EMUA Solution for 3900 Series BTS
Short Description
Download EMUA Solution for 3900 Series BTS...
Description
EMUA Solution in 3900 Series Site
Security Level: Internal Open
EMUA Solution for 3900 Series BTS 00102313 Xiao Fei 2009-6-10 1. Alarm Assignment: .....................................................................................................................1 1.1 Define EMUA alarms and port: .......................................................................................1 1.2 Map BTS alarm to BSC alarm: .......................................................................................2 2. Configure BSC Alarm: ...............................................................................................................3 3. EMUA Board Configuration......................................................................................................4 3.1 Slot Number: .....................................................................................................................4 3.2 Configure EMUA Board Attributes: ...............................................................................4 3.3 Binding BTS alarm with BSC alarm:..............................................................................5 Bind Alarm ..............................................................................................................................5 4. Trouble Shooting .........................................................................................................................5 In 3900 series BTS, UEIU/UPEU are used to provide environmental alarm connections, however, the total number of alarms of these 2 boards are only 16. If there are over 16 alarms to be connected, we could use EMUA board which can provide 32 Environmental Alarms.
1. Alarm Assignment: 1.1 Define EMUA alarms and port:
2009-06-19
HUAWEI Confidential
Page1, Total6
EMUA Solution in 3900 Series Site
Security Level: Internal Open
1.2 Map BTS alarm to BSC alarm: The Alarm ID arranges from 6292 to 6354. In BSC, the available BTS Custom Environment Alarm ID arrange from 65384 to 65533. For example: Monitoring Unit Port
Port No.
Alarm ID
Alarm Name
BSC Alarm ID
Alarm Level
S1+/S1-
1
6292
AC Main Alarm
65420
Major
S2+/S2-
2
6294
DC High Voltage Alarm
65422
Major
S3+/S3-
3
6296
DC Low Voltage Alarm
65424
Warning
2009-06-19
HUAWEI Confidential
Page2, Total6
EMUA Solution in 3900 Series Site
Security Level: Internal Open
65426
S4+/S4-
4
6298
S5+/S5-
5
6300
65428
S6+/S6-
6
6302
65430
S7+/S7-
7
6304
65432
S8+/S8-
8
6306
65434
S9+/S9-
DC Module Alarm
Low Voltage Load Disconnect Alarm
9
6308
65436
S10+/S10-
10
6310
65438
S11+/S11-
11
6312
65440
S12+/S12-
12
6314
65442
S13+/S13-
13
6316
65444
S14+/S14-
14
6318
65446
S15+/S15-
15
6320
65448
S16+/S16-
16
6322
65450
S17+/S17-
17
6324
65452
S18+/S18-
18
6326
65454
S19+/S19-
19
6328
65456
S20+/S20-
20
6330
65458
S21+/S21-
21
6332
65460
S22+/S22-
22
6334
65462
S23+/S23-
23
6336
65464
S24+/S24-
24
6338
65466
S25+/S25-
25
6340
65468
S26+/S26-
26
6342
65470
S27+/S27-
27
6344
65472
S28+/S28-
28
6346
65474
S29+/S29-
29
6348
65476
S30+/S30-
30
6350
65478
S31+/S31-
31
6352
65480
S32+/S32-
32
6354
65482
Major
Warning
2. Configure BSC Alarm: Method 1--Define on M2000 for Method 2 Define on BSC for each BSC NE Alarm Setting-Alarm Alarm Maintenance-Query Alarm Configuration Choose BSC, Change Alarm Name Set Environment Aalrm Configuration Click "Apply"
2009-06-19
HUAWEI Confidential
all
BSC
Definition-Add and
Level
Page3, Total6
EMUA Solution in 3900 Series Site
Security Level: Internal Open
3. EMUA Board Configuration In BSC data, EMUA is configured as DEMU board.
3.1 Slot Number: If we connect RS485 to UPEU MON0, the EMUA should be configured in slot0. If we connect RS485 to UPEU MON1, the EMUA should be configured in slot1.
3.2 Configure EMUA Board Attributes: 2009-06-19
HUAWEI Confidential
Page4, Total6
EMUA Solution in 3900 Series Site
Security Level: Internal Open
In LMT: 9 Board Parameter Configuration Enabled: yes 9 Special Alarm Switch Enabled: not chosen=enabled; chosen=disabled; 9 Common Alarm Switch Enabled: not chosen=enabled; chosen=disabled; 9 Special Alarm Switch Valid Level Configuration: should be “High Level” (not chosen) 9 Common Alarm Switch Valid Level Configuration: chosen= Low Level; not chosen=High Level MML Command: “MOD DEMUBP”.
3.3 Binding BTS alarm with BSC alarm: Bind Alarm SET ALMPORT: SITENAME="OSV2", CN=0, SRN=2, SN=0, PN=1, SW=OPEN, AID=65420, PT=BOOL, AVOL=LOW; SET ALMPORT: SITENAME="PRAB", CN=0, SRN=2, SN=0, PN=2, SW=OPEN, AID=65422, PT=BOOL, AVOL=LOW; SET ALMPORT: SITENAME="PRAB", CN=0, SRN=2, SN=0, PN=3, SW=OPEN, AID=65424, PT=BOOL, AVOL=LOW; SET ALMPORT: SITENAME="PRAB", CN=0, SRN=2, SN=0, PN=4, SW=OPEN, AID=65426, PT=BOOL, AVOL=LOW; SET ALMPORT: SITENAME="PRAB", CN=0, SRN=2, SN=0, PN=9, SW=OPEN, AID=65436, PT=BOOL, AVOL=LOW;
4. Trouble Shooting 1. Board Communication Alarm, Board Type=70, Alarm ID: 6420. 2009-06-19
HUAWEI Confidential
Page5, Total6
EMUA Solution in 3900 Series Site
Security Level: Internal Open
BBU fail to communicate with EMUA board, check: Power Input and DC Switch of EMUA; The data configuration of slot number is consistent with Physical Connection of MON Port. 2. Alarm report are opposite with actual alarm status For example, the door alarm report to BSC when the door is closed and vise versa. Check: Alarm Switch Valid Level Configuration is consistent with actual voltage level.
2009-06-19
HUAWEI Confidential
Page6, Total6