Setup of Laptop Connecting to the Controller Module Log into the Controller Module Main screen of Power System Configuring the Power System Configuring the Date and Time Active alarm Group Configuring Alarm Group Current event log Mains configuration Rectifier configuration Battery string configuration Log out procedure Disconnect from Controller unit
Eltek How to Guide 16082011EH
2
1. SETUP OF LAPTOP
Return to Index
Eltek How to Guide 16082011EH
3
1. ENABLE USB PORT
RIGHT CLICK ON THE USB ICON THEN CHOOSE THE SILICON LABS ELTEK SMARTPACK. Eltek How to Guide 16082011EH
4
1. Connection to Controller unit
To confirm connection is to right click on USB icon then connection should be highlighted and or displaying a tick on the left hand side of the description of the connection. Eltek How to Guide 16082011EH
5
1. CHOOSE THE SOFTWARE
Power Suite 2.3 is the software to use for the ELTEK RACK. There are other software versions in circulation. Use 2.3 first, if not download the version being used on site by using the CD that is located on the shelf of the Eltek Rack. Eltek How to Guide 16082011EH
6
2. Connect to the Controller unit
Return to Index
Eltek How to Guide 16082011EH
7
2. Setup Settings
IMPORTANT: Click on the FIND COM PORT tab. Eltek How to Guide 16082011EH
8
2. Setup Settings Step 2 Step 1 Will be the Same port number
Step 1: Click on the Pen Icon to setup Communication Port Number. Step 2: Write the same number port on the Communication Port Windows that you got in FIND COM PORT Number. Eltek How to Guide 16082011EH
9
2. Setup Settings
Password is 003
Log in password is 0003 Eltek How to Guide 16082011EH
10
3. Log into Controller
Click on the ‘Login’ tab in the ‘Access’ menu. This slide is of version 3.2 Return to Index
Eltek How to Guide 16082011EH
11
3. Log into the Controller module
Enter the password ‘709’ in the Security tab and press OK. This slide is of version 3.2 Eltek How to Guide 16082011EH
12
4.
Main screen of Power System
Displays the working system of the ELTEK rack Return to Index
Eltek How to Guide 16082011EH
13
5. Configuring the Power system
Return to Index
In the ‘Company’ tab ’enter your company name’ followed by – KORDIA. In the ‘Site’ tab, enter the Site JV number followed by the site name (e.g. JS9975 Menangle). Change the Install date and the Service date to the current date. Eltek How to Guide When you have finished, click Apply then OK 16082011EH
14
6. Configuring the Date & Time
Return to Index
Click on the ‘Adjust Date & Time’ tab in the Tools menu. This slide is of version 3.2 Eltek How to Guide 16082011EH
15
6. Configuring the Date & Time
Then click on the ‘Get PC time & date’ button and click OK. This slide is of version 3.2 Eltek How to Guide 16082011EH
16
7. Active Alarm Group
In the Active Alarm Groups tab are the configured and current alarms
Return to Index
Eltek How to Guide 16082011EH
17
8. Configuring Alarm Group
Click on ‘Outputs’ tab and tick the boxes as detailed below then tick Apply then OK tabs. Note: If RBS is installed and utilising -48V to +24V DC converter then the ‘CONVERTER FAIL’ Alarm must be assigned to ‘Alarm output1’ (DC Urgent) How to Guide 16082011EH instead of ‘Alarm output2’. ThisEltek slide is of version 3.2
18
9. Current Event Log
Click on the EVENT LOG tab, this will display the LATEST xx EVENTS tab, click on this tab which then displays all the recent events, alarms. Return to Index
Eltek How to Guide 16082011EH
19
10. Mains Configuration
Click on the Mains tab, this will then display the Mains Summary tab. The number of Phases that the Eltek rack has is configured here. Return to Index
Eltek How to Guide 16082011EH
20
11. Rectifier Configuration
Return to Index
Click on Rectifiers to see or display the Summary, Configuration or Efficiency Manager. The number of rectifiers in the Eltek rack is configured Eltek How to Guide 16082011EH in the Configuration tab.
21
12. Battery String Configuration
Return to Index
Click on the BATTERY tab, this will then display the Status, Configuration, Test, Boost, Temperature Monitor & Summary Configuration. The number of battery strings in the Eltek rack is configured in the Eltek How to Guide 16082011EH Configuration tab.
22
13. LOG OUT
Click on either the DISCONNECT tab or the LOG OUT tab
Return to Index
Eltek How to Guide 16082011EH
23
14. Disconnect from Controller unit
Return to Index
Right click on the USB icon and choose the Silicon Labs Eltek Smartpack to disconnect from the unit. Eltek How to Guide 16082011EH The description should either not be highlighted or no tick beside it.