EMUA Connection
November 1, 2017 | Author: IndRa Id | Category: N/A
Short Description
Download EMUA Connection...
Description
EMUA HUAWEI
Protocol Type
Setting of the 4-bit DIP Switch of the SW_ADDR
GSM/CDM 0001 A WCDMA 0010
0
ON
1
OFF
ON
1 2 3 4
INSTALLATION OF EMUA
DC-PDU
Power utk EMUA dikonek pada port Spare pada DC-PDU
Kabel monitor alarm di konek pada UPEU port MON1
Kabel monitor alarm di konek pada UPEU port MON1
Type : EMUA Sensor LSA Box Port No. 7 4 6 1 5 8 2
3 9
Alarm Box EMU
EAC DIP Switch
Alarm Description
Physical port
Number
Position
Rectifier Failure Heat Detector Active Door Open PLN Power Failure Smoke Alarm DC power too low DC Fan active Temperature & Humadity Infrared Waterlog AC #1 AC #2 Smoke Alarm Access Equipment
S1 S2 S3 S4 S5 S7 S8 DEFAULT DEFAULT DEFAULT
SW12A_1 SW12A_2 SW12A_3 SW12A_4 SW12A_5 SW12A_7 SW12A_8 SWTHE 1 & 2 SWBKE_3 SWBKE_1
disesuaikan disesuaikan disesuaikan disesuaikan disesuaikan disesuaikan disesuaikan ON OFF OFF
S6
SW12A_6
disesuaikan
DEFAULT DEFAULT
SWBKE_2 SWBKE_4
ON ON
Extended Boolean Port No. (BTS Scripts) 0 1 2 3 4 6 7
script: set cbtsenvswtextport:btsid=xxx,portid=0,opmode=def,alminfo="Rectifier Failure",confirm=y; set cbtsenvswtextport:btsid=xxx,portid=1,opmode=def,alminfo="Heat Detector Active",confirm=y; set cbtsenvswtextport:btsid=xxx,portid=2,opmode=def,alminfo="Door Open",confirm=y; set cbtsenvswtextport:btsid=xxx,portid=3,opmode=def,alminfo="PLN Power Failure",confirm=y; set cbtsenvswtextport:btsid=xxx,portid=4,opmode=def,alminfo="Smoke alarm",confirm=y; set cbtsenvswtextport:btsid=xxx,portid=6,opmode=def,alminfo="DC Power Too Low",confirm=y; set cbtsenvswtextport:btsid=xxx,portid=7,opmode=def,alminfo="DC FAN Active",confirm=y;
S4 S8 S6 S2 S5 S3 S1 S7
Sensor
Relay
SW_BKE
DIP switch
status
DIP switch
status
Water Log Sensor Smoke Detect Alarm Infrared Door Open
NC NC NC NC
SW_BKE_1 SW_BKE_2 SW_BKE_3 SW_BKE_4
OFF ON OFF ON
enable enable enable enable
ON
disable
ON OFF
disable disable
Water Log
dari kiri kekanan: putih, hijau, merah, konek ke water sensor
Temperature & Humadity
T+
T-
RH+ RH-
Infra Red
_ TAMP
+
R NC
PS48180-1800-X6
2 Jumper 2
3
3 LSA Box Port 7 2
3
For Implementation Only used 4 Relays. There are : Relay 1 : Power Failure / AC Mains Relay 2 : High / Under Voltage Relay 3 : Rectifier Failure / Rectifier module broken Relay 4 : BLVD
LSA Box Port No.
Censors Alarm Description
Relay Position
7
Rectifier Failure
NC
8
DC Power Too Low
NC
Port S1 S7
LSA Box Port No 8
EAC Box DIP Switch Number
Position
SW12 A1 SW12 A7
up up