Electrical Protection & Relay Coordination Study Sample
Short Description
Electrical Protection & Relay Coordination Study Sample on Offshore Platform...
Description
REV.
DATE
DESCRIPTION
COMPANY
A
20 November 2013
Issued For Review
RBW
CH
DBK
B
13 December 2013
Issued For Approval
RBW
CH
DBK
0
17 March 2014
Approved for Construction
RBW
CH
DBK
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
RECORD OF REVISION The revisions listed below have been incorporated in this copy of the document.
REV NO.
SECTION
PAGE NO.
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
DESCRIPTION OF CHANGES
Page 2 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006 TABLE OF CONTENTS 1.
GENERAL
4
1.1
4
INTRODUCTION
2.
OBJECTIVE
4
3.
POWER SYSTEM OVERVIEW
4
4.
ASSUMPTION AND CALCULATION BASIS
6
4.1 4.2
BASIS OF STUDY STUDY CASES
6 6
TIME-CURRENT CURVES
7
5.
5.1 Largest Motor Feeder Protection Setting 7 5.2 LV Switchgear Incoming ACB and Largest Static Load Feeder Protection Setting 7 Relay Coordination Between Incoming ACB with Motor Feeder and Static Load Feeder 8 5.3 MV Switchgear (RMU) Protection Setting and Coordination with Incoming ACB Relay 8 Relay Coordination between RMU with LV Switchgear ACB 9 9 6.1 6.2 6.3
RMU Under/Over Voltage, Under/Over Frequency Protection Transformer Protection Earth Fault Protection & Monitoring
9 10 10
7.
SUMMARY
11
8.
APPENDIXES
11
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 3 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
1.
GENERAL
1.1 Husky CNOOC (Madura) Ltd. (HCML) plans to develop the Madura BD Field gas reserves for the sale of gas to buyers in Java. This field is located offshore in the Madura Strait East Java, about 65 km east of Surabaya and about 16km south of Madura Island. The project envisaged development of a wellhead platform (WHP); an offshore spread-moored Floating, Production, Storage and Offloading (FPSO) barge with gas processing facilities, Gas Metering Station (GMS); flexible risers from wellhead platform to FPSO and Export gas pipeline from WHP to GMS. The facility is designed for 110 mmscf/d sales gas. The unmanned wellhead platform with four well slots and two slots for future expansion would be located at 125 meters distance from FPSO and set in 182 feet of water.
2.
OBJECTIVE This report covers the Protection Relay Coordination Study for Madura BD Field Wellhead Platform. The purpose of carrying out the study is to determine the required settings for all main electrical protective devices to ensure proper coordination and safe operation of all equipments under fault conditions. Software ETAP (Electrical Transient Analysis Program) version.12 have been utilized in this calculation study.
3.
POWER SYSTEM OVERVIEW Madura BD Field Wellhead Platform electrical network system is made up of 1 unit of 6.6kV 60Hz Junction Box, 1 unit of 6.6kV 60Hz Ring Main Unit / MV Switchgear (10-RMU-6600-01), 1 unit of 6.6kV/480V 60Hz 400 kVA rating Transformer (10-TF-480-01), and 1 unit of 480V 60Hz LV Switchboard/MCC (10-MCC-480-01) to channel generated electrical power to respective electrical consumer. Below is a sketch presenting the overall electrical power network configuration for the Madura BD Field Wellhead Platform.
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 4 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
During normal operation, the electrical power of well head platform comes from Gas Turbine Generator at FPSO which is located near the well head platform. The generated power has 6.6kV voltage and 60Hz frequency. The power deliver from FPSO through 6.6 kV sub-sea cable (300 Meter Length) to 6.6kV Junction Box located at Cellar-Deck of well head platform, then goes to MV Switchgear (RMU) for isolating/connecting the power. The 6.6kV voltage is stepped down to 480V voltage by 400KVA Rating Transformer. The 480V voltage side of transformer is connected to 480V LV switchgear that will deliver electrical power to electrical loads at well head platform. During Main Power Failure at FPSO (Emergency situation), the emergency generator at FPSO will operate immediately to replace the failed Main Generator providing electrical power for electrical loads at FPSO and well head platform. All electrical loads of well head platform during normal operation can be handling by emergency generator of FPSO during Main Power Failure situation. Other electrical source for well head platform is from portable generator or supply boat generator that can be connected through socket outlet at boat landing connected to 480V low voltage switchgear/MCC. This source has an interlocked scheme with main incomer from 400KVA Transformer. This source only operated when power from FPSO is cut-off and maintenance work is needed to be done at well head platform. The amount of electrical power from this socket outlet is limited (around 69.28 KVA) due to limited capacity of portable generator or supply boat generator. Sections below provide a brief description of the expectation for the studies that is being carried out in this report.
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 5 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
4.
ASSUMPTION AND CALCULATION BASIS
4.1 Protection is arranged to cover the electrical power system completely, leaving no parts unprotected. When fault occurs, the protection is required to selectively trip only the nearest circuit breaker. The fault clearing time, the operating time of the relay and time taken for its breaker opening, shall not exceed 1.0 second of the short circuit withstand time of the MV Junction Box, RMU and LV Switchgear. The relay current setting is selected to permit continuous equipment full load current flow through the relay without the relay operating. For main distribution transformer feeder, the current setting selected for high voltage side overcurrent relay and low voltage side overcurrent relay shall ensure that the relays do not operate during energizing of the transformer which may draw up to 12 times transformer rated full load current. For motor feeders, the current setting selected shall ensure that the relay does not operate during the starting of the motor which may draw up to 6.5 times motor rated full load current. Transformer thermal limit curve are develop in etap using manufacturer data. Motor starting curve and motor thermal limit curve (MEG Injection Pump Motor) are develop based on below data: Motor starting time = depend on total inertia and load characteristic (in here, 1.2 sec, based on etap results for largest motor starting simulation study). Motor stall time = 19-21 sec (Cold) and 22-24 sec (Hot) based on WEG motor data. The upstream protective devices will provide selectivity with the downstream feeder protective devices. In general, an attempt has been made to achieve a time margin of 0.20.3 sec between upstream relay and downstream relay for clearing of down-stream fault when the fault currents flow through both devices simultaneously.
4.2 1. Normal Operating Condition (power supplied from FPSO). This scenario will represent the normal platform operating condition. The details of this scenario are listed below: a.
Normal Operating of FPSO Generators are running
b.
All possible motor contributing loads are running
2. Summary of fault level on each busbars / equipments can be seen at document WHP-SYE-003 (Electrical Short Circuit Study).
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 6 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
5.
TIME-CURRENT CURVES The time-current curves are modelled in the program as graphical plots of the interaction of the system overcurrent devices. These time-current curves are used to establish the recommended setting and characteristics of overcurrent devices. The time-current curves are plotted using the electrical power system study software ETAP 12. The time-current curves (TCC) showing protective relay coordination in this power system will be describe below. First is the protective device coordination at largest motor feeder, between MCCB to protect motor and cable against overload and short-circuit current with considering motor starting current, motor thermal limit, and cable thermal limit. Second is the protective device coordination between incoming Air Circuit Breaker (ACB) of LV switchgear with largest motor feeder and largest static load feeder. The incoming ACB time current curves must be on the rightabove side of time current curves of largest motor and static load. This arrangement will give selective trip sequence between downstream and upstream protection device, mean that the downstream device should operate first and if it fails then the upstream device should be operate. Third is the coordination between the incoming circuit breaker ACB of LV switchgear (low voltage side of transformer) with medium voltage circuit breaker relay of RMU (high voltage side of transformer) with considering inrush current, thermal limit of transformer and thermal limit of cables. The setting of protection devices for above coordination are describe below.
5.1 The setting of MCCB relay of MEG Injection Pump motor are described below. Thermal Magnetic MCCB Full Load Current
: 43.9 A
Sensor Plug (In)
: 100 A
Long-Time Pick-Up (LTPU)
: 0.52 (52A)
Long-Time Band
: 3s
Short-Time Pick-Up (STPU)
: 10 (1000A)
Short-Time Band
: 0.25s
Instantaneous Pick-Up
: 9 (900A)
Type/Maker
: T2S/ABB
The time current curve of above settings can be seen at appendix-D. From the curve can be seen that thermal part are located right side of motor full load ampere but still at left side - below of motor thermal limit and cable ampacity. The magnetic part curve are located right side of motor starting current, motor thermal limit and cable ampacity but it still at left-below of cable thermal limit curve. 5.2
Largest static load feeder is the heat tracing control panel, which is 40 KVA. The protection setting is described below.
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 7 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006 Thermal Magnetic MCCB Full Load Current
: 59.4 A
Sensor Plug (In)
: 100 A
Long-Time Pick-Up (LTPU)
: 0.68 (68A)
Long-Time Band
: 3s
Short-Time Pick-Up (STPU)
: 1 (100A)
Short-Time Band
: 0.1s
Instantaneous Pick-Up
: 1 (100A)
Type/Maker
: T2S/ABB
The protection setting of incoming ACB is described below. Over Current Device - 50 & 51 Full Load Current
: 481.1 A
Sensor Plug (In)
: 800 A
Long-Time Pick-Up (LTPU)
: 0.7 (560A)
Long-Time Band
: Curve A
Short-Time Pick-Up (STPU)
: 10 (8000A)
Short-Time Band
: Curve B
Instantaneous Pick-Up
: 10 (8000A)
Type/Maker
: SACE PR111/ABB
The time current curve of coordination relay/protection device settings between Incoming ACB with motor feeder and static load feeder can be seen at appendix-E. From the curve can be seen that Incoming ACB relay is located at right side above of motor feeder relay and static load feeder relay. Mean that, any fault happened at motor feeder or static load feeder, will trip first the motor feeder relay or static load feeder relay, if these relay fails, then the incoming ACB relay will trip.
5.3
The protection setting of RMU relay is described below. Over Current
Device 50 & 51
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 8 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006 Full Load Current
: 34.99 A
CT Ratio
: 75:5
Curve Type
: Extremely Inverse
Pickup
: 0.92 (0.05-20 x CT Sec)
Time Dial
: 11.94, 3x =7.87 s, 5x=2.95s, 8x=1.5s
Instantaneous Pick-Up
: 20 (0.05-20 x CT Sec)
Time Delay
: 0.25 s
Type/Maker
: Multilin 750/760/GE
The relay coordination between RMU with LV Switchgear ACB can be seen at appendix-F. The time current curve show the ACB relay curve is located right-above of transformer full load current and inrush current curve but left-below of LV cable ampacity, LV cable thermal limit and transformer thermal limit curve. The RMU relay curve is also located right-above of transformer full load current and inrush current but left-below of MV cable ampacity, MV cable thermal limit and transformer thermal limit curve. The ACB relay curve is located left-below of RMU relay curve with some time margin. At the instantaneous part, the time margin between ACB relay and RMU relay curve is 0.25 S. It is mean that when a fault located at LV side happened, the ACB relay will operate instantaneously, and if this relay fails to operate, the RMU relay will be operated after 0.25 S delay time.
6.1 Under Voltage / Over Voltage Protection
Device 27/59
VT Ratio: 6600V /110V The under-voltage relay is to be set at 80% with time delay so that to ride through the momentary voltage dip during the starting of large motors. -
Set alarm level at 85% = (85/100) x 110V = 93.5V
-
Set trip time delay at 6 seconds.
-
Set trip pickup level at 80% = (80/100) x 110V = 88V
-
Set trip time delay at 3 seconds.
The overvoltage relay is set at 110% of the rated transformer voltage to protect the transformer against continuous overvoltage due to transients. -
Set trip 1 pickup level at 110% = (110/100) x 110V = 121V
-
Set trip 1 time delay at 3 seconds
-
Set trip 2 pickup level at 125% = (125/100) x 110V = 137.5V
-
Set trip 2 time delay at 0.5 seconds
Under Frequency and Over Frequency Protection MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Device 81(U) Page 9 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006 -
Set under frequency alarm at 2.5% of rated frequency = 97.5% x 50 = 48.75 Hz
-
Set alarm time delay at 10 seconds.
-
Set trip under frequency pickup at 5% of rated frequency = 95% x 50 = 47.5 Hz
-
Set trip time delay at 10 seconds.
6.2
6.3
The 480V system is high resistance earthed at transformer LV side star point. The resistance value is 55.5 ohm and can limit earth/ground fault to 5A. When earth fault happened, the earth fault will not trip the protection system, but it will be detect / monitored by relay meter at grounding panel. The relay meter will send alarm to PCS for annunciation. The grounding panel also equipped with pulsation circuit with can detect the location of the ground fault. Therefore, the faulted line can be isolated. The 208/120V system is solidly earthed at transformer star point. The 208/120V Small Power & Lighting and 208/120V UPS are using Neutral and protective earth conductor separate (TN-S grounding system).The earth Leakage Relay (ELR) protection is provided in following circuit / feeder: -
Lighting and Socket circuits in Lighting and Small Power Distribution Board. Socket Outlet Circuits in UPS Distribution Board.
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 10 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
7.
SUMMARY Summary of the recommended protective device settings are shown from Appendix B to Appendix C. Relay coordination from Largest Motor Feeder (MEG Injection Pump Motor), Largest Static Load Feeder (Heat Tracing Control Panel) to LV Incoming ACB is shown in Appendix E. Relay coordination from RMU to ACB is shown in Appendix F.
.
8.
APPENDIXES 1)
APPENDIX A - OVERALL ONE LINE DIAGRAM
2)
APPENDIX B - RELAY SETTING TABLE RMU, ACB & TRANSFORMER
3)
APPENDIX C - RELAY SETTING TABLE MOTOR FEEDER & STATIC LOAD FEEDER
4)
APPENDIX D - TIME CURRENT CURVES FOR LARGEST MOTOR FEEDER
5)
APPENDIX E - TIME CURRENT CURVES COORDINATION ACB, MOTOR & STATIC LOAD FEEDER
6)
APPENDIX F - TIME CURRENT CURVES COORDINATION RMU & ACB
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 11 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
APPENDIX A
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
SINGLE LINE DIAGRAM
Page 12 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
APPENDIX B - RELAY SETTING TABLE RMU, ACB & TRANSFORMER
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 13 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
APPENDIX C - RELAY SETTING TABLE MOTOR FEEDER & STATIC LOAD FEEDER
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 14 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
APPENDIX D - TIME CURRENT CURVES FOR LARGEST MOTOR FEEDER
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 15 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
APPENDIX E - TIME CURRENT CURVES COORDINATION ACB, MOTOR & STATIC LOAD FEEDER
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 16 of 17
MADURA BD FIELD DEVELOPMENT - EPCI WHP ELECTRICAL PROTECTION & RELAY COORDINATION STUDY DOC NO. : WHP-SYE-006
APPENDIX F - TIME CURRENT CURVES COORDINATION RMU & ACB
MADURA BD FIELD DEVELOPMENT - EPCI CONTRACT NO.: 332003560
Page 17 of 17
Cbl66
Cbl65
Cbl64
Cbl63
Cbl62
Cbl69
Cbl71
Cbl74
Cbl68
Cbl67
Nov 20, 2013
Cbl75
Bus81
CB74
Bus83
Cbl77
Bus75
CB72
CB73
Bus82
Cbl76
CB75
Bus84
Project File: HCML_Relay
Load22 Load21 Load20 Load19 Load18 Load24 Load26 Load25 Load27 1.4 kVA 0.71 kVA 0.71 kVA0.71 kVA 0.71 kVA 0.29 kVA 0.29 kVA 0.04 kVA 0.02 kVA
Bus76
Cbl70
Bus77
CB66
Cbl78
Load5 Load6 Load7 Load8 Load9 Load10 2.8 kVA 2.8 kVA 3.5 kVA 2.9 kVA 2.8 kVA 1.4 kVA Load23 1.4 kVA
Cbl72
Bus78
CB67
MOV3 2.24 kW
CB26
CB27
CB28
MOV7 2.24 kW
Bus64
MOV8 2.24 kW
MOV10 2.24 kW
Mtr15 3 kW
Bus46
MOV11 2.24 kW
Bus68
CB32
CB31
Bus67
MOV9 2.24 kW
Bus66
CB30
Mtr14 0.3 kW
Bus45
Mtr13 3 kW
Bus44
Mtr3 1.12 kW
CB29
2.4 kVA Load12
Bus65
Load11 20.4 kVA
Bus41
Bus40
T3 25 kVA
MOV6 2.24 kW
Bus63
MOV5 2.24 kW
Bus62
MOV4 2.24 kW
Bus61
CB25
CB24
Bus60
MOV2 2.24 kW
Bus59
MOV1 2.24 kW
Bus58
CB23
CB22
Cbl29
09:20:05
Cbl73
Bus79
CB68 Cbl24
Bus80
CB69 Cbl28
Bus30
CB70
Mtr12 6 kW
Cbl30
Bus29
CB71
Bus7 0.48 kV
Cbl25
Bus28
CB61
CB54
Mtr4 1.12 kW
Cbl26
Bus27
CB60
2SW1
CB53
Bus20
Mtr2 25.36 kW
Mtr11 6 kW
Cbl27
Bus26
CB59
CB52
Battery2
Bus18
Battery1
Mtr1 Load13 25.36 kW 47.1 kVA
Mtr10 0.75 kW
Bus43
Cbl31
page 1
Cbl17
Cbl60 Cbl32
Load4 2.8 kVA
Cbl18
Bus22 Cbl33
Bus25
Cbl19
Cbl59
0.208 kV Cbl34
Bus24
Cbl20
25 kVA
Cbl61
CB58
Cbl9
T2
CB57
Cbl11
Mtr9 0.75 kW
Cbl40
CB56
Cbl12
Bus42
Cbl38
Load15 Mtr26 3.9 kVA 3.4 kW
Cbl37
Bus39 Mtr16 0.3 kW
Bus47
CB40
Cbl43
Bus21 0.208 kV
Cbl13
Bus38
CB41
Cbl44
Bus17
Cbl14
Bus37
CB39
CB38
Mtr17 3 kW
Bus48
Mtr18 0.3 kW
Bus49
Mtr19 3 kW
Bus50
CB44
CB43
CB42
Mtr20 0.3 kW
Bus51
Mtr21 3 kW
Bus52
Mtr22 0.3 kW
Bus53
Mtr24 1.5 kW
CB51
Open
CB62
Open
CB63
Mtr27 3.4 kW
Bus72
Load16 3.9 kVA
Bus71 Mtr25 0.75 kW
Bus57
Load14 2.4 kVA
Bus56
CB50
CB49
Bus55
Mtr23 1.5 kW
Bus54
CB48
CB47
CB46
CB45
Cbl48
dcBus1 dcCB1 dcBus2
Cbl15
Bus36
CB37
Cbl49
Mtr7 Mtr8 18.65 kW 18.65 kW Load1 Load2 29.4 kVA 29.4 kVA Load3 29.4 kVA
Cbl16
Bus35
CB36
Cbl50
Mtr6 3.73 kW
Cbl5
Bus11
CB35
Cbl51
Mtr5 3.73 kW
Cbl6
Bus10
Cbl7
Bus9
Cbl8
Bus8
CB34
CB33
CB21
CB20
Cbl54
UPS1
CB19
Cbl21
CB6
Cbl22
Bus70
CB5
Cbl23
Bus69
CB4
Cbl35
Bus19
CB3
Cbl55
UPS2
Open
Open
Cbl36
Bus16
CB14
CB13
Cbl39
Bus15
CB12
Cbl41
Bus14
CB11
Cbl42
Bus13
CB10
Cbl45
Bus12
CB9
Cbl46
Bus34
CB8
Cbl10
CB7
Cbl47
Bus33
CB18
Cbl52
Bus32
CB17
Cbl53
Bus31
CB16
Cbl56
CB55
CB15
Cbl4
T1 400 kVA
Cbl3
Cbl2
Open
CB64
Load17 3.9 kVA
Bus73
Cbl57
Bus23 0.208 kV
Bus6 0.48 kV
CB2
Bus5
Bus4
Bus3
CB1
Bus2
Cbl1
U1 130.434 MVAsc
Bus1 6.6 kV
One-Line Diagram - OLV1 (Edit Mode)
Open
CB65
Mtr28 3.4 kW
Bus74
Cbl58
630
800
Incoming Low Voltage Feeder
Transformer
2
3
Description
Incoming Medium Voltage Feeder
Tag Number
1
No.
Rating (Amp)
481.1
Full Load Current (Amp) 34.99 75/5A 6600/110V
CT/VT Ratio
Under Voltage Over Voltage
27 59
49
63
71
VTA
VTA
50
51
Over Thermal Relay Low Stage Low Low Stage High Pressure Relay High Stage High High Stage Low Level Relay Low Stage Low Low Stage
Sensor Plug (In) Long Time Pick-Up (LTPU) Long Time Band Short Time Pick-Up (STPU) Short Time Band Instantaneous Pick-Up
81U Under Frequency
Instantaneous Protection
Curve Type Pickup Time Dial
Protection Function
50
51
VTA
SACE PR 111
Multilin 750/760
Relay Type ANSI
6s 3s 3s 0.5s 10s 10s
85% x 110V = 93,5V Alarm 80% x 110V = 88V Trip 110% x 110V = 121V Trip 1 125% x 110V = 137,5V Trip 2 97.5% x 50 = 48.75Hz Alarm 95% x 50 = 47,5Hz Trip
VTA VTA
VTA VTA
VTA VTA
800 A 0.7 (560 A) Curve A 10 (8000A) Curve B 10 (8000)
0.25s
td
20 (0.05-20 x CT Sec)
Extremely Inverse 0.92 (0.05-20 x CT Sec) 11.94, 3x=7.87s, 5x=2.95s, 8x=1.5s
Setting
MULTILIN 760/750 SR
PROTECTION RELAY SETTING RECOMMENDATIONS
ENGINEERING, PROCUREMENT, CONSTRUCTION AND INSTALLATION (EPCI) FOR MADURA BD FIELD PLATFORM DEVELOPMENT PROJECT
Remark
Page 1 of 4
Tag Number
Description
G-1003A
G-1003B
10-NCCP-240-01
G-1002A
G-1002B
G-1005A
G-1005B
G-1005C
G-1005D
G-1004C
G-1004D
G-1007A
G-1007B
10-UU-208-01A
10-UU-208-01B
10-UT-208-01
HCP-7710
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Heat Tracing Control Panel
230 V AC UPS (Bypass Transformer)
230 V AC UPS B
208 V AC UPS A
MEG Injection Pump Motor B
MEG Injection Pump Motor A
Liquid Pump Motor B
Liquid Pump Motor A
Hydraulic Pump Motor D
Hydraulic Pump Motor C
Hydraulic Pump Motor B
Hydraulic Pump Motor A
PPD Injection Pump B Motor
PPD Injection Pump A Motor
Nav Aids Battery Charger
Open Drain Sump Pump B Motor
Open Drain Sump Pump A Motor
LV SWITCGEAR/MCC (10-MCC-480-01)
No.
40.00
20.00
20.00
20.00
25.40
25.40
18.70
18.70
6.00
6.00
6.00
6.00
0.75
0.75
2.00
3.70
3.70
Rating (kW)
59.40
33.30
33.30
33.30
43.90
43.90
32.32
32.32
10.37
10.37
10.37
10.37
1.50
1.50
2.67
6.54
6.54
68.3
38.3
38.3
38.3
50.5
50.5
37.17
37.17
11.93
11.93
11.93
11.93
1.73
1.73
3.1
7.5
7.5
115 - 125% FLC
Required Rating Full Load OL/CB Current A A
F
F
F
F
M
M
M
M
M
M
M
M
M
M
F
M
M
Feeder Type
3s
3s
3s
3s
3s
3s
3s
3s
0.48 (12A) 0.6 (37.8A) 0.6 (37.8A) 0.52 (52A) 0.52 (52A) 0.64 (40.3A) 0.64 (40.3A) 0.64 (40.3A)
3s
3s
0.48 (12A)
0.68 (68A)
3s
0.48 (12A)
1 (100A)
1(63A)
1(63A)
1(63A)
10(1000A)
10(1000A)
10(630A)
10(630A)
1(25A)
1(25A)
1(25A)
1(25A)
0.1s
0.1s
0.1s
0.1s
0.25s
0.25s
0.25s
0.25s
0.1s
0.1s
0.1s
0.1s
1(100A)
1(63A)
1(63A)
1(63A)
9(900A)
9(900A)
10(630A)
10(630A)
7.5(187.5A)
7.5(187.5A)
7.5(187.5A)
7.5(187.5A)
T2S
T2S
T2S
T2S
T2S
T2S
T2S
T2S
T2S
T2S
T2S
T2S
T2S-TMD
Magnetic Trip = fixed (25A)
Thermal Trip = 70% (2.24A)
3s
T2S-TMD
T2S
T2S
MCCB Type
Magnetic Trip = fixed (25A)
10(100A)
10(100A)
Ins Pick-up
Thermal Trip = 70% (2.24A)
0.1s
0.25s
0.25s
ST Band
T2S
1(10A)
10(100A)
10(100A)
ST Pickup
160
160
160
160
160
160
160
160
160
160
160
160
160
160
160
160
160
MCCB Frame Rated
100
63
63
63
100
100
63
63
25
25
25
25
3.2
3.2
10
10
10
MCCB Rated Current
Phase Fault Protection
1(10A)
3s
3s
3s
LT Band
0.48 (12A)
0.4(4A)
0.8(80A)
0.8(80A)
LT Pick-up
Relay Setting
Relay / Protection Device Data
PROTECTION RELAY SETTING RECOMMENDATIONS
ENGINEERING, PROCUREMENT, CONSTRUCTION AND INSTALLATION (EPCI) FOR MADURA BD FIELD PLATFORM DEVELOPMENT PROJECT
Remarks
Page 2 of 4
Tag Number
Description
DB-7710
DB-7730
10-WO-480-001
10-WO-480-002
10-WO-480-003
G-1001A
G-1001B
ACCU-01
ACCU-02
ACCU-03
ACCU-04
ACCU-05
FCU-01
FCU-02
FCU-03
FCU-04
FCU-05
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
Fan Coil Unit-E
Fan Coil Unit-D
Fan Coil Unit-C
Fan Coil Unit-B
Fan Coil Unit-A
Air Cooled Condensing Unit-E
Air Cooled Condensing Unit-D
Air Cooled Condensing Unit-C
Air Cooled Condensing Unit-B
Air Cooled Condensing Unit-A
Diesel Pump Motor B
Diesel Pump Motor A
Welding Outlet-03
Welding Outlet-02
Welding Outlet-01
MOV Distribution Board
Lighting & Small Power DB
LV SWITCGEAR/MCC (10-MCC-480-01)
No.
0.30
0.30
0.30
0.30
0.30
3.00
3.00
3.00
3.00
3.00
1.10
1.10
25.00
25.00
25.00
24.62
17.34
Rating (kW)
0.60
0.60
0.60
0.60
0.60
5.31
5.31
5.31
5.31
5.31
2.21
2.21
37.59
37.59
37.59
29.61
25.75
0.69
0.69
0.69
0.69
0.69
6.11
6.11
6.11
6.11
6.11
2.54
2.54
43.2
43.2
43.2
34.1
29.6
115 - 125% FLC
Required Rating Full Load OL/CB Current A A
M
M
M
M
M
M
M
M
M
M
M
M
F
F
F
F
F
Feeder Type
3s
3s
3s
0.72 (45.4) 0.72 (45.4) 0.72 (45.4)
0.7 (70A)
0.7 (70A)
0.7 (70A)
0.7 (70A)
0.7 (70A)
0.4 (40A)
T2S-TMD
T2S-TMD
T2S-TMD
T2S-TMD
T2S-TMD
Magnetic Trip = fixed (11.2A) Magnetic Trip = fixed (11.2A) Magnetic Trip = fixed (11.2A) Magnetic Trip = fixed (11.2A)
Thermal Trip = 70% (1.12A)
Thermal Trip = 70% (1.12A)
Thermal Trip = 70% (1.12A)
Thermal Trip = 70% (1.12A)
T2S
T2S
T2S
T2S
T2S
T2S
T2S
T2S
T2S
T2S
T2S
MCCB Type
Magnetic Trip = fixed (11.2A)
7.5 (75A)
7.5 (75A)
7.5 (75A)
7.5 (75A)
7.5 (75A)
7.5 (75A)
1(63A)
1(63A)
1(63A)
1(63A)
1(63A)
Ins Pick-up
Thermal Trip = 70% (1.12A)
0.1s
0.1s
0.1s
0.1s
0.1s
0.1s
0.1s
0.1s
0.1s
0.1s
0.1s
0.1s
ST Band
T2S 1 (10A)
1 (10A)
1 (10A)
1 (10A)
1 (10A)
1 (10A)
1 (10A)
1(63A)
1(63A)
1(63A)
1(63A)
1(63A)
ST Pickup
160
160
160
160
160
160
160
160
160
160
160
160
160
160
160
160
160
MCCB Frame Rated
1.6
1.6
1.6
1.6
1.6
10
10
10
10
10
10
10
63
63
63
63
63
MCCB Rated Current
Phase Fault Protection
7.5 (75A)
3s
3s
3s
3s
3s
3s
3s
3s
0.56 (35.3A)
0.4 (40A)
3s
LT Band
0.48 (30.2A)
LT Pick-up
Relay Setting
Relay / Protection Device Data
PROTECTION RELAY SETTING RECOMMENDATIONS
ENGINEERING, PROCUREMENT, CONSTRUCTION AND INSTALLATION (EPCI) FOR MADURA BD FIELD PLATFORM DEVELOPMENT PROJECT
Remarks
Page 3 of 4
Tag Number
Description
PU-01
PU-02
DH-01
EF-01
35
36
37
38
Exhaust Fan
Duct Heater
Pressurize Fan B
Pressurize Fan A
LV SWITCGEAR/MCC (10-MCC-480-01)
No.
0.75
2.00
1.50
1.50
Rating (kW)
1.50
2.67
3.01
3.01
1.73
3.1
3.4615
3.4615
115 - 125% FLC
Required Rating Full Load OL/CB Current A A
M
F
M
M
Feeder Type
0.4(4A)
0.4 (40A)
0.4 (40A)
LT Pick-up
1(10A)
1 (10A)
1 (10A)
ST Pickup
Thermal Trip = 70% (2.24A)
3s
3s
3s
LT Band
Relay Setting
0.1s
0.1s
0.1s
ST Band
T2S
T2S-TMD
Magnetic Trip = fixed (25A)
T2S
T2S
MCCB Type
160
160
160
160
MCCB Frame Rated
3.2
10
10
10
MCCB Rated Current
Phase Fault Protection
1(10A)
7.5 (75A)
7.5 (75A)
Ins Pick-up
Relay / Protection Device Data
PROTECTION RELAY SETTING RECOMMENDATIONS
ENGINEERING, PROCUREMENT, CONSTRUCTION AND INSTALLATION (EPCI) FOR MADURA BD FIELD PLATFORM DEVELOPMENT PROJECT
Remarks
Page 4 of 4
Amps X 10 Bus7 (Nom. kV=0.48, Plot Ref. kV=0.48) .5
1
3
5
10
30
50
100
300
500
1K
3K
5K
1K
10K 1K
Cable5 Ampacity
500
500
CB3
300
300
ABB SACE PR221 (T2) Sensor = 100 LT Pickup = 0.52 (52 Amps) LT Band = 3s ST Pickup = 10 (1000 Amps) ST Band = 0.25s (I^x)t = IN Inst. Pickup = 9 (900 Amps)
100
50
100
50
30
30
Mtr1-Hot
10
5
5
Mtr1-starting
3
3
1
1
.5
.5
.3
.1
.3
Cable5 - P
CB3
.1
Cable5 1-3/C 16
.05
.05
.03
.01
.03
Mtr1 HP1
.5 34
3
5
10
30
50
100
300
500
1K
Amps X 10 Bus7 (Nom. kV=0.48, Plot Ref. kV=0.48) Star488 Project: Location: Contract: Engineer: Filename: C:\ETAP 1200\star1\star2.OTI
Date: SN: Rev: Fault:
11-20-2013 PT-BIRU Base Phase
3K
5K
.01 10K
ETAP Star 12.0.0C
Seconds
Seconds
10
Amps X 100 Bus6 (Nom. kV=0.48, Plot Ref. kV=0.48) .5
1
3
5
10
30
50
100
300
500
1K
3K
5K
1K
10K 1K
CB2 500
500
ABB SACE PR111 Sensor = 800 LT Pickup = 0.7 (560 Amps) LT Band = Curve A ST Pickup = 1 (800 Amps) ST Band = Curve C (I^x)t = OUT Inst. Pickup = 12 (9600 Amps)
300
100
300
100
50
30
CB3
30
10
ABB SACE PR221 (T2) Sensor = 100 LT Pickup = 0.52 (52 Amps) LT Band = 3s ST Pickup = 10 (1000 Amps) ST Band = 0.25s (I^x)t = IN Inst. Pickup = 9 (900 Amps)
10
5 3
5 3
CB4 ABB SACE PR221 (T2) Sensor = 100 LT Pickup = 0.68 (68 Amps) LT Band = 3s ST Pickup = 1 (100 Amps) ST Band = 0.1s (I^x)t = IN Inst. Pickup = 1 (100 Amps)
1
.5
1
.5
.3
.3
.1
.1
.05
.05
.03
.03 CB2
Bus6
CB3
CB4
.01 .5
1
3
5
10
30
50
100
300
500
1K
Amps X 100 Bus6 (Nom. kV=0.48, Plot Ref. kV=0.48) Star495 Project: Location: Contract: Engineer: Filename: C:\ETAP 1200\star1\star2.OTI
Date: SN: Rev: Fault:
11-20-2013 PT-BIRU Base Phase
3K
5K
.01 10K
ETAP Star 12.0.0C
Seconds
Seconds
50
Amps X 10 Bus3 (Nom. kV=6.6, Plot Ref. kV=6.6) .5
1
3
1K
5
10
T1 FLA
500
30
50
100
300
50
3K
5K
Relay2 - P - 50 OC1
T1
GE Multilin 750/760 CT Ratio 75:5 Inst = 20 (0.05 - 20 xCT Sec) Time Delay = 0.25 s
400 kVA (Secondary) 4 %Z Delta-Wye Resistor Grd Curve Shift = 1
100
1K
Cable3 Ampacity
Cable4 Ampacity
300
500
10K 1K
500 300
100
50
30
30
Relay2 - P - 51 OC1 ABB SACE PR111 Sensor = 800 LT Pickup = 0.7 (560 Amps) LT Band = Curve A ST Pickup = 1 (800 Amps) ST Band = Curve C (I^x)t = OUT Inst. Pickup = 12 (9600 Amps)
5 3
10
5 3
1
1
.5
Cable4 - P
.5
Cable3 - P
.3
.3 CB1 ±
Bus3
I>
Relay2
Cable3
.1
1-3/C 70
T1 400 kVA
.05
.1
T1 Inrush
.05
.03
.03
Cable4 2-3/C 150
CB2
.01 .5
1
3
5
10
30
50
100
300
500
1K
Amps X 10 Bus3 (Nom. kV=6.6, Plot Ref. kV=6.6) Star494 Project: Location: Contract: Engineer: Filename: C:\ETAP 1200\star1\star2.OTI
Date: SN: Rev: Fault:
11-20-2013 PT-BIRU Base Phase
3K
5K
.01 10K
ETAP Star 12.0.0C
Seconds
Seconds
GE Multilin 750/760 CT Ratio 75:5 ANSI - Extremely Inverse Pickup = 0.92 (0.05 - 20 xCT Sec) Time Dial = 11.94 3x = 7.87 s, 5x = 2.95 s, 8x = 1.5 s
CB2
10
View more...
Comments