Instruction manual Ensite Pro Configuration Tool Version: 2.0 June 2001 Part no.: 4416.593

Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel.: +31 15 2698600, Fax: +31 15 2619574 Email: [email protected] http://www.enraf.com Offices in: Netherlands - France - Germany - Russia - UK - USA - China - Singapore

Instruction manual Ensite Pro Configuration Tool

Page 1

Copyright 1999 - 2001 Enraf B.V. All rights reserved. Reproduction in any form without the prior consent of Enraf B.V. is not allowed. This instruction manual is for information only. The contents, descriptions and specifications are subject to change without notice. Enraf B.V. accepts no responsibility for any errors that may appear in this instruction manual. The warranty terms and conditions for Enraf products applicable in the country of purchase are available from your supplier. Please retain them with your proof of purchase.

Page 2

Preface

Preface This manual describes how to work with the configuration tool Ensite Pro. It has been written for the technicians involved in the commissioning and service of the series 880 CIU Prime and Plus.

Safety and prevention of damage ‘Cautions’ and ‘Notes’ have been used throughout this manual to bring special matters to the immediate attention of the reader. A Caution draws attention to an action which may damage (the operation of) the equipment.

A Note points out a statement deserving more emphasis than the general text.

Legal aspects

The information in this instruction manual is copyright property of Enraf B.V., Netherlands. Enraf B.V. disclaims any responsibility for personal injury or damage to equipment caused by: • •

Deviation from any of the prescribed procedures; Execution of activities that are not prescribed;

Additional information Please do not hesitate to contact Enraf or its representative if you require additional information.

Instruction manual Ensite Pro Configuration Tool

Page 3

Table of contents

Table of Contents Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Ensite Pro configuration tool - General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Configuration Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Procedure steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Preparation ...................................................... 8 Retrieving configuration data of gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Configuration of the Tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Configuration of CIU Prime’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Configuration of CIU Plus’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Linking Gauges, Tanks and CIU’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Downloading configuration data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Start Ensite Pro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Select site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Global settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Configure data inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Density . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Vapour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Scan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

17 18 20 21 22 23 24 25 26 27

Configure tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Vapour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Roof . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

28 29 30 32 33 34 35 36 37

Configure CIU Prime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Page 4

Table of contents HostPort 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HostPort 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hot standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FieldPorts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tambient . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

39 40 42 43 46

Configure CIU Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 HostPorts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Modbus settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Entities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hot standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FieldPort 1 & 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

50 50 51 52 53 55

Configure links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Data inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CIU Prime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

56 56 57 58

Communication setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Download configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Upload configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Service note(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Set date and time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Print configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Show diagnostic data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Tank viewer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Scan viewer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 User privileges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Stop Ensite Pro . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Appendix A: related documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

Instruction manual Ensite Pro Configuration Tool

Page 5

Introduction

Introduction The configuration of the new tank inventory system consists of modular parts: • • • •

Entis Pro CIU Plus CIU Prime field instrumentation

Entis Pro

This system displays calculated data from the CIU Plus. It is a Windows®NT based program, displaying data in windows, boxes, tables, graphs, etc.

CIU Plus

This unit calculates volume and mass. It requests input data from the CIU Prime and calculates all other data. It presents data to higher layered systems like Entis Pro, SCADA, DCS, ENSITE, etc.

CIU Prime

This unit is an interface between the field instrumentation (e.g. 854 ATG, 873 SmartRadar, etc.) and inventory systems (CIU Plus, PLC, ENSITE, etc.).

Field instrumentation The instruments in the field collect data such as level, temperature, density and/or pressure. The instruments are based on several principles: mechanical, servo, radar, hydrostatic and capacitive or a combination. The instruments measure the data and transmit it upon request of higher layered systems.

Ensite Pro

Ensite Pro is a configuration tool for commissioning, diagnostics and documentation of the series 880 CIU Prime / Plus.

Commissioning

Some information will be asked to fill in, needed to program the CIU Prime / Plus. Ensite Pro automatically puts the input on the right (default) positions.

Diagnostics

The build in diagnostic data views, reads and writes data direct from and to the CIU Prime / Plus.

Documentation

The whole configuration can be printed to have a hard back-up. See later in this manual.

Page 6

Ensite Pro configuration tool - General

Ensite Pro configuration tool - General The configuration tool works with windows. Within these windows are buttons, on which the function is written. One of the characters on a button is underlined. Throughout the configuration tool, common buttons are used. Their description is given once: Press the ‘Ok’-button to set the parameters and work with it accordingly. Press the ‘Cancel’-button to ignore any changes made. The program returns to the previous window. In some cases this button has been renamed into Close” Press the ‘Apply’-button to set the parameters and work with it accordingly, but remain in the active window. Check the ‘Advanced’-button to activate the advanced part in the active window.

Activate functions

The function of a button can be activated in several ways:

- mouse



- ‘Alt’-key



- ‘Tab’-key



move the mouse pointer to the button and click the left mouse button press the ‘Alt’-key simultaneously with the underlined character key of the text on the button press the ‘Tab’-key to scroll over all buttons. When the desired button is reached (marked), press the ‘Enter’-key

Instruction manual Ensite Pro Configuration Tool

Page 7

Configuration procedure

Configuration Procedure This chapter describes the general configuration procedure for the 880 CIU Prime, CIU Plus. For programming the 880 series CIU’s, it is necessary to use Ensite Pro. It is programmable to communicate via one of the higher levels, i.e. via a CIU Plus to a CIU Prime, or even via Entis Pro to any of the connected CIU’s. Procedure steps

The complete configuration procedure consists out of the following steps: • • • • • •

Preparation

Preparation Retrieving configuration data of gauges. Configuration of Tanks Configuration of the CIU Prime(s) Configuration of CIU Plus(‘s) Linking Gauges, Tanks and CIU’s Before you start configuring 880 series CIU and possible one or more Entis Pro stations, certain preparations are necessary. Be sure that the following information is available:

• • • • • • •

Site layout Field cabling information (which gauges are connected on the same pair of field wires, etc.) Tag names of field devices (gauges, CIU and tanks) Tank information (strapping tables, or tank capacity tables, roof details, etc.) Information on the types of stored product Host communication setup (if applicable, i.e. modbus memory maps, etc.) Modems and possible other communication hardware connected to the CIU’s

The first step in Ensite Pro is the creation of a site. This allows the program to store multiple configuration sets, with each a separate database. After a new site has been created, the program will prompt for a set of global settings. These settings are required for initiating the configuration database. Once the global settings are entered, Ensite Pro will create a site database. If there is a .LOG file available for this gauge it can be extracted by Ensite Pro. The data extraction pre-sets all the relevant configuration parameters. The next step is the creation off all tanks.

Page 8

Configuration procedure Retrieving configuration data of gauges As first step the gauges should be configured correctly. This can best be done by means of the DOS program ENSITE. With ENSITE the so called .LOG files can be created. These .LOG files contain all the programmable settings of relevant gauge. If no gauges are installed yet, it is also possible to prepare these in ENSITE. They can then later be down loaded into the gauge. Configuration of the Tanks Also the creation of the tanks is a straightforward process. At the creation of a new tank, the user is always prompted for a name. Preferably use the same name as the name already in use on site. Once the tank has been created, the user has to enter specific tank details, like Tank shape, Roof details, etc. Tank strapping tables or capacity tables can be linked via an external file. This file needs to be conform the TCT specification as specified in this manual. The format is a simple ASCII, comma delimited format. The straps can either be manually entered, or be calculated out of a formula, depending on what information is available. The strapping file can contain a maximum of 2000 straps. The total capacity of the CIU+ is 20000 straps. The data can best be prepared by means of a spreadsheet program like Excel or Lotus 123. Users already using Entis+, can contact the factory for a TCT extraction program. This program extracts the strapping table out of the internal Entis+ database, and converts it into an Ensite Pro compatible format. Once all the tanks are created in the database, the user can either start with the configuration of the CIU Primes or the CIU Pluses. Configuration of CIU Prime’s In the 880 series CIU Prime, the following parts can be configured: • • • • •

HostPort 1 HostPort 2 Hot standby (if applicable) Field ports The hot stanby settings are required if redundant CIU Primes are installed.

The Field ports settings depend on the type of interface card installed in the CIU Prime.

Instruction manual Ensite Pro Configuration Tool

Page 9

Configuration procedure Configuration of CIU Plus’s In the 880 series CIU Plus, the following parts can be configured: • • • • •

Hostports Hot standby (if applicable) FieldPort 1 FieldPort 2 The hot standby settings are required if redundant CIU Primes and/or CIU Pluses are installed.

The host port setting are required to make the CIU Plus compatible with the connected hardware and software, i.e. a PLC, Entis Pro or a DCS system. The FieldPort settings inform the CIU Plus about the communication setting to one or more CIU Primes. Linking Gauges, Tanks and CIU’s After all the data inputs, Tanks, CIU Primes and CIU Pluses are configured the linking of all devices can commence. On basis of the actual or planned installation, the user has now to link the hardware: • • •

the data inputs to the tanks, the tanks to the CIU Primes, the CIU Primes to the CIU Pluses.

Downloading configuration data Once you have verified all the settings of all the devices, you can download the configuration database into the respective CIU’s. The first time it is advised to do downloading directly on the targeted CIU (Prime of Plus). Ensite Pro offers this downloading as a standard feature, even over modem lines. Later modifications on the CIU configuration can also be done via a CIU Plus into a CIU Prime, or even via Entis Pro from any of the network stations. Always make a backup of the site database before making any modifications. In doubt upload the configuration.

Page 10

Start Ensite Pro

Start Ensite Pro Ensite Pro can be started in the following way: Windows 95/98/NT

• press ‘Start’-button • select ‘Programs’ • activate ‘Ensite Pro’-shortcut The splash screen is shown, followed by the login window:

Ensite Pro login

Instruction manual Ensite Pro Configuration Tool

Page 11

Start Ensite Pro When the correct password is given (the Administrator’s default password is ‘Ensite Pro’), the program starts up with the following window:

Only three buttons are illuminated:

Select site A site gives an overview of the configuration at a specific customer’s site. Selecting a site gives you access to a database Help The build in help document assists at any time.

User privileges Access parameters for different users can be set or selected. A site must be created to be able to work with the configuration tool. Press the upper left button to illuminate all other buttons.

Page 12

Select site

Select site A site gives an overview of the configuration at a specific customer’s site. Selected sites are highlighted.

Press this button to copy the highlighted site from the list. Only specific data must be changed afterwards. When the site is not in the list (yet), a new site has to be created. Press the ‘New’-button to add a site:

Press the ‘Ok’-button to let the new site appear in the listbox. Press this button to select the highlighted site to work with. You can also double click on the highlighted site name. Press this button to import an earlier made site database.

Press this button to remove the highlighted site from the list.

Instruction manual Ensite Pro Configuration Tool

Page 13

Global settings

Global settings This window automatically pops up after a site has been created. In this window, global settings for the selected site can be programmed. These global settings cover the way data is represented. Data in the fields ‘Dimensions’ and ‘Text’ can only be changed/set after a new site has been created, all other data can also be changed/set at a later stage. Level and volume dimensions entered must be consistent with the dimensions of the tank strap tables intend to use.

Dimensions Level Temperature Density Pressure Flow

Select: Select: Select: Select: Select:

Volume Mass

Select: Select:

m, mm, ft, in, in/16, fis or 1/256 in °C, °F kg/m3, °API, lbs/ft3, dens60/60 or lbs/USgal kgf/m2, Pa, kPa or psi (lbf/in2 ) m3/min, m3/h, l/min, bbls/min, bbls/h, USgal/min, Usgal/h or UKgal/h l, m3, USgal, bbls or UKgal kg, metric ton, USton, lbs or long ton

Std. ambient air pressure Enter ambient air pressure in kPa (default = 101.325 kPa). Air density

Page 14

Enter air density in kg/m3 (default = 1.226 kg/m3 ).

Global settings

After all global settings are made, the program warns the user that it is not possible to change the settings anymore:

When confirmed, the program displays the following window:

The following buttons are available:

Select site. A site gives an overview of the configuration at a specific customer’s site. Global settings. Global settings cover the way data is represented, as well as some local figures. These settings are valid for the particular site only. Configure data inputs. The data inputs collect data such as level, temperature, density and/or pressure. 26

Configure tanks. A tank is a (large) container to store liquids or gases.

Configure CIU Prime. The CIU Prime is an interface between the field instrumentation and inventory systems. To setup the CIU Prime, the port configuration must be programmed. Configure CIU Plus. The CIU Plus calculates volume, standard volume, mass, density, flow rate etc. To setup the CIU Plus, the port configuration must be programmed.

Instruction manual Ensite Pro Configuration Tool

Page 15

Global settings Configure links. After all individual components (CIU Prime, CIU Plus, tanks and data inputs) have been configured, they have to be linked to each other. Communication setup. To be able to communicate via the configuration tool, communication parameters must be set. Download configuration. The (new) programmed configuration must be downloaded for the CIU Prime / Plus to work with. Upload configuration. The upload function is standard disabled in the toolbar.

Service note(s). The build in text editor gives the possibility to store information about the current site. Set date and time. The current date and time of the CIU Prime / Plus , can be (re-)set.

Print configuration. The whole configuration can be printed to have a hard copy.

Show diagnostic data. The build in diagnostic data views, reads and writes data direct from and to the CIU Prime / Plus. Tank viewer. All measured and calculated data from one tank can be viewed.

Scan viewer. The field scan can be viewed.

Help. The build in help document assists at any time.

User privileges. Access parameters for different users must be set.

Page 16

Configure data inputs

Configure data inputs The data inputs (instruments in the field) collect data such as level, temperature, density and/or pressure. The instruments measure the data and transmit it upon request of higher layered systems.

Press the ‘Copy’-button to copy the highlighted data input from the list. Only specific data must be changed afterwards. When the data input is not in the list (yet), a new data input has to be created. Press the ‘New’-button to add a data input:

Press the ‘Edit’-button to edit data from the highlighted data input: - Gauge - Level

- Water - Temperature

- Density - Pressure

- Vapour - Scan

Press the ‘Delete’-button to remove the highlighted data input from the list.

Instruction manual Ensite Pro Configuration Tool

Page 17

Configure data inputs

Gauge

Gauge LOG file Press the ‘Browse’-button to select a gauge log file.

Press the ‘Extract’-button to fill in the data from the gauge log file in the next tabs. A warning is generated before a log file is extracted while settings have been entered already. All dimensions in a gauge log file must be compatible with the system dimensions.

Page 18

Configure data inputs Gauge Gauge type Gauge details

Select:: Select::

Unknown, 802, 811, 812, 813, 816, 818, 829, 854, 865, 866, 872, 873, 877, 894, 973 or 999 h for 854 gauges using the ZLQ record (up to software version SPUA1.0) - for 854 gauges (with software version SPUA2.0 onwards)

Allowed gauge commands Check if allowed (TG; 811, 854, 894 only) Test gauge Block gauge Check if allowed (BL; 811, 854, 894 only) Tank profile Check if allowed (TP; 854, 894 only) Gauge alarm test Check if allowed (AT; 873 only) Lock test Check if allowed (LT; 811, 854, 894 only) Water dip Check if allowed (I3; 811, 854, 894 only) Interface profile Check if allowed (IP; 854, 894 only) Verify command Check if allowed (CA; 854, 894 only) Reset gauge Check if allowed (RS) Interface 2 command Check if allowed (I2; 854, 894 only) Gauge types ‘816' and ‘818' are only supported via 858 CIU. Gauge type ‘829' is only supported in 867 emulation mode. All three gauge types require the extended field address for 858 CIU or 867 receiver (TOI 858 = P or R, TOI 867 = L). Gauge type ‘999' is a generic Enraf gauge with no special processing (default processing used).

General limits: All instruments from one tank must be connected to the same FieldPort. Using BPM cards: Up to 50 data inputs can be equally divided over the four FieldPorts of the CIU Prime, with a maximum of 15 data inputs per line. The instrument address on each port is free selectable between 00...99. The instrument address must be unique for all data inputs on the same CIU. Using RS232/485 cards: Field addresses may contain 3 digit address numbers.

Instruction manual Ensite Pro Configuration Tool

Page 19

Configure data inputs

Level

Level enabled 0.1 mm level resolution Negative levels enabled

Check to enable level scan. Check to enable. This selection is only possible if the level dimension is set to ‘m’ or ‘mm’ and if the gauge type is not 811, 813, 866 or 872. Check to enable. This selection is only possible for gauge types 854, 872, 873 and 894.

No alarm when gauge in test Check to disable gauge alarms during operational commands. Level killed Manual overwrite

Check to disable level scan. Enter manual product level. First enable level.

Level address Level TOI Level TOR

Page 20

Enter level transmission address Select: A, B, C, E or M Select: B, J, L, M or ZLQ (the combination of level TOR ‘ZLQ’ and level type ‘Ullage’ is not possible. With level type ‘Ullage’, use level TOR ‘L’).

Configure data inputs

Water

Water probe enabled

Check to enable water level scan from external probe.

Water dipping enabled Offset Min. water level

Check to enable water level scan from servo gauge. Enter water level offset Enter minimum water level. This value is used when no water level is found.

Manual overwrite

Enter manual water level. Only possible if water probe or dip is enabled First enable water dip or water probe.

Water address Water TOI Water TOR

Enter water level transmission address Select: A, B, C, E or M Select: B, J, L, M or ZLQ (the combination of water TOR ‘ZLQ’ and level type ‘Ullage’ is not possible. With level type ‘Ullage’, use water TOR ‘L’) Water in foreground scan Check to enable

Instruction manual Ensite Pro Configuration Tool

Page 21

Configure data inputs

Temperature

Temperature enabled Element type

Check to enable product temperature scan. Select: No element available, MRT, MRT with bottom spot, MRT with bottom and top spot, One spot element, Two spot element or MTT Lowest element position Enter lowest temperature element position.

Product temp. killed Manual overwrite

Check to disable product temperature scan. Enter manual product temperature First enable temperature.

Temp. address Enter product temperature transmission address Temp. TOI Select: A, B, C, E or M Temp. TOR Select: C or ZAG Temp. in foreground scan Check to enable

Page 22

Configure data inputs

Density

HIMS (HTMS) enabled

Check to enable density scan from HIMS configuration.

Density dip enabled Min. dip level

Check to enable density scan from servo gauge. Enter minimum density level

Manual overwrite

Enter manual (=observed) density together with the observed temperature. Firs enable HIMS/HTG or Density dip

Density address Enter density transmission address Density TOI Select: B, C or E Density TOR Select: ZQQ Density in foreground scan Check to enable

Instruction manual Ensite Pro Configuration Tool

Page 23

Configure data inputs

Pressure

Pressure enabled Absolute pressure Relative pressure

Check to enable vapour pressure scan. Select if applicable Select if applicable

Vapour pressure killed Manual overwrite

Check to disable vapour pressure scan. Enter manual vapour pressure First enable Pressure

Pressure address Enter vapour pressure transmission address Pressure TOI Select: A, B, C, E or M Pressure TOR Select: ZP3 Pressure in foreground scan Check to enable

Page 24

Configure data inputs

Vapour

Vapour temperature enabled Check to enable vapour temperature scan. Vapour temp. killed Manual overwrite

Check to disable vapour temperature scan. Enter manual vapour temperature First enable vapour temperature.

V. Temp. address Enter vapour temperature transmission address V. Temp. TOI Select: A, B, C, E or M V. Temp. TOR Select: C or ZAG V. Temp. in foreground scan Check to enable

Instruction manual Ensite Pro Configuration Tool

Page 25

Configure data inputs

Scan

Field Display Indicator Scan enable Check to enable indicator scan. Scan address Enter FDI transmission address Scan TOI Select: A, B, C, E or M Scan TOR Select: B, C, J, L, M, ZAG, ZLQ, ZP3 or ZQQ Scan in foreground scan Check to enable

Page 26

Configure data inputs

Tank

Linked to tank

This field displays the tank name on which the level gauge is connected. This box is not editable.

Instruction manual Ensite Pro Configuration Tool

Page 27

Configure tanks

Configure tanks Select or enter a tankname. All tank related data can be entered in this section.

Press the ‘Copy’-button to copy the highlighted tank name from the list. Only specific data must be changed afterwards. When the tank is not in the list (yet), a new tank has to be created. Press the ‘New’-button to add a tank:

Press the ‘Edit’-button to edit data from the highlighted tank: - Tank - Vapour - Flow - TCT - Product - Shell - Roof Press the ‘Delete’-button to remove the highlighted tank from the list.

Page 28

Configure tanks

Tank

Shape

Select the tank shape, visualising icon for this tank. 0...7: Enraf default (0 = No shape defined, 1 = Cylindrical fixed roof, 2 = Cylindrical with floating roof, 3 = Cylindrical with internal floater, 4 = Spherical tank, 5 = Bullet, 6 = Underground bullet, 7 = Irregular cavern) reserved for future expansion by Enraf 8...99: 100...255: user defined tank shapes. Create your own tank icon, name it ‘TankShape.ico’ and place it in the ‘\Pictures’-subdirectory.

Level type

Select:

Innage or Ullage/Outage

Volume corr.

Select:

- None (no Vapour Mass) - S&W corr. (Liq. Mass from NSV; no Vap. Mass) - Vapour calc. Liq/Vol Ratio ISO/TC28/SC-3-N - Vapour calc. Molar Method ISO/TC28/SC-3-N - Vapour calc. Method API research proj. 44 - Vapour calc. Molar Method ISO 6578

Tank status Tank available Tank scan disabled

Check if available Check to disable

Instruction manual Ensite Pro Configuration Tool

Page 29

Configure tanks

Air density

In case the air density for this tank deviates from the one entered in global settings it can be manually be edited per tank.

Product

Product name

Enter the product’s name

Corrections API/ASTM Table

Select:

Prod. Code TC Range checking VCF TCF DCF

Page 30

- No GSV calculation - Dref/VCF D1250-1980 T5/6 - Dref/VCF D1250-1980 T23/24 - Dref/VCF D1250-1980 T53/54 - DCF calculation - TCF calculation - VCF D4311-1990 T1 - VCF D4311-1990 T2 - Manual VCF entry - VCF D4311-1996 T1 Select: N.A., A, B, C, D or E Enter expansion factor in 10-7 /°C (in case of product code ‘C’) Check to enable temperature and density range checkings Enter volume correction factor Enter temperature correction factor Enter density correction factor

Configure tanks

Mass Calculation in air Select if applicable in vacuum Select if applicable HIMS/HTMS not allowed Check to enable HTG Check to enable Manual ref. density Enter the product’s reference density Ref. temperature Enter local reference temperature S&W Enter sediment and water percentage Press the ‘Advanced’-button to enable/disable volume calculation details:

VCF

A selection can be made between a calculation in 4 or 5 decimals

Instruction manual Ensite Pro Configuration Tool

Page 31

Configure tanks

Vapour Data in this tab can only be filled in if in the ‘Tank’-tab the ‘Volume corrections’ is set to ‘Vapour’.

Vapour calc. details Liq/Vol. ratio Molar value

Enter liquid to volume ratio (default = 250). Enter molar weight of gas composition (default = 0).

Vapour mass calculation in air Select if applicable in vacuum Select if applicable

Page 32

Configure tanks

Shell

Tank shell calibrated (W&M) Check to enable CTSh correction (acc. API Chapter 12.1) Check to enable tank shell expansion correction

Tank shell exp. coeff. Enter tank shell expansion coefficient Tank shell ref. temperature Enter tank shell reference temperature Insulation factor Enter tank shell insulation factor. This can be a figure between 0 and 1, in which 1 is for fully insulated tanks.

Instruction manual Ensite Pro Configuration Tool

Page 33

Configure tanks

Flow

Moving detection interval Enter interval time (in s) after which level increase/decrease must be checked (default = 30 sec). Moving detection trip level Enter minimum trip level after which level increase/decrease will be indicated (default = 0 ). Flow calculation interval Enter interval time (in s) after which volume increase/decrease must be checked (default = 60 sec). Flow calculation damping Enter damping factor (0...1) for stable read-out (default = 0.15).

Page 34

Configure tanks

Roof

Zone 1 Enabled Check to enable No GOV calculation Check to disable volume calculation when level is in zone 1 No Water Volume calculation Check to disable Weight Enter roof weight High Enter no-go-zone 1 high level Low Enter no-go-zone 1 low level Check to enable Zone 2 Enabled No GOV calculation Check to disable volume calculation when level is in zone 2 No Water Volume calculation Check to disable Extra Weight Enter roof weight High Enter no-go-zone 2 high level Low Enter no-go-zone 2 low level

High/low zones The program will issue a warning if the low value is higher than the high value.

Instruction manual Ensite Pro Configuration Tool

Page 35

Configure tanks

TCT

Tank Capacity Table

Browse View

The format of this file can be found in the ‘Instruction manual series 880 CIU Plus’. Press the ‘Browse’-button to select a tank capacity table

Press the ‘View’-button to view the tank capacity table

Water volume if no water found Enter water volume Shell capacity

Enter shell capacity

High level High TOV

Enter level that corresponds with high TOV (for graphical purposes) Enter volume that corresponds with high level (for graphical purposes in Entis Pro) Enter level that corresponds with low TOV (for graphical purposes in Entis Pro) Enter volume that corresponds with low level (for graphical purposes in Entis Pro)

Low level Low TOV

Page 36

Configure tanks

Links Data in this tab can only be viewed. No entry is possible.

Linked via Primary CIU Plus

Linked via CIU Prime Primary

Secondary

Linked via Secondary CIU Plus

Linked via CIU Prime Primary

Secondary

The name of the primary CIU Plus is displayed, via which the tank is connected.

The name of the primary CIU Prime is displayed, via which the tank is connected. The name of the secondary CIU Prime is displayed, via which the tank is connected.

The name of the secondary CIU Plus is displayed, via which the tank is connected.

The name of the primary CIU Prime is displayed, via which the tank is connected. The name of the secondary CIU Prime is displayed, via which the tank is connected.

Instruction manual Ensite Pro Configuration Tool

Page 37

Configure CIU Prime

Configure CIU Prime The CIU Prime is an interface between the field instrumentation (e.g. 854 ATG, 873 SmartRadar, etc.) and inventory systems (CIU Plus, DCS, PLC, etc.).

Input boards

There are four slots available in the CIU Prime. These slots can handle two different types of boards: • •

Output boards

BPM ( Bi-Phase Mark) to interface the Enraf field bus. RS-232C/RS485 input board to interface the 858 CIU.

Two fixed RS-232C/RS485 output boards interface to a CIU Plus, DCS, PLC, etc.

Press the ‘Copy’-button to copy the highlighted CIU Prime from the list. Only specific data must be changed afterwards. When the CIU Prime is not in the list (yet), a new CIU Prime has to be created. Press the ‘New’-button to add a CIU Prime:

Page 38

Configure CIU Prime

Press the ‘Edit’-button to edit data from the highlighted CIU Prime: - HostPort 1 - Hot standby - Tambient - HostPort 2 - FieldPorts Press the ‘Delete’-button to remove the highlighted data input from the list.

HostPort 1

Config. name RTU address Baudrate Modbus mapping CIU Plus compliant

W&M sealed User specified

Enter the name of the connected device (up to 10 characters). Enter the RTU address (default = 31) Select: 1200, 2400, 4800, 9600 or 19200

Select if a CIU Plus is connected to this port. All data will be filled in on pre-defined positions. Check if applicable Select if no CIU Plus is connected to this port. All data will be filled in on user specified positions. Press the ‘Settings’-button to program these positions (refer to the chapter ‘Modbus settings’).

Instruction manual Ensite Pro Configuration Tool

Page 39

Configure CIU Prime

Stop bits Parity Turn-around delay Duplex mode Mode Multi Party

Select: 1 or 2 Select: Odd, Even or None Enter reply waiting time in ms (default = 100 ms) Select: Full or Half Select: RS-232C or RS-485 Select: Point-to-point or Multi-drop If ‘RS-232C’ is selected, while in reality RS-485 hardware is applied, communication can not be established.

HostPort 2

Config. name RTU address Baudrate

Page 40

Enter the name of the connected device (up to 10 characters). Enter the RTU address (default = 31) Select: 1200, 2400, 4800, 9600 ,19200 or 38400.

Configure CIU Prime

Modbus mapping CIU Plus compliant

W&M sealed User specified

CIU 858 compatible MSU mode Stop bits Parity Turn-around delay Duplex mode Mode Multi Party

Select if there is a CIU Plus connected to this port. All data will be filled in on pre-defined positions. Check if applicable Select if there is no CIU Plus connected to this port. All data will be filled in on user specified positions. Press the ‘Settings’-button to program these positions (refer to the second next chapter, ‘Modbus settings’).

Check to enable CIU emulation Check to enable Select: 1 or 2 Select: Odd, Even or None Enter reply waiting time in ms (default = 100 ms) Select: Full or Half Select: RS-232C or RS-485 Select: Point-to-point or Multi-drop If ‘RS-232C’ is selected, while in reality RS-485 hardware is applied, communication can not be established.

Instruction manual Ensite Pro Configuration Tool

Page 41

Configure CIU Prime

Hot standby If any changes are made to any of the CIU Prime settings (while a hot standby counterpart is defined), the program will generate a warning to keep the configurations of both units synchronous.

Hot standby enabled Counterpart

Check to enable hot standby functionality Select name of other CIU Prime

Hot standby mode

Select:

Primary or Secondary

If ‘Primary’ is selected, while no secondary CIU Prime exists, the hot standby facility can not be established.

Page 42

Configure CIU Prime

FieldPorts

The setting in ‘Poll strategy’ determines the sequence in which the FieldPorts are scanned: P = FieldPort scans parallel, without waiting for other FieldPorts 1 = FieldPort scans in sequence with other FieldPorts with code 1 2 = FieldPort scans in sequence with other FieldPorts with code 2

Examples: PPPP = all ports scan parallel (= default) P111 = port 1 scans parallel; others scan sequentially 1122 = ports 1 and 2 and ports 3 and 4 scan in a separate sequence PPP1 = all ports scan parallel (sequence 1 contains only one port) FieldPort 1, 2, 3, 4 Type

Poll strategy

Select: Select:

None, CIU-GPU (= RS-communication) or BPM-GPU (= Enraf fieldbus) 1, 2 or P.

Instruction manual Ensite Pro Configuration Tool

Page 43

Configure CIU Prime

Press the ‘Settings’-button to set the FieldPort communication settings:

CIU-GPU

BPM-GPU

- FieldPort

Here the name of the FieldPort is displayed.

- Type

Here the type of the FieldPort is displayed.

- Baudrate

Select: 1200, 2400, 4800, 9600 or 19200

Page 44

Select: 1200 or 2400

Configure CIU Prime

CIU-GPU

BPM-GPU

- Stopbits

Select: 1 or 2

N.A.

- Parity

Select: Odd, Even or None

N.A.

-Turn-around delay

Enter reply waiting time in ms (default = 20 ms)

- Handshake

Select: Full or Half

- Mode

Select: RS-232C or RS-485

Select: EN-BPM

- FieldPort time-out

Enter timeout in ms (default = 200 ms)

Enter timeout in ms (default = 75 ms)

- FieldPort sensitivity - FieldPort retries

N.A.

N.A.

Enter sensitivity (default = 7)

Enter number of retries (default = 3)

-Communication fail delay Enter a time between 0 and 255 seconds

See note 1

- Data fail delay

Enter a time between 0 and 255 seconds

See note 2

= Enabled

Check to enable

N.A.

If ‘RS-232C’ is selected, while in reality RS-485 hardware is applied, communication can not be established.

Note 1 When a field communication fail occurs it is possible to maintain last valid scan data in the CIU Prime database during a configurable amount of time. The communication fail delay mechanism is reset on the reception of data. A field communication fail can be caused by: - modem delays bad cabling - no answer because of a re - initializing gauge

Note 2 When a data fail occurs it is possible to maintain the last valid scan data in the CIU Prime database during a configurable amount of time. The data fail mechanism is reset on the reception of valid data. A data fail can be caused by: - re-initialization of a gauge - 802/811 digitizer failure

Instruction manual Ensite Pro Configuration Tool

Page 45

Configure CIU Prime

Tambient

Tamb. Broadcast enable Check to enable Ambient temperature scan

Tamb. scan enable Tamb. Address Tamb. TOI Tamb. TOR

Page 46

Check to enable ambient temperature scan. Enter ambient temperature transmission address Select: A, B, C, E or M Select: C or ZAG

Configure CIU Plus

Configure CIU Plus The CIU Plus calculates volume, standard volume, mass, density, flow rate, etc. It receives data from the CIU Prime and calculates all other data. It presents data to higher layered systems like Entis Pro, SCADA, DCS, etc.

Input boards

Two fixed RS-232C/RS485 input boards interface to a CIU Prime.

Output boards

Up to four RS-232C/RS485 output boards can be installed to interface host communication (Modbus) to Entis Pro, SCADA, DCS, etc. For a description of the Modbus protocol, refer to the related instruction manual.

Press the ‘Copy’-button to copy the highlighted CIU Plus from the list. Only specific data must be changed afterwards. When the CIU Plus is not in the list (yet), a new CIU Plus has to be created. Press the ‘New’-button to add a CIU Plus:

Instruction manual Ensite Pro Configuration Tool

Page 47

Configure CIU Plus

Press the ‘Edit’-button to edit data from the highlighted CIU Plus: - HostPorts - FieldPort 1 - Hot standby - FieldPort 2 Press the ‘Delete’-button to remove the highlighted data input from the list.

HostPorts

HostPort 1, 2, 3, 4 Config. name Type

Enter a name, identifying the connected device (up to 10 characters). Select: None or Modbus RTU Press the ‘Settings’-button to set HostPort communication settings:

Page 48

Configure CIU Plus

Config. name RTU address Baudrate

Mode Parity Stopbits Duplex mode Turn around delay Multi party Modbus mapping Entis Pro conform

W&M sealed User specified

Here the name of the connected device is displayed. Here the RTU address of the HostPort is displayed (default = 41). Select: 1200, 2400, 4800, 9600 ,19200 or 38400.

Select: RS-232C or RS-485 (Check the hardware) Select: Odd, Even or None Select: 1 or 2 Select: Full or Half Enter reply waiting time in ms (default = 100 ms) Select: Point-to-point or Multi-drop

Select if Entis Pro is connected to this port. All data will be filled in on pre-defined positions. Check if applicable Select if Entis Pro is not connected to this port. All data will be filled in on user specified positions. Press the ‘Settings’-button to program Modbus settings.

Instruction manual Ensite Pro Configuration Tool

Page 49

Modbus settings

Modbus settings Data

Data Orientation

Start address Record interval

Select:

Tank oriented (= data grouped by tank) or Data oriented (= data grouped by entity) Enter start address (default = 0) Enter the number of registers between tank records (default = 0050 for the Plus/Prime)

Advanced Always force Data output to Fail if validity indicates failure. Select to force the modbus registers to FFFFF in case of invalid data. If not selected the last measured value will be stored

Upon Prime Plus comm.fail. Force data output to Fail Select to force the modbus registers to FFFFF in case of invalid data. If not selected the last measured value will be stored

Page 50

Modbus settings

Tanks

Tanks Available

This column displays all available tanks. Press the ‘arrow up’-button to move the highlighted tank in the ‘Tanks in User Record’-column one position up. Press the ‘arrow down’-button to move the highlighted tank in the ‘Tanks in User Record’-column one position down. Press the ‘arrow right right’-button to move all tanks to the ‘Tanks in User Record’-column. Press the ‘arrow left left’-button to move all tanks to the ‘Tanks Available’-column. Press the ‘arrow right’-button to move the highlighted tank in the ‘Tanks Available’-column to the ‘Tanks in User Record’-column. Press the ‘arrow left’-button to move the highlighted tank in the ‘Tanks in User Record’-column to the ‘Tanks Available’-column.

Tanks in User Record

This column displays all tanks, selected for communication.

Instruction manual Ensite Pro Configuration Tool

Page 51

Modbus settings

When links are changed (adding, moving or deleting tanks) after having the Modbus mapping input, the Modbus mapping of tanks will be reset to default. Press the ‘Default’-button to restore all default settings.

Entities

Available Entities

This column displays all available entities. Press the ‘arrow up’-button to move the highlighted entity in the ‘ID’-column one position up. Press the ‘arrow down’-button to move the highlighted entity in the ‘ID’-column one position down. Press the ‘arrow left left’-button to move all entities in the ‘ID’-column to the ‘Available Entities’-column. Press the ‘arrow right right’-button to move all entities in the ‘Available entities’-column to the ‘ID’-column.

Page 52

Modbus settings

Press the ‘arrow left’-button to move the highlighted entity in the ‘ID’-column to the ‘Available Entities’-column. Press the ‘arrow right’-button to move the highlighted entity in the ‘Available entities’-column to the ‘ID’-column. # Name type Size Scale offset Entity

Entity ID number Entity name Entity type / dimension Number of registers Scaling factor Offset value When in the list an entity is highlighted, it is possible to change the type, size, scale and/or offset. Press the ‘Default’-button to restore “Entis Pro default’ default settings.

Hot standby If any changes are made to any of the CIU Plus settings (while a hot standby counterpart is defined), the program will warn to keep the configurations of both units synchronous.

Instruction manual Ensite Pro Configuration Tool

Page 53

Modbus settings

Hot standby enabled Counterpart

Check to enable hot standby functionality Select name of other CIU Plus

Hot standby mode

Select:

Primary or Secondary

If ‘Primary’ is selected, while no secondary CIU Plus exists, the hot standby facility can not be established.

Connection Ciu Prime connected to one Plus only The ports of the CIU Primes and Pluses must be connected according to the diagram.

CIU Primes connected to both primary and secondary Plus The ports of the CIU Primes and Pluses must be connected according to the diagram.

Page 54

Modbus settings

FieldPort 1 & 2

Baudrate Parity Stop bits Turn around delay Mode

Select: 1200, 2400, 4800, 9600 or 19200 Select: Odd, Even or None Select: 1 or 2 Enter reply waiting time in ms (default = 0 ms) Select: RS-232C or RS-485 If ‘RS-232C’ is selected, while in reality RS-485 hardware is applied, communication can not be established.

Retries FieldPort timeout Duplex mode Break signal Multi party

Enter number of retries (default = 3) Enter timeout in ms (default = 1100 ms) Select: Full or Half Check to enable Select: Point-to-point or Multi-drop

Instruction manual Ensite Pro Configuration Tool

Page 55

Configure links

Configure links After all individual components (CIU Prime, CIU Plus, tanks and data inputs) have been configured, they have to be linked to each other.

Data inputs

The left column displays the available tanks, the right column displays the available data inputs. Drag a data input from the right list to the tank where it is physically connected to.

Page 56

Configure links

Tanks

The left column displays the available CIU Primes, the right column displays the available tanks. Expand the structure of the CIU Prime by clicking the ‘plus’. Now the four FieldPorts appear. Drag a tank from the right list to the FieldPort of the CIU Prime where it is physically connected to.

Instruction manual Ensite Pro Configuration Tool

Page 57

Configure links

CIU Prime

The left column displays the available CIU Pluses, the right column displays the available CIU Primes. Expand the structure of the CIU Plus by clicking the ‘plus’. Now the two FieldPorts appear. Drag a HostPort of the CIU Prime from the right list to the FieldPort of the CIU Plus where it is physically connected to. Press the ‘Overview’-button to have a site overview.

Page 58

Communication setup

Communication setup To be able to communicate via the configuration tool, communication parameters must be set.

Connected to Entis Pro

Select if connected to Entis Pro

CIU Plus

Select if connected to CIU Plus; select CIU Plus name = HostPort Select CIU Plus HostPort

CIU Prime

Select if connected to CIU Prime; select CIU Prime name = HostPort Select CIU Prime HostPort

PC Port Settings Comm. port Baudrate Parity Stopbits Turn around delay Retries Reply timeout

Select communication port of PC where configuration tool is installed Select: 1200, 2400, 4800, 9600, 19200 or 38400. Select: Odd, Even or None Select: 1 or 2 Select reply waiting time in ms (default = 10 ms) Enter the number of retries (default = 2) Enter the reply waiting time (default = 3000 ms)

Instruction manual Ensite Pro Configuration Tool

Page 59

Communication setup

Press the ‘Monitor’-button to view communication. The following window is shown:

Stop presentation

Check to freeze data on the monitor.

Messages

Received Total In failure

Number of received messages Number of failing messages

Transmitted Number of transmitted messages Total Press the ‘Reset’-button to reset the message counters.

Client application

Page 60

Displays the number of applications (programs) running simultaneously.

Download configuration

Download configuration The (new) programmed configuration must be downloaded for the CIU Prime / Plus to work with. In case a CIU Prime is connected to a Plus the CIU Prime must be downloaded first as the Plus requires the CRC’s of Prime.

CIU Prime/CIU Plus

These panes displays the following columns

Name

Displays the name of the available CIU’s. Click on the name to select.

CRC

The CIU Prime / Plus calculates an overall CRC over the settings. Ensite Pro fetches this CRC after a download and saves it in its database. The CRC status can be: Situation CRC OK CRC unknown (not yet retrieved) CRC wrong

Color Green Orange Red

Text Ok Unknown Mismatch

The ‘Unknown’ condition includes the situation where an earlier attempt to retrieve the CRC has failed due to a communication error. In case of such an error, the CRC status is always unchanged, whether it was green, orange or red.

Changed

The Changed status can be ‘Y’ or ‘N’ (Yes/No). The status is ‘Y’ if a new CIU is created or if any CIU setting is changed. The CRC status and the Changed status can change independently.

Instruction manual Ensite Pro Configuration Tool

Page 61

Download configuration

Press the ‘Monitor’-button to view communication. The following window is shown. For details see the “ Communication setup” chapter. Press to show Kill CRC’s window. The “Kill CRCs button forces a full download for the selected CIU. Press the ‘INI-File’-button to generate a number of files, needed for Entis Pro. The INI-files can only be generated after the whole configuration is downloaded in the CIU’s. Press the ‘Check CRC’-button to refresh the CRC status of the highlighted CIU. This means that the overall CRC is fetched from the CIU and compared with the stored CRC in the database. Press the ‘Download’-button to download the settings of the highlighted CIU. Depending on the CRC status and the Changed status a full or a partial (= only changed settings) download will be started. Hot standby

In case of Hot standby proceed as follows: • • • •

download the Primary CIU Prime download the secondary CIU Prime download the Primary CIU Plus download the Secondary CIU Plus

When downloading through Entis Pro, the CIU Plus must be connected to HostPort 1.

After a successful download, all manual overwrite values in the Ensite Pro settings database will be cleared.

Page 62

Upload configuration

Upload configuration This function is standard disabled in the toolbar. It is only available for experienced users. Contact factory. An existing configuration of a CIU Prime / Plus can be uploaded to work with.

CIU Prime/CIU Plus

These panes displays the following columns

Name

Displays the name of the available CIU’s. Click on the name to select.

CRC

The CIU Prime / Plus calculates an overall CRC over the settings. Ensite Pro fetches this CRC after a download and saves it in its database. The CRC status can be: Situation CRC OK CRC unknown (not yet retrieved) CRC wrong

Color Green Orange Red

Text Ok Unknown Mismatch

The ‘Unknown’ condition includes the situation where an earlier attempt to retrieve the CRC has failed due to a communication error. In case of such an error, the CRC status is always unchanged, whether it was green, orange or red.

Instruction manual Ensite Pro Configuration Tool

Page 63

Upload configuration Changed

The Changed status can be ‘Y’ or ‘N’ (Yes/No). The status is ‘Y’ if a new CIU is created or if any CIU setting is changed. The CRC status and the Changed status can change independently. Press the ‘Monitor’-button to view communication. The following window is shown. For details see the “ Communication setup” chapter. Press to show Kill CRC’s window. In case you want to force a full Upload for the selected CIU. Always grayed.

Press the ‘Check CRC’-button to refresh the CRC status of the highlighted CIU. This means that the overall CRC is fetched from the CIU and compared with the stored CRC in the database. Press the ‘Upload’-button to upload the settings of the highlighted CIU.

When uploading through Entis Pro, the CIU Plus must be connected through HostPort 1.

Page 64

Service note(s)

Service note(s) When information about the current site must be stored, the build in text editor gives the possibility to do that.

Instruction manual Ensite Pro Configuration Tool

Page 65

Set date and time

Set date and time With this menu, the internal clock of a CIU Prime and/or CIU Plus can be set. Selecting a CIU from the list to see and/or (re-)set the current data and time.

New Date & Time New date and time = hours = mins = secs = month

= year

Check to set new date and time: select: 00...23 select: 00...59 select: 00...59 select: January, February, March, April, May, June, July, August, September, October, November, December select: 0000...9999

Daylight Saving Time ON Check to change between summer- and wintertime. The CIU does not switch automatically from winter time to summer time and back again.

Page 66

Print configuration

Print configuration The whole (site, CIU Prime, CIU Plus, tank, data input) configuration can be printed to have a hard back-up.

Site

Global settings CIU Plus CIU Prime Tank settings Data inputs

Select print template (default = Site.rpt) Check to print global settings Check to print CIU Plus settings; select name and HostPort Check to print CIU Prime settings; select name and HostPort Check to print tank settings; select name Check to print data input settings; select name

Instruction manual Ensite Pro Configuration Tool

Page 67

Print configuration

Link information

Select print template (default = LinkOverview.rpt)

Modbus mapping

Select print template (default = ModbusMapping.rpt)

Service notes

Select print template

Entity definition

Select print template (default = Entity97.rpt) Press the ‘Preview’-button to see how the print-out will look like.

Press the ‘Print’-button to activate the printer and print the configuration. Press the ‘Printer Setup’-button to set the printer parameters.

Page 68

Show diagnostic data

Show diagnostic data This window displays all diagnostic data (serial number, software version, run hours, last fatal error) of the selected CIU Prime/Plus.

Column description Entity Description Index DataSetIndex Value

= entity number = entity name = entity index value = where does this data come from = entity value

Press the ‘Print’-button to activate the printer and print the diagnostic data.

Database analysis

In order to analyse an erroneous database of the CIU a printout can be made. To avoid sending a fax and files separately it is possible to store the diagnostic printouts into files by pressing the envelope icon of the report form. Pressing this icon the “Export window” will pop up. Select the Format and the Destination. Change the file name and store it. If you now create a ZIP-file of the complete site the diagnostic is included. You can now e-mail the file.

Backup

This can done as follows: • •

Use the Widow explorer and locate the root directory of the site (C:\program\files\Ensite Pro\....) Select the site directory, click right and select “add to zip” (only if WinZIp is installed). Normally the Zip-file will fit on a floppy disk. If not use the MbdTools to compress the database. You can find this utility on the Ensite Pro installation CD.

Instruction manual Ensite Pro Configuration Tool

Page 69

Show diagnostic data

Press the ‘R/W Data’-button to read from and/or write to the CIU Prime/Plus:

The entity detail information can be enabled by pressing the “books” icon.

Request Press the ‘Jump to’-button to select the entity, matching the number in the field ‘Entity’. The text of the ‘Jump to’ button will change into ‘Filter’ Press the ‘Filter’-button to select the entities, starting with the number in the field ‘Entity’.

Entity Enter the required entity number. Index Enter the entity’s index value. Data set index Select the tank number where this index relates to. Enter the value to be written. This can be either in Dec. or Hex.

Value Response Value

Here the response to the request above is given. Press the ‘Enter conf’-button to go into configuration mode. It is now possible to write entities. Press the ‘Exit conf’-button to go out of configuration mode. It is now not possible o write entities. Press the ‘Read’-button to retrieve the value of the requested entity.

Press the ‘Write’-button to overwrite the value of the requested entity. This is only possible in configuration mode.

Page 70

Show diagnostic data

Press the ‘Reset Diagn. Counters’-button to .....

Press the ‘Update’-button to fetch the current values from the selected CIU Prime/Plus and fill in the ‘Value’-column.

Clear Configuration

The clear configuration procedure should only be done when a an existing database must be replaced by a new one. This procedure should not be done in case of modifying an existing database. Click on the R/W button in the “Diagnostic window”. Enter 7502 in the Entity/name field and hex 30 in the value field and press Write. Within a few seconds the CIU will be reset. The CIU Prime will indicate this by simultaneous flashing of the receive and transmit Led’s of the installed IP modules. On the CIU Plus a window will pop up with the message “Letterbox empty caused by reset of CIU” To be sure that the CIU has completed the previous command, read the CIU name (Prime entity 502 and Plus entity 602) The name should be default (“DefPrime” for the CIU prime and “DefPlus” for CIU Plus).

Clear Novram

The clear Novram procedure should only be done when a an existing database must be replaced by a new one. This procedure should not be done in case of modifying an existing database. Click on the R/W button in the “Diagnostic window”. Enter 7507 in the Entity/name field and press Write. Within a few seconds the CIU will be reset. The CIU Prime will indicate this by simultaneous flashing of the receive and transmit Led’s of the installed IP modules. On the CIU Plus a window will pop up with the message “Letterbox empty caused by reset of CIU” To be sure that the CIU has completed the previous command, read the CIU name ( Prime entity 502 and Plus entity 602) The name should be default (“0” for the CIU prime and “CIUPlus” for CIU Plus).

Instruction manual Ensite Pro Configuration Tool

Page 71

Tank viewer

Tank viewer The tank viewer displays all details for a single tank.

CIU

Select the CIU Prime/Plus

Tank

Select the tank

Product

Here the product name is displayed (CIU)

(Tank)

(Product)

Global settings

Field data

Inventory data

Reference data

Press the ‘Print’-button to activate the printer and print the current view.

Page 72

Scan viewer

Scan viewer The scan viewer displays the scanning sequence, showing the data inputs being requested.

CIU

Select CIU to work with

Column description

Tank name AT VP OD PT FG-tim BG-tim

Measured data statuses

= tank name = ambient temperature # = vapour pressure PL = observed density WL = product temperature VT = time of last foreground scan = time of last background scan

= scan sequence nr. = product level = water level = vapour temperature

The displayed status is build up out of two characters, being: 1st character:

2nd character:

F = foreground scan B = background scan X = not scanned - = measured data K = killed data & = manual data F = communication fail

Press the ‘Print’-button to activate the printer and print the current view.

Instruction manual Ensite Pro Configuration Tool

Page 73

Help

Help Click on this icon for on-line assistance.

Page 74

User privileges

User privileges The configuration tool can be operated by different users. The list box displays all users that already exist.

Press the ‘New User’-button to add a new user to the list

Name Password Confirm password

Enter user name Enter password Enter password again to confirm

Press the ‘Change Password’-button to change the password of a user that already exists:

Old password New password Confirm new password

Enter the old password Enter the new password Enter new password again to confirm

Press the ‘Delete’-button to remove the highlighted user from the list.

Instruction manual Ensite Pro Configuration Tool

Page 75

Stop Ensite Pro

X

Stop Ensite Pro To stop the configuration tool, press the ‘X’-button in the upper right corner of the configuration tool window. Next, the action has to be confirmed:

After confirmation, the configuration tool window will be closed. To use the configuration tool again, is has to be (re-)started.

Page 76

Appendix A

Appendix A: related documents Title Installation guide Ensite Pro configuration tool Instruction manual series 880 CIU Prime Instruction manual series 880 CIU Plus

Instruction manual Ensite Pro Configuration Tool

Page 77

Notes

Page 78

Notes

Instruction manual Ensite Pro Configuration Tool

Page 79

Röntgenweg 1 2624 BD, Delft : +31 15 2698600 Tel. E-mail : [email protected] Website : http://www.enraf.com P.O. Box 812 2600 AV, Delft Netherlands

We at Enraf are committed to excellence. Your Enraf distributor

Information in this publication is subject to change without notice. Enraf is a registered trademark ã Enraf B.V. Netherlands

â

Page 80