GC LT 5-22

Fig. 3 Par.8.4 Modelli dal GC6 al GC55 e GC LT 15

Warning: To guarantee an adequate water supply, the internal diameter of the tube must be at least the same as the diameter of the connection on the machine.

When assembling and tightening external tubes, care must be taken not to exert excess pressure in order to avoid damage to the internal tubes.

Instruction, use and maintenance manual –

©02_10/02

Page 32

Model GC

Processing water chiller

8.4.1 WATER PIPES CONNECTION Each connection, usually found at the rear of the machine, has a plate with a symbol that refers to the type of connection required.

PROCESS WATER INLET (red color) Connect the process return pipe that runs from the process machine. ALL VERSION PROCESS WATER OUTLET (blue color) Connect the process water supply pipe that runs to the process machine.

MANUAL WATER LOAD Only manual load – don’t put the tank under sous pression

UPON DEMAND

Warning:

AUTOMATIC WATER LOAD Connect the automatic water supply pipe that runs from the water mains. A filter must be fitted at a point before the water enters the system.

FAILING ANY PRIOR TO THE ORDER, THE MACHINES ARE SUPPLIED WITH A MANUAL LOADING DEVICE. IT IS STRICTLY FORBIDDEN TO PROVIDE THE MACHINE WITH AN AUTOMATIC LOADING DEVICE IF NOT AUTHORISED BY THE MANUFACTURER. The pressure value in the water tank must never exceed the atmospheric pressure value.

Page 33

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

8.4.2 IN-OUT CONNECTION SIZES OPERATING WATER

OPERATING WATER

AUTOMATIC WATER

MANUAL WATER

INLET

OUTLET

LOAD

LOAD

FILTER DIAMETER

3 LT

1”

1”

½”

1”

2”

5 LT

1”¼

1”¼

½”

1”

2”

7.5 LT

1”¼

1”¼

½”

1”

2”

11 LT

1”¼

1”¼

½”

1”

2”

15 LT

1”¼

1”¼

½”

1”

2”

22 LT

1”¼

1”¼

½”

1”

2”

MODEL GC

Instruction, use and maintenance manual –

©02_10/02

Page 34

Model GC

Processing water chiller

8.4.3 HYDRAULIC ATTACKS POSITION GC-LT

Figure paragraph 8.4.3

Page 35

MODEL GC

f

g

h

l

GC LT 3

180

920

755

440

GC LT 5

300

1145

960

550

GC LT 7.5

236

1333

1018

560

GC LT 11

236

1333

1018

560

GC LT 15

160

1360

1075

660

GC LT 22

380

1360

1180

620

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

8.5 USE OF ANTIFREEZE IN THE PROCESS WATER The machine can operate without antifreeze up to a preset temperature of no less than +5°C. In case of temperatures lower than +5°C, it is necessary to use an anti-freeze agent. Even at ambient temperatures above 5°C use of antifreeze is advisable as it confers better flow properties on the water in the system. Check that the antifreeze used does not contain substances that may corrode the basic materials used to manufacture the machine (steel, copper and aluminium). The Builder recommends the use of the following antifreeze liquid KLEENTEK CL3295 (containing Antifreeze agent). DOSES OF ANTIFREEZING AGENT TO BE USED ACCORDING TO THE TEMPERATURE OF THE OPERATING WATER PROCESS WATER TEMPERATURE

+5° C

0° C

-5° C

-10°C

-20°C

-30°C

Percentage of antifreeze

10%

20%

25%

30%

40%

45%

DOSES OF ANTIFREEZING AGENT TO THE USED ACCORDING TO THE ROOM TEMPERATURE ENVIRONMENTAL TEMPERATURE

+5° C

0° C

-5° C

-10°C

-15°C

Percentage of antifreeze

-

15%

20%

25%

30%

8.5.1 % GLYCOL YIELD DIAGRAM – EVAPORATOR POWER

% Glycol

% Evaporator power yield Figure paragraph 8.5.1

Example: Percentage of anti-freezing agent in the circuit = 40% Reduction percentage of the chiller power = -15%

Instruction, use and maintenance manual –

©02_10/02

Page 36

Model GC

Processing water chiller

8.5.2 RATIO BETWEEN THE COOLING AND CONCENTRATION POINTS OF WATER SOLUTIONS IN GLYCOL

Figure paragraph 8.5.2

Example: Required water temperature = -20°C Percentage of required glycol = 38%

8.5.3 ANTIFREEZE LIQUID FILLING SYSTEM FILL-CHILL (OPTIONAL, FOR VERSION GC 9 TO GC 55 ONLY) Upon demand, the machine can be equipped with a device for the automatic filling of antifreeze liquid: it is made up of a tank called FILL-CHILL that must be connected to the machine by means of the rubber pipe supplied with the refrigerator automatic filling connection. The filling system is completely automatic and is equipped with an anti-flooding device, which stops the loading activity in the presence of water leakage from the machine. FILL-CHILL 120 = Cap. 120 Liter Figure paragraph 8.5.3

Attention: The exhausted antifreeze liquid will have to be collected separately from any other waste material not to damage the surrounding environment; once collected it will have to be eliminated by a specialised company in compliance with the Regulations in force in the country where the machine is installed.

Make use of monoethylene or ethylene type glycol exclusively. The use of propylene glycol will damage the mechanical seals on the pumps beyond repair. Only use the type of antifreeze agent recommended by the Builder : in case a different type is used, the user must first check its physical and chemical features (included in the documentation attached to the element)and check its similarities with the supplied one: in case they are not similar, it is necessary to immediately contact the Builder about the product use.

Page 37

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

8.5.4 WATER CONTENT IN THE TANK MOD. GC

TANK CAPACITY (LT.)

GC LT 3 GC LT 5 GC LT 7.5 GC LT 15 GC LT 22

35.0 35.0 35.0 92.0 92.0

To know the exact quantity of anti-freezing agent, it is necessary to know the exact content in the pipeline and add it to the quantity of the tank capacity.

8.5.5 WATER PIPES CAPACITY Ø PIPES

NOMINAL DIAMETER

Water contained liters/meters

½”

15

0.218

¾”

20

0.382

1”

25

0.608

1”¼

32

1.046

1”½

40

1.412

Warning:

The water content in the distribution line should also be considered in order to calculate the correct percentage of glycol to be used.

Instruction, use and maintenance manual –

©02_10/02

Page 38

Model GC

Processing water chiller

CHAPTER 9- CONTROL PANEL 9.1 CONTROL PANEL FOR MODELS GC 2 TO GC 6

Figure paragraph 9.1

LED

FUNCTION

LED

FUNCTION

Low gas pressure alarm

Interblock alarm

High gas pressure alarm

Water level alarm

Electric alarm

Power

9.2 DISPLAY AND FUNCTIONS

3

4 6

2

5

1 KEY

FUNCTION

LED

Used for the set point setting and to program the functioning parameters (re. 1 fig. 9.2)

n

Used to decrease the values or to select Parameters (re. 2 fig. 9.2) Used to increase the values or to select parameters (re. 3 fig. 9.2)

Page 39

Led SET

Led OUT

Led AL

Figure paragraph 9.2

FUNCTION Signalize the set point programming mode (on) or the parameters programming mode (flashing) (re. 4 fig. 9.2) Signalize when the output is on (on), off (off) or inhibited (flashing) (re. 5 fig. 9.2) Signalize the alarm state on, off or silented (flashing) (re. 6 fig. 9.2)

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

9.2.1 SET POINT PROGRAMMING Press key

then release it, led SET will flash and the SET value will be shown on display.

To modify press key

so as to increase value or

so as to decrease it.

These keys count one digit at a time but if the keys are pressed for over one second the value increases or decreases fast and after two seconds the speed increases even more, so as to reach the desired value immediately. The outgoing from the Set programming mode occurs automatically by not pressing any key for about 5 seconds, thus the temperature process value will again be displayed.

9.3 CONTROL PANEL FOR MODELS GC 9 TO GC 55

Figure chapter 9.3

LED

FUNCTION

LED

FUNCTION

H1 – High water temperature alarm

H10 – Fan alarm

H2 – Low water temperature alarm

H11 – Compressor running

H3 – High gas pressure alarm

H12 – Ventilation running

H4 – Low gas pressure alarm

H13 – Pump 1 running

H5 – Compressor alarm

H14 – Pump 2 running (OPTIONAL)

H6 – Interblock alarm

H15 – Power

H7 – Pump alarm

ON-OFF Chiller

H8 – Flowswitch alarm

Alarm reset

H9 – Water level alarm

Parameters setting

Instruction, use and maintenance manual –

©02_10/02

Page 40

Model GC

Processing water chiller

9.4 DISPLAY AND FUNCTIONS

Figure paragraph 9.4

KEY

FUNCTION

KEY

FUNCTION

Visualization of outlet water temperature (°C) PRECISION: +/- 0.1°C

Confirm setting

Increase value

Decrease value

9.4.1 MODIFYNG THE TEMPERATURE SETTING 1. Press the

.

key.

2. The display shows the temperature setting

3. Press the

4.

Press the

Page 41

key to increase or the

key decrease the value.

key to memorise the temperature setting.

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

9.4.2 RESETTING THE ALARM Once the alarm has been eliminated:

1. Press

to stop the sound signal of alarm.

2. Refer to the table of paragraph 9.3 to identify the type of alarm.

3. Refer to chapter 13 Troubleshooting to find the solution

4. Once the problem has been identified and solved, press

.

9.4.3 MODIFYNG THE CONFIGURATION PARAMETERS 1.

Press the

key for more than 3 seconds.

2.

The display visualises the parameter to be modified (for example P01)

3.

Find the parameter to be modified with the

4.

Press the

key to display the parameter to be modified.

5.

Press the

key to increase or the

6.

Press the

key to memorise the new parameter value.

7.

Repeat from point 3. To point 6. To modify the other parameters.

8.

Press the

and

key .

key decrease the value.

key to exit.

Instruction, use and maintenance manual –

©02_10/02

Page 42

Model GC

Processing water chiller

CHAPTER 10- MACHINE USE 10.1 START-UP AND WORK CYCLE(FOR MODELS GC 9 TO GC 55 VERSION EXCLUDED GC-E) 1. Turn on the power supply to the refrigerator unit by turning the power switch to position 1.

Do not carry out this operations on the GC – E

2. Check that the light

is on.

3. Wait for the tank to fill with water; after 2 minutes ( parameter value P 23) the luminous and acoustic signals WATER FILLING ALARM Press the

are activated.

key to stop the acoustic alarm.

The WATER FILLING ALARM

stays on; the

flashing light indicates that the water filling

is completed and therefore the signal can be switched off WATER FILLING ALARM pressing the

4. Press the

key .

key to start up the refrigerator unit.

5. Check to make certain the pump rotates clockwise

.

6. Check to make certain the fan rotates in the direction indicated by the arrow.

Attention: If there is a fault in machine functioning, the machine will stop automatically signalling the fault on the control panel.

Page 43

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

10.2 UNFORESEEN STOPPING DUE TO A POWER CUT In case the machine stops because of a temporary lack of power, the machine will not start running again once the power supply is restored. If the machine supervisor wants that the machine starts automatically once the power supply is restored, he must set the parameter P7 autostart = 1 (only for models 9 to 55). This is poses no danger to people in the vicinity of the machine.

10.3 STOPPING THE MACHINE MANUALLY If the daily or weekly breaks are short, the refrigerator unit can be stopped with the

key.

If however, the refrigerator unit will remain inactive for long periods (holiday periods or plant stoppages), it is advisable to turn off the power supply by turning the power switch to position 0. In models 2 to 6, act on the main switch. Attention: The protection systems on the machine have been provided by the manufacturer to protect the operator during his work on the machine.

If the refrigerator is left switched off for long periods, the danger of freezing due to negative room temperature should be considered. Empty system to avoid this occurring.

10.4 RESET THERMOMAGNETIC PROTECTION (FOR VERSION GC 9 TO GC 55 ONLY) 1.

Turn the main switch to “0” to open the electric board.

2. Once the control panel closing the electric board has been removed, identify the magnetothermal switch according to the electric diagram supplied with the machine

3. Turn the switch to “1” , to start it again.

4. Close the control panel, turn the main switch to “1” and restart the machine.

Figure paragraph 10.4

Attention: Before restarting the machine, check the cause that has stopped it.

Instruction, use and maintenance manual –

©02_10/02

Page 44

Model GC

Processing water chiller

CHAPTER 11- MACHINE MAINTENANCE I GC series refrigerators function autonomously and continuously and are therefore not fitted with fixed control or command positions. The machine is designed to function continuously for 24 hours per day. This rhythm of work can only be maintained if preventative programmed maintenance measures are adopted. Adequate maintenance is essential for long lasting machine function and optimum performance. The machine must therefore be inspected and receive routine maintenance in order to maintain the technical, productive and safety conditions established by the Manufacturer over time. Attention:

Any extraordinary modification and maintenance different from the maintenance and replacement interventions described in this chapter must not be carried out without first contacting EUROCHILLER S.r.l. Company, who will decide whether to give their authorisation or not according to each specific case, or will propose the intervention of one of their qualified engineers. Please note that wrong interventions can cause anomalous functioning conditions, cause damages to the machine and be a source of dangers for the personnel using the machine. The Builder is not to be held responsible for the dangers that may derive from the above-mentioned operations. All maintenance, adjustment setting and replacement operations described in this Instruction manual must be carried out ONLY AFTER having switched off the machine and disconnected the machine plug from the main line socket.

11.1 PROGRAMMED MAINTENANCE To maintain in operation the refrigerator in correct way, perform the operations of maintenance as suitable following: PERIODICALLY

OPERATION OF MAINTENANCE

WEEKLY

Cleaning filters panel.

MONTLY

Clean the finned group capacitor using compressed air blown from the inside to the outside.

ACCORDING TO USE

Clean the plate evaporator (this operation must be carried out only by skilled operators).

To shut all the screw of the electric terminals. (AFTER 1 WEEK Check that all screws are properly tightened on all mechanical parts AND ANNUALLY) A complete maintenance programme can be obtained from Eurochiller Srl technical assistance department.

Page 45

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

11.2 MAINTENANCE OPERATIONS FOR AXIAL FANS (VER. GC-A)

1. The fixing of the fan protection grid must be checked periodically(the screws must be shuted).

2. Clean the ventilator blades to eliminate any dust deposit.

Figure paragraph 11.2

11.3 CLEANING THE FILTERS PANEL 1. The filter panels must be cleaned periodically as excessive build up of dust can impede air circulation inside the refrigerator and therefore compromise functioning. 2. Remove the panel, situated on the rear side, upwards.

3. Clean the panels with a jet of compressed air or with flowing water.

4. The panels must be periodically replaced (depending on the environmental conditions where the refrigerator unit is installed) to guarantee complete filtering.

Figure paragraph 11.3

5. It is advisable to blow compressed air into the capacitor from the inside of the refrigerator to the outside every month without folding the aluminium winglets of the capacitor. N.B.: In this case, it is necessary to de-energise the machine and open a panel for an easier cleaning.

Instruction, use and maintenance manual –

©02_10/02

Page 46

Model GC

Processing water chiller

11.4.2 RESET OF THE GAS HIGH PRESSURE GAUGE (FOR VERSION GC 9 TO GC 55 ONLY) 1. Remove the protection panels

2. Identify the pressure switch with the identification table 3. Reactivate the pressure switch by manually moving the push button (green) in the direction indicated by the arrow. 4. Replace the protection panel and turn the refrigerator unit on. Figure paragraph 11.4.2

GAS CIRCUIT PRESSURE SWITCH IDENTIFICATION TABLE FFF

REFERENCE TO FUNCTION

PRA 1

Gas circuit high pressure manostat

PRB 1

Gas circuit low pressure manostat

N.B.: The refrigerator cannot run if the panels have been removed. Attention:

Before restarting the gas circuit high pressure gauge, it is necessary to check the cause that has stopped it.

Page 47

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

11.4 MAINTENANCE ON-OFF LEVEL SWITCHES In case highly encrusting liquids are used, it is advisable to periodically inspect and descale the slide bar and the float, if necessary. If such problem occurs too often, use a filter with a higher protection.

11.5 MAINTENANCE PUMPS When the pump is not used, empty it completely if freezing may be expected. Before restarting the unit, check that the shaft is not jammed and fill the pump casing completely with liquid. It is advisable to use a little quantity of anti-freezing agent to keep the most delicate part of the pump greased.

11.6 MAINTENANCE AN REGULATING DIFFERENTIAL BY-PASS VALVE (FOR VERSIONS GC 9 TO GC 55 ONLY) The differential by-pass valve is positioned between the flow and return piping. This device does not require a particular maintenance. To adjust the liquid flow among the pipes, turn the knob to the desired value of the graduated scale (values indicating the difference metres of pressure between the inlet and outlet): • The value 6 indicates that the valve is closed (more water passes). • The value 1 indicates that the valve is opened (less water passes).

11.7 AMOUNT OF COOLANT. TYPE OF OIL. Only the Manufacturer’s qualified staff shall carry out gas/oil filling activities.

COOLANT AMOUNT INSIDE THE REFRIGERATING

TYPE OF OIL RELATIVE TO GAS AND

CIRCUIT

COMPRESSOR TYPES

MODEL

COOLANT KILOS (R404A)

GC LT 3 GC LT 5 GC LT 7.5 GC LT 11 GC LT 15 GC LT 22

2 4 6 6.5 6.5 7

TYPE GAS

PISTON/SCREW COMPRESSOR

SCROLL COMPRESSOR

POLYOLESTER GAS POLYOLESTER OIL ISO32 R407c Maneurop 160PZ Maneurop 160PZ

GAS R22

HCFC Mineral Maneurop White oil 160P

HCFC Mineral Maneurop White oil 160P

11.9 CLEANING THE CONTROL INSTRUMENTS (PERFORM WITH MACHINE SWITCHED OFF) The instrument should be cleaned with a slightly damp, non-abrasive cloth that does not contain solvents.

Instruction, use and maintenance manual –

©02_10/02

Page 48

Model GC

Processing water chiller

CHAPTER 12- MODIFYNG THE PROTECTED PARAMETER (FOR VERSIONS GC 9 TO GC 55 ONLY) Attention: Any modification to the parameters contained in this chapter must be ONLY carried out by the machine operator or by the Builder's qualified engineer. Please note that any wrong intervention may cause an anomalous functioning condition, damage the machine and be a source of dangers for the operators using it.

1. Turn the power switch in position 0.

2. Turn the power switch in position 1 and hold it down

3. Find the parameter to modify with the

and

.

.

4. Press the

key to display the parameter to be modified.

5. Press the

key to increase or the

6. Press the

key to memorise the new parameter values.

7. At the end of the operation press

Page 49

key to decrease the value.

.

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

12.1 GC LT PROGRAMME PARAMETERS PAR

DESCRIPTION

MIN

MAX

GC 9-55

UNIT

P1

SET POINT minimum limit

-30

40

10

Celsius

P2

SET POINT minimum limit

-30

40

28

Celsius

NO

P3

Compressors starting minimum time

0

180

60

Seconds

YES

P4

Compressors stop minimum time

0

180

10

Seconds

YES

P5

Minimum time between the start up of one step and the next (For fixed switch off 10 sec.)

Seconds

YES

P6

Free

P7

15

NO

0

180

Autostart (yes=1/no=0)

0

3

0

Flag

NO

P8

Minimum alarm delay

0

90

5

Seconds

YES

P9

Flow switch alarm delay

0

120

30

Seconds

YES

P 10

External inter-blocks configuration 1=block 2=Oil diff.

0

2

*

Flag

YES

P 11

Circuits present

1

3

1

Number

YES

P 12

Pumps present

1

2

1

Number

YES

P 13

Regulation band

1

5

2

Celsius

NO

P 14

Part-winding duration

0

60

30

s./10

YES

P 15

Presence of hot gas valve

0

1

*

Flag

YES

P 16

Fans present

0

5

1

Number

YES

P 17

High temperature alarm threshold

10

40

30

Celsius

NO

P 18

High water temperature alarm delay

1

20

3

Minutes

NO

P 19

Low temperature alarm threshold

P 20

Low temperature delay

P 21

Water loading minimum time

P 22

Water filling delay

P 23

Water filling time out

P 24

Operation delay of the 1 ventilator and following.

P 25

Free

P 26

Thousands of hours compressor 1

P 27

Hours of compressor1

P 28

Thousands of hours compressor 2

P 29

Hours of compressor 2

P 30

Thousands of hours compressor 3

P 31

Hours of compressor 3

P 32

Thousands of hours pump 1

P 33

Hours of pump 1

P 34

Thousands of hours pump 2

P 35

Hours of pump 2

P 36

Probe 2 offset

P 37

10

st

YES

-40

20

*

Celsius

NO

0

250

60

Seconds

NO

0

60

1

Seconds

YES

0

10

2

Seconds

YES

0

120

120

Seconds

YES

0

10

1

Seconds

YES

0 0

YES

250

0

h. x 1000

0

999

0

Hours

0

250

0

h. x 1000

0

999

0

Hours

0

250

0

h. x 1000

0

999

0

Hours

0

250

0

h. x 1000

0

999

0

Hours

0

250

0

h. x 1000

0

999

0

Hours

-50

50

0

1/10°C

Water level alarm configuration (1=antiflooding)

0

1

0

Flag

NO

P 38

Interblocks locking mode

0

1

0

Flag

YES

P 39

Antifreeze pump set

0

5

3

°C

YES

P 40

Antifreeze resistances set

0

5

5

°C

YES

P 41

Antifreeze configuration

0

2

**

Flag

YES

P 42

Probe 2 presence

0

1

***

Flag

YES

P 43

PROBE 2 OFFSET

-50

+50

0

1/10°C

YES

YES

*P10 External inter-blocks configuration: 0 = GC 1,5÷11 1 = GC 15÷22 *P15 Presence of hot gas valve:0 = Without optional 1 = With op *P19 Low temperature alarm threshold: -34 = GC LT -7 = GC BT **P41 Antifreeze configuration: 0 = Without optional 1 = Pump start only 2 = Pump start + resistance ***P42 Probe 2 presence: 0 = Without optional 1 = With optional

Instruction, use and maintenance manual –

©02_10/02

Page 50

Model GC

Processing water chiller

12.2 IN / OUT LIST The two tables below indicate the inputs and outputs of the electronic cards. To visualise the data of the CONTENT columns, the operator will have to follow the instructions in Chapter 12 MODIFICATION OF THE PROTECTED PARAMETERS: the programming parameters will be displayed at the end of the list (exactly after the parameter P43). INDIEX

MEANING

STATE

INDIEX

MEANING

STATE

i.41

Max p. 1

0 = open

1 = closed

u.73

Free

0 = open

1 = closed

i.42

Min p. 1

0 = open

1 = closed

u.74

Free

0 = open

1 = closed

i.43

Magnet. Switch comp. 1

0 = open

1 = closed

u.75

Alarm

0 = open

1 = closed

i.44

Magnet. Switch pump 1

0 = open

1 = closed

u.76

Compressor 1

0 = open

1 = closed

i.45

Magnet. Switch fans 1

0 = open

1 = closed

u.77

Pump 1

0 = open

1 = closed

i.46

Free

0 = open

1 = closed

u.78

Fans 1

0 = open

1 = closed

i.47

Flowswitch

0 = open

1 = closed

u.79

Hot gas

0 = open

1 = closed

i.48

Level

0 = open

1 = closed

u.80

Water load

0 = open

1 = closed

i.49

Min p. 2

0 = open

1 = closed

u.81

Free

0 = open

1 = closed

i.50

Magnet. Switch comp. 2

0 = open

1 = closed

u.82

Free

0 = open

1 = closed

i.51

Min p. 3

0 = open

1 = closed

u.83

Free

0 = open

1 = closed

i.52

Magnet. Switch comp. 3

0 = open

1 = closed

u.84

Free

0 = open

1 = closed

i.53

Magnet. Switch pump 2

0 = open

1 = closed

u.85

Free

0 = open

1 = closed

i.54

Magnet. Switch fans 2

0 = open

1 = closed

u.86

Part winding 1

0 = open

1 = closed

i.55

Remote On-off

0 = open

1 = closed

u.87

Part winding 2

0 = open

1 = closed

i.56

Free

0 = open

1 = closed

u.88

Part winding 3

0 = open

1 = closed

i.57

Magnet. Switch fans 3

0 = open

1 = closed

u.89

Compressor 2

0 = open

1 = closed

i.58

Magnet. Switch fans 4

0 = open

1 = closed

u.90

Compressor 3

0 = open

1 = closed

i.59

Magnet. Switch fans 5

0 = open

1 = closed

u.91

Pump 2

0 = open

1 = closed

i.60

Max p. 2

0 = open

1 = closed

u.92

Fans 2

0 = open

1 = closed

i.61

Max p. 3

0 = open

1 = closed

u.93

Fans 3

0 = open

1 = closed

i.62

Free

0 = open

1 = closed

u.94

Fans 4

0 = open

1 = closed

i.63

Free

0 = open

1 = closed

u.95

Fans 5

0 = open

1 = closed

i.64

Free

0 = open

1 = closed

u.96

Auxiliary

0 = open

1 = closed

i.65

Free

0 = open

1 = closed

A97

Probe 2 (optional)

0 = open

1 = closed

i.66

Free

0 = open

1 = closed

i.67

Free

0 = open

1 = closed

i.68

Free

0 = open

1 = closed

i.69

Free

0 = open

1 = closed

i.70

Free

0 = open

1 = closed

i.71

Free

0 = open

1 = closed

i.72

Free

0 = open

1 = closed

Page 51

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

12.3 PARAMETERS PROGRAMMING (FOR VERSIONS GC 2 TO GC 6) To accede to the operating parameters it is necessary to press key

holding it down for about 5

seconds, after which the led SET will flash and the code of the first parameter will be visualized on the display. At this point key

can be released and by pressing

or

the desired parameter can be

selected. Once the parameter on which we intended to operate has been selected to modify it press

, than

released it, the set of the parameter will show up. To modify this value press

or

so as to increase or decrease the value.

Once the desired value has been set press and than release

and the selected parameter code can

be read on the display. By pressing

or

it is therefore possible to choose another one and modify it as previously

mentioned. To outgoing from the programming mode no key is to be pressed for about 20 seconds, the instrument will automatically return to normal functioning mode, visualizing the temperature process value.

Instruction, use and maintenance manual –

©02_10/02

Page 52

Model GC

Processing water chiller

12.4 PROGRAMMABLE PARAMETERS Here following are described all the instrument parameters; pls. note that some of them could do not appear because are according to the kind of used instrument.

12.4.1 PARAMETERS TABLE Par.

Description

1 Uneditable parameter CC MEASURE AND VISUALIZATION 2

CA

Calibration

3 Unit of measurement ru 4 Decimal Point dP TEMPERATURE CONTROL

5

d

Differential switching point

6

LS

Minimun Set

7

HS

Maximun Set

8

HC

Range

Default

--

--

-15.0..+15.0 °C-°F C-F on-oF 0.0 … 15.0 (HC=C) 0.0 … 15.0 (HC=C) °C-°F -58…HS °C-°F LS…199 °C-°F H-C

Output operatine mode Relay status in case of erroe 9 oF-on rP probe COMPRESSOR PROTECTION AND DELAY AT SWITCH ON 10 Compressor type protection 1-2-3 PS Time delay compressor 11 0…31 min. Pt protection 12 Output delay at power on 0…99 min. od TEMPERATURE ALARMS (NOT ACTIVED) 0…50 13 High alarm HA °C-°F 0…50 14 Low alarm LA °C-°F 1…31 15 Alarm differential Ad °C-°F 16 Alarm delay at power on 0…99 hrs. PA DIGITAL INPUT (NOT ACTIVED) 17 Digital input function 0 -3 FI 18 Digital input logic mode on-oF LI SET POINT LS…HS 19 Set point SP °C-°F

Page 53

Note

0.0 C on

2.0

-10 +25 C oF 1 1 1 0 0 0 0 0 oF 0

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

12.5 PARAMETERS DESCRIPTION MEASURE AND VISUALIZATION PARAMETERS: They permit to define the visualization modalities of the temperature measured by the probe. CA - CALIBRATION: Positive or negative offset whose value is added to the value red by the probe from which is depending the control functioning. ru - UNIT OF MEASUREMENT: Determines the visualization of the temperature in Centigrade or Fahrenheit degree. It is to be remember that the change of this parameter modifies the visualization but not the Set and the Set limit ("LS" and "HS") programmed (eg. if the Set was 50°C and the unit changes, the Set will rest 50°F). dP - DECIMAL POINT : Allows the insertion of the decimal point on the display and therefore to determine resolution of the reading value in the range from -19.9 to 19.9 (on= with decimal point, oF= without decimal point) SET LIMITS PARAMETERS: They permit to limit the Set programming into a desired range, in order to avoid Set values which may damage the controlled plant. LS – MINIMUMSET: Minimum value programmable as Set Point. HS – MAXIMUM SET: Maximum value programmable as Set Point. TEMPERATURE CONTROL PARAMETERS: They permit to define the temperature regulator functioning and the output control in case of probe error. SP - SET POINT :Temperature control Set Point value. d - DIFFERENTIAL : It’s the output OUT activation and deactivation value respect to the Set Point. HC – OUTPUT FUNCTIONING MODE : It defines whether the output OUT has to control and Heating or a Cooling process (H=Heating, C= Cooling). rP - OUTPUT RELAY STATE IN CASE OF ERROR PROBE: Select output relay state in case of error probe (on = relay on, oF = relay off). COMPRESSOR PROTECTION AND DELAY AT SWITCH ON: They permit to introduce eventual delays at the output OUT activation in order to avoid compressor short cycles in the refrigeration applications or at each instrument start. When the output has to be activated but it’s inhibited by these functions the led OUT blink. PS - COMPRESSOR TYPE PROTECTION: Select the type of protection for the compressor against "short cycle". The possibles selections are: 1 = delay before start 2 = delay after stop 3 = delay between starts Pt - TIME DELAY COMPRESSOR PROTECTION: Time delay setting for parameter "PS" intended in min. During this time the output will be off. The output will be turned on therefore when the regulator required it and this time has expired. The function is not active programming “Pt” =0. od - OUTPUT DELAY AT POWER ON: Time delay of OUT relay activation after power on and expressed in min.

Instruction, use and maintenance manual –

©02_10/02

Page 54

Model GC

Processing water chiller

ALARMS PARAMETERS: They permit to program the temperatur alarms modalities. The high and low temperature alarm can be disactivated setting the relative parameters "HA" or "LA" at 0. When the alarm is functioning to stop the buzzer push any of the programming key. In the mean time of the alarm signalation, although the buzzer is silented, the instrument signalize the alarm through the AL led and it visualize, during the normal functioning alternatively "HI" (High Alarm) or "LO" (Low Alarm) and the temperature measure by the probe. (THESE ALARMS ARE NOT ACTIVED). HA - HIGH ALARM: Temperature value in respect with Set point above at which the alarm will be on (The alarm will be on when the process temperature will be upper then the value SP + HA). LA - LOW ALARM: Temperature value in respect with the Set point below at which the alarm will be on (The alarm will be on when the process temperature will be lower then the value SP - LA). Ad - ALARM DIFFERENTIAL: Value between starting and stopping of alarm signal (par. HA and LA). PA - ALARM DELAY AT POWER ON: Time delay after power on during which the alarm will not be activated (expressed in hrs).

12.6 ERRORS SIGNALLING Error

Cause

Action

-uu oo

The probe may be interrupted or in short-circuit Verify the correct connection between or may read a value outside of the allowed probe and instrument and finally verify range the correct functioning of the probe itself

EE

Internal memory error

Verify and, if necessary, reprogram the parameters.

12.7 CLEANING It’s recommended to clean the instruments only with a cloth welted with water or with a detergent neither abrasive nor containing solvents.

Page 55

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

CHAPTER 13- TROUBLESHOOTING

AT THE END OF EACH REMEDY, PRESS ALARM RESET TWICE.

13.1 LED H1 / H2 – (PAR 9.3)

Instruction, use and maintenance manual –

©02_10/02

Page 56

Model GC

Processing water chiller

AT THE END OF EACH REMEDY, PRESS ALARM RESET TWICE.

13.2 LED H3

Page 57

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

AT THE END OF EACH REMEDY, PRESS ALARM RESET TWICE.

13.3 LED H4

Instruction, use and maintenance manual –

©02_10/02

Page 58

Model GC

Processing water chiller

AT THE END OF EACH REMEDY, PRESS ALARM RESET TWICE.

13.4 LED H5 / H7 / H10

Page 59

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

AT THE END OF EACH REMEDY, PRESS ALARM RESET TWICE.

13.5 LED H8 / H9

Instruction, use and maintenance manual –

©02_10/02

Page 60

Model GC

Processing water chiller

CHAPTER 14- LIST OF COMPONENTS TABLE 1 Ref. 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114

TABLE 2

DESCRIPTION OF COMPONENT Base Front wall Rear wall Right hand side casing Left hand side casing Capacitor Air filter “Z” shaped profile for filter Electrical panel box P.G. cover Internal electrical panel plate Electrical panel Plate for front wall and electrical panel Internal pump pressure gauge Round seal for electrical panel cover

Ref. 150 151 152 153 154 155

DESCRIPTION OF COMPONENT Container centrifuge fan Centrifuge container casing Axial fan casing Centrifuge fan Axial fan Centrifuge fan casing

TABLE 3 Ref.

TABLE 4

DESCRIPTION OF COMPONENT

200 201 202 203 204 205 206 207 208

Capacitor Tap – filter tube High pressure tube Pilot light – expansion valve tube Low pressure tube Tap Dehydrating filter Liquid indicator High pressure switch 208 bis Mono-phase fan speed regulator 209 Compressor 210 Thermostatic valve 211 Plate evaporator Low pressure switch 212 Gas safety valve (for versions GC 12 to GC 55 213 only)

Ref. 300 301 302 303 304 305 306 307 308 309 310 311 312 313

DESCRIPTION OF COMPONENT Chamber Chamber cover Evaporator support Tube Pump Stainless steel pressure gauge ½" drain cock Float Hose Tank ¾" by-pass valve Safety valve Air outlet valve Galvanised cap for float

314 Flowswitch

TABLE 5 Ref. 400 401 402

DESCRIPTION OF COMPONENT Control panel tray Keyboard Control panel

Page 61

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

TABLE 1: GC 2 – 4 REVISION 00

TABLE 1: GC 6 – 18 REVISION 00

Instruction, use and maintenance manual –

©02_10/02

Page 62

Model GC

Processing water chiller

TABLE 1: GC 23 – 25 REVISION 00

TABLE 1: GC 45 –55 REVISION 00

Page 63

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

TABLE 2: GC 2 – 55 REVISION 00

Instruction, use and maintenance manual –

©02_10/02

Page 64

Model GC

Processing water chiller

TABLE 3: GC 2 – 6 REVISION 00

TABLE 3: GC 9 – 23 REVISION 00

Page 65

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

TABLE 3: GC 25 – 45 REVISION 00

TABLE 3: GC 55 REVISION 00

Instruction, use and maintenance manual –

©02_10/02

Page 66

Model GC

Processing water chiller

TABLE 4: GC 2 – 6 REVISION 00

TABLE 4: GC 9 – 55 REVISION 00

Page 67

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

TABLE 5: GC 9 – 55 REVISION 00

Instruction, use and maintenance manual –

©02_10/02

Page 68

Model GC

Processing water chiller

CHAPTER 15- SPARE PARTS REQUESTS SPARE PART REQUEST FORM This form should be completed and sent by fax. A computerised version to be sent by e-mail is also available on request.

COMPANY NAME ADDRESS CITY

PROVINCE

COUNTRY

TELEPHONE

FAX

E-MAIL

WEBSITE

CONTACT PERSON

MODEL OF MACHINE (Eg. GC-A 23) REGISTRATION NUMBER YEAR OF CONSTRUCTION LIST OF SPARE PARTS N.B. If machine information is not known, specify the code shown on the product Qty.

Description

Table

Item/Art. Code

Example 1

DATE

___________________

Page 69

Air filter

1

106

STAMP AND SIGNATURE

______________________________

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

SPARE PARTS REQUESTS GC- 2 - 6 Monophase version 3.0 Rev. 0 date 01/01/2002 REF. 106 105 305 154 211 210 205 207 206 212 208 208 bis 209 300 307 314 304 TM Q Q1 KM1 F2 T1 P1 PTC1000 LDS

Tab. DESCRIPTION 1 Air suction filter 1 Gas capacitor 4 Water pressure gauge 2 Fan 3 Evaporator 3 Thermostatic valve 3 Liquid line tap 3 Liquid indicator 3 Gas filter 3 Low pressure switch 3 High pressure switch 3 Mono-phase fan speed regulator 3 Compressor 4 Water tank 4 Float 4 Flowswitch 4 Water pump Mechanic seals for pump * Main disconnector * Automatic switch * Compressor counter * Auxiliary 24V fuse * Transformer * Thermostat temperature * Temperature probe and union * Alarm LED diagram

QTY 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2

STANDARD SUGG. MANUFACTURER** Yes Yes Eurochiller Yes No Eurochiller Yes Yes Eurochiller Yes No Ziehl-Abegg Yes No Swep Yes No Danfoss Yes No Castel Yes No Castel Yes Yes Castel Yes Yes Alco Yes Yes Alco No Yes Alco Yes No LG Elec. Yes No Eurochiller Yes Yes Valco No No Califfi Yes No Lowara / Yes Lowara Yes No ABB Yes No Merlin Gerin Yes Yes Telemecanique Yes Yes Yes Yes Elca Yes Yes Tecnologic Yes Yes Lae Yes No Eurochiller

* = Refer to layout on wiring diagrams. ** = Supplier reference is not binding and may be altered without prior notice

Instruction, use and maintenance manual –

©02_10/02

Page 70

Model GC

Processing water chiller

SPARE PARTS REQUESTS GC- 9/55 Vers. 3.0 Rev. 0 Tab. REF. DESCRIPTION 106 1 Air suction filter 200 3 Gas capacitor 305 4 Water pressure gauge 154 2 Axial fan (GC-A Version) 153 2 Centrifuge fan (GC-C Version) 211 3 Evaporator 210 3 Thermostatic valve 205 3 Liquid line tap 207 3 Liquid indicator 206 3 Gas filter 212 3 Low pressure switch 208 3 High pressure switch 208 bis 3 Condensation control pressure switch 209 3 Compressor 213 3 Gas safety valve *** 309 4 Water tank 307 4 Float 312 4 Air discharger (closed tank version) 311 4 Safety valve (closed tank version) 310 4 Automatic by-pass 314 4 Flowswitch 304 4 Water pump 401 5 Control keyboard TM Mechanical seal for pump Q * Main disconnector Q/R * Automatic casing oil resistance switch Q1 * Automatic compressor switch Q2 * Automatic water pump switch Q3 * Automatic fan switch KM1 * Compressor counter KM2 * Pump counter KM3 * Pump counter R * Compressor oil casing resistance K/F * Phase sequence control QF1 * Automatic transformer switch QF2 * Automatic auxiliary 12 VOLT switch QF3 * Automatic auxiliary 24 VOLT switch T1 * Transformer TS * Command keyboard SB * Basic microprocessor board PTC1000 * Temperature probe + union

QTY 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

01/01/2002

STANDARD SUGG. MANUFACTURER** Yes Yes Eurochiller Yes No Eurochiller Yes Yes Eurochiller Yes No Ziehl-Abegg Yes No Nicotra Yes No Swep Yes No Danfoss Yes No Castel Yes No Castel Yes Yes Castel Yes Yes Saginomya Yes Yes Saginomya No Yes Danfoss Yes No Danfoss Yes No Castel Yes No Eurochiller Yes Yes Valco Yes Yes Caleffi Yes Yes Caleffi Yes No Caleffi No No Caleffi Yes No Lowara Yes Yes Eurochiller / Yes Lowara Yes No ABB Yes No Merlin Gerin Yes No Telemecanique Yes No Telemecanique Yes No Telemecanique Yes Yes Telemecanique Yes Yes Telemecanique Yes Yes Telemecanique Yes Yes Dandoss Yes No Gavazzi Yes No Merlin Gerin Yes No Telemecanique Yes No Telemecanique Yes Yes Elca Yes Yes Eurochiller Yes Yes Eurochiller Yes Yes Lae

* = Refer to layout on wiring diagrams. ** = Supplier reference is not binding and may be altered without prior notice *** = Models GC 2 to GC 9 excluded

Attention: All spare part and or accessory requests or orders will be forwarded to the manufacturer, EUROCHILLER S.r.l.

Page 71

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

SPARE PARTS REQUESTS GC-LT Rev. 0 Tab. REF. DESCRIPTION 106 1 Air suction filter 200 3 Gas capacitor 305 4 Water pressure gauge 154 2 Axial fan (GC-A Version) 153 2 Centrifuge fan (GC-C Version) 211 3 Evaporator 210 3 Thermostatic valve 205 3 Liquid line tap 207 3 Liquid indicator 206 3 Gas filter 212 3 Low pressure switch 208 3 High pressure switch 208 bis 3 Condensation control pressure switch 209 3 Compressor 213 3 Gas safety valve *** 309 4 Water tank 307 4 Float 312 4 Air discharger (closed tank version) 311 4 Safety valve (closed tank version) 310 4 Automatic by-pass 314 4 Flowswitch 304 4 Water pump 401 5 Control keyboard TM Mechanical seal for pump Q * Main disconnector Q/R * Automatic casing oil resistance switch Q1 * Automatic compressor switch Q2 * Automatic water pump switch Q3 * Automatic fan switch KM1 * Compressor counter KM2 * Pump counter KM3 * Pump counter R * Compressor oil casing resistance K/F * Phase sequence control QF1 * Automatic transformer switch QF2 * Automatic auxiliary 12 VOLT switch QF3 * Automatic auxiliary 24 VOLT switch T1 * Transformer TS * Command keyboard SB * Basic microprocessor board PTC1000 * Temperature probe + union

Instruction, use and maintenance manual –

QTY 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

01/01/2002

STANDARD SUGG. MANUFACTURER** Yes Yes Eurochiller Yes No Eurochiller Yes Yes Eurochiller Yes No Ziehl-Abegg Yes No Nicotra Yes No Swep Yes No Danfoss Yes No Castel Yes No Castel Yes Yes Castel Yes Yes Saginomya Yes Yes Saginomya No Yes Danfoss Yes No Danfoss Yes No Castel Yes No Eurochiller Yes Yes Valco Yes Yes Caleffi Yes Yes Caleffi Yes No Caleffi No No Caleffi Yes No Lowara Yes Yes Eurochiller / Yes Lowara Yes No ABB Yes No Merlin Gerin Yes No Telemecanique Yes No Telemecanique Yes No Telemecanique Yes Yes Telemecanique Yes Yes Telemecanique Yes Yes Telemecanique Yes Yes Dandoss Yes No Gavazzi Yes No Merlin Gerin Yes No Telemecanique Yes No Telemecanique Yes Yes Elca Yes Yes Eurochiller Yes Yes Eurochiller Yes Yes Lae

©02_10/02

Page 72

Model GC

Processing water chiller

LIST OF REFERENCES GC Mono-phase WIRING DIAGRAM CALIBRATION ITEM

DESCRIPTION

Rev. 0 Date 19/02/02

PAGE

GC2

GC3

GC4

GC6

MANUFACTURER

Q

2 pole switch

1

16 A

16 A

16 A

16 A

AB

Q1

1P+N switch

1

16 A

16 A

20 A

20 A

M&G

KM1

Counter

3

/

/

/

/

Telemecanique

M1

Compressor

1

/

/

/

/

LG

M2

Fan

1

/

/

/

/

Zhiel

M3

Pump

1

/

/

/

/

Lowara

T1

Transformer

2

30 VA

30 VA

30 VA

30 VA

Elca

F2

Fuse

2

1A

1A

1A

1A

Wimer

P1

Thermoregulator

2

/

/

/

/

Tecnologic

RL

Float

3

/

/

/

/

Valco

PR1/A High pressure switch

3

27 bar

27 bar

27 bar

27 bar

Alco

PR1/B Low pressure switch

3

1,4 bar

1,4 bar

1,4 bar

1,4 bar

Alco

FL** Flow switch

3

/

/

/

/

Caleffi

*= ** =

For the GC 55 version only Optional

N.B.: The values shown refer to the GC A series with a voltage of 230 V 50 Hz

Page 73

Instruction, use and maintenance manual –

©02_10/02

Model GC

Processing water chiller

LIST OF REFERENCES GC TRI-PHASE WIRING DIAGRAM CALIBRATION ITEM

DESCRIPTION

Q

On/off switch

Q1

Thermomagnetic switch

Q1/1*

Thermomagnetic switch

Q1/2*

Thermomagnetic switch

Q2

Thermomagnetic switch

Q3

Thermomagnetic switch

Q/R

2 pole automatic switch

QF1

2 pole automatic switch

QF2

1 pole automatic switch

QF3

1 pole automatic switch

M1

Compressor

M2

Pump

M3

Fan

K/F

Phase control relay

KM1

Counter

KM2

Counter

KM3

Counter

T1

Transformer

PR1A

High pressure switch

PR1B

Low pressure switch

Rev. 0 Date 19/02/02

PAGE

GC9

1

16 A

16 A

20 A

20 A

25 A

25 A

32 A

40 A

63 A

AB

1

7A

9A

10,5 A

12 A

15 A

15 A

20 A

26 A

/

Telemecanique

1

/

/

/

/

/

/

/

/

17 A

Telemecanique

1

/

/

/

/

/

/

/

/

17 A

Telemecanique

1

2A

2A

2A

2A

2,5 A

2,5 A

5A

4,5 A

5A

Telemecanique

1

1A

2A

2A

2A

1,5 A

1,5 A

1,5 A

3A

3A

Telemecanique

1

/

/

6A

6A

6A

/

/

/

/

M&G

2

6A

6A

6A

6A

6A

6A

6A

6A

6A

M&G

2

1A

1A

1A

1A

1A

1A

1A

1A

1A

Telemecanique

2

2A

2A

2A

2A

2A

2A

2A

2A

2A

Telemecanique

1

/

/

/

/

/

/

/

/

/

Danfoss

1

/

/

/

/

/

/

/

/

/

Lowara

1

/

/

/

/

/

/

/

/

/

Zhiel

2

/

/

/

/

/

/

/

/

/

Gavazzi

3

/

/

/

/

/

/

/

/

/

Telemecanique

3

/

/

/

/

/

/

/

/

/

Telemecanique

3

/

/

/

/

/

/

/

/

/

Telemecanique

2

63 VA

63 VA

63 VA

63 VA

63 VA

63 VA

63 VA

63 VA

63 VA

Elca

3

27 bar

27 bar

27 bar

27 bar

27 bar

27 bar

27 bar

27 bar

27 bar

Saginomya

4

1,5 bar 1,5 bar 1,5 bar 1,5 bar 1,5 bar 1,5 bar 1,5 bar 1,5 bar 1,5 bar

Saginomya

Y/HG** Hot gas solenoid valve Y/RL

Water load solenoid valve

FL**

Flowswitch

R

Compressor resistance

RL

Float

*= ** =

For the GC 55 version only Optional

GC12 GC15 GC18 GC23 GC25 GC35 GC45 GC55

MANUFACTURER

3

/

/

/

/

/

/

/

/

/

Castel

3

/

/

/

/

/

/

/

/

/

Ceme

4

/

/

/

/

/

/

/

/

/

Caleffi

1

/

/

27 W

27 W

27 W

/

/

/

/

Danfoss

4

/

/

/

/

/

/

/

/

/

Valco

N.B.:The values shown refer to the GC A series with a voltage of 400 V 50 Hz

Instruction, use and maintenance manual –

©02_10/02

Page 74

Model GC

Processing water chiller

CHAPTER 16- MACHINE DEMOLITION Whenever and for whatever reason the machine needs to be eliminated and demolished all machine components must be dismantled separately and certain basic rules must be observed to protect public health and the environment. 1. All sheathes, flexible hosing and plastic components, or non-metal parts must be dismantled and grouped according to material type. This way wherever possible, materials can be melted down for recycling. 2. The machine body and all metallic parts must be dismantled and grouped according to metal type. This way they can be melted down and recycled. 3. The exhausted gas will have to be collected separately from any other waste material not to damage the environment; once collected it will have to be eliminated by a specialised company in compliance with the Regulations in force in the country where the machine is installed. 4. The motor oil must be collected and eliminated separately.

All rights reserved. Reproduction of this manual in any form, even partial is strictly prohibited, including printing, photocopying, microfilming or other means, as well as computer processing, or copying using electronic means.

Page 75

Instruction, use and maintenance manual –

©02_10/02

EUROCHILLER S.r.l. INTERNATIONAL COOLING Via Milano, 69 27030 CASTELLO D’AGOGNA (PV) ITALIA TEL. 0384-298985 - FAX 0384-298984 SERVICE 0384-298981 e-mail [email protected]

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF